		 MAINS POWERED 230V~   
					9V Alkaline Battery Back-Up   
					Model Ei144 Heat   
					Easi-Fit base   
					9V Alkaline Battery back up   
					Fixed temperature fast response thermistor type   
					sensor, range 54°C to 62°C   
					Test/Hush button   
					Advanced suppression and calibration technology   
					Interconnectable to other Ei mains powered alarms   
					Low power cell warning   
					Kitemarked to BS5446-2:2003   
					5 year guarantee   
					Product Description   
					Operation   
					The Ei144 is a Heat Alarm that runs on 230V AC mains   
					power, and has a 9V alkaline battery back up in the   
					event of mains failure. The 9V battery will last for up to 4   
					years in standby mode, and capable of powering the   
					heat detector for up to 2 years in the event of mains   
					failure.   
					The green indicator will illuminate to show mains   
					power is present   
					The red indicator will flash every 40 seconds to   
					show that the detector has performed an automatic   
					self test   
					The Ei144 is supplied with the Easi-Fit base that allows   
					very quick and simple installation of the heat alarm. The   
					Easi-Fit base automatically connects both mains power   
					and battery as the detector head slides on to the Easi-Fit   
					base.   
					The red indicator will flash rapidly to show an alarm   
					condition for the heat detector   
					The “Test/Hush” button will either silence false   
					alarms or perform a unit self test   
					The Ei144 has the ability to interconnect up to twelve   
					alarms to allow all alarms to sound if just one of the   
					interconnected alarms should be triggered.   
					In “Test” mode the alarm will perform a self test and   
					sound the horn   
					In “Hush” mode the alarm enters a ten minute period   
					of reduced sensitivity to overcome false alarm   
					conditions, and will then automatically reset itself   
					The Ei144 has built in circuitry to aid suppression of   
					voltage transients and RF interference to further reduce   
					the chances of false alarms under such conditions.   
					When interconnected to other Ei mains powered   
					alarms, an alarm on one detector will trigger all other   
					interconnected alarms within one second (only the   
					triggered alarm will flash a red indicator)   
					The Ei144 heat alarm gives a fire warning when the   
					temperature at the unit reaches 580C. Heat alarms are   
					ideal for use in kitchens and garages, where the use of   
					optical or ionisation alarms would lead to unwanted   
					nuisance alarms.   
					The heat detector will emit a beep every 40 seconds   
					to indicate that the battery back up is depleted and   
					needs replacing   
					On escape routes this alarm must be interconnected   
					Shannon Free Zone, Shannon, Co. Clare, Ireland.   
					Ph.+353 61 471277 Fx.+353 61 471053   
					Email. [email protected]   
					
					E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice.   
					Ei144 DataSht RevA   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |