Frigidaire Yard Vacuum FRS09PYC1 User Manual

AIll nabosuttthae llation  
of your  
Split Type Room Air Conditioner  
Model(indoor/outdoor):  
FRS09PYW1/FRS09PYC1  
FRS12PYW1/FRS12PYC1  
FRS184YW2/FRS184YC2  
FRS18PYW2/FRS18PYC2  
FRS224YW2/FRS224YC2  
FRS22PYW2/FRS22PYC2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To prevent injury to the user or other people and property damage, the  
following instructions must be followed.  
Incorrect operation due to ignoring of instructions may cause harm or  
damage. The seriousness is classified by the following indications.  
1. Connect with the power properly.  
Otherwise, it may cause electric  
shock or fire due to excess heat  
generation.  
2. Always ensure effective grounding.  
No grounding may cause electric  
shock.  
3. Disconnect the power if strange  
sounds, smell, or smoke comes  
from it. It may cause fire and  
electric shock.  
4. Do not operate or stop the unit by  
switching on or off the power. It  
may cause electric shock or fire due  
to heat generation.  
5. Do not operate with wet hands or in  
damp environment. It may cause  
electric shock.  
6. Do not allow water to run into  
electric parts. It may cause failure of  
machine, electric shock or fire.  
7. Do not use the power cord near  
flammable gas or combustibles,  
such as gasoline, benzene, thinner,  
etc. It may cause an explosion or fire.  
9.Do not damage or use an  
unspecified power cord. It may  
cause electric shock or fire.  
10.Do not place heavy object on the  
power cord and ensure that the  
cord will not be compressed. There  
is danger of fire or electric shock.  
8. Do not use the power cord close to  
heating appliances. It may cause  
fire and electric shock.  
Safety precautions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
05  
11.Do not open the unit during  
operation. It may cause electric  
shock or injury.  
12.Do not drink water drained  
from air conditioner. It contains  
contaminants and could make  
you sick.  
13.Do not disassemble or modify unit.  
It may cause failure of appliance  
and electric shock.  
14.When the air filter is to be  
removed, do not touch the metal  
parts of the unit. It may cause an  
injury.  
15.When the unit is to be cleaned,  
switch off, and turn off the circuit  
breaker. Do not clean unit when  
power is on as it may cause fire,  
electric shock or injury.  
16.Avoid direct exposure of occupants  
to air flow.  
17.Turn off the main power switch when  
not using the unit for a long time.  
18.The air conditioner may be dusted  
with an oil free cloth, or washed  
with a cloth dampened in a solution  
of warm water and mild dishwashing  
detergent. Rinse thoroughly and wipe  
dry. Wring excess water from cloth  
before wiping around controls.  
20.Always insert the filters securely.  
Clean filter once every two weeks.  
Operation without filters may  
cause failure.  
21.Always install circuit breaker and a  
dedicated power circuit. No  
installation may cause fire and  
electric shock.  
19.Ensure that the installation bracket of  
the outdoor unit will not damage  
due to prolonged exposure. If  
bracket damages, there will be  
concern of damage due to falling  
of unit.  
22.Do not place obstacles around air-  
inlets or inside of air-outlet. It may  
cause failure of appliance or  
accident.  
Safety precautions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
06  
Choosing the installation site  
Installation Warnings  
1. Carefully read the installation manual before beginning.  
2. Follow each step as shown.  
3. Observe all local, state and national electric codes. This appliance must be  
installed by a qualified licensed HVAC technician in accordance with all  
applicable codes. All electrical connections should be performed by a licensed  
electrician.  
4. Pay attention to danger and safety notices  
Precautions for Installation  
Installation at the following sites may cause problems. If you must inevitably install  
the unit at one of these sites, please consult your local distributor beforehand:  
1. Sites with machine oil.  
2. Sites with a high concentration of salinity, such as coastal areas.  
3. Sites with sulfuric gas, such as hot water springs.  
4. Sites with high frequency equipment, such as wireless equipment, welding  
machines and medical installations.  
5. Sites with flammable gases or volatile material.  
6. Sites with special environmental conditions.  
7. Laundry rooms.  
06  
Choosing the installation site  
Download from Www.Somanuals.com. All Manuals Search And Download.  
07  
Indoor Unit  
inside wall, always leaving a space of  
at least 6" between the top of the  
indoor unit and the ceiling.  
1. The unit must be installed at a site  
that does not obstruct the flow of  
air.  
2. The site must support the weight of  
the indoor unit.  
3. The site must be easily accessible  
for maintenance and replacement  
of the air filter.  
4. The site must allow for the  
necessary space around the indoor  
unit, as shown in the sideward  
figure.  
5. There should be at least 3 feet (1  
meter) between the unit and radio  
or television devices. It is ideal  
that the unit be installed at the  
center.  
8. The site must allow for the easy  
removal of the connector pipe and  
drain hose.  
9. The unit must be installed at a site  
protected from direct sunlight.  
More  
than 6"  
More  
than 6"  
More  
than 6"  
6. It must be far from fire, smoke or  
flammable gases.  
7.  
We recommend the indoor unit to be  
installed as high up as possible on the  
More  
than 1.65'  
Outdoor Unit  
More  
than 1'  
More  
than 1'  
1. The outdoor unit must be  
installed at a convenient site  
that is not exposed to strong  
winds. The site should be dry  
and well ventilated.  
06  
2. The site must support the weight  
of the outdoor unit and allow  
for vertical installation.  
More  
than 6.6'  
3. There must not be the possibility  
of increased noise and vibration  
at the site.  
More  
than 1.65'  
4. The unit must be installed at a  
site where the noise produced  
6. The site must provide enough  
space around the unit, as shown  
in the figure.  
by its operation and air  
discharge does not disturb the  
neighbors or animals.  
7. Children must not be able to  
access the installation site.  
5. The site cannot have any  
leakage of flammable gases.  
Download from Www.SoCmanuhalso.como. Asll Miannuagls Seatrhch Aend Diownnlosadt. allation site  
08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
More than 6"  
Indoor unit  
3
More than 6"  
6
More than 6"  
Air filter  
4
5
More than 1.65'  
More than 1'  
A
More  
than 1.65'  
8
7
6
B
C
Outdoor  
unit  
More than 6.6'  
2
Attention  
1. This illustration is for explanation purposes only.  
2. Copper tubes must be insulated independently  
Parts list  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Indoor unit installation  
Installation plates and dimensions  
6" or more from  
the ceiling  
Installation plate  
Indoor unit outline  
6" or more  
from the wall  
6" or more  
from the wall  
Refrigerant pipe  
hole (right) Ø 2.56"  
Refrigerant pipe  
hole (right) Ø 2.56"  
3.39"  
3.39"  
A
<
12000 Btu's  
(A:33.31" B:10.83")  
6" or more from  
the ceiling  
Installation plate  
A
Indoor unit outline  
6" or more  
from the wall  
6" or more  
from the wall  
Refrigerant pipe  
hole (right) Ø 2.56"  
Refrigerant pipe  
hole (right) Ø 2.56"  
1.58''  
1.58''  
7.91''  
5.31''  
=18000 Btu's  
(A:36.97" B:11.73")  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit installation  
11  
6" or more from  
the ceiling  
Installation plate  
A
Indoor unit outline  
6" or more  
from the wall  
6" or more  
from the wall  
1.97''  
1.97''  
Refrigerant pipe  
hole (right) Ø 2.56"  
Refrigerant pipe  
hole (right) Ø 2.56"  
3.94''  
4.88''  
=21500 Btu's  
(A:39.69" B:12.40")  
Fixing the Installation Plate  
1. Install the installation plate  
horizontally over the structural  
parts on the wall using the spaces  
indicated on the plate, as shown  
in the figures above.  
Attention  
Fit the Installation Plate and drill holes  
in the wall according to the wall  
structure and corresponding mounting  
points on the installation plate  
(Dimensions are in “mm” unless  
otherwise stated).  
2. In the case of tiled, concrete or  
similar walls, create 0.2"  
diameter holes. Place anchorage  
supports for the appropriate  
assembly screws.  
Installation plate  
3. Fix the installation plate to the  
wall with eight A type screws.  
4. At all times securing to the wall  
studs is recommended.  
Drilling the Hole  
Wall  
1. Determine the position of the  
hole for the pipes using the  
installation plate and drill the  
pipe hole so that it is tilted slightly  
downward.  
Indoor unit  
Outdoor unit  
2. Always use a pipe cover with an  
opening when drilling.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit installation  
12  
Connective pipe and drainage installation  
Connective pipe  
Pipe cover  
(right)  
Pipe  
holder  
Pipe cover  
(left)  
1. For the left-hand and right-hand  
piping, remove the pipe cover from  
the side panel.  
The pipe cover  
Left piping  
must be kept as it may be used  
when relocating the air  
to any other place.  
conditioner  
Rear left  
piping  
Rear right  
piping  
Right piping  
2. For the rear-right-hand and rear-left-  
hand piping, install the piping as  
shown in the sideward figure. Bend  
the connective pipe to be laid at  
a height of 1.69" or less from  
Connective  
pipe  
Indoor unit  
outline  
Fix the end of the  
the wall.  
connective pipe.  
Drainage  
Do not block  
water flow  
by a rise.  
Do not block  
water flow  
by a rise.  
1. Run the drain hose sloping  
downward. Do not install the drain  
hose as illustrated sideward.  
2. When connecting extension drain  
hose, insulate the connecting part  
of extension drain hose with a  
shield pipe, do not let the drain  
hose slack.  
Do not put the end  
of drain hose into water.  
Fastening the Indoor Unit  
Upper hook  
1. Pass the piping through the hole in  
the wall.  
2. Put the upper claw at the back of  
the indoor unit on the upper hook of  
the installation plate, move the  
indoor unit from side to side to see  
that it is securely hooked.  
Lower hook  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
Indoor unit installation  
3. Piping can easily be made by  
lifting the indoor unit with a  
cushioning material between the  
indoor unit and the wall. Get it  
out after finish piping.  
4. Push the lower part of the indoor  
unit up on the wall, Then move  
the indoor unit from side to side,  
up and down to check if it is  
hooked securely.  
Cushioning  
material  
Piping and wrapping  
Ponding  
box  
1. Bundle the tubing, connecting  
cable, and drain hose with tape  
securely and evenly as shown  
in the sideward figure.  
Indoor unit  
Cable  
connection  
Pipe room  
2. Because the condensed water  
from rear of the indoor unit is  
gathered in ponding box and is  
piped out of room, do not put  
anything else in the box.  
Connective  
pipe  
Wrapping  
belt  
Drain hose  
Attention  
1. Connect the indoor unit first, then the outdoor unit.  
2. Do not allow the piping to let out from the back of the indoor unit.  
3. Be careful not to let the drain hose slack.  
4. Both of the auxiliary piping should be heat insulation.  
5. Be sure that the drain hose is located at the lowest side of the bundle. Locating  
at the upper side may cause drain pan to overflow inside the unit.  
6. Never intercross nor intertwist the power wire with any other wiring.  
7. Run the drain hose sloped downward to drain out the condensed water  
smoothly.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit installation  
14  
Outdoor unit installation  
1. Install the outdoor part of the unit  
on a rigid surface to avoid excess  
noise and vibration.  
2. Direct the air vent toward an area  
without obstacles.  
3. Install the unit at the site where it is  
to as little wind as possible,  
exposed  
especially in areas where it is  
frequently windy.  
4. If the installation site is exposed to  
heavy winds, such as in coastal  
areas, place the unit along the  
widest part of the wall or use  
protective plates.  
5. Be sure there is no obstacle which  
blocks radiating air, including  
schrubs or bushes.  
Strong wind  
Outdoor uniDtowinlnoadsfrotmaWwlwl.aSomtainuoalsn.com. All Manuals Search And Download.  
15  
$
Air inlet  
Settlement of outdoor unit  
Anchor the outdoor unit tightly and  
horizontally on a concrete or rigid  
mount with a bolt and nut 0.39" or  
0.32" diameter (Purchased separately).  
Air  
inlet  
%
Air outlet  
Aft)  
B( ft)  
Outdoor unit dimension ft(WxHxD)  
ꢀꢁꢊꢉꢃ[ꢆꢁꢊꢊꢃ[ꢆꢁꢅꢇꢃ  
1ꢊꢊ'  
ꢆꢁꢉꢈꢃ  
ꢀꢁꢅꢅꢃ  
ꢅꢁꢂꢈꢃ  
ꢆꢁꢆꢉꢃ  
ꢆꢁꢀꢉ'  
ꢀꢁꢂꢀꢃ[ꢀꢁꢄꢅꢃ[ꢆꢁꢄꢅꢃ  
ꢄꢁꢅꢀꢃ[ꢀꢁꢇꢂꢃ[ꢆꢁꢈꢅꢃ  
Condensate drainage of outdoor unit  
(no for cooling only)  
The condensate and defrosting water formd during heating  
in the outdoor unit can be properly discharged by drainage  
pipe .  
Installation method:Insert the drain connection into one of the  
Ø
25 holes of the chassis and then connect drainage pipe with  
drain nozzle. Insert drainage plugs into the other holes  
(Only for 12000Btu's).  
<
•ꢆꢉꢅꢅꢅꢋ%WXꢃV  
12000 Btu's  
Drain  
connection  
Chassis  
Drain  
connection  
Chassis  
Drainage  
Plug  
Outdoor unit installation  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant piping connection  
Unit comes with 16.4' tubing bundle. It is not recommended to cut. If too long,  
loop for excess.  
Note: Keep original bend so not kinking of the tube occurs.  
Flaring work  
Main cause for refrigerant leakage is  
due to defect in the flaring work.  
Pipe  
Carry out correct flaring work using the  
following procedure:  
1. Cut the pipes and the cable.  
A) Use the piping kit accessory or  
pipes purchased locally.  
Wrong  
Correct  
Oblique Roughness Burr  
B) Measure the distance between the  
indoor and the outdoor unit.  
C) Cut the pipes a little longer than the  
measured distance.  
D) Cut the cable 4.9ft longer than the  
pipe length.  
2. Burr removal  
Pipe  
A) Completely remove all burrs from  
the cut cross section of pipe/tube.  
Reamer  
Point  
down  
B) Put the end of the copper  
tube/pipe in a downward direction  
as you remove burrs in order to  
avoid dropping burrs into the  
tubing.  
Flare nut  
3. Put nut on.  
Remove flare nuts attached to  
indoor and outdoor unit, then put  
them on pipe/tube having  
completed burr removal.(It is not  
possible to put them on after flaring  
work)  
Cooper tube  
17  
Refrigerant piping connection  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Flaring work.  
Firmly hold copper pipe in a  
die in the dimension shown in  
the table below.  
Bar  
Copper  
pipe  
Handle  
A (inch)  
OUTER  
Yoke  
Red arrow mark  
DIAMETER (inch)  
Min.  
Max.  
0.051  
0.063  
0.071  
0.095  
0.028  
0.039  
0.039  
0.087  
1/4  
3/8  
1/2  
5/8  
Clamp  
handle  
Connection Adjustment  
1. Align the pipes to be connected.  
Caution: Excessive twisting may  
break the nut, depending on the  
installation conditions.  
2. Screw the flare nut with your  
fingers, and then tighten it with  
a spanner and torque wrench,  
as shown in the following figure.  
Pipings  
Indoor unit  
tubing  
Flare  
nut  
OUTER  
DIAMETER (inch)  
TIGHTENING  
.
TORQUE (lbf in)  
ADDITIONAL TIGHTENING  
.
TORQUE (lbf in)  
1/4  
3/8  
1/2  
5/8  
139  
260  
434  
651  
174  
304  
477  
694  
18  
Refrigerant piping connection  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power voltage should meet the  
requirements in the following  
table.  
3. Over current protection and circuit  
disconnect should meet the  
requirements in the following table  
and the applicable local and national  
electrical codes.  
Electrical Data Table  
Outdoor Fan  
System  
Voltage  
Volts-Ph.-  
Freq  
Operating  
Voltage  
Compressor  
Indoor Fan  
FLA HP  
Max. Fuse/Circuit  
Breaker  
MIN. Circuit  
Ampacity  
(MCA)  
Capacity  
(BTU)  
Output  
Watts  
Output  
Watts  
Amps(MOCP)  
(Min/Max) RLA  
LRA  
FLA  
HP  
Volts  
ǂ
9K  
115-1-60 103/127 16.03  
ǂ
26  
26  
41  
41  
0.17  
0.17  
0.62  
0.9  
0.04  
0.04  
0.08  
0.12  
30  
30  
60  
90  
115V-AC  
115V-AC  
0.38  
0.38  
0.03  
0.03  
0.03  
0.05  
20  
20  
20  
35  
22  
23  
16  
16  
35  
40  
25  
25  
12K  
18K  
115-1-60 103/127 17.53  
ǂ
208/230-1-60 187/253 11.54  
ǂ
208/230V-AC 0.25  
208/230V-AC 0.45  
21.5K 208/230-1-60  
11.71  
187/253  
Connecting (Power and Control Cable)  
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four  
wires and provides the power for the indoor unit as well as the communication signal and ground between the outdoor and indoor unit.  
Two wires are high voltage AC power, one is low voltage DC signal and one is a ground wire.  
Consult local building codes, NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect the cable to the indoor unit  
Electrical box  
cover  
1. The inside and outside connecting  
cable can be connected without  
removing the front grille.  
2. Connecting cable between indoor  
unit and outdoor unit shall be  
approved polychloroprene  
sheathed flexible cord, type  
designation 16AWG or heavier  
cord.  
3. Lift the indoor unit panel up,  
remove the electrical box cover by  
loosening the screw.  
4. Ensure the colour of wires of  
outdoor unit and the terminal Nos.  
are the same to the indoors  
respectively.  
5. Wrap those cables not connected  
with terminals with insulation  
tapes, so that they will not touch  
any electrical components. Secure  
the cable onto the control board  
with the cord clamp.  
Terminal block of indoor unit  
Cable  
Code wire  
N(1) 2  
3
1.57"  
0.39"  
To Outdoor Unit  
20  
Download from Www.Somanuals.com. All Manuals Search And DoEwnlloaed. ctrical work  
1.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Caution  
After the confirmation of the above conditions, prepare the wiring as follows:  
1. Never fail to have an individual power circuit specifically for the air  
conditioner. As for the method of wiring, be guided by the circuit diagram  
posted on the inside of control cover.  
2. The screws which fasten the wiring in the casing of electrical fittings are  
liable to come loose from vibrations to which the unit is subjected during  
the course of transportation. Check them and make sure that they are all  
tightly fastened. (If they are loose, it could cause burn-out of the wires.)  
3. Specification of power source.  
4. Confirm that electrical capacity is sufficient.  
5. See to that the starting voltage is maintained at more than 90 percent of  
the rated voltage marked on the name plate.  
6. Confirm that the cable thickness is as specified in the power source  
specification.  
7. Always install an earth leakage circuit breaker in a wet or moist area.  
8. The following would be caused by voltage drop: vibration of a magnetic  
switch, which will damage the contact point, fuse breaking, disturbance of  
the normal function of the overload protector.  
9. The means for disconnection from a power supply shall be incorporated  
in the fixed wiring and have an air gap contact separation of at least 1/8 inch  
in each active (phase) conductors.  
Air purging  
Air and moisture in the refrigeration system have undesirable effects as indicated  
below:  
1. Pressure in the system rises.  
2. Operating current rises.  
5. Water may lead to corrosion of  
parts in the refrigeration system.  
Therefore, the indoor unit and tubing  
between the indoor and outdoor unit  
must apply leakage test and be evacuated  
to remove any noncondensables and  
moisture from the system.  
3. Cooling or heating(only for  
models with heating function)  
efficiency drops.  
4. Moisture in the refrigerant circuit  
may freeze and block capillary  
tubing.  
Electrical work and air purging  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purging with vacuum pump  
1. Check that each tube(both liquid and gas side tubes) between the indoor and  
outdoor units have been properly connected and all wiring for the test run has  
been completed. Remove the service valve caps from both the gas and the  
liquid side on the outdoor unit. Note that both the liquid and the gas side  
service valves on the outdoor unit are kept closed at this stage.  
2. When relocating the unit to another place, perform evacuation using vacuum  
pump.  
3. Pipe length and refrigerant amount:  
Air  
purging  
Additional amount of  
refrigerant to be charged  
Connective  
pipe length  
Less than 25'  
Use vacuum pump.  
Use vacuum pump.  
R410a: 0.32ozs/ft (Pipe length-25')  
'
25'~65.6  
<
( 12000Btu's)  
R410a: 0.22ozs/ft (Pipe length-25')  
(=18000Btu's)  
Use vacuum pump.  
25'~98.4'  
R410a: 0.32ozs/ft (Pipe length-25')  
(=21500Btu's)  
Caution in handling the packed valve integrated in the outlets of  
outdoor unit.  
1. Operation of opening packed valve: Open the valve stem until it hits against  
the stopper. Do not try to open it further.  
2. Operation of closing packed valve: Securely tighten the valve stem with a special  
tool. Then securely tighten the valve stem cap with a spanner or the like. Refer to  
tightening torque table in page 17 for valve stem cap tightening torque  
Note: There is a charging port integrated in the low side outlet, but not in the  
high side outlet. The low side outlet is shown in the sketch map below.  
Flare nut  
Refrigerant  
Valve body  
Outdoor unit  
Indoor unit  
Gas  
A
C
Cap  
D
Charge port  
B
Packed valve  
Valve stem  
Stopper  
Half union  
23  
Air purging  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When using the vacuum pump  
For method of using a manifold valve, refer to its operation manual.  
Indoor unit  
1. Completely tighten the flare nuts at  
connection point A, B, C and D.  
Connect valve core removal tool to  
the charging port, then connect  
vacuum hose to valve core tool.  
Open the schrader valve.  
Outdoor unit  
Note: The schrader valve is inside  
the charging port.  
2. Connect the other charge hose of  
manifold valve to the vacuum pump.  
3. Fully open the handle Lo of the  
manifold valve.  
Manifold valve  
-76cm/Hg  
Charge  
hose  
4. Operate the vacuum pump to  
evacuate. After starting evacuation,  
slightly loose the flare nut of the  
Lo valve on the gas pipe side and  
check if the air is entering (Operation  
noise of the vacuum pump changes  
and a compound meter indicates  
0 instead of minus), then tighten  
the flare nut. The procedure verifies  
if there are blocks inside the tubes.  
Handle Hi  
Handle Lo  
Charge hose  
Vacuum pump  
5. Make evacuation for 15 minutes  
or more and check that the  
compound meter indicates  
display in the pressure indicator is  
a little higher than the atmosphere  
pressure. This procedure verifies if  
the refrigerant goes through the  
tubes correctly.  
5
-7.6 x 10 MicronsHg (-1x10 Pa).  
After the evacuation is completed,  
fully close the handle Lo of the  
manifold valve and stop the  
7. Close the schrader valve, then  
remove the valve core tool.  
operation of the vacuum pump.  
Replace the charging port cap.  
6. Turn the stem of the packed  
8. Fully open the packed valve  
valve B about 45o  
stems B and A.  
9. Securely tighten the cap of the  
packed valve.  
counterclockwise for 6~7  
seconds after the gas comes  
out, then tighten the flare nut  
again. Make sure the pressure  
Air purging  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical safety  
Perform the electric safety check after completing installation:  
1. Insulated resistance: The insulated resistance must be more than 2M .  
2. Grounding work: After finishing grounding work, measure the grounding  
resistance by visual detection and grounding resistance tester. Make sure the  
grounding resistance is less than 4 .  
3. Electrical leakage check (performing during test running): During test operation  
after finishing installation, the serviceman can use the electric probe and  
multimeter to perform the electrical leakage check. Turn off the unit  
immediately if electrical leakage happens. Check and find out the solution  
ways till the unit operates properly.  
Gas leak check  
Soap water method  
indoor unit  
Apply a soap water or a liquid neutral  
check point  
detergent on the indoor unit  
connection or outdoor unit connections  
by a soft brush to check for leakage of  
the connecting points of the piping. If  
bubbles come out, the pipes have  
leakage point.  
Cover  
Outdoor unit  
check point  
Leak detector  
Use the leak detector to check for  
leakage.  
Caution  
A: Lo packed valve, B: Hi packed valve  
C and D are ends of indoor unit  
connection.  
25  
Electrical safDeowtnyload afromnWwdw.Sogmaanuasls.colme. AllaMaknualscSeharceh AcndkDownload.  
Test running  
Perform test operation after completing gas leak check at the flare nut  
connections and electrical safety check.  
1. Connect the power, press the ON/OFF button on the remote controller to  
turn the unit on.  
2. Use the MODE button to select COOL, HEAT(Only for models with heating  
function), AUTO and FAN to check if all the functions work well.  
3. When the ambient temperature is too low(lower than 63 F), the unit  
o
cannot be controlled by the remote controller to run in cooling mode,  
manual operation can be taken. Manual operation is used only when the  
remote controller is disable or maintenance necessary.  
Auto/OFF  
Manual control button  
26  
Test running  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparing the device for operation  
1. Contact a specialist to install the device.  
2. Guarantee that the unit is appropriately fastened and complies with all of  
the aforementioned safety norms.  
3. Before operating the air conditioner, ensure that the air filter is installed  
correctly.  
4. If the unit has been out of use for a long period of time, it is recommended  
that the air filter be cleaned before use. During continuous use, clean the air  
filter every two weeks.  
5. This air conditioner was designed for use under the following conditions:  
MODE  
*
Cool  
Heat  
Temperature  
Indoor Outdoor  
41°F~115°F 61°F~86°F 5°F~75°F  
Dehumidifier  
Temperature  
Temperature  
Indoor  
Outdoor  
Indoor  
Outdoor  
61°F~86°F  
61°F~86°F 41°F~115°F  
only for models with heating function  
*
Attention  
If air conditioner is used outside of the above conditions, certain safety protection  
features may come into operation and cause the unit to function abnormally.  
Room relative humidity should be less than 80%. If the air conditioner operates in  
excess of this figure, the surface of the air conditioner may attract condensation.  
Please set the horizontal louver to its maximum angle (vertically to the floor), and  
set HIGH fan mode.  
Optimum performance will be achieved within these operating temperature.  
27  
Preparing the device for operation  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Blower PB 265LN User Manual
Echo Chipper ES 1000 User Manual
Echo Edger PE 230 User Manual
Eiki Projector AH 69601 User Manual
Fellowes Paper Shredder DS 1400C User Manual
Frigidaire Dishwasher 154889301 User Manual
Frigidaire Microwave Oven FFMO1611LB User Manual
Garland Gas Heater BCO G 10 User Manual
GE Garbage Disposal GFC1000Y User Manual
GE Washer WBSR3000 User Manual