1 - Introduction
1.1
Introduction
The General Electric (GE) Digital Energy NetPro 19” UPS, a truly on-line uninterruptible power supply,
protects your equipment from all forms of power interference, including complete power failures.
1.2
Safety Rules
x CAUTION: RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The appliance
outlets may be electrically live, even when the UPS is disconnected from the mains.
x The UPS contains potentially hazardous voltages. Do not open the UPS, there are no user
serviceable parts inside.
x All maintenance and service work, except for replacement of the batteries, should be
performed by qualified service personnel.
1.3
Transport / Storage
x No liability can be accepted for any transport damage when the equipment is shipped in non-
original packaging.
x During transport the battery drawer must either be removed or fixed with two screws at the rear
side of the UPS (A, fig. 1).
x Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature
must be within -20 +45 qC. If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 25°C.
x If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Be sure that the battery drawer is connected to the UPS. Subsequently connect the unit to a wall
outlet and recharge the batteries for 24 hours:
-
-
if the storage temperature is within -20 and +30°C: every 3 months,
if the storage temperature is within -20 and +45°C: every month.
Please note that with completely discharged batteries the UPS will not start at all. External
charging or replacement of the batteries will be necessary.
2 - Installation
The shipping box contains a NetPro 19” UPS, two IEC male-female power cords, a data cable, a CD
ROM and this manual. Inspect the UPS for damage after unpacking. If any damage is present please
immediately notify the carrier and place of purchase.
IMPORTANT:
Before making any connection and switching on the NetPro 19” UPS, please check the following
conditions:
x
x
your mains supply is 220 - 240 Volts and 50 Hz (if the mains frequency is 60Hz, the output
frequency of the UPS can be changed, see section 3.4), and
the total power demand of the connected equipment does not exceed the rated output power of
the NetPro 19” UPS (indicated on the rating label).
WARNING
Connecting the UPS output to neutral or ground will result in a malfunctioning UPS.
2.1
Installation Rules
x The UPS is intended to be used in normal domestic and office situations.
x Protect the UPS, according to the wiring rules, with a 16A D-type fuse.
x The UPS must be powered from a single phase grounded wall outlet. Do not use extension
cords.
x Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.
x The ambient temperature should not exceed 40qC. Optimal battery lifetime is obtained if the
ambient temperature does not exceed 30qC.
x It is important that ventilation air can move freely around and through the unit. Do not block the air
vents.
x Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.
x Be careful when connecting laser printers: be sure that the demanded power does not exceed the
capacity of the UPS.
x The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.
OPM_NPE_19X_600_1K5_2GB_V030
2
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
2.2
Installation Procedure
A
B
4
5
1
6
2
3
fig. 1
1.
2.
Remove the transport screws (A, fig. 1) and store them in the free holes (B, fig.1). Mount the
NetPro 19” UPS in the 19” rack. The module must be supported by mounting rails, do not mount
it by using the front brackets only. The front brackets allow mounting of handles (not included).
Make sure that the air vents in the side panels of the module are not blocked by the mounting
rails or the side panels of the 19” rack.
3. 1000VA model only:
Battery extension module(s) can be installed to
increase the battery runtime. Connect the DC
2
connector of the battery module (7, fig. 2) to the DC
socket of the UPS (2, fig. 1/2). You will hear a click
7a
when the cable is properly installed. Block the DC
connector: install the small locking plate (7a, fig. 2)
that came with the battery module, and fasten it with
the screw provided. Using the DC connector of the
battery module (not shown) you can install a second,
third, etc. module. See also section 5.1.
7
4. Switch off your computer, and unplug it from the
socket-outlet.
fig. 2
5. Disconnect the power cord from the computer
(rating 250Vac/10A) and connect this cord to the
mains input socket (5, fig. 1) of the UPS. See fig. 4.
6. Using the output cord(s) provided, connect the
computer(s) to the appliance outlet(s) (1, fig. 1) of
the UPS. Spread the loads over the appliance
outlets as equally as possible. If you use a
distribution box to connect more than one appliance
per outlet, please note that the maximum AC-current
rating of each appliance outlet is 10Amps. See fig. 3.
fig. 3
7. Connect the mains cord of the UPS to a working,
grounded AC wall socket outlet. See fig. 4. The
green LED 'on' (8, fig. 6) will blink now: mains power
is available and the batteries are charging. If the
LED does not blink but illuminates continuously
instead, press ‘0’ for one second.
fig. 4
8.
9.
For best results, allow the UPS to recharge the batteries during a period of approx. 2 hours. It is
acceptable to use the UPS without first charging the battery, but the runtime may be reduced.
For advanced communication possibilities, the RS232 interface port (6, fig. 1) can be connected
to a computer system and/or optional interface cards (3, fig. 1) can be added. See chapter 4.
OPM_NPE_19X_600_1K5_2GB_V030
3
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
3 - Operation
Please refer to figure 6.
3.1
Start-up
3.1.1 Start-up, mains available
1
2
Press keypad 'I' (14, fig. 6) briefly; LED ‘on’ (already blinking) will illuminate continuously now.
The equipment connected to the UPS can now be switched on.
3.1.2 Start-up, mains not available
If the mains input is absent (power cord not connected, or mains failure):
Press keypad 'I' until the buzzer sounds.
1
The LEDs 'on' and 'on battery' (13, fig. 6) will illuminate. The UPS operates on battery: it
discharges the batteries.
3.2
Use: Normal Operation
3.2.1 Normal operation conditions:
x
x
x
x
the mains supply is present,
the UPS is on,
the load does not exceed the capacity of the UPS and
the operating temperature is below alarm level
3.2.2 Load indication (fig. 5)
1
2
During normal operation, press keypad 'I' briefly.
Yellow LEDs will blink during 3 seconds, the number is load
dependent (in case of overload LED 'alarm' (9, fig. 6) blinks as well).
fig. 5
3.2.3 Auto-off (no-load shutdown)
If this function is activated, the UPS will switch off during a mains failure when the load is less
than 5% of the maximum load. In this way unnecessary discharging of the batteries is avoided.
The unit will automatically turn on again when mains power is restored. The default setting of the
no-load shutdown function is: activated. Changing of the setting is described in 3.4.
3.2.4 Automatic bypass switch
The UPS is equipped with an automatic bypass switch. This switch automatically transfers the
load to the mains if the UPS is unable to deliver the demanded output power due to overload or
overtemperature. The UPS will switch back to normal operation when the overload has been
removed or the temperature has dropped below alarm level.
If a power failure occurs during bypass operation, the UPS will switch to battery operation and
eventually, when the batteries are depleted, output power is lost. If the UPS functions under
overload or overtemperature conditions it may not be able to protect the load.
See also 3.3.6 and 3.4.
3.2.5 Switching off
1
Press keypad ‘0’ (15, fig. 6) for 1 second. If the UPS is switched off the output will always be
absent for a few seconds to ensure that the connected equipment is able to reboot.
If electric isolation is required, unplug the power cord from the wall outlet.
2
OPM_NPE_19X_600_1K5_2GB_V030
4
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
3.3
Use: Status and Alarm Indications
o
!
status indications
low priority alarms
:
:
:
the operating mode
abnormal operating situations
!! high priority alarms
situations in which the actual
output voltage of the UPS is no
longer guaranteed; immediate
action should be taken
8
9
10
11 12 13 14
15
Indicators on front panel
on by- progr.
repl.
batt.
on
batt.
on
alarm
buzzer*
pass
shutd.
Situation
o
o
!
Charger on (3.3.1)
- - - - -
- - - - -
fig. 6
Normal operation (3.3.2)
On battery (3.3.3)
- - - - -
1x/8 s.
- - - - -
1x/s.
!!
!!
!
Battery low (3.3.4)
On bypass (3.3.5)
- - - - -
- - - - -
- - - - -
1x/s.
- - - - -
- - - - -
1x/8s.
Bypass out of limits
(3.3.6)
- - - - -
1x/s.
!!
!!
Overload (3.3.7)
- - - - -
- - - - -
- - - - -
1x/s.
High temperature (3.3.8)
Replace battery (3.3.9)
!
- - - - -
1x/8s.
o
Progr. shutdown
pending (3.3.10)
- - - - -
o
Progr. shutdown in
progress (3.3.10)
Operating modes and corresponding indications, see 3.3.1. – 3.3.10.
- - - - = intermitting
= continuous
*
= resettable: press push button ‘I’ > 2 secs.
OPM_NPE_19X_600_1K5_2GB_V030
5
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
3.3.1 Charger on
The batteries are charging, see 2.2 step 7.
3.3.2 On line: normal operation
See 3.2.1.
3.3.3 On battery
The UPS uses the energy stored in the batteries: see chapter 7 ‘Batteries - runtime’.
The UPS will shutdown
x
x
x
after the batteries have been discharged (automatic restart), or
if keypad 'O' is pressed (restart via front panel required) or
if a 'UPS shutdown' command is given by the computer
(restart via front panel required).
Runtime indication (fig. 7)
During battery operation, press keypad 'I' briefly. The 4 yellow LEDs
indicate during 3 seconds the remaining runtime for the actual load.
fig. 7
3.3.4 Battery low (end of runtime)
The batteries are nearly discharged: the remaining runtime is less than 2 minutes. Controlled
shutdown of any computer equipment is absolutely necessary at this point.
If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes
after the 'battery low' alarm started. If only part of the output capacity of the UPS is used this
period can be longer, with aged batteries this period can be shorter.
When the batteries are fully discharged, the UPS is no longer able to power the connected
equipment.
3.3.5 On bypass
The bypass switch connected the load directly to the mains supply due to either overload or
overtemperature.
If keypad 'I' is momentarily pressed, the 4 yellow LEDs function during 3 seconds as a load
indication. See also 3.2.2. If 4 yellow LEDs and the red LED illuminate, bypass operation is
caused by an overload. If only yellow LEDs illuminate (the red LED is off) during load indication,
bypass operation is caused by overtemperature. Take appropriate measures: reduce load and/or
temperature.
3.3.6 Bypass out of limits
The mains voltage or mains frequency are outside bypass input tolerance but inside UPS input
tolerance (see chapter 7). Bypass operation is inhibited: if for whatever reason the UPS is not
able to deliver the required output, output power is lost. If the input frequency is often out of
tolerance – during which bypass operation is inhibited and an alarm is generated – it may be
useful to disable the bypass function after which the unit operates as a UPS without automatic
bypass switch. See 3.4.
3.3.7 Overload
The demanded power exceeds the normal capacity of the UPS. If keypad 'I' is momentarily
pressed to obtain a load indication all yellow LEDs will blink, and the red LED will remain blinking.
The alarm occurs when the load is > 100%. If the load exceeds 150% the UPS will immediately
switch to bypass, assuming that the conditions for a transfer to bypass are fulfilled.
If an overload condition between 110-150% persists, the UPS will eventually also switch to
bypass operation.
During an overload the UPS may automatically switch off within a few minutes (load dependent)
and output power is lost:
x
x
x
if a transfer to bypass is inhibited (see 3.3.6), or
if the bypass function has been disabled (see 3.4), or
if the UPS operates on battery (see 3.3.3).
To avoid these problems, be absolutely certain that the power demands of the protected
equipment are within the limits of the UPS.
OPM_NPE_19X_600_1K5_2GB_V030
6
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
3.3.8 High temperature
The LED Indication is the same as during overload (see 3.3.7), but if keypad 'I' is momentarily
pressed to obtain a load indication the red LED will go out.
Overtemperature can be caused by:
x
x
x
extreme environmental temperature,
lack of proper ventilation,
overload situation.
Take appropriate measures; if the temperature is allowed to rise further the UPS will switch to
bypass operation (if allowed). If bypass operation is inhibited, the unit will switch off and output
power is lost.
3.3.9 Replace battery
Either the batteries are almost chemically worn out or the battery wiring, including the battery
fuse, is faulty. If the batteries are aged, they must be replaced as soon as possible to ensure full
protection for your equipment (see 6.2). Perhaps the 'replace battery' alarm occurs after a test
which you started immediately after installation or after a power failure. In this case the alarm may
be incorrect as the batteries have been (partly) discharged during transport or storage or during
the power failure. Allow the UPS to recharge the batteries. See also 3.5.
3.3.10 Programmed shutdown
The UPS monitoring software allows you to program a 'sleep period' of the UPS by sending two
commands to the UPS:
x
x
shut down after # minutes (blinking LED), and subsequently:
shut down during # hours (continuous LED).
During the 'sleep period' the UPS is not completely switched off as it has to keep track of the
remaining sleep time. However, if a mains failure occurs during the sleep period and the battery
capacity eventually drops below 80% of the normal capacity, the UPS will automatically switch off
in order to save battery power. When the mains returns the UPS will start up automatically. The
programmed sleep time however is lost.
The programmed shutdown in progress can be cancelled:
x
x
press keypad 'I' for at least 5 seconds to cancel shutdown and switch UPS on.
press keypad '0' for at least 5 seconds to cancel shutdown and switch UPS off.
3.4
Use: Setup Mode
The setup mode can only be entered if the UPS is connected to a live wall outlet and switched off
(LED 'on' blinks).
Press keypads 'O' and 'I' simultaneously. Press 'O' before 'I', otherwise the unit will be switched
on. Three yellow LEDs can illuminate:
LED is
LED
indicating
on*
off
ꢀ 'on bypass'
ꢀ 'progr. shutdown'
ꢀ 'replace battery'
: the bypass switch is
: the no-load shutdown is
: the output frequency is
active
active
50 Hz
not active
not active
60Hz
* = default
1
2
Scroll through the three functions with keypad 'I', the one selected blinks.
Toggle the setting of the selected function by pressing 'O' during approx 1 sec. (LED does not
blink anymore)
3
Store the new settings and leave the setup mode by pressing 'O' and 'I' simultaneously.
NOTE:
The unit can be used as a frequency converter: the input frequency range is 45-66Hz, the
output frequency is selectable 50/60Hz. If the unit is used as a frequency converter, the
bypass function is no longer available. As a result an audible alarm will be generated
continuously (see 3.3.6). To avoid this, we advise to disable the bypass.
WARNING:
Changing of the output frequency can cause severe damage of equipment
connected to the appliance outputs of the UPS: Be sure that the new frequency is
suitable for the connected equipment!
OPM_NPE_19X_600_1K5_2GB_V030
7
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
3.5
Battery Management
Maximum battery life and reliability are obtained by the following features:
x
Quick battery test
The quick battery test checks whether the batteries and their wiring are healthy. If a quick battery
test shows that the batteries are close to being worn out, a 'replace battery' alarm will be
generated (see 3.3.9). The batteries must be replaced as soon as possible (see 6.2).
Automatic battery test
The NetPro 19” UPS conducts periodic automatic battery tests:
x 5 hours after manual switch-on
x 5 hours after return of mains following any power failure, and
x 30 days from the last battery test
Manual battery test
A quick battery test can be initiated manually through UPS software, via the RS232 Interface
Port. For details please refer to the manual of your monitoring software.
NOTE: If the test is started manually immediately after installation or after a power failure,
the UPS may generate a false 'replace battery' alarm as the batteries have been (partly)
discharged during transport/storage or during the power failure.
x
Deep battery test
A deep battery test, to be initiated through the UPS software via the RS232 port, checks the
actual battery capacity in order to ensure accurate runtime prediction. During a deep battery test
the batteries will be discharged until 'battery low' alarm level. Please note that immediately after a
deep battery test the expected runtime is very short: allow the UPS to recharge its batteries. For
details please refer to the manual of your UPS software.
x
x
Temperature compensated battery charging
This feature adjusts the battery charge voltage to the ambient temperature. As a result poor
charging of the batteries under low temperature conditions and overcharging of the batteries
under high temperature conditions are avoided.
Load dependent battery-end-voltage
The allowable final battery voltage depends on the discharge current: the higher the current, the
lower the 'end-of-discharge' battery voltage. In this way maximum battery capacity is obtained
without overdischarging. Overdischarging would result in shortened service life and failure to
recover normal capacity.
x
x
Charger off at end of charge
Only charging when necessary, increases battery lifetime.
Automatic boost charge
This feature reduces the battery recharge time considerably: totally depleted batteries will be
recharged to 90% in approx. 1.5 hours, provided that discharging took place at 100% load.
OPM_NPE_19X_600_1K5_2GB_V030
8
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
4 - Communication
4.1
RS232 Port (fig. 8)
The RS 232 Port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communication
between the UPS and the computer (UPS software required). The interface port is operative as soon as
the mains power cord is plugged into a live wall outlet, even if the UPS is switched off.
We strongly recommend to use only original GE Digital Energy software products in combination with
the interface port.
5 = COMMON
8 = UPS CONNECTED
Pin # Function
fig. 8
MAINS FAILURE
1
2
3
4
5
6
7
8
9
RS232 input (UPS shutdown)
RS232 output
General alarm1)
Plug and Play
Common
Bypass active
Battery low
5
9
4
8
3
7
2
6
1
DC
PnP
RS232
GENERAL ALARM
BATTERY LOW
BYPASS ACTIVE
UPS connected
Mains failure
DC
DATA FROM
UPS
RS232
PORT
RS232
DATA TO UPS
DC
RS232
1)
REMOTE UPS
SHUT DOWN
Active if the output voltage of the UPS is no longer
guaranteed due to other circumstances than already
indicated by pin 6-7-9:
MAX: +48V 100mA
-
Output converter overload
-
-
-
-
Overtemperature (pre-)alarm
High charger voltage
Bypass out of limits
Inverter shutdown (due to inverter failure or batt. failure)
4.2
Relay Interface Card (option)
The card is equipped with potential free change-over contacts for the following alarms:
•
•
•
•
mains failure
general alarm
battery low
bypass active
For more information please refer to the user manual that comes with the interface card.
4.3
SNMP Interface Card (option)
This card allows the data interface to be connected directly to an Ethernet network.
For more information please refer to the user manual that comes with the interface card.
OPM_NPE_19X_600_1K5_2GB_V030
9
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
5 - Optional Features
Apart from the options described in 4.2 and 4.3 the following options are possible:
5.1
Extended Runtime (NetPro 19” 1000)
Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this
case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of the
available runtime (please contact your dealer). Dependent of the charge condition of the new batteries the
new runtime calculations may temporarily be unreliable.
The additional batteries increase the recharging time for the unit, all other operational information is the
same as for standard models. It is not allowed to connect an external charger to the UPS!
5.2
PowerFLAG SerVICe Box for Modem Connection
If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem,
a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial in
and check the status of the UPS to perform remote diagnostics. This way service costs, specially in
remote areas, can be reduced considerably.
6 - Maintenance
6.1
General
The UPS is virtually maintenance free: take care of proper environmental conditions and keep air
inlets/outlets free of dust. Please read 2.1.
6.2
Batteries
6.2.1 General
The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the
number of discharge cycles.
As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is performed
regularly to ensure failsafe operation (see section 3.5). When the condition of the battery is critical, a
'replace battery' alarm will be activated (see 3.3.9). Replace the batteries as soon as possible. See 6.6.2.
NOTE: under certain circumstances a manual battery test can result in a false alarm: please see 3.5
'quick battery test'.
6.2.2 Battery replacement
-
-
-
WARNING: first read the safety rules in section 1.2.
When replacing the batteries, use the same number and voltage(V)/capacity(Ah).
Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.
-
-
Never dispose of batteries in a fire: they may explode.
Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to
electrolyte, wash immediately with plenty of water.
Avoid charging in a sealed container.
Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and only use insulated tools.
-
-
Battery replacement procedure: see next page
OPM_NPE_19X_600_1K5_2GB_V030
10
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
Battery replacement procedure
Refer to the label on the battery drawer.
1.
2.
Be sure that the transport screws (A, fig. 1) have
been removed.
Remove the front panel of the battery compartment.
Use a screw driver or pen as a lever.
3.
4.
Remove the two screws that hold the battery drawer.
Disconnect the DC connectors. Use a screwdriver
as a lever.
5.
6.
Remove battery drawer. Be careful, heavy weight!
Remove clamp (two screws) and replace the
batteries.
7.
Reinstall battery clamp, do not pinch or clamp the
wires.
8.
9.
Slide in the battery drawer.
Connect the DC connectors, a small spark is
normal. Fasten the two screws.
10. Reinstall the front panel.
fig. 9
OPM_NPE_19X_600_1K5_2GB_V030
11
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
7 - Troubleshooting
Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see 4, fig.1) and be sure that the UPS is
not overloaded.
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,
or if the information is insufficient to solve the problem, please contact your dealer or consult
PROBLEM
POSSIBLE CAUSE
SOLUTION
Thermal Circuit Breaker (TCB)
tripped
UPS overload
Reduce load, reset TCB
(4, fig. 1)
System failure
Contact your dealer or consult
LED 'on bypass' blinks
Most probably an overload
Overtemperature
See 3.3.7, reduce the load
See 3.3.8
Allow the UPS to cool down
UPS will not switch on (without
using 'battery start')
Line cord not connected
Read 2.2
Connect line cord
and the output has been off for
a few secs. (see also 3.2.5)
Dead wall socket outlet, or
mains voltage out of limits
Contact qualified electrician
UPS overtemperature
See 3.3.8
Allow UPS to cool down
Tripped Thermal Circuit Breaker See above
UPS will not switch on after
Batteries have been discharged Contact your dealer or consult
storage
UPS switched off automatically
UPS overtemperature
See 3.3.8
Allow UPS to cool down
Mains failure, battery
discharged
Wait until mains returns
Programmed shutdown in
progress
See 3.3.10
UPS received shut down
command from computer during
mains failure
Wait until mains returns
The load is < 5% of the max.
load and no mains power is
present.
Wait until mains returns
(No-load shutdown function is
active, see 3.2.3)
LED ‘replace battery’
illuminates, buzzer is silent
Battery test just after installation Allow the UPS to recharge the
or mains failure batteries
Battery test shows weak battery Read 6.2, replace batteries
OPM_NPE_19X_600_1K5_2GB_V030
12
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Download from Www.Somanuals.com. All Manuals Search And Download.
g
GE Digital Energy
8 - Specifications
NetPro 19” model
:
600
1000
1500
Ratings
Voltage Amperes (VA)
with computer type load
Watts (W)
:
:
600
360
1000
600
1500
900
with resistive load
Input thermal circuit breaker (A)
Input fuse (A)
:
:
5
8
5
8
7
10
Input converter
AC input voltage
:
:
220 - 240 V
100% load: 187 - 264 V
70% load: 120 - 264 V
AC input voltage range
input >264 Vac: UPS switches to battery operation
input >312 Vac: UPS shuts down, manual restart required
187 V (at any load)
Minimum start-up AC voltage
Input current waveform
:
:
sinusoidal
conform or better than EN 61000-3-2 (IEC 555-2)
Input current (A) at nom. inp. volt.
Input power factor
Input frequency range
Inrush current
:
:
:
:
2.0
3.3
5.0
1
45 - 66 Hz
none
Output converter
AC output voltage
:
:
:
:
:
:
:
:
:
230 V (suitable for 220 - 240 V loads)
± 2%
AC output voltage tolerance
Output frequency
50 or 60 Hz, front selectable
nominal ± 0.15% unless synchronized to the mains
sine wave
Output frequency range
Output waveform
Harmonic distortion
< 2% (typical 1.5%) with linear load
0.6 (0.7 at 90% load)
suitable for loads with c.f. up to 6:1
max. 10 A per outlet
Power factor
Crest factor (peak to RMS current)
Capacity appliance outlets
Bypass
AC input voltage range
Frequency tracking rate
Frequency tracking range
Phase difference
:
:
:
:
:
195 - 264 V
2 Hz/sec.
nominal ± 10%
< 7º
Typical transfer time, msec
4
Overload capability
Overload behaviour (battery operation)
:
:
Fully protected against overload and short circuits
110% during 5 minutes; 150% during 5 seconds
Overload behaviour during
bypass operation
:
depends on rating of thermal circuit breaker
typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc)
Number of 7 Ah batteries
Type
:
:
:
:
:
24
2
36
3
48
4
sealed lead acid, maintenance free
up to 6 years (depending on use)
1.5 A
Service life
Recharge current
Battery recharge time
(batt. discharged at 100% load)
Runtime in minutes
at typical load (75%)
VA/Watts
:
:
1.5 hours for 90% capacity, std battery
12
12
10
100/60
:
:
:
:
:
:
64
34
15
9
-
-
104
54
27
15
9
124
71
36
24
12
6
200/120
400/240
600/360
1000/600
1500/900
-
General
Weight without battery drawer (kg)
Weight with battery drawer (kg)
Dimensions (hxwxd, mm)
Depth required in 19” rack (mm)
Enclosure / protection
:
:
:
:
:
14
19
14
22
14
24
133.5 (3HU) x 450 (19”) x 440
420 (without connectors)
steel - plastic / IP20
Environment
Safety
:
:
:
:
:
EN 50091-1-1, EN 60950, IEC 950
EN 50091-2
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
Max. relative humidity
-10 to +40ºC
< 45 dB(A), load and temperature dependent
95% (non-condensing)
OPM_NPE_19X_600_1K5_2GB_V030
13
GE DE NetPro 19” 600-1500: User manual 3.0 (GB)