INSTALLATION,
OPERATION
&
MAINTENANCE
MANUAL
SINGLE PACKAGED ROOF TOP AIR CONDITIONERS
'PT' SERIES
MODELS: PT036 - PT360
Part Number: 800-213-03
Download from Www.Somanuals.com. All Manuals Search And Download.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
GENERAL
GENERAL STATEMENT
This unit is from the PT series that was designed & built for the optimum performance. However, it is required that you become well
acquainted with good practices for the proper installation/operation/and maintenance procedures in order to ensure a safe trouble free
operation, year after year.
Please read through the whole manual contents before you attempt to install/operate/ and maintain the unit.
Most of the procedures described in this manual require certain skills and experience. The installation and other maintenance procedures
should be performed only by highly skilled and experienced technicians. The end user’s role should be limited to the cleaning of the
filter.
Please consult your nearest “COOLINE” representative for further information.
The PT units can be supplied, depending on the End User requirement, as the basic “Cool Only” version, or the “Heat & Cool” version
(with electric heater module).
WARRANTY
All of the PT series of Packaged Roof Top Units are covered by the standard warranty terms against any manufacturer defect. Should
you encounter any problem that falls under the warranty terms please contact your nearest “COOLINE” representative.
SAFETY ISSUES
There are three degrees of safety hazards that are identified throughout this manual as WARNING (where the situation will result in
personal injury), CAUTION (where personal injury might occur), and ATTENTION (where minor personal injury and/or property dam-
age could happen). Please understand and respect those identifications.
WARNING: The PT units operate on a high voltage with moving parts (at high speed) which can lead to serious injuries and/
or damage to the unit. Never attempt to service the unit unless the main electrical power supply has been disconnected.
CAUTION: Extra care should be observed when installing, test running, adjusting, servicing, or maintaining the unit as the
hazard of explosion, fire, electrical shock, and potential personal injury and property damage are present.
When performing any task pertaining to the installation and maintenance of the unit, the skilled technician should observe all the
applicable safety measures (wear of safety helmet, boots, gloves, and goggles. Use of proper handling materials for brazing and use
of wet cloth for quenching. A fire extinguisher should be easily accessible etc.). He should also read all the instructions and information
in this Manual prior to attempting to perform any installation or servicing of the unit.
All applicable local codes should also be observed.
INSPECTION FOR DAMAGE
The unit should be carefully inspected visually for any sign of physical damage due to mishandling. Whenever a damage is detected,
please indicate it on the corresponding delivery note before you sign it and inform your nearest “COOLINE” office.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
GENERAL
These units are shipped completely assembled, charged, and wired. They do not require any field installation of refrigerant tubing.
Units require external power, thermostat wiring, condensate drain piping and ducting as applicable.
Size of unit for an installation should be based on a heat gain calculation made according to applicable standards. Units must also be
installed in accordance with regulations of the "National Fire Protection Association" and local electrical codes. Where local regulations
conflicts with the instructions in this manual, installer should adhere to local standards.
Prepare your concrete pad or steel stand based on the corresponding dimensions. Remove shipping protective covers and wooden
crating and lift unit from base and place in position with suitable rubber vibration isolators.
All field installed accessories are to be installed by the customer with necessary reinforcements as required.
LOCATION OF UNIT
When selecting the location for the unit, the following points should be kept in mind:
1. Provisions for a concrete pad or steel stand base.
2. That the terrain allows for drainage away from the unit.
3. If the unit is to be roof mounted, inspect the roof for load bearing capacity. The roof should have sufficient structural strength to
carry the weight of the unit.
4. Install unit on vibration isolation pads, i.e. on rubber mounting pads.
5. Availability of electric power.
6. To position the unit for unrestricted air circulation of the condenser air inlet and to prevent any possibility of air recirculation from the
condenser fan discharge air (see figure on next page).
7. Check minimum clearances required for your unit, with regard to walls, or other obstructions (see figure on next page).
8. Air cooled equipment should not be installed under low structural overhangs which can cause condenser air recirculation or
restriction. Observe minimum of clearance (see figure on next page).
9. Care should be taken to prevent air from other sources from entering condenser, if this air is at a high temperature.
10. Level the unit on its final location and be sure that the levelling tolerance is ±5 mm per linear meter in any direction.
CAUTION: Do not install the unit as indoor unit, install it in an open area, and unit air inlets must not be located near exhaust
vents or other source of contaminated air.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE CLEARANCE
MODELS: PT036 - PT120
MODELS: PT180 - PT360
D
D
E
C
A
C
A
B
B
NOTE: Only two condenser fans for models PT180 - PT240.
NOTE: All dimensions are in cm.
MODEL
DIMENSIONS
MODEL
NUMBER
PT180
PT215
PT240
DIMENSIONS
NUMBER
PT036
PT048
PT060
PT075
PT090
PT100
PT120
A
B
C
D
A
B
C
D
E
85
85
85
90
90
90
90
105
105
105
105
105
105
105
85
85
85
90
90
90
90
150
150
150
200
200
200
200
120
120
120
120
120
120
120
120
115
115
115
115
250
250
250
250
90
90
90
90
PT300
PT360
120
120
115
250
90
A : Clearance dimension from condenser coil
B : Clearance dimension from compressor, control box & evaporator coil
C : Clearance dimension from condenser coil & blower
D : Clearance dimension over the condenser fan
A :Clearance dimension from condenser coil
B :Clearance dimension from compressor, control box, blower, evaporator coil & filter
C :Clearance dimension from condenser coil & filter
E : Clearance dimension from filter access panel
D :Clearance dimension over the condenser fan
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS
• Insert 2" nominal pipe through holes in the base rail as shown in the figure below for slings.
• Holes in base rail are centered around the unit center of gravity.
• Use wooden pallet or spreader bar when rigging, to prevent the slings from damaging the unit.
• Rollers may be used to move the unit on the roof or ground.
CAUTION: All panels should be in place when rigging.
MODELS: PT036 - PT360
LIFT
LIFT
SPREADER BAR
PROPER CLEARANCE TO BE
PROVIDED.
COMPRESSOR
END
Note:
1 .PIPE DIA 1 1/2" FOR PT036 TO PT075 MODELS
2. PIPE DIA 2" FOR PT090 TO PT360 MODELS
NOMINAL PIPE THRU UNIT FOR SLINGS TO AVOID BASE DAMAGE.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDENSATE DRAIN CONNECTION
•
Use standard PVC pipe with NPT connection for the condensate drain. Provide a 'P' trap immediately at the condensate drain connection.
• Piping has to be sloped away from the unit.
• Remember to remove the drain hole plug before operating the unit. Avoid bends & elbows.
DUCT CONNECTION
The units can be connected to the ducting in horizontal configuration. Connect ducting using flexible duct connection. The duct should
be properly designed and the drive package should match the required CFM & corresponding external static pressure.
ATTENTION: Avoid abrupt changes in size and/or direction of duct to ensure proper unit performance.
ELECTRIC HEATERS
Electric heater kit is installed in the unit at the supply air opening space.
UNIT WEIGHT & WEIGHT DISTRIBUTION
WEIGHTS (Kg.)
MODEL
NUMBER
J
K
36
41
45
52
92
91
91
99
89
94
130
145
M
51
L
34
P
Q
PT036
PT048
PT060
PT075
PT090
PT100
PT120
PT180
PT215
PT240
PT300
PT360
67
-
-
72
57
39
-
-
-
-
76
62
42
86
70
45
-
-
116
134
135
155
182
186
226
256
95
73
-
-
98
73
-
-
98
73
-
-
152
94
85
108
177
181
221
249
105
103
107
158
175
101
105
148
151
98
202
216
J
P
K
CONDENSER SECTION
M
Q
L
SUPPLY AIR/
RETURN AIR
6
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT DIMENSIONS
PT036 - PT075
POWER SUPPLY INLET
AIR IN
CONDENSER COIL
CONDENSATE DRAIN OUTLET [BOTH ENDS]
MOUNTING HOLES Ø
13 [0.5] [ 4 EACH]
TOP VIEW
SUPPLY
AIR
OPENING
ACCESS PANEL
FOR BLOWER
AND MOTOR
SUPPLY AIR
FILTER ACCESS
PANEL [BOTH ENDS]
CONDENSER COIL
COMPRESSOR/CONTROLS
ACCESS PANEL
RETURN AIR
OPENING
FRESH AIR
OPENING
RETURN AIR
DRAIN OUTLET
[BOTH ENDS]
51 [2.00]
15 [0.59]
SIDE VIEW
FRONT VIEW
SIDE VIEW
DIMENSIONS
MODEL
A
B
C
D
E
F
G
H
J
K
L
M
PT036 - PT060 1460(57.48) 1025(40.35) 1430(56.3)
PT075 1775(69.88) 1150(45.28) 1745(68.7)
700(27.56) 163(6.42) 373(14.68) 250(9.84) 500(19.69) 57(2.24) 304(11.96) 343(13.49) 340(13.39)
800(31.5) 175(6.89) 480(18.9) 325(12.8) 672(26.46) 80(3.15) 280(11.02) 275(10.83) 600(23.62)
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT DIMENSIONS
PT090 - PT120
TOP VIEW
SIDE VIEW
FRONT VIEW
SIDE VIEW
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT DIMENSIONS
PT180
TOP VIEW
SIDE VIEW
FRONT VIEW
SIDE VIEW
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT DIMENSIONS
PT215 - PT240
TOP VIEW
SIDE VIEW
SIDE VIEW
FRONT VIEW
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT DIMENSIONS
PT300 - PT360
TOP VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
CABLE SIZE
• All wiring should be in accordance with local standards.
• Before making any connection, check the electric power supply, it must have the same characteristics as what is displayed in the
nameplate.
• For selecting cable size, refer to wire ampacity table at different MCA (Minimum Circuit Amps) provided in unit electrical data, which
is listed as a guideline (see table below).
• Wiring connection to the unit must have suitable insulation of a minimum temperature of 600C.
CONDUCTOR SIZE
POWER
SUPPLY
MODEL
No.
MCA
METRIC
MM2
AWG
PT036
PT048
PT060
PT075
PT090
PT100
PT120
PT180
PT215
PT240
PT300
15.2
20.8
22.1
20.9
25.1
30
33.6
54.8
60
14
12
12
12
10
10
8
6
6
4
2.5
4
4
4
6
6
380/415-3-50
(4 wire)
10
16
16
25
26.6
65
80.3
3
PT360
92.8
2
33.6
LEGEND: MCA - Minimum Circuit Amps
Notes: 1. Customer is to select cable size also with cross reference as per cable manufacturer data for voltage reduction per unit
length. The above cable ampacity table is for guidance only.
2. The selected cables for specified units is as per following characteristics:
a. Unit without electric heaters.
b. Any extra electrical accessories shall add to MCA rate, for more information, refer to unit electrical tables in the catalog.
OPERATION INSTRUCTIONS
START-UP INSPECTION & CHECK LIST
After the installation is completed in all respect, the following points should be covered before the system is switched on for operation.
1. Check unit location as per installation instructions.
2. Make sure all electrical fasteners/connections are tight and clean.
3. All controls are set according to manufacturer's instructions (low & high pressure switch, pump down solenoid, etc...)
4. Make sure all valves are open (compressor suction & discharge service valves, liquid line, etc.).
5. Follow all the instructions from the warning tags and stickers.
6. Check if condenser & blower fan are free to turn without wobbling.
7. Remove straps & wooden pieces that holds the compressor in place during transportation.
8. Compressor crankcase heater should be energized for 24 hours (special attention should be taken to disable compressor contactor
before energizing the unit.
9. Expansion valve bulb is strapped properly at correct location (applicable for PT075 - PT360 only).
10. Circuit breaker/fused disconnect switch.
11. Blower fan belt is properly tightened and pulleys are properly aligned (applicable for PT075 - PT360 only).
12. All refrigerant service valve caps are installed.
13. All piping, piping insulation and piping supports are properly installed.
14. Thermostat is the right one and installed properly.
15. Connect the manifold gauge to suction & discharge line service valves. Prepare recommended instruments for checking Voltage,
Amps, RPM, CFM, static pressure, etc.
16. Start the blower fan and condenser fan. Check the amperage against the nameplate ampere.
17. Start the compressor & observe the compressor discharge and suction pressures. If not within system design limits, determine
why & take corrective action.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTRICAL DATA
MODELS: PT036 - PT060
VOLTAGE
RANGE
FM
COMPRES-
SOR
BLOWER
MOTOR
ELECTRIC
HEATER
POWER
SUPPLY
(V-Ph-Hz)
LEGEND:
MODEL
NUMBER
MCA
MOCP
FLA
HP
- Full Load Amps
MIN. MAX. FLA RLA LRA
HP
FLA
kW
FLA
–
–
15.2
20
- Horse Power
5/6
7.6/9.1 16.4/18.3 20/20
PT036
380/415-3-50 342
(4 WIRE)
457
457
457
2.3
2.3
2.3
5.9
10.4
9.6
42
55
65
0.75
5.5
5.5
7.8
BM
- Blower Motor
7.5/10* 11.4/15.2 21.1/25.9 25/30
12*
–
18.2
–
29.6
20.8
30
30
LRA
RLA
- Locked Rotor Amps
- Rated Load Amps
5/6
7.6/9.1 20.8/20.8 30/30
380/415-3-50 342
(4 WIRE)
0.75
PT048
PT060
7.5/10* 11.4/15.2 21.1/25.9 35/30
MCA - Minimum Circuit Amps
12*
–
18.2
–
29.6
22.1
30
30
MOCP - Maximum Over Current Protection
5/6
7.6/9.1 22.1/22.1 30/30
FM
- Fan Motor (Condenser)
380/415-3-50 342
(4 WIRE)
1
7.5/10* 11.4/15.2 24/28.8
30/30
35
*Combination of heater modules
12*
18.2
32.5
MODELS: PT075 & PT090
MODEL NUMBER
DESCRIPTION
PT075
PT090
COMPR-
ESSOR
(each)
COMPR-
ESSOR
(each)
VOLTAGE
POWER
ELECTRIC
HEATER
ELECTRIC
HEATER
FM
(each)
BM
BM
RANGE
SUPPLY
MCA
MOCP
MCA
MOCP
(V-Ph-Hz)
Min.
Max.
FLA
RLA LRA HP FLA Nom. kW
FLA
RLA LRA HP FLA Nom. kW
FLA
–
–
24
24/24
24/24
27.3/33
42.5
30
30/30
30/30
30/35
45
–
–
20.7
30
5/6
7.6/9.1
5/6
7.6/9.1
20.7/20.7
30/30
30/30
30/35
30
1.5 3.4
2
3.6
4.7
7.5/10* 11.4/15.2
12*/15* 18.2/22.8
20*
–
7.5/10* 11.4/15.2 20.7/23.3
12*/15* 18.2/22.8
27/32.8
30.4
380/415-3-50 (4 WIRE)
342
457
2.3
12 101
8.2 50
–
25.1
30
(1.9 FOR
PT090)
–
–
20.9
5/6
7.6/9.1
25.1/25.1
30/30
30/30
30/35
45
5/6
7.6/9.1
20.9/20.9
30/30
30/30
30/35
2
3.6
3
7.5/10* 11.4/15.2 25.1/25.1
12*/15* 18.2/22.8 28.6/34.4
20*
7.5/10* 11.4/15.2 20.9/23.5
12*/15* 18.2/22.8
27.3/33
30.4
43.9
MODELS: PT100 & PT120
MODEL NUMBER
DESCRIPTION
PT100
PT120
COMPR-
ESSOR
(each)
COMPR-
ESSOR
(each)
VOLTAGE
POWER
ELECTRIC
HEATER
ELECTRIC
HEATER
FM
(each)
BM
BM
RANGE
SUPPLY
MCA
MOCP
MCA
MOCP
(V-Ph-Hz)
Min.
Max.
FLA
RLA LRA HP FLA Nom. kW
FLA
RLA LRA HP FLA Nom. kW
FLA
–
–
29.1
35
35/35
35/35
35/45
60
–
–
28.9
35
7.5/10
11.4/15.2 29.1/29.1
10*/12* 15.2/18.2 29.1/29.1
15*/20* 22.8/30.4 34.4/43.9
7.5/10
11.4/15.2 28.9/28.9
35/35
35/35
35/45
40
2
3.6
4.7
3
4.7
9.2
10*/12* 15.2/18.2 28.9/28.9
15*/20* 22.8/30.4
33/42.5
25*
–
38
53.4
380/415-3-50 (4 WIRE)
342
457
1.9
10.4 55
10 74
–
33.6
40
–
–
30
7.5/10
11.4/15.2 33.6/33.6
40/40
40/40
40/50
60
7.5/10
11.4/15.2
30/30
30/30
40/40
40/40
40/45
3
5
10*/12* 15.2/18.2 33.6/34.3
15*/20* 22.8/30.4
25* 38
10*/12* 15.2/18.2
40/49.5
15*/20* 22.8/30.4 34.4/43.9
59
13
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTRICAL DATA
MODELS: PT180 & PT215
DESCRIPTION
MODEL NUMBER
PT180
PT215
COMPR-
ESSOR
(each)
COMPR-
ESSOR
(each)
VOLTAGE
RANGE
ELECTRIC
HEATER
ELECTRIC
HEATER
FM
(each)
POWER
SUPPLY
(V-Ph-Hz)
BM
BM
MCA
MOCP
MCA
MOCP
Min.
Max.
FLA
RLA LRA HP FLA Nom. kW
FLA
RLA LRA HP FLA Nom. kW
FLA
–
–
51
60
–
–
56.2
70
7.5/10
11.4/15.2
10*/12* 15.2/18.2
15*/20* 22.8/30.4
25*/30* 38/45.6
51/51
51/51
51/51
59/68.5
54.8
60/60
60/60
60/60
60/70
70
7.5/10
11.4/15.2 56.2/56.2
10*/12* 15.2/18.2 56.2/56.2
15*/20* 22.8/30.4 56.2/56.2
70/70
70/70
70/70
70/70
70
5
9.2
5
9.2
17.3 111
25*/30* 38/45.6
–
59/68.5
&
&
380/415-3-50 (4 WIRE)
342
457
1.9
19.2 125
–
–
–
60
16.4 95
7.5/10
11.4/15.2 54.8/54.8
70/70
70/70
70/70
70/80
7.5/10
11.4/15.2
60/60
60/60
60/60
63.8/73.3
7070
70/70
70/70
70/80
7.5 13
7.5 13
10*/12* 15.2/18.2 54.8/54.8
15*/20* 22.8/30.4 54.8/54.8
25*/30* 38/45.6
10*/12* 15.2/18.2
15*/20* 22.8/30.4
25*/30* 38/45.6
63.8/73.3
MODELS: PT240 & PT300
MODEL NUMBER
DESCRIPTION
PT240
PT300
COMPR-
ESSOR
(each)
COMPR-
ESSOR
(each)
VOLTAGE
ELECTRIC
HEATER
ELECTRIC
HEATER
FM
(each)
POWER
RANGE
SUPPLY
BM
BM
MCA
MOCP
MCA
MOCP
(V-Ph-Hz)
Min.
Max.
FLA
RLA LRA HP FLA Nom. kW
FLA
RLA LRA HP FLA Nom. kW
FLA
–
–
60.9
80
–
–
78.2
100
7.5/10
11.4/15.2 60.9/60.9
60.9/60.9
80/80
80/80
80/80
80/80
80
10*/12* 15.2/18.2 78.2/78.2 100/100
15*/20* 22.8/30.4 78.2/78.2 100/100
7.5 13
7.5 13
10*/12* 15.2/18.2
15*/20* 22.8/30.4 60.9/60.9
25*/30* 38/45.6
–
25*/30* 38/45.6
78.2/78.2 100/100
63.8/73.3
35*/40* 53.2/60.8 82.8/92.3 100/100
380/415-3-50 (4 WIRE)
342
457
1.9
19.6 118
25.6 167
–
63
–
–
80.3
100
7.5/10
11.4/15.2
63/63
80/80
80/80
80/80
80/80
10*/12* 15.2/18.2 80.3/80.3 100/100
15*/20* 22.8/30.4 80.3/80.3 100/100
10 15.1
10 15.1
10*/12* 15.2/18.2
15*/20* 22.8/30.4
25*/30* 38/45.6
63/63
63/63
25*/30* 38/45.6
80.3/80.3 100/100
66.4/75.9
35*/40* 53.2/60.8 85.4/94.9 100/100
MODEL: PT360
MODEL NUMBER
PT360
DESCRIPTION
LEGEND:
COMPR-
ESSOR
(each)
FLA
HP
- Full Load Amps
- Horse Power
VOLTAGE
RANGE
ELECTRIC
HEATER
FM
(each)
POWER
SUPPLY
(V-Ph-Hz)
BM
MCA
MOCP
Min.
Max.
FLA
RLA LRA HP FLA Nom. kW
FLA
BM
- Blower Motor
–
–
85.3
110
10*/12* 15.2/18.2 85.3/85.3 110/110
15*/20* 22.8/30.4 85.3/85.3 110/110
LRA
RLA
- Locked Rotor Amps
- Rated Load Amps
10 15.1
25*/30* 38/45.6
85.3/85.3 110/110
35*/40* 53.2/60.8 85.4/94.9 110/110
MCA - Minimum Circuit Amps
380/415-3-50 (4 WIRE)
342
457
1.9
27.8 198
–
–
92.8
110
MOCP - Maximum Over Current Protection
10*/12* 15.2/18.2 92.8/92.8 110/110
15*/20* 22.8/30.4 92.8/92.8 110/110
15 22.6
FM
- Fan Motor (Condenser)
25*/30* 38/45.6
92.8/92.8 110/110
*Combination of heater modules
35*/40* 53.2/60.8 94.8/104.3 110/110
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Performex-1TM CONTROLLER : OPERATION & FUNCTIONS
The COOLINE Packaged units are provided with technologically advanced new PerformexTM Controller Microprocessor Based
Electronic Control Board, incorporating the following benefits and features:
- COMPLETE UNIT CONTROL: Provides complete unit control for heating and cooling application whether single
stage or two stage utilizing the input from sensor that measure temperatures during unit operation.
- COMPRESSOR LOCKOUT: If any of the unit’s safety controls trip due to abnormal conditions the Electronic
Control locks out the compressor, preventing restart, unless attended by qualified service technicians. The unit can
be re-started only by reset the thermostat after ensuring safe system conditions.
- LEAD LAG OPERATION: The unit electronic controls automatically alternate lead and lag the compressors for
even operation. Compressor #1 can be set always lead as an option.
- ANTI-RECYCLE TIMER: For compressor safety in case of accidental manual reset or immediate recycling of
thermostat due to load demand. This considerably improves compressor life.
- PUMP DOWN OPTION: In units equipped with pump down system the time delay creates the required time gap between
the solenoid opening and compressor start to equalize the pressure in the system prior to compressor start up.
- AUTO/MANUAL RESET OF THE ALARM SIGNALS.
- FULL CONTROL OF THE INDOOR FAN: Fan operation can be selected either to run continuously or stage with
the compressor/heaters.
- PROTECTION: The PerformexTM Controller will provide the following protection:
1. Compressor high pressure protection (option)
2. Compressor low pressure protection
ELECTRONIC THERMOSTAT
LCD display: a) Room temperature display
b) Mode of operation (Cool/Heat/Auto/Fan system control)
c) Set temperature
d) Compressor Status - ON/OFF/FAULT
e) Error Codes
1. ON/OFF: Press the ON/OFF button & the unit shall be switched ON. A status Led adjacent to this button shall light up indicating the
unit is switched ON. To shut off the unit, press this button again.
2. MODE: Press the mode button to select the desired mode. On selection the corresponding icon shall be displayed on the LCD
display panel.
3. TEMPERATURE RANGE AND SETTING: The operating temperature range is 160C to 300C (610F to 860F), both inclusive. Press
the UP or DN button to select the desired temperature. The temperature setting is effective only for the Cool, Heat and Auto modes.
4. INDOOR (EVAPORATOR) FAN: There is one indoor fan with single fan speed. When fan speed on LCD panel is HIGH, indoor fan
will always turns on. Indoor fan can be set off, when the compressor is cut off by setting the fan speed to AUTO on the LCD panel
by pressing Fan button. By pressing the Fan button again the fan speed can resume to HIGH.
5. COOL MODE: Whenever the unit is started in cool mode (without Pump Down Solenoid-PDS), the compressors will be turned on
one by one depending on the load requirement of the unit.
6. HEAT MODE (HEATER MODEL): Whenever the unit is started in heat mode, the heaters shall be switched ON one by one to
meet the load requirement.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
7. LEAD/LAG OPERATION: Whenever a compressor needs to be on, the controller will turn on the compressor with
the shorter accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the other
compressor will on first. Similarly, the compressor with the longer accumulated run time will be the first one to be
cut off. This is to load the compressors evenly over long run period. Balance loading is enabled when compressor
#1 lead option is disabled.
8. AUTO MODE: In Auto mode, operating mode will be selected automatically between Heat and Cool mode, depend-
ing on the Room Temperature and Set Temperature.
9. ERROR CODE:
Error code is displayed on the LCD panel. When system on and error code is shown, the ON/OFF LED on the LCD panel will blink.
When system off, error code is still display for thermistor error but the ON/OFF LED will be off.
E06
E07
E10
E11
Compressor 1 high pressure trip (or contact open)
Compressor 2 high pressure trip (or contact open), (not applicable for single compressor units)
Compressor 1 low pressure trip
Compressor 2 low pressure trip, (not applicable for single compressor units)
CRANKCASE HEATER
The crankcase heater is provided to hold the compressor oil reservoir at higher temperature than the coldest part in the system.
• Power must be supplied to crankcase heater for a minimum of 12-hours prior to system start-up. If power is off for 6-hours or more,
crankcase heater must be energized for 12-hours before operating the system. Otherwise compressor damage may result.
PUMP DOWN CONTROL
If the unit is provided with pumpdown system, then a solenoid type valve is installed in the liquid line ahead of expansion valve to
prevent flow of refrigerant into the evaporator during off cycle. The controller is wired to solenoid valve which energize in cooling and
opening the valve. Whenever the thermostat temperature is satisfied, the solenoid will close followed compressor off after pumping the
refrigerant from low side of the system until the low pressure switch open the control circuit.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE INSTRUCTIONS
AIRFLOW ADJUSTMENT (Applicable for PT075 - PT360 only)
The airflow could be adjusted by adjusting pulleys of blower motor or belt tension with proper mounting and alignment of the pulleys:
• Refer to fan performance tables in the catalog for selecting applicable airflow, RPM and brake horse power at specified static
pressure.
• Select the appropriate drive as per motor and blower characteristic in the catalog.
• The set screw shall be loosened to make the pulley moving.
• Adjust pulley’s diameter, opening counter clockwise to reduce RPM and further reduce airflow, while closing clockwise increases
RPM and airflow.
• Tighten the set screw and then install the belts.
• Test the unit operating airflow for further adjustment.
CRANKCASE HEATER
• Periodic checking for proper operation or crankcase heater is highly recommended as follows:
a) Check continuity of the heater using multimeter device.
b) Check grounding of the heater by Meggar device (to prevent electrical hazards).
c) Observe whether the heater is warming down the compressor near the oil sump.
CLEANING OF COILS & FILTERS
• Turn off the power supply.
• Take out access panel of evaporator coil.
• Remove the filter from its access panel.
• Protect electrical components and motors from water washing.
• Clean the coil by flushing water by pressure washer followed by compressed air from supply to return direction.
• Filter shall be cleaned every six month, in some hygienic application it is recommended for replacement.
• Cleaning drain pan and trap is recommended once in a year to prevent bacteria growing under the coil.
BELT TENSION TESTING PROCEDURE INSTRUCTION (Applicable for PT075 - PT360 only)
To determine the lbs. force required to tension a drive, you simply do the following:
1. Measure the Belt span as shown.
2. Divide belt span by 64 to get belt deflection needed to check tension.
3. Set large "0" ring on span scale at required belt deflection. This scale is in 1/16" increments.
4. Set small "0" ring at zero on the "Force Scale" (plunger).
5. Place the larger end of the tension checker squarely on one belt at the center of the belt span. Apply force on the plunger until the
bottom of the large "0" ring is even with the top of the next belt or with the bottom of a straight edge laid across the sheaves.
6. Read the force scale under the small "0" ring to determine force required to give the needed deflection.
7. Compare the force scale reading with the correct value for the belt style and cross section used, as given in table on next page.
The force should be between the minimum and maximum values shown.
8. If there is too little deflection force, the belts should be tightened. If there is too much deflection force, the belts should be
loosened.
Note: Tension new drives at the maximum deflection force recommended. Check the tension at least two times during the first day's
operation as there normally will be a rapid decrease in belt tension until belts have run in. Check the tension periodically after the first
day's operation and keep tension in recommended area. The correct operating tension for a V-belt drive is the lowest tension at which
the belts will not slip under the peak load conditions. Shafts must be adequate for the tensions required.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
BELT TENSION TESTING PROCEDURE
BELT SPAN
64
DEFLECTION =
FORCE SCALE
SMALL
"0"
RING
BELT SPAN
SPAN SCALE
LARGE
"0"
RING
BELT TENSION CHECKER
MEASURE THE BELT DEFLECTION FORCE
BELTS
DEFLECTION FORCE - LBS.
BELT TYPE
BELT CROSS SECTION
SMALL PULLEY PITCH DIA. (P.D.)
RANGE
MINIMUM
MAXIMUM
1.25 – 1.75
2 – 2.25
2.5 – 3
1/2
5/8
3/4
5/8
7/8
1-1/8
–
3 L
2.1 – 2.8
3 – 3.5
3.7 – 5
3 – 4.2
4.5 – 5.2
1-1/8
1-1/2
1-7/8
1-5/8
2-1/8
2-5/8
2-7/8
3-3/8
A
B
4 L
5 L
2
2-3/8
TYPICAL HIGH AND LOW VOLTAGE FIELD WIRING CONNECTIONS
L1
L2
L3
N
FUSED DISCONNECT SWITCH
OR CIRCUIT BREAKER
PACKAGED UNIT
CONTROL PANEL
L1
L2
L3
N
LEGEND
ECB - ELECTRONIC CONTROL BOARD
HVTB - HIGH VOLTAGE TERMINAL BLOCK
LI - LINE1
L2 - LINE2
L3 - LINE3
G
N - NEUTRAL TERMINAL BLOCK
G - GROUND
FIELD WIRING
CONTROL WIRES-INTERCONNECTING
( USE 16 TO 22 AWG WIRE)
A
B
+5V GND
INDOOR THERMOSTAT
18
Download from Www.Somanuals.com. All Manuals Search And Download.
PREVENTIVE MAINTENANCE SCHEDULE
CAUTION: Disconnect power supply and allow all rotating parts to stop before servicing the unit.
FREQUENCY OF MAINTENANCE, MONTHS
(FIRST 4 YEARS)
I T E M
6
12
Clean air filter (Aluminum)*
X
Pressure wash condenser & cooling coil as required
X
X
Check blower belt, tension, wear tear/replace if required
Check alignment of pulleys
X
X
X
X
X
X
X
X
X
X
X
X
Clean drain pan, drain pipe
Clean blower wheel
Check for loose bolts/screws & tighten as necessary
Check all electrical controls, components, wiring terminals, etc..., for sparks,
over heat, loose connections/repair or correct
Check for rusted/paint
Check all temperature, pressure readings as applicable and satisfy the
operation performance
Run test all motors and check the amperage
Grease/oil as required
Check vibration isolators
Clean and fix thermal bulbs in the correct location. Insulate it.
Check canvass connections, insulation damage
* If fiberglass filters used, replace it yearly.
NOTE: Always observe for abnormal noise or vibration.
MAINTENANCE TOOLS/EQUIPMENT REQUIRED
STANDARD : Screw drivers (Slot & Phillips), adjustable wrenches, pliers, refrigeration wrenches & socket set wrenches, pulley
puller, etc.
SPECIAL
:
Manifold gauge set, R-22 charging cylinder, belt tension checker, leak detector, vacuum pump with electronic gauges,
thermometer, hook type ammeter/voltmeter/ohmmeter and oxy-acetylene brazing set etc.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLE SHOOTING CHART
SYMPTOM
CAUSES
CHECK & CORRECTIVE MEASURE
Thermostat shows no display
1. Power off/Blown fuse
1. Check the power. Switch ON the circuit breaker.
Replace fuse if it blown.
2. Faulty field wiring
3. Loose connections
4. Defective thermostat
2. Check wiring against diagram.
3. Check and correct it.
4. Replace it.
Thermostat LCD panel display is not
bright & does not function properly
1. Replace battery
1. Battery life is over
1. Correct belt. Check tension and alignment.
2. Check wiring against diagram.
3. Check and correct it.
4. Replace if.
1. Blower belt slipped/not fixed
2. Faulty wiring
3. Burned wiring
4. Defective blower motor contactor
5. Defective blower motor
Blower not running, compressor short
cycles
5. Replace it.
Blower running, no sufficient air
1. Wrong rotation (Applicable initial start up/or after
a power failure), 3 phase motor
1. Check the rotation of blower, interchange phase
of blower motor from blower motor contactor.
Blower running, but with not enough
supply air
1. Loose Belt
1. Adjust it & check belt tension.
2. Adjust the pitch of the pulley.
3. Check and remove the obstructions.
4. Verify static pressure and fan performance data.
5. Change pulley (if blower motor ampere within rated load).
6. Check all dampers opened properly. Balance air.
7. Clean it.
2. Variable pulley wide open
3. Return air obstructed
4. High static pressure
5. Improper pulley selection
6. Closed dampers/improper air balance
7. Dirty filter
8. Dirty cooling coil
8. Clean it.
Blower running and delivers excess
air
1. Adjust the pitch of the pulley.
2. Select suitable combination.
3. Check the duct design.
1. Variable pulley needs more tightening
2. Improper pulley/motor selection
3. Low external static pressure
1. Re-set the unit and determine the reason. Check
high & low pressure (refer to symptom for "low/
high suction pressure & high discharge pressure").
2. Replace it.
3. Check and replace it.
4. Replace it.
Blower runs, compressor not working
1. Safety circuit open due to low suction pressure,
high discharge pressure, overload protector
2. Defective compressor contactor
3. Burned wiring
4. Defective compressor
Compressor runs, but short cycling
1. a) Verify the reason for low suction pressure
1. Safety circuit open due to:
a) Low suction pressure
(refer to symptom for "low suction pressure")
.
b) Verify the reason for high discharge pressure
(refer to symptom for "high discharge pressure").
c) Check dome temperature. RLA each phase.
Verify the reason.
b) High discharge pressures
c) Overload protector
2. Check and relocate as required.
2. Thermostat in cold location
3. High thermostat setting
3. Lower the temperature setting to 210C for test.
1. a) Verify the reason & correct it (refer to symptom
Thermostat shows faulty indication
Low suction pressure
1. Safety circuit open due to:
a) Low pressure switch
b) High pressure switch
c) Overload protector
for "low suction pressure")
.
b) Verify the reason for high discharge pressure.
(refer to symptom for "high discharge pressure").
c) Check comp. RLA against nameplate for each phase,
check comp. dome temperature, etc. & correct it.
1. Check for gas leak & charge freon as required.
2. Adjust it. Check belt tension.
3. Adjust the pulley.
4. Clean it.
5. Clean it.
6. Check return air grille sizes, etc. against design.
7. Verify and correct it.
8. Check and correct/replace it.
1. Less Freon
2. Loose belt
3. Variable pulley widely open
4. Dirty filter
5. Dirty cooling coil
6. Return air restricted
7. Improper expansion valve bulb installation/location
8. Restriction in expansion valve/filter dryer
High suction pressure
1. Verify and adjust it.
2. Adjust air quantity.
1. Excess freon charge
2. Excess air quantity
3. Check & verify. Isolate the area to be cooled & observe.
4. Check design/unit selection.
5. Check superheat & adjust it, if required.
6. Check and replace compressor.
3. High room temperature condition
4. Undersize unit (serving large area)
5. Expansion valve widely open
6. Defective compressor valve
High discharge pressure
1. Fan blade stuck with ventury. Check & correct it.
2. Check freon and adjust it, if necessary.
3. Clean it.
4. Verify the reason and correct it.
5. Check and replace it.
1. Condenser fan motor not working properly
2. Excess freon charge
3. Dirty condenser
4. High ambient condition/Air in condenser obstructed
5. Defective fan motor capacitor
6. Defective fan motor
6. Check and replace it.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLE SHOOTING CHART
SYMPTOM
CAUSES
CHECK & CORRECTIVE MEASURE
1. Low suction pressure
1. Verify the reason & correct it (refer to symptom
for "low suction pressure")
Unit works continuously, no sufficient
cooling
.
2. High discharge pressure
2. Verify the reason and adjust the freon, if required.(refer
to symptom for "high discharge pressure").
3. Refer to symptom for "blower works, less air".
4. Determine the reason (refer to symptom for
"cooling coil ice up") & correct it.
3. Less air quantity
4. Cooling coil ices up
5. Second stage (If exists) not working
5. Set the thermostat to lower temperature (210C)/
or verify the reason.
6. Serving large area
6. Check the design.
1. Low ambient condition
2. Safety low pressure switch open due to low
suction pressure
3. Fan cycling (whenever applicable) setting low
4. Thermostat setting too low
5. Cooling coil ices-up
1. Check and verify the ambient temperature.
2. Check the reason and correct it (refer to
symptom for "low suction pressure")
3. Adjust the fan cycling.
4. Adjust the thermostat setting.
5. Verify the reason and correct it (refer to
symptom for "cooling coil ice up").
Unit not cooling properly during night
time
.
6. Verify the reason and correct it (refer to
6. Less air quantity
symptom for "blower works, less air")
.
Not sufficiently cooling during
daytime
1. High discharge pressure
1. Check and verify the reason (refer to symptom
for "high discharge pressure").
2. Adjust thermostat.
3. Check the design/unit selection.
4. Check and verify the reason (refer to symptom
2. High thermostat setting
3. Serving large area
4. Less air quantity
for "blower works, less air")
5. Check the ambient condition.
6. Clean it.
.
5. High ambient condition
6. Dirty condenser
Cooling coil ices up
1. Less freon
2. Less air quantity
1. Check for gas leak & charge freon as required.
2. Determine the reason and correct it (refer to
symptom for "blower works, less air")
3. Clean it.
4. Clean it.
.
3. Dirty filter
4. Dirty cooling coil
1. Rectify the reason of low suction pressure (refer
1. Safety circuit open due to low pressure switch
Unit is not restarting (after a cut-off)
Unit is taking long time to restart
to symptom for "low suction pressure")
.
1. Shift the location as required.
1. Thermostat in cold location
Compressor goes lockout (pump
down system)
1. Check freon charge and confirm FLA.
2. Check pumpdown solenoid valve operation.
1. Imbalance freon
2. Malfunctioning pumpdown solenoid valve
1. Check pumpdown solenoid valve and replace it.
Taking more time for the pumpdown
cycle, cooling coil ices up
1. Leaky pumpdown solenoid valve
1.Check and correct it properly.
2. Check and correct it properly.
3. Check and tighten.
4. Tighten the pipe support.
5. Check the balance, alignment, bracket, etc.
Correct it/replace it.
6. Replace the motor.
7. Adjust belt tension.
8. Align pulley.
1. Improper installation
Noisy unit
2. Improper vibration isolators
3. Loose parts or mountings
4. Tubing rattle
5. Bent fan blade causes vibration
6. Defective bearings
7. Belt tension is high
8. Blower motor pulley is not aligned
1. Check and correct it.
1. Improper installation
Unit operational noise listening inside
the building
2. Check and correct it.
2. Improper vibration isolators
3. Verify the reason of noisy unit & correct it.
4. Verify the design/Relocate the unit if necessary.
5. Check & verify the design.
3. Abnormal noise in the unit
4. Unit too close to the slab/wall openings
5. Duct design (high static)
6. Remove wooden packing (if any).
6. Wooden packing beneath the compressor is not removed
1. Rectify the reason & correct it.
2. Check the compressor amperage each phase.
3. Check and correct it.
4. Check and verify the reason.
5. Check and replace it.
6. Check and replace it.
Compressor not working
1. Low voltage
2. Single phase failure
3. Burned wirings
4. Overload protector open
5. Defective contactor
6. Burned compressor motor winding
7. Damaged (stuck) compressor
7. Check and replace it.
1. Check and correct the wiring.
2. Check meggar test.
1. Burned wirings
2. Grounded wirings
Circuit breaker of the unit trips
3. Check wiring against diagram.
4. Replace it, if required.
5. Check the circuit breaker ratings.
3. Faulty field wiring
4. Grounded compressor/blower motor
5. Undersize circuit breaker
21
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT036 - PT075 (Single compressor units)
HEATER DATA TABLE
(SEE HEATER DATA TABLE)
HEATER CONNECTION DETAILS
DIP SWITCH SETTINGS
JUMPER SETTING ON ECB
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT036 - PT075 (Single compressor units)
LEGEND
AUXILIARY RELAY
AIRFLOW SWITCH
AR
STANDARD OPTIONS
1. UVM OPTION
AFS
ATB
BM
AUXILIARY TERMINAL BLOCK
BLOWER MOTOR
BMC
CC
BLOWER MOTOR CONTACTOR
COMPRESSOR CONTACTOR
AUXILIARY CONTACT
*
CCA
CB
2. SMOKE DETECTOR OPTION
*
CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
ECB
FCS
F
ELECTRONIC CONTROL BOARD
FAN CYCLING SWITCH
FUSE
3. VOLT FREE CONTACT OPTIONS
A. UNIT ON & OFF INDICATION OPTION
FACTORY INSTALLED B.M SPEED
*
FL
FUSE LINK
FM
FAN MOTOR (CONDENSER)
FAN MOTOR CONTACTOR
FAULT RELAY
FMC
FR
HC
HEATER CONTACTOR
HIGH PRESSURE SWITCH
HIGH VOLTAGE TERMINAL BLOCK
HEATER
HPS
HVTB
HTR
JP
JUMPER
L1
LINE 1
TO HVTB TO NTB
TO HVTB TO NTB
L2
LINE 2
L3
LINE 3
LPS
LUG
NTB
O/L
OHT
PDS
SSPS
SD
LOW PRESSURE SWITCH
LUG GROUND
NEUTRAL TERMINAL BLOCK
OVER LOAD
*
*
OVER HEAT THERMOSTAT
PUMP DOWN SOLENOID
SOLID STATE PROTECTIVE SYSTEM
SMOKE DETECTOR
C. BM ON,OFF & TRIP INDICATION OPTION
TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM
_ _ _
UNDER VOLTAGE MONITOR
FIELD WIRING
PRESSURE SWITCH SETTINGS
4. HPS CONNECTION OPTION
+
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
CRANKCASE HEATER CONNECTION
1. POWER SUPPLY, 380/415V-3PH-50Hz.
2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS
EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR
MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPER-
ATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY COOLINE.
6. COMPRESSOR IS PROVIDED WITH INTERNAL OVERLOAD.
7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT090 - PT120 (Dual compressor units)
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT090 - PT120 (Dual compressor units)
3. VOLT FREE CONTACT OPTIONS
LEGEND
CONNECTION APPLICABLE FOR
A. UNIT ON & OFF INDICATION OPTION
1PH FM ONLY
BM WITH EXTERNAL OLR
AR
AUXILIARY RELAY
AFS
ATB
BM
AIRFLOW SWITCH
TO HVTB TO NTB
L2
N
AUXILIARY TERMINAL BLOCK
BLOWER MOTOR
BMC
CC
BLOWER MOTOR CONTACTOR
COMPRESSOR CONTACTOR
AUXILIARY CONTACT
CCA
CB
CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
ECB
FCS
F
ELECTRONIC CONTROL BOARD
FAN CYCLING SWITCH
FUSE
FL
FUSE LINK
FM
FAN MOTOR (CONDENSER)
FAN MOTOR CONTACTOR
FAULT RELAY
CRANKCASE HEATER CONNECTION
FMC
FR
HC
HEATER CONTACTOR
HIGH PRESSURE SWITCH
HIGH VOLTAGE TERMINAL BLOCK
HEATER
HPS
HVTB
HTR
JP
C. BM ON,OFF & TRIP INDICATION OPTION
JUMPER
L1
LINE 1
STANDARD OPTIONS
1. UVM OPTION
L2
LINE 2
L3
LINE 3
LPS
LUG
NTB
O/L
OHT
PDS
SSPS
SD
LOW PRESSURE SWITCH
LUG GROUND
NEUTRAL TERMINAL BLOCK
OVER LOAD
FAN MOTOR CONTROL CONNECTION
(APPLICABLE FOR FM WITH T.O.P)
OVER HEAT THERMOSTAT
PUMP DOWN SOLENOID
SOLID STATE PROTECTIVE SYSTEM
SMOKE DETECTOR
2. SMOKE DETECTOR OPTION
TRANS TRANSFORMER
T'STAT THERMOSTAT
HPS OPTION
UVM
_ _ _
UNDER VOLTAGE MONITOR
FIELD WIRING
+
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
1. POWER SUPPLY, 380/415V-3PH-50Hz.
2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS
EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR
MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPER-
ATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY COOLINE.
6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.
7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT180 - PT240 (Dual compressor units)
CONNECTION FOR COMPRESSOR
WITH MOTOR OVERLOAD
TO HVTB
CONNECTION FOR SCROLL COMP. WITH SSPS
HEATER DATA TABLE
CONNECTION FOR MANUEROP COMP. WITH SSPS
(SEE HEATER DATA TABLE)
HEATER CONNECTION DETAILS
230V
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT180 - PT240 (Dual compressor units)
STANDARD OPTIONS
LEGEND
1. UVM OPTION
AR
AUXILIARY RELAY
AFS
ATB
BM
AIRFLOW SWITCH
TO HVTB
AUXILIARY TERMINAL BLOCK
BLOWER MOTOR
TO HVTB
BMC
CC
BLOWER MOTOR CONTACTOR
COMPRESSOR CONTACTOR
AUXILIARY CONTACT
CCA
CB
2. SMOKE DETECTOR OPTION
CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
ECB
FCS
F
ELECTRONIC CONTROL BOARD
FAN CYCLING SWITCH
FUSE
3. VOLT FREE CONTACT OPTIONS
A. UNIT ON & OFF INDICATION OPTION
FL
FUSE LINK
FM
FAN MOTOR (CONDENSER)
FAN MOTOR CONTACTOR
FAULT RELAY
FMC
FR
HC
HEATER CONTACTOR
HIGH PRESSURE SWITCH
HIGH VOLTAGE TERMINAL BLOCK
HEATER
COMP. WITH CIRCUIT BREAKER OPTION
HPS
HVTB
HTR
JP
HVTB
JUMPER
L1
LINE 1
LUG
L2
LINE 2
L3
LINE 3
LPS
LUG
NTB
O/L
OHT
PDS
SSPS
SD
LOW PRESSURE SWITCH
LUG GROUND
NEUTRAL TERMINAL BLOCK
OVER LOAD
OVER HEAT THERMOSTAT
PUMP DOWN SOLENOID
SOLID STATE PROTECTIVE SYSTEM
SMOKE DETECTOR
LOW AMBIENT OPTION
TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM
_ _ _
UNDER VOLTAGE MONITOR
FIELD WIRING
C. BM ON,OFF & TRIP INDICATION OPTION
+
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
1. POWER SUPPLY, 380/415V-3PH-50Hz.
2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS
EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR
MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPER-
ATING THE SYSTEM.
FAN MOTOR CONTROL CONNECTION
(APPLICABLE FOR FM WITH T.O.P)
A) STANDARD CONNECTION
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY COOLINE.
6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.
B) WITH LOW AMBIENT OPTION
7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS
SHOWN. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH
TO CLOSE, BEFORE STARTING THE UNIT.
8. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT300 - PT360 (Dual compressor units)
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS : PT300 - PT360 (Dual compressor units)
LEGEND
AUXILIARY RELAY
AIRFLOW SWITCH
AR
AFS
ATB
BM
AUXILIARY TERMINAL BLOCK
BLOWER MOTOR
BMC
CC
BLOWER MOTOR CONTACTOR
COMPRESSOR CONTACTOR
AUXILIARY CONTACT
CCA
CB
CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
ECB
FCS
F
ELECTRONIC CONTROL BOARD
FAN CYCLING SWITCH
FUSE
FL
FUSE LINK
FM
FAN MOTOR (CONDENSER)
FAN MOTOR CONTACTOR
FAULT RELAY
FMC
FR
HC
HEATER CONTACTOR
HIGH PRESSURE SWITCH
HIGH VOLTAGE TERMINAL BLOCK
HEATER
HPS
HVTB
HTR
JP
JUMPER
L1
LINE 1
L2
LINE 2
L3
LINE 3
LPS
LUG
NTB
O/L
OHT
PDS
SSPS
SD
LOW PRESSURE SWITCH
LUG GROUND
NEUTRAL TERMINAL BLOCK
OVER LOAD
OVER HEAT THERMOSTAT
PUMP DOWN SOLENOID
SOLID STATE PROTECTIVE SYSTEM
SMOKE DETECTOR
TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM
_ _ _
UNDER VOLTAGE MONITOR
FIELD WIRING
+
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
1. POWER SUPPLY, 380/415V-3PH-50Hz.
2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS
EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR
MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPER-
ATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY COOLINE.
6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.
7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS
SHOWN. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH
TO CLOSE, BEFORE STARTING THE UNIT.
8. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
MODEL NUMBER
COMPRESSOR
PT036L PT048L PT060L PT075L PT090 PT100L PT120L PT180L PT215L
800-684-08 800-672-52 800-643-01 800-674-78 800-684-09 800-672-52 800-674-25 800-674-67/81 800-674-38
800-555-26 800-555-26 800-555-26 800-555-26 800-545-68 800-545-68 800-545-68 800-545-68 800-545-68
FAN MOTOR
FAN MOTOR CAPACITOR
BlOWER MOTOR (STANDARD)
BLOWER WHEEL
800-353-15 800-353-15 800-353-15 800-353-15
N.A.
N.A.
N.A.
N.A.
N.A.
800-546-94 800-546-94 800-546-95 800-544-13 800-544-16 800-544-16 800-544-17 800-544-72 800-544-72
800-707-10 800-707-10 800-707-10 800-707-46 800-707-02 800-707-02 800-707-02 800-707-02 800-707-23
800-225-02 800-225-02 800-225-02 800-225-02 800-224-23 800-224-23 800-224-23 800-224-23 800-224-23
800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-736-22
800-736-27 800-736-27 800-736-27 800-095-01 800-095-01 800-095-01 800-095-01 800-098-55 800-098-55
800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02
800-195-16 800-195-20 800-195-22 800-181-00 800-183-01 800-181-00 800-181-00 800-182-00 800-182-00
800-194-13 800-194-13 800-194-17 800-191-01 800-191-00 800-191-00 800-191-00 800-196-00 800-194-01
800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
800-625-46 800-625-46 800-625-46 800-625-46 800-625-29 800-625-29 800-625-29 800-625-74 800-625-74
800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-05 800-531-05
800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-200-00 800-200-00 800-200-00
CONDENSER FAN PROPELLER
COMPRESSOR CONTACTOR
BL0WER MOTOR CONTACTOR
AIRFLOW SWITCH
EXPANSION VALVE
DISTRIBUTOR
LOW PRESSURE SWITCH
HIGH PRESSURE SWITCH (OPTION
FAN GRILLE
)
FILTER DRIER
SIGHT GLASS (OPTION)
MODEL NUMBER
COMPRESSOR
PT240L PT300L PT360L
800-674-19 800-674-12 800-674-72
800-545-68 800-545-68 800-545-68
800-544-73 800-544-73 800-544-74
800-707-23 800-707-23 800-707-23
800-224-23 800-225-02 800-225-02
800-736-22 800-736-22 800-736-22
800-098-55 800-098-55 800-098-57
800-005-02 800-005-02 800-005-02
800-185-00 800-186-00 800-186-00
800-194-01 800-196-10 800-191-34
800-557-00 800-557-00 800-557-00
800-558-00 800-558-00 800-558-00
800-625-74 800-625-46 800-625-46
800-531-05 800-531-05 800-531-01
800-200-00 800-200-00 800-200-01
FAN MOTOR
BlOWER MOTOR (STANDARD)
BLOWER WHEEL
CONDENSER FAN PROPELLER
COMPRESSOR CONTACTOR
BL0WER MOTOR CONTACTOR
AIRFLOW SWITCH
EXPANSION VALVE
DISTRIBUTOR
LOW PRESSURE SWITCH
HIGH PRESSURE SWITCH (OPTION
FAN GRILLE
)
FILTER DRIER
SIGHT GLASS (OPTION)
OPTIONAL ITEMS:
ANTI ICE THERMOSTAT : 800-644-22 (COMMON TO ALL MODELS)
RETURN AIR FILTERS
Aluminum filter (1” Thick) : 800-254-10 (2 Each) for PT036 - PT060, 800-254-11 (2 Each) for PT075, 800-254-12 (2 Each) for PT090 - PT120,
800-254-13 (2 Each) for PT180, 800-254-14 (4 Each) for PT215 - PT240 & 800-254-15 (4 Each) for PT300 - PT360.
Aluminum filter (2” Thick) : 800-254-16 (2 Each) for PT036 - PT060, 800-254-17 (2 Each) for PT075, 800-254-18 (2 Each) for PT090 - PT120,
800-254-19 (2 Each) for PT180, 800-254-20 (4 Each) for PT215 - PT240 & 800-254-21 (4 Each) for PT300 - PT360.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
|