GSH10 CommERCial
11 EER Split SyStEm
HEat pump
7½ to 10 tonS
Standard Features
• Energy-efficient compressor with internal pressure
relief valve
• High-capacity, steel-cased, bi-flow heat pump
filter dryer
• Factory-installed suction line accumulator
• Liquid refrigerant return protection
• Check flowrater heating mode expansion device
• Reliable, time-initiated, temperature-terminated
defrost control
• Low-pressure switch
• Discharge line muffler
• Brass liquid and suction line service valves mounted
at a 90° angle with sweat connections and service ports
• High-efficiency copper tube/aluminum fin coil
• Complies with ASHRAE Standard 90.1
• ETL Listed
Cabinet Features
• Goodman brand sound control top design
• Steel louver coil guard protects coil from damage
and adds strength to the unit
• Heavy-gauge, galvanized-steel cabinet
• Attractive Architectural Gray powder-paint
finish with 500-hour salt-spray approval
• When properly anchored, meets the 2001 Florida Building
Code unit integrity requirements for hurricane-type winds
(Anchor bracket kits available.)
Contents
Nomenclature....................................................................2
Product Specifications .......................................................3
Expanded Cooling Data .....................................................4
Expanded Heating Data...................................................10
Wiring Diagram................................................................11
Dimensions ......................................................................12
Accessories .......................................................................12
* Complete warranty details available from your local dealer or at
SS-GSH10C
6/11
Supersedes 1/10
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
SpECifiCationS
GSH10
0903A*
GSH10
0903B*
GSH10
1203A*
Nominal Capacities
Cooling (BTU/h)
Heaꢀng (BTU/h)
EER/IEER
87,000
84,000
11/--
76
90,000
84,000
11/11
76
110,000
100,000
11/11.5
77
Decibels
Compressor
RLA
25.6
196
25.6
196
30.1
225
LRA
Condenser Fan Motor
Horsepower
1
1
1
FLA
5.6
5.6
5.6
Refrigerant Lines
Liquid Valve Size (“O.D.)
Sucꢀon Valve Size (“O.D.) (7½ tons)
Sucꢀon Valve Size (“O.D.) (10 tons)
Valve Type
⅝"
1⅜"
⅝"
1⅜"
⅝"
1⅜"
1⅝"
1⅝"
1⅝"
Sweat
Sweat
Sweat
Electrical Data
Voltage/Phase
208-230/3
37.6
208-230/3
37.6
208-230/3
43.2
Minimum Circuit Ampacity¹
Max. Overcurrent Protecꢀon²
Min / Max Volts
60
60
70
197/253
½" or ¾"
254
197/253
½" or ¾"
254
197/253
½" or ¾"
315
Electrical Conduit Size
Ship Weight (lbs)
¹
Wire size should be determined in accordance with Naꢀonal Electrical Codes; extensive wire runs will require
larger wire sizes
² May use fuses or HACR type Circuit Breakers of the same size as noted
Notes
•
•
•
Always check the S&R plate for electrical data on the unit being installed.
Installer will need to supply 1⅛” to 1⅜” or 1⅛” to 1⅝” as appropriate.
Unit charge with dry nitrogen/helium; must safely dispel holding charge from unit. Evacuate and charge with
R-22 per Installaꢀon Manual.
•
Installaꢀon of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS
DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
SS-GSH10C
3
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd CoolinG data — GSH100903a* / aR090
4
SS-GSH10C
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd CoolinG data — GSH100903a* / aR090 (Cont.)
SS-GSH10C
5
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd CoolinG data — GSH100903B* / aR090
6
SS-GSH10C
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd CoolinG data — GSH100903B* / aR090 (Cont.)
SS-GSH10C
7
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd CoolinG data — GSH101203a* / aR120
8
SS-GSH10C
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd CoolinG data — GSH101203a* / aR120 (Cont.)
SS-GSH10C
9
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
ExpandEd HEatinG data
GSH100903A* / AR090
Outdoor Ambient Temperature
65°F 60°F 55°F 50°F 47°F 45°F 40°F 35°F 30°F 25°F 20°F 17°F 15°F 10°F
5°F
0°F
-5°F -10°F
MBh
∆T
103.1 97.6 91.8 85.9
33.1 31.4 29.5 27.6
8.04 7.89 7.74 7.59
24.4 22.6 21.1 19.8
3.75 3.62 3.47 3.31
12.8 12.4 11.9 11.3
82.0 79.5 73.8 68.1
26.4 25.5 23.7 21.9
7.50 7.44 7.29 7.14
19.1 18.7 17.6 16.7
3.20 3.13 2.96 2.79
66.0 61.0 56.1 53.0
21.2 19.6 18.0 17.0
7.48 7.32 7.16 7.06
16.0 15.3 14.5 14.2
2.58 2.44 2.30 2.20
51.0 45.8 40.6 35.4
16.4 14.7 13.1 11.4
7.00 6.83 6.67 6.51
14.0 13.3 12.4 11.6
2.14 1.96 1.78 1.59
30.2 24.8
9.7
6.34 6.18
10.7 9.6
1.39 1.17
8.0
kW
Amps
COP
EER
10.9 10.7 10.1
9.5
190
43
8.8
182
38
8.3
174
34
7.8
167
30
7.5
163
28
7.3
160
27
6.7
154
23
6.1
148
20
5.4
142
17
4.8
137
15
4.0
132
11
Hi PR
Lo PR
244
72
234
66
225
62
215
57
210
54
206
52
198
48
GSH100903B* / AR090
Outdoor Ambient Temperature
65°F 60°F 55°F 50°F 47°F 45°F 40°F 35°F 30°F 25°F 20°F 17°F 15°F 10°F
5°F
0°F
-5°F -10°F
MBh
∆T
105.8 100.1 94.2 88.1
32.1 30.4 28.6 26.7
8.03 7.88 7.73 7.58
30.2 28.1 26.4 24.9
3.85 3.72 3.57 3.40
13.2 12.7 12.2 11.6
84.1 81.5 75.7 69.8
25.5 24.8 23.0 21.2
7.49 7.42 7.28 7.12
24.1 23.7 22.4 21.4
3.29 3.21 3.05 2.87
64.1 59.1 54.5 51.4
19.5 18.0 16.5 15.6
7.95 7.77 7.59 7.49
20.5 19.7 18.8 18.4
2.36 2.23 2.10 2.01
49.5 44.4 39.4 34.3
15.0 13.5 12.0 10.4
7.42 7.24 7.06 6.88
18.2 17.4 16.3 15.5
1.95 1.80 1.63 1.46
29.3 24.0
8.9
7.3
kW
6.70 6.52
14.4 13.2
1.28 1.08
Amps
COP
EER
11.2 11.0 10.4
9.8
209
43
8.1
200
39
7.6
191
34
7.2
183
30
6.9
179
28
6.7
176
27
6.1
169
23
5.6
162
20
5.0
156
17
4.4
150
15
3.7
145
11
Hi PR
Lo PR
268
72
257
67
247
63
236
57
230
54
226
52
217
48
GSH101203A* / AR120
Outdoor Ambient Temperature
65°F 60°F 55°F 50°F 47°F 45°F 40°F 35°F 30°F 25°F 20°F 17°F 15°F 10°F
5°F
0°F
-5°F -10°F
MBh
∆T
132.6 125.5 118.2 110.5 105.5 102.2 95.0 87.6
85.4 78.8 72.5 68.5
19.8 18.2 16.8 15.9
9.69 9.47 9.26 9.13
18.4 17.6 16.7 16.3
2.58 2.44 2.29 2.20
66.0 59.2 52.5 45.8
15.3 13.7 12.1 10.6
9.05 8.83 8.62 8.41
16.1 15.2 14.1 13.3
2.13 1.96 1.78 1.59
39.0 32.0
30.7 29.1 27.4 25.6
10.41 10.21 10.01 9.81
28.3 26.2 24.5 23.0
3.73 3.60 3.45 3.29
12.7 12.3 11.8 11.3
24.4 23.7 22.0 20.3
9.70 9.62 9.43 9.23
22.1 21.7 20.4 19.3
3.18 3.11 2.95 2.78
9.0
7.4
kW
8.19 7.98
12.2 10.9
1.40 1.17
Amps
COP
EER
10.9 10.6 10.1
9.5
172
39
8.8
165
36
8.3
157
32
7.8
151
28
7.5
147
26
7.3
145
25
6.7
139
21
6.1
134
18
5.4
128
15
4.8
124
13
4.0
120
11
Hi PR
Lo PR
221
66
212
62
203
58
195
53
190
50
186
48
179
44
High pressure is measured at the sucꢀon service valve ( the larger valve).
Low pressure is measured at the gauge port connecꢀon.
Amps = Outdoor unit amps (comp.+fan)
kW = Total system power
Calculaꢀons are based on nominal CFM and 70 °F indoor dry bulb.
10
SS-GSH10C
Download from Www.Somanuals.com. All Manuals Search And Download.
pRoduCt SpECifiCationS
WiRinG diaGRam
SS-GSH10C
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Product SPecificationS
dimenSionS
W
D
Dimensions
Model
W"
35½
35½
D"
H"
41½
37½
H
GSH100903**
GSH101203**
35½
35½
acceSSorieS
GSH10
090**
GSH10
120**
Model
Description
•
ABK-20
Anchor Bracket Kit
X
X
X
X
X
X
X
X
AFE18-60A
FSK01A¹
All-fuel Kit
Freeze Protecꢀon Kit
OT18-60A²
Outdoor Thermostat with Lockout Stat
•
Contains 20 brackets; four brackets needed to anchor unit to pad
Installed on indoor coil
¹
²
Required for heat pump applicaꢀons where ambient temperatures fall below 0 °F with 50% or higher
relaꢀve humidity.
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without
notice or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
12
SS-GSH10C
Download from Www.Somanuals.com. All Manuals Search And Download.
|