Eaton Electrical Power Supply BladeUPS Bar User Manual

®
®
Powerware BladeUPS Bar  
Installation Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1
2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
2
5
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Checking the Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5
5
5
6
7
3
4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Service and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1  
Introduction  
®
®
Up to six of Eaton’s Powerware BladeUPS uninterruptible power  
systems (UPSs) can be installed in an industry standard rack outfitted  
with a BladeUPS Bar 60 for interconnecting the cabinets’ wiring.  
Figure 1 shows an installed BladeUPS Bar 60. The wireway fits into the  
bottom 6U of standard rack space.  
BladeUPS Bar 60  
Wireway  
Front Covers  
Figure 1. BladeUPS Bar 60 Installed in Rack  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
Safety Warnings  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions that you should follow during installation and  
maintenance of the BladeUPS Bar 60. Please read all instructions before operating the  
equipment and save this manual for future reference.  
VIGTIGE SIKKERHEDSANVISNINGER  
GEM DISSE ANVISNINGER  
Denne manual indeholder vigtige instruktioner, som skal følges under installation og  
betjening af BladeUPS Bar 60-enheden. Læs venligst alle instruktioner inden betjening af  
udstyret og gem denne manual mhp. fremtidige opslag.  
BELANGRIJKE VEILIGHEIDSINSTRUCTIES  
BEWAAR DEZE INSTRUCTIES  
Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie en  
het gebruik van BladeUPS Bar 60. Lees alle instructies voordat u de apparatuur in bedrijf  
neemt en bewaar deze handleiding als naslagwerk.  
TÄRKEITÄ TURVAOHJEITA - SUOMI  
SÄILYTÄ NÄMÄ OHJEET  
Tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava BladeUPS Bar 60-yksikön  
asennuksen ja käytön yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohje  
myöhempää tarvetta varten.  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
Ce manuel contient des instructions importantes que vous êtes invité à suivre lors de toute  
procédure d’installation et de fonctionnement de la BladeUPS Bar 60. Veuillez consulter  
entièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuel  
afin de pouvoir vous y reporter ultérieurement.  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
WICHTIGE SICHERHEITSANWEISUNGEN  
AUFBEWAREN  
Dieses Handbuch enthält wichtige Hinweise, welche Sie bei der Installation und Wartung  
des BladeUPS Bar 60 beachten sollten. Bitte lesen Sie alle Anweisungen des Handbuches  
bevor sie mit dem Gerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.  
IMPORTANTI ISTRUZIONI DI SICUREZZA  
CONSERVARE QUESTE ISTRUZIONI  
Il presente manuale contiene importanti istruzioni da seguire durante l’installazione e il  
funzionamento di BladeUPS Bar 60. Leggere integralmente le istruzioni prima di utilizzare  
l’apparecchiatura e conservare il presente manuale per futuro riferimento.  
VIKTIGE SIKKERHETSINSTRUKSJONER  
GJEM DISSE INSTRUKSJONENE  
Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og  
bruk av BladeUPS Bar 60. Les alle instruksjoner før utstyret tas i bruk, og gjem håndboken til  
fremtidig referanse.  
INSTRUÇÕES DE SEGURANÇA IMPORTANTES  
GUARDE ESTAS INSTRUÇÕES  
Este manual contém instruções importantes que devem ser seguidas durante a instalação e  
operação da BladeUPS Bar 60. Leia todas as instruções antes de operar o equipamento e  
guarde este manual para consultá-lo futuramente.  
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
СОХРАНИТЕ ЭТИ УКАЗАНИЯ  
В данном руководстве содержатся важные инструкции по установке и  
обслуживанию внешнего батарейного модуля или устройства распределения  
электропитания. Перед работой с оборудованием прочтите все инструкции.  
Сохраните данное руководство для дальнейшего использования.  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
Este manual contiene instrucciones importantes que debe seguir durante la instalación y el  
funcionamiento del BladeUPS Bar 60. Por favor, lea todas las instrucciones antes de poner  
en funcionamiento el equipo y guarde este manual para referencia en el futuro.  
VIKTIGA SÄKERHETSFÖRESKRIFTER  
SPARA DESSA FÖRESKRIFTER  
Den här anvisningen innehåller viktiga instruktioner som du ska följa under installation och  
användning av BladeUPS Bar 60. Läs alla instruktioner innan du använder utrustningen och  
spara den här anvisningen för framtida referens.  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2  
Installation  
This section explains:  
S Equipment inspection  
S BladeUPS Bar 60 setup and installation  
Inspecting the Equipment  
If any equipment has been damaged during shipment, keep the shipping  
cartons and packing materials for the carrier or place of purchase and file  
a claim for shipping damage. If you discover damage after acceptance,  
file a claim for concealed damage.  
To file a claim for shipping damage or concealed damage: 1) File with  
the carrier within 15 days of receipt of the equipment; 2) Send a copy of  
the damage claim within 15 days to your service representative.  
NOTE Check the battery recharge date on the shipping carton label. If the date has expired  
and the batteries were never recharged, do not use the UPS. Contact your service  
representative.  
Setup  
The BladeUPS Bar 60 comes with all hardware required for installation in  
a standard EIA or JIS rack with square and round mounting holes.  
Tools Required  
To assemble the components, the following tools may be needed:  
S Torque wrench with the following attachments:  
-
-
Hex socket size 10 mm for M6 hex bolt  
Hex socket size 8 mm for M5 hex bolt  
®
S Torque driver with a Pozidriv #2 for Pozidriv M4 screw  
S Large screwdriver or crowbar for lifting the bar in place  
S Pliers for installing cage nuts  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Checking the Package Contents  
Verify that the following items are included:  
S BladeUPS Bar 60  
A six-socket bar with (1) attached terminal block assembly,  
(1) attached base bracket, and (3) attached mounting brackets  
S Wireway main housing with (2) attached side brackets, (1) attached  
terminal block housing, and (1) attached wireway access cover  
S Front cover mounting panel  
S (2) front covers  
S Ferrite assembly with 38 cm (15) tie wrap  
S This user’s guide  
S Packaged hardware items:  
-
-
-
-
-
-
-
(14) M6×12 hex bolts, plus (1) extra  
(4) M5×16 hex bolts  
(6) M6×12 pan-head screws, plus (1) extra  
(16) M4×8 pan-head screws  
(6) M6 split lock washers, plus (1) extra  
(4) M5 cage nuts  
(3) M6 hex nuts, plus (1) extra  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Installation  
To install the BladeUPS Bar 60:  
1. Remove the access cover and terminal block housing from the  
wireway housing (see Figure 2). Retain the wireway terminal block  
housing, wireway access cover, and screws. Leave the two side  
brackets installed on the wireway housing (see side bracket  
locations in Figure 3).  
2. Verify that the side brackets are in the most closed position and  
that the adjustment screws are tightened to prevent the side  
brackets from moving.  
CAUTION  
If the side brackets are loose, they can move during wireway placement and cause injury.  
Wireway  
Housing  
Wireway  
Terminal Block  
Housing  
M6×12 Hex Bolts  
(2 places)  
Wireway Access Cover  
M4×8 Pan-Head Screws  
(14 places)  
Figure 2. Wireway Disassembly  
3. Place the wireway housing into the bottom of the rack so that the  
adjustable side brackets are at the front of the rack (see Figure 3).  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
4. Install an M6 hex nut onto each of the three wireway studs to  
secure the wireway to the rear of the rack. Install the first stud in  
the fourth hole location from the bottom. Do not tighten the nuts.  
Figure 4 shows the nuts installed.  
5. Loosen the three adjustment screws on each side of the wireway  
housing and adjust the side brackets for the depth of the rack. Do  
not retighten the screws.  
6. Install six M6×12 pan-head screws and M6 split lock washers to  
secure the two wireway side brackets to the front of the rack.  
Install the first screws in the fifth hole location from the bottom.  
Torque the screws to 5.1 0.8 Nm (45 7 lb in).  
7. Tighten the three M6 hex nuts installed in Step 4. Torque the nuts  
to 5.1 0.8 Nm (45 7 lb in).  
8. Retighten the six side bracket adjustment screws loosened in  
Step 5. Torque to 3.4 Nm (30 lb in).  
M6 Hex Nuts on  
Wireway Studs  
(3 places)  
Rear of Rack  
Wireway  
Housing  
Side Bracket  
Adjustment  
Screws  
M6×12 Pan-Head  
Screws and M6 Split  
Lock Washers  
(3 places  
each side)  
(3 places each side)  
Adjustable  
Side Brackets  
(1 each side)  
Front of Rack  
Figure 3. Wireway Installation  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
9. Place the ferrite assembly on the floor of the wireway and secure  
with the supplied tie wrap. Loop the tie wrap through both  
attachment sites on the wireway floor and through the ferrite  
assembly. See Figure 4.  
10. Note the orientation of the base bracket installed on the bar for later  
re-installation (see Figure 5). Remove and retain the base bracket  
and hardware.  
11. Place the bar in the rack as shown in Figure 4.  
NOTE The bar can rest on the floor of the rack until secured in place. After complete  
installation, the bar will be secured to the rack and wireway as shown in Figure 4.  
Bar  
M6 Hex Nuts  
on Wireway  
Studs  
(3 places)  
Ferrite Assembly  
(secured to  
wireway floor with  
tie wrap)  
Rear of Rack  
Wireway Floor Tab  
(above bar base sheetmetal)  
Figure 4. Ferrite and Bar Placement  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
NOTE Verify that the bar is secure as shown in Figure 4. The sheetmetal at the base of the  
bar should be below the tab on the wireway floor.  
12. Secure the bar to the wireway with three M6×12 hex bolts. Install  
the bolts from the front of the rack. See Figure 5. Torque the bolts  
to 5.1 0.8 Nm (45 7 lb in).  
13. Reinstall the base bracket removed in Step 10. Install the bolts from  
the front of the rack. See Figure 5. Torque the bolts to 5.1 0.8 Nm  
(45 7 lb in).  
NOTE Do not change the original orientation of the base bracket. Verify that the threaded  
holes mount to the rack, not to the bar.  
Base Bracket  
Rear of Rack  
M6×12 Hex Bolts  
(3 places)  
Front of Rack  
Figure 5. Bar Base Installation  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
14. Secure the base bracket to the rack with three M6×12 hex bolts.  
Install the bolts from the rear of the rack.  
Use a large screwdriver or crowbar to lift the bar in place to align  
the holes in the base bracket with the holes in the rack.  
Install the lowest bolt in position 2, then use positions 9 and 15.  
Verify that the base bracket stud aligns completely with the rack  
hole below the top bolt (position 14). See Figure 6. Torque the bolts  
to 5.1 0.8 Nm (45 7 lb in).  
15. Install two M6×12 hex bolts in each of the bar’s three mounting  
brackets, securing the length of the bar to the rack. See Figure 6.  
Torque the bolts to 5.1 0.8 Nm (45 7 lb in).  
NOTE Loosening the mounting brackets slightly may allow easier alignment to the vertical  
rail of the rack. Retighten the mounting brackets when alignment is complete.  
M6×12 Hex Bolts  
(2 places) per  
Mounting Bracket  
(3 places)  
NOTE One mounting  
bracket shown.  
Base Bracket Stud  
(below top bolt)  
M6×12 Hex Bolts  
through Rack to  
Base Bracket  
(3 places)  
Rear of Rack  
Figure 6. Bar Bracket Installation  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
16. Install two M4×8 pan-head screws into the tab on the wireway  
floor, securing the base of the bar to the wireway. See Figure 7.  
Torque the screws to 1.7 0.2 Nm (15 2 lb in).  
M4×8 Pan-Head Screws  
(2 places)  
Rear of Rack  
Wireway Floor Tab  
(above bar base sheetmetal)  
Figure 7. Wireway Tab Attachment  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
17. Using two M6×12 hex bolts, secure the left side of the wireway  
terminal block housing to the rack. See Figure 8. Torque the bolts to  
5.1 0.8 Nm (45 7 lb in).  
18. Using nine M4×8 pan-head screws, secure the wireway terminal  
block housing to the wireway and to the bar. See Figure 8. Torque  
the screws to 1.7 0.2 Nm (15 2 lb in).  
Wireway  
Terminal Block  
Housing  
M6×12 Hex Bolts  
M4×8 Pan-Head Screws  
(2 places)  
(9 places)  
Figure 8. Wireway Terminal Block Housing Installation  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
19. Using five M4×8 pan-head screws, install the wireway access  
cover. See Figure 9. Torque the screws to 1.7 0.2 Nm  
(15 2 lb in).  
M4×8 Pan-Head Screws  
(5 places)  
Wireway Access Cover  
Figure 9. Wireway Access Cover Installation  
20. Verify the six information labels are attached to the wireway as  
shown in Figure 10.  
Figure 10. Wireway Labels  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
21. Using four M5×16 hex bolts and four M5 cage nuts, secure the  
front cover mounting panel to the front of the rack. Verify that the  
bent edge of the panel is at the top. See Figure 11.  
Install the lower bolts and cage nuts into the second holes from the  
bottom of the rack frame. Torque the bolts to 5.1 0.8 Nm  
(45 7 lb in).  
Bent Edge of Panel  
M5×16 Hex Bolts  
and M5 Cage Nuts  
(4 places)  
Front Cover  
Mounting Panel  
Front of Rack  
Figure 11. Front Cover Mounting Panel Installation  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
22. Snap the two front covers into place, as shown in Figure 12.  
Front Covers  
(2 pieces)  
Figure 12. Front Cover Installation  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3  
Specifications  
This section provides the following specifications:  
Table 1. BladeUPS Bar 60  
Dimensions (WxDxH)  
14.0×11.3×183.8 cm (5.5×4.4×72.4)  
90.1 cm (35.5), excluding front covers  
Depth of Wireway  
Weight  
Bar: 19 kg (42 lb)  
Wireway enclosure: 20 kg (45 lb)  
Total Weight: 39 kg (87 lb)  
UPS Connections  
Rack Placement  
Up to 6, using Anderson input/output connectors  
Bottom wireway fits into the bottom 6U of standard rack space  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4  
Service and Support  
If you have any questions or problems with the BladeUPS Bar, call your  
Local Distributor or the Help Desk at one of the following telephone  
numbers and ask for a UPS technical representative.  
United States:  
Canada:  
1-800-843-9433 or 1-919-870-3028  
1-800-461-9166 ext 260  
All other countries:  
Call your local service representative  
Please have the following information ready when you call the Help  
Desk:  
S Model number  
S Serial number  
S Version number (if available)  
S Date of failure or problem  
S Symptoms of failure or problem  
S Customer return address and contact information  
If repair is required, you will be given a Returned Material Authorization  
(RMA) Number. This number must appear on the outside of the package  
and on the Bill Of Lading (if applicable). Use the original packaging or  
request packaging from the Help Desk or distributor. Units damaged in  
shipment as a result of improper packaging are not covered under  
warranty. A replacement or repair unit will be shipped, freight prepaid for  
all warrantied units.  
NOTE For critical applications, immediate replacement may be available. Call the Help  
Desk for the dealer or distributor nearest you.  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE AND SUPPORT  
EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*164201723P01*  
164201723 P01  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Cypress Computer Hardware CY7C09079V User Manual
Dell All in One Printer 968 User Manual
Delta Electronics Power Supply HCB1380 User Manual
Dynacord Music Mixer PSX 1250 User Manual
Dynacord Speaker System D 8 User Manual
FEIN Power Tools Grinder WSs 12 125 User Manual
Fisher Price Baby Accessories T4144 User Manual
Fisher Price Car Seat T3643 User Manual
Fisher Price Motorized Toy Car 74547 User Manual
Fostex Car Speaker FW187 User Manual