Generac Portable Generator 004721 0 004722 0 004723 0 004724 0 004725 0 004725 1 004725 2 004725 3 004726 0 User Manual

Owner’s Manual  
Liquid-cooled, Prepackaged  
Standby Generators  
Model Numbers  
004721-0, 004722-0,  
004723-0, 004724-0,  
004725-0, 004725-1,  
004725-2, 004725-3,  
004726-0  
Not intended for use in critical life support applications.  
!
!
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT  
INSTALLATION!!  
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!  
This manual should remain with the unit.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
INTRODUCTION ..................................IFC  
SAFETY RULES ......................................2  
Section 3 OPERATION....................12  
3.1 Using a Standard “GTS” Transfer Switch....12  
3.2 Control Console Components......................12  
3.3 Manual Transfer and Startup......................13  
3.4 Automatic Operation ..................................13  
3.5 Weekly Exercise Cycle..................................13  
3.6 Engine Heater..............................................14  
Section 4 — MAINTENANCE ..............14  
Section 1 — GENERAL  
INFORMATION..................4  
1.1 Generator......................................................4  
1.2 Transfer Switch ............................................4  
1.3 Automatic System Operation ........................4  
1.4 Generator AC Connection Systems................4  
1.5 Main Circuit Breaker ....................................4  
1.6 Generator Fuel System..................................4  
1.7 Engine Protective Devices..............................5  
1.8 Unpacking ....................................................6  
1.9 Lifting the Generator ....................................6  
1.10 Specifications ................................................7  
1.11 Fuel Consumption ........................................7  
1.12 Reconfiguring the Fuel System ......................7  
1.13 Torque Specifications....................................8  
1.14 Engine Oil Recommendations ......................8  
1.15 Coolant Recommendations............................8  
1.16 Before Installation ........................................8  
Section 2 — INSTALLATION ................8  
2.1 Standby Generator Installation ....................8  
2.2 Generator Location ......................................9  
2.3 Generator Mounting and Support ................9  
2.4 Basic Standby Electric System......................9  
2.5 Emergency Circuit Isolation Method ..........10  
2.6 Total Circuit Isolation Method ....................10  
2.7 Grounding the Generator ............................10  
2.8 Generator AC Neutral Connections ............10  
2.9 Transfer Switch Start Signal Connections ..10  
2.10 Battery Installation......................................11  
2.11 Preparation Before Start-Up........................11  
4.1 Maintenance Performed by Authorized  
Service Facilities..........................................14  
4.2 Cooling System............................................15  
4.3 Overload Protection for Engine DC  
Electrical System ........................................15  
4.4 Checking Fluid Levels ................................15  
4.5 Maintenance Owner/Operator  
Can Perform................................................15  
4.6 Miscellaneous Maintenance ........................17  
4.7 Scheduled Maintenance ..............................19  
Section 5 — TROUBLESHOOTING......22  
5.1 Troubleshooting Points................................22  
Section 6 — NOTES............................23  
Section 7 — INSTALLATION  
DIAGRAM ......................25  
Section 8 — ELECTRICAL DATA ........26  
Section 9 — EXPLODED VIEWS AND  
PARTS LISTS ................30  
Section 10 — WARRANTY .................48  
®
Generac Power Systems, Inc.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe  
operation be copied and posted in potential hazard areas. Safety should be stressed to all  
operators, potential operators, and service and repair technicians for this equipment.  
!
!
!
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be  
followed during installation and maintenance of the generator and batteries.  
!
!
!
!
!
GENERAL HAZARDS  
WARNING:  
The engine exhaust from this product  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
For safety reasons, Generac recommends that this  
equipment be installed, serviced and repaired by a  
Generac Authorized Service Dealer or other compe-  
tent, qualified electrician or installation technician  
who is familiar with applicable codes, standards and  
regulations. The operator also must comply with all  
such codes, standards and regulations.  
• Installation, operation, servicing and repair of this  
(and related) equipment must always comply with  
applicable codes, standards, laws and regulations.  
Adhere strictly to local, state and national electrical  
and building codes. Comply with regulations the  
Occupational Safety and Health Administration  
(OSHA) has established. Also, ensure that the gener-  
ator is installed, operated and serviced in accordance  
with the manufacturer’s instructions and recommen-  
dations. Following installation, do nothing that might  
render the unit unsafe or in noncompliance with the  
aforementioned codes, standards, laws and regula-  
tions.  
• The engine exhaust fumes contain carbon monoxide  
gas, which can be DEADLY. This dangerous gas, if  
breathed in sufficient concentrations, can cause  
unconsciousness or even death. For that reason, ade-  
quate ventilation must be provided. Exhaust gases  
must be piped safely away from any building or  
enclosure that houses the generator to an area where  
people, animals, etc., will not be harmed. This  
exhaust system must be installed properly, in strict  
compliance with applicable codes and standards.  
• Keep hands, feet, clothing, etc., away from drive belts,  
fans, and other moving or hot parts. Never remove  
any drive belt or fan guard while the unit is operating.  
• Adequate, unobstructed flow of cooling and ventilat-  
ing air is critical to prevent buildup of explosive gases  
and to ensure correct generator operation. Do not  
alter the installation or permit even partial blockage  
of ventilation provisions, as this can seriously affect  
safe operation of the generator.  
!
!
WARNING:  
This product contains or emits chemicals  
known to the state of California to cause  
cancer, birth defects or other reproductive harm.  
Study these SAFETY RULES carefully before installing,  
operating or servicing this equipment. Become familiar  
with this Owner’s Manual and with the unit. The genera-  
tor can operate safely, efficiently and reliably only if it is  
properly installed, operated and maintained. Many acci-  
dents are caused by failing to follow simple and funda-  
mental rules or precautions.  
Generac cannot possibly anticipate every possible  
cirumstance that might involve a hazard. The warn-  
ings in this manual, and on tags and decals affixed to  
the unit are, therefore, not all-inclusive. If using a pro-  
cedure, work method or operating technique that  
Generac does not specifically recommend, satisfy your-  
self that it is safe for others. Also make sure the proce-  
dure, work method or operating technique chosen does  
not render the generator unsafe.  
DANGER  
Despite the safe design of this generator,  
!
operating this equipment imprudently, neglecting  
its maintenance or being careless can cause  
possible injury or death. Permit only responsible  
and capable persons to install, operate or main-  
tain this equipment.  
Potentially lethal voltages are generated by these  
machines. Ensure all steps are taken to render the  
machine safe before attempting to work on the  
generator.  
• Keep the area around the generator clean and unclut-  
tered. Remove any materials that could become haz-  
ardous.  
• When working on this equipment, remain alert at all  
times. Never work on the equipment when physically  
or mentally fatigued.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running gen-  
!
erators.  
®
2
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
• Inspect the generator regularly, and promptly repair • Generators installed with an automatic transfer  
or replace all worn, damaged or defective parts using  
switch will crank and start automatically when nor-  
mal (utility) source voltage is removed or is below an  
acceptable preset level. To prevent such automatic  
start-up and possible injury to personnel, disable the  
generator’s automatic start circuit (battery cables,  
etc.) before working on or around the unit. Then,  
place a “Do Not Operate” tag on the generator control  
panel and on the transfer switch.  
only factory-approved parts.  
• Before performing any maintenance on the generator,  
disconnect its battery cables to prevent accidental  
start-up. Disconnect the cable from the battery post  
indicated by a NEGATIVE, NEG or (–) first.  
Reconnect that cable last.  
• Never use the generator or any of its parts as a step.  
Stepping on the unit can stress and break parts, and  
may result in dangerous operating conditions from  
leaking exhaust gases, fuel leakage, oil leakage, etc.  
• In case of accident caused by electric shock, immedi-  
ately shut down the source of electrical power. If this  
is not possible, attempt to free the victim from the  
live conductor. AVOID DIRECT CONTACT WITH  
THE VICTIM. Use a nonconducting implement, such  
as a dry rope or board, to free the victim from the live  
conductor. If the victim is unconscious, apply first aid  
and get immediate medical help.  
• Never wear jewelry when working on this equipment.  
Jewelry can conduct electricity resulting in electric  
shock, or may get caught in moving components  
causing injury.  
ELECTRICAL HAZARDS  
• All generators covered by this manual produce dan-  
gerous electrical voltages and can cause fatal electrical  
shock. Utility power delivers extremely high and dan-  
gerous voltages to the transfer switch as well as the  
standby generator. Avoid contact with bare wires, ter-  
minals, connections, etc., on the generator as well as  
the transfer switch, if applicable. Ensure all appropri-  
ate covers, guards and barriers are in place before  
operating the generator. If work must be done around  
an operating unit, stand on an insulated, dry surface  
to reduce shock hazard.  
• Do not handle any kind of electrical device while  
standing in water, while barefoot, or while hands or  
feet are wet. DANGEROUS ELECTRICAL SHOCK  
MAY RESULT.  
• If people must stand on metal or concrete while  
installing, operating, servicing, adjusting or repairing  
this equipment, place insulative mats over a dry  
wooden platform. Work on the equipment only while  
standing on such insulative mats.  
FIRE HAZARDS  
• Keep a fire extinguisher near the generator at all  
times. Do NOT use any carbon tetra-chloride type  
extinguisher. Its fumes are toxic, and the liquid can  
deteriorate wiring insulation. Keep the extinguisher  
properly charged and be familiar with its use.  
Consult the local fire department for any questions  
pertaining to fire extinguishers.  
EXPLOSION HAZARDS  
• The National Electrical Code (NEC), Article 250  
requires the frame and external electrically conduc-  
tive parts of the generator to be connected to an  
approved earth ground and/or grounding rods. This  
grounding will help prevent dangerous electrical  
shock that might be caused by a ground fault condi-  
tion in the generator set or by static electricity. Never  
disconnect the ground wire.  
• Wire gauge sizes of electrical wiring, cables and cord  
sets must be adequate to handle the maximum elec-  
trical current (ampacity) to which they will be sub-  
jected.  
• Before installing or servicing this (and related) equip-  
ment, make sure that all power voltage supplies are  
positively turned off at their source. Failure to do so  
will result in hazardous and possibly fatal electrical  
shock.  
• Connecting this unit to an electrical system normally  
supplied by an electric utility shall be by means of a  
transfer switch so as to isolate the generator electric  
system from the electric utility distribution system  
when the generator is operating. Failure to isolate the  
two electric system power sources from each other by  
such means will result in damage to the generator  
and may also result in injury or death to utility power  
workers due to backfeed of electrical energy.  
• Properly ventilate any room or building housing the  
generator to prevent build-up of explosive gas.  
• Do not smoke around the generator. Wipe up any fuel  
or oil spills immediately. Ensure that no combustible  
materials are left in the generator compartment, or  
on or near the generator, as FIRE or EXPLOSION  
may result. Keep the area surrounding the generator  
clean and free from debris.  
• Generac generator sets may operate using one of sev-  
eral types of fuels. All fuel types are potentially FLAM-  
MABLE and/or EXPLOSIVE and should be handled  
with care. Comply with all laws regulating the storage  
and handling of fuels. Inspect the unit’s fuel system  
frequently and correct any leaks immediately. Fuel  
supply lines must be properly installed, purged and  
leak tested according to applicable fuel-gas codes  
before placing this equipment into service.  
• Diesel fuels are highly FLAMMABLE. Gaseous fluids  
such as natural gas and liquid propane (LP) gas are  
extremely EXPLOSIVE. Natural gas is lighter than air,  
and LP gas is heavier than air. Install leak detectors  
accordingly.  
®
Generac Power Systems, Inc.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 - General Information  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
1.1 GENERATOR  
1.3 AUTOMATIC SYSTEM OPERATION  
When this generator, along with its transfer switch, has  
been installed and interconnected, a circuit board in  
the generator panel constantly monitors utility power  
source voltage. Should that voltage drop below a pre-  
set value, and remain at such a low state for a preset  
amount of time, the generator cranks and starts. After  
the generator starts, the transfer switch transfers load  
circuits so the generator can power them.  
This equipment is a liquid-cooled, engine-driven gen-  
erator set. The generator is designed to supply elec-  
trical power that operates critical electrical loads  
during utility power failure. The unit has been facto-  
ry-installed in a weather resistant, all metal enclosure  
and is intended for outdoor installation only. Use this  
generator as a source of electrical power for the oper-  
ation of 120 and/or 240 volts, single phase loads.  
These models are available. They are rated as follows:  
When utility source voltage has been restored, the  
switch re-transfers back to the utility source voltage  
and the generator then shuts down.  
Models 0047210 and 0047220: Provides 15,000  
watts (15 kW) of single phase power.  
Please reference the transfer switch manual for spe-  
cific information.  
Models 0047230 and 0047240: Provides 20,000  
watts (20 kW) of single phase power.  
Models 0047250, 0047251, 0047252, 0047253,  
and 0047260: Provides 25,000 watts (25 kW) of sin-  
gle phase power.  
1.4 GENERATOR AC CONNECTION  
SYSTEMS  
The generator was shipped from the factory with its  
stator AC output leads connected in a single-phase,  
three-wire generator AC connection system (Figure  
1.1). The stator assembly in this system consists of a  
pair of stationary windings, with two leads brought  
out of each winding. Each single winding can supply  
120 volts AC, 60 Hertz. When the two windings are  
connected in series, a 240 volts, 60 Hertz AC output  
results. Typically the two “hot” leads in the circuit are  
Wires No. 11 and 44. The “Neutral” leads are the  
junction of Wires 22 and 33.  
If this generator is used to power electrical  
load circuits normally powered by a utility  
power source, it is required by code to install  
!
a transfer switch. The transfer switch must  
effectively isolate the electric system from the  
utility distribution system when the generator  
is operating (NEC 701). Failure to isolate an  
electrical system by such means results in  
damage to the generator and may also result  
in injury or even death to utility power work-  
ers due to backfeed of electrical energy.  
Figure 1.1 - Generator AC Connection System  
1.2 TRANSFER SWITCH  
This generator system may include a matched auto-  
matic transfer switch which is intended to be used in  
conjunction with the Guardian generator. It is sup-  
plied in either a NEMA 1 enclosure (15 kW model  
004721, 20 kW models 004723) or a NEMA 3R  
enclosure (25 kW models 004725). The NEMA 1  
enclosure is intended for indoor use only. The NEMA  
3R enclosure is weather proof and can be used  
indoors or outdoors. Follow these rules:  
• Install the transfer switch on a firm, sturdy sup-  
porting structure.  
To prevent switch distortion, level the switch if nec-  
essary. This can be done by placing washers  
between the switch enclosure and the mounting  
surface.  
• Never install the switch where water or any corro-  
sive substance might drip onto the enclosure.  
• Protect the switch at all times against excessive  
moisture, dust, dirt, lint, construction grit and cor-  
rosive vapors.  
1.5 MAIN CIRCUIT BREAKER  
The generator’s main circuit breaker is included with  
the unit as shipped from the factory. The breaker for  
each unit is described in Figure 1.2 at the top of page  
5.  
1.6 GENERATOR FUEL SYSTEM  
The generator has been factory tested and adjusted  
using a natural gas fuel system. If propane (LP  
requirements) gas is preferred, contact an authorized  
service dealer. Refer to Secion 1.12.  
• Failure to utilize a Generac/Guardian transfer  
switch with this generator will void the warranty.  
®
4
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 - General Information  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Figure 1.2 - Main Circuit Breaker  
Model  
Rating  
15,000  
20,000  
25,000  
Phase  
Actual Current  
C/B Rating*  
% over rating  
112%  
Circuit Breaker  
70A BQ2  
004721/004722  
004723/004724  
004725/004726  
1
1
1
62.5  
83.3  
104.2  
70  
90  
125  
108%  
120%  
90A BQ2  
125A BQ2  
* Amp Rating of CB structured under model.  
Recommended fuels should have a Btu content of at  
least 1,000 Btus per cubic foot for natural gas and at  
least 2,520 Btus per cubic foot for LP gas. Ask the  
fuel supplier for the Btu content of the fuel being  
used.  
1.7.1 LOW OIL PRESSURE SWITCH  
This switch is normally-closed (N.C.), but is held  
open by engine oil pressure during engine running.  
Should operating oil pressure drop below about 8-10  
psi (55-68 kPa), the switch contacts close and the  
engine shuts down automatically (Figure 1.4).  
Fuel pressure for both natural gas and liquid  
propane set ups should be 11 inches to 14 inches  
of water column (0.6 psi) at all load ranges.  
Figure 1.4 - Low Oil Pressure Switch  
NOTE:  
A seperate gas line and regulator may be needed  
to assure proper gas pressure (11-14”) to the gen-  
erator. Low gas pressure can cause hard starting  
and could affect engine durability.  
Gaseous fuels such as natural and LP  
(propane) gas are highly explosive. Even the  
slightest spark can ignite such fuels and cause  
!
an explosion. No leakage of fuel is permitted.  
Natural gas, which is lighter than air, tends to  
collect in high areas. LP gas is heavier than air  
and tends to settle in low areas.  
1.7.2 HIGH COOLANT TEMPERATURE SWITCH  
This normally open (N.O.), thermostatic switch has  
sensing tip which is immersed in captive coolant.  
Should coolant temperature exceed about 230°F  
(110°C), the switch contacts close, which causes the  
engine to shut down automatically (Figure 1.5).  
1.7 ENGINE PROTECTIVE DEVICES  
The engine has several safety switches which cause  
the engine to automatically shut down under the fol-  
lowing conditions: low oil pressure, high coolant tem-  
perature, engine overspeed, low coolant level or over-  
crank (Figure 1.3).  
Figure 1.5- High Coolant Temperature Switch  
Figure 1.3 - Engine Protective Devices  
1.7.3 LOW COOLANT LEVEL SWITCH  
Should engine coolant level drop below the level of  
the high coolant temperature switch, it is possible for  
the engine to overheat without automatic shutdown.  
To prevent such overheating without automatic shut  
down, the engine has a low coolant level sensor. If the  
engine coolant drops too low, the engine automatical-  
ly shuts down (Figure 1.6 on page 6).  
®
Generac Power Systems, Inc.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
• LED 2 is YELLOW. This LED is on when the circuit  
Figure 1.6 - Low Coolant Level Sensor  
board battery charger is on. This LED will cycle on  
and off with the battery charger, 4.85 hours on the  
4.85 hours off.  
• LED 3 is GREEN. This LED will flash when the cir-  
cuit board has load voltage available to it. This  
LED will function when voltage is available across  
T1 and T2.  
1.7.6 OVERCRANK SHUTDOWN  
After 90 seconds of crank-rest cycles, this function  
ends cranking if the engine fails to start in that  
90-second span.  
1.7.6 DC FUSE  
1.7.4 OVERSPEED SHUTDOWN  
This clearly labeled fuse is located on the front panel  
of the control system. It protects the panel wiring and  
components from damaging overload. Always  
remove this fuse before commencing work on the  
generator. The unit will not start or crank if the fuse  
is blown. Replace the fuse with one of the same size,  
type, and rating. Generac normally uses an AGC fuse  
rated at 15 amps (part number 022676).  
The Pre-pack circuit board on liquid cooled units  
receives AC frequency (rpm) signals directly from the  
stator AC power windings, via sensing leads S15 and  
S16. Should AC frequency exceed about 72 Hz, cir-  
cuit board action will automatically shutdown the  
engine (Figure 1.7).  
*Rated power of generator is subject to and limit-  
ed by such factors as ambient temperature, alti-  
tude, engine condition, and other factors. Engine  
power will decrease about 3.5% for each 1000 feet  
above sea level and will decrease an additional 1%  
for each 10°F above 60°F. Maximum output power  
of the generator is limited by maximum engine  
power.  
1.8 UNPACKING  
1.8.1 UNPACKING PRECAUTIONS  
Handle shipping cartons and crates with care. Use  
care to avoid damage from dropping, bumping, colli-  
sion, etc. Store and unpack cartons with the proper  
side up, as noted on the shipping carton.  
Figure 1.7 - Control Module Assembly  
Circuit Board  
1.8.2 INSPECTION  
PRE-PACKAGED STANDBY  
After unpacking, carefully inspect the generator for  
any damage that may have occurred during ship-  
ment. If loss or damage is noted at the time of deliv-  
ery, have the person(s) making delivery note all dam-  
age on the freight bill or affix their signature under  
the consignor’s memo of loss or damage.  
J2  
U13  
U14  
U17  
U15  
E
M14  
A
M15  
C17  
C18  
C12  
M3  
M8  
M1  
Q7  
C1  
R1  
U1  
Q14  
M10  
R68 R60  
C24  
C21  
C25  
C22  
U5  
U4  
LED3  
U16  
SW1  
BR1  
U12  
C3  
R56  
CR1  
Q9  
C2  
C5  
C
U2  
R12  
C4  
Q1  
U6  
U18  
U3  
R11 R10 CR7  
U19  
U7  
CR37  
K4  
Q4  
K2  
K3  
C19  
U9  
Q5  
Q3  
Q12  
Q11  
U10  
1.9 LIFTING THE GENERATOR  
U8  
C23  
Q2  
C20  
C8  
C15  
Q15  
C10  
C9  
C11  
LED2  
U20  
Q16  
C14  
C16  
C7  
K1  
LED1  
M9  
Q6  
When lifting or hoisting equipment is used,  
be careful not to touch overhead power lines.  
The generators weight of more than 900  
Q13  
M4  
M2  
C13  
R55  
CUT R83  
FOR 50HZ  
CR41  
2002 GENERAC POWER SYSTEMS, ASSY #076009A  
!
pounds requires proper tools, equipment, and  
qualified personnel to be used in all phases of  
handling and unpacking.  
1.7.5 PCB OPERATION LED’S  
• LED 1 is RED. The LED is on when utility sensing  
is NOT available to the circuit board. This LED will  
function only when the Auto/Off/Manual switch is  
set in the Auto position.  
®
6
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
NOTE:  
1.10 SPECIFICATIONS  
Fuel consumption is given at rated maximum con-  
tinuous power output when using natural gas  
rated at 1000 Btu per cubic foot and LP gas rated  
2520 Btu per cubic foot. Actual fuel consumption  
obtained may vary depending on such variables as  
applied load, ambient temperature, engine condi-  
tions and other environmental factors.  
1.10.1 GENERATOR SPECIFICATIONS  
Single-Phase  
Model  
004725 004723 004721  
004726 004724 004722  
Rated Max. Cont.  
25  
20  
15  
Fuel pressure for both natural gas and liquid  
propane set ups should be 11 inches to 14 inches  
of water column (0.6 psi) at all load ranges.  
AC Power Output (kW)  
Rated voltage (volts)  
No. of Rotor Poles  
120/240  
2
4
Driven Speed of Rotor  
Rotor Excitation System  
Type of Stator  
3600  
3600  
1800  
NOTE:  
Direct excited brush type  
A seperate gas line and regulator may be needed  
to assure proper gas pressure (11-14”) to the gen-  
erator. Low gas pressure can cause hard starting  
and could affect engine durability.  
4 Wire  
Class F  
Rotor/Stator Insulation  
1.10.2 ENGINE SPECIFICATIONS  
1.12 RECONFIGURING THE FUEL  
Make..............................................................................Mitsubishi  
Displacement ..............................................92 inches3 (1.5 liters)  
Cylinder Arrangement......................................................4, in-line  
Valve Arrangement................................................Overhead Cam  
Firing Order........................................................................1-3-4-2  
Number of Main Bearings............................................................5  
Compression Ratio ..............................................................9 to 1  
No. of Teeth on Flywheel ........................................................104  
Ignition Timing  
at 1800 rpm ..................................................35 degrees BTDC  
at 3600 rpm ..................................................43 degrees BTDC  
Spark Plug Gap ..................................................0.020-0.025 inch  
Recommended Spark Plugs  
Champion ....................................................................RN11YC4  
Oil Pressure....................................................................30-50 psi  
Crankcase Oil Capacity........................3.0 U.S. quarts (2.8 liters)  
Recommended Engine Oil........................................SAE 15W-40  
Type of Cooling System ..................Pressurized, closed recovery  
Cooling Fan ..............................................................Pusher Type  
Cooling System Capacity ......................2 U.S. gallons (7.6 liters)  
SYSTEM  
NOTE:  
All models are configured for natural gas from the  
factory.  
To reconfigure the fuel system from NG to LP, follow  
these steps:  
1. Turn the main gas supply off.  
2. Remove the carburetor fuel hose from the outlet  
port (Port 1) of the demand regulator (Figure  
1.8).  
3. Remove the brass hose fitting from the outlet port  
(Port 1) of the demand regulator.  
4. Remove pipe plug from Port 2.  
5. Install brass hose fitting into Port 2.  
6. Install pipe plug into Port 1.  
7. Connect carburetor gas hose to brass fitting.  
8. Tighten all clamps and plugs.  
9. Make sure fuel supply is of the proper pressure  
and type for configuration.  
10. Reverse the procedure to convert back to natural  
gas.  
Recommended Coolant............................Use a 50-50 mixture of  
ethylene glycol base.  
Figure 1.8 — Reconfigure the Fuel System  
Port 1  
Port 2  
1.11 FUEL CONSUMPTION  
25 kW Models  
Using Natural Gas ........................................441 cu. ft. per hour  
Using LP Gas..............................175 cubic ft.(4.8 gal.) per hour  
20 kW Models  
FUEL HOSE  
FUEL HOSE  
BRASS HOSE  
FITTING  
BRASS HOSE  
FITTING  
PLUG  
PLUG  
OUT  
PORT 1  
OUT  
PORT 2  
HOUSING  
PORTS  
HOUSING  
PORTS  
Using Natural Gas ........................................359 cu. ft. per hour  
Using LP Gas ............................143 cubic ft. (4.0 gal.) per hour  
15 kW Models  
Using Natural Gas ........................................277 cu. ft. per hour  
Using LP Gas..............................110 cubic ft.(3.1 gal.) per hour  
NG FUEL SYSTEM  
LP FUEL SYSTEM  
®
Generac Power Systems, Inc.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
NOTE:  
1.16 BEFORE INSTALLATION  
Before installing this equipment, check the ratings of  
both the generator and the transfer switch. Read  
“Emergency Isolation Method” and “Total Circuit  
Isolation Method” in the installation manual (Part No.  
079699).  
Port 1 is for NG only and Port 2 is for LP vapor  
only. No provision for simultaneous fuels has been  
made.  
DANGER  
The generator’s rated wattage/amperage capacity  
must be adequate to handle all electrical loads that  
the unit will power. The critical (essential) loads may  
need to be grouped together and wired into a sepa-  
rate “emergency” distribution panel.  
Serious injury or damage may occur if not con-  
figured properly. Please consult an authorized  
Generac Service Dealer with any questions.  
!
1.13 TORQUE SPECIFICATIONS  
This generator can be installed in conjunction with a  
standard Generac “GTS” type transfer switch, if  
desired.  
Cylinder Head ............................................15 (+ 90° + 90°) ft.lb.  
Intake Manifold ................................................................13 ft.lb.  
Exhaust Manifold..............................................................13 ft.lb.  
The standard transfer switch has no sensing or con-  
trolling circuit boards. Instead, the generator control  
console houses a “Printed Circuit Board Assembly”,  
which controls all phases of operation, including  
engine start up and load transfer.  
1.14 ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 15W-40 engine oil at the  
factory. Use a high-quality detergent oil classified “For  
Service CC, SD, SE, SF.” Detergent oils keep the engine  
cleaner and reduce carbon deposits. Use oil having the  
following SAE viscosity rating, based on the ambient  
temperature range anticipated before the next oil  
change:  
2.1 STANDBY GENERATOR  
INSTALLATION  
DANGER  
Temperature  
Above 80° F (27° C)  
32° to 80° F (-1° to 27° C)  
Below 32° F (0° C)  
Oil Grade (Recommended)  
SAE 30W or 15W-40  
Connecting this generator to an electrical sys-  
tem normally supplied by an electric utility  
shall be by means of a transfer switch, so as  
to isolate the electric system from the utility  
distribution system when the generator is  
operating. Failure to isolate the electric sys-  
tem by these means will result in damage to  
the generator and may also result in injury or  
death to utility workers due to backfeed of  
electrical energy.  
SAE 20W-20 or 15W-40  
SAE 10W or 15W-40  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
!
1.15 COOLANT RECOMMENDATIONS  
Use a mixture of half low silicate ethylene glycol base  
anti-freeze and deionized water. Cooling system  
capacity is about 8 U.S. quarts (7.6 liters). Use only  
deionized water and only low silicate anti-freeze. If  
desired, add a high quality rust inhibitor to the rec-  
ommended coolant mixture. When adding coolant,  
always add the recommended 50-50 mixture.  
If an open bottom is used, the engine-genera-  
tor is to be installed over non-combustible  
materials and should be located such that com-  
bustible materials are not capable of accumu-  
lating under the generator set.  
Only qualified, competent installation contractors or  
electricians thoroughly familiar with applicable  
codes, standards and regulations should install this  
standby electric power system. The installation must  
comply strictly with all codes, standards and regula-  
tions pertaining to the installation.  
Do not use any chromate base rust inhibitor  
with ethylene glycol base anti-freeze or chromi-  
This genset must be installed on a level surface. The  
base frame must be level within 1/2 inch all around.  
!
umhydroxide (“green slime”) forms and will  
cause overheating. Engines that have been  
operated with a chromate base rust inhibitor  
must be chemically cleaned before adding eth-  
ylene glycol base anti-freeze. Using any high  
silicate anti-freeze boosters or additives will  
also cause overheating. Generac Power Systems  
also recommends that any soluble oil inhibitor  
is NOT used for this equipment.  
After the system has been installed, do nothing  
that might render the installation in noncompli-  
ance with such codes, standards and regula-  
tions.  
!
®
8
Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
NOTE:  
• Install the generator on high ground where water  
levels will not rise and endanger it.  
For more information about the installation of a  
standby system, order Engine-Generator Standby  
Electric Power Systems Installer’s Guide and  
Reference Manual (part #046622) from a Generac  
Authorized Service Dealer.  
• Allow sufficient room on all sides of the generator  
for maintenance and servicing. A good rule is to  
allow five feet of space on all sides.  
• Where strong prevailing winds blow from one  
direction, face the generator air inlet openings into  
the prevailing winds.  
• Install the generator as close as possible to the  
transfer switch. This reduces the length of wiring  
and conduit.  
• Install the generator as close as possible to the fuel  
supply, to reduce the length of piping. HOWEVER,  
REMEMBER THAT LAWS OR CODES MAY REG-  
ULATE THE DISTANCE.  
2.1.1 NFPA STANDARDS  
The following published standards booklets pertain-  
ing to standby electric systems are available form the  
National Fire Protection Association (NFPA),  
Batterymarch Park, Quincy, MA 02269:  
• NFPA No. 37, STATIONARY COMBUSTION  
ENGINES AND GAS TURBINES.  
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-  
TEMS FOR HEALTH CARE FACILITIES.  
• NFPA No. 220, STANDARD TYPES OF BUILDING  
CONSTRUCTION  
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING  
• NFPA No. 70, NATIONAL ELECTRICAL CODE.  
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE  
LIQUIDS CODE.  
2.3 GENERATOR MOUNTING AND  
SUPPORT  
Retain the generator compartment to a concrete slab  
with 1/4-inch masonry type anchor bolts. Be sure the  
bolts are long enough to retain the compartment. The  
slab should be at least six inches thick and should  
extend beyond the enclosure to a distance of at least  
three inches on all sides. See Section 7, Installation  
Diagram.  
• NFPA No. 10, INSTALLATION, MAINTENANCE AND  
USE OF PORTABLE FIRE EXTINGUISHERS.  
2.1.2 OTHER PUBLISHED STANDARDS  
In addition to NFPA standards, the following infor-  
mation pertaining to the installation and use of  
standby electric systems is available:  
2.4 BASIC STANDBY ELECTRIC  
SYSTEM  
Figure 2.1 shows a schematic diagram of a basic  
standby electric system. Both the UTILITY power  
supply and the STANDBY (generator) output are con-  
nected to an approved transfer switch. The transfer  
switch is required by electrical code and serves the  
following functions:  
• Article X, NATIONAL BUILDING CODE, available  
from the American Insurance Association, 85 John  
Street, New York, N.Y. 10038.  
• AGRICULTURAL WIRING HANDBOOK, obtainable  
from the Food and Energy Council, 909 University  
Avenue, Columbia, MO, 65201.  
• ASAE EP-364.2, INSTALLATION AND MAINTE-  
NANCE OF FARM STANDBY ELECTRIC POWER,  
available from the American Society of Agricultural  
Engineers, 2950 Niles Road, St. Joseph, MI 49085.  
• A52.1, AMERICAN NATIONAL STANDARD FOR  
CHIMNEYS, FIREPLACES AND VENTING SYS-  
TEMS, available from the American National  
Standard Institute, 1430 Broadway, New York, N.Y.  
10018.  
• Permits the LOAD circuits to be connected to only  
one power supply at a time.  
• Prevents electrical backfeed between the generator  
and the UTILITY power circuits.  
Notice that both the STANDBY and the UTILITY  
power supplies to the transfer switch are protected  
against overload by a main line circuit breaker.  
Figure 2.1 – Basic Standby Electric System  
2.2 GENERATOR LOCATION  
Install the generator set, in its protective enclosure  
outdoors, where adequate cooling and ventilating air  
always is available. Consider these factors:  
• Install the unit where air inlet and outlet openings  
will not become obstructed by leaves, grass, snow,  
etc. If prevailing winds will cause blowing or drift-  
ing, consider using a windbreak to protect the unit.  
®
Generac Power Systems, Inc.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
NOTE:  
DANGER  
Generac recommends the use of a Generac Power  
Systems “GTS” type transfer switch in conjunc-  
tion with this generator.  
Do not connect the ground wire to any pipe  
that carries a flammable or explosive substance  
– FIRE or an EXPLOSION may result.  
Proper grounding helps protect personnel against  
electrical shock in the event of a ground fault condi-  
tion in the generator or in connected electrical  
devices. In addition, grounding helps dissipate static  
electricity that often builds up in ungrounded  
devices.  
2.5 EMERGENCY CIRCUIT ISOLATION  
METHOD  
This prevents overloading the generator by keeping  
electrical loads below the wattage/amperage capacity  
of the generator. If the generator is powering only crit-  
ical loads, within the wattage/amperage capacity, dur-  
ing utility power outages, consider using the emer-  
gency circuit isolation method.  
Figure 2.2 – Generator Grounding Lug (typical)  
Critical electrical loads are grouped together and  
wired into a separate “Emergency Distribution  
Panel.” Load circuits powered by that panel are with-  
in the wattage/amperage capacity of the generator set.  
When this method is used, it is difficult to overload  
the generator. The transfer switch must meet the fol-  
lowing requirements:  
• It must have an ampere rating equal to, or greater  
than, the total amperage rating of the emergency  
distribution panel circuit.  
• Have it installed between the building’s main dis-  
tribution panel and the emergency distribution  
panel.  
2.6 TOTAL CIRCUIT ISOLATION  
METHOD  
2.8 GENERATOR AC NEUTRAL  
When a generator capable of powering all electrical  
loads in the circuit is to be installed, use the “Total  
Circuit Isolation Method.” It is possible for the gener-  
ator to be overloaded when this isolation method is  
employed. The following apply to the transfer switch  
in this type of system.  
CONNECTIONS  
Generac Power Systems uses an UNGROUNDED AC  
neutral. Grounding is recommended only at the main  
service entrance. If the neutral wire is grounded and  
one of the phase loads becomes grounded, the exces-  
sive current opens the load circuit breaker or col-  
lapses the generator field. The actual result depends  
on the electrical characteristics of the particular  
installed generator.  
• Ampere rating of the transfer switch must be equal  
to, or greater than, the ampere rating of the normal  
incoming utility service.  
• The transfer switch is installed between the utility  
service entrance and the building distribution  
panel.  
2.9 TRANSFER SWITCH START SIGNAL  
CONNECTIONS  
2.7 GROUNDING THE GENERATOR  
The National Electrical Code requires the frame and  
external electrically conductive parts of this equip-  
ment to be properly connected to an approved earth  
ground and/or grounding rods. For that purpose, a  
GROUND LUG (Figure 2.2) is provided on the gener-  
ator mounting base. Consult a qualified electrician  
for grounding requirements in the area. Grounding  
procedures must meet local regulations.  
If the generator is to be installed with an automatic  
transfer switch, such as a Generac GTS-type switch,  
it is necessary to connect the two-wire start  
control system.  
Connect the two-wire start signal from the automatic  
transfer switch to the automatic start connection,  
which is located in the right hand corner inside the  
control panel. Match wires 178 and 183 in the trans-  
fer switch to 178 and 183 on the terminal strip in the  
control panel. The conductors for the two-wire start  
circuit must be in their own conduit.  
®
10 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
• Spilled electrolyte is to be washed down with an  
2.10 BATTERY INSTALLATION  
DANGER  
acid-neutralizing agent. A common practice is to  
use a solution of one pound (500 grams) bicarbon-  
ate of soda to one gallon (4 liters) of water. The  
bicarbonate of soda solution is to be added until  
the evidence of reaction (foaming) has ceased. The  
resulting liquid is to be flushed with water and the  
area dried.  
Standby generators installed with automatic  
transfer switches will crank and start automati-  
!
cally when NORMAL (UTILITY) source voltage is  
removed or is below an acceptable preset level.  
To prevent such automatic start-up and possible  
injury to personnel, do not connect battery  
cables until the NORMAL source voltage at the  
transfer switch is correct and the system is  
ready to be put into operation.  
Lead acid batteries present a risk of fire  
because they generate hydrogen gas. The fol-  
lowing procedure are to be followed:  
• DO NOT SMOKE when near batteries,  
• DO NOT cause flame or spark in battery area, and  
• Discharge static electricity from body before touch-  
ing batteries by first touching a grounded metal  
surface.  
Servicing of batteries is to be performed or super-  
vised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized person-  
nel away from batteries.  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after  
charging. The slightest spark can ignite the gas  
and cause an explosion. Such an explosion can  
shatter the battery and cause blindness or  
other injury. Any area that houses a storage  
battery must be properly ventilated. Do not  
allow smoking, open flame, sparks or any spark  
producing tools or equipment near the battery.  
For recommended batteries, see “Specifications.” All  
batteries must be at 100 percent state-of-charge  
before they are installed on the generator.  
When using maintenance-free batteries, it is not nec-  
essary to check the specific gravity or electrolyte level.  
Have these procedures performed at the intervals  
specified in Section 4, “Maintenance.” A negative  
ground system is used. Battery connections are  
shown on the wiring diagrams. Make sure all batter-  
ies are correctly connected and terminals are tight.  
Observe battery polarity when connecting batteries  
to the generator set.  
Battery electrolyte fluid is an extremely caustic  
sulfuric acid solution that can cause severe  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If the fluid is spilled, flush  
the affected area immediately with clear water.  
!
NOTE:  
Damage will result if the battery connections are  
made in reverse.  
Do not dispose of the battery in a fire. The bat-  
tery is capable of exploding.  
Do not open or mutilate the battery. Released  
!
2.11 PREPARATION BEFORE START-UP  
The instructions in this section assume that the stand-  
by generator has been properly installed, serviced,  
tested, adjusted and otherwise prepared for use by a  
competent, qualified installation contractor. Be sure to  
read the “Safety Rules” on Pages 2 and 3, as well as all  
other safety information in this manual, before  
attempting to operate this (and related) equipment.  
electrolyte can be toxic and harmful to the skin  
and eyes.  
The battery represents a risk of high short cir-  
cuit current. When working on the battery,  
always remove watches, rings or other metal  
objects, and only use tools that have insulated  
handles.  
2.10.1 VENTED BATTERIES  
2.11.1 PRIOR TO INITIAL START-UP  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically  
conductive and corrosive. The following proce-  
dures are to be observed:  
Prior to initially starting the generator, it must  
be properly prepared for use. Any attempt to  
crank or start the engine before it has been  
properly serviced with the recommended types  
and quantities of engine fluids (oil, coolant,  
fuel, etc.) may result in an engine failure.  
!
!
• Wear full eye protection and protective clothing,  
• Where electrolyte contacts the skin, wash it off  
immediately with water,  
Before starting the generator for the first time, the  
installer must complete the following procedures. For  
follow-up maintenance information and/or service  
intervals, please refer to Section 4, “Maintenance.”  
• Where electrolyte contacts the eyes, flush thor-  
oughly and immediately with water and seek med-  
ical attention, and  
®
Generac Power Systems, Inc. 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Operation  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
2.11.2 TRANSFER SWITCH  
3.1 USING A STANDARD “GTS”  
If this generator is used to supply power to any elec-  
trical system normally powered by an electric utility,  
the National Electrical Code requires that a transfer  
switch be installed. The transfer switch prevents elec-  
trical backfeed between two different electrical sys-  
tems. (For additional information, see the applicable  
transfer switch manual for this unit.) The transfer  
switch, as well as the generator and other standby  
components, must be properly located and mounted  
in strict compliance with applicable codes, standards  
and regulations.  
TRANSFER SWITCH  
When required, the pre-packaged standby generator  
can be installed with a standard Generac “GTS” type  
engineered automatic transfer switch.  
When a GTS type transfer switch is used, it controls  
automatic operation and automatic transfer as fol-  
lows:  
• Solid state circuits in the transfer switch monitor  
utility power source voltage.  
• When utility source voltage drops below a pre-set  
level, transfer switch action closes the circuit. The  
engine then cranks and starts as controlled by the  
pre-packaged generator’s Control Module circuit  
board.  
• After the engine starts and when the generator AC  
output voltage and frequency have reached a  
pre-set value, transfer switch circuits signal the  
transfer switch main contacts to actuate to the  
“STANDBY” power source side. Generator AC out-  
put then powers load circuits.  
• When the utility power source voltage is restored  
above a pre-set level, transfer switch solid state  
circuits signal the switch main contacts to move  
back to their utility power source side.  
2.11.3 FUEL SYSTEM  
Make sure the fuel supply system to the generator (a)  
delivers the correct fuel at the correct pressure and  
(b) is properly purged and leak tested according to  
code. No fuel leakage is permitted. See  
“Specifications” (Section 1.10) for more information.  
2.11.4 GENERATOR SET LUBRICATION  
Check the engine crankcase oil level before operating  
and add oil to the proper level – the dipstick “FULL”  
mark. Never operate the engine with the oil level  
below the dipstick ADD” mark. See “Specifications”  
(Section 1.10) and “Engine Oil Recommendations”  
(Section 1.14).  
Following re-transfer back to the utility power  
source side, transfer switch circuit board action  
opens the circuit. Engine then shuts down.  
NOTE:  
NOTE:  
This engine is shipped from the manufacturer  
with 15W-40 oil. This oil should be changed after  
30 hours of operation.  
If the generator is installed in conjunction with a  
standard GTS type transfer switch, refer to the  
applicable transfer switch manual for exact oper-  
ating parameters and timing sequences.  
2.11.5 ENGINE COOLANT  
3.2 CONTROL CONSOLE  
Have the engine cooling system properly filled with  
the recommended coolant mixture. Check the system  
for leaks and other problems. See “Specifications”  
(Section 1.10) and “Coolant” (Section 1.15).  
COMPONENTS  
The components of a liquid-cooled generator control  
console (Figure 3.1) are as follows:  
Figure 3.1 - Liquid-Cooled Generator Panel  
2.11.6 BELT TENSION  
Check the engine fan belt tension and condition prior  
to placing the unit into service and at recommended  
intervals. Belt tension is correct when a force of  
approximately 22 pounds (10 kg), applied midway  
between pulleys, deflects the belt about 3/8- to 5/8-  
inch (10 to 16 mm).  
FUSE  
15-A  
AGC  
FAULT  
INDICATOR  
HOUR METER  
AUTO  
2.11.7 ELECTRICAL SYSTEM  
SET  
EXERCISE  
TIME  
OFF  
Make sure the generator is properly connected to an  
approved earth ground and/or ground rod.  
ON  
MANUAL  
Make sure the generator battery is fully charged, prop-  
erly installed and interconnected, and ready for use.  
Check to ensure that there are no loose electrical con-  
nections. Restrain any loose wires to keep them clear  
of any moving generator set components.  
®
12 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 - Operation  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
NOTE:  
3.2.1 HOURMETER  
This fuse will not remove the positive (+) battery  
input power from the PCB when it opens. This  
means the exercise timer will not be reset. If this  
fuse does open, carefully check the wiring to the  
start, fuel, field boost and transfer outputs before  
replacing the fuse.  
Indicates time the engine-generator has operated, in  
hours and tenths of hours. Use the hourmeter along  
with the periodic maintenance schedule for the gen-  
erator set.  
3.2.2 AUTO/OFF/MANUAL SWITCH  
Use this three-position switch as follows:  
3.2.6 SET EXERCISE TIME SWITCH  
• Set the switch to AUTO for fully automatic opera-  
tion. See Automatic Operation”, Section 3.4.  
• Set switch to MANUAL position to crank and start  
the generator engine.  
This switch allows for programming the generator to  
start and exercise automatically. See “Weekly  
Exercise Cycle” (Section 3.5).  
• Set switch to OFF position to shut down an oper-  
ating engine. With OFF selected, operation will not  
be possible.  
3.3 MANUAL TRANSFER AND  
START-UP  
To transfer electrical loads to the STANDBY (GEN-  
ERATOR) power source side and start the engine  
manually, refer to the Owner’s Manual of the particu-  
lar transfer switch.  
DANGER  
With switch set to AUTO, engine can crank  
and start suddenly without warning. Such  
automatic start up normally occurs when utili-  
!
3.4 AUTOMATIC OPERATION  
To set the system for fully automatic operation, pro-  
ceed as follows:  
ty source voltage drops below a pre-set level.  
To prevent possible injury that might be  
caused by such sudden starts, set  
AUTO/OFF/MANUAL switch to OFF before  
working on or around the unit. Then, place a  
"DO NOT OPERATE" tag on control console.  
• Check that load circuits are connected to the  
utility power supply.  
• Set the AUTO/OFF/MANUAL switch to its AUTO  
position.  
3.2.3 FAULT INDICATOR LAMP  
The lamp goes ON when one or more of the following  
engine faults occurs and when engine shuts down.  
• Set the generator main circuit breaker to its ON or  
CLOSED position.  
3.5 WEEKLY EXERCISE CYCLE  
The generator will start and exercise once every seven  
days. During this weekly exercise, the unit runs for  
about 20 minutes and shuts down. Transfer of loads  
to generator output does not occur during the exer-  
cise.  
• Low oil pressure  
• High coolant temperature  
• Low coolant level  
• Overcrank  
• Overspeed  
3.2.4 15 AMP FUSE  
The fuse protects the control console’s DC control  
circuit against electrical overload. If the fuse has  
melted open because of an overload, engine cranking  
and startup cannot occur. If replacement of the fuse  
is necessary, use only an identical 15-amp fuse. (Type  
AGC, part number 022676).  
To select day and time for exercising, proceed as  
follows:  
• Set the AUTO/OFF/MANUAL switch to OFF.  
• Set generator main circuit breaker to OFF or  
OPEN.  
• Locate the rocker switch on the control panel iden-  
tified with the words “Set Exercise Time” (Figure  
3.2).  
3.2.5 7.5 AMP INLINE FUSE  
This inline fuse is connected in the 15A line that runs  
between the Auto/Off/Manual switch and position 10  
of the 76009A PCB. This fuse protects the start, fuel,  
field boost, and transfer outputs from the PCB and  
will open if there is excessive current draw on any  
one of these outputs.  
• Push “Set Exercise Time” switch to ON position for  
20 to 30 seconds and then release. Switch will  
spring back into its original position when  
released.  
Wait 30 seconds before setting the AUTO/OFF/  
MANUAL switch to AUTO position.  
®
Generac Power Systems, Inc. 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Refer to applicable wiring diagram(s) and electrical  
schematic(s) at back of manual for wiring connec-  
tions. Customer supplies a 120V 15A Utility fed cir-  
cuit for the block heater.  
If the AUTO/OFF/MANUAL switch is switched  
too soon, the engine may start. If engine does  
start, it will shut down automatically in about  
two (2) minutes.  
!
4.1 MAINTENANCE PERFORMED BY  
AUTHORIZED SERVICE FACILITIES  
• Set the generator main circuit breaker to its ON or  
CLOSED position.  
• Generator is now programmed to start and exer-  
cise every seven days thereafter, on day and time of  
day the switch was actuated.  
• Place a sign on the generator control panel and the  
transfer switch, indicating the day and time the  
generator will be exercising.  
A. EVERY THREE MONTHS  
1.Check battery state of charge and condition.  
2.Inspect and test fuel system.  
3.Check transfer switch.  
4.Inspect exhaust system.  
5.Check engine ignition system.  
6.Check fan belts.  
NOTE:  
If battery terminals are disconnected, the exercise  
timer needs to be reset for correct automatic exer-  
cise operation.  
B. ONCE EVERY SIX MONTHS  
1.Test Engine Safety Devices (low oil pressure, low  
coolant level, high coolant temperature).  
Figure 3.2 - “Set Exercise” Switch  
C. ONCE ANNUALLY  
1.Test engine governor. Adjust or repair, if needed.  
2.Clean, inspect generator.  
3.Flush cooling system.  
D. FIRST 100 OPERATING HOURS  
1.Change engine oil and oil filter. (After initial  
change, service engine oil and filter at 150 oper-  
ating hours or six months, whichever comes  
first.)  
2.Retorque cylinder head. (See Torque Specs,  
Section 1.13.)  
3.Retorque intake and exhaust manifold. (See  
Torque Specs, Section 1.13.)  
3.6 ENGINE HEATER  
This standby generator comes equipped with a block  
heater (Figure 3.3), similar to the block heaters used  
in automotive applications. The block heater is wired  
to a grounded plug.  
E. EVERY 500 OPERATING HOURS  
1.Service air cleaner.  
2.Check starter.  
3.Check engine DC alternator.  
Figure 3.3 - Engine Block Heater  
F. EVERY 800 OPERATING HOURS  
1.Retorque cylinder head. (See Torque Specs,  
Section 1.13.)  
2.Retorque intake and exhaust manifold. (See  
Torque Specs, Section 1.13.)  
3.Check engine compression.  
4.Check valve clearance.  
®
14 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Figure 4.1 - Oil Dipstick and Oil Fill Cap  
4.2 COOLING SYSTEM  
Air intake and outlet openings in the generator com-  
partment must be open and unobstructed for contin-  
ued proper operation. This includes such obstruc-  
tions as high grass, weeds, brush, leaves and snow.  
OIL DIPSTICK  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it  
to shut down. (See Section 7 for installation drawings  
and vent locations.)  
The exhaust system parts from this product get  
extremely hot and remains hot after shutdown.  
High grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materials may  
ignite and burn from the heat of the exhaust  
system.  
4.4.2 BATTERY FLUID  
Check battery electrolyte fluid at least once weekly.  
Fluid should cover separators in all battery cells. If  
fluid level is low, add distilled water to cover tops of  
separators. DO NOT USE TAP WATER IN BATTERY.  
4.3 OVERLOAD PROTECTION FOR  
ENGINE DC ELECTRICAL SYSTEM  
Engine cranking, start up and running are controlled  
by a solid state Engine Controller circuit board.  
Battery voltage is delivered to that circuit board via a  
15 amp fuse. These overcurrent protection devices  
will open if the circuit is overloaded.  
4.4.3 ENGINE COOLANT  
Check coolant level in coolant recovery bottle. See  
Specifications, Section 1.10.  
• Add recommended coolant mixture as necessary.  
• Periodically remove radiator pressure cap to make  
sure the coolant recovery system is functioning  
properly. Coolant should be at bottom of radiator  
filler neck. If coolant level is low, inspect gasket in  
radiator pressure cap. Replace cap, if necessary.  
To have pressure cap tested, contact an authorized  
Generac Service Dealer. Inspect cooling system  
and coolant recovery system for leaks.  
If a circuit breaker opens or a fuse element  
melts, find the cause of the overload before  
resetting the circuit breaker or replacing the  
!
fuse.  
4.4 CHECKING FLUID LEVELS  
4.4.1 CHECK ENGINE OIL  
Check engine crankcase oil level (Figure 4.1) at least  
every 20 hours of operation, or prior to use.  
4.5 MAINTENANCE OWNER/  
OPERATOR CAN PERFORM  
• Remove oil dipstick and wipe dry with a clean,  
lint-free cloth.  
4.5.1 CHECK ENGINE OIL LEVEL  
Refer to “Checking Fluid Levels” in Section 4.4.  
• Install oil dipstick, then remove again.  
• Oil should be between FULL and ADD marks.  
• If oil level is below the dipstick ADD mark, remove  
oil fill cap. Add the recommended oil to bring oil  
level up to the FULL mark. DO NOT FILL ABOVE  
THE “FULLMARK. See Section 1.14 for recom-  
mended oils.  
4.5.2 CHECK BATTERY  
• Check battery fluid level each week as outlined  
under “Check Fluid Levels”.  
• Check battery cables for condition, tightness, cor-  
rosion or damage. Clean, tighten or replace as  
necessary.  
4.5.3 EXERCISE SYSTEM  
Start the generator engine at least once every seven  
days and let it run at least 20 minutes. See Section  
3.5, “Weekly Exercise Cycle”.  
®
Generac Power Systems, Inc. 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
4.5.4 INSPECT COOLING SYSTEM  
4.5.10 CHANGING ENGINE OIL  
• Inspect engine cooling system at least once each  
month.  
• Check hoses for damage, deterioration, leaks, etc.  
Correct any discrepancies found.  
• Check hose clamps for tightness.  
Refer to maintenance performed by authorized serv-  
ice facilities for engine oil and filter change frequen-  
cies.  
Drain the oil while the engine is still warm from run-  
ning. This means warm up the engine, shut it down  
and drain immediately as follows:  
4.5.5 CHECK ENGINE COOLANT LEVEL  
1. Remove OIL DRAIN HOSE from its retaining clip.  
2. Loosen and remove OIL DRAIN HOSE CAP.  
Drain oil completely into suitable container.  
3. When all oil has drained, install and tighten OIL  
DRAIN HOSE CAP, and re-install into its retaining  
clip.  
See “Checking Fluid Levels” in Section 4.4.  
4.5.6 PERFORM VISUAL INSPECTION  
Complete a thorough visual inspection of the entire  
engine-generator monthly. Look for obvious damage,  
loose, missing or corroded nuts, bolts and other fas-  
teners. Look for fuel, oil or coolant leaks.  
4. Turn OIL FILTER (Figure 4.2) counterclockwise  
and remove. Dispose of old filter.  
Figure 4.2 - Oil Filter  
4.5.7 INSPECT EXHAUST SYSTEM  
Inspect the exhaust system at least once every three  
months. Check all exhaust system pipes, mufflers,  
clamps, etc. for condition, tightness, leaks, security,  
damage.  
4.5.8 CHECK FAN BELT  
• Inspect fan belts every three months. Replace any  
damaged, deteriorated, worn or otherwise defec-  
tive belt.  
• Check fan belt tension. Thumb pressure, exerted  
midway between pulleys, should deflect about 3/8  
to 3/4 inch. Adjust belt tension as required.  
OIL FILTER  
4.5.9 INSPECT ENGINE GOVERNOR  
Visually inspect electronic governor.  
5. Apply light coating of new engine oil to seal of new  
oil filter. Install FILTER and tighten by hand only.  
DO NOT OVERTIGHTEN.  
6. Remove OIL FILL CAP. Add recommended oil (see  
SPECIFICATIONS). DO NOT FILL ABOVE THE  
DIPSTICK “FULLMARK. Crankcase oil capacity  
is 4.0 U.S. quarts (3.8 liters).  
DANGER  
DANGER: Do not attempt to adjust the gover-  
nor. Only qualified service facilities should  
adjust the governor. Excessively high operat-  
!
ing speeds are dangerous and increase the  
risk of personal injury. Low speeds impose a  
heavy load on the engine when adequate  
engine power is not available and may short-  
en engine life. Correct rated frequency and  
voltage are supplied only at the proper gov-  
erned speed. Some connected electrical load  
devices may be damaged by incorrect fre-  
quency and/or voltage. Only qualified service  
technicians should adjust the governed speed.  
After refilling the crankcase with oil, always  
check oil level on dipstick. NEVER OPERATE  
ENGINE WITH OIL BELOW THE DIPSTICK  
!
“ADD” MARK.  
7. Start engine and check for oil leaks.  
4.5.11 CHANGING THE ENGINE AIR CLEANER  
To replace the engine air cleaner, (part number  
059402), simply remove the air cleaner cover and  
replace the air filter making sure it is positioned  
properly before reattaching the cover (Figure 4.3).  
®
16 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Figure 4.3 – Engine Air Cleaner  
4.6 MISCELLANEOUS MAINTENANCE  
Air Cleaner  
4.6.1 CLEANING THE GENERATOR  
Keep the generator as clean and as dry as possible.  
Dirt and moisture that accumulates on internal gen-  
erator windings have an adverse effect on insulation  
resistance.  
Periodically clean generator exterior surfaces. A soft  
brush may be used to loosen caked on dirt. Use a  
vacuum system or dry, low pressure air to remove  
any accumulations of dirt. The generator is housed  
inside an all-weather enclosure, clean the enclosure  
with a soft, damp cloth or sponge and water. Apply a  
coat of automotive type wax once a year to help pre-  
vent corrosion.  
(Doors Removed for Clarity)  
Once each year, have the generator cleaned and  
inspected by an Authorized Service Dealer. That deal-  
er will use dry, low pressure air to clean internal  
windings. Parts inside the control console should be  
cleaned and inspected at this time as well.  
See the “Scheduled Maintenance,” Section 4.7, for air  
cleaner maintenance.  
4.5.12 SPARK PLUGS  
Reset the spark plug gap or replace the spark plugs  
as necessary. See Section 4.7.  
Finally, have the insulation resistance of stator and  
rotor windings checked. If insulation resistances are  
excessively low, the generator may require drying.  
1. Clean the area around the base of the spark plugs  
to keep dirt and debris out of the engine. Clean by  
scraping or washing using a wire brush and com-  
mercial solvent. Do not blast the spark plugs to  
clean.  
2. Remove the spark plugs and check the condition.  
Replace the spark plugs if worn or if reuse is  
questionable. See the “Scheduled Maintenance,”  
Section 4.7, for recommended inspection.  
3. Check the spark plug gap using a wire feeler  
gauge. Adjust the gap to 0.5-0.6 mm (0.020-0.025  
inch) by carefully bending the ground electrode  
(Figure 4.4).  
4.6.2 BATTERY  
All lead-acid storage batteries discharge when not in  
use. Refer to specific instructions and warnings that  
accompany the battery. If such information is not  
available, observe the following precautions when  
handling a battery:  
• DO NOT use jumper cables and a booster battery  
to crank or start the generator engine.  
• DO NOT recharge a weak battery while it is  
installed in the generator. Remove battery from  
generator and recharge in a well-ventilated area,  
away from fuel vapors, sparks, heat or flames.  
• Battery electrolyte fluid is an extremely caustic  
sulfuric solution that can cause severe burns. DO  
NOT permit fluid to contact eyes, skin, clothing,  
painted surfaces, wiring insulation, etc. If any bat-  
tery fluid is spilled, flush the affected area with  
clear water immediately.  
Figure 4.4 – Setting the Spark Plug Gap  
SET PLUG GAP AT 0.5-0.6 mm  
(0.020-0.025 inch)  
• Always wear safety glasses, rubber apron and  
gloves when handling a battery.  
• Batteries give off explosive hydrogen gas while  
charging. The gas can form an explosive mixture  
around the battery for several hours after charging.  
Any spark, heat or flames can ignite the gas and  
cause an explosion which can shatter the battery,  
causing blindness or other serious injury.  
4.5.13 COOLANT CHANGE  
Every year, have Authorized Service Facility drain,  
flush and refill the cooling system. See SPECIFICA-  
TIONS (Section 1.10) for cooling system recommen-  
dations.  
®
Generac Power Systems, Inc. 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
4.6.3 BATTERY MAINTENANCE  
The battery should be inspected per the “Scheduled  
Maintenance,” Section 4.7. The following procedure  
should be followed for inspection:  
Be sure the AUTO/OFF/MANUAL switch is set to  
the OFF position before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as  
the battery cables are connected.  
!
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries  
and, if necessary, fill with DISTILLED WATER  
ONLY. DO NOT USE TAP WATER IN BATTERIES.  
3. Have the state of charge and condition checked.  
This should be done with an automotive-type bat-  
tery hydrometer.  
Be sure the utility power supply is turned off,  
or sparking may occur at the battery posts as  
the cables are attached and cause an explosion.  
4.6.4 BATTERY REPLACEMENT  
When replacing batteries, use the same number and  
the type of battery that follows:  
DANGER  
BCI Group No.  
CCA  
525 @ 0 deg. F  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after  
charging. The slightest spark can ignite the gas  
and cause an explosion. Such an explosion can  
shatter the battery and cause blindness or  
other injury. Any area that houses a storage  
battery must be properly ventilated. Do not  
allow smoking, open flame, sparks or any spark  
producing tools or equipment near the battery.  
26/26R  
NOTE:  
The BCI number should be located directly  
on the battery.  
PERIODIC REPLACEMENT PARTS  
Part Name  
Oil Filter  
Radiator Cap  
Air Cleaner  
Spark Plug  
Generac’s Part Number  
# 0A45310244  
# 046627  
Battery electrolyte fluid is an extremely caustic  
sulfuric acid solution that can cause severe  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If the fluid is spilled, flush  
the affected area immediately with clear water.  
!
# 059402  
# 0A45310275  
Do not use any jumper cables or booster bat-  
tery to crank and start the generator engine. If  
!
the battery has completely discharged, remove  
it from the generator for recharging.  
®
18 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
4.7 SCHEDULED MAINTENANCE  
The following is a recommended maintenance schedule for Generac Guardian small standby and residential gen-  
erator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an  
average service application. They will need to be decreased (performed more frequently) if the unit is used in a  
severe application. Use the unit hour meter or calendar time, whichever occurs first, from the previous mainte-  
nance interval to determine the next required maintenance interval.  
Service Maintenance Interval Information:  
The various service maintenance intervals are designated by interval numbers as follows:  
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten-  
tial problem areas.  
Performed monthly or following each 10 hours of operation of the unit and requires approximately .5 man-  
hours per unit to complete.  
This inspection may be performed by the end user providing the following safety steps are taken to prevent  
the engine from starting automatically without warning:  
To prevent injury, perform the following steps in the order indicated before starting any maintenance:  
Disable the generator set from starting and/or connecting to the load by setting the control panel  
AUTO-OFF-MANUAL switch to the OFF position.  
Remove the control panel fuse.  
Turn off utility supply to engine water heater.  
Turn off the battery charger by turning off utility supply to the transfer switch.  
Remove the negative battery cable.  
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condi-  
tion from burning out sensitive control panel components and circuits.  
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal  
operation when required.  
2 A break-in service inspection of the generator set to insure it is ready to operate and carry the load when  
required, and to identify any potential problem areas.  
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of  
the unit and requires approximately 2.5 man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an authorized Generac Service Dealer.  
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed semi-annually or following each 50 hours of operation of the unit and requires approximately 1.5  
man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an authorized Generac Service Dealer.  
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and  
to identify any potential problem areas.  
Performed annually or following each 100 hours of operation of the unit and requires approximately 4.0  
man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an authorized Generac Service Dealer.  
®
Generac Power Systems, Inc. 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Maintenance  
Tasks  
Level 1  
Recom-  
mended  
Level 2  
Required  
Level 3  
Required  
Level 4  
Task  
Task  
Task  
Task  
Comp.  
Comp. to be done Comp. to be done Comp.  
Required  
to be done (Date-  
3 months/  
Break-in  
30 hrs.  
(Date-  
Initials)  
Semi-  
annually/  
50 hrs.  
(Date-  
Initials)  
to be done (Date-  
Annually/ Initials)  
100 hrs.  
monthly/  
10 hrs.  
Initials)  
1. Disable the unit from  
operating per the first page  
warning.  
2. Check the engine oil level.  
Adjust as necessary.  
3. Check the engine coolant  
level. Adjust as necessary.  
4. Check the engine coolant  
thermal protection level.  
Correct as necessary.  
5. Check the natural gas  
delivery system on gas  
engine driven units.  
Tighten connections as  
necessary.  
6. Check the air inlets and  
outlets for debris. Clean as  
necessary.  
7. Check the battery  
electrolyte level if  
accessible. Adjust as  
necessary.  
8. Check the battery posts,  
cables, and charger for  
loose connections,  
corrosion, and proper  
operation. Correct as  
necessary.  
9. Check the unit wiring for  
loose connections,  
corrosion, and damage.  
Correct as necessary.  
10. Check the engine  
accessory drive belts for  
wear, weather cracking,  
and damage. Replace as  
necessary.  
11. Visually inspect the unit  
looking for leaks, wear or  
damage, loose connections  
or components, and  
corrosion. Correct as  
necessary.  
12. Test the engine and  
transfer switch safety  
devices. Correct and/or  
adjust as necessary.  
®
20 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Maintenance  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Maintenance  
Tasks  
Level 1  
Recom-  
mended  
Level 2  
Required  
Level 3  
Required  
Level 4  
Task  
Task  
Task  
Task  
Comp.  
Comp. to be done Comp. to be done Comp.  
Required  
to be done (Date-  
3 months/  
Break-in  
30 hrs.  
(Date-  
Initials)  
Semi-  
annually/  
50 hrs.  
(Date-  
Initials)  
to be done (Date-  
Annually/ Initials)  
100 hrs.  
monthly/  
10 hrs.  
Initials)  
13. Initiate an automatic start  
and transfer of the unit to  
site load and exercise it for  
at least 1 hour looking for  
leaks, loose connections  
or components, and  
abnormal operating  
conditions. Correct as  
necessary.  
14. Start and exercise the unit  
at full rated load (use a  
load bank if the site load is  
not enough) for at least 2  
hours looking for leaks,  
loose connections or  
components, and abnormal  
operating conditions.  
Correct as necessary.  
15. Change the engine oil.  
16. Replace the engine oil  
filter(s).  
17. Replace the engine air  
filter(s).  
18. Check the engine spark  
plugs on gas engine driven  
units. Clean and re-gap or  
replace as necessary.  
19. Perform a 5 minute no-load  
operational run of the unit  
looking for any post service  
problems.  
20. Return the unit to standby  
setup for operation when  
required.  
®
Generac Power Systems, Inc. 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Troubleshooting  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
5.1 TROUBLESHOOTING POINTS  
PROBLEM  
CAUSE  
CORRECTION  
Engine won’t crank.  
1. 15 amp fuse blown.  
1. Replace fuse.  
2. Loose or corroded or defective  
battery cables.  
2. Tighten, clean or replace  
battery cables as necessary.  
3. Defective starter contactor.  
4. Defective starter motor.  
5. Dead or Defective Battery.  
3. Replace contactor.  
4. Replace starter motor.  
5. Remove, change or replace battery.  
Engine cranks but won't start  
1. Out of fuel.  
2. Fuel solenoid (FS) is defective  
3. Open Wire #14 from Engine Control  
circuit board.  
1. Replenish fuel.  
2. Replace solenoid.  
3. Reconnect wire.  
4. Spark plugs defective.  
4. Clean, regap or replace plugs.  
1. Clean or replace as needed.  
Engine starts hard, runs rough.  
Engine starts then shuts down.  
1. Flame arrestor (air cleaner) plugged or  
damaged.  
2. Plugged fuel line.  
3. Defective spark plugs.  
2. Unclog fuel line.  
3. Clean, regap or replace plugs.  
1. Engine oil level is low.  
2. Engine is overheated.  
3. Defective Low Oil Pressure Switch  
4. Defective Coolant Temperature Switch  
5. Defective Control Module circuit board.  
6. Coolant Level is Low.  
1. Check oil and add oil as needed.  
2. Check cooling system for leaks.  
3. Replace switch.  
4. Replace switch.  
5. Replace board.  
6. Repair leak - Add coolant.  
7. Replace Switch.  
7. Defective Low Coolant Level Switch  
AUTO/OFF/MANUAL Switch at OFF,  
engine continues to run  
1. Defective AUTO/OFF/MANUAL switch  
1. Replace switch.  
2. Reconnect/close wire.  
2. Open/disconnected wire #15A between  
AUTO/OFF/MANUAL switch and Control  
Module circuit board.  
3. Defective Control Module circuit board  
3. Replace board.  
No AC output from generator.  
1. Check main line circuit breaker.  
2. Check circuit breaker & fuses.  
3. Transfer switch set to NORMAL position  
4. Generator internal failure.  
1. Reset to ON or CLOSED.  
2. Reset and replace, if necessary.  
3. Set to GENERATOR position.  
4. Contact an Authorized Generac  
facility.  
5. Thermal circuit breaker open.  
5. Auto-reset - Wait five min. and  
attempt restart.  
®
22 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 — Notes  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
®
Generac Power Systems, Inc. 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 — Notes  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
®
24 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 - Installation Diagram  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Drawing No. 0E1533  
®
Generac Power Systems, Inc. 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Electrical Data  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Wiring Diagram — Control Panel —Drawing No. 0E0345  
2
7
K
L A  
4
+
®
26 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Electrical Data  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Wiring Diagram — 1.5L Engine — Drawing No. 0E0343-A  
LOS  
WLS  
DIS  
DC-VR  
3
1
2
4
5
CC  
FS  
14  
48  
0
49 13 14  
13  
13  
85  
56  
85  
0
0
0
RED  
3
4
5
6
8
9
85  
85  
85  
56  
0
85  
CONTROL  
PANEL  
0
0
14  
CONNECTION  
0
0
0
8
9
10  
11  
12  
13  
14  
14  
14  
GRD  
10  
11  
12  
16  
DC-A  
49  
48  
RED  
SM  
LEGEND  
CC - CONTROL CONTACTOR  
DIS - DISTRIBUTOR  
12-V.  
BATTERY  
BLACK  
DCA - DC ALTERNATOR  
EH - ENGINE HEATER  
GRD  
FS - FUEL SOLENOID  
GRD - GROUND  
EH  
LOS - LOW OIL PRESSURE SWITCH  
SM - STARTER MOTOR  
TO 120V/15A  
UTILITY FED  
CIRCUIT  
BLACK  
WHITE  
WTS - WATER TEMPERATURE SWITCH  
WLS - WATER LEVEL SENSOR  
GREEN  
TO  
ELECTRONIC  
GOVERNOR  
GOVERNOR  
ACTUATOR  
CONTROLLER  
ACTUATOR  
CONNECTOR  
®
Generac Power Systems, Inc. 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Electrical Data  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Wiring Diagram — 1.5L Guardian — Drawing No. 0E1525  
RED  
RED  
BLACK  
BLACK  
BLUE  
BLUE  
®
28 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 - Electrical Data  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Electrical Schematic — 1.5L — Drawing No. 0A7182-B  
WTS  
LOS  
85  
85  
WLS  
0
0
13  
0
CC  
56  
0
0
56  
14  
14  
FS  
14  
14  
13  
49  
49  
49  
49  
0
14  
13  
12V BATTERY  
(+)  
(-)  
13  
RED  
BLACK  
CC  
SM  
16  
0
0
GRD  
BLACK  
WHITE  
LEGEND  
EH  
GREEN  
CC - CONTROL CONTACTOR  
DCA - DC ALTERNATOR  
EH - ENGINE HEATER  
FS - FUEL SOLENOID  
GRD - GROUND  
ISC - IGNITION SYSTEM CONTACT  
LOS - LOW OIL SWITCH  
SM - STARTER MOTOR  
WTS - WATER TEMPERATURE SWITCH  
WLS - WATER LEVEL SWITCH  
ACTUATOR  
CONNECTOR  
®
Generac Power Systems, Inc. 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Governor Assembly — Drawing No. 0E1331-B  
5
4
3
ITEM (13) NEOPRENE  
COATING  
2
1
14  
6
7
10  
WIRE HARNESS  
15  
SECURE WIRE HARNESS  
WITH TIE WRAP AS SHOWN.  
12  
7
16  
9
"A"  
17  
TO "A"  
10  
7
6
INTAKE MANIFOLD  
(REF.)  
CARBURETOR ARM  
(REF.)  
11  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
098290  
098941A  
098958A  
098942A  
098225  
043146  
022097  
084543A  
098783  
037398  
0E1326  
0A7106  
074031  
029333A  
022507  
022473  
064526  
0E1694  
1
1
REF  
1
2
3
5
1
1
2
1
1
AR  
10  
2
2
1
1
ASM MOTOR STEPPER  
HOUSING GOVERNOR CONNECTOR  
CONNECTOR INTERFACE ASSEMBLY  
COVER CONNECTOR HOUSING  
SCREW FHM #2 X 5/8 SELF TAP  
SCREW HHC M6-1.0 X 10 G8.8  
WASHER LOCK M6-1/4  
SCREW PHM M3-0.5 X 12MM  
LEVER STEPPER MOTOR  
NUT LOCK HEX #10-32 NYL INS  
ASSY. CARBURETOR LINKAGE ROD  
BRACKET STEPPER MOTOR  
LIQUID NEOPRENE  
TIE WRAP 7.4"X.19" BLK UL  
SCREW HHC 1/4-20 X 1/2 G5  
WASHER FLAT 1/4 ZINC  
SCREW TAP HWH #6-25 X 3/8 ZINC  
SPRING,ANTI LASH  
®
30 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Mounting Base — Drawing No. 0E0768-B  
8
7
6
14  
5
7
13  
6
4
9
10  
5
15  
15  
7
6
6
11  
16  
2
17  
18  
20  
3
9
10  
22  
1
15  
20  
22  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
0D8656  
027482  
070936  
070936C  
039253  
022145  
022129  
045771  
071956  
051730  
021991  
0D9335  
0D9336  
0C2454  
047411  
022097  
022473  
055414  
049813  
026850  
0A1694  
1
2
2
2
8
12  
16  
4
4
4
1
2
2
16  
1
1
1
1
5
BASE MOUNTING 1.5L STNRD & ACSTC  
WASHER SHAKEPROOF EXT 5/16 STL  
DAMPENER VIBRATION  
VIB. ISO. 70-75 DURO  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER FLAT M8  
SCREW HHC M8-1.25 X 60 G8.8  
EARTH STRAP  
PANEL SUPPORT  
PANEL BRACKET  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
LUG SLDLSS #2-#8 X 17/64 CU  
NUT HEX M6 X 1.0 G8 YEL CHR  
WASHER SHAKEPROOF EXT 1/4 STL  
1-1/2" BUTTON PLUG  
1
2
®
Generac Power Systems, Inc. 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW and 20 kW Generators  
Standard Compartment — Drawing No. 0E0771-D  
®
32 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW and 20 kW Generators  
Standard Compartment — Drawing No. 0E0771-D  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
0D8666  
0D8664C  
0D8657  
0D8660  
0A7568  
0D8659  
0D8662  
0D8661  
0D8658  
067042  
0C2454  
033530  
051716  
022152  
0912970064  
023762  
1
1
1
2
2
1
1
1
1
2
40  
3
3
3
3
3
3
6
6
1
1
1
1
3
1
6
21  
1
1
ROOF ACSTC&STND CMPRTMNT 1.5L  
DUCT CENTER 1.5L  
SUPPORT RADIATOR 1.5L MITSU  
BRACE SIDE 1.5L MITSU  
DOORWELDMENT 1.5EPS  
CORNER POST REAR RH SIDE 1.5L  
DOOR REAR COMPARTMENT 1.5L  
BRACE REAR 1.5L MITSU  
CORNER POST REAR LH SIDE 1.5L  
LATCH & CAM  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
SCREW PHM #10-32 X 5/8 ZINC  
NUT HEX M5-0.8 G8 YEL CHR  
WASHER LOCK #10  
ASSEMBLY BASE-DOOR GROUND WIRE  
WASHER SHAKEPROOF EXT #10 STL  
GRD WIRE ASS'Y 99HSB  
WASHER LOCK #8-M4  
SCREW PPHM #8-32 X 5/16  
NUT HEX 1/4-20 STEEL  
ASSEMBLY COVER ACCESS  
WASHER FLAT 1/4 ZINC  
WASHER LOCK M6-1/4  
GASKET CLIP-ON SELF GRIPPING  
LATCH AND CAM  
NUT HEX JAM 3/8-24 SS  
GASKET CLIP-ON SELF GRIPPING  
DUCT LH SIDE 1.5L  
DUCT RH SIDE 1.5L  
0912970063  
022264  
067035  
022127  
0C2634A  
022473  
022097  
0D2023  
0C2164  
037337  
0D2023  
0D8664A  
0D8664B  
®
Generac Power Systems, Inc. 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 25 kW Generators  
Acoustic Compartment — Drawing No. 0E0772-E  
®
34 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 25 kW Generators  
Acoustic Compartment — Drawing No. 0E0772-E  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
0D8666  
0D8664C  
0D8657  
0D8660  
0A7568  
0D8659  
0D8662  
0D8661  
0D8658  
067042  
0C2454  
033530  
051716  
022152  
0912970064  
023762  
1
1
1
2
2
1
1
1
1
2
40  
3
3
3
3
3
3
6
6
13  
1
9
9
9
2
2
1
1
2
1
1
2
2
2
2
2
2
1
1
2
2
3
1
6
1
1
ROOF ACSTC & STND CMPRTMNT 1.5L  
DUCT CENTER 1.5L  
SUPPORT RADIATOR 1.5L MITSU  
BRACE SIDE 1.5L MITSU  
DOOR WELDMENT 1.5 EPS  
CORNER POST REAR RH SIDE 1.5L  
DOOR REAR COMPARTMENT 1.5L  
BRACE REAR 1.5L MITSU  
CORNER POST REAR LH SIDE 1.5L  
LATCH & CAM  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
SCREW PHM #10-32 X 5/8 ZINC  
NUT HEX M5-0.8 G8 YEL CHR  
WASHER LOCK #10  
ASSEMBLY BASE-DOOR GROUND WIRE  
WASHER SHAKEPROOF EXT #10 STL  
GRD WIRE ASS'Y 99HSB  
WASHER LOCK #8-M4  
SCREW PPHM #8-32 X 5/16  
WASHER SELF LOCKING DOME  
ASSEMBLY COVER ACCESS  
WASHER FLAT 1/4 ZINC  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
45  
46  
47  
0912970063  
022264  
067035  
078115  
0C2634A  
022473  
022097  
022127  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
0D8663  
0D8665  
0E0072D  
0E0072B  
0E0072Q  
0E0072C  
0E0072A  
0E0072M  
0E0072P  
0E0072L  
0E0072N  
0E0072G  
0E0072J  
0E0072F  
0E0072E  
0E0072K  
0E0072H  
0D2023  
0C2164  
037337  
BAFFLE CNTRL PNL 1.5L ACOUSTIC  
BAFFLE DOOR 1.5L ACOUSTIC UNIT  
ACSTC INSLTN 1.5L DUCT RH PNL  
ACSTC INSLTN 1.5L DUCT LH PNL  
ACSTC INSLTN 1.5L RAD SUPPORT  
ACSTC INSLTN 1.5L DUCT FNT PNL  
ACSTC INSLTN 1.5L ROOF PANEL  
ACSTC INSLTN 1.5L SIDE DR PNL  
ACSTC INSLTN 1.5L SIDE DR PNL  
ACSTC INSLTN 1.5L SIDE BRC PNL  
ACSTC INSLTN 1.5L DR BAFFLE PL  
ACSTC INSLTN 1.5L RR CRNR TOP  
ACSTC INSLTN 1.5L RR CRNR BOTT  
ACSTC INSLTN 1.5L REAR DR PNL  
ACSTC INSLTN 1.5L REAR BRC PNL  
ACSTC INSLTN 1.5L BAFFLE PANEL  
ACSTC INSLTN 1.5L CNTRL SUPPT  
GASKET CLIP-ON SELF GRIPPING  
LATCH AND CAM  
NUT HEX JAM 3/8-24 SS  
DUCT LH SIDE 1.5L  
DUCT RH SIDE 1.5L  
0D8664A  
0D8664B  
®
Generac Power Systems, Inc. 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Control Panel — Drawing No. 0E0778-G  
®
36 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Control Panel — Drawing No. 0E0778-G  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
3
0D9322  
0D9332  
0D9325A  
1
1
1
PANEL BACK & BOTTOM GUARDIAN  
PANEL LH SIDE GUARDIAN & SPRN  
PANEL FRONT CONTROL GUARDIAN  
W/ SILKSC  
PANEL RH SIDE C-PANEL SML BRK  
HOURMETER  
LIGHT 12VDC .02A LED RED PILOT  
HOLDER FUSE  
FUSE 15A X AGC15  
SWITCH ROC DPDT ON-OFF-ON  
SWITCH ROCKER DPST 125V SPD  
ASSEMBLY REGULATOR POTTED  
TFMR ASM CMA 240/12V  
PP LOGIC ASM 50/60HZ  
HARNESS CONTROL PANEL PP  
GUARDIAN  
RELAY SOLENOID 12VDC PNL MNT  
CIRCT BRK 4 X 1 ETA 46-500-P  
BLOCK TERM 20A 7 X 6 X 1100V  
BLOCK TERM 20A 2 X 6 X 1100V  
BLOCK TERM 20A 20 X 6 X 1100V  
ASSY L.C. ELECT GOV  
DECAL CUST. CONNT. PRE-PACK1.5L  
DECAL TERMINAL STRIP PRE-PACK  
NUT SPACER.250 PCB  
SCREW PPH TAPPING #6 X 5/8 SS  
SCREW PHM M6-1.0 X 20MM  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
SCREW PHTT M4-0.7 X 16 ZYC  
WASHER SHAKEPROOF EXT #10  
STL  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
0C2267  
023897  
0C2454  
054199  
081988  
0E2514  
0A1354A  
074908  
020911  
051713  
049226  
051716  
036261  
0D9334  
061979  
022237  
022241  
057073  
055440  
0D8671  
0912970080  
049813  
033121  
026850  
14  
15  
4
1
1
1
1
4
4
5
5
5
4
1
1
1
1
1
1
1
1
1
1
1
SCREW HHTT M5-0.8 X 12 BP  
WASHER FLAT #10 ZINC  
SCREW TH-FRM M6-1X16 N WA Z/JS  
DECAL HIGH VOLTAGE  
DECAL EXERCISE INFO  
STRAIGHT WIRE CONNECTOR 1 1/2"  
REGULATOR - DC ALT  
SCREW HHTT M5-0.8 X 10 BP  
SCREW PPHM M5-0.8 X 30 ZINC  
WASHER FLAT M5  
4
5
6
7
8
0D9330  
0C1457  
064009  
032300  
022676  
0E4494  
082573  
083048  
083264  
076009A  
0E0331  
1
1
1
1
1
1
1
1
1
1
1
9
10  
11  
12  
13  
14 *  
WASHER LOCK M5  
NUT HEX M5-0.8 G8 YEL CHR  
RIVET POP .125 X .129-.133/#30  
PANEL, TOP  
BUS BAR  
WASHER LOCK 3/8  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
056739  
049350  
047822  
048766  
057335  
098647  
0E1454  
0E1459  
072566  
080882  
0A8955  
022097  
022473  
0C2212  
023762  
1
1
1
1
1
1
1
1
4
4
2
3
2
10  
2
NUT HEX 3/8-16 STEEL  
JUNCTION BLOCK 3/8-16  
SCREW HHC M5-0.8 X 25 G8.8  
HINGE CONTINUOUS 1.5L CNTL PNL  
WIRE ASSEMBLY  
NUT HEX M6 X 1.0 G8 YEL CHR  
SCREW HHC #10-32 X 1/2  
WASHER SHAKEPROOF EXT 1/4  
STL  
NUT HEX #10-32 STEEL  
WASHER LOCK #10  
CAPACITOR FILTER ASY  
SCREW PHTT #6-32 X 5/8 ZYC  
DECAL WARNING REMOVE FUSE  
54  
55  
56  
57  
58  
022158  
022152  
0A3968  
0C2323  
0E3783  
1
1
1
2
1
* NOT SHOWN  
®
Generac Power Systems, Inc. 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Engine — Drawing No. 0E1228-E  
®
38 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Engine — Drawing No. 0E1228-E  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
4
5
6
7
8
9
0A4531  
022473  
0A45310258  
0A4355  
0E2632  
022097  
022507  
052212  
046526  
022131  
0C2499  
055993  
045772  
023586  
020692  
0A7005  
052243  
0A4772  
070901  
051735  
056768  
022145  
022129  
022259  
052213  
047411  
052830  
045771  
058306  
030795  
0A2711A  
048665  
075885  
0A45310257  
0E1100  
0E0561  
1
2
1
1
1
8
2
2
4
20  
2
1
1
2
1
2
1
1
2
3
3
9
18  
2
11  
2
1
12  
5
2
1
1
1
1
1
1
ENGINE-1.5L  
WASHER FLAT 1/4 ZINC  
GASKET-EXHAUST MANIFOLD  
MANIFOLD-EXHAUST  
HEAT SHIELD EXH 1.5L  
42  
43  
44  
45  
46  
061012  
039253  
0A5110  
0A7006  
025507  
1
4
1
1
2
PLUG STD PIPE 1/8 SCKT HD  
SCREW HHC M8-1.25 X 20 G8.8  
PIPE WATER-INLET  
O-RING 1-1/16 X 1-5/16 X 1/8  
WASHER SHAKEPROOF EXT 7/16  
STL  
SPACER .41 X .75 X .25 ST/ZNC  
SWITCH OIL PRESSURE  
ELBOW 90D STREET 1/8  
ADAPTOR 1/8 NPTF TO 1/8-28  
PLUG STD PIPE 1/4 STEEL SQ HD  
SCREW HHC M10-1.5 X 110 G8.8  
SCREW HHC M8-1.25 X 35 G8.8  
SCREW HHC M12-1.25 X 55 G8.8  
WASHER LOCK M12  
PULLEY-CRANKSHAFT (1800 RPM)  
BUILT PRIOR TO 11/20/02  
PULLEY-CRANKSHAFT (1800 RPM)  
BUILT AFTER 11/20/02  
PULLEY-CRANKSHAFT (3600 RPM)  
BUILT PRIOR TO 11/20/02  
PULLEY-CRANKSHAFT (3600 RPM)  
BUILT AFTER 11/20/02  
BRACKET - ALT SUPPRT  
DC ALTERNATOR-12V  
ARM ADJUST ALTERNATOR  
SCREW HHC M6-1.0 X 70 G8.8  
WASHER FLAT M6  
WASHER LOCK M6-1/4  
SCREW HHC 1/4-20 X 1/2 G5  
SCREW HHC M10-1.25 X 25 G8.8  
WASHER-LOCK-M10  
WASHER FLAT 3/8 ZINC  
STAMPING ENG FOOT  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
022500B  
0A8584  
036277  
042574  
026073A  
0A6701  
039414  
0A5568  
051769  
0A4804  
2
1
1
1
1
1
1
1
1
1
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
30  
31  
32  
33  
34  
35  
36  
37  
38  
SPACER .41 X .75 X .12 STL/ZNC  
NUT HEX M10-1.5 G8 YEL CHR  
SCREW SHC 5/16-18 X 2 G8.8 NZ  
STARTER-12V  
SPACER .56 X 1 X .37 ST/ZNC  
SCREW HHC M10-1.5 X 60 G8.8  
ENGINE PLATE  
SLEEVE DOWEL BLHSG  
SCREW HHC M10-1.5 X 70 G8.8  
SCREW HHC M10-1.5 X 90 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX 5/16-18 STEEL  
SCREW HHC M10-1.25 X 20 G8.8  
SCREW HHC M6-1.0 X 16 G8.8  
SCREW HHC M10-1.25 X 45 G8.8  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW SHC M8-1.25 X 25 G12.9  
SCREW HHC 5/16-18 X 1 G5  
ADAPTER-THERMOSTAT  
GASKET THERMOSTAT  
0A4804A  
0A4800  
1
1
1
0A4800A  
57  
58  
59  
60  
61  
62  
63  
64  
0A5839  
0A1354B  
0A4839  
055816  
1
1
1
4
9
1
1
1
1
1
1
1
1
1
1
1
2
049811  
0E1936  
0A2628  
0A5275  
0A5586  
0A4814  
0A45310244  
0C1852  
0912970066  
070928  
FAN COOLING 15"  
PULLEY - FAN 95 DIA  
V-BELT 3/8 X 32-1/8 1.5L  
V-BELT 3/8 X 28.9 1.5L  
SPACER PULLEY  
THERMOSTAT 195 DEG  
65  
66  
67  
68  
69  
70  
71  
72  
GASKET INLET MANIFOLD  
MANIFOLD INTAKE MACHINED  
ASSY WATER LEVEL SENSOR C/E  
PL  
SW-TMP 245 DEG 3/8 NPT  
BARBED EL 90 3/8 NPT X 5/8  
PLUG STD PIPE 3/8 STEEL SQ HD  
FILTER OIL  
ADAPTER DRAIN OIL  
GROUND WIRE (STARTER)  
CLAMP HOSE - OIL DRAIN  
HOSE ASM.-OIL DRAIN  
CAP HEX 1/4NPT BRASS  
SCREW CRMPTIT 1/4-20 X 5/8  
39  
40  
41  
0A6751  
034339  
026925  
1
1
1
069860C  
069811  
075443  
®
Generac Power Systems, Inc. 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Radiator — Drawing No. 0E0769-G  
®
40 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Radiator — Drawing No. 0E0769-G  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4 *  
5
6
7
8
9
0D8657  
0A5734  
0A6237  
0A6238  
084918  
050967  
048031C  
099502  
083709  
052250  
047411  
022097  
049813  
022473  
084427  
050967  
075443  
056892  
0A6284  
0A6258  
029032  
031669  
060035  
022127  
046627  
0C7649  
0C2454  
076749  
0E0726  
035461  
0A7275  
0A2111  
065852  
047290A  
1
1
1
1
1
1
4
4
1
2
4
8
2
9
1
1
6
4
1
1
1
4
4
4
1
1
4
1
1
1
3
2
2
1
SUPPORT RADIATOR 1.5L MITSU  
RADIATOR 1.5L  
VENTURI 1.5L MODINE  
GUARD FAN 1.5L MODINE  
HEATER ENGINE 0500W 120V  
HOSE 5/8 ID RIA 250F 12"  
CLAMP HOSE BAND 1/4  
CLAMP HOSE #24 B1.06 - 2.00  
CLAMP WIRE HOSE .573 - .551  
TAPE FOAM 1 X 1 (12" LG)  
SCREW HHC M6-1.0 X 16 G8.8  
WASHER LOCK M6-1/4  
10  
11  
12  
13  
14  
15  
16  
17 *  
18  
19  
20  
21  
22  
23  
24  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
NUT HEX M6 X 1.0 G8 YEL CHR  
WASHER FLAT 1/4 ZINC  
BRACKET HEATER  
HOSE 5/8 ID RIA 250F 18"  
SCREW CRMPTIT 1/4-20 X 5/8  
SCREW CRIMPTITE 10-24 X 3/8  
HOSE - LOWER RADIATR  
HOSE - UPPER RADIATR  
HOSE 9/32 ID (36" LG)  
BOLT CARR 1/4-20 X 1-3/4 JS500  
SPACER .41 X .75 X .87 ST/ZNC  
NUT HEX 1/4-20 STEEL  
CAP RADIATOR  
CLAMP HOSE .38-.87  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
TANK COOLANT RECOVERY  
BRACKET WATER BOTTLE 1.5L MIT  
BARBED STR 1/4 NPT X 3/8  
FOAM 1.5 X 1 ADH BAK  
SCREW SWAGE 10-32 X 5/16 Z/YC  
SPRING CLIP HOLDER .37-.62  
ASSY. RAD. DRAIN HOSE  
* FAN GUARD KIT 0E3596 (NOT USED WITH LEVEL ONE GUARDING)  
®
Generac Power Systems, Inc. 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Fuel System — Drawing No. 0E0774-D  
18  
13  
21  
24  
8
25  
22  
17  
16  
29  
"C"  
"D"  
14  
30  
12  
34  
36  
31  
37  
35  
32  
33  
38  
39  
40  
19  
41  
26  
20  
6
28  
PORT  
"OUT 1"  
(NATURAL GAS)  
41  
3
6
11  
43  
9
14  
42  
10  
"D"  
23  
40  
41  
7
6
PORT  
"OUT 2"  
2
15  
11  
5
27  
4
®
42 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Fuel System — Drawing No. 0E0774-D  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1 *  
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16 **  
17  
18  
19  
20  
21 **  
22 **  
23  
24  
25  
26  
27  
28  
29  
---------  
1
1
1
2
2
6
2
1
1
1
1
1
1
4
1
1
1
1
1
1
4
4
1
1
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
2
WELDMENT MOUNTING BASE  
FLANGE FUEL INLET  
ASSY REGULATOR 1.5L N.G.OR LPV  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
BRACKET-RAD HOSE  
BARBED EL 90 5/16 X 1/8 NPT  
HOSE 9/32 ID 11"  
FUEL HOSE ASSM. NAT.GAS/L.P.V.  
HOSE 9/32 ID 6.5"  
COVER AIR CLEANER  
CLAMP HOSE BAND 1/4  
DECAL INLET PRESSURE  
ADAPTER,CARB.TO AIR CLNR  
FILTER ELEMENT  
NUT WING 1/4-20 NYLK  
CARBURETOR ASSY. 1.5L  
CARBURETOR GASKET  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER LOCK M5  
ELBOW 90D STREET 3/4  
STUD TH 1/4-20 X 3 G2 ZNC FULL  
NUT HEX 1/4-20 STEEL  
075580  
0E1006  
039253  
022145  
022129  
045771  
0A7040  
032552  
029032  
0E1056  
029032  
0A5547  
048031C  
0D1509  
0E0591  
059402  
037561  
0E1028  
059401  
091526  
049226  
026307  
062522  
022127  
022259  
050279  
0A6125  
0D8492Q  
0D8492R  
0E1104  
0E0668  
0E0590  
0C5133  
0E0665  
0E1108  
033138  
022152  
0E0645  
063463A  
0E1558  
057823  
0E1111  
042907  
0C2454  
NUT HEX 5/16-18 STEEL  
DECAL FUEL INLET NG  
STUD 5/16-18 X 1.25 F THR  
DECAL EMISSION CTRL 1.5 NG 2004 (10-15KW NATURAL GAS)  
DECAL EMISSION CTRL 1.5 LP 2004 (10-15KW LP VAPOR UNITS)  
GASKET AIR CLEANER ADAPTER  
O-RING 2-028 1.38 X 1.50 X .06  
VENTURI 18MM  
30 **  
31 **  
32 **  
33 **  
34 **  
35 **  
36 **  
37 **  
38 **  
39 **  
40  
O-RING 29.82 X 2.62  
SCREW THROTTLE PIN STOP  
THROTTLE ARM REWORK  
SCREW HHM #10-32 X 5/8  
WASHER LOCK #10  
LEVER THROTTLE STOP  
BARBED STR 3/8NPT X 1/2 W/VS  
HOSE LPG & NAT GAS 1/2 ID (23"LG)  
CLAMP HOSE #10 .56 - 1.06  
PLATE, GAS REGULATOR MOUNTING  
SCREW HHC M8-1.25 X 16 G8.8  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
41  
42  
43  
44  
*
SHOWN IN OTHER VIEW  
** INCLUDED IN ITEM 19 (CARBURETOR ASY. )  
®
Generac Power Systems, Inc. 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Alternator — Drawing No. 0A9348-F  
®
44 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Alternator — Drawing No. 0A9348-F  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
098671  
098681  
098675  
098936  
0A5336A  
0A1659  
071912  
049226  
051713  
022129  
098672  
098673  
098674  
098682  
098683  
098684  
098676  
098677  
098678  
097620  
098937  
097621  
0A5382  
075591  
075476  
0A5601  
075554B  
0A9375  
022152  
097146  
042558  
0A5061  
0A4989  
053557  
051769  
049541  
046526  
045772  
087599  
077043E  
022131  
072578  
0A7043  
049808  
058589  
023365  
0A8830  
072080  
1
1
1
1
1
1
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
4
4
4
1
1
1
1
1
6
4
4
4
1
1
4
1
5
5
1
4
4
1
ASSY ROTOR 10KW  
ASSY ROTOR 15KW  
ASSY ROTOR 20KW  
ASSY ROTOR 25KW  
HOUSING BLOWER  
SCREEN AIR OUTLET  
SCREW PPHM M5-0.8 X 8 SS  
WASHER LOCK M5  
WASHER FLAT M5  
2
3
4
5
6
7
8
WASHER LOCK M8-5/16  
ASSY STATOR 10KW A  
ASSY STATOR 10KW D  
ASSY STATOR 10KW GJK  
ASSY STATOR 15KW 1PH A  
ASSY STATOR 15KW 3PH D  
ASSY STATOR 15KW 1PH GJK  
ASSY STATOR 20KW 1PH A  
ASSY STATOR 20KW 1PH D  
ASSY STATOR 20KW 1PH GJK  
ASSY STATOR 25KW 1PH A  
ASSY STATOR 25KW 1PH D  
ASSY STATOR 25KW 3PH D  
BEARING CARRIER REAR  
ASSY HOLDER BRUSH  
SCREW PPHM M4-0.7 X 16  
COVER REAR BEARING CARRIER  
BOLT STATOR X 16" LG  
SCREW RHM #10-24 X 2  
WASHER LOCK #10  
FAN & RING GEAR ASSEM.  
KEY SQ 3/8 X 1 STEEL  
SPACER-FLEX PLATE  
PLATE, FLEX  
SCREW HHC M12-1.75 X 40 G8.8  
WASHER LOCK M12  
SCREW HHC M10-1.5 X 35 G8.8  
WASHER LOCK M10  
NUT HEX M10-1.5 G8 YEL CHR  
PLUG PLASTIC 3/8 NPT  
FLEX CONDUIT 1" BLACK (NOT SHOWN)  
WASHER FLAT 3/8-M10 ZINC  
SPACER ROTOR SHAFT  
SCREW HHC M12-1.25 X 25 G8.8  
WASHER FLAT M12  
DECAL WARN ENG START  
WASHER SHAKEPROOF INT #8  
WASHER FLAT .34 ID X .75 OD  
DECAL, DANGER STANBY UNITS  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
26 *  
27  
28  
29  
30  
31  
32  
33  
35  
36  
* USED ON PRE-PACKAGED UNITS ONLY  
®
Generac Power Systems, Inc. 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Battery — Drawing No. 0E0770-A  
8
STARTER  
SOLENOID  
2
13  
4
14  
8
3
1
TO ENGINE  
BLOCK  
16  
5
6
7
9
15  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
4
5
6
7
8
9
13  
14  
15  
16  
17  
077483  
038804D  
038805B  
0742600131  
022131  
046526  
052213  
075763  
0D8668  
050331A  
050331  
0C2454  
025507  
027482  
1
1
1
1
1
1
1
3
1
1
1
2
1
2
BATT 12VDC 75-AH 26  
CABLE BATT RED #4 X 20.00  
CABLE BATT BLK #4 X 23.00  
ASSY,WIRE#16 RED 1.6  
WASHER FLAT 3/8 ZINC  
WASHER LOCK M10  
SCREW HHC M10-1.25 X 20 G8.8  
BOOT, BATTERY CABLE  
BRACKET, BATTERY HOLD DOWN 1.5  
BATTERY POST COVER (RED+)  
BATTERY POSTCOVER (BLACK-)  
SCREW TH-FRM M6-1X16 N WA Z/JS  
WASHER SHAKEPROOF EXT 7/16 STL  
WASHER SHAKEPROOF EXT 5/16 STL  
®
46 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 - Exploded Views and Parts  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
Muffler — Drawing No. 0E0773-A  
10  
9
14  
8
15  
6
12  
13  
9
3
7
3
5
4
3
2
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
3
0A4355  
0E2844  
036434  
036449  
0E0109  
0C1318  
0D8657  
0E0170  
0D9437  
060366  
039253  
022145  
022129  
045771  
0A8974  
027837  
1
1
3
3
1
1
1
1
1
2
4
4
4
4
1
2
MANIFOLD EXHAUST 1.5L  
NIPPLE TOE 1.5NPTX5.5 BLK IRON  
BOLT U 5/16-18 X 2.09  
SADDLE 2 INCH  
PIPE,EXHAUST 1.5L STNDRD&ACSTC  
FLEX PIPE EXHAUST  
SUPPORT, RADIATOR 1.5L MITSU  
BLANKET, EXHAUST 1.5L MITSU  
MUFFLER,1.5L ACOUSTIC&STANDARD  
STRAP MUFFLER 6" DIA  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
CAP RAIN 2"  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
SCREW RHM 1/4-20 X 2-1/4  
®
Generac Power Systems, Inc. 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT  
YOUR WARRANTY RIGHTS AND OBLIGATIONS  
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission  
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be  
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control  
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifi-  
cation or improper maintenance of your engine.  
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will  
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.  
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:  
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur-  
ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or  
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.  
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:  
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory  
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance  
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the  
completion of all scheduled maintenance.  
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or  
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap-  
proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.  
You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a prob-  
lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.  
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.  
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:  
1-800-333-1322  
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System  
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited  
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by  
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms  
between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the  
Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe impor-  
tant rights and obligations with respect to your new engine.  
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty serv-  
ice, evidence must be presented showing the date of the sale to the original purchaser/owner.  
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol-  
lowing address:  
ATTENTION WARRANTY DEPARTMENT  
GENERAC POWER SYSTEMS, INC.  
P.O. BOX 297  
WHITEWATER, WI 53190  
Part 1  
®
48 Generac Power Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
EMISSION CONTROL SYSTEM WARRANTY  
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:  
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on  
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con-  
tinue for 24 consecutive months thereafter.  
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or  
equipment and to each subsequent purchaser/owner that each of its engines is ...  
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its  
authority, and  
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-  
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine man-  
ufacturer’s application for certification.  
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:  
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall  
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the  
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual  
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or  
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS  
Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part  
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection  
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the  
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.  
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no  
charge to the owner at a Generac Authorized Warranty Service Facility.  
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-  
ble for diagnostic costs if the repair is deemed warrantable.  
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused  
by a failure under warranty of any emission-related part covered by the ECS Warranty.  
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient  
to meet the expected demand for such emission-related parts.  
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS  
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac  
ECS Warranty obligations.  
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac  
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.  
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of  
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.  
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:  
1) Fuel Metering System:  
3) Ignition System including:  
a) Spark plug  
b) Ignition module  
1.2) LPG/Natural Gas carburetion assembly and its internal  
components.  
a) Fuel controller (if so equipped)  
4) Catalytic Muffler Assembly (if so equipped) including:  
a) Muffler gasket  
b) Exhaust manifold  
b) Mixer and its gaskets (if so equipped)  
c) Carburetor and its gaskets (if so equipped)  
d) Primary gas regulator (if so equipped)  
e) LP liquid vaporizer (if so equipped)  
5) Crankcase Breather Assembly including:  
a) Breather connection tube  
2) Air Induction System including:  
a) Intake pipe/manifold  
b) Air cleaner  
*Generac engine types covered by this warranty statement include the following:  
1) Prepackaged Standby Generator  
2) Auxiliary Power Unit (APU) Generator  
3) Standby Generator  
Part 2  
®
Generac Power Systems, Inc. 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators  
GENERAC POWER SYSTEMS STANDARD "TWO YEAR" LIMITED WARRANTY FOR  
GUARDIAN® "PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"  
For a period of two years Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon  
examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under  
normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner  
claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All trans-  
portation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This  
warranty applies only to Generac Guardian prepackaged emergency automatic standby generators sold and rated for use in  
"Standby" applications.  
WARRANTY SCHEDULE  
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and  
maintenance is required):  
• Engine - All Components  
• Alternator - All Components  
• Transfer System - All Components  
All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate  
Manual.  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
• Generac Guardian generators that utilize non-Generac replacement parts.  
• Generac Guardian generators utilizing non-Generac/Guardian automatic transfer switches.  
• Any Generac Guardian generators used as rental or trailer mounted applications.  
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where  
utility power service does not normally exist.  
• Costs of normal maintenance, adjustments, installation and start-up.  
Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.  
Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with  
all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty  
will not cover repair when normal use has exhausted the life of a part(s) or engine.  
Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire,  
freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.  
• Damage related to rodent infestation.  
• Products that are modified or altered in a manner not authorized by Generac in writing.  
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or  
replacement of the defective part(s).  
Failure due to misapplication.  
Telephone, cellular phone, facsimile, internet access or other communication expenses.  
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit  
warranty period.  
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.  
• Rental equipment used while warranty repairs are being performed.  
• Overnight freight costs for replacement part(s).  
• Overtime labor.  
• Starting batteries, fuses, light bulbs and engine fluids.  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES  
NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not  
allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT  
SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A  
DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or conse-  
quential damages, so the above limitation may not apply to you.  
This warranty gives you specific legal rights. You also have other rights from state to state.  
GENERAC® POWER SYSTEMS, INC.  
P.O. BOX 297  
WHITEWATER, WI 53190  
Part No. 0E1151  
Revision J (06/28/04)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Everpure Plumbing Product EV9007 10 User Manual
Extron electronic Stereo System USP 507 User Manual
Fisher Price Camping Equipment R3931 User Manual
Fujitsu Network Card FPCAC14A User Manual
Fujitsu Scanner fi 4220C2 User Manual
GE Conference Phone 28115 Series User Manual
GE Cordless Telephone 26920R User Manual
Geemarc Telephone Jupiter 10 User Manual
Gianni Industries Door EM 10001LZ User Manual
Global Upholstery Co Patio Furniture 2050 3 User Manual