FieldServer Network Router FS 8700 72 User Manual

A Sierra Monitor Company  
Driver Manual  
(Supplement to the FieldServer Instruction Manual)  
FS-8700-72 Secutron Modul-R  
APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after August 2008  
Driver Version:  
Document Revision:  
1.01  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 3 of 15  
1.  
Secutron Modul-R driver Description  
The Secutron Modul-R driver allows the FieldServer to transfer data to and from a Client and a Server  
panel on a single point to point network over RS-232 using Secutron Modul-R protocol.  
The protocol is strictly command/response with the Client polling a Server device. A Server device can  
report the generation and clearing of alarms to the polling Client. One panel can be connected per  
FieldServer port. The driver supports networked panels connected to a single port. The server driver  
only supports 10 panels due to memory limitations. A Server panel can consist of up to 100 circuits.  
Whan an alarm is generated, a bit is set and when the alarm is cleared, the bit is cleared. The panel  
number is identified by the Node_ID in the configuration file.  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies PART #  
FS-8917-16  
FS-8700-72  
Description  
Pigtail cable for RJ45 Port  
Driver Manual.  
.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 4 of 15  
3.  
Hardware Connections  
The FieldServer is connected to the panels as shown below.  
Configure the panels according to manufacturer’s instructions.  
Connector Pinouts  
RJ-45 Pin From RJ-45  
To Secutron  
1
8
5
Brown  
White/Orange Rx  
Blue/white GND  
Tx  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 5 of 15  
4.  
Configuring the FieldServer as a Secutron Modul-R driver Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration  
Manual. The information that follows describes how to expand upon the factory defaults provided in the  
configuration files included with the FieldServer (See “.csv” files on the provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer to  
communicate with Secutron Modul-R panels.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order  
to enable the FieldServer for Secutron Modul-R driver communications, the driver independent  
FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses  
need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to  
be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.  
4.1.  
Data Arrays/Descriptors  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up  
to  
15  
Data_Array_Name Provide name for Data Array  
alphanumeric  
characters  
Provide data format. Each Data Array can only take Bit, Byte, Packed_Bit,  
Data_Format  
on one format.  
Uint16  
Number of Data Objects. Must be larger than the data  
Data_Array_Length storage area required for the data being placed in this 1-10,000  
array.  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
p1c1_devices,  
p1c1_function,  
p1c69_restart,  
p1c69_function,  
p1c90_reset,  
Data_Array_Format,  
Bit,  
Byte,  
Bit,  
Byte,  
Bit,  
Data_Array_Length  
1
1000  
1000  
100  
100  
100  
p1c90_function,  
Byte,  
The Poller Data Array will contain non-zero data when communications with the panel is OK.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 6 of 15  
4.2.  
Client Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify through which port the device is  
connected to the FieldServer  
Port  
P1-P81  
150, 300, 1200, 2400, 4800, 9600  
(Vendor limitation)  
Baud*  
Specify baud rate  
Parity*  
Specify parity  
None (Vendor limitation)  
Data_Bits*  
Specify data bits  
8 (Vendor limitation)  
1 (Vendor limitation)  
Stop_Bits*  
Protocol  
Specify stop bits  
Specify protocol used  
Secutron  
None  
Handshaking* Specify hardware handshaking  
Example  
//    Client Side Connections  
Connections  
Port,  
P1,  
Protocol,  
Secutron,  
Baud,  
9600,  
Parity,  
None,  
Handshaking  
None  
4.3.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column  
Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Node_Name Provide name for Node  
Generic Node ID unique to port. Also used as panel  
number.  
Specify protocol used  
Specify which port the device is connected to the  
FieldServer  
Node_ID  
Protocol  
Port  
0-999  
Secutron  
P1-P81  
Example  
// Client Side Nodes  
Nodes  
Node_Name,  
Node_1,  
Node_ID,  
1,  
Protocol,  
Secutron,  
Connection  
P1  
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 7 of 15  
4.4.  
4.4.1.  
Client Side Map Descriptors  
FieldServer Specific Map Descriptor Parameters  
Column Title  
Map_Descriptor_Name Name of this Map Descriptor  
Function  
Legal Values  
Up to 32 alphanumeric characters  
Name of Data Array where data One of the Data Array names  
is to be stored in the FieldServer from “Data Array” section above  
Data_Array_Name  
Data_Array_Offset  
Function  
0 to (Data_Array_Length-1) as  
specified in “Data_Array” section  
Starting location in Data Array  
Function  
Descriptor  
of  
Client  
Map  
Rdbc, Passive_Client  
One of the node names specified  
in “Client Node Descriptor” above  
Node_Name  
Name of Node to fetch data from  
The number of devices on the  
Length  
circuit the Map Descriptor must 0-999  
detect  
Used to enable packed bit when  
using a Packed_Bit Data Array Flag, -  
on the Map Descriptor  
Block_Type*  
4.4.2.  
Driver Specific Map Descriptor Parameters  
Column Title  
Secutron_Type  
Secutron_Circuit Identifies the circuit or panel zone  
Function  
Legal Values  
Identifies the type of data the Map Descriptor Poller, Device,  
points to  
Function  
0-99  
4.4.3.  
Timing Parameters  
Column Title  
Scan_Interval  
Function  
Rate at which data is polled  
Legal Values  
>= 0s  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 9 of 15  
5.  
Configuring the FieldServer as a Secutron Modul-R driver Server  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration  
Manual. The information that follows describes how to expand upon the factory defaults provided in the  
configuration files included with the FieldServer (See “.csv” files provided with the FieldServer).  
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order  
to enable the FieldServer for Secutron Modul-R driver communications, the driver independent  
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) need  
to be declared in the “Server Side Nodes” section, and the data to be provided to the Client needs to be  
mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.  
5.1.  
Data Arrays  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Data_Format  
Provide name for Data Array  
Provide data format. Each Data Array Bit,  
can only take on one format.  
Packed_Bit,  
Byte,  
Uint16  
Number of Data Objects. Must be larger  
Data_Array_Length  
than the data storage area required for 1-10,000  
the data being placed in this array.  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
p1c1_devices,  
p1c1_function,  
p1c69_restart,  
p1c69_function,  
p1c90_reset,  
Data_Array_Format,  
Bit,  
Byte,  
Bit,  
Byte,  
Bit,  
Data_Array_Length  
1
1000  
1000  
100  
100  
100  
p1c90_function,  
Byte,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 10 of 15  
5.2.  
Server Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device is connected  
to the FieldServer  
Port  
P1-P82  
150, 300, 1200, 2400, 4800, 9600  
(Vendor limitation)  
Baud*  
Specify baud rate  
Parity*  
Specify parity  
None (Vendor limitation)  
Data_Bits*  
Specify data bits  
8 (Vendor limitation)  
1 (Vendor limitation)  
Stop_Bits*  
Protocol  
Specify stop bits  
Specify protocol used  
Secutron  
None  
Handshaking* Specify hardware handshaking  
Example  
//    Server Side Connections  
Connections  
Port,  
P1,  
Protocol,  
Secutron,  
Baud,  
9600,  
Parity,  
None,  
Handshaking  
None  
5.3.  
Server Side Node Descriptors  
Section Title  
Nodes  
Column  
Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Node_Name Provide name for Node  
Generic Node ID unique to port. Also used as panel  
number.  
Node_ID  
0-9  
Protocol  
Port  
Specify protocol used  
Port to which node belongs  
Secutron  
P1-P8  
Example  
// Server Side Nodes  
Nodes  
Node_Name,  
Node_1,  
Node_ID,  
1,  
Protocol,  
Secutron,  
Connection  
P1  
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 11 of 15  
5.4.  
5.4.1.  
Server Side Map Descriptors  
FieldServer Specific Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
Map_Descriptor_Name Name of this Map Descriptor  
Name of the Data Array where  
Up to 32 alphanumeric characters  
One of the Data Array names from  
“Data Array” section above  
Data_Array_Name  
data is to be stored in the  
FieldServer  
0 to (Data_Array_Length-1) as  
specified in “Data_Array” section  
Data_Array_Offset  
Function  
Starting location in Data Array  
Function  
of  
Client  
Map  
Server  
Descriptor  
The name of the Node the Map One of the Node Names specified  
Node_Name  
Descriptor is attached to  
in “Server Node Descriptor” above  
The number of devices on the  
Length  
circuit the Map Descriptor must 0-999  
represent  
Used to enable packed bit when  
using a Packed_Bit Data Array Flag, -  
on the Map Descriptor  
Block_Type*  
5.4.2.  
Driver Specific Map Descriptor Parameters  
Column Title  
Secutron_Type  
Secutron_Circuit Identifies the circuit or panel zone  
Function  
Legal Values  
Identifies the type of data the Map Descriptor points to Device, Function  
0-99  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 12 of 15  
Appendix A. Advanced Topics  
Appendix A.1.  
Event Function or Condition Codes  
When the Client driver receives an event from the panel, it stores the event’s function or condition  
code in the Secutron_Type=function Map Descriptor’s Data Array at the device number’s offset,  
Example:  
Device=3 on Circuit=1 goes into alarm – the Panel reports an event with function code A (Decimal 65)  
The Map Descriptor Secutron_Type=device, Secutron_Circuit=1 will set a bit and store the event  
function code A (Decimal 65) at offset 3 in the Map Descriptors’ Data Array.  
The Secutron_Type=device Map Descriptors will set a bit if any of the events listed below occur on  
that circuit or zone. The bit will be cleared if the panel reports the event as cleared.  
The full list of event function codes are:  
ASCII value  
Decimal  
Meaning  
65  
Alarm  
A
B
C
D
E
G
H
I
66  
67  
68  
69  
71  
72  
73  
74  
77  
78  
80  
81  
82  
83  
84  
85  
87  
Bypass  
Comlink  
Duplicate Addressable Device  
Maintenance Alert  
Ground Fault  
Hot Key Pressed  
Illegal Addressable Device  
Switch  
Missing Addressable Device  
Non-Fire/Non-Reporting  
Pull Station Alarm  
Releaser Abort  
Releaser Halt  
Supervisory  
Trouble or Parameter Change  
Wrong Device Type  
Waterflow Alarm  
J
M
N
P
Q
R
S
T
U
W
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 13 of 15  
Appendix A.2.  
Panel Circuit or Zone numbers  
The panel groups events under circuit or zone numbers. When setting up a Client configuration it is  
necessary to create Map Descriptors to trap the events from the zones or circuits you want to see  
data from.  
If an event is received that has no corresponding Map Descriptor defined, this will be reported on the  
RuiNet E screen. This is a useful configuration tool to ensure that all required data is stored.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-72 Secutron Manual  
Page 14 of 15  
Appendix A.3.  
Panel Power-up, Restarts and Resets  
When the panel powers up or is restarted it will send an event on zone/circuit 69 device 0.  
When the panel is reset from the Hot Keys on the front panel, it will send an event on zone/circuit 90,  
device 9.  
The Client driver will clear all the Secutron_Type=device and Secutron_Type=function Data Arrays  
when it traps any of these 2 events, provided the circuit 69 and 90 Map Descriptors have been set up  
as per the example Map Descriptors under the Client Side configuration instructions.  
Other events for Circuits 69 and 90 are shown below for which a bit will be set in the  
Secutron_Type=device Map Descriptor’s Data Array at the device offset values shown below:  
Circuit  
Events  
003 – Illegal Instruction  
000 – Power On/Hard reboot  
001 - Watchdog  
002 – Clock Monitor  
001 – Fire Drill  
002 - Lamp Test  
003 – Releaser Disconnect  
004 – Relay disconnect  
005 – Test mode  
006 – Signal Disconnect  
007 - Acknowledge  
008 – Signal Silence  
009 - Reset  
010 – Common Disconnect  
011 – General Alarm  
012 - Halt  
Program Restart  
(Circuit 69)  
004 – Unused Interrupt  
005 – Orphan Interrupt  
026– Switch 11 On  
027 – Switch 12 On  
028 – Switch 13 On  
029 – Switch 14 On  
030 – Switch 15 On  
031 – Switch16 On  
032 – Switch 1 Off  
033 – Switch 2 Off  
034 – Switch 3 Off  
035 – Switch 4 Off  
036 – Switch 5 Off  
037 – Switch 6 Off  
038– Switch 7 Off  
039– Switch 8 Off  
040– Switch 9 Off  
041– Switch 10 Off  
042– Switch 11 Off  
043 – Switch 12 Off  
044 – Switch 13 Off  
045 – Switch 14 Off  
046 – Switch 15 Off  
047 – Switch16 Off  
051 – Manual Restart  
Hot Key Activation  
(Circuit 90)  
013 - Abort  
Function number of the Hot Key  
pressed.  
013 – 2nd Stage Inhibit  
016 – Switch 1 On  
017 – Switch 2 On  
018 – Switch 3 On  
019 – Switch 4 On  
020 – Switch 5 On  
021 – Switch 6 On  
022– Switch 7 On  
023– Switch 8 On  
024– Switch 9 On  
025– Switch 10 On  
Appendix A.4.  
Driver Messages, Error Messages and Optional Map Descriptors  
The Client driver will report all events it receives from the panel on the RuiNet F screen.  
If an event is received that has no corresponding Map Descriptor defined, this will be reported on the  
RuiNet E screen. This is a useful configuration tool to ensure that all required data is stored.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Eiki Flat Panel Television PLD 42UE User Manual
Evo Fitness Home Gym 5102 User Manual
FieldServer Computer Drive FS 8704 01 User Manual
Focal Car Amplifier DUAL MANAGER User Manual
Gardena Trimmer TS 350 User Manual
Gateway Camcorder DV S20 User Manual
GE Air Conditioner AGE14 User Manual
GE Air Conditioner AGF06 User Manual
Gemini Car Stereo System CDX 2200 User Manual
GE Monogram Range ZDP486LDPSS User Manual