Goodman Mfg Air Conditioner SS CPG180 240 User Manual

CPG CommerCial  
15- & 20-Ton, Three-phase  
paCkaged gas/eleCTriC UniTs  
15 Tons  
20 Tons  
Cooling CapaCiTy: 180,000 BTU/h  
Cooling CapaCiTy: 240,000 BTU/h  
heaTing CapaCiTy: 350,000 BTU/h  
heaTing CapaCiTy: 400,000 BTU/h  
Contents  
Nomenclature.............................................................................................2  
Product Features ......................................................................................3  
Product Specifications...........................................................................4  
Airflow Data..................................................................................................6  
Expanded Cooling Data........................................................................8  
Dimensions................................................................................................ 12  
Wiring Diagrams .................................................................................... 16  
Accessories................................................................................................. 20  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6/11  
Supersedes 2/11  
prodUCT speCifiCaTions  
prodUCT feaTUres  
Standard Features  
R-410A chlorine-free refrigerant  
TuffTube™ tubular heat exchanger  
High-efficiency scroll compressor  
Copper tube / aluminum fin coils  
High- and low-pressure switches  
High-capacity, steel-cased filter dryer  
Built-in filter rack with standard 2lters  
(convertible to 4lters)  
24-volt terminal strip  
Contactor with lugs  
Easy to service  
Bottom utility entry  
Complies with California NOx  
emissions standards  
AHRI Certified; ETL Listed  
Cabinet Features  
Heavy-gauge, galvanized-steel cabinet  
with UV-resistant powder-paint finish  
Full Perimeter Rail  
Sloped drain pan  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
prodUCT speCifiCaTions  
prodUCT speCifiCaTions 15 Tons  
CPG180350  
3B***  
CPG180350  
4B***  
CPG180***  
7B***  
Cooling Capacity  
Total, BTU/h  
Sensible BTU/h  
EER / IEER  
Decibels  
180,000  
127,500  
10.8 / 11  
88  
180,000  
127,500  
10.8 / 11  
88  
180,000  
127,500  
10.8 / 11  
88  
ARI Reference #s  
3965698  
3965698  
3965698  
Heating Capacity  
Max. Input: High / Low KBTU/h  
Output: High / Low KBTU/h  
Steady State Efficiency (%)  
Temperature Rise: High / Low (°F)  
No. of Burners  
350 / 262  
280 / 210  
80  
30-60 / 20-50  
7
350 / 262  
280 / 210  
80  
30-60 / 20-50  
7
350 / 262  
280 / 210  
80  
30-60 / 20-50  
7
Evapoartor Motor / Coil  
Motor Type (Belt Drive)  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Std Staꢀc  
5,400  
12.7  
5.0 - 1,725  
TXV  
Std Staꢀc  
5,400  
6.4  
5.0 - 1,725  
TXV  
Std Staꢀc  
5,400  
5.1  
5.0 - 1,725  
TXV  
Metering Device  
Filter Size (#)  
Drain Size (NPT)  
20 x 25 x 2 (6)  
1"  
20 x 25 x 2 (6)  
1"  
20 x 25 x 2 (6)  
1"  
R-410A Refrigerant Charge Cir #1 & 2  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
290 oz.  
20  
4 / 16  
290 oz.  
20  
4 / 16  
290 oz.  
20  
4 / 16  
2 (15" x 12")  
1VP50 x 1⅛"  
2 (15" x 12")  
1VP50 x 1⅛"  
2 (15" x 12")  
1VP50 x 1⅛"  
Motor Sheave  
Blower Sheave / Belt  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
BK90 x 1³/₆" / BX42  
BK90 x 1³/₆" / BX42  
BK90 x 1³/₆" / BX42  
3
3
3
⅓ - 1,075  
22 / 3  
7,200  
53.3  
⅓ - 1,075  
22 / 3  
7,200  
53.3  
⅓ - 1,075  
22 / 3  
7,200  
53.3  
Rows Deep / Fins per Inch  
Compressor  
2 / 18  
2 / 18  
2 / 18  
Quanꢀty / Type  
2 / Scroll  
25 / 164  
29.5 / 195  
2 / Scroll  
12.2 / 100  
14.7 / 95  
2 / Scroll  
9.0 / 78  
12.2 / 80  
Compressor RLA / LRA CIR. #1  
Compressor RLA / LRA CIR. #2  
Electrical Data / Static  
Voltage / Phase / Frequency  
Standard Max Staꢀc  
208-230/3/60  
1.2  
460/3/60  
1.2  
575/3/60  
1.2  
Outdoor Fan FLA / LRA  
Total Unit Amps  
2.4 / 5.2  
74.4  
1.2 / 2.6  
36.9  
.9 / 2.2  
29  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
81.8  
100  
2⅛"  
⅞"  
2155  
2270  
40.6  
50  
2⅛"  
⅞"  
2155  
2270  
32.1  
40  
2⅛"  
⅞"  
2155  
2270  
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
prodUCT speCifiCaTions 20 Tons  
CPG240  
4003B***  
CPG240  
4004B***  
CPG240  
4007B***  
Cooling Capacity  
Total, BTU/h  
Sensible BTU/h  
EER / IEER  
Decibels  
240,000  
170,000  
9.8 / 10.0  
88.3  
240,000  
170,000  
9.8 / 10.0  
88.3  
240,000  
170,000  
9.8 / 10.0  
88.3  
AHRI Reference #s  
3897346  
3897346  
3897346  
Heating Capacity  
Max. Input High / Low (KBTU/h)  
Output BTU/h  
Steady State Efficiency (%)  
Temperature Rise Range (°F) High/Low  
No. of Burners  
400 / 300  
320 / 240  
80  
25-55 / 15-45  
8
400 / 300  
320 / 240  
80  
25-55 / 15-45  
8
400 / 300  
320 / 240  
80  
25-55 / 15-45  
8
Evaporator Motor / Coil  
Motor Type (Belt Drive)  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Std Staꢀc Belt Drive  
Std Staꢀc Belt Drive  
Std Staꢀc Belt Drive  
7,000  
12.7  
5.0 - 1,725  
TXV  
7,000  
6.4  
5.0 - 1,725  
TXV  
7,000  
5.1  
5.0 - 1,725  
TXV  
Metering Device  
Filter Size (#)  
Drain Size (NPT)  
25 x 25 x 2 (6)  
1"  
25 x 25 x 2 (6)  
1"  
25 x 25 x 2 (6)  
1"  
R-410A Refrigerant Charge Cir #s 1 & 2  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave  
320 oz.  
20  
4 / 16  
320 oz.  
20  
4 / 16  
320 oz.  
20  
4 / 16  
2 (15" x 15")  
1VP60 x 1⅛"  
2 (15" x 15")  
1VP60 x 1⅛"  
2 (15" x 15")  
1VP60 x 1⅛"  
Blower Sheave / Belt  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
BK100 x 1/₆" / BX46  
BK100 x 1/₆" / BX46  
BK100 x 1/₆" / BX46  
3
3
3
⅓ - 1,075  
22 / 3  
7,200  
53.3  
⅓ - 1,075  
22 / 3  
7,200  
53.3  
⅓ - 1,075  
22 / 3  
7,200  
53.3  
Rows Deep / Fins per Inch  
Compressor  
2 / 18  
2 / 18  
2 / 18  
Quanꢀty / Type  
2 / Scroll  
33.3 / 239  
2 / Scroll  
17.9 / 125  
2 / Scroll  
12.8 / 80  
Compressor RLA / LRA ea.  
Electrical Data / Static  
Voltage / Phase / Frequency  
Standard Max Staꢀc  
Outdoor Fan FLA / LRA  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
208-230/3/60  
1.4  
460/3/60  
1.4  
1.2 / 2.6  
45.8  
50  
60  
2⅛"  
⅞"  
2275  
2390  
575/3/60  
1.4  
.9 / 2.2  
33.4  
37  
45  
2⅛"  
⅞"  
2275  
2390  
2.4 / 5.2  
86.5  
95  
125  
2⅛"  
⅞"  
2275  
2390  
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
prodUCT speCifiCaTions  
airflow daTa 15 Tons  
Standard Belt Drive ― Down Shot  
Turns Open  
ESP  
(" H₂O)  
0
1
2
3
4
5
6
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
0.00  
2.76  
2.41  
2.05  
CFM  
6827  
6161  
5434  
BHP  
2.67  
2.34  
2.02  
CFM  
6394  
5706  
4949  
BHP  
2.28  
1.98  
1.68  
CFM  
5982  
5271  
BHP  
1.94  
1.66  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
7079  
6405  
5668  
3.20  
2.83  
2.45  
6623  
5923  
5152  
6903  
6198  
5418  
3.32  
2.92  
2.51  
6717  
5975  
5147  
3.42  
2.99  
2.55  
High-Static Belt Drive ― Down Shot  
Turns Open  
ESP  
(" H₂O)  
0
1
2
3
4
5
6
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
6690  
5922  
5056  
BHP  
3.69  
3.22  
2.74  
CFM  
6008  
5182  
BHP  
3.02  
2.58  
CFM  
BHP  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
5321  
2.43  
6653  
5857  
4948  
3.95  
3.44  
2.91  
6634  
5808  
4855  
2.80  
2.43  
2.05  
6638  
5784  
4788  
4.55  
3.95  
3.32  
6683  
5803  
4.93  
4.27  
Notes  
Airflow table represent dry coil with filters installed; SCFM correcꢀon factor for wet coil is 4%.  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaꢀon that exceed the above could  
require a larger motor. Minimum rated SCFM is 350 per ton.  
High-staꢀc airflow requires installaꢀon of high kit (HSKT180G) or factory-built high-staꢀc model.  
Unit factory shipped with the sheave set at 2.5 turns open.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
airflow daTa 20 Tons  
Standard Belt Drive ― Down Shot  
Turns Open  
ESP  
(" H₂O)  
0
1
2
3
4
5
6
CFM  
BHP  
CFM  
BHP  
CFM  
9359  
8632  
7879  
7097  
BHP  
4.92  
4.39  
3.86  
3.35  
CFM  
8991  
8251  
7484  
BHP  
3.79  
3.39  
2.99  
CFM  
8621  
7867  
7085  
BHP  
3.54  
3.15  
2.75  
CFM  
8188  
7363  
BHP  
3.27  
2.85  
CFM  
7826  
6992  
BHP  
3.04  
2.63  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
9018  
8279  
7513  
6716  
3.18  
2.96  
2.73  
2.49  
7957  
7179  
6368  
4.82  
4.23  
3.66  
High-Static Belt Drive ― Down Shot  
Turns Open  
ESP  
(" H₂O)  
0
1
2
3
4
5
6
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
9001  
8262  
7495  
BHP  
6.83  
6.15  
5.48  
CFM  
8394  
7632  
6841  
BHP  
6.01  
5.35  
4.71  
CFM  
7797  
7012  
BHP  
4.78  
4.20  
CFM  
BHP  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
7227  
4.28  
8891  
8148  
7377  
6.83  
6.15  
5.48  
8811  
8065  
7290  
6.86  
6.19  
5.52  
7998  
7221  
6.89  
6.10  
Notes  
Airflow table represent dry coil with filters installed; SCFM correcꢀon factor for wet coil is 4%.  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaꢀon that exceed the above could  
require a larger motor. Minimum rated SCFM is 350 per ton.  
High-staꢀc airflow requires installaꢀon of high kit (HSKT240) or factory-built high-staꢀc model.  
Unit factory shipped with the sheave set at 2.5 turns open.  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
prodUCT speCifiCaTions  
expanded Cooling daTa 15 Tons  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
expanded Cooling daTa 15 Tons (ConT.)  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
prodUCT speCifiCaTions  
expanded Cooling daTa 20 Tons  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
expanded Cooling daTa 20 Tons (ConT.)  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
prodUCT speCifiCaTions  
dimensions  
88/₂”  
133½”  
50/₂”  
5/₂”  
Vertical Discharge (Top of Unit)  
Gas Inlet Location (¾” NPT)  
9⅔”  
46¹/₀”  
Flue Vent  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
UniT ClearanCes  
Maintain an adequate clearance around the unit for safety, service, maintenance, and  
proper unit operation. Leave a total clearance of 75on the main control panel side  
of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace.  
Leave a clearance of 48on all other sides of the unit for possible compres-  
sor removal or service access, and to ensure proper ventilation and  
condenser airflow. Do not install the unit beneath any obstruction.  
Install the unit away from all building exhausts  
to inhibit Ingestion of exhaust air into the unit’s fresh-  
air intake.  
36minimum  
roof overhang  
eleCTriCal enTranCe loCaTions  
12¹/”  
3³/”  
High-Voltage  
Entrance  
Low-  
Voltage  
Entrance  
3/”  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
prodUCT speCifiCaTions  
roof CUrB insTallaTion — rigging  
Provisions for forks have been included in the unit base frame. No other  
fork locations are approved.  
Unit must be lifted by the four lifting holes located at the base frame  
corners.  
Lifting cables should be attached to the unit with shackles.  
The distance between the crane hook and the top of the unit must  
not be less than 60.  
Two spreader bars must span over the unit to prevent damage to the  
cabinet by the lift cables. Spreader bars must be of sufficient length  
so that cables do not come in contact with the unit during transport.  
Remove wood struts mounted beneath unit base frame before set-  
ting unit on roof curb. These struts are intended to protect unit base  
frame from fork lift damage. To remove the struts, extract the sheet  
metal retainers and pull the struts through the base of the unit. Refer  
to rigging label on the unit.  
Important: If using bottom discharge with roof curb, duct-work should  
be attached to the curb prior to installing the unit. Duct-work dimensions  
are shown in Roof Curb Installation Instructions Manual.  
Refer to the Roof Curb Installation Instructions  
for proper curb installation. Curbing must be  
installed in compliance with the National Roofing  
Contractors Association Manual.  
Lower unit carefully onto roof mounting curb.  
While rigging the unit, the center of gravity will  
cause the condenser end to be lower than the  
supply air end.  
Compressor 1  
40”  
Bring condenser end of unit into alignment with  
the curb. With condenser end of the unit resting on  
curb member and using curb as a fulcrum, lower  
opposite end of the unit until entire unit is seated  
on the curb. When a rectangular cantilever curb is  
used, take care to center the unit. Check for proper  
alignment and orientation of supply and return  
openings with duct.  
Compressor 2  
58”  
Corner & Center-of-Gravity Locations  
Weights  
15-Ton Units  
Weights  
(lbs.)  
20-Ton Units  
(lbs.)  
Corner Weight A  
Corner Weight B  
Corner Weight C  
Corner Weight D  
Shipping Weight  
Operaꢀng Weight  
570  
535  
Corner Weight A  
Corner Weight B  
Corner Weight C  
Corner Weight D  
Shipping Weight  
Operaꢀng Weight  
655  
535  
545  
600  
510  
485  
2270  
2155  
2390  
2275  
To assist in determining rigging requirements, unit weights are shown to the right.  
Note: These weights are calculated without installed accessories.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
roof CUrB insTallaTion  
Curb installations must comply with local codes and should follow the established guidelines of the National Roofing  
Contractors Association.  
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for  
adequate fastening method prior  
to setting the unit on the curb.  
Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for  
field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the  
sheet metal curb is included in the curb accessory package.  
Determine sufficient structural support before locating and mounting the curb and package unit.  
Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting  
the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type  
curbs are not available from the factory.  
Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.  
Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate  
supply and return duct openings.  
Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installation  
after unit placement  
is not recommended.  
See the manual shipped with the roof curb for assembly and installation instructions.  
123 Curb Top O.D.  
119¾ Curb Top O.D.  
17²/₅  
17²/₅  
17²/₅  
74¾  
Curb O.D.  
61⅞  
61⅞  
23⅞  
78 Curb  
Top O.D.  
1⅝ Typ.  
Insulated  
Panels  
11¼  
1¾  
1¾  
123 Curb Bottom O.D.  
1⅜  
Typ.  
77½ Curb Bottom O.D.  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
prodUCT speCifiCaTions  
wiring diagram Cpg180/240***3B*** Three-phase 208-230 BelT drive  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
wiring diagram Cpg180/240***3B*** Three-phase 208-230 BelT drive  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
prodUCT speCifiCaTions  
wiring diagram Cpg180/240***4B***/7B* Three-phase 460/575 BelT drive  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  
prodUCT speCifiCaTions  
wiring diagram Cpg180/240***4B/7B*** Three-phase 460/575 BelT drive  
SS-CPG180-240  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
prodUCT speCifiCaTions  
aCCessories  
Fits  
Model Sizes  
Item #  
Description  
14CURB180240  
25FD180240  
25MFD180240  
CDK180  
Roof Curb 14" Tall  
15-20 tons  
15-20 tons  
15-20 tons  
15 tons  
25% Manual Fresh Air Damper  
25% Motorized Fresh Air Damper  
Concentric Duct Kit  
CDK240  
Concentric Duct Kit  
20 tons  
DNECONGS180240  
GHRC-1  
Downflow Economizer  
15-20 tons  
All Models  
All Models  
Hurricane Restraint Clip  
High Alꢀtude Kit  
HAKT36300  
LPKT180240  
LP Conversion Kit  
HSKT180  
High Staꢀc Kit  
15 tons  
HSKT240  
High Staꢀc Kit  
20 tons  
HZCURB180240ED  
HZCURB180240SDS  
HZCURB180240SDN  
LAKT03  
Horizontal Discharge Curb — End Discharge  
Horizontal Discharge Curb — Side Discharge¹  
Horizontal Discharge Curb — Side Discharge²  
Low Ambient Kit  
15-20 tons  
15-20 tons  
15-20 tons  
15-20 tons  
15-20 tons  
15-20 tons  
PE1802402  
Power Exhaust 208/230v  
Power Exhaust 460v  
PE1802404  
¹ Duct openings on service side  
² Duct openings on non-service side  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without  
notice or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. Houston, Texas • Printed in the USA.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG180-240  

Echo Bear Cat Chipper CH4540 User Manual
Electro Voice Home Security System P 1200 User Manual
Escort CD Player 3004B User Manual
EverFocus Security Camera EQ610 User Manual
Exmark Lawn Mower TR23KC User Manual
Extron electronic Car Satellite TV System 330 D User Manual
Extron electronic Network Card RGB 400 Series User Manual
Fisher Price Car Seat 75320 User Manual
GE Waffle Iron 898678 User Manual
Gianni Industries Door 10020 User Manual