Dehumidifier
SERVICE MANUAL
MODEL: DH3010B(DHA3012DL)
DH4010B(DHA4012DL)
DH5010B(DHA5012DL)
CAUTION
- BEFORE SERVICING THE UNIT,
READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
- ONLY FOR AUTHORIZED SERVICE.
Download from Www.Somanuals.com. All Manuals Search And Download.
1. PREFACE
This Service Manual provides various service information, containing the mechanical and electrical parts etc.
This dehumidifier was manufactured and assembled under the strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precaution prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
• Disconnect power supply before servicing or replacing any electrical or non-electrical component.
• Do not cut off the grounding prong or alter the plug in any manner at any circumstances.
1.2 FEATURES
• Quiet
• High efficiency
• Adjustable humidistat
• Automatic defrost
• Automatic shut-off
• Bucket-full indicator light
• Easy roll casters
• Removable & large capacity bucket.
• Washable air filter
• 2 fan speeds
• Drain hose connection.
1.3 DIMENSIONS (mm/in)
445 (17 1/2)
320 (12 9/16)
340 (13 3/8)
—3—
Download from Www.Somanuals.com. All Manuals Search And Download.
1.4 SPECIFICATIONS
MODELS
DH3010B
DH4010B
DH5010B
(DHA3012D*)
(DHA4012D*)
(DHA5012D*)
ITEMS
CAPACITY (Pint/Day)
POWER SUPPLY (Phase, V, Hz)
REFRIGERANT
30
40
50
1ø, 115V, 60Hz
R134a
R22
REFRIGERANT CHARGE, oz(g)
CONTROL, DEFROST
4.76(135)
5.11(145)
7.05(200)
+ 2
– 3
+ 2
OPEN : 32°F(0°C
)
OPEN : 32°F(0°C
)
– 3
–
+ 3
– 3
+ 3
– 3
CLOSE : 52.6°F(13°C
)
CLOSE : 53.6°F(13°C
)
OPEN : 28.4°F(-2°C ±2)
OPEN : 26.6°F(-3°C ±2)
OPEN : 28.4°F(-2°C ±2)
THERMOSTAT
HUMIDISTAT
CLOSE : 55.4°F(13°C ±2) CLOSE : 55.4°F(13°C ±2) CLOSE : 55.4°F(13°C ±2)
CONTROL RANGE : 20% ~ 80% RH
NORMAL SETTING : 42 ± 5% RH
COMPRESSOR MODEL NO.
TYPE
LX86HACG
P220MC
QA075CH
QA082CH
WORKING TIME: 0.2 ~ 0.7 sec.
RETURN TIME: 60 sec.
TIME
P.T.C.
–
ASSEMBLY
AMPERE
7A
MAXIMUM
VOLTAGE
300V
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR(FUSE) FOR MOTOR
PROTECTOR
CAPACITOR
-
25µF, 270VAC
6A/125VAC, 12A/250VAC
SWITCH, ROTARY
MOTOR ASSEMBLY, SINGLE
SWITCH ASSEMBLY, MICRO
Shaded pole motor, 65W/1A↓, Thermal cutoff : 266°F/130°C
16A/125VAC, 8A/250VAC
OUTSIDE
DIMENSIONS
W x H x D, mm(in)
WITHOUT BUCKET
320 x 530 x 340 (12 9/16 x 20 13/16 x 13 3/8)
320 x 530 x 445 (12 9/16 x 20 13/16 x 17 1/2)
WITH BUCKET
NET WEIGHT, kg(lbs)
21.5(47)
17.2(38)
17.7(39)
※ NOTE : Specifications are subject to minor change without notice for further improvement.
—4—
Download from Www.Somanuals.com. All Manuals Search And Download.
1.5 CONTROL
Humidity Control
•
When you first use the dehumidifier, turn the humidity
control to 5 or 6. If you still have moisture, turn the
humidity control to a higher setting.
5
Low
High
6
4
7
3
1
MAX is the highest setting.
8
2
• When excess moisture and dampness odors are gone,
adjust the control to a lower setting. Use the
Auto
Shut-Off
9
Off
Max.
dehumidifier as long as excess moisture is present.
Fan Speed
Humidity Control
Fan Speed
Auto Shut-Off
•
The fan control adjusts the fan speed.
•
Glows when the bucket is ready to be emptied, or when
the bucket is removed or not replaced in the proper
position.
Set the fan control to HIGH for maximum moisture
removal. When the humidity has been reduced and
quiet operation is preferred, set the fan control to LOW.
• The Water Level Control Switch shuts off the
dehumidifier when the bucket is full, or when the bucket
is removed or not replaced in the proper position.
1.6 HOW TO OPERATE DEHUMIDIFIER
1.6.1 HOW DOES THE DEHUMIDIFIER WORK?
Moist, humid air is drawn over a cold refrigerated
dehumidifying coil. Moisture in the air condenses on this
coil and drains into a bucket (or through the bucket into a
hose and drain).
Condenser
Fan
Evaporator
Dry
Air Out
Humid
Air In
Dry, clean air is drawn over the condenser where it is
actually heated several degrees and discharged out the
front grille into the room.
Motor
Bucket
It is normal for the surrounding air to become slightly
warmer as the dehumidifier operates.
This warming effect further reduces the relative humidity
of the surrounding air.
Drain
Connection
Compressor
Figure 1
Side View
1.6.2 LOCATION FOR THE DEHUMIDIFIER
Allow at least 12 inches of space on all sides of the
unit for good air circulation.
I The dehumidifier must be operated in an enclosed
area to be most effective.
Air In
I Close all doors, windows and other outside
openings to the room.
Place the dehumidifier in a location that does not
restrict air flow into the rear coil or out the front grille.
12"
12"
A dehumidifier operating in a basement will have little
or no effect in drying an adjacent enclosed storage
area, such as a closet, unless there is adequate
circulation of air in and out of the area.
Air Out
Figure 2
—5—
Download from Www.Somanuals.com. All Manuals Search And Download.
1.6.3 MICRO SWITCH
The micro switch assembly, which is located on the barrier of inside unit, automatically shuts off the dehumidifier when the
bucket is full (note, the Auto Shut Off lights, to indicate bucket must be emptied). The bucket replaces in its place, the unit again
turns itself on.
1.6.4 AUTO DEFROST
When frost builds up on the cooling coils, the compressor will cycle off until the frost disappears. The fan continues to run.
NOTE: This unit is designed to be operated at temperatures above 65°F(18°C). If the dehumidifier is operated in low
temperature conditions, the temperature and humidity conditions of room are low, some frost can be formed in
its evaporator coil and the unit will be operated ON/OFF repeatedly. In this case, please check on your room
temperature condition and stop the unit.
1.6.5 HUMIDISTAT
Humidistat controls constant relative humidity in the room
automatically.
5(42%)
40%
42% R.H
4(50%)
When the relative humidity in the room increases to the
selected level, the dehumidifier starts automatically. And the
relative humidity drops to the selected level, the
dehumidifier stops automatically.
6(35%)
3(60%)
7(30%)
When the first using the dehumidifier, it is recommended,
for the first three or four days, to operate the unit with the
humidistat control set to MAX. At this setting, the unit will
run continuously.
When the sweating has stopped and the dampness odors
have gone, it is preferable to select the humidistat position
that will best suit local conditions.
2(70%)
8(25%)
9(20%)
The relative humidity range it can control is from 20 % to
80%. (See Figure 3)
1(80%)
Off
Max.
NOTE: The relative humidity at the number is the
DEAD DIAL
approximate value.
Figure 3
1.6.6 DRIER (For some models)
Dryer is used to prevent capillary blockage from moisture in
the refrigerant system and H/E, condenser and evaporator.
Also, dryer is used to remove corrosion of the components.
NOTE: When dryer is replaced, proper injection to
capillary is needed. On opening the dryer, it
should be welded instantly. The oxidization of
dryer inside and all tubes inside after welding
can be prevented.
Dryer
Figure 4
—6—
Download from Www.Somanuals.com. All Manuals Search And Download.
2. CIRCUIT DIAGRAM
• MODEL : DH3010B/DHA3012DL
SWITCH,
ROTARY
BK
WH
4
BK(HI)
1
RD(LO)
GR/YL
GR/YL
6
C
BK(HI)
N.C
RD(L)
N.O
MOTOR
OR(COM)
BR
BR
BR
BK
6
1
2
M
3
4
TERMINAL
BLOCK
S
5
COMP.
BK
BL
C
O.L.P.
CONTROL,
DEFROST
WIRING DIAGRAM
3854A20015H
PART NO.
DH3010B
LOCATION
Q'TY
PER SET MARKS
RE-
DESCRIPTION
NO.
6411A20001Q
6600A20001A
4681A20040A
6748C-0003A
2521C-A8605
6750C-0002S
6912A30001F
6614A30001H
5216A20001A
6600A30003C
6640A40001A
1
1
1
1
1
1
1
1
1
1
1
S, A
S
POWER CORD ASSEMBLY
SWITCH, ROTARY
1
2
S
MOTOR ASSEMBLY, SINGLE
P.T.C. ASSEMBLY
COMPRESSOR
3
S
4
S
5
S
O.L.P.
6
S
LAMP, NEON
7
S
CONTROL, DEFROST
HUMIDISTAT
8
S, A
S
9
SWITCH ASSEMBLY, MICRO
TERMINAL BLOCK
10
11
S
※ S: SERVICE PARTS
A: ALTERNATE PARTS
N: NOT SERVICE PARTS
—7—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MODEL : DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE)
SWITCH,
ROTARY
BK
WH
4
BK(HI)
1
RD(LO)
GR/YL
GR/YL
6
C
C
BK
RD
OR
N.O
N.C
MOTOR
H
BR
BR
BR
BK
RD
1
2
S
RD
BK
R
COMP.
BK
C
BL
O.L.P.
CONTROL,
DEFROST
WIRING DIAGRAM
3854A20015G
PART NO.
LOCATION
Q'TY
PER SET MARKS
RE-
DESCRIPTION
DH4010B
DH5010B
NO.
6411A20001Q
6600A20001A
4681A20040A
0CZZA20001Q
1
1
1
1
1
1
1
1
1
1
S, A
S
POWER CORD ASSEMBLY
SWITCH, ROTARY
MOTOR ASSEMBLY SINGLE
CAPACITOR
1
2
S
3
S
4
2520UABC2FA
6750U-L039A
5416AR2179J
6614A30001F
S
COMPRESSOR (ROTARY)
O.L.P.
5
S
6
6912A30001F
S
LAMP, NEON
7
–
S
CONTROL, DEFROST
HUMIDISTAT
8
5216A20001A
6600A30003C
S, A
S
9
SWITCH ASSEMBLY, MICRO
10
※ S: SERVICE PARTS
A: ALTERNATE PARTS
N: NOT SERVICE PARTS
—8—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MODEL : DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOSTAT CONTROL TYPE)
BK
WH
SWITCH,
ROTARY
4
(
)
BK HI
(
1
)
RD LOW
GR/YL
GR/YL
6
C
BK
RD
OR
N.O
C
H
MOTOR
N.C
BR
BR
BR
BK
1
2
RD
RD
BK
S
R
COMP
C
L
C
BK
BL
THERMOSTAT
O.L.P
3854A20015M
WIRING DIAGRAM
PART NO.
LOCATION
Q'TY
PER SET MARKS
RE-
DESCRIPTION
DH4010B
DH5010B
NO.
6411A20001Q
6600A20001A
4681A20040A
0CZZA20001Q
1
1
1
1
1
1
1
1
1
1
S, A
S
POWER CORD ASSEMBLY
SWITCH, ROTARY
MOTOR ASSEMBLY SINGLE
CAPACITOR
1
2
S
3
S
4
2520UABC2FA
6750U-L039A
5416AR2179J
2H01127J
S
COMPRESSOR (ROTARY)
O.L.P.
5
S
6
6912A30001F
S
LAMP, NEON
7
2H01127K
S
THERMOSTAT
8
5216A20001A
6600A30003C
S, A
S
HUMIDISTAT
9
SWITCH ASSEMBLY, MICRO
10
※ S: SERVICE PARTS
A: ALTERNATE PARTS
N: NOT SERVICE PARTS
—9—
Download from Www.Somanuals.com. All Manuals Search And Download.
3. DISASSEMBLY INSTRUCTIONS
3.1 MECHANICAL PARTS
3.1.1 BUCKET AND AIR FILTER
2
1. Disconnect the power supply.
2. Turn the Humidity Control off.
3. Remove the bucket. (See Figure 5)
4. Flex the filter at the lower right corner and take it
off. (See Figure 5)
1
Figure 5
3.1.2 FRONT GRILLE
1. Remove 2 screws which fasten the front grille.
2. By pushing the both sides of front grille, pull the
front grille forward and upward. (See Figure 6)
Push
Push
Figure 6
3.1.3. CABINET AND CONTROL BOX
1. Remove the Bucket, the Air filter and Front grille
according to the procedure above.
2. Remove 3 screws that fasten Control box.
(See Figure 7)
3. Remove 9 screws on all sides of the cabinet.
4. Lift the Cabinet from the base.(See Figure 8)
5. Remove a screw fasten the earth wire on the front
of control box.
6. Unhook control box from two hooks on the shroud.
(See Figure 8)
Figure 7
Figure 8
—10—
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2 CONTROL PARTS
3.2.1 ROTARY SWITCH, HUMIDISAT AND
NEON LAMP
1. Unfasten screws located in the bottom side of control box
(see Figure 9) and fasten capacitor clamp. (DH5010B/DH4010B)
And then unfold two sides of control box. (See Figure 9)
2. Disconnect housing and all leads of rotary switch,
humidistat and neon lamp.
3. Remove 4 screws which fasten the rotary switch
and humidistat.
4. Pull the neon lamp out.
DH5010B
DH4010B
DH3010B
3.2.2 CAPACITOR
1. Remove each screw that fastens capacitor after
control box is stretched upper wand.(See Fig. 9)
2. Disconnect all leads of capacitor then remove them
from control box.
Figure 9
3.2.3 DEFROST CONTROL (Some Models)
1. Disconnect all leads of the defrost control in the
Control Box.
Defrost
control
2. Remove the defrost control from the suction tube.
(See Figure 10)
Figure 10
3.2.4 THERMOSTAT CONTROL(Some Models)
1. Disconnect all leads of the thermostat on the
control box.
2. Remove the capacitor in the control box.(some
models)
3. Remove two screws that fasten the thermostat from
the control box. (See figure 11)
Figure 11
3.2.5 MICRO SWITCH ASSY
1. Disconnect the housing with three leads connected
in the Micro switch.
2. Turn the nut left and take off the micro switch from
the barrier. (See Figure 12)
Figure 12
3.2.6 POWER CORD ASSY
1. After the control box opens, remove a screw that
fastens the earth wire of the Power cord.
2. Disconnect housing and all leads of power cord
then remove it from the unit. (See Figure 13)
Figure 13
—11—
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.7 FAN AND MOTOR
1. Turn the nut left and full out the Fan by hands carefully.
2. Remove 2 screws that fasten Heat Exchange.
3. Lift the H/E and open the H/E around 45 degree clockwise carefully. (See Figure 14)
4. Unfasten 3 screws that secure the Motor and earth wire. (See Figure 15)
5. Remove the Motor.
Figure 14
Figure 15
3.2.8 SHROUD AND BARRIER
1. Discharge the refrigerant by using a refrigerant Recovery System.
2. After purging the unit completely, unbrace the Discharge and the Suction tube connected compressor carefully.
3. Remove 2 screws that fasten the H/E.
4. Unfasten 3 screws that secure the shroud on back and sides and upward the shroud from Barrier.
5. Unfasten 2 screws that secure the Barrier to base pan.
6. Pull the Barrier backward then take it up from the base.
Figure 16
—12—
Download from Www.Somanuals.com. All Manuals Search And Download.
3.3 REFRIGERATING CYCLE
3.3.1 CONDENSER, EVAPORATOR AND
CAPILLARY TUBE(HEAT
EXCHANGE ASSEMBLY)
1. Remove the insulation on the H/E assembly
2. Pierce the pinch-off tube to discharge the
TM
refrigerant, using a FREON recovery system.
3. After discharging the refrigerant completely,
remove 2 screws between the shroud and H/E.
(See Figure 17)
4. Lift the H/E and open the H/E around 45 degree
clockwise carefully.
5. Unbrace two interconnecting tubes of the
evaporator and condenser carefully.
Figure 17
6. Remove the H/E assembly from the shroud.
(See Figure 18)
7. Unbrace the capillary tube at the connections of
each condenser and evaporator. (See Figure 19)
8. Remove 4 screws between condenser and
evaporator. (See Figure 19)
Figure 18
Figure 19
—13—
Download from Www.Somanuals.com. All Manuals Search And Download.
3.3.2 P.T.C. OR OVERLOAD PROTECTOR (O.L.P.) FOR RECIPROCATING COMPRESSOR
1. Remove the cabinet. (Refer to section 3.1.3)
2. Remove a screw or a nut which fastens the
terminal cover
3. Disconnect the lead wire from the overload
protector or P.T.C. assembly.
4. Remove the overload protector(O.L.P) or P.T.C.
assembly. (See Figure 20)
Using Recipro Compressor model
Figure 20
3.3.3 ROTARY COMPRESSOR
1. Remove the cabinet. (Refer to section 3.1.3)
2. Discharge the refrigerant by using a refrigerant
Recovery System.
3. After purging the unit completely, unbrace the
suction and discharge tubes at the compressor
connections.
4. Remove the nuts and washers which fasten the
compressor. (See Figure 21)
5. Remove the compressor. (See Figure 21)
Using Rotary Compressor models
Figure 21
—14—
Download from Www.Somanuals.com. All Manuals Search And Download.
3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM
1. When replacing the refrigeration cycle, be sure to
discharge the refrigerant system by using a
refrigerant recovery system.
2. After discharging the unit completely, remove the
desired component, and unbrace the pinch-off
tubes.
7. Recharge as follows :
1) Refrigeration cycle systems are charged from the
High-side. If the total charge cannot be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in Figure
22B.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not
take it. Close valve A.
5) With the unit running, open valve B and add the
balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps B and C until the balance of the
charge is in the system.
4. Solder the pinch-off tubes with service valves.
5. After doing the above procedures, the valve must
be closed and left in place on the system for any
subsequent procedures.
6. Evacuate as follows.
1) Connect the vacuum pump, as illustrated in
Figure 22A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns
counterclockwise and leave the valves closed.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
CAUTION
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being drawn
into the vacuum pump.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum are obtained. Close
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See Figure 22B.
Open valve C.
NOTE: THE REFRIGERANT R134a IS
USED SOME MODELS.
CHECK THE SPECIFICATION
LABEL ON THE CABINET.
When discharging refrigerant R134a, purging instrument
should be used only for R134a, without mixing that of
refrigerant R22.
Discharge the line at the manifold connection.
When checking the leakage of refrigerant R134a,
leakage test tool should be used only for R134a.
5) The system is now ready for final charging.
The pump for discharging should be high efficiency.
Final discharging value must be managed below 0.5 Torr.
Maximum water should be less than quantity 150mg in
the cycle-all tubes and H/E assembly-system.
If water quantity is over 150mg, it causes acid or
corrosion in the cycle system and the capillary tube to be
clogged by water and harmful materials.
The model charged the refrigerant R134a should be
used dryer to prevent water from overflowing.
—15—
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable
of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.
EVAPORATOR ASSEMBLY
(LOW PRESSURE SIDE)
EVAPORATOR ASSEMBLY
(LOW PRESSURE SIDE)
CONDENSER ASSEMBLY
(HIGH PRESSURE SIDE)
CONDENSER ASSEMBLY
(HIGH PRESSURE SIDE)
COMPOUND GAUGE
COMPOUND GAUGE
MANIFOLD
GAUGE
A
MANIFOLD
GAUGE
A
B
B
CAPILLARY
TUBE
CAPILLARY
TUBE
SEE INSETS
BELOW
SEE INSETS
BELOW
COMPRESSOR
COMPRESSOR
LOW HI
A
B
A
B
EXTERNAL
VACUUM PUMP
CHARGING
CYLINDER
C
Figure 22B-Charging
Figure 22A-Pulling Vacuum
—16—
Download from Www.Somanuals.com. All Manuals Search And Download.
4. TROUBLESHOOTING GUIDE
Problem
Possible Causes
Remedy
Dehumidifier does not start.
The dehumidifier is unplugged.
Make sure the dehumidifier's plug is
pushed completely into the outlet.
The fuse is blown/circuit
breaker is tripped.
Check the house fuse/circuit breaker
box and replace the fuse or reset
the breaker.
Water has reached its preset level.
Empty the bucket and replace properly.
Bucket is not in the proper
position and light is on.
Make sure the slots on both sides of
the bucket are positioned correctly.
Check if wiring loose or fails.
Replace wiring.
Dehumidifier does not dry
the air as it should.
The control may not be set high
enough.
Turn the Humidity Control knob to a
higher number.
Room temperature is too low.
Moisture removal is best at higher
room temperatures.
Lower room temperatures will reduce
the moisture removal rate.
This unit is designed to be operated
at temperatures above 65°F(18°C)
Airflow is restricted.
Make sure there are no curtains,
blinds or furniture blocking the front
or back of the dehumidifier.
Doors and windows may
not be closed tightly.
Check that all doors, windows and
other openings are securely closed.
Clothes dryer may be blowing
moisture-laden air into the room.
Install the dehumidifier away from
the dryer.
The dryer should be vented to the
outside.
Check for gas leakage at heat
exchange and connecting tube.
Ineffective dehumidifying
Repair gas leak.
Check if the air filter are clogged
with dust.
Clean the air filter.
Check if the unit is securely
positioned.
Set and use the dehumidifier at a
sturdy, flat, and level place.
Noise
—17—
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDITION
CAUSE
REMEDY
1. Dehumidifier does not start. (Both
compressor and fan motor do not
operate.)
No power
C
heck power supply at outlet.
Correct if none.
Poor plug contact at outlet.
Bucket is full.
Install plug properly or replace it.
If Auto Shut Off lights, empty the bucket
and replace properly.
Humidity control is at Off position
Wire disconnect or loose
Turn the humidity control switch toward
Max.
Connect wire. Refer to wiring diagram for
terminal identification. Repair or replace
loose terminal.
Capacitor.
Test capacitor.
(Discharge capacitor before testing.)
Replace if not within ±10% of
manufacturer's rating. Replace if shorted,
open, or damaged.
2. Motor runs but compressor does not
run.
Voltage (115V ± 10%)
Wiring
It must be between 103.5V and 126.5V. If
not within limits, call an electrician
Check the wire connections; If loose,
repair or replace the terminal. If the wires
are disconnected, refer to wiring diagram
for identification, and replace the wires.
Check the wire connections; If not
according to the wiring diagram, correct
the connections.
Rotary switch
Defrost control
Check for continuity, refer to the wiring
diagram for terminal identification. Replace
the switch if the circuit is open.
The Defrost Control senses frost build-up
on the evaporator coil and automatically
shuts off the compressor. The fan
continues to run, drawing air across the
coil, and melting the frost. When the coil is
defrosted, the compressor automatically
restarts, and dehumidifying resumes.
Capacitor
Check the capacitor.
(Discharge capacitor before servicing.)
Replace if not within ±10% of
manufacturer's rating. Replace if shorted,
open, or damaged.
Compressor
Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor.
Overload protector (O.L.P.)
Check the compressor O.L.P. if externally
mounted. Replace if open. (If the
compressor temperature is high, remove
O.L.P., cool, and retest.)
3. Does not defrost control.
Defrost control is defective.
Low relative humidity
Poor air circulation
Check defrost control, replace it.
Turn dehumidifier off.
4. Insufficient dehumidification
Move dehumidifier to obtain free and
unobstructed air circulation.
H/E clogged with dust and dirt
Air filter is dirty.
Clean evaporator and/or condenser assembly
Clean it.
Motor is not operating.
Check Motor, repair or replace it.
—18—
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDITION
CAUSE
REMEDY
5. Noisy operating
Fan
If cracked, out of balance, or partially
missing, replace it
Some material plunged and rattle.
Tube hits frame.
Remove it.
Adjust tubing routine carefully.
Check Motor Mount. If loose, tighten it.
Replace compressor.
Tighten them.
Fan blade hits frame
Internal compressor noise.
Loose set screws
Worn bearings of Motor Assembly
If knocking sounds continue when running
or loose, replace the motor. If the motor
hums or noise appears to be internal while
running, replace motor assembly.
The bucket is not installed properly.
The bucket should be properly positioned
on the hangers of the drain pan.
6. Water drips
Connection may be loose.
Leak in bucket
Check connection and repair.
Replace bucket.
Water drips when bucket removed for
emptying.
Before removing bucket, the unit should
be turned off.
Bucket overflows.
Check micro switch and float.
7. Compressor cycles on overload
protector. (O.L.P.)
High or low line voltage. (115V ± 10%)
Check line voltage. It must be between
103.5V and 126.5V volts.
If intermittent, provide new supply.
Poor air circulation.
Move dehumidifier for free and
unobstructed air flow.
Heat Exchange clogged with dust or dirt.
Motor
Clean dust or dirt on the Heat Exchange.
If not running, determine the cause.
Replace if required.
Bad P.T.C. assembly (if assembled)
Short circuit or ground in electrical circuit
Unit pressures not equalized
Check P.T.C., Repair.
Check electrical circuit. Repair.
Allow 2 or 3 minutes for pressure to
equalize before starting compressor.
Capacitor
Wiring
Test the capacitor.
Check the terminals. If loose, repair or
replace.
Refrigeration system
Stuck compressor
Check the system for a restriction.
Check compressor, replace compressor
Overload protector (O.L.P.)
Check O.L.P., if externally mounted.
Replace if open. (If the compressor
temperature is high, remove the O.L.P.,
cool, and retest.)
—19—
Download from Www.Somanuals.com. All Manuals Search And Download.
5. EXPLODED VIEW - INTRODUCTION
• MODEL: DH3010B/DHA3012DL
349600
152302
346811
269120 266003 252160
264110
249950
W6640
549990
266140
359012
135312
149410
130900
147910
148380
354211
266011
554030
35211A
667482
567502
554160
352113
552111
550140
130411
—20—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE)
349600
152302
346811
269130 266003 252160
264110
249950
W0CZZ
549990
359012
135312
149410
130900
147910
148380
354211
554030
266011
35211A
567502
554160
550140
552111
352113
130411
—21—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOSTAT CONTROL
349600
152302
346811
269120 266003 252160 269310
264110
249950
W0CZZ
549990
359012
135312
149410
130900
147910
148380
354211
554030
266011
35211A
567502
554160
552111
352113
550140
130411
—22—
Download from Www.Somanuals.com. All Manuals Search And Download.
6. REPLACEMENT PARTS LIST
• MODEL: DH3010B, DHA3012DL
PART NO.
LOCATION
DESCRIPTION
REMARK
NO.
DH3010B/DHA3012DL
130411
130900
135312
147910
148380
149410
152302
249950
W6640
264110
266003
252160
266011
266140
269120
346811
35211A
352113
354211
549990
550140
552111
554030
554160
359012
567502
349600
667482
BASE ASSY, WELD(SINGLE)
CABINET
3041AD2007B
3090A10001J
3531A20012B
4791A10002B
4838A20005A
4941A30002A
5230AD3005A
4995A20085F
6640A40001A
6411A20001Q
6600A20001A
5216A20001A
6600A30003C
6614A30001H
6912A30001F
4681A20040A
5211A30373B
5211A30367A
5421A10009B
4999A10001A
5040AR4195A
5211A10085C
5403A10008B
2521C-A8605
5900A20007A
6750C-0002S
4960A20009A
6748C-0003A
GILLE ASSY, FRONT
BARRIER ASSY
TANK, BUCKET
KNOB ASSY
FILTER(MECH), AIR
CONTROL BOX ASSY
TERMINAL BLOCK
POWER CORD ASSY
SWITCH, ROTARY
HUMIDISTAT
ALT) 6411A20001R
ALT) 5216A20001B
SWITCH ASSY, MICRO
CONTROL DEFROST
LAMP, NEON
MOTOR ASSY, SINGLE
TUBE ASSY, SUCTION SINGLE
TUBE ASSY, DISCHARGE SINGLE
EVAPORATOR ASSY
SHROUD ASSY
ISOLATOR
TUBE ASSY, CAPILLARY
CONDENSER ASSY
COMPRESSOR ASSY, FINAL
FAN, TURBO
O.L.P
MOUNT, MOTOR
P.T.C
—23—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE)
PART NO.
LOCATION
NO.
DESCRIPTION
REMARK
DH4010B/DHA4012DL DH5010B/DHA5012DL
130411
130900
135312
147910
148380
149410
152302
W0CZZ
249950
264110
266003
252160
266011
266140
269120
346811
35211A
352113
354211
549990
550140
552111
554030
554160
359012
567502
349600
BASE ASSY, WELD(SINGLE)
CABINET
3041AD2007C
3090A10001J
3531A20012B
4791A10002A
4838A20005A
4941A30002A
5230AD3005A
0CZZA20001Q
4995A20085E
6411A20001Q
6600A20001A
5216A20001A
6600A30003C
GILLE ASSY, FRONT
BARRIER ASSY
ALT)4791A10002B
TANK, BUCKET
KNOB ASSY
FILTER(MECH), AIR
CAPACITOR
CONTROL BOX ASSY
POWER CORD ASSY
SWITCH, ROTARY
HUMIDISTAT
ALT) 6411A20001R
ALT) 5216A20001B
SWITCH ASSY, MICRO
CONTROL DEFROST
LAMP, NEON
-
6614A30001F
6912A30001F
4681A20040A
MOTOR ASSY, SINGLE
TUBE ASSY, SUCTION SINGLE
TUBE ASSY, DISCHARGE SINGLE
EVAPORATOR ASSY
SHROUD ASSY
5211A10071B
5211A10070C
5421A10009D
5211A10071A
5211A10070A
5421A10009A
4999A10001A
4830A30005A
BUSHING
TUBE ASSY, CAPILLARY
CONDENSER ASSY
COMPRESSOR ASSY, FINAL
FAN, TURBO
5211A10085D
5211A10085A
5403A10008A
5416AR2179J
5403A10008C
2520UABC2FA
5900A20007A
O.L.P
6750U-L039A
4960A20009A
MOUNT, MOTOR
—24—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOSTAT CONTROL TYPE)
PART NO.
LOCATION
NO.
DESCRIPTION
REMARK
DH4010B/DHA4012DL DH5010B/DHA5012DL
130411
130900
135312
147910
148380
149410
152302
W0CZZ
249950
264110
266003
252160
266011
269310
269120
346811
35211A
352113
354211
549990
550140
552111
554030
554160
359012
567502
349600
BASE ASSY, WELD(SINGLE)
CABINET
3041AD2007C
3090A10001J
3531A20012B
4791A10002A
4838A20005A
4941A30002A
5230AD3005A
0CZZA20001Q
GILLE ASSY, FRONT
BARRIER ASSY
ALT)4791A10002B
TANK, BUCKET
KNOB ASSY
FILTER(MECH), AIR
CAPACITOR
CONTROL BOX ASSY
POWER CORD ASSY
SWITCH, ROTARY
HUMIDISTAT
4995A20085J
4995A20085G
6411A20001Q
ALT) 6411A20001R
ALT) 5216A20001B
6600A20001A
5216A20001A
6600A30003C
SWITCH ASSY, MICRO
THERMOSTAT
2H01127K
2H01127J
LAMP, NEON
6912A30001F
4681A20040A
MOTOR ASSY, SINGLE
TUBE ASSY, SUCTION SINGLE
TUBE ASSY, DISCHARGE SINGLE
EVAPORATOR ASSY
SHROUD ASSY
5211A10071B
5211A10071A
5211A10070A
5421A10009A
5211A10070C
5421A10009D
4999A10001A
4830A30005A
BUSHING
TUBE ASSY, CAPILLARY
CONDENSER ASSY
COMPRESSOR ASSY, FINAL
FAN, TURBO
5211A10085D
5211A10085A
5403A10008A
5416AR2179J
5403A10008C
2520UABC2FA
5900A20007A
O.L.P
6750U-L039A
4960A20009A
MOUNT, MOTOR
—25—
Download from Www.Somanuals.com. All Manuals Search And Download.
• MEMO •
—26—
Download from Www.Somanuals.com. All Manuals Search And Download.
March, 2001
P/No : 3828A30039T
Printed in Korea
Download from Www.Somanuals.com. All Manuals Search And Download.
|