Contents
SECTION
PAGE
Notice to the Installer .................................................................................................. 4
INSTALLATION GUIDELINES ...................................................................................... 5
Codes ................................................................................................................. 5
Installation Location ............................................................................................ 5
Closet and Alcove Installation ............................................................................. 6
Standard Clearances .......................................................................................... 6
Air for Combustion and Ventilation ..................................................................... 7
Chimney Inspection ............................................................................................ 10
Flue / Chimney / Vent Connector ........................................................................ 10
Power (Side-Wall) Venting – Important Note Regarding ..................................... 11
Draft Regulator .................................................................................................... 11
Duct Work and Air Conditioning .......................................................................... 12
Air Filter Mounting ............................................................................................... 12
Electrical Connections ........................................................................................ 14
Room Thermostat ............................................................................................... 14
Combustion Chamber ......................................................................................... 15
Oil Burner and Oil Nozzle Installation .................................................................. 15
Fuel System Installation ....................................................................................... 18
Horizontal / Counterflow Furnace Setup ............................................................. 19
INITIAL OPERATION OF THE FURNACE .................................................................... 21
Initial Burner Operation ....................................................................................... 21
Supply/Return Airflow and Air Temperature ........................................................ 23
Furnace Limit and Blower Controls ..................................................................... 25
Room Thermostat ............................................................................................... 26
Instructions to Our Customer / End User ............................................................. 26
SERVICE ....................................................................................................................... 27
Troubleshooting .................................................................................................. 27
Flame Sensor (“Cad Cell”) Checkout Procedure ................................................ 31
Replacement Parts ............................................................................................. 32
MAINTENANCE ............................................................................................................. 33
Air Filter(s) ........................................................................................................... 33
Oil Burner ............................................................................................................ 33
Blower and Motor ................................................................................................ 33
Heat Exchanger .................................................................................................. 33
Flue and Chimney ............................................................................................... 35
USERS INFORMATION ................................................................................................. 36
Operating Instructions ........................................................................................ 36
Oil Supply ........................................................................................................... 37
Extended Shutdown ........................................................................................... 38
Combustion Air and Ventilation Supply ................................................................ 38
Inspection Areas ................................................................................................. 38
2
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A: SOURCES FOR REFERENCED STANDARDS ................................... 40
APPENDIX B: ELECTRICAL DIAGRAMS ..................................................................... 41
APPENDIX C: SPECIFICATION SHEETS .................................................................... 43
APPENDIX D: REPLACEMENT PARTS ....................................................................... 46
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Notice to the Installer
Installation of this oil-fired furnace must be performed by a qualified installer in accordance
with all local codes and authorities having jurisdiction. In the absence of local governing codes,
installation shall conform to these instructions and to the regulations of the National Fire
Protection Association’s Standard for the Installation of Oil-Burning Equipment, NFPA 31-
2001, and the National Electrical Code, ANSI/NFPA 70-2002, or the latest editions thereof.
A qualified installer, also referred to in this instruction manual as a “qualified heating
contractor”, is an individual, or agency, properly licensed and experienced to install and
service oil-burning equipment in accordance with all local codes and ordinances.
Material and Workmanship
This furnace was built with the highest quality materials and attention to workmanship.
However, omissions and defects occasionally occur. Before installing the furnace,
inspect the furnace thoroughly. If missing parts, defective material, or poor workmanship
are evident, report the model and serial numbers imprinted on the furnace rating label
to the seller for adjustment.
Packaging
A complete furnace is contained within two (2) packages. The factory completed all
feasible assembly. However certain components including oil burner and draft regulator
and, if supplied, door handle, air filter(s), and air filter rack(s), must be assembled to the
furnace, or the venting system, in the field. Refer to the assembly instructions.
Shipping Damage
If this furnace was damaged during transit, please immediately request the
transportation company inspect the furnace and issue a concealed damage report.
The party receiving the furnace should file the claim for shipping damage. Report any
shipping damage immediately.
It is absolutely essential that a damage report be obtained. If a concealed damage
report is not obtained, we cannot provide assistance in recovering your claim against
the transportation company.
Warranties
c WARNING: The manufacturer of this equipment assumes no liability for any
damages resulting from unauthorized modifications made to the furnace, or any
components thereof, or improper installation of the furnace in the field.
Furthermore, any such field modifications VOID THE WARRANTY and place
responsibility for safe and reliable operation of the furnace on those who
performed the modification(s).
Complete and return any enclosed warranty cards. These must be on file to verify
installation dates for replacement of any warrantied part(s).
4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION GUIDELINES
Codes
All local codes and regulations take precedence over the instructions in this manual and
shall be followed accordingly. In the absence of local codes, this installation must
conform to these instructions and to the regulations of the National Fire Protection
Association (NFPA) publications, the Standard for the Installation of Oil-Burning
Equipment, NFPA 31-2001, and the National Electrical Code, ANSI/NFPA 70-2002, or
the latest editions thereof. To obtain copies of these publications for a fee, contact the
NFPA at the address given in Appendix A of this manual.
Installation Location
c WARNING:
• These furnaces are designed for indoor installation ONLY.
• These furnaces are NOT to be used as construction heaters.
• DO NOT hang the horizontal / counterflow furnace from a structure, or
surface, by any integral part or fastener of the furnace. The furnace was
not designed to support itself in this manner.
In as much as practical, the furnace should be positioned near a chimney or vent and
should be centralized with respect to the air distribution system.
For a utility room installation, the entrance door must be wide enough to permit the
largest part of the furnace to pass through the doorway or allow sufficient clearance to
permit the replacement of another appliance, e.g. a water heater, in the room.
If the furnace is installed in a residential garage, it must be installed so the burner is
located higher than 18 inches above the floor, unless the required combustion air is
taken from the exterior of the garage. Also, the furnace must be located or protected to
avoid physical damage from impacts by vehicles.
Highboy and lowboy furnace models must rest on sturdy, stable, and level surfaces.
The horizontal / counterflow model may be mounted on a level surface, as described
above, or it may be suspended from an overhead structure or surface. If this model is
suspended from hanger rods, support the furnace from the bottom casing surface
at three (3) places, across both ends of the casing and across the casing, near the
middle of the furnace. Generally, a simple support frame for the furnace can be
fabricated from structural steel angle, threaded steel rod, and fastener hardware, refer
to Figure 1. Adjust the height of the support angles to level the unit in position.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1: Recommended Support Frame for Horizontal / Counterflow Furnaces
Closet and Alcove Installation
All furnace models may be installed in a closet or alcove on combustible flooring with
specified (standard) clearances to combustible construction. The horizontal /
counterflow furnace model requires an optional combustible surface-mounting
base (model # CSFB-HC68) for vertical installation (i.e., counterflow
configuration) directly on combustible materials, refer to Figure 2.
Figure 2: Counterflow Furnace Combustible Surface-Mounting Base
Standard Clearances
Standard clearances are mandatory minimum clearances from heated surfaces of the
furnace to combustible materials to assure protection from fire hazard during furnace
operation. (Refer to the Standard for the Installation of Oil-Burning Equipment, NFPA
31-2001, for definitions of combustible and non-combustible materials.)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessibility clearances, which are typically greater, may exceed fire protection
clearances. Therefore, consider providing at least 24 inches of clearance from the front
(and the rear, for lowboy furnaces) of the furnace to obstructions and surfaces for
adequate service and maintenance access.
The minimum clearances from furnace casing surfaces to combustible materials are:
• 3 inches from casing sides and rear
• 8 inches from front casing of furnace to the closet door, with exception of:
o the lowboy rear flue model only requires 3 inches from front casing of the
furnace to the closet door
o the horizontal / counterflow furnace requires 22 inches from front casing of
the furnace to the closet door
• 9 inches from flue pipe/vent connector
• 3 inches from casing top
• 3 inches from any side of supply air plenum
• 3 inches above supply air ducts, within 6 feet of furnace
• For the horizontal / counterflow furnace only, when the optional combustible
surface-mounting base is used with the furnace in the counterflow configuration,
adequate clearances from the supply end surface of the furnace casing to
combustible surfaces are provided by the design of the mounting base.
Though these are approved clearances for these furnaces, space must be provided at
the front (18 inches minimum, 24 inches recommended) and at the rear of the furnace
for access, service, and replacement of the oil burner, air filter(s), circulating air blower,
and fan motor.
Air for Combustion and Ventilation
c CAUTION: Relief openings in the front or top of the furnace casing should not
be obstructed or blocked. These openings supply combustion and ventilation air
to the furnace.
Chloride, fluoride, iodide, and bromide bearing compounds when present, even in low
concentrations, in air supplied for combustion to the furnace, can result in accelerated
and severe corrosion of the heat exchanger and/or the venting system. This condition
can occur with less efficient furnaces, but is more likely to happen on furnaces with
efficiencies of 80% or greater.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Often, household chemicals contain chloride-bearing compounds. There are many
compounds representative of this classification of chemicals. A few common examples
are listed below.
• Cleaning solvents
• Varnish and paint removers
• Bleaches
• Fabric softeners
• Water softener salt
• Tile adhesives
Avoid storing or using these chemicals within close proximity to the furnace. In addition,
avoid storing or using any chemicals, of an unknown and possibly flammable nature, in
close proximity to the furnace. If it is necessary to store or use chemicals in the same
space as the furnace, the area should be well-ventilated and all containers should be
sealed when not in use. If possible, keep chemicals in a separate, well ventilated, room
closed off from the furnace with a door.
The furnace shall be installed in a location within the building that permits a satisfactory
supply of air for combustion, ventilation, and proper operation of the venting system.
While all forms of building construction cannot be covered in detail in this manual, this
requirement may usually be met by application of one of the following methods in
ordinary building construction. However, applicable local installation codes always take
precedence and shall be followed.
The content of certain pertinent passages of NFPA 31-2001 on methods to obtain and
ensure adequate airflow to the furnace has been excerpted and, in some cases,
paraphrased below for reference purposes. Consult the Standard for the Installation of
Oil-Burning Equipment, NFPA 31-2001, for special cases and further details.
1. Utility Room (example of a confined space)
a. In buildings of conventional construction with normal air infiltration, two (2)
permanent openings connecting to a well-ventilated crawl space, attic, or
another large, well-ventilated internal area shall be provided. Each opening
shall have a minimum free area of one (1) square inch per 1000 BTUH of total
input rate (sum of the individual appliance input rates) of all appliances to be
installed in the utility room. One opening should be located near, or in, the
ceiling of the room and the other should be located near, or in, the floor.
b. In buildings of unusually tight construction (e.g. those having continuous
water vapor barriers; tightly-fitting, or weather-stripped, doors and windows;
and gasketed, caulked, or sealed outer wall joints and penetrations), wherein
infiltration and air exchange with the outdoors is very limited (0.35 air changes
per hour, or less), provision must be made to provide sufficient air for
combustion. The following method will usually be adequate to ensure
sufficient airflow into the space.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Provide two (2) permanent openings, one (1) located within 12 inches of the
floor and one (1) within 12 inches of the ceiling, or roof, of the room. These
openings shall allow for direct exchange of air between the room and
outdoors. If required, ducting between the room and the outdoors shall be
provided.
• For horizontally -oriented ducts, each opening shall have a minimum free
area of one (1) square inch per 2000 BTUH of the total input rate (sum of
the individual appliance input rates) of all appliances to be installed in the
room.
• For vertically -oriented ducts, the minimum free area may be reduced to
one (1) square inch per 4000 BTUH of the total input rate (sum of the
individual appliance input rates) of all appliances to be installed in the
room.
• The minimum dimension of any air opening shall not be less than 3-
inches.
• When an opening in the outside wall must be provided, it should be
furnished with properly screened metal sleeves.
2. Full Basement (example of an unconfined space)
a. Where a furnace is installed in a full basement, in a building of conventional
construction with normal air infiltration, infiltration is normally adequate to
provide air for combustion and ventilation.
b. In buildings of unusually tight construction (such as those where weather
stripping and storm sash windows are used, and where basement windows
are also weather-stripped), one (1) permanent opening connecting to a well-
ventilated attic, or with the outdoors shall be provided, using a duct, if
necessary. This opening shall have a minimum free area of one (1) square
inch per 5000 BTUH of total input rate (sum of the individual appliance input
rates) of all appliances to be installed in the basement.
When an opening in the outside wall must be provided, it should be furnished
with properly screened metal sleeves.
If an exhaust fan, additional air consuming machines (e.g. an air compressor), or a
return air grill is present in the furnace room, there should be increased concern about
providing adequate airflow to the furnace. Additional efforts may be required to assure
an adequate supply of combustion and ventilation air is available to the furnace under
all conditions.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Chimney Inspection
The chimney, vent, or any passageway for the stack gases to flow to the outdoor
atmosphere is a very important part of the heating system. No furnace, regardless of the
efficiency of the design, can perform satisfactorily when the chimney to which it is
connected is inadequate or in poor condition. Any of the following symptoms may
indicate a chimney has severe structural damage and is unsuitable for use.
• Chimney appears to be leaning to the side.
• Chimney appears to have structural damage, i.e. loose or missing blocks or
bricks, or excessive deterioration at mortar joints.
• Tile liner damaged or missing.
• Flue gas leakage along the length of the chimney between the chimney
connector and discharge termination.
• Excessive corrosion at the cleanout port or at the chimney connector entrance
into the chimney.
• Structural debris, i.e. mortar or tile liner flakes, in base of the flue way.
A qualified person shall inspect the chimney to confirm it is correctly sized for the
application, properly constructed, and in sound condition. Refer to the Standard for the
Installation of Oil-Burning Equipment, NFPA 31-2001, for details on proper chimney
sizing and construction. If needed, the chimney should be cleaned before installing the
furnace. Any accumulation of dirt or debris at the bottom of the flue should be removed.
Flue / Chimney / Vent Connector
c CAUTION:
• DO NOT install a manual damper in the chimney or vent connector.
• Motorized and thermally- activated type vent dampers are NOT
recommended for use on these furnaces.
It is desirable to install the shortest vent connector (also referred to as a flue or chimney
connector) possible with the fewest number of fittings, i.e. transitions and elbows.
Generally, 6-inch diameter, 24 Ga. or heavier, single wall, lock seam-type, galvanized
steel vent pipe and fittings are satisfactory materials for the fabrication of a vent
connector. However, always consult local codes and authorities for specific minimum
requirements.
For some installations, it may be prudent to turn the furnace flue elbow 90 degrees
clockwise, with respect to the front of the furnace, such that the elbow is open to the
right-hand side of the unit, rather than upward. Turning the flue elbow may better
facilitate connection of the vent connector piping to the flue elbow on the highboy and
front flue, lowboy furnaces. Due to the presence of the fan and limit control and the
wiring harness, the elbow may not be rotated 90 degrees counterclockwise. The
installer must carefully mark and cut a hole in the furnace housing to allow the vent
connector to pass through the housing.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
If desired, with the furnace flue elbow turned to the right, the standard furnace top front
panel (p/n 52-17346-1) may be replaced with the top front panel from the rear flue
lowboy model (p/n 52-17383-1). Refer to Appendix D: Replacement Parts for sketches
of these parts. Contact your Crown distributor to purchase this part.
All horizontal sections of the vent connector must slope upward not less than ¼ inch per
foot from the furnace to the vent termination. Long horizontal sections of the venting
system must be supported at least every five (5) feet with metal straps to prevent
sagging of the vent piping. Secure all joints in the vent connector with sheet metal
screws or equivalent fasteners. Vent piping must not be inserted beyond the inside wall
of the chimney flue.
Power (Side-Wall) Venting – Important Note Regarding
c CAUTION: Crown Boiler Company will NOT assume responsibility for damage
to, and deterioration of, exterior building materials, e.g. brick, siding, clapboards,
and etc., in close proximity to the vent terminal due to operation of a power
vented, oil furnace. This policy is applicable regardless of the cause of sooting.
Two (2) problems typically arise when power venting any oil-fired appliance.
1) Soot buildup may occur at an accelerated rate on critical components of the
furnace oil burner, e.g. the primary control flame sensor (“cad cell”), the burner
head, and oil nozzle.
2) Severe damage may occur to external surfaces of the structure in the event the
furnace continually produces a high level of smoke in the flue gases. Excess
smoke and soot can be produced for many reasons, some of which cannot be
successfully controlled by the installer and the appliance manufacturer.
NOTICE: Crown Boiler recommends the use of a chimney to vent residential oil
furnaces. If a power venter must be used, it is the responsibility of the installer
and power venter manufacturer to design, assemble, and demonstrate proper
operation of the power venting system with the furnace.
Draft Regulator
A barometric-type, draft regulator is supplied with the furnace. Installation or operating
conditions that produce excess amounts of draft can reduce the heating efficiency of the
furnace. The purpose of the regulator is to adjust and control the flow of flue gases from
the furnace by stabilizing the amount of chimney draft to which the furnace is subjected.
Generally, install the barometric draft regulator in the vent connector as close as
possible to the flue outlet collar of the furnace. However, always refer to the draft
regulator
manufacturer’s
installation
instructions
for
application
specific
recommendations.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Duct Work and Air Conditioning
Design and installation of the duct system should follow the current guidelines of the Air
Conditioning Contractors of America (ACCA) or the American Society of Heating,
Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE). Refer to the Residential
Duct Systems, Manual D, from the ACCA, and the ASHRAE Handbook Fundamentals
volume, from ASHRAE, for recommended practices in duct system design and
installation. To obtain copies of these publications for a fee, contact the ACCA and the
ASHRAE at the addresses given in Appendix A of this manual.
All furnaces are tested over a range of external static pressure that simulates the airflow
resistance of the ductwork, fittings, and diffusers connected to the furnace for a typical
(average) duct system. The furnace blower and blower motor have been selected to
work successfully against the following range of duct system resistance.
Recommended range of duct system resistance for all models: 0.2 to 0.5 in. W.G.
external static pressure.
Due to the need to maintain an adequate supply of combustion and ventilation air, the
furnace shall not be installed in small room without return air duct system. A duct the full
size of the furnace return air opening shall extend to a location outside the furnace
room.
If the furnace is used in connection with summer air conditioning (cooling), the furnace
should be installed in parallel with, or on the upstream side of, the evaporator coil to
avoid water vapor condensation in the furnace heat exchanger. If the cooling unit is
installed in a parallel flow arrangement, dampers (or other means used to control
airflow) should be provided to prevent chilled air from entering the furnace. If such a
damper is manually operated, it must be equipped with a means to prevent operation of
either unit, unless the damper is placed in either the full heat or full cool position.
NOTICE: Return air grilles and supply registers in the air distribution system
should never be obstructed.
Air Filter Mounting
c CAUTION: If cutting openings in the furnace casing is required, DO NOT cut
any supporting clips or angles. Cut as close to the scribed line as possible, but
DO NOT cut the base clip or blower pan support angle.
Lowboy furnaces are factory-equipped with permanent-type, air filters located above the
blower compartment, in the rear of the furnaces.
NOTICE: Horizontal / counterflow furnaces are not factory-equipped with an air
filter or filter rack. Furthermore, the furnace blower compartment does not contain
enough free space to permit an air filter to be mounted within the furnace casing.
However, the installer should supply, or fabricate, a filter rack and mount an air filter in
the return air plenum above, or upstream of, the furnace blower compartment.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
On the highboy furnace, it is necessary to cut the return air opening in the lower side, or
rear, of the casing depending upon the needs of the specific installation, refer to Figure
3.
Figure 3: Cutaway view of fan section of a typical highboy furnace.
The side casings have each been pre-punched with four (4), square, knockout openings
for use in locating the proper position for the return air filter rack. On the side of the
furnace, where the return air duct will attach, scribe a line connecting the outside edges
of the knockout openings to form a rectangle. Using a punch, or a large screwdriver,
and a hammer, remove the knockouts and cut the return air opening in the casing.
Sheet metal shears, or a power metal cutting tool, will be required to cut the casing.
Position the open end of the filter rack to the front of the furnace to permit access for
filter replacement. Align the filter rack with the rectangular hole and mark the locations
on the casing of the pre-punched mounting holes in the filter rack flange. Drill pilot holes
in the casing and permanently attach the filter rack to the furnace with screws, or pop-
rivets (these fasteners are not included). Connect the return air plenum to the filter rack
and slide the air filter into position.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Connections
NOTICE: All field wiring must conform to local, state, and national installation
codes.
A disconnecting switch equipped with overcurrent protection rated at 15 A. (e.g. a time
delay-type fuse or inverse time, circuit breaker) should be installed in the service line for
shutting down and protecting the furnace and electrical system.
Since the furnace is entirely pre-wired at the factory, it is only necessary to connect the
building electrical service lines to the two (2) pigtail wires extending from the fan center
junction box. The fan center is mounted inside the furnace burner compartment or
mounted on the front exterior of the furnace, in the case of the horizontal / counterflow
model. The service lines to the furnace should be no smaller than 14 Ga., insulated
copper wire with a temperature rating of 60ºC, or greater.
Connect an equipment ground wire to the furnace at the fan center junction box. If
wiring is run through metal electrical conduit, it may not be necessary to run a separate
equipment ground wire. Consult local codes and authorities for specific minimum
requirements.
A two (2) wire connection to the room thermostat from the oil primary control is also
necessary. This is typically a low voltage (24 VAC) circuit. Consult the National
Electrical Code, ANSI/NFPA 70-2002, for guidelines for proper wiring methods and
materials for this circuit.
Refer to the electrical diagrams contained in Appendix B of this manual for an electrical
schematic, a connection diagram, and operating instructions.
Room Thermostat
A room thermostat is not furnished with this furnace. However, a thermostat is required
to properly operate the furnace control system in a typical residential heating
application.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
The room thermostat should be located on an interior wall in the natural circulating path
of the room air.
The thermostat should not be installed in a location where it is directly exposed to,
• cold air infiltration, i.e. drafts from outside openings such as windows and doors,
• air currents produced by supply air registers, and
• heat from a nearby source, such as a fireplace, electrical appliances, lamps,
solar radiation, a wall enclosing warm air ducts, a chimney, or a flue gas vent.
These phenomena will adversely influence the operation of the thermostat, preventing it
from properly controlling the room temperature. Conversely, avoid installing the room
thermostat in a location where the natural circulation of air is blocked, such as behind
doors, in shelves, or in corners.
Generally, a room thermostat should be set at the lowest temperature that is
comfortable to the building occupants. This will result in the lowest cost to heat the
building.
Combustion Chamber
The furnace combustion chamber is a hollow, circular cylinder sealed at the bottom end
and open at the top end. The chamber is made of a lightweight, insulating, “soft”,
refractory material. The refractory material is composed of organically bound, alumina-
silica fibers that provide a high temperature region for combustion of the oil to occur.
This type of material exhibits quiet operation and improved combustion efficiency due to
faster heat-up times compared to hard, dense, ceramic refractory materials.
Oil Burner and Oil Nozzle Installation
c CAUTION: This oil furnace is designed to use No. 2 distillate fuel (home
heating) oil only.
This furnace is designed to utilize any one (1) of the following four (4), specially
modified, oil burners interchangeably:
• R.W. Beckett Corp. model AF burner, specification #’s CI3701 & CI3702,
• R.W. Beckett Corp. model NX burner, specification # CI4002
• Carlin Combustion Technology, Inc. model EZ-1HP, specification #
8528200BCLBR1, and
• Riello Canada Inc. model 40-F3, specification # C8511477.
NOTICE: NO other burners may be used in this application.
The heat output from the furnace is fixed, based on the size of nozzle installed in the oil
burner. Four (4) heat input rates are permissible: 85,000, 105,000, 120,000, and
140,000 BTUH.
• For the Riello 40-F3 burner option only, the maximum heat input rate is
133,000 BTUH.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Nozzle selection (i.e. heating capacity of the furnace) shall be based on a rate of heat
loss (heating load) calculation for the building. These calculations should be made
according to the manuals provided by the Air Conditioning Contractors of America
(ACCA) or the American Society of Heating, Refrigeration and Air Conditioning
Engineers, Inc. (ASHRAE).
Refer to the Residential Load Calculation, Manual J, from the ACCA, and the ASHRAE
Handbook Fundamentals volume, from ASHRAE, for the recommended procedure to
compute the design heating load of a residence. To obtain copies of these publications
for a fee, contact the ACCA and the ASHRAE at the addresses given in Appendix A of
this manual.
The oil burner is shipped in a separate carton from the furnace. In the field, it is
necessary to mount the oil burner, secure it to the furnace, and connect the wiring
harness to complete the installation. Refer to the following steps.
1) Remove the oil burner from the shipping carton and remove any shipping
materials adhering to the burner.
2) If it is necessary to adjust the heating capacity of the furnace, by changing the oil
burner nozzle, refer to these instructions. Also, consult the oil burner
manufacturer’s operating instructions (included with the burner) for detailed
instructions on this procedure.
a) The oil nozzle is factory installed in the oil burner. To change the oil
nozzle, remove the nozzle through the front end of the burner air tube. (If
the oil burner is already installed, the oil burner can be removed from the
heat exchanger mounting plate to gain access to the nozzle. Alternatively,
the nozzle and electrode assembly may be removed from the rear of the
burner assembly without removing the oil burner from the furnace.)
b) Install an appropriate replacement nozzle of the correct size, spray angle,
and spray type. Refer to the Specification Sheets, in Appendix C of this
manual, for nozzle recommendations.
3) The furnace may have been handled roughly while in transit. Under some
conditions, the combustion chamber can shift out of position. Check for proper
alignment of the burner air tube with the circular opening in the combustion
chamber and trial fit the burner to check the insertion depth of the oil burner into
the combustion chamber.
The end of the burner air tube should be inserted no farther than 1/4 inch back
from the inside surface of the combustion chamber, refer to Figure 4. Do not
allow the burner tube/end cone to physically touch or protrude into the chamber.
High temperatures in the combustion chamber can result in damage to the tube,
the end cone, or both. A distance greater than 1/4 inch back from the inside
chamber wall may cause flame impingement on the combustion chamber wall
and subsequent sooting or carbon char buildup.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 4: Side view of correct burner insertion into combustion chamber
4) Push the burner flange gasket (included with the burner) on to the burner
mounting plate threaded studs. Seat the gasket against the mounting plate.
5) Using fasteners supplied in the parts bag with each furnace, three (3) 5/16 in.
brass hex nuts and three (3) steel flat washers, install and secure the burner to
the mounting studs on the burner mounting plate, refer to Figure 5. (For
counterflow / horizontal units, refer to the next section “Horizontal / Counterflow
Furnace Setup”)
Figure 5: Installing and Securing the Oil Burner to the Furnace Mounting Plate
NOTICE: For the Riello 40-F3 burner only, an insulating annulet (included with
the burner) must be installed over the end of the burner air tube. The annulet fills
17
Download from Www.Somanuals.com. All Manuals Search And Download.
the gap between the outer surface of the air tube and the inner wall surface of
the combustion chamber opening to provide a seal, keeping hot combustion
gases within the chamber.
6) Insert and secure the cable or conduit from the wiring harness in the burner
junction box. Snap together the two (2) mating, multipin quick connections, on
the wiring harness from the furnace fan center and the wiring harness of the oil
burner, inside the burner junction box.
• For the Riello 40-F3 burner only, wiring connections are made inside
the burner sound cover (an orange sheet metal shroud covering the
front of the burner). Secure the cable or conduit to the burner
enclosure back plate.
The oil burner provided with this furnace requires initial inspection, set-up, and proper
adjustment. Refer to this manual and the oil burner manufacturer’s operating
instructions for detailed information on the following items.
• Initial firing of burner
• Adjusting the burner combustion air
• Adjusting the fuel pump pressure
• Setting the draft control
NOTICE: This oil furnace must be installed and adjusted by only qualified oil
heating contractor using calibrated combustion test instruments to ensure safe
and reliable operation of the furnace.
Fuel System Installation
In situations where the oil storage tank is installed at the same level with, or above, the
burner, a single oil supply line run from the oil tank to the burner will be usually be
adequate. No return line will be required. If the oil tank is installed below the burner and
the lift exceeds approximately 8-ft. (6-1/2 ft. for the Riello 40-F3 burner), an oil supply
line and an oil return line are recommended.
Refer to the Standard for the Installation of Oil-Burning Equipment, NFPA 31-2001, and
the oil burner operating instructions for detailed information on oil storage tank & oil
supply/return line installation.
NOTICE: We recommend installing a high efficiency oil filter, in the oil supply line,
capable of filtering 10 to 20 micron diameter (or preferably smaller) particles from
the fuel.
If available, the use of ultra-low or low sulfur (less than 0.0015% S and 0.0015 -
0.05% S, by weight, respectively), no. 2 fuel oil is highly recommended. Low sulfur
fuel oil can help to significantly reduce instances of blockage and corrosion of the oil
burner fuel delivery system (especially the nozzle), the furnace heat exchanger, and the
flue gas venting system. Air pollutants emitted by the furnace and the typical
malodorous smell of oil combustion will be reduced.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Horizontal / Counterflow Furnace Setup
The horizontal / counterflow furnace is shipped from the factory upright for vertical
installation (counterflow configuration). If the furnace is to be installed lying down on the
right-hand or left-hand side (horizontal configuration), the positions of the oil burner and
the fan and limit control thermostat may have to be changed. The horizontal furnace
may be turned end for end, or rotated, making the top into the bottom, as shown in
Figure 6. Refer to the following instructions for installing the oil burner and thermostat.
Figure 6: A horizontal furnace rotated 180° (or flipped end for end) to reverse
airflow direction
1) When the furnace is installed in the horizontal configuration, the oil burner
must be mounted in an upright position. It will be necessary to cutoff one (1) of
the threaded burner-mounting studs before attempting to install the burner. Trial
fit the burner to the burner mounting plate to determine which stud to remove. (A
rotary tool with a cutting (abrasive) disk or a hacksaw should work well to remove
the stud.) A machine screw (furnished with the parts package) will substitute for
the removed stud and provide a third point to secure the burner flange to the
burner mounting plate. Thread the screw through the burner-mounting flange and
into the open hole within the burner mounting plate.
2) Install the flange gasket and the burner on the mounting plate threaded studs.
Using fasteners supplied in the parts bag with each furnace [use two (2) or three
(3) 5/16 in. brass hex nuts and flat washers, as required], secure the burner to
the mounting studs on the burner mounting plate.
3) Secure the electrical conduit of the wiring harness to the oil burner junction box
(or for the Riello burner, the burner enclosure back plate) with the hardware
provided.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
4) When the furnace is installed in the horizontal configuration, the high limit
and fan control must also be located in the upper position on the casing when the
furnace is placed in the final installed position, refer to Figure 7. If the control
must be relocated, remove the cover of the control to gain access to the
mounting screws. Remove the mounting screws and the control. Insert the
control into the alternate mounting hole in the casing and mark the screw
locations. Drill pilot holes for the new screws. Install the control in the new
mounting location and secure it with the mounting screws. Replace the cover of
the control. A metal, snap-in cap is furnished with the furnace to close the
unused hole, for the control, in the casing.
Figure 7: Correct locations for the horizontal furnace high limit and fan control.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
INITIAL OPERATION OF THE FURNACE
Initial Burner Operation
c WARNING: To avoid possible explosion, DO NOT attempt to light the burner if:
• Oil has accumulated in the base of the combustion chamber.
• The furnace is full of fuel vapors.
• The combustion chamber is very hot.
c CAUTION: The oil burner must be installed and adjusted using recently (within
the last year) calibrated combustion instruments by a qualified heating contractor
prior to placing the furnace in operation. Refer to this manual and the oil burner
instruction manual for details.
c CAUTION:
• To minimize initial fuel oil and combustion odors, ventilate the building
well while operating the furnace for the first time.
• Do not run the oil pump dry (without oil) for more than two (2) minutes.
Damage to the oil pump may result.
To initially operate the furnace:
1) Turn the electrical disconnecting switch to the “OFF” position.
2) Set the room thermostat above room temperature.
3) Be sure the oil tank is full of clean # 2 fuel oil.
4) Open all shutoff valves in the oil line.
5) Turn on the electrical disconnecting switch and prime the burner oil pump
according to the pump manufacturer’s instructions.
6) When ignition is established, make a temporary air adjustment for a clean,
smoke-free flame. At this point, the final burner adjustment should be made
using test instruments to measure oil pump pressure, smoke number, carbon
dioxide (CO2), carbon monoxide (CO), draft, and flue gas temperature.
• Refer to item (4) under the Troubleshooting section of this manual for a list
of required test instruments.
In order to achieve the best combustion efficiency, the following procedure is
recommended.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
7) Measure the oil pump pressure. If required, adjust it to deliver the
appropriate pressure for the burner. The oil pump should be set to produce,
• 130 PSIG, for the R.W. Beckett model AF burner,
• 150 PSIG, for the R.W. Beckett model NX burner,
• 140 PSIG, for the Carlin Combustion model EZ-1HP, and
• 150 PSIG, for the Riello model 40-F3.
NOTICE: On the Riello model 40-F3 burner only, the oil pump port threads
conform to British Standard Parallel Pipe (BSPP) thread design. Pressure
gages or pipefittings with American National Standard Taper Pipe (NPT)
threads will NOT mate with the BSPP design. Special gages compatible with
BSPP thread, or adapter fittings, are required.
8) Carbon Dioxide (CO2) and Carbon Monoxide (CO) – In order to assure that
proper and safe combustion is taking place, carbon dioxide and carbon
monoxide measurements must be taken. A CO2 reading within the limits of
Table 1 with no measurable CO is desirable. The maximum acceptable CO
reading is about 50 PPM. If the CO reading is too high, open the burner air
shutter, or air band, slightly to permit more combustion air to the flame.
Recheck the CO level and adjust as required.
NOTICE: On the Riello 40-F3 burner only, it will be necessary to remove
the oil burner sound cover to make adjustments to the oil pump pressure and
airflow. The presence of the burner sound cover over the burner acts to
restrict airflow to the burner. Thus, combustion quality will be adversely
affected when the cover is installed after airflow adjustments are made. If
adjustments to burner airflow are made w/o the burner cover, it is necessary
to confirm these adjustments produce satisfactory smoke, carbon dioxide,
and carbon monoxide readings w/ the burner cover installed. Repeated
adjustments and tests may be required.
9) Draft – Draft measurements should be taken through the overfire port and in
the vent connector, not more than 12 inches away from the furnace outlet. A
5/16 in. hex washer head bolt plugs the overfire port in the burner mounting
plate. Remove the bolt and insert a suitable draft measurement gage. After
the chimney (or stack gas passageway) has warmed up to operating
temperature, approximately 15 to 20 minutes of burner operation, adjust the
barometric damper to obtain the correct overfire draft reading. The overfire
draft should read 0.02 in. W.G. The draft measured at the flue (stack draft)
should read no more than 0.05 in. W.G.
NOTICE: The overfire draft is the more important measurement and
should be used to adjust the setting of the barometric draft control.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
10) Flue Gas Temperature – The flue gas temperature will vary depending on
heat input rate, air temperature rise across the heat exchanger, and air
flowrate through the furnace. To prevent excessive water vapor condensation
from the flue gases, the gross flue gas temperature should not fall below
330ºF. In addition, if the gross flue gas temperature exceeds 650ºF, the
heating efficiency of the furnace will be reduced.
To reduce high flue temperatures, after properly adjusting the burner, check
for blocked supply/return airflow. Remove any blockages, increase fan
speed, or consider reducing the furnace heat input rate. Also, verify there is
no air leakage into the combustion chamber from around the burner mounting
flange or heat exchanger mounting plate. If flue gas temperatures are too low,
consider increasing the heat input rate or reducing the amount of
supply/return airflow.
11) Cycle the furnace several times to verify the burner lights off and shutsdown
smoothly without excessive noise or smoke production.
Table 1: Oil Burner Application and Specifications for the Crown Furnaces
Furnace Model:
Burner Model:
All
R.W. Beckett, AF R.W. Beckett, NX Carlin Combustion,
EZ-1HP
Riello, 40-F3
Standard Nozzle:
Delavan, 0.75 GPH Delavan, 0.60 GPH Delavan, 0.65 GPH Delavan, 0.70 GPH
/ 80 deg. angle /
hollow cone
/ 60 deg. angle /
semi solid (W)
/ 60 deg. angle /
hollow cone
/ 60 deg. angle /
hollow cone
Oil Pump Pressure (PSIG):
Burner Head Type:
Head / Turbulator Setting:
Air Band Setting:
Air Shutter / Damper Setting:
Overfire Draft (in. W.G.):
Smoke Spot, Max. (Bacharach Scale):
Carbon Dioxide, CO2, Maximum (%):
Carbon Dioxide, CO2, Minimum (%):
Carbon Monoxide, CO (PPM)
Oil Solenoid Valve Equipped:
Prepurge Time (sec):
130
F3
Z = 1.125 in.
Fully-closed
5
150
Standard
140
Standard
A = 0.65
0.6
150
F3
2
-
3
3
-
-
Fully-closed
0.02
# 1
13
12*
0
No
Yes
No
Yes
None
None
Postpurge Time (sec):
Ignition Type:
Interrupted
* When operating these furnaces at the lowest input rate (84,000 BTUH), the carbon dioxide (CO2)
value may not be able to be adjusted above 12%. This is normal and does not necessarily indicate
a problem.
Supply/Return Airflow and Air Temperature
The supply/return airflow shall be set to obtain an air temperature rise, across the
furnace, in the range of 70 to 100ºF. Since the flow resistance of each duct system is
slightly different, the airflow (fan speed) may have to be changed in the field to achieve
a satisfactory temperature rise.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
One way to measure the temperature rise across the furnace is to insert temperature
measuring devices (e.g. thermometers) into the return air duct and into the supply air
duct about 12 inches from the furnace. After the furnace has been firing continually for
over 20 minutes, read the temperature difference between the two (2) thermometers.
The temperature difference should not exceed 100ºF, nor be less than 70ºF. A
temperature rise of 85ºF is considered to be optimum for comfort. For better energy
efficiency, a temperature rise closer to 70ºF is recommended.
The blower (fan) speed fan is adjusted by changing the fan motor winding energized by
the control system. The furnace is set on the lowest fan speed, “L”, at the factory, refer
to Table 2. To adjust the fan speed, follow this procedure.
a. Turn off all electrical power to the furnace at the disconnecting switch.
b. Remove the blower compartment access door.
c. Move the orange wire from the low speed terminal block, marked “L”, to the next
higher fan speed (medium low), marked “ML” on the terminal block, refer to
Figure 8. Other available higher fan speeds are medium high, marked “MH” and
high, marked “H”.
NOTICE: The red wire is normally positioned on the high fan speed, for
cooling applications. However, the red wire may be moved to another
terminal block position, as required.
d. Replace the blower compartment access door.
e. Restore electrical power to the furnace at the disconnecting switch.
With the furnace operating, measure the air temperature rise across the furnace again.
If the value does not fall in the range of 70 to100ºF, repeat the above procedure.
Figure 8: Blower Motor Terminal Blocks and Wiring
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Furnace Limit and Blower Controls
All furnaces are equipped with a combined thermostatic high temperature limit and
blower (fan) control. The high temperature limit is set such that it does not permit a
supply (discharge) air temperature above 200ºF.
The thermostatic fan control should be set so the greatest fuel utilization efficiency of
the furnace is obtained. Generally, a blower “ON” setting of 130ºF should give the best
result. After the burner shuts down, the circulating air blower will continue to operate
until the air temperature inside the furnace falls below the lower setting on the fan
control.
This delay on blower shutdown extracts residual heat from the furnace heat exchanger
that would ordinarily be lost to the outdoor atmosphere. If a longer, or shorter, cooldown
period is desired, the fan control differential setting may be reset to lengthen, or shorten,
the cycle as desired. Refer to Table 2 for the standard fan and high limit control settings.
Table 2: Standard Furnace Fan / Limit Control and Speed Settings
High Limit Thermostat Setting (deg. F.):
230 (highboy / lowboy models)
190 (horizontal / counterflow model)
Fan “On” Setting (deg. F.):
130
Fan “Off” Setting (deg. F.):
100
Standard Fan Speed for 105 MBTUH Input Rate:
Low, Orange Wire to “L” Terminal
In addition to the combined fan and limit control, the horizontal / counterflow furnace is
equipped with an auxiliary high limit temperature control located in the blower
compartment, refer to the electrical diagram in Appendix B. The purpose of this control
is to prevent overheating of the blower motor and air filter(s), if airflow is severely
reduced.
If the duct system becomes partially, or totally, blocked or the furnace air filter(s)
become excessively dirty causing the blower to fail to circulate enough air, the
thermostatic high temperature limit (or, if equipped, the auxiliary high temperature limit)
may activate to prevent very high discharge air temperatures from occurring.
Should airflow be restricted, the furnace might cycle on and off too frequently or become
inoperative. To correct this condition, verify that all supply and return dampers and
registers in the air distribution system are open. If this fails to resolve the problem, turn
off the electrical power to the furnace. Remove the blower compartment access door to
examine the air filter(s) and blower for blockages or a loose blower wheel. (On the
highboy and horizontal / counterflow furnaces, air filters should be mounted external to
the furnace casing.) If possible, correct the condition by cleaning or replacing the air
filter(s), freeing the blower wheel of any foreign materials, or securing the blower wheel
to the fan motor shaft. Always replace the blower compartment access door when
service is finished. Restore electrical power to the furnace.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Room Thermostat
Most room thermostats are equipped with user adjustable, or selectable, levels of heat
anticipation. This feature helps to reduce the amount of room air temperature overshoot
that occurs after a heating cycle.
To adjust the heat anticipator, measure the electrical current output of the oil burner
primary safety control to the room thermostat. (If measurement is not possible, the value
of current output may be marked on the cover of the control). Set the thermostat heat
anticipator to match the electrical current output of the oil primary safety control.
Instructions to Our Customer / End User
! WARNING: If the burner does not operate properly after depressing the oil
primary reset button three (3) times, turn off the electrical power to the furnace
and close the manual oil shutoff valve. Immediately contact a qualified heating
contractor for service.
Before leaving a new installation, the installer should show the customer or end user
where the furnace instruction manual is kept. He should also discuss the following
points:
1) Describe the general operation of the furnace and, if properly equipped, the
cooling system.
2) Show the location of the furnace air filter(s) and those in the duct system, if
equipped. Demonstrate how to remove, clean, and replace the air filter(s).
3) Demonstrate how to set and adjust the room air temperature using the room
thermostat.
4) Demonstrate how to operate (turn on and off), the heating system and, if properly
equipped, the cooling system and the circulating air blower.
5) Show the location of the oil primary safety control in the furnace. Describe when
and demonstrate how to depress the oil primary reset button.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE
Troubleshooting
c WARNING: When testing electrical equipment, always follow standard
electrical safety procedures.
Before beginning these troubleshooting procedures, always review these basic points.
1) Check for 120 VAC power to the furnace. If there is no voltage, check the
disconnecting switch for circuit breaker trip or blown fuses.
2) Make sure the room thermostat is set on the heating mode and is “calling for
heat”.
3) Check for sufficient oil supply and that all oil shutoff valves are open.
4) To successfully service this oil furnace, the following recently (within the last
year) calibrated instruments must be available.
• Smoke spot test kit with Bacharach-type oil burner smoke scale
• Carbon dioxide (CO2) and carbon monoxide (CO) test kit or analyzer
• Flue gas temperature measuring instrument
• Draft gauge, capable of measuring 0.01 to 0.25 in. W.G. draft
(Draft is the pressure differential between the static pressure measured in
the vent pipe, or just above the combustion chamber, and the indoor
atmospheric pressure. Under normal operating conditions, it will have a
negative value, i.e. the pressure in the combustion chamber and the vent
system are less than room air pressure.)
• Multimeter (analog or digital type)
• Oil pressure gauge, capable of measuring at least 0 to 200 PSIG
• Burner electrode and nozzle setting gauge
5) Be familiar with the correct operation of these instruments as well as how to
adjust the oil burner settings (refer to burner manufacturer’s literature).
A. Symptom: Furnace does not operate.
Items to check:
c WARNING: Repeated operation of the oil primary safety control
reset button can cause a build-up of unburned oil in the combustion
chamber. An accumulation of oil in the combustion chamber is a
hazardous situation and may cause a fire or explosion.
1) Make sure the disconnecting switch is “ON” and the circuit breaker has
not tripped, or fuses have not blown.
2) Confirm there is 120 VAC at the fan center junction box.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
3) Confirm the room thermostat is wired correctly, set on the “HEAT”
mode, and “calling for heat”.
4) For all primary controls, lockout can be confirmed by measuring
voltage from the oil primary safety control to the burner motor. If none,
depress the oil primary reset button. [On the Honeywell oil primary
control, lockout has occurred if the indicator light (an LED) is rapidly
flashing; depress the oil primary reset button.]
If the burner does not operate properly after depressing the reset
button three (3) times, turn off the electrical power to the furnace
and close the manual oil shutoff valve. Immediately contact a
qualified heating contractor for service.
B. Symptom: Burner short cycles or “locks out” on oil primary safety control.
Items to check:
1) Fuel oil tank nearly empty or oil flow restriction. Refill oil tank, replace
oil filter, open all shutoff valve(s), and purge oil line(s) of air.
2) If the oil primary control has not “locked out” (e.g., on the Honeywell
primary control, the indicator light is not flashing), measure the
electrical current to the room thermostat. Set the heat anticipator on
the room thermostat to the current value measured. Also, check the
wiring between the thermostat and primary control to be sure it is
correct and no loose connections exist.
3) Inspect the burner flame sensor, “cad cell”, to be sure the lens is clean
and the cell is correctly aimed at the flame.
4) Inspect the burner oil nozzle for blockages and signs of deterioration.
Replace the nozzle, if required. Also, measure and reset the electrode
gap and alignment. If badly worn or deformed, replace the electrodes.
(Refer to the burner manufacturer’s instructions.)
5) Confirm there is a strong spark across electrodes. Generally, viewing a
spark jump across the electrodes is sufficient indication the ignition
transformer is operating correctly. Testing an electronic ignition
transformer with a transformer tester is generally not
recommended.
6) Inspect the heat exchanger through the cleanout ports for signs of
excessive soot, scale buildup, or blockage. If a heavy deposits are
present, clean the heat exchanger.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Symptom: Burner short cycles on high limit thermostat, but does not “lock
out” on oil primary safety control.
Items to check:
1) Open dampers or registers in the air distribution system. Clear any
duct system restrictions.
2) Inspect and clean all air filters in the air distribution system.
3) Inspect blower for interference with rotation or locked rotor condition.
Also, confirm the blower wheel is secured to the fan motor shaft.
4) The fan motor or run capacitor may be damaged. Test and replace the
motor or capacitor, as required.
5) Increase fan speed.
D. Symptom: Unable to achieve clean combustion by making burner air
adjustments.
Items to check:
1) Measure the burner air tube insertion depth and alignment. The end of
the tube should not protrude inside the combustion chamber. The end
of the tube should be approximately ¼ inch away from the inner wall
surface of the combustion chamber.
2) Inspect the oil nozzle for excessive wear, blockage, or deterioration.
Measure and, if necessary, reset the nozzle depth or turbulator
location with respect to end of the burner head. Replace the nozzle, if
necessary (refer to the oil burner manufacturer’s instructions).
3) Measure the oil pump pressure. If required, adjust the pressure to
burner nameplate value. (This is the typical minimum pressure
required to obtain the full input rate from the furnace).
4) Verify the burner is configured as specified in Table 1 and adjusted
according to the Initial Burner Operation section of this manual and
the burner manufacturer’s instructions.
5) Measure the overfire draft. If required, adjust the barometric damper to
increase the stack draft to obtain an overfire draft of 0.02 in. W.G. with
the burner operating. (This is the typical minimum draft required to
obtain the specified flue gas combustion analysis values given in Table
1.) If the specified overfire draft cannot be obtained with a stack draft of
0.02 in. W.G., the heat exchanger may be partially blocked and could
require cleaning.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
6) Measure the draft at the point where the vent connector attaches to the
heat exchanger flue pipe. With the burner operating, the stack draft
should not exceed 0.05 in. W.G. If the stack draft has been adjusted
above this value to give the proper overfire draft, the heat exchanger
will require cleaning.
If there is little or no stack draft, the chimney flue way may require
cleaning, the chimney is too restrictive, or a downdraft condition exists.
E. Symptom: Furnace blower will not start.
Items to check:
1) Confirm there is 120 VAC at the blower motor terminal block.
2) If there is not 120 VAC at the blower terminal block, measure the
voltage at the fan center relay. If the fan can be activated by itself from
the room thermostat subbase, confirm it will operate. If so, the fan
center relay contacts may be burnt, or damaged, or the fan limit control
may be defective. Test these components and replace the defective
component, as required.
3) If there is 120 VAC at the blower terminal block, either the run
capacitor or blower motor may be damaged. Test and replace the
capacitor or motor, as required.
F. Symptom: Blower cycles on and off after the burner has shutdown.
Item to check:
1) Increase the fan limit control differential. Typically, the fan “off” setting
should be 30 degrees F. below the fan “on” setting. Adjust the setting
as required.
NOTICE: If the fan and high limit control is faulty, it should be
replaced. However, it must only be replaced by the same make
and model as the original. All the original temperature settings
should be duplicated on the replacement model as well. REMOVE
THE LOW VOLTAGE JUMPER IN THE CONTROL, IF EQUIPPED.
Refer to the electrical diagram for proper electrical connections.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Flame Sensor (“Cad Cell”) Checkout Procedure
On the Honeywell oil primary control, to check the electrical resistance of the flame
sensor (referred to as a cadmium sulfide photocell, or “cad cell”), depress the reset
button on the oil primary safety control while the burner is firing. The oil primary control
will report the measured resistance range of the cad cell by flashing the LED (light
emitting diode) one (1) to four (4) times. Refer to the oil burner manufacturer’s
instructions for further details.
For all primary controls, an alternate procedure to check the flame sensor operation is
as follows:
1)
Remove the flame sensor lead wires from the terminals (labeled “CAD
CELL” on the underside of the Honeywell control) of the oil primary safety
control module. Start the burner. Shortly after combustion is established,
place a temporary jumper wire across the cad cell terminals, or leads, of
the control. Connect an ohmmeter across the flame sensor lead wires.
The measured resistance should be less than,
• 1600 Ohms for the Honeywell cad cell,
• 1500 Ohms for the Carlin cad cell, and
• 1200 Ohms for the Riello cad cell.
NOTICE: On the Riello 40-F3 burner only, it may be difficult or
impossible to measure the actual operating resistance of the cad cell with
the burner operating. With the electrical power off, carefully remove the
printed circuit board from the Riello oil primary control and subject the cad
cell to direct sunlight. The measured resistance of the cad cell should
reduce to 50 Ohms, or less. Cover the cad cell and measure the dark cell
resistance, refer to step 3 below.
2)
3)
Stop the burner and remove the jumper wire.
With the burner off, measure the resistance of the flame sensor with the
ohmmeter. The resistance of the sensor without “seeing” a light source
(so-called “dark” cell resistance) should be greater than,
• 20,000 Ohms for the Honeywell cad cell,
• 50,000 Ohms for the Carlin cad cell, and
• 40,000 Ohms for the Riello cad cell.
4)
If the sensor resistances are outside the acceptable ranges given above,
confirm the lens of the cell is clean and the cell is located correctly in the
burner housing. If the cell is clean and correctly located, replace the flame
sensor.
NOTICE: All resistances are approximate values only and will vary
depending upon the intensity of the light source (flame or sunlight) and the
condition or age of the cad cell.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
On the Riello 40-F3 burner only, the cad cell is an integral part of the oil
primary control. If replacement of the cad cell is required, the entire
primary control must be replaced.
Replacement Parts
Appendix D of this manual contains a list of replacement parts available for these
furnaces.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
Air Filter(s)
c CAUTION: To avoid injury from moving parts, hot surfaces, or electrical
shock, shut off the power to the furnace and allow the furnace to cool BEFORE
removing any furnace access doors to service air filters.
Highboy and lowboy furnace models are factory-supplied with a permanent-type, air
filter. At least twice a year, remove the air filter(s) for cleaning. Clean a filter by soaking
it in water with a mild detergent and then rinsing it with clean water. Allow the filter to air
dry before reinstalling it in the furnace filter rack.
If the furnace, or duct system, is equipped with disposable-type (paper element), air
filters, inspect them every month for an excessive accumulation of dust and dirt.
Replace disposable air filters at least twice a year. Make certain the replacement filter is
the same size as the one being replaced. The filter size is marked on the outer edge of
the air filter. Install the filter with the arrow marked on the filter pointing toward the
furnace.
Oil Burner
NOTICE: A qualified heating contractor MUST service the oil burner in this
furnace at least once a year.
Generally, service to the burner will involve a thorough inspection and cleaning of the
burner, replacement of the oil nozzle and oil filter, and readjustment of the burner to
achieve proper ignition and clean combustion.
Blower and Motor
NOTICE: The fan motor has sealed bearings that do NOT require lubrication.
The blower and fan motor will not normally require any service. This furnace is
equipped with a directly-driven blower. Therefore, it will not require any retensioning or
replacement of a drive belt.
Heat Exchanger
c CAUTION: DO NOT attempt to clean the heat exchanger unless electrical power
and fuel flow to the furnace are turned off and the furnace is at room temperature.
c CAUTION: The combustion chamber refractory material is fragile and can be
easily damaged. If the inner radiator of the heat exchanger is cleaned, avoid
scraping or hitting the walls of the combustion chamber.
CAUTION: Do not brush or scrape the surface of the combustion chamber. It can be
easily damaged.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTICE: A qualified heating contractor MUST inspect the heat exchanger in this
furnace at least once a year. If heavy deposits are found, immediate cleaning is
required.
All heat exchanger surfaces should be as clean as possible for the most efficient
operation of the furnace. The heat exchanger may require cleaning after every heating
season, as combustion of fuel oil tends to produce soot, particulate matter, and scale,
due to corrosion. These materials coat the inner walls of the heat exchanger. This
coating reduces the heat transfer effectiveness of the heat exchanger and can hinder
the flow of flue gases from the furnace.
NOTICE: Accumulation of heavy soot deposits over one heating season may
indicate the oil burner is out of adjustment.
The heat exchanger may be inspected and cleaned through two (2) access, or cleanout,
ports located in the burner compartment, on highboy and lowboy models, or protruding
through the front casing panel, on the horizontal/counterflow model. Each cleanout port
consists of a 2-inch O.D. tube closed by a pressed-in cap, refer to Figure 9.
Figure 9: Location and Design of the Highboy Heat Exchanger Cleanout Ports
Using a screwdriver, or a large pair of adjustable jaw pliers, remove each cleanout port
cap. With the aid of a portable light source, peer into the heat exchanger. As much as
possible, loosen all material and deposits clinging to the heat exchanger walls using
wire brushes, or any suitable tool. Collect and remove this material by hand or with the
assistance of a vacuum cleaner and a nozzle-type attachment.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
The heat exchanger may also be cleaned through the flue pipe connection. With the
furnace turned off and at room temperature, carefully remove the vent connector and
the heat exchanger flue pipe, if equipped, to inspect and clean the heat exchanger.
The inner radiator of the heat exchanger may be cleaned from the inside of the
combustion chamber. This involves removal of the burner and the burner mounting
plate from the heat exchanger.
Using a portable light source with a mirror inserted through and into the heat exchanger,
check for an accumulation of soot, scale, and particulate matter on the walls and in the
base of the drum, or on the floor of the combustion chamber. If a significant
accumulation is present, it should be removed. Use a flexible wire brush to loosen the
deposits on the heat exchanger walls. Remove any loose foreign material using a
vacuum cleaner.
Replace all gaskets, if removed, with new (unused) gaskets. Reassemble the burner
mounting plate, burner flange, and new gaskets in the reverse order they were
removed. A rubber mallet, or equivalent tool, may be useful for reinstalling the caps in
the cleanout tubes.
Flue and Chimney
At least once a year, thoroughly inspect the heat exchanger flue pipe, the vent
connector, the chimney, or vent, and the barometric damper for signs of sagging, loose
connections, excessive corrosion, and deterioration. Clean, repair, or replace any
components for continued safe and proper operation of the furnace.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
USERS INFORMATION
c WARNING:
• The area around the furnace should be kept free and clear of flammable vapors,
liquids, and material, especially papers and rags.
• NEVER burn garbage or refuse in the furnace. NEVER try to ignite oil by tossing
burning papers or other material into the furnace.
• This oil furnace is designed to burn No. 2 distillate fuel (home heating) oil ONLY.
NEVER USE GASOLINE OR A MIXTURE OF OIL AND GASOLINE.
• DO NOT attempt to make repairs to the furnace yourself!
Operating Instructions
For your safety, read this information before operating this furnace.
c WARNING: Failure to follow these instructions may result in fire or explosion
causing property damage, personal injury, or loss of life.
WHAT TO DO IN THE EVENT OF AN OIL LEAK:
• Do not try to operate this or any other nearby appliance.
• If present, close the manual oil shutoff valve on the fuel oil supply line.
• Immediately call a qualified heating contractor for service.
• If you cannot reach a qualified heating contractor, call the fuel oil supplier of the
fire department.
DO NOT use this furnace if any component was underwater. Immediately call a
qualified heating contractor to inspect the furnace and replace any part of the furnace
control system that was underwater.
This furnace does not have a pilot light. It is equipped with an electronic ignition system
that automatically lights the burner. DO NOT attempt to light the burner by hand.
TO OPERATE THIS FURNACE:
1) Adjust the room thermostat to the lowest setpoint and set the operating mode, if
equipped, to “OFF”.
2) Turn off all electric power to the furnace at the disconnecting switch.
3) Turn the manual oil shutoff valve to the open or “ON” position.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
4) This furnace is equipped with an electronic ignition system that automatically
lights the burner. DO NOT try to light the burner by hand.
5) Turn on the electric power to the furnace at the disconnecting switch.
6) Adjust the room thermostat to the desired setpoint and set the operating mode, if
equipped, to “HEAT”.
7) If the furnace will not operate, call a qualified heating contractor for service.
TO INTERRUPT (STOP) OPERATION OF THIS FURNACE:
1) Adjust the room thermostat to the lowest setpoint and set the operating mode, if
equipped, to “OFF”.
2) If service will be performed, turn off all electric power to the furnace at the
disconnecting switch.
3) Turn the manual oil shutoff valve to the closed or “OFF” position.
Oil Supply
• If available, the use of ultra-low or low sulfur (less than 0.0015% S and 0.0015 -
0.05% S, by weight, respectively), no. 2 fuel oil is highly recommended. Low
sulfur fuel oil can help to significantly reduce instances of blockage and corrosion of
the oil burner fuel delivery system, including the nozzle, the furnace heat exchanger,
and the flue gas vent system. These benefits can appreciably decrease or eliminate
service calls due to poor fuel quality. Air pollutants emitted by the furnace as well as
the typical malodorous smell of oil combustion will also be reduced. Consult your fuel
oil supplier about the availability of low-sulfur, fuel oil.
• DO NOT allow the fuel tank to run completely dry during the heating season. If the
fuel tank runs completely dry, it may be necessary to purge the oil lines of trapped
air. If necessary, contact a qualified heating contractor to bleed the oil lines and
restart the burner.
• During the warmer weather, keep the tank full to prevent condensation of moisture
on the inside surface of the tank. The presence of moisture in the tank is beneficial
to the growth of biological fuel contaminants (bacteria, mold, fungus, yeast, etc.).
• Keep the cap on the fuel tank fill pipe tightly closed at all times to prevent the
entrance of moisture, foreign matter, insects, etc. Consider adding a guard or filter to
the tank vent pipe to reduce the entrance of water and foreign matter into the tank.
Also, check the tank, vent, and fill pipe for cracks and leaks. Have any necessary
tank repairs performed ASAP.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
• Annually, have a bottom sample from the fuel oil tank taken for analysis. If present
in excessive quantities, sludge and water should be removed. Fuel oil additives may
be of benefit in helping to resolve some problems that are indicated by the analysis.
In severe cases, tank cleaning may be required. Consult your fuel oil supplier for
recommendations.
Extended Shutdown
If the furnace will be shutdown for an extended period of time:
1) Adjust the room thermostat to the lowest set point and set the operating mode, if
equipped, to “OFF”.
2) Open the disconnecting switch serving the furnace.
3) Close the manual oil shutoff valve.
4) To promote smooth startup and nuisance free operation, fuel oil quality must be
maintained at a high level. In cases where biological contamination of the fuel oil
tank is evident or suspected, consider treating the fuel oil with a biocide approved
for fuel oil applications. In addition, for non-low sulfur fuel oils, an antioxidant
additive may be beneficial in promoting fuel stability. After adding any fuel oil
treatment, completely fill the oil tank to promote mixing of the additive with the
fuel.
Combustion and Ventilation Air Supply
The furnace and venting system require a generous amount of clean air to operate
safely. Lack of adequate combustion and ventilation air can result in erratic operation of
the burner, noisy and poor combustion, sooting of the combustion chamber, and fuel
odors in the air. Never block off or restrict the supply of air to the furnace.
Inspection Areas
Burner Compartment: On the highboy and lowboy furnace models, the burner
compartment can be inspected by removing the front door of the furnace. Look for signs
of excessive heat, such as discoloration of components, damage to material from rust or
corrosion, soot or carbon build-up, and evidence of fuel oil leakage.
Exterior Of Furnace: The exterior of the furnace should be inspected for signs of
excessive heat such as discoloration of materials and damage from rust or corrosion.
Confirm the base or frame supporting the furnace in level and in sound condition.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting System: The furnace flue pipe, vent connector, barometric damper, and
chimney should be inspected for:
• Signs of excessive rust, corrosion pitting, and holes.
• Signs of condensation or moisture leakage (sometimes indicated by soot or
condensate streaks).
• Evidence of structural damage, and loose or disconnected piping joints.
• Presence animal nests.
• Free movement of the vane of the barometric damper without binding or
interference.
If any problems are evident, call a qualified heating contractor for assistance.
NOTICE: A qualified heating contractor MUST service the oil burner and inspect
the heat exchanger in this furnace at least once a year.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A: SOURCES FOR REFERENCED STANDARDS
1. Air Conditioning Contractors of America
1712 New Hampshire Avenue, N.W.
Washington, D.C. 20009
2. American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc.
1791 Tullie Circle N.E.
Atlanta, Georgia 30329
3. National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02269
40
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B: ELECTRICAL DIAGRAMS
41
Download from Www.Somanuals.com. All Manuals Search And Download.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX C: SPECIFICATION SHEETS
Crown Furnace Oil-Fired Highboy Furnace Specifications
Model
CHB 68-112
119,000 105,000
Heat Input Rate (BTUH):
140000 *
115000 *
84,000
70,000
Nominal Thermal Efficiency (%):
Heating Capacity (BTUH):
Nominal Temp. Rise (deg. F.):
Minimum AFUE Rating (%):
Gross Heat Exchange Area (sq. ft.):
Casing Height (in.):
83.6
98,000
87,000
85
82.4
27.8
58
22.25
31
Casing Width (in):
Casing Depth (in.):
6
Nominal Flue Outlet Dia. (in.):
Height from Floor to Center of Flue (in.):
Supply Air Outlet Size (in. x in.):
Return Air Inlet Size (in. x in.):
Air Filter Quantity & Size (in. x in.):
Approx. Shipping Weight (lb.):
Electrical Requirements (VAC/Hz/Ph):
Total Current (Amps.):
53.5 (flue opens upward)
20 x 20
23.5 x 13 (installer must cut opening in lower side casing)
one, 16 x 25
260
120 / 60 / 1
10.2 (w/ R.W. Beckett oil burner)
15
Max. Fuse Size (Amps.):
Directly-driven, DWDI, FC centrifugal, w/ 10 in. dia. wheel
Blower Specifications:
Blower Motor Size (HP):
1/2
Permanent split capacitor, 4
Motor Type & Number of Speeds:
High Speed Airflow (SCFM) @ 0.4 in.
W.G. External Static Pressure:
1350
R.W. Beckett pressure atomizing type, Model AF (Standard)
R.W. Beckett pressure atomizing type, Model NX (Alternate)
Carlin Combustion pressure atomizing type, Model EZ-1HP (Alternate)
Riello pressure atomizing type, Model 40-F3 (Alternate)
5.875, effective
Burner Specifications:
Air Tube Length (in.):
Fixed, flame retention
Burner Head Type:
# 2 distillate (domestic heating oil)
Fuel Type:
Nozzle Rating for Beckett AF (GPH):
Nozzle Rating for Beckett NX (GPH):
Nozzle Rating for Carlin EZ-1HP (GPH):
Nozzle Rating for Riello 40-F3 (GPH):
Spray Angle (Deg.) **:
1.00
0.85
0.85
0.90
0.85
0.65
0.75
0.80
0.75
0.60
0.65
0.70
0.60
0.50
0.50
0.55
80 / 60 / 60 / 60
Hollow / Semi Solid / Hollow / Hollow
130 / 150 / 140 / 150
Interrupted, Direct Spark
None
Spray Pattern **:
Oil Pump Pressure (PSIG) **:
Ignition Control Type:
Pre/Post Purge Feature(s):
Automatic Oil Solenoid Valve:
Combustion Chamber Type:
None
Preformed, refractory (ceramic fiber matrix material)
Clearances to Combustible Materials
(Minimums)
Sides (in.):
Top (in.):
Front (in.):
Rear (in.):
Flue/Vent Pipe (in.):
Supply Plenum Surfaces (in.):
3
3
8
3
9
3
* with Riello 40-F3 burner the maximum heat input rate is 133,000 BTUH. The corresponding heating
capacity will be approx. 109,000 BTUH.
** with Beckett AF burner / with Beckett NX burner / with Carlin EZ-1HP burner / with Riello 40-F3 burner
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Crown Furnace Oil-Fired Lowboy Furnace Specifications
CLBF 68-112 (Front Flue) or CLBR 68-112 (Rear Flue)
Model
Heat Input Rate (BTUH):
Nominal Thermal Efficiency (%):
Minimum Heating Capacity (BTUH):
Nominal Temp. Rise (deg. F.):
Minimum AFUE Rating (%):
Gross Heat Exchange Area (sq. ft.) ** :
Casing Height (in.):
140000 *
119,000
105,000
84,000
84.2
114000 *
98,000
87,000
70,000
85
82.0
27.8 (front flue) / 30.0 (rear flue)
41.5
22.25
Casing Width (in):
47
Casing Depth (in.):
6
37.5 (front flue opens upward)
31 (rear flue exits horizontally rearward)
20 x 20
Nominal Flue Outlet Dia. (in.):
Height from Floor to Center of Flue (in.):
Supply Air Outlet Size (in. x in.):
Return Air Inlet Size (in. x in.):
20 x 12.5
Air Filter Quantity & Size (in. x in.):
two, 10 x 20 ea.
300
120 / 60 / 1
10.2 (w/ R.W. Beckett oil burner)
15
Approx. Shipping Weight (lb.):
Electrical Requirements (VAC/Hz/Ph):
Total Current (Amps.):
Max. Fuse Size (Amps.):
Directly-driven, DWDI, FC centrifugal, w/ 10 in. dia. wheel
1/2
Blower Specifications:
Blower Motor Size (HP):
Permanent split capacitor, 4
1400
Motor Type & Number of Speeds:
High Speed Airflow (SCFM) @ 0.4 in.
W.G. External Static Pressure:
R.W. Beckett pressure atomizing type, Model AF (Standard)
R.W. Beckett pressure atomizing type, Model NX (Alternate)
Carlin Combustion pressure atomizing type, Model EZ-1HP (Alternate)
Riello pressure atomizing type, Model 40-F3 (Alternate)
5.875, effective
Burner Specifications:
Air Tube Length (in.):
Fixed, flame retention
Burner Head Type:
# 2 distillate (domestic heating oil)
Fuel Type:
Nozzle Rating for Beckett AF (GPH):
Nozzle Rating for Beckett NX (GPH):
Nozzle Rating for Carlin EZ-1HP (GPH):
Nozzle Rating for Riello 40-F3 (GPH):
Spray Angle (Deg.) *** :
1.00
0.85
0.85
0.90
0.85
0.65
0.75
0.80
0.75
0.60
0.65
0.70
0.60
0.50
0.50
0.55
80 / 60 / 60 / 60
Hollow / Semi Solid / Hollow / Hollow
130 / 150 / 140 / 150
Interrupted, Direct Spark
None
Spray Pattern ***:
Oil Pump Pressure (PSIG) *** :
Ignition Control Type:
Pre/Post Purge Feature(s):
Automatic Oil Solenoid Valve:
Combustion Chamber Type:
None
Preformed, refractory (ceramic fiber matrix material)
Clearances to Combustible Materials
(Minimums)
3
Sides (in.):
3
Top (in.):
8 (front flue) / 3 (rear flue)
Front (in.) ** :
3
9
3
Rear (in.):
Flue/Vent Pipe (in.):
Supply Plenum Surfaces (in.):
* with Riello 40-F3 burner the maximum heat input rate is 133,000 BTUH. The corresponding heating
capacity will be approx. 109,000 BTUH.
** for front flue model / for rear flue model
*** with Beckett AF burner / with Beckett NX burner / with Carlin EZ-1HP burner / with Riello 40-F3 burner
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Crown Furnace Oil-Fired Horizontal/Counterflow Furnace Specifications
Model
CHC 68-96
Heat Input Rate (BTUH):
119,000
98,000
105,000
84.2
86,000
85
82.0
27.8
84,000
69,000
Nominal Thermal Efficiency (%):
Minimum Heating Capacity (BTUH):
Nominal Temp. Rise (deg. F.):
Minimum Efficiency Rating (AFUE):
Gross Heat Exchange Area (sq. ft.):
22.25 (in horizontal configuration)
61.25 [in counterflow (vertical) configuration]
61.25 (in horizontal configuration)
22.25 [in counterflow (vertical) configuration]
Casing Height (in.):
Casing Width (in.):
22.25
Casing Depth (in.):
6
Nominal Flue Outlet Dia. (in.):
11 (in horizontal configuration, flue exits horizontally forward)
30.5 [in counterflow (vertical) configuration, flue exits horizontally
Height from Floor to Center of Flue (in.):
16 x 16
16 x 16
Supply Air Outlet Size (in. x in.):
Return Air Inlet Size (in. x in.):
Air Filter Quantity & Size (in. x in.):
Approx. Shipping Weight (lb.):
None Supplied
280
Electrical Requirements (VAC/Hz/Ph):
120 / 60 / 1
10.2 (w/ R.W. Beckett oil burner)
15
Total Current (Amps.):
Max. Fuse Size (Amps.):
Directly-driven, DWDI, FC centrifugal, w/ 10 in. dia. wheel
Blower Specifications:
1/2
Blower Motor Size (HP):
Permanent split capacitor, 4
Motor Type & Number of Speeds:
High Speed Airflow (SCFM) @ 0.4 in.
W.G. External Static Pressure:
1350
R.W. Beckett pressure atomizing type, Model AF (Standard)
R.W. Beckett pressure atomizing type, Model NX (Alternate)
Carlin Combustion pressure atomizing type, Model EZ-1HP (Alternate)
Riello pressure atomizing type, Model 40-F3 (Alternate)
5.875, effective
Burner Specifications:
Air Tube Length (in.):
Fixed, flame retention
Burner Head Type:
# 2 distillate (domestic heating oil)
Fuel Type:
Nozzle Rating for Beckett AF (GPH):
Nozzle Rating for Beckett NX (GPH):
Nozzle Rating for Carlin EZ-1HP (GPH):
Nozzle Rating for Riello 40-F3 (GPH):
Spray Angle (Deg.)*:
Spray Pattern *:
Oil Pump Pressure (PSIG)*:
Ignition Control Type:
0.85
0.65
0.75
0.80
0.75
0.60
0.65
0.70
0.60
0.50
0.50
0.55
80 / 60 / 60 / 60
Hollow / Semi solid / Hollow / Hollow
130 / 150 / 140 / 150
Interrupted, Direct Spark
None
Pre/Post Purge Feature(s):
Automatic Oil Solenoid Valve:
Combustion Chamber Type:
None
Preformed, refractory (ceramic fiber matrix material)
Clearances to Combustible Materials
(Minimums)
3
3
Sides (in.):
Top (in.):
22
3
Front (in.):
Rear (in.):
9
3
Flue/Vent Pipe (in.):
Supply Plenum Surfaces (in.):
* with Beckett AF burner / with Beckett NX burner / with Carlin EZ-1HP burner / with Riello 40-F3 burner
45
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D: REPLACEMENT PARTS
Highboy Model
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Lowboy Front Flue Model
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Lowboy Rear Flue Model
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Horizontal/Counterflow Model
49
Download from Www.Somanuals.com. All Manuals Search And Download.
|