®
Powerware 9170+ Rail Kit
9- and 12-Slot Cabinets
Installation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Rack-Mount Installation
To install a 9- or 12-slot uninterruptible power system (UPS) cabinet into
a rack, you must order a cabinet specifically designed for rack-mounting.
Nine- and 12-slot battery cabinets ASY-0749 and ASY-0750 are also
available for rack-mounting. These models can be installed in an
EIA-standard 48.3 cm (19”) equipment rack and include a rack-mounting
kit with the brackets and required hardware.
To install the UPS or battery cabinet in the equipment rack:
NOTE The 9- and 12-slot cabinets are heavy [9-slot: 72 kg (158 lb); 12-slot: 89 kg (196 lb)].
This procedure requires two people to lift and position the cabinet into the equipment rack.
Install the cabinet in the rack before installing power and battery modules and before making
connections to the intended power source.
1. Remove the four screws (two on either side) securing the top cover
of the cabinet. Carefully lift the cover straight up and off to avoid
stressing the front panel display. Set the cover aside.
2. Remove the cabinet side covers by lifting the top edge. No other
hardware must be detached. Store or discard the side covers.
3. Carefully replace the cabinet top cover and secure with the four
screws removed in Step 1. Position the cover lip to fit behind the
front panel display.
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
1
Download from Www.Somanuals.com. All Manuals Search And Download.
RACK-MOUNT INSTALLATION
4. Install six metal clip nuts (nine clip nuts for 12-slot cabinets) onto
each side flange along the front of the cabinet (see Figure 1).
NOTE DO NOT install metal clip nuts in the bottom cabinet section.
Metal Clip Nuts
Tab Slots
Tab Slots
Metal Clip Nuts
Tab Slots
Metal Clip Nuts
Figure 1. Metal Clip Nut and Tab Slot Locations
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
2
Download from Www.Somanuals.com. All Manuals Search And Download.
RACK-MOUNT INSTALLATION
5. Install two rack-mount ears (three for 12-slot cabinets) on each side
of the cabinet (see Figure 2).
Insert the two offset tabs on the rear edge of the ear into the
matching tab slots on the cabinet side frame (see Figure 1). Pivot
the ear forward until it is flush against the cabinet side frame.
Secure each ear with three 1/4-20×1/2” Phillips-head bolts; screw
the bolts into the metal clip nuts installed in Step 4.
NOTE DO NOT install rack-mount ears in the bottom cabinet section.
Rack-Mount Ear
Rack-Mount Ear
Rack-Mount Ear
Figure 2. Rack-Mount Ears Installed
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
3
Download from Www.Somanuals.com. All Manuals Search And Download.
RACK-MOUNT INSTALLATION
6. Select the proper holes in the rail that position the cabinet at the
desired location in the rack.
7. Install one equipment rail on each side of the rack using four
10-32×1/2” flat-head screws per rail.
8. With one person lifting each side of the cabinet, position the cabinet
onto the two equipment rails (see Figure 3).
Carefully slide the cabinet into the equipment rack until the
rack-mount ears of the cabinet are flush with the front vertical rails
of the rack. Verify that the holes in the ears align with the holes in
the rack.
Equipment Rail
Figure 3. Rails Holding UPS Cabinet
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
4
Download from Www.Somanuals.com. All Manuals Search And Download.
RACK-MOUNT INSTALLATION
®
9. Secure the cabinet in the rack using 10-32×1/2” Torx screws or
other appropriate customer-specified screws.
10. Follow the instructions in the UPS user’s guide to install the power
and battery modules.
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
United States:
Canada:
All other countries:
1-800-356-5737 or 1-919-870-3149
1-800-461-9166 ext 260
Call your local service representative
Please have the following information ready when you call the Help
Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization
(RMA) Number. This number must appear on the outside of the package
and on the Bill Of Lading (if applicable). Use the original packaging or
request packaging from the Help Desk or distributor. Units damaged in
shipment as a result of improper packaging are not covered under
warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the Help
Desk for the dealer or distributor nearest you.
+
EATON Powerware® 9170 Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
5
Download from Www.Somanuals.com. All Manuals Search And Download.
*164201420B*
164201420 B
Download from Www.Somanuals.com. All Manuals Search And Download.
|