4
RT
(Supersedes PJ478-1)
PJ490
161-891364-004
JULY, 2004
SRCCH-1 and SRCCH-2
Self Regulating Crankcase Heaters
GENERAL
SRCCH-1 and SRCCH-2 Self-Regulating Crankcase Heaters are
supplied with flexible lock-strap and pre-stripped 28” cold leads for
easy connection and hardwiring. These heaters are only to be used on
up to 40” diameter compressors located in non-hazardous areas.
ELECTRIC SHOCK/FIRE HAZARD. Do not expose
heater to temperatures above 150˚F.
INSTALLATION
Before installing the SRCCH-1 or SRCCH-2 heater, a megger test
should be performed to check integrity of electrical insulation jacket of
the heating cable.
Use SRCCH-1 for 120V operation and SRCCH-2 for 208-277V
operation.
MEGGER TESTING:
To use the SRCCH-1 and SRCCH-2 heaters, wrap cable around
crankcase and tighten the flexible lock-strap. Make certain to have
good contact between the heater and the surface of the crankcase.
Connect leads to GFCI protected circuit.
Megger testing should be performed before first use and periodi-
cally thereafter. Unplug assembly. Using a 2500 Vdc megohmmeter
(500 Vdc minimum), check the insulation resistance between the
power leads (black and white clamped simultaneously) and the green
ground lead. Reading should be at least 20 meg-ohms regardless of
cable length.
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heating cable and
accessories. A qualified person must perform
installation and service of heating cable and
accessories. Heating cable must be effectively
grounded in accordance with the National
Electrical Code. Failure to comply can result in
personal injury or property damage.
If low reading occurs, cable and insulation should be inspected for
signs of damage. DO NOT attempt to repair damaged heating cable.
If physical damage is found, the entire unit should be replaced.
© 2010 Chromalox, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
|