PHÖNIX Messtechnik GmbH
PHÖNiX
Magnetgesteuerte Grenzschalter
Typ 740.0060
Typ 740.0065
Typ 740.0065NA
BEDIENUNGSANLEITUNG
Magnetically operated Level Switch
Type 740.0060
Type 740.0065
Type 740.0065NA
INSTRUCTION MANUAL
Download from Www.Somanuals.com. All Manuals Search And Download.
2.1
2.2
Delivery
10
10
Reversing the direction of switching
3 COMMISSIONING
11
3.1
Mounting
11
3.2
Electrical connections
11
11
11
12
3.2.1
3.2.2
3.2.3
Power switch
Miniswitch
Namur switch
3.3
Setting the switch position
12
4 OPERATING INSTRUCTIONS
12
12
13
13
4.1
4.2
4.3
Two-step action with overlap with one PHÖNIX type 740.0060 level switch
Using the type 740.0065NA in a hazardous area
Heat protection in high temperature
5 MAINTENANCE
6 WARRANTY
13
13
14
14
14
7 DISPOSAL
8 TROUBLE SHOOTING
9 TECHNICAL DATA
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
2
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Allgemeine Beschreibung
Die PHÖNIX Grenzschalter Typ 740.0060/65 werden zusammen mit magnetisch gesteuerten Flüssig-
keitsstandanzeigern verwendet. Ihr Schaltverhalten ist bistabil. Bei Stromausfall und -wiederkehr ist der
Schaltzustand durch magnetische Speicherung stets aktuell. Die Wirkungsrichtung des Schaltvorgangs ist
durch Montage der Platine umkehrbar (Kap. 2.2).
Der Grenzschalter besitzt eine Hysterese, die vom verwendeten Anzeiger abhängig ist (s. Kap. 9). Hier-
durch ergibt sich die Möglichkeit einer Zweipunkt-Regelung.
Auch für den Einsatz in Anlagen mit starken Vibrationen ist dieser Schalter aufgrund des massearmen
Schaltelements gut geeignet.
1.1 Typ 740.0060
Mit dem PHÖNIX Grenzschalter Typ 740.0060 sind zwei Betriebsarten möglich:
a) Der Betrieb als
. Diese Betriebsart empfiehlt sich zum Schalten
elektronischer Leistungsschalter
großer Lasten an Wechselspannung, da die Lastschaltung kontaktlos erfolgt (Triac). Schutzmaßnah-
men für den Reedkontakt entfallen, da dieser lediglich den Steuerstrom des Triac schaltet.
b) Der Betrieb als Kleinsignalschalter. Diese Betriebsart ist angebracht zum Schalten von 0/4...20 mA
Stromschleifen, NAMUR Signalen, Logikpegeln, kleinen Wechsel- oder Gleichspannungen, etc.
ACHTUNG: Die gleichzeitige Verwendung beider Betriebsarten ist nicht möglich!
Last
Abb. 1: Prinzipschaltung 740.0060
1.2 Typ 740.0065/65N
Der Grenzschalter Typ 740.0065 (Abb. 2a) ist die zum ausschließlichen Betrieb als Kleinsignalschalter
reduzierte Variante des Typs 740.0060. Der Typ 740.0065NA ist zusätzlich - wie in Abb. 2b dargestellt -
mit Widerständen (RS=1k, RP=10k) bestückt, um in Namurschaltkreisen eingesetzt werden zu können.
Abb. 2a: Prinzipschaltung 740.0065
Abb. 2b: Prinzipschaltung 740.0065NA
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
3
Download from Www.Somanuals.com. All Manuals Search And Download.
2 Montagehinweise
2.1 Lieferzustand
Die PHÖNIX Grenzschalter Typ 740.0060/65 werden ausgeliefert wie in der nachstehenden Abb. 3a dar-
gestellt:
AUS
EIN
Abb. 3a: Lieferzustand
EIN
AUS
Abb. 3b: nach Umkehr der Wirkrich-
tung
2.2 Umkehr der Wirkungsrichtung
Eine Umkehr der Wirkungsrichtung entspricht der entgegengesetzten Schaltfunktion bei gleicher Magnet-
polarität. Dabei ist darauf zu achten, dass die Kabelverschraubung immer nach unten zeigt, wie in den
Abb. 3a und 3b dargestellt.
Vorgehensweise:
•
•
•
•
Abnehmen des Gehäusedeckels
Abnehmen der Sicherheitsabdeckung (nur beim Typ 740.0060)
Bei Bedarf: Abklemmen aller Anschlussdrähte
Entfernen der Schraube und des Sechskantbolzens sowie der Erdungsschraube beim Aluminiumge-
häuse
•
Nach Drehen der Platine um 180° Schraube, Sechskantbolzen sowie Erdungsschraube beim Alumini-
umgehäuse wieder einsetzen
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
4
Download from Www.Somanuals.com. All Manuals Search And Download.
•
•
•
•
Anklemmen der Anschlussdrähte
Anbringen der Sicherheitsabdeckung (nur bei Typ 740.0060, sehr wichtig !!)
Lösen des Halters
Montage des Halters an der gegenüberliegenden Seite. Um den Abstand aufrecht zu halten die zweite
Reihe Bohrungen benutzen.
•
Anbringen des Gehäusedeckels
3 Inbetriebnahme
Der Anschluss darf nur von geschultem Fachpersonal unter Einhaltung der einschlägigen Sicherheitsvor-
schriften vorgenommen werden
3.1 Montage
Die Montage des Schalters erfolgt mittels der
Gehäuse
zwei mitgelieferten Spannbänder wie in Abb. 4
dargestellt. Die PG - Verschraubung hat stets
nach unten zu zeigen, der Schaltpunkt liegt etwa
auf halber Gehäusehöhe. Die optionale Hitze-
schutzplatte befindet sich zwischen Gehäuse und
Haltewinkel.
Montage-
winkel
Befestigungs-
schrauben Halter
optionaler
Hitzeschutz
Schalt-
punkt
Bänder-
paar
M20x1,5
Abb. 4: Montage des Schalters mittels der
mitgelieferten Spannbänder
3.2 Elektrischer Anschluss
3.2.1 Leistungsschalter
Bei Betrieb mit Wechselstrom ist die Funktion der eines mechanischer Schalter vergleichbar, beispiels-
weise können als Last Relais, Schütze, Magnetventile etc. geschaltet werden. Aufgrund der Beschaltung
(s. Abb. 1) des Halbleiterschaltelements (Triac) fließt jedoch auch im geöffneten Zustand ein geringer
Strom über C1 (47nF).
Last
Abb. 5b: Minimal Last
Abb. 5a: Anschluss als Leistungsschalter
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
5
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.2 Kleinsignalschalter
In dieser Schaltung ist der Grenzschalter ein normaler mechanischer Schalter (Reedkontakt) für kleine
Gleich- oder Wechselspannungen. Für den Reedkontakt sind daher die üblichen Schutzmaßnahmen vor-
zusehen (s. Abb. 6b).
Bei Schaltspannungen >24V ist beim Typ 740.0060
R1 zu entfernen (s. Abb. 1).
Kleinlast
Grenzwerte (s. Kap. 9) und Schutzmaßnahmen
(s. Abb. 6b) beachten.
Abb. 6b: Schutzmaßnahmen für Gleich- und
Abb. 6a: Anschluss als Kleinsignalschalter
Wechselspannungen
3.2.3 Namur-Schalter
Abb. 7: Anschluß als Namur-Schalter
3.3 Grundeinstellung des Schaltzustandes
Vor der Inbetriebnahme muss jeder Schalter in die richtige Schaltlage gebracht werden, abhängig von der
Position des Schwimmers. Dies kann mit Hilfe eines Richtmagneten (BG10XXXXMAKU, im Lieferumfang
der PHÖNIX - Anzeiger enthalten) erfolgen, der am Gehäuse vorbei in Pfeilrichtung (vergl. Abb. 3a und
3b) bewegt wird. Der Richtmagnet kann auch geringfügig seitlich am Gehäuse vorbei bewegt werden.
Der Schaltzustand kann durch Anschluss eines Durchgangsprüfers (Summer, Ohmmeter) an den Klem-
men 1 und 3 überprüft werden. Dabei ist die Betriebsspannung abzuschalten!
4 Bedienung
4.1 Zweipunkt-Regelung mit 740.0060
Aufgrund der Hysterese (s. Kap. 9) des bistabilen Schaltelements kann der Schalter zur Zweipunktrege-
lung von Flüssigkeitsständen verwendet werden.
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Abb. 8: Verwirklichung einer Zweipunkt-Regelung mit einem PHÖNIX Grenzschalter Typ 740.0060
unter Ausnutzung der Schalthysterese
4.2 Einsatz des Typs 740.0065NA im explosionsgefährdeten Bereich
Durch Beschaltung des Reedkontakts mit Widerständen gemäß Abb. 2b ist der Typ 740.0065NA für den
Einsatz in Namurschaltkreisen geeignet. Da nur passive elektrische Bauteile eingebaut sind, deren Er-
wärmverhalten eindeutig festliegt, ist der Schalter nach VDE165 per Herstellerbescheinigung auch für den
Einsatz in explosionsgefährdeten Bereichen der Zonen 1 und 2 zugelassen. Die maximale Eigenerwär-
mung wird durch RS (RT= 180°C/W) und den Grenzwerten des verwendeten Trennschaltverstärkers fest-
gelegt. Bei Verwendung des Typs 740.1061 (Pmax=51mW) beträgt diese höchstens 10°C.
Typ 740.0065N
Typ 740.0065N
Ex-
sicherer
Bereich Bereich
Versorgungsspannung
Abb. 9: Verwendung des Typs 740.0065NA im explosionsgefährdeten Bereich
4.3 Hitzeschutzblech für erhöhte Temperaturen
Bei Mediumtemperaturen >150°C (>260 °C bei 740.0065NA) ist zur Verringerung der Wärmeeinstrahlung
vom Anzeiger eine Hitzeschutzplatte (Best.-Nr.: 5745000159) zwischen Anzeiger und Schalter einzubau-
en. Der Schalter darf dann auf keinen Fall mit dem Anzeiger einisoliert werden.
5 Wartung
Die Schalter 740.0060/65/65N sind wartungsfrei.
6 Garantie
Wir gewähren auf unsere Produkte eine Garantiezeit von 24 Monaten. Vorraussetzung ist die sachgemä-
ße Behandlung entsprechend der Bedienungsanleitung. Bei Verschleiß- und Ersatzteilen beschränkt sich
die Garantie auf Material - und Konstruktionsfehler.
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
7
Download from Www.Somanuals.com. All Manuals Search And Download.
7 Entsorgung
Der Kunde übernimmt die Pflicht, die gelieferte Ware nach Nutzungsbeendigung auf eigene Kosten nach
den gesetzlichen Vorschriften ordnungsgemäß zu entsorgen.
8 Störungsbeistand
Fehler
Ursache
Abhilfe
keine Funktion
kein bistabiles Verhalten
kein Öffnen (740.0060)
Verdrahtung, Sicherung, Versorgung
Halter falsch montiert
Leistungsschalter: Laststrom zu klein
Kleinsignalschalter: Spannung > 24V
Last zu groß
überprüfen
auf Abstand setzen
Reedschalter verwenden
Widerstand R1 entfernen
Schaltverstärker verwenden
Hitzeschutzblech (-platte)
verwenden
öffnet spontan (Kleinsignal)
Temperatur zu hoch
Für weitere Unterstützung steht die Firma PHÖNIX Messtechnik GmbH zur Verfügung.
9 Technische Daten
Allgemeine Daten
Auslegungsdaten
Hysterese ca. [mm]
max. Gehäuse-
temperatur.
Verwendung als
max. Mediumstemp.
Anzeiger-Typ
ohne Heizmantel mit Heizmantel
150 °C *)
bei Umg.Temp.85 °C
710.104/2XX
710.100
710.110...160
6
10
15
15
20
25
Leistungs-
schalter
(Triac)
70 °C
400 °C *)
bei Umg.Temp.55 °C
90 °C
120 °C
120 °C
Kabelverschraubung nach unten
IP65
150 °C *)
bei Umg.Temp.120 °C
Kleinsignal-
schalter
(Reed)
Alu/Makrolon
500 °C *)
bei Umg.Temp.70 °C
mit Bänderpaar, Best.Nr. s. Seite 2
Makr.: 82x80x55/0,15 kg
Alu:
75x80x57/0,3 kg
*) Isolierung zwischen Schalter und Anzeiger ab
150 °C im Rohr
(ab 260 °C bei 740.0065NA)
Elektrische Daten Leistungsschalter
Elektrische Daten Kleinsignalschalter1)
Betriebsspannung Nennwert:
Betriebsspannung Grenzwert:
Lastrom Nennwert:
AUS-Strom (230 V~)
max. Schaltleistung:
24 V~ bis 230V~
Max. Betriebsspannung1):
400 V= / 230 V~
0,5 A
250 V~
24 mA~ bis 2,5 A~
6 mA~
Max. Laststrom1):
Max. Schaltleistung1):
Beachten Sie die in 3.2.2 vor-
geschlagenen Schutzmass-
nahmen beim Schalten indukti-
ver Lasten!
5 W
550 VA
-
1) Es gilt zu beachten, dass keiner der drei Parameter Umax, Imax, Pmax überschritten werden darf!
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
8
Download from Www.Somanuals.com. All Manuals Search And Download.
1 General
The PHÖNIX type 740.0060/65 level switches can be used on all PHÖNIX magnetically-operated level
gauges. The switching behaviour is bistable. Should the electrical supply fail and return, the position of the
impulse magnet will be "memorised". The direction of the switching can be changed by reversing the
printed circuit board (see chapter 2.2).
The level switch hysteresis depends on the liquid level gauge (s. chapter 9) and can be used as a two-
step action.
Because of its low mass switching element this level switch is particularly suitable in installations with
strong vibrations,
1.1 Type 740.0060
Two types of operation are available with the PHÖNIX type 740.0060 level switch.
a) Used as electronic power switch, it is recommendable for the switching of heavy AC-loads, as the
switching occurs contactless (TRIAC). Protective measures for the REED-switch are not necessary, as
it is only used for the control circuit of the TRIAC,
b) Used as a Reed miniswitch, it is usable for the switching of 0/4-20 mA current loops, NAMUR-signals,
logic levels, small AC/DC-voltages etc.
ATTENTION: TRIAC and REED cannot be used at the same time!
Fig.1 Circuit design 740.0060
1.2 Type 740.0065/65NA
The level switch type 740.0065 (fig. 2a) is reduced to a Reed miniswitch for low level AC/DC loads. The
type 740.0065NA is alternative - as shown in fig. 2b - fitted with two resistors (RS=1k, RP=10k) for usage
in NAMUR circuits.
Fig. 2a: Circuit 740.0065
Fig. 2b: Circuit 740.0065NA
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
9
Download from Www.Somanuals.com. All Manuals Search And Download.
2 Mounting instructions
2.1 Delivery
The PHÖNIX type 740.0060/65 level switch can be delivered in the configurations shown below:
OFF
ON
Fig. 3a: as delivered
ON
OFF
Fig. 3b: with inverted switching di-
rection
2.2 Reversing the direction of switching
A reversal of the direction of switching involves the opposite switching function. Please note that the ca-
ble-gland is always directed downwards, as shown in fig. 3a and 3b.
Instruction:
•
•
•
•
•
Remove the switch cover
Remove the safety access panel (type 740.0060 only)
If necessary remove all connecting wires from the terminal
Take off screw, hexagon bolt and - for aluminium housing - the earth terminal
After turning the circuit board 180° remount with screws , hexagon bolt and.- for aluminium housing-
the earth terminal.
•
•
Reconnect the wires into the terminal
Put on the safety access panel (type 740.0060 only, very important !!)
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
10
Download from Www.Somanuals.com. All Manuals Search And Download.
•
•
Mount the bracket on the opposite side of the switch box. Use the second row of holes to keep the
distance.
Remount the switch cover
3 Commissioning
Authorised skilled personnel only recommended to connect the electrical circuits.
3.1 Mounting
The mounting of the switch is done by two col-
lars, which are supplied together with the switch,
as shown in Fig. 4. The cable gland is directed
housing
downwards in any case. The switching point is
situated nearby the middle of the box. The heat
protection is optional for high temperature appli-
cations and is situated between the switch box
and the mounting bracket.
mounting
bracket
mounting screws
holder
optional
heat protection
switching
point
collars
M20x1,5
Fig. 4: The mounting to the tube is done by
two collars.
3.2 Electrical connections
3.2.1 Power switch
In AC applications the function is comparable to a mechanically operating switch and can be used in con-
junction with load relays, gate switches, solenoid valves etc. Because of the wiring (fig. 1) of the solid
state switch (Triac) a small permanent current will pass through C1 (47nF).
Last
Fig. 5b: Minimum load
Fig. 5a: Connected as a power switch
3.2.2 Miniswitch
For this type of operation, the PHÖNIX type 740.0060 level switch is used as a normal mechanical
(REED) switch for low AC/DC-currents. The usual safety precautions for Reed switch contacts must be
observed (s. fig. 6b).
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
11
Download from Www.Somanuals.com. All Manuals Search And Download.
For switch type 740.0060 at voltages >24 V remove
the resistor marked with R1 (s. fig. 1).
low load
Please observe limit values (chapter 8) and safety
precautions (s. fig. 6b).
Fig. 6b: safety precautions for operation in low
DC/AC circuits.
Fig. 6a: Connected as a mini switch
3.2.3 Namur switch
740.0065NA
Fig. 7: Connecting of the Namur switch
3.3 Setting the switch position
Before starting-up, the bistable Reed contact must be properly set, in relation to the float in the level
gauge. This can be accomplished by using the control magnet (PHÖNIX part BG10XXXXMAKU, delivered
with liquid level gauges). This is moved up or down along the switch according to figs. 3a and 3b. The
switching function can be tested using an appropriate alarm or ohmmeter on the terminals 1 and 3. In this
case the system voltage, external wires must be disconnected !
4 Operating instructions
4.1 Two-step action with overlap with one PHÖNIX type 740.0060 level switch
Due to the Hysteresis of the bistable level switch type 740.0060 (see chapter 9) it can be used for a two-
step action of liquid levels.
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 8: A two-step action with a PHÖNIX level switch type 740.0060 utilising its hysteresis.
4.2 Using the type 740.0065NA in a hazardous area
The limit switch type 740.0065NA is designed for usage in NAMUR-circuits (s. fig. 2b). It consists only of
passive devices (switch and resistors), which allows - according to EN 50020 / VDE 0170 part 7 - the us-
age in hazardous areas zone 1 and 2, if they are part of a intrinsic save circuit and the maximum values of
voltage, current and power are not exceeded. The maximum of self heating is determined by RS (RT=
180°C/W) and the utilised power supply. If using the type 740.1061 (Pmax=51mW), the heating up is less
than 10°C.
Typ 740.0065N
Typ 740.0065N
hazardous safe
supply
area
area
Fig. 9: Usage of the type 740.0065NA in a hazardous area
4.3 Heat protection in high temperature
If medium temperature is more than 150°C (>260 °C for 740.0065NA) to reduce the heat radiation a heat
protection plate (Order-No.: 5745000159) has to be mounted between the tube and the switch. In this
case the switch must not be isolated together with the tube.
5 Maintenance
The switch is free of maintenance.
6 Warranty
We grant a guarantee period of 24 months for our products, provided that they have been handled and
operated under conditions described in the Operating Manual. In case of wear and spare parts we only
guarantee for failures in construction and material.
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
13
Download from Www.Somanuals.com. All Manuals Search And Download.
7 Disposal
The customer/enduser is obliged to take care for the disposal within the legal regulations.
8 Trouble shooting
Failure
no function
Problems
Correction
check it
rise distance
wrong wiring, fuses, current supply
wrong mounting of the housing
power switch: low current
Mini-switch: supply voltage > 24V
load is too high
no bistable behaviour
the switch is always closed
(740.0060)
the switch opens spontane-
ously (miniswitch)
use it as a mini-switch
remove resistor R1
use an isolating switch amplifier
use a heat protection plate
temperature is too high
9 Technical Data
General Data
Design Data
Hysteresis ca. [mm]
max. temperature
of pipe
max. temp.
of housing
Operating mode
Gauge-Type
on basic pipe
on heating jacket
150 °C *)
at amb.Temp.85 °C
Power switch
(Solid state
Triac-relay)
70 °C
710.104/2XX
710.100
710.110...160
6
10
15
15
20
25
400 °C *)
at amb.Temp.55 °C
90 °C
120 °C
120 °C
150 °C *)
at amb.Temp.120 °C
Cable gland downwards
Small signal
switch
(Reed)
IP65
Alu/Makrolon
with strap retainers
(Accesories s. page 2)
Makr.: 82x80x55/0,15 kg
500 °C *)
at amb.Temp.70 °C
*)Insulate between housing and pipe above
150 °C in pipe
(>260 °C for 740.0065NA)
Alu:
75x80x57/0,3 kg
Electrical data power switch
Electrical data miniswitch
Operating voltage nominal:
Operating voltage limit:
Load current nominal:
OFF-current (230 V~)
max. power limit:
24 V~ to 230V~
250 V~
24 mA~ to 2,5 A~
6 mA~
Operating voltage limit:
Operating current limit:
Rupturing capacity UxImax
400 V= / 230 V~
0,5 mA
5 W
:
550 VA
-
1) Take into account that none of the three parameters Umax, Imax, Pmax may be exceeded!
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
14
Download from Www.Somanuals.com. All Manuals Search And Download.
PHÖNiX
PHÖNIX Messtechnik GmbH
PHÖNIX Messtechnik GmbH
Salzschlirfer Straße 13
D-60386 Frankfurt
Tel. +49/69/41 67 42 - 20
Fax +49/69/41 67 42 - 29
e-mail: [email protected]
Weitere Produkte:
Further products:
Schauglasanzeiger
Sight Glass Level Gauges
Magnetanzeiger
Magnetic Level Gauges
Schwimmmerschalter
Float Switches
Schwimmer Füllstandmesser
Float Level Gauges
Verdränger Füllstandmesser
Displacer Level Gauges
Ultraschall Füllstandmesser
Ultrasonic Level Gauges
Optoelektronische Grenzwertgeber
Optoelectronic Level Switches
Ultraschall Grenzschalter
Ultrasonic Switches
DR7400060 REV. 26-10-06
PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29
15
Download from Www.Somanuals.com. All Manuals Search And Download.
|