Programming guide
Xr500 SerieS Canadian
Command ProCeSSor™ Panel
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of ConTenTS
XR500 Series Canadian Programming Guide
Digital Monitoring Products
i
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of ConTenTS
Digital Monitoring Products
ii
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of ConTenTS
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
iii
Table of ConTenTS
Digital Monitoring Products
iv
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of ConTenTS
XR500 Series Canadian Programming Guide
Digital Monitoring Products
v
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of ConTenTS
Digital Monitoring Products
vi
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
This page intentionally left blank.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
vii
inTroduCTion
Introduction
1.1
Before you Begin
This guide provides programming information for the DMP XR500, XR500N, and XR500E Command
Processor™ Panel. After this Introduction, the remaining sections describe the functions of each
programming menu item along with the available options. Before starting to program, we recommend
that you read through the contents of this guide. The information contained here allows you to quickly
learn the programming options and operational capabilities of the XR500, XR500N, and XR500E panels.
In addition to this guide, you should also read and be familiar with the following XR500 Series Canadian
documents:
• XR500 Series Canadian Installation Guide (LT-0681CAN)
• XR500 Series Canadian Programming Sheet (LT-0678CAN)
• XR100/XR500 Canadian Security Command® User’s Guide (LT-0683CAN)
Internal Programmer
The panel contains all of its programming information in an on-board processor and does not require an
external programmer. You can perform all programming tasks through a 32-character DMP alphanumeric
keypad set to address one.
Programming Information Sheet
Included with each panel are the Programming Information Sheets. These list the various programming
prompts and available options for programming the panel. Before starting to program, we recommend you
completely fill out each sheet with the programming options you intend to enter into the panel.
Having completed programming sheets available before entering data helps prevent errors and can shorten
the time you spend programming. Completed sheets also provide you with an accurate panel program
record you can keep on file for future system service or expansion. The remainder of this Introduction
provides instructions for starting and ending a programming session using the alphanumeric keypad.
1.2
Getting Started
Ground Yourself Before Handling the Panel! Touch any grounded metal, such as the enclosure, before
touching the panel to discharge static.
Remove All Power From the Panel! Remove all AC and Battery power from the panel before installing or
connecting any modules, cards, or wires to the panel.
Before starting to program the XR500 Series Canadian panel, make sure the panel is properly grounded and
AC and battery power is applied to the appropriate panel terminals. All wiring connections and grounding
instructions are detailed in the XR500 Series Canadian Installation Guide (LT-0681).
(LT-0759).
Accessing the Programmer
1. Install the reset jumper across the two J16
J3
Phone Line
J4
Tamper
J6
Interface
Card
reset pins for two seconds.
2. Remove the reset jumper and place it over just
one pin for future use.
3. Enter the code 6653 (PROG) into a
32-character alphanumeric keypad set
to address one, supervised mode. Press
COMMAND.
Link LED
Activity LED
Expansion
Connector
Momentarily place the Reset
jumper over both of the J16
pins to reset the panel.
J1
Ethernet
J21
J23
Power
LED
RS-232
J22
LX-Bus
R
L
X
OVC
J2
Output 1
K6
Output 2
J10
Battery
Start
J11
3
4
5
6
K7
J16
Reset
J8
PROG
Outputs 3-6
AC AC +B –B BELLGND RED YEL GRN BLK SMK GND Z1 GND Z2 Z3 GND Z4 Z5 GND Z6 Z7 GND Z8 Z9+ Z9– Z10+Z10–
4. The keypad displays PROGRAMMER.
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
You are now ready to start programming the panel.
Figure 1: XR500 Series Canadian Panel Showing Reset
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
1
inTroduCTion
1.3
Encrypted Communications (XR500N/XR500E only)
Some installations require secure data communications. DMP offers NIST approved AES encrypted
communication. Use a unique passphrase to enable encrypted communications and provide a secure
means for data communications. See Network Options.
An XR500E panel communicates using AES encryption. If you currently have an XR500N panel installed, you
may purchase a separate feature key to activate encrypted communications using the Feature Upgrade
process. Encrypted communication cannot be enabled on a standard XR500 panel. For more information
on the Feature Upgrade process see Section 21 in this document.
1.4
Programmer Operation
There are 21 programming sections to choose from:
Programming Item
Initialization
Section in This Manual
Programming Item
Output Information
Output Groups
Menu Display
Section in This Manual
2
3
12
13
14
15
16
17
18
19
20
21
22
Communication
Network Options
Messaging Setup
Device Setup
4
5
Status List
6
Printer Reports
PC Log Reports
Area Information
Zone Information
Stop
Remote Options
System Reports
System Options
Bell Options
7
8
9
10
11
Output Options
Set Lockout Code
Feature Upgrade
To choose a section for programming, press any top row Select key when the keypad displays the name of
that section. Sections 2 through 22 contain detailed instructions for each programming step.
1.5
Programmer Lockout Codes
The panel allows you to enter the programming function without entering a lockout code using steps
1 to 4 listed in Getting Started. We recommend, however, that you install a Lockout Code to restrict
programming to only those persons your company authorizes. You can do this by using the SET LOCKOUT
CODE feature in the Programmer. The Lockout Code restricts any unauthorized panel programming.
After resetting the panel and entering the code 6653, the keypad displays PROGRAMMER. Press COMMAND
to advance through the programming sections until SET LOCKOUT CODE displays (after STOP). Press any
top row Select key. The keypad displays ENTER CODE: – . Enter a 3 to 5 digit Programmer Lockout Code
and press COMMAND. The keypad displays ENTER AGAIN followed by ENTER CODE: –. Enter the same 3 to
5 digit code a second time and press COMMAND. The keypad displays CODE CHANGED.
Note: The panel does not accept a 5-digit Lockout Code higher than 65535.
Before accessing programmer functions enter the new code number. Write the Lockout Code number down
and keep it in a secure place with access limited to authorized persons only. Lost Lockout Codes require
the panel to be sent back to DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set
Lockout Code command.
1.6
Reset Timeout
The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the
panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad
displays: RESET PANEL. You must reset the panel and enter the program code then begin programming
within the next 30 minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30
minutes, the panel terminates programming. All data entered up to that time is Not saved unless you run
the Stop routine.
Note: Use the Stop routine to exit panel Programming. Ensure the keypad displays “SAVING PROGRAM” to
save all programming changes entered.
Digital Monitoring Products
2
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
inTroduCTion
1.7
1.8
Power Up
When the XR500 Series Canadian panel is powered up after an AC power failure, any zone transitions are
not recognized for 60 seconds. Normal zone processing resumes at the end of the 60 seconds.
Keypads
DMP offers multiple keypads in a variety of styles. All DMP keypads provide the same programming
capabilities. Each keypad and its operation are shown and described in the following sections.
32-Character Display
32-Character Display
R
Power LED
Armed LED
Power LED
Armed LED
ABC PRINTING
FR I 2 : 51 AM
JONES RESIDENCE
FRI
A
R
M
E
D
12:51 PM
Select Keys
Select Keys
!
1
2
3
4
A B C
D EF
GH
I
J KL
Backlit Logo
and Proximity
Antenna
5
6
8
VWX
7
S T U
M
N
Z
O
P
Q
R
COMMAND
COMMAND Key
Back Arrow Key
9
Y
0
COMMAND Key
Back Arrow Key
Data Entry Digit keys
Data Entry Digit keys
Figure 3: Security Command Keypad
Figure 4: Thinline/Aqualite Keypad
1.9
Special Keys
The following special keys/areas are common to all DMP keypads.
COMMAND (CMD) Key
Pressing the COMMAND key allows you to go forward through the programming menu and through each
step of a programming section. As you go through the programming, the keypad display shows any current
programming already stored in the panel memory. If no change is required for a prompt, press the
COMMAND key to advance to the next step.
The COMMAND key is also used to enter information into the panel’s memory such as phone numbers or
zone names. Press the COMMAND key after entering information.
Back Arrow (<—) Key
Use the Back Arrow key to back up one step while programming. The Back Arrow key is also used when
an error is made while entering information. Press the Back Arrow key once to erase the last character
entered.
Select Keys/Areas
The top row of keys are called the Select keys on Security Command, Thinline, and Aqualite keypads.
Each time you need to press a Select key, the keypad displays the function or options above one of the
keys or in the Select Area. Displaying choices above individual Select keys or in Select Areas allows them
to be used for many different applications. For example, you can enter AM or PM when programming the
automatic test time or answer YES or NO for a system option.
During programming, the Select keys/areas also allow you to change information currently in panel
memory by pressing the appropriate Select key/area under or on the display. You then enter the new
information using the keypad data entry digit keys.
When there are more than four response options available, press the COMMAND key to display the next one
to four options. Pressing the Back Arrow key allows you to review the previous four choices.
The Select keys/areas are also used for choosing a section from the programming menu. Press any Select
key or touch the Select Area when the programming section name you want displays.
Note: On Security Command, Thinline and Aqualite keypads, when instructed to press the first Select
key, press the far left Select key; the second Select key is the second from the left; third Select key is
second from the right; and the fourth Select key is the far right key. See Figures 6 and 7.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
3
inTroduCTion
1.10 Entering Alpha Characters
Some options during programming require you to enter alpha characters. To enter an alpha character,
press or touch the key that has that letter written below it. The keypad displays the number digit of the
key. Next, press the Select key/area that corresponds to the location of the letter under the key. Pressing
a different Select key/area changes the letter. When another digit key is pressed, the last letter displayed
is retained and the process starts over.
A
B
C
(
A
B
C
(
First Letter
Second Letter
Third Letter
Special Character
First Letter Second Letter Third Letter Special Character
Figure 5: Security Command Select Keys
Figure 6: Thinline/Aqualite Select Keys
1.11 Entering Non-Alpha Characters
To enter a space in an alpha entry, press the 9 digit key followed by the third Select key/area. The three
characters on the 9 digit key are Y, Z, and space. You can also enter the following characters: – (dash),
. (period), * (asterisk), and # (pound sign) using the 0 (zero) key and the four Select keys/areas from left
to right. For example, to enter a – (dash), press the 0 (zero) key and then the left Select key/area. A
dash now appears in the keypad display. Figures 7 and 8 show the character location for
Security Command, Thinline, and Aqualite keypads.
1
5
9
2
6
0
3
4
8
7
CMD
Figure 7: Security Command
Special Characters
Figure 8: Thinline/Aqualite
Special Characters
1.12 Keypad Displays Current Programming
Each programming prompt displayed at the keypad shows the currently selected option in the panel
memory. These options are either shown as a number, a blank, or a NO or YES. To change a number or
blank to a new number, press any top row Select key or touch any Select Area. The current option is
replaced with a dash. Press the number(s) on the keypad you want to enter as the new number for that
prompt. It is not necessary to enter numbers with leading zeros. The panel automatically right justifies
the number when you press the COMMAND key.
To change a programming prompt that requires a NO or YES response, press the Select key or touch the
Select Area for the response not selected. See Figure 12.
For example, if the current prompt is selected as YES and you want to change it to NO, on Security
Command, Thinline, or Aqualite keypads press the third top row Select key. The display changes to NO.
Press the COMMAND key to display the next prompt.
Press the black colored top
row Select key/area.
The keypad displays the new
selection. Press CMD to advance.
THEN
Security
Command
Keypads
BELL TST
BELL TST
YES
NO
Thinline
Aqualite
Keypads
BELL TST
YES
BELL TST
NO
Figure 9: Changing the Current Programming Option
Digital Monitoring Products
4
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
inTroduCTion
1.13 Multiple Displays
For many programming and user options, such as Area selections, Menu Displays, and Status Lists, there
are several displays containing programming. For example, when programming Menu Displays, keypads 1
through 16 display on two separate displays. First, keypads 1 through 8 display. Press the COMMAND key
to display keypads 9 through 16. This same scheme is used for areas 1 through 32.
Note: Areas not pre-programmed at installation to display at this keypad cannot be viewed.
1.14 Asterisks in Programming
Asterisks display next to a programming option that is already selected. As shown in the example, options
that are selected to display the current programming selection have an asterisk next to the number. Those
that are not selected simply display the number. In the Devices example, keypads 3, 8, 9, and 15 are not
selected. In the Areas example, areas 3, 8, 9, 15, 19, 23, 25, and 31 are not selected. In both examples
the numbers with asterisks are selected.
Devices
Areas
*1 *2
*5 *6
3
*7
*4
8
9
*10 *11 *12
*1 *2
*5 *6
3
*7
*4 *17 *18
19 *20
23 *24
*13 *14 15 *16
8
*21 *22
25 *26 *27 *28
*29 *30 31 *32
9 *10 *11 *12
*13 *14 15 *16
To select or deselect a number, simply enter the number using the digit keys on the keypad. This same
scheme is used when viewing the panel armed status and other programming and operational functions.
Remember to press the COMMAND key to display the rest of the device or area numbers.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
5
iniTializaTion
Initialization
NOTE: WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN AND ‘SAVING
PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE PROGRAMMING CHANGES. SEE SECTION 17.1.
INITIALIZATION
2.1
Initialization
This function allows you to clear selected parts of the panel program back to the
factory defaults in preparation for system programming. Run the initialization
function on all new installations.
For each section of the panel program you
can initialize, a NO or YES option is provided.
CODES?
NO YES
Selecting YES advances you to
a confirmation prompt.
SURE?
YES NO
Selecting NO advances
you to the next prompt.
If you select YES, the panel initializes that section of
the program and advances you to the next prompt.
If you select NO, the panel advances you to the next
section prompt but does not initialize that section of
the program.
SCHEDS?
NO YES
INIT ALL? NO YES
2.2
2.3
Clear All Memory
NO - Leaves existing programming intact then displays Clear All Codes.
SURE?
YES NO
YES - Clears all memory then displays Reset Panel. Reset the panel by shorting J16
and re-enter programming mode to continue.
CODES?
SURE?
NO YES
YES NO
Clear All Codes
NO - Leaves existing codes intact.
YES - Clears the user code and user profile memory and assigns user code number 99
to the highest user position.
Note: The user name for the default user code is created using the current
programmed primary user language.
SCHEDS?
SURE?
NO YES
YES NO
2.4
2.5
2.6
Clear All Schedules
NO - Leaves existing schedules intact.
YES - Clears all shift, and output schedules.
EVENTS?
SURE?
NO YES
YES NO
Clear Display Events Memory
NO - Leaves existing event memory intact.
YES - Clears the events memory.
ZONES?
SURE?
NO YES
YES NO
Clear Zone Information
NO - Leaves existing zone information intact.
YES - Clears the zone information for all zones. All zones are marked * UNUSED *
and must be renamed before being able to display on any system keypad.
AREAS?
SURE?
NO YES
YES NO
2.7
2.8
Clear Area Information
NO - Leaves existing area information intact.
YES - Clears the area information for all areas. All areas are marked * UNUSED * and
must be renamed before being able to display on any system keypad.
OUTPUTS? NO YES
SURE?
Clear Output Information
NO - Leaves existing output information intact.
YES NO
YES - Clears all programmed Output names and any output cutoff assignment.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
6
Download from Www.Somanuals.com. All Manuals Search And Download.
iniTializaTion
COM/RMT? NO YES
2.9
Clear Communication and Remote Options
NO - Leaves existing communication and remote options intact.
YES NO
SURE?
YES - Clears communication and remote options programming to factory defaults.
DEFAULTS NO YES
2.10
Set to Factory Defaults
NO - Leaves existing panel programming intact.
YES NO
SURE?
YES - Sets the remainder of the panel programming back to the factory defaults.
Note: Sets the Programming and User language to English.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
7
CommuniCaTion
Communication
Communication
Configure the communication options for the panel. The information you program
3.1
3.2
COMMUNICATION
varies with the Communication Type you select.
Account Number
The Account Number is a 1 to 5 digit number used to identify which panel is sending
a message. Enter the account number sent to the SCS-1R Receiver. Messages may
be sent to a central station or via PC Log Reports to a PC. The default is 12345.
ACCOUNT NO: 12345
NET, CELL, 232 and DD - The range of valid account numbers for a panel is 1 to
65535. For accounts of four digits or less, do not enter leading zeros.
CID - Choose an account number between 1 and 9999.
3.3
Transmit Delay
XMIT DELAY:
30
Enter the number of seconds (15 to 45) the panel waits before sending burglary
zones (Night, Day, or Exit) reports to the receiver. Other zone type reports are
sent immediately. Alarm bells and relay outputs are not delayed during this
period. Program Burglary Outputs for pulsed or steady, and set Abort Reports to
YES if Opening and Closing reports are not being sent. Enter 0 (zero) to disable this
function. The default is 30.
If the area where the alarm occurred is disarmed during the Transmit Delay time,
only an Abort Report (S45) message is sent to the receiver. If the area where
the alarm occurred is disarmed after the alarm message is sent to the receiver
but before the Bell Cutoff time expires even if the alarm was silenced, an Alarm
Cancelled (S49) message is sent. Otherwise the alarm is sent at the end of the
delay. The Alarm Cancelled report cannot be disabled.
Note: For Commercial Burglary Installations, the combined Transmit Delay
(Abort Window) and Entry Delay must not exceed one (1) minute.
3.4
3.5
Communication Path
PATH: -
Up to eight communication paths may be programmed. Each path is designated as
a primary or backup communication route. Path 1 is always Primary but other paths
may be programmed as additional primary or backup.
Each primary path establishes a new path group. A path group is made up of the
primary path and its subsequent backup paths. Typical communication takes place
on the primary path with backup paths being used only when the primary path fails
or when the backup path is programmed to duplicate messages. There is no option
to backup path 8.
Communication Type
Specifies the communication method the panel uses on this path to report system
events to DMP SCS-1R Receivers or non-DMP receivers. Default is DD for Path 1, and
NONE for Path 2-8.
COMM TYPE:
DD
NONE DD NET CID
NONE - For local systems. Selecting NONE ends communication programming.
DD - Digital Dialer communications to a DMP SCS-1R Receiver.
NET - Network communication using the panel onboard network connection. The
DMP Network/Output reporting format is transmitted over a data network to the
SCS-1R Receiver.
CID - This option allows the panel to communicate to non-DMP receivers using the
Contact ID format.
CELL - This option allows communication over the GPRS network using digital
cellular technology with the 463G or CellCom Series Digital Cellular Communicator.
CELL 232
232 - This option sends serial data and can be used for radio backup or other
communication options, and uses the on-board serial port.
Select 232 when using a 462N Interface Card or DB-9 backup communications by
directly connecting to the RS-232 port on the panel. If using the on-board RS-232
port, set the XR500 Series Canadian panel J23 jumper to R and briefly reset the
panel using the J16 jumper to activate RS-232 operation. Refer to the XR500 Series
Canadian Installation Guide (LT-0681CAN).
Digital Monitoring Products
XR500 Series Canadian Programming Guide
8
Download from Www.Somanuals.com. All Manuals Search And Download.
CommuniCaTion
3.6
3.7
Path Type
PATH TYPE: BACKUP
The Path Type defines if the path is Primary or Backup. Because Path 1 is Primary,
this prompt only displays for paths 2-8. Default is Backup.
PRIMARY
BACKUP
Note: If the Primary Communication Type is CELL, then the backup Communication
Type can only be NET or 232.
Test Report
TEST RPT: YES
Test Report determines if test reports are sent on this path. Reports are sent
according to the programming in Test Frequency and Test Time. Default is Yes.
Select YES to allow the programmed test report to be sent on the path currently
being programmed.
NO YES DEFER
Select DEFER to not send a test report if the panel communicates any message to the
receiver within the time set in Test Frequency. Select NO to not send test reports on
this path.
3.8
3.9
TEST FREq: 1 DY Test Frequency
Test Frequency determines the frequency of the test report. Enter a number from
1 to 60 and select DY (Day) or HR (Hour) by pressing the far right top row select key.
Default is 1 Day.
Test Day
TEST DAY: SUN
Use this option to set the day of the Test Report. This prompt appears only when Test
Report is Yes, Test Frequency is Day and a multiple of seven. Press the COMMAND key
to display the first four days of the week. Press the COMMAND key to display the last
three days. Select the day of the week to send the test report. Default is Sunday.
3.10
3.11
Test Time
TEST TIME:
0:00 AM
Use this option to select the time of day for Test Reports. Select the hour, minute
and AM/PM. Enter 0:00 AM to disable this feature. Default is 0:00 AM.
Check In
NO YES
CHECKIN:
This option displays if the COMM TYPE is NET, 232 or CELL. Check-in reports are a
method of supervising the panel for communication with the receiver. For NET the
default is YES. For CELL or 232 the default is NO.
Select RND (Random) for the panel to check-in at random times from 6 to 60 minutes
CHECKIN:
NO YES RND ADPT when all areas are disarmed. If any area is armed a check-in is sent every 6 minutes.
Select ADPT (Adaptive) for a backup path to adapt to the check-in programming
from this groups primary path if the primary path becomes unavailable. Check-in
programming includes Check-in and Fail Time.
Select ADP3 (Adaptive 3) for a backup path to adapt using a 3 minute Check-in and
Fail Time if the primary path becomes unavailable. This option also indicates a
Communication Trouble (S10) if the cell tower is unavailable for 3 minutes.
When YES is selected, enter the number of minutes between check-in reports, from
2 to 240 for NET and 232 or 3 to 240 for CELL, when the panel is armed or disarmed.
For CELL or 232 the default is 0. For NET the default is 200.
CHECKIN:
ADP3
CHECKIN MINS: 200
FAIL TIME:
240
3.12
Fail Time
This option displays if CHECKIN is set to YES. Entering a FAIL TIME allows the
receiver to miss multiple check-ins before logging that the panel is missing. The
maximum fail time is 240 minutes. For example, if CHECKIN is 10 and FAIL TIME is
30, the receiver only indicates a Panel Not Responding after 30 minutes. The FAIL
TIME must be equal to or greater than the CHECKIN time. Default is 0 for CELL and
232. Default is 240 for NET.
3.13
3.14
Encryption (XR500E only)
ENCRYPT NO YES
Select Yes to enable encryption for the path currently being programmed. Default is NO.
Receiver IP
RECEIVER IP
This option displays only if the Communication Type is NET or CELL. Enter the
Receiver IP address where the panel sends network messages. The Receiver IP
Address must be unique and cannot be duplicated on the network. Enter all 12
digits and leave out the periods. For example, enter IP address 192.168.0.250 as
192168000250. The periods display automatically.
000.000.000.000
XR500 Series Canadian Programming Guide
Digital Monitoring Products
9
Download from Www.Somanuals.com. All Manuals Search And Download.
CommuniCaTion
3.15
Receiver Port
RECEIVER PORT -
2001
Enter the receiver port number. Valid range is 1 to 65,535. Default is 2001.
3.16
First Telephone Number
This option displays only if the Communication Type is DD or CID.
FIRST PHONE NO.
This is the first number the panel dials when sending reports to the receiver. Phone
numbers can have two lines of 16 characters each to equal up to 32 characters.
Enter P to program a three-second pause in the dialing sequence. The P character
counts as part of the 32 allowable characters.
Enter R as the first character for rotary (pulse) phone function. The R character
counts as part of the 32 allowable characters.
Call Waiting: You can place the “* 7 0 P” (Star, Seven, Zero, Pause) in the telephone
number first position to cancel Call Waiting. For example, program NET with second
line DD and phone number *70P555-1212, and you have NET with Call Waiting
cancelled on the second line.
Caution: A call waiting cancel programmed on a non-call waiting telephone line
would prevent communication to the central station.
3.17
Second Telephone Number
SECOND PHONE NO.
The panel dials the second number when two successive tries using the first number
fail. If the panel cannot reach the receiver after two attempts using the second
number, it returns to the first number and makes two additional attempts. A total of
ten dialing attempts are made using the first and second phone numbers.
Each number can be up to 32 characters in length including any P or R characters
entered for pause or rotary connections or call waiting cancel option.
Should all ten attempts fail, the panel continues to attempt sending the message
using the next programmed path. If all programmed communication paths fail, the
panel clears the communication buffer and makes one communication attempt each
hour to send a TRANSMIT FAILED (S87) report to the receiver. Access the User Menu
Display Events feature to view the report information not sent to the receiver or
download the report with DMP Remote Link™ software.
3.18
3.19
Advanced Programming
ADVANCED? NO YES
Select Yes to enter the Advanced Programming menu for the communication path
currently being programmed.
First GPRS APN
FIRST GPRS APN
SECURECOM400
-
Enter the first APN (Access Point Name). This allows an access point for cellular
communication and is used to connect to a DNS network. The APN may contain two
lines of 16 characters to equal 32 characters. Default is set to SECURECOM400.
Second GPRS APN
SECOND GPRS APN
Enter the second APN (Access Point Name). This works as a backup in case the first
APN fails. The APN may contain two lines of 16 characters to equal 32 character
Default is set to SECURECOM400.
SECURECOM400
-
3.20
3.21
FAIL TEST HRS:
0
Fail Test Hours
This option sets the frequency for a Backup or Adaptive path to send a test report
when the closest previous path fails within its path group.
For example, if a backup path is programmed to send a weekly test report and the
Fail Test Frequency is set to 2 hours, when the previous path fails within its group,
the backup path starts sending a test every 2 hours until the previous path restores.
If Fail Test Frequency is set to 0, test reports are sent only according to Test Report
programming. Range is 0 to 24 hours. Default is 0.
PROTOCOL: TCP
Protocol
This option displays only when Communication Type is NET.
Select TCP to communicate over the network using TCP protocol. Select UDP to
communicate using UDP protocol. Default is TCP.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
10
Download from Www.Somanuals.com. All Manuals Search And Download.
CommuniCaTion
RETRY SECONDS: 6
3.22
Retry Seconds
This option displays for NET or 232 Communication Types.
Enter the number of seconds (between 6 and 15) the panel should wait before
retrying to send a message to the receiver if an acknowledgment was not received.
The panel retries as many times as possible for a period of one minute before
sending a network trouble message. For example, if retry time is set to 15, the
panel retries four times. The default Retry Time is 6 seconds.
Note: If TCP is enabled, the minimum Retry Time programmed is 6 seconds.
3.23
3.24
Substitution Code
NO
SUB CODE
This option displays when the Communication Type is NET, CELL or 232. The Panel
Substitution Code increases the level of security by helping to ensure that the panel
sending the message to the receiver has not been substituted by another panel. The
default is NO.
NO YES SHARED
Select YES to send a substitution code with every message.
Select SHARED (SHR) to use the same substitution code as operating in the previous
path.
232 Communication Port
This option displays when Communication Type is 232.
232 COMM PORT:
O
This option sets the physical RS-232 port to the on-board connector or one of the DMP
Model 461 Interface Adaptor Card slots labeled A, B, C, D, or E. Use slot A if using a
462N Network Interface Card with or without the 461 card.
O
D
A
E
B
C
Enter O to use the on-board connector. Set the XR500 Series Canadian panel J23
jumper to R and briefly reset the panel using the J16 jumper to activate RS-232
operation. Default is O (On-board).
3.25
3.26
232 Setup String
232 SETUP:
-
-
This option displays when the Communication Type is 232. Enter up to two lines of 16
characters to equal up to 32 characters for the destination address that may include
an IP address. Example: If using a DMP iCOM, enter AT#UCXXX.XXX.XXX.XXX#PPPPP
where X is the IP address and P is the port number.
893A
NO YES
893A:
This option displays when the Communication Type is DD or CID.
The 893A option allows reports to be sent to the receiver on a second DD line using
the 893A module. Default is No.
When using this option, Test Report messages (S07 Automatic Recall Test or
S88 Unrestored System Recall Test) are sent to the receiver at the frequency
programmed in Test Frequency, alternating between the first and second phone line.
For example, a DD path with an 893A module set for daily test report frequency
sends a test report through phone line 1 one day and phone line 2 the next day.
If 893A option is set to YES, enter up to a 3 digit prefix to be dialed before the
second phone number. If no prefix is entered, the second phone number is dialed as
originally entered.
2ND LINE PREFIX:
-
3.27
3.28
Alarm Switch
ALARM SWITCH:
1
This prompt displays for DD or CID Communication Types.
Enter the number of attempts to send an alarm message before switching to the next
path. Range is from 1 to 10. All non-alarm messages are sent for 10 attempts on the
dialer before a switch is initiated. If the path immediately following this channel is
not a backup path, this option has no effect. Default is 1.
NO YES
DUPLICATE ALARMS
Duplicate Alarms
This prompt displays for BACKUP paths. If Yes is selected, the current backup path
duplicates all alarms occurring on its group primary path. Default is No.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
11
CommuniCaTion
3.29
Alarm Reports
ALARM
YES
This prompt displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Alarm Reports. Default is Yes.
When YES is selected, the following reports are sent to the receiver for all zone
types:
NO YES FIRE
• Alarm
• Bypass
• Reset
• Restore
When FIRE is selected, the following reports are sent for Fire, Fire Verify and
Supervisory Zones:
• Alarm
• Bypass
• Reset
• Restore
3.30
SPV/TRBL YES
NO YES FIRE
Supervisory/Trouble Reports
This prompt displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Supervisory/Trouble Reports. Default is Yes.
When YES is selected, the following reports are sent for all zone types:
• Trouble
• Low Battery
• Missing
• Fault
• Restorals
• System Troubles
• System Restoral
When FIRE is selected, the following reports are sent for Fire, Fire Verify, and
Supervisory Zones:
• Trouble
• Low Battery
• Missing
• Fault
• Restorals
• System Troubles
• System Restoral
3.31
3.32
Opening/Closing and User Reports
O/C USER NO YES
This prompt displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Opening/Closing and User Reports. Default
is Yes.
When YES is selected, the following reports by user are sent to this receiver.
• Opening
• Closing
• Bypass
• Reset
• Code changes (including adding, deleting, changing)
• Schedule changes (temporary, permanent, shift)
• Holiday date changes
Door Access Report
YES
DOOR ACS
This prompt displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Door Access Reports. Default is Deny.
Select YES to enable Door Access Granted and Denied reports to this receiver
whenever a door access is granted to a user. The Door Access Granted report is
only sent if the keypad number has also been selected in Access Keypads under the
SYSTEM REPORTS programming.
NO YES DENY
Note: To minimize cellular data, Door Access Granted reports are not sent on a CELL
path type.
Select DENY to enable Door Access Denied reports only to this receiver when a door
access is denied to a user.
SEND COMM TRBL:
NO YES
3.33
3.34
Send Communication Trouble
This prompt displays for each path and determines if and how communication
trouble on the path is sent to the receiver. A trouble message indicates both the
path number and communication type that failed. Default is Yes.
SEND PATH INFO:
NO YES
Send Path Information
This prompt displays for each path and if YES, each panel message includes path
information such as path number, communication type, and path type. Default is No.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
12
Download from Www.Somanuals.com. All Manuals Search And Download.
neTwork oPTionS
Network Options (XR500N/XR500E only)
Network Options are provided to define the network configuration for the panel. This information will be
used during communication of messages via network or email.
Note: IP addresses and port numbers may need to be assigned by the network administrator. When
entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods.
For example, IP address 192.168.000.250 is entered as 192168000250.
DHCP
NO YES
4.1
DHCP Mode Enabled
If the panel uses a dynamic IP address select YES. When set to YES, the panel
operates using DHCP and does not use the Local IP Address number. When the DHCP
option is set to NO, the panel uses the IP address entered in Local IP Address. The
default value for DHCP mode is YES.
LOCAL IP ADDRESS
4.2
4.3
4.4
Local IP Address
Enter the local IP address. The Local IP Address must be unique and cannot be
duplicated. The default local IP address is 192.168.0.250.
192.168.0.250
GATEWAY ADDRESS
Gateway Address
192.168.0.1 Enter the local gateway address. The Gateway IP Address is needed to exit your
local network. The default gateway address is 192.168.0.1.
SUBNET MASK
255.255.255.000
Subnet Mask
Enter the local subnet mask assigned to the panel. The default subnet mask address
is 255.255.255.000.
DNS SERVER
192.168.0.1
4.5
4.6
DNS Server
Enter the IP address of the DNS (Domain Name System) used by the panel to resolve
domain names into IP addresses. The default address is 192.168.0.1.
PASSPHRASE
-
Passphrase (XR500E only)
To enable encryption type an 8 to 16-character Passphrase using alphanumeric
characters. If you leave the Passphrase blank, the panel communicates with the
SCS-1R Receiver, but the data is not encrypted. The Passphrase is blank by default.
The XR500E panel is capable of communicating encrypted data to an SCS-101
Network Line Card installed at the receiver. The XR500E panel and the SCS-101 must
have the same secret password called a Passphrase.
Note: DO NOT LOSE THE PASSPHRASE. A lost or forgotten Passphrase requires that
the XR500E panel and every iCOM-E unit reporting in to the same iCOM-E unit at the
receiver be individually reprogrammed with a new passphrase.
Note: An XR500E panel communicates using AES encryption. If you currently have
an XR500N panel installed, you may purchase a separate feature key to activate
encrypted communications using the Feature Upgrade process described in the
Feature Upgrade Section. Encrypted communication cannot be enabled on a
standard XR500 panel.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
13
meSSaging SeTuP
Messaging Setup
MESSAGING SETUP
5.1
Messaging Setup
This section allows you to enter the information needed to receive messages
directly from the panel via email and In Touch™ SMS Text using Network or Cellular
communication. All of the name and password options below allow up to 32
lowercase characters to be entered. The Destination addresses allow up to 48
characters to be entered. System Name is displayed with initial caps.
The transmitted messages are:
• Zone Alarms by Zone Name
• Zone Troubles by Zone Name
• Zone Bypass by User
• Arming (Closings) by User
• Disarming (Openings) by User
• Late to Close
• AC Power Trouble and Restoral
• System Low Battery
• Ambush
• Abort, Cancel and Alarm Verified by User
• Check-in by user
5.2
5.3
Enable Messaging
Select YES to allow the panel to send messages to three programmed destinations.
Default is NO.
ENABLE MESSAGING
NO YES
System Name
SYSTEM NAME
-
Enter a unique name for the panel. The panel name is used as the sender of the
message. The text entered is displayed with initial caps. If this field is left blank, the
panel account number is sent.
DESTINATION 1
-
5.4
Destination 1
Enter the first email address or cell phone number where messages will be sent. The
message can be sent to any device (computer, cell phone, PDA) as long as a valid
email address or cell phone number is entered. When entering email addresses,
press the 7 digit key followed by the fourth Select Key to add the @ symbol and the
9 digit key followed by the fourth Select Key to add the _ symbol. See the Entering
Non-Alpha Characters section for additional symbols.
Note: Mail servers that require Transport Layer Security (TLS) encryption are not
supported by the XR500 Series.
5.5
Destination 1 User Number
DESTINATION 1
USER NUMBER:
If Destination 1 is a 10-digit cellular number, enter a user’s user number from this
account. This option is used when sending commands such as arming or disarming
back to the panel using In Touch™ SMS Text from the same cell phone or PDA. The
user number must have the authority to perform the commands as if it occurred at the
keypad. In Touch™ SMS Text command operation is available in XR500 Series panels
using version 205 or higher. Entering 0 (zero) disables this option. Default is 0.
0
DESTINATION 2
-
5.6
5.7
Destination 2
Enter the second destination email address or cell phone number.
Destination 2 User Number
If Destination 2 is a cellular number, enter the user’s User Number for
arming/disarming authorization.
DESTINATION 2
USER NUMBER:
0
DESTINATION 3
-
5.8
Destination 3
Enter the third destination email address or cell phone number.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
14
Download from Www.Somanuals.com. All Manuals Search And Download.
meSSaging SeTuP
5.9
Destination 3 User Number
If Destination 3 is a cellular number, enter the user’s User Number for
DESTINATION 3
USER NUMBER:
0
arming/disarming authorization.
5.10
EMAIL COMM TYPE
NET CELL
Email Communication Type
Choosing NET sends email messages over the network. Choosing CELL sends email
messages via cellular communication. Default is NET. This prompt appears only if
any destination above is an e-mail address and the panel is a network panel (has an
Ethernet connector).
O/C EMAIL NO YES
5.11
5.12
O/C Email
Select YES to allow the panel to send Opening and Closing reports via email. Default
is NO. This prompt displays if any destination above is an email address.
O/C SMS
NO YES
O/C SMS
Select YES to allow the panel to send Opening and Closing messages to a cell phone
via SMS protocol. Default is NO. This option displays if any destination above is a
cell phone number.
MONTHLY LIMIT:
0
5.13
Monthly Limit
This option displays if any programmed destination is a cell phone number using
NET or CELL communication or an email address using CELL communication. If
all destinations are email addresses using NET communication, this option does
not display. This number limits the monthly incoming and outgoing SMS messages
allowed to be sent or received by the panel.
A panel event that causes messages to be sent to destination cell phone numbers
or destination email addresses is counted towards the panel’s monthly limit. For
example, if an alarm message is sent to a cell phone number and an email address
using CELL communication, a total of 2 messages are counted towards the monthly
limit for the panel. SMS messages sent from a cell phone to the panel, including
status requests and In Touch™ SMS Text messaging commands, also count toward the
monthly limit. The limit is reset at midnight on the 14th of every month. Range is
from 0 to 999. When 0 is entered, there is no limit on the number of messages able
to be sent or received by the panel. Default is 0.
Note: The SecureCom Wireless text plan selected for the panel should match or
exceed the programmed Monthly Limit.
The remaining options only appear if email messaging has been selected to be sent via network. The options allow
the email server to be selected by the installing dealer. Typically this is the email service provided by the installing
dealer. This allows opportunity for additional services to be provided to the end user.
SMTP SERVER
-
5.14
SMTP Server
Enter the SMTP (Simple Mail Transfer Protocol) Server name. The SMTP email server
is responsible for sending the email to its destination. An example SMTP email
server name is: mail.somedomain.com. The domain should be the email server that
provides email support for your alarm customers.
SMTP PORT:
25
5.15
5.16
SMTP Server Port
The SMTP server port number is the port that the panel uses to initiate a TCP
connection with the email server. The default port is 25.
SMTP USERNAME
-
SMTP Username
Most SMTP servers require a username to send email. This is sent to the SMTP server
in conjunction with the SMTP Password to provide email authentication to the server.
SMTP PASSWORD
-
5.17
5.18
SMTP Password
Most SMTP servers require a password to send email. This is sent to the SMTP server
in conjunction with the SMTP Username to provide email authentication to the server.
Passwords display as lowercase.
FROM EMAIL
-
From Email Address
Enter the email address on file with the email service. This displays in the email
message as the sender’s address.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
15
deviCe SeTuP
Device Setup
Device Setup
DEVICE SETUP
6.1
This section allows you to define the XR500 Series Canadian panel physical
configuration. You can install and address up to sixteen supervised devices on the
keypad data bus.
DEVICE NO:-
6.2
Device Number
DEVICE 1: DOOR
Enter the device number on the keypad bus you are programming. The keypad bus
can have up to 16 devices.
Note: After you program each option for the first device, repeat these programming
steps for each additional devices.
DOOR - (XR500 Version 205) The device is an access control device and is either a
keypad or a Wiegand Interface Module.
DOOR KPD FI NONE
KEYPAD - (XR500 Version 205) The device is either a keypad or a zone expander
device.
FIRE - The device is a Remote Fire Command Center.
NONE - No device is set for this address.
6.3
6.4
Door Name
DOOR NAME 1
ACCESS AREAS:
The door name displays. To change the name, press any top row Select key then
enter up to 16 characters for the door name. Press COMMAND to continue device
setup programming.
Access Areas
Press the COMMAND key to program Access Areas. To select an area, enter the area
number using the digit keys on the keypad. When an area is selected, an asterisk
appears next to the area number. Enter the number again to deselect the area.
Press COMMAND to display the next set of areas. Refer to the Multiple Displays
section at the beginning of this document.
Users must have matching access area numbers assigned to their code to receive a
door access at this device.
If you do not enter any area numbers, all users with Door Access authority receives a
door access without regard to schedules. If the user code is programmed for Anti-Pass
YES, then the user is logged into all matching areas. This user is not allowed to access
these areas again until they have egressed the area. See Egress Areas.
When all areas accessed by a door are armed, the door is locked by the panel.
Note: For an All/Perimeter, Home/Sleep/Away, or Home/Sleep/Away with Guest
system, Access Areas should be left at factory default settings.
6.5
EGRESS AREAS:
Egress Areas
Press the COMMAND key to program Egress Areas. To select an area, enter the area
number using the digit keys on the keypad. When an area is selected, an asterisk
appears next to the area number. Enter the number again to deselect the area.
Press COMMAND to display the next set of areas. Refer to the Multiple Displays
section at the beginning of this document.
Note: For an All/Perimeter, Home/Sleep/Away, or Home/Sleep/Away with Guest
system, Egress Areas should be left at factory default settings.
Note: If an area is programmed as an access area, it cannot be programmed as an
egress area and therefore does not display during Egress Areas programming.
Use this option to detect Anti-passback violations. Anti-passback requires a user to
properly exit (egress) an area they have previously accessed. If users fail to exit
through the proper card reader location they are not granted access on their next
attempt. Users must have matching access area numbers assigned to their profile,
to receive a door access at this device. If the user is programmed for Anti-Pass
YES, then the user is logged out of all matching areas. This allows the user to again
access the area. See Access Areas section.
If you do not enter any area numbers, all users with Door Access authority receives a
door access without regard to schedules. If you are not using the Anti-Pass feature
leave Egress Areas blank.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
16
Download from Www.Somanuals.com. All Manuals Search And Download.
deviCe SeTuP
DISPLAY AREAS:
6.6
Display Areas
Press the COMMAND key to program Display Areas. To select an area between 1 and
32, enter the area number using the keypad digit keys. When an area is selected, an
asterisk appears next to the area number. Enter the number again to deselect the
area. Press COMMAND to display the next set of areas. Default is all area numbers.
Refer to the Multiple Displays section at the beginning of this document.
*1 *2 *3 *4
*5 *6 *7 *8
*9 *10 *11 *12
*13 *14 *15 *16
Display Areas allows the XR500 Series burglary activities to be segmented so that
only specific area(s) and their associated operation appear at a particular keypad.
Area number(s) selected in this field affect the way users interact with the system
from this particular device. For example: Program Device 1 to show only the zone
activities and armed status of Area 1.
*17 *18 *19 *20
*21 *22 *23 *24
*25 *26 *27 *28
*29 *30 *31 *32
Enter the area number(s) that this keypad is to display. This allows specific area control
from specific keypads, as well as annunciation of zones assigned to those area(s). When
Display Areas is left defaulted (all areas selected), Menu Display and Status List items
determine whether zone alarms and troubles display at this device, regardless of area
assignment. Also, all system areas may be armed and disarmed from this device.
Note: For an All/Perimeter or Home/Sleep/Away system, Display Areas should be
left at factory default settings.
For Home/Sleep/Away with Guest arming systems, the Display Areas selection
determines which system the keypad arms and disarms. With areas 1, 2 or 3 being
the first areas selected, the keypad is assigned to the Main system. With area 4, 5 or 6
being the first areas selected, the keypad is assigned to the Guest 1 system. With area
7, 8 or 9 being the first areas selected, the keypad is assigned to the Guest 2 system.
Keypads can have additional areas assigned for Event Display.
User Action Allowed
When an area(s) is selected, the following user actions are allowed:
• Arming or Disarming of the area(s) selected from the ARM or DISARM menu
• Alarm Silence for the area(s) selected
• Zone Bypass of zones assigned to the area(s) selected
• Zone Monitor of zone assigned to the area(s) selected
• Shift schedule changes allowed for the area(s) selected
• Closing Check Schedule Extend is allowed for the area(s) selected
• Door Schedules changes are allowed for devices that have a matching area(s)
as defined in Device Access Areas
• Door On/Off Menu operation is allowed for devices that have a matching area(s)
as defined in Device Access Areas
Note: The previous user actions also require the matching area(s) be programmed in
User Profile: Arm/Disarm area(s).
Status Display Allowed
When an area(s) is chosen, the following displays are allowed:
• Armed Status of the selected area(s)
• Zone Alarms and troubles for burglary (NT, DY, EX, A1, A2) type zones assigned to
the selected area(s)
• Late to Close status of the selected area(s)
• Zone Status (normal/fault) of zones that are assigned to the selected area(s)
Options and Actions Not Affected
The following options are not affected by the Display Areas operation. The User
Code authority level controls access to these items.
• Sensor Reset Menu
• Outputs On/Off Menu
• System Status Menu
• Forgive Anti-Passback
• System Test/Panic Test • User Profiles
• Service Request
• Fire Drill
• Set System Time and Date
• Display Events
• 24-hour zones display at keypads based on Status List programming only
Note: A common area and its operations cannot be assigned to a specific keypad.
Display Areas example: When Device 1 has Display Areas set to 20, 21, and 22, it
annunciates troubles and alarms only for zones assigned to those areas.
When arming/disarming from Device 1, only areas 20, 21, and 22 may be armed/
disarmed, even when the User Profile has authority to arm/disarm other system areas.
Exception: Disarming of other areas not selected in Display Areas can be
accomplished by presenting a card that has disarming authority and matching profile
areas with areas assigned in Device Access Areas.
XR500 Series Canadian Programming Guide
Digital Monitoring Products
17
Download from Www.Somanuals.com. All Manuals Search And Download.
deviCe SeTuP
STRIKE TIME:
5
6.7
Strike Time
This option displays if DOOR is selected as Device Type.
Enter a door access time, between 1 and 250 seconds, during which a keypad or access
control device relay is activated. Magnetic locks or electric door strikes are connected
to the relay and released for the length of the strike time. Default is 5 seconds.
Enter 0 (zero) to activate the device relay with a toggle action. This allows the user
to activate or deactivate the device relay each time a valid user code is entered.
The device relay is activated or deactivated until a user code is entered again.
Note: The Request to Exit door access time of a keypad or Model 733 Wiegand
Interface Module is not affected by this selection. It remains at 5 seconds.
Strike Delay
STRIKE DELAY:
0
6.8
6.9
This option displays if DOOR is selected as Device Type.
Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered
or a card read occurs. When a valid code or card read or code is received, the activation
of the door strike is delayed for the number of minutes programmed. The standard door
strike message is sent to the Central Station receiver and logged in the Display Events at
the time of card read or code entry and is not delayed. During this delay, all subsequent
codes entered or cards presented to the reader for a door strike are ignored and no
record of the attempt is stored. Enter 0 (zero) to disable. Default is 0 (zero).
Fire Exit Release
FIRE EXIT NO YES
Select YES to allow the door access relay at this address to be released whenever
Fire panic keys are pressed or a Fire or Fire Verify zone alarm is in the Status List.
The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire
Verify zone alarms from the Status List. Select NO to not allow the door access relay
at this address to be released.
OUT GROUP NO YES
OVERRIDE NO YES
6.10
6.11
Output Group
Select YES to allow the output group (relays) assigned to the user profile to turn ON
when the device relay is activated for the programmed strike time. This could be
used to operate an elevator control. Default is NO. See the User Profiles section in
the Appendix of this document for more information about profiles.
Schedule Override
Use this option to allow door ON/OFF schedules to be overridden by the armed
condition of the system. Selecting YES causes the on time for a door schedule to be
ignored when all areas assigned to Access Areas for this device are armed. Should
any area become disarmed after the door schedule on time, the device output turns
on. A door output which is on during a disarmed period automatically turns off when
all access areas assigned to the device become armed, even if the scheduled off
time has not been reached. This feature can be used to keep doors locked when a
factory opens late, or is forced to close early, due to a snow storm or other cause.
Select NO to allow door schedules to operate independent of system armed status.
Note: When OVERRIDE is YES and there are no areas programmed in ACCESS AREAS,
the door schedule for that device does not work. Either set OVERRIDE to NO or
enter an area number in ACCESS AREAS.
AUTO FORCE ARM
6.12
Auto Force Arm Device?
Select YES to have all Display Areas assigned to this keypad automatically arm and
force arm faulted zones at arming. The user is not prompted to select areas to
arm or force arm faulted zones after choosing ARM at the keypad. If Closing Code
is programmed as YES, only the matching areas between the Display Areas and
the User Code’s authorized areas arm. Also, when YES is selected, the user is not
prompted to select areas to disarm after entering a code at Entry Delay or after
choosing Disarm at the keypad. All matching areas assigned to the User Code and to
this keypad are automatically disarmed. When NO is selected, the user is prompted
to select areas (ALL NO YES) and choose to force arm or bypass at arming and
disarming. Default is NO.
DEVICE?
NO YES
DOOR REAL-TIME
6.13
6.14
Door Real-Time Status?
Select YES to have real-time door status messages sent to PC Log reporting and Entré
reporting for this device. Messages are sent anytime the panel turns the door relay on or
off. Default is NO.
STATUS?
NO YES
SEND DOOR FORCED
Send Door Forced Message?
Select YES to have the panel send a real-time door status message of Forced Open (FO)
to PC Log reporting and Entré reporting when the door relay is off, but the door zone has
transitioned from its normal state. Default is NO.
MESSAGE? NO YES
Digital Monitoring Products
XR500 Series Canadian Programming Guide
18
Download from Www.Somanuals.com. All Manuals Search And Download.
deviCe SeTuP
6.15
Program 734 Options
PROGRAM 734
Select YES to program the 734 Wiegand Interface Module. Device type must be set to
OPTIONS? NO YES
DOOR.
6.15.1
Activate Zone 2 Shunt
ACTIVATE ZONE 2
SHUNT?
Select YES to activate the Soft-Shunt™ option.
NO YES
Selecting NO allows standard zone operation on Zone 2 and displays the ACTIVATE
ZONE 3 REX option. Default setting is NO.
If the door being released by the 734 module is protected (contact installed), you
can provide a programmable Soft-Shunt entry/exit timer by connecting its contact
wiring to the 734 module Zone 2. When the on-board Form C relay activates and
the user opens the door connected to Zone 2, the zone is shunted for the number of
seconds programmed in ZONE 2 SOFTSHUNT TIME allowing the user to enter/exit.
If Zone 2 does not restore (door closed) within the programmed time minus ten
seconds, the piezo sounds every other second during the timer last ten seconds. If
Zone 2 restores prior to the end of the programmed time, the piezo silences. If the
zone does not restore after the ten second piezo time, the 734 ends the shunt and
indicates the open or short zone condition to the panel.
If you select YES, pressing the COMMAND key displays ZONE 2 SOFTSHUNT TIME. The
Back Arrow returns to the Program 734 Options.
6.15.2
Zone 2 Soft-Shunt Time
ZONE 2 SOFTSHUNT
Enter the number of Soft-Shunt seconds to elapse before the Soft-Shunt timer
expires. Range is from 20 to 250 seconds. Press any top row select key to enter the
number of seconds. If the door remains open when the timer expires a zone open/
short is sent to the panel for Zone 2. The default is 40 seconds.
Press the COMMAND key to move forward to RELOCK ON ZONE 2 FAULT. The Back
Arrow returns to the ACTIVATE ZONE 2 SHUNT option.
TIME:
40
6.15.3
6.15.4
Relock on Zone 2 Fault?
RELOCK ON ZONE 2
Selecting NO leaves the relay on when Zone 2 faults to an open or short condition
during Soft-Shunt. Selecting YES turns the relay off when Zone 2 faults open or short
during Soft-Shunt. The default is NO.
FAULT?
NO YES
Press the COMMAND key to display ACTIVATE ZONE 3 REX:. The Back Arrow returns to
the ZONE 2 SOFTSHUNT TIME: option.
Activate Zone 3 Request to Exit
ACTIVATE ZONE 3
REX?
Selecting YES activates the Zone 3 Request to Exit (REX) option.
NO YES
Selecting NO allows standard zone operation on Zone 3 and displays the ACTIVATE
ONBOARD SPEAKER option. Default setting is NO.
Optionally connect a PIR (or other motion sensing device) or a mechanical switch to
Zone 3 to provide REX capability to the system. When Zone 3 shorts, the on-board
Form C relay activates for the programmed number of seconds. During this time,
the user can open the protected door to start the programmed Soft-Shunt™ entry/
exit timer. After the programmed number of seconds, the relay restores the door to
its locked state.
The 734 module provides a shunt-only option for REX on Zone 3. When Zone 3 opens
from a normal state, only a Soft-Shunt occurs: the on-board relay does not activate.
This shunt-only option uses two methods of REX. The first REX device provides the
programmed Soft-Shunt entry/exit timer. The second REX device, or manual device
such as a door knob, unlocks the door.
An example of the shunt-only configuration is a door to an office that is locked 24
hours a day. Users pass a REX motion detector positioned by the door to begin the
programmed exit timer. Within the programmed number of seconds the user must
then manually activate a second device, such as a REX device or manual door knob,
to unlock the door. If the door is opened after the programmed number of seconds,
the zone goes into alarm.
If you select YES, pressing the COMMAND key displays ZONE 3 REX STRIKE TIME. The
Back Arrow returns to the ACTIVATE ZONE 2 SHUNT option.
ZN 3 REX STRIKE
TIME:
6.15.5
Zone 3 REX Strike Time
5
Enter the number of REX seconds to elapse. Range is from 5 to 250 seconds. Press
any top row select key to enter the number of seconds. The default is 5 seconds.
Press the COMMAND key to move forward to the ACTIVATE ONBOARD SPEAKER option.
The Back Arrow returns to ACTIVATE ZONE 3 REX.
XR500 Series Canadian Programming Guide
Digital Monitoring Products
19
Download from Www.Somanuals.com. All Manuals Search And Download.
deviCe SeTuP
6.15.6
Activate Onboard Speaker
Select YES to enable the onboard piezo speaker for local annunciation. Select NO to
turn the piezo off for all operations. This does not affect remote annunciator open
collector (RA) operation. The default is YES.
ACTIVATE ONBOARD
SPEAKER? NO YES
Press the COMMAND key to display the CARD OPTIONS option. The Back Arrow
returns to ACTIVATE ZONE 3 REX.
CARD OPTIONS:
CARD OPTIONS:
6.15.7
Card Options
DMP
Press any top row Select key to display options. Press the select key under DMP or
CUSTOM to select that option. Select DMP to indicate the reader sends a 26-bit DMP
data string. Press the COMMAND key to display REQUIRE SITE CODE.
DMP
CUSTOM
Note: When set to DMP, the 734 converts 17 bits of the 26-bit data string into a
5-digit number.
Select CUSTOM if using a non-DMP card or user code length of 6 to 10 digits.
Default is DMP.
6.15.8
Custom Card Definitions
26 When using a custom product, enter the total number of bits to be received in
Wiegand code including parity bits.
WIEGAND CODE
LENGTH:
Press any top row Select key to enter a number between 0-255 to equal the number
of bits. Default is 26 bits.
Typically, an access card contains data bits for a site code, a user code, and start/
stop/parity bits. The starting position location and code length must be determined
and programmed into the 734 Module.
0 1 1 1 0 1 0 1 1 0 1 1 0 1 0 1 0 0 0 1 1 0 0 1 1 1
Site Code
Position = 1
Length = 8
User Code
Position = 9
Length = 16
Last Bit
Received
Position = 25
First Bit
Received
Position = 0
In this example the Wiegand Code Length = 26 bits.
SITE CODE
POSITION:
6.15.8.1
6.15.8.2
Site Code Position
1
Enter the site code start position in the data string. Press any top row Select
key to enter a number between 0-255. Default is 1.
SITE CODE
LENGTH:
Site Code Length
Enter the number of characters the site code contains. Press any top row
Select key to enter a number between 1-16. Default is 8.
8
USER CODE
POSITION:
6.15.8.3
6.15.8.4
User Code Position
9
Define the User Code start bit position. Press any top row Select key to
enter a number between 0-255. Default is 9.
USER CODE
LENGTH:
User Code Length
Define the number of User Code bits. Press any top row Select key to enter
a custom number. Custom numbers can only be a number between 16-32.
The default is the DMP value of 16 which is pre-programmed.
16
Digital Monitoring Products
XR500 Series Canadian Programming Guide
20
Download from Www.Somanuals.com. All Manuals Search And Download.
deviCe SeTuP
6.15.9 REqUIRE SITE
Require Site Code
Press the top row Select key under YES to use a site code.
CODE?
NO YES
In addition to User Code verification, door access is only granted when any one site
code programmed at the SITE CODE ENTRY option matches the site code received in
the Wiegand string.
6.15.9 .1
Site Code Display
You can program up to eight three-digit site codes. Site code range is 0-999.
Any previously programmed site codes display. Dashes represent blank site
codes.
SITE CODE 1: -
Site Code 1 displays first. Enter a three-digit site code number followed by
the command key to advance to the next prompt, Site Code 2. To delete
an existing site code, press any select key. Either enter a new site code
followed by command, or press command to leave blank and continue to the
next site code. Repeat these steps to change, delete, or add up to 8 site
codes.
Note: A card with a site code greater than three digits cannot be used.
Use only cards with three-digit site codes.
NO OF USER CODE
6.15.10
6.15.11
Number of User Code Digits
DIGITS:
5
The 734 module recognizes user codes from four to ten digits in length. Press any
top row Select key to enter a user code digit length between 4-10 digits. This
number must match the user code number length being used by the panel. Default
is 5. For an XR500 Area System, use 4 to 10 digits (typically 5). For all other systems
and panels, use 4 digits.
Any selection above 5 digits require entry of the custom card definitions with custom
site and user code positions for the Wiegand string. When searching the bit string
for the user code, the digits are identified and read from left to right.
Degraded Mode
This option defines the relay action when communication with the panel has not
occurred for five seconds. Press any top row Select key to display relay action
options. Press the Back Arrow key to return to the NO OF USER CODE DIGITS:.
Choose the Degraded Mode Action required.
DEGRADED MODE:
OFF SITE ANY ON
Press the first Select key to choose OFF [Default] (Relay Always Off) — The relay
does not turn on when any Wiegand string is received. Off does not affect any REX
operation.
DEGRADED MODE:
RELAY ALWAYS OFF
DEGRADED MODE:
ACCEPT SITE CODE
Press the second Select key to choose SITE (Accept Site Code) — Door access
is granted when the Wiegand site code string received matches any site code
programmed at SITE CODE ENTRY. For details refer back to the REQUIRE SITE CODE
option.
DEGRADED MODE:
ANY WIEGAND READ
Press the third Select key to choose ANY (Any Wiegand Read) — Door access is
granted when any Wiegand string is received.
DEGRADED MODE:
RELAY ALWAYS ON
Press the fourth Select key to choose ON (Relay Always On) — The relay is always on.
Press the COMMAND key to display the next action.
DEGRADED MODE:
LAST
Press the first Select key to choose LAST (Keep Last State) — The relay remains in the
same state and does not change when communication is lost.
DEGRADED MODE:
PRESERVE LAST
After choosing the action, the DEGRADED MODE option and the newly defined action
display.
Programming is now complete. Press the COMMAND key to display DEVICE NO. Press
the Back Arrow to return to the NO OF USER CODE DIGITS option.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
21
remoTe oPTionS
Remote Options
REMOTE OPTIONS
REMOTE KEY:
7.1
7.2
Remote Options
This section allows you to enter the information needed for Remote Command/
Remote Programming operation.
Remote Key
This option allows you to enter a code of up to 16 characters. The Remote Link™
program must give the correct key to the panel before being allowed any remote
functions. All panels are shipped from the factory with the key preset as blank.
To enter a remote key or change the current one, press a top row Select key and
enter any combination of up to 16 digits. Press COMMAND. The current key display
as astericks.
7.3
7.4
Remote Disarm
REMOTE DISARM?
YES allows the panel to be disarmed remotely. NO disables remote disarming.
Default is NO.
NO YES
Allow Dialer Remote
ALLOW DIALER
YES allows remote programming over the phone line. Default is YES.
Receiver Key Operation:
REMOTE?
NO YES
With YES selected, the panel requests the receiver’s key during its first message to
the SCS-1R Receiver and this becomes the alarm receiver key. A receiver key is an
alphanumeric code programmed into the receiver and identifies it to alarm panels.
The panel retains this alarm receiver key in memory and allows remote commands
to be accepted over the dialer from the alarm receiver. If an alarm occurs during
a remote connect, the alarm report is immediately sent to the alarm receiver and
does not appear at the remote programming software.
YES also enables remote commands and programming to be accepted from a
secondary receiver other than the alarm SCS-1R Receiver. The panel requests
the service receiver key the first time it is contacted by another receiver and this
becomes the service receiver key. The panel retains this service receiver key in
memory and accepts remote commands from the service receiver. If an alarm occurs
during a remote connect, the panel disconnects from the service receiver and calls
the alarm receiver. Alarm reports are only sent to the alarm receiver.
It is important that the alarm receiver key and the service receiver key programmed
into the receiver at the central station are NOT the same so the panel can determine
the difference between receivers.
When NO is selected, remote commands and programming are not accepted from the
SCS-1R Receiver using digital dialer and all memory of receiver keys is cleared.
7.4.1
Armed Answer Rings
ARMED ANSWER
RINGS:
Enter the number of rings the panel counts before answering the phone line when
all system areas are armed. Any number from 0 to 15 can be entered. If 0 (zero)
is entered, the panel does not answer the phone when all system areas are armed.
The default is 8 (eight).
8
Answering machine bypass procedure: Entering a number greater than 0 (zero) into
either Armed Rings or Disarmed Rings, allows a central station operator to connect
remotely with the panel.
How it works: The operator calls the panel, allows the telephone to ring one time,
and then hangs up. The panel stores this as an attempt to communicate. The
operator then calls back within 30 seconds. The panel seizes the telephone line to
allow remote programming.
Note: This feature does not interfere with the normal operation of the Arm Rings or
Disarm Rings functions.
7.4.2
Disarmed Answer Rings
DISARMED ANSWER
RINGS:
Enter the number of rings the panel counts before answering the phone line while
any system areas are disarmed. Any number from 0 to 15 can be entered. If 0 (zero)
is entered, the panel does not answer the phone when any system area is disarmed.
The default number is 8 (eight).
8
Digital Monitoring Products
XR500 Series Canadian Programming Guide
22
Download from Www.Somanuals.com. All Manuals Search And Download.
remoTe oPTionS
7.4.3
7.4.4
PC Modem
PC MODEM NO YES
YES allows the panel to answer the telco link and connect with Remote Link through
the PC Modem at 2400 baud. NO disables PC Modem communication.
Manufacturer Authorization
MANUFACTURER
Select YES to allow DMP Technical Support technicians to access the panel during
system service or troubleshooting. This authorization automatically expires within
one hour.
AUTH?
NO YES
DMP remote service is provided on a read only basis: DMP technicians can look
at the system programming and make suggestions only. Alterations can only be
accomplished by installing company service personnel.
ALLOW NETWORK
7.5
Allow Network Remote
REMOTE?
NO YES
This option displays only if the panel has network capability. YES allows remote
programming over the network. Changing this prompt does not change any other
network programming prompts. Default is YES.
7.5.1
Network Programming Port
Enter the programming port number. The programming port identifies the port used
to communicate messages from the panel. The default Programming Port setting is
2001.
NETWORK PROG
PORT:
2001
7.5.2
7.6
Encrypt Network Remote
ENCRYPT NETWORK
YES encrypts data sent over network. Default is NO.
REMOTE?
NO YES
Allow Cellular Remote
ALLOW CELL
REMOTE?
YES allows remote programming using cellular connection. Default is YES.
NO YES
7.6.1
First GPRS APN
FIRST GPRS APN:
Enter the first APN (Access Point Name). This allows an access point for cellular
communication and is used to connect to a DNS network. The APN may contain two
lines of 16 characters to equal 32 characters. Default is set to SECURECOM400.
SECURECOM400
-
Second GPRS APN
SECOND GPRS APN:
Enter the second APN (Access Point Name). This works as a backup in case the first
APN fails. The APN may contain two lines of 16 characters to equal 32 character
Default is set to SECURECOM400.
SECURECOM400
-
ENCRYPT CELL
7.6.2
Encrypt Cellular Remote
REMOTE?
NO YES
YES encrypts data sent over a cellular connection. Default is NO.
7.7
7.8
Allow RS-232 Remote
ALLOW 232
REMOTE?
YES allows remote programming over the on-board RS-232 port. Default is YES.
NO YES
Entré Connection
ENTRE
CONNECTION: NONE
This option displays only if the panel has network capability. Select NET to allow
a dedicated network connection with Entré. Options are NONE or NET. Default is
NONE.
7.8.1
7.8.2
Entré Incoming TCP Port
ENTRE INCOMING
This option displays only if NET is chosen for the Entré connection. Enter the
programming port number for the incoming Entré connection. The programming port
identifies the port used to communicate messages to and from the Entré software.
This port cannot be the same port as programmed in Network Programming Port.
The default Programming Port setting is 2011.
TCP PORT:
2011
Entré IP Address
ENTRE IP
This option displays only if NET is chosen for the Entré connection. Enter the Entré
IP address where the panel sends network messages. The Entré IP Address must be
unique and cannot be duplicated on the network. Enter all 12 digits and leave out
the periods. For example, enter IP address 192.168.0.250 as 192168000250. The
periods display automatically. Default is 0.0.0.0
000.000.000.000
7.8.3
Entré Outbound TCP Port
ENTRE OUTBOUND
TCP PORT: 2001
This option displays only if NET is chosen for the Entré connection. Enter the
programming port number for the outbound Entré connection. The programming port
identifies the port used to communicate messages to the Entré software. Default is
2001.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
23
remoTe oPTionS
7.8.4
Entré Backup IP Address
ENTRE BACKUP IP:
000.000.000.000
This option displays only if NET is chosen for the Entré connection. Enter the IP
backup address where the panel sends network messages if the first Entré IP Address
fails. The Entré IP Address must be unique and cannot be duplicated on the network.
Enter all 12 digits and leave out the periods. For example, enter IP address
192.168.0.250 as 192168000250. The periods display automatically. Default is
0.0.0.0
7.8.5
7.8.6
7.8.7
7.9
Entré Backup TCP Port
ENTRE BACKUP TCP
This option displays only if NET is chosen for the Entré connection. Enter the
backup programming port number for the outbound Entré connection in case the
connection to the primary IP fails. Default is 2001.
PORT:
2001
Entré Checkin
ENTRE CHECKIN
MINUTES:
0
Select the rate at which check-in messages are sent over the Entré connection.
Select 0 (zero) to disable check in messages. Range is 0, 3-240 minutes.
Default is 0.
Entré Passphrase
To enable encryption enter an 8 to 16-character Passphrase using alphanumeric
characters. If you leave the Passphrase blank, the panel communicates with Entré,
but the data is not encrypted. The Passphrase is blank by default.
ENTRE PASSPHRASE
-
Send Local Changes
This option allows the panel to automatically update Remote Link at the central
station with any changes made to the panel.
SEND LOCAL
CHANGES? NO
Select NET or DD to send local programming changes or User Menu changes to user
codes, user profiles, schedules, or holiday dates to Remote Link after exiting the
programming or User Menu. If NET is selected, changes are sent using Network. If
DD is selected, changes are sent using Dialer. Default is NO to disable this feature.
SEND LOCAL
NO NET DD
7.9.1
Remote Change IP
REMOTE CHANGE IP
000.000.000.000
This option displays when NET is selected for Send Local Changes. Enter the IP
address containing up to 12 digits. The Net IP Address must be unique and cannot
be duplicated on the network. Enter all 12 digits and leave out the periods. For
example, enter IP address 192.168.0.250 as 192168000250. The periods display
automatically. Default is 000.000.000.000
REMOTE CHANGE
7.9.2
7.9.3
Remote Change Port
This option displays when NET is selected for Send Local Changes. Enter the Port
number. Valid numbers are from 0 to 65535. Default is 2002.
PORT:
2002
Remote Telephone Number
This option displays when DD is selected for Send Local Changes. Press COMMAND to
enter the phone number the panel dials when sending programming changes. After
entering a phone number, the panel sends any panel changes to Remote Link.
REMOTE PHONE NO.
-
-
The phone number can have two lines of 16 characters each to equal 32. Enter a
P to program a two second pause in the dialing sequence. The P character counts
as part of the 32 allowable characters. Enter *70P as the string first characters to
cancel call waiting. Dial tone detect is an automatic panel function.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
24
Download from Www.Somanuals.com. All Manuals Search And Download.
SySTem rePorTS
System Reports
SYSTEM REPORTS
8.1
8.2
System Reports
Select specific system reports the panel sends to the receiver.
ABORT
NO YES
Abort Report
YES allows the panel to send an alarm abort report to the receiver any time an area
is disarmed during Transmit Delay before an alarm report is sent and the Bell Cutoff
Time has not expired. After disarming an area, if any other area remains armed and
has zone(s) in alarm, the alarm abort report is not sent.
If the communication type is set to DD, a Warning: Alarm Bell Silenced report is also
sent if the alarm bell is silenced.
Note: Abort Reports are not sent for Fire, Fire Verify, or Supervisory type zones.
RESTORAL:
YES
8.3
Restoral Reports
This option allows you to control when and if a zone restoral report is sent to the
central station receiver. Press any Select key to display the following options:
NO
YES
DISARM
NO - Disables the zone restoral report option. Zones continue to operate normally
but do not send restoral reports to the receiver.
YES - Enables the zone restoral report option. Zone restorals are sent whenever a
zone restores from a trouble or alarm condition.
DISARM - Causes the panel to send restoral reports for a non-24-hour zone whenever
a zone that has restored from a trouble or alarm condition is disarmed. All 24-hour
zones send restoral reports as they restore.
BYPASS
NO YES
8.4
8.5
8.6
Bypass Reports
YES allows the panel to send all zone bypasses, resets, and force arm reports to the
receiver. The bypass report includes the zone number, zone name, and the user
name and number of the individual operating the system. Reports are only sent if
O/C User in Communications is set YES for Receiver 1 or Receiver 2.
SCHD CHG NO YES
CODE CHG NO YES
Schedule Change Reports
YES allows the panel to send all schedule changes to the receiver. The report
includes the day, opening time, closing time, extend schedule time, and the user
name and number of the individual making the change. Schedule changes made
through Remote Link™ are not sent to the printer or Display Events.
Code Change Reports
YES allows the panel to send all code additions, changes, and deletions to the
receiver. The code change report includes the user name and number added or
deleted and the user name and number of the individual making the change. Code
changes made through Remote Link™ are not sent to the printer or Display Events.
Reports are only sent if O/C User in Communications is set YES for Receiver 1 or
Receiver 2. The default setting is YES.
ACCESS KEYPADS:
8.7
Access Keypads
Select the keypad addresses (1 through 16) that send door access reports to the
receiver. Enter the keypad number using the digit keys. An asterisk next to the
number indicates that the keypad is selected. Press COMMAND to display the next
set of keypads.
A report is sent with each door access made from the selected keypads. Keypads at
addresses not selected still operate the door relay but do not send access reports.
The report includes the user number, user name, keypad address, and device name.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
25
SySTem rePorTS
AMBUSH
NO YES
8.8
Ambush
YES allows an ambush report to be sent anytime user code number 1 is entered at
a keypad. NO disables the ambush report and allows user number 1 to operate the
same as all other codes.
PANIC TST NO YES
8.9
Panic Test Communication (XR500N/XR500E only)
YES allows the panic zone test verification and failure results to be sent to the
central station receiver. NO disables the panic test report. The default setting is
NO. The system test start, stop, panic zone verification, and panic zone failure
messages sent to the central station and the trips count operation are the same as
used under the Walk test. See Using the Walk Test section in the Appendix.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SySTem oPTionS
System Options
SYSTEM OPTIONS
9.1
9.2
System Options
This section allows you to select system-wide parameters.
System
This option allows you to program how the areas operate for arming and disarming.
The options you can choose are listed below:
SYSTEM:
AREA
AREA - All 32 areas can be programmed and operated independently.
ALL/PERIMETER - Area 1 is the Perimeter and Area 2 is the Interior.
AREA A/P H/A GST
HOME/SLEEP/AWAY - Area 1 is the Perimeter, Area 2 is the Interior, and Area 3 is the
Bedrooms. With the HOME/SLEEP/AWAY option, the user can:
1. Select HOME to arm just the perimeter.
2. Select SLEEP to arm the perimeter and interior (non bedroom areas).
3. Select AWAY to arm all three areas.
Note: A Home/Sleep/Away system can be configured to use all three areas or
only use the Home and Away areas.
HOME/SLEEP/AWAY WITH GUEST- This allows the alarm system to be divided into a
main house HOME/SLEEP/AWAY system and two other guest houses that also are set
up as HOME/SLEEP/AWAY systems.
Areas 1, 2, and 3 are the Perimeter, Interior, and Bedrooms for the Main house
system. Areas 4, 5, and 6 are the Perimeter, Interior, and Bedrooms for the Guest
1 house system. Areas 7, 8, and 9 are the Perimeter, Interior, and Bedrooms for
the Guest 2 house system. These areas are automatically assigned per system and
cannot be changed. See Display Areas in Device Setup to assign keypads to a system.
Zones are assigned to a system by assigning the system’s area numbers to the zone in
Zone Information programming.
When either All/Perimeter or Home/Sleep/Away is selected, the area names are
automatically assigned and cannot be modified.
Note: Areas 3-32 in an All/Perimeter system, areas 4-32 in a Home/Sleep/Away
system, and areas 10-32 in a Home/Sleep/Away with Guest system are not available
for use and are initialized.
INST ARM NO YES
9.3
Instant Arming
When YES is selected, the arming keypad displays INSTANT for selection during the exit
countdown delay when arming fewer than all areas of the system. At the time instant
arming is selected, any entry and exit delays programmed for the areas being armed
are ignored. The entry delay for previously armed areas is not affected by instant
arming. When NO is selected, INSTANT does not display during arming. Default is NO
for an Area System, and YES for an All/Perimeter or Home/Sleep/Away system.
CLS WAIT NO YES
9.4
9.5
Closing Wait
When YES is selected, the keypad displays ONE MOMENT... while waiting for
an acknowledgement from the receiver before arming the selected area(s) and
performing a Bell Test (if selected). Exit delays begin after the Closing Wait.
Opening/Closing reports must be YES to enable Closing Wait.
ENTRY DLY 1:
ENTRY DLY 2:
ENTRY DLY 3:
ENTRY DLY 4:
30
60
Entry Delay 1
Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay 1.
When an armed Exit type zone is faulted, the keypad prewarn tone begins sounding.
All keypads programmed to prewarn for that zone display ENTER CODE:- and the
name of the zone causing the entry delay. When the first digit of a code is entered,
the prewarn tone stops at that keypad. If an invalid code is entered, the prewarn
tone begins sounding again. The area must be disarmed before the delay expires
or an alarm report is sent to the receiver and an alarm sounds. All zones in that
area are delayed along with the Exit zone. Entry Delay times can be from 30 to 250
seconds. Repeat the above for each entry delay being used in the system.
90
120
Note: Specific Exit Error operation is based on the Entry Delay used (1-4) with an EX
type zone. See Exit Delay.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
27
SySTem oPTionS
CRS ZONE TM:
4
9.6
Cross Zone Time
Enter the time allowed between zone faults. When zones are cross zoned, the same
zone or a second cross zoned zone must fault within this time in order for an alarm
report for both zones to be sent to the receiver. If the cross zone time expires
without the second zone faulting, only a zone fault from the first zone is reported.
Cross-zone time can be from 4 to 250 seconds. Entering 0 (zero) disables this
function. Default is 4. See the Appendix.
RETARD DELAY:
PWR FAIL HRS:
10
9.7
9.8
Zone Retard Delay
Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, Auxiliary 2, Arming,
and Panic type zones. The retard delay only functions when the zone is shorted.
The zone must remain shorted for the entire length of the Retard Delay before being
recognized by the panel. The Zone Retard Delay can be from 1 to 250 seconds.
Entering a 0 (zero) disables this function.
1
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off for
the length of the programmed delay time, an AC power failure report is sent to the
receiver. The delay time can be from 1 to 15 hours. Entering a 0 (zero) sends the
power failure report after a 15-second delay. The default setting is 1.
SWGRBYPS TRIPS: 1
9.9
Swinger Bypass Trips
Enter the number of times (1 or 2) a zone can go into an alarm or trouble condition
within one hour before being automatically bypassed. You can select one or two
trips. Bypassed zones are automatically reset when the area they are assigned to is
disarmed. All 24-hour zones are reset when any area of the system is disarmed. A
programming Stop operation restores a bypassed zone. Entering 0 (zero) disables
this function. Default is 1.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires
before the trip counter is exceeded, the trip counter returns to 0 (zero). If the trip
counter is exceeded before the hour expires, the zone is automatically bypassed by
the panel. A Bypass Report is sent to the receiver if Bypass Reports is YES.
9.10
9.11
Reset Swinger Bypass
RST SBYP NO YES
When YES is selected, an automatically bypassed zone is reset if it remains in a
normal condition for one complete hour after being bypassed. A report of the
automatic reset is sent to the receiver if Bypass Reports has been selected as YES.
Default is NO.
TIME CHG NO YES
Time Zone Changes
This function allows the panel to request automatic time changes from the DMP
SCS-1R Receiver on Path 1. For the receiver to send time changes, it must be
programmed to send time changes and must be receiving time change updates from
the network automation computer at least every 24 hours. Default is YES.
HRS FROM GMT:
6
When time zone is programmed YES, enter the number (0-23) that indicates the
Greenwich Time zone (GMT) where the panel is located. The default is 6.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
28
Download from Www.Somanuals.com. All Manuals Search And Download.
SySTem oPTionS
GMT City/Time Zone
GMT City/Time Zone
London, Monrovia, Lisbon, Dublin, Casablanca, Edinburgh
13
14
15
16
17
18
19
20
21
22
23
New Cadelonia
0
1
Cape Verde Island, Azores
Guam, Sydney
Mid-Atlantic, Fernando de Noronha
Buenos Aires, Georgetown, Brasilia, Rio de Janeiro
Atlantic Time (Canada), Caracas, La Paz, Santiago
Eastern Time (US, Canada) Bogota, Lima, Arequipa
Central Time (US, Canada), Mexico City, Saskatchewan
Mountain Time (US, Canada), Edmonton
Pacific Time (US, Canada), Tijuana
Alaska
Tokyo, Seoul
2
Hong Kong, Singapore
Bangkok, Hanoi
Dhaka, Almaty
3
4
5
Islamabad, Karachi
Abu Dhabi, Kazan
Moscow, Bagdad
Eastern Europe
Rome, Paris, Berlin
6
7
8
9
Hawaii
10
11
12
Midway Island, Samoa
Fiji, Marshall Island, Wellington, Auckland, Kwajalein, Kamchatka
LATCH SV NO YES
9.12
9.13
Latch Supervisory Zones
Selecting YES latches supervisory zone alarms on the keypad display until the sensor
reset operation is performed. Selecting NO automatically clears the alarm from the
keypad display when the supervisory zone restores to a normal condition. Default is YES.
PROG LANGUAGE
Programming Menu Language
Press the COMMAND key to select the programming language. Any changes in PROG
LANGUAGE do not take effect until the STOP routine completes.
PRI LANG: ENGLSH
The current primary programming language displays. The default language is
English. Press a Select key to change the primary programming language.
ENG SPN FRN
Select the primary programming language.
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
SEC LANG:
NONE
The current secondary programming language displays. Selecting a secondary
language allows the installer to view programming in English, Spanish, or French.
When the Programming Menu is accessed, the installer is prompted to choose the
programming display language. If SEC LANG: is set to NONE, the option to choose
a language does not display. To select a secondary language, press the Select key
below the language. Default is NONE.
NONE ENG SPN FRN
Select the secondary programming language.
NONE = No secondary language options are displayed
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
USER LANGUAGE
9.14
User Menu and Status List Language
Press the COMMAND key to select User language.
PRI LANG: ENGLSH
ENG SPN FRN
The current primary user language displays. The default language is English. Press a
Select key to change the primary User language.
Select the primary user language.
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
SEC LANG:
NONE
The current secondary user language displays. Selecting a secondary user language
allows the user to view the User Menu and Status List text in English, Spanish, or
French. When the User Menu is accessed, the user is prompted to choose the display
language. Status List text displays in the selected language until another language
is chosen. If SEC LANG: is set to NONE, the option to choose a language does not
display. To select a secondary language, press the Select key below the language.
Default is NONE.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
29
SySTem oPTionS
For example, when Spanish is selected at a keypad, the User Menu and Status List
text display in Spanish at that keypad. When the user later accesses the keypad,
pressing the COMMAND key once displays the option for English, Spanish, or French.
Pressing the COMMAND key again continues to display the Status List text in Spanish.
Later on, if English or French is selected at that keypad, the User Menu and Status
List text display in the selected language at that keypad.
NONE ENG SPN FRN
Select the secondary user language.
NONE = No secondary language options are displayed
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
BYPASS LIMIT
0
9.15
9.16
Bypass Limit
Enter the maximum number of zones (0 to 8) that can be bypassed in any single area
when that area is being armed at a keypad. If more zones than the limit are in a
non-normal state or already bypassed at arming, arming does not occur and Arming
Stopped displays. The Bypass limit does not affect auto arming or keyswitch arming.
Entering 0 (zero) allows no limit. Default is 0 (zero).
Card Plus PIN (XR500E only)
CARD PLUS PIN:
Select YES to require all users to present a proximity credential and enter a PIN
number wherever user code entry is required for system functions accessed from a
keypad. Select NO to disable Card Plus PIN operation. Default is NO.
Note: The Card Plus PIN option is not designed to operate with All/Perimeter or
Home/Sleep/Away systems.
NO YES
For an XR500E system using Card Plus PIN, two code entries are required by a user to
operate the system from a keypad. The first must be a code entered from a Wiegand
interface device (card, fob, etc.) using a reader such as the built-in reader of a DMP
Keypad. An external reader may also be used. The second code (User Pin) is keyed
in at the keypad or could be a second card or fob.
For a Card Plus PIN system, user codes (Card and PIN) are typically administered
using DMP System Link software.
When this option is first turned on at a keypad, the factory default (user number
9999, user code 99) must be available to enter the user menu at a keypad to then
add user codes and PIN numbers or to change existing users to add their PIN number.
If user 9999 was previously removed, re-enter this user and then set Card Plus
Pin = YES. Afterwards, user 9999 can be removed and the system only allows card
plus PIN entries.
Note: Current users of an existing system are immediately affected in that they must
have their user code information changed to add the user PIN.
9.17
House Code
WIRELESS
HOUSE CODE: 0
When using a DMP wireless system, enter a house code between 1 and 50. When
using FA Series wireless enter 99. See Wireless programming in Zone Information.
Default is 0 indicating no wireless system is being used.
The DMP house code identifies the panel, DMP receiver, and DMP transmitters to
each other. When operating, the DMP receiver listens for transmissions that have
the programmed house code and transmitter serial number.
Note: The flexibility of DMP two-way wireless operation allows an existing house
code to be changed in the panel at any time. The transmitters may take up to two
minutes to learn the new house code and continue operation.
Note: When any wireless zone programming is changed in the panel, wireless
receiver zone programming is updated. At that point, all wireless zones display as
normal for approximately 1 minute, regardless of the actual state of the zone.
9.18
Detect Wireless Jamming
DETECT WIRELESS
JAMMING: NO YES
This option displays when the House Code entered is for a DMP 1100 Series Wireless
system (1-50). When enabled and the wireless receiver detects jamming, a trouble
or alarm message displays in the Status List and is sent to the central station
receiver. Select YES to enable jamming messages to display in the Status List.
Select NO to disable jamming messages. Default is NO.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
30
Download from Www.Somanuals.com. All Manuals Search And Download.
SySTem oPTionS
9.19
Wireless Audible Annunciation
WLS AUDIBLE: DAY This option displays when the House Code entered is for a DMP 1100 Series Wireless
system (1-50). Press any top row key to select the keypad buzzer annunciation
WIRELESS AUDIBLE
ANY DAY MIN
method for wireless low battery and missing messages. Select ANY to enable
annunciation anytime. Select DAY to enable annunciation except during sleeping
hours (9 PM to 9 AM). Select MIN (minimum) to annunciate only Fire and Fire Verify
zones during daytime hours (9 AM to 9 PM). Default is DAY.
9.20
9.21
Enable Keypad Panic Keys
KEYPAD PANIC KEYS
This option allows the two-button panic key operation selected at the keypad to
send the Panic, Emergency, or Fire message to the central station receiver. Select
YES to enable the two-button panic operation to operate. To disable the two-button
panic operation, select NO. Default is YES.
ENABLED: NO YES
Occupied Premises
OCCUPIED
PREMISES: NO YES
For All/Perimeter or Home/Sleep/Away systems, select YES to allow the panel to
automatically disarm the interior area(s) when arming all areas and a perimeter
zone is not tripped during the exit delay. Select NO to disable this feature. Default
is YES.
Note: With a Home/Sleep/Away with Guest arming system, this feature only applies
to the main system.
9.22
Enhanced Zone Test
ENHANCED ZONE
Select YES to allow enhanced zone test operation. The default is NO.
NO YES
TEST:
Enhanced operation allows:
• Panic Test and Walk Test functions can be restricted to operate only during an
Area 32, Shift 4 schedule if programmed. If no schedule is entered, the walk
test always operates.
• A Verify message is sent each time a zone is tested. If a zone is tripped
multiple times, a Verify message is sent for each trip. This allows the Central
Station to record the number of devices per zone.
• The Verify message for each zone test is sent at the time the trip occurs
instead of at the end of Walk Test.
• The System Test Begin and System Test End Central Station messages indicate
the type of zone being tested. The System Test Begin message also includes
the user name and number.
9.23
9.24
Dual EOL
DUAL EOL NO YES
Select YES to enable the use of dual 1K EOL resistors on panel zones one to eight.
This zone operation is used for medium or high risk ULC Listed applications. Please
see Dual EOL section in the XR500 Series Canadian Installation Guide for complete
details. Select NO to disable this feature. Default is YES.
Send 16 Character Names
This option allows central stations to select being sent either the first 16 characters
of the name field or the entire programmed name, up to 32 characters, for user
name, user profile, zone name, area name, output name, and group name.
SEND 16 CHAR
NAMES:
NO YES
Select YES to have the first 16 characters of the name field sent to the central
station. Select NO to send the exact number of characters entered in the name field
from 1 up to the maximum of 32 characters. Default is YES.
Note: Using 32 character names increases the length of the DMP Serial 3 message
from the panel to the receiver. The SCS-1R receiver does not require an update to
pass these messages to the Host Automation System of the Central Station. Before
using names longer than 16 characters, determine whether the Host Automation
System of your Central Station can accept 17 to 32 character names. If not, only use
16 character names.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
31
bell oPTionS
Bell Options
10.1
10.2
Bell Options
This section allows you to program the panel bell output functions.
BELL OPTIONS
Bell Cutoff Time
Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the
area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell
output. The default is 15 minutes.
BELL CUTOFF: 15
Note: To support the Alarm Verify feature on an All/Perimeter or Home/Sleep/Away
system, set the Bell Cutoff Time to greater than 0.
Note: For SIA CP-01 False Alarm Reduction Installations, the Bell Cutoff Time must
be set to a minimum of six (6) minutes.
10.3
Automatic Bell Test
Select YES to turn on the Bell Output for 2 seconds each time the system is
completely armed from a keypad. This test is delayed until the Closing Wait
acknowledge is received (if programmed). If the Closing Wait acknowledge is not
received within 90 seconds, the bell test does not occur. Arming performed from an
Arming zone or from Remote Link™ does not activate the Bell Test.
BELL TST NO YES
10.4
10.5
Bell Output
Enter the output number when needed to follow the panel Bell Output operation for
all action and off conditions. Enter 0 (zero) to disable.
BELL OUTPUT:
0
Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action for
an LX-Bus output is pulse.
Bell Action
This section defines the type of Bell Output for zone alarms. Press COMMAND to
display the default Bell Output for each zone type. Press any Select key and enter
S for a Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output,
and N for no Bell Output.
BELL ACTION . . . . .
Note: Trouble conditions do not activate the Bell Output.
10.5.1
10.5.2
10.5.3
10.5.4
10.5.5
10.5.6
10.5.7
Fire Bell Action
Defines Bell Action for Fire Type zones. The default is P.
FIRE
TYPE:
P
Burglary Bell Action
Defines Bell Action for Burglary Type zones and Exit Error output. The default is S.
BURGLARY TYPE: S
SUPRVSRY TYPE: N
Supervisory Bell Action
Defines Bell Action for Supervisory Type zones. The default is N.
Panic Bell Action
Defines Bell Action for Panic Type zones. The default is N.
PANIC TYPE:
EMERGNCY TYPE:
AUXLRY 1 TYPE:
AUXLRY 2 TYPE:
N
N
Emergency Bell Action
Defines Bell Action for Emergency Type zones. The default is N.
Auxiliary 1 Bell Action
Defines Bell Action for Auxiliary 1 Type zones. The default is N.
N
N
Auxiliary 2 Bell Action
Defines Bell Action for Auxiliary 2 Type zones. The default is N.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
32
Download from Www.Somanuals.com. All Manuals Search And Download.
ouTPuT oPTionS
Output Options
11.1
Output Options
This section allows you to program panel output options. The panel provides two
Form C relays (1 and 2) and four switched ground (open collector) outputs numbered
3 to 6. Expand the system up to 500 additional relay outputs using J22 LX-Bus on
the panel, multiple 716 Output Expander Modules, and up to five interface cards. In
addition, 45 wireless outputs are available when using the 1100X wireless receiver.
Refer to the XR500 Series Canadian Installation Guide (LT-0681) for complete
information.
OUTPUT OPTIONS
Select from the following output numbers:
• 1 to 6
• 450 to 474 — Slow response time* wireless outputs (activates within 15 seconds)
• 480 to 499 — Fast response time* wireless outputs (activates within 1 second)
• 500 to 999 — LX-Bus output, Relay output, Zone expansion output
• D1 to D16 — Keypad door strike relay for addresses 1-16
• G1 to G20 — Output group
* The response time of a wireless output is the time it takes for a wireless output to
activate once the panel event occurs. You determine whether a wireless output is a
slow or fast response based on the output number assigned. A slow response output
number extends battery life, but response time may be up to 15 seconds. A fast
response output number responds within 1 second, but reduces battery life. Refer
to the specific wireless output installation guide to determine battery life.
11.2.1
Cutoff Output
Outputs 1 to 6 can be entered here to turn off after a time specified in CUTOFF
TIME. To disable this option, press any Select key to clear the display then press
COMMAND. The Cutoff Output displays dashes when no outputs are selected.
CO OUTS: - - - - - -
11.2.2
11.3
Output Cutoff Time
If a Cutoff Output (1-6) is assigned, enter a Cutoff Time of 1 to 99 minutes for the
output to remain on. Enter 0 (zero) for continuous output.
CUTOFF TIME:
0
Communication Trouble Output
Enter the output number to turn on when a DD system fails to communicate on
three successive dial attempts or if the backup communication line transmits a
report. The Communication Trouble Output also turns on when NET is selected
as the primary communication method and NET communication fails after one
minute. When NET communication is restored the Communication Trouble Output
automatically turns off.
COMM TRBL OUT: 0
To manually turn the output off, disarm any area or select Off for the output number
in the User Menu Outputs On/Off section. Enter 0 (zero) to disable this output.
11.4
11.5
Fire Alarm Output
Enter the output number to turn on when a fire type zone is placed in alarm. The
output is turned off using the Sensor Reset option while no additional fire type zones
are in alarm. Enter 0 (zero) to disable. This output is not compatible with Cutoff
Outputs.
FIRE ALR OUT:
FIRE TRB OUT:
0
Fire Trouble Output
Enter the output number to turn on when a fire type zone is placed in trouble, when
a supervisory type zone is placed in alarm or trouble, or when any system monitor
(AC, Battery, Phone Line 1 or Phone Line 2) is placed in trouble. The output turns off
when all fire and supervisory type zones, or system monitors are restored to normal.
Enter 0 (zero) to disable this output. This output is not compatible with Cutoff
Outputs. This output can be connected to a lamp, LED, or buzzer using the DMP
Model 716 Output Expansion Module.
0
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
33
ouTPuT oPTionS
11.6
Panic Alarm Output
Enter the output number to turn on when any Panic type zone is placed in an alarm
condition. The output is turned off after all Panic zones are restored from an alarm
condition and a Sensor Reset is performed. Enter 0 (zero) to disable.
PANIC ALM OUT:
0
Wireless Outputs
• The Panic Alarm is compatible with the Model 1118 Wireless Remote Indicator
Light and the Model 1116 Wireless Relay Output connected to a Model 572
Indicator LED.
• When a Panic Alarm occurs, the LED turns on steady for five minutes and then
turns off.
• When a Panic Test is initiated from the keypad, the LED flashes quickly for five
minutes.
• For a Panic Alarm, a fast response wireless output number is recommended.
11.7
11.8
Ambush Output
Enter the output number to turn on when an Ambush code is entered at a keypad.
The output is turned off using the Sensor Reset option. Enter 0 (zero) to disable.
AMBUSH OUT:
ENTRY OUT:
0
Entry Output
Enter the output number to turn on at the start of the entry delay time. The output
turns off when the area is disarmed or the entry delay time expires. Enter 0 (zero)
to disable.
0
0
0
11.9
Exit Output
Enter the output number to turn on when an exit delay time starts in any area of
the system. The output turns off when the area arms or when the arming has been
stopped. Enter 0 (zero) to disable.
EXIT OUT:
11.10
Ready Output
Enter the output number to turn on when all disarmed burglary zones are in a
normal state. The output is turned off when any disarmed burglary type zone is in
a bad state. Enter 0 (zero) to disable. This output is not compatible with Cutoff
Outputs.
READY OUT:
11.11
11.12
Telephone Trouble Output
Enter the output number to turn on when the phone line monitor on the panel phone
line is lost. Enter 0 (zero) to disable this output.
PH TRBL OUT:
LATE CLS OUT:
0
0
Late To Close Output
Enter the output number to turn on at the expiration of a Closing schedule. The
output activates simultaneously with the CLOSING TIME! keypad display. The output
is turned off when the area is armed, the Closing is extended, or the schedule is
changed. Enter 0 (zero) to disable this output.
11.13
11.14
Device Fail Output
Enter the output number to turn on when an addressed device fails to respond to
polling from the panel. A Missing Device report is sent to the receiver. The output
is turned off when the device responds to polling or is removed from programming in
the system. Enter 0 (zero) to disable this output and LX-Bus™ device fail reporting
to the receiver. If any addressed device is unsupervised, this output cannot be used.
DVC FAIL OUT:
SNSR RST OUT:
0
0
Sensor Reset Output
Enter the output number to turn on when a Sensor Reset is performed at a keypad.
The output turns off automatically 5 seconds later. This function can be used to
reset smoke detectors that are operated by an external power supply through a
Model 716 Output Expander Module. Enter 0 (zero) to disable this output.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
34
Download from Www.Somanuals.com. All Manuals Search And Download.
ouTPuT oPTionS
11.15
11.16
Closing Wait Output
Enter the output number to turn on for approximately four (4) seconds when Closing
Wait is programmed as YES and the panel successfully communicates the closing
message at arming. If the closing message does not communicate successfully, this
output does not turn on.
CLS WAIT OUT:
0
Arm-Alarm Output
Enter the output number to turn on steady when any area of the system is armed. If
an alarm occurs causing the keypads to turn Red, this output pulses and continues to
pulse for approximately five (5) minutes after the panel is disarmed. Enter 0 (zero)
to disable.
ARM-ALARM OUT: 0
Wireless Outputs
• The Arm-Alarm Output is compatible with the Model 1117 Wireless LED
Annunciator and the Model 1116 Wireless Relay Output connected to a Model
572 Indicator LED.
• When the Model 1117 is battery operated, the LED is off when the system is
armed to conserve battery life. If an alarm occurs, the output flashes quickly.
• When using the Model 1116 connected to a Model 572, the LED is on when the
system is armed. If an alarm occurs, the output pulses.
• To operate the Arm-Alarm output within one second, program a fast response
number from 480 to 499. Fast response operation reduces overall wireless
output battery life.
• To operate the Arm-Alarm output within 15 seconds, program a slow response
number from 450 to 474. Slow response operation increases overall wireless
output battery life.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
35
ouTPuT informaTion
Output Information
12.1
12.2
Output Information
This section allows you to program wireless outputs and name wired outputs.
OUTPUT INFO
Output Number
Enter an output number. Entry range is 1 to 6, 450 to 474, 480 to 499, 500 to 999.
OUTPUT NO. X X X
12.3
Output Name
This section allows you to define a 32 character alphanumeric name for any output
numbers. The name can display on the keypad when a user performs the browser
feature at Outputs On/Off. See the XR100/XR500 User’s Guide (LT-0683CAN)
Appendix for browser operation.
OUTPUT NAME
12.4
12.5
Output Real-Time Status
OUTPUT REAL-TIME
Selecting YES allows Real-Time Status reports, such as Output ON, OFF, PULSE, or
TEMPORAL to be sent using PC Log reports. Selecting NO disables Real-Time Status
for this output device. Default is NO.
STATUS
NO YES
Serial Number
This option and the next option only display when the output number entered is for
a wireless output. Enter the eight-digit serial number found on the wireless device.
SERIAL#: XXXXXXXX
This message displays when the serial number is already programmed for another
output. The programmed output number displays.
ALREADY IN USE
OUTPUT NO: XXX
12.6
Supervision Time
Press any top row key to select the supervision time required for the wireless
output. Press COMMAND to accept the default time. Default is 240 minutes.
SUPRVSN TIME: 240
Note: Refer to the Wireless Check-in and Supervision Time Definitions section of the
Appendix for supervision information.
Press the Select key under the required number of minutes. The wireless output
must check in at least once during this time or a missing condition is indicated for
that output. Zero (0) indicates an unsupervised transmitter.
SELECT MINUTES:
0
3
60
240
Note: When the panel is reset, a receiver is installed or powered down and powered
up, or programming is complete, the supervision timer restarts for all wireless
outputs.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
36
Download from Www.Somanuals.com. All Manuals Search And Download.
ouTPuT grouPS
Output Groups
OUTPUT GROUPS
13.1
Output Groups
This function allows you to assign outputs to groups. Output groups can be assigned
to other areas of programming such as Output Options or Alarm Action of Zone
Information, just like single outputs are assigned. This allows the entire group of
outputs to turn on and off as required by the programming option.
GROUP NO: -
13.2
13.3
Group Number
Enter a group number from 1 to 20. Up to 20 different groups may be assigned.
GROUP NAME X X
Group Name
The group name displays. To change the default name, press any top row Select key
then enter up to 32 characters for the group name. Press COMMAND to enter the
outputs to be assigned to the group.
OUTPUT NO 1:
OUTPUT NO 2:
OUTPUT NO 3:
OUTPUT NO 4:
OUTPUT NO 5:
OUTPUT NO 6:
OUTPUT NO 7:
OUTPUT NO 8:
0
0
0
0
0
0
0
0
13.4
Output Number
Enter the Output number. Entry range is 1 to 6, 450 to 474, 480 to 499, 500 to 999
(outputs), D1 to D16 (doors), and G1 to G20 (groups). The maximum number of
outputs that can be assigned to a specific group is eight.
An output group may be assigned as one of the output numbers in another output
group.
Example: Output Group 1 consists of only four assigned outputs. Output Group
1 could be assigned as one output in Output Group 2. Output Group 2 could still
have 7 other outputs assigned to that group. When Output Group 2 is turned on, 11
outputs could be turned on. This allows Output Groups to be assigned within other
Output Groups providing many combinations.
Output groups 1 to 10 can be assigned by a user profile for applications such as
elevator control. See the XR500 User’s Guide (LT-0683CAN) Output Group section for
additional information.
Output groups 11 to 20 cannot be assigned to a profile and are available for
installation applications such as special lighting, etc. To assign these groups to a
profile, use Remote Link™ or System Link™ software from DMP.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
37
menu diSPlay
Menu Display
14.1
MENU DISPLAY
Menu Display
Menu Display allows you to select at which keypad addresses the user can access the
following functions.
To select a keypad, enter the device number (keypad address) using the digit keys
on the keypad. When a keypad is selected, an asterisk appears next to the keypad
address. Enter the number again to deselect the keypad. Press the COMMAND key
to display the next set of keypads (9 through 16). Refer to the Multiple Displays
section at the beginning of this document.
14.2
ARMED STATUS:
Armed Status
Enter the keypad addresses (1 through 16) that show the armed areas. The User
Menu Armed Areas function also displays the custom area name you enter in Area
Information.
When only areas one to eight are used, the Armed Status display is 1 2 3 4 5 6 7 8.
When areas nine or higher are used the system Armed Status display reads ALL
SYSTEM ON or SYSTEM ON. Press the COMMAND key to display additional areas.
Refer to the Multiple Displays section at the beginning of this document and in the
XR500 User’s Guide (LT-0683CAN).
14.3
14.4
TIME DISPLAY:
Time
Enter the keypad addresses that can display the time and day of the week.
ARM/DIS DISPLAY:
Arm/Disarm
Enter the keypad addresses from which users can arm and disarm areas.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
38
Download from Www.Somanuals.com. All Manuals Search And Download.
STaTuS liST
Status List
15.1
STATUS LIST
Status List
This function allows you to select the zone alarms and troubles, and system monitor
troubles displayed at the keypads. The Status List function operates automatically
when the keypad is not performing any other function.
The keypad stays in the Status List until the user arms or disarms or selects a menu
option. Status List alternates with the Armed Status on keypad addresses selected
in the Menu Display - Armed Status section. You can choose to have System Monitor
troubles placed in the list, the different zone types placed in the list, and at which
keypad addresses they display.
To select a keypad, enter the device number (keypad address) using the digit keys
on the keypad. When a keypad is selected, an asterisk appears next to the keypad
address. Enter the number again to deselect the keypad. Press the COMMAND key
to display the next set of keypads (9 through 16). Refer to the Multiple Displays
section at the beginning of this document.
15.2
15.3
DISPLAY KEYPADS:
Display Keypads
This option defines which keypad addresses display the various status information.
Any combination of addresses can be entered to display the status items that follow.
If you do not want a particular status item to display, do not enter any addresses.
SYSTEM TROUBLES: System Monitor Troubles
Specifies the keypad addresses (1 through 16) where any trouble on a System Monitor
displays. The System Monitors include the following:
•
•
•
•
•
•
•
•
AC Power
Battery Power
Closing Check
Panel Box Tamper
Phone Line 1
Phone Line 2
Wireless Receiver Trouble
Wireless Jamming Trouble or Alarm
(requires the 893A Dual Phone Line Module)
The System Monitor name is placed in the Status List and the keypad steady trouble
buzzer sounds. The buzzer remains on until any keypad top row Select key is
pressed. The name remains in the list until the condition is restored. The buzzer
sounds at 10:00 am daily until the system trouble is cleared from the Status List.
15.4
FIRE ZONES:
Fire Zones
Specifies the keypad addresses (1 through 16) where all fire zone alarms and troubles
display. The zone name displays and, if it is a trouble condition, the keypad steady
trouble buzzer sounds. The buzzer remains on until any top row Select key is
pressed and a user code is entered. If a trouble condition remains in the display, the
buzzer sounds at 10:00 am daily until the trouble is cleared from the Status List.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad
for Fire:
On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
39
STaTuS liST
15.5
Burglary Zones
BURGLARY ZONES:
Specifies the keypad addresses (1 through 16) where all burglary zone alarms and
troubles display. Burglary zones include Night, Day, and Exit type zones. Burglary
zone troubles remain in the list until the zone restores. All keypads are selected by
default.
For zone alarms, only the last burglary zone tripped remains in the list. The alarm
remains in the list until another burglary zone goes into alarm, any area of the
system is disarmed, or 10 minutes elapse without an alarm. This ensures that if a
burglary is in progress the last zone tripped remains in the list even if the zone is
restored.
The keypad buzzer sounds for one second on burglary alarms.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad
for Burglary:
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
You can further define which keypad address shows a Burglary Zone event by
entering that area number in the Display Areas menu during Device Setup.
15.6
SPRVISORY ZONES:
PANIC ZONES:
Supervisory Zones
Specifies the keypad addresses (1 through 16) where all supervisory zone alarms
and troubles display. Supervisory zones are entered in the status list and sound the
keypad buzzer until a valid user code is entered at any keypad address. If a trouble
condition remains in the display, the buzzer sounds at 10:00 am daily until the
supervisory trouble is cleared from the Status List.
15.7
15.8
15.9
Panic Zones
Specifies the keypad addresses (1 through 16) where all panic zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for panic alarms or troubles.
EMERGENCY ZONES: Emergency Zones
Specifies the keypad addresses (1 through 16) where all emergency zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for emergency alarms or troubles.
AUX 1 ZONES:
Auxiliary 1 Zones
Specifies the keypad addresses (1 through 16) where all Auxiliary 1 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for Auxiliary 1 alarms or troubles.
You can further define which keypad address shows an Auxiliary 1 Zone event by
entering that area number in the Display Areas menu during Device Setup.
15.10 AUX 2 ZONES:
Auxiliary 2 Zones
Specifies the keypad addresses (1 through 16) where all Auxiliary 2 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for Auxiliary 2 alarms or troubles.
You can further define which keypad address shows an Auxiliary 2 Zone event by
entering that area number in the Display Areas menu during Device Setup.
15.11
Communication Trouble
Specifies when communication troubles are displayed on keypads that are
programmed to display System Monitor Troubles. Default is NO.
COMM PATH TRBL:
ALL NO YES
Select YES to display communication trouble when any communication path fails.
Select ALL to display communication trouble only when all paths have failed.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
40
Download from Www.Somanuals.com. All Manuals Search And Download.
PrinTer rePorTS
Printer Reports
16.1
PRINTER REPORTS Printer Reports
This section allows you to define the operation of a local printer connected to the
panel through the use of a DMP 462P Printer Interface Card. The 462P allows you to
connect the DMP SCS-PTR or other compatible 40-character or 80-character serial
printer to the panel.
Printing the panel event buffer
The Display Events option in the User Menu contains a PRINT command that allows
the user to send the contents of the panel event buffer to a local printer. The PRINT
option is visible whether or not a 462P Printer Interface Card is attached to the
panel.
16.2
16.3
ARM/DIS NO YES Arm and Disarm Reports
Prints arming, disarming, and Late to Close reports. Includes the area number,
name, and action (armed, disarmed, or late), the user number, user name, and time
and date.
ZONE
NO YES Zone Reports
Prints changes in the active zones status. Includes the zone number, name, and type
as well as the action (alarm, trouble, bypass, etc.) user number (if applicable) and
area name. When the Walk Test or Panic Zone Test is performed, Verify and Fail
messages also print for each zone.
16.4
USR CMDS NO YES User Command Reports
Prints user code changes, outputs turned ON or OFF (if operated by a schedule, SCH
is shown in Display Events in place of the user number), schedule changes, and User
Menu functions.
16.5
16.6
DOOR ACS NO YES Door Access Reports
Prints door access activity. Includes the door number, first and second user number,
first and second user name, and the time and date of the door access.
SUPV MSG NO YES Supervisory Reports
Prints System Monitor Troubles and system events. See Status List - System Monitor
Troubles.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
41
PC log rePorTS
PC Log Reports
17.1
PC LOG REPORTS PC Log Reports
This section allows you to program the types of PC Log Reports the panel sends
through the 462N Network Interface Card or through the J21 Serial Connector
directly on the XR500 Series Canadian panel. The reports include information such
as the type of activity, time and date of the activity, and user name and number.
These data reports can be accessed from a PC using the Advanced Reporting Module.
See the Installation Guide (LT-0681CAN) for detailed J21 setup information or the
User’s Guide (LT-0683CAN) for more information.
Note: The network connection that sends PC Log Reports is not monitored for
network trouble. The PC Log Reports option should NOT replace the primary
communication method or act as a backup communication method.
If there is trouble with the network connection, the panel continues to attempt to
send the PC Log Reports until the connection is reestablished. The panel then sends
the reports. A Network Trouble message is NOT sent if the connection is lost since
this report tool is not designed to be monitored by a receiver. The PC Log Reports
have the lowest priority of panel reports sent.
For information about the 462N card capabilities with PC Log Reports and Network
Communication method, see 462N Card Examples in the Appendix.
Note: The PC Log Address String entered CANNOT be the same as that entered in
Communication.
COMM TYPE: NONE
17.2
17.3
Communication Type
Select the Communication Type to send the PC Log Reports. Default is NONE.
NONE NET 232
Net IP Address
NET IP ADDRESS
This option displays when the Communication Type for PC Log Reports is NET. Enter
the IP address containing up to 16 characters. The Net IP Address must be unique and
cannot be duplicated on the network. Enter all 12 digits and leave out the periods.
For example, enter IP address 192.168.0.250 as 192168000250. The periods display
automatically.
NET PORT 2001
17.4
17.5
Net Port
This option displays when Communication Type for PC Log Reports is Net. Enter the
Port number. Valid numbers are from 0 to 65535. Default is 2001.
232 COMM PORT:
O
232 Communication Port
This option displays when Communication Type for PC Log Reports is 232. To enable
PC Log Reports, select either the on-board connector (O) or select A, B, C, D or E for
the corresponding slot in use on the DMP Model 462N Network Interface card. The
slots are labeled from left to right, beginning with A. Default is O.
Set the XR500 Series panel J23 jumper to R and briefly reset the panel using the J16
jumper to activate RS-232 operation.
17.6
17.7
17.8
232 SETUP:
232 Setup
This option displays when Communication Type for PC Log Reports is 232. Enter up
to 32 characters.
ARM/DIS NO YES Arm and Disarm Reports
Sends arming, disarming and Late to Close events. Includes the area number, name
and action, the user number and name, and the time and date.
ZONE
NO YES Zone Reports
Sends changes in the status of active zones. Includes the zone number, name, type,
the action (alarm, trouble, bypass, etc.), user number (if applicable), and area
name. For a Walk Test, Verify and Fail messages are sent for each zone.
17.9
USR CMDS NO YES User Command Reports
Sends user code changes, schedule changes, and door access denied events.
Digital Monitoring Products
42
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
PC log rePorTS
17.10 DOOR ACS NO YES Door Access Reports
Sends door access activity: door number, user number and name, and time and date.
17.11 SUPV MSG NO YES Supervisory Reports
Sends system monitor reports, such as AC and battery, and system event reports.
Supervisory Reports also sends the following reports:
• Abort
• Exit Error
• Ambush
• System Recently Armed
• *Late to Close
• Alarm Bell Silenced
• Unauthorized Entry
* Only sent as a Supervisory Report if Area Schedules is not enabled, Closing
Check is enabled, and an opening/closing schedule has been programmed.
Note: To send these reports to the PC Log, you must enable SUPV MSG.
17.12
PC Log Real-Time Status
Select YES to send Real-Time Status reports for zones, doors, and outputs. The
specific reports must also be selected by individual zone or output. The Real-Time
Status messages are sent to a PC running a graphic display software. Default is NO.
PC LOG REAL-TIME
STATUS NO YES
The messages that can be sent are:
•
•
•
•
•
•
•
•
Door Open with zone number
Door Closed with zone number
Door Open with door number
Door Closed with door number
Output On
Output Off
Output Pulse
Output Temporal
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
43
area informaTion
Area Information
18.1
AREA INFORMATION Area Information
Allows you to assign functions to the different areas in the system. All non-24-hour
zones must be assigned to an active area. See Zone Information.
You activate an area by assigning it a name. See Area Name. A name is given to
each active area in place of a number to assist the user during arming and disarming.
When only areas one to eight are used, the Armed Status display is 1 2 3 4 5 6 7 8.
When areas nine or higher are used the system Armed Status display reads ALL
SYSTEM ON or SYSTEM ON. Press the COMMAND key to display additional areas.
Refer to the Multiple Displays section at the beginning of this document and in the
XR500 User’s Guide (LT-0683CAN).
18.2
EXIT DELAY:
60 Exit Delay
Enter the exit delay time for all Exit type zones in this area. When the exit delay
time starts, all activity on that zone and other non-24-hour zone types in the area
is ignored until the exit delay expires. The keypad displays the Exit Delay time
countdown and annunciates the Exit Delay tone at 8 second intervals until the last
10 seconds when annunciation is at 3 second intervals.
The exit delay can be from 30 to 250 seconds. Default is 60 seconds.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay
timer restarts. This restart can occur only once. The Exit Delay restart is disabled
when programmed for High Line Security operation.
Exit Error Operation: At arming, when an entry/exit zone (EX) is faulted at the end
of the exit delay then one of two sequences occur:
For Entry Delay 1 EX type zones:
• the bell sounds for the length of time set in Bell Cutoff programming.
• the Entry Delay operation starts requiring code entry to disarm
• if not disarmed, a zone alarm and an exit error are sent to the receiver.
For Entry Delay 2-4 EX type zones:
• the zone is force armed and a zone force arm message is sent to the receiver
• an Exit Error is sent to the receiver
• the bell sounds for the length of time set in Bell Cutoff programming
18.3
18.4
BURG BELL OUT:
0
Burglary Bell Output
Enter the output number (0 to 6, 500 to 999, G1 to G20, or D1 to D16) that is turned
on any time a Burglary type zone is placed in alarm. The output is turned off when
you disarm any area and no other Burglary type zones are in alarm. The output can
also be turned off using the Alarm Silence option in the User Menu or by entering
a user code with the authority to silence alarms. The duration of this bell output
follows the time entered in the System Options>Bell Cutoff Time prompt. See the
Output Options - Bell Cutoff Time section. If Bell Test is selected YES, the Burglary
Bell Output entered here is turned on for two seconds each time the system is
armed.
Opening/Closing Reports
This option allows an Opening report to be sent to the receiver whenever any area is
disarmed. A Closing report is also sent to the receiver when any area is armed.
O/C RPTS NO YES
Digital Monitoring Products
XR500 Series Canadian Programming Guide
44
Download from Www.Somanuals.com. All Manuals Search And Download.
area informaTion
18.5
CLS CHK
NO YES Closing Check
Select YES to enable the panel to verify that all areas in the system are armed
after permanent or extended schedules expire. If the Closing Check finds any areas
disarmed past the scheduled time, the keypads selected to display System Trouble
Status displays CLOSING TIME! and emits a steady beep. When Area Schedules is set
to YES in Area Information, the specific area and name display followed by — LATE.
When Auto Arm is NO, if within ten minutes the system is not armed or if the
schedule is not extended, a Late to Close report is sent to the SCS-1R Receiver.
When Auto Arm is YES, the area arms. See Automatic Arming section.
If the area becomes disarmed outside of any schedule, the Closing Check sequence
occurs after the Late Arm Delay time. See Late Arm Delay.
When Closing Check is NO and Auto Arm is YES, the system immediately arms when
the schedule expires. No warning tone occurs.
In addition, when Closing Check is NO, the option to extend a schedule does not
display when the schedule expires.
18.6
18.7
CLS CODE NO YES Closing Code
When YES is selected, a code number is required for system arming. If NO is
selected, a code number is not required for system arming.
ANY BYPS NO YES Any Bypass
When YES is selected, zones can be bypassed without a code number during the
arming sequence. A code number is always required to use the Bypass Zones option
from the menu.
18.8
18.9
AREA SCH NO YES Area Schedules
Select YES to allow each area to set its own shift schedules 1 to 4. Enter NO to
provide one set of schedules for this system.
Note: Area Schedules are not designed to operate with All/Perimeter or Home/
Sleep/Away systems.
EARLY AMBUSH:
0
Early Morning Ambush (XR500N/XR500E only)
Enter the number of minutes (1 to 15) before a silent alarm (Early Morning Ambush S33)
is sent to the central station using the area 1 account number. Enter 0 (zero) to disable
this option.
When a user code is entered to disarm area 1 at a keypad or reader with Access
Areas assigned to area 1, the same or different user code must be entered within the
programmed number of minutes to prevent an ambush message from being sent to
the receiver. The second user code also must have authority to disarm area 1.
In addition, a zone activation with Alarm Action Message C also cancels the Early
Morning Ambush timer and stops an Ambush message from being sent to the receiver.
See Report to Transmit section in Zone Information.
The keypad does not display any indication that the ambush timer is running.
Indications can be provided by assigning an output number to Entry Out and Ambush
Out in Output Options. Entry Out turns on one minute before the timer expires and
turns off at expiration. Ambush Out turns on at the timers’ expiration and turns off
when Sensor reset is performed.
18.10
AREA NO: -
Area Number
Enter the number of the area to program. After entering the area number, press
COMMAND to enter the area name. Only Area systems allow the area name to be
changed.
Note: When All/Perimeter or Home/Sleep/Away is selected as the system type, the
Area Number does not display.
18.10.1
All/Perimeter Programming
When All/Perimeter is selected as the system type, program the Interior and
Perimeter areas as needed.
INT
PERIM
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
45
area informaTion
18.10.2
Home/Sleep/Away Programming
When Home/Sleep/Away is selected as the system type, program the Interior,
INT BDRM PERIM
* UNUSED *
Bedroom, and Perimeter areas as needed.
18.11
Area Name
The area name can be up to 32 alphanumeric characters. To add an area name to the
system, press any Select key and then enter up to 32 characters for the new area name.
Press COMMAND to continue. For instructions on entering alphanumeric characters see
section 1.7 Entering Alpha Characters. Inactive areas are marked * UNUSED *. Only
systems programmed for Area arming have the option available to change the area name.
To mark an active area unused, press any top row Select key to delete the old name,
then press the COMMAND key. The programmer automatically programs the name
as *UNUSED*. If you have already cleared Area Information during Initialization, all
areas are marked * UNUSED *. See Initialization section.
Home/Sleep/Away with Guest systems display the area name, but the names cannot
be changed. The following are the display names that appear on the keypad:
Area Display
Area Display
Area Display
1
2
3
Perimeter
4
5
6
Guest1 Perimeter
7
8
9
Guest2 Perimeter
Interior
Guest1 Interior
Guest2 Interior
Bedrooms
Guest1 Bedrooms
Guest2 Bedrooms
18.12 ACCOUNT NO: 12345 Account Number
Enter the account number to be sent to the receiver for this area. Choose an account
number compatible with the Communication Type selected in Communications. The
default Account Number is the one previously entered in Communications. This
account number is used when sending area messages and events to the central station
See the Area Account Number Messages in the Appendix.
.
18.13 AUTO ARM NO YES Automatic Arming
Select YES to allow this area to arm automatically according to permanent, temporary,
or extended schedules. If no schedules are programmed, the area auto arms every hour.
If closing check is selected as YES, the automatic arming function does not take
place until the expiration of a ten minute Closing Check delay. See Closing Check.
If the area has been disarmed outside of any permanent or temporary schedule, the
closing check sequence occurs one hour after the area is disarmed.
At arming, bad zones are handled according to the option selected in section Bad
Zones. If a closing report is sent, the user number is indicated as SCH on the SCS-1R
Receiver. NO disables automatic arming for this area.
18.14 BAD ZONES:
BYP Bad Zones
At the time of automatic arming, some zones in the area may not be in a normal
condition. This option allows you to program the panel response to these bad zones.
This option does not display if AUTO ARM is NO.
BYP - All bad zones are bypassed. A report of the bypass is sent to the receiver if
REF
BYP FORC
Bypass Reports is YES. The report indicates SCH as the user number.
FORC - All bad zones are force armed. Zones force armed in a bad condition are
capable of restoring and reporting an alarm if tripped. A forced zone report is
transmitted if Bypass Reports is YES. The report indicates SCH as the user number.
REF - The automatic arming is refused and no arming takes place. A No Closing
report is sent to the receiver regardless of the Closing Check selection.
18.15 AUTO DIS NO YES Automatic Disarming
NO disables automatic disarming by schedule for this area. When YES is selected,
the area automatically disarms according to permanent or temporary schedules. If
an opening report is sent to the receiver, the user number is indicated as SCH.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
46
Download from Www.Somanuals.com. All Manuals Search And Download.
area informaTion
18.16
Armed Output Number
ARMED OUTPUT:
0
0
Enter the output to turn on when this area is armed. If an exit delay is used for this
area, the Armed Output turns on at the start of the exit delay. The output is turned
off when this area is disarmed. The output cannot be turned on from the User Menu
Outputs On/Off option.
18.17 LATE OUTPUT:
Late Output Number
Enter the output to turn on when this area is not armed by its scheduled time and
Area Late or Closing Time displays at a keypad and the keypad buzzer is on. The
output is turned off when the keypad buzzer is silenced by pressing any key. Default
is 0 (zero).
18.18 LATE/ARM DLY: 60 Late Arm Delay
Enter 4 to 250 minutes to delay before automatic re-arming occurs after the area
becomes disarmed outside of schedules. See Closing Check. Default is 60 minutes.
Note: The Late Arm Delay can be superseded by the Re Arm Delay setting of the
User Profile assigned to the user who disarmed the area. Refer to the Re Arm Delay
section in the XR500 Series Canadian User’s Guide (LT-0683CAN).
18.19 BANK/SAF NO YES Bank Safe & Vault (XR500N/XR500E only)
NO disables the Bank Safe & Vault feature for this area. When selected as YES,
schedules set for this area and the time of day cannot be changed while the area is
armed.
Program schedules before arming: A Bank Safe & Vault area can only be disarmed
during scheduled times. If the area becomes armed before programming a schedule,
the panel must be reset before the area can be disarmed from a keypad or the Bank
Safe & Vault option in Area Information must be set to NO.
Zones assigned to Bank Safe & Vault areas cannot be bypassed or force armed. Do
not assign Bank Safe & Vault area to an Arming zone. Arming zones can disarm Bank
Safe & Vault areas outside of a schedule.
18.20 COMMON NO YES Common Area
Select YES to enable this area to operate as a common area. This area is armed
when the last area in the system is armed and is disarmed when the first area in the
system is disarmed. You can have multiple common areas in each system. For the
common area to work properly, do not assign the common area to any user code.
When a user code can arm and disarm the common area from a keypad at any time,
the common area does not function as a common area.
18.21 ARM FIRST NO YES Arm First Area
Select YES to enable this area to operate as an Arm First area. This area is
automatically armed when any non-Arm First area assigned to the same keypad is
armed but does not disarm when other areas become disarmed. Assign areas to
keypads using the Display Areas option in Device Setup programming. You can have
multiple Arm First areas in a system and divide them among keypads if needed. If
an Arm First area has faulted zones that cannot be bypassed, arming stops and the
areas are not armed. Correct the problem with the Arm First area and then begin
the arming process again. Default value is NO.
Note: The Arm First automatic arming only occurs when arming from a keypad.
Arming from a zone, schedule, or remotely is not affected and Arm First areas do not
automatically arm.
18.22 TWO MAN NO YES Two Man Rule (XR500N/XR500E only)
Select YES to require two user code entries to disarm and/or allow door access to
this area. When a user presents a code to a keypad or reader requesting a door
access or disarm, 2ND CODE displays and requires the entry of a different user code
with at least the same authority. The second user code must be entered within 30
seconds.
NO disables the Two Man Rule for this area.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
47
zone informaTion
Zone Information
19.1
ZONE INFORMATION Zone Information
Zone Information allows you to define the operation of each protection zone used in
the system. All protection zones, whether located on a command processor panel,
Security Command keypad, or zone expander are programmed the same way.
19.2
ZONE NO: -
Zone Number
Enter the number of the zone you intend to program. Available zone numbers are
shown in the table below. The keypad zone numbers begin with the keypad address
and are followed by the particular zone from that keypad. For example, a 7073 at
keypad address 7 would provide zones 71, 72, 73, and 74.
Press COMMAND to enter a zone name.
Address
Programming Zone Number
Panel
1-10
11-14
1
2
21-24
3
31-34
4
41-44
5
51-54
6
61-64
7
71-74
8
81-84
9
91-94
10
101-104
111-114
121-124
11
12
13
131-134
141-144
151-154
161-164
400-449
500-599
600-699
700-799
800-899
900-999
14
15
16
1100 Series Key Fob
LX-Bus 1 (A)
LX-Bus 2 (B)
LX-Bus 3 (C)
LX-Bus 4 (D)
LX-Bus 5 (E)
Note: For 1100 Series Key Fob zones (400-449), programming continues at the 1100
Series Key Fobs Section.
19.3
* UNUSED *
Zone Name
Zone names can have up to 32 alphanumeric characters. A name must be given to
each zone in the system. The name can display at the keypads during arming and
disarming so the user does not have to memorize zone numbers. Users can asso-
ciate a zone name with a particular protection point. A zone that is not part of the
system must be marked unused.
To add a zone name to the system, press any Select key and then enter up to 32
characters for the new zone name. Press COMMAND to continue.
To mark a zone unused, delete the old name by pressing a top row Select key, then
press the COMMAND key. The programmer automatically programs the name as
* UNUSED *. If you have already cleared Zone Information during Initialization, the
zones is marked * UNUSED *.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
48
Download from Www.Somanuals.com. All Manuals Search And Download.
zone informaTion
19.4
Zone Type
ZONE TYPE: BLANK
The Zone Type defines the panel response to the zone being opened or shorted.
This is called the Alarm Action. There are up to 13 possible alarm action responses
depending on the zone type and any restrictions it may have. See the Zone Type
chart in the Appendix.
When you assign a Zone Type to a zone, automatic zone responses are made. There
are 12 Zone Types to choose from. Application descriptions for each zone type can
be found in the Appendix of this manual.
To enter a new Zone Type, press any Select key. The display lists all of the available
Zone Types four at a time.
Blank, Night, Day, or Exit. Press COMMAND for additional zone types.
EX
- -
FI
NT DY
PN EM SV Fire, Panic, Emergency, or Supervisory. Press COMMAND for additional zone types.
A1
A2 FV AR Auxiliary 1, Auxiliary 2, Fire Verify, or Arming (keyswitch). Press COMMAND for
additional zone types.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone
Type, the zone must be assigned to an active area. If you select Fire, Fire Verify,
Panic, Emergency, or Supervisory as the Zone Type, it is a 24-hour zone that is always
armed and no area assignment is needed.
Zone Type Specifications
The panel contains 12 default zone types for use in configuring the system. These zone
types provide the most commonly selected functions for their applications. All zone
types except the Arming zone type can be customized by changing the options listed
below. Arming zone type programming continues at Arming Zone Area Assignment.
Refer to the Appendix for complete zone type descriptions.
19.5
Area Assignment
Enter the area number where the Night, Day, Exit, Auxiliary 1, or Auxiliary 2 zone
is being assigned. For an Area system, area numbers 1-32 can be assigned. For a
Home/Sleep/Away with Guest system, area numbers 1-9 can be assigned.
AREA NO: -
In an All/Perimeter or Home/Sleep/Away system, the currently selected area,
Perimeter, Interior, Bedroom displays.
AREA:
INT
PERIMETER
On an All/Perimeter system, select INT to program zones for the interior area and
select PERIM to program zones for the perimeter area.
PERIM
On a Home/Sleep/Away system, select INT to program zones for the interior area,
select BDRM to program zones for the bedroom area, and select PERIM to program
zones for the perimeter area.
INT BDRM PERIM
19.6
Fire Bell Output
This output (1 to 6, 500 to 999, G1 to G20, or D1 to D16) is turned on any time a
Fire, Fire Verify, or Supervisory zone is placed in alarm. The output is turned off by
any the following actions:
FIRE BELL OUT:
0
• When the User Menu Alarm Silence function is performed.
• When a valid user code is entered to silence the bell.
• When the Silence key is pressed on the 630F Remote Fire Command Center.
• Using the Outputs On/Off function in the User Menu.
• The expiration of the Bell Cutoff time.
This output can be connected to a lamp, LED, or buzzer using the DMP Model 716
Output Expansion Module.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
49
zone informaTion
19.7
Arming Zone Area Assignment
In an Area or Home/Sleep/Away with Guest system, if the zone has been
programmed as an Arming Type (AR), enter the areas that the zone controls.
ARM/DIS AREAS
When the zone changes from normal to shorted, the programmed areas toggle between
the armed or disarmed condition using the Style programming below. When restored to
normal, no action occurs. When the zone is opened from a normal (disarmed) state, a
trouble is reported. When opened from a shorted (armed) state, an alarm is reported
and the zone is disabled until you disarm the area(s) from either a keypad or Remote
Link™ computer.
To visually indicate the armed state of the area(s), you can assign an Armed Output
to individual areas and use remote LEDs at the keyswitch. The LED turns on or off to
indicate to the user the armed state of the area(s).
In an All/Perimeter or Home/Sleep/Away system, this option specifies the areas to
be armed by the Arming Type zone. For All/Perimeter systems, choose PERIM or ALL,
for Home/Sleep/Away or Home/Away systems, choose HOME, SLEEP, or AWAY.
ARM AREAS: PERIM
Perimeter/All - Specify whether the arming zone arms just the Perimeter (PERIM) or
the Perimeter and Interior areas (ALL) for All/Perimeter systems. When disarming,
all areas are disarmed.
PERIM
ALL
Home/Sleep/Away - Specify whether the arming zone arms the Perimeter (HOME),
the Perimeter and Interior (SLEEP), or all three areas (AWAY). When disarming, all
areas are disarmed.
HOME SLEEP AWAY
Arming Zone Operation
If any bad zones are present when the Arming zone is shorted, the LED delays
lighting for 5 seconds. If during the 5-second delay the Arming zone is shorted
again no arming takes place. If 5 seconds expire without the zone shorting again
or restoring to normal, the areas arm and bad zones are force armed. To allow bad
zones to be force armed, the Any Bypass option must be set to YES. If Any Bypass
option is set to NO, arming does not occur. See the Area Information - Any Bypass
section. A priority zone cannot be force armed.
19.8
Style
STYLE:
This option specifies the style for the arming/disarming operation. The default style
is TGL (toggle). Press any Select key to display the STYLE options. To view more
style options press the COMMAND key.
TGL ARM DIS STEP TGL (Toggle) - When the zone changes from normal to shorted, the programmed
areas toggle between the armed or disarmed condition. When restored to normal,
no action occurs. When the zone opens from a normal (disarmed) state, a trouble is
reported. When opened from a shorted (armed) state, an alarm is reported and the
zone is disabled until you disarm the area(s) from either a keypad or Remote Link.
ARM - When the zone is shorted, the programmed areas are armed. When restored to
normal, no action occurs. When the zone is opened from a normal (disarmed) state, a
trouble is reported. When opened from a shorted (armed) state, an alarm is reported.
DIS (Disarm) - When programmed, a short disarms the programmed areas. When
restored to normal, no action occurs. When the zone is opened from a normal
(disarmed) state, a trouble is reported.
STEP - A short arms the areas and beeps the keypads once. A normal condition
causes no action. An open condition disarms the programmed areas and beep the
keypads for one second.
Note: This arming style is designed for wireless arming pendants. When using an
arming/disarming keyswitch locate the keyswitch within the protected area.
MNT
MNT (Maintain) - When the zone is shorted, the programmed areas are armed.
When restored to normal, the programmed areas are disarmed and any alarm bells
are silenced. When the zone is opened from a normal (disarmed) state, a trouble
is reported. If opened from a shorted (armed) state, an alarm is reported and the
zone is disabled until you disarm the area(s) from either a keypad or Remote Link.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
50
Download from Www.Somanuals.com. All Manuals Search And Download.
zone informaTion
19.9
NEXT ZN? NO YES Next Zone
Select YES to terminate zone programming. The display returns to Zone Number,
allowing you to enter a new zone number. Select NO to make alterations to the
Alarm Action for a zone. Alarm Action is defined beginning with section 16.12.
To program zones for wireless operation, select NO at the NEXT ZONE - NO YES
option. The WIRELESS NO YES option displays. If the zone you are programming
is intended for wireless devices, select YES. Select NO to continue programming
non-wireless zones in the 500 to 999 range.
• Zones 400 to 449 can be programmed for 1100 Series Key Fobs.
• Zones 500 to 699 can be programmed for FA Series Wireless.
• Zones 500 through 999 can be programmed for DMP 1100 Series Wireless.
DMP Wireless
For a DMP 1100X Wireless Receiver set the House Code from 1 to 50. See House Code programming
in System Options. Zones 500 through 999 can be programmed as Wireless zones. Set the XR500 Series
Canadian panel J23 jumper to X to enable on-board DMP Wireless operation. Briefly reset the panel using
the J16 jumper to activate Wireless operation. Refer to the XR500 Series Canadian Installation Guide
(LT-0681).
For an 1100 Series Key Fob see section 19.11.
For an FA Series Remote Wireless Receiver see section 19.12.
NOTE: All wireless programming is stored in the XR500 Series Canadian panel. The 1100X Wireless
Receiver obtains the necessary programming information from the panel each time the receiver powers
up, when the programmer STOP routine is selected or the panel is reset. The receiver memory refresh
takes up to 10 seconds to complete depending on the number of wireless zones programmed and the Red
LED remains on during this time. Normal receiver operation is inhibited during the memory refresh period.
ZONE INFORMATION
WIRELESS? NO YES
19.10
Wireless
Select YES to program this zone as a DMP wireless zone. You must program
the wireless House Code prior to adding DMP wireless zones to the system. See
House Code programming in System Options. Default is NO.
19.10.1
Serial Number Entry
TRANSMITTER
SERIAL#: XXXXXXXX Enter the eight-digit serial number found on the wireless device.
This message displays when the serial number is already programmed for
another zone. The programmed zone number displays.
ALREADY IN USE
ZONE NUMBER: XXX
19.10.2
Contact
TRANSMITTER
CONTACT:XXXXXXXX
This option displays if the serial number entered is for an 1101 or 1103 Universal
Transmitter or 1114 Wireless Four-Zone Expander. Press any top row key to
select the contact.
This option displays when programming an 1101 or 1103 Transmitter. Select INT
to use the internal reed switch contacts. Select EXT to connect an external
device to the 1101 or 1103 terminal block. Default is INTERNAL.
TRANSMTR CONTACT
INT EXT
By allowing both of the Model 1101 or 1103 transmitter contacts (INT and
EXT) to be used at the same time, two zones may be programmed from
one transmitter. When using both contacts, you must use consecutive zone
numbers. Zones 531 and 532 or zones 890 and 891 are acceptable zone
assignments.
For example, program transmitter serial number 01345678 as Zone 521 with
an INT contact type and Zone 522 with an EXT contact type. The same serial
number is used for both zones.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
51
zone informaTion
This option displays when programming the 1114 Wireless Four-Zone Expander
TRANSMTR CONTACT
with four input contacts. The same serial number is used for all four contacts.
Select the contact number to program. When using the contacts, you must use
consecutive zone numbers. Default is Contact 1.
1
2
3
4
For example, use serial number 08345678 to program Contact 1 for Zone 561,
Contact 2 for Zone 562, Contact 3 for zone 563, and Contact 4 for zone 564.
A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.
This message displays when the Contact is already programmed for another
zone. The programmed zone number displays.
ALREADY IN USE
ZONE NUMBER: XXX
This option only displays when EXT is selected as the Contact type. For external
devices connected to the 1101 or 1103 terminal block, select NO to use normally
closed (N/C) contacts. Select YES to use normally open (N/O) contacts. Default
is NO.
ZONE INFORMATION
NORM OPN NO YES
19.10.3
Supervision Time
Press any top row key to select the supervision time required for the wireless
zone. Press COMMAND to accept the default time. Default is 240 minutes.
TRANSMITTER
SUPRVSN TIME: 240
Note: Refer to the Wireless Check-in and Supervision Time Definitions section
of the Appendix for supervision information.
Press the Select key under the required number of minutes. The transmitter
must check in at least once during this time or a missing condition is indicated
for that zone. 1100 Series transmitters automatically checkin based on the
supervision time selected for the wireless zone, no additional programming
is needed. If two zones share the same transmitter, the last programmed
supervision time is stored as the supervision time for both zones. Zero (0)
indicates an unsupervised transmitter.
SELECT MINUTES:
0
3
60
240
Note: When the panel is reset or a receiver is installed or powered down and
powered up, the supervision timer restarts for all wireless zones.
19.10.4
19.10.5
LED Operation
LED OPERATION
NO YES
Select YES to turn on an 1142 Hold-up transmitter LED during Panic or
Emergency operation. Select NO to turn the LED off during Panic or Emergency
operation. The LED always operates when the transmitter case is open and the
tamper is faulted. Default is YES.
Disarm/Disable
DISARM DISABLE
NO YES
Select YES to disable the zone tripped message (short) to the 1100X Series
Receiver from the 1126 PIR transmitter during the disarmed period. When
disabled, the 1126 only sends supervision, tamper and low battery messages
during the disarmed period to extend transmitter battery life. Select NO to
always send zone tripped messages in addition to supervision, tamper and low
battery. Default is YES.
19.10.6
19.10.7
PIR Pulse Count
WIRELESS PIR
Select the number of infrared pulses (2 or 4) the 1126 PIR should sense before
sending a short message to the 1100X Series Receiver. Default is 4.
PULSE COUNT: 4
PIR Sensitivity
Select the sensitivity setting for the 1126 PIR. Selecting LOW sets the 1126 to
operate at 75% sensitivity for installations in harsh environments. Selecting
HIGH sets the PIR to maximum sensitivity. Default is LOW.
WIRELESS PIR
SENSITIVITY:LOW
19.10.8
NEXT ZONE NO YES Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.
Digital Monitoring Products
52
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
zone informaTion
1100 Series Key Fobs
For an 1100 Series Key Fob set the House Code from 1 to 50. See House Code programming in System
Options. Only zones 400 to 449 can be programmed as 1100 Series Key Fob zones. Refer to the 1100
Series Key Fob Programming Sheet (LT-0706) supplied with the 1100X Wireless Receiver and the 1100 Series
Key Fob Install Guide (LT-0703) as needed.
To operate arming and disarming properly, the Key Fob should be assigned to a User Number with
appropriate area assignments, however, the User Number does not have to exist at the time the Key
Fob is programmed. The Key Fob User Number can be added later by the User.
The following programming continues from the Zone Number section when zone 400-449 is selected.
19.11.1
Key Fob User Number
Enter the User Number (1-9999) used to identify the key fob user and their
arming and disarming authority. Default is blank.
KEY FOB USER
NUMBER: XXXX
Displays when the User Number entered does not exist in User Code
programming. The key fob can be added, but the user must eventually be
added to cause the key fob to operate.
USER XXXX
NOT IN USE
19.11.2
19.11.3
Key Fob Serial Number
TRANSMITTER
SERIAL#: XXXXXXXX Enter the eight-digit serial number found on the wireless device.
Key Fob Supervision Time
Press any top row key to select the supervision time required for the key fob
zone. Press COMMAND to accept the default time. Default is 0 for key fobs.
TRANSMITTER
SUPRVSN TIME: 0
Press the Select key under the required number of minutes. The key fob must
check in at least once during this time or a missing condition is indicated for
that zone. 1100 Series key fobs automatically checkin based on the supervision
time selected for the wireless zone, no additional programming is needed.
Zero (0) indicates an unsupervised transmitter.
SELECT MINUTES:
0
3
60
240
Note: When the panel is reset or a receiver is installed or powered down and
powered up, the supervision timer restarts for all wireless zones.
19.11.4
19.11.5
Number of Key Fob Buttons
NO. OF KEY FOB
BUTTONS: X
Enter the number of buttons (1, 2, or 4) on the key fob being programmed.
Note: If the key fob is a one-button model, programming continues at the
Button Action section. Default button assignment for one-button key fobs is a
Panic Alarm (PN) with no output assigned.
Key Fob Button Selection (Four Buttons)
This prompt only displays if the key fob being programmed is a four-button
model. Press the Select key under the key fob button to program. The
following list identifies the default button assignments:
TOP Arming with no areas assigned
BUTTON:
TOP BTM LFT RGT
BTM Disarming with no areas assigned
LFT Panic Alarm (PN) with no output assigned
RGT Arming with Area 1 assigned
19.11.6
Key Fob Button Selection (Two Buttons)
This prompt only displays if the key fob being programmed is a two-button
model. Press the Select key under the key fob button to program. The
following list identifies the default button assignments:
TOP Arming with no areas assigned
BUTTON:
TOP BTM
BTM Disarming with no areas assigned
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
53
zone informaTion
19.11.7
Button Action
BUTTON ACTION
This option specifies the Button Action for an individual key fob button. The
default action for the button selected is displayed. Press any Select key to
display the Button Action options. To view more options press COMMAND.
yyy = the name of the button being programmed (TOP, BTM, LFT, RGT).
yyy:
XXXXXXXX
ARM (Arm) - Arms selected areas and force arms bad zones.
DIS (Disarm) - Disarms selected areas.
BUTTON ACTION
ARM DIS TGL STA
TGL (Toggle Arm) - Toggles arm/disarm for selected areas and force arms bad
zones when arming.
STA (Status) - Causes the key fob LED to indicate the arm/disarm status of the
system.
PN (Panic) - Triggers a Panic zone type alarm with no restoral.
BUTTON ACTION
PN PN2 EM EM2
PN2 (Panic 2) - Triggers a Panic zone type alarm with no restoral when pressed
simultaneously with any other Panic 2 button. No action occurs when pressed
alone.
EM (Emerg) - Triggers an Emergency zone type alarm with no restoral.
EM2 (Emerg 2) - Triggers an Emergency zone type alarm with no restoral when
pressed simultaneously with any other Emergency 2 button. No action occurs
when pressed alone.
OUT (Output) - Causes an output to turn on steady, pulse, momentary, toggle or
off.
BUTTON ACTION
OUT RST
UN
RST (Sensor Reset) - Causes the panel to perform a standard Sensor Reset.
UN (Unused) - The button is not used and performs no action.
19.11.8
Button Press Time
BUTTON
PRESS TIME: XXXXX
This option specifies the amount of time (SHORT or LONG) the user must press
the button before the key fob sends a message to the wireless receiver. The
default press time displays. Press any Select key to set the Button Press Time
for Arm, Disarm, Toggle, Status, Output, and Sensor Reset.
Note: The Button Press Time is not programmable on Panic (PN or PN2),
Emergency (EM or EM2) or Unused (UN) zones. For those zones the button press
time is always two (2) seconds.
SHORT - Press the button for one-half (1/2) second to send the message to the
wireless receiver.
PRESS TIME:
SHORT
LONG
LONG - Press the button for two (2) seconds to send the message to the wireless
receiver.
19.11.9
Arm/Disarm Area Selection
In an Area system or Home/Sleep/Away with Guest system, this specifies the
areas to be armed/disarmed by the Key Fob button being programmed. To
select an area between 1 and 32, enter the area number using the keypad digit
keys. Default is no areas enabled.
ARM/DIS AREAS:
In order to arm or disarm selected areas, the Profile assigned to the User
Number needs to have the same area numbers selected. Any area may be
selected at Arm/Disarm Areas but only matching area numbers are armed or
disarmed when the specific button is pressed. For example, in Areas selection,
areas 1, 3, and 7 are selected. In the User Profile Arm and Disarm Areas, areas
1, 2, 4, and 7 are selected. When the user presses the button to Arm or Disarm
area(s), only matching areas 1 and 7 Arm/Disarm.
Note: When more areas are selected at Arm/Disarm Areas than are authorized
in the User Profile, in the future the user can be given access authority to
additional areas through the User Profile without requiring additional panel
programming to select Arm/Disarm Areas. See User Profiles in the Appendix or
refer to the XR500 Series Canadian User’s Guide (LT-0683CAN).
Digital Monitoring Products
XR500 Series Canadian Programming Guide
54
Download from Www.Somanuals.com. All Manuals Search And Download.
zone informaTion
In an All/Perimeter or Home/Sleep/Away system, this specifies the area to be
armed by the Key Fob button being programmed. For All/Perimeter systems,
choose PERIM or ALL, for Home/Sleep/Away or Home/Away systems, choose
HOME, SLEEP, or AWAY.
ARM AREAS: PERIM
Note: Areas 3 and higher in an All/Perimeter system, and areas 4 and higher in a
Home/Sleep/Away system are not available for use.
After selecting the areas, for one-button key fobs the Zone No.: prompt
displays. For two-button or four-button key fobs, the Key Fob Button Selection
option displays to program additional buttons.
19.11.10 OUTPUT NO: XXX
Output Number
You can specify a relay output to operate when OUT (Output), PN (Panic), PN2
(Panic 2), EM (Emergency), or EM2 (Emergency 2) is selected for a key fob
Button Action and the button is pressed. Valid range is 1 to 6, 500 to 999,
D1 to D16, or G1 to G20. For an output turned on by a PN, PN2, EM, or EM2
button action, the output turns off when any area is disarmed.
To enter an output number, press a top row Select key followed by the output
number. Press the COMMAND key.
19.11.11
Output Action
OUTPUT ACTION:
yyy: XXXXXXXX
This option allows you to define the output action (STD, PLS, MOM, TGL, OFF)
for the selected output number. The default is Steady.
yyy = the name of the button being programmed (TOP, BTM, LFT, RGT).
xxxxxxxx = the currently defined output action.
STD (Steady) - The output is turned on and remains on.
OUTPUT ACTION?
STD PLS MOM TGL
PLS (Pulse) - The output alternates one second on and one second off.
The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
Note: Pulse is not available for key fob button output programmed D1 to D16 or
G1 to G20.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the on state and off state. Each
button press toggles the output state.
Note: Toggle is not available for key fob button output programmed G1 to G20.
OFF (Off) - The output is turned off. If programmed, the output was turned
on by some other means such as another button press, a zone action, or a
schedule.
OUTPUT ACTION?
OFF
Note: When the output is assigned to PN/PN2 or EM/EM2 button action and is
turned on, the output turns off when any area is disarmed.
When the output action is steady, pulse or toggle and the output is turned on,
the output remains on until:
— the output cutoff time expires
— the output is reset from the keypad menu
— toggled off
19.11.12 NEXT ZONE NO YES Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.
Note: All wireless programming is stored in the XR500 Series Canadian panel. The 1100X Wireless
Receiver obtains the necessary programming information from the panel each time the receiver powers
up, when the programmer STOP routine is selected or the panel is reset. The receiver memory refresh
takes up to 10 seconds to complete depending on the number of wireless zones programmed and the Red
LED remains on during this time. Normal receiver operation is inhibited during the memory refresh period.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
55
zone informaTion
FA Series Wireless
For an FA Series Remote Wireless Receiver set the House Code to 99. See House Code programming in
System Options. Only zones 500 to 699 can be programmed as FA Series Wireless zones for maximum of
200 Wireless Zones.
For a DMP 1100X Wireless Receiver see section 16.10.
19.12
Wireless
ZONE INFORMATION
WIRELESS? NO YES
Select YES to program a wireless zone connected to an FA Series FA400-DMP Remote
Wireless Receiver. Press the COMMAND key to continue with wireless programming.
19.12.1 CHECK IN TM:
60 Check-in Time
You can set wireless transmitters to check in automatically every 10, 30, or 60
seconds or not at all. To change the 60 second default, press any top row Select
key to display NONE 10 30 60. Select the check-in time you want for this zone.
Note: Refer to the Wireless Check-in and Supervision Time Definitions section of
the Appendix for supervision information.
19.12.2 INT CONT NO YES Internal Contact
Select YES to use an internal contact on the wireless transmitter. Select NO
to use an external contact. When you select NO, the following two prompts
display.
19.12.3 EOL
NO YES End-of-Line
Select YES to supervise an external contact connected to the wireless
transmitter. At the contact, install a 2.2k Ohm End-of-Line resistor in parallel
for Normally Open contacts and in series for Normally Closed contacts.
19.12.4 NRM OPEN NO YES Normally Open
Select NO if the contact connected to the wireless transmitter is Normally
Closed.
19.12.5
NEXT ZONE NO YES Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.
19.13 ALARM ACTION . . . . Alarm Action
This option allows you to change any Zone Type standard definitions. When the Zone
Type is specified, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a
non-24-hour zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that is
always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone initiates an alarm, the panel performs a Sensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the
reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is
repeated and a zone fault report is sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.
19.14 DISARMED OPEN
Disarmed Open
Defines the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to define: Report to transmit, Relay Output to
activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press COMMAND to continue.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
56
Download from Www.Somanuals.com. All Manuals Search And Download.
zone informaTion
19.15
Report to Transmit
TROUBLE
MSG:
A
Press any Select key to display the following report options: A, T, L, S, C, and - (dash).
T
L
-
ALARM - Select A to send an alarm report to the receiver and activate the bell
output according to zone type. The zone name appears in the panel alarmed zones
and status lists.
TROUBLE - Select T to send a trouble report to the receiver. The zone name
appears in the panel alarmed zones and status lists.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell
output activates and the zone name appears in the panel alarmed zones and status
lists.
- (Dash) - When you select a – (dash), reports are NOT sent to the receiver. The bell
output does not activate and there is no display in the panel alarmed zones or status
list. Only the relay output selected in the next section operates.
D
S
C
DOOR PROPPED - Selecting D allows the following operation: The time programmed
into ENTRY DLY 4 in the System Option section begins to count without displaying
on keypad. If the time expires and the zone has not returned to normal, the keypad
trouble buzzer starts and CLOSE THE DOOR appears on the keypads programmed into
the PREWARN ADDRESS section. The time programmed into ENTRY DLY 4 begins to
count down again internally. If the time expires a second time and the zone has not
returned to normal, a fault report is sent to the receiver and the zone name - OPEN
message displays on the keypads until a code is entered. The bell output does not
activate for the Door Propped operation.
SILENCE/RESET - Select S when the zone (not FI, SV, or FV) is connected to a DMP
Model 303 Silence/Reset switch, the zone can be used to silence the alarm bell and
perform a sensor reset without using a keypad. A report is NOT sent to the receiver
except for the bell silence report.
CANCEL AMBUSH - Select C for the zone to cancel the Early Morning Ambush timer
and stop an Ambush message from being sent to the receiver. Faulting the zone
takes the place of a second user code being entered at the keypad and is only
available for non-fire type zones. Area assignment for the zone does not affect this
option. See Early Morning Ambush in Area Information programming.
19.16 OUTPUT NO:
0
Output Number
You can specify any of the Relay Outputs on the XR500 Series panel to be activated
by a zone condition (1 to 6, 500 to 999 if Model 716 used, D1 to D16, G1 to G20).
The output can be activated regardless of the report to transmit or whether or not
the zone is programmed as local. An output activated by an armed zone is turned
off when the zone area is disarmed by a user.
To enter an output number, press a top row Select key followed by the output
number. Press the COMMAND key.
19.17 OUTPUT:
NONE Output Action
Entering an Output Number displays this prompt. This prompt allows you to assign
an output action to the relay: Steady, Pulse, Momentary, or Follow.
Note: Some wireless devices whether powered using an AC adaptor or a battery,
ignore some output action programming.
STD PLS MOM FOLW STEADY - The output is turned on and remains on until the area is disarmed, an
output cutoff time expires, or the output is reset from the keypad menu.
PULSE - The output alternates one second on and one second off.
Note: The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off
normal, or bad condition. When the zone restores, the output is turned off.
After you make the three selections in the sections above, the display prompts you for the same three
selections for Disarmed Short, Armed Open, and Armed Short conditions. If the zone is a 24-hour type,
only the Armed Open and Armed Short conditions display. When you have programmed all of the zone
conditions, the Swinger Bypass selection then displays.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
57
zone informaTion
19.18
Swinger Bypass
SWGR BYP NO YES
Selecting YES allows the zone to be swinger bypassed by the panel according to the
specifications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The
Bypass condition displays in the keypad Status List. Selecting NO disables swinger
bypassing for this zone.
How it works
If within one hour, a zone trips the total number of times as specified in Swinger
Bypass Trips, the panel bypasses it until the following conditions occur; the area
in which the zone is assigned is disarmed, the zone is manually reset through the
Bypass Zones? keypad User Menu function, the zone remains normal for one hour and
the Reset Swinger Bypass is YES.
If the zone trips fewer than the specified times within one hour, the bypass trip
counter returns to 0 (zero) and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
19.19 PREWARN KEYPADS: Prewarn Keypad Addresses
At the entry delay start, all keypad addresses selected here display ENTER CODE:-.
If you want the prewarn to sound at all 16 addresses, leave the default setting.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row Select key to clear the addresses shown.
Press the COMMAND key when the address selection is complete.
The prewarn tone stops at the keypad where the first user code digit is entered. If
no keys are pressed for five seconds or an invalid user code is entered, the prewarn
tone resumes at that keypad.
19.20 ENTRY DELAY:
1
Entry Delay
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System
Options.
19.21 RETARD
NO YES Zone Retard Delay
When you select YES, the zone operates with the zone retard delay. The retard
functions only in zone short conditions.
The zone must remain shorted for the full length of the retard delay before the
panel recognizes its condition. If you select NO, the zone operates without a retard
delay.
19.22 PRESGNL KEYPADS: Presignal Keypad Addresses
You can enable any combination of keypad addresses to sound a presignal tone
during the time a zone is in retard delay. The presignal tone silences when the zone
restores or the retard delay expires.
To enable a presignal address, press any top row Select key followed by the number
of the keypad address. You can enable the presignal for all 16 keypad addresses.
To disable a presignal address press the matching number digit again. Press the
COMMAND key when the address selection is complete. The Presignal prompt is only
displayed when Retard is selected as YES.
19.23 FAST RSP NO YES Fast Response
Select YES to provide a zone response time of 167ms. Select NO to provide a normal
zone response time of 500ms. Zones 500 to 999 have a fixed response time and do
not display this prompt.
19.24
Cross Zone
CRS ZONE NO YES
Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed
zones to fault within a programmed time before an alarm report is sent to the receiver.
When the first cross zoned zone trips, the cross zone time specified in System
Options begins to count down. When a second cross zoned zone trips or the first
zone trips a second time before the end of the count down, the bell action assigned
to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel
sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning
for Fire verify zones or for any Fire zones that have Retard Delay enabled.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
58
Download from Www.Somanuals.com. All Manuals Search And Download.
zone informaTion
19.25 PRIORITY NO YES Priority
Select YES to provide additional protection for the premises by requiring this zone to
be in a normal condition before its assigned area can be armed.
19.26
Fire Panel Slave Input
FIRE PANEL SLAVE
This option is available on Fire Zones (FI) only and allows a fire zone the ability to
provide slave communication operation for a separate fire alarm control panel. If
YES, this zone will transmit a restoral immediately when restored by the fire panel
being monitored. A sensor reset is not required to generate the restoral message.
If NO, this zone will operate as a standard fire type zone and a sensor reset is
required before the zone will return to normal. Default is NO.
INPUT:
NO YES
19.27
19.28
Area Follower
FOLLOW AREA:
0
Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit
or entry delay that is currently running in the area that is specified. Default is 0.
Zone Real-Time Status
Selecting YES allows Real-Time Status reports, such as Door Open or Closed with
zone number, to be sent using PC Log reporting. Selecting NO disables Real-Time
Status for this zone. Default is NO.
ZONE REAL-TIME
STATUS NO YES
19.28.1
Door Number
DOOR NUMBER: 0
If ZONE REAL-TIME STATUS is selected as YES, enter a door number (keypad bus
address) of 1-16. When a door number is selected, the door number is included
in the status report instead of the zone number. Enter 0 (zero) to disable this
feature and report the zone number. Default is 0 (no door).
19.29 ZONE AUDIT DAYS: Zone Audit Days
Enter the number of days (0 to 365) allowed to elapse without the zone being tripped
0
before a fault message is sent. The message is sent to the receiver(s) programmed
to receive Supervisory/Trouble Reports at 10:00 am following the expiration of the
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins
to countdown the number of days programmed. After the countdown expires, a fault
message is sent and the Zone Audit Days timer restarts and begins to countdown the
number of days programmed. Available for all zone types except fire and fire verify.
Enter 0 (zero) to disable this function. Default is 0 (zero).
19.30
Report with Account Number for Area
This option is only available for 24-hour zone types (Fire, Fire Verify, Panic,
Emergency, or Supervisory).
REPORT WITH ACCT
NO. FOR AREA:
0
Enter the area number (1-32) to assign as a 24-hour zone type. This option sends
the account number of the programmed area with messages. If the entered area
number does not exist or is not valid, the account number programmed in the
Communication section is sent. Select 0 (zero) to have the report sent with the
account number programmed in Communication. Default is 0
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
59
SToP
Stop
20.1
STOP
Stop
Save Programming
WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN
AND ‘SAVING PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE
PROGRAMMING CHANGES.
At the STOP prompt, pressing any Select key allows you to exit the Programmer
function of the panel. When selected, the panel performs an internal reset and
exits the programmer.
The STOP routine causes the following conditions to occur:
• All 1100 Series DMP Wireless transmitters are reset to NORMAL
• The panel Status List is cleared
During the reset, all keypad displays are momentarily blank for two seconds. After
the reset, the programming function terminates and the keypads return to the status
list display.
The STOP prompt does not disarm the system. Any new areas or zones that were
added during programming are not armed until the system is disarmed and armed
again.
Missing LX-Bus™ Modules Displayed
The Programmer includes a feature following the STOP routine that displays the
name of any programmed LX-Bus module not currently connected to the panel. For
example, if you had enabled any LX-Bus options and not yet installed a 481 LX-Bus
Expansion Card, after the STOP routine the panel displays NO LXBUS CARD. This is a
helpful reminder to install the card. This feature can also be a troubleshooting tool
to indicate a problem if you installed the card and this message still displays. The
following list shows the different messages and their associated LX-Bus cards.
Keypad Display
NO LXBUS CARD
NO PRINTER CARD
NO HOST CARD
Missing Card
481 LX-Bus™ Expansion Card
462P Printer Interface Card
462N Network Interface Card
(with NETWORK communication selected)
The above messages clear automatically from the keypad after a few moments.
Power Up
When the XR500 Series Canadian panel is powered up after an AC power failure,
any zone transitions are not recognized for 120 seconds. Normal zone processing
resumes at the end of the 120 seconds.
Set Lockout Code
SeT loCkouT Code
21.1
SET LOCKOUT CODE Set Lockout Code
Pressing COMMAND at the STOP prompt displays SET LOCKOUT CODE. This allows
you to program a code that is then required to gain access to the panel internal
Programmer through the keypad. You can change this code at any time to any
combination of numbers from three to five digits long. You do not need to enter
leading zeros when using the lockout code. Initializing the panel does not clear a
Lockout Code. Lockout Codes can be changed through Remote Link.
Once you have changed the code, it is important to write it down somewhere and
store it in a safe place. Lost Lockout Codes require the panel to be sent back to
DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set Lockout
Code command.
Lockout Code restriction
Do not set a Lockout Code higher than 65535.
Digital Monitoring Products
XR500 Series Canadian Programming Guide
60
Download from Www.Somanuals.com. All Manuals Search And Download.
feaTure uPgrade
Feature Upgrade
22.1
FEATURE UPGRADE
Feature Upgrade
In the Programming Menu, pressing COMMAND at the SET LOCKOUT CODE prompt
displays FEATURE UPGRADE. This allows you to enable additional features in the
panel. Press any top row Select key to display the first available feature. ENABLED
or DISABLED displays indicating whether this feature is currently used in this panel.
Press the COMMAND key to display additional feature(s).
ENTER KEY
-
To enable a feature, press any top row Select key anywhere in the features list to
display the ENTER KEY prompt.
Enter the factory-supplied feature key for the specific panel and press the COMMAND
key. The feature specific to the key displays as ENABLED.
Note: XR500 Series version 106 or higher panels require a six (6) character feature
key. Version 105 panels require a 16-character feature key.
If the feature key entered is not accepted, the ENTER KEY prompt displays again.
Re-enter the feature key and press the COMMAND key.
ENCRYPTION
DISABLED
22.1.1
Encryption
Enable this feature to provide 128 bit AES data encryption. This feature upgrade
can only be enabled on an XR500N panel version 105 or higher. For installations
where an XR500 panel is installed, it is recommended the XR500 be replaced with an
XR500E panel.
To complete encryption installation, access System Status in the User Menu to verify
the encryption status (ON or OFF). If the status displays OFF, it indicates that the
Passphrase has not been entered and data transmissions are not encrypted. See
Network Options to set up a Passphrase.
ALL NO YES OPTN
DISABLED
22.1.2
22.1.3
All No Yes Option
This feature offers the ability to disable the ALL NO YES option at arming or
disarming. When this feature is enabled, the ALL NO YES option does not display
at any system keypad during arming or disarming. Each area assigned to the user
profile is chosen to be armed or disarmed independently.
SVC USER AUTH
DISABLED
Service User Authentication
This feature offers the ability to authenticate service personnel before allowing
access to panel programming or performing any user operations. When this feature
is enabled and a valid Service User code is entered for system operation or 6653 is
entered for programming, the Service Code entry option displays.
When the service person enters the Service Code, the panel authenticates the code
with the Service Code preprogrammed in the SCS-1R receiver, and access to panel
programming or the User Menu is granted. The Service Code can be used for system
operation for 30 minutes before authenticating again. If the code entered is not
validated, access to programming or the User Menu using the Service User code is
denied.
Note: The Service User code is user number zero (0) and can only be created in the
panel remotely. The SCS-1R receiver must have firmware version 902 or higher to
authenticate service personnel.
Purchasing Feature Upgrades
To purchase a feature upgrade, you may contact DMP Customer Service with the
feature you would like to enable and the panel serial number. The serial number(s)
should be sent in writing via e-mail or fax. A separate feature key is issued for each
panel. The feature key only enables the requested feature on the specified panel.
The panel serial number can be located several different ways:
• Printed on a label located on the right side of the XR500 PCB.
• Using panel diagnostics. See the Appendix.
• Using Remote Link™ (version 1.18 or greater). See the Remote Link User’s
Guide (LT-0565).
— Initial Panel Connection screen
— System Information screen.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
61
aPPendiX
Appendix
23.1 False Alarm Reduction
System Recently Armed report
The System Recently Armed report (S78) is sent to the receiver when a burglary zone goes into alarm
within two minutes of the system being armed.
23.2 Diagnostics function
The XR500 Series Canadian panel contains a Diagnostics function that allows you to test the communication
integrity of the LX-Bus™, identify individual zones, and also display the present electrical state of any
zone. The Diagnostics function also allows you to test the integrity of the cellular communication, cellular
signal, and email communication. To use Diagnostics, reset the panel, enter the Diagnostics code 2313
(DIAG), and press COMMAND.
Test LX-Bus
The first Diagnostic function you displayed is: TEST LX-BUS. This function allows you to test the ability
of the 481, 462N, 462P, 462FM, and 472 Interface Cards to communicate with zone and output expander
modules connected to their LX-Bus circuits.
To continue, press any top row Select key. The keypad displays LX-BUS:. Using the digit keys, enter the
LX-Bus number, 1 to 5, to test that LX-Bus circuit. The keypad now displays ADDRESS: - . Enter a 2-digit
LX-Bus device address and press COMMAND. When testing LX-Bus devices, enter only the addresses to
which the modules have been set.
Important Note: A device address is not the same as a zone number. If you are testing 714 or 715 Zone
Expander Modules, which each contain four zones, the device address is the first zone number. When the
panel polls a 714 on the LX-Bus, it recognizes it as a four zone device and does not poll the remaining
three zones. The 714 module internally polls the remaining zones and transmits any status changes to the
panel. This greatly reduces the amount of time it takes the panel to poll all LX-Bus devices.
The keypad next displays TESTING . . . STOP during the device testing. At any time, you can Select
STOP to end polling. The panel records the number of no responses from the device. If all polls are
received back by the panel correctly, the keypad displays 00000/65535 FAIL.
If one or more polling attempts fail, the keypad displays * * * * */65535 FAIL with the * representing the
number of failed polling attempts. A display of 65535/65535 FAIL indicates a problem with the interface
card or its LX-Bus wiring such as a bad or broken wire, harness not properly connected, or excessive noise
or distance. It can also mean that a zone number was entered that did not match a device address. Press
the Back Arrow key to enter a new device address or press COMMAND to exit the TEST LX-BUS.
Zone Finder
The second Diagnostic function is the Zone Finder. Press COMMAND to display ZONE FINDER. This function
allows you to identify individual zones on devices connected to the LX-Bus of an interface card, the panel,
or any zones on the keypad data bus. To use ZONE FINDER, press any top row Select key. The display
changes to FAULT ZONE. The next zone on the system that changes from a normal to an open or shorted
state is displayed as ZONE NO: * * *. To continue, press the Back Arrow key.
Zone State
Press the COMMAND to display the third Diagnostic function: ZONE STATE. This function allows you to
enter any zone number and check its current electrical state (Normal, Open, or Shorted). Press any Select
key. The display changes to ZONE NUMBER: _ . Enter in the zone number you want to check and press
COMMAND. The panel displays the current state of the zone as NRML (normal), OPEN, or SHORT.
LX-Bus Status
The fourth Diagnostic function is the LX-BUS STATUS. This function allows the panel to poll all devices
connected to the LX-Bus of an interface card and check for any Overlapped, Missing, or Extra addresses.
Below is a description of each status item:
Overlap - An overlap occurs when one device address is the same as any of the last three zones on another
714 or 715. The overlap feature cannot determine when two devices have the same address.
Example: Model 714 Address 00 = Zones 500 501 502 503, and the Model 711 Address 02 = Zone 502.
Zone 502 would report as an Overlap because both the 714 and 711 have devices set to 502.
Missing - A missing occurs when a zone between 500 and 999 has been programmed in ZONE INFORMATION
and no device with that zone address has been installed on the LX-Bus. To correct the problem, check
your zone programming and zone expansion module addressing.
Extra - A device is installed on the LX-Bus but none of its zones are programmed into the system.
Digital Monitoring Products
62
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
aPPendiX
MAC Address
Short for Media Access Control address. This hardware address uniquely identifies each network node. Not
to be confused with an IP address, which is assignable. In the Diagnostics function, the MAC address is the
panel on-board network hardware address. Press any top row Select key to display the panel MAC address.
Press the COMMAND key to view the next prompt.
Serial Number
This number is the network communicator serial number. Reference this number for communicator date-
of-manufacture, hardware version, etc. Press any top row Select key to display the Serial Number. Press
the COMMAND key to view the next prompt.
Current Flash
This option displays Flash 1 or Flash 2 indicating which physical flash chip the panel is currently using. Press any
top row Select key to display the current flash information. Press the COMMAND key to view the next prompt.
Communication Status
This option tests the individual components of cellular or network communication. The displayed results
are shown below.
Cellular Results:
Successful Display
MODEM OPERATING
TOWER DETECTED
SIM REGISTERED
APN ACCEPTED
Failure Display
NO MODEM FOUND
NO TOWER
NOT REGISTERED
APN ERROR
CELL COMM GOOD
NO ACK RECEIVED
Network Results:
Successful Display
LINK OK
Failure Display
LINK ERROR
DHCP OK
DHCP ERROR
NO GATEWAY
NO DESTINATION
GATEWAY FOUND
DEST FOUND
COMM PATH GOOD
NOT CONNECTED
NO ACK RECEIVED
Cellular Signal
This option provides a way to test the cellular signal strength. Press any top row Select key to test the cell
SIGNAL: XXXXXXX
signal. The display shows:
. The x’s represent the signal strength 0-7.
Email Status
The Email Status menu, located in Diagnostics, tests each component of the panel’s e-mail
communication. The test proceeds until the first component failure or until all components have been
tested with positive results. The test screen displays after each component and displays for two seconds
or until the CMD key has been pressed. The displayed results are shown below.
Email Results:
Successful Display
EMAIL ENABLED
LINK OK
Failure Display
Successful Display
FROM ADDR SENT
DEST ADDR SENT
DATA MODE SENT
MESSAGE SENT
Failure Display
EMAIL DISABLED
FROM ADDR FAILED
DEST ADDR FAILED
DATA MODE FAILED
MSG SEND FAILED
DISCONNECT FAIL
LINK ERROR
SMTP SERVER OK
DEST ADDRESS OK
CONNECTING
INVALID SERVER
DEST ADDR FAILED
CANNOT CONNECT
AUTH MODE FAILED
BAD PASSWORD (or USERNAME)
DISCONNECTED
EMAIL SUCCESS
AUTH MODE SENT
PASSWORD SENT
Exiting the Diagnostics program
To exit the Diagnostics function, press the COMMAND key until STOP displays. Press any Select key to exit
the diagnostics function. The keypad returns to the Status List display.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
63
aPPendiX
23.3 Using the 984 Command Function
This feature allows you to connect to a service receiver, is used primarily to bring a new account on-line
and upload panel programming completed in Remote Link™.
Note: When not in the Programming Menu, the function 984 + COMMAND can be entered at the keypad,
and a remote options menu appears. This menu contains the following options:
NUMBER: The panel allows you to enter into the keypad a phone number you want the panel to dial.
Enter any required prefixes and area codes. After completing panel programming in Remote Link, set a trap
to seize the panel when it calls. Traps are set by selecting Panel > Trap. Refer to the Remote Link User’s
Guide (LT-0565), or the Remote Link Help File.
Then, from the panel, enter 984 and press the COMMAND key, while the panel is in the Status List. The
keypad display changes to NBR TEST PICKUP. Press the Select key under NBR. Enter the phone number
for the service receiver connected to the Remote Link computer. Press each number key slowly and
deliberately. The panel dials each number as it is pressed. If you make a mistake, press the Back Arrow
key. The panel stops dialing and return to the Status List.
You can enter up to 32 characters for the phone number. Once you have entered 16 characters the LCD
display is full: Press the COMMAND key to enter the final 16 characters. To enter a # (pound sign) press the
‘0’ then the fourth (far right) Select key, and to enter an * (asterisk) press the third Select key. Program
a pause by entering the letter P. Program CID message communication by entering the letter T in the first
position. Cancel call waiting by entering *70P as the first characters. These characters are counted as
part of the allowable 32 characters. Press COMMAND after you enter the phone number.
The panel calls the receiver connected to Remote Link to download the new programming. Remote Link
then traps the panel.
Note: The panel makes ten attempts to reach the receiver. While attempting to contact the receiver, if
the panel needs to send an alarm report, the panel stops dialing and uses the phone line to send its report.
TEST: The panel allows you to perform a Communication Status Test on each component of the
panel’s cellular or network communication paths. While the Status List displays, enter 984 and press the
COMMAND key. The keypad display changes to NBR TEST PICKUP. Press the Select key under TEST to
allow the panel to perform a Communication Status Test. The display prompts the user for a user code to
be entered. The user code must have the authority to perform a System Test.
Upon entry of a Cell or Network path when prompted, the test runs and the results display on the keypad.
See Diagnostic Functions section for a description of the Communication Status results.
PICKUP: The panel picks up the phone line when Remote Link™ calls in. The phone must be ringing
before selecting PICKUP. After completing panel programming in Remote Link, connect to the panel by
selecting Panel > Connect. Refer to the Remote Link User’s Guide (LT-0565), or Help File for complete
information about connecting to panels.
While the panel displays in the status list and the telephone line at the panel rings, enter 984 and press
the COMMAND key. The keypad display changes to NBR TEST PICKUP. Press the Select key under PICKUP
to allow the panel to seize the line. The panel immediately seizes the phone line and sends a carrier
tone to the receiver. A verification process occurs and, if successful, the panel grants remote access to its
programming and Event Buffer.
After the panel has seized the line, send the file from Remote Link by selecting Panel > Send. Remote Link
then uploads the new programming into the panel. You may also Request Events by selecting Panel > Request
Events in Remote Link. The panel begins sending the first event or access that occurred on or after the start
date specified by Remote Link and finishes by sending the last event or access that occurred on or before the
end date specified by Remote Link. If necessary, a Request Events upload in progress can be cancelled.
Keypad Displays
When the PICKUP option is used, the keypad displays LINE SEIZED. This indicates that the panel has
seized the line and is executing its program. If the line cannot be accessed, or if the PICKUP option is
used before all connect attempts are made, the keypad displays SYSTEM BUSY.
Digital Monitoring Products
64
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
aPPendiX
23.4 Using the Walk Test
The XR500 Series Canadian panel provides a walk test feature that allows a single technician to test the
protection devices connected to zones on the system. Conduct the Walk Test within 30 minutes of resetting
the panel. The Walk Test automatically ends if no zones are tripped for 20 minutes. TEST IN PROGRESS
displays at all keypads programmed with the same Area Display features. When five minutes remain, TEST
END WARNING displays. The Walk Test only tests zones assigned to the areas programmed into the keypad
in Area Display. If any areas are armed the Walk Test does not start and SYSTEM ARMED displays.
WALK TEST
Walk Test
To conduct the Walk Test, reset the control panel by momentarily placing a jumper
on J16. From the keypad, enter the code 8144. The keypad displays WALK TEST
for four seconds. If the system is monitored and the communication type is DD or
NET, the system sends a System Test Begin report to the central station. After four
seconds, the keypad displays the zone type choices for testing.
Note: If ENHANCED ZONE TEST in System Options is set to YES, the Walk Test can
be limited to only operate during the Area 32, Shift 4 schedule if programmed. If no
schedule is entered, the walk test always operates.
BG
FI PN SV Zone Types
Select the zone type you want to test. An asterisk next to the zone type indicates
the zone type chosen for testing. Press the Select key again to deselect the zone
type. When you have selected all the zone types you want for testing, press the
COMMAND key to display the next Walk Test option. Pressing the Back Arrow key
exits the Walk Test.
Note: For the Wireless Check-in Test, make sure no zone types are selected and
press the COMMAND key. Pressing the Back Arrow key exits the Walk Test.
BG (Burglary zones) - Select BG to test burglary zones. Includes all NT, DY, EX, A1,
and A2 zones.
FI (Fire zones) - Select FI to test fire zones. Includes all FI and FV zones.
PN (Panic zones) - Select PN to test panic zones. Includes all PN and EM zones.
SV (Supervisory zones) - Select SV to test supervisory zones. Includes all SV zones.
Note: During the Walk Test, trip each zone device or button on the system for 1 to 2
seconds. You do NOT have to hold the zones for 2 seconds in normal mode for PN
type zones. You are only required to hold the panic during the Walk Test because
the zone takes additional time to report when the system is in test mode.
WLS PIR
WLS (Wireless Check-in Test) - Select WLS to automatically test wireless transmitter
communications. Includes all wireless devices except key fobs and transmitters
programmed for a supervision time of 0 (zero).
PIR (Wireless PIR Walk Test) - The PIR Walk Test allows the installer to verify the 1126
operation. When enabled, the 1126 LED flashes each time motion is detected for up to
30 minutes. This is a local test only and no messages are sent to the Central Station.
BELL NO YES PULS Bell Action
This option selects the bell output action when a zone under test faults. This option
allows the panel bell, and/or burglary bell, and/or fire bell to turn ON and then OFF
each time a zone is tripped (opened or shorted).
NO - Select NO for no bell output action during Walk Test.
YES - Select YES to turn on any bell output for 2 seconds during Walk Test.
PULS - Select PULS to turn on any bell output for 1/4 second during Walk Test. Any
LX-Bus device output turns on for 1.6 seconds due to the polling cycle.
TRIPS: XXX
END Trip Counter For Walk Test
Once in the Walk Test, walk around and trip each protective device. Continue
tripping devices until the entire system is tested.
With each zone trip during the Walk Test:
• Keypad display increments each time a selected zone is opened or shorted
• The keypad buzzes for two seconds
• The panel sounds the alarm bells as programmed in Bell Action
• Each time a FI, FV, or SV zone trips, a Sensor Reset occurs.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
65
aPPendiX
If ENHANCED ZONE TEST is selected as YES:
A Verify message is sent at the time the zone trip occurs instead of at the end of the
Walk Test. For FI, FV or SV zone types, the Verify message is sent at the initial trip.
For all other zone types, the Verify message is sent when the zone restores. This
allows the Central Station to count the number of devices per zone.
END - Select END to stop the Walk Test. When the Walk Test ends or a 20-minute
time-out expires, a final Sensor Reset occurs. The System Test End message is
sent to the receiver along with Verify and Fail messages for each zone under test.
Faulted zones then display on the keypad.
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a supervision
check-in message.
CKIN:XXX/ZZZ
END
• The number of zones that check in. (XXX in the example).
• The total number of wireless zones programmed for supervision that should
check in. (ZZZ in the example).
END - Select END to stop the Wireless Check-in Test. When the test ends or
a 20-minute time-out expires, normal wireless zone processing returns. If
all transmitters check-in, both numbers match within three (3) minutes. If a
transmitter has multiple zones (1101, 1114, etc.), all zones are included in the
counts. Failed wireless zones display on the keypad.
TEST END WARNING Test End Warning
When five minutes remain on the 20 minute Walk Test timer, the keypad displays
TEST END WARNING. If no additional test zone trips occur, the test ends and a final
Sensor Reset automatically occurs. The System Test End message is sent to the
receiver along with Verify and Fail messages for each zone under Walk test. Faulted
zones then display on the keypad.
Failed Zones Display
SOUTH LOBBY
ZONE: 10
-FAIL For each zone that did not trip (failed) at least once during the Walk Test, all
keypads with matching Area Display programming display the zone name and number
and buzz for one second. Any selected (*FI *PN *SV) 24-hour zone that is faulted at
the end of the Walk Test displays a trouble condition for that zone regardless of the
message programmed for the open or short condition of the zone and a zone trouble
is sent to the receiver. Press the COMMAND key to display the next failed zone.
Note: For the Wireless Check-in Test, failed wireless zones display only on the
keypad. Zone Verify/Fail reports are not sent to the central station receiver for the
wireless check-in test.
Local Printer for Walk Test
When the Walk Test is completed, a Verify or Fail message for each zone tested prints to the local printer.
The Walk Test messages printing is enabled through Printer Reports programming.
Note: If ENHANCED ZONE TEST is selected as YES, the Verify messages are printed at the time the zone
trip occurs and not printed at the test end.
23.5 Keypad Speaker Operation
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary,
Zone Monitor, and Prewarn events. The list below details the conditions under which the speaker is turned
on and off for each event.
Fire
On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence.
Burglary
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
Zone Monitor On - One time only when a monitored zone is tripped.
Off - After one tone.
Prewarn
On - During Entry Delay.
Off - When Entry Delay expires.
Digital Monitoring Products
66
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
aPPendiX
23.6 Cross Zoning
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to
allow an intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an
intruder to trip the devices and allow only a zone fault report be sent to the central station.
When a Cross Zoned zone trips a FAULT report is sent to the SCS-1R Receiver. When two Cross Zoned zones
trip within the Cross Zone Time, both zones send ALARM signals to the receiver. For example, if zones 1
and 2 are Cross Zoned zones, and only zone 1 trips, a FAULT report is sent to the receiver for zone 1. If
zone 1 trips and zone 2 trips within the Cross Zone Time, an ALARM report is sent to the receiver for zone
1 and zone 2.
Report Type
Immediately Delayed
23.7 Events Manager
Alarm
Trouble
Restore
Opening
Closing
Bypass
Reset
Supervisory
Add Codes
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
The Events Manager allows you to delay sending
certain reports to the central station receiver.
Reports can be kept in the panel memory until
overwritten by new activity or held until the
memory buffer reaches 50 events or 50 door access
granted events. When the buffer is full, the panel
automatically sends the stored reports to the
central station receiver. The table lists the panel
reports you can delay using the Events Manager
option.
Delete Codes
Change Codes
Permanent Schedule Change
Temporary Schedule Change
Door Access
23.8 User Profiles
A profile defines the authority of each user
code in the system. Profiles are programmed in
the Keypad User Menu. Several characteristics
associated with each User Profile define its
authority within the system. To effectively
Door Access Denied
Late to Close
Force Armed Zone
program an XR500 Series system, you must understand the interrelationship between profiles, devices,
output groups, and areas. Below is a brief explanation of the User Profile elements. For more information
about user profiles, refer to the User Profiles Record and the XR100/XR500 User’s Guide (LT-0683).
Note: Profiles cannot be changed via keypad in an All/Perimeter or Home/Sleep/Away system. Use the
default profiles 1 through 10.
Profile Number - Each profile may be assigned a unique number from 1 to 99.
Profile Name - Each profile may be assigned a 32-character name. The Profile Number is the default name.
Area Number - Each profile may be assigned specific areas of the system for arming and disarming.
When creating profiles 1 to 98, NO areas are assigned by default. The default for profile 99 is ALL areas
assigned. Profile 99 is preprogrammed in the system at the factory.
Access Area Number - Each profile may be assigned door access area assignments. Default for profile 1 to 98
is NO areas assigned. Default for profile 99 is ALL areas assigned. Profile 99 is preprogrammed at the factory.
Output Group Assignment - Each profile may be assigned an output group number from 1 to 10. Default
for profile 1 to 98 is NO output group assigned. Default for profile 99 is output group 10. Your system may
by programmed to turn on an output group at certain keypads when door access occurs.
User Menu Assignments - Each user profile may have any of the menus assigned to it as shown in the
following User Profile Record. The User Profile Record lists the user menu profile assignments and the
system functions users are allowed to access based on the profile numbers assigned to their codes.
Always make sure that at least one administrator in your system has a profile with all authorities and
areas.
23.9 User Profiles Record
This User Profiles Record can be used as a tool when programming Devices, Profiles, Areas, and Output
Groups. Because these programming options are interrelated, use this sheet to plan the system before you
begin the installation and programming process.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
67
aPPendiX
Profile
#
Arm/Disarm
Areas
Output
Access Areas Group
Profile Name
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
1 2 3 4 A
23.10 FA Series Transmitter Information
A House ID Number is like an address for FA Series wireless transmitters so they know with which panel
they should be communicating. The House ID Number is based on the last two digits of the panel primary
account number.
Be sure that the primary panel account number is programmed before programming any wireless
transmitters. Because the House ID is based on the account number, entering or changing the primary
account number after programming the transmitters requires you to reprogram all of the transmitters.
Cross Talk
If you have more than one account within a five-mile radius, there is a possibility that “cross talk” can
occur. “Cross talk” is when transmitters communicate with multiple panels when the transmitters have
the same House ID. If you have two panels within a five-mile radius that use wireless zones, be sure that
the last two digits of the account numbers are not the same.
For example, ABC Plumbing has a panel with an account number of 12345 that uses wireless zones. The
House ID for the wireless transmitters at ABC Plumbing is 45. Two blocks away, XYZ Printing has an
account number of 22345 and the panel also uses wireless zones. The House ID for the transmitters for
XYZ Printing is 45. Because the two accounts have the same last two digits in the account numbers, the
House ID is the same. Therefore, the wireless transmitters “cross talk” and report to both panels bearing
the same House ID.
To avoid “cross talking”, panels within a five-mile radius must not have the same two digits in the primary
account number. If a “cross talk” issue is already present, you must delete the wireless transmitter zones,
enter the proper account numbers, and then reprogram the wireless transmitters.
Digital Monitoring Products
68
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
aPPendiX
23.10.1Wireless Check-in and Supervision Definitions
FA Series Check-in Time Explained
The check-in time programmed for FA Series wireless transmitters is the number of seconds between
each message sent from the transmitter to the FA Series receiver for supervision purposes. This time is
programmable for each transmitter from 10, 30, or 60 seconds. Selecting 0 (zero) disables check-in. If no
messages are received from a transmitter in any four-hour period, a transmitter missing is generated by
the FA Series receiver and communicated to the panel.
DMP 1100 Series Supervision Time Explained
The supervision time programmed for DMP 1100 Series wireless is the number of minutes that must elapse
before a transmitter missing message is generated for a transmitter that is not sending its automatically
generated supervision message. The supervision time is programmable to 3, 60, 240 minutes. Selecting 0
(zero) disables supervision time.
23.11 Keypad Bus and LX-Bus Zone Type Descriptions
This section describes applications for the default Keypad and LX-Bus zone types in Zone Information
programming.
-- (Blank Zone)
Customizable zone type. By default, no actions are programmed to occur with Blank Zone. A zone name
must be entered to use this zone type: This zone type is not the same as an *UNUSED* zone.
NT (Night Zone)
Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs and
Glassbreak detectors.
DY (Day zone)
Used for emergency doors or fire doors to sound the keypad buzzer and display the zone name when the
zone is faulted. Day zones also send alarm reports to the receiver during the system armed periods.
EX (Exit zone)
Initiates the entry delay timer when its assigned area is fully armed. Also, can initiate an exit delay timer
to allow a user to exit an area after the arming process starts.
PN (Panic zone)
Used for connecting to mechanical devices that allow a user to signal an emergency alarm. Panic zones
can provide either a silent or audible alarm with or without reporting to a central station receiver.
EM (Emergency zone)
These are used for reporting medical or other non-panic emergencies to the central station receiver.
SV (Supervisory zone)
Used to provide 24-hour zone supervision to devices associated with fire systems. Typical applications are
tamper switches on Post Indicator Valves (PIVs), gate valves, and low and high temperature gauges.
FI (Fire zone)
Used for any type of powered or mechanical fire detection device. Typical applications are for smoke
detectors, sprinkler flowswitches, manual pull stations, and beam detectors. Retard, cross zoning, and
presignal options are available for the Fire zone type.
FV (Fire Verify zone)
Used primarily for smoke detector circuits to verify the existence of an actual fire condition. When a Fire
Verify zone initiates an alarm, the panel performs a Fire Reset. If any Fire Verify zone initiates an alarm
within 120 seconds after the reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the
cycle repeats.
A1 and A2 (Auxiliary 1 and Auxiliary 2)
These zones are similar to a Night zone and are typically used to protect restricted areas within a
protected premises.
AR (Arming zone)
This zone allows you to connect a keyswitch to a zone and use it to arm and disarm one or more areas.
23.12 Zone Type Specifications
The XR500 Series Canadian panel contains multiple default zone types for use in configuring the system.
These zone types provide the most commonly selected functions for their applications. All zone types
can be customized by changing the variable options listed below. The Keypad Bus Zone Information table
below reflects the zone types for Keypad Bus Zones. The XR500 Series LX-Bus Zone Information table on
the next page reflects the zone types for LX-Bus Zones.
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
69
aPPendiX
Keypad Bus Zone
Information
Type
Area Fire Disarmed Disarmed
Armed
Open
Armed
Short
Bell
Open
Short
Assign Disarm condition of
NT, DY, EX, A1, and A2 only
INT
PERIM
BDRM
or
-- NT
DY EX
FI PN
EM SV
A1 A2
FV AR
Assign Prewarn and Entry
Delay for EX only
Assign Retard and Presignal
for FI, SV, A1, and A2 only
TGL
ARM
DIS
STEP
MNT
A
T
L
S
P
M
F
A
T
L
S
P
M
F
A
T
L
S
P
M
F
A
T
L
S
P
M
F
N
1
1
N
1
N
N N
0
N
0
or to or or to or or or to or to
Zone Type Defaults
1
to
32
-
-
-
-
Y
16
4
Y
16
Y
Y
Y 16 Y 16
D
S
C
D
S
C
D
S
C
D
S
C
Night
Day
Exit
Fire
NT
DY
EX
FI
PN
EM
SV
A1
A2
FV
AR
-
T
-
0
0
0
S
S
S
-
T
-
0
0
0
S
S
S
A
A
A
T
T
T
T
T
T
T
0
0
0
0
0
0
0
0
0
0
S
S
S
S
S
S
S
S
S
S
A
A
A
A
A
A
A
A
A
A
0
0
0
0
0
0
0
0
0
0
S
S
S
S
S
S
S
S
S
S
Y
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N
0
0
N
N
N
0
0
0
1-16
1
0
0
0
N
+
Panic
Emergency
Supervisory
Auxiliary 1
Auxiliary 2
Fire Verify
Arming
N
N
N
+
+
+
T
T
0
0
S
S
A
A
0
0
S
S
0
0
N
N
0
0
TGL
*Output Options: 1 to 6, 450 to 474, 480 to 499, 500 to 999, D1 to D16, G1 to G20. + = Set retard to YES before selecting presignal.
= Zone functions not available.
23.12.1 Keypad Bus Zone Type Defaults
These are complete spellings of the abbreviations used for the zone types, such as Night and Exit.
Type - These are the abbreviations used for the zone types, such as NT and EX.
Area - For an Area or Home/Sleep/Away with Guest system this is 1 to 32. For an All/Perimeter or Home/
Sleep/Away system, this is the Interior, Bedroom, or Perimeter. Select the area for NT, DY, EX, A1, A2, and
AR types.
Fire Bell Out - Only available for FI, FV, and SV zones. Use any output zone number listed.
Message - A = alarm report, T = trouble report, L = local, no report, — (dash) = no report, D = door propped
(When SV zone is connected to 303 Silence/Reset Switch), S = sensor reset/alarm silence,
C = early morning ambush cancel.
Output - These are 1 to 6 on-board and 500 to 999 off-board relay outputs, 450 to 474 and 480 to 499
wireless outputs, D1 to D16, and G1 to G20.
Action - This selects the action of the output: S = steady, P = pulse, M = momentary, and F = follow
Swinger - The zone can be automatically shunted after a programmed number of trips.
Prewarn - This selects the keypad address that sounds the entry prewarn for this zone.
Entry Delay - This is the entry delay timer selected as the default for this zone.
Retard Delay - Provides a programmed retard time before an alarm initiates from a shorted zone. When
used on an arming zone, the retard delay occurs when the zone is shorted before the armed state has
changed. If the arming zone has Maintain as the Style, the retard delay also occurs when the zone returns
to a normal state.
Presignal - Provides a keypad tone for zones in retard delay. Retard must be YES before Presignal can be
selected.
Fast Response - Provides a 167ms zone response instead of the normal 500ms response.
Cross Zone - Provides cross zoning with any of the 574 zones.
Priority - Requires this zone to be in a normal condition before the area can be armed.
Style - The abbreviations for arming zone style:
TGL = Toggle, ARM = Arm only, DIS = Disarm only, STEP = Wireless arming, MNT = Maintain
Digital Monitoring Products
70
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
aPPendiX
S t y l e
23.12.2 LX-Bus Zone Type Defaults
These are complete spellings of the abbreviations used for the
D o o r N u m b e r
zone types, such as Night and Exit.
e R p o r t s i m e e R a l - T
A r e a l l o F w o
r i P o r i t y
Type - These are the abbreviations used for the zone types,
such as NT and EX.
Z o n e C r o s s
e s p o n s F e a s t R
r e P s i g n a l
Area - For an Area or Home/Sleep/Away with Guest system
this is 1 to 32. For an All/Perimeter or Home/Sleep/Away
system, this is the Interior, Bedroom, or Perimeter. Select the
area for NT, DY, EX, A1, A2, and AR types.
e R t a r d D e l a y
E n t r y D e l a y
r e P w a r n
Fire Bell Out - Only available for FI, FV, and SV zones. Use
any output zone number listed.
S w i n g e r
A c t i o n
Wireless - This indicates wireless equipment is being used.
DMP Wireless - These options are for use with the DMP 1100X
Wireless Receiver.
*
*
O u t p u t
M e s s a g e
A c t i o n
FA Series Wireless - These options are for use with the
FA400-DMP Remote Wireless Receiver.
O u t p u t
M e s s a g e
Message - A = alarm report, T = trouble report,
L = local, no report, — (dash) = no report,
A c t i o n
D = door propped (When SV zone is connected to 303 Silence/
Reset Switch), S = sensor reset/alarm silence, C = early
morning ambush cancel.
*
O u t p u t
M e s s a g e
A c t i o n
Output - These are 1 to 6 on-board and 500 to 999 off-board
relay outputs, 450 to 474 and 480 to 499 wireless outputs, D1
to D16, and G1 to G20.
*
O u t p u t
M e s s a g e
Action - This selects the action of the output:
S = steady, P = pulse, M = momentary, and F = follow
O p e n
N o r m a l l y
E n d - o f - L i n e
C o n I N t a T c t
Swinger - The zone can be automatically shunted after a
programmed number of trips.
i m T e
C h e c k - i n
Prewarn - This selects the keypad address that sounds the
entry prewarn for this zone.
S e n s i t 1 i 1 v i 2 t 6 y
C o u n t P u l s e 1 1 2 6
D i s a b l e
Entry Delay - This is the entry delay timer selected as the
default for this zone.
D i s a r m 1 1 / 2 6
O p e r a t i o n
L E D 1 1 4 2
S u p e r v i s i o n
Retard Delay - Provides a programmed retard time before an
alarm initiates from a shorted zone. When used on an arming
zone, the retard delay occurs when the zone is shorted before
the armed state has changed. If the arming zone has Maintain
as the Style, the retard delay also occurs when the zone
returns to a normal state.
i m T e
1 1 1 4 C o n t a c t
N / O ?
C o n t a c t
1 1 0 1 E X T
1 1 0 1 C o n t a c t
i r e W l e s s
Presignal - Provides a keypad tone for zones in retard delay.
Retard must be YES before Presignal can be selected.
*
O u t p u t
Fast Response - Provides a 167ms zone response instead of the
normal 500ms response.
Cross Zone - Provides cross zoning with any of the 574 zones.
Priority - Requires this zone to be in a normal condition
before the area can be armed.
Style - The abbreviations for arming zone style:
TGL = Toggle, ARM = Arm only, DIS = Disarm only,
STEP = Wireless arming, MNT = Maint
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
71
aPPendiX
23.13 Common Keypad Messages
There are several common keypad messages that the keypad displays to inform the technician and
end-user. The common messages are described below. Possible solutions are also provided.
Message
Meaning
Possible Solutions
Change the user access areas if access to
the area is needed. If access is not needed,
the user cannot enter the area.
The user has attempted a door access for an
area they are not assigned.
INVALID AREA
The user code you entered is not recognized
by the system.
A user attempted a function that is outside of
the assigned profile.
A user code assigned to a specific schedule has
entered outside of the valid schedule.
The area you are attempting to disarm or
access is a Two Man Area.
INVALID CODE
INVALID PROFILE
INVALID TIME
Check the user code and try again.
Check the user profile settings.
See Schedules and User Codes.
A second and different user code must be
entered.
ENTER 2ND CODE
Users still on the premise should arm the
system or extend the schedule to a later
time.
Users still on the premise should arm the
system or extend the schedule to a later
time.
The scheduled has expired but the area is not
armed.
CLOSING TIME
LATE TO CLOSE
The system was not armed at its scheduled
closing time.
The user must exit the area through the
proper door. If not possible, your system
administrator should select the Forgive
option in the User Codes menu.
Check that all AC connections are good.
Check that the battery connections are good
and the battery is still good.
A user assigned the anti-passback option has
attempted to re-enter an area from which they
did not exit properly.
FAILED TO EXIT
AC TROUBLE
The system is not getting proper power.
The battery is either low or missing.
BATTERY TROUBLE
PHONE LINE 1
TROUBLE
There is trouble with the phone line
supervision.
Plug in the phone line.
Make sure the J16 jumper is removed from
the panel. Make sure there is not a short or
open condition on the green data wire to the
keypad. You may also need to check that all
of the keypads and expansion modules on
the bus are good.
SYSTEM TROUBLE or There is a problem with one or more
SERVICE REqUIRED
components in the system.
Wait a few moments for the system to
complete the task. Make sure the J16
jumper is not on the panel. If the message
displays for a long period of time, the
processor could be locked up.
Program a device to be supervised.
Make sure all wires are connected.
Program one of the devices to a unique
address.
Verify your communication type, account
number, and phone number. Make sure the
telephone line is connected and working
properly.
The system is performing another task with a
higher priority.
SYSTEM BUSY
There is not a supervised device on the bus.
There is low voltage or an open yellow wire.
4-WIRE BUS TROUBLE
TRANSMIT FAIL
Two devices share the same address.
The panel has attempted to communicate
with the central station 10 times and has not
succeeded.
NON-POLLED
ADDRESS
ENTER CODE (to
enter Programming)
The device is not set to DOOR, KEYPAD or
FIRE in Device Setup during programming.
A lockout code has been programmed for the
panel.
Program the device as DOOR, KEYPAD or
FIRE in Device Setup.
Enter the lockout code.
The panel is unable to communicate with the
wireless receiver.
The wireless receiver is missing.
Verify the receiver is properly connected to
the panel. Verify the correct House Code is
programmed in System Options.
WIRELESS TROUBLE
Digital Monitoring Products
XR500 Series Canadian Programming Guide
72
Download from Www.Somanuals.com. All Manuals Search And Download.
aPPendiX
23.14 Area Account Number Messages
XR500 systems send an area account number instead of the system account number with the following
panel messages/events based on the area assigned to the zone that initiated the alarm:
•
•
•
•
•
•
WARNING: Alarm Bell Silenced (S34)
Abort Signal Received (S45)
Cancel Signal Received (S49)
ALERT: System Recently Armed (S78)
ALERT: Exit Error (S80)
ALARM: Verify Signal Received (S96) (not currently sent on area arming systems)
The XR500 has always sent the area account number for the following messages:
•
•
•
Zone event messages for all non-24 hour zones assigned to an area
Arming
Disarming
The XR500 sends the following messages using the area account number based on the lowest area number
in Display Areas programming from the keypad being used:
•
•
•
•
•
•
User Code Add/Change/Delete
Door Access/Denied
User 1 Ambush and Early Morning Ambush
System Test Begin/End
Unauthorized Entry
Service Code and Service Request
The XR500 sends the following messages using the area account number based on the area number:
Late to Arm for area schedules
•
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Monitoring Products
73
reviSionS
Revisions to This Document
This section explains the changes made to this document during this revision. It lists the version, identifies
the change(s) made, the related section number and heading, and a summary of the change.
Guide
Version Section Number and Heading
Quick Explanation of Changes
1.08
6.4 Access Areas
6.7 Strike Time
Added statement about door locking
Added device type information
6.8 Strike Delay
Added device type information
6.13 Door Real-Time Status
6.14 Send Door Forced Message
6.15 Program 734 Options
7 Remote Options
Added Door Real-Time Status prompt
Added Send Door Forced Message prompt
Added Program 734 Options prompts
Complete restructure and reorganization
Allow up to 16 characters
7.2 Remote Key
7.4 Allow Dialer Remote
7.5 Allow Network Remote
7.6 Allow Cellular Remote
7.7 Allow RS-232 Remote
7.8 Entré Connection
Added Allow Dialer Remote prompt
Added Allow Network remote prompts
Added Allow Cell Remote prompts
Added Allow RS-232 Remote prompt
Added Entré Connection prompts
19.30 Report with Acct Number for Area Added Report with Account Number for Area prompt
1.07
3.34 Send Path Information
5.4 Destination 1
Added Send Path Information section
Added TLS Encryption note
5.5 Destination 1 User Number
5.7 Destination 2 User Number
5.9 Destination 3 User Number
5.13 Monthly Limit
Added Destination 1 User Number section
Added Destination 2 User Number section
Added Destination 3 User Number section
Added Monthly Limit option
6.2 Device Number
Added new Device Types
6.3 Door Name
Added option of entering up to 32 characters
Added First/Second GPRS APN section
Added Send 16 Character Names option
Added option of entering up to 32 characters
Added option of entering up to 32 characters
Changed exit delay minimum from 45 to 30 seconds
Added option of entering up to 32 characters
Added option of entering up to 32 characters
Added Fire Panel Slave Input option
Added Zone Audit Days section
7.14 First/Second GPRS APN
9.23 Send 16 Character Names
12.3 Output Name
13.3 Group Name
18.2 Exit Delay
18.11 Area Name
19.3 Zone Name
19.26 Fire Panel Slave Input
19.29 Zone Audit Days
23.3 Using the 984 Command Function Changed Keypad to Test
23.8 User Profiles Added option of entering up to 32 characters
Digital Monitoring Products
74
XR500 Series Canadian Programming Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Listings and Approvals
This Class A digital apparatus complies with
Canadian ICES-003
NIST Validated XR500E Encrypted Command
Processor Panel Certificate #130
ANSI/SIA CP-01-2000 False Alarm Reduction
Underwriters Laboratories Canada (ULC) Listed
ULC S545
Household Fire
ULC Subject-C1023 Household Burglar
ULC/ORD-C1076
ULC S304-06
Proprietary Burglar
Central Station Burglar
800-641-4282
www.dmp.com
Made in the USA
INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
Download from Www.Somanuals.com. All Manuals Search And Download.
|