GE Zenith Controls
e
Entelli-Switch 250
Microprocessor Controller
Transfer Switch Control Panel
71R-2000
5/03
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation and Maintenance Manual
Safety / Installation
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
The safe operation of your switch is GE Zenith’s focus.
Final Equipment Inspection
The proper storage, installation, operation and mainte-
Prior to energizing the transfer switch:
1. Remove any debris incurred, with a vacuum, due
to shipment or installation.
nance will help increase the life of the switch.
CAUTION
Due to hazardous voltage and current, GE Zenith rec-
ommends that a GE Zenith Certified technician or a
qualified electrician must perform the
2. Verify that all cabled connections are
correct and that phase rotation of both sources
match.
3. Check engine start connections.
4. Verify the correct connection of all
control wires.
installation and maintenance of the switch.
5. Check settings of all timers and adjust
as necessary.
6. Adjust any optional accessories as required.
7. Check the lug torque values of the power
connections.
Equipment Inspection
and Storage
Once you have received the transfer switch, inspect
it for any damage. This includes damage to the
enclosure, power panel, control panel and wiring
harness. If any damage is found or suspected, file a claim
as soon as possible with the carrier and notify the nearest
GE Zenith representative.
NOTE:
Lug torque values are specified
in the power panel manual.
8. Make sure that all covers and barriers are
installed and properly fastened.
NOTE:
Power panels ship from GE Zenith
in Source 1 Position.
Before installation, if it is necessary, store the transfer
switch in a clean dry place, protected from dirt and
water. Provide ample air circulation and heat, if neces-
sary, to prevent condensation.
WARNING
Do not use a blower since debris may
become lodged in the electrical and
mechanical components and cause damage.
Operating
Storage
Temperature
Temperature (Ambient):
Humidity
-30°C to
5% to 95%
(non-con-
densing)
40-400 AMP
(molded shell)
+75°C
Each GE Zenith transfer switch is factory wired and
tested. A complete information package is furnished
with each switch which includes:
a. Sequence of operation.
(-22°F to
+167°F)
-20°C to +65°C
(-4°F to +149°F)
b. Description and operation of
all accessories supplied.
c. Power panel connection diagram
and schematic.
d. Description and identification of
all customer field connections.
40-4000 AMP
(all other frame
and panel types)
-20°C to +60°C
(-4°F to +140°F)
Installation of GE Zenith transfer switches includes:
a. Mounting the transfer switch cabinet.
b. Connection of Source 1, Source 2,
and Load cables or bus bars.
Table 1
c. Connection of external control
circuits as required.
■
■
GE Zenith Controls
3
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Initial Energization
4
5
6
1
Before proceeding, refer to the information package
supplied with the ATS and read and understand the
information on all accessories provided.
P Relay
(Engine Start)
2
E
Contact rating is
10 Ampere at 120VAC
or 28VDC Gold plated
1. Unlock the enclosure.
2. Open the enclosure.
3. Verify the correct system voltage.
3
Figure 1
NOTE:The equipment rating nameplate on
the transfer switch lists the voltage.
See Figure 3.
Engine Start
Control Connections
4. Close Source 1 circuit. breaker.
The engine-start terminals are clearly identified by a
label on the microcontroller backplate. In the case of
manual transfer switches, or in other applications not
requiring the microprocessor, clearly marked terminal
blocks are provided in the upper left corner of the con-
trol panel for the engine start control wires.
NOTE:The controller will illuminate Source 1
Available LED if proper voltage
is sensed.
5. Verify the phase to phase voltages at Source 1
line terminals.
6. Close Source 2 circuit breaker.
7. Start the generator’s engine.
Figure 2 shows location of engine start connections
for Bypass Isolation Transfer Switch. Figure 5 (pg.6)
shows location of engine start connections for
Automatic Transfer Switch.
NOTE:
The controller will illuminate Source 2
Available LED when preset voltage
and frequency levels are reached.
Terminals for field connections to the A3 Source 2
auxiliary contacts and the A4 Source 1 auxiliary contacts
are also provided. These terminals are clearly marked
and appear on the side of the power panel. On 400
amp metal frame units these terminals appear on
the bracket above the operator handle.
8. Verify the phase to phase voltages at Source 1
line terminals.
9. Verify that the phase rotation of Source 1
is the same as the phase rotation of
Source 2.
10. Shut down the generator’s engine.
11. Place the starting control in the Automatic position.
12. Complete the visual inspection of the transfer switch.
13. Close the enclosure.
14. Lock the enclosure.
g
GE Zenith Controls
SERIAL NUMBER:
RATING:
VOLTS -
AMPS -
HZ -
PHASE -
SYSTEM VOLTS:
MODEL NUMBER:
Figure 3
CAUTIONS
Certain accessories, per specific
schematics, can inhibit automatic transfer.
Engine Gen-Set could start when
engine control wires are attached.
Figure 2 (Typical)
■
■
4
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
(cont’d)
1. Unlock the enclosure.
Initial Energization (cont’d)
After all options and accessories are checked and
verified, follow these steps to set up the ATS. Refer to
Entelli-Switch 250 display Figure 4. The annunciation
LEDs illuminate to indicate (1) source availability,
(2) ATS position, and (3) Entelli-Switch 250 control
function (timing).
2. Open the enclosure.
3. Place the Disconnect Switch in the Inhibit.
NOTE:
This step is only performed if the
“DS” Option was purchased.
4. Close the external (up-stream) Source 1
circuit breaker.
NOTES: Source 1 Available and Source 1
Position LED’s will illuminate.
If Source 1 Available LED does not
illuminate, verify that Source 1 Voltage
is above the preset restore value.
The Gen-Set will start and run while
Source 2 stop DelayTimer is timing.
S 1 O K
21: 56
M O N 23 A P R 2002
5. Close the External (up-stream) Source 2 line
circuit breaker.
6. Start the engine generator in MANUAL mode.
M O RE
T E S T
NOTE:
When the voltage and frequency
reach preset values, the Source 2
Available LED will illuminate.
7. Verify the phase to phase voltages at Source 2
line terminals.
8. Verify that the phase rotation of
Source 2 is the same as the phase
rotation of Source 1.
9. Shut down the generator's engine.
(Place in Automatic Mode.)
NOTE:
Source 2 Available LED
will turn off.
Figure 4 – LCD and keypad
NOTE:
The engine generator will continue
to run for the duration of Source 2
Stop DelayTimer.
10. Place the disconnect switch to ENABLE.
11. Complete the visual inspection of the
transfer switch.
12. Close the enclosure.
13. Lock the enclosure.
WARNING
When performing a hi-pot or
dielectric test on the power section,
DISCONNECT the control panel plugs from
the microprocessor to avoid potential damage.
■
■
GE Zenith Controls
5
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Control Connections
Figure 5
Clock Program
Backup Battery
Remove protective
strip to enable clock
functions
Engine Start
Connections
Network Connector
Input/Output
Connectors
to I/O Modules
To R/T Box
To Power
Panel
A complete information package is furnished with
each transfer switch including a complete connection
diagram and schematic which details all necessary
control circuit field connections.
The terminals are clearly identified by a label on the
microcontroller backplate. In the case of manual trans-
fer switches, or in other applications not requiring the
microprocessor, clearly marked terminal blocks are
provided in the upper left corner of the control panel
for the engine start control wires.
The engine start control wires connect to the
engine start relay terminals located to the left
of the microprocessor. Figure 5 shows the location
of these terminals.
■
■
6
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Entelli-Switch 250 Controller
Entelli-Switch 250 Controller
Consists of two major assemblies:
Engine Start Relay P
I. The Microprocessor contains the following:
I/O Interface
Entelli-Switch 250
Board
A. Entelli-Switch 250 Board - Customer Input
and Output (I/O) for system interface. Located
on the left hand side of the back of the unit
(see figure 6)
1. I/O accessories that can be found here are:
a. Engine start relay P output
b. Pre-Signal to transfer T3, W3 and
UMD output (optional)
Battery Strip
and
Access
Code Label
c. Transfer Inhibit Q3 and Q7 input
(optional)
d. Remote test Q2 input (optional)
e. Network interface ZNET
input/output (optional)
B. LCD and Keypad located on the exterior
of the door (see figure 7)
1. User accessibility to the following:
a. LED indication of source
availability
b. LED indication of transfer
switch position
c. LCD screen indicates:
(1) timer count down (numeric)
(2) event reporting (text)
R/T Box
d. Keypad provides user interface to:
[in conjunction with LCD screen]
(1) Setting sensors and timers
(2) Configuring logic accessories
II. The R/T box (relay transformer box) contains
Figure 6
the following: (see figure 6)
A. Relays which are required for controller output
to energize the transferring mechanism of the
transfer switch at line voltage.
B. Transformers which drop line voltage
to control level for controller input.
S 1 O K
21: 56
M O N 23 A P R 2002
M O RE
T E S T
Figure 7
■
■
GE Zenith Controls
7
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Entelli-Switch 250 Controller
(cont’d)
LCD & Keypad
no changes can be made without entry of the access code.
The factory set six-digit access code is located on a white
label on the back of the unit (see figure 10 pgs. 17-19).
These options are accessible through the LCD and
keypad (see figure below). To become familiar with the
options loaded into a particular unit, scrolling through
the SET and CFG menu will show the descriptions of
the options (see pages 17-18). These menus are the very
same menus that are used to access the setting and/or
configuration of these options. The SET (setting) menu
is primarily used to show or change, time and voltage
settings. The CFG menu is primarily used to turn an
option on or off. When scrolling through these menus,
The Entelli-Switch 250 has many logic options. Each
controller is downloaded with options at the time of
manufacture. The collection of options that any one
controller has is specified at the time of order placement.
The following pages include all the options that can
reside in the controller. Not all units include all options.
Source 2 Position
LED (Red) indicates
Power Panel (ATS)
is closed to
Source 2 position
Source 1 LED (Green)
indicates Source 1 is
acceptable for use
Source 1 Position LED (Green)
indicates Power Panel (ATS)
is closed to Source 1 position
Source 2 (Red)
indicates Source 2
is acceptable for use
LCD Screen
Exercise Event
"Impending"
S1 OK
01: 50
FRI 31 MAY 2003
* E *
CurrentTime,
Day and
Date of Display
SET Menu
MORE CFG TEST SET
Keypad
Menus (MORE, CFG,TEST)
#4 or the word
on the LCD above the key.
The word above the key
changes depending on which
screen is being displayed.
#2 or the word
#3 or the word
#1 or the word
on the LCD above the key.
The word above the key
changes depending on which
screen is being displayed.
on the LCD above the key.
The word above the key
changes depending on which
screen is being displayed.
on the LCD above the key.
The word above the key
changes depending on which
screen is being displayed.
Figure 8
■
■
8
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
User Setting for Voltage & Frequency
Standard 3-Phase Sensing
on 3 and 4 Pole Units
Under Voltage "Fail"
Factory Default: 80%
Source 1
This adjustment determines the low voltage threshold.
Adjust via the SET menu. Range is 75% to 98% in 1%
increments (see page 18).
Under Voltage "Restore"
Factory Default: 90%
This adjustment determines the minimum acceptable
voltage required to transfer to Source 1.
Adjust via the SET menu. Range is 85% to 100% in
1% increments (see page 18).
"Fail" must be a minimum of 2 % below "Restore"
setting. Once voltage falls below threshold, T timer
will be bypassed to expedite the transfer to Source 1.
Once satisfied, the T timer will begin timing
to transfer to Source 1.
Over Voltage "Fail"
Factory Default: 110%
This adjustment determines the maximum acceptable
Over Voltage. Adjust via the SET menu. Range is 105%
to 110% in 1% increments (see page 18). Once exceed-
ed, the T timer will be bypassed to expedite the transfer
to Source 1.
Under Voltage "Fail"
Factory Default: 80%
This adjustment determines the low voltage threshold.
Adjust via the SET menu. Range is 75% to 98% in 1%
increments (see page 18).
"Fail" must be a minimum of 2 % below "Restore"
setting. Once voltage falls below threshold, P timer
begins timing to signal Source 2 Generator to start.
Over Voltage "Restore"
Factory Default: 105%
This adjustment determines the minimum acceptable
Over Voltage threshold at which the transfer switch is
allowed to transfer to Source 2. Adjust via the SET
menu. Range is 103% to 105% in 1% increments
(see page 18). “Restore” must be a minimum of
2% below “Fail” setting.
Under Frequency "Restore"
Factory Default: 95%
This adjustment determines the minimum acceptable
frequency required to transfer to Source 1.
Adjust via the SET menu. Range is 90% to 100% in
1% increments (see page 18).
Once satisfied, the T timer will begin timing
to transfer to Source 1.
Under Frequency "Restore"
Factory Default: 95%
Under Frequency "Fail"
Factory Default: 90%
This adjustment determines the minimum acceptable
frequency required to transfer to Source 2.
Adjust via the SET menu. Range is 90% to 100% in
1% increments (see page 18).
Once satisfied, the W timer will begin timing
to transfer to Source 2.
This adjustment determines the low frequency threshold.
Adjust via the SET menu. Range is 88% to 98% in 1%
increments (see page 18).
"Fail" must be a minimum of 2 % below "Restore"
setting. Once satisfied, the T timer will begin timing to
transfer to Source 1.
Under Frequency "Fail"
Over Frequency "Restore"
Factory Default: 90%
Factory Default: 102%
This adjustment determines the low frequency threshold.
Adjust via the SET menu. Range is 88% to 98% in
1% increments (see page 18).
"Fail" must be a minimum of 2 % below "Restore" setting.
Once satisfied, the W timer will begin timing to transfer
to Source 2.
This adjustment determines the minimum acceptable
Over Frequency threshold at which the transfer switch
is allowed to re-transfer to Source 1.
Adjust via the SET menu. Range is 102% to 104% in
1% increments (see page 18). “Restore” must be a
minimum of 1% below “Fail” setting.
Over Frequency "Fail"
Over Frequency "Fail"
Factory Default: 105%
Factory Default: 105%
This adjustment determines the maximum acceptable
Over Frequency.
Adjust via the SET menu. Range is 103% to 105% in 1%
increments (see page 18).Once exceeded, the P timer
begins timing to signal the generator to start.
This adjustment determines the maximum acceptable
Over Frequency. Adjust via the SET menu. Range is
103% to 105% in 1% increments (see page 18). Once
exceeded, the T timer will be bypassed to expedite the
transfer to Source 1.
Source 2
Over Frequency "Restore"
Factory Default: 102%
Under Voltage "Restore"
Factory Default: 90%
This adjustment determines the minimum acceptable
Over Frequency threshold at which the transfer switch is
allowed to re-transfer to Source 2. Adjust via the SET
menu. Range is 102% to 104% in 1% increments
(see page 18). “Restore” must be a minimum of
1% below “Fail” setting.
This adjustment determines the minimum acceptable
voltage required to transfer to Source 2.
Adjust via the SET menu. Range is 85% to 100% in
1% increments (see page 18).
Once satisfied, the W timer will begin timing
to transfer to Source 2.
■
■
GE Zenith Controls
9
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory Group Packages
Table 2
Group Packages
Accessories
STDS
EXES
CONS
SENS
SPES
PSGS
6P
A1
A1E
A3
2
2
2
2
2
2
2
2
3
3
A4
Calibrate
CDT
CDP
**DS
*DT
*DW
E
EL/P
K/P
L1
L2
L3
L4
*LN
P1
Q2
Q3
Q7
R1-1
R1-3
R15
*R15D
R16
R50
S5P
S12P
S13P
T
2
2
2
2
2
2
2
2
2
2
2
2
T3/W3
U
UMD
VI
W
YEN
Standard Accessory included in the group package.
Optional Accessory not included but can be added to group package.
Optional Accessory. Can not be used with accessory having the same symbol.
N/A
Denotes an Accessory with 2 circuits as a standard.
Denotes an Accessory with 3 circuits as a standard.
2
2
3
Delayed Transition Units Only.
Optional for 40-400 Amp
*
**
■
■
10
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory Definitions
6P
CDT
Test Switch, Momentary
Load or NO-Load. One event exerciser with adjustable
Engine exercise timer. Exercise duration can be set
between 5 and 60 minutes in 1 minute increments. Can
be configured to run every 1, 7, 14, or 28 days. Factory
Default is 20minutes. When exerciser is impending,
(*E*) appears in the upper right hand corner of LCD
screen. See page 15 for instructions. Configured via
CFG (see page 17). Set via SET menu (see page 18).
6A
Test Switch, Maintained Auto/Momentary Test
6AP
Test Switch, Maintained/Momentary utilizing keypad
6B
Test Switch, Maintained - Auto / Momentary - Test,
Key Operated
CTAP
Alarm Panel on transfer to Source 2 with Silence button.
6C
DS
Test Switch, Maintained - Auto / Maintained - Test,
Key Operated
Disconnect Switch, Auto/Inhibit.
Inhibits transfer in either direction when in inhibit.
Allows automatic operation when in Auto.
(40-400 Amps optional, 600-4000 Amps standard)
A1
Auxiliary Contact, operates on Source 1 line failure.
DT (DelayedTransition Only)
A1E
Time Delay from Neutral Switch position to Source 1
position. Adjustable 0-10 minutes in 1 second incre-
ments. Standard setting is 5 seconds Adjust via SET
menu (see page 18)
Auxiliary Contact, operates on Source 2 line failure.
A3
Auxiliary Contact: Closed in emergency (Source 2)
Additional Available (10 max.) and need to be specified.
DW (DelayedTransition Only)
Time Delay from Neutral Switch position to Source 2
position. Adjustable 0-10 minutes in 1 second incre-
ments. Standard setting is 5 seconds.Adjust via SET
menu (see page 18)
A4
Auxiliary Contact: Closed in normal (Source 1)
Additional Available (10 max.) and need to be specified.
A62
E
Sequential Universal Motor Load Disconnect Circuit.
Normally closed auxiliary contacts for motor loads.
Open 0-60 seconds prior to transfer, after transfer,
or both in either direction then re-close in timed
sequence after transfer.
Engine Start Contact
EL/P
Event Log: Sequentially Numbered Log
of 16 events that track
date, time, reason and action taken
System Data: Total Life Transfers (N2P)
Days Powered Up
AB3
Auxiliary Contact: Closed in bypass emergency
(Source 2) (S.P.D.T.) (Standard up to 400 Amp)
Additional Available (10 max.) and need to be specified.
Total Transfers to S2
Total S1 Failures
Time S1 available in Hrs
Time S2 available in Hrs. (N1P)
AB4
Auxiliary Contact: Closed in bypass normal (Source 1)
(S.P.D.T.) (Standard up to 400 Amp) Additional
Available (10 max.) and need to be specified.
F
Fan contact, operates when generator is running.
B9
HT
Battery charger connections.
Heater and Thermostat
Calibrate
K
While monitoring the actual Phase to Phase voltage lev-
els and Frequency with a calibrated test equipment, the
Phase to Phase voltage sensing and Frequency can be
adjusted accordingly. Calibration capabilities are available
for Frequency and AB, BC, CA Phase to Phase voltage for
both Sources. Adjust via SET menu (see page 18)
Frequency Meter, Door mount.
K/P
Frequency Indication for S1 and S2
L
LNP Center-off position LCD-Indicator
Indicating LED lights:
CDP
Clock Exerciser Load/ No Load: Allows the Generator
to start and run unloaded or to simulate a power
failure, start Generator and run under load.
Can be configured by end user for 1, 7, 14,
28, 365 day cycle. (See page 16)
L1 Indicates Switch in Source 2 position.
L2 Indicates Switch in Source 1 position.
L3 Indicates Source 1 available.
L4 Indicates Source 2 available.
■
■
GE Zenith Controls
11
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory Definitions
(cont’d)
Q7
M1
Inhibit transfer to Source 1 circuit. Energize Q7 input
to prevent transfer to Source 1.
Single Phase Amp Meter
M2
R1-1/R1-3
Three Phase Amp Meter
Source 1 Over Voltage sensing for single
and three phase systems.
M80
Source 1 Over Voltage "Fail"
Factory Default: 110%
3000 Digital Power Monitor
This adjustment determines the maximum acceptable
over voltage. Adjust via the SET menu. Range is 105%
to 110% in 1% increments (see page 18).
Once exceeded, the P timer begins timing to signal
the Generator to start.
M82
5200 Digital Power Meter
M83A
EPM 5300 Digital Power Meter with Modbus Port
Source 1 Over Voltage "Restore"
M83B
Factory Default: 105%
EPM 5350 Digital Power Meter with Ethernet Port
This adjustment determines the minimum acceptable
over Voltage threshold at which the Transfer Switch is
allowed to automatically transfer to Source 1. Adjust via
SET menu. Range is 103% to 108% in 1% increments.
"Restore" must be a minimum of 2% below "Fail" setting
(see page 18).
M84
7430 Digital Power Meter , Wye or Delta
M85A
EPM 9450 Digital Power Meter, Ethernet
R15/R15D
Should Source 2 become overloaded, a signal
can be given to switch to the dead or Mid position.
M85B
Load Shed
EPM 9450 Digital Power Meter with Internal 56K Mod.
M86A
EPM 9650 Digital Power Meter, Wye or Delta,
RS232 or RS485
R16
Phase Rotation Sensing
Can be turned on or off via CFG menu (see page 17).
Factory Default is on.
M86B
EPM 9650 Digital Power Meter, Wye or Delta,
RS232 or RS485
This feature prevents Line Source to Line Source trans-
fers from occurring between dissimilar phase sequences.
This condition is primarily caused by an installation
error. Connections from Source 1 and Source 2 need
be verified, compared, and corrected to remedy the
inconsistent phase rotation between the sources.
WARNING: Turning off this feature can cause
severe damage to loads.
N1
Running Time Meter, Door mount
N2
Operation Counter, Door Mount
P1
R26
Time Delay Source 2 Start. Adjustable 0-10 seconds.
Standard setting is 3 seconds.
Adjust via SET menu (see page 18)
Interruptable Power Rate Provisions.
Allow transfer out of Source 1 position to Source 2 or
dead Source 2. Alarm and Pre-Signal circuit included.
P2
R50
Time Delay S2 Start. Adjustable 1/6 to 300 seconds.
In Phase Monitor this feature restricts Live to Live
Source Transfers to occur unless both Sources are within
7 electrical degrees or less of each other. (live Source to
live Source transfers usually occur during transfer back
to Source 1 or during Testing). R50 does not change
the operation of the Automatic Transfer Switch in a
power failure mode. After all timer functions have
elapsed, the CHECKING FOR SOURCE SYNCHRO-
NISM will be displayed as well as the direction of
transfer (S1-S2 for example denotes transfer from
Source 1 to Source2). When synchronism is accomplished,
transfer will take place.
Q2
Remote Peak Shave or Area Protection Circuit.
Energize Q2 to simulate Source 1 Line failure causing
the Generator to start and transfer the load to Source 2.
Should Emergency fail during this operation, Transfer
Switch will retransfer back to Source 1.
Q3
Remote inhibit transfer to Source 2 circuit. Energize
Q3 input to allow transfer to Source 2. To enable Q3
option, engage Q3 jumper.
■
■
12
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory Definitions
(cont’d)
Notes: - If S2 Frequency is less than S1 Frequency,
S13P
display will show a series of (- - - - -…..) symbols.
- If S2 Frequency is greater than S1 Frequency,
display will show a series of (+++++…..) symbols.
- Each (-) or (+) symbol represents 10 electrical
degrees out of phase. A maximum of 18 symbols
(180 electrical degrees) can be monitored.
- The number of (-) or (+) symbols decrease
as the two sources approach synchronism
and increase as the two sources drift out
of synchronism.
Transfer Commit. Configured via CFG menu.
(see page 17) When this Feature is set to OFF:
The transfer Switch is not committed to transfer unless
the outage duration is longer than the timers that
precede the transfer to Source 2 position. This assumes
that the outage will be an isolated event. When this
Feature is set to ON: The transfer Switch is committed
to transfer to Source 2 position once the W timer has
begun timing, even if Source 1 power returns before
the transfer to Source 2. This is to ensure that the
transfer takes place, because one outage may be
followed by another.
- If S1 and S2 Frequencies are identical, the
display will show a series of alternating
- - - -
symbols (++++…) which also indicate the
S14
approximate out of phase degrees
Test / Auto / Source 1 Selector, Door mount
In the event that the Sources do not come within 7
electrical degrees of each other within 60 seconds, the
unit will display the message: SYNCH CHECKING and
will allow the user to BYPASS. If the BYPASS button is
pressed, the unit will display the message: WARNING
MAY CAUSE DAMAGE TO THE LOAD. Pressing XFR
will actually bypass the R50. Since R50 is a passive device,
the length of time it takes to reach Synchronism is de-
pendent on the frequency difference between the two
Sources. Source 1 is usually a Utility and the frequency
is not within the control of the consumer. Source 2
needs to be adjusted to create an adequate difference
in order for the transfer to happen a timely fashion.
SW1
Auto/Off/Start Engine control selector, Door mount
(Keyed or non-keyed operation available)
SW2
Auto / Off Engine control selector, Door mount
(Keyed or non-keyed operation available)
SW3
Source Priority Selector Switch, Door mount
Allows selection of Source 1 or Source 2 to be the Prime
Source. Transfer Switch will transfer to selected Prime
Source if that Source is available. (Keyed or non-keyed
operation available)
Note: For optimum performance, Source 2
Generator should be adjusted a Maximum of
2 Hertz above or below the Utility frequency,
minimum of 0.1 Hertz. (58 to 59.9) or
T
Time Delay (S1) Source 1 Stable Timer. To delay trans-
fer to Source 1 (immediate retransfer on Source 2 fail-
ure). Adjustable 0-60 minutes in 1 second increments.
Standard setting is 30 minutes. Adjust via SET menu
(see page 18)
(60.1 to 62) Hertz. Adjustment of Generator
to 60Hertz could cause lengthy transfer delay.
R50 Feature can be turned ON or OFF via CFG Menu
(see page 17). Factory Default if OFF.
S5P
T3/W3
Auto / Semi Manual selector
Elevator Pre-Signal Auxiliary Contacts: Open 0-60
seconds prior to transfer to either direction,
re-closes after transfer.
In "Auto" position, retransfer to Source 1 is automatic
after the T timer has timed out. The T time delay is
bypassed if Source 2 fails.
In "Manual", retransfer to Source 1 is upon depression
of BYPASS DELAY button YEN or if Source 2 fails.
U
(S2) Source 2 Stop Delay Timer. Allows Engine to run
unloaded after switch retransfer to Source 1. Adjustable
0-60 minutes in 1 second increments. Standard setting is
5 minutes. Adjust via SET menu (see page 18)
S12P
Auto / Manual Selector
In "Auto" position, the Automatic Transfer Switch
functions automatically as specified with the Switch
drawings.
In "Manual" the Automatic Transfer Switch will transfer
to either direction upon depression of Source 1 or
Source 2 transfer buttons.
UMD
Universal Motor Load Disconnect Circuit: Auxiliary
Contact opens 0-60 seconds prior to transfer in either
direction, re-closes after transfer. Can be configured by
end user for Pre-transfer, Post-transfer, or both.
Should Source 1 fail, the Generator (Source 2), will
automatically start. Once transferred in Manual, the
Switch maintains position selected even if selected
power fails.
■
■
GE Zenith Controls
13
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessory Definitions
(cont’d)
VI
W
Voltage Imbalance (Three Phase)
Time Delay (S2) Source 2 Stable Timer. To delay trans-
fer to Source 2. Adjustable 0-5 minutes in 1 second
increments. Standard setting is 1 second. Adjust via SET
menu (see page 18)
For a three phase source, this feature monitors phase
voltage ratios based on a selected range within a
selected time window. Should any phase fall below the
selected lower window limit or exceed the selected
higher window limit within the selected time frame,
the controller initiates transfer to the other source.
YEN
Bypass Timers Key utilizing Keypad. When applicable,
the system prompts the user to press a button to bypass
(T) or (W) Timers should the user so desires.
Range: 5% to 20% of Nominal voltage,
10 to 30 seconds window, user adjustable.
Resolution: 1% Increments
Minimum Differential: 2% between “Fail”
and “Restore” settings.
ZNET
Network Communications Interface Card
Factory default: 10% “Fail”, 8% “Restore”, 30 Seconds.
See CFG Menu page 17 to configure ON or OFF.
See SET Menu page 18 to set Percentage and time
windows
How to Set the System Clock
How to Set the System Clock
Set System Clock, time and date
12. Press SAVE (This will enter this value and complete
the clock setting).
13. Use the up and down keys to change the date.
14. Press SAVE (this will enter this value and move
cursor to year).
15. Use the up and down keys to change year.
16. Press SAVE (this will enter this value and
compete the clock setting).
·
If the clock is not set, the display will show
SET SYSTEM CLOCK on the second line
of the S1 OK screen.
·
The S1 OK screen will show time (hours and
minutes) on the second line if the system clock
has been set. (Date on third line)
Setting the System Clock
(Start from S1 OK screen)
1. Remove battery protective white plastic strip
near P relay. *
17. To edit settings, press SEL and repeat steps 6-16.
18. If the setting is satisfactory, press MORE
(unit then returns to the SET menu then
press BACK, then ESC.)
2. Press MORE then press SET.
3. Press MORE and scroll to SET SYSTEM CLOCK
using the MORE key.
*
Replacement battery part #K-4100
Battery will last 5 years and provides power to retain clock
function only (Controller functions without battery).
4. Press SEL.
5. ENTER ACCESS CODE located on the white label
on the back of the controller.
6. Press SEL.
7. Use the up and down keys to change the hour value.
8. Press SAVE (this will enter this value and move
cursor to minutes).
9. Use the up and down keys to change the minutes.
10. Press SAVE (this will enter this value and move
cursor to month).
11. Use the up and down key up to change the month.
■
■
14
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
CDT One EventTimer Exerciser
•
If the CDT Exerciser is Factory configured for a
Load Exerciser, the Controller will immediately start
a load exercise. The controller will start the
generator, transfer the load to Source 2 and remain
in Source 2 for the duration set for EXER S2 RUN
TIME in the SET menu. The controller will
Load or No-Load
One event Exerciser with adjustable Timer. Exercise
duration can be set between 5 and 60 minutes in
1 minute increments. Can be configured to run every
1,7,14, or 28 days. Factory default is 20 minutes.
retransfer the load back to Source 1 after the S1
stable timer has timed out and run the generator
unloaded for the duration of the S2 stop delay timer
(Engine Cool Down Timer).
If the CDT Exerciser is Factory configured for a
No-Load Exerciser, the Controller will immediately
start a No-load exercise. The controller will start the
generator and run it unloaded for the duration of
the S2 stop delay timer (Engine Cool Down Timer).
How to CONFIGURE (CFG) and Set (SET)
the Timer Exerciser
1. Beginning from the S1 OK screen,
press MORE then CFG.
2. Press MORE to scroll to CONFIG TIMER
EXERCISER screen.
3. The third line of the CONFG TIMER EXERCISER
will show either DAILY, WEEKLY, 14 DAY, 28 DAY,
or OFF.
•
Exercise will be repeated at the same time as initiated
on every 1, 7, 14, or 28 days according to the selection
made in the Configure CFG menu.
4. If the third line of the CONFG TIMER EXERCISER
shows DAILY, WEEKLY, 14 DAY, or 28 DAY as
desired, then proceed to step 10.
5. If the third line of the CONFG TIMER EXERCISER
shows OFF or if another timer selection is desired,
continue.
How to Bypass (Cancel) an exercise during
an exercise cycle
1) Press BPASS
6. Press SEL.
2) Allow the controller to complete the Engine
cool down cycle
7. Enter ACCESS code located on white label
on the back of the controller.
If the CDT Exerciser is Factory configured for a
No-Load Exerciser Or allow the controller to complete
retransfer to Source 1 If the CDT Exerciser is Factory
configured for a Load Exerciser
8. Press UP or DOWN to select DAILY, WEEKLY,
14 DAY, or 28 DAY as desired.
9. Press SAVE.
10. Press MORE to scroll to CONFG TIMER
EXERCISER (XFR) or (NO XFR).
11. Press Up or Down to select XFR (Load Transfer)
or NO XFR (No Load Transfer).
How to Bypass the next exercise event and Keep
the rest of scheduled events unchanged
1) Press Test
12. Press SAVE.
2) Press MORE
13. Press MORE repeatedly to BACK then S1 OK screen.
3) Press BYPASS EXER
To re-institute the next exercise event back,
press CANCL BPASS
Set (SET) the Exerciser:
14. Beginning from the S1 OK screen,
press MORE then SET.
How to initiate a new exercise start time
1) Press TEST
15. Press MORE repeatedly until
EXER S2 RUN TIME screen.
2) Press MORE
16. Press SEL
3) Press EXER CANCL
4) Press START TIMER TEST
17. Enter ACCESS code located on white label
on the back of the controller.
18. Press SEL
How to check the next exercise event
1) From S1 OK screen, press MORE three times.
2) The unit will display the PLANT EXERCISER NEXT
event in DAYS, HOURS, and MINUTES
3) Press ESC to S1 OK Screen.
19. Cursor is indicated as a line under character to
be changed. Change values with up and down keys.
20. Press SAVE when complete.
21. Press MORE repeatedly until SET USER SETUP
then press BACK then ESC to the S1 OK screen.
Notes:
-
How to Initiate CDT Exerciser and to start an
exercise cycle every 1, 7, 14, or 28 days
From S1 screen
*E* appears in the upper right hand corner
of LCD screen when exercise is impending.
For Load Exerciser, actual exercise period
(ATS in S2 position)= CDT (Exerciser)
-
1) Press TEST
2) Press MORE
timing period +T (S1 stable Timer) timing period.
3) Press START TEST TIMER (to initiate Test).
■
■
GE Zenith Controls
15
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
CDP Clock Exerciser
6. Cursor is indicated as a line under character to
be changed. Change values with up and down keys.
Press SAVE after each entry to save value and to
move to the next value to be changed.
Load / No-Load Clock Exerciser
Allows the Generator to start and run unloaded or to
simulate a power failure, start Generator and run under
load. Can be configured by the end user for 1, 7, 14, 28,
or 365 day cycles.
7. Press BACK when complete.
8. Press MORE repeatedly until SET USER SETUP.
Press BACK then ESC to the S1 OK screen.
•
A total of 7 independent No Load exercise periods
(up to 10 hours each) can be programmed for each
of the daily, weekly, 14-day, and 28-day exercisers.
A total of 12 independent No Load exercise periods
(up to 10 hours) can be programmed for the
365-day Exerciser.
How to Bypass (Cancel) an exercise during
an exercise cycle
1) Press BPASS
•
2) Allow the controller to complete the Engine
cool down cycle.
If the CD Exerciser is configured or Set for a No-Load
Exercise. Or allow the controller to complete retransfer
to Source 1. If the CD Exerciser is configured for a
Load Exerciser
How to Configure (CFG) the Exerciser
1. Beginning from the S1 OK screen, press MORE
then CFG.
2. Press MORE to scroll to CONFIG CLOCK
EXERCISER screen.
3. The third line of the CONFG CLOCK EXERCISER
will show either DAILY, WEEKLY, 14 DAY, 28 DAY,
365 DAY or OFF.
4. If the third line of the CONFG CLOCK EXERCISER
shows DAILY, WEEKLY, 14 DAY, 28 DAY, or 365 DAY
as desired, press MORE repeatedly to BACK.
Press ESC then proceed to the SET menu to
set the EXERCISER.
How to Bypass the next exercise event and Keep
the rest of scheduled events unchanged
1) Press TEST
2) Press MORE
3) Press BYPASS EXER
To re-institute the next exercise event back,
press CANCL BPASS
5. If the third line of the CONFG CLOCK EXERCISER
shows OFF, continue.
6. Press SEL.
7. Enter ACCESS code located on white label on
the back of the controller.
8. Press UP or DOWN to select DAILY, WEEKLY,
14 DAY, 28 DAY, or 365 DAY as desired.
9. Press SAVE.
How to check the next exercise event
1) From S1 OK screen, press MORE three times.
2) The unit will display the PLANT EXERCISER NEXT
event in DAYS, HOURS, and MINUTES
3) Press ESC to S1 OK Screen.
Notes:
•
•
•
•
In the S1 OK screen, an (*E*) appears in the upper
right hand corner of LCD screen when exercise
is impending.
For Load Exerciser, actual exercise period
(ATS in S2 position)= CDT (Exerciser)
timing period +T (S1 Stable Timer) timing period.
A value greater than zero must be entered in the
Exerciser duration field to be accepted as a valid
exercise period.
The Exercise cycle will be repeated on a regular
basis as programmed and initiated in the SET menu
depending on what Exerciser was configured
(selected) in the CFG menu.
10. Press MORE repeatedly to BACK then ESC
to S1 OK screen.
How to set (SET) the DAILY Exerciser
1. Beginning from the S1 OK screen, press MORE
then SET.
2. Press MORE repeatedly until SET EXERCISER
screen.
3. Press SEL.
4. Enter ACCESS code located on white label
on the back of the controller.
5. Press SEL
Cursor
Indicates # of
Exercise Periods
Load No-Load (CDP)
Exercise Indicator
#1
SET
NL
Indicates type of Exerciser
DAILY, WEEKLY, 14-DAY,
28-DAY or 365-DAY
EXERCISER
00:00
SAVE
Exercise duration for this
event in hours and minutes
up to 10 hours per event
v
BACK
^
Indicates Exerciser start:
Time for DAILY Exerciser
Time & Day for WEEKLY Exerciser
Time, Date & Month for 14-DAY,
28-DAY and 365-DAY Exerciser
(24 Hour System)
Up and Down
Use to change values.
To save value and to
move cursor to next
field to be changed.
To previous field
or to exit screen.
Figure 9
■
■
16
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Entelli-Switch 250 User Setup - CFG Menu
S1 OK
01: 50
FRI 31 MAY 2003
Turn options ON or OFF via
keypad through the CFG menu
MORE
TEST
Enter six digit access code
(The factory assigned six-digit access code
is located on the back of the controller)
1 VAB = ___
VBC = ___
VCA = ___
2 VAB = ___
VBC = ___
VCA = ___
MORE
MORE
CFG
SET
ESC
WARNING
1
Controller inputs must be relay isolated.
Customer
Input
Voltage
Network Communications
(Option)
CONFIG
USER SETUP
{
*
J2
1
PROG 1
J2-3
N.O.
To J2/J4 Input
N.C.
BACK
2
3
PROG 2
GRD (Input Sink)
LS OUT
4
2
Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
5
NIA OUT
6
5
6
7
ELEV. PRE. OUT
ALARM OUT
STE OUT
11
12
13
Output Contacts
1
2
From J2/J4
Output
7
{
{
R1
R2
8
—TIMER EXERCISER (CDT)
1, 7, 14, 28 Day (pg. 11 & 15)
8
9
10
14
15
16
3
4
Output Contacts
9
J4-3
10
11
12
13
14
15
16
MOTOR DISC. OUT
—CLOCK EXERCISER
LOAD OR NO LOAD (CDP)
1, 7, 14, 28, 365 Day (pg. 11 & 16)
TMS IN
11
12
13
5
6
7
INHIB. > S1
INHIB. > S2
LS IN
R1
Output
R1
Output
—TEST KEY (6)
Maintained/Momentary (pg. 11)
14
15
16
8
9
*
Input and output availability
subject to factory configuration.
R2
Output
R2
Output
*
J4
—TRANSFER COMMIT (S13)
ON/OFF (pg. 13)
10
1
2
Contact Rating: 10A @ 277VAC or 30VDC
3
+12V (Output Source)
LN OUT
L4 OUT
4
—AUTO / MANUAL (S5 or S12)
ON/OFF (pg. 13)
Lithium Battery
User Access Code
Exerciser Battery
5
Replacement - K-4100 (BR2032)
6
Service Life - 10 Years+
L3 OUT
7
+ During normal operation
L2 OUT
—IN-PHASE MONITOR (R50)
ON/OFF (pg. 13)
8
L1 OUT
Default - 121212
9
YN IN
10
11
12
13
14
YE IN
TSNL IN
Q2/TSL IN
S12 IN
—S1 OVER VOLTAGE (R1-1 or R1-3)
ON/OFF (pg. 12)
24-Hour Service
(773) 299-6600
S5 IN
—S1 UNDER FREQUENCY
ON/OFF (pg. 9)
TM
Entelli-Switch 250
—S2 OVER VOLTAGE
ON/OFF (pg. 9)
Figure 10
—S2 OVER FREQUENCY
ON/OFF (pg. 9)
—PHASE IMBALANCE (VI)
ON/OFF (pg. 14)
—PHASE ROTATION MATCH (R16)
ON/OFF (pg.12)
—LOAD DISCONNECT TD (UMD)
(pg.13)
—TRANSFER ALARM (CTAP)
ON/OFF (pg.11)
—NETWORK (ZNET)
ON/OFF (pg. 14)
Optional Accessories
■
■
GE Zenith Controls
17
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Entelli-Switch 250 User Setup - SET Menu
S1 OK
01: 50
FRI 31 MAY 2003
Change adjustable values
through the SET menu.
MORE
TEST
Enter six digit access code
(The factory assigned six-digit access code
is located on the back of the controller)
1 VAB = ___
VBC = ___
VCA = ___
2 VAB = ___
VBC = ___
VCA = ___
MORE
MORE
CFG
SET
ESC
WARNING
1
Controller inputs must be relay isolated.
Customer
Input
Voltage
Network Communications
(Option)
{
SET
USER SETUP
*
J2
1
PROG 1
J2-3
N.O.
To J2/J4 Input
N.C.
2
3
PROG 2
BACK
GRD (Input Sink)
LS OUT
4
2
Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
5
NIA OUT
6
5
6
7
ELEV. PRE. OUT
ALARM OUT
STE OUT
11
12
13
Output Contacts
1
2
From J2/J4
Output
7
{
{
R1
R2
8
8
9
10
14
15
16
Output Contacts
3
4
9
—SET SYSTEM CLOCK (pg.14)
—DAYLIGHT SAVINGS ON/OFF
J4-3
10
11
12
13
14
15
16
MOTOR DISC. OUT
TMS IN
11
12
13
5
6
7
INHIB. > S1
INHIB. > S2
LS IN
R1
Output
R1
Output
—CLOCK EXERCISER (CDP)
(pg.11 & 16)
14
15
16
8
9
*
Input and output availability
subject to factory configuration.
R2
Output
R2
Output
—EXER S2 RUNTIME (CDT)
(pg.11 & 15)
*
J4
10
1
2
Contact Rating: 10A @ 277VAC or 30VDC
3
+12V (Output Source)
LN OUT
L4 OUT
—S1 UNDER VOLTAGE (pg.9)
4
Lithium Battery
User Access Code
Exerciser Battery
5
Fail
Restore
Replacement - K-4100 (BR2032)
6
Service Life - 10 Years+
L3 OUT
7
+ During normal operation
L2 OUT
8
L1 OUT
Default - 121212
9
YN IN
—S1 UNDER FREQUENCY (pg.9)
10
11
12
13
14
YE IN
Fail
Restore
TSNL IN
Q2/TSL IN
S12 IN
24-Hour Service
(773) 299-6600
S5 IN
—S1 OVER VOLTAGE (pg.12)
TM
Entelli-Switch 250
Fail
Restore
Figure 10
—S1 OVER FREQUENCY (pg.9)
—TIME DELAY S2 START (P1)
(pg.12)
Fail
Restore
—TIME DELAY S2 STABLE (W)
(pg.14)
—S2 UNDER VOLTAGE (pg.9)
Fail
Restore
—LOAD PRESIGNAL TD (T3/W3)
(pg.13)
—S2 UNDER FREQUENCY (pg.9)
Fail
Restore
—LOAD DISCONNECT TD (UMD)
(pg.13)
—S2 OVER VOLTAGE (pg.9)
—ATS OPEN TIME TO S2 (DW)
DELAY units only (pg.11)
Fail
Restore
—TIME DELAY S1 STABLE (T) (pg.13)
—S2 OVER FREQUENCY (pg.9)
Fail
Restore
—ATS OPEN TIME TO S1 (DT)
DELAY units only (pg.11)
—SET % PHASE IMBALANCE (VI)
FAIL 5%, RESTORE 3% (pg.14)
—S2 STOP DELAY (U) (pg.13)
—CALIBRATE S1 (pg.11)
—CALIBRATE S2 (pg.11)
—SET PHASE IMBALANCE (VI)
TIME DELAY 30 seconds (pg.14)
Optional Accessories
■
■
18
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Entelli-Switch 250 User Setup - System Info
View System Data
S1 OK
01: 50
FRI 31 MAY 2003
Enter six digit access code
(The factory assigned six-digit access code
is located on the back of the controller)
MORE
TEST
WARNING
1
Controller inputs must be relay isolated.
—PHASE TO PHASE VOLTAGE, S1 & S2
Customer
Input
Voltage
Network Communications
(Option)
{
—FREQUENCY INDICATION FOR S1 & S2
(K/P) (pg.11)
*
J2
1
PROG 1
J2-3
N.O.
To J2/J4 Input
N.C.
2
3
PROG 2
—PLANT EXERCISER:
Next Impending Exerciser
(shows only if set)
GRD (Input Sink)
LS OUT
4
2
Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
5
NIA OUT
6
5
6
7
ELEV. PRE. OUT
ALARM OUT
STE OUT
11
12
13
Output Contacts
1
2
From J2/J4
Output
7
{
{
R1
R2
8
8
9
10
14
15
16
3
4
Output Contacts
9
—SYSTEM INFO:
J4-3
10
11
12
13
14
15
16
MOTOR DISC. OUT
Serial #: Unit Serial #
Rev #:
Software Revision #
TMS IN
11
12
13
5
6
7
INHIB. > S1
INHIB. > S2
LS IN
Event Log: Sequentially Numbered Log
R1
R1
Output
of 16 events that track
Output
date, time, reason and action taken
Data:
Total Life Transfers (N2P)
14
15
16
8
9
*
Input and output availability
subject to factory configuration.
Days Powered Up
R2
Output
R2
Output
*
J4
Total Transfers to S2
Total S1 Failures
Time S1 available in Hrs
Time S2 available in Hrs. (N1P)
10
1
2
Contact Rating: 10A @ 277VAC or 30VDC
3
+12V (Output Source)
LN OUT
L4 OUT
4
Lithium Battery
User Access Code
Exerciser Battery
5
Replacement - K-4100 (BR2032)
6
Service Life - 10 Years+
L3 OUT
—CHANGE USER ACCESS CODE
7
+ During normal operation
L2 OUT
8
L1 OUT
Default - 121212
9
YN IN
10
11
12
13
14
YE IN
TSNL IN
Q2/TSL IN
S12 IN
24-Hour Service
(773) 299-6600
S5 IN
TM
Entelli-Switch 250
Figure 10
■
■
GE Zenith Controls
19
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing
CAUTION
Due to hazardous voltage and current, GE Zenith
recommends that a GE Zenith Certified technician
or a qualified electrician must perform the
installation and maintenance of the switch.
Test Options
The ATS can be tested in either of two positions:
1) “Auto Position”
Full Transfer Test - This test checks the complete
operation of the ATS by transferring the load’s
power source from Source 1 to Source 2.
2) “Test Position”
WARNING
Both power sources must be disconnected
This procedure is recommended for Preventive
Maintenance (PM) of ATS without interrupting the
Load thru the BYPASS/ISOLATION SWITCH.
before manual operation of the switch.
NOTE: A periodic test of the transfer switch
under load conditions is recommended
to insure proper operation. (See National
Electric Code articles 700 and 701).
Introduction
A manual operator handle is provided with the
transfer switch for maintenance purposes only. Manual
operation of the switch must be checked before it is
operated electrically. Both power sources must be
disconnected before manual operation of the
switch. Insert the handle and operate the transfer
switch between the Source 1 and Source 2 positions.
The transfer switch should operate smoothly without
binding. Return the switch to the Source 1 position,
remove the handle, and return it to the holder provided.
WARNING
When performing a hi-pot or dielectric test
on the power section, DISCONNECT the
control panel plugs from the microprocessor
to avoid potential damage.
After completing the inspection, cleaning and servicing
of the transfer switch, reinstall the switch cover, and
close and lock the cabinet door. Reclose the circuit
breakers feeding the utility and generator sources
to the switch.
Initiate the electrical transfer test by activating the
test switch. P timer will time out and the microcon-
troller will send an engine start signal. When
the W time has elapsed, the switch will complete
its transfer by closing into the Source 2.
Deactivating the test switch will start retransfer to
Source 1. The switch will complete its retransfer to
Source 1 after the time delay of the T timer. The U
engine overrun timer allows the engine generator to
run unloaded for a preset cool down period.
■
■
20
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing
(cont’d)
NOTICE
A periodic test of the transfer switch under load conditions is recommended to insure proper operation.
(See National Electric Code articles 700 and 701)
ATSTesting
Start generator and verify proper voltage, frequency and phase
sequence (match to Source 1). Shut down gen set and place in
Auto. Complete the visual inspection of the transfer switch, and
close the cabinet door.
SYSTEM TEST
FAST XFR
NO
MORE TEST LOAD XFR
Initiate the test by pressing the TEST button on the LCD
keypad. The controller will then prompt for your access code.
After entering the code, three test options will appear—
XFR LOAD, FAST TEST and NO XFR (See Figure 11).
•
•
XFR LOAD test starts the generator and using
the current timer settings, transfers the load
to Source 2.
FAST TEST test presets timer values to a maximum
30 seconds during the test. After completion of
the test, all timers are reset to their original
values. (T3, W3, DT and DW remain)
NO XFR test starts the generator but does not
transfer the load to the Source 2.
Figure 11
to run unloaded. A manual pushbutton BYPASS is provided to
bypass the "U" time delay if desired. Upon completion of the
(U) timing cycle, the controller sends an Engine stop signal.
•
Press and hold the desired test option button until the switch
transfers to Source 2 (load test) or until the generator has
been run for the desired amount of time (no load test).
Releasing the test button before W timer timeout will abort
the test (Exception: when the transfer commit option, is
configured “ON”).
DelayedTransition
Source 1 Power Failure:
When the test is initiated, the controller initiates the Time
Delay Source 2 Start (Engine Start Timer "P") cycle. A manual
CANCEL button is provided to cancel the test if desired Upon
completion of the (P) time delay, an Engine start Signal is sent
to Source 2. When Source 2 voltage and frequency reach the
preset "Restore" values, the time delay to open Source 1 timer
(W) begins its timing cycle to ensure voltage and frequency sta-
bilization before re-transfer. A manual pushbutton BYPASS is
provided to bypass the "W" time delay if desired. After the (W)
time delay, the CCNO relay energizes the CNO solenoid to
open the transfer switch out of Source 1 position. The time
delay to Source 2 timer (DW) begins its timing cycle. After the
(DW) time delay, the CCE relay energizes. The switch then
completes transfer to Source 2 by energizing the CE solenoid.
The SE limit switch activates to de-energize the CCE relay.
To test lamps, press TEST then scroll through MORE, then
press LAMP TEST. To cancel LAMP TEST press MORE.
StandardTransition
When the test is initiated, the controller initiates the Time Delay
Source 2 Start Timer (Engine Start Timer "P") cycle. A manual
CANCEL button is provided to cancel the test if desired. Upon
completion of the (P) time delay, an Engine start Signal is sent to
Source 2. When Source 2 voltage and frequency reach the preset
"Restore" Values, the time delay to Source 2 Timer (W) begins its
timing cycle to ensure voltage and frequency stabilization before
transfer. A manual pushbutton BYPASS is provided to bypass the
"W" time delay if desired. After the (W) time delay, the CCE relay
energizes the CE solenoid to close the transfer switch in to Source
2. The SE limit switch activates to de-energize the CCE relay.
Restoration of Source 1 Power:
Deactivating the test switch initiates re-transfer to Source
1sequence.The delay to open Source 2 Timer (T) begins its tim-
ing cycle to ensure voltage and frequency stabilization before
retransfer. A manual pushbutton BYPASS is provided to bypass the
"T" time delay if desired. After the (T) time delay, the CCEO relay
energizes the CEO solenoid to open the switch out of Source 2
position. The time delay to Source 1 timer (DT) begins its timing
cycle. After the (DT) time delay, the CCN relay energizes the CN
solenoid to complete re-transfer of the switch to Source 1. The SN
limit switch activates to de-energize the CCN relay.
Restoration of Source 1 Power:
Deactivating the test switch initiates re-transfer to Source 1
sequence.The delay to Source 1 Timer (T) begins its timing cycle
to ensure voltage and frequency stabilization before retransfer.
A manual pushbutton BYPASS is provided to bypass the "T" time
delay if desired. After the (T) time delay, the CCN relay energizes
the CN solenoid to retransfer the switch to Source 1. The SN limit
switch activates to de-energize the CCN relay.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay
to Engine Stop "U") begins its cycle to allow Source 2 Engine
to run unloaded. A manual pushbutton BYPASS is provided to
bypass the "U" time delay if desired. Upon completion of the
(U) timing cycle, the controller sends an Engine stop signal.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay
to Engine Stop "U") begins its cycle to allow Source 2 Engine
■
■
GE Zenith Controls
21
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing
(cont’d)
NOTICE
A periodic test of the transfer switch under load conditions is recommended to insure proper operation.
(See National Electric Code articles 700 and 701)
ClosedTransition
GE Zenith Closed Transition Transfer Switches are
designed to Transfer the Load between two available
sources with out interrupting power to the Load
(Make-Before-Break). Paralleling of the two sources
occurs within a predefined window of synchronization
and lasts less than 100 milliseconds. The initial Source
is then disconnected.
The ATS defaults to an open transition transfer when
Source 1 fails. Closed transition transfer is not possible
with only one source available. If the optional Transition
Mode Selector (TMS) is available, one can select an
Open Transition Transfer or a Closed Transition
Transfer when both Sources are available..
If while in Closed Transition Mode, the ATS fails to
open the source it is attempting to "transfer out of"
within 100 milliseconds, an Alarm will sound and the
source that the ATS just closed into will be opened
leaving the ATS in its initial source while disabling all
other transfer operations until the problem is corrected
and the "Fail to Open Lockout Reset" has been pressed.
Initiating a Closed Transition
When a Test is initiated, the controller initiates the
Time Delay Source 2 Start (Engine Start Timer "P")
cycle. Upon completion of the (P) time delay, an
Engine start Signal is sent to Source 2. When Source 2
voltage and frequency reach the preset "Restore" values,
the time delay to open Source 1 timer (W) begins its
timing cycle. After the (W) time delay, the ATS closes
into Source 2 only after the controller ensures the prop-
er phase relationship between the two Sources. After the
ATS closes into Source 2, the SE limit switch becomes
activated to de-energize the CCE relay and energize
the CCNO relay which opens the ATS out of Source 1.
The SNO limit switch activates to de-energize the
CCNO relay. The ATS has now closed into Source 2
position without interrupting the load.
A signal will be provided (STE) to Shunt Trip the
Generator Circuit Breaker if the Transfer Switch
remains closed into both Sources for more than 325
milliseconds. The load will then be fed by the Source 1.
The maximum time that the two Sources would be
parallel, under these conditions, is less than 500
milliseconds. Before operating the Closed Transition
Transfer Switch, the condition must be corrected and
the Shunt Trip reset. Refer to procedure for servicing
the Switch after Shunt Tripping occures.
Re-Transfer with Closed Transition
Deactivating the Test Switch initiates the re-transfer.
When Source 1 voltage and frequency reach the preset
"Restore" values, the time delay to open Source 2 timer
(T) begins its timing cycle. After the (T) time delay, the
ATS closes into Source 1 only after the controller
ensures the proper phase relationship between the two
Sources. After the ATS closes into Source1, the SN limit
switch becomes activated to de-energize the CCN relay
and energize the CCEO relay which opens the ATS out
of Source 2. The SEO limit switch activates to de-ener-
gize the CCEO relay. The ATS has now closed back into
Source 1 position without interrupting the load.
The unit is Factory set to accomplish transfer
within 5 electrical degrees.
Requires an Isochronous Governor with an
operating frequency of 60+/- 0.2 Hz.
Requires a Shunt Trip Breaker on the Generator set
with a response time not exceeding 50 milliseconds.
■
■
22
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Emergency Service
Procedure for Extended
ParallelTime
10)Re-install the transfer switch after maintenance
with contacts closed to the same source as the
ZTSCTTransfer Switch
bypass switch. Reinstall the manual handle in its
holder and the service access cover on the left
If Source 2 breaker shunt trip was triggered after
side of the transfer switch.
an extended parallel time (malfunction) occurred.
11)Re-connect the transfer switch to AUTO.*
Follow these steps to open the transfer switch.
b. Auto Location:
1) Disconnect all power sources from the transfer
switch by opening all line breakers
(Source 1 and Source 2).
Removal of the closed transition transfer switch if
Source 1 and Source 2 contacts remain open.
2) Open the cabinet door and turn the disconnect
switch to the INHIBIT position.
3) Remove the service access cover on the left hand
side of the transfer switch.
4) The manual operator and the manual handle will
now be exposed. Insert the handle into the
Source 2 side operator. Open the Source 2
side contacts.
1) Close the bypass switch into the available source.*
2) Turn the DS to INHIBIT. Remove the transfer
switch service access cover. Close the transfer
switch into the same source as the bypass switch.
(Incorrect sequencing is prevented by the
interlocks while the transfer switch is in AUTO only.)
3) Remove the transfer switch from the bypass-
isolation transfer switch to inspect and repair.*
5) Close the cabinet door.
6) Energize Source 1 to supply the load until
further repairs can be done.
c. Test Location:
Removal of the closed transition transfer switch if
both Source 1 and Source 2 contacts remain open.
ZBTSCTTransfer/Bypass Switch
1) Close the bypass switch contacts (BN) as
indicated on the bypass instruction label
on the cabinet door.
2) Disconnect all power sources from bypass-isolation
closed transition transfer switch.
a. Auto Location:
Removal of closed transition transfer switch after
Source 2 breaker shunt trip.
1) Disconnect all power sources from bypass-
isolation transfer switch.
3) Open bottom cabinet door. Turn the Disconnect
Switch (DS) to the INHIBIT position.
4) Remove the service access cover on the left side
of the transfer switch.
5) The manual operator and the manual handle will
not be exposed. Insert the handle into the Source 1
side and close the Source 1 contacts.
6) Close the bottom cabinet door.
7) Energize Source 1 power.
8) Remove the automatic transfer switch from the
bypass-isolation transfer switch.*
9) Re-install the transfer switch after maintenance
with contacts closed to the same source as the
bypass switch. Reinstall the manual handle in
its holder and the service access cover on the
left side of the transfer switch.
2) Open the bottom cabinet door and turn the
Disconnect Switch (DS) to the INHIBIT position.
3) Remove the service access cover on
the left hand side of the transfer switch.
4) The manual operator and the manual handle will
now be exposed. Insert the handle into the
Source 2 side manual operator. Open the
Source 2 side contacts.
5) Close bottom cabinet door.
6) Energize Source 1 power.
7) Close the bypass contacts (BN).*
8) Isolate the transfer switch.*
9) Remove the transfer switch from the bypass-
isolation transfer switch as indicated on the
bypass instruction label to inspect and repair.
10)Re-connect the transfer switch to AUTO.*
* As described in the Sequence of Operation section located in the ZTSCT/ZBTSCT Series Manual (71R-5000)
■
■
GE Zenith Controls
23
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Sequence of Operation
StandardTransition
DelayedTransition
Source 1 Power Failure:
Source 1 Power Failure:
When Source 1 voltage or frequency has fallen below
the preset "Fail" values, the controller initiates the Time
Delay Source 2 Start Timer (Engine Start Timer "P")
cycle. Upon completion of the (P) time delay, an
Engine start Signal is sent to Source 2. When Source 2
voltage and frequency reach the preset "Restore" Values,
the time delay to Source 2 Timer (W) begins its timing
cycle to ensure voltage and frequency stabilization
before transfer. A manual pushbutton BYPASS is provid-
ed to bypass the "W" time delay if desired. After the (W)
time delay, the CCE relay energizes the CE solenoid to
close the transfer switch in to Source 2. The SE limit
switch activates to de-energize the CCE relay.
When Source 1 voltage or frequency has fallen below
the preset "Fail" values, the controller initiates the
Time Delay Source 2 Start (Engine Start Timer "P")
cycle. Upon completion of the (P) time delay, an
Engine start Signal is sent to Source 2. When Source 2
voltage and frequency reach the preset "Restore" values,
the time delay to open Source 1 timer (W) begins its
timing cycle to ensure voltage and frequency stabiliza-
tion before re-transfer. A manual pushbutton BYPASS is
provided to bypass the "W" time delay if desired. After
the (W) time delay, the CCNO relay energizes the CNO
solenoid to open the transfer switch out of Source 1
position. The time delay to Source 2 timer (DW) begins
its timing cycle. After the (DW) time delay, the CCE
relay energizes. The switch then completes transfer to
Source 2 by energizing the CE solenoid. The SE limit
switch activates to de-energize the CCE relay.
Restoration of Source 1 Power:
When Source 1 power reach the preset "Restore" values,
the controller initiates re-transfer to Source
1sequence.The delay to Source 1 Timer (T) begins its
timing cycle to ensure voltage and frequency stabiliza-
tion before retransfer. A manual pushbutton BYPASS is
provided to bypass the "T" time delay if desired. After
the (T) time delay, the CCN relay energizes the CN
solenoid to retransfer the switch to Source 1. The SN
limit switch activates to de-energize the CCN relay.
Restoration of Source 1 Power:
When Source 1 power reach the preset "Restore" values,
the controller initiates re-transfer to Source 1
sequence.The delay to open Source 2 Timer (T) begins
its timing cycle to ensure voltage and frequency stabi-
lization before retransfer. A manual pushbutton BYPASS
is provided to bypass the "T" time delay if desired. After
the (T) time delay, the CCEO relay energizes the CEO
solenoid to open the switch out of Source 2 position.
The time delay to Source 1 timer (DT) begins its timing
cycle. After the (DT) time delay, the CCN relay ener-
gizes the CN solenoid to complete re-transfer of the
switch to Source 1. The SN limit switch activates to de-
energize the CCN relay.
Immediately after re-transfer, the S2 Stop Delay Timer
(Delay to Engine Stop "U") begins its cycle to allow
Source 2 Engine to run unloaded. A manual pushbut-
ton BYPASS is provided to bypass the "U" time delay if
desired. Upon completion of the (U) timing cycle, the
controller sends an Engine stop signal.
Immediately after re-transfer, the S2 Stop Delay Timer
(Delay to Engine Stop "U") begins its cycle to allow
Source 2 Engine to run unloaded. A manual pushbut-
ton BYPASS is provided to bypass the "U" time delay if
desired. Upon completion of the (U) timing cycle, the
controller sends an Engine stop signal.
Table 3
Timer Designations as they appear in the SET menu
ATS Type
P
W
DW
T
DT
U
Standard
Transition
Time Delay
S2 Start
Time Delay
S2 Stable
Time Delay
S1 Stable
S2 Stop
Delay
Delay/ Open
Transition
Time Delay
S2 Start
Time Delay
S2 Stable
ATS Open
Time to S2
Time Delay
S1 Stable
ATS Open
Time to S1
S2 Stop
Delay
Source 1
Fails
Transfer to Source 2
Transfer to Source 1
Engine
Cooldown
Source 1
Returns
■
■
24
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Sequence of Operation
(cont’d)
ClosedTransition
The ATS defaults to an open transition transfer when
Source 1 fails. Closed transition transfer is not possible
with only one source available. If the optional Transition
Mode Selector (TMS) is available, one can select an
Open Transition Transfer or a Closed Transition
Transfer when both Sources are available..
GE Zenith Closed Transition Transfer Switches are
designed to Transfer the Load between two available
sources with out interrupting power to the Load
(Make-Before-Break). Paralleling of the two sources
occurs within a predefined window of synchronization
and lasts less than 100 milliseconds. The initial Source
is then disconnected.
If while in Closed Transition Mode, the ATS fails to
open the source it is attempting to "transfer out of"
within 100 milliseconds, an Alarm will sound and the
source that the ATS just closed into will be opened
leaving the ATS in its initial source while disabling all
other transfer operations until the problem is corrected
and the "Fail to Open Lockout Reset" has been pressed.
Initiating a Closed Transition
When a Test is initiated, the controller initiates the
Time Delay Source 2 Start (Engine Start Timer "P")
cycle. Upon completion of the (P) time delay, an
Engine start Signal is sent to Source 2. When Source 2
voltage and frequency reach the preset "Restore" values,
the time delay to open Source 1 timer (W) begins its
timing cycle. After the (W) time delay, the ATS closes
into Source 2 only after the controller ensures the
proper phase relationship between the two Sources.
After the ATS closes into Source 2, the SE limit switch
becomes activated to de-energize the CCE relay and
energize the CCNO relay which opens the ATS out of
Source 1. The SNO limit switch activates to de-energize
the CCNO relay. The ATS has now closed into Source 2
position without interrupting the load.
A signal will be provided (STE) to Shunt Trip the
Generator Circuit Breaker if the Transfer Switch
remains closed into both Sources for more than 325
milliseconds. The load will then be fed by the Source 1.
The maximum time that the two Sources would be
parallel, under these conditions, is less than 500
milliseconds. Before operating the Closed Transition
Transfer Switch, the condition must be corrected and
the Shunt Trip reset. Refer to procedure for servicing
the Switch after Shunt Tripping occures.
Re-Transfer with Closed Transition
The unit is Factory set to accomplish transfer within
5 electrical degrees.
Requires an Isochronous Governor with an operating
frequency of 60+/- 0.2 Hz.
Requires a Shunt Trip Breaker on the Generator set
with a response time not exceeding 50 milliseconds.
Deactivating the Test Switch initiates the re-transfer.
When Source 1 voltage and frequency reach the preset
"Restore" values, the time delay to open Source 2 timer
(T) begins its timing cycle. After the (T) time delay, the
ATS closes into Source 1 only after the controller
ensures the proper phase relationship between the two
Sources. After the ATS closes into Source1, the SN limit
switch becomes activated to de-energize the CCN relay
and energize the CCEO relay which opens the ATS out
of Source 2. The SEO limit switch activates to de-ener-
gize the CCEO relay. The ATS has now closed back into
Source 1 position without interrupting the load.
■
■
GE Zenith Controls
25
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay/Transformer (R/T Box)
StandardTransition
the MX250 from the line voltage, further protecting
Each MX250 microprocessor based ATS controller
requires a relay/transformer box to apply line voltage to
the ATS operator via coil control relays. Also required is
power for the MX150 printed circuit board and an appli-
cation of sensing voltage proportional to line voltage.
This is accomplished by the relay transformer box. This
method of switching operator voltage and applying power
and sensing voltage to the printed circuit board isolates
the controller from harmful line transients. Two versions
of the R/T box exist depending on the type of ATS
(standard transition or delayed transition).
The following layout drawings of the R/T Box compo-
nents (standard and delayed transition) include a bill of
materials for replacement parts. Schematics are included
to indicate proper wiring.
PRI.
PRI.
1
PRI.
SEC.
SEC.
SEC.
1
2
3
2
(inside)
3
Figure 12
Figure 13
40-3000 Amp - All Other StandardTypes
40-225 Amp Molded Power Section
Transformer Usage (see Figure 13)
Transformer Usage (see Figure 12)
R/T Box
Assembly
Part No.
Primary
Voltage
at 50/60 Hz
1 VA
XFMR
Part No.
25 VA
XFMR
Part No.
R/T Box
Assembly
Part No.
Primary
Voltage
at 50/60 Hz
1 VA
XFMR
Part No.
25 VA
XFMR
Part No.
50P-1026
50P-1027
50P-1028
50P-1029
50P-1030
50P-1031
50P-1032
50P-1033
120V
K-3216
K-3217
K-3218
K-3219
K-3220
K-3221
K-3222
K-3223
K-3224
K-3225
K-3226
K-3227
K-3228
K-3229
K-3230
K-3231
57P-1015
57P-1016
57P-1017
57P-1018
57P-1019
57P-1020
57P-1021
57P-1022
120V
K-3216
K-3217
K-3218
K-3219
K-3220
K-3221
K-3222
K-3223
K-3224
K-3225
K-3226
K-3227
K-3228
K-3229
K-3230
K-3231
208-220V
230-240V
277V
380-400V
416-440V
460-480V
575-600V
208-220V
230-240V
277V
380-400V
416-440V
460-480V
575-600V
Bill of Material
Bill of Material
Item
Part No.
Description
Qty
2
Item
Part No.
Description
Qty
2
1
2
3
See Chart
See Chart
K-1274
Transformer (1 VA)
Transformer (25 VA)
Relay Flange Mounted
1
2
3
See Chart
See Chart
K-1260
Transformer (25 VA)
Transformer (1 VA)
Coil Control Relay (24V)
2
2
2
2
■
■
26
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay/Transformer (R/T Box)
(cont’d)
Delayed / Closed Transition
PRI.
SEC.
1
2
3
Figure 14
Transformer Usage
Bill of Material
Item
Part No.
Description
Qty
2
R/T Box
Assembly
Part No.
Primary
Voltage
1 VA
XFMR
25 VA
XFMR
1
2
3
See Chart
See Chart
K-1260
Transformer (25 VA)
Transformer (1 VA)
Coil Control Relay (24V)
at 50/60 Hz
Part No.
Part No.
2
50P-1034
50P-1035
50P-1036
50P-1037
50P-1038
50P-1039
50P-1040
50P-1041
120V
K-3216
K-3217
K-3218
K-3219
K-3220
K-3221
K-3222
K-3223
K-3224
K-3225
K-3226
K-3227
K-3228
K-3229
K-3230
K-3231
4
208-220V
230-240V
277V
380-400V
416-440V
460-480V
575-600V
■
■
GE Zenith Controls
27
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay/Transformer (R/T Box)
(cont’d)
StandardTransition R/T Box Schematic
30 31
32
20 21 22
XN1 - SOURCE 1 CONTROLTRANSFORMER
XN2 - SOURCE 1 3 PHASE SENSINGTRANSFORMER
XE1 - SOURCE 2 CONTROLTRANSFORMER
XE2 - SOURCE 2 3 PHASE SENSINGTRANSFORMER
XE2
10V
XE1
10V
XN2
10V
XN1
10V
24V
11V
24V
11V
SOURCE 2 24V OUTPUT
SOURCE 1 24V OUTPUT
3 PHASE SOURCE 2 SENSING
900
800
907
(18)
(BLANK)
(BLANK)
GROUND
CCN
CCE
GND
901
801
CCE - COIL CONTROL RELAY (SOURCE 2)
CCN - COIL CONTROL RELAY (SOURCE 1)
COMMON
902
903
904
803
804
807
806
805
906
905
SINGLE PHASE SOURCE 2 SENSING
3-PHASE SOURCE 1 SENSING
SOURCE 1 CONTROL POWER
SOURCE 2 CONTROL POWER
(1)
J5
Figure 15
Delayed / ClosedTransition R/T Box Schematic
22
31
32
21
30
20
XN1 - SOURCE1 CONTROLTRANSFORMER
XN2 - SOURCE1 3 PHASE SENSINGTRANSFORMER
XE1 - SOURCE 2 CONTROLTRANSFORMER
XE2 - SOURCE 2 3 PHASE SENSINGTRANSFORMER
XE1
10V
XN1
10V
XE2
10V
XN2
10V
24V
24V
11V
11V
900
800
907
SOURCE 2 24V OUTPUT
SOURCE 1 24V OUTPUT
3 PHASE SOURCE 2 SENSING
(18)
808
908
GND
901
801
902
903
904
803
804
807
806
805
906
905
CCEO - COIL CONTROL RELAY (OPEN SOURCE 2)
CCNO - COIL CONTROL RELAY (OPEN SOURCE 1)
GROUND
CCEO
CCN
CCNO
CCE
CCE - COIL CONTROL RELAY (SOURCE 2)
CCN - COIL CONTROL RELAY (SOURCE 1)
COMMON
SINGLE PHASE SOURCE 2 SENSING
3-PHASE SOURCE 1 SENSING
SOURCE 1 CONTROL POWER
SOURCE 2 CONTROL POWER
(1)
J5
Figure 16
■
■
28
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting and Diagnostics
DANGER
HAZARDOUS VOLTAGES CAN CAUSE SEVERE INJURY OR DEATH.
These charts may indicate problems that require authorized GE Zenith service personnel.
Hazardous voltages may exist on termination plugs other than those that go into the Entelli-Switch 250.
GeneralTroubleshooting
The following troubleshooting guide is used to recognize,
and determine basic faults. When using this guide, it will
ask several questions about the condition of the switch.
This guide will then list an order of the possible faults.
You will then look at the first suspected fault to determine
if it is the problem. If it is not a fault, you go to the
second suspected fault. If you go through all of the
suspected faults, or the chart instructs you to, call
a GE Zenith Representative for further assistance.
NOTE: When you use the troubleshooting charts,
the Annunciation column refers to the LED’s on
the control panel.
Symptom
Annunciation
Possible Cause(s)
Corrective Action
Engine does not START
SOURCE 2
AVAILABLE
LED off
Engine start wires not
terminated properly
Check engine start connections
Generator is in OFF position
Investigate why Engine Control
Switch was turned off
Engine does not stop
LCD Display -
U timing cycle not complete
Check U timer setting
“TD Engine Cool Down”
SOURCE 1 POSITION, and
SOURCE 1 and SOURCE 2
AVAILABLE LEDs on,
Engine start wires not
terminated correctly
Check Engine Start Connections
Place generator in AUTO
Generator in MANUAL
but U timer has timed out
ATS will not transfer
to SOURCE 2
SOURCE 2 AVAILABLE
LED off
SOURCE 2 voltage or frequency
not within acceptable parameters
Check: Engine Start Connections,
Generator Breaker, Generator Output,
and Engine Control Switch
ZTG Series
None
Power supply connector unplugged Plug in connector
LCD Display -
W timing cycle not complete
Check WTimer setting
“S1 _ _ _ _ TD XFR S1>S2
Time Remaining _ _ _ _”
ATS will not transfer
to SOURCE 1
DW timing cycle not complete
Check DWTimer setting
LCD Display -
“ATS Open
Time Remaining _ _ _ _”
ZTGD Series
Check utility and utility breakers
SOURCE 1 voltage or frequency
not within acceptable parameters
SOURCE 1 AVAILABLE
LED off
None
Power supply connector unplugged Plug in connector
LCD Display -
“Diagnostic Code 001”
Limit switch or RT box
connector unplugged
CallTechnical Services
LCD Display -
“S1 OK
Time Remaining _ _ _ _
Bypass”
T timing cycle not complete
Check TTimer setting
LCD Display -
TD timing cycle not complete
Check DTTimer setting
“ATS Open
Time Remaining _ _ _ _”
Table 4
■
■
GE Zenith Controls
29
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance andTesting
CDT battery replacement - lithium batteries may
CAUTION
Due to hazardous voltage and current, GE Zenith rec-
ommends that a GE Zenith Certified technician or a
qualified electrician must perform the
last up to 10 years, however it is recommended
that battery replacement be included in a 3-5 year
service cycle. The battery maintains the exerceser
memory only and does not otherwise affect the
operation.
installation and maintenance of the switch.
WARNING
Both power sources must be disconnected
Testing
A manual operator handle is provided with the
transfer switch for maintenance purposes only.
Manual operation of the switch must be checked
before it is operated electrically. Both power sources
must be disconnected before manual operation
of the switch. Insert the handle and operate the
transfer switch between the Source 1 and Source 2
positions. The transfer switch should operate smoothly
without binding. Return the switch to Source 1
position, remove the handle, and return it to
the holder provided.
before manual operation of the switch.
A preventive maintenance program will insure high
reliability and long life for the transfer switch. The
preventive maintenance program for the transfer
switch should include the following items:
Inspection and Cleaning
The switch should be inspected for any accumulation
of dust, dirt, or moisture, and should be cleaned by
vacuuming or wiping with a dry cloth or soft brush.
do not use a blower since debris may become lodged
in the electrical and mechanical components and
cause damage.
After completing the inspection, cleaning and servicing
of the transfer switch, reinstall the switch cover,
and close and lock the cabinet door. Reclose the
circuit breakers feeding the utility and generator
sources to the switch.
Remove the transfer switch barriers and check the
condition of the contacts. Any surface deposits must
be removed with a clean cloth (do not use emery
cloth or a file). If the contacts are pitted or worn
excessively, they should be replaced. A general
inspection of mechanical integrity should be made
to include loose, broken or badly worn parts.
Initiate the electrical transfer test by activating the
TS test switch. P timer will time out and the micro-
controller will send an engine start signal. When
the W time has elapsed, the switch will complete
its transfer by closing into Source 2.
Deactivating the test switch will start retransfer to
Source 1. The switch will complete its retransfer
to Source 1 after the time delay of the T timer.
The U engine overrun timer allows the engine
generator to run unloaded for a preset cool
down period.
Servicing
All worn or inoperative parts must be replaced
using GE Zenith recommended replacement parts.
Please refer to the Replacement Parts manual for
specific part information and ordering procedures.
Please contact the GE Zenith Technical Services
Department for the Replacement Parts manual.
NOTE:
A periodic test of the transfer switch
under load conditions is recommended
to insure proper operation. (See National
Electric Code articles 700 and 701).
The operating mechanism of the transfer switch
is lubricated with Lubriplate 105. The lubricant
applied at the factory provides adequate lubrication for
the lifetime of the switch. Should debris contaminate
the mechanism, clean and apply additional Lubriplate.
WARNING
When performing a hi-pot or dielectric test
on the power section, DISCONNECT the
control panel plugs from the microprocessor
to avoid potential damage.
GE Zenith can provide complete preventative main-
tenance services. Please contact the GE Zenith Technical
Services Department for additional information.
■
■
30
GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
■
■
GE Zenith Controls
31
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Download from Www.Somanuals.com. All Manuals Search And Download.
GE Zenith Controls
g
A Product of GE Industrial Systems
General Electric Company
830 West 40th Street, Chicago, IL 60609 USA
773 299-6600, Fax: 773 247-7805
Download from Www.Somanuals.com. All Manuals Search And Download.
|