1.  
Spectronics Description  
The Spectronics driver allows the FieldServer to transfer data to and from devices over either  
RS-232 or RS-485 using Spectronics protocol. The FieldServer can emulate either a Server or  
Client.  
The information that follows describes how to expand upon the factory defaults provided in the  
configuration files included with the FieldServer.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 4 of 15  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies  
PART #  
Description  
FS-8915-10  
7’ Patch Cable  
FS-8917-01  
FS-8700-01  
RJ45 to DB25M connector adapter  
Driver Manual  
2.2.  
Provided by Supplier of 3rd Party Equipment  
PART #  
DESCRIPTION  
Spectronics Device  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 5 of 15  
3.  
Hardware Connections  
It is possible to connect a Spectronics device to any of the existing serial ports on the  
FieldServer1. These ports simply need to be configured for Spectronics in the configuration file.  
Configure the Spectronics device according to manufacturer’s instructions.  
8917-01 WIRE LIST  
DB25M  
FUNCTION FROM  
TO  
COLOUR  
RX  
CTS  
DSR  
GND  
GND  
DTR  
RTS  
TX  
RJ45-01 DB25M-03 WHITE  
RJ45-02 DB25M-05 BROWN  
RJ45-03  
YELLOW  
RJ45-04 DB25M-07 GREEN  
RJ45-05  
RJ45-06  
RED  
BLACK  
RJ45-07 DB25M-04 ORANGE  
RJ45-08 DB25M-02  
BLUE  
8917-04 WIRE LIST  
DB25F  
FUNCTION FROM  
TO  
COLOUR  
RX  
CTS  
DSR  
GND  
GND  
DTR  
RTS  
TX  
RJ45-01 DB25F-02 WHITE  
RJ45-02 DB25F-04 BROWN  
Typical DB9/DB25  
kit assemblies are  
shown here. Refer  
to the third party  
device literature  
for exact  
RJ45-03  
YELLOW  
RJ45-04 DB25F-07 GREEN  
RJ45-05  
RJ45-06  
RED  
BLACK  
configuration  
RJ45-07 DB25F-05 ORANGE  
required.  
RJ45-08 DB25F-03  
BLUE  
8917-03 WIRE LIST  
FUNCTION FROM  
TO  
COLOUR  
GREY  
DB9M  
RX  
CTS  
DSR  
GND  
GND  
DTR  
RTS  
TX  
RJ45-01 DB9M-02  
RJ45-02 DB9M08 BROWN  
RJ45-03 DB9M-06 YELLOW  
RJ45-04 DB9M-05 GREEN  
RJ45-05  
RJ45-06 DB9M-04  
RED  
BLACK  
RJ45-07 DB9M-07 ORANGE  
RJ45-08 DB9M-03  
BLUE  
8917-02 WIRE LIST  
DB9F  
FUNCTION FROM  
TO  
COLOUR  
WHITE  
GREEN  
BLUE  
Rx  
GND  
Tx  
RJ45-01 DB9F-03  
RJ45-04 DB9F-05  
RJ45-08 DB9F-02  
RJ45 Connector  
OR  
(408)-262-2299  
FIELDSERVER  
MODBUS RTU  
CONNECTION DIAGRAM  
BASE NAME:  
FILE NAME:  
DATE: 4/20/04  
BY: MC  
1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 6 of 15  
4.  
Configuring the FieldServer as a Spectronics Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FS).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a Spectronics Server.  
4.1.  
Data Arrays/Descriptors  
The configuration file tells the FieldServer about its interfaces, and the routing of data  
required. In order to enable the FieldServer for Spectronics communications, the driver  
independent FieldServer buffers need to be declared in the “Data Arrays” section, the  
destination device addresses need to be declared in the “Client Side Nodes” section, and  
the data required from the servers needs to be mapped in the “Client Side Map Descriptors”  
section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Provide name for Data Array  
Provide data format. Each FLOAT, BIT, UInt16, SInt16,  
Data Array can only take on Packed_Bit, Byte,  
Data_Array_Format  
Data_Array_Length  
one format.  
Packed_Byte, Swapped_Byte  
Number of Data Objects. Must  
be larger than the data  
storage area required by the 1-10,000  
map descriptors for the data  
being placed in this array.  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
DA_DI_01,  
Data_Format,  
UInt16,  
UInt16,  
Bit,  
Data_Array_Length  
200  
200  
200  
200  
DA_DO_01,  
Bit,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 7 of 15  
4.2.  
Client Side Connection Descriptors  
Section Title  
Connections  
Column Title Function  
Legal Values  
Specify which port the device is connected  
to the FieldServer  
Port  
P1-P8, R1-R22  
110 – 115200, standard baud  
rates only  
Baud*  
Specify baud rate  
Parity*  
Specify parity  
None (Vendor limitation)  
Data_Bits*  
Specify data bits  
Specify stop bits  
Specify protocol used  
8 (Vendor limitation)  
1 (Vendor limitation)  
Spectronics  
Stop_Bits*  
Protocol  
Handshaking* Specify hardware handshaking  
RTS, RTS/CTS, None  
0-32000 s, 1 s  
Poll Delay*  
Time between internal polls  
Example  
//  
Client Side Connections  
Connections  
Port,  
P8,  
Protocol,  
Spectronics,  
Baud,  
9600,  
Parity,  
None,  
Handshaking,  
None,  
Poll_Delay  
0.100s  
4.3.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Node_Name  
Provide name for node  
Station address of physical server  
node  
Specify protocol used  
Specify which port the device is  
connected to the FieldServer  
Node_ID  
Protocol  
Port  
1-255  
Spectronics  
P1-P8, R1-R22  
Example:  
// Client Side Nodes  
Nodes  
Node_Name,  
Spec_device1,  
Node_ID,  
1,  
Protocol,  
Spectronics,  
Port  
P8  
2 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 8 of 15  
4.4.  
4.4.1.  
Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
Name of this Map  
Descriptor  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array  
where data is to be  
stored in the  
One of the Data Array  
names from “Data Array”  
section above  
Data_Array_Name  
FieldServer  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Function of Client Map  
Descriptor  
RDBC  
4.4.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
Name of Node to fetch  
data from  
Node_Name  
Length  
Length of Map Descriptor  
Starting address of read  
block  
1-125 (Register,AI)  
Address  
40001, 30001, etc  
-2,147,483,648 to  
2,147,483,647, 0  
Data_Array_Low_Scale*  
Data_Array_High_Scale*  
Scaling zero in Data Array  
-2,147,483,648 to  
2,147,483,647, 100  
Scaling max in Data Array  
Scaling zero in Connected -2,147,483,648 to  
Node 2,147,483,647, 0  
Scaling max in Connected -2,147,483,648 to  
Node 2,147,483,647, 100  
Node_Low_Scale*  
Node_High_Scale*  
4.4.3.  
Timing Parameters  
Column Title  
Scan_Interval  
Function  
Rate at which data is polled  
Legal Values  
0.001s  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 9 of 15  
4.4.4.  
Map Descriptor Example.  
// Client Side Map Descriptors  
Map_Descriptors  
Map_Descriptor_Name,  
CMD_AI_01,  
CMD_AO_01,  
CMD_DI_01,  
CMD_DO_01,  
Data_Array_Name,  
Data_Array_Offset,  
Function, Node_Name,  
Address, Length, Scan_Interval  
DA_AI_01,  
DA_AO_01,  
DA_DI_01,  
DA_DO_01,  
0,  
0,  
0,  
0,  
RDBC,  
RDBC,  
RDBC,  
RDBC,  
Spec_Device1,  
Spec_Device1,  
Spec_Device1,  
Spec_Device1,  
30001,  
40001,  
10001,  
00001,  
20,  
20,  
20,  
20,  
1.000s  
1.000s  
1.000s  
1.000s  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 10 of 15  
5.  
Configuring the FieldServer as a Spectronics Server  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a Spectronics Client.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required.  
In order to enable the FieldServer for Spectronics communications, the driver independent  
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual  
node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to  
the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to  
do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
5.1.  
Server Side Connection Descriptors  
Section Title  
Connections  
Column Title Function  
Legal Values  
Specify which port the device is connected  
to the FieldServer  
Port  
P1-P8, R1-R23  
110 – 115200 standard baud  
rates only  
Even, Odd, None, Mark,  
Space  
Baud*  
Parity*  
Specify baud rate  
Specify parity  
Data_Bits*  
Stop_Bits*  
Protocol  
Specify data bits  
Specify stop bits  
7, 8  
1 (Vendor limitation)  
Spectronics  
Specify protocol used  
Handshaking* Specify hardware handshaking  
RTS, RTS/CTS, None  
Example  
//  
Server Side Connections  
Connections  
Port,  
P1,  
Protocol,  
Spectronics,  
Baud,  
9600,  
Parity,  
None,  
Handshaking  
None  
3 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 11 of 15  
5.2.  
Server Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Node_Name  
Node_ID  
Function  
Legal Values  
Up to 32 alphanumeric characters  
1 – 255  
Spectronics  
Provide name for node  
Node ID of physical server node  
Specify protocol used  
Protocol  
Example  
Nodes  
Node_Name,  
Spec_Srv_11,  
Node_ID,  
11,  
Protocol  
Spectronics  
5.3.  
5.3.1.  
Server Side Map Descriptors  
FieldServer Specific Map Descriptor Parameters  
Column Title  
Function  
of this  
Descriptor  
Legal Values  
Map Up to 32 alphanumeric  
characters  
Name  
Map_Descriptor_Name  
Name of Data Array where One of the Data Array  
data is to be stored in the names from “Data Array”  
Data_Array_Name  
FieldServer  
section above  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Server  
Function of Server Map  
Descriptor  
5.3.2.  
Driver Specific Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
Name of Node to fetch data  
from  
Node_Name  
Data_Type  
Length  
Data type  
Register, Coil, AI, DI  
Length of Map Descriptor  
Starting address of read  
block  
1 - 125  
Address  
40001, 30001, etc  
Data_Array_Low_Scale* Scaling zero in Data Array  
-32767 to 32767, 0  
-32767 to 32767, 100  
-32767 to 32767, 0  
Data_Array_High_Scale* Scaling max in Data Array  
Node_Low_Scale*  
Node_High_Scale*  
Scaling zero in Connected  
Node  
Scaling max in Connected  
Node  
-32767 to 32767, 100  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 12 of 15  
5.3.3.  
// Server Side Map Descriptors  
Map_Descriptors  
Map Descriptor Example.  
Map_Descriptor_Name,  
SMD_AI_01,  
SMD_AO_01,  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
Data_Array_Offset,  
0,  
0,  
Function,  
Server,  
Server,  
Node_name,  
Spec_Srv_11,  
Spec_Srv_11,  
Address,  
30001,  
40001,  
Length,  
200,  
200,  
Data_Array_Low_Scale,  
0,  
0,  
Data_Array_High_Scale  
100,  
100,  
Node_Low_Scale  
0,  
0,  
Node_High_Scale  
10000  
10000  
Map Descriptors  
Map_Descriptor_Name,  
SMD_DI_01,  
Data_Array_Name,  
DA_DI_01,  
DA_DO_01,  
Data_Array_Offset,  
0,  
0,  
Function,  
Server,  
Server,  
Node_name,  
Spec_Srv_11,  
Spec_Srv_11,  
Address,  
10001,  
00001,  
Length  
200  
200  
SMD_DO_01,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 13 of 15  
Appendix A. Advanced Topics – Spectronics  
Appendix A.1. Default Data Types  
When a Spectronics address range is specified, a particular Data Type is implied. The  
defaults are as follows:  
Address range  
40001 - 49999  
30001 - 39999  
10001 - 19999  
00001 - 09999  
Data_Type  
Register  
Analog _Input  
Digital_Input  
Coil  
Function Code (Write)  
16  
n/a.  
n/a.  
15  
Function Code (Read)  
3
4
2
1
Appendix A.2. Single Writes  
When writing the default data types can be overwritten using the “Single_Coil” and  
“Single_Register” settings as part of the Map Descriptor configuration. In that case the  
Function codes for writes will be as follows:  
Address range Data_Type  
Function Code (Write)  
40001 - 49999  
30001 - 39999  
Single_Register 6  
Coil  
5.  
Example: FC 6 = Write Single Register  
Add a parameter to the Spectronics client side Map Descriptor called Data_Type.  
If you specify the Data_Type as Single_Register and the Function as WRBC or WRBX,  
then a Spectronics poll with FC 6 will be generated.  
Of course Single_Register implies a length of one, and even if you try to set the length  
longer in the csv file, the length is limited to 1 in the driver.  
Appendix A.3. Write-Thru Operation  
Consider a client Map Descriptor that is configured to read data using a FC 3 (Read Multiple  
Register) operation. It is now possible do a write thru operation on the existing Client Map  
Descriptor by storing data to the Client Map Descriptors Data Array.  
The Write Cache Map Descriptor that is created will use the following function codes  
depending on the Cache Map Descriptor Length and the Clients Node Type.  
Single Register Write - FC 6 - When the length of the Cache Map Descriptor is one. This will  
normally be the case.  
Multiple Register Write – FC 16 - When the length of the Cache Map Descriptor is larger  
than one or the Node_Type has been set to “Block_Mode”.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 14 of 15  
Appendix A.4. Connection to York Modbus Microgateway  
If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the  
Microgateway is defined by the address DIP switches. If switch 4 is set to ‘On’ and the other  
switches are set to ‘off’ then Node_ID of the Microgateway is ‘247’, the parity is ‘Even’, and  
the stop bits are 1. Other Node_ID combinations can be found in the York Modbus  
Microgateway Installation Manual.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-42_Spectronics Driver Manual  
Page 15 of 15  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Eiki CRT Television LC XT1 User Manual
Eizo Computer Monitor ColorEdge Calibration Color LCD Monitor User Manual
Estate Range W10173325A User Manual
Extron electronic Speaker SI 26X User Manual
Frymaster Fryer Y SM80 User Manual
Fujitsu Network Card ADA 16FX User Manual
Fujitsu Photo Scanner C150 E049 02EN User Manual
Fundex Games Board Games Loteria User Manual
Genesis Advanced Technologies Speaker AMP 1 User Manual
GE Ventilation Hood CV936 User Manual