Cornelius Refrigerator 000 PLUS User Manual

AURORAR10,000 PLUS  
COOLING UNIT  
Ins tallation Manual  
Part No. 300614000  
November 8, 1989  
Revised: April 12, 1993  
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION  
This Manual must be read and understood before installing or operating this equipment  
PRINTED IN U.S.A  
ÓIMI CORNELIUS INC; 1989-93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS (contd)  
Page  
14  
14  
14  
14  
14  
14  
14  
14  
15  
15  
15  
15  
15  
ADJUSTING CO2 REGULATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
ADJUSTING DISPENSING VALVES WATER FLOW RATE . . . . . . . . . . . . .  
ADJUSTING WATER-TO-SYRUP RATIO OF DISPENSED PRODUCT .  
ADJUSTING SIZE OF DRINK DISPENSED . . . . . . . . . . . . . . . . . . . . . . . . . . .  
REPLENISHING CO2 SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
REPLENISHING SYRUP SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CLEANING AND SANITIZING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
DAILY CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SANITIZING SYRUP SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
COOLING UNIT MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
COOLING UNIT AIR INTAKE AND EXHAUST FILTERS . . . . . . . . . . . . . . . .  
CHECKING ICE WATER BATH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
COOLING UNIT CARBONATOR MAINTENANCE . . . . . . . . . . . . . . . . . . . . .  
DOUBLE LIQUID CHECK VALVE ASSEMBLIES YEARLY MAINTENANCE  
(OR AFTER WATER SYSTEM DISRUPTIONS). . . . . . . . . . . . . . . . . . . . . . . .  
15  
COOLING UNIT CARBONATED WATER CIRCULATING PUMP MOTOR  
LUBRICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
15  
16  
16  
17  
REMOTE CONDENSER COIL AND FAN ASSY MAINTENANCE . . . . . . . . . . . .  
CLEANING CO2 GAS CHECK VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SERVICE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
COOLING UNIT MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
PERIODIC CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CLEANING COOLING UNIT AIR INTAKE AND EXHAUST FILTERS. . . . . .  
PREPARING COOLING UNIT FOR SHIPPING, STORING, OR RELOCATING  
PERIODIC INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
REMOTE CONDENSER COIL AND FAN ASSEMBLY MAINTENANCE . . . . . . .  
CHECKING ICE WATER BATH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CHANGING ICE WATER BATH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
17  
17  
17  
17  
17  
18  
18  
18  
DOUBLE LIQUID CHECK VALVE ASSEMBLIES YEARLY MAINTENANCE  
(OR AFTER WATER SYSTEM DISRUPTIONS) . . . . . . . . . . . . . . . . . . . . . . .  
19  
21  
21  
21  
21  
22  
22  
22  
22  
23  
26  
26  
27  
27  
LUBRICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
PRIMARY CO2 REGULATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SECONDARY CO2 REGULATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WATER FLOW RATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WATER-TO-SYRUP RATIO OF DISPENSED PRODUCT . . . . . . . . . . . . .  
CLEANING AND SANITIZING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
DAILY CLEANING OF UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SANITIZING POST-MIX SYRUP SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . .  
REPLENISHING CO2 SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
REPLENISHING SYRUP SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SYRUP FLAVOR CHANGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CLEANING CO2 SYSTEM GAS CHECK VALVES . . . . . . . . . . . . . . . . . . . . . . . . . .  
SECONDARY CO2 REGULATORS AND CO2 MANIFOLD CO2 GAS  
CHECK VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
27  
300614000  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS (contd)  
Page  
27  
COOLING UNIT CO2 INLET LINE CO2 GAS CHECK VALVE . . . . . . . . . . .  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
30  
WATER-TO-SYRUP RATIO OF DISPENSED DRINK TOO LOW OR TOO  
HIGH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
30  
30  
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW REGULATOR DOES  
NOT INCREASE TO DESIRED WATER-TO-SYRUP RATIO. . . . . . . . . . . . . . . .  
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW REGULATOR DOES  
NOT DECREASE TO DESIRED WATER-TO- SYRUP RATIO’. . . . . . . . . . . . . .  
31  
31  
DISPENSED PRODUCT CARBONATION TOO LOW. . . . . . . . . . . . . . . . . . . . . . .  
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT  
FOAMS IN CUP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
31  
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING  
VALVE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
31  
31  
32  
32  
32  
32  
32  
ONLY CARBONATED WATER DISPENSED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
ONLY SYRUP DISPENSED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WARM PRODUCT BEING DISPENSED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WATER PUMP MOTOR WILL NOT OPERATE. . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WATER PUMP MOTOR WILL NOT SHUT OFF. . . . . . . . . . . . . . . . . . . . . . . . . . . .  
ERRATIC CYCLING OF CARBONATOR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WATER PUMP MOTOR OPERATES BUT WATER PUMP DOES NOT PUMP  
WATER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
33  
33  
33  
WATER PUMP CAPACITY TOO LOW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
COMPRESSOR DOES NOT OPERATE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM  
SUFFICIENT ICE BANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
34  
35  
35  
36  
CONDENSER FAN MOTOR NOT OPERATING . . . . . . . . . . . . . . . . . . . . . . . . . . .  
AGITATOR MOTOR NOT OPERATING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
LIST OF FIGURES  
FIGURE 1. AURORAR10,000 PLUS COOLING UNIT . . . . . . . . . . . . . . . . . . . . . . .  
FIGURE 2. FLOW DIAGRAM (TYPICAL INSTALLATION) . . . . . . . . . . . . . . . . . . .  
FIGURE 3. 240/24VAC POWER TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . .  
FIGURE 4. COOLING UNIT SPACE REQUIRED . . . . . . . . . . . . . . . . . . . . . . . . . . .  
FIGURE 5. PARTS IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
FIGURE 6. LIQUID CHECK VALVE ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . .  
FIGURE 7. CO2 GAS CHECK VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
4
7
10  
20  
22  
26  
FIGURE 8. REFRIGERATION FLOW DIAGRAM (REQUIRES CONNECTION TO  
REMOTE CONDENSER COIL AND FAN ASSY) . . . . . . . . . . . . . . . . . . . . . . . . . .  
28  
29  
FIGURE 9. WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
LIST OF TABLES  
TABLE 1. DESIGN DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
TABLE 2. LOOSE-SHIPPED PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2
5
iii  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL INFORMATION  
IMPORTANT: To the us er of this manual - This manual is a guide for ins talling, operating, and  
maintaining this equipment. Refer to Table of Contents for page location of detailed information  
pertaining to ques tions that aris e during ins tallation, operation, s ervice and maintenance, or  
troubles hooting this equipment.  
GENERAL DESCRIPTION  
This section gives the description, theory of operation, and design data for the AuroraR10,000 Plus Cooling  
Unit, hereafter referred too as a Cooling Unit.  
COOLING UNIT DESCRIPTION  
The Cooling Unit is designed to provide cooled syrup, carbonated water, and plain water to the dispensing  
station through an insulated python (length as ordered). The Cooling Unit refrigeration system is cooled by a  
Remote Condenser Coil and Fan Assembly which is connected to the Cooling Unit.  
The Cooling Unit consists of a refrigeration system with a two horsepower compressor and a Hydro BoostR  
(plain water pre-cooler) which pre-cools plain water on its way to the carbonated water tank. The Cooling Unit  
also consists of a plain water pump. The plain water pump pumps plain water through the Hydro BoostR ,  
through the plain water cooling coils, and into the carbonated water tank. The carbonated water circulating  
pump circulates cold carbonated water from the Cooling Unit to the dispensing station and back to the Cooling  
Unit.  
The cabinet panels are easily removed to facilitate installation and service and maintenance.  
An optional Cooling Unit Stand (P/N 309309000) is available to elevate Cooling Unit up off floor. Also available  
is an Aurora Service System Analyzer (P/N 30919700) that may be used to analyze and troubleshoot the  
Cooling Unit refrigeration system.  
CAUTION: Before s hipping or relocating the Cooling Unit s yrup cooling coils mus t be  
s anitized and all s anitizing s olution mus t be purged from the coils . All water mus t als o be  
purged from the plain and carbonated water s ys tems . A freezing ambient environment will  
caus e res idual s anitizing s olution or water remaining ins ide the Cooling Unit to freeze res ulting in  
damage to internal components .  
FIGURE 1. AURORAR10,000 PLUS COOLING UNIT  
300614000  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1. Des ign Data  
COOLING UNIT DATA  
Model No.  
416654  
Overall Dimensions:  
Height  
25-inches  
36-1/2 inches  
24-1/2 inches  
Width  
Depth  
NOTE: Overall dimens ions if Cooling Unit is placed on optional Cooling Unit Stand (P/N 309309069).  
Height (approximate)  
Width  
Depth  
72-5/16 inches  
37-1/2 inches  
25-3/8 inches  
Weights:  
Shipping  
Dry Weight  
Ice Bank Weight  
385 pounds  
pounds  
40 ± pounds  
Capacities:  
Water Bath (no ice bank)  
18 gallons  
2 HP  
Compressor Horsepower  
Refrigeration System:  
Refrigerant Type and Charge  
See Cooling Unit Nameplate  
Ambient Operating Temp.  
50° F to 100° F  
Electrical Requirements:  
Operating Voltage  
See Cooling  
Unit  
Nameplate  
Current Draw  
REMOTE CONDENSER COIL AND FAN ASS’Y DATA (P/N 309602000)  
Overall Dimensions:  
Height  
27 inches  
22-inches  
38-inches  
Width  
Depth  
Weight:  
Shipping  
85 pounds  
Ambient Operating Temp.  
Electrical Requirements:  
Operating Voltage  
-22° F to 158° F  
208/230VAC, Single Phase,  
60Hz  
Current Draw  
2.5 Amps  
300614000  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM THEORY OF OPERATION  
(see Figure 2)  
A CO2 cylinder delivers carbon dioxide gas (CO2) to primary CO2 regulator assembly which deliver regulated  
CO2 gas to adjustable secondary CO2 regulators. Secondary CO2 regulators delivers regulated CO2 gas to the  
carbonated water tank inside the Cooling Unit and also to the soft drink tanks. Plain water enters the Cooling  
Unit and is pumped through and is pre-cooled by the refrigerated Hydro Boostâ coil. Cooled water continues  
through the plain water cooling coils and into the carbonated water tank. Cold plain water entering the  
carbonated water tank is carbonated by regulated CO2 gas pressure also entering the tank. Carbonated water  
leaves the carbonated water tank and enters the inlet side of the carbonated water circulating pump.  
Carbonated water passes through the carbonated water circulating pump, through the carbonated water cooling  
coil, and exits the Cooling Unit through an insulated python to a turnaround inside the dispensing station.  
Carbonated water returns to the Cooling Unit by passing through the insulated python, through the Cooling Unit  
carbonated water cooling coils, through the carbonated water tank which makes up the carbonated water  
circulating system. As carbonated water is being dispensed from the dispensing station, carbonated water  
circulating system is continuously being replenished from the carbonated water tank.  
Plain water enters through the Cooling Unit two plain water inlet lines, through the plain water cooling coils, and  
exists the Cooling Unit out through insulated python to the dispensing station. Regulated CO2 gas pressure  
exerted upon the soft drinks contents forces syrup from tanks, through Cooling Unit syrup inlet lines, through  
syrup cooling coils, and exists the Cooling Unit out through an insulated python to the dispensing station.  
The Cooling Unit refrigeration system is cooled by a Remote Condenser Coil and Fan Assembly (P/N  
309602000) that is authorized by IMI Cornelius Inc. Use of any other Remote Condenser Coil and Fan  
Assembly must be authorized by IMI Cornelius Inc. Use of an unauthorized Remote Condenser Coil and Fan  
Assembly will automatically void the Cooling Unit factory warranty.  
300614000  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
300614000  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
This section covers unpacking and inspection, selecting location, installing the Cooling Unit and the Remote  
Condenser Coil and Fan Assembly preparing for operation, and operation.  
UNPACKING AND INSPECTION  
NOTE: The Cooling Unit and the Remote Condens er Coil and Fan As s embly were thoroughly ins pected  
before leaving the factory and the carrier has accepted and s igned for them. Any damage or  
irregularities s hould be noted at time of delivery (or not later than 15 days from date of delivery) and  
immediately reported to the delivering carrier. Reques t a written ins pection report from Claims  
Ins pector to s ubs tantiate any neces s ary claim. File claim with the delivering carrier, not with IMI  
Cornelius Inc.  
1. After Cooling Unit has been unpacked, remove shipping tape and other packing material.  
2. Unpack LOOSE-SHIPPED PARTS. Make sure all items are present and in good condition.  
Table 2. Loos e-Shipped Parts  
Name  
Item  
No.  
Part No.  
309852000  
770407  
Qty.  
24  
12  
2
1
Tubing Clamp  
2
Barbed Connector, 1/4 by 3/8  
Barbed Connector, 1/2 by 1/2  
Label, Line Identification  
3
770424  
4
311962000  
1
NOTE: The following Remote Condens er Coil and Fan As s embly and Refrigeration Line Kits are rec-  
ommended for us e with Cooling Unit (P/N 416654000). Refrigeration Lines Kit (as ordered) is us ed to  
connect Condens er Coil and Fan As s embly to the Cooling Unit.  
5
6
309602000  
300598025  
300598050  
Remote Condenser Coil and Fan Assy  
Refrigeration Line Kit, 25-ft. long, 90  
Refrigeration Line Kit, 50-ft. long, 90  
1
1
1
IDENTIFICATION OF LOOSE-SHIPPED PARTS  
1. BARBED CONNECTORS (item 2) used to connect Cooling Unit outlet lines to insulated python lines.  
Connections are secured with TUBING CLAMPS (item 1).  
2. BARBED CONNECTORS (item 3) are used to connect Cooling Unit outlet carbonated water lines to  
insulated python lines.  
3. LABEL, LINE IDENTIFICATION (item 4) to be installed on Cooling Unit and syrup flavors to be recorded in  
proper spaces on label.  
4. REFRIGERATION LINE KIT (items 6) is used to connect REMOTE CONDENSER COIL AND FAN ASSY  
(item 5) to Cooling Unit.  
SELECTING LOCATION  
COOLING UNIT  
Select location for Cooling Unit installation that will (1) Allow the shortest possible insulated python route from  
the Cooling Unit to the Dispensing Station location; (2) Allow the shortest possible refrigeration lines (not to  
exceed 50-ft in length) route from Remote Condenser Coil and Fan Assembly to the Cooling Unit; (3) REFER  
TO THE COOLING UNIT NAMEPLATE FOR THE REQUIRED POWER CIRCUIT OPERATING VOLTAGE, HZ,  
AND THE MINIMUM CIRCUIT AMPACITY OF THE COOLING UNIT. The power circuit for the Cooling Unit  
must be wired through a 40-amp minimum rated disconnect switch (not provided) and the power circuit must be  
5
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fused as indicated on the Unit nameplate. The power circuit may also be wired through an equivalent HACR  
type circuit breaker rather then the disconnect switch. THE POWER CIRCUIT MUST BE MADE UP OF  
COPPER CONDUCTORS AND ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL  
CODES; (4) Close to a plain water source supply line with proper requirements; (5) Sufficient space around  
Cooling Unit (see Figure4) for proper air circulation (18-inches on sides and back, front side open to room, and  
top open to ceiling); (6) Be close to permanent floor drain to route Cooling Unit water tank drain and overflow  
hoses to the floor drain.  
REMOTE CONDENSER COIL AND FAN ASSY  
CAUTION: Remote Condens er Coil and Fan As s emblies authorized by IMI Cornelius Inc.  
(P/N 309602000)  
1. An extreme warm climate installation may require extra caution in Remote Condenser Coil and Fan  
Assembly location. Avoid hot sunny locations and seek shaded area if possible. The use of a structure to  
shade the Unit from direct sun exposure and/or a platform extending Unit an additional 18-inches above  
the rooftop is highly recommended and will improve performance. Ample space must be provided on all  
sides and above Unit for proper air circulation through Unit and also access for service and maintenance.  
DO NOT BLOCK AIR CIRCULATION THROUGH UNIT.  
2. Remote Condenser Coil and Fan Assembly must be installed in level position and must be anchored with  
adequate fastening devices.  
INSTALLING REMOTE CONDENSER COIL AND FAN ASSY  
(see Figure 6)  
1. Remote Condenser Coil and Fan Assembly must be installed meeting requirements of SELECTING  
LOCATION. Remote Condenser Coil and Fan Assembly must be installed in a level position and must be  
anchored with adequate fastening devices.  
2. Route refrigeration lines of REFRIGERATION LINE KIT (item 6) from Remote Condenser Coil and Fan  
Assembly down to Cooling Unit location.  
3. Connect ends of refrigeration lines to Condenser Coil and Fan Assembly refrigeration connectors.  
INSTALLING COOLING UNIT  
NOTE: Cooling Unit outlet lines , plain water, CO2, and s yrup inlet lines , Remote Condens er Coil and  
Fan As s embly refrigeration lines and power circuit cable, and Cooling Unit power circuit cable each  
mus t be long enough when connected to Cooling Unit to allow pulling Unit out approximately  
36-inches from operating pos ition for s ervice and maintenance. When Cooling Unit is in operating  
pos ition, exces s power circuit cable, Remote Condens er Coil and Fan As s embly refrigeration lines and  
power circuit cable and plain water s ource and CO2 inlet lines may be coiled up behind Unit.  
PLACING COOLING UNIT IN LOCATION  
NOTE: An optional Cooling Unit Stand (P/N 309309069) is available to elevate Cooling Unit up and off  
the floor.  
1. Place Cooling Unit in position approximately 36-inches out from operating position to allow access all  
around the Unit.  
2. Remove two screws securing Cooling Unit top cover, then remove cover.  
CONNECTING REMOTE CONDENSER COIL AND FAN ASS’Y REFRIGERATION LINES  
TO COOLING UNIT  
(see Figure 5)  
Connect refrigeration lines, from Remote Condenser Coil and Fan Assembly, to refrigeration connectors on front  
of Cooling Unit.  
300614000  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECTING ELECTRICAL POWER CIRCUIT TO COOLING Unit  
(see Figures 5 and 9)  
IMPORTANT: Before 208/230VAC s ingle-phas e 60Hz electrical power circuit is connected to the cooling  
unit, s ervice power voltage entering the building mus t be identified. Service power voltage entering the  
building will either be 208 or 230VAC and may be pos ted on the main s ervice box. If not, the ins taller  
mus t contact the local electrical power company for information. If thes e two voltage identification  
attempts s hould fail, a voltage reading Mus t be performed. If s ervice power voltage is below 218VAC,  
the red electrical wire connected to the 240VAC terminal on LINE (primary) s ide of the 240/24VAC power  
trans former ins ide the cooling unit s witches electrical control box (s ee Figure 3 and 9) mus t be  
dis connected from the 240VAC terminal and be connected to the 208VAC terminal. If voltage is above  
218VAC, power trans former red electrical wire will remain connected to the 240VAC terminal. If ins taller  
is not s ure of the s ervice power voltage entering the building, leave red electrical wire connected to the  
240VAC terminal on the power trans former. If s ervice power voltage is below 218VAC, proceed as  
follows :  
1. Remove four s crews s ecuring electrical control box cover, then remove cover for acces s to the  
240/24VAC power trans former.  
2. Remove red electrical wire from the 240VAC terminal on LINE (primary) s ide of power trans former  
and connect it to the 208VAC terminal.  
C
208V  
240V  
RESET BUTTON  
FIGURE 3. 240/24VAC POWER TRANSFORMER  
WARNING: Make s ure 40-amp minimum-rated dis connect s witch (not provided) is in OFF’  
pos ition.  
1. Remove cover from electrical handy box on back of Cooling Unit.  
WARNING: The Cooling Unit mus t be electrically grounded to avoid pos s ible fatal electrical  
s hock or s erious injury to the operator. A green ground wire is provided ins ide electrical  
box to connect power circuit ground wire which electrically grounds the Cooling Unit.  
Connect 208/230VAC Single-Phase 60Hz power circuit from 40-amp minimum rated disconnect switch (not  
provided) fused at 40-amps (slow-blow’) to electrical wires inside electrical handy box on back of Cooling Unit.  
COOLING UNIT MUST BE PROPERLY GROUNDED. POWER CIRCUIT MUST BE MADE UP OF COPPER  
CONDUCTORS, AND ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES.  
DO NOT CONNECT ELECTRICAL POWER TO COOLING UNIT AT THIS TIME.  
7
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECTING ELECTRICAL POWER CIRCUIT TO REMOTE CONDENSER COIL AND  
FAN ASSY  
(see Figure 5 and 9)  
CAUTION: The Cooling Unit refrigeration s ys tem is cooled by a Remote Condens er Coil  
and Fan As s embly (P/N 309602000) that is authorized by IMI Cornelius Inc. Us e of an  
unauthorized Remote Condens er Coil and Fan As s embly will automatically void the  
Cooling Unit factory warranty.  
NOTE: Electrical power circuit may be connected to the Remote Condens er Coil and Fan As s embly  
(P/N 309602000) in two ways . The preferred way is to draw electrical power from the cooling unit  
contactor which allows the Remote Condens er Coil and Fan As s embly to operate only when the  
cooling unit refrigeration s ys tem is operating. The optional way is to connect a s eparate electrical  
power circuit (independent of the cooling unit) through an appropriately rated and fus ed dis connect  
s witch or an equivalent HACR circuit breaker which allows the Remote Condens er Coil and Fan  
As s embly to operate at all times (independent of cooling unit operation).  
1. Connect and route electrical power circuit cable from Remote Condenser Coil and Fan Assembly through  
fuse box (not provided), fused at 15-amps (maximum) down to Cooling Unit location. REMOTE  
CONDENSER COIL AND FAN ASSEMBLY MUST BE PROPERLY GROUNDED, POWER CIRCUIT  
MUST BE MADE UP OF COPPER CONDUCTORS, AND ALL WIRING MUST CONFORM TO NATIONAL  
AND LOCAL ELECTRICAL CODES.  
2. Route Remote Condenser Coil and Fan Assembly Power cable electrical wires through electrical handy  
box on back of Cooling Unit to inside of electrical control box.  
3. Connect Remote Condenser Coil and Fan Assembly power cable electrical wires to T1 and T2 terminals on  
contactor inside Cooling Unit electrical control box.  
4. Install electrical control box cover and secure with four screws.  
5. Install cover on electrical handy box on back of Cooling Unit.  
CONNECTING PLAIN WATER INLET SUPPLY LINE TO COOLING UNIT  
(see Figure 2)  
NOTE: IMI Cornelius Inc. recommends that a water s hutoff valve be ins talled in plain water inlet s upply  
line connected to Cooling Unit and that water s upply be filtered. WATER PIPE CONNECTIONS AND  
FIXTURES DIRECTLY CONNECTED TO A POTABLE WATER SUPPLY SHALL BE SIZED, INSTALLED  
AND MAINTAINED ACCORDING TO FEDERAL, STATE, AND LOCAL LAWS.  
CAUTION: Plain water inlet s upply line to Cooling Unit mus t be 1/2-inch I.D. minimum.  
Check water flow rate of water inlet s upply line. MINIMUM FLOW RATE MUST BE AT LEAST  
300-GALLONS PER HOUR. If flow rate is les s than 300-gallons per hour, ‘s tarvingof  
carbonator water pump will occur. Starving will allow water pump to overheat caus ing s afety  
thermos tat on pump outlet to dis rupt electrical power to and s top water pump motor. Carbonated  
water circulating pump overheating could occur if water inlet s upply line flow rate drops below  
300-gallons per hour. INCOMING PLAIN WATER INLET SUPPLY LINE WATER PRESSURE MUST  
REMAIN A MINIMUM OF 10-PSI BELOW THE CARBONATOR CO2 OPERATING PRESSURE.  
(Example: Operating pres s ure is 90-ps i and maximum water pres s ure can be no more than 80-ps i,  
etc.)  
1. Before connecting plain water inlet supply line to Cooling Unit, open water line shutoff valve for a period of  
time to flush out any metal shavings and other contaminates that may have resulted from plumbing  
connections.  
300614000  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Connect flexible plain water inlet supply line (1/2-inch I.D. min.), meeting water inlet supply line  
requirements of preceding CAUTION note, to Cooling Unit 3/8-in. flare (5/8-18) bulkhead fitting on back of  
Unit labeled WATER INLET’. DO NOT OPEN WATER INLET SUPPLY LINE SHUTOFF VALVE AT THIS  
TIME.  
CONNECTING CO INLET SUPPLY LINE TO COOLING UNIT  
2
(see Figure 2)  
WARNING: CO2 dis places oxygen. Strict attention mus t be obs erved in the prevention of  
CO2 (carbon dioxide) gas leaks in the entire CO2 and s oft drink s ys tem. If a CO2 gas leak is  
s us pected, particularly in a s mall area, immediately ventilate the contaminated area before  
attempting to repair the leak. Pers onnel expos ed to high concentration of CO2 gas will experience  
tremors which are followed rapidly by los s of cons cious nes s and s uffocation.  
Connect flexible CO2 inlet supply line to Cooling Unit 1/4-in. flare (7/16-20) bulkhead fitting of back of Unit  
labeled CO2 INLET’. DO NOT TURN ON CO2 SUPPLY TO COOLING UNIT AT THIS TIME.  
CONNECTING SYRUP SOURCE LINES TO COOLING UNIT SYRUP INLET LINES  
(see Figure 2)  
Connect syrup source lines, from No. 1 through No. 10 soft drink tanks location, to Cooling Unit syrup inlet lines  
labeled No. 1 through No. 10. DO NOT CONNECT SOFT DRINK TANKS INTO SYRUP SYSTEMS AT THIS  
TIME.  
CONNECTING COOLING UNIT SYRUP OUTLET LINES TO INSULATED PYTHON SYRUP  
LINES  
(see Figure 2)  
Connect Cooling Unit syrup outlet lines labeled No. 1 through No. 10, to insulated python lines labeled No. 1  
though No. 10 using BARBED CONNECTORS (item 2). Secure connections with TUBING CLAMPS (item 1).  
CONNECTING COOLING UNIT PLAIN WATER OUTLET LINES TO INSULATED PYTHON  
PLAIN WATER LINES  
(see Figure 2)  
Connect Cooling Unit plain water outlet lines to insulated python plain water lines using BARBED  
CONNECTORS (item 2). Secure connections with TUBING CLAMPS (item 1).  
CONNECTING COOLING UNIT CARBONATED WATER OUTLET LINES TO INSULATED  
PYTHON CARBONATED WATER LINES  
(see Figure 2)  
NOTE: The Cooling Unit carbonated water outlet lines are us ed to make up the carbonated water  
circulating s ys tem between the Cooling Unit and the dis pens ing s tation as explained in SYSTEM  
THEORY OF OPERATION in GENERAL INFORMATION SECTION.  
Connect Cooling Unit carbonated water outlet lines to insulated python carbonated water lines using BARBED  
CONNECTORS (item 3).  
9
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18 -IN.  
COOLING UNIT  
18 -IN.  
18 -IN.  
AIR FLOW  
(OPEN TO ROOM)  
FIGURE 4. COOLING UNIT SPACE REQUIRED  
PLACING COOLING UNIT IN OPERATING POSITION  
1. Very carefully, move Cooling Unit back into operating position leaving space around Unit (see Figure 4) as  
specified in SELECTING LOCATION. MAKE SURE THERE ARE NO KINKS IN COOLING UNIT INLET  
LINES, AND (IF APPLICABLE) REMOTE CONDENSER AND FAN ASSEMBLY REFRIGERATION LINES.  
NOTE: To comply with National Sanitation Foundation (NSF) requirements , Cooling Unit not ins talled  
on optional Cooling Unit Stand (P/N 309309-069) mus t have its bas e s ealed to floor with Dow-Corning  
RTV 731 or equivalent.  
2. Tilt Cooling Unit up to expose bottom of Unit base.  
3. Liberally apply silastic sealant such as Dow-Corning (RTV 731) or equivalent on Unit base bottom edges.  
NOTE: Do not move Cooling Unit after pos itioning or s eal from Unit bas e to floor will be broken.  
4. Lower Cooling Unit into operating position to complete seal from Unit base to floor. Apply additional sealant  
around bottom of base. Seal must have a minimum radius of 1/2-inch to prevent cracks and crevices and  
to ensure a complete seal.  
5. Route Cooling Unit water tank overflow hose to permanent floor drain.  
6. Seal area around drain and overflow hoses where they exit from Unit using Dow Corning (RTV 731) or  
equivalent).  
PREPARING COOLING UNIT FOR OPERATION  
1. Make sure plug in end of Cooling Unit water tank drain hose is secure.  
Note: Some Cooling Units are equipped with a water tank water level float control. Open s hutoff valve  
in plain water inlet s upply line. Due to s low water fill rate of the water level float control, water tank may  
be hand filled until water runs out of the water tank overflow hos e. CLEAN LOW-MINERAL-CONTENT  
WATER MUST BE USED WHERE A LOCAL WATER PROBLEM EXIST.  
2. Fill water tank with clean water until water starts flowing from water tank overflow hose. USE LOW  
MINERAL CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS.  
3. Open shutoff valve in plain water inlet supply line.  
4. Adjust primary CO2 regulator (see Figure 2) on CO2 cylinder to a minimum nominal setting of 120-psi or  
24-psi higher than highest setting required by the secondary CO2 regulators. Loosen CO2 regulator  
adjusting screw locknut. Turn adjusting screw to the right (clockwise) until regulator gage registers nominal  
120-psi, then tighten adjusting screw locknut.  
300614000  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Adjust carbonator secondary CO2 regulator (see Figure 2) to a nominal 90-psi. Loosen CO2 regulator  
adjusting screw locknut. Turn adjusting screw to the right (clockwise) until regulator gage registers nominal  
90-psi, then tighten adjusting screw lock nut. CO2 PRESSURE TO CARBONATORS MUST NOT EXCEED  
120-PSIG.  
OPERATION  
WARNING: Dis connect electrical power to Cooling Unit and Remote Condens er Coil and  
Fan As s embly to prevent pers onal injury before attempting any Cooling Unit or Remote  
Condens er Coil and Fan As s embly internal maintenance. Only qualified pers onnel s hould  
s ervice internal components or electrical wiring.  
CAUTION: to prevent Hydro-Boos tâ coil freeze up during initial Cooling Unit s tart-up, the  
following s tart-up procedure mus t be performed as follows :  
1. Make sure Hydro Boostâ bypass shutoff valve inside Cooling Unit (see Figure 2) is in ‘‘CLOSED (handle  
not in line with tubing) position.  
2. Make sure Cooling Unit REFRIGERATION POWER, CARBONATOR MOTOR, and CIRCULATING  
MOTOR Power switches are in OFF positions.  
3. Connect electrical power to Cooling Unit at disconnect switch. Connect electrical power to Remote  
Condenser Coil and Fan Assembly at disconnect switch.  
4. Place CARBONATOR MOTOR power switch in ON position.  
5. Place REFRIGERATION power switch in ONposition. Agitator motor and carbonator pump motor only  
will start and fill Hydro-BoostR coil with plain water. APPROXIMATELY 2-1/2 MINUTES AFTER  
CARBONATOR PUMP MOTOR HAS STARTED, REFRIGERATION COMPRESSOR, AND  
COMPRESSOR COOLING FAN, WILL START.  
NOTE: As ice bank forms in water tank, water expans ion will take place and exces s water will es cape  
through water tank overflow hos e to permanent floor drain.  
Cooling Unit will begin forming an ice bank and refrigerated Hydro-Boostâ coil will also be chilling water. When  
full ice bank has been formed, Cooling Unit compressor and compressor cooling fan will stop but agitator motor  
will continue to operate circulating ice water bath in water tank.  
6. Dispense from dispensing station until carbonated water appears at dispensing valve which indicates  
Cooling Unit plain and carbonated water systems have been filled.  
7. Place CIRCULATING MOTOR power switch in ON position. Circulating pump will start and begin  
circulating carbonated water in carbonated water circulating system as explained in SYSTEM THEORY OF  
OPERATION in GENERAL INFORMATION SECTION.  
8. Dispense carbonated water from dispensing valve to make sure all air has been purged from system.  
9. If Cooling Unit plain water outlet line has been connected to a dispensing station dispensing valve,  
dispense from valve until all air has been purged from plain water system.  
10. Adjust soft drink tanks secondary CO2 regulators (see Figure 2) as follows:Sugar  
Syrup Soft Drink Tanks CO2 Regulator.  
Adjust sugar syrup soft drink tanks secondary CO2 regulator at 40-psig for syrup lines up to 10-feet in  
length plus one pound for each additional length of 10-feet, plus one pound for each 2-feet of vertical lift.  
For example: if syrup line total length is 30-feet and total vertical lift is 6-feet, then 40-psig + 2-psig  
(1-pound for every 10-feet of length over 10-feet which is 20-feet) + 3-psig (1-pound for every 2-feet of  
vertical lift which is 6-feet); total equals 40 + 2 + 3 = 45-psig CO2 regulator setting.  
11  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Low-Calorie (diet) Syrup Soft Drink Tank CO2 Regulator.  
Adjust low-calorie (diet) soft drink tank  
secondary CO2 regulator for low-calorie drink at 10-psig for  
syrup lines up to 30-feet in length. Syrup lines longer than 30-feet in length may require a slightly higher  
CO2 regulator setting to 12-psig maximum. Excessive CO2 pressure may cause low-calorie syrup  
carbonation resulting in foam.  
IMPORTANT: Syrup s ys tems mus t be s anitized as ins tructed before s yrup is connected into s yrup  
s ys tems .  
11. Connect soft drink tanks into syrup systems.  
12. Dispense from dispensing station dispensing valves until product is dispensed.  
LEAK CHECK AND INSULATING COOLING UNIT OUTLET LINES  
1. Check all CO2, plain and carbonated water, and syrup connections for leaks and repair if evident.  
2. Make sure Cooling Unit outlet lines connections to insulated python lines are well insulated.  
3. Install Cooling Unit top cover and secure with two screws.  
DISPENSING STATION ADJ USTMENTS  
ADJ USTING WATER FLOW RATE  
Refer to Installation Instructions provided with Dispensing Station for dispensing valve water flow rate  
adjustment instructions.  
ADJ USTING WATER-TO-SYRUP RATIO OF DISPENSED PRODUCT  
Adjust Dispensing Station dispensing valves for Water-to-Syrup Ratio of dispensed product as instructed in  
dispensing station Installation Instructions.  
INSTALLING LINE IDENTIFICATION LABEL  
Install LABEL, LINE IDENTIFICATION (item 4) on Cooling Unit and record syrup flavors in proper spaces.  
300614000  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATORS INSTRUCTIONS  
This section covers operating controls, daily pre-operation check, adjustments, replenishing CO2 and syrup  
supplies, cleaning and sanitizing, Cooling Unit maintenance, Remote Condenser Coil and Fan Assembly  
maintenance, lubrication, and servicing CO2 gas check valves.  
WARNING: Dis connect electrical power to Cooling Unit and Remote Condens er Coil and  
Fan As s embly to prevent pers onal injury before attempting any internal maintenance. Only  
qualified pers onnel s hould s ervice internal components or electrical wiring.  
OPERATING CONTROLS  
COOLING UNIT REFRIGERATION POWER SWITCH  
(see Figure 5)  
REFRIGERATION POWER switch, located on front of Cooling Unit, placed in ‘‘OFFposition will interrupt  
electrical power to refrigeration compressor, agitator motor, compressor cooling fan, carbonated water  
circulating pump, and the carbonator pump motor. REFRIGERATION POWER switch placed in ‘‘ON position  
will start the carbonator pump motor (if carbonated water is being called for), the carbonated water circulating  
pump motor, and the agitator motor. Under certain conditions approximately 2-1/2 minutes after the  
REFRIGERATION POWER SWITCH has been placed in ‘‘ON position refrigeration compressor and  
compressor cooling fan will start.  
COOLING UNIT CARBONATOR MOTOR SWITCH  
(see Figure 5)  
CARBONATOR MOTOR power switch, located on front of Cooling Unit, placed in ‘‘OFFposition will interrupt  
electrical power to carbonator pump motor. Switch must be placed in ‘‘ONposition before carbonator pump  
motor will operate.  
COOLING UNIT CIRCULATING MOTOR SWITCH  
(see Figure 5)  
CIRCULATING MOTOR power switch, located on front of Cooling Unit, placed in ‘‘OFF position will interrupt  
electrical power to carbonated water circulating pump. Switch must be placed in ‘‘ONposition before circulating  
pump will operate.  
REFRIGERATION SYSTEM TEMPERATURE SENSING DEVICE AND HIGH-PRESSURE  
CUTOUT SWITCH  
(see Figure 5)  
This Cooling Unit is equipped with a refrigeration system temperature sensing device and a high-pressure  
sensing cutout switch that will shut refrigeration system down should the system overheat due to a clogged  
condenser coil in the Remote Condenser Coil and Fan Assembly. If refrigeration system does not automatically  
restart itself after system has cooled down, high-pressure sensing cutout switch (see Figure 5) will have to be  
pressed to reset switch. MAKE SURE REFRIGERATION SYSTEM PROBLEM IS CORRECTED. OPERATING  
REFRIGERATION SYSTEM IN THIS MANNER FOR PROLONGED PERIOD OF TIME COULD RESULT IN  
COMPRESSOR FAILURE.  
13  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DAILY PRE-OPERATION CHECK  
4. Make sure CO2 cylinder regulator assembly 1800-psi gage indicator is not in shaded (change CO2  
cylinder’) portion of dial. If so, CO2 cylinder is almost empty and must be replaced.  
5. Sufficient syrup supply in all soft drink tanks. If not, replenish syrup supply as instructed.  
ADJ USTMENTS  
ADJ USTING CO REGULATORS  
2
CO2 regulators should be periodically checked for proper pressure settings and if necessary, adjusted as  
instructed.  
ADJ USTING DISPENSING VALVES WATER FLOW RATE  
If adjustment of dispensing valves water flow rate should be necessary, adjust as instructed in Dispensing  
Station Installation Instructions.  
ADJ USTING WATER-TO-SYRUP RATIO OF DISPENSED PRODUCT  
Water-To-Syrup Ratio of dispensed product should be checked and if necessary, adjusted as instructed in  
Dispensing Station Installation Instructions.  
ADJ USTING SIZE OF DRINK DISPENSED  
Adjust drink size of dispensed product as instructed in Dispensing Station Installation Instructions.  
REPLENISHING CO2 SUPPLY  
WARNING: CO2 dis places oxygen. Strict attention mus t be obs erved in the prevention of  
CO2 (carbon dioxide) gas leaks in the entire CO2 and s oft drink s ys tem. If a CO2 gas leak is  
s us pected, particularly in a s mall area, immediately ventilate the contaminated area before  
attempting to repair the leak. Pers onnel expos ed to high concentration of CO2 gas will experience  
tremors which are followed rapidly by los s of cons cious nes s and s uffocation.  
NOTE: When indicator on CO2 cylinder regulator as s embly 1800-ps i gage is in s haded (change CO2  
cylinder’) portion of the dial, CO2 cylinder is almos t empty and s hould be changed. CO2 s upply s hould  
be checked daily and if neces s ary, replenis hed as ins tructed.  
REPLENISHING SYRUP SUPPLY  
Syrup supply should be checked daily and if necessary, replenished as instructed.  
CLEANING AND SANITIZING  
DAILY CLEANING  
Perform daily cleaning of dispensing station as instructed in dispensing station installation instructions. Outside  
of Cooling Unit must be cleaned periodically.  
300614000  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SANITIZING SYRUP SYSTEMS  
Syrup systems should be sanitized every 90 days as instructed following Sanitizer Manufacturers  
recommendations.  
COOLING UNIT MAINTENANCE  
COOLING UNIT AIR INTAKE AND EXHAUST FILTERS  
CAUTION: Air filters on the Cooling Unit mus t be removed and cleaned every 30 days as  
ins tructed. Exces s ive accumulation of dus t, lint, and greas e on the air filters will res trict  
airflow through the Unit which will caus e the refrigeration s ys tem to overheat.  
The Cooling Unit cabinet is equipped with are intake and exhaust filters which allow air to circulate through the  
cabinet to cool the compressor. Air filters must be cleaned every 30 days as instructed. Area around Cooling  
Unit must be kept free of obstructions at all times for proper air circulation through the Unit.  
CHECKING ICE WATER BATH  
Note: Some Cooling Units are equipped with a water tank water level float control. A gurgle heard from  
the Cooling Unit indicates water level in water tank is low. This indicates the water level float control is  
not operating properly and mus t be replaced.  
A gurgle heard from the Cooling Unit indicates water level in water tank is low and more water should be added  
to the tank for maximum product cooling. Periodically check, and if necessary, add water to the water tank as  
instructed.  
COOLING UNIT CARBONATOR MAINTENANCE  
Lubrication.  
Carbonator water pump motor bearings must be oiled periodically as instructed.  
DOUBLE LIQUID CHECK VALVE ASSEMBLIES YEARLY MAINTENANCE (OR AFTER  
WATER SYSTEM DISRUPTIONS).  
(see Figure 2)  
The two double liquid check valve assemblies are located in plain water lines connected between the plain  
water cooling coils and the carbonated water tank. The double liquid check valve assemblies must be inspected  
and cleaned at least once a year under nor work, earthquake, etc.) Inspect and clean double liquid check valve  
assemblies as instructed.  
COOLING UNIT CARBONATED WATER CIRCULATING PUMP MOTOR LUBRICATION  
Carbonated water circulating pump motor bearings must be oiled periodically as instructed.  
15  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMOTE CONDENSER COIL AND FAN ASSY MAINTENANCE  
(see Figure 5)  
CAUTION: Remote Condens er Coil and Fan As s embly connected to the Cooling Unit is  
equipped with a condens er coil that mus t be cleaned every 30-days . Allowing condens er  
coil to become clogged will caus e refrigeration s ys tem to overheat which will automatically  
s hut refrigeration s ys tem down. After condens er coil has been cleaned, high-pres s ure cutout  
s ens ing s witch (s ee Figure 5) will have to be pres s ed to res tart refrigeration s ys tem. OPERATING  
COOLING UNIT IN THIS MANNER FOR PROLONGED PERIOD OF TIME COULD RESULT IN  
COMPRESSOR FAILURE.  
Area on top of and around Remote Condenser Coil and Fan Assembly must be kept free of obstruction at all  
times. Condenser coil must be cleaned as instructed to maintain proper cooling of coil.  
CLEANING CO2 GAS CHECK VALVES  
(see Figure 2)  
The CO2 gas check valves must be inspected and serviced at least once a year under normal conditions and  
after any CO2 system servicing or disruption as instructed.  
300614000  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE AND MAINTENANCE  
The Remote Rooftop Condenser Coil and Fan Assembly Condenser Coil must be cleaned every 30 days.  
Circulating air, required to cool the coil, is drawn in at bottom and is exhausted out through top of Unit. Clean  
the condenser coil as follows:  
1. Disconnect electrical power to Cooling Unit at disconnect switch, then disconnect electrical power from  
Remote Condenser Coil and Fan Assembly at disconnect switch.  
2. Clean bottom side of condenser coil using vacuum cleaner, whisk broom, or soft-bristle brush to remove  
any debris from coil.  
3. Check and make sure fan blade moves freely and is not touching any surfaces, are not bent, or out of  
balance. check and make sure wire guard is properly installed and securely fastened.  
4. Check and make sure roof area immediately surrounding Unit is free and clear of any debris that may have  
collected such as leaves, paper, trash, etc.  
5. Restore electrical power to Cooling Unit at disconnect switch, then connect electrical power to Remote  
Condenser Coil and Fan Assembly at disconnect switch.  
COOLING UNIT MAINTENANCE  
PERIODIC CLEANING  
Periodically wash all external surfaces of Cooling Unit, rinse with clean water, then wipe dry with a clean soft  
cloth. DO NOT USE ABRASIVE TYPE CLEANERS.  
CLEANING COOLING UNIT AIR INTAKE AND EXHAUST FILTERS.  
(see Figure 5).  
This section describes Service and Maintenance procedures to be performed on Cooling Unit and Remote  
Condenser Coil and Fan Assembly.  
WARNING: Dis connect electrical power to Cooling Unit and Remote Condens er Coil and  
Fan As s embly to prevent pers onal injury before attempting any Cooling Unit or Remote  
Condens er Coil and Fan As s embly internal maintenance. Only qualified pers onnel s hould  
s ervice internal components or electrical wiring.  
PREPARING COOLING UNIT FOR SHIPPING, STORING, OR RELOCATING  
CAUTION: Before s hipping, s toring, or relocating this Unit, the s yrup s ys tems mus t be  
s anitized and all s anitizing s olution mus t be purged from the s yrup s ys tems . All water mus t  
als o be purged from the plain and carbonated water s ys tems . A freezing ambient  
environment will caus e res idual water in the Unit to freeze res ulting in damage to internal  
components .  
PERIODIC INSPECTION  
Check entire system for leaks or damaged components. Repair as necessary.  
17  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMOTE CONDENSER COIL AND FAN ASSEMBLY MAINTENANCE  
CAUTION: Remote Condens er Coil and Fan As s embly connected to this Cooling Unit is  
equipped with a condens er coil that mus t be cleaned every 30-days . Allowing condens er  
coil to become clogged will caus e refrigeration s ys tem to overheat which will automatically  
s hut refrigeration s ys tem down. After condens er coil has been cleaned, high-pres s ure s ens ing  
cutout s witch (s ee Figure 5) mus t be pres s ed to res tart refrigeration s ys tem. OPERATING  
COOLING UNIT IN THIS MANNER FOR PROLONGED PERIOD OF TIME COULD RESULT IN  
COMPRESSOR FAILURE.  
CAUTION: Air filters on the Cooling Unit mus t be removed and cleaned every 30 days as  
ins tructed. Exces s ive accumulation of dus t, lint, and greas e on the air filters will res trict  
airflow through the Unit which will caus e the refrigeration s ys tem to overheat.  
The Cooling Unit cabinet is equipped with air intake and exhaust filters which allow air to circulate through the  
cabinet to cool the compressor. The air filter must be cleaned every 30 days. Excessive accumulation of dust,  
lint, and grease on filters will restrict air flow through the Unit. Air filter may be removed and washed out with  
detergent solution or may be vacuumed. Area around Cooling Unit must be kept free of obstructions at all times  
for proper air circulation throughout the Unit.  
CHECKING ICE WATER BATH  
(see Figure 5)  
Note: Some Cooling Units are equipped with a water tank water level float control. A gurgle heard from  
the Cooling Unit indicates water level in water tank is low. This indicates the water level float control is  
not operating properly and mus t be replaced.  
A gurgle heard from Cooling Unit indicates water level in water tank is low and more water should be added to  
the tank for maximum product cooling. Ice water bath and ice bank should be checked for cleanliness and water  
tank coils should be checked for excessive mineral deposit build-up as follows:  
1. Disconnect electrical power from Cooling Unit at disconnect switch.  
2. Remove two screws securing Cooling Unit top cover, then remove cover.  
3. Using flashlight, inspect ice water bath and ice bank for cleanliness, ice water bath should be clear and ice  
bank free of foreign particles.  
4. If cleaning of water tank is necessary, refer to CHANGING ICE WATER BATH in this section.  
5. Fill water tank with clean water until water starts flowing from water tank overflow hose. USE LOW  
MINERAL CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS.  
6. Install Cooling Unit top cover and secure with two screws.  
7. Restore electrical power to Cooling Unit at disconnect switch.  
CHANGING ICE WATER BATH  
(see Figure 5)  
1. Disconnect electrical power from Cooling Unit at disconnect switch.  
2. Remove two screws securing Cooling Unit top cover, then remove cover.  
300614000  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: If your Cooling Unit is equipped with a water tank water level float control, clos e s hutoff valve in  
plain water inlet s upply line.  
3. Make sure end of water tank drain hose is routed to floor drain, then remove plug from end of hose and  
allow water to drain from tank.  
CAUTION: Never us e an ice pick or other ins truments to remove ice from evaporator coils .  
Such practice can res ult in punctured refrigeration circuit.  
4. Allow ice bank to melt. Hot water may be used to speed melting.  
5. Thoroughly rinse inside of water tank with clean water.  
6. Install plug in end of water tank drain hose.  
Note: If your Cooling Unit is equipped with a water tank water level float control, open s hutoff valve in  
plain water inlet s upply line.  
7. Fill water tank with clean water until water starts flowing from water tank overflow hose. USE LOW  
MINERAL CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS.  
8. Install Cooling Unit top cover and secure with two screws.  
9. Connect electrical power to Cooling Unit at disconnect switch.  
DOUBLE LIQUID CHECK VALVE ASSEMBLIES YEARLY MAINTENANCE (OR AFTER  
WATER SYSTEM DISRUPTIONS)  
(see Figures 2 and 6)  
WARNING: The two double liquid check valve as s emblies mus t be ins pected and s erviced  
at leas t once a year under normal circums tances , and after any dis ruptions (plumbing  
work, earthquake, etc.) to the water s upply s ys tem that might caus e turbulent (erratic) flow  
of water through the s ys tem. Fouled liquid check valves could caus e CO2 gas to back flow from  
the carbonated water tank into the water s ys tem and create a health hazard in the s ys tem.  
The two double liquid check valve assemblies are located in plain water lines connected between the plain  
water cooling coils and the carbonated water tank. Inspect and clean the double liquid check valve assemblies  
as follows:  
1. Disconnect electrical power from Cooling Unit at disconnect switch.  
2. Close shutoff valve in plain water inlet supply line.  
3. Note pressure setting on carbonator CO2 regulator, then turn regulator adjusting screw to the left  
(counterclockwise) until regulator gage reads 0-psi.  
4. Pull up on carbonator tank relief valve to release CO2 pressure from tank.  
5. Remove two screws securing Cooling Unit top cover, then remove cover.  
6. Remove double liquid check valve assembly from plain water line connected between plain water cooling  
coil and carbonated water tank.  
7. Remove one check valve from the other, then disassemble each check valve as shown in Figure 6.  
19  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMOTE CONDENSER  
COIL AND FAN ASSY  
FIGURE 5. PARTS IDENTIFICATION  
300614000  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Wipe each part with clean lint-free cloth. Inspect each part, especially the ball, for burrs, nicks, corrosion,  
deterioration, and other damage. Discard ball seat and any damaged or suspicious parts and replace with  
new parts during reassemble.  
9. Reassemble check valves as shown in Figure 6. ALWAYS install new ball seat (QUAD RING) (P/N  
312418-000.  
NOTE: Make s ure when as s embling check valves together, check valve female end with white tapered  
gas ket ins ide, is on inlet s ide of double liquid check valve as s embly.  
10. Assemble check valves together. DO NOT OVERTIGHTEN.  
11. Install double liquid check valve assembly in plain water line connected between plain water cooling coil  
and carbonated water tank.  
12. Repeat preceding steps 6 through 11 to service other double liquid check valve in other plain water line  
connected between plain water cooling coil and carbonated water tank.  
13. Turn carbonator CO2 regulator adjusting screw to the right (clockwise) until its gage indicates pressure  
setting observed in step 3 preceding.  
14. Open shutoff valve in plain water inlet supply line.  
15. Restore electrical power to Cooling Unit at disconnect switch.  
16. Dispense carbonated water at dispensing station and allow carbonator to cycle on and off. Check for water  
leaks and repair if evident.  
17. Disconnect electrical power from Cooling Unit at disconnect switch.  
18. Install Unit top cover and secure with two screws.  
19. Restore electrical power to Cooling Unit at disconnect switch.  
LUBRICATION  
The carbonator water pump and the carbonated water circulating pump motor bearings must be oiled  
periodically, refer to oiling instructions on the motors. DO NOT OVER OIL.  
ADJ USTMENTS  
NOTE: To readjus t CO2 regulator to a lower s etting loos en adjus ting s crew lock nut, then turn s crew to  
the left (counterclockwis e) until pres s ure gage reads 5-ps i lower than new s etting will be. Turn  
adjus ting s crew to the right (clockwis e) until gage regis ters new s etting, then tighten lock nut.  
PRIMARY CO REGULATOR  
2
(see Figure 2).  
Adjust primary CO2 regulator on CO2 cylinder to a minimum nominal setting of 120-psi or 24-psi higher than  
highest setting required by the secondary CO2 regulators. Loosen CO2 regulator adjusting screw locknut. Turn  
adjusting screw to the right (clockwise) until regulator gage registers nominal 120-psi, then tighten adjusting  
screw locknut.  
SECONDARY CO REGULATORS  
2
(see Figure 2).  
Carbonator Secondary CO2 Regulator.  
Adjust carbonator secondary CO2 regulator to a nominal 90-psi. Loosen CO2 regulator adjusting screw locknut.  
Turn adjusting screw to the right (clockwise) until regulator gage registers nominal 90-psi, then tighten adjusting  
screw locknut. CO2 PRESSURE TO CARBONATORS MUST NOT EXCEED 125-PSIG.  
21  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sugar Syrup Soft Drink Tanks CO2 Regulators.  
Adjust sugar syrup soft drink tanks secondary CO2 regulator at 40-psig for syrup lines up to 10-feet in length  
plus one pound for each additional length of 10-feet, plus one pound for each 2-feet of vertical lift. For example:  
if syrup line total length is 30-feet and total vertical lift is 6-feet, then 40-psig + 2-psig (1-pound for every 10-feet  
of length over 10-feet which is 20-feet) + 3-psig (1-pound for every 2-feet of vertical lift which is 6-feet); total  
equals 40 + 2 + 3 = 45-psig CO2 regulator settings.  
1
3
2
6
4
5
ITEM  
NO  
PART NO  
NAME  
1
317963000  
312415000  
*312418000  
312419000  
312196000  
317965000  
Housing  
2
Flat Washer, Stainless Steel  
3
Ball Seat (quad ring)  
Ball  
4
5
Spring  
6
Retainer  
FIGURE 6. LIQUID CHECK VALVE ASSEMBLY  
Low-Calorie (diet) Syrup Soft Drink Tank CO2 Regulator.  
Adjust low-calorie (diet) soft drink tank secondary CO2 regulator for low-calorie drink at 10-psig for syrup lines  
up to 30-feet in length. Syrup lines longer than 30-feet in length may require a slightly higher CO2 regulator  
setting to 12-psig maximum. Excessive CO2 pressure may cause low-calorie syrup carbonation resulting in  
foam.  
WATER FLOW RATE  
Refer to Installation Instructions provided with Dispensing Station for dispensing valve water flow rate  
adjustment instructions.  
WATER-TO-SYRUP RATIO OF DISPENSED PRODUCT  
Adjust dispensing station dispensing valves for Water-to-Syrup Ratio of dispensed product as instructed in  
dispensing station Installation Instructions.  
CLEANING AND SANITIZING  
DAILY CLEANING OF UNIT  
1. Remove cup rest from the drip tray.  
300614000  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Wash drip tray in place on the Unit, then rinse drip tray with hot water allowing water to drain out through  
the drain hose.  
3. Wash cup rest, then rinse the cup rest with clean water. Install cup rest in the drip tray.  
4. Clean all external surfaces of the Unit with a sponge. Rinse out the sponge with clean water, then wring  
excess water out of the sponge and wipe off all external surfaces on the Unit. Wipe Unit dry with a clean  
soft cloth. DO NOT USE ABRASIVE CLEANERS.  
5. Remove nozzle and syrup diffusers from the dispensing valves. Place nozzles and syrup diffusers in  
sanitizing solution.  
6. Wash the nozzles and syrup diffusers in sanitizing solution, then rinse them with potable water.  
7. Re-install nozzles and syrup diffusers back on the dispensing valves.  
SANITIZING POST-MIX SYRUP SYSTEMS  
IMPORTANT: Only qualified Service Pers onnel s hould perform s anitizing procedure on the pos t-mix  
s yrup s ys tems .  
The post-mix syrup systems should be sanitized every 90-days using a non-scented household liquid bleach  
containing a 5.25 % sodium hypochlorite concentration. Proceed as follows to sanitize the post-mix syrup  
systems.  
1. Disconnect syrup supplies from syrup systems.  
2. Rinse quick disconnects (syrup tanks systems) or bag-in-box connectors (syrup bag-in-box systems) in  
warm potable water.  
STEP 1. WASH SYRUP SYSTEMS  
3. Using a clean syrup tank (syrup tank system) or a five-gallon container (bag-in-box system), prepare a full  
tank or container of liquid dishwasher detergent by using 70_ F (21_ C) to 100_ F (38_ C) potable water  
and 0.5 oz. (15 ml) of liquid dishwasher detergent to one gallon of potable water. Stir detergent solution to  
thoroughly mix the solution.  
4. Syrup Tank Systems.  
A. Observe and note CO2 pressure setting on the syrup tanks CO2 regulator, then re-adjust CO2  
regulator to 60 to 80-psi. Pressurize syrup tank containing detergent solution to 60 to 80-psi.  
B. Connect detergent solution tank, pressurized at 60 to 80-psi, into one of the syrup systems.  
Bag-in Box Syrup Systems.  
C. Install bag valves, cut from empty bag-in-box syrup containers, on ends of syrup containers syrup  
outlet tubes connectors.  
D. Place all syrup outlet tubes, with bag valves on their ends, in container containing detergent solution.  
5. Flush the syrup system and dispensing valve as follows:  
A. Place waste container under applicable dispensing valve.  
B. Activate the dispensing valve for one minute to purge all syrup and flush out the syrup system.  
C. Continue to activate the dispensing valve in cycles (ON” for 15-seconds, OFF, then ON” for  
15-seconds). Repeat ON” and OFF” cycles for 15-cycles.  
6. Connect detergent solution to the remaining syrup systems and flush syrup out of the syrup systems as  
instructed in step NO TAG preceding.  
23  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Remove detergent solution source from the syrup system.  
STEP 2. FLUSH SYRUP SYSTEMS  
8. Syrup Tank Systems.  
Connect syrup tank containing potable water, pressurized at 60 to 80-psi, into one of the syrup systems.  
Bag-in-Box Syrup System.  
Fill five-gallon container with potable water, then place all bag-in-box syrup containers syrup outlet tubes in  
container containing potable water.  
9. Flush detergent solution out of the syrup system and dispensing valve as follows:  
A. Place waste container under applicable dispensing valve.  
B. Activate the dispensing valve for one minute to purge all detergent solution and flush out the syrup  
system.  
C. Continue to activate the dispensing valve in cycles (ON” for 15-seconds, OFF, then ON” for  
15-seconds). Repeat ON” and OFF” cycles for 15-cycles.  
10. Connect potable water source to the remaining syrup systems and flush detergent solution out of the syrup  
systems as instructed in step NO TAG preceding.  
11. Remove potable water source from the syrup system.  
STEP 3. SANITIZE SYRUP SYSTEMS  
12. Using a clean syrup tank (syrup tanks system) or a five-gallon container (bag-in-box system), prepare  
sanitizing solution using 70_ F (21_ C) to100_ F (38_ C) potable water and 0.5 oz. (15 ml) of non-scented  
household liquid bleach that contains a 5.25 % sodium hypochlorite concentration to one gallon of potable  
water. This mixture must not exceed 200 PPM of chlorine. Stir sanitizing solution to thoroughly mix.  
13. Syrup Tank Systems.  
Connect sanitizing solution tank, pressurized at 60 to 80-psi, into one of the syrup systems.  
Bag-in-Box Syrup System.  
Place all bag-in-box syrup containers syrup outlet tubes in container containing sanitizing solution.  
14. Sanitize the syrup system and dispensing valve as follows:  
A. Place waste container under applicable dispensing valve.  
B. Activate the dispensing valve for one minute to purge all water from and install sanitizing solution in  
the syrup system and dispensing valve.  
C. Continue to activate the dispensing valve in cycles (ON” for 15-seconds, OFF, then ON” for  
15-seconds). Repeat ON” and OFF” cycles for 15-cycles.  
15. Repeat stepsNO TAG and NO TAG to flush water out of and install sanitizing solution in the remaining  
syrup systems and dispensing valves.  
16. Remove sanitizing solution source from the syrup system.  
17. Allow sanitizing solution to remain in the syrup systems for not less than 10 or no more than 15-minutes  
(max.) contact time.  
STEP 4. WATER FLUSH SYRUP SYSTEMS  
300614000  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: Flus h s anitizing s olution from the s yrup s ys tems as ins tructed. Res idual  
s anitizing s olution left in the s yrup s ys tems could create a health hazard.  
18. Fill syrup tank (syrup tank system) or a five-gallon container (bag-in-box system) with potable water.  
19. Syrup Tank Systems.  
Connect syrup tank containing potable water, pressurized at 60 to 80-psi, into one of the syrup systems.  
Bag-in-Box Syrup System.  
Place all bag-in-box syrup containers syrup outlet tubes in container containing potable water.  
20. Flush sanitizing solution from the syrup system and the dispensing valve as follows:  
A. Place waste container under applicable dispensing valve.  
B. Activate the dispensing valve for one minute to purge all sanitizing solution out of the syrup system  
and the dispensing valve.  
C. Continue to activate the dispensing valve in cycles (ON” for 15-seconds, OFF, then ON” for  
15-seconds). Repeat ON” and OFF” cycles for 15-cycles.  
21. Repeat steps NO TAG and NO TAG preceding to purge sanitizing solution out of the remaining syrup  
systems and  
dispensing valves.  
22. Remove potable water source from the syrup system.  
STEP 5. PURGE WATER OUT OF SYRUP SYSTEMS (RESTORE OPERATION)  
23. Syrup Tank Systems.  
A. Noting syrup tanks CO2 regulator pressure setting observed in step 4 preceding, readjust CO2  
regulator to the observed pressure setting,  
B. Connect tanks containing syrup into syrup systems.  
Bag-in-Box Syrup System.  
C. Remove all bag valves from bag-in-box syrup containers outlet tubes connectors.  
D. Connect bag-in-box syrup containers into the syrup systems.  
24. Place waste container under dispensing valves. Dispense from all dispensing valves to permit syrup to  
purge all potable water from the syrup systems and the dispensing valves. Continue to dispense from the  
dispensing valves until only syrup is dispensed from the syrup systems and valves.  
WARNING: To avoid pos s ible pers onal injury or property damage, do not attempt to  
remove the s yrup tank cover until CO2 pres s ure has been releas ed from the tank.  
25. Dispose of waste sanitizing solution in a sanitary sewer, not in a storm drain, then thoroughly rinse the  
inside and the outside of the container that was used for sanitizing solution to remove all sanitizing solution  
residue.  
25  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLENISHING CO2 SUPPLY  
WARNING: CO2 dis places oxygen. Strict attention mus t be obs erved in the prevention of  
CO2 (carbon dioxide) gas leaks in the entire CO2 and s oft drink s ys tem. If a CO2 gas leak is  
s us pected, particularly in a s mall area, immediately ventilate the contaminated area before  
attempting to repair the leak. Pers onnel expos ed to high concentration of CO2 gas will experience  
tremors which are followed rapidly by los s of cons cious nes s and s uffocation.  
NOTE: When indicator on CO2 cylinder primary CO2 regulator as s embly 1800-ps i gage is in s haded  
(change CO2 cylinder’) portion of dial, CO2 cylinder is almos t empty and s hould be changed.  
1. Fully close (clockwise) CO2 cylinder valve.  
2. Slowly loosen primary CO2 regulator assembly coupling nut allowing CO2 pressure to escape, then remove  
regulator assembly from empty CO2 cylinder.  
3. Unfasten safety chain and remove empty CO2 cylinder.  
FIGURE 7. CO2 GAS CHECK VALVE  
WARNING: To avoid pers onal injury and/or property damage, always s ecure CO2 cylinder in  
upright pos ition with s afety chain to prevent it from falling over. Should valve become  
accidentally damaged or broken off, CO2 cylinder can caus e s erious pers onal injury.  
4. Position CO2 cylinder and secure with safety chain.  
5. Make sure gasket is in place inside primary CO2 regulator coupling nut, then install regulator on CO2  
cylinder.  
6. Open (counterclockwise) CO2 cylinder valve slightly to allow lines to slowly fill with gas, then open valve  
fully to back-seat valve. (Back-seating valve prevents leakage around valve shaft).  
REPLENISHING SYRUP SUPPLY  
NOTE: The following ins tructions are applicable only when replenis hing s ame flavor s yrup. Refer to  
SYRUP FLAVOR CHANGE when changing s yrup flavor.  
1. Disconnect empty soft drink tank from syrup system.  
2. Check soft drink tank quick disconnects for sticky or restricted operation. Wash disconnects in warm water.  
300614000  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Connect full tank of syrup into syrup system.  
SYRUP FLAVOR CHANGE  
1. Perform sanitizing procedure on syrup system syrup flavor change will be made on.  
2. Check soft drink tank quick disconnects for sticky or restricted operation. Wash disconnects in warm water.  
3. Connect full tank of new flavor syrup into syrup system.  
CLEANING CO2 SYSTEM GAS CHECK VALVES  
SECONDARY CO REGULATORS AND CO  
MANIFOLD CO GAS CHECK VALVES  
2
2
2
(see Figures 2 and 7)  
The secondary CO2 regulators and CO2 manifold CO2 gas check valves must be inspected and serviced at  
least once a year under normal conditions and after any servicing or disruption of the CO2 system. ALWAYS  
REPLACE BALL SEAT (QUAD RING SEAL) EACH TIME GAS CHECK VALVES ARE SERVICED.  
COOLING UNIT CO INLET LINE CO GAS CHECK VALVE  
2
2
(see Figures 2 and 7)  
CO2 inlet line CO2 gas check valve, located inside Cooling Unit, must be inspected and serviced at least once a  
year under normal conditions and after any servicing or disruption of the CO2 system. ALWAYS INSTALL NEW  
BALL SEAT (QUAD RING) SEAL EACH TIME GAS CHECK VALVE IS SERVICED.  
27  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REFRIGERATION LINES CONNECTED  
BETWEEN COOLING UNIT AND REMOTE  
CONDENSER COIL AND FAN ASSY MUST  
NOT EXCEED 50 -FEET IN LENGTH.  
REMOTE CONDENSER  
COIL AND FAN ASSY  
REFRIGERATION LINES VERTICAL  
RISE MUST NOT EXCEED 20 -FEET.  
FIGURE 8. REFRIGERATION FLOW DIAGRAM (REQUIRES CONNECTION TO REMOTE CONDENSER  
COIL AND FAN ASSY)  
300614000  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
IMPORTANT: Only qualified pers onnel s hould s ervice internal components or electrical wiring.  
WARNING: If repairs are to be made to a product s ys tem, remove quick dis connects from  
the applicable product tank, then relieve the s ys tem pres s ure before proceeding. If repairs  
are to be made to the CO2 s ys tem, s top dis pens ing, s hut off the CO2 s upply, then relieve the  
s ys tem pres s ure before proceeding. If repairs are to be made to the refrigeration s ys tem, make s ure  
electrical power is dis connected from the unit.  
TROUBLESHOOTING POSE-MIX SYSTEM  
Trouble  
Probable Cause  
Remedy  
WATER-TO-SYRUP RATIO’  
OF DISPENSED DRINK TOO  
LOW OR TOO HIGH.  
A. Dispensing valve syrup flow  
regulator not properly  
adjusted.  
A. Adjust Water-To-Syrup Ratio’  
(refer to dispensing station  
installation Instructions).  
B. CO2 gas pressure to soft drink B. Adjust soft drink tanks secondary  
tanks insufficient to push  
syrup out of tanks.  
CO2 regulator as instructed.  
ADJUSTMENT OF  
A. No syrup supply.  
A. Replenish syrup supply as  
instructed.  
DISPENSING VALVE SYRUP  
FLOW REGULATOR DOES  
NOT INCREASE TO DESIRED  
WATER-TO-SYRUP RATIO.  
B. Soft drink tank quick  
disconnects not secure.  
B. Secure quick disconnects.  
C. Soft drink tanks secondary  
CO2 regulator out of  
adjustment.  
C. Adjust soft drink tanks secondary  
CO2 regulator as instructed.  
D. Dispensing valve syrup flow  
regulator, soft drink tank quick  
disconnect, or syrup line  
restricted.  
D. Sanitize syrup system as  
instructed.  
E. Tapered nylon washer inside  
tube swivel nut connector  
distorted from being  
E. Replace nylon washer. Make sure  
washer seats properly in swivel  
nut.  
overtightened restricting syrup  
flow.  
F. Dirty or inoperative piston or  
cylinder in dispensing valve  
syrup flow regulator.  
F. Disassemble and clean  
dispensing valve syrup flow  
regulator.  
300614000  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble  
Probable Cause  
Remedy  
ADJUSTMENT OF  
A. Dirty or inoperative piston or  
cylinder in dispensing valve  
syrup flow regulator.  
A. Disassemble and clean  
dispensing valve syrup flow  
regulator.  
DISPENSING VALVE SYRUP  
FLOW REGULATOR DOES  
NOT DECREASE TO  
DESIRED WATER-TO- SYRUP  
‘‘RATIO’.  
DISPENSED PRODUCT  
CARBONATION TOO LOW.  
A. Carbonator CO2 regulator out  
of adjustment for existing  
water conditions or  
A. Adjust carbonator CO2 regulator  
as instructed.  
temperature.  
B. Water, oil, or dirt in CO2  
supply.  
B. Remove contaminated CO2  
supply. Clean CO2 system (lines,  
regulators, etc.) using a mild  
detergent. Replenish with a clean  
CO2 supply.  
DISPENSED PRODUCT  
COMES OUT OF  
A. Oil film or soap scum in cups.  
A. Use clean cups.  
DISPENSING VALVE CLEAR  
BUT FOAMS IN CUP.  
B. Ice used for finished drink is  
sub-cooled.  
B. Do not use ice directly from  
freezer. Allow ice to become wet’  
before using. (Refer to following  
NOTE)  
NOTE: Crus hed ice als o caus es dis pens ing problems . When finis hed drink hits s harp edges of ice,  
carbonation is releas ed from finis hed drink.  
DISPENSED PRODUCT  
PRODUCES FOAM AS IT  
LEAVES DISPENSING VALVE.  
A. Carbonator CO2 regulator  
pressure set too high for  
existing water conditions or  
temperature.  
A. Reduce carbonator CO2 regulator  
pressure setting as instructed.  
B. Syrup over-carbonated with  
CO2.  
B. Remove soft drink tank quick  
disconnects. Relieve tank CO2  
pressure, shake tank vigorously,  
then relieve tank CO2 pressure as  
many times as necessary to  
remove over-carbonation.  
C. Tapered nylon washer inside  
tube swivel nut connection  
distorted from being  
C. Replace nylon washer. Make sure  
washer is properly seated in  
swivel nut.  
overtightened restricting syrup  
flow.  
ONLY CARBONATED WATER A. Quick disconnect not secure  
DISPENSED. on soft drink tank.  
A. Secure quick disconnect on soft  
drink tank.  
B. Out of syrup.  
B. Replenish syrup supply as  
instructed.  
C. Inoperable Dispensing Station. C. Repair Dispensing Station.  
D. Dispensing valve syrup flow  
regulator not properly  
adjusted.  
D. Adjust dispensing valve syrup  
flow regulator (refer to Installation  
Instructions provided with  
Dispensing Station).  
31  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble  
Probable Cause  
Remedy  
ONLY CARBONATED WATER E. Dispensing valve syrup flow  
E. Sanitize syrup system as  
instructed.  
DISPENSED (cont).  
regulator, soft drink tank quick  
disconnect, or syrup lines  
restricted.  
ONLY SYRUP DISPENSED.  
A. Plain water inlet supply line  
shutoff valve closed.  
A. Open plain water inlet supply line  
shutoff valve.  
B. CARBONATOR MOTOR  
power switch in OFF’  
position.  
B. Place switch in ON position.  
C. Water filter clogged.  
C. Replace water filter.  
WARM PRODUCT BEING  
DISPENSED.  
A. Carbonated water circulating  
pump CIRCULATING MOTOR  
power switch in OFF’  
position.  
A. Place circulating pump  
CIRCULATING MOTOR power  
switch in ON position.  
B.  
Inoperable carbonated water  
circulating pump or motor.  
B. Replace pump or motor.  
WATER PUMP MOTOR WILL  
NOT OPERATE.  
A. Inoperative water pump motor. A. Replace water pump motor.  
B. Water safety thermostat  
inoperative.  
B. Replace safety thermostat.  
C. Loose connections and/or  
open electrical circuit.  
C. Tighten connections and/or repair  
open circuit.  
D. Overheated motor cut off by  
thermal overload protector.  
D. Check for proper line voltage.  
Check for restricted pump  
discharge.  
E. Water pump binding (new or  
replacement pumps only.)  
E. Remove water pump from motor,  
rotate pump or motor shaft 180  
degrees, then recouple pump to  
motor.  
F. Inoperative liquid level sensing F. Replace liquid level sensing  
probe. probe.  
G. Inoperative liquid level sensing G. Replace liquid level sensing PC  
PC board.  
board.  
H. No 24 VAC to liquid level  
sensing PC board.  
H. Check electrical wiring and  
transformer for 24 VAC output.  
WATER PUMP MOTOR WILL  
NOT SHUT OFF.  
A. Inoperative liquid level sensing A. Replace liquid level sensing  
probe. probe.  
B. Inoperative liquid level sensing B. Replace liquid level sensing PC  
PC board.  
board.  
C. Liquid level sensing probe  
wired wrong.  
C. Correct liquid sensing probe  
wiring.  
D. Leak in carbonated water  
system.  
D. Repair leak in carbonated water  
system.  
ERRATIC CYCLING OF  
CARBONATOR.  
A. Inoperative liquid level sensing A. Replace liquid level sensing  
probe. probe.  
B. Inoperative liquid level sensing B. Replace liquid level sensing PC  
PC board. board.  
300614000  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble  
Probable Cause  
Remedy  
ERRATIC CYCLING OF  
CARBONATOR (cont).  
C. Liquid level sensing probe  
wired wrong.  
C. Correct liquid level sensing probe  
wiring.  
D. Dirty or oily liquid level sensing D. Clean liquid level sensing probe.  
probe.  
WATER PUMP MOTOR  
OPERATES BUT WATER  
PUMP DOES NOT PUMP  
WATER.  
A. Water inlet supply line shutoff  
valve closed.  
A. Open water inlet supply line  
shutoff valve.  
B. Kinked water inlet supply line.  
B. Straighten water inlet supply line.  
C. Remove restriction.  
C. Restriction between water  
pump outlet and carbonator  
tank inlet.  
D. Foreign object in water pump  
bypass.  
D. Clean bypass. (Note: Count  
number of turns bypass screw  
makes when removing and install  
same number of turns).  
E. Water pump worn out.  
E. Replace water pump.  
WATER PUMP CAPACITY  
TOO LOW.  
A. Water supply capacity too low. A. Water inlet supply must be at a  
minimum of 300-gallons per hour  
with a maximum water pressure  
of 80-psi.  
B. Water filter clogged.  
B. Replace water filter cartridge as  
instructed.  
C. Inoperative water pump.  
C. Replace water pump.  
TROUBLESHOOTING REFRIGERATION SYSTEM  
COMPRESSOR DOES NOT  
OPERATE.  
A. Ice bank sufficient.  
A. Refrigeration not called for.  
B. REFRIGERATION POWER  
switch in OFFposition.  
B. Place REFRIGERATION POWER  
switch in ON position.  
C. Electrical power to Cooling  
Unit turned off.  
C. Turn on electrical power to  
Cooling Unit.  
D. No Cooling Unit power source. D. Replace fuse or reset circuit  
Blown fuse or tripped circuit  
breaker.  
breaker.  
E. Loose, disconnected, or  
broken wiring.  
E. Tighten connections or replace  
broken wiring.  
F. Hi-pressure cutout switch  
tripped.  
F. Reset pressure switch (see  
REFRIGERATION SYSTEM  
TEMPERATURE SENSING  
DEVICE AND HIGH-PRESSURE  
CUTOUT SWITCH in  
OPERATORS INSTRUCTIONS  
SECTION.  
G. Low Voltage.  
G. Voltage must be at least 208 volts  
at compressor terminals when  
compressor is trying to start.  
H. Inoperable run capacitor, start H. Replace inoperable part.  
capacitor, or relay.  
I.  
Inoperable compressor.  
I.  
Replace compressor.  
33  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble  
Probable Cause  
Remedy  
COMPRESSOR DOES NOT  
OPERATE (cont).  
J. Inoperable control board  
J. Replace control board.  
K. Inoperable contactor  
K. Replace contactor.  
L. No voltage to control board.  
L.  
Check for loose or broken wiring.  
Check 240/24 VAC power  
transformer for 24 VAC output.  
(see NOTE below).  
M. Inoperable control board or  
water/ice sensor PC board.  
M. Replace control board.  
N. Inoperable ICE SENSOR.  
N. Replace ICE SENSOR.  
O. EVAP IN, COND OUT, or  
EVAP OUT sensor is open,  
shorted, or out of temperature  
range.  
O. Replace inoperable sensor.  
P. Hydro Boostâ WATER  
SENSOR is shorted or open  
circuit.  
P. Check for loose, broken, or  
disconnected wire or plug at  
pre-cool coil. Repair or replace  
wire or secure plug. If Hydro  
Boostâ WATER SENSOR is  
inoperable, replace sensor.  
NOTE: Confirm which s ens or has failed by us ing the Aurora Series Sys tem Analyzer (P/N 309197-000).  
NOTE: The 240/24 VAC power trans former has an overload res et button located on its 24 VAC output  
s ide (s ee Figure 3). An overload on the trans former will caus e its res et button to pop out dis rupting  
the 24 VAC output to the main control board. Overload button mus t be pres s ed in to res tore 24 VAC  
output.  
COMPRESSOR OPERATES  
CONTINUOUSLY BUT DOES  
NOT FORM SUFFICIENT ICE  
BANK  
A. Cooling capacity is exceeded  
by overdrawing.  
A. Reduce amount of drinks drawn  
per given time.  
B. Air circulation through Remote B. Check and if necessary, clean  
Condenser Coil and Fan  
Assembly Condenser Coil is  
restricted.  
condenser coil as instructed.  
C. Insufficient refrigerant charge.  
C. Check Cooling Unit sight glass for  
bubbles or liquid break. Find and  
repair refrigeration leak, the  
replenish refrigerant charge.  
D. Inoperative or disconnected  
pulse-modulating expansion  
valve (see REFRIGERATION  
FLOW DIAGRAM).  
D. Check that expansion valve is  
operating by touch (should be  
able to feel valve pulse).  
Check for loose or disconnected  
wire to solenoid coil. If necessary,  
troubleshoot expansion valve with  
a gage set to see if it is opening.  
If expansion valve is not opening,  
suction pressure will be in a  
vacuum.  
300614000  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble  
Probable Cause  
Remedy  
COMPRESSOR OPERATES  
CONTINUOUSLY BUT DOES  
NOT FORM SUFFICIENT ICE  
BANK (cont).  
E.  
Inoperative control board. No  
output from board to  
solenoids.  
E. Check LEDs on control board to  
see if they are modulating. Check  
for 24V output to pulse  
modulating expansion valve (see  
WIRING DIAGRAM).  
If control board green LED is on  
and yellow LED Is flashing; but no  
24V output, replace board.  
CONDENSER FAN MOTOR  
NOT OPERATING  
A. Blown power circuit fuse.  
B. Fan blade obstructed.  
A. Replace power circuit fuse.  
B. Remove obstruction.  
C. Inoperative condenser fan  
motor.  
C. Replace condenser fan motor.  
D. Compressor contactor  
inoperable.  
D. Replace compressor contactor.  
A. Remove obstruction.  
AGITATOR MOTOR NOT  
OPERATING.  
A. Agitator motor propeller  
obstructed.  
B. Low voltage.  
B. Voltage must be at least 208 volts  
at compressor terminals when  
compressor is trying to start.  
C. Loose, disconnected, or  
broken wiring.  
C. Tighten connections or replace  
broken wiring.  
D. Inoperative agitator motor.  
D. Replace agitator motor.  
35  
300614000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un-  
der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire prod-  
uct, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the  
equipment model number, serial number and the date of purchase.  
IMI Cornelius Offices  
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166  
AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930  
BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552  
D
FAX (32) 3 665 2307  
BRAZIL D RUA ITAOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829  
ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644  
FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201  
GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438  
GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491  
HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222  
ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814  
NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361  
SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604  
SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379  
USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255  
LD004  
4/21/98  
300614000  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE LEFT BLANK INTENTIONALLY  
300614000  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMI CORNELIUS INC.  
CORPORATE HEADQUARTERS:  
One Cornelius Place  
Anoka, Minnesota 55303-6234  
(612) 421-6120  
(800) 238-3600  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Cortelco Conference Phone 2204 User Manual
Curtis Portable CD Player CD 290 User Manual
Digi Switch MIL 4511H User Manual
Dynex Microphone DX USBMIC 13 User Manual
Extron electronic Tablet Accessory 68 1407 01 User Manual
Federal Security Camera Speaker 300GC User Manual
Flip Video TV Cables 100210 RR User Manual
GE Dishwasher GHD3500 series GSD3400 series User Manual
Generac Pressure Washer 1292 2 User Manual
Gigabyte Network Card GN WPKG User Manual