| 	
		 ® 
					BARNES   
					INSTALLATION and OPERATION MANUAL   
					Submersible Non-Clog Pump   
					Explosion Proof, Class I, Groups C & D, Division 1   
					Series: 8XSE-HA   
					20 - 30HP, 870RPM, 60Hz   
					30 - 75HP, 1150RPM, 60Hz   
					100 - 150HP, 1750RPM, 60Hz   
					IMPORTANT!   
					Read all instructions in this manual before operating pump.   
					As a result of Crane Pumps & Systems, Inc., constant product improvement program,   
					product changes may occur. As such Crane Pumps & Systems reserves the right to   
					change product without prior written notification.   
					A Crane Co. Company   
					420 Third Street   
					83 West Drive, Bramton   
					Ontario, Canada L6T 2J6   
					Phone: (905) 457-6223   
					Fax: (905) 457-2650   
					Piqua, Ohio 45356   
					Phone: (937) 778-8947   
					Fax: (937) 773-7157   
					
					Form No. 084841-Rev. H   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SAFETY FIRST!   
					Please Read This Before Installing Or Operating Pump.   
					This information is provided for SAFETY and to PREVENT   
					EQUIPMENT PROBLEMS. To help recognize this information,   
					observe the following symbols:   
					Do not block or restrict discharge hose, as discharge   
					hose may whip under pressure.   
					IMPORTANT! Warns about hazards that can result   
					in personal injury or Indicates factors concerned with   
					assembly, installation, operation, or maintenance which   
					could result in damage to the machine or equipment if   
					ignored.   
					WARNING! - DO NOT wear loose clothing that may   
					become entangled in the impeller or other moving parts.   
					WARNING! - Keep clear of suction and discharge   
					openings. DO NOT insert fingers in pump with power   
					connected.   
					CAUTION ! Warns about hazards that can or will cause minor   
					personal injury or property damage if ignored. Used with symbols   
					below.   
					Always wear eye protection when working on pumps.   
					WARNING ! Warns about hazards that can or will cause serious   
					personal injury, death, or major property damage if ignored. Used   
					with symbols below.   
					Make sure lifting handles are securely fastened each   
					time before lifting. DO NOT operate pump without   
					safety devices in place. Always replace safety devices   
					that have been removed during service or repair.   
					Secure the pump in its operating position so it can not   
					tip over, fall or slide.   
					Hazardous fluids can   
					cause fire or explo-   
					sions, burnes or death   
					could result.   
					Extremely hot - Severe   
					burnes can occur on contact.   
					Hazardous fluids can Hazard-   
					ous pressure, eruptions or ex-   
					plosions could cause personal   
					injury or property damage.   
					DO NOT exceed manufacturers recommendation for   
					maximum performance, as this could cause the motor   
					to overheat.   
					Biohazard can cause   
					serious personal injury.   
					DO NOT remove cord and strain relief. Do not connect   
					conduit to pump.   
					Rotating machinery   
					Amputation or severe   
					laceration can result.   
					Hazardous voltage can   
					shock, burn or cause death.   
					WARNING! Cable should be protected at all times to   
					avoid punctures, cut, bruises and abrasions - inspect   
					frequently. Never handle connected power cords with   
					wet hands.   
					Only qualified personnel should install, operate and repair   
					pump. Any wiring of pumps should be performed by a qualified   
					electrician.   
					WARNING ! - To reduce risk of electrical shock, pumps   
					and control panels must be properly grounded in   
					accordance with the National Electric Code (NEC) or the   
					Canadian Electrical Code (CEC) and all applicable state,   
					province, local codes and ordinances.   
					WARNING! To reduce risk of electrical shock, all wiring   
					and junction connections should be made per the NEC   
					or CEC and applicable state or province and local   
					codes. Requirements may vary depending on usage   
					and location.   
					WARNING! - To reduce risk of electrical shock, always   
					disconnect the pump from the power source before   
					handling or servicing. Lock out power and tag.   
					WARNING! Submersible Pumps are not approved for   
					use in swimming pools, recreational water installations,   
					decorative fountains or any installation where human   
					contact with the pumped fluid is common.   
					WARNING! Operation against a closed   
					discharge valve will cause premature bearing   
					WARNING! Products Returned Must Be Cleaned,   
					Sanitized, Or Decontaminated As Necessary Prior   
					To Shipment, To Insure That Employees Will Not Be   
					Exposed To Health Hazards In Handling Said Material.   
					All Applicable Laws And Regulations Shall Apply.   
					and seal failure on any pump, and on end   
					suction and self priming pump the heat build   
					may cause the generation of steam with resulting dangerous   
					pressures. It is recommended that a high case temperature   
					switch or pressure relief valve be installed on the pump body.   
					Bronze/brass and bronze/brass fitted pumps may   
					contain lead levels higher than considered safe for   
					potable water systems. Lead is known to cause cancer   
					and birth defects or other reproductive harm. Various   
					government agencies have determined that leaded   
					copper alloys should not be used in potable water   
					applications. For non-leaded copper alloy materials of   
					construction, please contact factory.   
					CAUTION ! Never operate a pump with a plug-in type   
					power cord without a ground fault circuit interrupter.   
					CAUTION! Pumps build up heat and pressure   
					during operation-allow time for pumps to cool   
					before handling or servicing.   
					WARNING! - DO NOT pump hazardous materials   
					(flammable, caustic, etc.) unless the pump is specifically   
					designed and designated to handle them.   
					IMPORTANT! - Crane Pumps & Systems, Inc. is not   
					responsible for losses, injury, or death resulting from a   
					failure to observe these safety precautions, misuse or   
					abuse of pumps or equipment.   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SECTION: A - PUMP SPECIFICATIONS   
					DISCHARGE ......................8” NPT, 125 lb. Flange Horizontal   
					LIQUID TEMPERATURE ...104°F (40°C) Continuous   
					VOLUTE .............................Cast Iron ASTM A-48, Class 30   
					with Cast Iron Wear Ring   
					SPEED ...............................870, 1150, 1750 RPM (Nominal)   
					UPPER BEARING:   
					Design ....................Single Row, Ball, Grease Lubricated   
					Load ......................Radial   
					MOTOR HOUSING.............Cast Iron ASTM A-48, Class 30   
					SEAL PLATE ......................Cast Iron ASTM A-48, Class 30   
					IMPELLER:   
					LOWER BEARING:   
					Design .....................Double Row, Ball, Grease Lubricated   
					Load.......................Radial & Thrust   
					Design....................3 Vane, Enclosed with Bronze wear   
					ring and pump out vanes on back   
					MOTOR: Design .................NEMA B, Three Phase Torque Curve   
					Air-Filled, Squirrel Cage Induction   
					side. Dynamically Balanced ISO   
					“UL” Listed for Class I, Groups C &   
					G6.3   
					D, Division 1, Explosion Proof   
					Material .................Cast Iron ASTM A-48, Class 30   
					SHAFT ...............................416 Stainless Steel   
					SQUARE RINGS.................Buna-N   
					HARDWARE .......................300 Series Stainless Steel   
					LIFTING CHAIN..................Yoke, Galvanized   
					PAINT ...............................Air Dry Enamel.   
					SEAL: Design ...................Tandem Mechanical, Oil Filled   
					Reservoir.   
					Material..................Rotating Faces - Carbone   
					Stationary Faces - Ceramic   
					Elastomer - Buna-N   
					Hardware -300 Series Stainless   
					CORD ENTRY.....................25 ft. (7.6 m) Std. Cord. Epoxy   
					Sealed Housing with Secondary   
					Insulation..............Class F.   
					SINGLE PHASE................Capacitor Start/Induction Run.   
					Start Capacitors included with   
					pump assembly. Controls require   
					external overload protection.   
					THREE PHASE.................Dual Voltage 230/460; Requires   
					Overload Protection to be Included   
					in control panel.   
					MOISTURE SENSOR .......Normally Open (N/O), Requires   
					Relay in Control Panel   
					TEMP SENSOR ................Normally Closed (N/C), Requires   
					Relay in Control Panel   
					OPTIONAL EQUIPMENT: Seal Material, Impeller Trims,   
					Additional Cord   
					Pressure Grommet for Sealing and   
					Strain Relief   
					inches   
					(mm)   
					8XSE20048HA - 49.06 (1246)   
					8XSE20058HA - 49.06 (1246)   
					8XSE25048HA - 49.06 (1246)   
					8XSE25058HA - 49.06 (1246)   
					8XSE30048HA - 49.06 (1246)   
					8XSE30058HA - 49.06 (1246)   
					8XSE30046HA - 49.06 (1246)   
					8XSE30056HA - 49.06 (1246)   
					8XSE40046HA - 49.06 (1246)   
					8XSE40056HA - 49.06 (1246)   
					8XSE50046HA - 49.06 (1246)   
					8XSE50056HA - 49.06 (1246)   
					8XSE60046HA - 49.06 (1246)   
					8XSE60056HA - 49.06 (1246)   
					8XSE75046HA - 54.50 (1384)   
					8XSE75056HA - 54.50 (1384)   
					8XSE100044HA - 54.50 (1384)   
					8XSE100054HA - 54.50 (1384)   
					8XSE125044HA - 54.50 (1384)   
					8XSE125054HA - 54.50 (1384)   
					8XSE150044HA - 54.50 (1384)   
					8XSE150054HA - 54.50 (1384)   
					IMPORTANT !   
					1.) MOISTURE AND TEMPERATURE SENSORS MUST BE CONNECTED TO VALIDATE THE UL LISTING.   
					2.) A NON-SPARKING BREAK AWAY FITTING MUST BE USED TO VALIDATE THE UL LISTING.   
					3.) A SPECIAL MOISTURE SENSOR RELAY IS REQUIRED IN THE CONTROL PANEL FOR PROPER OPERATION OF THE MOISTURE SENSORS.   
					CONTACT BARNES PUMPS FOR INFORMATION CONCERNING MOISTURE SENSING RELAYS FOR CUSTOMER SUPPLIED CONTROL PANELS.   
					4.) THESE PUMPS ARE UL LISTED FOR PUMPING WATER AND WASTEWATER. DO NOT USE TO PUMP FLAMMABLE LIQUIDS.   
					5.) INSTALLATIONS SUCH AS DECORATIVE FOUNTAINS OR WATER FEATURES PROVIDED FOR VISUAL ENJOYMENT MUST BE INSTALLED IN   
					ACCORDANCE WITH THE NATIONAL ELECTRIC CODE ANSI/NFPA 70 AND/OR THE AUTHORITY HAVING JURISDICTION. THIS PUMP IS NOT   
					INTENDED FOR USE IN SWIMMING POOLS, RECREATIONAL WATER PARKS, OR INSTALLATIONS IN WHICH HUMAN CONTACT WITH PUMPED   
					MEDIA IS A COMMON OCCURRENCE.   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				C-1.1) Submergence:   
					SECTION B: GENERAL INFORMATION   
					It is recommended that the pump be operated in the   
					submerged condition and the sump liquid level should never   
					be less than dimension “A” in Figure 1. The time required   
					to draw the well down from top of motor to the minimum   
					submergence level should not be greater than 15 minutes.   
					NOTE: Outer shaft seal must be in liquid when motor is   
					operated, whether motor is submerged or in air.   
					B-1) To the Purchaser:   
					Congratulations! You are the owner of one of the finest pumps   
					on the market today. CP&S pumps are products engineered   
					and manufactured of high quality components. Over one   
					hundred years of pump building experience along with a   
					continuing quality assurance program combine to produce a   
					pump which will stand up to the toughest applications. This   
					manual will provide helpful information concerning installation,   
					maintenance, and proper service guidelines.   
					B-2) Receiving:   
					Recommended Submergence   
					Level   
					Upon receiving the pump, it should be inspected for damage   
					or shortages. If damage has occurred, file a claim immediately   
					with the company that delivered the pump. If the manual   
					is removed from the packaging, do not lose or misplace.   
					B-3) Storage:   
					Short Term- CP&S Pumps are manufactured for efficient   
					performance following short inoperative periods in storage.   
					For best results, pumps can be retained in storage, as factory   
					assembled, in a dry atmosphere with constant temperatures   
					for up to six (6) months.   
					Minimum Submergence Level   
					A = 12”   
					Long Term - Any length of time exceeding six (6) months,   
					but not more than twenty-four (24) months. The unit should   
					be stored in a temperature controlled area, a roofed over   
					walled enclosure that provides protection from the elements   
					(rain, snow, wind-blown dust, etc.), and whose temperature   
					can be maintained between +40 deg. F and +120 deg. F.   
					(4.4 - 49°C). Pump should be stored in its original shipping   
					container. On initial start up, rotate impeller by hand to   
					assure seal and impeller rotate freely. If it is required that   
					the pump be installed and tested before the long term   
					storage begins, such installation will be allowed provided:   
					Bottom of Feet   
					FIGURE 1   
					C-2) Discharge:   
					Discharge piping should be as short as possible. Both a   
					check valve and a shut-off valve are recommended for   
					each pump being used. The check valve is used to prevent   
					backflow into the sump. Excessive backflow can cause   
					flooding and/or damage to the pump. The shut-off valve   
					is used to stop system flow during pump or check valve   
					servicing.   
					1.) The pump is not installed under water for more than   
					one (1) month.   
					2.) Immediately upon satisfactory completion of the test,   
					the pump is removed, thoroughly dried, repacked in the   
					original shipping container, and placed in a temperature   
					controlled storage area.   
					WARNING ! - These pumps are suitable for   
					application in CLASS I, GROUPS C & D,   
					HAZARDOUS LOCATIONS and require a non-   
					sparking break away fitting. Failure to use the   
					non-sparking BAF voids warranty.   
					B-4) Service Centers:   
					For the location of the nearest Barnes Service Center, check   
					your Barnes representative or Crane Pumps & Systems, Inc.,   
					Service Department in Piqua, Ohio, telephone (937) 778-8947   
					or Crane Pumps & Systems Canada, in Brampton, Ontario,   
					(905) 457-6223.   
					Barnes Pumps, Inc. supplies a Non-Sparking break away   
					fitting discharge system designed to allow the submersible   
					wastewater pump to be installed or removed without requiring   
					personnel to enter the wet well.   
					Place the Break Away Fitting (BAF) in position. Temporarily   
					secure the guide rails in the upper mounting brackets and   
					locate the base elbow on the bottom of the wet well. Level the   
					base elbow with grout and/or shims. Install the intermediate   
					support brackets, if required. Make sure the rails are in a true   
					vertical position so the pump will clear the access opening   
					and will slide freely down the rails into place on the discharge   
					base elbow. once the rails are in proper alignment, bolt the   
					base elbow into the floor of the station and connect the   
					discharge pipe to the elbow. Connect the movable portion   
					and other supplied fittings of the BAF onto the pump and   
					lower into wet well. See the Break Away Fitting manual for   
					more information.   
					SECTION C: INSTALLATION   
					C-1) Location:   
					These self-contained pumping units are Listed for Class I,   
					Groups C & D, Division 1 locations and are recommended   
					for use in a sump, lift station or basin. This pump is designed   
					for submerged continuous duty (15 minutes duty in air   
					at nameplate horsepower), pumping sewage, effluent,   
					wastewater or other nonexplosive or noncorrosive liquids not   
					above 104°F (40°C). Never install the pump in a trench, ditch   
					or hole with a dirt bottom; the legs will sink into the dirt and   
					the suction will become plugged.   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				If a rigid conduit is used to install the pump it must meet   
					Class I, Division 1 requirements of the National Electrical   
					Code. Conduit must be stainless steel or coated metal,   
					resistant to sewage water.   
					C-4.2) Control Cable:   
					The cord assembly mounted to the pump must not be   
					modified in any way except for shortening to a specific   
					application. Any splice between the pump and the control   
					panel must be made in accordance with all applicable electric   
					codes. It is recommended that a junction box (if used) with   
					seal fittings be mounted outside the sump or be of at least   
					Nema 7 (EEMAC-7) explosion proof construction if located   
					within the wet well. A UL listed seal fitting MUST be used in   
					conduit leaving the hazardous location. DO NOT USE THE   
					CONTROL CABLE TO LIFT PUMP.   
					C-3) Liquid Level Controls: Intrinsically Safe   
					WARNING ! - Level control floats used within the   
					hazardous location, must be in an intrinsically   
					safe control circuit suitable for use in CLASS I,   
					GROUPS C & D, HAZARDOUS LOCATIONS.   
					The level controls are to be supported by a mounting bracket   
					that is attached to the sump wall, cover or junction box. Cord   
					grips are used to hold the cords in place on the mounting   
					bracket. The control level can be changed by loosening   
					the grip and adjusting the cord length as per the plans and   
					specifications. Be certain that the level controls cannot   
					hang up or foul in it’s swing and that the entire pump is still   
					submerged when the level control is in the “Off” mode.   
					C-4.3) Wire Size:   
					If additional cable is required consult a qualified electrician for   
					proper wire size. See table for further electrical information.   
					A Warrick Control® intrinsically safe relay, Series 27, is   
					an acceptable panel mounted relay, providing the relay is   
					properly installed and maintained.   
					The primary (A.C. supply line) circuit is not intrinsically safe,   
					therefore the relay must be located in a “SAFE” location (a   
					place that is not classified as a hazardous location). The   
					secondary circuit is intrinsically safe, however, any splice   
					must be made in a “SAFE” location and any control cord that   
					is cut or damaged must be replaced immediately.   
					C-3.1) Level Control Float System:   
					It is recommended to use a two float, on and off, level control   
					system. An additional float, incorporated with an alternator   
					switching system will be required for a duplex system. A high   
					level alarm may be required to alert maintenance personnel.   
					A low level cut off may be required to provide system   
					shutdown if the main level control system malfunctions. The   
					off or low level float should be positioned so that the liquid   
					level never drops below the minimum submergence level.   
					THREE PHASE, 200-230 VOLT AC   
					Power Cable   
					Green (Ground)   
					White   
					Motor Lead Number   
					Green   
					2 & 8   
					Red   
					3 & 9   
					Black   
					1 & 7   
					4, 5 & 6 Together   
					C-4) Electrical Connections:   
					WARNING! - All model pumps and control panels   
					must be properly grounded per the National   
					Electric Code or Canadian Electric Code, state,   
					province and local codes. Improper grounding   
					voids warranty.   
					All electrical controls and motor starting equipment must   
					be installed outside the hazardous area unless approved   
					explosion proof controls are used.   
					C-4.1) Power Cable:   
					The cord assembly mounted to the pump must not be   
					modified in any way except for shortening to a specific   
					application. Any splice between the pump and the control   
					panel must be made in accordance with all applicable electric   
					codes. It is recommended that a junction box (if used) with   
					seal fittings be mounted outside the sump or be of at least   
					Nema 7 (EEMAC-7) explosion proof construction if located   
					within the wet well. A UL listed seal fitting MUST be used in   
					conduit leaving the hazardous location. DO NOT USE THE   
					POWER CABLE TO LIFT PUMP.   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				MODEL NO   
					"A"   
					HP VOLT/ Hz RPM NEMA FULL LOCKED CORD CORD CORD O.D.   
					WINDING   
					DIM   
					Ph   
					(Nom) START LOAD ROTOR SIZE TYPE ± .02 (.5) RESISTANCE   
					CODE AMPS   
					AMPS   
					141.0   
					109.0   
					174.0   
					139.2   
					199.0   
					159.0   
					210.0   
					168.0   
					282.0   
					226.0   
					322.0   
					258.0   
					409.0   
					315.0   
					534.0   
					427.0   
					703.0   
					562.0   
					864.0   
					691.0   
					1080.0   
					864.0   
					in (mm)   
					0.985 (25)   
					0.985 (25)   
					0.985 (25)   
					0.985 (25)   
					0.985 (25)   
					0.985 (25)   
					0.985 (25)   
					0.985 (25)   
					1.125 (29)   
					1.125 (29)   
					1.350 (34)   
					1.350 (34)   
					1.550 (39)   
					1.550 (39)   
					1.550 (39)   
					1.550 (39)   
					1.680 (43)   
					1.680 (43)   
					1.930 (49)   
					1.930 (49)   
					2.070 (53)   
					2.070 (53)   
					MAIN   
					.76   
					8XSE20048HA   
					8XSE20058HA   
					8XSE25048HA   
					8XSE25058HA   
					8XSE30048HA   
					8XSE30058HA   
					8XSE30046HA   
					8XSE30056HA   
					8XSE40046HA   
					8XSE40056HA   
					8XSE50046HA   
					8XSE50056HA   
					8XSE60046HA   
					8XSE60056HA   
					8XSE75046HA   
					8XSE75056HA   
					8XSE100044HA   
					8XSE100054HA   
					8XSE125044HA   
					8XSE125054HA   
					8XSE150044HA   
					8XSE150054HA   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					49.06   
					54.50   
					54.50   
					20   
					20   
					25   
					25   
					30   
					30   
					460/3   
					575/3   
					460/3   
					575/3   
					460/3   
					575/3   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					60   
					870   
					870   
					G 
					G 
					G 
					G 
					F 
					27.8   
					22.0   
					36.5   
					28.8   
					43.0   
					34.4   
					40.0   
					32.0   
					52.0   
					42.6   
					67.0   
					53.6   
					76.9   
					61.4   
					92.0   
					73.6   
					123.0   
					98.4   
					153.0   
					122.0   
					182.0   
					145.0   
					8/4   
					8/4   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					SOW   
					1.21   
					.52   
					870   
					8/4   
					870   
					8/4   
					870   
					8/4   
					.42   
					.66   
					.36   
					.58   
					.30   
					.47   
					.25   
					.38   
					.17   
					.27   
					.13   
					.23   
					.08   
					.12   
					.05   
					.08   
					.05   
					.07   
					870   
					F 
					8/4   
					30 460/3   
					30 575/3   
					40 460/3   
					40 575/3   
					50 460/3   
					50 575/3   
					60 460/3   
					60 575/3   
					75 460/3   
					75 575/3   
					1150   
					1150   
					1150   
					1150   
					1150   
					1150   
					1150   
					1150   
					1150   
					1150   
					1750   
					1750   
					1750   
					1750   
					1750   
					1750   
					G 
					G 
					G 
					G 
					F 
					8/4   
					8/4   
					6/4   
					6/4   
					4/4   
					F 
					4/4   
					F 
					2/4   
					F 
					2/4   
					G 
					G 
					G 
					G 
					F 
					2/4   
					2/4   
					54.50 100 460/3   
					54.50 100 575/3   
					54.50 125 460/3   
					54.50 125 575/3   
					54.50 150 460/3   
					54.50 150 575/3   
					1/4   
					1/4   
					2/0/4   
					2/0/4   
					3/0/4   
					3/0/4   
					F 
					E 
					E 
					Moisture and Temperature sensor cord for all models is 18/5 SOW, 0.485 (12.3mm) ± .02 (.51mm) O.D.   
					Winding Resistance ± 5%. Winding resistance measured in OHMS @ 25°C. (Between Lines)   
					Pump rated for operation at ± 10% voltage at motor.   
					THREE PHASE, 460 VOLT AC   
					Power Cable   
					Green(Ground)   
					Black   
					White   
					Red   
					Motor Lead Number   
					Green   
					1 
					2 
					MOISTURE AND TEMPERATURE SENSORS   
					Control Cable   
					Black   
					Lead Number   
					P1 (Temperature Sensor)   
					P2 (Temperature Sensor)   
					W1 (Moisture Sensor)   
					W2 (Moisture Sensor)   
					Ground   
					White   
					Red   
					3 
					4 & 7 Together   
					5 & 8 Together   
					6 & 9 Together   
					Orange   
					Green   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				WARRANTY NOTE: Both the temperature   
					sensor and moisture detection system must   
					be connected to the motor circuitry such that   
					the motor will be de-energized or sound alarm   
					if excessive motor temperatures are reached   
					and/or if water is detected in the seal chamber   
					and/or motor chamber. Failure to have the above   
					mentioned systems installed and operative,   
					nullifies warranty.   
					a. Proper grounding per NEC.   
					b. A temperature sensing circuit (see Fig. 2A & B)   
					c. A moisture detection circuit with continuity test   
					circuit (see Fig. 3)   
					d. An intrinsically safe level control system.   
					e. A main power manual disconnect and lock out.   
					f. A motor starter and overload system.   
					g. Single phase only, requires a capacitor power   
					pack (see Fig. 2B).   
					C-4.4) Overload Protection:   
					Control panels for single phase pumps MUST be purchased   
					The normally closed (N/C) thermal sensor is embedded in the from the factory and it is advisable that all three phase control   
					motor windings and will detect excessive heat in the event   
					an overload condition occurs which will then trip and stop the   
					pump. The thermal sensor leads marked P1 and P2 MUST   
					be connected in series with the stop button of the pilot circuit   
					of the magnetic motor controller located in the control panel   
					so that the thermostat will open the circuit before dangerous   
					temperatures are reached. A manual momentary start switch   
					is required to prevent the automatic restarting of the motor   
					when the thermostat resets. For a typical wiring diagram,   
					refer to Fig. 2. In the event of an overload, the source of this   
					panels are also purchased from the factory.   
					SECTION: D START-UP OPERATION   
					D-1) Check Voltage and Phase:   
					Before operating pump, compare the voltage and phase   
					information stamped on the pump’s identification plate to the   
					available power.   
					D-2) Check Pump Rotation:   
					condition should be determined and rectified before the pump Before putting pump into service for the first time, the motor   
					is put back into normal operation. DO NOT LET THE PUMP rotation must be checked. Improper motor rotation can   
					CYCLE OR RUN IF AN OVERLOAD CONDITION OCCURS! result in poor pump performance and can damage the motor   
					and/or pump. To check the rotation, suspend the pump   
					If current through the temperature sensor exceeds the values   
					listed, an intermediate control circuit relay must be used to   
					reduce the current or the sensor will not work properly.   
					freely, momentarily apply power and observe the “kickback”.   
					“Kickback” should always be in a counter-clockwise direction   
					as viewed from the top of the pump motor housing.   
					D-2.1) Incorrect Rotation for Three-Phase Pumps:   
					In the event that the rotation is incorrect for a three-phase   
					installation, interchange any two power cable leads at the   
					control box. DO NOT change leads in the cable housing   
					in the motor. Recheck the “kickback” rotation again by   
					momentarily applying power.   
					TEMPERATURE SENSOR ELECTRICAL RATING   
					VOLTS   
					CONTINUOUS   
					AMPERES   
					INRUSH   
					AMPERES   
					110-120   
					220-240   
					440-480   
					3.00   
					1.50   
					0.75   
					30.0   
					15.0   
					7.5   
					D-2.3) Test Procedure For Moisture Sensor Control:   
					With a Warrick moisture detection control, type 2800, a   
					normally closed push button and neon indicating lamp is   
					provided as a means of checking the moisture sensing   
					components. When the push button is depressed, the   
					indicating lamp will be illuminated to indicate (A) power is   
					supplied to the control, (B) the control is operative, and (C)   
					wiring to the moisture sensing probes in the motor is intact.   
					This procedure should be performed periodically to confirm   
					integrity of the circuit.   
					C-4.5 Moisture Sensors:   
					A normally open (N/O) detector is installed in the pump seal   
					chamber, which will detect any moisture present, and a   
					continuity test resistor built into the motor. The test resistor   
					is rated 1 watt at 330K ohms. The moisture sensors MUST   
					be connected to moisture detector control, which includes a   
					continuity test circuit, see Fig. 3 for typical wiring diagram.   
					The normally closed (N/C) contact of the moisture detector   
					MUST be connected in series with the stop button of the   
					pilot circuit of the magnetic motor controller. A Warrick   
					moisture detection control, Type 2800 is an acceptable   
					control if properly installed and maintained. Wiring must be   
					provided from the moisture detector sensor probe leads of   
					the motor designated W1 and W2 to terminals 9 and 10 of   
					the 2800-XXX control. Terminal pair 1-2 must be continuously   
					energized from an A-C supply line of electrical characteristics   
					shown on the data table. In the event of moisture detection,   
					the pump should be pulled and the source of the failure   
					located and repaired. IF MOISTURE DETECTION HAS   
					OCCURRED, SCHEDULE MAINTENANCE AS SOON AS   
					POSSIBLE!   
					D-3) Start-Up Report:   
					Included at the end of this manual are two start-up report   
					sheets, these sheets are to be completed as applicable.   
					Return one copy to Barnes Pumps, Inc. and store the second   
					in the control panel or with the pump manual if no control   
					panel is used. It is important to record this data at initial start-   
					up since it will be useful to refer to should servicing the pump   
					be required in the future.   
					D-3.1) Identification Plate:   
					Record the numbers from the pump’s identification plate on   
					both START-UP REPORTS provided at the end of the manual   
					for future reference.   
					C-4.6) Control Panel and Electrical System:   
					The control panel and the electrical system MUST be   
					properly designed and wired to include at least, but not   
					limited to the following;   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TYPICAL THERMAL PROTECTION   
					WIRING DIAGRAM   
					FIGURE 2   
					FIGURE 3   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				D-3.2) Insulation Test:   
					NOTE: If impeller (7) is replaced, also replace impeller ring   
					(8). If only the impeller ring (8) requires replacing, split the   
					ring and remove, be careful not to damage impeller.   
					Before the pump is put into service, an insulation (megger)   
					test should be performed on the motor. The resistance values   
					(ohms) as well as the voltage (volts) and current (amps)   
					should be recorded on the start-up report.   
					To remove Impeller (7), removing cap screw (10) (or nut)   
					and washer (9) (and spring washer (11) if so equipped). The   
					impeller is keyed onto the shaft with a square key (6) and   
					to remove, pull impeller straight off the shaft using a wheel   
					puller if required. Inspect gasket (1H) if suction cover (1E)   
					has been removed, and replace if cut or damaged. Before   
					reinstallation, check the motor shaft and impeller bore for   
					damage.   
					D-3.3) Pump-Down Test:   
					After the pump has been properly wired and lowered into the   
					basin, sump or lift station, it is advisable to check the system   
					by filling with liquid and allowing the pump to operate through   
					it’s pumping cycle. The time needed to empty the system, or   
					pump-down time along with the volume of water, should be   
					recorded on the start-up report.   
					F-1.2) Reassembly:   
					To install wear ring (1F) first apply retaining compound to the   
					bore of suction cover (1E) and then press wear ring (1F) into   
					bore of suction cover (1E) until seated. Position gasket (1H)   
					on volute, and locate suction cover (1E) on volute (1), apply   
					thread locking compound to socket head screws (1D)ÿand   
					SECTION E: PREVENTATIVE MAINTENANCE   
					As the motor is Air-filled, no lubrication or other maintenance   
					is required, and generally Barnes Pumps will give very   
					reliable service and can be expected to operate for years of   
					normal sewage pumping without failing. However, as with any tighten into volute (1). To install impeller (7), first apply   
					mechanical piece of equipment a preventive maintenance   
					program is recommended and suggested to include the   
					following checks:   
					retaining compound to groove at bottom of impeller and press   
					impeller ring (8) on impeller (7), then apply a thin film of oil   
					to motor shaft and slide impeller straight onto shaft, keeping   
					keyways lined up. Drive key (6) into keyway. Locate spacer   
					(9), and Lock-spring washer (11) on shaft, apply thread   
					locking compound to cap screw (10) threads, thread cap   
					screw (10) into shaft and torque to 35 ft. lbs. Rotate impeller   
					to check for binding.   
					1) Test moisture detector control “Test Switch” for   
					continuity of circuit. Water in the seal chamber will   
					energize a seal leak warning light at the control panel.   
					This is a warning light only and does not stop the motor.   
					It indicates the seal has leaked and must be repaired.   
					This should be done within 2 or 3 weeks to prevent   
					further damage. See section D-2.3.   
					2) Inspect impeller and body for excessive build-up or   
					clogging and repair as required per section F-1.   
					3) Inspect outer shaft sealÿand replace as required per   
					section F-2.   
					Install impeller and motor assembly over studs and onto   
					volute (1). Apply thread locking compound to threads of each   
					stud (3). Position lockwasher (5) on studs (3) and thread   
					nut (4) onto stud (3) and torque to 24 ft. lbs. Check for free   
					rotation of motor and impeller.   
					4) Check motor for ground leakage and proper amp draw.   
					Motor and inner seal repair per section F-3.   
					F-2) Outer Shaft Seal Service:   
					SECTION F: SERVICE AND REPAIR   
					NOTE: All item numbers in ( ) refer to Figures 7 & 8.   
					CAUTION! - Handle seal parts with extreme care.   
					DO NOT scratch or mar lapped surfaces.   
					WARNING ! - Electrical power to the pump motors   
					must be disconnected and locked out to prevent   
					any dangerous electrical hazards or personnel   
					danger before any service work is done to the   
					pump.   
					CAUTION ! - Operating pump builds up   
					heat and pressure; allow time for pump to   
					cool to room temperature before handling   
					or servicing.   
					F-1) Impeller and Volute Service:   
					F-1.1) Disassembly and Inspection:   
					To clean out the pump body (1), or clean out or replace   
					impeller (7), or replace wear ring (1F) and impeller ring (8),   
					disconnect power, remove hex nuts (5) and vertically lift motor   
					assembly from the pump body (1), and then lift out back plate   
					(12). Clean out the pump body, if necessary, examine wear   
					ring (1F) and replace if worn. If the wear ring (1F) requires   
					replacing, split the wear ring (1F) and remove, be careful not   
					to damage the suction cover (1E). Clean and examine impeller   
					(7) for pitting or wear, also check impeller ring (8) for scaring or   
					excessive wear, replace if required.   
					FIGURE 4   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				F-2.1) Disassembly and Inspection:   
					F-3) Motor & Inner Shaft Seal Service   
					To expose outer shaft seal (13) for examination, remove   
					Impeller and Volute per Section F-1.1. Set motor assembly   
					(2) in the up position to prevent loss of oil. Remove snap   
					ring from motor shaft, then retaining ring (13D), spring (13C)   
					and rotating member (13B) from shaft, See Fig. 4. Examine   
					all seal parts and especially contact faces. Inspect seal for   
					signs of wear such as uneven wear pattern on stationary   
					members, chips and scratches on either seal face. DO NOT   
					interchange seal components, replace the entire shaft seal   
					(13). If replacing seal, remove stationary (13A) from mounting   
					plate by prying out with flat screw driver.   
					The XSE Submersible Pump motor is manufactured by   
					Reliance Electric Co. and must be serviced and repaired by   
					Reliance approved service centers only.   
					For lead reconnection information, contact Reliance Electric   
					Co., giving motor serial number.   
					WARNING ! - These motors are U/L Listed   
					for application in CLASS I, GROUPS C & D   
					EXPLOSION PROOF Environments. All repairs,   
					other than lead reconnects and outer seal   
					replacement, shall be performed by an authorized   
					reliance service facility. Any other repairs   
					performed by the customer or NON-RELIANCE   
					SERVICE Facilities negates the U/L Listing and   
					motor warranty.   
					F-2.2) Reassembly:   
					Lightly oil (DO NOT use grease) outer surface of stationary   
					member (13A). Press stationary member (13A) firmly into   
					mounting plate using a seal pusher, nothing but the seal   
					pusher is to come in contact with seal face (see Fig. 5).   
					SECTION: G REPLACEMENT PARTS   
					G-1 ORDERING REPLACEMENT PARTS:   
					When ordering replacement parts, ALWAYS furnish the   
					following information:   
					IMPORTANT ! - DO NOT hammer on the seal   
					pusher- it will damage the seal face.   
					Stationary Member (13A)   
					Polished Face Out   
					1. Pump serial number and date code. (Paragraph G-4)   
					2. Pump model number. (Paragraph G-3)   
					3. Pump part number. (Paragraph G-2)   
					4. Part description.   
					5. Item part number.   
					6. Quantity required.   
					7. Shipping instructions.   
					8. Billing Instructions.   
					Motor Mounting Plate   
					Seal Pusher   
					FIGURE 5   
					Make sure the stationary member is in straight and that   
					the rubber ring is not out of it’s groove. Lightly oil (DO NOT   
					use grease) shaft and inner surface of bellows on rotating   
					member (13B) see Fig. 6. With lapped surface of rotating   
					member (13B) facing inward toward stationary member   
					(13A), slide rotating member (13B) onto shaft using a seal   
					pusher, until lapped faces of (13A) and (13B) are together.   
					(see Fig. 4).   
					Reliance Motor   
					Rotating Member (13B)   
					G-2 PART NUMBER:   
					Stationary   
					The part number consists of a six (6) digit number, which   
					appears in the catalog. A one or two letter suffix may follow this   
					number to designate the design configuration. This number is   
					used for ordering and obtaining information.   
					G-3 MODEL NUMBER:   
					This designation consists of numbers and letters which   
					represent the discharge size, series, horsepower, motor phase   
					and voltage, speed and pump design. This number is used for   
					ordering and obtaining information.   
					Seal Pusher   
					Bullet   
					FIGURE 6   
					IMPORTANT! - It is extremely important to keep   
					seal faces clean during assembly. Dirt particles   
					lodged between these faces will cause the seal to   
					leak.   
					G-4 SERIAL NUMBER:   
					The serial number block will consist of a six digit number,   
					which is specific to each pump and may be preceded by   
					a alpha character, which indicates the plant location. This   
					number will also be suffixed with a four digit number, which   
					indicates the date the unit was built (Date Code). EXAMPLE:   
					A012345 0490.   
					Place spring (13C) over shaft and in place on rotating   
					member (13B), making sure it is seated on retainer and not   
					cocked or resting on bellows tail. Slide retaining ring (13B)   
					over shaft and let rest on spring (13C). Assemble impeller   
					and volute as outlined in paragraph F-1.2.   
					Reference the six digit portion (Serial Number) of this number   
					when referring to the product.   
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TROUBLE SHOOTING   
					CAUTION ! Always disconnect the pump from the electrical power source before handling.   
					If the system fails to operate properly, carefully read instructions and perform maintenance recommendations.   
					If operating problems persist, the following chart may be of assistance in identifying and correcting them:   
					MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER.   
					NOTE: Not all problems and corrections will apply to each pump model.   
					PROBLEM   
					CAUSE   
					CORRECTION   
					Pump will not run   
					1. Poor electrical connection, blown fuse,   
					tripped breaker or other interruption of power,   
					improper power supply.   
					2. Motor or switch inoperative (to isolate   
					cause, go to manual operation of pump).   
					2a. Float movement restricted.   
					1. Check all electrical connections for   
					security. Have electrician measure current   
					in motor leads, if current is within ±20%   
					of locked rotor Amps, impeller is probably   
					locked. If current is 0, overload may be   
					tripped. Remove power, allow pump to cool,   
					2b. Switch will not activate pump or is defective. then recheck current.   
					2c. Defective motor   
					2a. Reposition pump or clean basin as   
					3. Insufficient liquid level.   
					required to provide adequate clearance for   
					float.   
					Pump will not turn off   
					2a. Float movement restricted.   
					2b. Disconnect level control. Set ohmmeter   
					for a low range, such as 100 ohms full scale   
					and connect to level control leads. Actuate   
					level control manually and check to see that   
					ohmmeter shows zero ohms for closed switch   
					and full scale for open switch. (Float Switch).   
					2c. Check winding insulation (Megger Test)   
					and winding resistance. If check is outside   
					of range, dry and recheck. If still defective,   
					replace per service instructions.   
					3. Make sure liquid level is at least equal to   
					suggested turn-on point.   
					4. Recheck all sizing calculations to   
					determine proper pump size.   
					5. Check discharge line for restrictions,   
					including ice if line passes through or into   
					cold areas.   
					6. Remove and examine check valve for   
					proper installation and freedom of operation.   
					7. Open valve.   
					8. Check impeller for freedom of operation,   
					security and condition. Clean impeller and   
					inlet of any obstruction.   
					9. Loosen union slightly to allow trapped air   
					to escape.Verify that turn-off level of switch   
					is set so that the suction is always flooded.   
					Clean vent hole.   
					10. Check rotation. If power supply is three   
					phase, reverse any two of three power supply   
					leads to ensure proper impeller rotation..   
					11. Repair fixtures as required to eliminate   
					leakage.   
					2b. Switch will not activate pump or is defective.   
					4. Excessive inflow or pump not properly sized   
					for application.   
					9. Pump may be airlocked   
					14. H-O-A switch on panel is in “HAND” position   
					Pump hums but does not run   
					1. Incorrect voltage   
					8. Impeller jammed or loose on shaft, worn or   
					damaged, impeller cavity or inlet plugged.   
					Pump delivers insufficient capacity   
					1. Incorrect voltage.   
					4. Excessive inflow or pump not properly sized   
					for application.   
					5. Discharge restricted.   
					6. Check valve stuck closed or installed backwards.   
					7. Shut-off valve closed.   
					8. Impeller jammed or loose on shaft, worn or   
					damaged, impeller cavity or inlet plugged.   
					9. Pump may be airlocked.   
					10. Pump running backwards   
					Pump cycles too frequently or runs   
					periodically when fixtures are not in use   
					6. Check valve stuck closed or installed   
					backwards.   
					11. Fixtures are leaking.   
					15. Ground water entering basin.   
					Pump shuts off and turns on indepen-   
					dent of switch, (trips thermal overload   
					protector). CAUTION! Pump may start   
					unexpectedly. Disconnect power supply.   
					1. Incorrect voltage.   
					4. Excessive inflow or pump not properly sized   
					for application.   
					8. Impeller jammed, loose on shaft, worn or   
					damaged, impeller cavity or inlet plugged.   
					12. Excessive water temperature.   
					(internal protection only)   
					Pump operates noisily or vibrates   
					excessively   
					2c. Worn bearings, motor shaft bent.   
					5. Debris in impeller cavity or broken impeller   
					10. Pump running backwards   
					13. Piping attachments to buiding structure too   
					rigid or too loose.   
					12. Check pump temperature limits & fluid   
					temperature.   
					13. Replace portion of discharge pipe with   
					flexible connector.   
					14. Turn to automatic position.   
					15. Check for leaks around basin inlet and   
					outlets.   
					12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIGURE 7   
					13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIGURE 8   
					14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				PARTS LIST   
					ITEM   
					1 
					QTY   
					1 
					1 
					4 
					4 
					8 
					1 
					1 
					2 
					1 
					1 
					8 
					16   
					8 
					16   
					8 
					16   
					1 
					PART NO.   
					084851   
					079698   
					005810   
					014256   
					079380   
					079190   
					079369   
					078994   
					079587   
					See Table 1   
					079379   
					079379   
					038519   
					038519   
					15-21-1   
					15-21-1   
					079381   
					DESCRIPTION   
					Volute Assembly   
					Volute   
					1A   
					1B   
					1C   
					1D   
					1E   
					1F   
					1G   
					1H   
					2 
					* 
					* 
					* 
					* 
					* 
					* 
					* 
					* 
					Nipple   
					Nipple Cap   
					Soc. Hd. Screw   
					Suction Cover   
					Wear Ring   
					Dowel Pin   
					Gasket   
					Motor (See Note: 1)   
					Stud   
					Stud   
					Lockwasher   
					Lockwasher   
					Hex Nut   
					Hex Nut   
					Key   
					5/8-11 x 1” Lg Stainless   
					Bronze   
					3 
					5/8 x 3” Lg Stainless   
					5/8 x 3” Lg Stainless   
					5/8 Stainless   
					20HP - 60HP   
					75HP - 150HP   
					20HP - 60HP   
					75HP - 150HP   
					20HP - 60HP   
					75HP - 150HP   
					4 
					5 
					5/8 Stainless   
					5/8-11 Stainless   
					5/8-11 Stainless   
					1/2 Sq x 3” Lg Stainless   
					6 
					7 
					1 
					Impeller, Cast Iron   
					14.50” Dia.   
					14.38” Dia.   
					14.25” Dia.   
					14.12” Dia.   
					14.00” Dia.   
					13.88” Dia.   
					13.75” Dia.   
					13.62” Dia.   
					13.50” Dia.   
					13.38” Dia.   
					13.25” Dia.   
					13.12” Dia.   
					13.00” Dia.   
					12.88” Dia.   
					12.75” Dia.   
					12.62” Dia.   
					12.50” Dia.   
					12.38” Dia.   
					12.25” Dia.   
					12.12” Dia.   
					12.00” Dia.   
					11.88” Dia.   
					11.75” Dia.   
					11.62” Dia.   
					11.50” Dia.   
					11.38” Dia.   
					11.25” Dia.   
					11.12” Dia.   
					11.00” Dia.   
					10.88” Dia.   
					10.75” Dia.   
					10.62” Dia.   
					10.50” Dia.   
					083723   
					75HP-1150   
					60HP-1150   
					50HP-1150   
					083723TA   
					083723TB   
					083723TC   
					083723TD   
					083723TE   
					083723TF   
					083723TG   
					083723TH   
					083723TJ   
					083723TK   
					083723TL   
					083723TM   
					083723TN   
					083723TP   
					083723TQ   
					083723TR   
					083723TS   
					083723TT   
					083723TU   
					083723TV   
					083723TW   
					083723TX   
					083723TY   
					083723TZ   
					083723UA   
					083723UB   
					083723UC   
					083723UD   
					083723UE   
					083723UF   
					083723UG   
					083723UH   
					150HP-1750   
					30HP-870, 40HP-1150, 125HP-1750   
					25HP-870, 30HP-1150   
					100HP-1750   
					20HP-870   
					Bronze   
					20 to 60 HP   
					75 to 135 HP   
					8 
					9 
					1 
					1 
					1 
					1 
					1 
					1 
					079377   
					079588   
					079376   
					1-111-1   
					Impeller Ring   
					Impeller Washer,   
					Stainless   
					Stainless   
					3/4-10 x 2” Lg Stainless   
					10   
					11   
					Hex Hd. Cap Screw, 20 to 60HP   
					(Supplied with Motor) Nut, 75 to 135HP   
					1-1/2-12 Stainless   
					75 to 135HP   
					052699   
					Lock-Spring Washer , 20 to 60HP   
					3/4 Steel   
					(Not Used)   
					079191   
					12   
					13   
					1 
					1 
					Back Plate   
					085980   
					084259   
					085981   
					085982   
					Outer Seal (See Note: 2)   
					Outer Seal (See Note: 2)   
					(OPTIONAL, Pump End)   
					(OPTIONAL, Pump End)   
					Carbon/Ceramic/Buna-N (STD)   
					Carbon/Ceramic/Buna-N (STD)   
					Tungsten/Carbide/Buna-N   
					Tungsten/Carbide/Buna-N   
					20HP - 60HP   
					75HP - 150HP   
					20HP - 60HP   
					75HP - 150HP   
					14   
					15   
					5Ft.   
					3 
					625-01583   
					625-00826   
					Chain   
					Cold Shut   
					.375 Steel   
					.437   
					16   
					1 
					124823   
					Adapter (Used with 360 Frame/320 Flange Motor)   
					15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TABLE 1 - MOTOR WITH VARIOUS CORD LENGTHS   
					PUMP MODEL   
					25FT   
					30FT   
					40FT   
					50FT   
					75FT   
					100FT   
					8XSE20048HA   
					8XSE20058HA   
					8XSE25048HA   
					8XSE25058HA   
					8XSE30048HA   
					8XSE30058HA   
					8XSE30046HA   
					8XSE30056HA   
					8XSE40046HA   
					8XSE40056HA   
					8XSE50046HA   
					8XSE50056HA   
					8XSE60046HA   
					8XSE60056HA   
					8XSE75046HA   
					8XSE75056HA   
					8XSE100044HA   
					8XSE100054HA   
					8XSE125044HA   
					8XSE125054HA   
					8XSE150044HA   
					8XSE150054HA   
					079688   
					095171   
					079689   
					095172   
					079690   
					095173   
					083725   
					092836   
					079691   
					092835   
					079692   
					092834   
					079591   
					093644   
					079693   
					092833   
					079378   
					092831   
					079694   
					092832   
					079874   
					092830   
					079688XC   
					095171XC   
					079689XC   
					095172XC   
					079690XC   
					095173XC   
					083725XC   
					092836XC   
					079691XC   
					092835XC   
					079692XC   
					092834XC   
					079591XC   
					093644XC   
					079693XC   
					092833XC   
					079378XC   
					092831XC   
					079694XC   
					092832XC   
					079874XC   
					092830XC   
					079688XE   
					095171XE   
					079689XE   
					095172XE   
					079690XE   
					095173XE   
					083725XE   
					092836XE   
					079691XE   
					092835XE   
					079692XE   
					092834XE   
					079591XE   
					093644XE   
					079693XE   
					092833XE   
					079378XE   
					092831XE   
					079694XE   
					092832XE   
					079874XE   
					092830XE   
					079688XF   
					095171XF   
					079689XF   
					095172XF   
					079690XF   
					095173XF   
					083725XF   
					092836XF   
					079691XF   
					092835XF   
					079692XF   
					092834XF   
					079591XF   
					093644XF   
					079693XF   
					092833XF   
					079378XF   
					092831XF   
					079694XF   
					092832XF   
					079874XF   
					092830XF   
					079688XH   
					095171XH   
					079689XH   
					095172XH   
					079690XH   
					095173XH   
					083725XH   
					092836XH   
					079691XH   
					092835XH   
					079692XH   
					092834XH   
					079591XH   
					093644XH   
					079693XH   
					092833XH   
					079378XH   
					092831XH   
					079694XH   
					092832XH   
					079874XH   
					092830XH   
					079688XL   
					095171XL   
					079689XL   
					095172XL   
					079690XL   
					095173XL   
					083725XL   
					092836XL   
					079691XL   
					092835XL   
					079692XL   
					092834XL   
					079591XL   
					093644XL   
					079693XL   
					092833XL   
					079378XL   
					092831XL   
					079694XL   
					092832XL   
					079874XL   
					092830XL   
					NOTE: 1 Standard motor includes, 25 foot power and control cables, moisture & temperature sensors and   
					carbon/ceramic/buna-n Inner & Outer shaft seals.   
					NOTE: 2 When ordering motor (item 2), Outer seal is supplied. Item 13 is for Outer seal replacement ONLY.   
					When ordering outer seal, furnish Reliance motor serial number.   
					16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMPORTANT!   
					WARRANTY REGISTRATION   
					Your product is covered by the enclosed Warranty.   
					Complete the Warranty Registration Form and return to   
					Crane Pumps & Systems, Inc. Warranty Service Group   
					If you have a claim under the provision of the warranty, contact your local   
					Crane Pumps & Systems, Inc. Distributor.   
					RETURNED GOODS   
					RETURN OF MERCHANDISE REQUIRES A “RETURNED GOODS AUTHORIZATION”.   
					CONTACT YOUR LOCAL CRANE PUMPS & SYSTEMS, INC. DISTRIBUTOR.   
					Products Returned Must Be Cleaned, Sanitized,   
					Or Decontaminated As Necessary Prior To Shipment,   
					To Insure That Employees Will Not Be Exposed To Health   
					Hazards In Handling Said Material. All Applicable Laws   
					And Regulations Shall Apply.   
					17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				BARNES®   
					Limited Warranty   
					We warrant to our immediate customer and to the ultimate consumer that products of our manufacture will be free of   
					defects in material and workmanship under normal use and service for the following time periods, when installed and   
					maintained in accordance with our instructions.   
					Pump Products: One (1) year from date of installation or (24) twenty-four months from date of shipment, whichever occurs   
					first. Cleaning Products: Twelve (12) months from date of installation or eighteen (18) months from date of shipment,   
					whichever occurs first. As used herein, “the ultimate consumer” is defined as the purchaser who first uses the product   
					after its initial installation or, in the case of product designed for non permanent installation, the first owner who used   
					the product. It is the purchaser’s or any sub-vendee’s obligation to make known to the ultimate consumer the terms and   
					conditions of this warranty. This warranty gives you specific legal rights, and there may also be other rights which vary   
					from state to state. In the event the product is covered by the Federal Consumer Product Warranties Law (1) the duration   
					of any implied warranties associated with the product by virtue of said law is limited to the same duration as stated herein,   
					(2) this warranty is a LIMITED WARRANTY, and (3) no claims of any nature whatsoever shall be made against us, until the   
					ultimate consumer, his successor, or assigns, notifies us in writing of the defect, and delivers the product and/or defective   
					part(s) freight prepaid to our factory or nearest authorized service station. Some states do not allow limitations on how long   
					an implied warranty lasts, so the above limitation may not apply. THE SOLE AND EXCLUSIVE REMEDY FOR BREACH   
					OF ANY AND ALL WARRANTIES WITH RESPECT TO ANY PRODUCT SHALL BE TO REPLACE OR REPAIR AT OUR   
					ELECTION, F.O.B. POINT OF MANUFACTURE OR AUTHORIZED REPAIR STATION, SUCH PRODUCTS AND/OR   
					PARTS AS PROVEN DEFECTIVE. THERE SHALL BE NO FURTHER LIABILITY, WHETHER BASED ON WARRANTY,   
					NEGLIGENCE OR OTHERWISE. Unless expressly stated otherwise, guarantees in the nature of performance   
					specifications furnished in addition to the foregoing material and workmanship warranties on a product manufactured   
					by us, if any, are subject to laboratory tests corrected for field performance. Any additional guarantees, in the nature of   
					performance specifications must be in writing and such writing must be signed by our authorized representative. Due to   
					inaccuracies in field testing if a conflict arises between the results of field testing conducted by or for user, and laboratory   
					tests corrected for field performance, the latter shall control. Components or accessories supplied by us but manufactured   
					by others are warranted only to the extent of and by the terms and conditions of the original manufacturer’s warranty.   
					RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FROM SYSTEMS ANALYSES AND   
					EVALUATIONS WE CONDUCT WILL BE BASED ON OUR BEST AVAILABLE EXPERIENCE AND PUBLISHED   
					INDUSTRY INFORMATION. SUCH RECOMMENDATIONS DO NOT CONSTITUTE A WARRANTY OF SATISFACTORY   
					PERFORMANCE AND NO SUCH WARRANTY IS GIVEN.   
					This warranty shall not apply when damage is caused by (a) improper installation, (b) improper voltage (c) lightning (d)   
					sand or other abrasive material (e) scale or corrosion build-up due to excessive chemical content. Any modification of the   
					original equipment will also void the warranty. We will not be responsible for loss, damage or labor cost due to interruption   
					of service caused by defective parts. Neither will we accept charges incurred by others without our prior written approval.   
					This warranty is void if our inspection reveals the product was used in a manner inconsistent with normal industry practice   
					and\or our specific recommendations. The purchaser is responsible for communication of all necessary information   
					regarding the application and use of the product. UNDER NO CIRCUMSTANCES WILL WE BE RESPONSIBLE FOR   
					ANY OTHER DIRECT OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOST PROFITS, LOST   
					INCOME, LABOR CHARGES, DELAYS IN PRODUCTION, IDLE PRODUCTION, WHICH DAMAGES ARE CAUSED   
					BY ANY DEFECTS IN MATERIAL AND\OR WORKMANSHIP AND\OR DAMAGE OR DELAYS IN SHIPMENT. THIS   
					WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTY, INCLUDING ANY   
					WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.   
					No rights extended under this warranty shall be assigned to any other person, whether by operation of law or otherwise,   
					without our prior written approval.   
					A Crane Co. Company   
					420 Third Street   
					83 West Drive, Bramton   
					Ontario, Canada L6T 2J6   
					Phone: (905) 457-6223   
					Fax: (905) 457-2650   
					Piqua, Ohio 45356   
					Phone: (937) 778-8947   
					Fax: (937) 773-7157   
					
					18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Notes   
					19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Notes   
					20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				START-UP REPORT   
					FOR SUBMERSIBLE PUMPS   
					This form is designed to provide assurance that customer service and a quality product are the number one priority with   
					Crane Pumps & Systems, Inc (CP&S). Please fill out the following questions as completely and accurate as possible.   
					When complete, mail this form to:   
					In U.S.A Send To:   
					In Canada Send To:   
					Crane Pumps & Systems, Inc   
					Attn: Warranty Service Group   
					420 Third Street   
					Crane Pumps & Systems, Inc.   
					Attn: Service Manager   
					83 West Drive, Brampton   
					Ontario, Canada L6T 2J6   
					Piqua, Ohio 45356   
					REPORTS THAT ARE NOT RETURNED CAN DELAY OR VOID WARRANTY.   
					Pump Owner’s Name:   
					Address:   
					Location of Installation   
					Person in Charge   
					Phone   
					Purchased From (Crane Pumps & Systems Representative/Distributor   
					Pump Model   
					Part Number   
					Serial No.   
					Voltage   
					Phase   
					Hertz   
					Horespower   
					Rotation: Direction of impeller rotation (Use C/W for clockwise, CC/W for counter-clockwise)   
					Method used to check rotation (viewed from bottom)   
					Does impeller turn freely by hand:   
					Yes   
					No   
					Condition of equipment   
					Condition of cable jacket   
					Resistance of cable jacket   
					Good   
					Good   
					Good   
					Fair   
					Fair   
					Fair   
					Poor   
					Poor   
					Poor   
					Resistance of cable and pump motor (measured at pump control)   
					Red-Black Ohms, Red-White Ohms, White-Black   
					Resistance of Ground Circuit between Control Panel and outside of pump   
					MEG Ohms check of insulation:   
					Ohms   
					Ohms   
					Red to Ground   
					White to Ground   
					Black to Ground   
					Muddy   
					Condition of equipment at Start-Up: Dry   
					Was Equipment Stored?   
					Wet   
					Length of Storage   
					Describe station layout   
					Liquid being pumped   
					Debris in bottom of station?   
					Was debris removed in your presence?   
					Are guide rails exactly vertical?   
					Is BAF stationary installed level?   
					Liquid level controls: Model   
					Are level controls installed away from turbulence?   
					Operation Check:   
					Tip lowest float (Stop Float), All pumps should remain off.   
					Tip second float (and Stop Float), one pump comes On.   
					Tip third float (and Stop Float), both pumps on (alarm on simplex).   
					Tip fourth float (and Stop Float), high level alarm on (omit on simplex).   
					If not CP&S level controls, describe type of controls   
					Does liquid level ever drop below volute top?   
					21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CP&S control panel part no. and brand   
					Number of pumps operated by control panel   
					NOTE: At no time should holes be made in top of control panel, unless proper sealing devices are utilized.   
					Control panel manufactured by others   
					Company name   
					Model number   
					Short circuit protection   
					Type   
					Number and size of short circuit device(s)   
					Overload type   
					Amp rating   
					Amp rating   
					Size   
					Do protection devices comply with pump and motor Amp rating?   
					Are all connections tight?   
					Is the interior of the panel dry?   
					ELECTRICAL READINGS:   
					Single Phase:   
					Voltage supply at panel line connection, Pump Off, L1, L2   
					Voltage supply at panel line connection, Pump On, L1, L2   
					Amperage: Load connection, Pump On L1   
					L2   
					Three Phase:   
					Voltage supply at panel line connection, Pump Off, L1 - L2   
					Voltage supply at panel line connection, Pump On, L1 - L2   
					L2 - L3   
					L2 - L3   
					L2   
					L3 - L1   
					L3 - L1   
					L3   
					Amperage: Load connection,   
					Pump On L1   
					FINAL CHECK:   
					Is pump seated on discharge properly?   
					Does check valve(s) operate properly?   
					Check for leaks?   
					Flow, Does station appear to operate at proper rate?   
					Pump down time   
					Low   
					Noise level:   
					Comments:   
					High   
					Medium   
					Equipment difficulties during start-up:   
					MANUALS:   
					Has operator received pump instructions and parts manual?   
					Has operator received electrical control panel diagram?   
					Has operator been briefed on Warranty?   
					Address of local CP&S Representative/Distributor:   
					I have received the above information (Name of Operator)   
					Name of Company   
					Date:   
					Date:   
					I Certify this report to be accurate (Name of Start-Up person)   
					Employed By:   
					Date and time of Start-Up   
					Present at Start-Up   
					( ) Engineer:   
					( ) Operator:   
					( ) Contactor:   
					( ) Other:   
					To be filled out by factory:   
					Start-Up form checked by:   
					Date warranty registration mailed:   
					22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMPORTANT!   
					WARRANTY REGISTRATION   
					Your product is covered by the enclosed Warranty.   
					Complete the Warranty Registration Form and return to   
					Crane Pumps & Systems, Inc. Warranty Service Group   
					If you have a claim under the provision of the warranty, contact your local   
					Crane Pumps & Systems, Inc. Distributor.   
					FOLD HERE AND TAPE, DO NOT STAPLE   
					**IMPORTANT!**   
					WARRANTY REGISTRATION   
					CUSTOMER’S NAME   
					ADDRESS   
					DATE INSTALLED   
					CITY   
					STATE   
					ZIP   
					ZIP   
					PHONE #   
					FAX #   
					DEALER’S NAME   
					CITY   
					STATE   
					MODEL NO.   
					PART NO.   
					SERIAL NO.   
					BRAND   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FOLD HERE AND TAPE, DO NOT STAPLE   
					PLACE   
					STAMP   
					HERE   
					CRANE PUMPS & SYSTEMS, INC.   
					WARRANTY SERVICE GROUP   
					420 THIRD STREET   
					PIQUA, OHIO   
					45356 - U.S.A.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |