PRODUCT SPECIFICATIONS  
CKF SERIES  
50 HZ  
COOLING-ONLY  
2- TO 6-TON  
CONDENSING UNIT  
NOMINAL CAPACITY:  
24,600 TO 64,000 BTU/H  
[10.6 KW TO 20.5 KW]  
This 50-Hz split system air conditioner allows for ground-level or rooftop applications  
and has been tested for optimum performance by an independent third party.  
Standard Features  
• Quiet-operating top discharge  
Cabinet Features  
• Unique Goodman® sound control design  
• Heavy-gauge, galvanized-steel cabinet properly  
reinforced and braced  
• Brass suction and liquid line shut-off valves  
• High-pressure manual reset control  
• Copper tube/aluminum n coils  
• Factory-installed liquid line lter dryer  
• Contactor with lug connections  
• Ground lug connection  
• Steel louver coil guard  
• Attractive architectural gray powder-paint nish  
with 500-hour salt spray approval  
• Removable access panels  
• Sweat connections on all units  
Accessories  
Totally enclosed, permanently lubricated  
condenser motor designed for PSC operation  
with internal thermal overload protection  
• Isolated compressor compartment  
• Energy-efcient compressor with internal  
overload protection  
• Cooling-only room thermostat (CT18-60)  
• Cooling/Heating room thermostat (CHT18-60)  
• Cooling/Heating digital thermostat (CHT18-60-HD)  
• Designed for use with A Series air handlers  
• Independent third-party performance tested  
with matching outdoor sections by ETL Testing  
Laboratories, Inc., per ARI Standard 210-240  
• CE Certied  
SS-CKF50  
11/06  
Supersedes 10/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT SPECIFICATIONS  
SPECIFICATIONS  
CKF24-2*  
CKF36-2*  
CKF36-5*  
CKF48-5*  
CKF60-5*  
CKF70-5*  
Capacities  
Nominal Cooling (BTU/h)  
EER¹  
24,600  
9.0  
34,000  
9.0  
34,000  
9.0  
44,000  
9.0  
55,000  
9.0  
64,000  
9.0  
Decibels  
76  
76  
78  
78  
80  
80  
Compressor  
RLA  
LRA  
12.5  
61  
17.9  
97.4  
5.3  
42  
7.4  
50  
9
74  
10.9  
101  
Volts  
220-240  
220-240  
380-420  
380-420  
380-420  
380-420  
Condenser Fan Motor  
Horsepower  
FLA  
1/4  
0.9  
220-240  
1/4  
0.9  
220-240  
1/4  
0.8  
380  
1/4  
0.8  
380  
1/4  
0.8  
380  
1/3  
1.2  
380  
Volts  
Refrigeration System  
Liquid Valve Size (“O.D.)  
Suction Valve Size (“O.D.)  
Valve Type  
Refrigerant Charge  
Shipped with Orice Size  
Condenser Fan / Coil  
Horsepower - RPM  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ft²)  
3/8  
3/4  
Sweat  
88  
3/8  
3/4  
Sweat  
89  
3/8  
7/8  
Sweat  
89  
3/8  
7/8  
Sweat  
113  
3/8  
7/8  
Sweat  
121  
3/8  
7/8  
Sweat  
153  
0.059  
0.068  
0.068  
0.078  
0.093  
0.096  
1/4-950  
20/3  
1800  
13.3  
1/4-950  
20/3  
1800  
13.3  
1/4-950  
20/3  
1800  
13.3  
1/4-950  
22/3  
2400  
15.6  
1/4-950  
22/3  
2600  
17.1  
1/3-1075  
22/3  
3200  
20  
Rows Deep/ Fins per Inch  
Fin Type  
Coil No. of Tubes  
Coil Tube Diameter (in.)  
Electrical Data  
1/19  
Ripple  
22  
1/19  
Ripple  
22  
1/19  
Ripple  
22  
1/19  
Ripple  
22  
1/19  
Ripple  
24  
1/22  
Ripple  
36  
0.375  
0.375  
0.375  
0.375  
0.375  
0.375  
Voltage-Hz / Phase  
Min. Circuit Ampacity²  
Max. Overcurrent Protection (amps)³  
Min / Max Volts  
Power Supply Conduit Size  
Ship Weight (lbs-[kg])  
220/240-50/1 220/240-50/1 380/415-50/3 380/415-50/3 380/415-50/3 380/415-50/3  
16.6  
25  
23.3  
40  
7.5  
15  
10  
15  
12  
20  
14.8  
20  
198/264  
1/2 or 3/4  
180 (82)  
198/264  
1/2 or 3/4  
184 (84)  
342/456  
1/2 or 3/4  
184 (84)  
342/456  
1/2 or 3/4  
191 (87)  
342/456  
1/2 or 3/4  
210 (95)  
342/456  
1/2 or 3/4  
228 (104)  
¹ Energy Efciency Ratio  
² Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
DIMENSIONS  
Model  
Width  
Depth  
Height  
CKF24-2*  
CKF36-2*  
CKF36-5*  
CKF48-5*  
CKF60-5*  
CKF70-5*  
26  
26  
26  
29  
29  
29  
26  
26  
26  
29  
29  
29  
29¾  
29¾  
29¾  
29¾  
32¼  
38¼  
SS-CKF50  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT SPECIFICATIONS  
SCHEMATIC WIRING DIAGRAM  
Power Circuit  
WIRE CODE: Y - Yellow • PU - Purple  
Low-Voltage Circuit  
Component Legend  
C - Contactor  
Comp - Compressor  
FC - Fan Motor Capacitor  
HP - High-pressure Control  
FM - Fan Motor  
IO - Internal Overload  
Single-Phase Line Voltage  
Quality Makes the Difference!  
All of our systems are designed and manufactured with the same high-quality standards, regardless of size or efciency. We have designed these units to signicantly reduce  
the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit is run-tested  
before it leaves the factory. That’s why we know... there’s no better quality.  
Goodman Manufacturing Company, L.P.  
2550 North Loop West, Suite 400  
Houston, Texas 77092 USA  
Visit our website at  
Goodman Products • Customer Services • Parts  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specications or designs without notice or without incurring obligations.  
Copyright © 2003 Goodman Manufacturing Company, L.P. Houston, Texas Printed in the USA. Goodman products are made proudly in the USA.  
4
SS-CKF50  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Ei Electronics Smoke Alarm Ei175 User Manual
Excalibur electronic Games World Series User Manual
Fagor America Electric Pressure Cooker Rapida User Manual
Fellowes Paper Shredder 125Ci 125i User Manual
Fisher Price Backyard Playset 75967 User Manual
GE Monogram Refrigerator ZISS480DXSS User Manual
GE Photo Printer JGBP85SEJ User Manual
GE Toaster 168989 User Manual
Giant Pressure Washer GP7122 User Manual
Globalsat Technology GPS Receiver BU 333N User Manual