Field Controls Oxygen Equipment FC95HRV User Manual

Operation and Installation Manual  
FC95HRV*  
FC155HRV  
FC200HRV*  
FC150ERV  
Heat Recovery Ventilators  
*
This product earned the ENERGY STAR by  
meeting strict energy efficiency guidelines set by  
Natural Resources Canada and the US EPA. It  
meets ENERGY STAR requirements only when  
used in Canada.  
69-Field  
0412  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting to Know your Heat and Energy Recovery Ventilator (FC Series)  
Thank you for purchasing a Field Control Heat/Energy Recovery  
Ventilator (HRV/ERV). The HRV/ERV provides fresh air to your  
home while recovering energy from the air it exhausts.  
There are numerous benefits to a properly installed, operated, and  
maintained HRV/ERV:  
• Recovers the majority of the energy contained in the exhausted  
stale air.  
• Uses the recovered energy to preheat or precool the fresh outdoor  
air introduced into the house  
• Distributes the fresh air throughout your home.  
• Exhausts the stale, contaminated air, found in today’s tight  
buildings.  
Ventilation and Control Options*  
Optional Controls are available to adjust the amount of ventilation  
in your home:  
• The Healthy Home System™ Control (HHSC) will automatically  
deliver fresh air to your home.  
• The Dehumidistat Ventilation Control (DHVC) is a manual  
control which features ON/OFF, High speed, Low Speed, and an  
electronic dehumdistat.  
• The Dehumidistat Control (DHI) can be used in conjunction with  
the HHSC to provide additional ventilation for high indoor  
humidity levels.  
*Refer to the individual control pages of this manual for more  
information about these controls.  
How the Dehumidistat Works (Colder Climates)  
High indoor humidity levels, during the heating season, have  
become a problem in many well insulated, tight homes. Excessive  
condensation on the windows is a visual sign of high indoor  
humidity levels. High indoor humidity levels can result in mold and  
mildew and the eventual degradation of the building structure itself.  
Your HRV/ERV reduces indoor humidity levels when the  
outdoor air is drier than the indoor air. These conditions usually  
occur during the heating season when outdoor temperatures are less  
than 15°C (59°F). During the heating season, the operation of the  
HRV/ERV may reduce indoor humidity levels sufficiently to  
eliminate the need for further dehumidification.  
Refer to the main control instructions located in the Operation and  
Installation Manual for instructions on how to set the dehumidistat.  
The dehumidistat function on the main control should be set to OFF  
for all seasons except the heating season, because a dehumidifying  
effect occurs only when the outdoor air is dryer than the indoor air.  
Set the RH level to 80 to turn the dehumidistat OFF. (Refer to the  
control instructions for information on how to set the  
Dehumidistat).  
DEHUMIDISTAT DISABLE - automatically disables the  
dehumidistat function on the main control when outdoor  
temperatures exceed 15°C (59°F) for a full 24 hour period. All other  
HRV features and functions operate normally while the  
dehumidistat function is disabled.  
If your home requires further dehumidification, use the  
dehumidistat feature located on any optional main control (refer to  
the Operation and Installation Manual for Optional Control  
information). This feature aggressively addresses high indoor  
humidity levels by initiating high speed ventilation when the indoor  
humidity levels rise above the adjustable set point on the control.  
DEHUMIDISTAT RE-ENABLE - automatically re-enables the  
dehumidistat function if either the outdoor temperature drops below  
15°C (59°F) for a full 24 hour period or if the HRV is reset  
(unplugged for 30 seconds).  
Glossary and Additional Information  
DEFROST MODE - To ensure reliable operation during cold  
weather, the HRV automatically cycles through its defrost mode  
when the outdoor temperatures drop below freezing.  
SELF-TEST - Each time the HRV/ERV is powered/energized, the  
self-test function automatically initiates. The HRV/ERV cycles  
through the available speeds and tests the damper motor operation.  
The HRV/ERV defaults back to the previous operational mode and  
speed selection after the self-test (approximately 60 seconds in  
duration).  
HRV/ERV - a Heat Recovery Ventilator (HRV/ERV) is designed  
to provide fresh air into a building while exhausting an equal  
amount of stale air. During the winter months, heat recovered from  
the stale air, before it is exhausted to the outdoors, warms the  
incoming cold fresh air. During the summer months, when the  
indoor space is air conditioned, the HRV/ERV helps to cool the  
incoming fresh air with the cool exhausted stale air.  
STANDBY - The HRV/ERV is powered/energized and waiting for  
ventilation to be initiated by an external control.  
TIMERS - These optional controls may be installed at specific  
exhaust locations (bathrooms etc.) to initiate high speed ventilation.  
Warranty  
Heat Recovery Ventilators (HRV) carry a Lifetime Warranty on the  
heat recovery core and a 5 (five) year replacement parts warranty.  
Energy Recovery Ventilators (ERV) carry a 5 (five) year warranty  
on the energy recovery core and a 5 (five) year replacement parts  
warranty.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Healthy Home System Control (HHSC)  
The Healthy Home System Control (HHSC) activates the  
HRV/ERV automatically to deliver fresh air into your home.  
Setting the Control  
The duration of the ventilation rate is adjustable on the HHSC.  
Your installer sets up this control during the installation of your  
system . Refer to the instructions that came with the HHSC for the  
setup information.  
The Healthy Home System™ Control (HHSC)  
Dehumidistat (Part DH1)  
Your HRV/ERV system produces a dehumidifying effect when  
outdoor humidity levels are lower than indoor humidity levels.  
These conditions occur normally when outdoor termperatures are  
below 60°F. An additional dehumidification effect is achievable  
with the Optional Dehumidistat (Part DH1).  
Dehumidistat Indicator  
LEDs  
Set to the desired humidity  
level. High speed ventilation  
will initiate when the indoor  
moisture level exceeds the set  
point on the control.  
The Optional DH1 Control may be combined with the Healthy  
Home System Control (HHSC). The DH1 will initiate high speed  
ventilation when the moisture level in the home exceeds the set  
point on the control. Once the humidity in the house is reduced,  
the HRV will revert back to the HHSC automatic setting. The  
Dehumidistat should be set to OFF for all seasons except the  
heating season.  
Dehumidistat  
Adjust button  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Dehumidistat Ventilation Control Part #DHVC  
The Dehumidistat Ventilation Control offers ON/OFF, High  
Speed/Low speed plus an electronic dehumidistat.  
Instruction card  
Key Features  
2 Speed Fan setting (Low/High)  
Electronic Dehumidistat  
Instruction Card is inserted in the control  
Slim-line design  
Connect to 3 wire 20 gauge low voltage wire.  
Dehumidistat  
Indicator LEDs  
On  
indicator  
light  
High Speed  
Indicator LED  
High/Low  
Speed  
button  
Turning on the Control  
Press and release the ON/OFF button. The "ON Indicator Light"  
will illuminate.  
ON/OFF  
button  
Adjusting the Ventilation Speed  
The unit will normally operate at low speed. Press and release the  
SPEED button to initiate high speed ventilation. The "High Speed  
Indicator LED" will illuminate.  
Humidity Control  
Your unit will produce a dehumidifying effect when outdoor  
humidity levels are lower than indoor humidity levels. Never use  
the dehumidistat feature when outdoor temperatures are above  
59° F (15° C).  
ATTENTION  
*Install a jumper between 2 (ON) and 3 (RED) on the  
HRV/ERV terminal block to configure the ON/OFF  
button to ON/STANDBY. Refer to “Setting Standby  
when using a Main Control” in this manual.  
Setting the Dehumidistat  
Press and release the DEHUMIDISTAT button until the  
DEHUMIDISTAT LED is at the desired setting. After 5 seconds  
the dehumidistat light will either flash or be on continuous.  
A flashing light indicates the humidity level is higher than the  
setting and the unit is operating on high speed ventilation. A  
continuous light indicates the humidity level is lower than the  
setting.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Vent Timer Control (VTC)  
The timer will override the Operational Mode (regardless of the  
setting) and initiate high speed ventilation. Upon completion of the  
timer cycle, the HRV/ERV returns to your selected Operational  
Mode and speed setting.  
ATTENTION  
If the system does not have a main control  
installed, the HRV/ERV Terminal Block must have  
a jumper installed between 2 (ON) and 3 (RED).  
Refer to “Operating the HRV/ERV without a Main  
Control” in this manual.  
Lifestyle 20/40/60 Minute Timer  
Initiates high speed ventilation for 20, 40 or 60 minutes. The  
20/40/60 Minute Status Lights indicate high speed operation.  
Lockout Mode is useful if you wish to disable the timer. Set  
lockout by holding the Select Button for 5 seconds. Unlock by  
holding for 5 seconds.  
20/40/60 Minute  
Status Lights  
Select Button  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Routine for HRV  
1. Inspect Exterior Hoods at least once a month.  
Make sure exhaust and fresh air supply hoods are not blocked or  
restricted by leaves, grass, or snow. In winter, it is especially  
important to make sure snow is not blocking the hoods or that frost  
has not built up on the wire mesh (bird screen).  
6. Clean Duct Work if Required  
The duct work running to and from the HRV may accumulate dirt.  
Wipe and vacuum the duct once every year. You may wish to  
contact a Heating/Ventilation company to do this.  
7. General Maintenance - Twice a Year  
Wipe down the inside of the cabinet with a damp cloth to remove  
dirt, bugs, and debris that may be present.  
WARNING: Blockage of hoods may cause an imbalance.  
2. Clean Air Filters (clean twice a year)  
The standard filters equipped with your HRV are removable and  
washable.  
a) simply open access door and slide core out  
b) remove filter clips  
c) once clips are removed filters can be taken off the core to be  
rinsed with water or a combination of mild soap and water. Do  
not clean in the dishwasher  
d) to re-assemble, place clean filter(s) (wet or dry) back into their  
positions against the core and return clips to their original  
position  
8. Cleaning the Fans  
Fans may accumulate dirt causing an imbalance and/or excessive  
vibration of the HRV. A reduction in the air flow may also occur.  
In new construction this may result within the first year due to  
heavy dust and may occur periodically after that over time  
depending on the outdoor conditions.  
unplug the HRV and open the service door  
remove the core  
remove ducting (metal and/or flexible insulated type) from  
the red and/or blue ports which are connected immediately  
in-line with the fan assembly  
e) slide core back into its’ original position  
3. Clean Core Twice a Year  
use a small brush, such as an old toothbrush or pipe cleaner,  
and insert first  
a) open access door.  
b) carefully grip ends of core and pull evenly outward. Core may  
be snug, but will slide out of the channel  
c) once removed from the cabinet remove filters  
d) wash core in warm soapy water (do not use dishwasher)  
e) install the clean filters  
f) install clean core  
Note: Core installation label on the outer end of the core.  
(a) through the large opening of the fan  
assembly and then  
(b) through the smaller opening in the end  
of the fan assembly.  
scrub individual fan blades until clean. Avoid moving or  
damaging balancing flat weight, clip is usually found on one  
or more of the fan blades  
To install the clean core:  
a) first mount the bottom flange of the core guide into the bottom  
H channel approximately 1/4” (6mm)  
b) mount the left or right side flange of the core guide  
approximately 1/4” (6mm) followed by the other side  
vacuum and wipe  
reassemble making sure ducting is reattached firmly and  
insulation and moisture barrier are sealed and taped  
c) mount the top flange of the core guide into the top H channel  
approximately 1/4” (6mm).  
Before attempting this task, thought should be given to having a  
qualified service technician complete the service work.  
d) with all four corners in place and the core straight and even,  
push hard in the centre of the core until the core stops on the  
back of the cabinet.  
NOTE: Core will appear to stick out from cabinet approximately 1/8”  
(3mm). This is designed this way so that the access door will fit tight  
against the core.  
WARNING  
Electric shock hazard. Can cause  
injury or death. Before attempting to  
perform any service or maintenance,  
turn the electrical power unit OFF at  
disconnect switch(es). Unit may have  
multiple power supplies.  
4. Motors - Maintenance Free  
5. Drain (condensate) Line - Clean once a year  
Inspect drain line, drain spout, and “P” trap for blockage, mould or  
kinks. Flush with warm soapy water and replace if worn, bent or  
unable to clean.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model FC95HRV  
Performance (HVI certified)  
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE  
The cross-flow heat recovery core transfers heat between the two  
airstreams. It is easily removed for cleaning or service.  
Net supply air flow in cfm (L/s) against external static pressure  
E.S.P  
(external static pressure)  
[cfm (L/s)]  
MOTORS AND BLOWERS  
@ 0.1" (25 Pa)  
@ 0.2" (50 Pa)  
@ 0.3" (75 Pa)  
@ 0.4" (100 Pa)  
76 (36)  
73 (34)  
70 (33)  
66 (31)  
Each air stream has one centrifugal blower driven by a common PSC  
motor. The unit has a 2 speed fan operation.  
FILTERS  
Washable air filters in exhaust and supply air streams.  
MOUNTING THE HRV  
@ 0.5" (125 Pa)  
60 (29)  
88%  
Four threaded inserts at corners of the cabinet designed to accept the “S”  
hooks and hanging straps supplied with the unit.  
Max. Temperature Recovery  
Sensible Effectiveness  
@ 60 cfm (28 L/s)  
32°F (0°C)  
32°F (0°C)  
88%  
75%  
DEFROST  
*Sensible Efficiency  
@ 60 cfm (28 L/s)  
Recirculating defrost system.  
CASE  
*Sensible Efficiency  
@ 61 cfm (29 L/s)  
Twenty gauge prepainted galvanized steel (G60) for superior corrosion  
resistance. Insulated to prevent exterior condensation. Drain connections  
2 - 1/2" (12 mm) OD.  
-13°F (-25°C)  
68%  
120  
59  
VAC @ 60HZ  
WATTS / Low speed.  
WATTS / High speed  
Amp rating  
WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs (25.4 kg)  
150  
0.9  
ELECTRONICS  
• Built-in Relay for Interfacing to furnace  
*Sensible Efficiency – thermal **Latent Efficiency – moisture  
Note: Effectiveness - based on temp. differential between the 2 airstreams  
Efficiency – takes into account all power inputs  
OPTIONAL CONTROLS  
80  
# DHVC Ventilation Control  
2 - High Speed  
1 - Low Speed  
Speed 2  
• 2 Speed Fan setting (Low/High) • Dehumidistat  
#HHSC Healthy Home System Control  
• Automatically activates the unit to deliver fresh air into your home  
70  
60  
50  
40  
30  
20  
#DH1  
Dehumidistat  
• Initiates high speed ventilation when the indoor humidity level exceeds  
the set point  
Speed 1  
OPTIONAL TIMERS  
#VTC  
Ventilation Timer Control - Initiates high speed ventilation  
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100'  
length  
OPTIONAL ACCESSORIES  
#WH 185 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh  
screen  
0
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
Static Pressure (in w.g.)  
DIMENSIONS FC95HRV inches (mm)  
All units conform to CSA and UL standards.  
Hanging  
straps (4)  
18.5"  
(470 mm)  
Threaded  
inserts (4)  
at corners  
WARRANTY  
18.5"  
EXHAUST  
Stale Air  
to outside  
Units carry a LIFETIME warranty on the  
heat recovery core and a 5 year  
replacement parts warranty.  
(470 mm)  
SUPPLY  
Fresh air  
from outside  
5" round collar  
Removable  
Heat Recovery  
Core  
5" round collar  
EXHAUST  
Return air  
from building  
SUPPLY  
Fresh air  
to building  
6" round  
(conv. to oval)  
collar  
minimum  
18 inches (459 mm)  
required for  
6" round (conv. to oval)  
collar  
Drain Pan  
service access  
16"  
(406 mm)  
Drain spout  
FRONT  
SIDE  
TOP  
Date: ___________________________________________  
Tag: _____________________Qty:___________________  
Project: _________________________________________  
Engineer: _______________________________________  
Contractor: ______________________________________  
Supplier: ________________________________________  
Quote#: _________________________________________  
Submitted by: ____________________________________  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Port Configuration and Airflow  
Model FC95HRV  
In order to make the HRV as space efficient as possible, the  
INDOOR supply and return ports are converted from round to oval  
shape. Overall size of the port remains the same. Simply bend a  
standard duct fitting to the correct shape, and attach to the oval  
port using the same method as for a round port.  
Round port bent to oval  
FC95HRV Air Flow  
Stale air enters the FRONT-RIGHT side port. The air passes down  
the front half of the core, then up the back half of the core and out  
the RIGHT-REAR port.  
Fresh outdoor air enters the LEFT-REAR port and passes down  
the back half of the core. Then the fresh outdoor air passes up the  
front half of the core and out the LEFT-FRONT port. This  
configuration allows the air to actually travel through the core  
twice, which makes the FC95HRV nearly as efficient as a double  
core unit.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model FC155HRV  
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE  
The cross-flow heat recovery core transfers heat between the two  
airstreams. It is easily removed for cleaning or service.  
Performance (HVI certified)  
Net supply air flow in cfm (L/s) against external static pressure  
E.S.P  
(external static pressure)  
[cfm (L/s)]  
MOTORS AND BLOWERS  
@ 0.1" (25 Pa)  
@ 0.2" (50 Pa)  
@ 0.3" (75 Pa)  
@ 0.4" (100 Pa)  
@ 0.5" (125 Pa)  
144 (68)  
134 (63)  
125 (59)  
113 (53)  
92 (43)  
Each air stream has one centrifugal blower driven by a common PSC  
motor. 2 speed fan operation.  
FILTERS  
Washable air filters in exhaust and supply air streams.  
MOUNTING THE HRV  
Four threaded inserts at corners of the cabinet designed to accept the “S”  
hooks and hanging straps supplied with the unit.  
@ 0.6" (150 Pa)  
73 (34)  
78%  
Max. Temperature Recovery  
Sensible Effectiveness  
@ 65 cfm (31 L/s)  
DEFROST  
32°F (0°C)  
32°F (0°C)  
73%  
64%  
Recirculating damper defrost system.  
*Sensible Efficiency  
@ 65 cfm (31 L/s)  
CASE  
*Sensible Efficiency  
@ 68 cfm (32 L/s)  
Twenty gauge prepainted galvanized steel (G60) for superior corrosion  
resistance. Insulated to prevent exterior condensation. Drain connections  
2 - 1/2" (12 mm) OD. Balancing ports are located in the door.  
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)  
-13°F (-25°C)  
66%  
120  
49  
VAC @ 60HZ  
WATTS / Low speed.  
WATTS / High speed  
Amp rating  
120  
1.4  
ELECTRONICS  
• Built-in Relay for Interfacing to furnace  
*Sensible Efficiency – thermal **Latent Efficiency – moisture  
Note: Effectiveness - based on temp. differential between the 2 airstreams  
Efficiency – takes into account all power inputs  
OPTIONAL CONTROLS  
# DHVC Ventilation Control  
• 2 Speed Fan setting (Low/High) • Dehumidistat  
#HHSC Healthy Home System Control  
• Automatically activates the unit to deliver fresh air into your home  
160  
2 - High Speed  
2
*1 - Low speed  
#DH1  
Dehumidistat  
* Manufacturers Data  
140  
120  
100  
80  
• Initiates high speed ventilation when the indoor humidity level exceeds  
the set point  
OPTIONAL TIMERS  
#VTC  
Ventilation Timer Control - Initiates high speed ventilation  
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100'  
length  
OPTIONAL ACCESSORIES  
60  
#WH 186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh  
1
screen  
40  
DIMENSIONS FC155HRV inches (mm)  
20  
0
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
Static Pressure (in w.g.)  
FRESH AIR  
FROM OUTSIDE  
STALE AIR  
FROM INSIDE  
*NOTE: Front clearance of 25 inches (635 mm)  
is recommended for servicing unit.  
FILTERS  
BALANCING DAMPER  
RECIRCULATING  
DEFROST  
DAMPER  
All units conform to CSA and UL standards.  
BLOWERS  
MOTOR  
CORE  
WARRANTY  
Units carry a LIFETIME warranty on the heat  
recovery core and a 5 year replacement parts  
warranty.  
STALE AIR  
TO OUTSIDE  
FRESH AIR  
TO INSIDE  
33 5/8"  
(850mm)  
14 3/4"  
(375)  
BALANCING DAMPER  
CONDENSATE DRAINS  
*All Duct Connections 6" (150mm)  
Date: ___________________________________________  
Tag: _____________________Qty:___________________  
Project: _________________________________________  
Engineer: _______________________________________  
Contractor: ______________________________________  
Supplier: ________________________________________  
Quote#:_________________________________________  
Submitted by: ____________________________________  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model FC200HRV  
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE  
The cross-flow heat recovery core transfers heat between the two  
airstreams. It is easily removed for cleaning or service.  
Performance (HVI certified)  
Net supply air flow in cfm (L/s) against external static pressure  
E.S.P  
(external static pressure)  
[cfm (L/s)]  
MOTORS AND BLOWERS  
@ 0.1" (25 Pa)  
@ 0.2" (50 Pa)  
@ 0.3" (75 Pa)  
@ 0.4" (100 Pa)  
@ 0.5" (125 Pa)  
@ 0.6" (150 Pa)  
@ 0.7" (175 Pa)  
@ 0.8" (200 Pa)  
207 (97)  
200 (94)  
184 (87)  
171 (80)  
152 (71)  
130 (61)  
116 (55)  
86 (40)  
Each air stream has one centrifugal blower driven by a common PSC  
motor. 2 speed fan operation.  
FILTERS  
Washable air filters in exhaust and supply air streams.  
MOUNTING THE HRV  
Four threaded inserts at corners of the cabinet designed to accept the “S”  
hooks and hanging straps supplied with the unit.  
Max. Temperature Recovery  
74%  
Sensible Effectiveness  
@ 66 cfm (31 L/s)  
DEFROST  
32°F (0°C)  
32°F (0°C)  
74%  
64%  
Recirculating damper defrost system.  
*Sensible Efficiency  
@ 66 cfm (31 L/s)  
CASE  
*Sensible Efficiency  
@ 109 cfm (51 L/s)  
Twenty gauge prepainted galvanized steel (G60) for superior corrosion  
resistance. Insulated to prevent exterior condensation. Drain connections 2  
- 1/2" (12 mm) OD. Balancing ports are located in the door.  
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs (33.5 kg)  
-13°F (-25°C)  
62%  
120  
87  
VAC @ 60HZ  
WATTS / Low speed.  
WATTS / High speed  
Amp rating  
164  
1.4  
ELECTRONICS  
• Built-in Relay for Interfacing to furnace  
*Sensible Efficiency – thermal **Latent Efficiency – moisture  
Note: Effectiveness - based on temp. differential between the 2 airstreams  
Efficiency – takes into account all power inputs  
OPTIONAL CONTROLS  
# DHVC Ventilation Control  
• 2 Speed Fan setting (Low/High) • Dehumidistat  
#HHSC Healthy Home System Control  
• Automatically activates the unit to deliver fresh air into your home  
220  
Hi 3 - High Speed  
Hi 3  
Hi 2 - Medium High Speed  
Hi 1 - Medium Speed  
Low - Low speed  
200  
180  
160  
140  
120  
100  
80  
#DH1  
Dehumidistat  
* Manufacturers Data  
• Initiates high speed ventilation when the indoor humidity level exceeds  
the set point  
Hi 2  
Hi 1  
OPTIONAL TIMERS  
#VTC  
Ventilation Timer Control - Initiates high speed ventilation  
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100'  
length  
LOW  
OPTIONAL ACCESSORIES  
60  
#WH 186 Weatherhoods, Two -6” (150 mm) c/w 1/4” (6 mm) mesh  
40  
screen  
0
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
Static Pressure (in w.g.)  
DIMENSIONS FC200HRV  
inches (mm)  
INSTALLER SELECTABLE HIGH SPEED SETTINGS  
Adjustable DIP switches are located on the circuit board. Hi3 is  
the factory setting. Refer to the Operation and Installation  
manual for the adjustment instructions.  
FRESH AIR  
FROM OUTSIDE  
STALE AIR  
FROM INSIDE  
FILTERS  
BALANCING DAMPER  
RECIRCULATING  
DEFROST  
DAMPER  
BLOWERS  
MOTOR  
CORE  
*NOTE: Front  
clearance  
of 25 inches  
(635 mm)  
All units conform to CSA and UL standards.  
STALE AIR  
TO OUTSIDE  
FRESH AIR  
TO INSIDE  
is recommended  
for servicing unit.  
WARRANTY  
Units carry a LIFETIME warranty on the heat  
recovery core and a 5 year replacement parts  
warranty.  
33 5/8"  
(850 mm)  
14 3/4"  
(375 mm)  
BALANCING DAMPER  
CONDENSATE DRAINS  
*All Duct Connections 6" (150 mm)  
All Duct Connections 6” (160 mm)  
Date: ___________________________________________  
Tag: _____________________Qty:___________________  
Project: _________________________________________  
Engineer: _______________________________________  
Contractor: ______________________________________  
Supplier: ________________________________________  
Quote#:_________________________________________  
Submitted by: ____________________________________  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model FC150ERV  
LATENT RECOVERY/MOISTURE TRANSFER CORE  
The cross-flow energy recovery core transfers heat and water vapor  
between the two airstreams. It is easily removed for cleaning or service.  
MOTORS AND BLOWERS  
Performance  
Net supply air flow in cfm (L/s) against external static pressure  
E.S.P  
(external static pressure)  
[cfm (L/s)]  
Each air stream has one centrifugal blower driven by a common PSC  
motor. 5 speed fan operation.  
@ 0.1" (25 Pa)  
@ 0.2" (50 Pa)  
@ 0.3" (75 Pa)  
@ 0.4" (100 Pa)  
@ 0.5" (125 Pa)  
@ 0.6" (150 Pa)  
@ 0.7" (175 Pa)  
151 (71)  
140 (66)  
131 (62)  
123 (58)  
107 (50)  
98 (46)  
FILTERS  
Washable air filters in exhaust and supply air streams.  
MOUNTING THE ERV  
Four threaded inserts at corners of case designed to accept the "S" hooks  
and hanging straps supplied with the unit.  
CASE  
81 (38)  
Twenty gauge prepainted galvanized steel (G60) for superior corrosion  
resistance. Insulated to prevent exterior condensation. Door balancing  
ports.  
@0.8 " (200 Pa)  
60 (28)  
Sensible Effectiveness  
@ 64 cfm (30 L/s)  
WEIGHT 75 lbs. (34Kg) SHIPPING WEIGHT 77lbs. (35Kg)  
ELECTRONICS  
32°F (0°C)  
32°F (0°C)  
81%  
69%  
*Sensible Efficiency  
@ 64 cfm (30 L/s)  
Built-in Relay for Interfacing to furnace  
Total Efficiency  
@ 64 cfm (30L/s)  
50%  
47%  
OPTIONAL CONTROLS  
95°F (35°C)  
# DHVC Ventilation Control  
• 2 Speed Fan setting (Low/High) • Dehumidistat  
#HHSC Healthy Home System Control  
• Automatically activates the unit to deliver fresh air into your home  
VAC @ 60HZ  
120  
63  
WATTS / Low speed.  
WATTS / High speed  
Amp rating  
173  
1.4  
#DH1  
Dehumidistat  
• Initiates high speed ventilation when the indoor humidity level exceeds  
the set point  
*Sensible Efficiency – thermal **Latent Efficiency – moisture  
Note: Effectiveness - based on temp. differential between the 2 airstreams  
Efficiency – takes into account all power inputs  
OPTIONAL TIMERS  
#VTC  
Ventilation Timer Control - Initiates high speed ventilation  
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100'  
length  
220  
2 - High Speed  
1 - Low speed  
200  
180  
160  
140  
120  
100  
80  
OPTIONAL ACCESSORIES  
#WH 186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh  
2
screen  
60  
1
40  
20  
DIMENSIONS FC150ERV inches (mm)  
0
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
Static Pressure (in w.g.)  
*
All Duct Connections 6"(150mm)  
ENTHALPIC CORE  
MOTOR  
STALE AIR  
FROM INSIDE  
FRESH AIR  
TO INSIDE  
All units conform to CSA and UL  
standards.  
BALANCING  
DAMPER  
BALANCING  
DAMPER  
FILTERS  
WARRANTY  
*NOTE: Front clearance  
of 25 inches (635 mm)  
is recommended  
CORE  
Units carry a five (5) year warranty  
on the enthalpic (ERV) core and a 5  
year replacement parts warranty.  
STALE AIR  
FRESH AIR  
FROM OUTSIDE  
TO OUTSIDE  
for servicing unit.  
3
/4"  
33-5/8"  
(850)  
14  
(375)  
BLOWERS  
Date: ___________________________________________  
Tag: _____________________Qty:___________________  
Project: _________________________________________  
Engineer: _______________________________________  
Contractor: ______________________________________  
Supplier: ________________________________________  
Quote#: _________________________________________  
Submitted by: ____________________________________  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Methods  
The Three Methods of Installation  
The following three installation methods are for the  
HRV/ERV system:  
Installing the Ducting Between the HRV/ERV &  
Living Areas in the House  
A well designed and installed ducting system will allow the  
• The Simplified installation.  
HRV/ERV to operate at its maximum efficiency.  
• The Partially Dedicated Installation  
• The Fully Dedicated Installation  
All ducts should be kept short and have as few bends or  
elbows as possible to maximize airflow. Forty-five degree  
elbows are preferred to 90° elbows. Use "Y" tees instead of  
straight tees whenever possible.  
All duct joints must be fastened with screws, rivets or duct  
sealant and wrapped with mastic or quality duct tape to  
prevent leakage. Mastic is preferred but if duct tape is used,  
we recommend aluminum foil duct tape.  
Simplified Installations  
The Simplified Installation draws stale air from the cold air  
return duct of the air handler/furnace and introduces an  
equal amount of fresh air farther downstream into the cold  
air return. Refer to "Simplified Installation Diagrams".  
Galvanized (rigid) ducting from the HRV/ERV to the living  
areas in the house is recommended whenever possible  
although flexible duct can be used in moderation if  
necessary.  
A short length (approximately 12 inches or 300mm) of non-  
metallic flexible insulated duct should be connected  
between the HRV/ERV and the supply/exhaust duct system  
to avoid possible noise transfer through the duct system.  
The air handler/furnace blower must be running when the  
unit is operating for this system to be effective. Refer to  
"Interlocking the HRV/ERV to an Air Handler/Furnace  
Blower".  
Partially Dedicated Installations  
The Partially Dedicated Installation draws stale air from  
specific points in the house and introduces an equal amount  
of fresh air into the cold air return. Refer to "Partially  
Dedicated Installation Diagrams".  
All ducts running through attics and unheated spaces must  
be sealed and insulated to code.  
Stale air ducts should be installed in areas of the home  
where the poorest indoor air quality exists (bathrooms and  
kitchen). Each location with a stale air duct should have a  
timer to initiate high speed ventilation. Refer to "Optional  
Timers" in this manual.  
ATTENTION  
Applications such as greenhouses, atriums,  
swimming pools, saunas, etc. have unique  
ventilation requirements which should be  
addressed with an isolated ventilation system.  
The air handler/furnace blower should be running when the  
HRV is operating to evenly distribute the fresh air  
throughout the house. Refer to "Interlocking the HRV/ERV  
to an Air Handler/Furnace Blower".  
Fully Dedicated Installations  
The Fully Dedicated Installation draws stale air from  
specific points in the house and delivers fresh air to specific  
locations of the house. This system is not connected to an  
air handler/furnace. Refer to "The Fully Dedicated  
Installation Diagrams" in this manual.  
Stale air ducts should be installed in areas of the home  
where the poorest indoor air quality exists (bathrooms and  
kitchen). Each location with a stale air duct should have a  
timer which will initiate high speed ventilation. Refer to  
"Optional Timers" in this manual.  
Fresh air ducts should be installed to all bedrooms and  
living areas, excluding bathrooms, kitchen and utility areas.  
Grilles should be located high on a wall or in ceiling  
locations. Grilles that diffuse the air comfortably are  
recommended. Refer to "Grilles" in this manual. Special  
care should be taken in locating grilles if the floor is the  
only option available. Areas such as under baseboard  
heaters will help to temper the air.  
Optional in-line duct heaters are available for mounting in  
the supply duct work to add heat if required.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Simplified Installation Diagrams  
Simplified Installation (Return/Return Method)  
Key Points  
The HRV/ERV must be balanced.  
It is mandatory that the furnace blower run continuously or  
HRV/ERV operation be interlocked with the furnace  
blower. (Refer to “Interlocking the HRV/ERV to an Air  
Handler/Furnace Blower.”)  
The duct configuration may change depending on the  
HRV/ERV model. See specifications for your unit.  
Check local codes / authority having jurisdiction for  
acceptance.  
A backdraft damper is required in the exhaust air duct to  
prevent outdoor air from entering the unit when the  
Furnace/Air Handler is running and the unit is in Standby,  
OFF or Recirculate.  
Sizing the Ductwork  
It is the responsibility of the installer to ensure all ductwork is  
sized and installed as designed to ensure the system will  
perform as intended.  
The amount of air (cfm) that an HRV/ERV will deliver is  
directly related to the total external static pressure (E.S.P.) of  
the system. Static pressure is a measure of resistance imposed  
on the blower by length of duct work plus the number of  
fittings used in the duct work.  
IOof oth te HV UPAISRAan
DIRECT CONNECTION of the SUPPLY AIR STREAM and  
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN.  
RETURN AIR  
40" (1m) MINIMUM  
3' min.  
recommended  
Dampers for  
balancing  
airflows  
Outdoors  
Backdraft  
Damper  
Cool Air  
Return  
Forced Air  
Furnace  
Leaf Hinge  
(not included)  
Install the Backdraft Damper with the leaf hinge vertical.  
The damper is installed on the “Stale Air to Outside Collar”.  
Spring-Loaded Backdraft Damper  
) arfDr at S
WARNING  
The Stale Air to Outside air duct requires  
a Backdraft Damper. This damper prevents  
outdoor air from entering the HRV  
during the operation of the Furnace/  
Air Handler while the HRV is in standby,  
OFF or Recirculate.  
Installation Notes  
Unit is normally balanced on HIGH speed with the furnace blower ON.  
A minimum separation of 40 inches (1m) is recommended between the  
two direct connections.  
The exhaust air connection should be upstream of the supply air  
connection to prevent exhausting any fresh air.  
Weatherhood arrangement is for drawing purposes only. Six feet (2m)  
minimum separation is recommended. The Weatherhood must also be 18"  
(460mm) above grade minimum.  
The airflow must be confirmed on site using the balancing procedures found in this manual  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Partially Dedicated Installation Diagrams  
Partially Dedicated System  
This installation enables stale air to be drawn from the  
poorest air quality areas of the home (bathrooms, kitchen).  
Key Points  
The HRV/ERV must be balanced.  
It is recommended that the furnace blower run  
continuously or HRV/ERV operation be interlocked  
with the furnace blower to evenly distribute the fresh air  
throughout the house.(Refer to “Interlocking the  
HRV/ERV to an Air Handler/Furnace Blower.”)  
The duct configuration may change depending on the  
HRV model. See specifications for your unit.  
Check local codes/authority having jurisdiction for  
acceptance.  
A backdraft damper is required in the exhaust air duct to  
prevent outdoor air from entering the unit when the  
Furnace/Air Handler is running and the unit is in  
Standby, OFF or Recirculate.  
Sizing the Ductwork  
It is the responsibility of the installer to ensure all  
ductwork is sized and installed as designed to ensure the  
system will perform as intended.  
The amount of air (cfm) that an HRV/ERV will deliver is  
directly related to the total external static pressure (E.S.P.)  
of the system. Static pressure is a measure of resistance  
imposed on the blower by length of duct work plus the  
number of fittings used in the duct work.  
DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN  
(Stale air drawn from key areas of home)  
EXHAUST AIR from various parts of home.  
i.e. bathrooms (if required), kitchens (if required).  
Return Air  
3' min.  
Outdoors  
recommended  
Dampers for  
balancing  
airflows  
Backdraft  
Damper  
Cool Air  
Return  
leaf hinge  
Forced Air  
Furnace  
(not included)  
Install the Backdraft Damper with the leaf hinge vertical.  
The damper is installed on the “Stale Air to Outside Collar”.  
Spring-Loaded Backdraft Damper  
WARNING  
Installation Notes  
The Stale Air to Outside air duct requires  
a Backdraft Damper. This damper prevents  
outdoor air from entering the HRV during  
the operation of the Furnace/Air Handler  
while the HRV is in standby, OFF or  
Recirculate.  
Unit is normally balanced on HIGH speed with the furnace blower ON.  
Weatherhood arrangement is for drawing purposes only. Six feet (2m)  
minimum separation is recommended. The Weatherhood must also be 18"  
(460mm) above grade minimum.  
The airflow must be confirmed on site using the balancing procedures  
found in this manual.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fully Dedicated Installation Diagrams  
Fully Dedicated System  
This is a stand alone HRV/ERV system which  
is not connected to a force air system. Stale air  
is drawn from key areas of the home (bathroom,  
kitchen) while fresh air is supplied to main  
living areas.  
Key Points  
The HRV/ERV must be balanced.  
The duct configuration may change  
depending on the HRV/ERV model. See  
specifications for your unit.  
Check local codes / authority having  
jurisdiction for acceptance.  
Fresh air to house -  
main living areas.  
bedrooms, livingroom,  
rec. room, etc.  
Stale air from various  
parts of home.  
i.e. bathrooms (if required)  
Kitchens (if required)  
Outdoors  
Dampers for  
balancing  
airflows  
Installation Notes  
• Unit is normally balanced on HIGH speed with the furnace blower ON.  
• Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation  
is recommended. The Weatherhood must also be 18" (460mm) above grade minimum.  
• The airflow must be confirmed on site using the balancing procedures found in this manual.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Location  
Install the unit in a heated space that provides convenient space for  
service access. A typical location is in either a mechanical room or  
an area close to the outside wall within close proximity to where  
the weatherhoods are mounted. If a basement area is inconvenient  
or non- existent, install the unit in a utility or laundry room.  
WARNING  
Improper installation, adjustment, alteration,  
service or maintenance can cause property  
damage, personal injury or loss of life.  
Installation and service must be performed by  
a qualified installer or service agency.  
Attic installations are not recommended due to:  
A) the complexity of work to install  
B) freezing conditions in the attic  
C) difficulty of access for servicing and cleaning  
CAUTION  
Leave sufficient clearance at the front of the access door for  
servicing the air filters and core. The recommended clearance is a  
minimum of 25" (635 mm) for opening and closing the door. Field  
Controls provides four straps for hanging the unit from the  
basement floor joists.  
Unit must be installed level to ensure proper  
condensate drainage. Due to the broad range of  
installation and operational conditions, consider  
the possibility of condensation forming on either  
the unit or connecting ducting. Objects below the  
installation may be exposed to condensate.  
Suspend the Unit with the Adjustable Hanging Straps  
Use 4 screws and 4 washers (not incldued) to attach the hanging By design, the adjustable hanging straps reduce the possibility of  
straps to the floor joists. The washer must be wider than the eyelet noise, resonance, and harmonics.  
of the grommet on the hanging strap.  
STEP 3. Hook the bottom grommets of the straps through the "S"  
hooks. Pull down vertically on the hand loops while lifting up the  
bottom of the cabinet. Repeat at opposite end of the unit.  
STEP 1. Insert the screws and washers (not included) through  
the Hanging Strap grommets and fasten to the joists.  
Joist  
Hanging Strap grommets  
Washers (not included)  
Note: Do not pull the  
Buckles  
Hand Loops in a  
horizontal or lateral  
direction during the  
Hand Loops  
installation/adjustment  
process.  
Screws (not included)  
Pull down on the hand  
loops while lifting  
the bottom of the unit.  
Buckles  
Hand Loops  
STEP 4. Level the unit from left to right and front to back.  
- Adjust the unit down by lifting up on the buckle.  
STEP 2. Unscrew the 4 machine screws located on the upper  
side of the unit. Attach the "S" hooks and reinsert the machine  
screws.  
- Adjust the unit up by pulling down vertically on the Hand  
Loops while lifting up the bottom of the cabinet.  
STEP 5. Fold the hand loops and excess strap and secure with a  
nylon tie (not included).  
DETAIL  
Straps  
Note:This illustration of the unit may  
vary from the unit you are installing.  
“S” hooks  
Hand Loops  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drain Connection (HRV only)  
Drain Connection  
DRAIN HOSE PLUMBING  
The HRV may produce some condensation during a defrost cycle.  
This water should flow into a nearby drain, or be taken away by a  
condensate pump.  
PRE-PUNCHED HOLES (2)  
DRAIN PAN  
DRAIN PAN  
CAUTION  
DRAIN  
SPOUT  
DRAIN  
SPOUT  
The HRV and all condensate lines must be  
installed in a space where the temperature is  
maintained above the freezing point or freeze  
protection must be provided.  
ZIP TIE  
TEE  
CONNECTOR  
1/2 " I.D.  
DRAIN HOSE  
TO DRAIN  
The HRV cabinet has prepunched holes for the drain (see below).  
Insert the drain spout through the hole in the drain pan. Be sure to  
install the "O ring" which seals each spout to the pan. HAND  
TIGHTEN the washer and lock nut which hold the drain spout in  
place.  
HARD PIPE PLUMBING  
PRE-PUNCHED HOLES (2)  
Construct a P-Trap using the plastic tee connector. Cut two lengths  
of 1/2" drain hose (not included) and connect the other ends to the  
two drain spouts. Position the "T" fitting to point upward and  
connect the drain line. Tape or fasten base to avoid any kinks. Pour  
a cup of water into the drain pan of the HRV after the drain  
connection is complete. This creates a water seal which will  
prevent odors from being drawn up the hose and into the fresh air  
supply of the HRV.  
DRAIN PAN  
DRAIN PAN  
1/2" HARD PIPE  
DRAIN  
SPOUT  
DRAIN  
SPOUT  
TEE  
JOINT  
TO DRAIN  
Note: Secondary drain pan may be required to protect from  
condensate leakage.  
CAUTION  
Drain trap and tubing MUST be below  
bottom of door with 1/4" per foot  
downwards slope away from unit.  
Grilles  
Adjustable grilles should be used to balance the flow rates into and  
out of various rooms. The grilles should not be adjusted after  
balancing the unit.  
The Techgrille  
The TECHGRILLE is a round, fully adjustable grille, which  
provides superior, quiet air distribution.  
Grilles or diffusers should be positioned high on the wall or in the  
ceiling. Kitchen Exhaust grilles must never be connected to the  
range hood. They should be installed at least 4 feet (1.2 m)  
horizontally away from the stove.  
Field supplied balancing dampers should be installed external to  
the unit to balance the amount of stale air being exhausted with the  
amount of fresh air being brought into the house. Refer to Air flow  
Balancing section.  
4” (100 mm) Part No. 99-EAG4  
5” (125 mm) Part No. 99-EAG5  
6” (150 mm) Part No. 99-EAG6  
CAUTION  
Do not mount exhaust grille within 4’  
(1.2m) (horizontally) of a stove to prevent  
grease from entering the unit.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weatherhood Installation  
Installing the Ducting from the  
Weatherhoods to the HRV/ERV  
Weatherhoods  
Fixed covered weatherhoods have a built-in bird screen with a 1/4"  
(6mm) mesh to prevent foreign objects from entering the  
ductwork.  
The inner and outer liners of the flexible insulated duct must be  
clamped to the sleeve of the weatherhoods (as close to the outside  
as possible) and the appropriate port on the HRV/ERV. It is very  
important that the fresh air intake line be given special attention to  
make sure it is well sealed. A good bead of high quality caulking  
(preferably acoustical sealant) will seal the inner flexible duct to  
both the HRV/ERV port and the weatherhood prior to clamping.  
5” (125 mm) Part No.WH 185  
6” (150 mm) Part No.WH 186  
Weatherhood Installation  
COLLAR IS SUPPLIED TO  
To minimize air flow restriction, the flexible insulated duct that  
connects the two outside weatherhoods to the HRV/ERV should  
be stretched tightly and be as short as possible.  
ENSURE VAPOUR BARRIER  
IS 100% SEALED TO  
WALL PLATE  
SCREEN  
(side view)  
Twisting or folding the duct will severely restrict air flow.  
Hard (rigid) ducting which has been sealed and insulated should be  
used for runs over 10’ (3.3 m). Refer to your building code.  
12" galvanized  
pipe supplied  
Intake Weatherhood Requirements  
Should be located upstream (if there are prevailing winds)  
from the exhaust outlet  
At least 6' (2 m) from the exhaust weatherhood  
At least 6' (2 m) away from dryer vents and furnace exhaust  
(medium or high efficiency furnaces)  
EXTERIOR  
WALL  
1/4" (6 mm) SCREEN  
(front view)  
1. Thermal Collar slides over galvanized  
sleeve of Weatherhood.  
2. Fasten Thermal Collar to Belt.  
3. Slide the Insulated Flexible Ducting over  
the Weatherhood's galvanized sleeve and  
fasten it to the Thermal Collar.  
A minimum of at least 6' (2 m) from driveways, oil fill pipes,  
gas meters, or garbage containers  
At least 18" (460 mm) above the ground, or above the depth  
of expected snow accumulation  
At least 3' (1 m) from the corner of the building  
Do not locate in a garage, attic or crawl space  
4. Hood is hinged to allow for easy access  
for cleaning of bird screen.  
OUTSIDE CORNER  
INSIDE CORNER  
36" (1m)  
recommended min.  
36" (1m)  
recommended min.  
Exhaust Weatherhood Requirements  
At least 6' (2 m) from the ventilation air intake  
At least 18" (460 mm) above ground or above the depth of  
expected snow accumulation  
At least 3' (1 m) away from the corner of the building  
Not near a gas meter, electric meter or a walkway where fog  
or ice could create a hazard  
6' (2m)  
recommended min.  
EXHAUST  
INTAKE  
Not into a garage, workshop or other unheated space  
18" (460mm) min.  
18" (460mm) min.  
When installing the weatherhood, its outside perimeter must be  
sealed with exterior caulking.  
ATTENTION  
CAUTION  
Local codes may require greater distances for  
exhaust and intake.  
Weatherhood arrangement - requires a minimum of  
6' (2m) separation and a minimum of 18" (460mm)  
above the ground, or above the depth of expected  
snow accumulation.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of the Dehumidistat or Dehumidistat Ventilation Control  
Standard Series Controls may be installed onto a flush mounted  
2" x 4" electrical switch box or it may be surface mounted onto a  
wall.  
ATTENTION  
Pay special attention not to damage the Contact  
Pins when attaching and detaching the Face Plate.  
(Figure B)  
Only 1 master control should be installed to a ventilation system  
(the Face Plate on this illustration may not be exactly the same as  
yours).  
1. Remove the Operating Instructions Card from the top of the  
Operating  
Instructions Card  
Control (Figure A).  
2. Separate the Face Plate from the Back Plate by firmly pulling  
apart (Figure B). Be careful not to damage Face Plate Contact  
Pins.  
Face  
Back  
Plate  
Plate  
3. Place the Back Plate of the control in the desired location on  
the wall and pencil mark the wall in the center of the Wire  
Opening, Top Screw Hole and Bottom Screw Hole (Figure C).  
Face Plate  
Contact  
Pins  
4. Remove the Back Plate and drill a 3/8" opening in the wall to  
allow for the Wire Opening and a 1/8" hole for the Wall  
Anchors for the top and bottom screw holes (Figure D).  
5. Pull 3/20 wire through the opening in the wall and the Wire  
Opening of the Back Plate (Figure C).  
Separate the  
Face Plate from  
the Back Plate.  
Figure A -  
Face Plate  
Figure B  
6. Connect Red, Green and Yellow to the Wiring Terminals  
located on the Back Plate (Figure C).  
Side View  
7. Secure a single wire to the Wire Retainer located on the Back  
Plate (Figure C).  
8. Attach the Back Plate to the wall using the 2 supplied screws  
Top Screw  
Hole  
and anchors.  
Drill a 1/8” hole  
for the Top Screw  
and Anchor  
9. Attach the Face Plate to the Back Plate (Figure B).  
Note: Be careful to correctly align the Face Plate to avoid  
damaging the Face Plate Contact Pins.  
TOP  
Wire  
Opening  
10. Insert the Operating Instructions Card into the control (Figure  
Drill a 3/8” hole  
for the Wire  
opening  
A).  
Wire  
11. Connect the 3/20 wire to the Terminal Block located on  
Retainer  
Drill a 1/8” hole  
for the Bottom  
Screw and  
ventilator (Figure E).  
Wiring  
Terminals  
Anchor  
Bottom  
Screw Hole  
Figure C  
Figure D  
Front View of Back Plate  
Drill holes in wall  
Wall Face  
Red #3  
Back  
Plate  
Yellow #4  
Green #5  
Face  
Plate  
Face Plate  
Contact  
Pins  
Figure E  
Terminal Block located  
on ventilator  
• Yellow to YELLOW #4  
• Red to RED #3  
• Green to GREEN #5  
Use 3/20 wire  
Dehumidistat Sensor  
Openings to room  
air allow accurate  
sensor readings.  
Figure F  
Correct Installation  
of Back Plate  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Operation of 20/40/60 Minute Timer  
Operating your 20/40/60 Minute Timer  
Press and release the Select Button to activate high speed  
override. The High Speed Status Light will illuminate and  
the unit will run on high speed ventilation for 20 minutes.  
High Speed  
Status Lights  
The 20/40/60 Minute timers provide an extended override  
time of 20 - 40 additional minutes simply by pressing and  
releasing the select button.  
Yellow  
Red  
The High Speed Status Light will dim after 10 seconds of  
run time.  
Select Button  
Green  
initiates high speed  
ventilation for 20, 40  
or 60 minutes.  
The High Speed Status Light will flash during the last 5  
minutes of the cycle.  
All timers connected to the unit will illuminate for the  
duration of the override when the Select Button is pressed.  
Lockout Mode  
Lockout Mode is used to disable the timers.  
NOTE ABOUT TIMERS  
The timer can be set to lockout mode by pressing and  
holding the Select Button for five seconds. After five  
seconds, the High Speed Status Light will flash; release the  
Select Button. The timer is now in lockout mode. If the  
Select Button is pressed during lockout mode the High  
Speed Status Light will momentarily illuminate but no  
override will be initiated.  
• Timers mount in standard 2” x 4” electrical boxes.  
• Wire multiple timers individually back to the unit.  
• Use 3/20 low voltage wire  
Red #3  
If lockout mode is initiated when the timer is activated, the  
timer will continue its timed sequence but will not allow any  
further overrides to be initiated. Lockout mode can be  
unlocked by pressing and holding the Select Button for five  
seconds. After five seconds the High Speed Status Light will  
stop flashing. Release the Select Button and the timer will  
now operate normally.  
Yellow #4  
Green #5  
Terminal Block  
Connections  
(from Timer to Terminal Block)  
Yellow on timer to YELLOW #4  
Red on timer to RED #3  
Green on timer to GREEN #5  
ATTENTION  
If the system does not have a main control  
installed, the HRV Terminal Block must have a  
jumper installed between 2 (ON) and 3 (RED).  
Refer to “Operating the HRV without a Main  
Control” in this manual.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of the Healthy Home System™ Control (HHSC)  
HRV/ERV control. The HHSC is also typically used to  
control an FAD fresh air damper.  
2. Complete all wiring connections before restoring power  
to the HVAC system and HRV/ERV.  
Choose a Location  
The HHSC controller can be installed anywhere in your  
home. To simplify the installation, locate the HHSC control  
near the HVAC system and/or the HRV/ERV, since the  
HHSC does not require routine adjustment or occupant  
interaction.  
Programming the HHSC Control  
1. Balance the fresh and stale airflows as instructed in this  
manual.  
To provide the occupants with direct access to the functions  
of the controls, install optional accessory controls  
throughout the house.  
2. Determine the cfm flow rate as instructed in this manual.  
3. To obtain the desired rate of fresh air exchange, refer to  
the HHSC Control Installation Instructions to determine  
the On/Off timer settings for the HHSC Control. Use the  
cfm flow rate determined in step 2 as the computed or  
measured fresh air flow rate (as calculated in the HHSC  
instructions). To ensure adequate ventilation, ensure that  
the “Fan On” time is equal to or greater than the “Vent  
On” time, as programmed in the HHSC Control.  
4. For continuous operation of the HRV/ERV, set  
“Fan On” and “Vent On” to “Un” (unlimited), and “Fan  
Off” and “Vent Off” to any setting except “Un”. This  
setting also causes the HVAC fan to run continuously.  
NOTE: The HHSC Control is factory programmed with the  
default settings of the two On/Off timer values. No  
configuration is required to use these factory default  
settings.  
How To Install the Controller  
1. Separate the HHSC controller cover from the wall plate  
(mounting base) to expose mounting holes  
(see illustration).  
2. Route wires through large hole in the mounting base.  
Mount base against wall and mark wall through  
3 mounting holes.  
3. If mounting on a metal or wood surface, drill three 1/8-in.  
pilot holes in wall where marked for the supplied  
mounting screws. If mounting on drywall or other  
surface, drill appropriate holes for wall anchors or other  
means of attachment.  
4. Secure mounting base to wall with either the 3 screws  
provided or other fasteners, while ensuring that all wires  
extend through the hole in mounting base.  
5. Adjust length and routing of each wire to reach the  
proper terminal and connector block on mounting base,  
while leaving a 1/4 in. length of extra wire. Strip only  
1/4 in. of insulation from each wire to prevent adjacent  
wires from shorting together when connected.  
6. Connect wires to their respective terminals on the  
connector block. (Figure 1) Both (R) and (C) must be  
connected for proper operation. Improper wiring or  
installation may damage the controller. Ensure wiring is  
correct before proceeding with installation or turning the  
unit on.  
Default settings:  
FAN OFF  
FAN ON  
VENT ON  
VENT OFF  
20 minutes  
10 minutes  
10 minutes  
20 minutes  
7. Push any excess wire into wall and against mounting  
base.  
8. Snap cover onto base, while ensuring pins align with  
sockets in connector.  
9. Once powered the HHSC automatically enters into  
operating mode.  
Complete the Wiring Connections  
1. Refer to subsequent wiring diagrams in this manual  
that correspond to the desired control configuration.  
NOTE: Disregard any wiring schematic(s) included with the  
HHSC Control Installation Instructions that do not pertain to  
Illustration of HHSC Control with cover off  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of the Healthy Home System™ Control (HHSC)  
HHSC CONTROL  
Gt  
C
Wt  
Gf  
R
V
HI  
C
1
2
6
7
LO  
ON  
R
FACTORY-INSTALLED JUMPER  
DO NOT REMOVE  
NO 8  
NC 9  
3
4
Y
BK  
5
10  
G
LO  
HI  
*
24C  
HRV/ERV WIRING TERMINALS  
R
C
W
Y
G
R
Y
W
G
FURNACE OR  
HEAT PUMP  
THERMOSTAT  
12V/24 VAC Field wiring, 20 AWG min. required  
* Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period.  
Setting up the HHSC Control  
The duration of the ventilation rate is adjustable  
on the Healthy Home System™ Control (HHSC).  
Refer to the instructions that accompanied the  
HHSC for setup information.  
The Healthy Home System™ Control (HHSC)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of the HHSC with the DH1 and 20/40/60 Minute Timers (test a)  
DH1 DEHUMIDISTAT  
(OPTIONAL)**  
%
HHSC CONTROL  
80  
Gt  
C
Wt  
Gf  
R
V
HI  
1
2
6
7
LO  
ON  
R
FACTORY-INSTALLED JUMPER  
DO NOT REMOVE  
C
NO  
NC  
BK  
20  
8
3
4
Y
9
R
Y
G
5
10  
G
LO  
HI  
*
24C  
HRV/ERV WIRING TERMINALS  
Y
Y
R
C
W
Y
G
R
Y
W
G
R
G
R
G
FURNACE OR  
HEAT PUMP  
THERMOSTAT  
12V/24 VAC Field wiring, 20 AWG min. required  
Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period.  
*
** One DH-1 Dehumidistat and/or one or more VTC timer controls may be connected as shown. Connect all  
Red, Yellow, and Green control terminals to the corresponding HRV/ERV terminals.  
VTC VENT TIMER CONTROL  
(OPTIONAL)**  
VTC VENT TIMER CONTROL  
(OPTIONAL)**  
Setting up the HHSC Control  
The duration of the ventilation rate is adjustable  
on the Healthy Home System Control™ (HHSC).  
Refer to the instructions that accompanied the  
HHSC for setup information.  
The Healthy Home System™ Control (HHSC)  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of the DHVC Ventilation Control with 20/40/60 Minute Timers (test c)  
DHVC VENTILATION  
CONTROL  
NOTE:These connections are not necessary  
if the system is configured as fully  
dedicated (no central HVAC connections).  
FACTORY-INSTALLED JUMPER  
FOR STANDBY-OFF OPERATION.  
SEE “SETTING STANDBY” SECTION  
OF INSTALLATION INSTRUCTIONS  
HI  
1
2
6
7
LO  
ON  
R
C
NO  
NC  
BK  
8
3
4
Y
9
R
Y
5
10  
G
G
LO  
HI  
24C  
HRV/ERV WIRING TERMINALS  
Y
Y
R
C
W
Y
G
R
Y
W
G
R
G
R
G
FURNACE OR  
HEAT PUMP  
THERMOSTAT  
12V/24 VAC Field wiring, 20 AWG min. required  
Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period.  
*
** One DH-1 Dehumidistat and/or one or more VTC timer controls may be connected as shown. Connect all  
Red, Yellow, and Green control terminals to the corresponding HRV/ERV terminals.  
VTC VENT TIMER CONTROL  
(OPTIONAL)**  
VTC VENT TIMER CONTROL  
(OPTIONAL)**  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Interlocking the HRV/ERV to an Air Handler/Furnace Blower  
Connecting the HRV/ERV as illustrated will ensure the Air  
Handler/Furnace Blower Motor is operating whenever the  
HRV/ERV is ventilating.  
CAUTION  
Consideration should be given to competing  
airflows when connecting the HRV/ERV in  
conjunction with an Air Handler/Furnace Blower  
system.  
The HRV/ERV must be interlocked to the Furnace/Air  
Handler with a Simplified Installation (Return/Return  
Installation) and should be interlocked with a Partially  
Dedicated Installation.  
HRV Terminal Block  
Wire  
Connector  
Furnace  
Thermostat  
Furnace Terminal Strip  
Setting “Standby” when using a Main Control  
The HRV/ERV will be “fully-off” when the  
OFF position is selected on the Main Control.  
Timers and /or other controls will not function  
when the HRV/ERV is in the OFF position.  
The “fully-off” feature can be modified to  
“standby-off” by adding a jumper on the  
Terminal Block between 2 (ON) and 3 (RED).  
“Standby” can also be achieved by setting the  
main control to the ON position and selecting  
speed 0*. Timers and /or additional controls  
will initiate high speed ventilation when  
activated.  
CAUTION  
Building codes in some areas require “fully-  
off” functionality. Check with your local  
building authority before modifying the unit  
to “standby -off”.  
Unintentional operation of the HRV by the  
end user may occur if the unit is modified  
from “fully-off” to “standby-off”.  
The Terminal Block  
(located on the HRV/ERV)  
* Speed 0 is not available on all controls  
Operating the HRV/ERV without a Main Control and Adding Dry Contact Controls  
A jumper must be in place between 2 (ON) and  
The HRV/ERV must have a Jumper in  
3 (RED) on the Terminal Block to activate the  
HRV/ERV for timers and/or dry contact  
controls.  
place between 2 (ON) and 3 (RED) on  
the Terminal Block when installing the  
unit without a Main Control.  
Adding Dry Contact Controls  
Low Speed - A jumper between 2 (ON) and  
1 (LOW) initiates low speed ventilation.  
High Speed - A jumper between 2 (ON) and  
6 (HI) initiates high speed ventilation.  
Dehumidistat - A dry contact for a dehumidistat  
is connected between 2 (ON) and 10 (BLK).  
The Terminal Block  
(located on the HRV/ERV)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Balancing the Air Flows  
Balancing the air flows is critical to ensuring that the amount of air introduced from the outside of the building equals the  
amount of air exhausted to the outside of the building. If these two air flows are not properly balanced, the following issues  
may occur:  
• A positive or negative pressure may occur in the house  
ATTENTION  
Continuous, excessive, positive pressure may  
• HRV/ERV may not operate at its maximum efficiency  
• The unit may not defrost properly  
drive moist indoor air into the external walls of  
the building. Once inside the external walls, moist  
air may condense (in cold weather) and degrade  
structural components or cause locks to freeze.  
Air Flow Measuring Gauges  
The magnehelic gauge and the digital manometer are suitable  
instruments for the balancing of air flows.  
Continuous, excessive, negative pressure may  
A magnehelic gauge with a scale of 0 to .25" w.c. is suitable  
for accurately measuring air duct velocity. The value on the  
gauge will be velocity pressure. A digital manometer requires  
the ability to display differential pressures at 3 digits of  
resolution.  
have several undesirable effects. In some  
geographic locations, soil gases such as methane  
and radon gas may be drawn into the home  
through basement or ground contact areas, and  
may also cause the backdrafting of vented  
combustion equipment.  
Gauge Attachments  
When sampling an air flow, various attachments are available  
for use on a magnehelic gauge or digital manometer.  
The following illustration shows a magnehelic gauge with  
a scale of 0 to .25" w.c. with a pitot tube attachment. This  
combination will measure the system air velocity pressure  
accurately, regardless of the duct size or shape (either round  
or rectangular).  
Balancing Preparation  
Prior to performing the air balancing procedure, perform the  
following steps:  
• Seal the ductwork system  
• Confirm the installation and proper operation of all the  
components of the HRV/ERV  
• Fully open the balancing dampers  
Magnehelic Gauge with a scale of 0 to .25” w.c.  
• Turn off all household exhaust devices (range hood, clothes  
dryer, bathroom fans)  
Pitot tube and gauge  
• Set the HRV/ERV at high speed  
• Prior to balancing the unit, first adjust air flows in branch  
lines to specific areas of the house  
DUCT  
• If the outdoor temperature is below 0˚C (32˚F), ensure the  
unit is not running in defrost  
AIR  
• Place the magnehelic gauge on a level surface and adjust it  
FLOW  
to zero  
Pitot tube  
• If the system is a Simplified or Partially Dedicated  
installation, operate the furnace/Air Handler at high speed  
Magnehelic gauge  
High Pressure Side  
Low Pressure Side  
Magnehelic Gauge (scale of 0 to .25” w.c.)  
with a Pitot Tube Attachment  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Balancing the Air Flows with a Pitot Tube  
STEP 1. Drill a 3/16” hole in the duct (ideally 3 feet downstream of  
any elbows or bends and 1 foot upstream of any elbows  
or bends) in the Fresh Air and Stale air streams.  
STEP 2. Insert the Pitot tube with the tip facing towards the air  
stream in the Stale Air From Building air stream. Move  
the Pitot tube around in the duct (facing towards the  
airflow) and take an average reading. Record the reading.  
Stale Air From Building  
Balancing  
Damper  
Drill 3/16” holes in  
Stale & Fresh Air  
ducts.  
Pitot tube tip facing  
towards the air stream.  
Magnehelic Gauge must be level.  
Fresh Air to Building  
Balancing Damper  
STEP 3. Repeat Step 2 to measure the Fresh Air to Building duct.  
STEP 4.  
B) Upon completion of balancing, seal  
the holes (foil tape recommended).  
Pitot tube tip facing  
towards the air stream.  
Magnehelic Gauge  
must be level.  
A) Review the readings and damper down the duct with the  
highest duct velocity pressure. Repeat Step 2 and Step 3  
until both ducts show indentical readings. For this example,  
the Fresh Air to Building air stream has the highest duct  
velocity pressure.  
Determining the cfm  
After balancing the air flows, calculate the cfm flow rate.  
Example  
This example shows how to determine the air flow for a 6” diameter duct.  
As shown in the illustration, the duct velocity pressure reads 0.025” w.c.  
on the magnehelic gauge. Use the chart that came with the magnehelic  
gauge to determine a duct velocity of 640 feet per minute for a duct  
velocity pressure of 0.025” w.c.  
Cfm Calculation  
cfm = feet per minute x cross section area of duct  
= 640 x 0.196  
= 125  
Cross Section Area of some common round duct sizes:  
0.087 for 4” diameter duct  
0.136 for 5” diameter duct  
0.196 for 6” diameter duct  
0.267 for 7” diameter duct  
Magnehelic Gauge reading .025” w.c.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air Flow Balancing using the Door Ports  
FC155HRV & FC200HRV only  
Door balancing ports (not on all models) are designed to be used in  
conjunction with a Magnehelic Gauge or Digital Manometer to  
Step 4  
Close the HRV Door. Initiate power and operate the HRV on high  
speed. Operate the forced air system on high speed (if the HRV is  
connected to the forced air system) .  
measure the Stale and Fresh airflows for balancing.  
Step 5  
Fresh Air  
Insert the 2 rubber fittings from the gauge to the STALE AIR  
Balancing Ports (upper right and lower left). Seal the FRESH AIR  
Balancing Ports (upper left and lower right) with tape. Record your  
reading.  
Stale Air  
Balancing Ports  
(top-right,  
bottom-left)  
Balancing Ports  
(top-left,  
bottom-right)  
Step 6  
Insert the 2 rubber fittings from the gauge to the FRESH AIR  
Balancing Ports (upper left and lower right). Seal the STALE AIR  
Balancing Ports (upper right and lower left) with tape. Record your  
reading.  
Illustration of a door with door ports  
Step 7  
Step 1  
Refer to the "Airflow Reference Chart" for your model and  
determine the FRESH AIR and STALE AIR flow rates (the chart is  
located on the lower portion of this page).  
Step 8  
Damper down the higher airflow and repeat Steps 5 to 7 as required  
until both airflows are identical (balanced).  
Step 9  
Prepare the air flow measuring device (i.e. Magnehelic Gauge or  
Digital Manometer) by connecting the hoses to the low and high  
pressure side of the gauge.  
Step 2  
Insert the hoses into the rubber fittings from the optional Door Port  
Adapter Kit (part # 99-182). Use light pressure and rotate until  
fitting is snug. Do not extend the hose past the rubber fitting.  
Step 3  
Remove the tape and rubber fittings and reinstall the 4 Door Port  
Covers.  
Open the HRV Door. Remove the 4 Door Port Covers by carefully  
pushing them out from the back side of the door (use the blunt end  
of a large drill bit etc.).  
Magnehelic Gauge hoses connected to  
STALE AIR balancing ports  
Airflow Reference Charts  
FC155HRV  
FC200HRV  
Manometer  
Airflow Numbers  
Manometer  
Reading  
Airflow Numbers  
(CFM)  
Reading  
(CFM)  
Fresh Air Stale Air  
Pressure  
(in. w.g.)  
0.100  
0.110  
0.120  
0.130  
0.140  
0.150  
0.160  
0.170  
0.180  
0.190  
0.200  
0.210  
0.220  
0.230  
0.240  
0.250  
0.260  
0.270  
0.280  
0.290  
0.300  
0.310  
0.320  
0.330  
0.340  
0.350  
0.360  
Pressure Fresh Air Stale Air  
(in. w.g.)  
0.100  
0.105  
0.110  
0.115  
0.120  
0.125  
0.130  
0.135  
0.140  
0.145  
0.150  
0.160  
0.170  
0.180  
0.190  
0.200  
0.210  
0.220  
0.230  
0.240  
0.250  
0.260  
0.270  
0.280  
0.290  
0.300  
0.310  
93  
80  
98  
91  
96  
96  
83  
102  
107  
111  
115  
120  
124  
128  
133  
137  
141  
145  
149  
153  
157  
161  
165  
169  
173  
177  
181  
185  
189  
192  
196  
200  
203  
99  
86  
101  
107  
112  
117  
122  
127  
132  
137  
142  
147  
152  
156  
161  
166  
171  
175  
180  
184  
189  
193  
198  
202  
207  
211  
215  
102  
105  
108  
111  
114  
117  
120  
123  
130  
136  
142  
148  
154  
160  
166  
172  
178  
184  
191  
197  
203  
209  
215  
221  
89  
92  
96  
99  
102  
105  
108  
111  
117  
123  
129  
135  
141  
147  
154  
160  
166  
172  
178  
184  
190  
196  
202  
209  
Illustration of measuring STALE airflow using a Magnehelic Gauge.  
Magnehelic Gauge hoses connected to  
FRESH AIR balancing ports  
Illustration of measuring FRESH airflow using a Magnehelic Gauge.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Balancing Dampers  
The FC155HRV and FC200HRV models have factory installed  
Balancing Dampers located in the “Fresh Air to Building” and  
“Stale Air from Building” collars.  
NOTE  
Installations where the HRV is ducted directly to  
the return of the furnace/Air Handler may  
require additional dampening on the fresh air to  
building duct.  
This is due to the high return static pressures  
found in some furnace installations.  
All other units require the installation of balancing dampers (not  
included) in the “Fresh Air to Building” and “Stale Air from  
Building” ductwork. Refer to the installation diagrams in this  
manual for the Simplified, Partially Dedicated, and Fully  
Dedicated systems.  
Observe the location of the screws  
when connecting ductwork to the  
collar. Screws should be located no  
further than 1/2” from the outside  
edge of the collar and they should  
be no longer than 3/4”.  
Push and turn with slotted  
screwdriver. Damper  
automatically locks when  
pressure is released.  
1/2”  
Illustration of Connecting ductwork to the  
Balancing Damper Collars  
Illustration of Adjusting the Factory Installed  
Balancing Damper  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting your HRV/ERV System  
SYMPTOM  
CAUSE  
SOLUTION  
Poor Air Flows  
• 1/4” (6 mm) mesh on the outside hoods is plugged  
• filters plugged  
• clean exterior hoods or vents  
• remove and clean filter  
• core obstructed  
• remove and clean core  
• house grilles closed or blocked  
• dampers are closed if installed  
• poor power supply at site  
• ductwork is restricting HRV  
• improper speed control setting  
• HRV airflow improperly balanced  
• check and open grilles  
• open and adjust dampers  
• have electrician check supply voltage at house  
• check duct installation  
• increase the speed of the HRV  
• have contractor balance HRV  
Supply air feels cold  
• poor location of supply grilles, the airflow may irritate  
the occupant  
• locate the grilles high on the walls or under the baseboards,  
install ceiling mounted diffuser or grilles so as not to directly  
spill the supply air on the occupant (eg. over a sofa)  
• turn down the HRV supply speed. A small duct heater  
(1kw) could be used to temper the supply air  
• placement of furniture or closed doors is restricting the  
movement of air in the home  
• outdoor temperature extremely cold  
• if supply air is ducted into furnace return, the furnace fan  
may need to run continuously to distribute ventilation  
air comfortably  
Dehumidistat is not Operating  
Humidity Levels are too High  
• outdoor temperature is above 15°C (59°F)  
dehumidistat is functioning normally (see “How the  
Dehumidistat Works” in this manual)  
• check that the correct terminals have been used  
• check external wiring for a short  
• improper low voltage connection  
• external low voltage is shortened out by a staple or nail  
• check dehumidistat setting it may be on OFF  
• set the dehumidistat at the desired setting  
• dehumidistat is set too high  
• set dehumidistat lower  
Condensation is appearing on the windows • HRV is undersized to handle a hot tub, indoor pool, etc.  
• lifestyle of the occupants  
• cover pools, hot tubs when they are not in use  
• avoid hanging clothes to dry, storing wood and venting clothes  
dryer inside. Heating wood may have to be moved outside  
• vent crawl space and place a vapour barrier on the floor  
of the crawl space  
• moisture coming into the home from an unvented or  
unheated crawl space  
• moisture is remaining in the washroom and kitchen areas  
• ducts from the washroom should be sized to remove moist  
air as effectively as possible, use of a bathroom fan for  
short periods will remove additional moisture  
• on humid days, as the seasons change, some condensation  
may appear but the homes air quality will remain high with  
some HRV use  
• condensation seems to form in the spring and fall  
• HRV is set at too low a speed  
• increase speed of the HRV  
Humidity Levels are too Low  
HRV and/or Ducts Frosting up  
• dehumidistat control set too low  
• blower speed of HRV is too high  
• lifestyle of occupants  
• set dehumidistat higher  
• decrease HRV blower speed  
• humidity may have to be added through the use of humidifiers  
• have a contractor balance HRV airflows  
• HRV air flows may be improperly balanced  
• Note: minimal frost build-up is expected on cores before  
unit initiates defrost cycle functions  
• HRV air flows are improperly balanced  
• malfunction of the HRV defrost system  
• have HVAC contractor balance the HRV  
• ensure damper defrost is operating during self-test  
Condensation or Ice Build Up in Insulated • incomplete vapour barrier around insulated duct  
• tape and seal all joints  
Duct to the Outside  
• a hole or tear in outer duct covering  
• tape any holes or tears made in the outer duct covering  
• ensure that the vapour barrier is completely sealed  
Water in the bottom of the HRV  
• drain pans plugged  
• improper connection of HRV’s drain lines  
• HRV is not level  
• ensure O-Ring on drain nozzle sits properly  
• look for kinks in line  
• check water drain connections  
• drain lines are obstructed  
• make sure water drains properly from pan  
• HRV heat exchange core is not properly installed  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Residential Wiring Diagram  
Models FC95HRv, FC155HRV, FC200HRV, and FC150ERV  
Field Controls FC95HRV, FC155HRV, FC200HRV, FC150ERV  
LEGEND  
HI  
LOW  
ON  
HIGH VOLTAGE  
COM  
NO  
NOTE: Jumper between  
2 ON and 3 RED  
Thermistor  
(Not on all units)  
12/24V LOW VOLTAGE  
RED  
YEL  
GRN  
NC  
BLK  
P5  
P4  
BLUE  
P7  
COMMS  
BLACK  
K2  
K7  
K3  
K4  
P9  
GREEN  
P1  
P3  
WHITE  
T4  
AUTO-  
TRANSFORMER  
K6  
K5  
SEE  
DEFROST  
DETAIL  
GREEN  
Note: If any of the original  
wire supplied with the unit  
must be replaced, use only  
TEW certified wire.  
NC  
NO  
B
A
NC  
NO  
COM  
COIL  
COM  
COIL  
CAPACITOR  
24VAC  
24VAC  
IMPORTANT: Control low voltage is 12/24VAC.  
DO NOT CONNECT EXTERNAL POWER  
SOURCES TO THE UNIT.  
FAN  
MOTOR  
DIRECT  
MOUNTED  
CAPACITOR  
AUTO-TRANSFORMER DETAIL  
PINS 1, 2, AND 3 ARE OPTIONAL  
DEFROST DETAILS (Not Applicable to FC150ERV)  
PLUG IN CONNECTOR  
P3  
PCB PLUG - IN  
1
4
5
6
1
2
3
2
FC95HRV  
AUTO  
P1  
TRANSFORMER  
PLUG IN  
CONNECTOR  
PCB PLUG - IN  
1
2
P6  
P3  
BLACK  
ORANGE  
RED  
P1  
BLACK  
3
4
1
2
ORANGE  
RED  
PIN 1 - BLACK  
PIN 2 - ORANGE  
PIN 3 - RED  
3
4
P6  
PIN 1 - BLUE  
PIN 4 - RED  
PIN 1 - GREEN  
PIN 1 - RED  
PIN 2 -YELLOW PIN 5 - WHITE  
PIN 3 - BROWN PIN 6 - BLACK  
PIN 2 - GREEN  
BI-DIRECTIONAL  
DAMPER MOTOR  
PIN 2 - ORANGE  
PIN 3 - BLACK  
PIN 4 - SPARE  
PIN 4 - SPARE  
59-FCWIRING  
REV. A  
LEAVE FOR HOMEOWNER  
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION  
Installing Contractor _________________________________________Telephone / Contact _____________________  
Serial Number______________________________________________Installation Date ________________________  
Model _________________________________________________________________________________________  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Extron electronic Stereo Receiver MVP 104 User Manual
FEIN Power Tools Grinder WSG 12 70E User Manual
Fisher Paykel Oven OS60NDTX User Manual
Fujitsu Scanner fi 5900C User Manual
Fusion Marine Radio MS DKIPUSB User Manual
GE DVR Digital Video Multiplexer Recorder User Manual
GE Heat Pump AZ85H18EAC User Manual
GE Microwave Oven JES1231 User Manual
Generac Portable Generator 5939 User Manual
Gigabyte Network Card GA 8AENXP D User Manual