Cooper Bussmann Switch Electronics Short Circuit Current Rating User Manual

Simplified Guide To  
Understanding  
Short-Circuit Current Rating  
FIND IT, FIX IT, FORGET IT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use this table to initiate the process of identifying the short-circuit current rating of your  
components and devices in power circuits. For further information contact your local  
Cooper Bussmann sales engineer, Cooper Bussmann Application Engineering,  
Supply Disconnect and OCPD  
200kA*  
5kA  
200kA*  
10kA**  
10kA  
5kA  
Feeder Circuit OCPD and Components  
200kA*  
5kA  
200kA*  
10kA**  
10kA  
200kA*  
Branch Circuit OCPD and Components  
200kA*  
5kA  
200kA*  
10kA**  
5kA***  
5kA***  
5kA  
+
*Class CC, J, T, R, and L UL248 Branch Circuit Type Fuses.  
**When used in conjunction with Class CC, J, T, R, and L UL248 Branch Circuit Type Fuses.  
***50HP or less 480V  
+Combination Rating is used for Sweep 1.  
For Sweep 2 IR=5kA (Default Value)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary of Terms  
Industrial Control Panel - An assembly of a  
systematic and standard arrangement of two or more  
components such as motor controllers, overload relays,  
fused disconnect switches, fuses, and circuit breakers  
and related control devices such as pushbutton  
stations, selector switches, timers, switches, and  
control relays with associated wiring, terminal blocks,  
pilot lights and similar components.  
Default  
Value  
Your  
Value  
Interrupting Rating - The highest current at rated  
voltage that a device is intended to interrupt under  
standard test conditions.  
Short-Circuit Current Rating – The prospective  
symmetrical fault current at a nominal voltage to which  
an apparatus or system is able to be connected without  
sustaining damage exceeding the defined acceptance  
criteria  
Control Circuit – A circuit that carries the electric  
signals directing the performance of a controller, and  
which does not carry the main power circuit. A control  
circuit is, in most cases, limited to 15 amp.  
10kA  
5kA  
Power Circuit – Conductors and components of  
supply, branch, and feeder circuits, supplying main line  
power to loads such as heaters, motors, lighting,  
receptacles, power transformers, and appliances.  
200kA*  
5kA***  
5kA***  
5kA***  
5kA***  
10kA  
2kA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Find It, Fix It, Forget It  
FIND IT – Look for... the Weakest Link  
3. Buy more expensive components with  
higher ratings — A 65kA circuit breaker will more  
than double your cost compared to a 14kA circuit  
breaker. The fusible solution provides an interrupting  
rating as high as 200kA, at a comparable cost to your  
existing design, making it the most economical solution.  
The SCCR marking for the assembly will be based  
upon the lowest short-circuit current or withstand rating  
of any power circuit component contained within the  
assembly — or the “weakest link”. Many components  
used in industrial control panels, industrial machinery  
and HVAC equipment may be the weakest link,  
including:  
• motor controllers  
• definite purpose contactors  
• supplemental protectors  
• circuit breakers (with low interrupting ratings)  
• power distribution blocks.  
FORGET IT — Use Current-Limiting Fuses  
Not only can modern current-limiting fusible solutions  
fix undesired weak links and obtain a high assembly  
short-circuit current rating, they can also provide  
enhancements to your design in the areas of flexibility  
of installation, increased workplace safety, and reliable  
protection through the life of your equipment. These  
enhancements take care of the hassle associated with  
equipment with limited ratings so you can FORGET IT!  
FIX IT — How To Get A Higher SCCR So  
Equipment Isn’t Limited  
Benefits of Using Cooper Bussmann Current-  
Limiting Fuses  
Straight Voltage Ratings:  
• Straight voltage ratings allow for more installations where  
equipment can be installed. Straight voltage rated  
equipment can be installed in any type of electrical system.  
With a straight voltage rating you can ship it anywhere and  
not have to worry.  
By fixing these weakest links, higher SCCRs can be  
achieved. In general, there are three options:  
1. Use overcurrent protective devices with  
higher interrupting ratings — Overcurrent  
protective devices with low interrupting ratings often  
become the weakest link and limit the SCCR of the  
assembly. The interrupting ratings of the overcurrent  
protective devices used directly affects the assembly  
rating. The only fix is to use devices with higher  
interrupting ratings.  
High Assembly SCCRs:  
• High SCCRs allow for more applications where equipment  
can be installed. With a high SCCR you can ship it  
anywhere and not have to worry.  
Circuit Breaker &  
Motor Starter  
Combination  
Fuse & Motor Starter  
Combination  
• Fusible disconnect with  
Cooper Bussmann LP-CC  
fuses marked interrupting  
rating 200kA  
• Three-pole circuit  
breaker marked  
• A wider range of fault current levels provides assurance that  
the equipment will be installed correctly and safely.  
• Meets the UL508A and NEC® requirements for SCCR  
marking.  
interrupting rating 14kA  
• Motor starter marked  
50kA when protected by  
fuses or circuit breakers  
• Motor starter marked 50kA  
when protected by fuses or  
circuit breakers  
• The SCCR is 50kA  
• The SCCR is 14kA  
• Marketing advantage over competitive equipment with a  
lower rating.  
2. Use current limitation to fix low rated  
components — It only takes one component with a  
low SCCR to limit the entire assembly. Many of the  
components used in industrial control applications have  
low short-circuit current ratings. Fix these low rated  
components and the assembly rating by using  
current limitation. Since current-limiting fuses reduce high  
level short-circuit currents to a minimal level, they allow  
the use of these lower rated devices while  
Increased Flexibility In Panel Use and Installation:  
• Valuable time that was spent gathering information for  
proper application is drastically reduced with fuses because  
modern current-limiting fuses can provide high assembly  
SCCRs and straight voltage ratings since they have:  
- High Interrupting Ratings of 200,000A or more  
- Excellent current limitation to protect low rated  
components at high short-circuit current levels  
providing a higher SCCR.  
- Straight voltage ratings so they can be installed in any  
type of application independent of the grounding scheme  
used, unlike devices with a slash voltage rating which are  
limited to installation in ONLY a solidly grounded wye  
type system  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooper Bussmann Products And  
Technical Support Delivered Worldwide  
Customer Assistance  
Customer Satisfaction Team  
Application Engineering  
Application Engineering assistance is available to all  
customers. The Application Engineering team is staffed  
by degreed electrical engineers and available by phone  
with technical and application support Monday – Friday,  
8:00 a.m. – 5:00 p.m. Central Time.  
The Cooper Bussmann Customer Satisfaction Team is  
available to answer questions regarding Cooper  
Bussmann products and services. Calls should be made  
between 8:00 a.m. – 4:30 p.m. Central Time  
for all US time zones.  
The Customer Satisfaction Team can be reached via:  
• Phone: 636-527-3877  
Toll-free fax: 800-544-2570  
• E-mail: [email protected]  
Application Engineering can be reached via phone, fax  
or email:  
• Phone: 636-527-1270  
• Fax: 636-527-1607  
• E-mail: [email protected]  
Emergency and After-Hours Orders  
To accommodate time-critical needs, Cooper Bussmann  
offers emergency and after-hours service for next flight  
out or will call. Customers pay only standard price for  
the circuit protection device, rush freight charges and a  
modest emergency fee for this service. Emergency and  
after-hours orders should be placed through the  
Customer Satisfaction Team. Call:  
Online Resources  
services:  
• Product cross reference  
• Arc-flash calculator  
• SCCR calculator  
• Training modules  
• 8:00 a.m. – 4:30 p.m. Central Time 636-527-3877  
• After hours 314-995-1342  
Your Authorized Cooper Bussmann Distributor is:  
©2005 Cooper Bussmann St. Louis, MO 63178  
636-394-2877 www.cooperbussmann.com  
Reorder #7009 11-05-5M  
Printed in USA  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Continental Electric Food Processor CE22391 User Manual
Cornelius Ice Maker UC 700 Series User Manual
Cortelco Telephone 2747 User Manual
Elation Professional Laminator 36 PRO User Manual
Electro Voice Microphone 1777 User Manual
Electro Voice Speaker System QRx 118S User Manual
Fellowes Air Cleaner AP 230H User Manual
Fisher Paykel Oven BI453 User Manual
Fisher Price Baby Toy 78333 User Manual
GE DVD Player DV 354 User Manual