Eaton Electrical Network Card 66103 User Manual

Network  
Management  
Card &  
Modbus/  
Jbus  
(66103)  
Installation manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Network Management Card & Modbus/Jbus (66103) is recommended for central UPSs  
protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS  
has its own IP address and uses the local computer capabilities to:  
Supply web pages (http or https (SSL)) with information on status conditions and measurements/  
settings/alarms,  
Integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates  
Unicenter,  
Communicate with shutdown modules installed on the protected servers (Network Shutdown  
Module),  
Send e-mail and SMS messages,  
Control the ON/OFF function of the UPS and the outlets,  
Monitor the Environment Sensor (optional, cat. no. 66846).  
UNPACKING AND CHECKS  
One Network Management Card & Modbus/Jbus (66103)  
One serial cable for configuration (34003918),  
One installation manual (34003906).  
CHECK ON UPS VERSION  
The Network Management Card & Modbus/Jbus (66103) is compatible with the Pulsar range UPSs  
available since 2006.Note.  
Important. Before installing the card, check that the UPS technical level (NT) is at least  
equal to that indicated in the table below.  
UPS  
Type  
Technical level (NT)  
02  
Pulsar  
700/1000/1500  
Pulsar M  
2200/3000  
03  
04  
01  
Pulsar MX  
4000/5000/10000  
15/20 kVA  
Pulsar MX Frame  
If the technical level of the UPS is lower than that indicated in the table, contact EATON.  
34003906EN/AE - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
.
OVERVIEW  
Jbus/modbus port  
MAC address  
ETHERNET 10/100BT port  
Service port (Settings/Sensor)  
Orange LED: RS232 activity  
Settings/Sensor  
1
00M  
10  
Green LED: communication  
with the UPS  
M
U
P
S
dat  
a
R
S
232  
6
6
1
0
3
Catalogue number  
Orange LED: 10/100M  
Green LED: connection +  
activity  
INDICATIONS  
ETHERNET port  
LED  
Colour  
Green  
Status  
Description  
ACT  
OFF  
ON  
Card not connected to network  
Card connected to network, but no activity  
Port is sending/receiving  
Flashing  
100M  
Orange  
OFF  
ON  
Port operating at 10 Mbits/s  
Port operating at 100 Mbits/s  
Service port (Settings/Sensor)  
LED  
Colour  
Green  
Status  
Description  
UPS Data  
OFF  
Card starting  
ON  
Flashing  
Communicating with UPS  
Normal operation  
Communication with UPS is operational  
RS232  
Orange  
OFF  
ON  
Configuration menu activated  
Normal operation  
Configuration menu not activated  
Communication with Environment Sensor (option)  
Flashing  
4 - 34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Network Management Card & Modbus/Jbus (66103) can be hot-plugged on all UPSs from  
EATON equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart  
the UPS.  
Remove the plastic cover of the Minislot.  
Note the MAC address of the card before inserting it.  
S
et  
ti  
n
g
s/  
S
en  
so  
r
ASI  
10  
0M  
10  
M
UP  
S
d
ata  
RS  
6
23  
2
6
1
0
3
ETHERNET  
Insert and secure the card with the screws.  
Connect the ETHERNET cable.  
Check the ETHERNET port indications.  
Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has  
terminated correctly.  
Note. Connection detection continues until the card has been connected to the network. Once  
connection is made, card start-up continues.  
IP SETTINGS  
Once the card has started, proceed as indicated below.  
Connect the serial cable to card’s service port and PC’s COM port  
TM  
Use a terminal emulator such as HyperTerminal  
with these settings  
Bits per second  
9600  
Data bits  
8
Stop bits  
1
Parity  
none  
Flow control  
none  
"Echo typed characters locally" option: disabled  
Type EATON (or eaton).  
The main configuration menu is displayed:  
EATON  
NETWORK MANAGEMENT CARD  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
5 : Jbus configuration  
6 : Sensor configuration  
0 : Exit  
34003906EN/AE - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Your network is equipped with a BOOTP/DHCP server (default)  
The card is configured by default with this service enabled. No manual configuration is required.The IP  
parameters are automatically collected by the card.  
From the main configuration menu: (see above)  
Press the 2 key (Network configuration).  
Press the 1 key(Read Network settings).  
The settings supplied by the server are displayed:  
Network configuration :  
MAC address : 00:06:23:00:1C:07  
Mode : DHCP  
IP address : 172.17.23.18  
Subnet mask : 255.255.248.0  
Gateway : 172.17.17  
Note the IP address.  
Press the 0 key (Exit).  
Press the 0 key (Exit).  
You can also use NMC Tool software utility to view the card IP adress  
connected PC.  
Your network is not equipped with a BOOTP/DHCP server  
Manual configuration is required.  
To set the network configuration, use terminal emulation (see above)  
From the main configuration menu:  
Press the 2 key (Network configuration).  
Press the 2 key (Modify Network settings).  
Follow the instructions and enter the IP parameters:  
1 : Read Network settings  
2 : Modify Network settings  
3 : Set ethernet speed  
0 : Exit  
For each of the following questions, you can press "Return" to  
select  
the value shown in braces, or you can enter a new value  
Should this target obtain IP settings from the network?[N] N  
Static IP address [172.17.16.16]?172.16.1.82  
Subnet mask IP address [255.255.0.0]? 255.255.255.0  
Gateway address IP address [0.0.0.0]? 172.17.17.1  
Done  
Wait until "Done" is displayed, indicating that the IP parameters have been saved.  
Press the 0 key (Exit).  
Press the 1 key (Reset).  
Press the 2 key (Restart).  
The card restarts with the new IP settings (after approx. one minute).  
6 - 34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESS TO SUPERVISION  
To check whether the Network Management Card & Modbus/Jbus (66103) is operational after  
installation and configuration, proceed as follows.  
Run a browser  
Enter in the address bar:  
http://IP address/ (e.g. http://172.16.1.82/)  
The home page is displayed  
Set the time by clicking the Time command.  
Continue configuration via the sections in the Settings menu.  
USER MANUAL  
This manual provides all the information required to install and configure the Network Management  
Card & Modbus/Jbus (66103).  
For more information on the supervision, control and configuration functions offered by the Network  
Management Card & Modbus/Jbus (66103), see the user manual on the Solution-Pac 2 CD-ROM or  
in the Products/Power Management section of the www.eaton.com/powerquality site.  
34003906EN/AE - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SENSOR CONNECTION (option)  
The Environment sensor is a Network Management Card & Modbus/Jbus option. It is available  
from EATON (cat. no 66846).  
The sensor remotely monitors the UPS environment by regularly measuring the temperature and  
humidity, and checking the states of two external contacts. It can also send alarms (e-mail, SNMP trap)  
tripped by pre-set thresholds.  
Connection is made via the Service port (Settings/Sensor) on the Network Management Card &  
Modbus/Jbus. The sensor is detected automatically. Configuration and supervision use a menu that  
may be accessed directly from the home page. For more information, see the user manual of the  
Network Management Card & Modbus/Jbus.  
10  
0M  
10  
M
UP  
S
d
lin  
k
a
ta  
R
S
23  
2
6
6
1
0
3
8 - 34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J BUS/ MODBUS  
RS232 link configuration and connection  
SA1  
SA2  
Pin Function  
SA2  
1
8
1
2
3
4
5
Received data (input)  
Not connected  
5
4
3
2
1
Transmitted data (output)  
Not connected  
Signal ground  
SG  
Txd  
Rxd  
RS485 link configuration and connection  
For proper operation, the polarity of EIA RS485 2-wire and 4-wire lines must be set at only one point  
and the lines terminated at the end.  
Polarity  
Normally, the master of the network sets the polarity of the line. The receiver inputs have a true failsafe  
feature wich eliminates the need for external bias resistors and ensures a logic high output level when  
the inputs are open or shorted. This guarantees that the receiver outputs are in a known state before  
communication begins and when communication ceases.  
Termination  
Termination is used to match impedance of a node to the impedance of the transmission line being  
used. When impedance are mismatched, the transmitted signal is not completely absorbed by the load  
and a portion is reflected back into the transmission line. The termination line is not necessary if the  
speed on the line is much less than 115Kbauds  
RS485  
SA1  
SA2  
RD = (B')  
1
2
3
4
5
R-  
R+  
T-  
RD = (A')  
TD = (B)  
TD = (A)  
SA2  
SA1  
1
8
1
8
T+  
0 V  
0 V  
The default setting of the RS485 is a 4 wires configuration without polarity and without termination.  
SA1 switches are used to make the termination and the topology of the line (2 or 4 wires). The  
termination resistance value is 166 Ω.  
SA1 description:  
1 : reserved  
2 : reserved  
3 : link termination between T- to R- (2 wires configuration) if set to ON  
4 : connection T- to R- (2 wires configuration ) if set to ON  
5 : connection T+ to R+ (2 wires configuration ) if set to ON  
6 : reserved  
7 : reserved  
8 : link termination between R+ and R- if set to ON  
34003906EN/AE - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 wires connection  
SA1  
SA2  
SA2  
SA1  
1
8
1
8
5
4
3
2
1
L - L +  
5V  
3V3  
3V3  
Rp  
polarity  
L-  
L-  
L-  
L-  
connection  
if end  
3
1
3
1
3
termination  
of the line  
Ra  
Ra  
7
Ra  
connection  
if end  
of the line  
termination  
SA1-3  
SA1-3  
L+  
L+  
L+  
L+  
2
4
2
4
polarity  
Rp  
0V  
0V  
0V  
transmit/receive  
data  
transmit/receive  
data  
transmit/receive  
data  
Card of an intermediate cubicle  
Master unit  
Card of an end-of-line cubicle  
Card settings of an intermediate cubicle  
SA1  
SA1  
SA2  
Link without polarity and without termination.  
Others settings  
SA1  
SA1  
SA2  
Link with termination.  
10 - 34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 wires connection  
SA1  
SA2  
SA2  
SA1  
1
8
1
8
5
4
3
2
1
T + T - R + R-  
master  
transmitt  
slave  
receiver  
slave  
receiver  
5V  
Rp  
polarity  
T-  
R-  
R-  
R-  
1
termination  
termination  
1
Ra  
Ra  
T+  
R+  
R+  
R+  
2
2
polarity  
Rp  
0V  
5V  
transmit data  
receive data  
receive data  
Rp  
Ra  
slave  
slave  
slave  
receiver  
transmitt  
transmitt  
R-  
T-  
T-  
T-  
connection if  
end of the line  
3
3
connection if  
end of the line  
R+  
T+  
T+  
T+  
4
4
Rp  
0V  
receive data  
transmit data  
transmit data  
Master unit  
Card of an intermediate cubicle  
Card of an end-of-line cubicle  
Card settings of an intermediate cubicle  
SA1  
SA1  
SA2  
Link without polarity and without termination.  
Others settings  
SA1  
SA1  
SA2  
Link with termination.  
34003906EN/AE - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration of the JBUS/MODBUS communication parameters  
Through settings port  
ETERNET  
/Sensor  
100M  
1
0M  
n  
=
UP  
L
Bl  
S
in  
dat  
a  
k
a
R
S2  
32  
6
6
1
0
3
Connect the RS232 link to a  
terminal  
(Microsoft Hyper terminal)  
Use the cord supplied with the card  
Connect the card to a computer  
Use a terminal emulator such as HyperTerminal  
TM  
with these settings  
Bits per second  
9600  
Data bits  
8
Stop bits  
1
Parity  
none  
Flow control  
none  
"Echo typed characters locally" option: disabled  
Check that UPS power is on.  
Type EATON (or eaton).  
The main configuration menu is displayed:  
EATON  
NETWORK MANAGEMENT CARD  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
5 : Jbus configuration  
6 : Sensor configuration  
0 : Exit  
Press the 5 key (Jbus configuration).  
The Jbus configuration menu is displayed:  
Jbus settings  
1 : Display Jbus settings  
2 : Modify Jbus settings  
3 : Display Jbus diagnostics  
4 : Reset Jbus diagnostics  
5 : Return to Jbus Default Configuration  
6 : Display Jbus frames  
0 : Exit  
12 - 34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Press the 2 key (Modifiy Jbus settings)  
Press «Return» key to modify the Jbus settings  
Setting Jbus configutration  
Set Slave number : 0x1*  
Set the Baud Rate [1:38400,2: 19200, 3:9600, 4: 4800, 5: 2400,  
6: 1200] :3  
Set data format[1: 8 bits, 2: 7 bits] :1  
Set stop bit[1: 1 bits, 2: 2 bits] :1  
Set parity [1: None, 2: Even, 3: Odd] :1  
Wait during the new setting is saved ...  
TLS/Slave JBUS initialized  
The Jbus configuration is now updated.  
* Hex format.  
Press the 0 key (Exit).  
Press the 0 key (Exit).  
Through a web browser  
Run a browser  
Enter in the address bar:  
http://IP address/ (e.g. http://172.16.1.82/)  
The home page is displayed  
Select the setting menu  
Set the parameters.  
Select the «Save» button to save the new parameters.  
34003906EN/AE - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TECHNICAL CHARACTERISTICS  
Physical characteristics  
Dimensions (W x D x H)  
Weight  
132 x 66 x 42 mm  
70 g  
RoHS  
100% compatible  
Storage  
Storage temperature range  
Ambient conditions  
Operating temperature range  
Relative humidity  
Card performance  
Supply voltage  
-10°C to 70°C  
0°C to 40°C  
90% RH max. without condensation  
5V ±5%  
Supply current (all LEDs ON and  
Environment Sensor connected)  
300 mA max.  
Functions  
Web supervision  
5 browsers max. (http),  
3 browsers max. (https)  
Languages  
Alarms  
English, French, German, Italian, Spanish  
E-mail, SNMP TRAP, Web page  
400 measurements or events  
Log  
Server protection  
Network  
Up to 100 servers protected  
Fast ETHERNET, 10/100 Mbits, auto-negotiation  
HTTP 1.1, SNMP V1, NTP, TFTP, SMTP, BOOTP/DHCP  
Identification  
Security  
Browsers  
NMS  
User name and password  
SSL 3.0, TLS 1.0  
Microsoft Internet Explorer 6.x or higher  
Enterprise Power Manager (EPM)  
Management-Pac 2  
MIB  
MIB II standard - UPS EATON MIB V1.7  
Settings (default values)  
IP network  
BOOTP/DHCP enabled  
IP address: 172.17.16.16 (manual configuration)  
Subnet mask: 255.255.0.0  
Gateway: 0.0.0.0  
NTP server: pool.ntp.org  
Web-page access control  
User name: EATON  
Password: EATON  
Service-port menu access control  
Date and time  
Password: EATON or eaton (not modifiable)  
Synchronise with an NTP server (GMT)  
Service port  
9600 bits/s, 8 bits, 1 bit stop, no parity  
RS485 port  
Slave nb:0x01, 9600 bits/s, 8 bits, 1 bit stop, no parity  
14 - 34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTROMAGNETIC COMPATIBILITY  
When correctly installed and used in accordance with manufacturer instructions, the card complies with  
the following standards:  
ITE (Information Technology Equipment) safety: IEC/EN 60950-1 2002  
EMC: EN 61000-6-2 (2002), EN 61000-6-3 (2002), IEC/EN 62040-2 (2002)  
In compliance with European directives:  
Low voltage: 73/23/EEC and 93/68/EEC.  
EMC: 89/336/EEC and 93/68/EEC.  
Federal Communication Commission (FCC) statement  
This equipment has been tested and found to comply with the limits for a Class B digital device,  
pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against  
harmful interference when the equipment is operated in a commercial environment.  
WEB SITE  
The information presented in this manual is also available in other languages in the download section  
of the EATON site (www.eaton.com/powerquality).  
34003906EN/AE - 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
34003906EN/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Crate Amplifiers Stereo Amplifier G40C User Manual
Cuisinart Cookware Eco Friendly Nonstick Cookware User Manual
Danby Refrigerator DCRM71BLDB User Manual
Dual Stereo System XD5125 User Manual
Elation Professional Network Card 60 Strip II WA User Manual
Fisher Price Baby Toy 77806 User Manual
Fisher Price Car Seat R6069 User Manual
Fisher Price Motorized Toy Car T2057 User Manual
FujiFilm Digital Camera 2600 Zoom User Manual
GE Door 19217 User Manual