Gentek Speaker SPKE4 User Manual

VII. ELECTRICAL SPECIFICATIONS:  
SPKE SERIES  
UL 1971 COMPLIANT  
MODEL NUMBERS  
SPEAKERS dBA @ 10 FEET  
PER UL 1480  
RATED WATTS  
SPKE4 SERIES  
SPKE8 SERIES  
1/8  
78  
78  
1/4  
81  
81  
1/2  
84  
84  
1
87  
87  
2
90  
90  
4
90  
90  
SPEAKER AND SPEAKER/STROBE  
WIRING DIAGRAM  
RATED WATTS  
1/8  
1/4  
1/2  
1
2
4
Installation Instructions-  
Owner's Information  
SPKE4*.................. SQUARE SPEAKER  
SPKE4*.................. SQUARE SPEAKER WITH 24 VDC STROBE  
SPKE8*.................. 8 IN. ROUND SPEAKER  
SPKE8*.................. 8 IN. ROUND SPEAKER WITH 24 VDC STROBE  
* Includes any of the following suffixes, number indicating candela rating, R (Red) or  
W (Off-White), W (Wall) or C (Ceiling).  
INPUT 25v RMS  
INPUT 70.7v RMS  
D
A
E
B
F
C
G
D
H
E
I
F
MODELS  
STROBE CURRENT RATINGS  
DC (mA)  
FWR (mA)  
PEAK  
236  
Cd  
15  
VOLTAGE  
INRUSH  
96  
114  
150  
110  
130  
160  
120  
140  
170  
110  
120  
160  
128  
148  
230  
PEAK  
94  
84  
AVG  
86  
78  
69  
105  
93  
INRUSH  
132  
176  
176  
245  
235  
310  
320  
300  
400  
180  
180  
220  
220  
280  
420  
AVG  
21V  
24V  
30V  
21V  
24V  
30V  
21V  
24V  
30V  
21V  
24V  
30V  
21V  
24V  
30V  
110  
100  
91  
216  
200  
280  
260  
245  
360  
340  
330  
480  
440  
400  
752  
704  
552  
76  
120  
110  
90  
140  
125  
115  
180  
160  
145  
224  
193  
165  
310  
298  
234  
15*& 30 (wall)  
15*(ceiling) & 60 (wall)  
30*(wall) & (ceiling)  
110  
I.  
INTRODUCTION  
77  
The Gentex SPKE Series is a high quality speaker and speaker/visual signal appliance. The  
SPKE Series is UL Listed for fire protective service. The high intensity strobe utilizes a Xenon  
flash tube which generates a high-intensity light visible from all sides. The strobe is UL Listed in  
compliance with UL 1971, Signaling Appliances for the Hearing Impaired (15/75 Cd and 30/75 Cd  
models are additionally listed in compliance with UL 1638).  
150  
120  
100  
180  
160  
140  
270  
240  
200  
130  
115  
95  
165  
142  
114  
240  
220  
179  
II. PRODUCT INFORMATION  
The SPKE Series speaker and speaker/strobe offer a choice of field selectable power taps, 1/8,  
1/4, 1/2, 1, 2 and 4 Watts for either 25v or 70.7v audio amplifiers. The speaker/strobe offers the  
option of a high intensity strobe which complies with UL 1971. The frequency range of the  
speakers is 400-4000Hz. All devices are suitable for line supervision. Speaker includes DC  
blocking capacitor which allows for supervision voltage of either polarity.  
SYNCHRONIZED STROBE RATINGS  
21V  
24V  
30V  
21V  
24V  
30V  
420  
490  
620  
420  
490  
620  
180  
160  
160  
440  
680  
580  
98  
92  
85  
144  
130  
116  
440  
600  
640  
550  
640  
700  
260  
350  
380  
920  
920  
640  
115  
107  
100  
172  
155  
138  
15 (Z suffix)  
15* (Z suffix)  
III. LOCATION  
This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with  
this installation manual, the recommendation of the local authorities having jurisdiction, and other  
NFPA Standards that provide standards on notification appliances for protective signaling  
systems.  
*-RATED 75 Cd PER UL 1638, FIRE PROTECTIVE VISUAL SIGNALING APPLIANCES.  
LIMITED WARRANTY  
GENTEX WILL NOT BE LIABLE FOR ANY LOSS, DAMAGE,  
INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND  
ARISING IN CONNECTION WITH THE SALE, USE OR REPAIR OF  
THIS APPLIANCE. THE MAXIMUM LIABILITY OF GENTEX SHALL  
NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY  
YOU FOR THE APPLIANCE. PLEASE NOTE THAT SOME STATES  
DO NOT ALLOW THE EXCLUSION OR LIMITATION OF  
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE  
EXCLUSION MAY NOT APPLY TO YOU.  
If a defect in workmanship, materials, or construction should  
cause your appliance to become inoperable within the warranty  
period, you must return the appliance to Gentex postage prepaid.  
You must also prove to the satisfaction of Gentex the date of  
purchase of your appliance. Warranty service may only be  
performed by Gentex personnel at Gentex's facilities in Zeeland,  
Michigan. You must also pack the appliance to minimize the risk of it  
being damaged in transit. You must also enclose a return address.  
Appliances returned for warranty service should be sent to: Gentex  
Corporation, 10985 Chicago Drive, Zeeland, MI 49464. If we  
receive an appliance in a damaged condition as the result of  
shipping, we will notify you and you must file a claim with the shipper.  
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND  
YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM  
STATE TO STATE.  
For a period of 24 months from the date of purchase, or a  
maximum of 30 months from the date of manufacture, Gentex  
warrants to you, the original purchaser, that your appliance will be free  
from defects in workmanship, materials, and construction under  
normal use and service. If a defect in workmanship, materials, or  
construction should cause your appliance to become inoperable within  
the warranty period, Gentex will repair your appliance or furnish you  
The Gentex "SPKE" is intended for indoor installation only. This appliance is not weatherproofed  
for outdoor or drip proof applications.  
Wall-mounted appliances shall have their bottoms at heights above the finished floor of not less  
than 80 in. (2m) and no greater than 96 in. (2.4m)**. Spacing shall be in accordance with Table A.  
If a room configuration is not square, the room size that will entirely encompass the room or  
subdivide the room into multiple squares shall be used.  
with  
a
new or rebuilt replacement appliance without charge to you  
except for postage required to return the appliance to us. Gentex will  
not reimburse you for repairs or replacement parts provided by other  
parties. Your repaired or replacement appliance will be returned to you  
free of charge and it will be covered under this warranty for the balance  
of the warranty period.  
This warranty is void if our inspection of your appliance shows that  
the damage or failure was caused by abuse, misuse, abnormal usage,  
faulty installation, improper maintenance, or repairs other than those  
performed by us.  
ANY WARRANTIES IMPLIED UNDER ANY STATE LAW,  
INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR  
FITNESS FOR A PARTICULAR PURPOSE, APPLY ONLY FOR THE  
WARRANTY PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT  
SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN  
IMPLIED WARRANTY LASTS, SO THE ABOVE EXCLUSION MAY  
NOT APPLY TO YOU.  
Maximum Room  
Size  
Minimum Required Light Output, Candela (Cd)  
(Effective Intensity)  
Two Lights per  
Room (Located  
on Opposite  
Four Lights  
per Room  
(One Light  
per Wall) (Cd)  
One Light  
per Room (Cd)  
Walls) (Cd)  
20' x 20'  
30' x 30'  
40' x 40'  
50' x 50'  
60' x 60'  
70' x 70'  
80' x 80'  
90' x 90'  
100' x 100'  
110' x 110'  
120' x 120'  
130' x 130'  
15  
30  
60  
N/A  
15  
30  
60  
95  
N/A  
N/A  
15*  
30*  
30*  
60*  
60  
95  
95  
135  
135  
185  
95  
135  
185  
240  
305  
375  
455  
540  
635  
95  
135  
185  
240  
240  
305  
375  
GENTEX CORPORATION  
TABLE A  
* - Must be used with the AVS44 Control Module due to distance between strobes being less than 55ft.  
10985 CHICAGO DRIVE, ZEELAND, MI 49464  
PHONE: 800-436-8391  
1-1-94  
550-105-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Chainsaw CS 356 User Manual
Electro Voice Microphone 635L User Manual
Electro Voice Speaker System HPT64 User Manual
Extron electronic Stereo System A RCA 10 User Manual
Extron electronic Switch 5cr Plus User Manual
Fujitsu Mouse FKB8729 Series User Manual
GE Clothes Dryer DBVH512EF User Manual
GE Clothes Dryer DCCB330GJ User Manual
GE Cordless Telephone 16179610 User Manual
Global Machinery Company Saw LS1200 User Manual