Chatsworth Products Network Card RIM 600 User Manual

Remote Infrastructure Management  
(RIM-600)  
User Manual  
Version 1.04  
800-834-4969  
©2006 Chatsworth Products, Inc. All rights reserved. CPI and MegaFrame are  
registered trademarks and TeraFrame is a trademark of Chatsworth Products, Inc.  
All other trademarks belong to their respective companies. MKT-60020-328-GT 1/06  
techsupport@chatsworth.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
Your RIM-600 has been carefully designed to give you years of safe, reliable performance. As with all  
electrical equipment, however, there are a few basic precautions you should take to avoid hurting your-  
self or damaging the unit:  
• Read the installation and operating instructions in this manual carefully. Be sure to save it for  
future reference.  
• Read and follow all warning and instruction labels on the product itself.  
• To protect the RIM-600 from overheating, make sure all openings on the unit are not blocked. Do  
not place on or near a heat source, such as a radiator or heat register.  
• Do not use your RIM-600 near water, or spill liquid of any kind into it.  
• Be certain that your power source matches the rating in the specifications of this manual. If you’re  
not sure of the type of power supply to your facility, consult your dealer or local power company.  
• Do not allow anything to rest on the power cord. Do not locate this product where the cord will be  
abused by persons walking on it.  
• Do not overload wall outlets and extension cords, as this can result in the risk of fire or electric  
shock.  
• To reduce the risk of electric shock, the power supply cord for the RIM-600 Host must have a  
grounded lug.  
• The RIM-600 Host power supply cord must be used in accordance with applicable UL/CSA/  
EN/IEC standards, and must meet the conductor size and length terms of the above-mentioned  
standards.  
• All RIM-600 components (Host, Node, PowerGate and PowerGate2) must be plugged into a  
grounded outlet.  
• Never push objects of any kind into this product through ventilation holes as they may touch  
dangerous voltage points or short out parts that could result in a risk of fire or electric shock.  
• To reduce the risk of electric shock, do not disassemble this product, but return it to CPI Customer  
Service, or another approved repair facility, when any service or repair work is required. Opening  
or removing covers may expose you to dangerous voltages or other risks. Incorrect reassembly  
can cause electric shock when the unit is subsequently used.  
• If anything happens that indicates that your RIM-600 is not working properly or has been  
damaged, unplug it immediately and follow the procedures in the manual for having it serviced.  
Return the unit for servicing under the following conditions:  
1. The power cord or plug is frayed or damaged.  
2. Liquid has been spilled into the product or it has been exposed to water.  
3. The unit has been dropped, or the enclosure is damaged.  
4. The unit doesn’t function normally when you’re following the operating instructions.  
Avoid using a telephone (other than a cordless type) during an electrical storm. There may be a  
remote risk of electric shock from lightning.  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
• To reduce the risk of fire or injury to persons, read and follow these instructions:  
1. Use only the specified type and size batteries.  
2. Do not dispose of the batteries in a fire. The cell may explode. Check with local codes for  
possible special disposal instructions.  
3. Do not open or mutilate batteries. Released electrolyte is corrosive and may cause  
damage to the eyes or skin. It may be toxic if swallowed.  
4. Exercise care in handling batteries in order not to short the battery with conducting  
materials such as rings, bracelets, and keys. The battery or conductor may overheat and  
cause burns.  
5. Remove main power and telephone connections before replacing the battery.  
FCC Requirements  
Part 68: The Chatsworth RIM-600 complies with 47 CFR, Part 68 of the rules. On the back of the  
unit there is a label that contains, among other information, the Certification Number and the Ringer  
Equivalence Number (REN) for this equipment. You must, upon request, provide this information to  
your local telephone company.  
The REN is useful to determine the quantity of devices that you may connect to your telephone line  
and still have all of those devices ring when your telephone number is called. In most, but not all areas,  
the sum of the RENs of all devices connected to one line should not exceed five (5.0). To be certain of  
the number of devices that you may connect to your line, you may want to contact your local telephone  
company to determine the maximum REN for your calling area.  
The applicable certification jack USOC for this equipment is: RJ11C. The facility interface code (FIC)  
for this equipment is: 02LS2.  
A compliant telephone cord and modular plug are provided with equipment. This equipment is  
designated to be connected to the telephone network or premises wiring using a compatible modular  
jack which is Part 68 compliant. See Installation Instructions for details.  
This equipment may not be used on coin service units provided by the telephone company. Connection  
to party lines is subject to state tariffs. Contact the state public utility commission, public service com-  
mission or corporation commission for information.  
Should the RIM-600 cause harm to the telephone network, the telephone company may discontinue  
your service temporarily. If possible, they will notify you in advance. But if advance notice isn’t  
practical, the telephone company may temporarily discontinue service without notice and you will be  
notified as soon as possible. You will be informed of your right to file a complaint with the FCC. The  
telephone company may make changes in its facilities, equipment, operations, or procedures where  
such action is reasonably required in the operation of its business and is not inconsistent with the rules  
and regulations of the FCC that could affect the proper functioning of your equipment. If they do, you  
will be notified in advance to give you an opportunity to maintain uninterrupted telephone service.  
If you experience trouble with the Chatsworth RIM-600, or you need information on obtaining service  
or repairs, please contact:  
Chatsworth Products, Inc.  
701 Industrial Drive  
New Bern, NC 28562  
800-834-4969  
Fax: 252-514-2977  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
If the equipment is causing harm to the telephone network, the telephone company may ask that you  
disconnect this equipment from the network until the problem has been corrected or until you are sure  
that the equipment is not malfunctioning.  
Part 15: This equipment has been tested and found to comply with the limits for a Class A digital  
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protec-  
tion against harmful interference when the equipment is operated in a commercial environment. This  
equipment generates, uses and can radiate radio frequency energy and, if not installed and used in  
accordance with the instructions, may cause harmful interference to radio communications. Operation  
of this equipment in a residential area is likely to cause harmful interference in which case the user will  
be required to correct the interference at his own expense.  
Telephone Consumer Protection Act (Host only)  
The FCC Telephone Consumer Protection Act of 1991 makes it unlawful for any person to use a com-  
puter or other electronic device, including FAX machines, to send a message unless such message con-  
tains, in a margin at the top or bottom of each transmitted page or on the first page of the transmission,  
the date and time it is sent and an identification of the business or other entity, or other individual send-  
ing the message, and the telephone number of the sending machine or such business, other entity, or  
individual. (The telephone number provided may not be a 900 number or any other number for which  
charges exceed local or long-distance transmission charges.)  
To comply with this law, you must enter the following information into your RIM-600:  
• Date and Time as described in the Unit Properties section of the Software Manual.  
• Name and telephone number to identify the source of the FAX transmission, as shown in the Unit  
Properties section of the Software Manual.  
General Requirements for all Automatic Dialers (Host only)  
When programming emergency numbers and (or) making test calls to emergency numbers:  
1. Remain on the line and briefly explain to the dispatcher the reason for the call.  
2. Perform such activities in the off-peak hours, such as early morning or late evenings.  
Canadian Department of Communications Statement (Host only)  
Notice: The Canadian Department of Communications label identifies certified equipment. This cer-  
tification means that the equipment meets certain telecommunications network protective operational  
and safety requirements. The Department does not guarantee the equipment will operate to the users  
satisfaction.  
Before installing this equipment, users should ensure that it is permissible to be connected to the facili-  
ties of the local telecommunications company. The equipment must also be installed using an accept-  
able method of connection. In some cases, the companys inside wiring associated with a single line  
individual service may be extended by means of a certified connector assembly (telephone extension  
cord). The customer should be aware that compliance with the above conditions may not prevent deg-  
radation of service in some situations.  
Repairs to certified equipment should be made by an authorized Canadian maintenance facility des-  
ignated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment  
malfunctions, may give the telecommunications company cause to request the user to disconnect the  
equipment.  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Users should ensure for their own protection that the electrical ground connections of the power utility,  
telephone lines and internal metallic water pipe system, if present, are connected together. This precau-  
tion may be particularly important in rural areas.  
CAUTION: Users should not attempt to make such connections themselves, but should contact the  
appropriate electric inspection authority, or electrician, as appropriate.  
The Ringer Equivalence Number (REN) assigned to each terminal device denotes the percentage of the  
total load to be connected to a telephone loop which is used by the device to prevent overloading. The  
termination on a loop may consist of any combination of devices subject only to the requirement that  
the total of the Ringer Equivalence Numbers of all the devices does not exceed 5.0. For RIM-600, the  
Ringer Equivalence Number is 0.3.  
The following Copyright applies to the Graphing features of the RIM-600 web page.  
Portions copyright 1994, 1995, 1996, 1997, 1998, 1999, 2000, 2001, 2002 by Cold Spring Harbor  
Laboratory. Funded under Grant P41-RR02188 by the National Institutes of Health.  
Portions copyright 1996, 1997, 1998, 1999, 2000, 2001, 2002 by Boutell.Com, Inc.  
Portions relating to GD2 format copyright 1999, 2000, 2001, 2002 Philip Warner.  
Portions relating to PNG copyright 1999, 2000, 2001, 2002 Greg Roelofs.  
Portions relating to gdttf.c copyright 1999, 2000, 2001, 2002 John Ellson ([email protected]).  
Portions relating to gdft.c copyright 2001, 2002 John Ellson ([email protected]).  
Portions relating to JPEG and to color quantization copyright 2000, 2001, 2002, Doug Becker and  
copyright © 1994, 1995, 1996, 1997, 1998, 1999, 2000, 2001, 2002, Thomas G. Lane. This software is  
based in part on the work of the Independent JPEG Group.  
Portions relating to WBMP copyright 2000, 2001, 2002 Maurice Szmurlo and Johan Van den Brande.  
Permission has been granted to copy, distribute and modify gd in any context without fee, including a  
commercial application, provided that this notice is present in user-accessible supporting documenta-  
tion.  
This does not affect your ownership of the derived work itself, and the intent is to assure proper credit  
for the authors of gd, not to interfere with your productive use of gd. If you have questions, ask.  
“Derived works” includes all programs that utilize the library. Credit must be given in user-accessible  
documentation.  
This software is provided “AS IS.” The copyright holders disclaim all warranties, either express or  
implied, including but not limited to implied warranties of merchantability and fitness for a particular  
purpose, with respect to this code and accompanying documentation.  
Although their code does not appear in gd 2.0.4, the authors wish to thank David Koblas, David  
Rowley, and Hutchison Avenue Software Corporation for their prior contributions.  
vi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 YEAR LIMITED WARRANTY  
PLEASE READ THIS WARRANTY CAREFULLY BEFORE USING THE PRODUCT.  
THIS LIMITED WARRANTY CONTAINS CHATSWORTH PRODUCTS’ STANDARD TERMS AND CONDITIONS. WHERE PERMITTED  
BY THE APPLICABLE LAW, BY KEEPING YOUR CHATSWORTH PRODUCT BEYOND THIRTY (30) DAYS AFTER THE DATE OF  
DELIVERY, YOU FULLY ACCEPT THE TERMS AND CONDITIONS SET FORTH IN THIS LIMITED WARRANTY.  
IN ADDITION, WHERE PERMITTED BY THE APPLICABLE LAW, YOUR INSTALLATION AND/OR USE OF THE PRODUCT  
CONSTITUTES FULL ACCEPTANCE OF THE TERMS AND CONDITIONS OF THIS LIMITED WARRANTY (HEREINAFTER REFERRED  
TO AS "LIMITED WARRANTY OR WARRANTY"). IF YOU DO NOT AGREE TO THE TERMS AND CONDITIONS OF THIS WARRANTY,  
INCLUDING ANY LIMITATIONS OF WARRANTY, INDEMNIFICATION TERMS OR LIMITATION OF LIABILITY, THEN YOU SHOULD  
NOT USE THE PRODUCT AND SHOULD RETURN IT TO THE SELLER FOR A REFUND OF THE PURCHASE PRICE. THE LAW  
MAY VARY BY JURISDICTION AS TO THE APPLICABILITY OF YOUR INSTALLATION OR USE ACTUALLY CONSTITUTING  
ACCEPTANCE OF THE TERMS AND CONDITIONS HEREIN AND AS TO THE APPLICABILITY OF ANY LIMITATION OF WARRANTY,  
INDEMNIFICATION TERMS OR LIMITATIONS OF LIABILITY.  
1. WARRANTOR: In this Warranty, Warrantor shall mean "Dealer, Distributor, and/or Manufacturer."  
2. ELEMENTS OF WARRANTY: This Product is warranted to be free from defects in materials and craftsmanship with only the limi-  
tations and exclusions set out below.  
3. WARRANTY AND REMEDY: One-Year Warranty — In the event that the Product does not conform to this warranty at any time  
during the time of one year from the date of installation or initial use, provided that this period shall not exceed 18 months from  
the original date of shipment from factory.  
This warranty shall terminate and be of no further effect at the time the product is: (1) damaged by extraneous cause such as  
fire, water, lightning, etc. or not maintained as reasonable and necessary; or (2) modified; or (3) improperly installed; or (4) mis-  
used; or (5) repaired or serviced by someone other than Warrantors’ authorized personnel or someone expressly authorized by  
Warrantor’s to make such service or repairs; (6) used in a manner or purpose for which the product was not intended; or (7) sold  
by original purchaser.  
LIMITED WARRANTY, LIMITATION OF DAMAGES AND DISCLAIMER OF LIABILITY FOR DAMAGES: THE WARRANTOR’S  
OBLIGATION UNDER THIS WARRANTY IS LIMITED TO REPAIR OR REPLACEMENT OF THE PRODUCT, AT THE WARRANTOR’S  
OPTION AS TO REPAIR OR REPLACEMENT. IN NO EVENT SHALL WARRANTORS BE LIABLE OR RESPONSIBLE FOR PAYMENT  
OF ANY INCIDENTAL, CONSEQUENTIAL, SPECIAL AND/OR PUNITIVE DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED  
TO ANY LABOR COSTS, PRODUCT COSTS, LOST REVENUE, BUSINESS INTERRUTPION LOSSES, LOST PROFITS, LOSS OF  
BUSINESS, LOSS OF DATA OR INFORMATION, OR FINANCIAL LOSS, FOR CLAIMS OF ANY NATURE, INCLUDING BUT NOT  
LIMITED TO CLAIMS IN CONTRACT, BREACH OF WARRANTY OR TORT, AND WHETHER OR NOT CAUSED BY WARRANTORS’  
NEGLIGENCE. IN THE EVENT THAT IT IS DETERMINED IN ANY ADJUDICATION THAT THE LIMITED WARRANTIES OF REPAIR  
OR REPLACEMENT ARE INAPPLICABLE, THEN THE PURCHASER’S SOLE REMEDY SHALL BE PAYMENT TO THE PURCHASER  
OF THE ORIGINAL COST OF THE PRODUCT, AND IN NO EVENT SHALL WARRANTORS BE LIABLE OR RESPONSIBLE FOR  
PAYMENT OF ANY INCIDENTAL, CONSEQUENTIAL, SPECIAL AND/OR PUNITIVE DAMAGES OF ANY KIND, INCLUDING BUT NOT  
LIMITED TO ANY LOST REVENUE, BUSINESS INTERRUTPION LOSSES, LOST PROFITS, LOSS OF BUSINESS, LOSS OF DATA OR  
INFORMATION, OR FINANCIAL LOSS, FOR CLAIMS OF ANY NATURE, INCLUDING BUT NOT LIMITED TO CLAIMS IN CONTRACT,  
BREACH OF WARRANTY OR TORT, AND WHETHER OR NOT CAUSED BY WARRANTORS’ NEGLIGENCE.  
WITHOUT WAIVING ANY PROVISION IN THIS LIMITED WARRANTY, IF A CIRCUMSTANCE ARISES WHERE WARRANTORS ARE  
FOUND TO BE LIABLE FOR ANY LOSS OR DAMAGE ARISING OUT OF MISTAKES, NEGLIGENCE, OMISSIONS, INTERRUPTIONS,  
DELAYS, ERRORS OR DEFECTS IN WARRANTORS’ PRODUCTS OR SERVICES, SUCH LIABILITY SHALL NOT EXCEED THE TOTAL  
AMOUNT PAID BY THE CUSTOMER FOR WARRANTORS’ PRODUCT AND SERVICES OR $250.00 US DOLLARS, WHICHEVER IS  
GREATER. YOU HEREBY RELEASE WARRANTORS FROM ANY AND ALL OBLIGATIONS, LIABILITIES AND CLAIMS IN EXCESS OF  
THIS LIMITATION.  
INDEMNIFICATION AND COVENANT NOT TO SUE: YOU WILL INDEMNIFY, DEFEND AND HOLD HARMLESS WARRANTORS,  
THEIR OWNERS, DIRECTORS, OFFICERS, EMPLOYEES, AGENTS, SUPPLIERS OR AFFILIATED COMPANIES, AGAINST ANY  
AND ALL CLAIMS, DEMANDS OR ACTIONS BASED UPON ANY LOSSES, LIABILITIES, DAMAGES OR COSTS, INCLUDING BUT  
NOT LIMITED TO DAMAGES THAT ARE DIRECT OR INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL, AND INCLUDING  
ATTORNEYS FEES AND LEGAL COSTS, THAT MAY RESULT FROM THE INSTALLATION, OPERATION, USE OF, OR INABILITY TO  
USE WARRANTORS’ PRODUCTS AND SERVICES, OR FROM THE FAILURE OF THE WARRANTORS’ SYSTEM TO REPORT A GIVEN  
EVENT OR CONDITION, WHETHER OR NOT CAUSED BY WARRANTORS’ NEGLIGENCE.  
vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
YOU AGREE TO RELEASE, WAIVE, DISCHARGE AND COVENANT NOT TO SUE WARRANTORS, THEIR OWNERS, DIRECTORS,  
OFFICERS, EMPLOYEES, AGENTS, SUPPLIERS OR AFFILIATED COMPANIES, FOR ANY AND ALL LIABILITIES POTENTIALLY  
ARISING FROM ANY CLAIM, DEMAND OR ACTION BASED UPON ANY LOSSES, LIABILITIES, DAMAGES OR COSTS, INCLUDING  
BUT NOT LIMITED TO DAMAGES THAT ARE DIRECT OR INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL, AND INCLUDING  
ATTORNEYS FEES AND LEGAL COSTS, THAT MAY RESULT FROM THE INSTALLATION, OPERATION, USE OF, OR INABILITY TO  
USE WARRANTORS’ PRODUCTS AND SERVICES, OR FROM THE FAILURE OF THE WARRANTORS’ SYSTEM TO REPORT A GIVEN  
EVENT OR CONDITION, WHETHER OR NOT CAUSED BY WARRANTORS’ NEGLIGENCE, EXCEPT AS NECESSARY TO ENFORCE  
THE EXPRESS TERMS OF THIS LIMITED WARRANTY.  
EXCLUSIVE WARRANTY: THE LIMITED WARRANTY OR WARRANTIES DESCRIBED HEREIN CONSTITUTE THE SOLE WARRANTY  
OR WARRANTIES TO THE PURCHASER. ALL IMPLIED WARRANTIES ARE EXPRESSLY DISCLAIMED, INCLUDING: THE  
WARRANTY OF MERCHANTIBILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR USE AND THE WARRANTY OF  
FITNESS FOR A PARTICULAR PURPOSE AND THE WARRANTY OF NON-INFRINGEMENT AND/OR ANY WARRANTY ARISING  
FROM A COURSE OF DEALING, USAGE, OR TRADE PRACTICE.  
It must be clear that the Warrantors are not insuring your premises or business or guaranteeing that there will not be damage to  
your person or property or business if you use this Product. You should maintain insurance coverage sufficient to provide com-  
pensation for any loss, damage, or expense that may arise in connection with the use of products or services, even if caused by  
Warrantors’ negligence. The warrantors assume no liability for installation of the Product and/or interruptions of the service due  
to strikes, riots, floods, fire, and/or any cause beyond Seller’s control, further subject to the limitations expressed in any License  
Agreement or other Agreement provided by Warrantors to purchaser.  
The agreement between the Warrantors and the Purchaser, including but not limited to the terms and conditions herein shall not  
be governed by the Convention for the International Sale of Goods. Where applicable, the Uniform Commercial Code as adopted  
by the State of Delaware shall apply.  
4. RETURNS AND REPAIRS: No products or part thereof shall be returned to CPI unless the customer first obtains a Customer  
Return Authorization (CRA) number from a CPI customer service representative. This number must appear clearly and promi-  
nently on all shipping containers. Containers without the labels will not be accepted.  
Products returned for warranty repair shall be shipped prepaid to CPI. Said products are subject to handling charges if no defects  
are found during inspection. All products returned to CPI shall be packaged to prevent damage during shipment. Any damage  
that occurs during shipment is the responsibility of the customer and the shipping company. CPI will send back repaired products  
freight prepaid.  
If CPI finds that products returned for repair, whether in or out of warranty, have failed due to misuse or negligence or have com-  
ponents removed, CPI will repair the product in accordance with “out-of-warranty” charges. If CPI finds products, in or out of  
warranty, to be damaged beyond repair, the customer can choose to have the product sent back “as is” or scrapped by CPI.  
5. LEGAL REMEDIES AND DISCLAIMER: Some jurisdictions may not allow, or may place limits upon, the exclusion and/or  
limitation of implied warranties, incidental damages and/or consequential damages for some types of goods or products sold to  
consumers and/or the use of indemnification terms. Thus, the exclusions, indemnification terms and limitations set out above  
may not apply, or may be limited in their application, to you. If the implied warranties can not be excluded, and the applicable law  
permits limiting the duration of implied warranties, then the implied warranties herein are to be limited to the same duration as  
the applicable written warranty or warranties herein. The warranty or warranties herein may give you specific legal rights that will  
depend upon the applicable law. You may also have other legal rights depending upon the law in your jurisdiction.  
6. CHOICE OF FORUM AND CHOICE OF LAW: In the event that a dispute arises out of or in connection with this Limited  
Warranty, then any claims or suits of any kind concerning such disputes shall only and exclusively be brought in either the Court  
of Los Angeles County, California or the United States District Court in Los Angeles, California.  
Regardless of the place of contracting or performance, this Limited Warranty and all questions relating to its validity, interpretation,  
performance and enforcement shall be governed by and construed in accordance with the laws of the State of Delaware, without  
regard to the principles of conflicts of law.  
Effective date 01/10/2006  
Chatsworth Products, Inc.  
701 Industrial Drive  
New Bern, NC 28562  
800-834-4969  
Fax: 252-514-2977  
viii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Table of Contents  
ix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
x
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
xi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
xii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
xiii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
xiv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
xv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
xvi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
xvii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
Index  
xviii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1: Installation  
Chapter 1: Installation  
Introduction  
Congratulations on your purchase of the Chatsworth RIM-600 Remote Infrastructure Management  
System. This one-of-a-kind solution will change the way you think about computer room and  
network monitoring. The system is designed to be a comprehensive method of ensuring 100%  
up-time of your computer systems. By monitoring all aspects of your computer room, including  
environmental conditions and network equipment, the system will keep you informed of the status  
of your infrastructure. Monitored conditions can include temperature levels, humidity levels, line  
voltage, leak detection, server response, UPS systems, and more. The system allows the computer  
professional to be notified immediately of any detected problems. Notification can occur via  
voice telephone call, pager, e-mail, or fax. An internal battery backup system insures that the unit  
will continue to run if main power fails. The system also includes the ability to remotely perform  
diagnostic tests via Touch-Tone commands or e-mail. And with the RIM-600 PowerGate, you can  
also remotely reboot equipment.  
Features  
The RIM-600 series of products includes the following key features:  
n Expandable architecture permitting up to thirty-one RIM-600 Nodes to be used with each  
RIM-600 Host.  
n Eight sensor inputs per Host/Node to monitor environmental conditions and/or alarm contacts  
from other computer equipment such as UPS systems..  
n 10/100BASE-T Ethernet port for inter-operation with other RIM-600 equipment and network  
devices.  
n RS-232 serial port for local configuration.  
n Internal battery backup for uninterrupted performance.  
n Microphone for detecting audible alarms such as smoke detectors.  
n Compact design allows rack-mount, wall-mount, or tabletop installation.  
n ConsoleView software to program and manage your RIM-600 system.  
Technical Support  
If any questions arise upon installation or operation of the RIM-600, please contact the CPI  
Technical Service Department at 800.834.4969 and have the following information available:  
• Date of purchase __________________  
• Serial number  
__________________  
Technical support is available from 5:00 AM to 5:00 PM, Pacific Standard Time.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
About This Manual  
This manual comprises the instructions and commands necessary to install and program the RIM-  
600. Additional summary and application chapters are included to help you speed programming  
and to understand RIM-600s features. You should thoroughly read this manual to establish a basic  
understanding of the system and keep it as a reference.  
HOST INSTALLATION and CONFIGURATION  
Physical Description  
The RIM-600 Host is housed in a 17”w x 1.75”h x 10”d enclosure, which is 1 EIA rack-mount  
space high.  
Front Panel Layout  
The front panel contains connections for eight sensor inputs, microphone input, Ethernet port, serial  
port, and status LEDs. See figure below:  
Figure 1: Front Panel Layout of the RIM-600 Host  
1 Serial Port  
2 Ethernet port (10/100Base-T)  
3 Phone line  
4 Sensor Inputs (8)  
5 Battery Power Alarm LED  
6 AC Power Alarm LED  
7 External Microphone Input  
8 Internal Microphone  
Serial Port  
The RS-232 serial port is used to configure network settings. The port operates at 9600 baud, no  
parity, and 1 stop bit.  
RJ-45 10/100BASE-T Ethernet Port  
This jack is for connecting to your network so that the RIM-600 Host can communicate with the  
RIM-600 Nodes and ping selected network servers and/or services. Two LEDs indicate received  
data (green) and transmitted data (yellow).  
Phone Jack  
Connect the RIM-600s Phone jack to a standard 2-wire analog phone line. The unit dials using  
touch-tones, with loop start only. The RIM-600 will recognize ringer frequencies from 16 to 60 Hz  
and will operate with all standard analog telephone systems that accept tone dialing.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
Certain private telephone systems and public switching equipment may not accept the units dialing  
or may generate an unacceptable ring signal. In those cases, a dedicated line may be required for  
the unit. Consult the supplier of your telephone system if you encounter problems.  
CAUTION: Never install telephone wiring during a lightning storm. Never install telephone  
jacks in wet locations unless the jack is specifically designed for wet locations. Never touch  
uninsulated telephone wires or terminals unless the telephone line has been disconnected at the  
network interface. Use caution when installing or modifying telephone lines.  
Sensor Inputs  
The sensor inputs are designed to interface with RIM-600 series sensors (See Chapter 7). The use  
of RJ-45 jacks for sensor inputs allows the use of existing structured cabling to connect remote sen-  
sors.  
Since the sensor produces an analog signal, it must connect directly to the Host or Node. The path  
from the sensor to the RIM-600 unit CANNOT pass through a network Hub or Switch.  
Sensor Input LEDs  
Each sensor input has two LEDs (red and green) to indicate the present status of the input. The  
key below describes the multiple modes of operation.  
Mode 0: No sensor at input  
Green: OFF  
Red:  
OFF  
Mode 1: Sensor present—No alarms  
Green: ON  
Red:  
OFF  
Mode 2: Alarm detected but has not exceeded recognition time  
Green: FAST BLINK  
Red:  
FAST BLINK  
Mode 3: New alarm exists and not yet acknowledged  
Green: SLOW BLINK  
Red:  
SLOW BLINK  
Mode 4: Input is in normal range, but alarm is still unacknowledged  
Green: ON  
Red:  
SLOW BLINK  
Mode 5: Alarm has been acknowledged, but input is still out of range  
Green: SLOW BLINK  
Red:  
Mode 6: Sensor in trouble  
Green: QUICK FLASH  
ON  
Red:  
QUICK FLASH  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
AC Power and Battery LEDs  
The AC Power and Battery alarm status is indicated by two red LEDs. Their modes of operation  
are described below.  
Mode 1: No Alarm  
LED: OFF  
Mode 2: Alarm detected but has not exceeded recognition time  
LED: FAST BLINK  
Mode 3: New Alarm exists and not yet acknowledged  
LED: SLOW BLINK  
Mode 4: Alarm has been acknowledged but input is still out of range  
LED: ON  
Microphone Jack  
The Host unit comes with a built-in microphone. Directly below the built-in mic is a separate jack  
for connecting an optional condenser microphone to sense audible alarms, such as smoke detectors.  
When an external microphone is connected, the internal microphone is disabled.  
Rear Panel  
The rear panel is where the main power switch is located. The main power cord attaches to the  
IEC320 connector. The unit can be powered from 90–260VAC 47–63Hz.  
ON/OFF Switch  
The on/off switch connects main power and battery power to the system. Note that the system will  
only turn on when main power is present. When main power fails, the internal battery will auto-  
matically supply power to the unit.  
Figure 2: Rear Panel of the RIM-600 Host  
Installation  
This section provides information on:  
n Operating environment  
n Rack, wall, and tabletop installation  
n Connecting sensors  
Parts Required  
Phillips  
Screwdriver  
9 pin F/F null  
modem cable  
Dumb terminal or PC  
w/9 pin com port  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
Operating Environment  
Before you install the RIM-600 Host be sure that your operating environment meets the physical  
requirements of the equipment.  
Operating Temperature: 32º122º Fahrenheit (0º50º C)  
Humidity:  
5–90 %RH, non-condensing  
Power:  
90–260VAC 47/63 Hz outlet within 6'  
Rack Requirements:  
Standard 19" equipment rack with supplied mounting bracket  
hardware. Requires 1.0 EIA rack mount space.  
Tabletop requirements: Flat area which can support an enclosure 17" wide by 10" deep by 2"  
high.  
Rack Mount Installation  
The RIM-600 Host can be rack mounted using the included rack mount brackets. Follow the steps  
below:  
1) Attach rack-mount brackets to the sides of the Host unit with a Phillips screwdriver.  
2) Attach the unit to the equipment rack using two pan-head screws per side. Tighten the  
screws with a Phillips screwdriver.  
3) Plug the power cord into a 90-260VAC outlet.  
Figure 3: Rack-mounted Host Unit  
Wall Mount Installation  
The RIM-600 Host can be wall mounted using the optional wall mount brackets. Follow the steps  
below:  
1) Attach the optional wall mount brackets to the sides of the RIM-600 using the eight black  
#6-32 screws. A Phillips screwdriver will be required. (Order part # 60075-001 Universal  
Wall Mount Kit)  
2) Attach the unit to the wall using two screws per side. Tighten the screws with a Phillips  
screwdriver.  
3) Plug the power cord into a 90-260VAC outlet.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Figure 4: Wall-mounted Host Unit  
Tabletop Installation  
The RIM-600 Host can be installed on a tabletop or shelf. Follow the steps below:  
1) Attach the four self-adhesive rubber feet to the four corners on the bottom of the RIM-600.  
2) Place the unit on a tabletop or shelf and connect the power cord into a 90-260VAC outlet.  
Figure 5: Tabletop-mounted Host Unit  
Power On Self Test (POST)  
When the power switch is turned on, the red and green input LEDs will begin a blinking pattern to  
indicate that the unit is booting up and performing internal diagnostic tests. The unit will also beep  
once, 25 seconds after power is applied. When the LEDs stop blinking, the unit is fully booted and  
operational. The boot and Power On Self Test take approximately 2 minutes.  
Connecting Sensors  
The RIM-600 Host has eight sensor inputs. Each input can accept any sensor type. Sensors are  
available to monitor the following:  
n Temperature  
n Smoke  
n Security  
n Motion  
n Humidity  
n Water detection  
n AC voltage  
n Alarm contacts from external equipment  
All RIM-600 sensors connect to the Host using standard RJ-45 cables. This makes it easy to con-  
nect sensors directly to the unit. Simply plug one end of the cable into the sensor and the other end  
into one of the sensor inputs on the Host.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
Another benefit of using RJ-45 connectors is that you can easily locate sensors at distant locations  
within your facility by using your existing structured cabling. For example: Suppose you have an  
RIM-600 installed in room A and you want to install a sensor in room B. If your existing cabling  
infrastructure has an unused cable path between room A and room B, then you simply use an RJ-45  
interconnect cable to connect the RIM-600 to the patch panel in room A, and an RJ-45 interconnect  
cable from the wall jack in room B to the sensor.  
CAUTION: The sensor produces an analog signal which must connect directly to the Host or  
Node. The path from the sensor to the RIM-600 unit CANNOT pass through a network Hub or  
Switch.  
Network Configuration  
The RIM-600 Host has a serial port on the front panel which is used to configure network settings  
and security options. A dumb terminal or terminal emulation software is required to get online  
and set up the configuration. The port is male DTE, so you will need to use a null modem cable.  
Terminal communication settings must be set to:  
n 9600 baud, no parity, 8 data bits, 1 stop bit  
To get online with the RIM-600, connect your terminal to the serial port and press <RETURN>. A  
menu will appear which will guide you through the setup.  
RIM-600 Host Unit V1.0.0.0  
Enter Password ()>  
{The DEFAULT PASSWORD for a New Unit is “rim600”}  
1. Display Enterprise status  
2. Display Network and Option configuration  
3. Configure Network settings  
4. Configure Enterprise Name  
5. Configure Web Server  
6. Configure Remote Access Server  
7. Enable Two-Way E-mail Responder  
8. Enable Microphone Listen-In  
9. Enable default Master Administrator Account (temporarily)  
0. Enable data modem  
A. Configure SNMP  
B. Change Admin Password  
C. Reset To Factory Defaults  
D. Display Statistics  
E. Reboot  
F. Logout  
Enter option->  
If you select Option 1 you will see the IP address and status of the Host and all associated nodes.  
A sample is shown below:  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Enterprise Status  
Unit  
Type IP  
Status  
Ok  
RIM-600 Monitor  
NY_Node  
Host 10.1.4.10  
Node 10.1.4.17  
Ok  
Press any key to return to main menu  
Option 2 will display the network configuration for the Host as well as web server, RAS, and two-  
way email settings. A sample of Option 2 is shown below:  
Network and Option Configuration  
Physical Address  
IP Address  
00:D0:C9:37:40:86  
10.1.4.10  
255.255.255.0  
10.1.4.1  
10.1.2.111  
RIM-600 Enterprise  
Enabled  
Subnet Mask  
Default Gateway  
DNS Server  
Enterprise name  
Web Server  
Web Server Security  
Web Programming Option  
Web Programming Security  
Remote Access Server  
RAS IP Port Address  
Two-Way E-mail Responder  
Microphone Listen-in  
Datamodem  
Enabled  
Enabled  
Enabled  
Enabled  
0.0.0.0  
Enabled  
Enabled  
Enabled  
SNMP RO community  
SNMP RW community  
SNMP Agent  
public  
private  
Enabled  
Allow remote configuration Disabled  
Press any key to return to main menu  
Option 3 will allow you to set all pertinent network settings listed under Option 2.  
NOTE: You can remotely reconfigure the Host network settings using the RIM-600  
ConsoleView software if the Allow Remote Configuration option is set to Y. However, the Host  
must initially be configured via the serial port before any remote configuration is possible.  
Option 4 allows you to configure or reconfigure the Enterprise name.  
Option 5 allows you to configure the Web server. When Web security is enabled, a Profile  
Username & Password must be entered to view the web page. A sample of the Web configuration  
menu is shown below:  
Configure Web Server  
1. Enable Web Server: Y/N  
2. Enable Web Status Security: Y/N  
3. Enable Web Programming option: Y/N  
4. Enable Web Programming Security: Y/N  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1: Installation  
5. Return to main menu  
Option 6 allows you to configure the RAS (Remote Access Server). This can be used to provide  
remote access to your network via a dial-up connection to the RIM-600 Host. Note that there are  
serious security risks associated with enabling this feature. A sample of the RAS menu is shown  
below:  
Configure Remote Access Server  
1. Enable/Disable RAS Support  
2. RAS IP address  
3. Return to main menu  
Enter option->  
Option 7 allows you to Enable or Disable the two-way email feature.  
Option 8 allows you to monitor on-site sound through either the built-in or an external microphone.  
Option 9 (Enable default Master Administrator Account (temporarily) should only be used in the  
event that no Master Administrator accounts can be accessed (e.g. the password(s) were forgotten).  
Enabling this feature will temporarily load the default Master Administrator account (username:  
admin, password: rim600). This temporary account will unload if any one of the following occurs:  
(1) Any of the Master Administrator accounts is edited, (2) A new Master Administrator account is  
created, or (3) The system reboots.  
Option 0 allows you to disable all inbound modem communications. This feature is provided for  
users who cannot have a device with a modem connected to their network.  
Option A allows you to program the SNMP Read-Only and Read-Write community strings.  
Configure SNMP  
1. Read-Only community string  
2. Read-Write community string  
3. Enable SNMP Agent  
4. Return to main menu  
Enter option ->  
Press ENTER to accept new setting or ESC to cancel  
Enter SNMP Read-Only community string (public) >  
Configure SNMP  
1. Read-Only community string  
2. Read-Write community string  
3. Enable SNMP Agent  
4. Return to main menuEnter option ->  
Press ENTER to accept new setting or ESC to cancel  
Enter SNMP Read=Write community string (private) >  
Configure SNMP  
1. Read-Only community string  
2. Read-Write community string  
3. Enable SNMP Agent  
4. Return to main menu  
Enter option ->  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
Option B allows you to change the Local Configuration password.  
Option C allows you to reset all settings to their default values.  
Option D will display statistics.  
Option E will save all changes and reboot the system. A reboot is required for changes to take  
effect.  
Option F will save all changes and logout, but the changes will not be activated until the system  
reboots.  
Local Configuration Definitions  
Password: This is the password which protects access to the local configuration parameters.  
The default password in a new unit is “rim600.”  
IP: This is the IP address assigned to the RIM-600 on your network. This address is provided by  
you or your network administrator. It is formatted as a standard dotted decimal number.  
Mask: This is the subnet mask which distinguishes the portion of the IP address that is the  
network ID from the portion that is the station ID.  
Gateway: A TCP/IP network must have a gateway to communicate beyond the LAN identified  
by the network ID. A gateway is a computer or router that is connected to two different  
networks and can move TCP/IP data from one to the other. If your TCP/IP network has more  
than one LAN or if you are connecting to the Internet, you will need to know the IP address  
of the gateway that will transfer TCP/IP data in and out of your LAN. A single LAN that is  
not connected to other LANs does not require a gateway setting.  
DNS: The DNS server is used to translate site names into actual numeric network addresses.  
Enter the IP address of the DNS server for your network.  
Enable Web: Setting this to “Y” will enable the web page feature of the RIM-600. Set this to  
"N" if you do not want the unit to produce a web page.  
Enable Web Password: Setting this to “Y” will require a valid user-name and password to be  
entered in order to view the web page.  
Enable RAS: Setting this to “Y” will enable Remote Network Access during a dial-up  
connection.  
RAS IP: This is the IP address assigned to the remote computer calling in to the host.  
Enable 2-Way E-mail: Setting this to “Y” will enable the 2-way email feature. With this  
feature enabled you can send commands to the RIM-600 via e-mail and receive responses  
back. Set this to "N" to disable this feature.  
Enterprise Name: The Enterprise name will appear at the top level of the RIM-600  
ConsoleView software whenever a user logs in to an RIM-600 Host. It provides identification  
consistency among multiple users and allows for future Enterprise features.  
Enable Microphone Listen-In: Enabling this feature will allow users to listen in through the  
microphone on the front panel of the unit when dialing the unit in Voice mode. Disabling this  
feature will prevent the microphone from being accessed during a telephone call.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
Battery Maintenance  
The RIM-600 Host includes an internal UPS that automatically switches to battery backup in the  
event of an AC power failure. The battery in the RIM-600 Host is a 12V 2.9AH gel cell. This bat-  
tery will keep the unit operating for approximately 3.5 hours when fully charged and under normal  
operating conditions.  
Service life  
Over time and with periodic use, the battery will begin to lose its capacity, resulting in less overall  
backup time. Under normal operating conditions, three or four years of dependable service life can  
be expected or between 200 and 1000 charge/discharge cycles, depending on the average depth  
of discharge. Eventually, battery replacement will be required to maintain a dependable level of  
service.  
Replacing the Battery  
The battery in the Host can be replaced by following the instructions listed below. Be sure to read  
all safety messages and follow the instructions in order as listed. Several tools will be required to  
change the battery:  
• small flathead screwdriver  
• needle-nose pliers  
14" nut driver  
CAUTION: REPLACE BATTERY ONLY WITH A 12V 2.9AH GEL CELL BATTERY.  
WARNING: DISCONNECT THE AC POWER CORD FROM THE BACK OF THE UNIT.  
THERE IS A RISK OF ELECTRICAL SHOCK UNLESS YOU  
DISCONNECT THE CORD.  
Figure 6: Battery location  
Step 1)  
Step 2)  
Step 3)  
Step 4)  
Locate the power switch on the rear of the unit and turn the RIM-600 off.  
Disconnect the power cord from the back of the unit.  
Disconnect the phone line from the front of the unit.  
Remove the RIM-600 from the rack.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Step 5)  
Step 6)  
Remove all of the screws in the top cover. Carefully remove the top cover.  
Locate the battery on the right side. There will be a red wire (positive)  
and a black wire (negative) connected to the battery. Using needle nose pliers,  
remove the connector with the black wire from the battery first. Gently wiggle it off.  
Step 7)  
Step 8)  
Using needle nose pliers, remove the connector with the red wire from the battery.  
Using the nut driver, remove the four nuts which hold down the battery bracket.  
Remove the bracket and battery.  
Step 9)  
Install the new battery and replace the bracket.  
Step 10) Attach the connector with the red wire to the positive terminal of the battery.  
Step 11) Attach the connector with the black wire to the negative terminal of the battery.  
Step 12) Replace the top RIM-600 cover and secure with the screws.  
Step 13) Re-install in rack.  
Step 14) Re-attach the power cord.  
Step 15) Re-connect the phone line.  
Step 16) Turn the Power Switch back on.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1: Installation  
Host Specifications  
RIM-600 Host Specifications  
Operating Specifications  
Temperature 32–122° F  
Humidity 5–90% RH non-condensing  
Power Supply 90–260VAC 47–63Hz  
Power Consumption (typ) 25 Watts  
Power Connection IEC 320  
Dimensions 1.75"h x 9.5"d x 19"w  
Backup Battery 12V 2.9AH Sealed Gel Cell  
Backup Time 3.5 Hours  
Communications Specifications  
Ethernet 10/100 Base-T, 10/100Mbps  
RS-232 DB9, 9600bps, DTE  
Modem 33.6Kbps  
Fax Group 3, 14.4Kbps  
Voice Processor Yes  
Environmental Monitoring  
AC Power (True RMS Voltage, Backup  
Battery Level, Sound Level (in dB)  
Internal Monitoring  
Number of Sensor Ports 8  
Temperature, Humidity, Water, Power,  
Infrared Motion, Smoke, Dry Contacts  
Sensor Types  
Sensor Input Connector RJ-45  
Sensor Cables CAT-5, 568B  
Cable Length 1000'  
Visual Indicators LEDs, Normal and Alarm  
External Microphone 3.5mm jack, electret condenser  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
NODE INSTALLATION & CONFIGURATION  
Physical Description  
The RIM-600 Node is housed in a 9.6"w x 1.75"h x 7"d enclosure, which is 1 EIA rack-mount  
space high.  
Front Panel Layout  
The front panel contains connections for eight sensor inputs, microphone input, Ethernet port, serial  
port, and power LED. See figure below:  
Figure 7: Front Panel Layout of the RIM-600 Node  
1 Sensor Inputs  
2 Microphone Jack  
3 Internal Microphone  
4 Ethernet Port (10/100BASE-T)  
5 Serial Port  
6 Power Switch  
7 Power LED  
Sensor Inputs  
The sensor inputs are designed to interface with RIM-600 series sensors (See Chapter 7). The use  
of RJ-45 jacks for sensor inputs allows the use of existing structured cabling to connect remote sen-  
sors.  
Microphone  
The Node unit comes with a built-in microphone. Directly below the built-in mic is a separate jack  
for connecting an optional condenser microphone to sense audible alarms, such as smoke detectors.  
When an external microphone is connected, the internal microphone is disabled.  
RJ-45 10/100BASE-T Ethernet Port  
This jack is for connecting to your network so that the RIM-600 Node can communicate with the  
RIM-600 Host and ping selected network servers and/or services. Two LEDs indicate Link Status  
(left) and Receive Date status (right).  
Serial Port  
The RS-232 serial port is used to configure network settings. The port is DB9 male DTE and oper-  
ates at 9600 baud, no parity, and 1 stop bit. A DB9 female–female null modem cable is required to  
configure network settings.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
ON/OFF Switch  
The on/off switch connects main power and battery power to the system. In the event that main  
power fails, the backup battery system will automatically power the system.  
Rear Panel  
The rear panel is where the main power cord exits the unit. A 120VAC/60Hz to 8VAC adapter pro-  
vides main power to the unit.  
Battery Compartment  
The battery compartment is located below the top panel. The unit requires (1) 6V 3.4AH  
rechargeable battery (included). To remove or replace the battery, remove the top cover with a small  
flat-head screwdriver.  
Installation  
This section provides information on:  
n Operating environment  
n Rack, wall, & tabletop installation  
n Connecting sensors  
n Replacing the battery  
Parts Required  
Phillips  
Screwdriver  
DB9 F/F null  
modem cable  
Dumb terminal or PC  
w/DB9 serial port  
Operating Environment  
Before you install the RIM-600 Node be sure that your operating environment meets the physical  
requirements of the equipment.  
Operating Temperature: 32º122º Fahrenheit (0º50º C)  
Humidity:  
5–90 %RH, non-condensing  
120VAC 60 Hz outlet within 6'  
Power:  
Rack Requirements:  
Standard 19" equipment rack with supplied mounting bracket  
hardware. Requires 1.0 EIA rack mount space.  
Tabletop requirements: Flat area which can support an enclosure 10" wide by 8" deep by  
2" high.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Battery Replacement  
The RIM-600 Node uses one (1) 6V 3.4AH rechargeable battery (included) for backup power in  
the event that main power fails. The unit will constantly recharge the battery whenever the power  
switch is turned on and the unit is plugged into a power supply.  
In the event you need to replace the battery, contact technical support for part number information.  
To install the new battery, first slide the power switch to the OFF position and disconnect the power  
adapter. Next, remove the top cover of the unit by removing the six screws using a small flat-head  
screwdriver. Remove the wire connectors from the old battery and replace it with the new one.  
Reconnect the wires to the new battery and reattach the top cover.  
Figure 8: Battery replacement in the Node unit  
Rack Mount Installation  
The RIM-600 Node can be rack mounted using the included rack mount brackets. Follow the steps  
below:  
1) Attach rack-mount brackets to the Node with a Phillips screwdriver.  
2) Attach the unit to the equipment rack using two pan-head screws per side. Tighten the  
screws with a Phillips screwdriver.  
3) Plug the power adapter into a power outlet.  
Figure 9: Rack-mounted Node Unit  
Wall Mount Installation  
The RIM-600 Node can be wall mounted using the optional wall mount brackets. Follow the steps  
below:  
1) Attach the optional wall mount brackets to the sides of the RIM-600 using the eight black #6-  
32 screws. A Phillips screwdriver will be required. (Order part # 60075-001 Universal Wall  
Mount Kit)  
2) Attach the unit to the wall using two screws per side. Tighten the screws with a Phillips  
screwdriver.  
3) Plug the power cord into a 120VAC 60Hz outlet.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
NOTE: An international version is available for 220V/50Hz operation. (Order part # 60001-002.)  
Figure 10: Wall-mounted Node Unit  
Tabletop Installation  
The RIM-600 Node can be installed on a tabletop or shelf. Follow the steps below:  
1) Attach the four self-adhesive rubber feet to the four corners on the bottom of the RIM-600.  
2) Place the unit on a tabletop or shelf and connect the power cord into a 120VAC 60Hz outlet.  
Figure 11: Tabletop-mounted Node Unit  
Connecting Sensors  
The RIM-600 Node has eight sensor inputs. Each input can accept any sensor type. Sensors are  
available to monitor the following:  
n Temperature  
n Smoke  
n Security  
n Motion  
n Humidity  
n Water detection  
n AC voltage  
n Alarm contacts from external equipment  
All RIM-600 sensors connect to the Node using standard RJ-45 cables. This makes it easy to con-  
nect sensors directly to the unit. Simply plug one end of the cable into the sensor and the other end  
into one of the sensor inputs on the Node.  
Another benefit of using RJ-45 connectors is that you can easily locate sensors at distant locations  
within your facility by using your existing structured cabling. For example: Suppose you have an  
RIM-600 Node installed in room A and you want to install a sensor in room B. If your existing  
cabling infrastructure has an unused cable path between room A and room B, then you simply use  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
an RJ-45 interconnect cable to connect the RIM-600 Node to the patch panel in room A, and an RJ-  
45 interconnect cable from the wall jack in room B to the sensor.  
The sensor produces an analog signal which must connect directly to the Host or Node.  
The path from the sensor to the RIM-600 unit CANNOT pass through a network Hub or  
Switch.  
Network Configuration  
The RIM-600 Node has a serial port on the front panel which is used to configure network settings  
and security options. A dumb terminal or terminal emulation software is required to get online and  
set up the configuration. The port is male DTE, so a DB9 female–female null modem cable will be  
required. Terminal communication settings must be set to:  
n 9600 baud, no parity, 8 data bits, 1 stop bit, no flow control  
To get online with the RIM-600 Node, connect your terminal to the serial port and press  
<RETURN>. A menu will appear which will guide you through the setup.  
RIM-600 Node Unit  
Main Menu  
Version: 4.10  
1. Display Network configuration  
2. Configure Network settings  
3. Display system statistics  
4. Reset to factory defaults  
5. Network Debug  
6. Reboot  
7. Logout  
Enter option->  
To display the present Network Configuration settings select Option 1. To program the Network  
settings select Option 2. Note that the Node must have network visibility of the Host for the  
RIM-600 system to function properly. For Network changes to take effect you must reboot the unit  
(option 5). A typical sample is shown below:  
Network Configuration  
Physical Address  
00:07:F9:00:10:18  
Parent Host IP address 10.1.2.47  
Node IP Address  
Subnet Mask  
Default Gateway  
DNS Server  
10.1.4.17  
255.255.255.0  
10.1.4.1  
10.1.2.111  
Node name  
48th Floor Chicago  
Allow remote configuration N  
Press any key to return to main menu  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 1: Installation  
NOTE: You can remotely reconfigure the Node network settings using the RIM-600  
ConsoleView software if the Allow Remote Configuration option is set to Y. However, the Node  
must initially be configured via the serial port before any remote configuration is possible.  
Option 3 will display operating statistics of the Node. This information may be useful for  
troubleshooting. A sample is shown below:  
Statistics  
Running (hrs)  
Ram free (KB)  
IP alarms  
Pkt rcvs  
Pkt errs  
Clock timeouts  
Socket errors  
Avg Pkt RTT (ms)  
DSP proc starts  
0
7136  
0
24  
0
0
0
20  
1
Disk free (KB)  
Error mask  
Input alarms  
Pkt xmts  
Ack timeouts  
Socket closes  
Socket connects  
Input Prog timeout  
IP proc starts  
209  
0
0
4
0
0
1
0
1
Press any key to return to main menu  
Option 4 will reset the Node to factory default settings. All programming and network settings will  
be deleted.  
Option 5 will reboot the system. You must reboot for new Network settings to take effect.  
Option 6 will logout without rebooting.  
Local Configuration Definitions  
Parent Host IP Address: This is the IP address of the RIM-600 Host that this Node is  
associated with.  
Node IP Address: This is the IP address assigned to the RIM-600 on your network. This  
address is provided by you or your network administrator. It is formatted as a standard dotted  
decimal number.  
Subnet Mask: This is the subnet mask which distinguishes the portion of the IP address that is  
the network ID from the portion that is the station ID.  
Default Gateway: A TCP/IP network must have a gateway to communicate beyond the LAN  
identified by the network ID. A gateway is a computer or router that is connected to two  
different networks and can move TCP/IP data from one to the other. If your TCP/IP network  
has more than one LAN or if you are connecting to the Internet, you will need to know the IP  
address of the gateway that will transfer TCP/IP data in and out of your LAN. A single LAN  
that is not connected to other LANs does not require a gateway setting.  
DNS Server: The DNS server is used to translate site names into actual numeric network  
addresses. Enter the IP address of the DNS server for your network.  
Node Name: This name will appear in the RIM-600 ConsoleView Software. In systems with  
many Nodes, the Name is useful for identifying one node from another.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Node Specifications  
Operating Specifications  
Temperature 32–122° F  
Humidity 5–90% RH non-condensing  
Power Supply 120VAC 60Hz  
Power Consumption 10 Watts  
Dimensions 1.8"h x 7.0"d x 9.6"w  
(1) 6V 3.4AH sealed rechargeable  
Backup Battery  
Backup Time 3.5 Hours  
Communications Specifications  
Environmental Monitoring  
Ethernet 10/100 Base-T, 10/100Mbps  
RS-232 DB9, 9600bps, DTE  
AC Power, Backup Battery Level, Sound  
Level (in dB)  
Internal Monitoring  
Number of Sensor Ports 8  
Temperature, Humidity, Water, Power,  
Infrared Motion, Smoke, Dry Contacts  
Sensor Types  
Sensor Input Connector RJ-45  
Sensor Cables CAT-5, 568B  
Cable Length 1000'  
External Microphone 3.5mm jack, electret condenser  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Chapter 2: RIM-600 Software  
Introduction  
This chapter is designed to help you program and use the RIM-600 to its fullest potential. The  
RIM-600 system helps you maintain, monitor, expedite and control the things that affect your  
information infrastructure.  
Help  
The RIM-600 ConsoleView Software provides an extensive Help system to supplement the  
documentation. Use RIM-600 Help to access information about commands and dialog boxes.  
Online help is also available simply by selecting Help from the main menu.  
RIM-600 Quick Start Guide  
This section presents a useful shorthand guide to configuring your RIM-600 System for the first  
time. More detailed information on the processes covered can be found in the sections that follow.  
Install Units and Configure Network Settings  
Install the RIM-600 Host and Node(s). Configure the Network settings through the serial port on  
the front of the units. A terminal or terminal-emulation program can be used. Set the terminal set-  
tings for 9600bps (8, N, 1). The default password is “rim600.”  
Install Software and Log In to Host  
Install the RIM-600 software from your CD-ROM or other media. Double-click on the RIM-600  
icon on your desktop. The RIM-600 ConsoleView screen will appear. From the main menu select  
Enterprise, then Add Enterprise Group. See below:  
Figure 1: Add Group  
Right-click on the words IP Unknown below the enterprise name and select Set IP Address. Enter  
the IP address for your RIM-600 Host and click OK. The software will prompt you for a username  
and password to log in.  
Default Username and Password  
For new units, the default username is admin and the default password is rim600. The software  
will now attempt to connect to your RIM-600 Host. A progress bar will show the software retriev-  
ing information from the Host.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Note: Do not save the default username and password, because it will be deleted automatically  
once a Master System Administrator profile is configured.  
Configure the Unit Properties for the Host and Node(s)  
Right-click on the word Host and select Unit Properties. Step through each tabbed page and enter  
the relevant information for your application. The Numeric Unit ID should be set to the Host's tele-  
phone number. Most Alphanumeric pagers work best when set to 1200bps.  
The Host can synchronize its clock each night to a time server. To use this feature the RIM-600  
must have network access to a server which supports one of the following: Network Time Protocol -  
NTP (RFC-1035), Time Protocol - TP (RFC-868), or Daytime Protocol - DP (RFC-867). Enter the  
IP Address of a Time Server which supports any one of these protocols.  
Expand the menus below the Host by clicking the plus sign next to the word Host. Any nodes asso-  
ciated with the Host should appear. Right-click on the Node names and select Node Properties.  
Configure the Node Properties for each Node.  
Configure Input Templates  
Environmental input programming Templates are used to load user specified defaults each time  
a new sensor is connected to a Host or Node. By properly configuring the Templates before you  
plug in your sensors, you can minimize the amount of programming required to set up your sen-  
sors. To configure the Templates, click the plus box next to the word Settings to expand the options  
under this heading. Next, expand the Input Templates. This will list all of the different sensor types.  
Right-click on each of the sensor names to bring up the individual Template programming screens.  
An example is shown below:  
Figure 2: Default Input Channel Settings  
Connect Environmental Sensors to Host and Node(s)  
Once you've configured the Input Templates, connect your sensors. This will automatically load the  
template programming for each sensor. All sensors connect to the Host and Node via RJ45 con-  
nectors. This allows you to use your existing structured cabling for wiring sensors throughout your  
infrastructure.  
Note: RIM-600 sensors are not IP devices and cannot connect to Hubs or switches.  
After connecting your sensors, customize the input alarm parameters for each sensor.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Configure User Profiles and Contacts  
Program the User Profiles and Contacts to control who has access to the RIM-600 and who gets  
contacted when an alarm occurs. Each user must have a Username, Password, and User Code.  
Right-click on Profiles and select Add New Profile. Enter information for each user. Click the  
Permissions button and be sure to set up at least one Master System Administrator account. To set  
up alarm contact information, right-click on the profile name and select Add New Contact. You can  
have up to eight contacts per user. The User Profile screen is shown below:  
Figure 3: User Profile  
Configure IP Alarms  
Program the IP addresses for each network device you want to monitor. Expand the Host menu by  
clicking the plus sign next to the name of your host. Next, right-click on IP Alarms and select Add  
New IP Alarm. Enter the information to configure the network device you wish to monitor. Be  
sure to enable the alarm. The RIM-600 unit will ping/connect to the IP address and port you select  
about once per minute. The IP Alarm programming screen is shown below:  
Figure 4: IP Alarm Setup screen  
Record and Assign Voice Messages  
Custom voice messages can be used to identify your RIM-600 Hosts/Nodes, PowerGates, Input  
sensors, IP alarms, and PowerGate outlets. Voice messages must first be recorded on your com-  
puter and then uploaded to the RIM-600 Host. Use the CustomVoice Manager screen to record and  
upload your voice messages. To access the CustomVoice Manager screen, expand the Host menu  
and select Voice. Note that Voice messages should be recorded at 8Khz, 8bit, mono, to keep the  
file size small. See the detailed section on Recording and Uploading Voice Messages later in the  
manual for more information. Voice messages are assigned to elements of your RIM-600 unit on  
the respective screens as listed below:  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
RIM-600 Host Identification message - Host Unit Properties Screen  
RIM-600 Node Identification message - Node Unit Properties Screen  
Input Sensor message  
IP Alarms message  
PowerGate messages  
- Input Channel Setup Screen  
- IP Alarm Setup Screen  
- PowerGate Setup Screen  
Software Installation and Hardware Requirements  
This section describes how to install and configure the RIM-600 ConsoleView Software for your  
enterprise.  
Hardware and Software Requirements  
Minimum Requirements:  
Intel Pentium processor or equivalent  
30 MB of free disk space  
32 MB of RAM (64 MB RAM recommended)  
Graphics card and monitor compatible with Microsoft Windows® 95, 98, NT, 2000, or XP  
Microsoft Windows® 95, 98, NT, 2000, or XP  
Mouse  
Soundblaster-compatible sound card, microphone and speakers  
Windows-compatible phone modem and/or RS-232 ports  
Software Installation  
The RIM-600 ConsoleView Software setup program makes installation quick and easy. Make sure  
that all Windows applications are closed before attempting to run setup.  
If you encounter problems during installation, please call CPI Technical Support at 800.834.4969.  
Installing from the CD  
1. Start Windows.  
2. Insert RIM-600 CD-ROM  
3. Select Start>Run and type in D:\Setup.exe and click OK.  
Note: If your CD-ROM is installed on a drive letter other than D, substitute the appropriate  
letter.  
4. Follow the prompts until the installation is finished.  
The RIM-600 ConsoleView Software for Windows will install to a directory named C:\Program  
Files\RIM600, unless you choose to change the directory name. The installation program will give  
you three installation choices: Typical, Compact, or Custom. For new installations choose Typical.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Figure 5: Installation screen  
Starting the RIM-600 ConsoleView Software  
Double-click the RIM-600 icon to start the RIM-600 ConsoleView Software. The software will  
automatically try to connect to all RIM-600 Hosts that have been configured. If this is the first time  
you are running the software, you will need to create an Enterprise Group and add a Host within  
each Enterprise. (See Configuring Hosts and Nodes)  
Configuring Hosts and Nodes  
Setting Up An Enterprise  
An Enterprise Group comprises a RIM-600 Host, any RIM-600 Nodes connected to that Host, and  
all of the environmental inputs connected to these units, regardless of proximity to the Host.  
Note: Before setting up your Enterprise software, you must have locally configured your Host  
and Node units—which is where you assign the Host its IP address. If you have not done this,  
the ConsoleView software will not be able to locate your Host. If you are connecting to your  
Host through a dialup connection, be sure to establish a PPP connection before running the  
software. (See Remote Login via Dialup) See the sections in your Host and Node Manuals on  
Local Configuration.  
To get started, double-click on the RIM-600 software icon. This will bring up the RIM-  
600 ConsoleView Screen.  
Figure 6: RIM-600 ConsoleView screen  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Adding an Enterprise Group  
From the ConsoleView menu, click on Enterprise and select Add Enterprise Group. In the left-hand  
column, a New Enterprise Group will appear. When you connect to the host, the Enterprise Name  
will update.  
Deleting an Enterprise Group  
If at any time you wish to delete an Enterprise group, click to highlight the Enterprise Group you  
would like to delete, select Enterprise from the main menu and choose Delete Enterprise Group.  
Adding a Host  
Right-click on the words IP Unknown below the enterprise name and select Set IP Address. Enter  
the IP address for your RIM-600 Host and click OK. The software will prompt you for a username  
and password to log in. For new units, the default username is admin and the default password is  
rim600. The software will now attempt to connect to your RIM-600 Host. A progress bar will show  
the software retrieving information from the Host.  
Default Username: admin  
Default Password: rim600  
Note: Do not save the default username and password, because it will be deleted  
automatically once a Master System Administrator profile is configured.  
Figure 7: Entering the Host address  
To see the programming, inputs, and accessories associated with the host, click in the box beside  
your enterprise group. The tree hierarchy will appear beneath the Host.  
Figure 8: Host Tree  
Connecting to a Host  
If you have a Host set up already, you can connect to it in one of two ways: Either right-click on  
the Host and select Connect from the dropdown menu, or double-click on the Host in the hierarchy.  
Both methods will bring up the prompt form where you type in your username and password to  
connect to the Host.  
Deleting a Host  
To delete a Host, right-click on the Host you would like to delete and select Delete Host from the  
contextual menu.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Setting the Unit Properties for the RIM-600 Host  
To set the global properties of your RIM-600, right-click on the Host name and select Unit  
Properties. On the System Info tab, enter the Unit Name, Description and Location. These param-  
eters will be used when sending alarms to identify the unit. Check the Auto-Connect on Startup  
box if you want the RIM-600 software to connect automatically with the unit at startup. See Figure  
below.  
Figure 9: System Info tab  
Next, select the Phone Settings tab. Enter the telephone number of the Host in the Numeric Unit  
ID field. The Numeric Unit ID will appear on alarm messages delivered to numeric pagers and fax  
machines.  
Figure 10: Phone Settings tab  
Select a custom voice message to identify your Host by clicking the arrow in the Custom Voice field  
and selecting a voice file. Custom voice messages can be recorded and uploaded to the Host on the  
Custom Voice Manager screen. The Host Custom Voice message is the first message spoken during  
a voice call. This message should describe the name and location where the Host is installed.  
Enter the number of Dialout Attempts you want the RIM-600 to make when an alarm occurs.  
Dialout attempts is the number of times the RIM-600 will try to call each contact.  
Select the Alphanumeric Pager speed (Alpha Page Speed) for your paging provider. Typically, 1200  
bps will work fine with most pagers.  
If your phone system does not produce a dial tone when you first lift the receiver, uncheck the box  
marked “Check for dial tone.”  
Set the “Rings until Answer” number. This will determine how many times the line must ring  
before the RIM-600 will answer.  
Set the “Intercall Delay. This is the time the unit waits between outgoing phone calls. During this  
period the unit will answer any incoming calls. To acknowledge an alarm via callback you must set  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
this value to at least 1 minute. When set to 0 the unit will dial back-to-back calls without the pos-  
siblity of calling in to acknowledge an alarm. The Intercall Delay can be set from 0–60 minutes.  
Test Dial Tone: The RIM-600 can be programmed to test periodically for dialtone to ensure that the  
telephone line is alive in the event that the unit has to dial out for an alarm. If the unit determines  
that a dialtone is not present, it will send a diagnostic alarm via e-mail and/or SNMP to profiles  
that are set up to receive diagnostic alarms (i.e. diagnostic class). Check to enable, then enter the  
test interval, in hours, in the every X hours box.  
Finally, select the Clock Settings tab. To set the time in the RIM-600 Host, click the button labeled  
Set to Current PC Time. Next, select the Hosts Time Zone according to its location. If you would  
like the unit to synchronize its time on a daily basis, enter the IP address of a compatible time serv-  
er.  
Figure 11: Clock settings tab  
The RIM-600 can be programmed to synchronize its clock to a reference time server every night  
at midnight. To use this feature the RIM-600 must have network access to a server which supports  
one of the following time code protocols:  
Network Time Protocol - NTP (RFC-1035)  
Time Protocol - TP (RFC-868)  
Daytime Protocol - DP (RFC-867)  
Click the Clock Settings tab. Enter the name or IP address of the time server in the Synchronize  
Clock field. To disable this feature, delete the name or IP address.  
Note: After setting the time zone, you must reboot for the new settings to take effect.  
Adding a Node  
Once the node has been connected to the network and the Local Configuration has been performed,  
it will automatically start communicating with the Host. From the RIM-600 Consoleview the Node  
will appear within the tree. See figure below.  
Figure 12: Structure tree with Node  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
The Node name will appear in green when host-to-node communications are working properly.  
If a communications problem occurs, the node name will initially turn yellow, to indicate that  
pending node trouble exists. If the problem persists for several minutes, the node name will turn  
red and a trouble alarm will be dispatched to Users who are members of the diagnostic class.  
Deleting a Node  
To delete a Node, right-click on the Node name in the tree and select Delete This Node.  
Changing Host Network Settings using ConsoleView  
You can remotely change the Host network settings using the ConsoleView software if the Allow  
Remote Configuration option is set in the Local Configuration options. However, before doing so  
consider the following:  
If you have any Nodes associated with the Host, they will stop communicating with Host if you  
change the IP address. So be sure to change the parent Host IP Address in the NODE before  
actually changing it in the Host itself.  
To change the network settings in the Host using ConsoleView, right-click on the unit name and  
select Network Settings. The first tab is titled Ethernet Settings, click the Modify button to bring up  
the Network Setup screen.  
Figure 13: Host Network Settings  
NOTE: If the Modify button is grey (inactive) then the unit either does not have the Allow  
Remote Configuration option set, or the units firmware does not support this feature and  
requires upgrading.  
Enter the new network parameters and click OK. A warning message will appear telling you that  
the unit must reboot. Click OK to proceed with the change. You will be disconnected while the unit  
reboots. If you changed the Hosts IP address, it will automatically change in ConsoleView as well,  
so that the software will connect to your host using the new IP address.  
Setting the Unit Properties for the Node  
To set the Properties of your RIM-600 Node, right-click on the Node name and select Node  
Properties. The Node Name will be copied from the node itself as programmed during the network  
configuration procedure. Enter the Location and Description in the fields provided. These param-  
eters will be used to identify the unit when sending alarms. Set the Custom Voice file to identify the  
Node when speaking over the telephone. (See Recording and Uploading Voice Messages for infor-  
mation on creating custom voice messages.)  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
In normal operation information is periodically passed between the Node and Host. This informa-  
tion mainly consists of current Input values and IP Alarm status. The amount of data transferred  
during this update is about 700 bytes. You can choose how often information is updated from the  
Node by selecting either periodic updates (Auto Send) or by selecting Update on a Percent Change  
basis. This can be used to control network traffic. When you enable the Auto Send Status Updates  
box, the Node will send an update (700 bytes) to the Host based on the Interval you program. When  
you choose the Send Update on Change option, the Node will only send an update when a sensor  
value increases or decreases by x% as programmed. You can even choose to enable both options for  
more flexibility.  
Note that if an alarm is detected, the Node will transmit this information to the Host immediately.  
The Node Properties screen is shown below:  
Figure 14: Node Properties Setup Tab  
Sample Application:  
1) Suppose you are concerned about network traffic generated by Node-to-Host communication but  
want to view input values that are no more than 20 minutes old.  
=>You can enable the Auto Send option and enter an interval of 1200 seconds (20 minutes). This  
will limit Node-to-Host data transfers to no more than 700 bytes every 20 minutes.  
2) Suppose that in addition, if the temperature changes by more than 3 degrees Fahrenheit (about  
4% at room temperature) you want to see this update immediately.  
=> You can enable the Send Update on Change option and enter a value of 4%. This will instruct  
the Node to send an update if the temperature changes by +/- 4% since the last update.  
Changing Node Network Settings  
You can remotely change the Node network settings using the ConsoleView software if the Allow  
Remote Configuration option is set in the Node Local Configuration options. However, before  
doing so consider the following:  
If you change the parent Host IP address in the Node, then the Node will no longer be in contact  
with the Host until the Hosts IP address also changes.  
To change the network settings, right-click on the Node Unit Name and select Node Properties.  
Click on the Network tab. Click on the Modify button to bring up the Network Setup screen.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Figure 15: Node Network Settings  
NOTE: If the Modify button is grey (inactive) then the unit either does not have the Allow  
Remote Configuration option set, or the units firmware does not support this feature and  
requires upgrading.  
Enter the new network parameters and click OK. The Node will reboot and temporarily disconnect  
from the Host.  
Configuring Environmental Inputs  
Each host or node can have up to 8 external sensors connected. The host or node will automatically  
identify what sensor type is connected to each input. To program the environmental input param-  
eters expand the host or node tree by clicking the plus box next to the host/node name.  
Channel Setup  
Next, click in the plus box beside Environmentals to expand the tree below it. Choose the input you  
would like to configure and right-click on the sensor name.  
Figure 16: Environmental Input Channels  
The Channel Setup screen will appear.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Figure 17: Channel Setup screen  
Set up the parameters for your environmental input on this screen.  
Name: Enter a name which describes what the sensor is monitoring. (ex: Mail Server, Data  
Center Rack #3, …)  
Type: The sensor type is determined automatically when the sensor is plugged into the host or node.  
Status: The status indicates if the sensor is presently within alarm limits. For devices such as  
Water Sensors or Smoke Detectors a Normal condition indicates that there is no water or smoke  
detected.  
In Use: This indicates that a valid sensor is plugged into the channel.  
Enabled: This indicates if the channel is currently enabled for alarm monitoring. If it is disabled,  
the RIM-600 will not send alarm messages. A channel can be enabled or disabled based on a 7-  
day + holiday time schedule.  
Schedule: Click this button to bring up the Edit Schedule screen. This screen allows you to  
set times when the channel is enabled or disabled. The blue line indicates days/times when the  
channel is enabled.  
Figure 18: Sensor Schedule screen  
The schedule example above enables the sensor Mon-Fri 8AM to 5PM.  
Editing the schedule:  
• Click on the All button in the top left corner of the grid to enable/disable the entire week.  
• Click on the day buttons down the left side of the grid to enable/disable entire days  
• Click on the hour buttons across the top of the grid to enable/disable entire hours  
• Drag the mouse over portions of the grid to enable/disable specific hours/days  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Channel Enabled: This box provides a simple means to enable or disable a sensor channel.  
Add to Datalog: Click this box to store the value or status of the channel in the datalogger.  
Value: This is the current value of the sensor connected to the channel (only valid for analog  
sensor types).  
Min: This is the minimum value reached by the sensor since it was connected to the unit.  
Max: This is the maximum value reached by the sensor since it was connected to the unit.  
Calibration: Enter a positive or negative offset in this field to calibrate the sensor value.  
High Limit: Enter the sensor high alarm limit in this field. When the value exceeds this limit for  
the duration of the recognition time, and if the channel is enabled, an alarm will be tripped.  
Low Limit: Enter the sensor low alarm limit in this field. When the value falls below this limit for  
the duration of the recognition time, and if the channel is enabled, an alarm will be tripped.  
Alarm Class: Click the drop down arrow and select the appropriate class for this sensor/channel.  
If you prefer you can create your own classes on the Class Setup screen.  
Figure 19: Alarm Class dropdown menu  
Custom Voice: Click the drop down arrow and select the custom voice message you would like  
assigned to this sensor/channel. Voice messages can be recorded on your PC and uploaded  
into the RIM-600 on the Custom Voice Manager screen (See Recording and Uploading Voice  
Messages).  
Figure 20: Custom Voice dropdown menu  
Wait (Recognition) Time: This is the time required for a fault condition to qualify as an alarm  
event. The sensor/channel must remain beyond the limits or in a fault condition continuously for  
this entire period of time in order to become an alarm.  
Reset Time: This is the time allowed for an acknowledged alarms fault condition to be corrected  
before the RIM-600 resets (reactivates) the alarm and begins the message delivery process all over  
again. The minimum reset time is 30 minutes.  
Alarm on Return to Normal: This feature makes the unit send a message (or messages) when a  
condition has moved within its programmed alarm limits or has gone from an alarm state to a  
Normal state. The person who acknowledged the alarm—in addition to all Inform Only contacts  
in the alarm class—will receive the message.  
SNMP Trap Level: When sending alarm messages via SNMP, this sets the priority of the SNMP  
trap. The choices are Major or Minor.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
Alarm Response via the PowerGate, PowerGate2, or Camera  
PowerGate  
When an alarm occurs, you can have PowerGate or PowerGate2 outlets automatically turn ON,  
turn OFF, or CYCLE power to a device. Cycling will switch an outlet OFF for 10 seconds and  
then switch it back ON. To set up a PowerGate, click the Alarm Response button on the Channel  
Setup Screen. A sample Alarm Response screen is shown below.  
Figure 21: Alarm Response screen for PowerGate  
Select Response Type: Choose “PowerGate.”  
PowerGate: Choose the specific PowerGate you’re programming.  
Outlet: Choose the PowerGate outlet you want to program for alarm response.  
New State: Select the action you want to have occur: On, Off, Cycle.  
Click the Add button to add this response to the list of current responses; click Delete to remove an  
action. Repeat for as many outlets as you wish to program.  
Camera Snapshots on Alarm  
Camera images may be sent to one or more users when an Environmental or IP alarm occurs. Up  
to four alarm responses (PowerGate or Camera Snapshot) may be programmed per input. To con-  
figure this feature choose Alarm Response from the Properties screen for the chosen input. The  
following screen will appear.  
Figure 22: Camera Alarm Response  
Click the down arrow in the Response Type menu and choose Camera. Select the name of the  
camera from which you would like to receive snapshots. Next, select the E-mail address where you  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
would like the snapshots to be sent. There are two options to determine the Duration over which  
snapshots will be sent. If you choose While in Alarm you will receive snapshots continuously until  
the input goes back to normal. If you choose Total you will receive a fixed number of snapshots  
once the alarm is detected. You can also select the time between snapshots in the Snapshot Interval  
field, and you can choose the maximum number of Snapshots Sent per E-mail. Camera snapshots  
will not work if a User Login is required in the camera.  
Note: the E-mail messages sent via Alarm Response operate independent of Profile Class and  
Contact Schedule.  
High Sound Alarms  
The RIM-600 measures the sound level with the built-in microphone on the front panel. This can  
be useful in detecting audible alarms in close proximity to the unit. To detect alarms at a distance  
from the unit, you can plug an external condenser microphone into the mic jack. Note that the  
audible alarm must be more than just a periodic beep. Only alarms that produce a loud, steady or  
pulsing signal (for example, smoke detector alarms) will be recognized by the RIM-600.  
The unit is programmed to trip an alarm if the sound level increases by a programmed number of  
decibels. On the High Sound programming screen this parameter is listed as “Change in dB.” The  
default setting is 30db. This means that if the audio level increases more than 30 dB for the dura-  
tion of the recognition time, an alarm will be tripped.  
To verify that your audible alarm is capable of tripping an alarm we recommend that you perform  
several tests to check the decibel increase at the RIM-600 unit. The test should involve tripping  
your audible alarm and checking the measured level within the ConsoleView Software. Using the  
data obtained from your testing, you can then set the Change in db parameter appropriately.  
If you are not concerned about High Sound alarms or if the unit is installed in a generally noisy  
environment that could easily trip false alarms, we recommend you disable the High Sound alarm  
monitoring via the Schedule.  
Realtime Strip Chart  
A realtime Strip Chart will show continuous values for sensors which provide an analog value. Just  
click on the sensor name and the chart will appear.  
The high and low scale of the chart is based on the Min and Max values. To reset Min/Max values,  
click on the Reset button to the right of the chart.  
Figure 23: Programmed Environmental Sensors  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Environmental Input Alarm Logic  
Each environmental input will automatically detect the type of sensor connected (temperature,  
humidity, power, motion...). Analog sensors will include high and low alarm limit programming  
options while two-state sensors (Normal/Alarm) will simply have a recognition time. In order for  
an alarm to be dispatched, the sensor must meet the following criteria:  
a) It must be Enabled—as configured through the schedule.  
b) It must have exceeded the programmed high or limit, continuously, for the duration of the  
wait (recognition) time. For two-state sensors it must be in the Alarm state, continuously, for  
the duration of the wait (recognition) time.  
c) It must be a member of a Class.  
d) There must be one or more User Profiles which include this Class.  
Once the alarm is dispatched, the alarm delivery process begins. (See Alarm Delivery and  
Acknowledgment for details.)  
Additionally, there is an option to re-trigger the alarm if it remains beyond the High/Low limits (or  
in an alarm state) too long. This programmable time period is called the Alarm Reset Time. This  
parameter can be set from 30 to 3600 minutes.  
DO NOT set the Alarm Reset Time too short, otherwise you will continue to dispatch the  
same alarm over and over resulting in numerous phone calls.  
Trouble Alarms  
The RIM-600 monitors the presence of all connected sensors to insure the reliability of the system.  
When a sensor is removed from a Host or Node for more than a minute, a trouble alarm is gener-  
ated. All trouble alarms are a part of the Diagnostic class, so any User who wishes to receive sen-  
sor Trouble Alarm, System Diagnostic or Fault Alarms can do so by including the Diagnostic class  
in their user Class List.  
Removing/Changing a Sensor  
Since the Host and Node monitor the presence of sensors, you must be careful when removing them  
to prevent a trouble alarm from occurring. The following procedure is recommended:  
a) Disable the sensor you wish to change/remove by clearing its schedule.  
b) Disconnect the sensor from the Host or Node.  
c) Login to the Host or Node and expand the Environmentals to display all of the inputs. Right  
click on the sensor to be removed and select Delete.  
A new sensor can now be connected to the empty channel.  
Special Notes  
To reset a Smoke detector alarm, you must momentarily disconnect it from the Host or Node, and  
then reconnect it. This will silence the alarm and return it to normal operating condition.  
Configuring Templates  
Environmental input programming Templates are used to load user-specified defaults each time a  
new sensor is connected to a Host or Node. By properly configuring the Templates before you plug  
in your sensors, you can minimize the amount of programming required to set up your sensors. To  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
configure the Templates, click the plus box next to the word Settings to expand the options under  
this heading. Next, expand the Input Templates. This will list all of the different sensor types.  
Figure 24: Template Types  
Right-click on each of the sensor names to bring up the individual Template programming screens.  
An example is shown below.  
Figure 25: Template  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
Configuring IP Alarms  
IP Alarm Setup  
Each host or node can monitor up to 64 IP addresses through pinging and port availability. In addi-  
tion, IP dependencies can be programmed to prevent multiple alarm messages from being sent  
when common network paths are down.  
Programming Alarm Parameters  
To program the IP Alarm parameters, expand the Host or Node by clicking the plus box next to  
the host/node name. Next, expand the IP Alarms. To configure a new IP Alarm, right-click on IP  
Alarms and select Add New IP Alarm. Next, right click on the New IP Alarm and select Setup. The  
IP Alarm Setup screen will appear.  
Figure 26: IP Alarm Setup screen  
Name: Enter a name which describes the IP address and port to be monitored.  
IP Address: Enter the numeric IP address of the device to be monitored.  
Port: Enter the port number to be monitored.  
Dependency IP: This is the IP address that must be responding for the monitored IP address to  
have a chance at responding. Or in other words, the monitored IP address is dependent upon the  
Dependency IP address to function.  
Alarm is Enabled: Unchecking this box will disable the IP alarm.  
Add to Datalog: Click this box to store the value or status of the channel in the datalogger.  
Last Response: This is the date/time that the IP device last responded.  
Last Alarm: This is the date/time that the last IP alarm occurred for this IP address.  
Last Ack: This is the date/time that the last IP Alarm for this channel was acknowledged.  
Status: The status indicates if the IP Address is presently responding or not. A Normal status  
indicates that the IP device is responding within the limits of the timeout and retry parameters.  
A Ping Timeout status indicates that the IP device is not responding within the timeout and retry  
parameters. An IP Route Down status indicates that the dependency IP is not responding and  
therefore the monitored IP address cannot be reached.  
Enabled: This indicates if the IP Address is currently enabled for alarm monitoring. If it is  
disabled, the RIM-600 will not send alarm messages. An IP Alarm can be enabled or disabled  
based on a 7-day + holiday time schedule.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Schedule: Click this button to bring up the Edit Schedule screen. This screen allows you to set  
times when the IP Alarm is enabled or disabled. The blue line indicates days/times when the  
channel is enabled.  
Figure 27: IP Schedule screen  
The schedule example above enables the IP alarm 24 hours a day, including holidays.  
Editing the schedule:  
• Click on the All button in the top left corner of the grid to enable/disable the entire week.  
• Click on the day buttons down the left side of the grid to enable/disable entire days  
• Click on the hour buttons across the top of the grid to enable/disable entire hours  
• Drag the mouse over portions of the grid to enable/disable specific hours/days  
Timeout: If the monitored IP address does not respond within this period of time, then the ping is  
considered a failure. If the number of consecutive failures exceeds the number of Retries then a  
Ping Timeout alarm is tripped.  
Retries: This is the number of times the monitored IP address is pinged after a failure, before a  
Ping Timeout alarm is tripped.  
Alarm Class: Click the drop-down arrow and select the appropriate class for this type of alarm.  
If you prefer you can create your own classes on the Class Setup screen to group certain types of  
alarms.  
Custom Voice: Click the drop-down arrow and select the custom voice message you would like  
assigned to this IP Alarm. Voice messages can be recorded on your PC and uploaded into the  
RIM-600 on the Voice screen.  
Reset Time: This is the time allowed for an acknowledged alarms fault condition to be corrected  
before the RIM-600 resets (reactivates) the alarm and begins the message delivery process all over  
again. The minimum reset time is 30 minutes.  
Alarm on Return-to-Normal: When this feature is enabled, the unit will send a message (or  
messages) when an IP device goes from a Ping Timeout state to a Responding state. The person  
who acknowledged the alarm—in addition to all Inform Only contacts in the alarm class—will  
receive the Return-to-Normal message.  
SNMP Trap Level: When sending alarm messages via SNMP, this sets the priority of the SNMP  
trap. The choices are Major or Minor.  
Note: See the previous section, “Alarm Response via the PowerGate, PowerGate2, or Camera”  
for information on responses to alarms via PowerGates or Cameras.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RIM-600 Manual  
Alarm Logic  
Network devices are monitored by the RIM-600 by pinging/connecting to programmed IP addresses  
about once a minute. The unit will only attempt to ping/connect to devices which are Enabled by  
the Schedule. Each time the network device responds, the RIM-600 updates the Last Response time.  
A time limit for responding is assigned to each IP Alarm to determine if the device is functioning  
properly. This time limit is called the ping Timeout. If a network device does not respond within  
this time period, the RIM-600 will count this as a ping failure. You can program the RIM-600 to  
try to ping/connect to the network device several times before tripping an alarm. The ping Retries  
determines how many times the RIM-600 will try to ping/connect to the device before sending an  
alarm. An alarm will only occur if the device fails to respond to consecutive ping attempts. Once  
a successful response is received, the failure counter will reset. For example: If the ping Retries is  
set to 3, then the RIM-600 must fail to ping/connect to the device 4 times in a row (initial attempt  
+ 3 retries) to trip an alarm. If the device were to respond after the second attempt, then the failure  
counter would reset, thus requiring four subsequent successive failures to trip an alarm. Once an  
alarm is recognized, the Last Alarm time will be updated.  
A dependency device (IP address) can be programmed for each IP Alarm. This is used to prevent  
numerous alarms from occurring when common network infrastructure problems arise. If the  
dependency device fails, then all IP alarms that have this dependency will be temporarily disabled  
from sending alarms until the dependency device returns to normal (e.g. starts responding to ping/  
connect requests). When an IP Alarms dependency is not responding, the status for the IP Alarm  
will be shown as “IP route down.” It is recommended that the dependency device be programmed  
such that it will go into alarm before any other devices. You can achieve this by setting the number  
of Retries for the dependency device to a lower value than the IP Alarms which rely on this device.  
In summary, for an IP Alarm to be dispatched, the following criteria must be met:  
a)The IP Alarm must be enabled—as configured through the schedule.  
b)It must have failed to respond to consecutive ping/connect requests and exceed the number of  
retries.  
c)It must be a member of a class.  
d)There must be one or more user profiles which include this class.  
Once the alarm is dispatched, the alarm delivery process begins. If any of the contacts are pro-  
grammed as Until Acknowledged, then the Last Ack time will update when the alarm has been  
acknowledged. In the case where all contacts are set to Inform Only, the Last Ack time will update  
immediately after the alarm occurs.  
Additionally, there is an option to re-dispatch the alarm if it remains in an alarm state too long. This  
programmable time period is called the Alarm Reset Time. This parameter can be set from 30 to  
3600 minutes. For example: Suppose the Alarm Reset Time is set to 180 minutes. Now suppose an  
IP device has stopped responding and trips an alarm which results in all programmed users receiv-  
ing their respective messages. If the IP device continues to remain unresponsive for 180 minutes,  
then the alarm will be dispatched again and everyone will be contacted once more.  
DO NOT set the Alarm Reset Time too short, otherwise you will continue to dispatch the  
same alarm over and over resulting in numerous phone calls, e-mails, etc.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Figure 28: IP Alarm Flowchart  
Removing an IP Alarm  
Expand the IP Alarms and right-click on the IP Alarm you wish to remove. Choose Delete this  
IP Alarm, and it will be removed.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Input/Alarm Classes  
Classes are used to associate environmental inputs and IP alarms with people. Each input sensor  
or IP address must be assigned to a Class. Each person or User Profile selects classes for which  
they have responsibility. To view the list of Classes, expand the Settings menu, then right-click on  
Classes and select Properties. Several classes have been pre-defined in the RIM-600 to give you a  
starting point. The default Classes are:  
• (Diagnostic)  
Temperature  
• Humidity  
• Water  
• Power  
• Other  
• Smoke  
• Security  
• Backup Battery  
• High Sound  
• IP Alarms  
Figure 29: Setup Classes  
You can have up to 64 classes in the RIM-600. To add Classes, just type in a new class name in  
the Class table list and click OK. The class programming screen is shown above. Note that the  
Diagnostic Class does not appear in the list shown above. This is because it is a special case,  
reserved for system faults, trouble alarms, and diagnostic alarms. The Diagnostic class cannot  
be edited or deleted. Any user who wishes to receive these types of alarms should include the  
Diagnostic class in their Profile Class list.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Configuring User Profiles and Contacts  
Configuring User Profiles  
The User Profile section controls who has access to the RIM-600 and who gets contacted when  
an alarm occurs. The User Profile programming screen describes attributes of the user including:  
name, title, company, dept, username, password, user code, time zone, classes, etc.  
When an alarm occurs the RIM-600 will check the list of User Profiles to see who should be con-  
tacted. Users whose class list includes the class of the alarm will be contacted. Each user can  
have up to 8 contact destinations (phone numbers, e-mail addresses, …). Up to 64 different User  
Profiles can be created. The RIM-600 can contact users using 6 different methods: voice, pager,  
alphanumeric pager, fax, e-mail, and snmp trap.  
The order of Profiles contacted can be changed. To move a Profile up or down in the list, click and  
hold the Profile you wish to move and drag it to its new location, then release the mouse button.  
The Profile should now display in its new location.  
Adding a Profile  
Right click on Profiles and select Add New Profile. The following screen will appear:  
Figure 30: User Profile screen  
The Name, Company, Department, and Title information are used to identify the user on reports  
that the unit sends.  
The Username, Password, and User Code are used for security purposes.  
You must have a Username and Password to:  
• go online with the unit  
• request two-way e-mail features  
• access other features of the unit.  
The User Code is a four digit number that is required to request a voice status report and to  
acknowledge alarms. When the RIM-600 receives a call, it will request the User Code. If a valid  
User Code is entered, the unit will match this code to the User's Class List and report the status  
of all Environmental Inputs and IP Alarms which correspond to the selected Classes. Voice Status  
reports check User permission, and a user can only receive information on items that he has per-  
mission to receive. This includes environmental and IP alarm status, PowerGate switching, ping  
requests, and microphone listen-in. (See “Permissions” section.)  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
The “Enable This Profile” option provides a convenient way to temporarily enable or disable a User  
Profile. When a Profile is disabled (unchecked), no alarms or reports will be sent to that user, and  
the user will not be permitted to log on to the system.  
Clicking the Permissions button will bring up the Permission screen.  
Permissions  
Each user profile has a programmable security level for each device (host/nodes) in the system. To  
set the Security Access level click the Permissions button. There are three access levels: Master  
System Administrator, Site Administrator, and User. The restrictions for each security level is as  
follows …  
Master  
System  
Admin  
Site  
Admin  
User  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Add user profiles  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Disable user profiles  
Edit unit properties  
Edit e-mail settings  
Edit Node properties  
Update firmware  
Configure data logger  
Add/delete classes  
Add/delete holidays  
Edit default input templates  
Delete sensors  
Disable IP alarms  
Reset min/max  
Other programming changes  
Add camera  
Acknowledge alarms  
Switch a PowerGate outlet  
Online via local PC  
Call in via voice  
Call in via modem  
Visit password protected Web Yes  
To configure a profile as a Master Administrator simply check the box at the top of the screen.  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Figure 31: Permissions screen  
To configure profiles for Site Administrator or User security levels, select the appropriate Host or  
Node(s) and click the arrow to copy the Host/Node(s) into the appropriate list. The double arrow  
>> will copy all units to the list while the single arrow > will copy just the selected unit to the list.  
Checking the box “This user can connect remotely via modem” at the bottom of the screen, allows  
the user listed at the top of the page to dial in to the system using a modem.  
In addition to controlling programming access when using the RIM-600 ConsoleView Software,  
permissions also have an effect during a telephone call. In voice mode the unit will recite only  
menus and status information for devices that the user has permission to hear. The associated  
Classes for each user will also control the content of voice reports. The same applies to two-way  
e-mail. A user can only receive information or send commands if they have the proper permissions  
and Class associations.  
Examples:  
1. If a User that has no Permissions on a particular Node, then the user will not be able to  
receive any Voice or e-mail reports that contain information about that Node.  
2. If a User has permissions on a particular Host/Node unit but none of the environmental  
sensors are in his class, then he will not receive any information about the environmental  
sensors.  
Classes  
Clicking the Classes button will bring up the Select Classes screen.  
Selecting Classes  
The User can choose to receive alarm reports from one or more Classes. The list on the left dis-  
plays all Available Classes. The list on the right shows Selected Classes for this profile. The Arrow  
Buttons are used to select or deselect classes. See the following Arrow Button definitions and the  
following figure:  
>
Move the highlighted class on the left to the right  
Move all classes on the left to the right (select all)  
Move the highlighted class on the right to the left  
Move all classes on the right to the left (deselect all)  
>>  
<
<<  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Figure 32: Class Selection screen  
Deleting a Profile  
From the hierarchy on the ConsoleView screen, right-click on the profile you wish to delete and  
select Delete This Profile in the contextual menu.  
Contacts  
The Contacts are the actual telephone numbers, e-mail addresses, pager numbers, etc… that the  
RIM-600 will contact when an alarm occurs. You can have up to 8 Contacts per User Profile.  
Each Contact can have its own Schedule so that you can have certain Contacts be Enabled during  
daytime hours and others Enabled during nighttime hours. Only Contacts which are Enabled when  
the alarm occurs, will be contacted.  
The order of Contacts can be changed at any time. To move a Contact up or down in the list, click  
and hold the Contact you wish to move and drag it to its new location, then release the mouse  
button. The Contact should now display in its new location.  
Adding Contacts  
To add a Contact, right-click on the User Profile you wish to add a contact to and select Add New  
Contact. An entry called New Contact will appear below the User Profile. Right-click on the New  
Contact and select Setup. The following screen will appear:  
Figure 33: Contact Setup Screen  
Enter a Name which describes the contact, like “Jims Cell,” “Acme Inc. Fax,” or “Jim at home.”  
Select the Contact Type using the drop down arrow. The choices are: Voice, Numeric Pager, Alpha  
Pager, Fax, Email, and SNMP.  
Destination: Enter the Telephone Number, E-mail Address, or Server Name/Address for the contact.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Voice Calls  
For most voice calls you can simply enter the telephone number of the person you want called.  
Consider the location of the RIM-600 Host when entering the number. If an area code is required to  
call from the Host to your telephone, be sure to include it.  
Examples:  
no area code required: 555-1234  
Area code required: (610)-555-1234  
1 + area code required: 1-(610)-555-1234  
You can also include additional codes within the telephone number. Listed below are the special  
code letters and a description of each:  
p = 2-second pause  
w = wait for answer  
b = blind dialing (makes the unit dial and start speaking the message without requesting that  
a key be pressed)  
! = flashes the phone line (momentary hang-up and reconnect, useful in some PBX systems)  
These codes can be useful if you want to call an extension within a business. For example, suppose  
your office was answered by an auto-attendant, but you know that if you dialed the extension the  
call would be transferred. In this case you can program the telephone number, insert a w to wait for  
the auto-attendant to answer, and then add the extension you want dialed.  
Example: 555-1234-w-170 {Extension 170 will be dialed after the auto-attendant answers}  
Numeric Pager Calls  
The RIM-600 can send alarm messages to numeric pagers. It will automatically send its ID tele-  
phone number when dialing to a numeric pager. All you have to do is enter the telephone number of  
your pager. Be sure to include the (area code) or 1 + (area code), as necessary.  
Example: (301)565-2300  
If your pager service is answered by a voice-prompted message, or if your pager service allows  
only a few seconds to enter a number before disconnecting, you will need to enter the telephone  
number differently. In this case, enter the pager telephone number + two or more pauses + the Host  
ID telephone number + #.  
Example: (301)565-2300-pp-844-1900-#  
Alphanumeric Pager Calls  
The unit can dial alphanumeric pagers to send alarm messages. The RIM-600 uses industry stan-  
dard TAP protocol, which is supported by most pager systems. The RIM-600 will send the type of  
alarm, the name of the Host or Node, the Input name, the current value, the programmed high or  
limit, and the time of the alarm. To program an alphanumeric pager destination, enter the pager ser-  
vice data/modem phone number followed by the letter A and then the pager ID.  
Example: (610)555-4500-A-0504099  
Contact your pager company if you do not know the data/modem telephone number or the pager ID  
for your alphanumeric pager.  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Fax Calls  
Enter the telephone number of the fax machine.  
E-mail  
Enter the e-mail address.  
SNMP  
Enter the SNMP server IP address in numeric form (e.g. 192.168.0.1)  
Schedule  
Click the Schedule button to bring up the Schedule screen for this Contact. Choose the times you  
want the Contact to be enabled by adjusting the blue bars. Areas where the blue bar appears indi-  
cates the day and time the Contact is Enabled.  
Figure 34: Contact Schedule screen  
For example, the schedule above enables the contact Mon-Fri 8AM to 5PM.  
Editing the schedule:  
• Click on the All button in the top left corner of the grid to enable/disable the entire week.  
• Click on the day buttons down the left side of the grid to enable/disable entire days  
• Click on the hour buttons across the top of the grid to enable/disable entire hours  
• Drag the mouse over portions of the grid to enable/disable specific hours/days  
Alarm Delivery Options  
There are additional options which appear on the Contact Setup screen depending upon the type  
of call. For alarm delivery you must select either Receives Unacknowledged Alarms or Receives  
Inform Only Alarms or both.  
Receives Unacknowledged Alarms: This option applies only to voice and pager calls. When select-  
ed the RIM-600 will call this contact until the alarm has been acknowledged or until the number of  
call attempts has been exhausted. If the alarm is acknowledged by another user, this contact will  
stop being called.  
Receives Inform-only Alarms: This means that the alarm message is for information purposes only.  
Once the alarm message has been delivered, the RIM-600 will stop calling this contact. This selec-  
tion is useful for insuring that a record of an alarm is sent. When this option is checked, the RIM-  
600 will always send an alarm message to this contact.  
Note: If no “Until Acknowledged” contacts are selected to receive an alarm message, the RIM-  
600 Host will self-acknowledge the alarm.  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Saving and Loading Programming  
The programming in your RIM-600 can be saved to a file. This gives you the ability to back up  
your programming or copy the same programming to another RIM-600 unit. Note that the file you  
save will not include custom voice files or settings entered through the serial port (network param-  
eters, web settings, two-way e-mail, RAS, etc.). To save your programming to a file, right-click on  
the name of your host and select Save Programming.  
To load a programming file into your RIM-600, right-click on the name of your host from the menu  
tree and select Load Programming. Select a programming file to load and click the Load button.  
Your unit will have to restart for the new programming to take effect. When the unit restarts, you  
will be logged off. After 10 or so seconds reconnect to the unit.  
Reconnecting  
At times your PC and RIM-600 Host units may become disconnected. This may happen due to a  
system restart or other communication-related problem. You can reconnect to a RIM-600 using  
the Reconnect command. To reconnect to a unit, click on File from the main menu and select  
Reconnect. Highlight the IP address of the unit you want to reconnect with and then click the  
Reconnect button.  
Figure 35: Reconnect Screen  
Recording and Uploading Voice Messages  
Custom voice messages can be assigned to many aspects of your RIM-600 system. Voice mes-  
sages are used during call-in status reports and alarm dial-out. This allows the system to identify  
and describe exactly where the problem is located, which equipment is affected, or which network  
device is not functioning. You can assign custom voice messages to the following:  
RIM-600 Host {See Host Properties}  
RIM-600 Node {See Node Properties}  
Each Environmental Input {See Channel Setup}  
Each IP Alarm {See IP Alarm Setup}  
Each PowerGate Device {See PowerGate Setup}  
Each PowerGate Outlet {See PowerGate Setup}  
Recording Voice Messages  
To record voice messages, click on the word Voice from the menu tree. This will display the  
CustomVoice Manager screen shown below.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Figure 36: Custom Voice Manager  
Click on the New button. This will display the MS Windows Sound Recorder program shown below.  
Figure 37: Sound Recorder screen  
For the voice messages to play back correctly you must set the recording format to PCM, 8KHz, 8  
bit, mono. To set these parameters click File, then Properties. Next, click the Convert Now button.  
In the Format field select “PCM.” In the Attributes field select “8,000 Hz, 8 Bit, Mono 8 KB/s.”  
See the following screen.  
Figure 38: Sound Specifications screen  
Next, save this recording format by typing “RIM-600” in the Name field and click Save As. Click  
OK on each screen until you get back to the Sound Recorder main screen.  
To record a message, click the button with the Red circle. To play a message, click the right arrow  
(Play) button. Trim off any silence before and after the message to ensure that the voice report  
flows smoothly. Messages can be trimmed by sliding the message position bar and selecting Edit  
from the main menu, and then either Delete Before Message Position or Delete After Message  
Position. Its important to minimize the length of the file to keep the message file size small  
and also to ensure that the message plays back smoothly when inserted into the message phrases.  
Once you’re satisfied with your message, save it by clicking File, then Save. Enter a name for the  
voice file and click OK. Continue this process until you’ve recorded all of the messages required.  
Next, upload your voice messages into the RIM-600 by clicking the Add button on the RIM-600  
CustomVoice Manager.  
Select the message you would like to upload then click OK. The new voice message will be loaded  
into the RIM-600 and will appear in the list.  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2: Software  
The window to the right displays all of the voice message file names stored in the RIM-600.  
To change the file name of a voice message click Rename. Enter a new file name and click OK.  
To delete a voice message, highlight the message and click the Delete button.  
To listen to a voice message, highlight the message and click the Listen button.  
Note: You must have a sound card and speakers/headphones to hear the audio.  
To save voice messages from your RIM-600 onto your computer, highlight the file name and click  
the Save button. Select the folder on your computer where you would like the file saved and click  
OK. This feature is useful to create a backup of the voice messages or to copy voice messages from  
one RIM-600 Host to another.  
Holiday Setup  
The RIM-600 allows you to program recurring or non-recurring holidays that you can use with-  
in your schedule programming. These schedules are used to enable or disable monitoring of  
Environmental and IP Alarms, and also to enable/disable times when users will receive alarm calls.  
To see which holidays are currently programmed, expand the Settings menu by clicking the plus  
sign next to the word Settings, then expand the Holidays menu by clicking the plus sign next to the  
word Holidays. See sample below:  
Figure 39: Holiday List  
To view the programming of a particular holiday, right-click on the holiday name and select  
Properties.  
To program a new Holiday, expand the Settings menu and right-click on the word Holidays, then  
select Add New Holiday. The new holiday programming screen will appear as shown below:  
Figure 40: New Holiday  
Enter a name for the holiday. Select the month, day, and year for the holiday. Finally, select wheth-  
er the holiday is recurring. Click OK when finished.  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Alarm Message Pop-Ups  
While online with one or more RIM-600 units through the ConsoleView Software, you can have  
an alarm message pop up on your computer screen whenever an alarm occurs. This could be an  
environmental or IP alarm on any Host or Node. You can configure this feature to display a general  
message indicating the Unit and Channel names, or you can associate a custom message with each  
input. The custom message can be displayed as plain text or HTML. The custom messages can be  
stored either on the local workstation or a drive that is regularly mapped to the workstation.  
Activating Alarm Pop-Ups  
Click on File, then Options from the main menu in the ConsoleView Software. The following  
screen will appear.  
Figure 41: Options Screen  
Within the section titled “Alarm Notification” click in the box to Enable Alarm Pop-Up  
Notifications. This will activate the Alarm Message Pop-Up feature. When an alarm occurs, a  
message will appear that simply displays the Unit and Channel names. If the user has permission  
to acknowledge the alarm, an Alarm Acknowledgment box will also appear. A sample message is  
shown below.  
Figure 42: Simple Alarm Popup  
Enabling Custom Pop-Up Messages  
To have custom messages pop up, you must enable this feature. Select Options from the main  
menu. Click in the box labeled Include Custom Message with Alarm Pop-Ups. Next, you must  
select where your custom messages will be stored (see below).  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Setting Pop-Up Text Location  
When using custom pop-up messages you must specify where these messages will be located. To  
do this, right-click on the name of your host within the menu tree and select Alarm Pop-Up Notice  
Location. Select the drive and folder where the messages will be stored.  
Editing Pop-Up Custom Message  
To edit the custom message for a particular environmental input or IP alarm, right-click on the cho-  
sen input and select Edit Alarm Pop-Up Message. The following screen will appear.  
Figure 43: Edit Popup Screen  
Messages can be displayed as text or HTML. Select the type of message you want to enter and type  
your message into the text area. This window will scroll to accommodate lengthy actions. Note  
that using HTML, you can embed web links in the message for more advanced actions. To test  
your HTML code, click the Preview button. To return to the edit screen click the Edit button. See  
samples below.  
Figure 44: HTML Edit Screen and HTML Preview Screen  
Audible Alarm Notification  
The ConsoleView Software can optionally beep or play a custom Wave file whenever an alarm is  
detected. To utilize this feature, click File, then Options from the main menu. Under the Alarm  
Notification section select Audible Alarm Notification. Next, select either System Beep or Play  
Wave. If you selected Play Wave, then you must select the Wave file to be played. Click on the  
speaker button to choose a Wave file. After you've made your choice, you can preview it by click-  
ing the Play button. See sample screen below:  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Figure 45: Alarm Notification screen  
E-Mail Setup and Two-Way E-Mail Commands  
The RIM-600 can send alarm messages via e-mail using SMTP as well as respond to commands  
via e-mail. See the Two-Way E-mail section for more information on sending commands.  
To set up the e-mail parameters right click on the Host name and select Network Settings. Select  
the Email Settings tab to see the following screen:  
Figure 46: E-mail Settings tab  
To have the unit send e-mail, you need to set the SMTP Server name and the Return e-mail Address,  
Username (if required) and Password (if required). To have the unit respond to Two-Way e-mail  
commands you must also set the POP Server name, e-mail account Username & Password, and the  
Mail Check Interval.  
SMTP Error messages  
If your e-mail settings are incomplete or incorrect there are some messages that will appear in the  
Event History log which may be helpful.  
The “Invalid Configuration” message will appear if you don’t have both the SMTP Server name  
and Return Address programmed. These are the minimum programming requirements to send e-  
mail. If you have at least these two items programmed and the RIM-600 is unable to deliver the  
message, then you will get the message “SMTP Server not Responding,” which essentially means  
that you have one or more of the following problems:  
(a) The wrong SMTP server name programmed.  
(b) The wrong username programmed.  
(c) The wrong password programmed.  
(d) A username is programmed but none is required.  
(e) A password is programmed but none is required.  
(f) All of the e-mail settings are programmed properly but the unit cannot reach your SMTP  
server for network routing reasons.  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
(g) The unit cannot reach your DNS server and thus cannot look up the SMTP server IP  
address.  
(h) The DNS server IP address is programmed incorrectly in the RIM-600 Network  
Configuration settings.  
Two Way E-Mail  
The RIM-600 Host has the ability to send and receive standard pop/smtp e-mail. In addition  
to using e-mail as a method of delivering outbound alarm messages, e-mail can also be used  
for remote access into the RIM-600. A set of commands is available that can be sent to a Host,  
within an e-mail, that will cause the Host to reply back to the sending e-mail address. Commands  
are available to inquire status, perform network ping and IP trace-route, and control outlets on a  
PowerGate.  
Note: Two-way e-mail is dependent upon User permissions. This means that the user can only  
receive information on items for which he has permission. (See “Permissions” section)  
In order to have the RIM-600 respond to e-mail commands you must first obtain an e-mail address  
for your RIM-600 from your internet provider, configure the e-mail settings for your RIM-600 Host  
(see e-mail setup), and have Two Way E-mail enabled (see Host Local Configuration in the Host  
Installation Manual).  
Note: The username and email address used in two-way e-mail commands must match a Profile  
Username and Contact. The response will be sent to the specified e-mail address.  
Requesting a Status Report  
To request a status report, send an e-mail message to your RIM-600 Host with the following information:  
To: <e-mail address of your RIM-600>  
Subject: rim600  
username: <valid profile username>  
email: <your e-mail address>  
command: status  
Requesting an IP Ping  
To request an IP ping, send an e-mail message to your Host with the following information:  
To: <e-mail address of your RIM-600>  
Subject: rim600  
username: <valid profile username>  
email: <your e-mail address>  
command: ping xxx.xxx.xxx.xxx  
Requesting a Trace Route  
To request an IP trace-route, send an e-mail message to your Host with the following information:  
To: <e-mail address of your RIM-600>  
Subject: rim600  
username: <valid profile username>  
email: <your e-mail address>  
command: traceroute xxx.xxx.xxx.xxx  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Requesting a PowerGate Outlet Command  
To request a PowerGate Outlet command, send an e-mail message to your RIM-600 Host with the  
following information:  
To: <e-mail address of your RIM-600>  
Subject: rim600  
username: <valid profile username>  
email: <your e-mail address>  
command: powergate "<PowerGate Name>" "<Outlet Name>" on/off/cycle  
For example:  
Subject: rim600  
username: jsmith  
command: powergate "Gear Rack #1" "Netgear switch #3" cycle  
Requesting a Picture from a Camera  
You can receive an e-mail with an attached picture from any camera configured in the RIM-600.  
The picture will be captured when the RIM-600 receives the e-mail request.  
To receive a picture, send an e-mail message to your RIM-600 Host with the following information:  
To: <e-mail address of your RIM-600>  
Subject: rim600  
username: <valid profile username>  
email: <your e-mail address>  
command: camera <camera name>  
For example:  
Subject: rim600  
username: jsmith  
command: camera NY Datacenter  
Requesting Help  
You can receive a brief overview of how to use and format two-way e-mail commands by requesting  
help.  
Send an e-mail message to your RIM-600 Host with the following information:  
To: <e-mail address of your RIM-600>  
Subject: rim600  
username: <valid profile username>  
email: <your e-mail address>  
command: help  
For example:  
Subject: rim600  
username: jsmith  
command: help  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Configuring a Video Camera  
The RIM-600 is compatible with the following network cameras.  
Axis:  
205  
241Q  
206 (CPI PN# 60065-001)  
241S  
206M  
2100  
206W  
2120  
210  
2400 Server  
2400+  
2420  
211  
213PTZ (unable to PTZ in Console View)  
2460 DVR (no Quad View as on Web page; clicking  
on image switches image to next camera)  
Panasonic:  
KX-HCM8 (CPI PN# 60065-005)  
BL-C10A  
KX-HCM10  
KX-HCM280  
These are all network video cameras that allow you to view live streaming video or capture images  
to e-mail when an alarm occurs. The camera or server connects to your network via an RJ-45 jack  
and supports 10/100 Mbit networks. Up to 128 cameras or servers may be associated with each  
Host or Node. The RIM-600 ConsoleView Software allows you easily to click and view live video  
wherever your camera is installed.  
When an Axis Camera Server is used, up to four cameras can be viewed at the same time. You can  
view a single camera by clicking on the video image you want to display. If you click again, it will  
return to the quad image. You can also capture a still image from either the quad or single camera  
display by right-clicking and choosing Capture Image.  
The first step is to get the camera running on your network. This process is independent of the  
RIM-600. Follow the instructions included with the camera to get it set up. Once the camera is  
properly set up, go into the RIM-600 ConsoleView Software. Cameras are added to the RIM-600  
by expanding the Settings menu and right-clicking on the word Cameras. Choose Add Camera.  
This will bring up the Camera Setup screen (see below). Enter the IP address, port number, and  
security settings (if required) of the camera according to how it has been configured on your net-  
work. See sample screen below:  
Figure 47: Camera Setup  
Select the camera type by clicking on the drop-down arrow and selecting the camera. Click OK  
when Finished.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Up to 128 cameras can be configured in a RIM-600 system. These can be a mix of Axis cameras,  
Axis camera servers, and Panasonic devices. Once the camera(s) have been configured they can  
then be associated with a particular Host or Node so that links for these cameras will appear within  
the menu tree for the chosen unit. You can associate a camera with more than one device if desired.  
To associate one or more cameras, right-click on Cameras within the menu tree for the selected  
host or node. See screen sample below.  
Figure 48: Associating Cameras  
The window on the left lists all cameras programmed into the system. The window on the right lists  
cameras associated with the selected Host or Node. To move a single camera to the other window,  
highlight the camera and click the single left/right arrow. To move all cameras to a new window,  
simply click the double arrows. This will copy all listed cameras to the other window.  
If you click on Cameras you will see thumbnails of all associated cameras. To view a large image  
of a particular camera, simply click on the image.  
Caution: The Panasonic and Axis cameras are Ethernet devices. They should be connected  
to your Ethernet network only. They do not connect directly to your RIM-600 Host or Node  
unit. Connection of either the Panasonic or Axis Cameras directly to your RIM-600 may cause  
undesirable results.  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2: Software  
Web Page  
The RIM-600 will produce a web page which includes:  
• The status of all Environmental Inputs and IP Alarms.  
• The ability to program most parameters.  
• Links to view logged data for each Input and IP alarm.  
• Links to view historical alarm information for each Input and IP alarm.  
• Graphs of the last 24 hours of logged data.  
• The present state of all PowerGate outlets.  
• Links to Live images from cameras.  
Figure 49: RIM-600 Web page  
The Web Page must be enabled through the Local Configuration process via the Hosts serial port.  
Optionally, the web page can also be password protected. You can program most parameters through  
the web page if the Web Page Programming option is enabled. This can be secured with the same  
permissions options as with the ConsoleView software. To gain access to the programming screens,  
you must log in on the web page.  
To view the Web Page, simply type in the Hosts IP address in your web browser.  
Graphs  
Anything you are data-logging, you can also graph. Graphs represent the last 24 hours of logged  
data for the particular Environmental/IP element you choose to view.  
To view a graph on your Web Page:  
1) Select the Unit.  
2) Select Environmental/IP alarms  
3) Select a specific environmental or IP from the displayed list (Ex: AC Power)  
4) Click the Graph button.  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
The summary will be replaced by a graph for the chosen Environmental/IP item. (See following  
figure.)  
Figure 50: Graph of AC Power  
Updating the Web Page  
You can enable Automatic Updates of the data and select the interval between updates by right-  
clicking on the Host and selecting Network Settings. Click on the WebView tab. Check the  
Automatic Refresh box and enter the number, in seconds, between updates, in the Update Every  
box.  
Figure 51: Web Page Refresh Enabled  
Remote Web Page  
The RIM-600 can send a copy of its web page to another web server via FTP (File Transfer  
Protocol), so that the web page can be viewed on another network (for example, on the Internet).  
To configure the unit to FTP the web page, right-click on the Host and select Network Settings.  
Next, click the tab labeled Web Page Delivery. A sample screen is shown below.  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Figure 52: Web FTP screen  
Click the Enable FTP Delivery box and fill in the necessary information for your FTP server. Your  
service provider will have to provide you with the FTP Server name and sub directory where your  
files will be uploaded. You will also be required to enter your username and password. You can  
set how often you want the web page to be updated by entering an interval time in the Update box.  
Enter a file name for the web page (e.g. rim600.html). When you’ve finished, click OK. Listed  
below are definitions of the FTP programming parameters.  
FTP Server: the host name of the FTP server for your service provider.  
Directory: The remote directory is the folder within the web site where the pages will upload.  
Username: Your user name for your web account.  
Password: The log-in password you need to access the folders and files in your web account.  
Update Interval: This time period determines how often the web page is uploaded.  
Create HTML as: This is the file name given to your web page.  
Create WML as: This is the file name given to web pages to be viewed with wireless phones. If  
no name is programmed, the unit will not ftp any wml files.  
Viewing the Remote Web Page  
To view the remote web page that the RIM-600 uploaded, you need to know its web address. This  
address corresponds to the Server name, plus the directory, plus the file name of the web page. It  
Note: Data Log and Event Log information are NOT available via the remote web page.  
History  
The RIM-600 stores both datalog and eventlog history internally. The datalog is a time-stamped  
collection of input values that can be used to view and graph environmental conditions over time.  
It can also store the status of IP devices. The user can choose which inputs or IP alarms are stored  
and specify the overall sampling rate. Care should be taken to select the number of inputs and sam-  
pling rate accordingly, since large amounts of data can potentially be logged. The more data being  
logged, the faster the history log will fill up.  
The eventlog contains time-stamped messages that describe activities performed by the unit such as  
alarm detection, user logins, telephone calls, and alarm acknowledgement. The eventlog history is  
useful when you want to review the historical events monitored and performed by the RIM-600.  
When a user goes online, information for both the datalog and eventlog history is automatically  
retrieved and stored in a database on a user-specified hard disk. This can be a drive on your own  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
computer or a network server. While the program defaults to saving the history database on your  
local drive, if the system will be used by many users it may be advantageous to store the database  
on a network drive. To specify the drive for saving History information click File, then Options  
from the main menu. A sample screen is shown below:  
Figure 53: History Options  
To change the location for storing the History database, click the folder button on the right side of  
the screen and choose a new location. The location you select will be displayed to the left.  
Use the up or down buttons to select the amount of history to be viewed when accessing the History  
option through the right-click menus in the ConsoleView software. This provides a quick view  
of the history for a particular Input or Profile. The default time is 24 hours (1 day). Clicking the  
arrows will increase or decrease the data time by days.  
Analog input values will automatically be graphed when viewing History through the right-click  
menus of the ConsoleView software. You can choose to have the graphed data displayed as a line  
graph or simply show the discrete data points.  
You can also deselect the Automatically Update buttons if you don’t want the Datalog or Eventlog  
to download each time you connect. If you are using a dialup connection, you may want to disable  
these functions to speed up the software loading process. (You can manually download the logs as  
desired by right-clicking on History in the menu tree.)  
Datalog History  
The RIM-600 can log up to 62,500 samples of environmental and IP Alarm history. When the log  
fills, it will overwrite the oldest data first. Environmental data will display the actual value, while  
IP Alarm data will display either Normal, Timed Out, or IP Down. All stored history is logged at the  
same interval as programmed on the History programming screen. To set up the Datalog History,  
right-click on History from the RIM-600 menu tree and select Properties. Enter the Interval time  
and click the Enable box. This will start the Datalog feature. The Datalog will store Environmental  
and IP Alarm values if datalogging is enabled on their respective programming screens.  
Figure 54: Datalog Setup Screen  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Viewing History  
Datalog History can be viewed through the ConsoleView software or via the RIM-600 web page. It  
can be viewed through the ConsoleView software in two ways: There is the quick view which can  
be displayed by right-clicking on an input or profile and selecting History, or you can perform a  
query on the entire history database using the HistoryView program (right-click on History in the  
menu tree and select HistoryView, or from the main menu select File, then HistoryView).  
History QuickView  
You can display a quick view of an input or profile by simply right-clicking on the item and  
selecting History. This will provide an event listing and graph of the input over the last 24 hours  
(default). You can change the amount of history displayed to several hours or several days by  
changing the setting on the Options screen under the File menu. A sample is shown below:  
Figure 55: AC Power History  
Querying the History Database with HistoryView  
The HistoryView program allows you to query the entire History database for all RIM-600 units.  
There are filters to select Samples, Alarms, System messages, or User Logins. You can view data  
from a RIM-600 Host and its associated Nodes combined, or individually. You can also graph sam-  
pled data.  
To begin, run the HistoryView program by right-clicking on History in the menu tree and select  
HistoryView, or from the main menu select File, then HistoryView. The first screen will prompt  
you to select a RIM-600 Host. Click in the box next the Host you want to Query. The program  
will then load the associated nodes and input names. Next, select the Host or Nodes that you want  
to query information on, then select any filters that you want to apply. If you select All you will see  
all events and data samples for the selected units. If you select Samples or Alarms you must then  
choose one or more Environmental Inputs or IP Alarms.  
Note: the number that precedes each Environmental and IP description corresponds to the unit  
number to which they’re connected (0 being the Host and 1-31 being the associated Nodes).  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
If you double-click on an item in the Environmental or IP Alarm box, all of the listed items will  
become selected and/or deselected. Last, select a time frame to perform the query and click View.  
The selected data will now be displayed. See sample screen below:  
Figure 56: History Viewer  
Graphing  
Graphing data is possible when the selected query contains only Samples.  
If you click on the Graph button, all of the points in the query will be displayed as a line graph.  
There are also options (from the Graph menu above) to format and display the data as a bar or area  
graph. You can have up to eight items displayed on the graph at once. To view different parts of  
the graph use the arrows on the bottom and sides to adjust the position. A graph can be printed by  
clicking the Print button at the top of the screen. You can copy the graph to the Windows clipboard  
by clicking the Copy button. This allows you to paste the graph into other applications. The Zoom  
In and Zoom Out buttons let you view the data with more or less detail. The Reset button restores  
the original view of the graph. When finished, click the Close button to return to the grid.  
Printing Data  
You can print the data viewed in the grid by clicking the Print button. Printing defaults to an Arial  
5 pt. font in order to fit one line of data across one line of an 8.5" x 11" sheet of paper printed in  
landscape mode. You may choose different fonts and type sizes.  
Exporting Data  
The Export button allows you to save the queried data in the grid to a file format which can be  
easily imported into other applications. Options include the ability to save the file in CSV format,  
formatted text (prn), and tab delimited (txt) format. Note: The exported data will represent only  
what you’ve selected to query.  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Software  
Click on File and select Export Field Names from the submenu if you want the field titles (Date,  
Time, Event Code, etc.) to be included with the data when you export.  
Copying to the Clipboard  
You can highlight and copy selected cells within the grid to the Windows clipboard. To highlight  
the data simply click-and-hold the left mouse button and drag the mouse over the cells you wish  
to highlight, then either right-click and select Copy, or click Edit from the main menu and select  
Copy. To select all of the data in the grid, right-click within the grid and choose Select All from the  
contextual menu, or click Edit from the main menu and choose Select All from the submenu. This  
will highlight all of the data in the grid. You can then perform the Copy function as previously  
described.  
Deleting Data  
The Delete button will remove the queried data displayed in the grid from the database.  
TheViewer Menu offers you other features as well to customize your report.  
Archiving  
As the history database grows it will begin to take longer to perform a query. It is recommended  
that the database be periodically archived to keep the size reasonable and to permit satisfactory  
performance of the HistoryView program. Archiving may be done as often as necessary for perfor-  
mance reasons but it must be done when the database reaches its physical limit. To find out how big  
the database is for a particular unit, select Database Statistics under the Archive menu. The size of  
the database and percent full will appear in the status bar along the bottom of the grid. A warning  
message will appear when the database reaches 80% of its capacity.  
To archive the history database select Archive from the main menu and then choose Select database  
to archive. Locate the history.db file for the unit you wish to archive and click Open. Next, enter  
the date range to archive (typically one or more months or a quarter). Click the Archive button. The  
archived data will be stored in a file that includes the “from” and “to” date range in a yr/mn/dy for-  
mat.  
After archiving its recommended that you Pack the history database (history.db) to delete the old  
data and reduce the file size. To do this select Pack Database from the Archive menu. Note that  
the Pack Database function can only be executed while offline with the RIM-600 unit. To run  
HistoryView while not connected, click File, then Run from the ConsoleView main menu.  
To view archived data, you will need to restore an archived database. To do this, choose Select  
archive to restore from the Archive menu. Next, choose the archive file you wish to restore and  
click Open. Next, click the Restore button. The archived data will be copied into the history data-  
base and a query can be performed.  
Manually Forcing History Downloads  
You can manually force full history downloads at any time. As previously stated, if you’re on a  
dialup connection, you may choose to disable auto updates, and need to download the data periodi-  
cally. To do this, go to your main RIM-600 menu and right-click on History in the tree diagram.  
Select Force Full Eventlog Download to manually download the Eventlog or Select Full Datalog  
Download to manually download the current datalog.  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
RIM-600 Manual  
Figure 57: A manual Datalog Download in progress  
Updating Firmware  
From time to time Firmware updates will become available to add features or improve the perfor-  
mance of your RIM-600. Most Firmware updates will be included as part of a complete RIM-600  
information on updates.  
To check the version of Firmware in your RIM-600, right-click on the Hostname and select Version  
Info. The following screen will appear.  
Figure 58: Version Info Screen  
The RIM-600 unit firmware comprises four files: BootSys version, RIM600 OS version, System  
Support version, and VoiceWare version. This screen includes functions to upload new firmware  
and restart the system. Always follow the instructions included with the new firmware files prior  
to installing any new versions. (Note that the Node firmware is installed separately on the Node  
Diagnostics screen.)  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

BenQ Projector W20000 User Manual
Blanco Indoor Furnishings 157 068 User Manual
Blanco Indoor Furnishings 506 528 User Manual
Bosch Power Tools Cordless Drill GBH 2 22 E User Manual
Bradford White Corp Water Heater 103 B User Manual
Braun Mobility Aid NL Series User Manual
Caframo Fan 743CA WBX User Manual
Canon Printer B540 User Manual
CDA Ventilation Hood CCA5 7 User Manual
Chicago Electric Marine Battery 66944 User Manual