GE Power Supply GEK 106465A User Manual

GE Consumer & Industrial  
Multilin  
g
CIO  
Remote CAN Digital I/O Module  
Instruction manual  
GEK-106465A  
Copyright © 2006 GE Multilin  
GE Multilin  
GE Multilin  
Avda. Pinoa, 10  
215 Anderson Avenue  
48170 Zamudio SPAIN  
T +34 94 485 88 00 F +34 94 485 88 45  
L6E 1B3 Markham, ON -CANADA  
T (905) 294 6222 F (905) 294 8512  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
5.  
INPUT/OUTPUT MODULES DESCRIPTION  
31  
31  
5.1. CIRCUIT SUPERVISION AND CONTACT SEAL-IN CIRCUITS  
5.1.1. CIRCUIT SUPERVISION.....................................................................................................................31  
5.1.2. CONTACT SEAL-IN ............................................................................................................................31  
5.2. CONTROL SETTINGS FOR INPUTS/OUTPUTS  
32  
5.2.1. INPUT/OUTPUT BOARDS SETTINGS...............................................................................................32  
5.2.2. INPUTS/OUTPUTS STATUS ..............................................................................................................36  
6.  
ACCEPTANCE TESTS  
39  
6.1. VISUAL INSPECTION  
6.2. GENERAL CONSIDERATIONS ON THE POWER SUPPLY NETWORK  
6.3. ISOLATION TESTS  
6.4. INDICATORS  
6.5. POWER SUPLY TESTING  
39  
39  
40  
40  
40  
41  
41  
6.6. COMMUNICATION WITH THE MASTER UNIT  
6.7. INPUTS AND OUTPUTS  
6.7.1. DIGITAL INPUTS.................................................................................................................................41  
6.7.2. CONTACT OUTPUTS .........................................................................................................................42  
6.7.3. CIRCUIT CONTINUITY SUPERVISION INPUTS ...............................................................................42  
6.7.4. LATCHING CIRCUITS.........................................................................................................................42  
2
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW  
1. OVERVIEW  
1.1.  
IMPORTANT PROCEDURES  
To help ensure years of trouble free operation, please read through the following chapter for information to help guide  
you through the initial installation procedures of your new relay.  
BEFORE ATTEMPTING TO INSTALL OR USE THE RELAY, IT IS IMPERATIVE THAT ALL WARNINGS AND  
CAUTIONS IN THIS MANUAL ARE REVIEWED TO HELP PREVENT PERSONAL INJURY, EQUIPMENT  
CAUTION: THE OPERATOR OF THIS INSTRUMENT IS ADVISED THAT IF THE EQUIPMENT IS USED IN A  
MANNER NOT SPECIFIED IN THIS MANUAL, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE  
IMPAIRED  
FIGURE 1-1 CIO FRONT VIEW  
Installation must be according to the national electric code of the appropriate country  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW  
1.1.1.  
INSPECTION CHECKLIST  
- Open the relay packaging and inspect the relay for physical damage.  
Refer to the label on the side of the relay verifies that the model number is the correct model ordered.  
FIGURE 1-2 IDENTIFICATION LABEL (A4454P5)  
- Please ensure that you receive the following items with your CIO unit:  
- Mounting screws for rear terminals and for fixing the relay to a cabinet  
- Wiring diagram  
For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin  
Home Page www.GEMultilin.com.  
4
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW  
Note: If there is any physical damage detected on the relay, or any of the contents listed are missing, please  
contact GE Multilin immediately at:  
EUROPE, MIDDLE EAST AND AFRICA:  
GE MULTILIN  
Avda. Pinoa, 10  
48170 Zamudio, Vizcaya (SPAIN)  
Tel.: (34) 94-485 88 00, Fax: (34) 94-485 88 45  
AMERICA, ASIA AND AUSTRALIA:  
GE MULTILIN  
215, Anderson Avenue  
L6E 1B3 Markham, ON (CANADA)  
Tel.: +1 905 294 6222, Fax: +1 905 201 2098  
The information provided herein does not intend to cover all details of variations of the equipment nor does  
it take into account the circumstances that may be present in your installation, operating or maintenance  
activities.  
Should you wish to receive additional information, or for any particular problem that cannot be solved by  
referring to the information contained herein, please contact GENERAL ELECTRIC MULTILIN.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW  
1.1.2.  
The CIO ground screw located on the rear of the unit must be correctly grounded.  
SAFETY INSTRUCTIONS  
This is required not only for personal protection, but also for avoiding a voltage difference between the CIO serial port  
and the master unit port, which could produce anomalies in communication.  
GE Multilin will not be responsible for any damage in the relay or connected equipment whenever this elemental  
safety rule is not followed.  
6
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW  
1.2.  
OVERVIEW  
1.2.1.  
INTRODUCTION TO F650 AND F600 FAMILY OF RELAYS  
This platform of relays has been designed to meet the goals that are appearing nowadays in the environment of new  
substations. Historically, protection, control and metering functions have been performed by electromechanical  
elements at the beginning, then static devices, and finally by digital equipment able to integrate all these functions in  
a single device, called IED (Intelligent Electronic Device).  
Due to the huge number of signals to be controlled and monitored nowadays in a substation environment, there is a  
new need for a great number of digital inputs and outputs to retrieve states and to signal or perform all different  
operations. CIO units respond to this need, allowing connection to F650 and F600 IEDs, and increasing the number  
of available inputs and outputs depending on the connected equipment.  
1.2.2.  
HARDWARE ARCHITECTURE  
CIO units incorporate a series of interconnected modules to operate. These modules are a power supply and  
input/output boards.  
CIO  
BUS  
Contact Inputs  
Contact Outputs  
FIGURE 1-3 HARDWARE ARCHITECTURE  
As shown on the diagram above, Contact Inputs/Outputs are signals associated to physical input/output contacts in  
the relay, and their status is sent/received through the CAN BUS of the associated equipment, F600 or F650.  
This CAN connection to the master unit can be made through fiber optic cable or through copper cable.  
CIO units can incorporate up to two I/O boards, each of which must have a unique address in the system. For this  
purpose, there is a switch at the rear of the unit with 16 positions (0 to F), that allows indicating the address for board  
H. The address of board J is fixed to “board H address + 1”.  
1.2.3.  
SOFTWARE ARCHITECTURE  
Each I/O board includes a microprocessor that manages communication with the master unit, as well as sampling  
and activation of the corresponding inputs and outputs.  
The firmware (software embedded in the boards) has been designed using object oriented programming techniques  
(ODD/OOP). These techniques are based on the use of objects and classes, and provide the software architecture  
with the same characteristics as the hardware architecture, i.e., modularity and flexibility.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW  
1.2.4.  
COMMUNICATIONS ARCHITECTURE  
CIO units incorporate a CAN BUS port in two physical media: glass fiber optic and cable. The fiber optic port allows  
connection to the master unit for a single CIO unit. For connections including several CIO units, the cable port must  
be used. If the master unit is a F650, then communication must always be in fiber optic.  
8
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESCRIPTION  
2. PRODUCT DESCRIPTION  
2.1.  
OVERVIEW  
The CIO module is an input/output extension for F650 and F600 units. Using this module, the number of available  
inputs/outputs can be increased, these inputs/outputs operation being identical to the one of the original I/Os in  
the master unit.  
The CIO module has been designed to be installed close to the substation switchgear, and connected to the main  
unit through a CAN bus in fiber optic or cable. Fiber optic connection provides total immunity against  
electromagnetic disturbances, as well as simplified wiring and commissioning.  
CIO module I/O configuration and management are performed exclusively from the master unit. This master unit  
manages the CIO inputs and outputs in the same way as its own.  
2.2.  
SUMMARY OF FEATURES  
INPUTS  
Inputs programmable from the master unit.  
Programmable activation voltage level  
Programmable debounce time for each inputs group  
Possibility to select positive or negative activation logic  
Possibility to select pulse or level activation.  
OUTPUTS  
Outputs programmable from the master unit  
Possibility to select positive or negative activation logic  
Selectable pulse mode activation  
Selectable latched configuration  
Breaker tripping and Closing circuits supervision  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESCRIPTION  
2.3.  
ORDERING CODE  
CIO units are available in 1/3 19’’ rack, 6 units high, and it includes a power supply module and a communication  
module, plus a maximum of two I/O modules. Each of these modules can be supplied in different versions, which  
must be specified when ordering. The required information to detail the requested unit is shown on the table below:  
TABLE 2-1 ORDERING CODE  
CIO  
H
-
J
-
-
-
DESCRIPTION  
I/O board 1 in slot H  
16 digital inputs + 8 outputs  
1
2
8 digital inputs + 8 outputs + 2 trip/close circuit supervision  
circuits  
4
5
32 digital inputs  
16 digital inputs + 8 analog inputs  
I/O board 1 in slot J  
0
1
4
5
None  
16 inputs + 8 outputs  
32 digital inputs (See Note 1)  
16 digital inputs + 8 analog inputs (See Note 1)  
Auxiliary Voltage  
LO  
HI  
24-48 Vdc (range 19.2 - 57.6)  
110-250 Vdc (range 88-300)  
120-230 Vac (range 96-250)  
Environmental Protection  
H
Harsh (Chemical) environment conformal coating  
(1) The digit selected for option J must be equal or higher than the digit selected for option H.  
CIOH1J5**: is a valid selection  
CIOH5J1**: is an invalid selection  
10  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESCRIPTION  
2.4.  
TECHNICAL SPECIFICATIONS  
TECHNICAL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE  
2.4.1.  
INPUTS  
Activation range:  
Programmable from 1 up to 255 Vdc in steps of 1 V  
Impedance  
> 100 kOhm  
Load for voltage supervision inputs  
Acknowledgement time  
Debounce time:  
2 mA + V/100 kOhm  
<1 m  
1 to 50 ms in steps of 1 ms  
2.4.2.  
OUTPUTS  
Permanent current  
Closing current  
Opening current  
16 A  
60 A during 1 second  
0.3 A with L/R = 40 ms at 125 Vdc  
0.25 A with L/R = 40 ms at 250 Vdc  
2.4.3.  
CONTROL POWER SUPPLY  
LO (low range)  
Range:  
24 to 48 Vdc (from 24 Vdc – 15% to 48 Vdc + 20%)  
HI (high range)  
Range:  
110 to 250 Vdc (from 110 Vdc – 15% to 250 Vdc + 20%)  
110 to 240 Vac (from 110 Vac – 15% to 240 Vac + 20%)  
5 W typical  
Consumption:  
Interruptions:  
0.25 W more per each activated output.  
Typical 100 ms, without unit reset.  
2.4.4.  
CAN BUS  
Baudrate:  
Media:  
125 kbits per second  
Glass fiber optic multimode with ST connectors.  
Maximum recommended length 1Km  
3 wire cable connection  
Maximum recommended length 500m  
2.4.5.  
- 10°C to + 60°C  
ENVIRONMENTAL CHARACTERISTICS  
Operation temperature:  
Storage temperature:  
Humidity:  
- 40°C to + 80°C  
95% without condensing.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESCRIPTION  
2.4.6.  
PACKAGING AND WEIGHT  
Net weight:  
Packaged:  
2.5 kg  
3.5 kg  
Package dimensions (WxHxD): 30x40x40 cm  
2.4.7.  
TYPE TESTS  
CATEGORY  
STANDARD  
CLASS TEST  
EMC  
IEC 1000-4-8 EN61000-4-8  
IV  
Power  
frequency  
magnetic  
field  
immunity test.  
IEC 1000-4-10 EN61000-4-10  
IEC 1000-4-3 IEC60255-22-3  
4
Damped oscillatory field immunity test  
III  
Radiated, radio-frequency  
electromagnetic field immunity test  
IEC 1000-4-3  
3
III  
4
Digital radiofrequency electromagnetic  
field  
IEC 1000-4-2 EN 61000-4-2 IEC60255-  
22-2  
Electrostatic discharge immunity test  
IEC 1000-4-16  
Test for immunity to conducted common  
mode disturbances in the frequency  
range 0Hz to 150 kHz immunity test.  
IEC 1000-4-5  
4
Surge immunity test  
IEC 1000-4-12 IEC 60255-22-1  
III  
Noise  
1
MHz. Oscillatory waves  
immunity test.  
IEC 1000-4-4 EC 61000-4-4 IEC60255-  
22-4  
IV  
III  
B
Electrical fast transient/burst immunity  
test  
IEC 1000-4-6 IEC60255-22-6  
Immunity to conducted disturbances,  
induced by radio-frequency fields  
EMC Emisivity  
Product  
IEC 60255-25 EN55022  
Conducted and radiated emissions class  
B
IEC60255-5  
2 kV Insulation  
IEC60255-5  
6kV .5J Impulse test  
IEC60255-11; IEC61000-4-29  
100 ms Power supply interruptions  
CIO has been designed to comply with the highest existing requirements. More specifically, UNIPEDE  
recommendations for high voltage substations are followed.  
2.4.8.  
APPROVALS  
ISO9001 Registered system.  
CE marking: Meets the CE standards relevant for protections.  
12  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3. HARDWARE  
3.1.  
MODULE DESCRIPTION  
Serial CAN BUS  
DIGITAL  
I/O  
Optional  
DIGITAL  
I/O  
Power Supply  
FIGURE 3-1 BLOCK DIAGRAM  
F650 units incorporate the following modules:  
Power supply  
Input/Output module  
Optionally, a second I/O module can be added.  
A relay connected to the low voltage side of the power supply monitors this voltage. The three contact terminals,  
normally open, common, and normally closed, are available at the external connector terminals. This relay monitors  
only the power supply integrity.  
This is a “fly-back” type power supply, providing high efficiency, stability and reliability thanks to the maturity of this  
technology. There are two available ranges, Hi and Low, in order to optimize efficiency and general performance,  
including the capability to tolerate auxiliary voltage interruptions (dips).  
Oversized components highly resistant to temperature are used. For example, all capacitors are specified to stand up  
to 105ºC, transformer components are specially designed to stand up to 180ºC, the used MOSFET transistor is of  
very low resistance, supports high voltage and is refrigerated by an oversized heat sink. This allows supporting  
extremely high temperatures, and prolonged overloads such as the ones occurring at batteries in deep charge mode  
(much higher than the maximum voltage shown in the Technical Characteristics section).  
High capacity capacitors are also used, providing high tolerance to prolonged dips, 100ms, even in the most  
unfavorable consumption conditions. This allows the relay to continue with normal operation without undesired resets,  
which would cause a long time of protection unavailability  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.2.  
MECHANICAL DESCRIPTION  
The model number and electrical characteristics of the unit are indicated on the label located on the right side of the  
relay case.  
The metallic case of the unit is highly resistant to corrosion. It is made of stainless steel (AISI 304), coated with an  
epoxy layer, and the rest of the metallic pieces are covered with a high quality resistive coating that has successfully  
passed at least 96 hours in the salt spray chamber (S/N ASTM B-117).  
The front of the relay is made of a conductor thermoplastic, flame retardant (V0), highly resistive material, which  
guarantees the unit’s immunity to all kinds of EMI/RFI/ESD interferences. As well, an IP51 (IEC 529) protection  
degree against dust and water through the front and with the relay mounted in the panel.  
In order to guarantee safety and preventing access to the unit by unauthorized personnel, the front communications  
port and the operation mode key are protected by a sealable cover.  
3.2.1.  
MOUNTING  
The unit is designed for both semi-flush mounting with the terminals on the back, and rear panel mounting, with the  
terminals towards the front. In both cases the relay should be secured to the panel with the M6 screws provided with  
the unit.  
FIGURE 3-2 SEMI-FLUSH MOUNTING  
14  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
FIGURE 3-3 REAR PANEL MOUNTING  
5,3"  
134,0  
4,5"  
114,0  
0,3"  
O
7,0  
7,5"  
190,5  
10,3"  
262,0  
FIGURE 3-4 DRILLING DIMENSIONS  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.2.2.  
REAR COVER DESCRIPTION  
Unit wiring is performed through the terminal blocks located on the rear.  
The rest of the terminal blocks for power supply, inputs/outputs, incorporate high quality connectors with the capacity  
to withstand a rated current of 15 A at 300 V. These terminal blocks admit a cable section of up to 2.5 mm2 (AWG  
12).  
16  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.3.  
WIRING  
3.3.1.  
EXTERNAL CONNECTIONS  
CIO units can hold up to two I/O modules. Each of these modules can be selected between the following options:  
Option 1:  
Option 2:  
Board with 16 inputs and 8 outputs.  
Board with 8 digital inputs, 4 circuit supervision outputs, 6 conventional outputs, and two current  
sensing outputs  
Each model has a different wiring diagram, as follows:  
FIGURE 3-5 WIRING DIAGRAM FOR MODELS CIOH2J1 (226B5113F1)  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
FIGURE 3-6 WIRING DIAGRAM FOR MODEL CIOH1J1 (226B5113F2)  
18  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.4.  
BOARDS  
3.4.1.  
BOARD OPTION 1  
CIO I/O board option 1 includes 16 inputs grouped in two series of 8 inputs with a common, and 8 conventional  
inputs.  
FIGURE 3-7 shows the location of terminals for both types of board:  
MIXED  
1
SUPERVISION  
2
TERMINA  
INPUTS  
1
2
3
4
5
6
7
8
CC1  
CC2  
CC3  
CC4  
CC5  
CC6  
CC7  
CC8  
COIL 1  
52/a  
COIL 1  
52/b  
CC1  
CC2  
CC3  
CC4  
9
COMMON 1/8 COMMON 1/4  
COMMON 9/16 COMMON 5/8  
10  
11  
12  
13  
14  
15  
16  
17  
18  
CC9  
CC5  
CC6  
CC7  
CC8  
CC10  
CC11  
CC12  
CC13  
CC14  
CC15  
CC16  
COIL 2  
52/a  
COIL 2  
52/b  
OUTPUTS  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
O1  
O1  
O2  
O3  
O4  
O5  
O6  
O2  
O3  
O4  
O5  
O6  
O7  
O8  
I SENS  
O7  
I SENS  
O8  
FIGURE 3-7 LOCATION OF TERMINALS  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.4.2.  
BOARD OPTION 2  
Option 2 I/O board includes two groups of 4 inputs with one common, in terminals 9 to 10. It also includes 6 auxiliary  
outputs, in terminals 19 to 30 with normally open contacts and two current sensing (latching) outputs.  
Besides, there are 2 groups of inputs for trip circuit supervision. The first group includes two isolated digital inputs,  
terminals 1-2 and 3-4. The second group, symmetrical and identical to the first, is formed by isolated voltage inputs  
15-16 and 17-18.  
Inputs in both groups are wet contacts, this means they need to receive a positive in the terminal labeled as + coming  
from a power supply whose negative is connected to the terminal labelled as -.  
Using voltage detectors and current sensing, it is possible to implement several trip or close circuit supervision  
schemes, as well as protection of the unit output contact.  
In order to implement these schemes, it is not necessary to perform any setting in the unit. Internal functions are  
always operative and provide the following logic operands:  
OPERAND  
DESCRIPTION  
CONTACT  
INPUT_00_08 Active when voltage is detected in terminals 1 - 2 (circuit 1)  
(Va_COIL1)  
CONTACT  
(Vb_COIL1)  
INPUT_00_09 Active when voltage is detected in terminals 3 - 4 (circuit 1)  
INPUT_00_10 Active when voltage is detected in terminals 15 - 16 (circuit 2)  
INPUT_00_11 Active when voltage is detected in terminals 17 - 18 (circuit 2)  
INPUT_00_12 Active if current is detected by sensor in output O7 (F31-F33)  
INPUT_00_13 Active if current is detected by sensor in output O8 (F34-F36)  
INPUT_00_14 Active when continuity is detected in circuit 1  
CONTACT  
(Va_COIL2)  
CONTACT  
(Vb_COIL1)  
CONTACT  
(O7_SEAL)  
CONTACT  
(O8_SEAL)  
CONTACT  
(SUP_COIL1)  
CONTACT  
INPUT_00_15 Active when continuity is detected in circuit 2  
(SUP_COIL2)  
A continuity failure is detected in a circuit when both voltage detectors (Va and Vb) detect lack of voltage during more  
than 500 ms. This function is not influenced by the breaker status.  
These operands can be associated to internal signals (virtual outputs), LEDs or unit outputs, to issue alarm signals or  
to block elements, for example for blocking the Breaker close if an abnormality is detected in the trip circuit.  
Available schemes are as follows:  
1. Without supervision  
2. With current supervision (with seal-in)  
3. With simple voltage supervision  
4. With double voltage supervision  
5. With current and simple voltage supervision (with seal-in)  
6. With current and double voltage supervision (with seal-in)  
20  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
The following lines describe the different types of connection to create each scheme in an easy way. As the  
supervision circuits are identical, we will describe connection examples for the first group. They are also applicable to  
the second group.  
The symmetrical location of digital inputs is an optimization for ensuring a high isolation between groups that,  
belonging to different groups could be connected to separate batteries, and therefore a greater distance between  
circuits is required.  
3.4.2.1. WITHOUT SUPERVISION  
This is a very frequent case, and we must only wire the tripping circuit to terminals 35 and 36, leaving unused  
terminals 34, 15, 16, 17, 18.  
FIGURE 3-8 CIRCUIT WITHOUT TRIPPING CIRCUIT SUPERVISION (A6631F1)  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.4.2.2. WITH CURRENT SUPERVISION (WITH SEAL-IN)  
In this case, as shown on FIGURE 3-9, the current supervision circuit consists in a circuit connected in series with the  
output contact, so that the external circuit is wired to terminals 34 and 36. This supervision circuit includes a low  
impedance reed relay that is activated when the current value exceeds 100 mA, and sends a signal to the main  
microprocessor. This indication can be used to produce a latching of the output relay, so that it will remain closed  
while the circulating current is over 100 mA. For this purpose we don’t need to program any setting, it is enough to  
wire it as shown on FIGURE 3-9.  
With this scheme, in the case of a failure to open from the breaker auxiliary contact, the CIO output relay will not be  
the one to open the tripping coil current, as in this case the contact may result damaged, as it is prepared for opening  
currents around 0.5 A at 125 Vdc.  
This latching or memory function is only guaranteed while the unit is powered.  
FIGURE 3-9 CURRENT SUPERVISION OF THE TRIPPING CONTACT (A6631F2)  
22  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.4.2.3. WITH SIMPLE VOLTAGE SUPERVISION  
FIGURE 3-10 SUPERVISION APPLICATION WITH AUXILIARY CONTACT 52A AND A RESISTOR (A6631F3)  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
INTERNAL STATE  
52 open  
V 52/a  
SUPERVISION  
Ok  
ON  
52 closed  
ON  
Ok  
TRIP  
OFF  
OFF  
Ok if t < 0.5 s  
Ok if t < 0.5 s  
TRIP with 52 open  
There is a possibility to monitor the trip circuit and trip coil continuity. This can be done by monitoring Vdc through the  
output contact when this is open.  
As shown on FIGURE 3-10, when the relay is not tripped, trip contact 35-36 remains open. If the breaker is closed, its  
auxiliary contact 52a is closed. Therefore, a little current is flowing, about 2 mA, through terminals 15 and 16 through  
the voltage detector circuit, which flows through 52/a and the tripping coil 52TC (TC = tripping coil). Current will only  
circulate when there is continuity in the whole circuit, so the complete circuit is monitored, and not only the trip coil.  
This circuit includes auxiliary 52/a as well as the whole wiring between the battery and the relay tripping terminals,  
and between these and the breaker tripping circuit.  
This is the first case shown on the table. With closed breaker, voltage is detected by V 52/a sensor, and this means  
that there is continuity in the supervised circuit.  
In this table, ON means that the voltage detector V52/a is active, detecting voltage presence.  
Status of Involved Elements  
CIRCUIT OUTPUT BREAKER  
Input to F650  
Decision  
OPERAND  
CONTACT  
OPERAND  
CONTACT  
STATUS  
STATUS  
STATUS  
(F35-F36)  
INPUT_00_10  
(Va_COIL2)  
INPUT_00_15  
(SUP_COIL2)  
V 52/a (F15-F16)  
Healthy  
Healthy  
Healthy  
Open  
Open  
52 closed  
52 open  
ON  
ON  
ON  
ON  
Closed  
52 closed  
OFF  
ON (if t < 500 ms)  
OFF (if t > 500 ms)  
Healthy  
Closed  
52 open  
OFF  
ON (if t < 500 ms)  
OFF (if t > 500 ms)  
Faulty  
Faulty  
Faulty  
Faulty  
Open  
Open  
52 closed  
52 open  
52 closed  
52 open  
OFF  
OFF  
OFF  
OFF  
OFF (500 ms delay)  
OFF (500 ms delay)  
OFF (500 ms delay)  
OFF (500 ms delay)  
Closed  
Closed  
24  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
For the second case shown on the table, open breaker, its auxiliary contact 52/a remains open, and current cannot  
flow through it for detecting continuity. In order to correctly monitor the circuit, a resistor must be used, not included in  
the protection, connected in parallel. The value of resistance will be selected so that the V 52/a input circuit minimum  
detection current flows, but not as high as to activate the breaker tripping coil. The figure shows the following  
equation:  
V min – 15  
R = -------------------  
2
Where:  
Vmin  
Is the minimum voltage, in Volts, expected in the battery (e.g. 80% of Vn)  
Resistance, in kilo ohms.  
R
2
2 mA of approximate current flowing through input V 52/a  
As shown in the second case in the table, with an open breaker, as current will flow through R if there is continuity in  
the WHOLE tripping circuit, voltage will be detected in input V 52/a.  
This works correctly in steady state. However, if the breaker trips, while it is opening, the V 52/a input signal can be  
deactivated without this meaning that the circuit is not correct. This is due to the fact that the tripping relay, terminals  
35-36, short circuits input V 52/a temporarily.  
Therefore, if there is a trip signal, it is admitted that no signal will be detected during a period of 1 s to allow the  
breaker to open, and reopen the tripping relay 35-36.  
FIGURE 3-11 shows the possibility of monitoring the circuit only when the breaker is closed. In this case resistance R  
will not be used, but it must be observed in the unit logic, that the corresponding signal CONTACT INPUT_00_15  
(SUP_COIL2), will be activated showing a failure when the breaker is open, and therefore it will be required to  
supervise the continuity failure signalling by the breaker status information.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
FIGURE 3-11 TRIP CIRCUIT AND TRIP COIL SUPERVISION USING AUXILIARY CONTACT 52/A. ONLY WITH  
CLOSED BREAKER (A6631F5)  
26  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
3.4.2.4. WITH DOUBLE VOLTAGE SUPERVISION  
FIGURE 3-12 SUPERVISION APPLICATION WITH AUXILIARY CONTACTS 52A AND 52B (A6631F4)  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE  
INTERNAL STATE  
52 open  
V 52/a  
V 52/b  
SUPERVISION  
ON  
ON  
OK  
OK  
52 closed  
ON  
OFF  
OFF  
ON  
TRIP  
OFF  
OFF  
Ok if t < 0.5 s  
OK  
TRIP with 52 open  
Status of Involved Elements  
Inputs to F650  
Decision  
CIRCUIT OUTPUT  
BREAKER  
STATUS  
OPERAND  
CONTACT  
OPERAND  
CONTACT  
OPERAND  
CONTACT  
STATUS  
STATUS  
(F35-F36)  
INPUT_00_10  
(Va_COIL2)  
V 52/a (15-16)  
INPUT_00_11  
(Vb_COIL2)  
V 52/b (17-18)  
INPUT_00_15  
(SUP_COIL2)  
Healthy  
Healthy  
Healthy  
Open  
Open  
52 closed  
52 open  
ON  
ON  
OFF  
ON  
ON  
ON  
Closed  
52 closed  
OFF  
OFF  
ON (if t < 500 ms)  
OFF (if t > 500 ms)  
Healthy  
Closed  
52 open  
OFF  
ON  
ON (if t < 500 ms)  
OFF (if t > 500 ms)  
Defective  
Defective  
Defective  
Defective  
Open  
Open  
52 closed  
52 open  
52 closed  
52 open  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF (500 ms delay)  
OFF (500 ms delay)  
OFF (500 ms delay)  
OFF (500 ms delay)  
Closed  
Closed  
There is a possibility to monitor the trip circuit continuity not only via its auxiliary contact 52/a, but also with auxiliary  
contact 52/b. This avoids the need to install a resistance in parallel with auxiliary 52/a. The correct connection is  
shown on FIGURE 3-12.  
The circuit works in a similar way to the one described in the previous section, but it uses both supervision inputs 15-  
16 and 17-18.  
The advantage in this case is that circuit supervision with 52 open is more complete, as input V 52/b is used through  
contact 52/b, (that is closed when the breaker is open).  
We must point out that in this scheme, the tripping contact, shown in the example as the CIO trip relay, can be the  
one in the relay (terminals 35 and 36), or be provided by another protection or by the parallel of several protections.  
This provides high flexibility in the use of this circuit.  
The battery voltage can also be monitored, by using one of the standard digital inputs.  
28  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
USER INTERFACES  
4. USER INTERFACES  
4.1.  
SOFTWARE  
CIO units need to be connected to a master unit, either an F650 or an F600. If the master unit is an F650, the CIO  
can be programmed using EnerVista F650Setup program; in case of using an F600 as master unit, the CIO can be  
programmed using GE-CONF software. In both cases, CIO inputs/outputs will be shown as if they were part of the  
master unit, with the same programming options as the master unit I/O.  
EnerVista F650Setup software provides a simple way to configure, monitor and maintain operation of F650 and the  
connected CIO unit. Please refer to the F650 user manual for a more detailed reference about EnerVista F650Setup.  
In the same way, please refer to GE-CONF software manual for details about programming a CIO unit connected to  
an F600 master unit.  
4.2.  
FRONT INDICATORS  
CIO units incorporate 2 LEDs on the front, one of them indicates that the unit is powered, and the other indicates  
activity on the CAN bus.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
USER INTERFACES  
30  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
5. INPUT/OUTPUT MODULES DESCRIPTION  
5.1.  
CIRCUIT SUPERVISION AND CONTACT SEAL-IN CIRCUITS  
5.1.1.  
CIRCUIT SUPERVISION  
CIO units can include type 2 boards. This type of board includes 4 voltage detectors for implementing tripping or  
opening circuit supervision control logics.  
5.1.2.  
CONTACT SEAL-IN  
The current seal-in circuit is used for verifying the current condition in a circuit during the time that the tripping contact  
remains closed. If the current in the tripping circuit is maintained over 100 mA, the function is sealed independently of  
the status of the function that caused the trip.  
This current seal-in function in tripping circuits is mainly used in applications where auxiliary contacts 52/a (in charge  
of cutting the current in the tripping circuit) are very slow. This may cause that, once the function that produced the  
trip is reset, the relay contact will open before the breaker auxiliary 52/a, even if the time delay of the first has expired.  
By using this function, we prevent the relay contact from cutting the current (basically inductive and high) from the  
tripping circuit, which could cause damage to the unit, as these currents exceed the nominal breaking characteristics.  
The circuit and the current threshold of the function are as follows:  
100 mA min  
I
FIGURE 5-1 CURRENT SUPERVISION  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
5.2.  
CONTROL SETTINGS FOR INPUTS/OUTPUTS  
This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the  
master unit communication software, EnerVista F650Setup for F650, or GE-CONF for F600.  
5.2.1.  
INPUT/OUTPUT BOARDS SETTINGS  
Settings relative to I/O boards are described in table 5-1:  
TABLE 5-1 I/O BOARD SETTINGS  
SETTING  
HMI  
DEFAULT  
RANGE  
STEP  
16 INP + 8OUT  
I/O board type (available only for  
CIO modules)  
8 INP + 8OUT +  
SUPV  
I/O Board_X Type  
NONE  
N/A  
NONE  
Input activation voltage threshold  
Group A  
Voltage Threshold A_X  
Voltage Threshold B_X  
80  
80  
0 – 255 V  
1 V  
1 V  
Input activation voltage threshold  
Group B  
0 – 255 V  
Debounce time Group A  
Debounce time Group B  
Debounce Time A_X  
Debounce Time B_X  
15  
15  
1 – 50 ms  
1 – 50 ms  
1 ms  
1 ms  
POSITIVE-EDGE  
NEGATIVE-EDGE  
POSITIVE  
Input type  
Input Type_X_CCY  
POSITIVE  
N/A  
NEGATIVE  
Delay Input  
Time_X_CCY  
Input signal time delay  
Output logic type  
0
0 – 60000 ms  
1 ms  
N/A  
POSITIVE-  
NEGATIVE  
Output Logic_X_0Z  
Output Type_X_0Z  
POSITIVE  
NORMAL  
PULSE  
Output type  
Output pulse length  
Being:  
NORMAL  
0
N/A  
LATCH  
Pulse Output  
Time_X_0Z  
0 – 60000 ms  
1 ms  
X
I/O board name, depending on the CIO model.  
For the I/O board selection in the relay model, associated digits to each board type are as follows:  
ASSOCIATED DIGIT  
F650PC BOARD  
SETTINGS  
BOARD TYPE  
0
1
2
NONE  
None  
Mixed  
16 INP+ 8OUT  
8 INP +8 OUT +SUPV  
Supervision  
32  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
CCY Is the name used for inputs in I/O boards  
Mixed, 16 digital inputs: CC1….CC16  
Supervision: 8 digital inputs: CC1,..., CC8  
0Z  
Is the name used for the different outputs in I/O boards, 8 outputs available for any of the two types of board  
(01,…., 08)  
Description of I/O board settings is as follows:  
General Board Settings:  
I/O Board Type: Selection of the I/O board type.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
Settings relative to Inputs:  
Input Activation Voltage Threshold: This value can be from 0 to 255 volts. There is a single setting for all inputs in  
the same group (inputs sharing the same common). In mixed and supervision boards there are two groups of inputs,  
called A and B.  
Debounce Time: This is the debounce time set for inputs (1 to 50 ms). The debounce time is the time window for  
input filtering. If an input suffers a change of level that lasts less than this set time, the change will not be considered.  
There is a single setting for all inputs in the same group.  
Delay Input Time: This is the delay applied to the input signal; the default value is zero, meaning no delay; the  
setting range is 0 to 60000 milliseconds (1 minute). This setting is used in slow switchgear applications.  
This is not a grouped setting; there is a different setting for each input. It is important not to confuse this delay input  
time with the debounce time used for filtering undesired transients in the input signal. The Debounce time is always  
added to the delay input time.  
Input Type: Type of logic associated to the physical input. Possible settings are, positive and negative.  
Positive and Negative settings correspond to signals that are activated or deactivated with the input level, considering  
the delay setting. Positive-edge, and Negative-edge settings correspond to signals that are activated with the change  
of the input signal; in this case, the Delay Input Time will not be considered, only the Debounce Time; this edge  
signals are deactivated automatically after one PLC scan cycle. FIGURE 5-2 shows the types of signals associated to  
the different input configuration types.  
FIGURE 5-2. INPUT LOGIC  
34  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
Settings relative to Outputs:  
Output Logic_0X _XX: Type of logic applied to outputs. Possible values are positive and negative. The default  
value is positive.  
Output Type_0X _XX: Type of output adjusted. Possible values are normal, latched or pulse; the default value is  
Normal.  
Pulse Output Time_0X _XX: This is the output pulse length in case the output type is selected to be pulse; the  
default value is 10000 ms.  
Output Logic: Type of logic applied to outputs; possible values are Positive and Negative; the default value is  
Positive. Depending on the type of setting selected, the physical output will be in the same direction (positive) or  
opposite (negative) the output activation command.  
Output Type: This is the set output type. Possible values are normal, latched or pulse; the default value is Normal.  
Normal type follows the activation command. Pulse type delays the time, according the Pulse Output Time setting.  
Latched type remains active after the activation command. The physical output reset when it is configured as latched  
can be performed using a deactivation command. Such command must be configured at Setpoint > Relay  
Configuration > Outputs > Contact Output Reset”.  
Pulse Output Time: This is the output pulse length, applicable only to signals set as pulse type; the default value is  
10000 ms and the setting range is 0 to 60000 ms (1 minute).  
FIGURE 5-3 shows the types of signals associated to the different output configuration types.  
FIGURE 5-3 OUTPUT LOGIC.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
5.2.2.  
INPUTS/OUTPUTS STATUS  
Signals associated to I/O boards are divided in several groups:  
Input activation signals (Contact Inputs):  
Contact input activation signals can be obtained at Actual > Status > Contact Inputs > Board X, being X the  
corresponding I/O board. Depending on the I/O board, inputs are represented as follows:  
TABLE 5-2: INPUT STATUS  
INPUT STATUS  
(X: board F, G, H, J)  
MIXED BOARD  
(TYPE 1)  
SUPERVISION BOARD  
(TYPE 2)  
CONT IP_X_CC1  
CC1  
CC1  
CONT IP_ X _CC2  
CONT IP_ X _CC3  
CONT IP_ X _CC4  
CONT IP_ X _CC5  
CONT IP_ X _CC6  
CONT IP_ X _CC7  
CONT IP_ X _CC8  
CONT IP_ X _CC9  
CONT IP_ X _CC10  
CONT IP_ X _CC11  
CONT IP_ X _CC12  
CONT IP_ X _CC13  
CONT IP_ X _CC14  
CONT IP_ X _CC15  
CONT IP_ X _CC16  
CC2  
CC2  
CC3  
CC3  
CC4  
CC4  
CC5  
CC5  
CC6  
CC6  
CC7  
CC7  
CC8  
CC8  
CC9  
Va_COIL1  
Vb_COIL1  
Va_COIL2  
Vb_COIL2  
O7_SEAL  
O8_SEAL  
SUP_COIL1  
SUP_COIL2  
CC10  
CC11  
CC12  
CC13  
CC14  
CC15  
CC16  
The operation logic for supervision signals (board type 2) is detailed in section 3.3.2. in this manual.  
36  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
Contact Outputs activation signals:  
These are the signals that mark the physical activation of contact outputs, independently from their associated logic.  
They can be obtained at Actual > Status > Contact Outputs > Board X, being X the corresponding I/O board. The  
output name is the same both for the mixed and supervision boards; the difference will be the symbol associated to  
the slot where the board is located in the unit (slot F, G, H or J).  
TABLE 5-3 CONTACT OUTPUT STATUS  
CONTACT OUTPUT STATUS  
(X: board F, G, H, J)  
CONT OP_X_01  
CONT OP_X_02  
CONT OP_X_03  
CONT OP_X_04  
CONT OP_X_05  
CONT OP_X_06  
CONT OP_X_07  
CONT OP_X_08  
Contact Output Activation Signals (Contact Output Operates):  
These are the logic signals associated to contact outputs that produce their activation. Actual > Status > Contact  
Outputs Operates > Board X, being X the corresponding I/O board. The name of these outputs is the same for the  
mixed and supervision boards, the only difference will be the slot where the output is located in the relay (slot F, G, H  
or J). These signals can be configured at Setpoint > Relay Configuration > Outputs > Contact Output Operate.  
TABLE 5-4 CONTACT OUTPUT OPERATES  
CONTACT OUTPUT  
OPERATES  
(X: board F, G, H, J)  
CONT OP OPER_X_01  
CONT OP OPER_X_02  
CONT OP OPER_X_03  
CONT OP OPER_X_04  
CONT OP OPER_X_05  
CONT OP OPER_X_06  
CONT OP OPER_X_07  
CONT OP OPER_X_08  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I/O MODULES DESCRIPTION  
Contact Output Reset Signals (Contact Output Resets):  
These are the logic signals associated to the contact output reset, which produce the reset of those signals previously  
configured as Latched. The status of these signals is obtained at Actual > Status > Contact Outputs Resets >  
Board X, being X the corresponding I/O board. The name of these outputs is the same for the mixed and supervision  
boards, the only difference will be the slot where the output is located in the relay (slot F, G, H or J). These signals  
can be configured at Setpoint > Relay Configuration > Outputs > Contact Output Reset  
TABLE 5-5 CONTACT OUTPUT RESETS  
CONTACT OUTPUT RESETS  
(X: board F, G, H, J)  
CONT OP RESET_X_01  
CONT OP RESET_X_02  
CONT OP RESET_X_03  
CONT OP RESET_X_04  
CONT OP RESET_X_05  
CONT OP RESET_X_06  
CONT OP RESET_X_07  
CONT OP RESET_X_08  
IO Board Status:  
These signals are associated to the different I/O boards. There are internal signals that provide information about the  
status of these boards, indicating whether there is any anomaly in the board, or whether the board is not available in  
the relay according to the relay model. This information can be accessed at Actual > Status > IO Board Status.  
TABLE 5-6 I/O BOARD STATUS  
BOARD STATUS  
BOARD F STATUS  
BOARD G STATUS  
BOARD H STATUS  
BOARD J STATUS  
38  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCEPTANCE TESTS  
6. ACCEPTANCE TESTS  
6.1.  
VISUAL INSPECTION  
Verify that the relay has not suffered any damage during transportation, and that all screws are correctly fixed, and all  
relay terminal boards are in good condition.  
6.2.  
GENERAL CONSIDERATIONS ON THE POWER SUPPLY NETWORK  
All devices running on AC current are affected by frequency. As a non-senoidal wave is the result of a fundamental  
wave plus a series of harmonics from this fundamental wave, it can be deducted that devices running on AC current  
are influenced by the applied waveform.  
For a correct testing of devices running on AC current, it is fundamental to use a current and/or voltage senoidal  
waveform. The pureness of a senoidal wave (lack of harmonics) cannot be expressed specifically for a specific  
device. However, any relay incorporating sintonized circuits, R-L and R-C circuits, will be affected by non-senoidal  
waveforms.  
These devices respond to the voltage waveform in a different way to the majority of AC current voltmeters. If the  
power supply network used for the testing contains wide harmonics, the voltmeter and relay responses will be  
different.  
When the device is tested, a power supply network with no harmonics in its waveform must be used.  
It is important to point out that the accuracy with which the test is performed depends on the network and on the  
instruments used. Functional tests performed with unsuitable power supply network and instruments are useful to  
check that the device operates properly and therefore its operating characteristics are verified in an approximate  
manner.  
The following sections detail the list of tests for verifying the device functionality.  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCEPTANCE TESTS  
6.3.  
ISOLATION TESTS  
During all tests, the screw located on the rear of the relay must be grounded.  
For verifying isolation, independent groups will be created, and voltage will be applied as follows:  
2000 RMS volts will be applied progressively among all terminals in a group, short-circuited between them  
and the case, during one second.  
2000 RMS volts will be applied progressively between groups, during one second.  
WARNING: No communication circuit shall be tested for isolation.  
Groups to be created will depend on the type of modules included in the CIO, selectable according to the model.  
The following table shows the different groups depending on the module type:  
SOURCE 1:  
I/O OPTION 1  
I/O OPTION 2.  
G1: K10, K18  
G2: K13, K14, K15  
G1: (Inp. 1)1…9  
G2: (Inp. 2) 10…18  
G3: (Out.) 19…36  
G1 (Spv 1): 1...4  
G2 (Inp. 1): 5...9  
G3 (Inp. 2): 10…14  
G4 (Spv 2): 15...18  
G5 (Out.): 19...30  
G6 (Out.): 31…36  
6.4.  
INDICATORS  
Feed the unit and verify that the Ready LED lights up.  
Communicate with the master unit and verify that the communication LED lights up showing activity on the CAN bus.  
6.5.  
POWER SUPLY TESTING  
Feed the unit to the minimum and maximum voltage. For each voltage value, verify that the alarm relay is activated  
when there is voltage, and it is deactivated when there is no feed. If the power supply source incorporates AC feed,  
this test will be performed also for VAC.  
Voltage values to be applied will be the ones indicated below according to the relay model:  
SUPPLY  
V min.  
88 Vdc  
V max.  
HI  
110-250 Vdc  
120-230 Vac  
300 Vdc  
250 Vac  
96 Vac  
LO  
24-48 Vdc  
20 Vdc  
57.6 Vdc  
40  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCEPTANCE TESTS  
6.6.  
COMMUNICATION WITH THE MASTER UNIT  
1. Connect the master unit to the CIO. Verify that the BUS LED blinks indicating communication between both  
units.  
2. Verify, using the master unit Setup program, that the CIO boards setting options are available. For example,  
using an F650 as master unit, verify in EnerVista F650 Setup, that the "Actual > Inputs/Outputs > I/O  
Board Status > Board H Status" and "Actual > Inputs/Outputs > I/O Board Status>Board J Status"  
appear as active.  
6.7.  
INPUTS AND OUTPUTS  
During all tests, the screw on the rear of the relay must be grounded.  
6.7.1.  
DIGITAL INPUTS  
During this test, the user will determine the activation/deactivation points for every input in the relay for the set voltage  
value of 30 Volts.  
Verify that the error does not exceed +/- 10% (+10% on activation, -10% on deactivation)  
Default board settings for the input test are as follows:  
Settings/Control Elements/Inputs Outputs/Board X  
I/O Board Type 1  
Voltage Threshold A_01 30 V  
Voltage Threshold B_01 40 V  
Debounce Time A_01  
Debounce Time B_01  
Input Type 01 00 (CC1)  
...  
15 ms  
15 ms  
POSITIVE  
...  
Input Type 01 15 (CC16) POSITIVE  
The inputs test is completed by groups of 8 inputs, as this type of board has 2 groups of 8 inputs with the same  
common. For the first 8 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 8  
inputs, the setting is Voltage Threshold B.  
Inputs (or contact converters, CC1 – CC15) must also be set to POSITIVE.  
I/O Board Type 2  
Voltage Threshold A_01 30 V  
Voltage Threshold B_01 40 V  
Debounce Time A_01  
Debounce Time B_01  
Input Type 01 00 (CC1)  
...  
5 ms  
5 ms  
POSITIVE  
...  
Input Type 01 07 (CC8)  
POSITIVE  
GEK-106465A  
CIO Remote CAN Digital I/O Module  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCEPTANCE TESTS  
The inputs test is completed by groups of 4 inputs, as this type of board has 2 groups of 4 inputs with the same  
common. For the first 4 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 4  
inputs, the setting is Voltage Threshold B.  
Inputs (or contact converters, CC1 – CC8) must also be set to POSITIVE.  
6.7.2.  
CONTACT OUTPUTS  
The correct activation of every output will be verified.  
For every output, activation command of a single contact must be given, and then verify that only that contact is  
activated (Setpoint/Force IO)  
For switched contacts, the change of state of both contacts shall be verified.  
6.7.3.  
CIRCUIT CONTINUITY SUPERVISION INPUTS  
Supervision inputs will be tested as normal inputs, revising the voltage level, which will be 19 Volts.  
Coil 1:  
Apply 19 Vdc to both 52/a and 52/b ”Coil 1” circuit supervision inputs and verify that they are activated.  
Apply -19 Vdc to both 52/a and 52/b ”Coil 1” circuit supervision inputs and verify that they are activated.  
Remove voltage from both inputs and verify that it takes them 500 ms to change state (deactivate).  
Coil 2:  
Apply 19 Vdc to both 52/a and 52/b ”Coil 2” circuit supervision inputs and verify that they are activated.  
Apply -19 Vdc to both 52/a and 52/b ”Coil 2” circuit supervision inputs and verify that they are activated.  
Remove voltage from both inputs and verify that it takes them 500 ms to change state (deactivate).  
6.7.4.  
LATCHING CIRCUITS  
Send a closing command to the latched contact.  
Make circulate a current of 200 mA through the contact in series with the sensing terminal.  
Send an opening command and verify that the contact does not open.  
Interrupt current and check than the contact is released.  
200  
I
Repeat the test for the other latched contact  
42  
CIO Remote CAN Digital I/O Module  
GEK-106465A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Eagle Home Products Air Compressor Portable Electric Gas Compressor User Manual
Echo Trimmer 670 200 User Manual
Eclipse Fujitsu Ten Car Stereo System CD4000 User Manual
Eiki CRT Television LC XS25 User Manual
Exmark Lawn Mower 0 User Manual
Extron electronic TV Cables DTP T HWP 231 D User Manual
Extron electronic TV Cables RG6 User Manual
Frigidaire Dehumidifier 2020264A0525 User Manual
Generac Power Systems Switch 004635 2 User Manual
GE Water Dispenser FQSLF User Manual