GCH and GCHIS-6 Circulation Heaters  
For Steam, Gas and Air Heating  
Specifications — Table A  
1” Pipe  
Outlet  
Dimensions (In.)  
Model  
Volts  
Phase  
kW  
W/In2  
A
B
C
D
GCH-60905  
GCH-61205  
GCH-62005  
GCH-62505  
GCH-63005  
GCHIS-6045  
GCHIS-6085  
GCHIS-6125  
GCHIS-6155  
GCHIS-6205  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
240 or 480  
1 or 3 L  
1 or 3 L  
1 or 3 L  
3Y  
9
23.8  
23.1  
23.3  
22.9  
22.7  
15  
41-3/4  
48-3/4  
60-1/4  
73-5/8  
86-5/8  
41-3/4  
48-3/4  
60-1/4  
73-5/8  
86-5/8  
30  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
11-3/8  
14-7/8  
20-5/8  
27-5/16  
33-7/8  
11-3/8  
14-7/8  
20-5/8  
27-5/16  
33-7/8  
1-1/4”  
12  
20  
25  
30  
4
37  
48-1/2  
61-7/8  
74-7/8  
30  
3Y  
3Y  
3Y  
8
15  
37  
Mtg. Lugs  
3Y  
12  
15  
30  
15  
48-1/2  
61-7/8  
74-7/8  
B
3/8-16 Tap  
3Y  
15  
C
1-1/2” Deep  
A
3Y  
15  
8”  
12-1/32”  
1” Pipe  
Inlet  
AR  
Thermostat  
8-3/4”  
1-3/8” K.O.  
For 1” Conduit  
GENERAL  
Depending upon the order specifications, the GCH-GCHIS-6 may  
or may not be factory equipped with an AR or other Chromalox ther-  
mostat. Such thermostats function to control outlet temperatures and to  
limit internal temperatures under abnormal flow conditions. These  
controls do not fail safe.  
Read and understand all instructions before  
installing, servicing or operating product. Failure  
to do so could result in personal injury or property  
damage.  
The GCH and GCHIS-6 series is a general-purpose gas or steam  
circulation heater intended for use indoors.  
The 6 INCOLOY® sheathed tubular elements are centered in a 5”  
diameter heating chamber and welded to a removable flange. The  
assembly is surrounded by 1-1/2” insulation and sheet metal jacket.  
The GCH series has a steel flange and chamber. The GCHIS series has  
stainless steel flange and chamber.  
The system designer is responsible for the safety  
of this equipment and should install adequate  
back-up controls and safety devices with their  
electric heating equipment. Where the conse-  
quences of failure could result in personal injury or  
property damage, back-up controls are essential.  
© 2010 Chromalox, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING  
CONTACTOR  
CONTACTOR  
CONTACTOR  
L1  
L2  
L3  
L1  
L2  
L3  
L1  
L2  
L3  
120V, 240V  
120V, 240V  
120V, 240V  
THERMOSTAT  
THERMOSTAT  
THERMOSTAT  
Figure 8 – GCHIS  
240V, 3øY  
Figure 9 – GCHIS  
40V, 3øY  
Figure 7 – GCH6  
480V, 3ø  
Instructions for converting  
240V LINE  
480V LINE  
GCH6, 240V, 3ø to GCH6, 480V, 3ø  
166-014828-024  
166-075229-018  
1. Remove all jumper straps and separate  
according to different lengths.  
166-075229-014  
2. Discard jumper straps 166-075229-018  
(1-1/4” long).  
3. Reassemble jumper straps 166-014828-  
024 (2-1/2” long) and 166-075229-014  
(1-1/2” long) as in Figure B.  
166-014828-024  
FIGURE B  
480V, 3ø (Series) Connected  
166-075229-014  
240V, 3ø (Parallel) Connected  
FIGURE A  
4. Replace washers and nuts.  
5. Check circuits.  
NOTE: Broken Lines Indicate “Customer-furnished”. However, thermostat could have been furnished by chromalox if so specified on order.  
OPERATION  
1. Do not heat materials that are corrosive to the heating element  
sheath or chamber.  
2. Terminal ends of heater must be protected from drippings, con-  
densation, spray or direct spill-over of material whose presence at  
the terminals may damage heater electrical insulation. Liquid-tight  
terminal enclosures are available to protect heater. Consult your  
local Chromalox Sales office.  
given discharge gas temperature, heater element  
sheath temperature and pipe body temperature  
tend to increase as gas flow (mass velocity)  
decreases. The standard GCH-6 has a 750˚F limita-  
tion on the carbon steel body and a 1500˚F limit on  
the INCOLOY sheath elements. Check factory if any  
doubt exists as to temperatures that will be  
encountered in your specific application. At pipe  
body temperatures above 750˚F, stainless steel  
pipe body is required (model GCHIS).  
3. If foreign material is carried by the gaseous flow, install suitable  
filters in the inlet pipe line to the heater.  
4. Do not allow heater to operate when steam, air or gas flow is inter-  
rupted.  
FIRE/EXPLOSION HAZARD. Safe operating condi-  
tions depend on operating pressure, mass velocity  
of gas and discharge temperature of the gas. At a  
FIRE/EXPLOSION HAZARD. Do not exceed the  
Pressure-Temperature rating of the flange as list-  
ed in ANSI B16.5.  
MAINTENANCE  
2. Periodically check temperature control and limit control operation  
to insure accurate and safe process operation.  
3. Check all electrical connections periodically and retighten con-  
nections which may have loosened in service. Replace wire and  
wire terminals that show signs of oxidation which would interfere  
with establishment of reliable electrical connections.  
ELECTRIC SHOCK HAZARD. Disconnect all power  
before installing or servicing heater. Failure to do so  
could result in personal injury or property damage.  
Heater must be installed and serviced by a qualified  
person in accordance with the National Electrical  
Code, NFPA 70.  
NOTE: Maintenance intervals to be determined by the user based on  
their knowledge of the heated medium and operating conditions.  
1. Remove heating element assembly periodically to check heater  
sheath for corrosion or excessive oxidation. Correct operating con-  
ditions to minimize sheath deterioration.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RENEWAL PARTS  
Catalog Number  
GCH-60905  
Volts  
Phase  
kW  
Heating Element  
240  
240  
480  
482  
1
3 L  
1
9
9
9
9
155-115143-001  
155-115143-002  
155-115143-003  
155-115143-004  
3 L  
240  
240  
480  
480  
2-1  
3 L  
1
12  
12  
12  
12  
155-115143-006  
155-115143-007  
155-115143-008  
155-115143-009  
GCH-61205  
GCH-62005  
3 L  
240  
240  
480  
480  
2-1  
3 L  
1
20  
20  
20  
20  
155-115143-011  
155-115143-012  
155-115143-013  
155-115143-014  
3 L  
240  
480  
480  
2-3 L  
2-1  
3 L  
25  
25  
25  
155-115143-016  
155-115143-017  
155-115143-018  
GCH-62505  
GCH-63005  
240  
480  
2-3 L  
3 L  
30  
30  
155-115143-020  
155-115143-021  
Note: When ordering parts for Model Numbers suffixed by “XX” or any other letter or any other letters not specifically identified on this instruction sheet, order Renewal Parts on special order basis, giving  
name of part, part number, model number and description. Note: Number in ( ) indicates quantity of same part number used. Model GCHIS - contact local Chromalox Representative.  
PARTS COMMON TO ALL HEATERS  
AR5524 Thermostat  
Standard Gasket  
300-013863-015  
132-017222-016  
Limited Warranty:  
Please refer to the Chromalox limited warranty applicable to this product at  
2150 N. RULON WHITE BLVD., OGDEN, UT 84404  
TA - U0 - EF  
Litho in U.S.A.  
Phone: 1-800-368-2493  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blomberg Washer WM 87120 NBL00 User Manual
Briggs Stratton Portable Generator 40273 User Manual
BRK electronic Network Card ADF Adapter User Manual
Cambridge Audio Blu ray Player 650BD User Manual
Campbell Hausfeld Nail Gun IN729000AV User Manual
Canon Camera Lens 18 55mm f 35 56 IS User Manual
Canon Digital Camera 3822B002 User Manual
Cardo Headphones S 2TM User Manual
Casio Digital Camera EX Z1 User Manual
Casio Digital Camera K1191PCM1DMX User Manual