62E
Energy Recovery Ventilators
50 Hz
Installation, Start-Up and
Service Instructions
Page
CONTENTS
Wheel Drive Components . . . . . . . . . . . . . . . . . . . . . . . 37
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Replacing the Throwaway Filters . . . . . . . . . . . . . . . . 37
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . .CL-1
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
Step 1 — Inspect the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 2 — Install Combination Roof Curb
(62EB-EU Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 3 — Install Drop in Damper Box
(62EB-EU Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 4 — Install Horizontal Base and Transition
(62EB-EU and 62E2-E7 Units) . . . . . . . . . . . . . . . . . . . . 7
Step 5 — Install Standard Roof Curb . . . . . . . . . . . . . . 14
• VERTICAL STAND-ALONE APPLICATIONS
• HORIZONTAL STAND-ALONE APPLICATIONS
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . 16
Step 7 — Make Electrical Connections . . . . . . . . . . 17
• POWER SUPPLY
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
• ELECTRICAL CONNECTIONS
Follow all safety codes. Wear safety glasses and work
gloves. These instructions describe how to install, start up, and
service 62E energy recovery ventilator (ERV) units.
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-32
Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Rain Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Energy Recovery Wheel. . . . . . . . . . . . . . . . . . . . . . . . . 22
• DRIVE BELT
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
• AIR SEALS
Airflow Settings and Adjustments. . . . . . . . . . . . . . . 22
• UNITS WITH EZERV CONROL OPTION
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ComfortLink™ Interface Device . . . . . . . . . . . . . . . . . 27
Optional BACnet or LON Communications
Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
GENERAL
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-36
Removing and Installing Non-Segmented
Wheel for Cleaning (62EB,E7 Units). . . . . . . . . . . 32
Removing and Installing Non-Segmented Wheel
for Cleaning (62ECC and 62E2C Units). . . . . . . . 33
Removing Wheel Segments for Cleaning (62ECD,
62ED-EU, 62E2D, and 62E3-E6 Units) . . . . . . . . . 33
Installing Wheel Segments. . . . . . . . . . . . . . . . . . . . . . . 33
Wheel Drive Motor and Pulley Replacement
(62EC-EU and 62E2-E6 Units) . . . . . . . . . . . . . . . . . 34
Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
• ALTERNATE BELT REPLACEMENT METHODS
Removing the Service Door . . . . . . . . . . . . . . . . . . . . . 35
Replacing a Blower (All ERV Cabinets Except
62EB and 62E7 Units) . . . . . . . . . . . . . . . . . . . . . . . . . 35
• EXHAUST SIDE
The 62E ERV units recover energy from building exhaust
air and pre-condition ventilation air. See Tables 1A-2B for unit
data. All 62EB-62EU units are configured for vertical dis-
charge (through the bottom). Vertical units may be installed on:
• a stand-alone roof curb
• a combination curb for direct coupled connection to a
rooftop unit
If horizontal supply and return is desired using a vertical
unit, the vertical unit may be installed on a horizontal supply/
return base.
NOTE: The horizontal supply/return base accessory includes a
roof curb. The horizontal supply/return base should NOT be
used with a stand-alone roof curb.
All 62E2-62E7 units are configured for horizontal discharge
(through the side). Horizontal units may be installed on a
stand-alone roof curb.
• SUPPLY SIDE
Replacing a Blower (62EB and 62E7
Size Cabinets). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
• EXHAUST OR SUPPLY SIDE
DIRECT COUPLED APPLICATIONS (Vertical) —
The
ERV unit can be installed directly coupled to a RTU (rooftop
unit). For vertical (through the roof) applications, the connec-
tion between the 62EB-62EU ERV unit and the RTU may be
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36,37
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Air Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620007-01 Printed in U.S.A. Form 62E-C1SI Pg 1 8-10 Replaces: New
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1A — Physical Data — SI (cont)
UNIT 62E
NOMINAL CAPACITY (L/s)
CAPACITY RANGE (L/s)
LD
3585
LG
4340
MD
2830
MG
5100
ND
5200
NG
6500
330-8260
PD
5950
PG
7080
1650-4250 2360-5665 1415-3540 2595-6845 2595-6370
2830-7315 3540-9440
MAXIMUM SHIPPING
WEIGHT (kg)
MAXIMUM OPERATING
WEIGHT (kg)
1232
1118
1308
1194
1397
1283
1397
1283
1482
1368
1482
1368
1533
1420
1608
1495
UNIT DIMENSIONS (mm)
Length (includes hoods)
Width
2355
2162
1687
2532
2339
1712
2685
2492
1737
2812
2619
1824
Height
ROTARY ENERGY
EXCHANGER
Type
Segmented
Size (Diam x Depth) (mm)
Nominal Drive Motor kW
SUPPLY/EXHAUST FANS
Type
1727 x 76
0.2
1880 x 76
0.2
2057 x 76
0.2
2184 x 76
0.2
Backward Inclined, Single Width Single Inlet
EC Motor with Integral Frequency Drive
Drive Type
Fan Option Code
(see fan option table)
F, G, L, M
F, G, M
F, G, M
F, G, M
G, M
F, G, M
G, M
FILTERS
Type
51 mm Pleated
Exhaust Air – Qty...Size
(L x W x D) (mm)
Outside Air – Qty...Size
(L x W x D) (mm)
6…406 x 635 x 51
6…406 x 635 x 51
6…457 x 635 x 51
6…457 x 635 x 51
6…508 x 508 x 51
6…508 x 508 x 51
8…508 x 610 x 51
8…508 x 610 x 51
UNIT 62E
RD
RG
SD
SG
TD
TG
UD
UG
NOMINAL CAPACITY (L/s)
CAPACITY RANGE (L/s)
6500
8000
7800
9400
8500
10250
9700
11800
3300-8025 4250-11325 3775-9450 5190-13685 4250-10380 5665-14630 4720-11800 6600-16990
MAXIMUM SHIPPING
WEIGHT (kg)
MAXIMUM OPERATING
WEIGHT (kg)
1974
1860
1974
1860
2126
2013
2126
2013
2486
2373
2486
2373
2486
2373
2486
2373
UNIT DIMENSIONS (mm)
Length (includes hoods)
Width
3015
2822
1824
3117
2924
1925
3294
3101
2068
3447
3251
2118
Height
ROTARY ENERGY
EXCHANGER
Type
Segmented
Size (Diam x Depth) (mm)
Nominal Drive Motor kW
SUPPLY/EXHAUST FANS
Type
Drive Type
Fan Option Code
(see fan option table)
2337 x 76
0.2
2515 x 76
0.2
2642 x 76
0.2
2794 x 76
0.2
Backward Inclined, Single Width Single Inlet
EC Motor with Integral Frequency Drive
H, K, J,
G, H, J, M,
G, H, J, N
H, J, K, N
K, J, N, P, R
H, K, J, N, P, R
N
N, P, R
FILTERS
Type
51 mm Pleated
Exhaust Air – Qty...Size
(L x W x D) (mm)
Outside Air – Qty...Size
(L x W x D) (mm)
10…508 x 508 x 51
10…508 x 508 x 51
8…610 x 610 x 51
8…610 x 610 x 51
8…635 x 635 x 51
8…635 x 635 x 51
8…635 x 635 x 51
8…635 x 635 x 51
LEGEND
DWDI — Double Width, Double Inlet
EC
—
Electronically Commutated
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1B — Physical Data — English
UNIT 62E
BA/7A
350
200-800
331
BC/7C
500
200-900
336
CC/2C
1000
500-1150
488
CD/2D
900
400-1100
502
CG/2G
1100
500-1400
502
DD/3D
1300
600-1600
627
DG/3G
1600
800-2000
627
NOMINAL CAPACITY (cfm)
CAPACITY RANGE (cfm)
MAXIMUM SHIPPING WEIGHT (lb)
MAXIMUM OPERATING WEIGHT (lb)
UNIT DIMENSIONS (in.)
Length (includes hoods)
Width
281
286
438
452
452
577
577
44.2/48.9
31.1/36.4
34.6/31.2
61.8/57.5
38.6/43.9
42.1/38.7
67.6/57.3
44.4/49.7
41.9/44.5
Height
ROTARY ENERGY EXCHANGER
Type
Monolithic
Segmented
Size (Diam x Depth) (in.)
Nominal Drive Motor Hp
SUPPLY/EXHAUST FANS
Type
19 x 1.0
0.09
19 x 2.0
0.09
25 x 2.0
0.09
25 x 3.0
0.09
30 x 3.0
0.09
Centrifugal DWDI
Direct
Backward Inclined, Single Width Single Inlet
EC Motor with Integral Frequency Drive
Drive Type
Fan Option Code
(see fan option table)
A
A, B
C
C
FILTERS
Type
2 in. Pleated
1…14 x 25 x 2
1…14 x 25 x 2
Exhaust Air – Qty...Size (L x W x D) (in.)
Outside Air – Qty...Size (L x W x D) (in.)
1...12 x 24 x 2
1...12 x 24 x 2
2…16 x 25 x 2
2…16 x 25 x 2
UNIT 62E
EB/4B
ED/4D
EF/4F
EG/4G
HB/5B
HD/5D
HF/5F
HG/5G
KD/6D
KG/6G
NOMINAL CAPACITY (cfm)
1,400
2,200
2,200
2,600
3,000
4,600
4,600
5,500
4,500
7,800
800-
1,800
1,100-
2,600
1,300-
2,700
1,300-
3,500
1,400-
3,600
2,200-
5,600
2,200-
5,400
3,000-
7,400
2,500-
5,500
4,000-
10,500
CAPACITY RANGE (cfm)
MAXIMUM SHIPPING
WEIGHT (lb)
MAXIMUM OPERATING
WEIGHT (lb)
1,120
1,070
1,158
1,108
1,120
1,070
1,158
1,108
1,739
1,689
1,771
1,721
1,739
1,689
1,771
1,721
2,550
2,300
2,550
2,300
UNIT DIMENSIONS (in.)
Length (includes hoods)
Width
85.5/70.8
54.6/59.9
50.5/54.7
103.9/80.1
67.0/72.3
55.9/67.1
114.5/86.1
77.6/82.9
61.9/77.7
Height
ROTARY ENERGY
EXCHANGER
Type
Segmented
52 x 1.5 52 x 3.0
Size (Diam x Depth) (in.)
Nominal Drive Motor Hp
SUPPLY/EXHAUST FANS
Type
36 x 1.5
1/6
36 x 3.0
1/6
36 x 1.5
1/6
36 x 3.0
1/6
52 x 1.5 52 x 3.0
1/6
64 x 3.0
1/4
1/6
Backward Inclined, Single Width Single Inlet
EC Motor with Integral Frequency Drive
Drive Type
Fan Option Code
(see fan option table)
C, E
E, F
E, F, L
E, F, L, M F, L, M
FILTERS
Type
Exhaust Air – Qty...Size
(L x W x D) (in.)
Outside Air – Qty...Size
(L x W x D) (in.)
2 in. Pleated
3…20 x 25 x 2
2…20 x 25 x 2
2…20 x 25 x 2
6…16 x 24 x 2
6…16 x 24 x 2
3…20 x 25 x 2
LEGEND
DWDI — Double Width, Double Inlet
EC Electronically Commutated
—
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1B — Physical Data — English (cont)
UNIT 62E
LD
LG
MD
MG
ND
NG
PD
PG
NOMINAL CAPACITY (cfm)
7,600
9,200
6,000
10,800
11,000
13,800
12,600
15,000
5000-
5500-
5500-
7000-
6000-
7500-
CAPACITY RANGE (cfm)
3,500-9,000
2,715
3000-7500
3,079
12,000
14,500
13,500
17,500
15,500
20,000
MAXIMUM SHIPPING
WEIGHT (lb)
MAXIMUM OPERATING
WEIGHT (lb)
2,883
2,633
3,079
2,829
3,267
3,017
3,267
3,017
3,381
3,131
3,545
3,295
2,465
2,829
UNIT DIMENSIONS (in.)
Length (includes hoods)
Width
92.7
85.1
66.4
99.7
92.1
67.4
105.7
98.1
68.4
110.7
103.1
71.8
Height
ROTARY ENERGY
EXCHANGER
Type
Segmented
Size (Diam x Depth) (in.)
Nominal Drive Motor Hp
SUPPLY/EXHAUST FANS
Type
68 x 3.0
1/4
74 x 3.0
1/4
81 x 3.0
1/4
86 x 3.0
1/4
Backward Inclined, Single Width Single Inlet
EC Motor with Integral Frequency Drive
Drive Type
Fan Option Code
(see fan option table)
F, G, L, M
F, G, M
F, G, M
F, G, M
G, M
F, G, M
G, M
FILTERS
Type
2 in. Pleated
Exhaust Air – Qty...Size
(L x W x D) (in.)
Outside Air – Qty...Size
(L x W x D) (in.)
6…16 x 25 x 2
6…16 x 25 x 2
6…18 x 25 x 2
6…18 x 25 x 2
8…20 x 20 x 2
8…20 x 20 x 2
8…20 x 24 x 2
8…20 x 24 x 2
UNIT 62E
RD
RG
SD
SG
TD
TG
UD
UG
NOMINAL CAPACITY (cfm)
13,800
17,000
16,500
20,000
18,000
21,700
20,500
25,000
7,000-
17,000
9,000-
24,000
8,000-
20,000
11,000-
29,000
9,000-
22,000
12,000-
31,000
10,000-
25,000
14,000-
36,000
CAPACITY RANGE (cfm)
MAXIMUM SHIPPING
WEIGHT (lb)
MAXIMUM OPERATING
WEIGHT (lb)
4351
4101
4351
4101
4688
4438
4688
4438
5481
5231
5481
5231
5481
5231
5481
5231
UNIT DIMENSIONS (in.)
Length (includes hoods)
Width
118.7
111.1
71.8
122.7
115.1
75.8
129.7
122.1
81.4
135.7
128.0
83.4
Height
ROTARY ENERGY
EXCHANGER
Type
Segmented
Size (Diam x Depth) (in.)
Nominal Drive Motor Hp
SUPPLY/EXHAUST FANS
Type
Drive Type
Fan Option Code
(see fan option table)
92 x 3.0
1/3
99 x 3.0
1/3
104 x 3.0
1/3
110 x 3.0
1/3
Backward Inclined, Single Width Single Inlet
EC Motor with Integral Frequency Drive
H, K, J,
G, H, J, M,
G, H, J, N
H, J, K, N
K, J, N, P, R
H, K, J, N, P, R
N
N, P, R
FILTERS
Type
2 in. Pleated
Exhaust Air – Qty...Size
(L x W x D) (in.)
Outside Air – Qty...Size
(L x W x D) (in.)
10…20 x 20 x 2
10…20 x 20 x 2
8…24 x 24 x 2
8…24 x 24 x 2
8…25 x 25 x 2
8…25 x 25 x 2
8…25 x 25 x 2
8…25 x 25 x 2
LEGEND
DWDI — Double Width, Double Inlet
EC
—
Electronically Commutated
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2A — Supply/Exhaust Fan Options Physical Data — SI
FAN OPTION CODE
A
B
C
E
F
G
H
Wheels
Qty...Width (mm)
1…128 x 110
2…128 x 110
1…400
1…500
2…500
3…500
4…500
Nominal Motor kW
(per each fan)
0.45
0.45
0.88
2.70
2.70
2.70
2.70
FAN OPTION
CODE
J
K
L
M
N
P
R
S
Wheels
5…500
2.70
6…500
2.70
1…630
2.90
2…630
2.90
3…630
2.90
7…500
2.70
8…500
1…250
2.70
Qty...Width (mm)
Nominal Motor kW
(per each fan)
2.70
Table 2B — Supply/Exhaust Fan Options Physical Data — English
FAN OPTION CODE
A
B
C
E
F
G
H
Wheels
Qty...Width (in.)
1…5 x 4 1/8
2…5 x 4 1/8
1…15 3/4
1…19 3/4
2…19 3/4
3…19 3/4
4…19 3/4
Nominal Motor Hp
(per each fan)
0.61
0.61
1.18
3.62
3.62
3.62
3.62
FAN OPTION
CODE
J
K
L
M
N
P
R
R
Wheels
5…19 3/4
3.62
6…19 3/4
3.62
1…24 3/4
3.89
2…24 3/4
3.89
3…24 3/4
3.89
7…19 3/4
3.62
8…19 3/4
3.62
1…9 7/8
3.62
Qty...Width (in.)
Nominal Motor Hp
(per each fan)
DIRECT COUPLED APPLICATIONS (Horizontal) — For
horizontal applications (above the roof) using 62EB-EU units,
the horizontal supply/return base and transition accessories
may be used.
INSTALL DUCTWORK — Ductwork will be installed in the
curb for combination curb applications. The supply duct will
hang from the top of the curb. The return duct will attach to a
stub duct provided with the combination roof curb.
For horizontal applications using 62E2-E7 units, a standard
roof curb and transition accessories may be used.
NOTE: Ductwork must be installed before the RTU is set in
place.
INSTALL GASKETS — The combination curbs come with a
gasketing package to provide a seal between the RTU and ERV
units and the top perimeter of the combination curb. Install the
gasket around the top perimeter of the curb and around the sup-
ply and return opening. Gasket strips must fit tightly together,
leaving no gaps for leakage.
INSTALL ROOFING MATERIALS — Insulate and add a
cant strip to the combination curb. Follow suggested and ac-
ceptable roofing procedures for applying roofing materials.
The roofing material should extend up to the wood nailer and
be secured under the counter flashing. Follow all local, nation-
al, and industry roofing standards. Refer to Fig. 4 for roofing
recommendations.
INSTALLATION
Step 1 — Inspect the Unit — Inspect the unit; file a
claim with the shipping company if the unit is damaged. Check
the packing list to ensure that the correct items have been
received and notify your Carrier representative of any
discrepancy.
Step 2 — Install Combination Roof Curb
(62EB-EU Units) — For 62EB-EU units, the combina-
tion roof curb is a single curb that supports both the ERV and
RTU and has internal supply and exhaust air transitions. See
Fig. 1.
NOTE: For horizontal applications with 62E2-E7 units, a stan-
dard roof curb and horizontal transition can be used.
Step 3 — Install Drop-In Damper Box (62EB-
EU Units) — The drop-in damper box accessories are de-
signed to fit into the return air openings of the standard factory
curb of Carrier RTUs. The damper box provides connections
for return air from the conditioned space, exhaust air to the
ERV, and ventilation air from the ERV. The ERV would be in-
stalled on a stand-alone roof curb and field-supplied ductwork
would be run between the damper box and ERV curb. See
Fig. 5. The maximum length of the field-supplied duct is 100
equivalent feet.
LOCATE THE COMBINATION CURB — Prior to locat-
ing the combination curb, consider the structural support re-
quired for the rooftop system and the duct drop location in rela-
tion to the joists. Allow sufficient space for service, clearance,
and locations of vents or other sources of air. Refer to Fig. 2
and 3 for ERV clearance requirements. Refer to the rooftop in-
stallation instructions for more information regarding location
considerations.
PREPARE ROOF CURB LOCATION — Cut a hole in the
roof for duct openings. Your local Carrier sales representative
can provide dimensional drawing for the combination curb.
See this drawing for duct opening dimensions. Frame the open-
ing to provide adequate structural support.
SET THE COMBINATION CURB — Set the combination
curb over the roof opening. Level the curb by placing shims
under the bottom flange of the curb. Secure the curb in place by
welding or fastening the curb to the roof.
LOCATE THE ERV ROOF CURB — Prior to locating the
ERV roof curb consider the structural support required for the
rooftop system, the duct drop location in relation to the joists,
and the 100 equivalent foot duct length limitation between the
ERV and RTU. Allow sufficient space for service, clearance,
and locations of vents or other sources of air. Refer to Fig. 2
and 3 for ERV clearance requirements. Refer to the rooftop in-
stallation instructions for more information regarding location
and installation considerations for the RTU curb.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
ASSEMBLE THE ERV ROOF CURB — Connect the curb
side and the curb end. Insert the tabs on the curb end into the
slots on the curb sides. See Fig. 6. Press firmly until the pieces
lock into place. It may be necessary to exert additional force on
top of the curb to lock the pieces in place. Ensure the curb piec-
es are locked together prior to proceeding further. Repeat for
other corners of the roof curb.
NOTE: If lifting or moving the roof curb assembly, hammer
the tabs over 90 degrees.
PREPARE ROOF CURB LOCATION — Cut a hole in the
roof for duct openings. See Fig. 7 for duct opening dimensions.
Frame the opening to provide adequate structural support.
SET THE ERV ROOF CURB — Fit the roof curb assembly
by measuring across the corners of the curb to ensure a square
fit. Set the roof curb over the roof opening. Level the curb by
placing shims under the bottom flange of the curb. Secure the
curb in place by welding or fastening the curb to the roof.
INSTALL DUCTWORK — Ductwork will be installed in the
ERV roof curb for applications utilizing the drop-in damper
box. The duct will hang from the top of the curb. Refer to
Fig. 7 to determine the duct size required. Provide field-
manufactured duct and place into the supply and return open-
ings in the curb.
roofing procedures for applying roofing materials. The roofing
material should extend up to the wood nailer and be secured
under the counter flashing. Follow all local, national, and in-
dustry roofing standards. Refer to Fig. 4 for roofing recommen-
dations.
INSTALL DROP-IN DAMPER BOX — Place the damper
box into the RTU curb. Allow the damper box flanges to rest
on the curb. Secure the damper box in place with 1-in. self-tap-
ping screws. Install ductwork to connect the damper box to the
ERV curb. The upper damper box connection must be ducted
to the ERV supply air, and the lower damper box connection
must be ducted to the ERV exhaust air. See Fig 5. Refer to the
drop-in damper box dimensional sheets to determine the duct
size required. Your local Carrier sales representative can pro-
vide you with this dimensional data.
Step 4 — Install Horizontal Base and Transi-
tion (62EB-EU and 62E2-E7 Units) — The hori-
zontal transition accessory is used to connect the ERV to the
horizontal return of a Carrier rooftop unit. To provide horizon-
tal exhaust and ventilation air connections on 62EB-EU units,
the horizontal base accessory must also be installed. The acces-
sory is not needed on 62E2-E7 units. The rooftop unit must be
installed on a standard 14 in. high roof curb and positioned at a
specific distance relative to the ERV base. A typical arrange-
ment is shown in Fig. 8 and 9. See Fig. 10 for 62E2-E7 unit di-
mensions. Your local Carrier sales representative can provide
you with dimensional data for the appropriate Carrier RTU and
62E model installation.
NOTE: Ductwork must be installed in the ERV curb before the
ERV unit is set in place.
NOTE: Drop-in damper box must be installed in the RTU curb
before the RTU is set in place.
INSTALL GASKETS — The ERV roof curbs come with a
gasketing package to provide a seal between the ERV unit and
the top perimeter of the roof curb. Install the gasket around the
top perimeter of the curb and around the supply and return
opening. Gasket strips must fit tightly together, leaving no gaps
for leakage.
LOCATE THE ROOF CURB — Prior to locating the roof
curb consider the structural support required for the rooftop
system. Allow sufficient space for service, clearance, and loca-
tions of vent or other sources of air. Refer to Fig. 2, 3, and 10
for ERV clearance requirements. Refer to the rooftop installa-
tion instructions for more information regarding location
considerations.
Proper location of the roof curb in relationship to the RTU
roof curb is critical for proper fit of the horizontal transition.
See Fig. 8 and 9. Refer to the ERV unit submittals provided by
your local Carrier sales representative for the correct
dimensions.
IMPORTANT: Gasket installation is critical for water
integrity. Improperly installed gaskets can result in air or
water leaks, leading to poor unit performance.
INSTALL ROOFING MATERIALS — Insulate and add a
cant strip to the roof curb. Follow suggested and acceptable
LEGEND
ERV
RTU
— Energy Recovery Ventilator
— Rooftop Unit
NOTES:
1. Return air ductwork sits 12 in. below bottom of
curb. (Stub duct provided.)
2. Dimensions shown in inches.
Fig. 1 — Typical Combination Curb
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Fork Pockets (Remove Before Installing on Curb)
LEFT SIDE
a62-330
TOP VIEW
DIMENSIONS (in.)
62E UNIT
TYPE
A
B
C
D
E
F
G
H
I
J
B
C
D
E
H
K
31.138
38.625
44.425
54.625
67.045
77.625
36.000
18.000
18.000
20.000
20.000
27.000
36.000
36.000
45.000
55.000
65.000
75.000
37.645
45.183
45.043
53.562
59.022
64.972
34.559
42.078
41.938
50.458
55.918
61.868
5.850
8.916
8.916
11.677
11.677
11.677
5.757
35.076
43.875
49.675
59.875
72.294
82.875
24.971
32.471
38.271
48.495
60.915
71.495
11.801
15.485
18.260
22.997
29.207
34.247
14.239
14.239
19.165
25.164
25.164
DIMENSIONS (mm)
62E UNIT
TYPE
A
B
C
D
E
F
G
H
I
J
B
C
D
E
H
K
791
914
457
457
508
508
686
914
956
878
149
226
226
297
297
297
146
362
362
487
639
639
891
634
300
393
464
584
742
870
981
914
1148
1144
1360
1499
1650
1069
1065
1282
1420
1571
1114
1262
1521
1836
2105
825
1128
1387
1703
1972
1143
1397
1651
1905
972
1232
1547
1816
NOTES:
1. Clearance above cabinet is 24 inches (610 mm).
2. All dimensions shown in inches.
Fig. 2 — 62EB-62EK Vertical Unit Cabinet Dimensions
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Fork Pockets (Remove Before Installing on Curb)
LEFT SIDE
a62-331
TOP VIEW
DIMENSIONS (in.)
62E UNIT
TYPE
A
B
C
H
I
J
K
L
M
N
L
M
N
P
R
S
T
82.750
89.750
95.750
100.750
108.750
112.750
119.750
125.625
30.000
30.000
30.000
32.000
32.000
32.000
32.000
32.000
85.000
95.000
97.000
105.000
115.000
115.000
122.000
125.000
85.536
92.536
98.536
103.536
111.536
115.536
122.536
130.875
76.471
83.471
89.471
94.471
102.471
106.471
113.471
119.495
36.985
40.485
43.485
45.985
49.985
51.985
55.485
58.497
69.500
70.500
71.500
74.910
74.910
78.910
84.490
86.510
66.396
67.396
68.396
71.806
71.806
75.806
81.386
83.405
85.076
92.747
99.747
105.747
110.747
118.747
122.747
129.747
135.727
92.076
98.076
103.076
111.076
115.076
122.076
127.971
U
DIMENSIONS (mm)
62E UNIT
TYPE
A
B
C
H
I
J
K
L
M
N
L
M
N
P
R
S
T
2102
2280
2432
2559
2762
2864
3042
3191
762
762
762
813
813
813
813
813
2159
2413
2464
2667
2921
2921
3099
3175
2173
2350
2503
2630
2833
2935
3112
3324
1942
2120
2273
2400
2603
2704
2882
3035
937
1765
1791
1816
1903
1903
2004
2146
2197
1686
1712
1737
1824
1824
1925
2067
2118
2161
2339
2491
2618
2821
2923
3101
3250
2356
2534
2686
2813
3016
3118
3296
3447
1028
1105
1168
1270
1320
1409
1486
U
NOTES:
1. Clearance above cabinet is 36 inches (915 mm).
2. All dimensions shown in inches.
Fig. 3 — 62EL-62EU Unit Cabinet Dimensions
9
Download from Www.Somanuals.com. All Manuals Search And Download.
A62-247ef
GASKETING
ROOF CURB
NAIL*
RIGID
INSULATION*
FLASHING*
CANT STRIP*
ROOF FELT*
ROOF DECK*
ROOF*
*Field provided.
Fig. 4 — Roofing Materials — Recommendation
a62-376.eps
NOTE: All dimensions shown in inches.
Fig. 5 — Typical Installation with Drop-in Damper Box
A62-246ef
END
SIDE
Fig. 6 — Assembling the Roof Curb
10
Download from Www.Somanuals.com. All Manuals Search And Download.
"A"
I.D.
"B"
TYP. 2X
"C"
TYP. 2X
"A"
I.D.
a62-377
14.000
NOTES:
1. All dimensions shown in inches.
2. Nailer sits even with top of curb. Do not cover any existing holes with nailer.
62E
UNIT
TYPE
62E
UNIT
TYPE
DIMENSION DIMENSION DIMENSION
DIMENSION DIMENSION DIMENSION
A (in.)
B (in.)
C (in.)
A (in.)
B (in.)
C (in.)
B
C
D
E
H
K
L
27.221
34.721
40.521
50.721
63.141
73.721
78.721
24.721
32.221
38.021
48.221
60.641
71.221
76.221
10.861
14.611
17.511
22.611
28.821
34.111
36.611
M
N
P
R
S
T
85.721
91.721
83.221
89.221
40.111
43.111
45.611
49.611
51.611
55.111
58.111
96.721
94.221
104.721
108.721
115.721
121.721
102.221
106.221
113.221
119.221
U
62E
UNIT
TYPE
62E
UNIT
TYPE
DIMENSION DIMENSION DIMENSION
DIMENSION DIMENSION DIMENSION
A (mm)
B (mm)
C (mm)
A (mm)
B (mm)
C (mm)
B
C
D
E
H
K
L
691
882
628
818
276
371
445
574
732
866
930
M
N
P
R
S
T
2177
2330
2457
2660
2762
2939
3092
2114
2266
2393
2596
2698
2876
3028
1019
1095
1159
1260
1311
1400
1476
1029
1288
1604
1873
2000
966
1225
1540
1809
1936
U
Fig. 7 — 62EB-62EU Unit Curb Dimensions
11
Download from Www.Somanuals.com. All Manuals Search And Download.
a62-378
25.00
NOTE: All dimensions shown in inches.
Fig. 8 — Typical 62EB-EU Unit Installation with Horizontal Base and Horizontal Transition
RETURN AIR OPENING
ENERGY RECOVERY UNIT
HVAC UNIT
HORIZONTAL
TRANSITION
a62-443
SUPPLY OPENING
Fig. 9 — Typical 62E2-E7 Unit Installation
12
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD TERMINAL STRIP
ACCESS
OUTSIDE AIR
HOOD
"D"
DUCT O.D.
WHEEL AND FILTER
ACCESS
EXHAUST
HOOD
DUCT CONNECTION
SPACE
ROOF CURB
SEE NOTE 3
"C"
"A"
"B"
CLEARANCE
CLEARANCE
DISCONNECT
LOCATION
OUTSIDE AIR
HOOD
"E"
36.000
CLEARANCE
EXHAUST
HOOD
DUCT CONNECTION
SPACE IF NO HOODS
ROOF CURB
"F"
"I"
"J"
"D" - 2.000
DUCT I.D.
"K"
DUCT I.D.
S/A
"D"
DUCT O.D.
"G"
"H"
"K"
DUCT I.D.
R/A
ONLY DUCT SLEEVE AND
ERV AIR DIVIDER SHOWING
DIMENSIONS (in.)
62E UNIT TYPE
A
B
C
D
E
F
G
H
I
J
K
7
2
3
4
5
6
36.000
18.000
18.000
18.000
24.000
18.000
36.000
36.000
40.000
50.000
64.000
75.000
1.869
1.179
3.795
4.238
4.516
9.542
28.995
36.495
42.295
52.495
64.915
75.495
31.734
39.171
44.847
55.066
67.486
78.066
36.375
43.875
49.675
59.875
72.295
82.875
32.176
39.663
45.463
55.673
68.093
78.673
31.186
38.673
44.473
54.673
67.093
77.673
11.984
16.215
16.215
21.132
27.131
27.131
36.905
41.239
41.099
49.631
53.013
58.963
12.813
16.497
19.272
23.997
30.207
35.247
DIMENSIONS (mm)
62E UNIT TYPE
A
B
C
D
E
F
G
H
I
J
K
7
2
3
4
5
6
914
457
457
457
610
457
914
47
736
806
924
817
1007
1155
1414
1730
1998
792
304
412
412
537
689
689
937
325
419
490
610
767
895
914
30
927
995
1114
1262
1521
1836
2105
982
1047
1044
1261
1347
1498
1016
1270
1626
1905
96
1074
1333
1649
1918
1139
1399
1714
1983
1130
1389
1704
1973
108
115
242
NOTES:
1. Clearance above cabinet is 24 in. (610 mm).
2. Dimensions are in inches.
3. Size the roof curb to allow for a clearance of 10-in. (254 mm) (minimum) between
the bottom of the exhaust hood and the top of the insulated roof material.
Fig. 10 — 62E2-62E7 Unit Cabinet Dimensions
13
Download from Www.Somanuals.com. All Manuals Search And Download.
ASSEMBLE THE ROOF CURB — Connect the curb side
and the curb end. Insert the tabs on the curb end into the slots
on the curb sides. See Fig 6. Press firmly until the pieces lock
in to place. It may be necessary to exert additional force to the
top of the curb to lock the pieces in place. Ensure the curb piec-
es are locked together prior to proceeding. Repeat for other cor-
ners of the roof curb. See Fig. 7 and 11 for roof curb dimen-
sions.
NOTE: If lifting or moving the roof curb assembly hammer
the tabs over 90 degrees.
14
"D"
A
A
"C"
ERV RAIL SITS DOWN
IN CHANNEL
.500
"B" I.D.
"B" I.D.
.941
B
DETAIL B
SCALE 1 : 3
SECTION A-A
14.559
"A"
"E"
DIMENSIONS (mm)
DIMENSIONS (in.)
62E UNIT
TYPE
62E UNIT
TYPE
A
B
C
D
E
A
B
C
D
E
7
2
3
4
5
6
718
258
354
428
557
715
849
797
938
859
7
2
3
4
5
6
28.286 10.143 31.397 36.927 33.816
35.882 13.941 38.993 40.446 37.335
41.682 16.841 44.793 40.306 37.195
51.882 21.941 54.993 48.826 45.715
64.302 28.151 67.413 54.286 51.175
74.882 33.441 77.993 60.236 57.125
911
990
1027
1024
1240
1379
1530
948
1059
1318
1633
1902
1138
1397
1712
1981
945
1161
1300
1451
a62-442
NOTE: Dimensions are in inches.
Fig. 11 — 62E2-62E7 Unit Roof Curb Dimensions
Apply the factory provided gasketing material to the top of
the horizontal base. Follow the rigging directions in the
Step 6 — Rig and Place Unit section to place the ERV on the
horizontal base. Position the ERV so that the ERV's LCD (liq-
uid crystal diode) display is on the opposite side of the horizon-
tal base's duct openings. Secure the ERV to the horizontal base
using 1-in. self-tapping sheet metal screws every 18 in. around
the perimeter.
NOTE: The ERV may also be mounted to the horizontal base
prior to being set on the roof curb.
Install Ductwork — Ductwork will be connected to the hori-
zontal box (62EB-EU units) or directly to the ERV (62E2-E7
units) for stand-alone horizontal discharge and exhaust applica-
tions. See Fig. 12 for the horizontal box connection dimen-
sions. See Fig. 10 for 62E2-E7 connection dimensions. Do not
support the duct from the horizontal box. Provide field
15
Download from Www.Somanuals.com. All Manuals Search And Download.
manufactured duct and attach to the supply and exhaust open-
ings on the horizontal box.
Spreader bars must be positioned to prevent cables from rub-
bing against the ERV unit.
Step 6 — Rig and Place Unit — To transfer the unit
from the shipping platform to the storage or installation site, re-
fer to the rigging label on the unit and these instructions.
WARNING
Never attempt to lift the ERV in any way that does not use
all four (4) eyehooks. Lifting the unit with an uneven distri-
bution of the weight may cause damage to the unit and/or
personal injury or death.
CAUTION
All panels must be in place when rigging. Unit is not
designed for handling by fork truck. Damage to unit may
result.
IMPORTANT: Remove the fork pockets from the ERV
unit before setting it on the roof curb.
Refer to Tables 1A and 1B for ERV unit weights. Check lift-
ing devices for capacity constraints.
Hook rigging shackles through the eyehooks in the ERV
unit. Connect lifting straps and spreader bars. See Fig 13.
Carefully lift the ERV unit and set on ERV roof curb. Do
not drop the ERV unit onto the roof curb, as damage may oc-
cur. Avoid twisting or uneven lifting of the unit. Never lift the
unit by the hoods or any means other than the provided lifting
holes or eyes.
FORK POCKETS (REMOVE
BEFORE INSTALLING ON CURB)
DIMENSIONS (in.)
C
62E UNIT
TYPE
A
B
D
E
B
C
D
E
H
K
L
M
N
P
R
27.221
34.721
40.521
50.721
63.141
72.721
78.721
85.721
91.721
96.721
12.111
15.861
18.761
23.861
30.071
34.861
37.861
41.361
44.361
46.861
8.750
14.000
14.000
18.000
21.000
24.000
26.022
26.022
26.022
31.011
33.052
22.604
22.604
26.600
29.604
32.604
34.637
34.637
34.637
39.615
41.682
12.500
15.400
20.500
26.710
31.500
34.500
38.000
41.000
43.500
16
on the ERV field control terminal strip. This will enable the
ERV to turn on and run.
EYE HOOK
(HIDDEN)
If the HVAC unit has an integrated economizer or power ex-
haust, it is sometimes necessary to provide an interface be-
tween the HVAC unit and the ERV controls to ensure proper
operation of the ERV’s supply/exhaust fan and energy recovery
wheel motors. The 62E has discrete inputs for this purpose and
damper end switches or relays may be used to coordinate the
economizer and power exhaust operation with the ERV.
EYE HOOK
When an ERV is mated to an electro-mechanical rooftop
unit with an economizer and a power exhaust, terminals C and
G on the ERV field control terminal strip are still connected to
the corresponding terminals on the rooftop unit cabinet (jumper
across R and G needs to be removed). However, in addition,
field supplied and installed end switches are required to coordi-
nate operation with the unit. For unit economizer operation, it
is necessary to install an Normally Open end switch (field pro-
vided) on the economizer actuator and connect to terminals 5
and 6 (ERV Shutdown) on the ERV terminal strip. This will
cause the ERV to shut down during unit economizer operation.
For power exhaust, based on building pressure control, no ad-
ditional ERV wiring is required, however if the ERV is to pro-
vide power exhaust functionality then a field-installed Normal-
ly Closed end switch is required to be installed between termi-
nals 7 and 8 on the ERV terminal strip.
a62-380
EYE HOOKS
FORK POCKETS
Fig. 13 — Rigging and Handling
Step 7 — Make Electrical Connections
WARNING
Prior to performing service or maintenance operations on
the ERV unit, turn off and disconnect all power switches to
the unit. Be aware that there may be more than one discon-
nect switch. Electrical shock could cause serious personal
injury or death.
High Voltage Wiring — Connect high voltage wiring to the
disconnect, see Fig. 14. Route the power wires in water tight
conduit from the disconnect switch box to the ERV distribution
block. To gain access to high voltage block, remove panel
marked with label stating, “High voltage terminal block locat-
ed behind this panel.”
IMPORTANT: Only trained, qualified installers and ser-
vice technicians should install, wire, start-up and service
equipment.
Table 3 — ERV Wheel Motor and Control
Transformer Electrical Data
CONTROL
POWER SUPPLY — The electrical characteristics of the
available power supply must agree with the unit nameplate
rating. Supply voltage must be within the limits shown. See Ta-
bles 3-5 for electrical and configuration data.
ELECTRICAL CONNECTIONS — The ERV unit must
have its own electrical disconnect box. If the disconnect option
has not been ordered from the factory, it must be field supplied
and installed per local codes. See Tables 3-5.
ERV WHEEL MOTOR
UNIT
V-Ph
TRANSFORMER
UNIT
V-Ph
115-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-1
230-3
460-3
460-3
575-3
230-3
460-3
460-3
575-3
230-3
460-3
460-3
575-3
230-3
460-3
460-3
575-3
W
80.5
FLA
0.70
0.30
0.30
0.15
0.15
0.12
0.30
0.30
0.15
0.15
0.12
0.30
0.15
0.15
0.12
1.04
0.52
0.52
0.30
0.75
0.38
0.38
0.30
2.50
1.20
1.20
0.95
3.40
1.70
1.70
1.40
V
FLA
0.65
0.33
0.33
0.16
0.16
0.13
0.33
0.33
0.16
0.16
0.13
0.33
0.16
0.16
0.13
0.33
0.16
0.16
0.13
0.33
0.16
0.16
0.13
0.33
0.16
0.16
0.13
0.33
0.16
0.16
0.13
115-1
230-1
230-3
400-3
460-3
575-3
230-1
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
69.0
69.0
62EB,E7
69.0
69.0
69.0
69.0
If the ERV unit has an electric pre-heater factory installed, it
will be wired through the ERV unit disconnect.
69.0
62EC,E2
69.0
Low Voltage Wiring — Wire low voltage per Fig. 14. The
field connection terminal strip is located behind the panel that
is adjacent to the control box. The correct panel is marked with
a green label stating “Attention: For field control of ERV, re-
move this panel to gain access to ERV field control terminal
strip.” The wires connecting to the field terminal strip can be
69.0
69.0
69.0
69.0
62ED,E3
62EE,E4
62EH,E5
69.0
69.0
3
routed through the nearest /4-in. hole and through conduit to
138.3
138.3
138.3
99.7
the RTU, or they can be routed down the sidewall of the cabi-
net using the wire pull provided and routed through the combi-
nation curb to the RTU.
99.7
101.0
101.0
99.7
CAUTION
When routing wires in the ERV always keep them away
from moving parts and sharp metal edges. Follow all local
and state codes when routing the ERV control wires.
332.4
319.1
319.1
315.8
452.0
452.0
452.0
465.3
62EK,EL,EM,
EN,EP,E6
If the ERV unit is mated to a RTU, terminals C and G on the
field control terminal strip of the ERV unit are connected to the
corresponding terminals on the RTU cabinet. Verify the jumper
is removed from the “ERV R” and “G” terminals; not doing so
may damage RTU control equipment.
When the ERV is to be run as a stand-alone configuration,
verify that a jumper is shorting the “ERV R” and “G” terminals
62ER,ES,
ET,EU
LEGEND
FLA
—
Full Load Amps
W
—
Watts
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4 — Supply and Exhaust Fans Electrical Data
FAN MOTOR
W
FAN
OPTION
62E
CHASSIS
UNIT
V-Ph
V-Ph
115-1
230-1
230-1
200-1
230-1
230-1
115-1
115-1
115-1
115-1
115-1
115-1
230-1
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
FLA
3.96
1.74
1.74
0.87
0.87
0.70
3.96
1.98
1.98
0.99
0.99
0.79
1.72
2.21
1.11
1.11
0.88
2.21
1.11
1.11
0.88
6.79
3.39
3.39
2.71
6.79
3.39
3.39
2.71
6.79
3.39
3.39
2.71
6.79
3.39
3.39
2.71
6.79
3.39
3.39
2.71
6.79
3.39
3.39
2.71
7.29
3.64
3.64
2.92
Qty
1
1
1
1
1
1
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
5
5
5
5
6
6
6
6
1
1
1
1
115-1
230-1
230-3
460-3
460-3
575-3
115-1
230-1
230-3
400-3
460-3
575-3
230-1
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
455
400
400
400
400
400
455
455
455
455
455
455
395
880
880
880
A
B
B,7
B,7
C,2
C
880
880
880
880
D,E,3,4
880
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2700
2900
2900
2900
2900
E,H,K,
4,5,6
E
F
H,K,L,
M,N,P,
4,6
L,M,N,
P, R
G
H
J
R,S,
T,U
R,S,
T,U
K
S,T,U
H,K,L
L
LEGEND
FLA — Full Load Amps
Qty — Quantity
W
— Watts
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4 — Supply and Exhaust Fans Electrical Data (cont)
FAN MOTOR
W
FAN
62E
UNIT
V-Ph
OPTION
CHASSIS
V-Ph
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
230-3
460-3
460-3
460-3
FLA
7.29
3.64
3.64
2.92
7.29
3.64
3.64
2.92
6.79
3.39
3.39
2.71
6.79
3.39
3.39
2.71
Qty
2
2
2
2
3
3
3
3
7
7
7
7
8
8
8
8
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
2900
2900
2900
2900
2900
2900
2900
2900
2700
2700
2700
2700
2700
2700
2700
2700
K,L,M,
N,P,R
M
N
P
R,S,
T,U
T,U
T,U
R
LEGEND
FLA — Full Load Amps
Qty — Quantity
W
— Watts
Table 5 — Electric Heat Electrical Data
HEATER
UNIT AND HEATER
V-Ph
62E CHASSIS
kW
FLA
17.39
8.70
5.03
2.51
2.51
115-1
230-1
230-3
400-3
460-3
575-3
115-1
230-1
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
B,7
B,C,2,7
B,C,D,E,2,3,4,7
B,C,D,E,2,3,4,7
B,C,D,E,2,3,4,7
B,C,D,E,2,3,4,7
B,7
2
2.01
43.48
21.74
12.57
6.28
6.28
5.03
20.11
10.05
10.05
8.04
25.13
12.57
12.57
10.05
37.70
18.85
18.85
15.08
50.26
25.13
25.13
20.11
B,C,2,7
B,C,D,E,H,2,3,4,5,7
B,C,D,E,H,2,3,4,5,7
B,C,D,E,H,2,3,4,5,7
B,C,D,E,H,2,3,4,5,7
D,E,H,3,4,5
5
D,E,H,3,4,5
D,E,H,3,4,5
D,E,H,3,4,5
8
E,H,K,L,4,5,6
E,H,K,L,4,5,6
E,H,K,L,4,5,6
E,H,K,L,4,5,6
H,K,L,M,N,5,6
H,K,L,M,N,5,6
H,K,L,M,N,5,6
H,K,L,M,N,5,6
H,K,L,M,N,P,5,6
H,K,L,M,N,P,5,6
H,K,L,M,N,P,5,6
H,K,L,M,N,P,5,6
10
15
20
LEGEND
FLA — Full Load Amps
— Watts
W
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Electric Heat Electrical Data (cont)
HEATER
UNIT AND HEATER
62E CHASSIS
V-Ph
kW
25
FLA
62.83
31.42
31.42
25.13
75.40
37.70
37.70
30.16
87.96
43.98
43.98
35.18
100.53
50.26
50.26
40.21
113.09
56.55
56.55
45.24
125.66
62.83
62.83
50.26
138.23
69.11
69.11
55.29
150.79
75.40
75.40
60.32
163.36
81.68
81.68
65.34
175.92
87.96
87.96
70.37
188.49
94.24
94.24
75.40
201.06
100.53
100.53
80.42
213.62
106.81
106.81
85.45
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
230-3
400-3
460-3
575-3
H,K,L,M,N,P,R,S,5,6
H,K,L,M,N,P,R,S,5,6
H,K,L,M,N,P,R,S,5,6
H,K,L,M,N,P,R,S,5,6
K,L,M,N,P,R,S,T,U,6
K,L,M,N,P,R,S,T,U,6
K,L,M,N,P,R,S,T,U,6
30
35
40
45
50
55
60
65
70
75
80
85
K,L,M,N,P,R,S,T,U,6
L,M,N,P,R,S,T,U
L,M,N,P,R,S,T,U
L,M,N,P,R,S,T,U
L,M,N,P,R,S,T,U
M,N,P,R,S,T,U
M,N,P,R,S,T,U
M,N,P,R,S,T,U
M,N,P,R,S,T,U
N,P,R,S,T,U
N,P,R,S,T,U
N,P,R,S,T,U
N,P,R,S,T,U
P,R,S,T,U
P,R,S,T,U
P,R,S,T,U
P,R,S,T,U
R,S,T,U
R,S,T,U
R,S,T,U
R,S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
S,T,U
T,U
T,U
T,U
T,U
U
U
U
U
U
U
U
U
LEGEND
FLA — Full Load Amps
— Watts
W
20
Download from Www.Somanuals.com. All Manuals Search And Download.
ERV OPTION BOARD #2
ERV OPTION BOARD #1
Fig. 14 — Typical Wiring Schematic
21
Download from Www.Somanuals.com. All Manuals Search And Download.
cassette through the wheel center. Tighten the screws so the air
seals tug slightly on the sheet of paper as the wheel is turned.
Re-check the air seals for tightness after adjustment.
START-UP
Use the following information to check unit PRIOR to start-up.
Replace the access door and apply power. Check that the
wheel rotates freely. If the wheel does not rotate or is binding,
remove the cassette and adjust.
For units with three phase power only: Remove the ser-
vice door to make sure the wheel is turning in the same direc-
tion as the sticker next to the motor shows. See Fig. 15. If the
wheel is turning in the wrong direction turn, off the disconnect
switch and have a qualified electrician swap any 2 of the power
leads on the load side of the disconnect switch.
CAUTION
Before turning the disconnect switch on, verify that the
voltage being provided to the ERV unit matches the volt-
age shown on the ERV nameplate. Failure to do so could
result in equipment damage.
Unit Preparation — Check that the unit has been in-
stalled in accordance with these installation instructions and all
applicable codes.
Check all fasteners and set screws for tightness. Verify that
all of the panels are in place and secure. Verify that any open-
ings to the ERV cabinet are clear of foreign materials.
Airflow Settings and Adjustments — With the
disconnect on, the display should show "ERV FAN SPEED"
on the top line of the display. The bottom line of the display
should show "OA=XXX EX=XXX" where the “X”s represent
the blower output percentage for the outside air blowers and
the exhaust air blowers.
Internal Wiring — Check all electrical connections in the
control box. Tighten as required.
NOTE: If any of the alarms are tripped, the LCD display will
scroll between the alarms and the normal display.
Rain Hoods — The outside air hood will include alumi-
num water entrainment filters, which should be in place prior
to starting the unit.
To measure the airflow the ERV units have factory-installed
airflow test ports, which allow the balancer of the job to easily
measure the static pressure across the ERV wheel. The static
pressure is measured on both the supply and return sides of the
wheel. Take this pressure reading and match up the wheel dif-
ferential pressure ( P) to pressure chart to display the cfm that
is flowing through the ERV wheel. See Table 6.
To balance the airflow remove the small panel next to the
control panel cover to access the user input controls. Press the
push button and turn the knob clockwise to increase or counter-
clockwise to decrease the outside air blower speed (use the test
ports and charts described above to calculate cfm levels). Press
the push button again to change the exhaust air blower speed.
Press the button again to return to the main screen. Replace the
user control cover when ERV cabinet is operating at the correct
blower speeds.
Energy Recovery Wheel
DRIVE BELT — Turn the energy recovery wheel by hand to
verify free operation. Inspect the belt, which drives the energy
wheel rotation. Make sure the belt rides smoothly through the
pulley and over the wheel rim.
AIR SEALS — Check that the air seals located around the
outside of the wheel and across the center, on both sides of the
wheel, are secure and in good condition. Air seals which are
too tight will prevent proper rotation of the energy recovery
wheel.
Air seal clearance may be checked by placing a sheet of pa-
per, like a feeler gage, against the wheel face. To adjust the air
seals, loosen all eight seal retaining screws. These screws are
located on the bearing support that spans the length of the
a62-383.eps
Fig. 15 — ERV Wheel Rotation
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 6 — Airflow vs. Pressure Drop Across ERV Wheel
62E UNIT
BA,7A
AIRFLOW VS. PRESSURE DROP ACROSS ERV WHEEL
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
94
47
94
60
118 142 165 189 212 236 260 283 307 330 354
62 77 95 109 127 142 157 174 189 207 221
118 142 165 189 212 236 260 283 307 330 354
75 90 104 119 134 149 164 179 194 209 224
378
239
378
239
519
261
472
261
566
251
—
—
—
—
—
425
1.08
—
—
—
—
—
—
—
—
—
—
—
—
—
—
661
296
—
—
—
—
—
—
—
401
254
543
274
496
274
590
261
—
—
—
—
—
BC,7C
CC,2C
CD,2D
CG,2G
DD,3D
DG,3G
EB,4B
ED,4D
236 260 283 307 330 354 378 401 425 448 472 496
112 124 137 149 162 174 187 199 211 224 236 249
189 212 236 260 283 307 330 354 378 401 425 448
112 124 137 149 162 174 187 199 211 224 236 249
283 307 330 354 378 401 425 448 472 496 519 543
112 124 137 147 159 169 182 194 204 216 229 239
—
—
519
286
614
274
—
—
—
—
—
543
299
637
286
—
—
—
—
—
283 330 378 425 472 519 566 614 661 708 755
114 132 149 167 184 199 216 234 251 269 286
—
—
—
425 472 519 566 614 661 708 755 802 850 897 944
117 132 149 164 179 197 211 226 244 259 274 291
—
—
378 425 472 519 566 614 661 708 755 802 850
164 177 192 207 221 234 249 264 276 291 306
—
—
—
—
—
1133
—
1180
—
1227
519 566 614 661 708 755 802 850 897 944 991 1038 1086
NOTE: Pressure sensing ports are provided on both sides of the
ERV wheel for testing and balancing.
23
Table 6 — Airflow vs. Pressure Drop Across ERV Wheel (cont)
62E
UNIT
AIRFLOW VS. PRESSURE DROP ACROSS ERV WHEEL
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
l/s
pa
1652 1888 2124 2360 2596 2832 3068 3304 3540 3776 4012 4248 4484
—
—
—
—
—
—
—
—
LD
LG
MD
MG
ND
NG
PD
PG
RD
RG
SD
SG
TD
TG
UD
UG
114
129
147
162
179
194
211
226
244
261
276
294
304
2360 2832 3068 3304 3540 3776 4012 4248 4484 4720 4956 5192 5428 5664 5900 6136 6372
122
2124 2360 2596 2832 3068 3304 3540 3776 4012 4248 4484 4720 4956 5192
124 139 152 167 179 194 207 221 234 249 264 276 291 304
144
154
164
177
187
197
209
219
229
239
251
261
271
284
—
—
294
—
—
304
—
—
2832 3304 3776 4248 4720 4956 5192 5428 5664 5900 6136 6372 6608 6844 7080 7316 7552
124 142 162 179 197 207 216 224 234 244 251 261 271 279 289 299 306
2596 2832 3068 3304 3540 3776 4012 4248 4484 4720 4956 5192 5428 5664 5900 6136 6372
124
3540 4012 4484 4956 5428 5900 6372 6844 7316 7788 8260 8732 9204
127 142 157 172 187 202 216 231 246 261 276 291 306
137
147
159
169
182
192
204
214
226
239
249
261
271
—
—
284
—
—
294
—
—
306
—
—
2832 3304 3776 4012 4248 4484 4720 4956 5192 5428 5664 5900 6136 6372 6608 6844 7080
119
3776 4248 4720 5192 5664 6136 6608 7080 7552 8024 8496 8968 9440 9912 10384
119 134 147 159 172 187 199 211 226 239 251 264 279 291 304
139
159
169
179
189
199
209
219
229
239
249
259
269
279
289
—
—
299
—
—
3304 3776 4248 4720 5192 5428 5664 5900 6136 6372 6608 6844 7080 7316 7552 7788 8024
127
4248 4720 5192 5664 6136 6608 7080 7552 8024 8496 8968 9440 9912 10384 10856 11328
122 134 147 159 169 182 194 207 216 229 241 254 266 276 289 301
144
162
182
199
209
216
226
234
244
254
264
271
281
289
299
309
—
—
3776 4248 4720 5192 5664 6136 6372 6608 6844 7080 7316 7552 7788 8024 8260 8496 8732
122 137 152 167 182 197 204 211 219 226 234 241 249 256 264 271 279
5192 6136 7080 7552 8024 8496 8968 9440 9912 10384 10856 11328 11800 12272 12744 13216 13688
124
4248 4720 5192 5664 6136 6608 7080 7552 8024 8496 8968 9440 9912 10384
127 139 154 167 182 197 209 224 236 251 266 279 294 306
144
164
174
184
194
204
214
224
234
244
254
264
274
284
—
—
294
—
—
304
—
—
5664 6608 7552 8496 8968 9440 9912 10384 10856 11328 11800 12272 12744 13216 13688 14160 14632
124
4720 5192 5664 6136 6608 7080 7552 8024 8496 8968 9440 9912 10384 10856 11328 11800
100 134 147 159 172 184 197 207 219 231 244 256 269 281 294 306
144
162
182
189
199
209
216
226
236
246
254
264
274
281
291
301
—
—
6608 7552 8496 9440 10384 11328 11800 12272 12744 13216 13688 14160 14632 15104 15576 16048 16520
127
144
159
177
192
209
216
224
231
241
249
256
264
274
281
289
296
NOTE: Pressure sensing ports are provided on both sides of the
ERV wheel for testing and balancing.
UNITS WITH EZERV CONTROL OPTION — With
the EzERV option, the LCD display will change to show the
amount of air moving through the cabinet in cubic feet per
minute (cfm). The screen is divided into two columns: The left
column showing the amount of outside air (Osa/CFM) and the
right column showing the exhaust air (Ext/CFM). To adjust the
fan speeds, remove the small panel next to the control panel
cover to access the user input controls. See Fig. 16.
Fig. 17 — ERV Cfm Screen
a62-385.eps
Offset Air Option — Press the push button once to bring up
the outside air cfm screen. Turn the knob clockwise to increase
or counterclockwise to decrease the amount of outside air com-
ing into the building. See Fig. 18.
a62-384.eps
Fig. 16 — LCD Display
Balanced Air Option — Press the push button once to bring
up the ERV cfm screen. Turn the knob clockwise to increase or
counterclockwise to decrease the amount of outside air coming
into the building. See Fig. 17. The exhaust airflow will auto-
matically adjust to equal the supply airflow. Press the button
again to return to the main screen. Replace the user control
cover.
-386.eps Fig. 18 — Outside Air Cfm Screen
Press the push button again to bring up the exhaust air offset
screen. A negative exhaust air offset would equate to a smaller
amount of air being exhausted from the building when com-
pared to the outside air being supplied to the building. Adjust
the knob clockwise to increase and counterclockwise to de-
crease the exhaust offset cfm level. See Fig. 19. Press the
24
Download from Www.Somanuals.com. All Manuals Search And Download.
button again to return to the main screen. Replace the user con-
trol cover.
exhaust air offset screen. A negative exhaust air offset would
equate to a smaller amount of air being exhausted from the
building when compared to the outside air being supplied to the
building. Adjust the knob clockwise to increase and counter-
clockwise to decrease the exhaust offset cfm level. Press the
button again to return to the main screen. Replace the user con-
trol cover.
Building Pressure Control Option — This option will hold
the outside air cfm level constant and will modulate the exhaust
airflow to maintain the building pressure set point. Press the
push button once to bring up the ERV cfm screen. Turn the
knob clockwise to increase or counterclockwise to decrease the
amount of outside air coming into the building. Press the push
button again to display the "Building Pressure Set Point"
screen. Adjust the knob clockwise to increase and counter-
clockwise to decrease the desired building pressure level. Press
the button again to return to the main screen. Replace the user
control cover.
Fig. 19 — Exhaust Air Offset Screen
387.eps
Modulating CO2 with Balanced Air Option (Fig. 20) —
This option allows the user to enter minimum and maximum
outside airflow levels. The user will then be allowed to enter
minimum and maximum CO2 levels. The EzERV program will
modulate the cfm of the ERV based on the building CO2 level.
To enter the user settings press the pushbutton once to display
the minimum cfm screen. Adjust the knob clockwise to
increase and counterclockwise to decrease the minimum cfm
level.
Modulating CO2 with Building Pressure Control Option —
This option will modulate the supply fan of the ERV based on
the building CO2 level, and will modulate the exhaust airflow
to maintain the building pressure set point. Follow the proce-
dure outlined above to configure the minimum and maximum
outside airflow and CO2 levels. After setting the maximum
CO2 level press the push button once more to display the build-
ing pressure set point screen. Adjust the knob clockwise to
increase and counterclockwise to decrease the desired building
pressure level. Press the button again to return to the main
screen. Replace the user control cover.
a62-388.eps
Fig. 20 — Modulating Cfm
Press the push button again to display the maximum cfm
screen. Adjust the knob clockwise to increase and counter-
clockwise to decrease the maximum cfm level. See Fig. 21.
Operating Sequence — When operation is called for
by the rooftop supply fan interlock or remote timer option, the
ERV supply blower(s), exhaust blower(s) and wheel motor will
be energized. The supply and exhaust blowers will provide the
adjusted/programmed airflow and the ERV wheel will rotate at
a constant speed unless influenced by one of the following con-
ditions. The sequence of operation is shown in Fig. 24.
LOW TEMPERATURE LOCKOUT — The optional low
temperature lockout function locks out the 62E ERV if the out-
door-air temperature entering the wheel is below the set point.
The low temperature lockout is factory set at –23.3 C (–10 F),
and can be field adjusted from –34.4 C to 37.8 C (–30 F to
100 F).
Fig. 21 — Maximum Cfm Screen a62-389.eps
Press the push button again to display the minimum CO2
level screen. Adjust the knob clockwise to increase and coun-
terclockwise to decrease the minimum CO2 level. See Fig. 22.
FROST PROTECTION — The frost protection option moni-
tors the pressure drop across the ERV wheel. If the pressure
drop rises above an adjustable limit, the outside air fan will be
de-energized for a 5-minute period. The setting must be field
set at 50% above (1.5 times) the pressure drop measured at the
maximum adjusted airflow and a clean, dry wheel.
ERV WHEEL VARIABLE FREQUENCY DRIVE
(VFD) — The ERV wheel VFD option monitors the pressure
drop across the ERV wheel. If the pressure drop rises above an
adjustable limit, the ERV wheel rotational speed will be re-
duced for a minimum of 5 minutes to defrost the wheel. The
setting must be field set at 50% above (1.5 times) the pressure
drop measured at the maximum adjusted airflow and a clean,
dry wheel.
Fig. 22 — Minimum CO2 Screena62-390.eps
Press the push button again to display the maximum CO2
level screen. Adjust the knob clockwise to increase and coun-
terclockwise to decrease the maximum CO2 level. See Fig. 23.
Fig. 23 — Maximum CO2 Screen a62-391.eps
The exhaust airflow will automatically adjust to equal the
supply airflow. Press the button again to return to the main
screen. Replace the user control cover.
NOTE: The scale for the cfm vs. CO2 level is based on a CO2
sensor that outputs 0-vdc at 0 ppm CO2 and 10-vdc at
2000 ppm CO2. For example, using the figures above, the air-
flow would modulate linearly from 1458 L/s (3090 cfm) at
3vdc to 2336 L/s (4950 cfm) at 5-vdc. A signal below 3-vdc
would result in a constant 1458 L/s (3090 cfm) while a signal
above 5-vdc would result in a constant 2336 L/s (4950 cfm).
PRE-HEATERS — Units may be equipped with electric pre-
heaters to prevent frost build-up on the wheel by slightly
warming the outdoor air. This feature monitors the pressure
drop across the ERV wheel and the outdoor-air temperature. If
the pressure drop rises above an adjustable limit and the out-
door-air temperature is below an adjustable set point, the heat-
ers will be energized. The wheel pressure drop setting must be
field set at 50% above (1.5 times) the pressure drop measured
at the maximum adjusted airflow and a clean, dry wheel. The
outdoor air thermostat is factory set to activate at –20.6 C
(–5 F), and can be field adjusted from –34.4 C to 37.8 C (–30 F
to 100 F).
Modulating CO2 with Offset Air Option — Follow the steps
above for modulating CO2 with balanced air. After setting the
maximum CO2 level press the push button again to display the
25
Download from Www.Somanuals.com. All Manuals Search And Download.
HVAC Supply Fan On
or ERV Timer Option Active
or Stand Alone Short
Pins 31 to 30 and 29 to 28
FALSE
TRUE
TRUE
Low Temp
Lock Out
FALSE
ERV Wheel Off
Option 51
Lockout
Activated
Wheel Maintenance Indicator Off
Supply Blower Maintenance Indicator Off
Exhaust Blower Maintenance Indicator Off
Supply Blower Off
Exhaust Blower Off
2-Pos Motor Closed
TRUE
FALSE
CO2 Level
Not High
Enough in
Space
TRUE
TRUE
FALSE
Economizer
Full Open
End Switch
ERV Wheel On
Wheel Maintenance Indicator On
Supply Blower Maintenance Indicator Off
Exhaust Blower Maintenance Indicator On
Supply Blower Off
Exhaust Blower On
2-Pos Motor Open
FALSE
Frost Option
Wheel Iced
TRUE
TRUE
FALSE
ERV Wheel Modulating
Supply Blower On
Exhaust Blower On
2-Pos Motor Open
Wheel Maintenance Indicator On
Supply Blower Maintenance Indicator On
Exhaust Blower Maintenance Indicator On
Frost Option
Wheel Iced
VFD
FALSE
ERV Wheel Stop/Jog
Supply Blower Off
Exhaust Blower On
2-Pos Motor Open
ERV Power
Exhaust
Mode
Wheel Maintenance Indicator On
TRUE
TRUE
Supply Blower Maintenance Indicator Off
Exhaust Blower Maintenance Indicator On
FALSE
Free Cooling
ERV Wheel Stop/Jog
Supply Blower On
Exhaust Blower On
2-Pos Motor Open
Wheel Maintenance Indicator On
Supply Blower Maintenance Indicator On
Exhaust Blower Maintenance Indicator On
Dry Bulb Enthalpy
Option and W1
and G are Off
FALSE
ERV Wheel On
Preheat available if
pressure or temperature
are correct for usage
Wheel Maintenance Indicator On
Supply Blower Maintenance Indicator On
Exhaust Blower Maintenance Indicator On
Supply Blower On
Exhaust Blower On
2-Pos Motor Open
Fig. 24 — ERV Sequence of Operation
a62-540
26
Download from Www.Somanuals.com. All Manuals Search And Download.
MOTORIZED DAMPERS — Units may have an optional
two-position outside-air damper, exhaust-air damper, or both.
The dampers will modulate closed when the ERV is off.
MODULATING CO2 CONTROL — The supply fan speed
27
BT485
TERMINATOR
BACNET
CONNECTION
(BAS PORT)
POWER LED
Tx1 LED
Rx1 LED
Tx2 LED
Rx2 LED
BACNET
BAUD RATE
DIP SWITCHES
EIA-485
JUMPERS
ADDRESS
ROTARY
SWITCHES
RUN LED
ERROR LED
Fig. 25 — UPC Open Controller
Fig. 26 — Network Wiring
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 27 — BT485 Terminator Installation
Table 8 — MS/TP Wiring Recommendations
SPECIFICATION
Cable
Conductor
Insulation
Color Code
Twist Lay
RECOMMMENDATION
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
22 or 24 AWG stranded copper (tin plated)
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Black/White
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Aluminum/Mylar shield with 24 AWG TC drain wire
Shielding
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
Jacket
DC Resistance
Capacitance
Characteristic Impedance
Weight
15.2 Ohms/1000 feet (50 Ohms/km) nominal
12.5 pF/ft (41 pF/meter) nominal conductor to conductor
100 Ohms nominal
12 lb/1000 feet (17.9 kg/km)
UL Temperature Rating
Voltage
SmokeGard 167°F (75°C), Halar -40 to 302°F (-40 to 150°C)
300 Vac, power limited
Listing
UL: NEC CL2P, or better
LEGEND
AWG
CL2P
DC
— American Wire Gage
— Class 2 Plenum Cable
— Direct Current
FEP
NEC
O.D.
TC
— Fluorinated Ethylene Polymer
— National Electrical Code
— Outside Diameter
— Tinned Copper
— Underwriters Laboratories
UL
TO ADDRESS THE UPC OPEN CONTROLLER — The
user must give the UPC Open controller an address that is
unique on the BACnet network. Perform the following proce-
dure to assign an address:
1. If the UPC Open controller is powered, pull the screw ter-
minal connector from the controller's power terminals la-
beled Gnd and HOT. The controller reads the address
each time power is applied to it.
0
1
9
2
8
7
3
10's
1's
5 4
6
0
1
9
2
8
7
3
5 4
6
2. Using the rotary switches (see Fig. 25 and 28), set the
controller's address. Set the Tens (10's) switch to the tens
digit of the address, and set the Ones (1's) switch to the
ones digit.
As an example in Fig. 28, if the controller’s address is 25,
point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
Fig. 28 — Address Rotary Switches
BACNET DEVICE INSTANCE ADDRESS — The UPC
Open controller also has a BACnet Device Instance address.
This Device Instance MUST be unique for the complete BAC-
net system in which the UPC Open controller is installed. The
Device Instance is auto generated by default and is derived by
29
Download from Www.Somanuals.com. All Manuals Search And Download.
adding the MAC address to the end of the Network Number.
The Network Number of a new UPC Open controller is 16101,
but it can be changed using i-Vu® Tools or BACView device.
By default, a MAC address of 20 will result in a Device In-
stance of 16101 + 20 which would be a Device Instance of
1610120.
DIP switch 3 is used to set up which port the building net-
work is connected to. This DIP switch will always be set to
OFF.
DIP switch 4 is used to tell the UPC controller the commu-
nication language of the building network. This should always
be set to ON, unless the network uses BACnet over ARC156.
CONFIGURING THE BAS PORT FOR BACNET MS/
TP — Use the same baud rate and communication settings for
all controllers on the network segment. The UPC Open con-
troller is fixed at 8 data bits, No Parity, and 1 Stop bit for this
protocol's communications.
If the UPC Open controller has been wired for power, pull
the screw terminal connector from the controller's power termi-
nals labeled Gnd and HOT. The controller reads the DIP
Switches and jumpers each time power is applied to it.
DIP switches 5-8 are used to set up the communication pro-
tocol. See Table 11 for settings.
NETWORK POINTS AND DESCRIPTIONS — The points
list for the controller is shown in Table 12.
BP (AV:1) — The BP (AV:1) parameter is a read-only value
that shows the current building pressure from the building pres-
sure sensor inside the ERV. This parameter is only applicable
for a building pressure based mode of operation.
DCV CO2 INSIDE (AV:2) — This parameter shows the read-
ing from the CO2 sensor that is connected to the ERV. The CO2
sensor is only provided with the ERV when the ERV has been
ordered with a CO2 based EzERV control scheme.
EAT SENSOR (AV:3), OAT SENSOR (AV:7), RAT SEN-
SOR (AV:9), AND SAT SENSOR (AV:19) — These status
points show the temperatures in all 4 quadrants of the ERV. The
status points will only display values other than 0 if the ERV
was ordered with temperature sensors.
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS
Port DIP switch DS4 to “E1-485.” Set the BMS Protocol DIP
switches DS8 through DS5 to “MSTP.” See Table 9.
Table 9 — SW3 Protocol Switch Settings
for MS/TP
DS8
DS7
DS6
DS5
DS4
DS3
Off
Off
Off
Off
On
Off
Verify that the EIA-485 jumpers below the CCN Port are set
to EIA-485 and 2W.
The example in Fig. 29 shows the BAS Port DIP Switches
set for 76.8k (Carrier default) and MS/TP.
EXHAUST AIR CFM (AV:5) AND OUTSIDE AIR CFM
(AV:8) — These status points provide the airflow that each fan
is moving if the ERV was ordered with the EzERV option. This
option is an integrated airflow monitoring station.
EX FAN POS (AV:4) AND OA FAN POS (AV:6) — The
fan speed status points provide feedback on a scale of 0 to
100% to show the output of each fan.
Set the BAS Port DIP Switches DS2 and DS1 for the appro-
priate communications speed of the MS/TP network (9600,
19.2k, 38.4k, or 76.8k bps). See Fig. 29 and Table 10.
REMOTE AIRFLOW CONFIGURATION MODE (AV:10)
— This mode sets up the mode of operation for the ERV. The
setting is associated with the control scheme the ERV was
ordered with from the factory. The appropriate setting for this
mode correlates with the last 3 characters of the part number
on the ERV.
Table 10 — Baud Selection Table
BAUD RATE
9,600
DS2
Off
On
Off
On
DS1
Off
Off
On
On
19,200
38,400
• For part number G-A, the mode is Offset Airflow Con-
trol (mode no. 1).
76,800
• For part number G-B, the mode is CO2 sensor based
Demand Control Ventilation with Offset Airflow Control
(mode no. 2).
• For part number G-D, the mode is Building Pressure sen-
sor based Airflow Control (mode no. 3).
• For part number G-E, the mode is CO2 sensor based
Demand Controlled Ventilation with Building Pressure
sensor based Airflow Control (mode no. 4).
• If the ERV part number does not have "G-" in it then
mode no. 0 should always be used.
Fig. 29 — DIP Switches
Table 11 — UPC Communication Protocol Settings (DIP Switches 5-8)
DIP SWITCH
PROTOCOL
TYPE
5
6
7
8
BACnet MSTP (m)
BACnet MSTP (s)
BACnet PTP
N2
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
Modbus
OFF
OFF
ON
LON SLTA
LON Plugin
Ethernet
ON
ON
ON
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — Network Points List
BACNET
READ/
BACNET
POINT NAME
OBJECT ID
WRITE
R
OBJECT NAME
AV:1
AV:2
BP
bp_1
dcv_co2_inside_1
DCV_CO2_INSIDE
R
AV:3
EAT_SENSOR
R
eat_sensor_1
AV:4
EX_FAN_POS
R
ex_fan_pos_1
AV:5
EXHAUST_AIR_CFM
R
exhaust_air_cfm_1
AV:6
OA_FAN_POS
R
oa_fan_pos_1
AV:7
OAT_SENSOR
R
oat_sensor_1
AV:8
OUTSIDE_AIR_CFM
R
outside_air_cfm_1
AV:9
RAT_SENSOR
R
rat_sensor_1
AV:10
AV:11
AV:12
AV:13
AV:14
AV:15
AV:16
AV:17
AV:18
AV:19
AV:20
AV:21
AV:22
AV:23
AV:24
AV:25
AV:26
AV:27
AV:28
AV:29
AV:30
BV:1
REMOTE_AIRFLOW_CONFIGURATION_MODE
REMOTE_BP_SENSOR
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R
R/W
R
R
remote_airflow_configeration_mode_1
remote_bp_sensor_1
REMOTE_BP_SETPOINT
REMOTE_EXHAUST_OFFSET_SETPOINT
REMOTE_MAX_CFM_SETPOINT
REMOTE_MAX_DCV_VALUE_SETPOINT
REMOTE_MIN_CFM_SETPOINT
REMOTE_MIN_DCV_VALUE_SETPOINT
REMOTE_SENSOR_DCV_VALUE
SAT_SENSOR
remote_bp_setpoint_1
remote_exhaust_offset_setpoint_1
remote_max_cfm_setpoint_1
remote_max_dcv_value_setpoint_1
remote_min_cfm_setpoint_1
remote_min_dcv_value_setpoint_1
remote_sensor_dcv_value_1
sat_sensor_1
UPC_SOFTWARE_VERSION_STAT
UPC_SOFTWARE_VERSION
EX_FILTER_BP
upc_software_version_stat_1
upc_software_version_1
ex_filter_bp_1
OA_FILTER_BP
oa_filter_bp_1
REMOTE_EX_FILTER_BP_SETPOINT
REMOTE_OA_FILTER_BP_SETPOINT
MMC_MAIN_BOARD_SOFTWARE_VERSION
REMOTE_EX_FAN_SPEED_SETPOINT
REMOTE_OA_FAN_SPEED_SETPOINT
ERV_VFD_WHEEL_POS
REMOTE_VFD_WHEEL_SPEED_SETPOINT
ERV_2POS_DAMPER_STAT
ERV_EX_STAT
remote_ex_filter_bp_setpoint_1
remote_oa_filter_bp_setpoint_1
mmc_main_board_software_version_1
remote_ex_fan_speed_setpoint_1
remote_oa_fan_speed_setpoint_1
erv_vfd_wheel_pos_1
remote_vfd_wheel_speed_setpoint_1
erv_2pos_damper_stat_1
erv_ex_stat_1
BV:2
BV:3
ERV_OA_STAT
R
erv_oa_stat_1
BV:4
ERV_WHEEL_STAT
R
erv_wheel_stat_1
BV:5
EX_BLOWER_ALARM
R
ex_blower_alarm_1
BV:6
BV:7
EX_DIRTY_FILTER_ALARM
FIX_WHEEL_ALARM
R
R
ex_dirty_filter_alarm_1
fix_wheel_alarm_1
BV:8
OA_BLOWER_ALARM
R
oa_blower_alarm_1
BV:9
OA_DIRTY_FILTER_ALARM
OA_LOWCFM
R
R
oa_dirty_filter_alarm_1
oa_lowcfm_1
BV:10
BV:11
BV:12
BV:13
BV:14
BV:15
BV:16
REMOTE_BP_SENSOR_ENABLE
REMOTE_DCV_SENSOR_ENABLE
REMOTE_ERV_DOWN_ENABLE
REMOTE_PWR_EXHAUST_ENABLE
REMOTE_START_STOP
R/W
R/W
R/W
R/W
R/W
R/W
remote_bp_sensor_enable_1
remote_dcv_sensor_enable_1
remote_erv_down_enable_1
remote_pwr_exhaust_enable_1
remote_start_stop_1
REMOTE_WHEEL_BYPASS_ENABLE
remote_wheel_bypass_enable_1
REMOTE BP SENSOR (AV:11) — This parameter is only
applicable if the ERV is running in a building pressure based
mode of operation and the parameter REMOTE BP SENSOR
ENABLE (BV:11) is set to 1. If the parameter is set to 0, then
the ERV will use the BP (AV:1) parameter. The ERV will mod-
ulate the exhaust fan to try to achieve the number that is set into
REMOTE BP SETPOINT (AV:12).
REMOTE BP SENSOR SETPOINT (AV:12) — This is the
desired building pressure. The ERV will modulate the exhaust
fan to try to achieve this set point. This parameter is only appli-
cable for a building pressure based mode of operation. The
ERV will use this value for its calculations if the REMOTE
AIRFLOW CONFIGURATION MODE (AV:10) is not 0. If
the REMOTE AIRFLOW CONFIGURATION MODE
(AV:10) is set to 0, then the ERV will use the value that has
been loaded locally into the ERV control board.
REMOTE EXHAUST OFFSET SETPOINT (AV:13) —
This parameter is applicable when REMOTE AIRFLOW
CONFIGURATION MODE (AV:10) is configured to 1 or 2.
This will set the difference by which the exhaust airflow will
follow the outside airflow. For example, if the demand control
ventilation set points are telling the outdoor air fan to run at
4,000 cfm, and the REMOTE EXHAUST OFFSET SET-
POINT (AV:13) is set to -1,000, then the exhaust fan will be
running at 3,000 CFM.
REMOTE SENSOR DCV VALUE (AV:18) — This parame-
ter is also only applicable if the ERV is running in a CO2 based
mode of operation and the parameter REMOTE DCV SEN-
SOR ENABLE (BV:12) is set to 1. If REMOTE DCV
31
Download from Www.Somanuals.com. All Manuals Search And Download.
SENSOR ENABLE (BV:12) is set to 0, then the ERV will use
the DCV CO2 INSIDE (AV:2) parameter. Any value can be
written into this parameter.
FIX WHEEL ALARM (BV:7) — This alarm indicates that
the ERV heat exchange wheel is not turning when it is sup-
posed to be turning. This alarm will never go active if the ERV
was not ordered with this alarm option.
EX DIRTY FILTER ALARM (BV:6) AND OA DIRTY
FILTER ALARM (BV:9) — This alarm indicates that the air
filters in the ERV need to be changed. These alarms are related
to parameters REMOTE EX FILTER BP SETPOINT (AV:24)
and REMOTE OA FILTER BP SETPOINT (AV:25). The set
points determine when the ERV is going to give a dirty filter
alarm. This alarm will never go active if the ERV was not or-
dered with the dirty filter alarm options.
The ERV will look at this parameter along with parameters:
REMOTE MIN DCV VALUE SETPOINT (AV:17), RE-
MOTE MAX DCV VALUE SETPOINT (AV:15), REMOTE
MIN CFM SETPOINT (AV:16), and REMOTE MAX CFM
SETPOINT (AV:14) to determine the settings for the ERV.
These 4 remote set points will only be used if the REMOTE
AIRFLOW CONFIGURATION MODE (AV:10) parameter is
not 0. Otherwise the values that have been loaded locally into
the ERV will be used.
EX FILTER BP (AV:22) AND OA FILTER BP (AV:23) —
These status points show the pressure drop across each air fil-
ter. This pressure drop is used to determine when the air filters
are dirty. These numbers will always be 0 unless the ERV was
ordered with this option.
OA LOW CFM (BV:10) — This alarm becomes active if the
desired outside air CFM set point is not being met. The alarm
will only trip if the desired outside air CFM set point has not
been satisfied for 5 minutes.
REMOTE BP SENSOR ENABLE (BV:11) — If this param-
eter is set to OFF the ERV will use the building pressure read-
ing off of the sensor inside the ERV. If the parameter is set to
ON, the ERV will use the building pressure value that is being
written in parameter REMOTE BP SENSOR VALUE.
REMOTE ERV DOWN ENABLE (BV:13) — This parame-
ter is another start/stop command for the ERV. Turning this pa-
rameter to 1 will shut the ERV down. Unlike the REMOTE
START STOP (BV:15) parameter, it is not dependant on the
REMOTE AIRFLOW CONFIGURATION MODE (AV:10)
parameter.
REMOTE PWR EXHAUST ENABLE (BV:14) — This pa-
rameter puts the ERV into a power exhaust mode that is usually
used in conjunction with the economizer of the rooftop unit.
The power exhaust mode turns off the wheel and the outside air
blower. The exhaust blower will continue to run at its current
set point. Setting this parameter to 1 will put the ERV into pow-
er exhaust mode.
REMOTE START STOP (BV:15) — This parameter allows
the user to turn on/off the ERV. Setting this parameter to 1 will
turn the ERV ON. The REMOTE START STOP works in con-
junction with the start/stop contact on the ERV field terminal
strip if the REMOTE AIRFLOW CONFIGURATION MODE
(AV:10) is set to 0. If the REMOTE AIRFLOW CONFIGU-
RATION MODE (AV:10) is not set to 0, then the REMOTE
START STOP parameter will override the field terminal strip.
REMOTE WHEEL BYPASS ENABLE (BV:16) — Setting
this parameter to 1 will turn off the ERV heat exchange wheel.
This mode is normally used to disable the wheel when free
cooling is available.
REMOTE EX FILTER BP SETPOINT (AV:24) AND
REMOTE OA FILTER BP SETPOINT (AV:25) — These
set points are related to the dirty filter indicator option of the
ERV. If the ERV has the dirty filter indicator option installed
this parameter will set the trip point for which the ERV will
give a dirty filter alarm. This number will be dependent on the
airflow that the ERV is set to. The best way to determine the
dirty filter set points is to use the unit status parameters called
EX FILTER BP (AV:22) and OA FILTER BP (AV:23). With
clean filters in the ERV, and the ERV running at its design con-
ditions, note the values of the filter status parameters. Multiply
those numbers by 1.5 and use them for the filter set points.
These set points will overwrite the value that was set locally
into the ERV. If this value is changed locally it will overwrite
the value that was set remotely.
REMOTE EX FAN SPEED SETPOINT (AV:27) AND
REMOTE OA FAN SPEED SETPOINT (AV:28) — These
parameters allow for direct input to tell the fans how fast to run.
The parameter needs to be set to a number between 1% and
100%. When this parameter is set to 0% the ERV’s internal
control board will take control of the fans.
ERV WHEEL SPEED (AV:29) — This status shows the
speed that the ERV heat exchanger wheel is running on a scale
of 0 to 100%. If the ERV was not ordered with a variable fre-
quency drive on the wheel this status will always read 100%.
REMOTE VFD WHEEL SPEED SETPOINT (AV:30)
—
This parameter allows for the wheel rotation speed to be varied.
This is often used to change the efficiency of the Energy Re-
covery Heat Exchanger Wheel to maintain a constant discharge
temperature. This needs to be entered as a number that is be-
tween 1% and 100%. Entering 0% will put the wheel speed in
automatic mode, and the ERV control board will take control.
To turn off the wheel use the REMOTE WHEEL BYPASS
ENABLE (BV:16) parameter.
SERVICE
CAUTION
ERV 2POS DAMPER STAT (BV:l) — This status shows if
the ERV is commanding the two-position dampers to open.
This status will update whether the ERV was ordered with two-
position dampers or not.
ERV EX STAT (BV:2) AND ERV OA STAT (BV:3) —
These status points output a logic 1 to show when the fan is
ON.
ERV WHEEL STAT (BV:4) — The ERV WHEEL STAT sta-
tus shows whether or not the ERV heat exchange wheel is
running.
Disconnect electrical power before servicing energy recov-
ery cassette. Failure to do so could result in personal injury.
Removing and Installing Non-Segmented Wheel
for Cleaning (62EB,E7 Units) — Non-segmented en-
ergy transfer wheels are secured to the shaft and bearing sup-
port beam by a Phillips head screw and hub cover. See Fig. 30.
To remove the energy transfer wheel, follow Steps 1-4
below. (See Fig. 30.) Reverse procedure for wheel installation.
1. Remove front seal assembly (pulley side of cassette) if
present.
2. Remove belt from pulley and position temporarily around
wheel rim.
3. Remove the hub cover from the wheel. Note the wheel to
shaft alignment pin under the hub cover. Ensure this pin
ERV EX BLOWER ALARM (BV:5) AND ERV OA
BLOWER ALARM (BV:8) — These alarms indicate a cata-
strophic failure of a blower in the ERV. The alarms can also in-
dicate a missing leg of incoming power, over voltage, under
voltage or extremely dirty incoming power to the ERV. These
alarms will never go active if the ERV was not ordered with the
blower alarm options.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
engages the notch at the end of the shaft when reinstalling
the wheel.
3. Remove the belt from the pulley and position temporarily
around the wheel rim.
4. Pull the wheel straight off the shaft. Handle wheel with
care to prevent distorting of the wheel.
4. Loosen the 2 set screws on each of the 2 wheel bearings.
See Fig. 31.
Removing and Installing Non-Segmented
CAUTION
Wheel for Cleaning
(62ECC and 62E2C
Units) — Non-segmented energy transfer wheels include
the shaft and are secured to 2 wheel support beams by 2 flange
bearings with locking collars. See Fig. 31.
When replacing wheel, retighten the 4 bearing set screws.
Premature bearing failure could result.
To remove the energy transfer wheel, follow Steps 1-4
below. Reverse procedure for wheel installation.
1. Pull the wheel with shaft straight out of the motor side
wheel support beam and bearing. Handle wheel with care
to prevent distorting of the wheel.
Removing Wheel Segments for Cleaning
(62ECD, 62ED-EU, 62E2D, and 62E3-E6 Units)
1. Unlock and open the segment retaining brackets on both
sides of the selected segment opening. Refer to Fig. 32.
2. Gently lift segment outward.
2. Remove the pulley side wheel support beam with bearing
by removing the 4 support beam screws.
3. Close segment retaining latches and rotate wheel 180 de-
grees to remove next segment. Follow this pattern to
remove all segments. This pattern will help keep wheel
balanced.
To install the segments, see the Installing Wheel Segments
section.
Alignment
Cassette
Pin
Housing/Frame
Shaft
A62-278ef
Bearings (2)
A62-279ef
Wheel &
Hub
Hub Cover
Fig. 30 — 62EB and 62E7 Energy
Transfer Wheel Assembly
Fig. 32 — Unlocking the
Segment Retaining Brackets
WHEEL,
HUB &
Installing Wheel Segments
WARNING
SHAFT
FLANGE
BEARINGS
(2)
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
NOTE: Both installation and removal procedures must be per-
formed from the pulley side of the cassette.
SET
SCREWS
(2) EACH
CAUTION
Weight of the installed segment will cause the wheel to
accelerate in rotation. Failure to maintain control of the
wheel rotation while installing all segments could cause
severe injury to fingers or hand caught between revolving
spokes and the bearing support beam. Handle of hammer,
or other stop, should be inserted through spokes and above
or below bearing support beams to limit rotation of unbal-
anced wheel. See Fig. 33.
WHEEL SUPPORT BEAMS
Fig. 31 — 62ECC and 62E2C Energy
Transfer Wheel Assembly
33
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Ease the segment downward until its outer rim clears the
inside of the wheel rim. Then press the segment inward
against the spoke flanges.
A62-280ef
4. Close and latch segment retaining brackets to the position
shown in Fig. 36. Make certain the retaining bracket is
fully engaged under the catch.
HAMMER
USED AS
“STOP”
PULL TAB
CATCH
A62-283ef
Fig. 36 — Latch Segment Retaining Brackets
Fig. 33 — Using a Stop on the Wheel
5. Slowly rotate, by hand, the first installed segment to the
bottom of the cassette, then install the second segment
opposite the first. Repeat this sequence with the 2 in-
stalled segments rotated to the horizontal position to bal-
ance the weight of installed segments. Continue this se-
quence with the remaining segments.
NOTE: The 62EBA, 62EBC, 62ECC, 62E7A, 62E7C, and
62E2C units contain non-segmented wheels which must be
completely removed to be cleaned.
1. Begin by positioning one segment opening at the top of
the cassette. Unlock and open the segment retaining
brackets on both sides of the selected segment opening.
2. Holding the segment as vertical as possible and
centered between spokes, insert nose of segment down-
ward between the hub plates. See Fig. 34.
Wheel Drive Motor and Pulley Replacement
(62EC-EU and 62E2-E6 Units)
1. Disconnect power to wheel drive motor.
2. Remove belt from pulley and position temporarily around
wheel rim.
3. Loosen setscrew in wheel drive pulley using Allen
wrench and remove pulley from motor drive shaft.
4. While supporting weight of drive motor in one hand,
loosen and remove 4 mounting bolts.
5. Install replacement motor with hardware kit supplied.
6. Install pulley to dimension shown in Fig. 37 and secure
setscrew to drive shaft.
7. Stretch belt over pulley and engage in groove.
Belt Replacement
1. Obtain access to the pulley side bearing access plate.
Remove 2 bearing access plate retaining screws and the
access plate.
A62-281ef
2. Using hexagonal wrench, loosen setscrew in bearing
locking collar. Using light hammer and drift (in drift pin
hole) tap collar in the direction of wheel rotation to
unlock collar. Remove collar.
3. Using socket wrench with extension, remove 2 nuts
which secure bearing housing to the bearing support
beam. Slide bearing from shaft.
NOTE: Slight hand pressure against wheel rim will lift weight
of wheel from inner race of bearing to assist bearing removal
and installation. If not removable by hand, use bearing puller.
Fig. 34 — Inserting a Segment of the Wheel
NOTE: The face of the segment, with the imbedded
stiffener (vertical support between nose and rim end of
segment) must face the motor side of the cassette. See
Fig. 35.
Imbedded Stiffeners
A62-282ef
CAUTION
Protect hands and belt from possible sharp edges of hole in
bearing support beam.
4. Using a wrench, remove diameter seal retaining screws or
hub seal retaining screws. Remove diameter seals or hub
seal from bearing beam. See Fig. 38.
5. Form a small loop of belt and pass it through the hole in
the bearing support beam. Grasp the belt at the wheel hub
and pull the entire belt down. Loop the trailing end of the
belt over the shaft (Fig. 38 shows belt partially through
the opening).
Fig. 35 — Motor Side View of Segment
34
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Reinstall the bearing onto the wheel shaft, being careful
to engage the 2 locating pins into the holes in the bearing
support beam. Secure the bearing with 2 self-locking
nuts.
all the wires. Disconnect the wiring from the terminals. Re-
move all the P-clips, wire ties, and hoses that will keep the
blower assembly from lifting out. Remove all the bolts that
hold the blower assembly in the ERV unit. Carefully lift the
blower assembly from its mounting plate.
NOTE: When removing 500 mm and 630 mm blowers it is
helpful to get assistance because of the blower's size and
weight.
7. Install the belts around the wheel and pulley according to
the instructions provided with the belt.
8. Reinstall diameter seals or hub seal and tighten retaining
screws. Rotate wheel in clockwise direction to determine
that wheel rotates freely with slight drag on seals.
9. Reinstall bearing locking collar. Rotate collar by hand in
the direction the wheel rotates (see label provided on each
cassette for wheel rotation). Lock in position by tapping
drift pin hole with hammer and drift. Secure in position
by tightening setscrew.
Follow these instructions in reverse order to install the new
blower.
SUPPLY SIDE — Turn off the power to the unit. Remove the
intake air hood (if equipped). Remove all of the screws from
the top panel on the supply side of the ERV. Be sure to remove
the screws on the center seam. Pry the top panel up from its
gasket seat, being careful not to bend the lid. Remove the ser-
vice doors on both sides and remove the filters or filter racks on
the supply side. Remove the cover from the blower motor and
note the location of all the wires. Disconnect the wiring from
the terminals.
10. Reinstall bearing access cover.
11. Apply power to wheel and ensure that the wheel rotates
freely without interference.
ALTERNATE BELT REPLACEMENT METHODS — Alter-
nate belt replacement methods may be used in some applica-
tions depending upon accessibility of the cassette. Consult
instructions provided with the belt for further information.
NOTE: Push the wheel out from underneath the blower that is
being disconnected for more room to work.
Removing the Service Door — To open the cabinet,
turn the eight ¼-turn latches counter clockwise. With a hand on
each handle of the door, carefully pull the door straight out.
Remove all of the P-clips, wire ties, and hoses that will keep
the blower assembly from lifting out. Remove all of the bolts
that hold the blower assembly in the ERV unit. Carefully lift
the blower assembly from its mounting plate.
NOTE: When removing 500 mm and 630 mm blowers it is
helpful to get assistance because of the blower's size and
weight.
Replacing a Blower (All ERV Cabinets Except
62EB and 62E7 Units)
EXHAUST SIDE — Turn off power to the unit. Remove all
screws from the top panel on the exhaust side of the ERV. Be
sure to remove the screws on the center seam. Pry the top panel
up from its gasket seat, being careful not to bend the lid. Re-
move the cover from the blower motor and note the location of
Follow these instructions in reverse order to install the new
blower.
DIMENSION A
WHEEL MODEL
NUMBER
62E UNIT SIZE ERV WHEEL
mm
3.2
in.
1/8
Insulation
A
ERC-1904
ERC-1906
B,7
C
6.4
1/4
C
ERC-2509
6.4
1/4
C,2
D,3
D
G
D
G
B
ERC-2510C
ERC-2513C
ERC-3014C
ERC-3019C
ERC-3615
3.2
1/8
3.2
1/8
Seal
3.2
1/8
Plate
3.2
1/8
6.4
1/4
D
F
ERC-3622
6.4
1/4
Dimension A
E,4
H,5
ERC-3623
6.4
1/4
Wheel
Drive
G
B
ERC-3628
6.4
1/4
ERC-5230
9.5
3/8
Motor
D
F
ERC-5248
9.5
3/8
ERC-5245
9.5
3/8
G
D
G
D
G
D
G
D
G
D
G
D
G
D
G
D
G
D
G
ERC-5262
9.5
3/8
ERC-6475
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
11.1
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
7/16
Pulley
K,6
L
ERC-6488
ERC-6876
ERC-68100
ERC-7490
A62-284ef
M
N
P
ERC-74122
ERC-81110C
ERC-81146C
ERC-86125C
ERC-86170C
ERC-92135C
ERC-92180C
ERC-99160C
ERC-99215C
ERC-104195C
ERC-104250C
ERC-110220C
ERC-110290C
NOTE: The ERV wheel model number contains the wheel series number, and
is located on a label near the drive pulley. For example, ERC-5245 is a 52
series wheel.
R
S
T
U
Fig. 37 — Pulley Location
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Belt (Shown in
Place)
Locking
Collar
Bearing
Support
Beam
Wheel Rim
Locking
Nut (2)
Wheel
Bearing
Bearing
Housing
Access Plate
Hub (2)
Taper - Lock
Hub Collar (2)
Retaining
Screws
Set Screw
Shaft
Drift Hole
Locating Pin
PULL
A62-285ef
FEED
Belt
Pulley
Side
Motor
Side
Fig. 38 — Belt Replacement (Diameter Seals Removed)
Measurable changes in latent energy transfer can occur in
shorter periods of time in applications such as moderate occu-
pant smoking or cooking facilities. In applications experienc-
ing unusually high levels of occupant smoking or oil-based
aerosols such as industrial applications involving the ventila-
tion of machine shop areas for example, annual washing of en-
ergy transfer may be necessary to maintain latent transfer effi-
ciency. Proper cleaning of the energy recovery wheel will re-
store latent effectiveness to near original performance.
Replacing a Blower (62EB and 62E7 Units)
EXHAUST OR SUPPLY SIDE — Turn off the power to the
unit. Remove all of the screws from the top panel. Pry the top
panel up from its gasket seat, being careful not to bend the lid.
Disconnect plug from the blower. Remove all of the P-clips,
wire ties and hoses that will keep the blower assembly from
lifting out. Remove all of the screws holding the blower in the
ERV unit and remove the blower. Follow these instructions in
reverse order to install the new blower.
To clean, gain access to the energy recovery wheel and
remove wheel. Brush foreign material from the face of the
wheel. Wash the wheel in a 5% solution of non-acid based coil
cleaner or alkaline detergent and warm water.
Soak in the solution until grease and tar deposits are
loosened.
NOTE: Some staining of the desiccant may remain and is not
harmful to performance.
Before removing, rapidly run finger across surface of wheel
to separate polymer strips for better cleaning action. Rinse
dirty solution from wheel and remove excess water before
reinstalling.
MAINTENANCE
Routine maintenance of the energy recovery cassettes
includes periodic cleaning of the energy recovery wheel as well
as inspection of the air seals and wheel drive components as
follows:
Cleaning — The need for periodic cleaning of the energy
recovery wheel will be a function of operating schedule, cli-
mate and contaminants in the indoor air being exhausted, and
the outdoor air being supplied to the building.
The air exchange wheel is “self-cleaning” with respect to
dry particles due to its laminar flow characteristics. Smaller
particles pass through; larger particles land on the surface and
are blown clear as the flow direction is reversed. Any material
that builds up on the face of the wheel can be removed with a
brush or vacuum. The primary need for cleaning is to remove
oil-based aerosols that have condensed on energy transfer
surfaces.
CAUTION
Do not use acid based cleaners, aromatic solvents, steam or
temperatures in excess of 76.7 C (170 F); damage to the
wheel may result.
A characteristic of all dry desiccants, such films can close
off micron sized pores at the surface of the desiccant material,
reducing the efficiency by which the desiccant can adsorb and
desorb moisture and also build up so as to reduce airflow.
In a reasonably clean indoor environment such as a school
or office building, measurable reductions of airflow or loss of
sensible effectiveness may not occur for several years.
Air Seals — Diameter seals are provided on each cassette
to minimize transfer of air between the counter flowing
airstreams.
To adjust diameter seals, loosen diameter seal adjusting
screws and back seals away from wheel surface See Fig. 39.
Rotate wheel clockwise until 2 opposing spokes are hidden
behind the bearing support beam. Using a folded piece of paper
36
Download from Www.Somanuals.com. All Manuals Search And Download.
as a feeler gage, position paper between the wheel surface and
diameter seals. Adjust seals towards wheel surface until a slight
friction on the feeler gage (paper) is detected when gage is
moved along the length of the spoke. Retighten adjusting
screws and recheck clearance with “feeler” gage.
Air Filters — With this ERV unit and with most other
forced air heating, cooling and ventilation systems, regular air
filter maintenance is of utmost importance. Proper filter main-
tenance will improve indoor air quality, keep the building air-
handling system clean for peak efficiency, and prolong the life
of the HVAC (Heating, Ventilation, and Air Conditioning)
equipment. The life of the air filters is directly related to the ap-
plication to which the ERV unit is installed. The air filters
should be inspected every couple of weeks until a maintenance
schedule is established. The ERV unit is equipped from the fac-
tory with throwaway filters, however if the installer changed
the filter type, consult the installer for filter maintenance
instructions.
Wheel Drive Components — The wheel drive motor
bearings are pre-lubricated and no further lubrication is neces-
sary. Make certain air cooling ports are not blocked.
The wheel drive pulley is secured to the drive motor shaft
by a setscrew. The setscrew is secured with removable adhe-
sive to prevent loosening. Annually confirm setscrew is secure.
The wheel drive belt is a urethane stretch belt designed to
provide constant tension through the life of the belt. No adjust-
ment is required. Inspect the drive belt annually for proper
tracking and tension. A properly tensioned belt will turn
the wheel immediately after power is applied with no visible
slippage during start-up.
Replacing the Throwaway Filters — After remov-
ing the service door (see Removing the Service Door section)
remove the spacer plugs and pull the filters or filter racks out of
the cabinet. Replace the filters with the original equipment
manufacturer replacements or equivalents. Refer to Tables 1A
and 1B for filter sizes.
A62-286ef
Rotation
To
Adjust
Adjusting Screws
Feeler Gage
Fig. 39 — Diameter Seal Adjustment
37
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
See Table 13 for troubleshooting information.
Table 13 — ERV Troubleshooting
SYMPTOM
POSSIBLE CAUSES
ACTION TO CHECK
POSSIBLE REMEDY
Disconnect switch is in the off
position
Verify that the disconnect switch is Move the disconnect lever to the 'ON'
in the 'ON' position
position.
Using a volt meter verify that the voltage
Check for power at the disconnect being supplied to the ERV matches the ERV's
No power to the ERV
switch
operating voltage. If the ERV operates on
three phase power check all three legs.
ERV will not turn on
Using a volt meter verify that the voltage on
the bottom side of the fuse block matches the
ERV's operating voltage. If the ERV operates
on three phase power check all three legs.
Check for power at the bottom of
the fuse block
One or more blown fuses
Look at the small transformer next
to the control circuit board to see if Depress the circuit breaker back in.
the black circuit pushed out
Control board transformer circuit
breaker is tripped
Use the user interface push button Adjust the fan speed / CFM demand levels by
The fan speed / CFM level is set
too low
to view the 'Outside Air' and
'Exhaust Air' settings
pressing the user interface push button and
turning the adjust knob.
Using a volt meter verify that the voltage on
the bottom side of the fuse block matches the
ERV's operating voltage. If the ERV operates
on three phase power check all three legs.
Check for power at the bottom of
the fuse block
One or more blown fuses
Using a continuity meter check for continuity
across the two wires that connect to the mer-
Rooftop Economizer Option (if
equipped) has shut down the ERV
because the rooftop unit is in 'Free
Cooling' mode
Check for continuity across the
ERV is running but
blowers will not turn
mercury switch on the economizer cury switch on the economizer damper. If the
damper.
contacts are open, the rooftop unit is in 'Free
Cooling'.
Smoke Detector Option (if
Using the wiring schematics verify that the
smoke detector is wired to the control board
properly.
equipped) has shut down the ERV
because it is sensing smoke in the
exhaust airstream on the ERV.
Check for wiring errors.
Use a thermometer to measure the outside
temperature. Use the wiring schematics to
verify that temperature probe on the intake air
side of the ERV is wired properly.
Check to see if the outside temper-
ature is above –30 F
(–34.4 C). Check for wiring errors
Low Temperature Lockout Option
(if equipped)
Use the user interface push button Adjust the fan speed / CFM demand levels by
The fan speed / CFM level is set
too low
to view the 'Outside Air' and
'Exhaust Air' settings
pressing the user interface push button and
turning the adjust knob.
Rooftop Economizer with Power
Relief Option (if equipped) has
shut down the supply blower
Using a continuity meter check for continuity
across the two wires that connect to the mer-
Check for continuity across the
mercury switch on the economizer cury switch on the economizer damper. If the
because the rooftop unit is in 'Free damper
Cooling' mode
contacts are open, the rooftop unit is in 'Free
Cooling'.
Only one of the two
blowers is turning
Using the wiring schematics verify that both
the power wires and the control wires are con-
nect properly.
One of the blowers is wired
incorrectly
Check for wiring errors.
The ERV Standard Frost Protec-
tion Option has turned off the sup- Check for frost on the wheel.
ply blower to defrost the wheel
Wait for Defrost mode to finish.
The ERV Enthalpy Control, Dry
bulb Control / Wheel Bypass Stop / Check for Stop / Jog movement of
Wait until sequence is completed.
Jog Option (if equipped) is
activated
wheel.
Check to see if the connector
between the wheel motor and the
cabinet wiring is securely
connected.
The wheel motor is unplugged.
Plug the two connectors together.
Blowers are on but
the wheel is not
turning
The wheel motor is wired
incorrectly.
Compare the wheel motor, control board and
relay are wired correctly.
Verify that the wheel belt is seated in the pul-
ley and on the rim of the wheel.
Check for wiring errors.
Check the wheel belt.
The wheel belt is off or broken
Carefully rotate the wheel by grabbing the
outer rim and spinnig the wheel. After letting
go the wheel should continue to spin for three
to four seconds. Should the air seals need
adjusting see the maintainence section of this
book.
The air seals on the wheel are too Check to see if the wheel spins
tight freely.
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620007-01 Printed in U.S.A. Form 62E-C1SI Pg 38 8-10 Replaces: New
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
I. PROJECT INFORMATION:
Job Name ____________________________
ERV Unit Designation __________________
Phone Number ________________________
II. DESIGN INFORMATION:
Start-Up Performed By __________________
Date __________________________________
Application ___________________________________________________________________________
CFM (Supply/Exhaust) _________________________________________________________________
External Static Pressure (Supply/Exhaust) __________________________________________________
Supply/Exhaust Configuration ____________________________________________________________
Voltage/Phase ________________________________________________________________________
ERV Unit Part Number _________________________________________________________________
Coupled to RTU or stand-alone ___________________________________________________________
Specify RTU.
NOTE: Complete This Section for Coupled Applications Only
Model Number ________________________________________________________________________
HVAC Unit Discharge Type (Down discharge or horizontal discharge.) ____________________________
Roof Curb (Option)
Yes
No
14-in. Tall Roof Curb (Field Installed)
Horizontal Supply/Return Base (Field Installed)
Combination ERV-RTU Curb (Field Installed)
Horizontal Transition
NOTE: Complete This Section for Coupled Applications Only.
Transition Part Number (Field Installed)
Electrical Disconnect (Option)
Fused (Factory Installed)
Yes
Yes
Yes
No
No
No
Switched (Factory Installed)
Two-Position Motorized Dampers (Option)
Outside Air Damper (Factory Installed)
Exhaust Air Damper (Factory Installed)
Pre-Heater (Option)
kW _______________
Temp Control (Factory Installed)
Temp and Static Pressure Control (Factory Installed)
Frost Protection (Option) (Factory Installed)
NOTE: Do Not Use With Pre-Heater.
Yes
No
ERV Wheel VFD (Option) (Factory Installed)
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Low Temperature Lock Out (Option) (Factory Installed)
Filter Maintenance Indicator (Option) (Factory Installed)
ERV Blower Maintenance Indicator (Option) (Factory Installed)
ERV Wheel Maintenance Indicator (Option) (Factory Installed)
Field-Installed Accessories
ERV Remote Mount Timer (Field Installed)
ERV Remote Control Readout (Field Installed)
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620007-01 Printed in U.S.A. Form 62E-C1SI Pg CL-1 8-10 Replaces: New
Download from Www.Somanuals.com. All Manuals Search And Download.
|