Continental Refrigerator CAD 20 User Manual

Technical Guide Form UTG-0204  
Continental Chillers LLC  
Phone: 317-337-9813 Fax: 317-337-9816  
UniPac™  
Single Phase  
Air Cooled Chillers  
Water Cooled Chillers  
Split System Chillers  
3 through 60 HP  
Shown, model USAC-8  
Packaged Air Cooled Chiller with  
Factory Mounted Chiller Pump  
Typical Scroll  
Compressor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
Standard Unit Specifications of UniPac™ Single Phase Chillers  
General Description  
Continental’s Single Phase Air and Water Cooled Chillers  
are packaged systems complete with scroll compressor(s), air  
Sight glass/ moisture indicator  
Suction line fully insulated, designed for proper oil return at  
minimum friction loss  
Discharge line formed of clean ACR type tubing and pre-formed  
radius fitting  
cooled  
or  
water  
cooled  
condenser(s),  
individual  
cooler/evaporator(s), independent refrigerant circuit(s) and a control  
center all mounted on a heavy duty structural steel frame.  
Control Center  
Scroll Compressor(s)  
All power, starting, safety and operating controls are mounted in  
a built in fully enclosed, weather proof control panel for air cooled  
models and NEMA-1 enclosures for indoor water cooled or  
condenserless models.  
Compressors are well proven state-of-the-art scrolls with fewer  
moving parts, less rotating mass, and less internal friction than  
traditional reciprocating compressors.  
Motor is suction gas-cooled, hermetically sealed, two pole,  
squirrel cage induction type and is directly driven at 3600 rpm.  
All compressor(s) are mounted on resilient pads to minimize  
vibration.  
Power controls include:  
Single point electrical terminal block for 230/1/60 power input  
Compressor-motor contactor(s)  
Compressor run capacitor(s)  
Fan motor contactor(s) (air cooled units only)  
Control circuit fuse  
Control circuit terminal block  
Air Cooled Condenser for Air Cooled Models  
Condenser Coil-industrial quality, seamless copper tube  
Fins-all aluminum, die formed with full self–spacing collars that  
completely cover the copper tube; fins are mechanically bonded to  
the copper tubes  
Safety/Operating controls include:  
Propeller Fans-large surface, low speed, low sound level propeller  
fans for vertical airflow; fans are statically and dynamically balanced  
and operate at low tip speeds for low vibration and sound levels  
Fan Guards- PVC coated for long life  
Fan Venturi- high collar fully spun venturi design for high efficiency  
and low outlet noise  
Fan Motors-special “enclosed air over” motor design with built-in  
overload protection; single phase motors operate at a low speed of  
1075 rpm  
Two position switch indicating off/system on – per circuit  
High Pressure control with manual reset –per circuit  
Low pressure control with auto reset – per circuit  
Adjustable chilled water temperature controller  
Adjustable freezestat  
Adjustable compressor anti-recycle timer(s)  
Relay(s)  
Built-in compressor-motor overload  
Water Cooled Condenser for Water Cooled Models  
Each water cooled condenser is of shell/coil design. The  
condenser water flows through special heat transfer copper tube.  
Refrigerant flows through the steel shell and a built in receiver.  
Testing, Evacuation and Refrigerant Charging  
Each completed system is pressure tested with nitrogen,  
evacuated with a high capacity vacuum pump, vapor charged with  
R-22 and fully tested for all operating and safety controls. Field  
charge of R-22 required.  
Split chiller systems are “dry run” tested for operating and  
safety controls.  
Cooler/Evaporator for All Models  
Each cooler/evaporator is of shell/coil design. The water to be  
chilled flows through special heat transfer copper tube. Refrigerant  
flows through the steel shell/receiver.  
Assembly  
All above components are assembled on a heavy-duty  
structural steel frame, formed of channels and angles as a rugged  
pre-engineered package. Each steel frame has mounting holes and  
“lifting eyes” on four sides for “spreader bar” lifting and rigging.  
The cabinet of air cooled units is made of heavy gauge  
galvanized steel.  
Refrigerant Piping  
Each Refrigerant circuit includes:  
Liquid line with charging connection  
Filter drier  
Liquid solenoid valve with 115 V coil (220 V or 24 V, optional)  
3
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
UniPac™ Options and Selection Procedures  
1. Control Transformer - For applications where a separate 115-volt power  
source is not available, a transformer can be installed and wired between the line  
voltage power terminal block and the 115-volt control circuit. Transformer primary  
fuses are included.  
2. Factory mounted and wired flow switch - This accessory is mandatory for  
Continental warranty to be effective. Provides protection from chiller freezing due to  
“no flow” through chiller-evaporator.  
3. Factory Mounted and Wired Chiller Water Pump/Valve - Includes chilled  
water circulating pump, pump starter, and isolation valve. Provides system pump for  
chilled water circulation- saves field labor and material. This pump is interlocked with  
the flow switch and “phased in” at the factory for proper rotation.  
4. Non-fused Disconnect - Factory mounted non-fused disconnect sized for  
model and voltage. This saves field labor and material.  
5. Low Evaporator Pressure Freezestat - Senses low evaporator pressure and  
shuts down system after sixty second time delay. Extra safety protection against low  
pressure due to gas shortage or freeze conditions.  
14. Copper Tube/Copper Fin Condenser Coil - Seamless copper tube with die  
formed copper fins, mechanically bonded to the tube. Provides maximum protection  
from salt-water environment due to the elimination of dissimilar metals.  
15. Complete Unit Coating - Your choice of paint, Blygold, Imron, polyester or  
Heresite coating for compete unit.  
16. Stainless Steel Hardware - For extra protection against corrosion.  
17. Low Speed Condenser Fan Motors - For lower noise levels  
18. Centrifugal Condenser Fans - For ducted applications  
19. Acoustical Enclosure - Compressor is located in an acoustical enclosure  
providing dampening of sound levels.  
20. Dual Unit Kit - Allows operation of two or more units  
21. Alarm Bell Contacts - Allows alarm bell connection to pressure controls for  
signaling if unit fails on manual reset safety controls. (alarm bell is not included but  
can be provided)  
22. Water Flange Kit - Factory or field mounted consists of 150lb raised face  
flanges to convert male pipe thread to flanged cooler connections.  
23. High Return Water Thermostat - Factory mounted thermostat senses high  
return water temperature at start-up. Allows unit to run un-loaded instead of shutting  
down due to high head pressure  
6. Pressure Gauges - Two-inch diameter gauges are factory installed and piped  
to compressor. High and low pressure for each refrigerant circuit.  
7. Indicator Lights - Three indicating lights show Power On, High Pressure Fail,  
and No Flow/Freeze for each refrigerant circuit.  
8. Vibration Isolators - Level adjusting spring type for one-inch deflection for  
field mounting-reduces vibration transmission.  
24. Brine Chilling  
brines/glycols/alcohols.  
-
Modified cooler and controls for various  
25. High entering Water Process Cooling - Secondary plate heat exchanger  
with pump, factory mounted and wired to protect compressor against burnouts due to  
high water temperatures.  
9. Low Ambient Controls - Standard units have fan cycling and are good for  
45°F ambient.  
a) For Low Ambient of 0°F. Includes a modulating solid state fan speed controller  
and a single phase condenser motor(s) as well as fan cycling.  
b) For Low Ambient of –20°F. Includes head pressure control valve in conjunction  
with oversized heated and insulated receiver(s) and fan cycling. Receiver includes  
pressure relief valve.  
10. Micro-Processor Controller  
11. Water Regulating Valve - Provides head pressure control for water cooled  
models USWC.  
26. Potable/Ingredient Water at 34°F  
applications.  
-
For bakeries/produce or other  
27. Cooler Heater with Thermostat - For freeze protection.  
28. Desuperheaters - Provides “free hot water” by recovering heat from super  
heated gas.  
29. Compressor Circuit Breaker - Both fused and non-fused short circuit  
protection for each compressor, further reducing chance of motor burnout.  
30. Digital Temperature Readout  
12. 90/10 Cu-Ni Condenser - For water cooled models, USWC.  
13. Blygold or Heresite Coated Condenser - Coil is coated with Blygold or  
Heresite for protection against elements. Minimal effect on heat transfer.  
31. Compressor Cycle Counter/Hour Meters  
32. Non-Ozone Depleting, Environmentally-Friendly Refrigerant  
Ratings and Selection Procedures  
Altitude: Ratings are based on altitude of sea level. For other ratings use the following  
correction factors  
1. Ratings: are in accordance with ARI standard for chillers. These ratings  
may be interpolated for any published chilled water temperatures between 40°F  
and 50°F but must not be extrapolated.  
2. Chilled Water Flow: based on 2.4 GPM per Ton and 10°F chilled water  
range. Limit 6°F minimum to 14°F maximum.  
Alt. Above  
Sea Level  
Sea Level  
1000  
Capacity  
Multiplier  
1.0  
Alt. Above  
Sea Level  
4000  
Capacity  
Multiplier  
.971  
1.0  
5000  
.962  
3. Cooler Fouling Factor: 0.00025 fouling is standard  
2000  
.995  
6000  
.951  
For 0.0005 fouling capacity correction factor = 0.982 x TR, 0.994 x kW  
For 0.00075 fouling capacity correction factor = 0.964 x TR, 0.989 x kW  
4. Water cooled condenser fouling factor : ratings are based on 0.00025 for  
condenser. For 0.00075 Condenser tons x 0.97 –kW x 1.045  
3000  
.980  
7000  
.949  
7. For ratings outside this catalog range consult Continental for assistance  
Tel:(317)337-9813 Fax:(317)337-9816  
5. Copper Fin Ratings: TR x 1.01 – kW x 0.99  
6. Ethylene Glycol Correction Factors: Following factors are to be applied  
Selection Procedures  
All units are rated in accordance with ARI Standard and cover a wide range of leaving  
chilled water temperatures and ambients from 85°F to 120°F.  
To select any chiller it is necessary to know:  
1. Capacity: ______ Tons  
2. Entering and leaving chilled water temperature: ______ °F  
3. Water Flow: ______ GPM  
4. Design ambient temperature: ______ °F or  
5. Entering/leaving cond. water temperature, for water cooled units: ______ °F  
Knowing any two of items 1,2 or 3, the third can be calculated as follows:  
GPM = Tons x 24  
to the standard ratings for ethylene glycol. For other glycols consult factory.  
Correction Factors  
% Wt.  
Ethylene  
Glycol  
Freeze  
Point  
(°F)  
GPM/  
°F /Ton  
24.1  
Tons  
.995  
.990  
.980  
.975  
.960  
kW  
VP  
1.02  
1.05  
1.10  
1.13  
1.18  
10  
20  
30  
40  
50  
1.000  
0.995  
.990  
0.985  
0.980  
26  
16  
5
-10  
-32  
24.8  
26.0  
27.3  
29.0  
Temp. Rise(Vt)  
4
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
Single Phase Air Cooled Ratings  
UniPac™  
Models USAC-3 through USAC-20  
3 through 20 Tons  
Ambient Air Temperature °F  
LCWT Model  
85  
95  
105  
115  
120  
°F  
USAC  
Cooler  
GPM  
Cooler  
GPM  
Cooler  
GPM  
Cooler  
GPM  
Cooler  
GPM  
TR  
kW  
TR  
kW  
TR  
kW  
TR  
kW  
TR  
kW  
3
5
2.6  
4.3  
3.0  
5.0  
6.2  
10.3  
20.6  
2.3  
3.9  
3.1  
5.2  
5.5  
9.4  
2.1  
3.5  
3.2  
5.4  
5.0  
8.4  
1.8  
3.0  
3.3  
5.5  
4.3  
7.2  
1.6  
2.8  
3.3  
5.8  
3.8  
6.7  
10  
15  
20  
3
8.6 10.0  
13.0 15.0  
17.2 20.0  
7.8 10.4  
18.7  
7.0 10.8  
16.8  
25.2  
6.0 11.0  
9.0 16.5  
14.4  
21.6  
5.6 11.6  
8.4 9.9  
13.4  
20.2  
26.9  
4.3  
40  
31.2 11.7 15.6  
41.3 15.2 20.8  
28.1 10.5 16.2  
36.5 14.0 21.6  
33.6 12.0 22.0  
28.8 11.2 23.2  
2.9  
4.6  
3.0  
5.1  
7.0  
11.0  
22.1  
2.5  
4.1  
3.2  
5.3  
6.0  
9.8  
2.2  
3.7  
3.2  
5.5  
5.3  
8.9  
2.0  
3.3  
3.4  
5.7  
4.8  
7.9  
1.8  
3.0  
3.4  
5.8  
5
7.2  
10  
15  
20  
3
9.2 10.2  
13.8 15.3  
18.4 20.4  
8.2 10.6  
19.7  
7.4 11.0  
17.8  
26.6  
6.6 13.7  
9.9 17.1  
15.8  
23.8  
6.0 11.6  
9.0 17.4  
14.4  
21.6  
28.8  
4.6  
42  
44  
45  
46  
48  
50  
33.1 12.3 15.9  
44.2 16.4 21.2  
29.5 11.1 16.5  
39.4 14.8 22.0  
35.5 13.2 27.4  
31.7 12.0 23.2  
3.1  
4.9  
3.1  
5.2  
7.4  
11.8  
23.5  
2.8  
4.4  
3.3  
5.4  
6.7  
10.6  
21.1  
2.4  
4.0  
3.4  
5.7  
5.8  
9.6  
2.1  
3.5  
3.5  
5.9  
5.0  
8.4  
1.9  
3.2  
3.5  
5.9  
5
7.7  
10  
15  
20  
3
9.8 10.4  
14.7 15.6  
19.6 20.8  
8.8 10.8  
8.0 11.4  
19.2  
7.0 11.8  
16.8  
25.2  
6.4 11.8  
9.6 17.7  
15.4  
23.0  
30.7  
4.7  
35.3 13.2 16.2  
47.0 17.6 21.6  
31.7 11.1 16.5  
42.2 16.0 22.8  
26.6 10.5 17.7  
38.4 14.0 23.6  
33.6 12.8 23.6  
3.2  
5.0  
3.1  
5.2  
7.6  
11.9  
23.8  
2.9  
4.5  
3.3  
5.5  
6.8  
10.8  
21.6  
2.5  
4.1  
3.5  
5.8  
6.0  
9.8  
2.1  
3.6  
3.6  
6.0  
5.0  
8.6  
2.0  
3.3  
3.6  
6.0  
5
7.9  
10  
15  
20  
3
9.9 10.4  
14.8 15.6  
19.9 20.8  
9.0 10.9  
8.2 11.5  
19.7  
7.3 11.9  
17.5  
25.9  
6.6 12.0  
9.9 18.0  
15.8  
23.8  
31.7  
4.8  
35.5 13.3 16.4  
47.8 18.0 21.8  
31.9 11.8 17.0  
43.2 11.9 20.1  
28.3 10.8 17.8  
28.6 14.4 23.8  
34.6 13.2 24.0  
3.2  
5.0  
3.1  
5.2  
7.7  
12.0  
24.0  
2.9  
4.6  
3.3  
5.5  
7.0  
11.0  
22.1  
2.6  
4.2  
3.5  
5.8  
6.2  
10.1  
20.2  
2.2  
3.7  
3.6  
6.0  
5.3  
8.9  
2.0  
3.4  
3.6  
6.1  
5
8.2  
10  
15  
20  
3
10.0 10.4  
15.0 15.6  
20.0 20.8  
9.2 11.0  
8.4 11.6  
7.4 12.0  
17.8  
6.8 12.2  
16.3  
24.5  
32.6  
5.3  
36.0 13.4 16.5  
48.0 18.4 22.0  
32.2 12.6 17.4  
44.2 16.8 23.2  
30.2 11.1 18.0  
40.3 14.8 24.0  
26.6 10.2 18.3  
35.5 13.6 24.4  
3.4  
5.2  
3.2  
5.3  
8.2  
12.5  
25.0  
3.0  
4.8  
3.4  
5.6  
7.2  
11.5  
23.0  
2.7  
4.3  
3.5  
5.9  
6.5  
10.3  
20.6  
2.4  
3.9  
3.7  
6.1  
5.8  
9.4  
2.2  
3.6  
3.7  
6.2  
5
8.6  
10  
15  
20  
3
10.4 10.6  
15.6 15.9  
20.8 21.7  
9.6 11.2  
8.6 11.8  
7.8 12.2  
18.7  
7.2 12.4  
17.3  
25.9  
51.8  
5.5  
37.4 14.4 16.8  
49.9 19.2 22.4  
34.6 12.9 17.7  
46.1 17.2 23.6  
31.0 11.7 18.3  
41.3 15.6 37.6  
28.1 10.8 18.6  
37.4 21.6 37.2  
3.5  
5.4  
3.2  
5.4  
8.4  
3.2  
5.0  
3.4  
5.7  
7.7  
12.0  
24.0  
2.8  
4.5  
3.6  
6.0  
6.7  
10.8  
21.6  
2.5  
4.1  
3.7  
6.2  
6.0  
9.8  
2.3  
3.8  
3.8  
6.3  
5
13.0  
9.1  
10  
15  
20  
10.8 10.8  
16.2 16.2  
21.6 21.6  
25.9 10.0 11.4  
38.9 15.0 17.1  
51.8 20.0 22.8  
9.0 12.0  
8.2 12.4  
19.7  
7.6 12.6  
18.2  
27.4  
36.5  
36.0 13.5 18.0  
48.0 18.0 24.0  
32.4 12.3 18.6  
43.2 16.4 24.8  
Compressor power input  
29.5 11.4 18.9  
39.4 15.2 25.2  
LCWT: Leaving chilled water temperature, °F  
TR: Tons of refrigeration cooling capacity  
kW:  
Cooler GPM:  
Flow rate in US GPM for cooler  
5
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
Single Phase Air Cooled Ratings  
UniPac™  
Models USAC-25 through USAC-60  
25 through 60 Tons  
Ambient Air Temperature °F  
LCWT Model  
85  
95  
105  
115  
120  
°F  
USAC  
Cooler  
GPM  
Cooler  
GPM  
Cooler  
GPM  
Cooler  
GPM  
Cooler  
GPM  
TR  
kW  
TR  
kW  
TR  
kW  
TR  
kW  
TR  
kW  
25  
30  
40  
50  
60  
25  
30  
40  
50  
60  
25  
30  
40  
50  
60  
25  
30  
40  
50  
60  
25  
30  
40  
50  
60  
25  
30  
40  
50  
60  
25  
30  
40  
50  
60  
21.5 25.0  
25.8 30.0  
34.4 40.0  
13.0 50.0  
51.6 60.0  
23.0 25.5  
28.0 31.0  
37.0 41.0  
46.0 51.0  
55.0 61.0  
24.5 26.0  
29.4 31.2  
39.0 41.6  
49.0 52.0  
59.0 62.4  
24.7 26.0  
29.7 31.2  
39.5 41.6  
49.5 52.0  
59.5 62.4  
25.0 26.0  
30.0 31.2  
40.0 41.6  
50.0 52.0  
60.0 62.4  
26.0 26.5  
31.0 32.0  
42.0 43.0  
52.0 53.0  
62.4 36.6  
27.0 27.0  
32.4 32.4  
43.0 43.0  
54.0 54.0  
64.8 64.8  
51.6 19.5 26.0  
61.9 23.4 31.2  
82.6 31.2 41.6  
31.2 39.0 52.0  
123.8 47.0 63.0  
55.2 20.5 26.5  
67.2 25.0 32.0  
88.8 33.0 43.0  
110.4 41.0 53.0  
132.0 49.0 63.6  
58.8 22.0 27.0  
70.6 26.4 32.4  
93.6 35.0 43.0  
117.6 44.0 54.0  
141.6 53.0 65.0  
59.3 22.5 27.3  
71.3 27.2 32.7  
94.8 36.0 43.5  
118.8 45.0 54.5  
142.8 54.1 65.5  
60.0 23.0 27.5  
72.0 28.0 33.0  
96.0 37.0 44.0  
120.0 46.0 55.0  
144.0 55.2 66.0  
62.4 24.0 28.0  
74.4 29.0 34.0  
100.8 38.0 45.0  
124.8 48.0 56.0  
149.8 57.6 67.2  
64.8 25.0 28.5  
77.8 30.0 34.0  
103.2 40.0 46.0  
129.6 50.0 57.0  
155.5 60.0 68.4  
46.8 17.5 27.0  
56.2 21.0 32.4  
74.9 28.0 43.0  
93.6 35.0 54.0  
112.8 42.0 65.0  
49.2 18.5 27.5  
60.0 22.0 33.0  
79.2 30.0 44.0  
98.4 37.0 55.0  
117.6 44.0 66.0  
52.8 20.0 38.5  
63.4 24.0 34.2  
84.0 32.0 46.0  
105.6 40.0 57.0  
127.2 48.0 68.4  
54.0 20.5 28.7  
65.3 24.5 34.6  
86.4 33.0 46.1  
108.0 41.0 57.5  
129.8 49.2 69.0  
55.2 21.0 29.0  
67.2 25.0 35.0  
88.8 34.0 46.0  
110.4 42.0 58.0  
132.5 50.4 69.6  
57.6 21.5 29.5  
69.6 26.0 35.4  
91.2 34.4 47.2  
115.2 43.0 59.0  
138.2 51.6 70.8  
60.0 22.5 30.0  
72.0 27.0 36.0  
96.0 36.0 48.0  
120.0 45.0 60.0  
144.0 54.0 72.0  
kW:  
42.0 15.0 27.5  
50.4 18.0 33.0  
67.2 24.0 44.0  
84.0 30.0 55.0  
100.8 36.0 66.0  
44.4 16.5 28.5  
52.8 20.0 34.0  
72.0 26.4 45.6  
88.8 33.0 57.0  
105.6 39.6 68.4  
48.0 17.5 29.5  
57.6 21.0 35.4  
76.8 28.0 47.0  
96.0 35.0 59.0  
115.2 42.0 71.0  
49.2 18.0 29.7  
58.8 21.5 35.7  
79.2 29.0 47.5  
98.4 36.0 59.5  
118.1 43.2 71.5  
50.4 18.5 30.0  
60.0 22.0 36.0  
81.6 30.0 48.0  
100.8 37.0 60.0  
121.0 44.4 72.0  
51.6 19.5 30.5  
62.4 23.4 36.6  
82.6 31.2 49.0  
103.2 39.0 61.0  
123.8 46.8 73.2  
54.0 20.5 31.0  
64.8 25.0 37.0  
86.4 33.0 50.0  
108.0 41.0 62.0  
129.6 49.2 74.4  
Compressor power input  
36.0 14.0 29.0  
43.2 17.0 35.0  
57.6 22.4 46.4  
72.0 28.0 58.0  
86.4 33.6 69.6  
39.6 15.0 29.0  
48.0 18.0 35.0  
63.4 24.0 30.0  
79.2 30.0 58.0  
95.0 36.0 69.6  
42.0 16.0 29.5  
50.4 19.2 35.4  
67.2 26.0 47.0  
84.0 32.0 59.0  
100.8 38.4 71.0  
43.2 16.5 30.3  
51.6 19.6 36.2  
69.6 26.5 48.0  
86.4 33.0 60.0  
103.7 39.7 72.1  
44.4 17.0 31.0  
52.8 20.0 37.0  
72.0 27.0 49.0  
88.8 34.0 61.0  
106.6 41.0 73.2  
46.8 18.0 31.0  
56.2 21.6 37.0  
74.9 29.0 49.6  
93.6 36.0 62.0  
112.3 43.2 74.4  
49.2 19.0 32.0  
60.0 23.0 38.0  
79.2 30.4 50.4  
98.4 38.0 63.0  
118.1 45.6 75.6  
33.6  
40.8  
53.8  
67.2  
80.6  
36.0  
43.2  
57.6  
72.0  
86.4  
38.4  
46.1  
62.4  
76.8  
92.2  
39.6  
47.0  
63.6  
79.2  
95.3  
40.8  
48.0  
64.8  
81.6  
98.4  
43.2  
51.8  
69.6  
86.4  
103.7  
45.6  
55.2  
73.0  
91.2  
109.4  
40  
42  
44  
45  
46  
48  
50  
LCWT: Leaving chilled water temperature, °F  
TR: Tons of refrigeration cooling capacity  
Cooler GPM:  
Flow rate in US GPM for cooler  
6
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
Single Phase Water Cooled Ratings  
UniPac™  
Models USWC-3 through USWC-60  
3 through 60 tons  
Condenser Leaving Water Temperature, °F  
LCWT Model  
85  
Cooler Cond  
GPM GPM  
95  
Cooler Cond  
GPM GPM  
100  
Cooler  
GPM  
°F  
USWC  
Cond  
GPM  
TR  
kW  
TR  
kW  
TR  
kW  
3
3.0  
3.0  
7.2  
9.0  
2.8  
3.0  
6.7  
8.4  
2.6  
3.0  
6.2  
7.8  
5
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
40.0  
50.0  
60.0  
3.5  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
40.0  
50.0  
60.0  
3.1  
12.0  
24.0  
36.0  
48.0  
60.0  
72.0  
96.0  
120.0  
144.0  
8.4  
15.0  
30.0  
4.7  
9.3  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
40.0  
50.0  
60.0  
3.1  
11.3  
22.3  
33.6  
44.6  
55.9  
67.0  
89.3  
111.6  
133.9  
7.9  
14.1  
27.9  
42.0  
55.8  
69.9  
83.7  
111.6  
139.5  
167.4  
9.9  
4.3  
8.6  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
40.0  
50.0  
60.0  
3.1  
10.3  
20.6  
31.2  
41.3  
51.6  
61.9  
82.6  
103.2  
123.8  
7.4  
12.9  
25.8  
39.0  
51.6  
64.5  
77.4  
103.2  
129.0  
154.8  
9.3  
10  
15  
20  
25  
30  
40  
50  
60  
3
45.0  
14.0  
18.6  
23.3  
27.9  
37.2  
46.5  
55.8  
3.3  
13.0  
17.2  
21.5  
25.8  
34.4  
43.0  
51.6  
3.1  
60.0  
40  
75.0  
90.0  
120.0  
150.0  
180.0  
10.5  
5
5.4  
5.2  
13.0  
25.9  
38.9  
51.6  
64.8  
78.0  
103.7  
129.6  
154.8  
9.6  
16.2  
5.2  
5.2  
12.5  
24.7  
37.2  
49.4  
61.9  
74.4  
98.6  
123.6  
148.3  
8.9  
15.6  
30.9  
46.5  
61.8  
77.4  
93.0  
123.3  
154.5  
185.4  
11.1  
16.5  
41.4  
49.5  
65.7  
82.5  
99.0  
132.6  
165.0  
197.1  
4.9  
5.2  
11.8  
23.5  
35.3  
47.0  
58.8  
70.6  
93.6  
117.6  
141.6  
8.2  
14.7  
29.4  
44.1  
58.8  
73.5  
88.2  
117.0  
147.0  
177.0  
10.2  
15.6  
31.2  
46.8  
62.4  
78.0  
93.0  
126.0  
156.0  
187.2  
10  
15  
20  
25  
30  
40  
50  
60  
3
10.8  
16.2  
21.5  
27.0  
32.5  
43.2  
54.0  
64.5  
4.0  
10.4  
15.6  
20.8  
26.0  
31.2  
41.6  
52.0  
62.4  
3.2  
32.4  
10.3  
15.5  
20.6  
25.8  
31.0  
41.1  
51.5  
61.8  
3.7  
10.4  
15.6  
20.8  
26.0  
31.2  
41.6  
52.0  
62.4  
3.2  
9.8  
10.4  
15.6  
20.8  
26.0  
31.2  
41.6  
52.0  
62.4  
3.2  
48.6  
14.7  
19.6  
24.5  
29.4  
39.0  
49.0  
59.0  
3.4  
64.5  
44  
81.0  
97.5  
129.6  
162.0  
193.5  
12.0  
5
5.8  
5.3  
13.9  
27.8  
41.8  
55.2  
69.6  
84.0  
111.4  
139.2  
165.6  
17.4  
5.5  
5.3  
13.2  
33.1  
39.6  
52.6  
66.0  
79.2  
106.1  
132.0  
157.7  
5.2  
5.3  
12.5  
25.0  
37.4  
49.9  
62.4  
74.4  
100.8  
124.8  
149.8  
10  
15  
20  
25  
30  
40  
50  
60  
11.6  
17.4  
23.0  
29.0  
35.0  
46.4  
58.0  
69.0  
10.6  
15.9  
21.7  
26.5  
32.0  
43.0  
53.0  
63.6  
34.8  
13.8  
16.5  
21.9  
27.5  
33.0  
44.2  
55.0  
65.7  
10.6  
15.9  
21.7  
26.5  
32.0  
43.0  
53.0  
63.6  
10.4  
15.6  
20.8  
26.0  
31.0  
42.0  
52.0  
62.4  
10.6  
15.9  
21.7  
26.5  
32.0  
43.0  
53.0  
63.6  
52.2  
69.0  
48  
87.0  
105.0  
139.2  
174.0  
207.0  
LCWT: Leaving chilled water temperature, °F  
TR: Tons of refrigeration cooling capacity  
kW:  
Compressor power input  
Cooler GPM:  
Cond GPM:  
Flow rate in US GPM for cooler  
Flow rate in US  
7
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
USAC Physical Data  
USAC-3, 4, 5, 8  
USAC-10, 12, 15, 20  
USAC-25, 30  
USAC-40, 50, 60  
Dimensions  
Water Connections  
Est R-22  
Charge, lbs.  
9/11  
12/18  
22/25/30/40  
50/60  
Model USAC  
Weight, lbs.  
L”  
48  
48  
90  
120  
90  
W”  
43  
43  
43  
43  
86  
86  
H”  
53  
53  
55  
55  
55  
55  
Inlet, MPT”  
Outlet, MPT”  
-3, 4  
-5, 8  
-10, 12, 15, 20  
-25, 30  
-40  
500/600  
650/900  
¾
1
2
3
4
4
¾
1
2
3
4
4
1,100/1,300/1,500  
2,000/2,300  
3,000  
4,000/4,500  
85  
110/140  
-50, 60  
120  
8
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
USWC Physical Data  
USWC-3, 5, 10  
USWC-15, 20  
USWC-25, 30  
Water Connections,  
Inlet”/Outlet”  
Dimensions  
Est R-22  
Charge, lbs.  
Model USWC  
Weight, lbs.  
L”  
W”  
34  
34  
34  
34  
H”  
48  
48  
48  
48  
Condenser  
Cooler  
-3, 5  
-10  
-15, 20  
-25, 30  
20  
20  
48  
84  
400/500  
700  
900/1,000  
1,200/1,600  
¾
1
¾
1
7/14  
24  
40/55  
65/80  
1 ½  
2
1 ½  
2
For models larger than USWC-30, please contact the factory for data  
9
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
Electrical Data  
USAC Packaged Air Cooled Chillers  
Total Unit  
Compressor Motor Data  
Condenser Fan Motor Data  
Standard Unit  
Optional Low Ambient Unit  
Single Phase/Single  
Speed Motor  
Single Phase/Speed  
Control  
Model  
Max  
Fuse  
Rec.  
Fuse  
HP  
Each  
RLA  
Each  
LRA  
Each  
MCC  
Each  
MCA  
Qty  
HP  
Each  
FLA  
Each  
Qty  
HP  
RLA  
HP  
RLA  
Qty  
Qty  
Each Each  
Each Each  
30  
33  
45  
55  
35  
40  
1
1
3
4
5
4
5
4
5
5
5
5
5
5
5
18.4  
22.1  
32.1  
22.1  
32.1  
22.1  
32.1  
32.1  
32.1  
32.1  
32.1  
32.1  
32.1  
95  
25.8  
31  
45  
31  
45  
31  
45  
45  
45  
45  
45  
45  
45  
1
1
1
1
2
2
2
2
2
2
4
4
4
0.75  
0.75  
0.75  
0.75  
0.75  
0.75  
0.75  
0.75  
1.5  
5.3  
5.3  
5.3  
5.3  
5.3  
5.3  
5.3  
5.3  
6.6  
6.6  
5.3  
6.6  
6.6  
_
_
_
_
1
1
1
1
1
1
2
2
2
_
_
1
1
1
1
1
1
1
1
1
1
2
2
2
0.75  
0.75  
0.75  
0.75  
0.75  
0.75  
0.75  
0.75  
1.5  
5.3  
5.3  
5.3  
5.3  
5.3  
5.3  
5.3  
5.3  
6.6  
6.6  
5.3  
6.6  
6.6  
USAC-3  
USAC-4  
137  
148  
137  
148  
137  
148  
148  
148  
148  
148  
148  
148  
_
_
45  
77  
55  
1
_
_
USAC-5  
55  
77  
60  
2
_
_
USAC-8  
83  
115  
105  
150  
180  
215  
250  
325  
390  
450  
90  
2
0.75  
0.75  
0.75  
0.75  
1.5  
1.5  
0.75  
1.5  
1.5  
5.3  
5.6  
5.3  
5.3  
6.6  
6.6  
5.3  
6.6  
6.6  
USAC-10  
USAC-12  
USAC-15  
USAC-20  
USAC-25  
USAC-30  
USAC-40  
USAC-50  
USAC-60  
83  
88  
3
115  
150  
185  
220  
290  
350  
420  
125  
160  
200  
230  
300  
370  
430  
3
4
5
6
1.5  
1.5  
8
0.75  
1.5  
0.75  
1.5  
10  
12  
1.5  
1.5  
Electrical Data  
USWC Packaged Water Cooled Chillers  
Total Unit  
Compressor Motor Data  
Model  
MCA  
25  
Max Fuse  
40  
Rec. Fuse  
30  
Qty  
1
HP Each  
RLA Each  
18.4  
22.1  
32.1  
22.1  
32.1  
22.1  
32.1  
32.1  
32.1  
32.1  
32.1  
32.1  
32.1  
LRA Each  
95  
MCC Each  
3
4
5
4
5
4
5
5
5
5
5
5
5
25.8  
31  
45  
31  
45  
31  
45  
45  
45  
45  
45  
45  
45  
USWC-3  
USWC-4  
28  
50  
35  
1
137  
148  
137  
148  
137  
148  
148  
148  
148  
148  
148  
148  
40  
72  
50  
1
USWC-5  
50  
72  
55  
2
USWC-8  
72  
104  
95  
80  
2
USWC-10  
USWC-12  
USWC-15  
USWC-20  
USWC-25  
USWC-30  
USWC-40  
USWC-50  
USWC-60  
72  
77  
3
104  
136  
169  
200  
265  
330  
395  
106  
169  
200  
233  
297  
360  
425  
115  
145  
175  
200  
275  
360  
400  
3
4
5
6
8
10  
12  
Notes:  
1. All units have across-the-line start.  
2. RLA (rated load amps) rated in accordance with ARI Standard.  
3. MCA (minimum circuit amps) equal 125% of the RLA for the largest motor in the circuit plus 100% of the RLA for all other motors in the circuit per N.E.C.  
4. Based on copper conductors with 75° C insulation per N.E.C. Table 310-16.  
5. Max fuse size is based on 225% of the RLA for the largest motor in the circuit plus 100% of the RLA for all other motors in the circuit per N.E.C. This is the  
largest fuse allowed per N.E.C. A smaller fuse is often recommended based on the unit application and ambient temperature.  
10  
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
Installation and Application Data  
4. For multiple units, a minimum lateral clearance of 10 feet between  
two units is recommended.  
General  
Continental UniPac™ Air Cooled Packaged Chillers models USAC  
are designed for outdoor installations and normal exposure to summer  
and winter conditions. The vertical condenser air discharge feature  
allows rooftop or ground installations. Horizontal units are also available.  
The enclosure door is provided to protect the electrical components  
against unauthorized access. However, consideration should be given to  
a field-installed protective fence to further reduce possibility of accidental  
damage or unauthorized entry, especially for ground level installations.  
Field installed fence must have a minimum of 50% open area.  
Field Piping  
1. If a circulating pump is field furnished, the pump must discharge into the  
cooler first and then through the cooler to the system.  
2. Provide stop valves on all inlet and outlet piping to facilitate servicing.  
3. Provide drain connections at low points to permit drainage of cooler and field  
piping.  
4. Provide air vents at high points easily accessible for servicing  
5. Provide a strainer on the inlet to the cooler.  
Continental UniPac™ Water Cooled Packaged Chillers models  
USWC ar designed for indoor installations and normal indoor conditions.  
However, if outdoor installation is required, the factory option of a  
complete unit enclosure and heater tape with thermostat for the cooler  
and condenser must be ordered.  
6. Provide wall hangers and rubber isolated piping hangers to reduce sound  
and vibration transmission though liquid piping.  
7. Provide thermometers and pressure gauges for installation in the inlet and  
outlet water lines. These items are available as optional features and are not  
included in the standard unit.  
8. Chilled water lines should be insulated to reduce heat pick up and prevent  
condensation.  
The following guidelines are recommended:  
9. For winter low ambient operation, it is recommended that a heater cable of 4  
watts per lineal foot of pipe be installed, and exposed lines be properly insulated  
to protect against freeze conditions.  
10. Flush all chilled water piping prior to final connection to the UniPac™ chiller  
systems.  
Location for Air Cooled Systems  
1. Whether it is a rooftop or ground level installation, select a place with  
unrestricted fresh air supply for the air cooled condenser and minimum sun  
exposure.  
2. Avoid locations between structures, beneath windows, or any other restriction  
that may affect adequate air supply to the condenser and where normal operating  
sounds may be objectionable.  
3. The condenser fans are propeller type and are not designed for use with duct  
work  
Location for Water Cooled Systems  
1. The preferred location for the water cooled system is a proper plant room  
with at least 4ft access on all four sides.  
Water Treatment  
Adequate water treatment should be determined locally, depending  
on the local water quality and the type of system. Any foreign material or  
dirt in the water system can adversely affect the performance of the  
UniPac™ unit.  
Freeze Protection  
Foundation  
Continental recommends use of a premixed glycol (Propylene or  
Ethylene) or HVAC heat transfer fluids. Contact factory for more details.  
Automotive antifreeze is not recommended because these often include  
silicates. Silicates end up coating the heat transfer surface reducing  
efficiency, fouling the system and shortening the life of the pump seals.  
All chillers should be mounted on a flat and level foundation, ground,  
or rooftop, capable of supporting the total operating weight of the unit  
and service personnel.  
(a)  
Ground Level It is important that the units be installed on a  
substantial base that will not settle, causing strain on the liquid lines, resulting in  
possible leaks. Mounting holes (9/16”) are provided in the unit steel channels for  
bolting the unit to its foundation. An independent one-piece concrete slab, not tied  
to the main building and with footers extended below the frost line, is  
recommended.  
Corrosive Atmosphere Operation  
Continental offers the following choices of condenser coil  
combinations for various corrosive atmospheres.  
(b)  
Roof-top Rooftop installations will require consideration by an  
Blygold or Heresite coating for aluminum fins; Copper Fins with  
Blygold or Heresite coating or complete unit coated with Blygold, Imron  
or Heresite.  
architect and contractor to have adequate structural strength to safely support the  
entire operating weight of the unit and service personnel. Structurally transmitted  
vibration and sound must be avoided by mounting the unit on proper isolators.  
Field Electric Wiring  
Clearances  
All field wiring must be in accordance with applicable local/national  
codes and ordinances  
1. Air cooled systems draw air from all sides; therefore units must be  
installed with sufficient clearances for air entrance to the condenser coil,  
for air discharge away from the condenser, and for servicing. Minimum  
clearances for all units are 4 feet on all sides.  
Continental chiller systems are factory wired for optimum reliability.  
Controls are factory set for the operating conditions. These controls must  
not be field modified without written consent from Continental; otherwise  
the warranty is voided. The use of a simple remote switch or timer is  
permitted but it must be connected to the Continental control panel at  
points specifically indicated for that purpose.  
2. In installations where winter operation is intended and snow  
accumulations are expected, additional height must be provided in order  
to insure normal condenser airflow.  
3. When free airflow to the condenser is reduced or restricted,  
condenser air may be recirculated, considerably reducing system  
capacity and increasing power consumption. All ratings are based on  
free air discharge.  
Remote chilled water set point option is available- see under  
options.  
11  
Phone: 317-337-9813  
Fax: 317-337-9816  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continental Single Phase Chillers  
UniPac™  
UniPac™Guide Spec  
All power starting and safety/operating controls shall be mounted  
in a fully enclosed control panel with access door  
Power controls shall include:  
Furnish and install where indicated on plans Qty______  
Continental UniPac™ model (USAC, USWC) _________  
packaged liquid chiller(s).  
Single point electrical terminal block  
Compressor-motor contactor(s)  
Compressor run capacitor(s)  
Fan motor contactor(s) (air cooled units only)  
Control circuit fuse  
The (each) unit shall have a cooling capacity of ______ Tons  
with ______ compressor kW when cooling _______GPM of water  
from ______°F to _______°F and a cooler fouling factor of 0.00025  
Hr. Sq. Ft °F/Btu. The water pressure drop shall not exceed  
______ feet of water through the cooler. The USAC entering air  
temperature will be _______°F. The USWC unit will be supplied  
with ______GPM of _______°F condenser water with a condenser  
fouling factor of 0.00025 Hr. Sq. Ft. °F/Btu. The condenser water  
pressure drop shall not exceed _______ft of water.  
Control circuit terminal block  
Safety/Operating controls shall include:  
Two position switch indicating off/system on – per circuit  
High Pressure control with manual reset –per circuit  
Low pressure control with auto reset – per circuit  
Adjustable chilled water temperature controller  
Adjustable freezestat  
Adjustable compressor anti-recycle timer(s)  
Relay(s)  
Built-in compressor-motor overload  
The unit overall dimensions shall not exceed ______ins. In  
length. _____ins in width and ______ins. In height. The unit  
operating weight shall not exceed ______lbs.  
General  
Packaged Liquid Chiller shall be completely factory assembled  
including all interconnecting refrigerant piping and internal wiring  
controls, mounted on a steel frame which accommodates the air  
(water) cooled condenser, compressor and cooler. The units shall  
be leak tested, evacuated and shipped with a vapor charge of R-22.  
Split chillers shall be field piped, pressure tested, evacuated  
and then field charged with R-22.  
Available Factory Supplied Accessories  
Control Transformer Factory mounted transformer converts unit  
power to control voltage for single point electrical (115, 240 or 24 volt).  
Flow Switch Factory mounted and wired to the control panel.  
Chilled Water Pump Package Factory mounted and wired chilled  
water pump with starter in the control panel and interlocked with flow  
switch.  
All units shall include the following:  
MicroProcessor Controls State-of-the-art microprocessor.  
Operating Gauges Suction and discharge gauges factory installed  
and piped to each compressor.  
Compressor Motor  
USAC/USWC compressor motor shall be state-of-the-art scroll  
with fewer moving parts and sweated without valves. All  
compressor(s) shall be mounted on resilient pads to minimize  
vibration. Safety internal relief per ASA-B9.1 Code.  
Indicating Lights are wired and mounted on control panel. Lights  
furnished for Power On, High Pressure and No Flow/Freeze.  
Vibration Isolators Level adjusting spring type 1” deflection or  
Neoprene pads, shipped loose.  
Low Ambient Accessory (Air Cooled Models Only) Standard unit will  
operate down to 45°F. Unit will operate down to 0°F with this factory-  
mounted accessory of fan speed control, or add low ambient to –20°F.  
Non-Fused Disconnect Switch Factory mounted and wired to control  
panel. NEMA 3R for air cooled, NEMA 1 for water cooled.  
Blygold Coated Condenser Copper tube/aluminum fin or copper  
tube/copper fin coated with Blygold.  
Cooler  
The cooler shall be direct expansion shell and coil type with  
refrigerant in the shell and liquid to be chilled in the tube. The  
design working pressure of the cooler shell (liquid) side shall be  
150 psig. And 200 psig for the tube (refrigerant) side. The cooler  
shall be insulated with ¾” closed cell insulation.  
Heresite Coated Condenser phenolic corrosion resistant coating for  
copper tube and aluminum fin coil or copper/copper coil.  
Copper Fin Condenser Coil Copper fin condenser coils.  
Sound Attenuator consists of sound absorbing material that  
surrounds compressor. Factory installed.  
Condenser-Air Cooled  
The condenser shall be of copper tube, aluminum fin  
construction. Fans shall be propeller-type direct driven by totally  
enclosed “air over” motors with built-in overload protection,  
positioned within the cabinets for weather protection.  
Dual Unit Kit allows operation of two or more units with parallel or  
series water circuit. Field mounted.  
Condenser – Water Cooled  
Alarm Bell Contacts allows alarm bell connection to pressure controls  
for signaling if unit fails on manual reset controls.  
Water Flange Kit Factory or field mounted consists of 150 lb raised  
flanges to convert to flanged cooler connections.  
The condenser shall be shell and coil type with water flowing  
through seamless copper tubes and refrigerant though the carbon  
steel shell  
High Return Water Thermostat Factory mounted thermostat senses  
high return water temperature at start-up. Allows unit to run un-loaded  
instead of shutting down due to high head pressure.  
Desuperheaters Provides “free hot water” by recovering heat from  
superheated gas.  
Compressor Cycle Counter/Hour Meters Cycle counter and hour  
meter.  
Remote Display Panel allows operator to monitor and control chiller  
operation from a remote location.  
Refrigerant Circuit  
Each refrigerant circuit shall be constructed of copper tubing  
with brazed joints, and shall include: filter drier, solenoid valve,  
sight glass, thermal expansion valve, with external equalizer. The  
entire suction line shall be insulated.  
Control Center  
The control center shall be NEMA-1 type for indoor models and  
weatherproof for outdoor models.  
Continental Chillers LLC  
Phone: 317-337-9813  
Fax: 317-337-9816  
PO Box 781555 – Indianapolis, IN 46278 USA  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Compaq Network Card 1600R User Manual
CyberData Telephone 011030 User Manual
Digicom Network Router 8E4389 User Manual
Dimplex Electric Heater Duo400i Duo500i User Manual
Elation Professional Indoor Furnishings Power Wash 575E User Manual
Estate Refrigerator W10193170A User Manual
EverFocus Security Camera ECZ230E User Manual
Fujitsu All in One Printer B19W 5 ECO User Manual
Gefen Home Theater System GTV CR 2SP User Manual
Global Machinery Company Lawn Mower RL504 User Manual