Carrier Refrigerator MPW015 045 User Manual

AQUASNAP®  
30MPA,MPW015-045  
Liquid Chillers with Scroll Compressors  
and ComfortLink™ Controls  
Controls, Start-Up, Operation,  
Service, and Troubleshooting  
SAFETY CONSIDERATIONS  
CAUTION  
Installing, starting up, and servicing this equipment can be  
hazardous due to system pressures, electrical components, and  
equipment location (elevated structures, mechanical rooms,  
etc.). Only trained, qualified installers and service mechanics  
should install, start up, and service this equipment.  
When working on this equipment, observe precautions in  
the literature, and on tags, stickers, and labels attached to the  
equipment, and any other safety precautions that apply. Follow  
all safety codes. Wear safety glasses and work gloves. Use  
care in handling, rigging, and setting this equipment, and in  
handling all electrical components.  
This unit uses a microprocessor-based electronic control  
system. Do not use jumpers or other tools to short out  
components, or to bypass or otherwise depart from recom-  
mended procedures. Any short-to-ground of the control  
board or accompanying wiring may destroy the electronic  
modules or electrical components.  
CAUTION  
To prevent potential damage to heat exchanger, always run  
fluid through heat exchanger when adding or removing  
refrigerant charge. Use appropriate brine solutions in cooler  
fluid loop to prevent the freezing of brazed plate heat  
exchanger when the equipment is exposed to temperatures  
below 32 F (0° C). Proof of flow switch is factory installed  
on all models. Do NOT remove power from this chiller dur-  
ing winter shutdown periods without taking precaution to  
remove all water from heat exchanger and optional  
hydronic system. Failure to properly protect the system  
from freezing may constitute abuse and may void warranty.  
WARNING  
Electrical shock can cause personal injury and death. Shut  
off all power to this equipment during installation. There  
may be more than one disconnect switch. Tag all discon-  
nect locations to alert others not to restore power until work  
is completed.  
WARNING  
DO NOT VENT refrigerant relief valves within a building.  
Outlet from relief valves must be vented outdoors in  
accordance with the latest edition of ANSI/ASHRAE  
(American National Standards Institute/American Society  
of Heating, Refrigerating and Air Conditioning Engineers)  
15 (Safety Code for Mechanical Refrigeration). The  
accumulation of refrigerant in an enclosed space can  
displace oxygen and cause asphyxiation. Provide adequate  
ventilation in enclosed or low overhead areas. Inhalation of  
high concentrations of vapor is harmful and may cause  
heart irregularities, unconsciousness or death. Misuse can  
be fatal. Vapor is heavier than air and reduces the amount  
of oxygen available for breathing. Product causes eye and  
skin irritation. Decomposition products are hazardous.  
CAUTION  
Compressors require specific rotation. Monitor control  
alarms during first compressor start up for reverse rotation  
protection. Damage to unit may result.  
CAUTION  
Refrigerant charge must be removed slowly to prevent loss  
of compressor oil that could result in compressor failure.  
CAUTION  
Puron® refrigerant (R-410A) systems operate at higher  
pressures than standard R-22 systems. Do not use R-22 ser-  
vice equipment or components on Puron refrigerant equip-  
ment. If service equipment is not rated for Puron  
refrigerant, equipment damage or personal injury may  
result.  
WARNING  
DO NOT attempt to unbraze factory joints when servicing  
this equipment. Compressor oil is flammable and there is  
no way to detect how much oil may be in any of the  
refrigerant lines. Cut lines with a tubing cutter as required  
when performing service. Use a pan to catch any oil that  
may come out of the lines and as a gage for how much oil  
to add to system. DO NOT re-use compressor oil. Damage  
to equipment or personal injury may result.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300053-01 Printed in U.S.A. Form 30MP-1T Pg 1 1-10 Replaces: New  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When a value is included as part of the path name, it will be  
shown at the end of the path name after an equals sign. If the  
value represents a configuration setting, an explanation will  
be shown in parenthesis after the value. As an example,  
ConfigurationOPT1MLV.S = 1 (Minimum Load Valve  
Select).  
Changing item values or testing outputs is accomplished in  
the same manner. Locate and display the desired item. Press  
so that the item value flashes. Use the arrow keys to  
ENTER  
change the value or state and press the  
key to accept  
ENTER  
key to return to the next higher level of  
it. Press the  
ESCAPE  
structure. Repeat the process as required for other items.  
Pressing the  
and  
keys simultaneously  
ENTER  
ESCAPE  
will scroll an expanded text description of the point name or  
value across the display. The expanded description is shown in  
the local display tables but will not be shown with the path  
names in text.  
Items in the Configuration and Service Test modes are pass-  
word protected. The words ‘PASS’ and ‘WORD’ will alternate  
on the display when required. The default password is 0111.  
Press  
and the 1111 password will be displayed. Press  
ENTER  
again and the first digit will begin to flash. Use the  
The CCN (Carrier Comfort Network®) point names are also  
referenced in the local display tables for users configuring the  
unit with CCN software instead of the local display. The CCN  
tables are located in Appendix B of the manual.  
ENTER  
arrow keys to change the number and press  
to accept  
ENTER  
the digit. Continue with the remaining digits of the password.  
The password can only be changed through CCN operator in-  
terface software such as ComfortWORKS®, ComfortVIEW™  
and Service Tool.  
Basic Control Usage  
SCROLLING MARQUEE DISPLAY — The scrolling mar-  
quee display is the standard interface display to the ComfortLink  
Control System for 30MP units. The display has up and down  
See Tables 2-14 and Appendix A for further details.  
ACCESSORY NAVIGATOR™ DISPLAY MODULE —  
The Navigator module provides a mobile user interface to the  
ComfortLink™ control system, which is only available as a  
arrow keys, an  
key, and an  
key. These  
ESCAPE  
keys are used to navigate through the different levels of the  
display structure. Press the key until the highest  
ENTER  
ESCAPE  
field-installed accessory. The display has up and down arrow  
operating level is displayed to move through the top 11 mode  
levels indicated by LEDs (light emitting diodes) on the left side  
of the display. See Fig. 1 and Tables 2-14.  
keys, an  
key, and an  
key. These keys are  
ESCAPE  
used to navigate through the different levels of the display  
structure. Press the key until ‘Select a Menu Item’  
ENTER  
ESCAPE  
is displayed to move through the top 11 mode levels indicated  
by LEDs on the left side of the display. See Fig. 2.  
Once within a mode or sub-mode, pressing the  
ENTER  
keys simultaneously will put the scrolling  
and  
ESCAPE  
marquee display into expanded text mode where the full mean-  
ing of all sub-modes, items and their values can be displayed  
Once within a Mode or sub-mode, a “>” indicates the cur-  
rently selected item on the display screen. Pressing the  
for the current selection. Press the  
and  
ESCAPE  
ENTER  
and  
keys simultaneously will put the Nav-  
ESCAPE  
ENTER  
keys to return the scrolling marquee display to its default menu  
of rotating display items (those items in Run StatusVIEW).  
In addition, the password will be disabled, requiring that it be  
entered again before changes can be made to password protect-  
igator module into expanded text mode where the full meaning  
of all sub-modes, items and their values can be displayed. Press-  
ing the  
and  
keys when the display says  
ESCAPE  
ENTER  
‘Select Menu Item’ (Mode LED level) will return the Navigator  
module to its default menu of rotating display items (those items  
in Run StatusVIEW). In addition, the password will be dis-  
abled, requiring that it be entered again before changes can be  
ed items. Press the  
text mode.  
key to exit out of the expanded  
ESCAPE  
NOTE: When the Language Selection (Configuration  
DISPLANG), variable is changed, all appropriate display  
expansions will immediately change to the new language. No  
power-off or control reset is required when reconfiguring  
languages.  
made to password protected items. Press the  
exit out of the expanded text mode.  
key to  
ESCAPE  
NOTE: When the Language Selection (Configuration  
DISPLANG), variable is changed, all appropriate display  
expansions will immediately change to the new language. No  
power-off or control reset is required when reconfiguring  
languages.  
When a specific item is located, the item name alternates  
with the value. Press the  
key at a changeable item  
ENTER  
and the value will be displayed. Press  
again and the  
ENTER  
value will begin to flash indicating that the value can be  
changed. Use the up and down arrow keys to change the value,  
When a specific item is located, the item name appears on the  
left of the display, the value will appear near the middle of the  
display and the units (if any) will appear on the far right of the  
and confirm the value by pressing the  
key.  
ENTER  
display. Press the  
key at a changeable item and the val-  
ENTER  
ue will begin to flash. Use the up and down arrow keys to change  
the value, and confirm the value by pressing the key.  
ENTER  
MODE  
Run Status  
Service Test  
Temperature  
Changing item values or testing outputs is accomplished in  
the same manner. Locate and display the desired item. Press  
Pressures  
Setpoints  
so that the item value flashes. Use the arrow keys to  
ENTER  
change the value or state and press the  
Alarm Status  
Inputs  
key to accept  
Outputs  
ENTER  
key to return to the next higher level of  
Configuration  
Time Clock  
Operating Modes  
Alarms  
ESCAPE ENTER  
it. Press the  
ESCAPE  
structure. Repeat the process as required for other items.  
Items in the Configuration and Service Test modes are pass-  
word protected. The words Enter Password will be displayed  
when required, with 1111 also being displayed. The default  
password is 1111. Use the arrow keys to change the number  
Fig. 1 — Scrolling Marquee Display  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
and press  
to enter the digit. Continue with the re-  
Configuration mode. Press  
mode. The display will read:  
> TEST OFF  
to obtain access to this  
ENTER  
ENTER  
maining digits of the password. The password can only be  
changed through CCN operator interface software such as  
ComfortWORKS, ComfortVIEW and Service Tool.  
METR OFF  
LANG ENGLISH  
Adjusting the Contrast — The contrast of the display can be  
adjusted to suit ambient conditions. To adjust the contrast of  
Pressing  
will cause the “OFF” to flash. Use the up  
ENTER  
or down arrow keys to change “OFF” to “ON”. Pressing  
will illuminate all LEDs and display all pixels in the  
the Navigator module, press the  
key until the dis-  
ESCAPE  
ENTER  
play reads, “Select a menu item.” Using the arrow keys move  
view screen. Pressing the up and down arrow keys simultane-  
ously allows the user to adjust the display brightness. Use the  
up or down arrow keys to adjust screen brightness. Press  
to the Configuration mode. Press  
this mode. The display will read:  
to obtain access to  
ENTER  
> TEST OFF  
METR OFF  
LANG ENGLISH  
to accept the change. The Navigator module will  
ENTER  
keep this setting as long as it is plugged in to the LEN bus.  
Pressing  
will cause the “OFF” to flash. Use the up  
ENTER  
or down arrow to change “OFF” to “ON”. Pressing  
Comf  
or  
ENTER  
will illuminate all LEDs and display all pixels in the view  
screen. Pressing and simultaneously  
t
Link  
ESCAPE  
ENTER  
allows the user to adjust the display contrast. Use the up or  
down arrows to adjust the contrast. The screen’s contrast will  
MODE  
Run  
Alar  
S
m
Status  
tatus  
Ser  
vice  
Te  
s
t
Te  
m
per  
atur  
es  
P
ressures  
Setpoints  
Inputs  
change with the adjustment. Press  
to accept the  
ENTER  
Outputs  
Configur  
ation  
Time Cloc  
change. The Navigator module will keep this setting as long as  
it is plugged in to the LEN bus.  
k
ESC  
Oper  
ating Modes  
Alar  
m
s
ENTER  
Adjusting the Backlight Brightness — The backlight of the  
display can be adjusted to suit ambient conditions. The factory  
default is set to the highest level. To adjust the backlight of the  
Navigator module, press the  
reads, “Select a menu item.” Using the arrow keys move to the  
key until the display  
ESCAPE  
Fig. 2 — Accessory Navigator™ Display Module  
Table 2 — Scrolling Marquee Display Menu Structure*  
RUN  
STATUS  
SERVICE  
TEST  
SET  
POINTS  
TIME  
CLOCK  
OPERATING  
MODES  
MODE  
TEMPERATURES PRESSURES  
INPUTS OUTPUTS CONFIGURATION  
ALARMS  
Auto  
View of  
Run Status  
(VIEW)  
Service  
Test Mode  
(TEST)  
Pressures  
Cooling  
Setpoints  
(COOL)  
General  
Inputs  
(GEN.I)  
General  
Outputs  
(GEN.O)  
Display  
Configuration  
(DISP)  
Time of  
Day  
(TIME)  
Unit Temperatures  
Modes  
(MODE)  
Current  
(CRNT)  
Circuit A  
(UNIT)  
(PRC.A)  
Unit Run  
Hour and  
Start  
Head  
Month,  
Date, Day,  
and Year  
(DATE)  
Outputs  
and Pumps  
(OUTS)  
Temperatures  
Circuit A  
(CIR.A)  
Circuit  
Inputs  
(CRCT)  
Outputs  
Circuit A  
(CIR.A)  
Unit  
Configuration  
(UNIT)  
Reset  
Alarms  
(RCRN)  
Pressure  
Setpoint  
(HEAD)  
(RUN)  
Circuit and  
Compressor  
Run Hours  
(HOUR)  
Brine  
Freeze  
Setpoint  
(FRZ)  
Daylight  
Savings  
Time  
Ciruit A Comp  
Test  
(CMPA)  
4-20mA  
Inputs  
(4-20)  
Unit Options 1  
Hardware  
(OPT1)  
Alarm  
History  
(HIST)  
(DST)  
Local  
Holiday  
Schedules  
(HOL.L)  
Compressor  
Starts  
(STRT)  
Unit Options 2  
Controls  
(OPT2)  
SUB-MODE  
Preventive  
Maintenance  
(PM)  
CCN Network  
Configuration  
(CCN)  
Schedule  
Number  
(SCH.N)  
Local  
Occu-  
Software  
Version  
(VERS)  
Reset Cool Temp  
(RSET)  
pancy  
Schedule  
(SCH.L)  
Set Point and  
Ramp Load  
(SLCT)  
Schedule  
Override  
(OVR)  
Service  
Configuration  
(SERV)  
Broadcast  
Configuration  
(BCST)  
LEGEND  
For example, using the language selection item:  
Language Selection (ConfigurationDISPLANG)  
Ckt — Circuit  
*Throughout this text, the location of items in the menu structure will be  
described in the following format:  
Item Expansion (Mode NameSub-mode NameITEM)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Run Status Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY  
EXPANSION  
SUB-MODE  
VIEW  
ITEM  
EWT  
LWT  
COMMENT  
ENTER  
XXX.X F  
ENTERING FLUID TEMP  
LEAVING FLUID TEMP  
ACTIVE SETPOINT  
CONTROL POINT  
XXX.X F  
SETP XXX.X F  
CTPT XXX.X F  
LOD.F  
STAT  
XXX  
X
LOAD/UNLOAD FACTOR  
CONTROL MODE  
0 = Service Test  
1 = Off Local  
2 = Off CCN  
3 = Off Time  
4 = Off Emrgcy  
5 = On Local  
6 = On CCN  
7 = On Time  
8 = Ht Enabled  
9 = Pump Delay  
OCC  
YES/NO  
OCCUPIED  
OVERRIDE MODES IN EFFECT  
PERCENT TOTAL CAPACITY  
REQUESTED STAGE  
CURRENT ALARMS & ALERTS  
TIME OF DAY  
MODE YES/NO  
CAP  
STGE  
ALRM  
TIME  
XXX %  
X
XXX  
XX.XX  
XX  
00.00-23.59  
1 = January, 2 = February, etc.  
01-31  
MNTH  
DATE  
YEAR  
MONTH OF YEAR  
XX  
DAY OF MONTH  
XX  
YEAR OF CENTURY  
RUN  
ENTER  
HRS.U XXXX HRS  
MACHINE OPERATING HOURS  
MACHINE STARTS  
STR.U  
HR.P1  
HR.P2  
XXXX  
XXXX.X  
XXXX.X  
PUMP 1 RUN HOURS  
PUMP 2 RUN HOURS  
HOUR  
STRT  
PM  
ENTER  
HR.A1 XXXX HRS  
HR.A2 XXXX HRS  
HR.A3 XXXX HRS  
COMPRESSOR A1 RUN HOURS  
COMPRESSOR A2 RUN HOURS  
COMPRESSOR A3 RUN HOURS  
COMPRESSOR A1 STARTS  
COMPRESSOR A2 STARTS  
COMPRESSOR A3 STARTS  
STRAINER MAINTENANCE  
STRAINER SRVC INTERVAL  
STRAINER SRVC COUNTDOWN  
ENTER  
ST.A1  
ST.A2  
ST.A3  
STRN  
XXXX  
XXXX  
XXXX  
ENTER  
ENTER  
SI.ST  
S.T.DN  
S.T.MN  
ST.DT  
XXXX HRS  
XXXX HRS  
YES/NO  
STRAINER MAINT. DONE  
STRAINER MAINT. DATES  
MM/DD/YY HH:MM  
User Entry  
ENTER  
S.T.M0  
S.T.M1  
S.T.M2  
S.T.M3  
S.T.M4  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Run Status Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY  
EXPANSION  
SUB-MODE  
VERS  
ITEM  
COMMENT  
ENTER  
AUX  
CESR131333-xx-xx  
CESR131279-xx-xx  
CESR131174-xx-xx  
CESR131171-xx-xx  
CESR130227-xx-xx  
xx-xx is Version number*  
MBB  
EMM  
MARQ  
NAVI  
xx-xx is Version number*  
xx-xx is Version number*  
xx-xx is Version number*  
xx-xx is Version number*  
*Press  
ENTER  
and  
ESCAPE  
simultaneously to obtain version number.  
Table 4 — Service Test Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
TEST  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
ON/OFF  
SERVICE TEST MODE  
To Enable Service Test Mode,  
move Enable/Off/Remote  
Contact switch to OFF. Change  
TEST to ON. Move switch to  
ENABLE.  
ENTER  
OUTS  
OUTPUTS AND PUMPS  
COOLER PUMP RELAY  
CLR.P  
CND.P  
UL.TM  
CC.H  
ON/OFF  
ON/OFF  
0 to 15  
CONDENSER PUMP  
COMP A1 UNLOAD TIME  
CRANKCASE HEATER  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
CW.VO  
CW.VC  
LL.SV  
RMT.A  
CONDENSER VALVE OPEN  
CONDENSER VALVE CLOSE  
LIQUID LINE SOLENOID  
REMOTE ALARM RELAY  
CMPA  
CIRCUIT A COMPRESSOR TEST  
COMPRESSOR A1 RELAY  
ENTER  
CC.A1  
UL.TM  
CC.A2  
CC.A3  
MLV  
ON/OFF  
0 to 15  
COMP A1 UNLOAD TIME  
COMPRESSOR A2 RELAY  
COMPRESSOR A3 RELAY  
MINIMUM LOAD VALVE RELAY  
ON/OFF  
ON/OFF  
ON/OFF  
Table 5 — Temperature Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
UNIT  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
ENT AND LEAVE UNIT TEMPS  
ENTER  
CEWT  
CLWT  
CDET  
CDLT  
OAT  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
COOLER ENTERING FLUID  
COOLER LEAVING FLUID  
CONDENSER ENTERING FLUID  
CONDENSER LEAVING FLUID  
OUTSIDE AIR TEMPERATURE  
SPACE TEMPERATURE  
SPT  
DLWT  
LEAD/LAG LEAVING FLUID  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — Temperature Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
CIR.A  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
TEMPERATURES CIRCUIT A  
ENTER  
SCT.A  
SST.A  
RGT.A  
D.GAS  
SH.A  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X ^F  
SATURATED CONDENSING TMP  
SATURATED SUCTION TEMP  
COMPR RETURN GAS TEMP  
DISCHARGE GAS TEMP  
SUCTION SUPERHEAT TEMP  
Table 6 — Pressure Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
PRC.A  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
PRESSURES CIRCUIT A  
ENTER  
DP.A  
SP.A  
XXX.X PSIG  
XXX.X PSIG  
DISCHARGE PRESSURE  
SUCTION PRESSURE  
Table 7 — Set Points Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
COOL  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
COOLING SETPOINTS  
ENTER  
CSP.1  
CSP.2  
CSP.3  
XXX.X F  
XXX.X F  
XXX.X F  
COOLING SETPOINT 1  
COOLING SETPOINT 2  
ICE SETPOINT  
Default: 44 F  
Default: 44 F  
Default: 32 F  
HEAD  
FRZ  
HEAD PRESSURE SETPOINTS  
HEAD SETPOINT  
ENTER  
ENTER  
H.DP  
XXX.X F  
XXX.X F  
Default: 95 F  
Default: 34 F  
BRINE FREEZE SETPOINT  
BRINE FREEZE POINT  
BR.FZ  
Table 8 — Inputs Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
GEN.I  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
GENERAL INPUTS  
ENTER  
STST  
FLOW  
CD.FL  
DLS1  
DLS2  
ICED  
STRT/STOP  
ON/OFF  
START/STOP SWITCH  
COOLER FLOW SWITCH  
CONDENSER FLOW SWITCH  
DEMAND LIMIT SWITCH 1  
DEMAND LIMIT SWITCH 2  
ICE DONE  
OPEN/CLSE  
ON/OFF  
ON/OFF  
ON/OFF  
DUAL  
ON/OFF  
DUAL SETPOINT SWITCH  
CRCT  
4-20  
CIRCUITS INPUTS  
ENTER  
FKA1  
FKA2  
FKA3  
ON/OFF  
ON/OFF  
ON/OFF  
COMPRESSOR A1 FEEDBACK  
COMPRESSOR A2 FEEDBACK  
COMPRESSOR A3 FEEDBACK  
4-20 MA INPUTS  
ENTER  
DMND  
RSET  
CSP  
XX.X MA  
XX.X MA  
XX.X MA  
4-20 MA DEMAND SIGNAL  
4-20 MA RESET SIGNAL  
4-20 MA COOLING SETPOINT  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Outputs Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
GEN.O  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
GENERAL OUTPUTS  
ENTER  
C.LWP  
C.DWP  
ALRM  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
COOLER PUMP RELAY  
CONDENSER PUMP  
ALARM RELAY  
CDWO  
CDWC  
CONDENSER VALVE OPEN  
CONDENSER VALVE CLOSE  
CIR.A  
OUTPUTS CIRCUIT A  
ENTER  
CC.A1  
D.SOL  
CC.A2  
CC.A3  
CCH  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
COMPRESSOR A1 RELAY  
DIGITAL SCROLL SOLENOID  
COMPRESSOR A2 RELAY  
COMPRESSOR A3 RELAY  
CRANKCASE HEATER RELAY  
LIQUID LINE SOLENOID  
LLSV  
MLV.R  
MINIMUM LOAD VALVE RELAY  
Table 10 — Configuration Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
DISP  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
DISPLAY CONFIGURATION  
ENTER  
TEST  
ON/OFF  
TEST DISPLAY LEDS  
Off = English  
On = Metric  
METR  
LANG  
ON/OFF  
X
METRIC DISPLAY  
LANGUAGE SELECTION  
Default: 0  
0 = English  
1 = Espanol  
2 = Francais  
3 = Portuguese  
PAS.E  
PASS  
ENBL/DSBL  
xxxx  
PASSWORD ENABLE  
SERVICE PASSWORD  
UNIT CONFIGURATION  
Default: Enable  
Default: 1111  
UNIT  
ENTER  
2=WaterCooled  
3=Split System  
TYPE  
x
UNIT TYPE  
SIZE  
SZA.1  
SZA.2  
SZA.3  
XX  
XX  
XX  
XX  
UNIT SIZE  
COMPRESSOR A1 SIZE  
COMPRESSOR A2 SIZE  
COMPRESSOR A3 SIZE  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Default: Yes (A1 Digital Scroll)  
Default: 7  
A1.TY  
MAX.T  
No/Yes  
0 to 15  
COMPRESSOR A1 DIGITAL?  
MAXIMUM A1 UNLOAD TIME  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
OPT1  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
UNIT OPTIONS 1 HARDWARE  
Default: Water  
1 = Water  
2 = Medium Temperature Brine  
ENTER  
FLUD  
X
COOLER FLUID  
MLV.S  
R.G.EN  
OAT.E  
D.G.EN  
CSB.E  
CPC  
YES/NO  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
ON/OFF  
MINIMUM LOAD VALVE SELECT  
RETURN GAS SENSOR ENABLE  
ENABLE OAT SENSOR  
Default: No  
DISCHARGE GAS TEMP ENABLE  
CSB BOARDS ENABLE  
COOLER PUMP CONTROL  
Default: On  
PM.DY  
DPME  
DFLS  
XX MIN  
COOLER PUMP SHUTDOWN DLY  
ENABLE CONDENSER PUMP  
ENABLE COND FLOW SWITCH  
ENABLE COND WTR SENSORS  
0 to 10 minutes, Default: 1 min.  
0 to 2  
x
ENBL/DSBL  
ENBL/DSBL  
CDWS  
OPT2  
UNIT OPTIONS 2 CONTROLS  
CONTROL METHOD  
CTRL  
X
Default: Switch  
ENTER  
0 = Enable/Off/Remote Switch  
2 = Occupancy  
3 = CCN Control  
Default: 60  
LCWT  
DELY  
ICE.M  
XX.X F  
XX  
HIGH LCW ALERT LIMIT  
MINUTES OFF TIME  
ICE MODE ENABLE  
Range: 2 to 60 F  
Default: 0 Minutes  
Range: 0 to 15 Minutes  
ENBL/DSBL  
Default: Disable  
CCN  
CCN NETWORK CONFIGURATION  
CCN ADDRESS  
Default: 1  
Range: 1 to 239  
CCNA  
XXX  
ENTER  
Default: 0  
CCNB  
BAUD  
XXX  
X
CCN BUS NUMBER  
CCN BAUD RATE  
Range: 0 to 239  
Default: 9600  
1 = 2400  
2 = 4800  
3 = 9600  
4 = 19,200  
5 = 38,400  
RSET  
RESET COOL TEMP  
CRST  
X
COOLING RESET TYPE  
Default: No Reset  
0 = No Reset  
ENTER  
1 = 4 to 20 mA Input  
2 = Outdoor Air Temperature  
3 = Return Fluid  
4 = Space Temperature  
Default: 0.0F  
MA.DG  
RM.NO  
RM.F  
XX.X F  
XXX.X F  
XXX.X F  
XX.X F  
4-20 - DEGREES RESET  
REMOTE - NO RESET TEMP  
REMOTE - FULL RESET TEMP  
REMOTE - DEGREES RESET  
RETURN - NO RESET TEMP  
RETURN - FULL RESET TEMP  
Range: –30 to 30F  
Default: 125F (51.7C)  
Range: 0° to 125F  
Default: 0.0F (-17.8C)  
Range: 0to 125F  
Default: 0.0F  
Range: –30 to 30F  
RM.DG  
RT.NO  
RT.F  
Default: 10.0F (5.6C)  
Range: 0to 125F COOLER T  
XXX.X F  
XXX.X F  
Default: 0.0F (0.0C)  
Range: 0to 125F COOLER T  
Default: 0.0F  
RT.DG  
DMDC  
XX.X F  
RETURN - DEGREES RESET  
DEMAND LIMIT SELECT  
Range: –30 to 30F (–34.4 to -1.1 C)  
X
Default: None  
0 = None  
1 = Switch  
2 = 4 to 20 mA Input  
3 = CCN Loadshed  
Default: 100%  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
XXX %  
XXX  
DEMAND LIMIT AT 20 MA  
LOADSHED GROUP NUMBER  
LOADSHED DEMAND DELTA  
MAXIMUM LOADSHED TIME  
DEMAND LIMIT SWITCH 1  
DEMAND LIMIT SWITCH 2  
Range: 0 to 100%  
Default: 0  
Range: 0 to 99  
Default: 0%  
Range: 0 to 60%  
XXX %  
XXX  
Default: 60 minutes  
Range: 0 to 120 minutes  
Default: 80%  
Range: 0 to 100%  
XXX %  
XXX %  
Default: 50%  
Range: 0 to 100%  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
EXPANSION  
SUB-MODE  
ITEM  
DISPLAY  
COMMENT  
LLEN  
ENBL/DSBL  
LEAD/LAG CHILLER ENABLE  
Default: Disable  
Default: Master  
MSSL  
SLVA  
SLVE/MAST  
XXX  
MASTER/SLAVE SELECT  
SLAVE ADDRESS  
Default: 0  
Range: 0 to 239  
ENTER  
Default: Master Leads  
0 = Master Leads  
1 = Slave Leads  
2 = Automatic  
RSET  
(cont)  
LLBL  
X
LEAD/LAG BALANCE SELECT  
Default: 168 hours  
LLBD  
LLDY  
PARA  
XXX  
XXX  
YES  
LEAD/LAG BALANCE DELTA  
LAG START DELAY  
Range: 40 to 400 hours  
Default: 5 minutes  
Range: 0 to 30 minutes  
PARALLEL CONFIGURATION  
Default: YES (CANNOT BE CHANGED)  
SLCT  
SETPOINT AND RAMP LOAD  
COOLING SETPOINT SELECT  
CLSP  
X
Default: Single  
0 = Single  
1 = Dual Switch  
2 = Dual CCN Occupied  
3 = 4 to 20 mA Input (requires  
EMM)  
ENTER  
RL.S  
CRMP  
SCHD  
Z.GN  
ENBL/DSBL  
RAMP LOAD SELECT  
COOLING RAMP LOADING  
SCHEDULE NUMBER  
Default: Enable  
Default: 1.0  
Range: 0.2 to 2.0  
X.X  
XX  
Default: 1  
Range: 1 to 99  
Default: 1.0  
Range: 1.0 to 4.0  
X.X  
DEADBAND MULTIPLIER  
SERV  
SERVICE CONFIGURATION  
ENABLE COMPRESSOR A1  
ENTER  
EN.A1  
EN.A2  
EN.A3  
REV.R  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
Unit dependent  
Unit dependent  
Unit dependent  
Default: Enable  
ENABLE COMPRESSOR A2  
ENABLE COMPRESSOR A3  
REVERSE ROTATION ENABLE  
BCST  
BROADCAST CONFIGURATION  
CCN TIME/DATE BROADCAST  
ENTER  
T.D.BC  
OAT.B  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
CCN OAT BROADCAST  
GLOBAL SCHEDULE BROADCAST  
CCN BROADCAST ACK’ER  
G.S.BC  
BC.AK  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 — Time Clock Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
TIME  
ITEM  
DISPLAY  
SUB-ITEM  
DISPLAY  
COMMENT  
EXPANSION  
TIME OF DAY  
ENTER  
HH.MM  
XX.XX  
HOUR AND MINUTE  
Military (00:00 – 23:59)  
DATE  
MONTH,DATE,DAY AND YEAR  
MONTH OF YEAR  
ENTER  
MNTH  
DOM  
DAY  
XX  
XX  
1-12 (1 = January, 2 = February, etc)  
Range: 01-31  
DAY OF MONTH  
DAY OF WEEK  
X
1-7 (1 = Monday, 2 = Tuesday, etc)  
YEAR  
XXXX  
YEAR OF CENTURY  
DST  
DAYLIGHT SAVINGS TIME  
MONTH  
ENTER  
STR.M  
STR.W  
STR.D  
MIN.A  
STP.M  
STP.W  
STP.D  
MIN.S  
XX  
X
Default: 4, Range 1 – 12  
Default: 1, Range 1 – 5  
Default: 7, Range 1 – 7  
Default: 60, Range 0 – 99  
Default: 10, Range 1 – 12  
Default: 5, Range 1 – 5  
Default: 7, Range 1 – 7  
Default: 60, Range 0 – 99  
WEEK  
DAY  
X
XX  
XX  
XX  
XX  
XX  
MINUTES TO ADD  
MONTH  
WEEK  
DAY  
MINUTES TO SUBTRACT  
HOL.L  
LOCAL HOLIDAY SCHEDULES  
HOLIDAY START MONTH  
HD.01 through HD.30  
Range 0 – 12  
ENTER  
MON  
DAY  
LEN  
XX  
XX  
START DAY  
Range 0 – 31  
XX  
XX  
DURATION (DAYS)  
Range 0 - 99  
SCH.N  
SCH.L  
SCHEDULE NUMBER  
Default: 1, Range 1 – 99  
LOCAL OCCUPANCY SCHEDULE  
ENTER  
ENTER  
PER.1  
OCCUPANCY PERIOD 1*  
PERIOD OCCUPIED TIME  
PERIOD UNOCCUPIED TIME  
MONDAY IN PERIOD  
OCC.1  
UNC.1  
MON.1  
TUE.1  
WED.1  
THU.1  
FRI.1  
XX:XX  
XX.XX  
Military (00:00 – 23:59)  
Military (00:00 – 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
TUESDAY IN PERIOD  
WEDNESDAY IN PERIOD  
THURSDAY IN PERIOD  
FRIDAY IN PERIOD  
SAT.1  
SATURDAY IN PERIOD  
SUNDAY IN PERIOD  
SUN.1  
HOL.1  
HOLIDAY IN PERIOD  
OVR  
SCHEDULE OVERRIDE  
ENTER  
OVR.T  
OVR.L  
T.OVR  
X
X
TIMED OVERRIDE HOURS  
Default: 0, Range 0-4 hours  
Default: 0, Range 0-4 hours  
User Entry  
OVERRIDE TIME LIMIT  
TIMED OVERRIDE  
YES/NO  
* Repeats for Occupancy Periods 2 through 8.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 12 — Operating Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
MODE  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
MODES CONTROLLING UNIT  
ENTER  
MD01  
MD03  
MD05  
MD06  
MD07  
MD09  
MD10  
MD13  
MD14  
MD15  
MD16  
MD17  
MD18  
MD19  
MD20  
MD21  
MD23  
MD24  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
CSM CONTROLLING CHILLER  
MASTER/SLAVE CONTROL  
RAMP LOAD LIMITED  
TIMED OVERRIDE IN EFFECT  
LOW COOLER SUCTION TEMPA  
SLOW CHANGE OVERRIDE  
MINIMUM OFF TIME ACTIVE  
DUAL SETPOINT  
TEMPERATURE RESET  
DEMAND LIMITED  
COOLER FREEZE PROTECTION  
LOW TEMPERATURE COOLING  
HIGH TEMPERATURE COOLING  
MAKING ICE  
STORING ICE  
HIGH SCT CIRCUIT A  
MINIMUM COMP ON TIME  
PUMP OFF DELAY TIME  
LEGEND  
CSM  
SCT  
WSM  
Chillervisor System Manager  
Saturated Condensing Temperature  
Water System Manager  
Table 13 — Alarms Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
CRNT  
ITEM  
COMMENT  
EXPANSION  
Alarms are shown as AXXX.  
Alerts are shown as TXXX.  
ENTER  
ENTER  
ENTER  
AXXX OR TXXX  
YES/NO  
CURRENTLY ACTIVE ALARMS  
RESET ALL CURRENT ALARMS  
ALARM HISTORY  
RCRN  
HIST  
Alarms are shown as AXXX.  
Alerts are shown as TXXX.  
AXXX OR TXXX  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14 — Operating Modes  
MODE  
NO.  
ITEM EXPANSION  
DESCRIPTION  
01  
03  
CSM CONTROLLING CHILLER  
MASTER/SLAVE CONTROL  
RAMP LOAD LIMITED  
Chillervisor System Manager (CSM) is controlling the chiller.  
Dual Chiller control is enabled.  
Rampload(pull-down)limitingineffect.Inthismode,therateatwhichleavingfluidtemperature  
isdroppedislimitedtoapredeterminedvaluetopreventcompressoroverloading.SeeCooling  
Ramp Loading (ConfigurationSLCTCRMP). The pull-down limit can be modified, if  
desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.  
05  
06  
TIMED OVERRIDE IN EFFECT  
LOW COOLER SUCTION TEMPA  
Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed  
schedule, forcing unit to Occupied mode. Override can be implemented with unit under  
Local (Enable) or CCN (Carrier Comfort Network®) control. Override expires after each use.  
Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-  
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If  
the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ  
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F  
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu-  
rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for  
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to  
decrease capacity as long as either condition exists.  
07  
SLOW CHANGE OVERRIDE  
Slow change override is in effect. The leaving fluid temperature is close to and moving  
towards the control point.  
09  
10  
MINIMUM OFF TIME ACTIVE  
DUAL SETPOINT  
Chiller is being held off by Minutes Off Time (ConfigurationOPT2DELY).  
Dual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set PointsCOOL  
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2)  
during unoccupied periods.  
13  
TEMPERATURE RESET  
DEMAND LIMITED  
Temperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-  
ing fluid set point upward and is currently controlling to the modified set point. The set point  
can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to  
20 mA signal.  
14  
Demand limit is in effect. This indicates that the capacity of the chiller is being limited by  
demand limit control option. Because of this limitation, the chiller may not be able to pro-  
duce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs  
or a 4 to 20 mA signal.  
15  
COOLER FREEZE PROTECTION  
LOW TEMPERATURE COOLING  
HIGH TEMPERATURE COOLING  
Cooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section  
for definition). The chiller will be shut down when either fluid temperature falls below the  
Freeze point.  
16  
17  
18  
Chiller is in Cooling mode and the rate of change of the leaving fluid is negative and  
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point  
exceeds fixed amount. Control will automatically unload the chiller if necessary.  
Chiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.  
Error between leaving fluid and control point exceeds fixed amount. Control will automatically  
load the chiller if necessary to better match the increasing load.  
MAKING ICE  
STORING ICE  
Chiller is in an unoccupied mode and is using Cooling Set Point 3 (Set PointsCOOL  
19  
20  
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.  
ChillerisinanunoccupiedmodeandiscontrollingtoCoolingSetPoint2(SetPointsCOOL  
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.  
HIGH SCT CIRCUIT A  
Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than  
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity  
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con-  
densing temperature.  
21  
MINIMUM COMP ON TIME  
PUMP OFF DELAY TIME  
Cooling load may be satisfied, however control continues to operate compressor to ensure  
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop  
volume.  
23  
24  
Cooling load is satisfied, however cooler pump continues to run for the number of minutes set  
by the configuration variable Cooler Pump Shutdown Delay (ConfigurationOPT1  
PM.DY).  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the main base board (MBB) is supplied with the current soft-  
ware. If necessary, reload current software. If the problem still  
persists, replace the MBB. A red LED that is lit continuously or  
blinking at a rate of once per second or faster indicates that the  
board should be replaced.  
GREEN LED — The MBB has one green LED. The Local  
Equipment Network (LEN) LED should always be blinking  
whenever power is on. All other boards have a LEN LED  
which should be blinking whenever power is on. Check LEN  
connections for potential communication errors at the board J3  
and/or J4 connectors. Communication between modules is  
accomplished by a 3-wire sensor bus. These 3 wires run in  
parallel from module to module. The J4 connector on the MBB  
provides both power and communication directly to the  
marquee display only.  
CONTROLS  
General — The 30MP liquid scroll chillers contain the  
ComfortLink™ electronic control system that controls and  
monitors all operations of the chiller.  
The control system is composed of several components as  
listed in the sections below. See Fig. 3 for a typical control box  
drawing. See Fig. 4 and 5 for control schematics.  
Main Base Board (MBB) — See Fig. 6. The MBB is  
the heart of the ComfortLink control system. It contains the  
major portion of operating software and controls the operation  
of the machine. The MBB continuously monitors input/output  
channel information received from its inputs and from all other  
modules. The MBB receives inputs from the discharge and  
suction pressure transducers and thermistors. See Table 15. The  
MBB also receives the feedback inputs from each compressor  
current sensor board and other status switches. See Table 16.  
The MBB also controls several outputs. Relay outputs con-  
trolled by the MBB are shown in Table 17. Information is  
transmitted between modules via a 3-wire communication bus  
or LEN (Local Equipment Network). The CCN (Carrier Com-  
fort Network) bus is also supported. Connections to both LEN  
and CCN buses are made at the LVT (low voltage terminal).  
YELLOW LED — The MBB has one yellow LED. The  
Carrier Comfort Network (CCN) LED will blink during times  
of network communication.  
Carrier Comfort Network® (CCN) Interface —  
The 30MP chiller units can be connected to the CCN if  
desired. The communication bus wiring is a shielded,  
3-conductor cable with drain wire and is supplied and installed  
in the field. See Table 18. The system elements are connected  
to the communication bus in a daisy chain arrangement. The  
positive pin of each system element communication connector  
must be wired to the positive pins of the system elements on  
either side of it. This is also required for the negative and  
signal ground pins of each system element. Wiring connections  
for CCN should be made at LVT. Consult the CCN Contrac-  
tor’s Manual for further information.  
NOTE: Conductors and drain wire must be 20 AWG (Ameri-  
can Wire Gage) minimum stranded, tinned copper. Individual  
conductors must be insulated with PVC, PVC/nylon, vinyl,  
Teflon, or polyethylene. An aluminum/polyester 100% foil  
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,  
or Teflon with a minimum operating temperature range of  
–20 C to 60 C is required. Wire manufactured by Alpha (2413  
or 5463), American (A22503), Belden (8772), or Columbia  
(02525) meets the above mentioned requirements.  
It is important when connecting to a CCN communication  
bus that a color coding scheme be used for the entire network  
to simplify the installation. It is recommended that red be used  
for the signal positive, black for the signal negative, and white  
for the signal ground. Use a similar scheme for cables contain-  
ing different colored wires.  
At each system element, the shields of its communication  
bus cables must be tied together. If the communication bus is  
entirely within one building, the resulting continuous shield  
must be connected to a ground at one point only. If the commu-  
nication bus cable exits from one building and enters another,  
the shields must be connected to grounds at the lightning  
suppressor in each building where the cable enters or exits the  
building (one point per building only). To connect the unit to  
the network:  
Energy Management Module (EMM) — The EMM  
module is available as a factory-installed option or as a field-  
installed accessory. The EMM module receives 4 to 20 mA  
inputs for the leaving fluid temperature reset, cooling set point  
and demand limit functions. The EMM module also receives  
the switch inputs for the field-installed 2-stage demand limit  
and ice done functions. The EMM module communicates the  
status of all inputs with the MBB, and the MBB adjusts the  
control point, capacity limit, and other functions according to  
the inputs received.  
Current Sensor Board (CSB) — The CSB is used to  
monitor the status of the compressors by measuring current and  
providing an analog input to the main base board (MBB).  
Enable/Off/Remote Contact Switch — The Enable/  
Off/Remote Contact switch is a 3-position switch used to  
control the chiller. When switched to the Enable position the  
chiller is under its own control. Move the switch to the Off  
position to shut the chiller down. Move the switch to the  
Remote Contact position and a field-installed dry contact can  
be used to start the chiller. The contacts must be capable of  
handling a 24 vac, 50-mA load. In the Enable and Remote  
Contact (dry contacts closed) positions, the chiller is allowed to  
operate and respond to the scheduling configuration, CCN  
configuration and set point data. See Fig. 7.  
Emergency On/Off Switch — The Emergency On/Off  
switch should only be used when it is required to shut the  
chiller off immediately. Power to the MBB, EMM, and  
marquee display is interrupted when this switch is off and all  
outputs from these modules will be turned off. See Fig. 7.  
Board Addresses — The main base board (MBB) has a  
3-position instance jumper that must be set to ‘1.’ The EMM  
board has 4-position DIP switches. All switches are set to ‘On’  
for all boards except the AUX2 board. The AUX2 board DIP  
switch settings are shown on the wiring schematic.  
1. Turn off power to the control box.  
2. Cut the CCN wire and strip the ends of the red (+), white  
(ground), and black (–) conductors. (Substitute appropri-  
ate colors for different colored cables.)  
3. Connect the red wire to (+) terminal on LVT of the plug,  
the white wire to COM terminal, and the black wire to the  
(–) terminal.  
4. The RJ14 CCN connector on LVT can also be used, but is  
only intended for temporary connection (for example, a  
laptop computer running Service Tool).  
Control Module Communication  
RED LED — Proper operation of the control boards can be  
visually checked by looking at the red status LEDs  
(light-emitting diodes). When operating correctly, the red status  
LEDs should be blinking in unison at a rate of once every  
2 seconds. If the red LEDs are not blinking in unison, verify  
that correct power is being supplied to all modules. Be sure that  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND FOR FIG. 3-5  
ALMR  
AUX  
C
Alarm Relay  
Auxilliary  
Contactor, Compressor  
Circuit Breaker  
CB  
CCB  
CH  
CCH  
COMP  
CR  
Compressor Circuit Breaker  
Crankcase Heater  
Crankcase Heater Relay  
Compressor  
Control Relay  
CSB  
CWFS  
CWP  
DGS  
DPT  
DTT  
DUS  
EMM  
EWT  
FB  
Current Sensor Board  
Chilled Water Flow Switch  
Chilled Water Pump  
Digital Scroll Compressor  
Discharge Pressure Transducer  
Discharge Temperature Thermistor  
Digital Unloader Solenoid  
Energy Management  
Entering Water Temperature  
Fuse Block  
FIOP  
FU  
factory Installed Option  
Fuse  
GND  
HPS  
LLSV  
LON  
LVT  
Ground  
High-Pressure Switch  
Liquid Line Solenoid Valve  
Local Operating Network  
Low Voltage Terminal  
Leaving Water Temperature  
Main Base Board  
LWT  
MBB  
MLV  
MP  
Minimum Load Valve  
Modular Motor Protection  
National Electrical Code  
Outdoor-Air Thermistor  
Plug  
NEC  
OAT  
PL  
RLY  
SPT  
SW  
Relay  
Suction Pressure Transducer  
Switch  
TB  
Terminal Block  
TRAN  
UPC  
Transformer  
Unitary Protocol Converter  
Terminal Block  
Terminal (Unmarked)  
Terminal (Marked)  
Splice  
Factory Wiring  
Field Wiring  
Accessory or Option Wiring  
To indicate common potential only; not to represent wiring.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPC LON  
OPTION  
EQUIP  
GND  
UPC  
TB3  
25242322212019181716151413121110 9  
8
7
6
5
4
3
2
1
LVT  
DISCONNECT  
OPTION CB1A/TB1A  
L1  
L2  
L3  
CCB-3  
CCB-2  
CCB-1  
EMM  
CSB-A2  
CSB-A3  
CSB-A1  
2
4
6
CCH  
CA3  
CA1  
CA2  
TRAN1  
MBB  
FB1  
LOCATED OVER EMM  
CB1  
CB2  
CB3  
REMOTE  
CONTROL  
OFF  
ON  
SW1  
OFF  
ENABLE  
SW2  
Fig. 3 — Typical Control Box — 30MP015-045 Units  
a30-4963  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TO FUSED DISCONNECT  
PER NEC  
TARN1  
a30-4965  
TO FUSED  
DISCONNECT  
PER NEC  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TRAN1  
A2  
B2  
CB2  
3.2 AMPS  
SW2  
C2  
SECONDARY 24V  
XF  
X1  
X2  
1
RED  
RED  
FU3  
BRN  
TB3  
GRN/YEL  
ORN  
MBB  
CB1  
3.2 AMPS  
ORN  
J10A  
1
2
3
4
5
6
7
8
9
1
2
3
4
5
1
2
ORN  
PNK  
LVT  
J12  
PNK  
ORN  
ORN  
ORN  
RLY 11  
GRA  
1
25  
3
ALMR  
ALARM RELAY  
SEE NOTE 7  
4
TB3  
1
5
BRN  
BRN  
BRN  
X2 TRAN1  
CWFS-3  
PNK  
2
24  
6
CR  
RLY 9  
CWP RELAY  
SEE NOTE 7  
7
2
3
8
J12  
6
LLSV-A  
RLY 10  
9
BLU  
ORN  
PNK  
20  
19  
18  
CR  
J10B  
CONDENSER FAN/PUMP RELAY  
SEE NOTE 7  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
RLY 5  
7
CONDENSER  
WATER  
VALVE  
J11  
1
ORN  
ORN  
(MPB ONLY)  
RLY 6  
6
7
RED  
RED  
GRA  
BRN  
BRN  
3
TB3  
RLY 7  
8
LLSV-A  
MLV-A  
BRN  
9
(MPA AND BRINE ONLY)  
10  
BLU  
ORN  
GRA  
VIO  
GRA  
C2 CA3  
MLV-A  
RLY 8  
RLY 1  
RLY 2  
RLY 3  
RLY 4  
BLU  
ORN  
GRA  
VIO  
C1 CCH C2  
(MPA ONLY)  
BRN  
BRN  
HPS-A  
11  
12  
BLK  
BLK  
BLK  
PNK  
PL1-1  
PL1-2  
MP-A1  
VIO  
VIO  
BRN  
BRN  
PL1-4  
PL2-4  
M1  
M2  
C1 CA1 C2  
SEE NOTE 11  
PL2-1  
13  
14  
VIO  
PL2-2  
M2 VIO  
BLK  
MP-A2  
VIO M1  
BRN  
BRN  
PL2-4  
PL3-4  
C1  
CA2  
C2  
15  
SEE NOTE 11  
PL3-1  
VIO  
PL3-2  
VIO  
MP-A3  
16  
17  
18  
VIO  
C2 CCH  
M1  
M2  
C1 CA3 C2  
BRN  
BRN  
SEE NOTE 11  
VIO  
(040,045 ONLY)  
PL3-4  
GRA  
GRA  
BRN  
BRN  
BRN  
LLSV-A  
MLV-A  
C2 CCH  
MLV FIOP  
BLK  
PNK  
1
3
PNK  
PNK  
PNK  
PNK  
BRN  
BLU  
BRN  
BRN  
BRN  
2
CWFS  
TB3  
LVT  
6
5
4
3
2
1
6
5
4
3
2
1
J11  
2
SEE NOTE  
8
PL1-3  
RED  
PL1-4  
BRN  
17  
T2 MP-A1 T1  
C2 CA1  
J6  
SEE NOTE  
9
3
4
5
6
7
8
9
RED  
PL2-3  
RED  
PL2-4  
BRN  
CWPI  
T2 MP-A2 T1  
BRN  
BRN  
C2 CA1  
C2 CA2  
(SEE  
NOTE  
12)  
SEE NOTE 10  
PL3-3  
RED  
PL3-4  
BRN  
CWFS  
4
2
C2 CA2  
C2 CA3  
T2 MP-A3 T1  
BRN  
BRN  
10  
1
2
3
4
5
6
1
2
3
4
5
6
MARQUEE  
DISPLAY  
16  
15  
14  
BLK  
WHT  
10  
9
RED  
WHT  
BLK  
RED  
WHT  
BLK  
1
2
3
4
5
6
1
2
3
4
5
6
9
8
7
6
5
4
VIO  
J4  
J3  
RED  
BRN  
BRN  
RED  
RED  
8
REMOTE  
ON-OFF  
SWITCH  
(SEE  
SW1  
ENABLE  
A1  
B1  
1
2
3
4
RED  
WHT  
BLK  
1
2
3
4
RED  
7
OFF  
ORN  
NOTE 5)  
C1  
6
13  
12  
J7  
1
MAIN  
BASE  
1
2
3
4
5
6
7
8
9
10  
5
2
DUAL  
SETPOINT  
3
AUX2  
4
BLU  
BLU  
VIO  
4
11  
12  
13  
14  
6
5
4
3
2
1
BOARD  
RED  
ORN  
BRN  
RED  
ORN  
BRN  
RED  
ORN  
BRN  
2
3
1
2
3
1
2
3
1
-
G
+
-
G
+
3
2
1
3
2
1
5
CSB  
A2  
CNPI  
CNFS  
6
7
8
3
2
1
DUS  
DTT  
-
7
8
VIO  
BRN  
3
7
J9  
J9  
J2  
J6  
CH1  
BLK  
8
CSB  
A3  
(040,045 ONLY)  
WHT  
RED  
9
DGS  
FIOP  
2
11  
1
2
10  
11  
12  
CH11  
-
1
2
RED  
BLK  
10  
11  
12  
CSB  
A1  
1
ON  
OFF  
1
DARK  
2
3
=
4
5
6
7
8
CONDENSER EWT  
ACCESSORY  
1
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
SWITCH LOCATION  
1
2
CONDENSER LWT  
ACCESSORY  
3
T-55  
ACCSY  
LVT  
SEN  
LVT  
4
J12  
T55  
LVT  
J10  
5
BLU  
3
23  
1
J13  
10  
9
1
2
GRA  
17  
16  
15  
14  
13  
12  
11  
1
2
3
4
5
6
BRN  
10  
9
4
3
2
1
6
VIO  
RED  
4
5
22  
21  
2
1
2
3
4
5
6
7
8
BLK  
4
3
2
1
EMM  
GRA  
RED  
RED  
BLU  
BLU  
RED  
3
ICE DONE  
8
WHT  
RED  
BRN  
RED  
BLK  
WHT  
RED  
7
BLK  
WHT  
RED  
3
8
J3  
J4  
4
7
RED  
WHT  
4
8
BLK  
WHT  
RED  
7
OAT ACCESSORY OR  
DUAL CHILLER LWT  
5
DLS STEP  
DLS STEP  
1
2
6
RGTA  
ACCESSORY  
5
6
9
6
5
J5  
6
5
7
BLK  
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
7
4
8
3
4
3
2
1
COOLER ENTERING  
FLUID TEMP  
J7  
J6  
RED  
8
BLK  
WHT  
RED  
3
4
3
2
1
9
2
9
2
BLK  
WHT  
RED  
J1  
BLK  
RED  
10  
11  
12  
13  
14  
1
10  
11  
12  
13  
14  
1
COOLER LEAVING  
FLUID TEMP  
J8  
BLK  
10  
9
8
7
6
5
4
3
2
1
FIOP/  
ACCESSORY  
DEMAND  
LIMIT  
4-20mA  
UPC  
7
8
+
-
1
PORT  
2
1
2
2
RED  
BLK  
1
NET  
+
-
LON  
OPTION  
VIO  
BRN  
3
2
3
4
5
NET  
N/C  
N/C  
3
J3 GND  
NET  
4
TEMP  
RESET  
4-20mA  
4
9
+
-
5
5
ORN  
PNK  
J4  
1
WHT  
SIGNAL  
B
6
RED  
6
+
7
PORT 1A  
2
8
C
A
COOLING  
SETPOINT  
4-20mA  
7
10  
+
-
DPTA  
GRN  
BLK  
1
2
3
NET  
NET  
+
2
8
8
9
-
9
9
SHIELD  
UPC OPT  
10  
10  
11  
12  
B
C
A
RED  
10  
11  
12  
+
11  
12  
SPTA  
GRN  
BLK  
-
a30-4966  
Fig. 5 — Typical Control Wiring Schematic — 30MP015-045 Units  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RGTA, CNDE, CNDL, EWT, LWT, and OAT are identical in  
temperature versus resistance and voltage drop performance.  
The dual chiller thermistor (DLWT) is 5 kat 77 F (25 C)  
thermistor. Space temperature thermistor (SPT) is a 10 kat  
77 F (25 C). See Thermistors section for temperature-resis-  
tance-voltage drop characteristics.  
COOLER LEAVING FLUID SENSOR (LWT) — The thermis-  
tor is installed in a well in the factory-installed leaving fluid  
piping coming from the bottom of the brazed-plate heat  
exchanger.  
COOLER ENTERING FLUID SENSOR (EWT) The therm-  
istor is installed in a well in the factory-installed entering fluid  
piping coming from the top of the brazed-plate heat exchanger.  
CONDENSER LEAVING FLUID SENSOR (CNDL) — The  
thermistor is installed in a well in the factory-installed leaving  
fluid piping coming from the bottom of the brazed-plate heat  
exchanger.  
IMPORTANT: A shorted CCN bus cable will prevent some  
routines from running and may prevent the unit from start-  
ing. If abnormal conditions occur, unplug the connector. If  
conditions return to normal, check the CCN connector and  
cable. Run new cable if necessary. A short in one section of  
the bus can cause problems with all system elements on the  
bus.  
Table 15 — Thermistor Designations  
PIN  
THERMISTOR CONNECTION  
POINT  
THERMISTOR INPUT  
CLWT  
CEWT  
J8-13,14 (MBB) Cooler Leaving Fluid  
J8-11,12 (MBB) Cooler Entering Fluid  
J8-9,10 (MBB)  
Circuit A Return Gas  
Temperature (accessory)  
RGTA  
J8-6,7 (MBB),  
LVT 4,13  
Outdoor-Air Temperature  
Sensor (accessory) or Dual  
LWT Sensor  
OAT  
COOLER ENTERING FLUID SENSOR (CNDE) The therm-  
istor is installed in a well in the factory-installed entering fluid  
piping coming from the top of the brazed-plate heat exchanger.  
J8-5,6 (MBB)  
LVT-3,4  
Accessory Remote Space  
Temperature Sensor  
SPT  
COMPRESSOR RETURN GAS TEMPERATURE SEN-  
SOR (RGTA) — This accessory thermistor can be installed in  
a well located in the suction line.  
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —  
This sensor is an accessory that is remotely mounted and used  
for outdoor air temperature reset. See Table 15.  
J8-1,2  
Condenser Entering Water  
Temperature Sensor  
Condenser Leaving Water  
Temperature Sensor  
CNDE  
CNDL  
J8-3,4  
LEGEND  
LWT — Leaving Water Temperature  
MBB — Main Base Board  
DUAL LEAVING WATER TEMPERATURE SENSOR  
(DLWT) — This input can be connected to the LVT. See Ta-  
ble 15. For dual chiller applications (parallel only are support-  
ed), connect the dual chiller leaving fluid temperature sensor  
(5 kthermistor, Carrier part no. HH79NZ029) to the outside  
air temperature input of the Master chiller. If outside air tem-  
perature is required for reset applications, connect the sensor to  
the Slave chiller and configure the slave chiller to broadcast the  
value to the Master chiller.  
REMOTE SPACE TEMPERATURE SENSOR (SPT) —  
The sensor (part no. 33ZCT55SPT) is an accessory sensor that  
is remotely mounted in the controlled space and used for space  
temperature reset. The sensor should be installed as a wall-  
mounted thermostat would be (in the conditioned space where  
it will not be subjected to either a cooling or heating source or  
direct exposure to sunlight, and 4 to 5 ft above the floor).  
Table 16 — Status Inputs  
STATUS SWITCH  
Condenser Flow Switch  
Dual Set Point  
PIN CONNECTION POINT  
LVT-11,17, J7-2, J6-2  
LVT-12,13, J7-3,4  
LVT-14,15  
LVT-16,17, J6-2, J7-10  
J9-11,12  
Remote On/Off  
Cooler Flow Switch Interlock  
Compressor Fault Signal, A1  
Compressor Fault Signal, A2  
Compressor Fault Signal, A3  
J9-5,6  
J9-8,9  
Table 17 — Output Relays  
RELAY  
NO.  
DESCRIPTION  
Energize Compressor A1  
Energize Compressor A2  
Energize Compressor A3  
Energize Minimum Load Valve  
Water Valve Open  
Water Valve Close  
Liquid Line Solenoid Valve  
Crankcase Heater Relay (30MPA Only)  
Chilled Water Pump  
Condenser Fan/Pump  
Alarm Relay  
Space temperature sensor wires are to be connected to  
terminals in the unit main control box. The space temperature  
sensor includes a terminal block (SEN) and a RJ11 female  
connector. The RJ11 connector is used access into the Carrier  
Comfort Network® (CCN) at the sensor.  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
K9  
K10  
K11  
To connect the space temperature sensor (Fig. 8):  
1. Using a 20 AWG twisted pair conductor cable rated for  
the application, connect 1 wire of the twisted pair to one  
SEN terminal and connect the other wire to the other  
SEN terminal located under the cover of the space  
temperature sensor.  
2. Connect the other ends of the wires to terminals 3 and 4  
on LVT located in the unit control box.  
Units on the CCN can be monitored from the space at the  
sensor through the RJ11 connector, if desired. To wire the RJ11  
connector into the CCN (Fig. 9):  
Table 18 — CCN Communication Bus Wiring  
PART NO.  
MANUFACTURER  
Regular Wiring  
1895  
Plenum Wiring  
Alpha  
American  
Belden  
Columbia  
Manhattan  
Quabik  
A48301  
884421  
IMPORTANT: The cable selected for the RJ11 connector  
wiring MUST be identical to the CCN communication bus  
wire used for the entire network. Refer to Table 18 for  
acceptable wiring.  
A21451  
8205  
D6451  
M13402  
6130  
M64430  
1. Cut the CCN wire and strip ends of the red (+), white  
(ground), and black (–) conductors. (If another wire color  
scheme is used, strip ends of appropriate wires.)  
Sensors — The electronic control uses 2 to 7 thermistors to  
sense temperatures for controlling chiller operation. See  
Table 15. These sensors are outlined below. Thermistors  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RED LED - STATUS  
GREEN LED -  
LEN (LOCAL EQUIPMENT NETWORK)  
YELLOW LED -  
CCN (CARRIER COMFORT NETWORK)  
INSTANCE JUMPER  
CEPL130346-01  
K11  
K10  
K9  
K5  
K8  
K6  
K7  
J1  
STATUS  
J2  
J3  
J10  
LEN  
J4  
K1  
K4  
K3  
K2  
CCN  
J5  
J6  
J7  
J8  
J9  
Fig. 6 — Main Base Board  
a30-4967  
Fig. 7 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations  
T-55 SPACE  
SENSOR  
a30-4968  
SPT (T10) PART NO. 33ZCT55SPT  
SENSOR  
6
5
4
3
2
1
CCN+  
LVT  
TO CCN  
CCN GND  
SEN  
SEN  
COMM 1  
BUS (PLUG)  
AT UNIT  
3
CCN-  
4
Fig. 8 — Typical Space Temperature  
Sensor Wiring  
Fig. 9 — CCN Communications Bus Wiring  
to Optional Space Sensor RJ11 Connector  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Insert and secure the red (+) wire to terminal 5 of the  
space temperature sensor terminal block.  
3. Insert and secure the white (ground) wire to terminal 4 of  
the space temperature sensor.  
4. Insert and secure the black (–) wire to terminal 2 of the  
space temperature sensor.  
5. Connect the other end of the communication bus cable to  
the remainder of the CCN communication bus.  
stages. The chilled fluid temperature set point can be automati-  
cally reset by the return fluid temperature, space, or outdoor-air  
temperature reset features. It can also be reset from an external  
4 to 20-mA signal (requires energy management module FIOP  
or accessory).  
The capacity control algorithm runs every 30 seconds. The  
algorithm attempts to maintain the Control Point at the desired  
set point. Each time it runs, the control reads the entering and  
leaving fluid temperatures. The control determines the rate at  
which conditions are changing and calculates 2 variables based  
on these conditions. Next, a capacity ratio is calculated using  
the 2 variables to determine whether or not to make any  
changes to the current stages of capacity. This ratio value  
ranges from –100 to +100%. If the next stage of capacity is a  
compressor, the control starts (stops) a compressor when the  
ratio reaches +100% (–100%). If installed, the minimum load  
valve solenoid will be energized with the first stage of capacity.  
Minimum load valve value is a fixed 30% in the total capacity  
calculation. The control will also use the minimum load valve  
solenoid as the last stage of capacity before turning off the last  
compressor. A delay of 90 seconds occurs after each capacity  
step change. Refer to Table 19.  
MINUTES LEFT FOR START — This value is displayed  
only in the network display tables (using Service Tool,  
ComfortVIEW™ or ComfortWORKS® software) and  
represents the amount of time to elapse before the unit will start  
its initialization routine. This value can be zero without the  
machine running in many situations. This can include being  
unoccupied, ENABLE/OFF/REMOTE CONTACT switch in  
the OFF position, CCN not allowing unit to start, Demand  
Limit in effect, no call for cooling due to no load, and alarm or  
alert conditions present. If the machine should be running and  
none of the above are true, a minimum off time (DELY, see  
below) may be in effect. The machine should start normally  
once the time limit has expired.  
Energy Management Module (Fig. 10) This  
factory-installed option (FIOP) or field-installed accessory is  
used for the following types of temperature reset, demand  
limit, and/or ice features:  
4 to 20 mA leaving fluid temperature reset (requires  
field-supplied 4 to 20 mA generator)  
4 to 20 mA cooling set point reset (requires field-  
supplied 4 to 20 mA generator)  
Discrete inputs for 2-step demand limit (requires field-  
supplied dry contacts capable of handling a 24 vac,  
50 mA load)  
4 to 20 mA demand limit (requires field-supplied 4 to  
20 mA generator)  
Discrete input for Ice Done switch (requires field-  
supplied dry contacts capable of handling a 24 vac,  
50 mA load)  
See Demand Limit and Temperature Reset sections on  
pages 27 and 31 for further details.  
CAUTION  
Care should be taken when interfacing with other manufac-  
turer’s control systems due to possible power supply  
differences, full wave bridge versus half wave rectification.  
The two different power supplies cannot be mixed.  
ComfortLink™ controls use half wave rectification. A  
signal isolation device should be utilized if a full wave  
bridge signal generating device is used.  
MINUTES  
OFF  
TIME  
(ConfigurationOPT2  
DELY) — This user-configurable time period is used by the  
control to determine how long unit operation is delayed after  
power is applied/restored to the unit. Typically, this time period  
is configured when multiple machines are located on a single  
site. For example, this gives the user the ability to prevent all  
the units from restarting at once after a power failure. A value  
of zero for this variable does not mean that the unit should be  
running.  
Loss-of-Cooler Flow Protection —  
A
proof-of-  
cooler flow device is factory installed in all chillers.  
Condenser Flow Protection — A proof-of-condens-  
er flow protection accessory can be field installed in the con-  
denser water piping of all chillers. The unit must be configured  
for the input to be enabled.  
LEAD/LAG DETERMINATION — This is a configurable  
choice and is factory set to be automatic for all units unless the  
unit is equipped with minimum load, then circuit A is lead  
(ConfigurationOPT2LLCS). The value can be changed  
to Circuit A or Circuit B leading as desired. Set at automatic,  
the control will sum the current number of logged circuit starts  
and one-quarter of the current operating hours for each circuit.  
The circuit with the lowest sum is started first. Changes to  
which circuit is the lead circuit and which is the lag are also  
made when total machine capacity is at 100% or when there is  
a change in the direction of capacity (increase or decrease) and  
each circuit’s capacity is equal.  
Thermostatic Expansion Valves (TXV) — All  
units are equipped from the factory with conventional TXVs.  
The 30MPA units and 30MPW units with medium temperature  
brine also have factory-installed liquid line solenoids. The liq-  
uid line solenoid valves are not intended to be a mechanical  
shut-off. For 30MPW units, when service is required, reclaim  
the refrigerant from the system.  
For 30MPA units when service is required, the compressor  
and evaporator can be serviced by closing the factory-installed  
liquid line service valve and field-installed discharge line ser-  
vice valve. After the valves are closed, reclaim the refrigerant  
from the system.  
The TXV is set at the factory to maintain approximately 8 to  
12° F (4.4 to 6.7° C) suction superheat leaving the cooler by  
monitoring the proper amount of refrigerant into the cooler. All  
TXVs are adjustable, but should not be adjusted unless abso-  
lutely necessary.  
CAPACITY CONTROL OVERRIDES — The following over-  
rides will modify the normal operation of the routine.  
Deadband Multiplier — The user configurable Deadband  
Multiplier (ConfigurationSLCTZ.GN) has a default  
value of 1.0. The range is from 1.0 to 4.0. When set to other  
than 1.0, this factor is applied to the capacity Load/Unload  
Factor. The larger this value is set, the longer the control will  
delay between adding or removing stages of capacity. Figure  
11 shows how compressor starts can be reduced over time if  
the leaving water temperature is allowed to drift a larger  
amount above and below the set point. This value should be set  
in the range of 3.0 to 4.0 for systems with small loop volumes.  
Figure 12 shows the operating envelope for the compressor.  
Capacity Control — The control system cycles com-  
pressors, digital scroll modulting solenoid (if equipped), and  
minimum load valve solenoids (if equipped) to maintain the  
user-configured leaving chilled fluid temperature set point. En-  
tering fluid temperature is used by the main base board (MBB)  
to determine the temperature drop across the cooler and is used  
in determining the optimum time to add or subtract capacity  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
First Stage Override — If the current capacity stage is zero,  
the control will modify the routine with a 1.2 factor on adding  
the first stage to reduce cycling. This factor is also applied  
when the control is attempting to remove the last stage of  
capacity.  
Slow Change Override — The control prevents the capacity  
stages from being changed when the leaving fluid temperature  
is close to the set point (within an adjustable deadband) and  
moving towards the set point.  
CEBD430351-0396-01C  
J1  
J2  
LEN  
J4  
J3  
STATUS  
J5  
J7  
J6  
TEST 2  
GREEN LED -  
LEN (LOCAL EQUIPMENT NETWORK)  
ADDRESS  
DIP SWITCH  
RED LED - STATUS  
Fig. 10 — Energy Management Module  
Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve  
CONTROL  
STEPS  
CAPACITY STEPS  
(% Displacement)  
30MP UNIT SIZE  
015  
1
2
3
18*  
50  
100  
1
2
3
1
2
3
25*  
50  
020  
030  
100  
34*  
50  
100  
1
2
3
4
21*  
33  
040  
67  
100  
1
2
3
4
22*  
33  
045  
67  
100  
*Hot gas bypass (minimum load) valve energized.  
NOTE: These capacity steps may vary due to different capacity  
staging sequences.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 STARTS  
DEADBAND EXAMPLE  
47  
46  
45  
8
7
6
5
44  
43  
42  
41  
0
200  
400  
600  
800  
1000  
3 STARTS  
TIME (SECONDS)  
STANDARD  
DEADBAND  
LEGEND  
LWT — Leaving Water Temperature  
MODIFIED  
DEADBAND  
Fig. 11 — Deadband Multiplier  
170  
160  
150  
140  
130  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
-30  
-20  
-10  
0
10  
20  
30  
40  
50  
60  
70  
80  
SST (F)  
LEGEND  
a30-4969  
SCT — Saturated Condensing Temperature  
SST  
Saturated Suction Temperature  
Fig. 12 — Operating Envelope for R-410A Compressor  
Ramp Loading  
Ramp  
loading  
(Configura-  
may be used as needed to obtain leaving fluid temperature  
close to set point.  
tionSLCTCRMP) limits the rate of change of leaving  
fluid temperature. If the unit is in a Cooling mode and config-  
ured for Ramp Loading, the control makes 2 comparisons be-  
fore deciding to change stages of capacity. The control calcu-  
lates a temperature difference between the control point and  
leaving fluid temperature. If the difference is greater than 4° F  
(2.2° C) and the rate of change (°F or °C per minute) is more  
than the configured Cooling Ramp Loading value (CRMP),  
the control does not allow any changes to the current stage of  
capacity.  
Cooler Freeze Protection — The control will try to prevent  
shutting the chiller down on a Cooler Freeze Protection alarm  
by removing stages of capacity. If the cooler fluid selected  
is Water, the freeze point is 34 F (1.1 C). If the cooler fluid  
selected is Brine, the freeze point is the Brine Freeze Point (Set  
PointsFRZBR.FZ). This alarm condition (A207) only  
references leaving fluid temperature and NOT Brine Freeze  
point. If the cooler leaving fluid temperature is less than the  
freeze point plus 2.0° F (1.1° C), the control will immediately  
remove one stage of capacity. This can be repeated once every  
30 seconds.  
Low Saturated Suction Protection — The control will try to  
prevent shutting a circuit down due to low saturated suction  
conditions by removing stages of capacity. The circuit alert  
condition (T116) compares saturated suction temperature to the  
configured Brine Freeze Point (Set PointsFRZBR.FZ).  
The Brine Freeze point is a user-configurable value that must  
be left at 34 F (1.1 C) for 100% water systems. A lower value  
Low Entering Fluid Temperature Unloading — When the  
entering fluid temperature is below the control point, the  
control will attempt to remove 25% of the current stages being  
used. If exactly 25% cannot be removed, the control removes  
an amount greater than 25% but no more than necessary. The  
lowest stage will not be removed.  
Hot Gas Bypass — If equipped, the hot gas bypass valve is  
energized only when one compressor is running on circuit A. If  
the close control feature is enabled the hot gas bypass valve  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
may be entered for systems with brine solutions, but this value  
should be set according to the freeze protection level of the  
brine mixture. Failure to properly set this brine freeze point val-  
ue may permanently damage the brazed plate heat exchanger.  
The control will initiate Mode 7 (Circuit A) to indicate a cir-  
cuit’s capacity is limited and that eventually the circuit may  
shut down.  
Cooling Set Point Select  
SINGLE — Unit operation is based on Cooling Set Point 1  
(Set PointsCOOLCSP.1).  
DUAL SWITCH — Unit operation is based on Cooling Set  
Point 1 (Set PointsCOOLCSP.1) when the Dual Set  
Point switch contacts are open and Cooling Set Point 2 (Set  
PointsCOOLCSP.2) when they are closed.  
Operation of Machine Based on Control  
Method and Cooling Set Point Selection Set-  
tings — Machine On/Off control is determined by the  
DUAL CCN OCCUPIED — Unit operation is based on  
Cooling Set Point 1 (Set PointsCOOLCSP.1) during the  
Occupied mode and Cooling Set Point  
2
(Set  
configuration of the Control Method  
(Configuration  
PointsCOOLCSP.2) during the Unoccupied mode as  
configured under the local occupancy schedule accessible only  
from CCN. Schedule Number in Table SCHEDOVR (See Ap-  
pendix B) must be configured to 1. If the Schedule Number is  
set to 0, the unit will operate in a continuous 24-hr Occupied  
mode. Control method must be configured to 0 (switch). See  
Table 20.  
OPT2CTRL) and Cooling Set Point Select  
(ConfigurationSLCTCLSP) variables. All units are fac-  
tory configured with Cooling Set Point Select set to 0 (single  
set point). With the control method set to 0, simply switching  
the Enable/Off/Remote Contact switch to the Enable or  
Remote Contact position (external contacts closed) will put the  
chiller in an occupied state. The control mode (Run  
StatusVIEWSTAT) will be 1 (OFF LOCAL) when the  
switch is Off and will be 5 (ON LOCAL) when in the Enable  
position or Remote Contact position with external contacts  
closed.  
4 TO 20 mA INPUT — Unit operation is based on an external  
4 to 20 mA signal input to the Energy Management Module  
(EMM).  
Cooler Pump Control — The AquaSnap® 30MP ma-  
chines are configured with the Cooler Pump Control (Configu-  
rationOPT1CPC) = ON.  
Two other control methods are available for Machine On/  
Off control:  
The maximum load allowed for the Chilled Water Pump  
Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil  
is powered from the chiller control system. The starter should  
be wired between LVT 24 and TB3-1. If equipped, the field-in-  
stalled chilled water pump starter auxiliary contacts should be  
connected in series with the chilled water flow switch between  
LVT 16 and LVT 17.  
OCCUPANCY  
SCHEDULE  
(ConfigurationOPT2  
CTRL = 1) — The main base board will use the operating  
schedules as defined under the Time Clock mode in the scroll-  
ing marquee display. These schedules are identical. The sched-  
ule number must be set to 1 for local schedule.  
The schedule number can be set anywhere from 65 to 99  
for operation under a CCN global schedule. The Enable/Off/  
Remote Contact must be in the Enable or Remote Contact posi-  
tion. The control mode (Run StatusVIEWSTAT) will be  
1 when the switch is Off. The control mode will be 3 when the  
Enable/Off/Remote Contact switch input is On and the time of  
day is during an unoccupied period. Similarly, the control  
mode will be 7 when the time of day is during an occupied  
period.  
Ice Mode — When Ice Mode is enabled Cooling Setpoint  
Select must be set to Dual Switch, Dual 7 day or Dual CCN  
Occupied and the Energy Management Module (EMM) must  
be installed. Unit operation is based on Cooling Setpoint 1  
(CSP.1) during the Occupied mode, Ice Setpoint (CSP.3) dur-  
ing the Unoccupied mode with the Ice Done contacts open and  
Cooling Setpoint 2 (CSP.2) during the Unoccupied mode with  
the Ice Done contacts closed. These 3 set points can be utilized  
to develop your specific control strategy.  
CCN SCHEDULE (ConfigurationOPT2CTRL  
=
2) — An external CCN device such as Chillervisor System  
Manager controls the On/Off state of the machine. This CCN  
device forces the variable ‘CHIL_S_S’ between Start/Stop to  
control the chiller. The control mode (Run Status  
VIEWSTAT) will be 1 when the switch is Off. The con-  
trol mode will be 2 when the Enable/Off/Remote Contact  
switch input is On and the CHIL_S_S variable is ‘Stop.’  
Similarly, the control mode will be 6 when the CHIL_S_S vari-  
able is ‘Start.’  
Service Test (See Table 4) Both main power and  
control circuit power must be on.  
The Service Test function should be used to verify proper  
operation of condenser output, compressors, minimum load  
valve solenoid (if installed), cooler pump, and remote alarm re-  
lay. To use the Service Test mode, the Enable/Off/Remote Con-  
tact switch must be in the OFF position. Use the display keys  
and Table 4 to enter the mode and display TEST. Press  
Table 20 illustrates how the control method and cooling set  
point select variables direct the operation of the chiller and the  
set point to which it controls. The illustration also shows the  
ON/OFF state of the machine for the given combinations.  
twice so that OFF flashes. Enter the password if re-  
ENTER  
quired. Use either arrow key to change the TEST value to the  
ON position and press  
. Press  
and the  
ESCAPE  
ENTER  
button to enter the OUTS or COMP sub-mode.  
Table 20 — Control Methods and Cooling Set Points  
COOLING SET POINT SELECT (CLSP)  
CONTROL  
OCCUPANCY  
TYPE  
0
1
2
3
STATE  
(CTRL)  
(single)  
(dual, switch)  
(dual, occ)  
(4 to 20 mA)  
Occupied  
Unoccupied  
Occupied  
Unoccupied  
Occupied  
Unoccupied  
ON,CSP1  
ON,CSP1  
ON,CSP1  
OFF  
ON,CSP1  
ON,CSP1  
ON*  
ON*  
ON*  
OFF  
ON*  
ON*  
ON,CSP1  
ON,CSP2  
Illegal  
Illegal  
ON,CSP1  
ON,CSP2  
ON†  
ON  
ON†  
OFF  
ON†  
ON†  
0 (switch)  
2 (Occupancy)  
3 (CCN)  
*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.  
†Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Test the condenser output, cooler pump, liquid line solenoid  
valve (30MPA only), crankcase heater, water valve (accesso-  
ry), and alarm relay by changing the item values from OFF to  
ON. These discrete outputs are then turned off if there is no  
keypad activity for 10 minutes. When testing compressors,  
lead compressor must be started first. All compressor outputs  
can be turned on, but the control will limit the rate by staging  
one compressor per minute. Minimum load valve can be tested  
with the compressors on or off. The relays under the COMP  
mode will stay on for 10 minutes if there is no keypad activity.  
Compressors will stay on until they are turned off by the opera-  
tor. The Service Test mode will remain enabled for as long as  
there is one or more compressors running. All safeties are mon-  
itored during this test and will turn a compressor, circuit or the  
machine off if required. Any other mode or sub-mode can be  
accessed, viewed, or changed during the TEST mode. The  
STAT item (Run StatusVIEW) will display “0” as long as  
the Service mode is enabled. The TEST sub-mode value must  
be changed back to OFF before the chiller can be switched to  
Enable or Remote contact for normal operation.  
Configuring and Operating Dual Chiller Con-  
trol — The dual chiller routine is available for the control of  
two units supplying chilled fluid on a common loop. This  
control algorithm is designed for parallel fluid flow arrangement  
only. One chiller must be configured as the master chiller, the  
other as the slave. An additional leaving fluid temperature  
thermistor (Dual Chiller LWT) must be installed as shown in  
Fig. 13 and 14 and connected to the master chiller. Refer to Sen-  
sors section, page 19, for wiring. The CCN communication bus  
must be connected between the two chillers. Connections can be  
made to the CCN screw terminals on LVT. Refer to Carrier  
Comfort Network® Interface section, page 14, for wiring infor-  
mation. Configuration examples are shown in Tables 21 and 22.  
Refer to Table 21 for dual chiller configuration. In this  
example the master chiller will be configured at address 1 and  
the slave chiller at address 2. The master and slave chillers  
must reside on the same CCN bus (ConfigurationCCN  
CCNB) but cannot have the same CCN address (Configu-  
rationCCNCCNA). Both master and slave chillers must  
have Lead/Lag Chiller Enable (ConfigurationRSET  
LLEN) configured to ENBL. Master/Slave Select (Config-  
urationRSET MSSL) must be configured to MAST for  
the master chiller and SLVE for the slave. Also in this example,  
the master chiller will be configured to use Lead/Lag Balance  
Select (ConfigurationRSETLLBL) and Lead/Lag Bal-  
ance Delta (ConfigurationRSETLLBD) to even out the  
chiller run-times weekly. The Lag Start Delay (Configura-  
tionRSETLLDY) feature will be set to 10 minutes. This  
will prevent the lag chiller from starting until the lead chiller  
has been at 100% capacity for the length of the delay time. Par-  
allel configuration (ConfigurationRSETPARA) can  
only be configured to YES. The variables LLBL, LLBD and  
LLDY are not used by the slave chiller.  
Dual chiller start/stop control is determined by configura-  
tion of Control Method (ConfigurationOPT1CTRL) of  
the Master chiller. The Slave chiller should always be config-  
ured for CTRL=0 (Switch). If the chillers are to be controlled  
by Remote Contacts, both Master and Slave chillers should be  
enabled together. Two separate relays or one relay with  
two sets of contacts may control the chillers. The Enable/Off/  
Remote Contact switch should be in the Remote Contact  
position on both the Master and Slave chillers. The Enable/Off/  
Remote Contact switch should be in the Enable position for  
CTRL=2 (Occupancy) or CTRL=3 (CCN Control).  
Both chillers will stop if the Master chiller Enable/Off/  
Remote Contact switch is in the Off position. If the Emergency  
Stop switch is turned off or an alarm is generated on the Master  
chiller the Slave chiller will operate in a Stand-Alone mode.  
If the Emergency Stop switch is turned off or an alarm is  
generated on the Slave chiller the Master chiller will operate in  
a Stand-Alone mode.  
Cooler Pump Sequence of Operation — At any-  
time the unit is in an ON status, as defined by the one of the  
following conditions, the cooler pump relay will be enabled.  
1. The Enable-Off-Remote Switch in ENABLE,  
(CTRL=0).  
2. Enable-Off-Remote Switch in REMOTE with  
a
Start-Stop remote contact closure (CTRL=0).  
3. An Occupied Time Period from an Occupancy Schedule  
in combination with items 1 or 2 (CTRL=2).  
4. A CCN Start-Stop Command to Start in combination  
with items 1 or 2 (CTRL=3).  
There are certain alarm conditions and Operating Modes  
that will turn the cooler pump relay ON. This sequence will de-  
scribe the normal operation of the pump control algorithm.  
When the unit cycles from an "On" state to an "Off' state,  
the cooler pump output will remain energized for the Cooler  
Pump Shutdown Delay (ConfigurationOPT1PM.DY).  
This is configurable from 0 to 10 minutes. The factory default  
is 1 minute. If the pump output was deenergized during the  
transition period, the pump output will not be energized.  
The Cooler Pump Relay will be energized when the ma-  
chine is "On." The chilled water pump interlock circuit consists  
of a chilled water flow switch and a field-installed chilled water  
pump interlock. If the chilled water pump interlock circuit does  
not close within five (5) minutes of starting, an A200 - Cooler  
Flow/Interlock failed to close at Start-Up alam1 will be gener-  
ated and chiller will not be allowed to start.  
If the chilled water pump interlock or chilled water flow  
switch opens for at least three (3) seconds after initially being  
closed, an A201 - Cooler Flow 1 Interlock Contacts Opened  
During Normal Operation alarm will be generated and the ma-  
chine will stop.  
The master chiller controls the slave chiller by changing its  
Control Mode (Run StatusVIEWSTAT) and its operat-  
ing setpoint or Control Point (Run StatusVIEWCT.PT).  
Condenser Pump/Condenser Fan Output Con-  
trol — The main base board (MBB) has the capability to  
control either a condenser fan output or a condenser pump out-  
put depending on the unit configuration.  
If the unit is configured for Configuration  
UNITTYPE = 2 (air cooled), then the output will be off as  
long as capacity is equal to 0 and will be energized 5 seconds  
before a compressor is started and remain energized until ca-  
pacity is 0 again.  
If the unit is configured for Configuration  
UNITTYPE = 3 (water cooled), then the output will be used  
for consenser pump control and additional configuration is re-  
quired. To enable the condenser pump control use Configura-  
tionOPT1DPME. The pump can be configured for no  
pump control, on when occupied, and on when capacity is  
greater than 0.  
THERMISTOR  
WIRING*  
LEAVING  
FLUID  
MASTER  
CHILLER  
RETURN  
FLUID  
SLAVE  
CHILLER  
INSTALL DUAL CHILLER LWT  
LEAVING FLUID TEMPERATURE  
THERMISTOR (T10) HERE  
*Depending on piping sizes, use either:  
• HH79NZ014 sensor/10HB50106801 well (3-in. sensor/well)  
• HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well)  
Fig. 13 — Dual Chiller Thermistor Location  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 — Dual Chiller Configuration (Master Chiller Example)  
SUB-MODE  
ITEM  
KEYPAD ENTRY  
DISPLAY  
ITEM EXPANSION  
COMMENTS  
DISP  
UNIT  
OPT1  
ENTER  
ENTER  
ESCAPE  
CTRL  
0
CONTROL METHOD  
SWITCH  
OPT2  
CTRL  
DEFAULT 0  
OPT2  
CCN  
1
CCNA  
CCNB  
ENTER  
CCN ADDRESS  
DEFAULT 1  
DEFAULT 0  
CCNB  
0
CCN  
ENTER  
CCN BUS NUMBER  
ESCAPE  
CCN  
RSET  
CRST  
LLEN  
DSBL  
DSBL  
ENBL  
ENBL  
LLEN  
MSSL  
MAST  
MSSL  
SLVA  
0
PROCEED TO  
SUBMODE RESET  
RSET  
ENTER  
COOLING RESET TYPE  
LEAD/LAG CHILLER ENABLE  
15 ITEMS  
SCROLLING STOPS  
VALUE FLASHES  
SELECT ENBL  
LLEN  
LLEN  
MSSL  
SLVA  
SLVA  
LLBL  
ENTER  
ENTER  
ENTER  
LEAD/LAG CHILLER ENABLE  
CHANGE ACCEPTED  
ESCAPE  
MASTER /SLAVE SELECT  
MASTER /SLAVE SELECT  
ENTER  
DEFAULT MAST  
ESCAPE  
SLAVE ADDRESS  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
SELECT 2  
0
2
ENTER  
2
SLAVE ADDRESS  
CHANGE ACCEPTED  
ESCAPE  
SLVA  
LLBL  
0
LEAD/LAG BALANCE SELECT  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
0
2
SELECT 2 - Automatic  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 — Dual Chiller Configuration (Master Chiller Example) (cont)  
SUB-MODE  
ITEM  
KEYPAD ENTRY  
DISPLAY  
ITEM EXPANSION  
COMMENTS  
RSET  
LLBL  
ENTER  
2
LEAD/LAG BALANCE SELECT  
CHANGE ACCEPTED  
ESCAPE  
LLBL  
LLBD  
168  
LLBD  
LLDY  
5
LEAD/LAG BALANCE DELTA  
LEAD/LAG BALANCE DELTA  
LLBD  
LLDY  
LLDY  
PARA  
ENTER  
DEFAULT 168  
ESCAPE  
LAG START DELAY  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
SELECT 10  
5
10  
ENTER  
ESCAPE  
ESCAPE  
ENTER  
10  
LAG START DELAY  
CHANGE ACCEPTED  
LLDY  
RSET  
YES  
MASTER COMPLETE  
NOTES:  
1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN.  
2. Parallel Configuration (PARA) cannot be changed.  
Temperature Reset — The control system is capable of  
handling leaving-fluid temperature reset based on return cooler  
fluid temperature. Because the change in temperature through  
the cooler is a measure of the building load, the return tempera-  
ture reset is in effect an average building load reset method.  
The control system is also capable of temperature reset based  
on outdoor-air temperature (OAT), space temperature (SPT), or  
from an externally powered 4 to 20 mA signal. Accessory sen-  
sors must be used for SPT reset (33ZCT55SPT) and for OAT  
reset (HH79NZ014). The energy management module (EMM)  
must be used for temperature reset using a 4 to 20 mA signal.  
See Tables 23 and 24.  
DIMENSIONS in. (mm)  
PART  
NUMBER  
A
B
10HB50106801  
10HB50106802  
3.10 (78.7)  
4.10 (104.1)  
1.55 (39.4)  
1.28 (32.5)  
A
0.505/0.495  
0.61  
DIA  
B
6” MINIMUM  
CLEARANCE FOR  
THERMISTOR  
REMOVAL  
1/4 N.P.T.  
Fig. 14 — Dual Leaving Water Thermistor Well  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 — Dual Chiller Configuration (Slave Chiller Example)  
SUB-MODE  
ITEM  
KEYPAD ENTRY  
DISPLAY  
ITEM EXPANSION  
COMMENTS  
DISP  
UNIT  
OPT1  
ENTER  
CTRL  
0
CONTROL METHOD  
SWITCH  
OPT2  
CTRL  
DEFAULT 0  
ESCAPE  
OPT2  
CCN  
CCNA  
1
CCNA  
ENTER  
ENTER  
CCN ADDRESS  
SCROLLING STOPS  
VALUE FLASHES  
1
SELECT 2  
(SEE NOTE 2)  
2
CCN  
CCNA  
CCNB  
ENTER  
ESCAPE  
ENTER  
2
CCN ADDRESS  
CHANGE ACCEPTED  
CCN  
0
DEFAULT 0  
(SEE NOTE 3)  
CCN BUS NUMBER  
ESCAPE  
CCN  
RSET  
CRST  
LLEN  
DSBL  
DSBL  
ENBL  
ENBL  
LLEN  
MSSL  
MAST  
MAST  
SLVE  
SLVE  
MSSL  
RSET  
PROCEED TO  
SUBMODE RSET  
RSET  
ENTER  
COOLING RESET TYPE  
LEAD/LAG CHILLER ENABLE  
15 ITEMS  
SCROLLING STOPS  
VALUE FLASHES  
SELECT ENBL  
LLEN  
LLEN  
MSSL  
MSSL  
ENTER  
ENTER  
ENTER  
LEAD/LAG CHILLER ENABLE  
MASTER /SLAVE SELECT  
CHANGE ACCEPTED  
ESCAPE  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
SELECT SLVE  
ENTER  
ESCAPE  
ESCAPE  
MASTER /SLAVE SELECT  
CHANGE ACCEPTED  
SLAVE COMPLETE  
NOTES:  
1. Slave Control Method (CTRL) must be configured for 0.  
2. Slave CCN Address (CCNA) must be different than Master.  
3. Slave CCN Bus Number (CCNB) must be the same as Master  
4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23 — Menu Configuration of 4 to 20 mA Cooling Set Point Control  
MODE  
(RED LED)  
KEYPAD  
ENTRY  
KEYPAD  
ENTRY  
ITEM  
EXPANSION  
SUB-MODE  
DISP  
ITEM  
DISPLAY  
COMMENT  
ENTER  
UNIT  
OPT1  
OPT2  
CCN  
CONFIGURATION  
RSET  
SLCT  
ENTER  
ENTER  
ENTER  
CLSP  
0
0
0
3
3
COOLING SETPOINT SELECT  
Scrolling Stops  
Flashing ‘0’  
Select ‘3’  
ENTER  
Change Accepted  
Table 24 — 4 to 20 mA Reset  
KEYPAD  
ITEM  
DISPLAY  
SUB-MODE  
RSET  
ITEM  
COMMENT  
ENTRY  
EXPANSION  
0 = no reset  
1 = 4 to 20 mA input  
2 = Outdoor air temp  
3 = Return Fluid  
COOLING RESET  
ENTER  
CRST  
1
TYPE  
4 = Space Temperature  
5.0 F  
(2.8 C)  
DEGREES COOL  
RESET  
Default: 0° F (0° C) Reset at 20 mA  
Range: –30 to 30 F (–16.7 to 16.7 C)  
MA.DG  
NOTE: The example above shows how to configure the chiller for  
4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F  
reset will occur at 20.0 mA. An EMM (energy management module)  
is required.  
RM.NO should be set to the temperature that no reset should  
occur. The variable RM.F should be set to the temperature that  
maximum reset is to occur. The variable RM.DG should be set  
to the maximum amount of reset desired. Figures 15 and 16 are  
examples of outdoor air and space temperature resets.  
To use return reset, four variables must be configured. In the  
Configuration mode under the sub-mode RSET, items CRST,  
RT.NO, RT.F and RT.DG must be properly set. See Table 26  
— Configuring Return Temperature Reset. This example pro-  
vides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C)  
cooler T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The  
variable RT.NO should be set to the cooler temperature differ-  
ence (T) where no chilled water temperature reset should oc-  
cur. The variable RT.F should be set to the cooler temperature  
difference where the maximum chilled water temperature reset  
should occur. The variable RM.DG should be set to the maxi-  
mum amount of reset desired.  
IMPORTANT: Care should be taken when interfacing with  
other control systems due to possible power supply differ-  
ences: full wave bridge versus half wave rectification. Con-  
nection of control devices with different power supplies  
may result in permanent damage. ComfortLink™ controls  
incorporate power supplies with half wave rectification. A  
signal isolation device should be utilized if the signal gen-  
erator incorporates a full wave bridge rectifier.  
To use outdoor air or space temperature reset, four variables  
must be configured. In the Configuration mode under the sub-  
mode RSET, items (ConfigurationRSETCRST),  
(ConfigurationRSETRM.NO),  
(Configuration  
RSETRM.F), and (ConfigurationRSETRT.DG)  
must be properly set. See Table 25 — Configuring Outdoor Air  
and Space Temperature Reset. The outdoor air reset example  
provides 0° F (0° C) chilled water set point reset at 85.0 F  
(29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at  
55.0 F (12.8 C) outdoor-air temperature. The space tempera-  
ture reset example provides 0° F (0° C) chilled water set point  
reset at 72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) re-  
set at 68.0 F (20.0 C) space temperature. The variable CRST  
should be configured for the type of reset desired. The variable  
To verify that reset is functioning correctly proceed to Run  
Status mode, sub-mode VIEW, and subtract the active set point  
(Run StatusVIEWSETP) from the control point (Run  
StatusVIEWCTPT) to determine the degrees reset.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 25 — Configuring Outdoor Air and Space Temperature Reset  
DISPLAY  
MODE  
(RED LED)  
KEYPAD  
ENTRY  
SUB-  
MODE  
KEYPAD  
ENTRY  
ITEM  
EXPANSION  
ITEM  
COMMENT  
Outdoor  
Air  
Space  
ENTER  
DISP  
UNIT  
OPT1  
OPT2  
CCN  
2 = Outdoor-Air Temperature  
(Connect to LVT-4,5)  
4 = Space Temperature  
(Connect to LVT-3,4)  
CONFIGURATION  
ENTER  
COOLING RESET  
TYPE  
RSET  
CRST  
2
4
REMOTE - NO  
RESET TEMP  
Default: 125.0 F (51.7 C)  
Range: 0° to125 F  
RM.NO*  
RM.F  
85 °F  
55 °F  
72 °F  
68 °F  
REMOTE - FULL  
RESET TEMP  
Default: 0.0° F (-17.7 C)  
Range: 0° to 125 F  
Default: 0° F (0° C)  
Range: –30 to 30 F  
(–34.4 to -1.1 °C)  
REMOTE - DEGREES  
RESET  
RM.DG  
15 °F  
6 °F  
*1 item skipped in this example.  
Table 26 — Configuring Return Temperature Reset  
MODE  
(RED LED)  
KEYPAD  
ENTRY  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
DISP  
ITEM DISPLAY  
COMMENT  
EXPANSION  
ENTER  
ENTER  
ENTER  
ENTER  
ENTER  
TEST  
TYPE  
FLUD  
CTRL  
ON/OFF  
TEST DISPLAY LEDs  
UNIT TYPE  
UNIT  
X
X
X
OPT1  
COOLER FLUID  
CONTROL METHOD  
OPT2  
CCN  
0 = No Reset  
ENTER  
1 = 4 to 20 mA Input (EMM required)  
(Connect to EMM TB6-2,3)  
CONFIGURATION  
RSET  
CRST  
3
COOLING RESET TYPE 2 = Outdoor-Air Temperature  
3 = Return Fluid  
4 = Space Temperature  
(Connect to TB5-5,6)  
RETURN FLUID - NO  
RESET TEMP  
Default: 10.0 F (5.6 C)  
Range: 0° to10 F COOLER T  
RT.NO* 10.0 F  
RETURN FLUID - FULL Default: 0 F (–17.8 C)  
RT.F  
2.0 F  
5.0 F  
RESET TEMP  
Range: 0° to 30 F COOLER T  
RETURN - DEGREES  
RESET  
Default: 0 F (0 C)  
Range: –30 to 30°F (–16.7 to 16.7 C)  
RT.DG  
*1 item skipped in this example.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Under normal operation, the chiller will maintain a constant  
leaving fluid temperature approximately equal to the chilled  
fluid set point. As the cooler load varies, the entering cooler  
fluid will change in proportion to the load as shown in Fig. 17.  
Usually the chiller size and leaving-fluid temperature set point  
are selected based on a full-load condition. At part load, the flu-  
id temperature set point may be colder than required. If the  
leaving fluid temperature was allowed to increase at part load,  
the efficiency of the machine would increase.  
Return temperature reset allows for the leaving temperature  
set point to be reset upward as a function of the return fluid  
temperature or, in effect, the building load.  
Demand Limit — Demand limit is a feature that allows  
the unit capacity to be limited during periods of peak energy us-  
age. There are 3 types of demand limiting that can be config-  
ured. The first type is through 2-stage switch control, which will  
reduce the maximum capacity to 2 user-configurable percentag-  
es. The second type is by 4 to 20 mA signal input which will re-  
duce the maximum capacity linearly between 100% at a 4 mA  
input signal (no reduction) down to the user-configurable level  
at a 20 mA input signal. The third type uses the CCN Loadshed  
module and has the ability to limit the current operating capaci-  
ty to maximum and further reduce the capacity if required.  
LEGEND  
EWT — Entering Water (Fluid) Temperature  
LWT  
Leaving Water (Fluid) Temperature  
Fig. 17 — Standard Chilled Fluid  
Temperature Control — No Reset  
To use demand limit, select the type of demand limiting to  
use. Then configure the demand limit set points based on the  
type selected.  
NOTE: The 2-stage switch control and 4 to 20-mA input sig-  
nal types of demand limiting require the energy management  
module (EMM).  
DEMAND LIMIT (2-Stage Switch Controlled) — To con-  
figure demand limit for 2-stage switch control set the Demand  
Limit Select (ConfigurationRSETDMDC) to 1. Then  
configure the 2 Demand Limit Switch points (Configura-  
tionRSETDLS1) and (ConfigurationRSETDLS2)  
to the desired capacity limit. See Table 27. Capacity steps are  
controlled by 2 relay switch inputs field wired to LVT as shown  
in Fig. 5.  
For demand limit by 2-stage switch control, closing the first  
stage demand limit contact will put the unit on the first demand  
limit level. The unit will not exceed the percentage of capacity  
entered as Demand Limit Switch 1 set point (DLS1). Closing  
contacts on the second demand limit switch prevents the unit  
from exceeding the capacity entered as Demand Limit Switch  
2 set point. The demand limit stage that is set to the lowest de-  
mand takes priority if both demand limit inputs are closed. If  
the demand limit percentage does not match unit staging, the  
unit will limit capacity to the closest capacity stage.  
LEGEND  
To disable demand limit configure DMDC to 0. See  
Table 27.  
LWT — Leaving Water (Fluid) Temperature  
Fig. 15 — Outdoor-Air Temperature Reset  
EXTERNALLY POWERED DEMAND LIMIT (4 to  
20 mA Controlled) — To configure demand limit for 4 to 20  
mA control set the Demand Limit Select (Configura-  
tionRSETDMDC) to 2. Then configure the Demand  
Limit at 20 mA (ConfigurationRSETDM20) to the  
maximum loadshed value desired. Connect the output from an  
externally powered 4 to 20 mA signal to terminal block LVT,  
terminals 7 and 8 (+,–). Refer to the unit wiring diagram for  
these connections to the optional/accessory energy manage-  
ment module and terminal block. The control will reduce al-  
lowable capacity to this level for the 20 mA signal. See Table  
27 and Fig. 18.  
CAUTION  
Care should be taken when interfacing with other manufac-  
turer’s control systems, due to possible power supply  
differences, full wave bridge versus half wave rectification.  
The two different power supplies cannot be mixed.  
ComfortLink™ controls use half wave rectification. A sig-  
nal isolation device should be utilized if a full wave bridge  
signal generating device is used.  
LEGEND  
LWT — Leaving Water (Fluid) Temperature  
Fig. 16 — Space Temperature Reset  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEMAND LIMIT (CCN Loadshed Controlled) — To con-  
figure Demand Limit for CCN Loadshed control set the De-  
mand Limit Select (ConfigurationRSETDMDC) to 3.  
Then configure the Loadshed Group Number (Configura-  
tionRSETSHNM), Loadshed Demand Delta (Configu-  
rationRSETSHDL), and Maximum Loadshed Time  
(ConfigurationRSETSHTM). See Table 27.  
The Loadshed Group number is established by the CCN  
system designer. The ComfortLink™ controls will respond to a  
Redline command from the Loadshed control. When the  
Redline command is received, the current stage of capacity is  
set to the maximum stages available. Should the loadshed con-  
trol send a Loadshed command, the ComfortLink controls will  
reduce the current stages by the value entered for Loadshed  
Demand delta. The Maximum Loadshed Time is the maximum  
length of time that a loadshed condition is allowed to exist. The  
control will disable the Redline/Loadshed command if no  
Cancel command has been received within the configured  
maximum loadshed time limit.  
Cooling Set Point (4 to 20 mA) — A field supplied  
and generated, externally powered 4 to 20 mA signal can be  
used to provide the leaving fluid temperature set point. Connect  
the signal to LVT-10,8 (+,–). See Table 27 for instructions to  
enable the function. Figure 19 shows how the 4 to 20 mA sig-  
nal is linearly calculated on an overall 10 F to 80 F range for  
fluid types (ConfigurationOPT1FLUD) 1 or 2. The set  
point will be limited by the fluid (FLUD) type. Be sure that the  
chilled water loop is protected at the lowest temperature.  
100  
50% CAPACITY AT 20 mA  
80  
60  
100% CAPACITY AT 4 mA  
40  
75% CAPACITY AT 12 mA  
20  
0
0
2
6
8
12  
16  
18  
4
20  
10  
14  
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT  
Fig. 18 — 4 to 20-mA Demand Limiting  
100  
(38)  
90  
(32)  
80  
(27)  
70  
(21)  
MAXIMUM  
SET POINT  
70 F (21.1 C)  
60  
(15)  
50  
(10)  
40  
(4.4)  
(FLUD = 1) MINIMUM  
SET POINT 38 F (3.3 C)  
30  
(-1)  
20  
(-7)  
(FLUD = 2) MINIMUM  
SET POINT 14 F (-10 C)  
10  
(-12)  
0
(-17)  
4
6.3  
8.6  
10.9  
13.1  
15.4  
17.7  
20  
4 TO 20 mA SIGNAL TO EMM  
EMM — Energy Management Module  
Fig. 19 — Cooling Set Point (4 to 20 mA)  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 27 — Configuring Demand Limit  
KEYPAD  
ENTRY  
KEYPAD  
MODE  
SUB-MODE  
DISP  
ITEM  
TEST  
TYPE  
FLUD  
CTRL  
CCNA  
CRST  
DISPLAY  
ITEM EXPANSION  
Test Display LEDs  
Unit Type  
COMMENT  
ENTRY  
CONFIGURATION  
ENTER  
ENTER  
ON/OFF  
ENTER  
ENTER  
ENTER  
ENTER  
ENTER  
UNIT  
X
X
X
X
X
OPT1  
Cooler Fluid  
OPT2  
Control Method  
CCN Address  
CCN  
RSET  
Cooling Reset Type  
Default: 0  
0 = None  
1 = Switch  
DMDC*  
X
Demand Limit Select  
2 = 4 to 20 mA Input  
3 = CCN Loadshed  
Default: 100%  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
XXX %  
XXX  
Demand Limit at 20 mA  
Range: 0 to 100  
Loadshed Group  
Number  
Default: 0  
Range: 0 to 99  
Loadshed Demand  
Delta  
Default: 0%  
Range: 0 to 60%  
XXX%  
XXX MIN  
XXX %  
XXX %  
Maximum Loadshed  
Time  
Default: 60 min.  
Range: 0 to 120 min.  
Demand Limit  
Switch 1  
Default: 80%  
Range: 0 to 100%  
Demand Limit  
Switch 2  
Default: 50%  
Range: 0 to 100%  
*Seven items skipped in this example.  
5. Oil should be visible in the compressor sightglass(es).  
See Fig. 20. An acceptable oil level in the compressors is  
from 1/8 to 3/8 of sight glass when the compressors are off.  
Adjust the oil level as required. See Oil Charge section on  
page 37 for Carrier approved oils.  
6. Crankcase heaters must be firmly attached to compres-  
sors, and must be on for 24 hours prior to start-up  
(30MPA units only).  
PRE-START-UP  
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,  
complete Start-Up Checklist for 30MP Liquid Chiller at  
end of this publication (page CL-1 to CL-8). The checklist  
assures proper start-up of a unit, and provides a record of  
unit condition, application requirements, system informa-  
tion, and operation at initial start-up.  
7. Electrical power source must agree with unit nameplate.  
Do not attempt to start the chiller until following checks  
have been completed.  
8. Check rotation of scroll compressors. Monitor control  
alarms during first compressor start up for reverse rota-  
tion protection alarm.  
System Check  
1. Check all auxiliary components, such as chilled fluid  
pumps, air-handling equipment, condenser pump or other  
equipment to which the chiller supplies liquid. Consult  
manufacturer's instructions. Verify that any pump inter-  
lock contacts have been properly installed. If the unit has  
field-installed accessories, be sure all are properly in-  
stalled and wired correctly. Refer to unit wiring diagrams.  
Table 28 — Minimum Flow Rates and Minimum  
Loop Volume (for Comfort Cooling)  
MINIMUM EVAPORATOR  
EVAPORATOR CONDENSER*  
LOOP VOLUME  
UNIT SIZE  
Gal./Min L/s Gal./Min L/s  
Gal.  
L
30MP015  
30MP020  
30MP030  
30MP040  
30MP045  
22  
28  
43  
55  
64  
1.4  
1.8  
2.7  
3.5  
4.0  
22  
28  
43  
55  
64  
1.4  
1.8  
2.7  
3.5  
4.0  
46.2  
60.9  
92.4  
78.4  
91.6  
174.9  
230.5  
349.7  
296.7  
346.7  
2. Use the scrolling marquee display to adjust the Cooling  
Set Point.  
3. Fill chilled fluid circuit with clean water (with recom-  
mended inhibitor added) or other non-corrosive fluid to  
be cooled. Bleed all air out of the high points of the sys-  
tem. If chilled water is to be maintained at a temperature  
below 40 F (4.4 C), a brine of sufficient concentration  
must be used to prevent freeze-up at anticipated suction  
temperatures. To ensure sufficient loop volume, see  
Table 28.  
LEGEND  
AHRI — Air Conditioning, Heating, and Refrigeration Institute  
N
V
Liters per kW  
Gallons per ton  
NOTES:  
Gallons = V x AHRI capacity in tons.  
Liters = N x AHRI capacity in kW.  
APPLICATION  
V
3
N
3.25  
6.5 to 10.8  
6.5 to 10.8  
4. Check tightness of all electrical connections.  
Normal Air Conditioning  
Process Type Cooling  
Low Ambient Operation  
6 to 10  
6 to 10  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All refrigerant charging should be done through the ¼-in.  
Schraeder connection on the liquid line. Do NOT add refriger-  
ant charge through the low-pressure side of the system. If com-  
plete charging is required, weigh in the appropriate charge for  
the circuit as shown on the unit nameplate. If partial charging is  
required, operate circuit at full load and add charge until the  
sight glass is clear of bubbles.  
a30-4978  
CAUTION  
Never charge liquid into low-pressure side of system. Do  
not overcharge. Overcharging results in higher discharge  
pressure, possible compressor damage, and higher power  
consumption. During charging or removal of refrigerant, be  
sure water is continuously circulating through the cooler to  
prevent freezing.  
The 30MPA units (condenserless) are shipped with a nitro-  
gen holding charge only. After chiller assembly is completed in  
the field, system must be fully charged. While the unit is run-  
ning at full capacity, add refrigerant until the sight glass is clear.  
R-410A is the normal refrigerant.  
OIL SIGHTGLASS  
Fig. 20 — Sight Glass Location  
Do not open the liquid valve until there is a charge in re-  
mainder of system. A positive pressure indicates a charge in  
system. With the unit operating at full load, check liquid line  
sight glass to be sure the unit is fully charged (bubbles in the  
sight glass indicate the unit is not fully charged).  
START-UP AND OPERATION  
CAUTION  
Crankcase heaters on 30MPA units are wired into the con-  
trol circuit, so they are always operable as long as the main  
power supply disconnect is on (closed), even if any safety  
device is open. Compressor heaters must be on for 24  
hours prior to the start-up of any compressor. Equipment  
damage could result if heaters are not energized for at least  
24 hours prior to compressor start-up.  
If there is no refrigerant vapor pressure in the system, the  
entire system must be leak tested. After repairing leaks, evacu-  
ate the system before recharging.  
Follow approved evacuation procedures when removing  
refrigeration. Release remaining pressure to an approved evac-  
uated cylinder.  
The liquid charging method is recommended for complete  
charging or when additional charge is required.  
Compressor crankcase heaters must be on for 24 hours be-  
fore start-up. To energize the crankcase heaters, close the field  
disconnect. Leave the compressor circuit breakers off/open.  
The crankcase heaters are now energized.  
CAUTION  
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-8.  
Be careful not to overcharge the system. Overcharging  
results in higher discharge pressure, possible compressor  
damage, and higher power consumption.  
Actual Start-Up — Actual start-up should be done only  
under supervision of a qualified refrigeration mechanic.  
EVACUATION AND DEHYDRATION — Because the  
30MP systems use polyolester (POE) oil, which can absorb  
moisture, it is important to minimize the amount of time that  
the system interior is left exposed to the atmosphere. Minimiz-  
ing the exposure time of the oil to the atmosphere will mini-  
mize the amount of moisture that needs to be removed during  
evacuation.  
Once all of the piping connections are complete, leak test  
the unit and then pull a deep dehydration vacuum. Connect the  
vacuum pump to the high flow Schraeder valve in the suction  
line and liquid line. For best results, it is recommended that a  
vacuum of at least 500 microns (0.5 mm Hg) be obtained. Af-  
terwards, to ensure that no moisture is present in the system,  
perform a standing vacuum-rise test.  
With the unit in deep vacuum (500 microns or less), isolate  
the vacuum pump from the system. Observe the rate-of-rise of  
the vacuum in the system. If the vacuum rises by more than  
50 microns in a 30-minute time period, then continue the dehy-  
dration process. Maintain a vacuum on the system until the  
standing vacuum requirement is met. This will ensure a dry  
system.  
By following these evacuation and dehydration procedures,  
the amount of moisture present in the system will be mini-  
mized. It is required that liquid line filter driers be installed  
between the condenser(s) and the expansion devices to capture  
any foreign debris and provide additional moisture removal  
capacity.  
1. Be sure all service valves are open (30MPA units only).  
2. Using the scrolling marquee display, set leaving-fluid set  
point (Set PointsCOOLCSP.1). No cooling range  
adjustment is necessary.  
3. Start chilled fluid pump (if not configured for cooler  
pump control).  
4. Turn ENABLE/OFF/REMOTE CONTACT switch to  
ENABLE position.  
5. Allow unit to operate and confirm that everything is func-  
tioning properly. Check to see that leaving fluid tempera-  
ture agrees with leaving set point (Set PointsCOOL  
CSP.1) or (Set PointsCOOLCSP.2), or if reset is  
used, with the control point (Run StatusVIEW  
CTPT).  
6. Check the cooler leaving chilled water temperature to see  
that it remains well above 32 F (0° C), or the brine freez-  
ing point if the unit is a medium temperature brine unit.  
7. Recheck compressor oil level (see Oil Charge section).  
Check Refrigerant Charge — All 30MPW units are  
shipped with a complete operating charge of R-410A and  
should be under sufficient pressure to conduct a leak test after  
installation. If there is no system pressure, admit nitrogen until  
a pressure is observed and then proceed to test for leaks. After  
leaks are repaired, the system must be dehydrated.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIQUID CHARGING METHOD — Add charge to the unit  
through the liquid line service valve. Never charge liquid into  
the low-pressure side of the system.  
medium temperature brine unit, the cooler LCWT can go  
down to 15 F (–9.4 C).  
Table 29 — Temperature Limits for  
Standard 30MP Units  
1. Close liquid line ball valve (30MPA only).  
2. Connect a refrigerant cylinder loosely to the high flow  
Schraeder valve connection on the liquid line. Purge the  
charging hose and tighten the connections.  
TEMPERATURE LIMIT  
Maximum Condenser LWT  
Minimum Condenser EWT  
Maximum Cooler EWT*  
Maximum Cooler LWT  
F
140  
70  
95  
70  
40  
C
60  
21  
35  
21  
4
3. Open the refrigerant cylinder valve.  
4. If the system has been dehydrated and is under vacuum,  
break the vacuum with refrigerant gas. For R-410A, build  
up system pressure to 101 psig and 32 F (697 kPa and  
0° C). Invert the refrigerant cylinder so that the liquid re-  
frigerant will be charged.  
5. a. For complete charge of 30MPW units, follow  
charging by weight procedure. When charge is  
nearly full, complete the process by observing the  
sight glass for clear liquid flow while the unit is  
operating. The use of sight glass charging is valid  
only when unit is operating at full capacity.  
Minimum Cooler LWT†  
LEGEND  
Entering Fluid (Water) Temperature  
Leaving Fluid (Water) Temperature  
EWT  
LWT  
*For sustained operation, EWT should not exceed 85 F (29.4 C).  
†Unit requires modification below this temperature.  
CAUTION  
b. For complete charge of 30MPA units or where  
refrigerant cylinder cannot be weighed, follow the  
condenser manufacturer’s charging procedure or  
follow charging by sight glass procedure. The use  
of sight glass charging is valid only when unit is  
operating at full capacity.  
Medium temperature brine duty application (below 32 F  
[0° C] LCWT) for chiller normally requires factory modifi-  
cation. Contact your Carrier representative for applicable  
LCWT range for standard water-cooled chiller in a specific  
application.  
6. a. The 30MPA condenserless units are shipped  
with a nitrogen holding charge. After installation  
with the field-supplied system high side, the com-  
plete system should be evacuated and charged per  
the condenser manufacturer’s charging procedure  
or charged until the sight glass is clear (with the  
unit running at full capacity). To achieve maxi-  
mum system capacity, add additional charge equal  
to the difference between the condenser optimal  
charge and the condenser minimum charge, which  
can be obtained from the charge data provided in  
the condenser installation instructions.  
VOLTAGE — ALL UNITS  
Main Power Supply — Minimum and maximum acceptable  
supply voltages are listed in the Installation Instructions.  
Unbalanced 3-Phase Supply Voltage — Never operate a motor  
where a phase imbalance between phases is greater than 2%.  
To determine percent voltage imbalance:  
a30-4979  
max voltage deviation  
from avg voltage  
% Voltage Imbalance = 100 x  
average voltage  
The maximum voltage deviation is the largest difference  
between a voltage measurement across 2 legs and the average  
across all 3 legs.  
Example: Supply voltage is 240-3-60.  
AB = 243 v  
b. To ensure maximum performance of 30MPW  
units, raise the compressor saturated discharge  
temperature (SDT) to approximately 100 F  
(37.8 C) by throttling the condenser water intake.  
Add charge until there is approximately 9 to 12° F  
(5.0 to 6.6° C) of system subcooling (SDT minus  
actual temperature entering the thermostatic  
expansion valve).  
BC = 236 v  
AC = 238 v  
1. Determine average voltage:  
Operating Limitations  
TEMPERATURES (See Table 29 for 30MP standard tem-  
perature limits).  
243 + 236 + 238  
Averagevoltage =  
3
717  
=
3
CAUTION  
= 239  
Do not operate with cooler leaving chiller water (fluid)  
temperature (LCWT) below 32 F (0° C) for standard units  
with proper brine solution or 40 F (4.4 C) for the standard  
units with fresh water, or below 15 F (–9.4 C) for units fac-  
tory built for medium temperature brine.  
2. Determine maximum deviation from average voltage:  
(AB) 243 – 239 = 4 v  
(BC) 239 – 236 = 3 v  
(AC) 239 – 238 = 1 v  
Maximum deviation is 4 v.  
3. Determine percent voltage imbalance:  
High Cooler Leaving Chilled Water (Fluid) Temperatures  
(LCWT) — During start-up with cooler the LCWT should not  
be above approximately 60 F (16 C).  
Low Cooler LCWT — For standard units with fresh water,  
the LCWT must be no lower than 40 F (4.4 C). For standard  
units with a proper brine solution, the LCWT must be no lower  
than 32 F (0° C). If the unit is the factory-installed optional  
4
% Voltage Imbalance = 100 x  
239  
= 1.7%  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This voltage imbalance is satisfactory as it is below the  
maximum allowable of 2%.  
mounting hardware. Using new tubing as required, reconnect  
compressor suction and discharge lines. Using hardware saved,  
reinstall the mounting bolts and washers through the compres-  
sor feet. Using proper techniques, braze suction and discharge  
lines and check for leaks. Reconnect oil equalization line.  
Re-install the crankcase heater (30MPA units). Reconnect  
the compressor power connections and high-pressure switch  
wiring as on the old compressor. Refer to Fig. 21. Following  
the installation of the new compressor, tighten all hardware to  
the following specifications. (See Table 30.)  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately. Do not operate unit until imbalance condition  
is corrected.  
Control Circuit Power — Power for the control circuit is  
supplied from the main incoming power through a factory-  
installed control power transformer (TRAN1) for all models.  
Field wiring connections are made to the LVT.  
Table 30 — Unit Torque Specification  
FASTENER  
RECOMMENDED TORQUE  
OPERATION SEQUENCE  
Compressor Mounting  
Bolts  
7 to 10 ft-lb (9.5 to 13.5 N-m)  
The unit is started by putting the ENABLE/OFF/REMOTE  
CONTACT switch in the ENABLE or REMOTE CONTACT  
position. When the unit receives a call for cooling (either from  
the internal control or CCN network command or remote con-  
tact closure), the unit stages up in capacity to maintain the leav-  
ing fluid set point. The first compressor starts 11/2 to 3 minutes  
after the call for cooling.  
For all units, if temperature reset is being used, the unit con-  
trols to a higher leaving-fluid temperature as the building load  
reduces. If demand limit is used, the unit may temporarily be  
unable to maintain the desired leaving-fluid temperature be-  
cause of imposed power limitations.  
Compressor Power  
Connections  
Compressor Ground  
Terminal Connections  
24 to 28 in.-lb (2.7- to 3.2 N-m)  
14 to 18 in.-lb (1.6 to 2.0 N-m)  
30MPW Condenser and 30MP Cooler  
BRAZED-PLATE COOLER AND CONDENSER HEAT  
EXCHANGER REPLACEMENT — Brazed-plate heat ex-  
changers cannot be repaired if they develop a leak. If a leak  
(refrigerant or water) develops, the heat exchanger must be  
replaced. To replace a brazed plate heat exchanger:  
1. Disconnect the liquid-in and liquid-out connections at the  
heat exchanger.  
2. Check that the replacement heat exchanger is the same as  
the original heat exchanger. For the condensers, compare  
part numbers on the heat exchangers. For the coolers, in-  
sulation covers the manufacturer’s part number. Make  
sure the depths of the replacement and original cooler  
heat exchangers are the same.  
3. Recover the refrigerant from the system, and unsolder the  
refrigerant-in and refrigerant-out connections.  
4. Remove the four nuts holding the heat exchanger to the  
brackets. Save the nuts.  
5. Install the replacement heat exchanger in the unit and at-  
tach to the bracket using the four nuts removed in Step 4.  
For sizes 015 and 020, torque is 7-10 ft-lb. For sizes 030-  
045, torque is 35 to 50 ft-lb.  
SERVICE  
WARNING  
Electrical shock can cause personal injury and death. Shut  
off all power to this equipment during service. There may  
be more than one disconnect switch. Tag all disconnect  
locations to alert others not to restore power until work is  
completed.  
Electronic Components  
CONTROL COMPONENTS — Unit uses an advanced elec-  
tronic control system that normally does not require service.  
For details on controls refer to Operating Data section.  
Access to the controls is through a hinged panel. Inner pan-  
els are secured in place and should not be removed unless all  
power to the chiller is off.  
6. Carefully braze the refrigerant lines to the connections on  
the heat exchanger. Lines should be soldered using silver  
as the soldering material with a minimum of 45% silver.  
Keep the temperature below 1472 F (800 C) under nor-  
mal soldering conditions (no vacuum) to prevent the cop-  
per solder of the brazed plate heat exchanger from chang-  
ing its structure. Failure to do so can result in internal  
or external leakage at the connections which cannot be  
repaired.  
Compressor Replacement — All models contain  
scroll compressors and have two or three compressors. A com-  
pressor is most easily removed from the side of the unit or  
above, depending on where clearance space was allowed dur-  
ing unit installation. See Fig. 21.  
Remove the junction box cover bolts and disconnect the  
compressor power and crankcase heater connections (30MPA  
only). Remove the cable from the compressor junction box.  
Remove the connections from the high-pressure switch. Re-  
move the crankcase heater. Knock the same holes out of the  
new compressor junction box and install the cable connectors  
from the old compressor.  
7. For coolers, ensure that the original size tubing is used  
(1/2-in. for sizes 015 and 020 and 5/8-in. for sizes 030-045)  
between the TXV and the cooler. The TXV must be lo-  
cated within 1 ft of the heat exchanger, with no bends be-  
tween the TXV outlet and the cooler inlet.  
8. Reconnect the water/brine lines.  
9. Dehydrate and recharge the unit. Check for leaks.  
The compressors are bolted to rails, which are in turn bolted  
to the unit basepan for all sizes. Remove the 4 bolts holding the  
compressor to the rail on the basepan. Save the mounting hard-  
ware for use with the new compressor. Carefully cut the com-  
pressor suction and discharge lines with a tubing cutter as close  
to the compressor as feasible. Remove high-pressure switch  
and pressure transducer(s) if required for compressor removal.  
Lift one corner of the compressor at a time and remove all the  
steel spacers. Remove the old compressor from the unit.  
BRAZED-PLATE COOLER AND CONDENSER HEAT  
EXCHANGER CLEANING — Brazed-plate heat exchang-  
ers must be cleaned chemically. A professional cleaning ser-  
vice skilled in chemical cleaning should be used. Use a weak  
acid (5% phosphoric acid, or if the heat exchanger is cleaned  
frequently, 5% oxalic acid). Pump the cleaning solution  
through the exchanger, preferably in a backflush mode. After  
cleaning, rinse with large amounts of fresh water to dispose of  
all the acid. Cleaning materials must be disposed of properly.  
Slide the new compressor in place on the rails. Lifting one  
side of the compressor at a time, replace all of the compressor  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The strainers in front of the water/brine inlets of the heat  
exchangers should be cleaned periodically, depending on con-  
dition of the chiller water/brine.  
Do not reuse oil that has been drained out, or oil that has  
been exposed to atmosphere.  
Check Refrigerant Feed Components  
Oil Charge  
CAUTION  
FILTER DRIER — The function of the filter drier is to main-  
tain a clean, dry system. The moisture indicator (described  
below) indicates any need to change the filter drier. The filter  
drier is a sealed-type drier. When the drier needs to be  
changed, the entire filter drier must be replaced.  
MOISTURE-LIQUID INDICATOR The indicator is located  
immediately ahead of the TXV to provide an indication of the  
refrigerant moisture content. It also provides a sight glass for  
refrigerant liquid. Clear flow of liquid refrigerant (at full unit  
loading) indicates sufficient charge in the system. Bubbles in the  
sight glass (at full unit loading) indicate an undercharged system  
or the presence of noncondensables. Moisture in the system,  
measured in parts per million (ppm), changes the color of the  
indicator as follows:  
The compressor in a Puron® refigerant (R-410A) system  
uses a polyol ester (POE) oil. This is extremely hygro-  
scopic, meaning it absorbs water readily. POE oils can  
absorb 15 times as much water as other oils designed for  
HCFC and CFC refrigerants. Take all necessary precau-  
tions to avoid exposure of the oil to the atmosphere. Failure  
to do so could result in possible equipment damage.  
Puron refrigerant systems use a polyol ester (POE) oil. Use  
only Carrier approved compressor oil. Oil should be visible in  
compressor oil sight glass. An acceptable oil level is from 1/8 to  
3/8 of sight glass. All compressors must be off when checking  
oil level. Recommended oil level adjustment method is as  
follows:  
Green (safe) —Moisture is below 75 ppm  
Yellow-Green (caution) — 75 to 150 ppm  
Yellow (wet) — above 150 ppm  
The unit must be in operation at least 12 hours before the  
moisture indicator gives an accurate reading, and must be in  
contact with liquid refrigerant. At the first sign of moisture in  
the system, change the corresponding filter drier.  
THERMOSTATIC EXPANSION VALVE (TXV) — The  
TXV controls the flow of liquid refrigerant to the cooler by  
maintaining constant superheat of vapor leaving the cooler.  
The valve(s) is activated by a temperature-sensing bulb(s)  
strapped to the suction line(s).  
ADD OIL — Recover charge from the unit. Add oil to suction  
line Schrader valve on tandem compressors sets and the com-  
pressor Schrader on the trios. (See Fig. 21.) When oil can be  
seen at the bottom of the sight glass, add oil in 5 oz increments  
which is approximately 1/8 in oil level. Run all compressors for  
20 minutes then shut off to check oil level. Repeat procedure  
until acceptable oil level is present.  
NOTE: Use only Carrier approved compressor oil. Approved  
sources are:  
The valve(s) is factory-set to maintain between 8° and 10° F  
(4.4° and 5.6° C) of superheat leaving the cooler. Check the  
superheat during operation after conditions have stabilized. If  
necessary, adjust the superheat to prevent refrigerant floodback  
to the compressor.  
Totaline . . . . . . . . . . . . . . . . . . . . . . 3MAF POE, P903-1601  
Mobil. . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA  
Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF  
HPS  
DPT  
LEGEND  
RGT  
CWFS — Chilled Water Flow Switch  
DPT  
EWT  
HPS  
LWT  
RGT  
SPT  
Discharge Pressure Transducer  
Entering Water Thermistor  
High Pressure Switch  
SPT  
Leaving Water Thermistor  
Return Gas Thermistor (Optional)  
Suction Pressure Transducer  
EWT  
(HIDDEN)  
CWFS  
LWT  
a30-5049  
Fig. 21 — Compressor Location — 30MP015-045 Units (30MPW045 Unit Shown)  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM LOAD VALVE — On units equipped with the  
factory-installed hot gas bypass option, a solenoid valve and  
discharge bypass valve (minimum load valve) are located  
between the discharge line and the cooler entering-refrigerant  
line. The MBB cycles the solenoid to perform minimum load  
valve function and the discharge bypass valve modulates to the  
suction pressure set point of the valve. The bypass valve has an  
adjustable opening setting between 95 to 115 psig (655 to  
793 kPa). The factory setting is 105 psig (724 kPa).  
The amount of capacity reduction achieved by the mini-  
mum load valve is not adjustable. The total unit capacity with  
the minimum load valve is shown in Table 19.  
PRESSURE RELIEF DEVICES — All units have one pres-  
sure relief device per circuit located in the liquid line which re-  
lieves at 210 F (100 C).  
COOLER FREEZE-UP PROTECTION  
WARNING  
On medium temperature brine units, the anti-freeze solu-  
tion must be properly mixed to prevent freezing at a tem-  
perature of at least 15 F (8.3 C) below the leaving-fluid  
temperature set point. Failure to provide the proper anti-  
freeze solution mixture is considered abuse and may impair  
or otherwise negatively impact the Carrier warranty.  
The main base board (MBB) monitors cooler leaving fluid  
temperature at all times. The MBB will rapidly remove stages  
of capacity as necessary to prevent freezing conditions due to  
the rapid loss of load or low cooler fluid flow.  
When the cooler is exposed to lower temperatures (40 F  
[4.4 C] or below), freeze-up protection is required using inhib-  
ited ethylene or propylene glycol.  
The 30MPW unit does not have a condenser pressure relief  
valve, because the brazed-plate condenser is not considered a  
pressure vessel, as defined in ANSI/ASHRAE 15 (American  
National Standards Institute/American Society of Heating,  
Refrigerating, and Air Conditioning Engineers) safety code  
requirements.  
For 30MPA condenserless units, pressure relief devices de-  
signed to relieve at the pressure determined in local codes,  
must be field-supplied and installed in the discharge line piping  
in accordance with ANSI/ASHRAE 15 safety code require-  
ments. Additional pressure relief valves, properly selected,  
must be field-supplied and installed to protect high side equip-  
ment and may be required by applicable codes.  
Thermistors — Electronic control uses up to five 5 k  
thermistors to sense temperatures used to control operation of  
the chiller. Thermistors EWT, LWT, RGTA, CNDE, CNDL,  
and OAT are identical in their temperature and voltage drop  
performance. The SPT space temperature thermistor has a  
10 kinput channel and it has a different set of temperature vs.  
resistance and voltage drop performance. Resistance at various  
temperatures are listed in Tables 32-35. For dual chiller opera-  
tion, a dual chiller sensor is required which is a 5 k  
thermistor.  
Most codes require that a relief valve be vented directly to  
the outdoors. The vent line must not be smaller than the relief  
valve outlet. Consult ANSI/ASHRAE 15 for detailed informa-  
tion concerning layout and sizing of relief vent lines.  
REPLACING THERMISTORS (EWT, LWT, RGT, CNDE,  
CNDL) — Add a small amount of thermal conductive grease  
to the thermistor well and end of probe. For all probes, tighten  
the retaining nut ¼ turn past finger tight. See Fig. 22.  
THERMISTOR/TEMPERATURE SENSOR CHECK — A  
high quality digital volt-ohmmeter is required to perform this  
check.  
1. Connect the digital voltmeter across the appropriate the-  
mistor terminals at the J8 terminal strip on the main base  
board (see Fig. 23).  
Check Unit Safeties  
HIGH-PRESSURE SWITCH — A high-pressure switch is  
provided to protect each compressor and refrigeration system  
from unsafe high pressure conditions. See Table 31 for high-  
pressure switch settings.  
The high-pressure switch is mounted in the discharge line of  
each circuit. If an unsafe, high-pressure condition should exist,  
the switch opens and shuts off the affected circuit. The CSB  
(current sensing board) senses the compressor feedback signal  
and generates an appropriate alarm. The MBB prevents the cir-  
cuit from restarting until the alert condition is reset. The switch  
should open at the pressure corresponding to the appropriate  
switch setting as shown in Table 31.  
2. Using the voltage reading obtained, read the sensor tem-  
perature from Tables 32-35.  
3. To check thermistor accuracy, measure temperature at  
probe location with an accurate thermocouple-type tem-  
perature measuring instrument. Insulate thermocouple to  
avoid ambient temperatures from influencing reading.  
Temperature measured by thermocouple and temperature  
determined from thermistor voltage reading should be  
close, ± 5° F (3° C) if care was taken in applying thermo-  
couple and taking readings.  
Table 31 — Factory Settings, High-Pressure  
Switch (Fixed)  
CUTOUT  
CUT-IN  
If a more accurate check is required, unit must be shut down  
and thermistor removed and checked at a known temperature  
(freezing point or boiling point of water) using either voltage  
drop measured across thermistor at the J8 terminal, by deter-  
mining the resistance with chiller shut down and thermistor  
disconnected from J8. Compare the values determined with the  
value read by the control in the Temperatures mode using the  
scrolling marquee display.  
UNIT  
Psig  
650  
kPa  
4482  
Psig  
500  
kPa  
3447  
30MP015-045  
Clear the alarm using the scrolling marquee display. The  
unit should restart after the compressor anti-short-cycle delay,  
built into the unit control module, expires.  
PRESSURE TRANSDUCERS — Each unit is equipped with  
a suction and discharge pressure transducer. These inputs to the  
MBB are not only used to monitor the status of the unit, but to  
also maintain operation of the chiller within the compressor  
manufacturer's specified limits. The input to the MBB from the  
suction pressure transducer is also used to protect the compres-  
sor from operating at low pressure conditions. If suction return  
gas thermistors are installed, then additional low superheat  
conditions are detected. In some cases, the unit may not be able  
to run at full capacity. The control module will automatically  
reduce the capacity of a circuit as needed to maintain specified  
maximum/minimum operating pressures.  
Pressure Transducers — The suction and discharge  
transducers are different part numbers and can be distinguished  
by the color of the transducer body, suction (yellow) and dis-  
charge (red). No pressure transducer calibration is required.  
The transducers operate on a 5 vdc supply, which is generated  
by the main base board (MBB). See Fig. 23 for transducer con-  
nections to the J8 connector on the MBB.  
TROUBLESHOOTING — If a transducer is suspected of be-  
ing faulty, first check supply voltage to the transducer. Supply  
voltage should be 5 vdc ± 0.2 v. If supply voltage is correct,  
compare pressure reading displayed on the scrolling marquee  
display module against pressure shown on a calibrated pressure  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
gauge. Pressure readings should be within ± 15 psig. If the  
two readings are not reasonably close, replace the pressure  
transducer.  
4. Wrong pump motor rotation. Pump must rotate clockwise  
when viewed from motor end of pump.  
CONDENSER EWT  
ACCESSORY  
1
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
1
2
Chilled Water Flow Switch A factory-installed  
flow switch is installed in the leaving fluid piping for all units.  
This is a thermal-dispersion flow switch with no field adjust-  
ments. The switch is set for approximately 0.5 ft/sec of flow.  
The sensor tip houses two thermistors and a heater element.  
One thermistor is located in the sensor tip, closest to the flow-  
ing fluid. See Fig. 24. This thermistor is used to detect changes  
in the flow velocity of the liquid. The second thermistor is  
bonded to the cylindrical wall and is affected only by changes  
in the temperature of the liquid. The thermistors are positioned  
to be in close contact with the wall of the sensor probe and, at  
the same time, to be kept separated from each other within the  
confines of the probe.  
In order to sense flow, it is necessary to heat one of the  
thermistors in the probe. When power is applied, the tip of the  
probe is heated. As the fluid starts to flow, heat will be carried  
away from the sensor tip. Cooling of the first thermistor is a  
function of how fast heat is conducted away by the flowing  
liquid.  
CONDENSER LWT  
ACCESSORY  
3
T-55  
ACCSY  
LVT  
T55  
SEN  
4
J12  
3
BLU  
VIO  
RED  
5
23  
22  
21  
6
4
5
7
8
OAT ACCESSORY OR  
DUAL CHILLER LWT  
RGTA  
ACCESSORY  
9
BASE  
BOARD  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
COOLER ENTERING  
FLUID TEMP  
RED  
BLK  
RED  
COOLER LEAVING  
FLUID TEMP  
J8  
BLK  
The difference in temperature between the two thermistors  
provides a measurement of fluid velocity past the sensor probe.  
When fluid velocity is high, more heat will be carried away  
from the heated thermistor and the temperature differential will  
be small. As fluid velocity decreases, less heat will be taken  
from the heated thermistor and there will be an increase in tem-  
perature differential.  
B
C
A
RED  
+
8
DPTA  
GRN  
BLK  
9
-
10  
B
C
A
RED  
+
11  
12  
SPTA  
GRN  
BLK  
-
a30-5043  
When unit flow rate is above the minimum flow rate, then  
the output is switched on, sending 24 vac to the MBB to prove  
flow has been established.  
For recommended maintenance, check the sensor tip for  
build-up every 6 months. Clean the tip with a soft cloth. If  
necessary, build-up (e.g., lime) can be removed with a common  
vinegar cleansing agent.  
The flow sensor cable is provided with (3) LEDs that indi-  
cate if 24 vac power is present and also status of the switch  
contacts. The LEDs are as follows:  
LEGEND  
ACCSY — Accessory  
DPT  
EWT  
LWT  
LVT  
OAT  
RGT  
SEN  
SPT  
Discharge Pressure Transducer  
Entering Water Temperature  
Leaving Water Temperature Sensor  
Low Voltage Terminal  
Outdoor Air Temperature Sensor  
Return Gas Temperature Sensor  
Sensor Terminal Block  
Space Temperature Sensor  
Fig. 23 — Thermistor Connections to  
Main Base Board, J8 Connector  
• Green LED ON – 24 vac present  
• One Yellow LED ON – Flow sensor switch OPEN  
• Two Yellow LED ON – Flow sensor switch CLOSED  
If nuisance trips of the sensor are occurring, follow the  
steps below to correct the situation:  
1. Check to confirm that the field-installed strainer is clean.  
Use the blow-down valve provided or remove the screen  
and clean it. For the case of VFD controlled pumps, en-  
sure that the minimum speed setting has not been  
changed.  
2. Measure the pressure drop across the cooler and compare  
this to the system requirements.  
3. Verify that cable connections at the switch and at the ter-  
minal block are secure.  
a30-499  
NOTE: Dimensions are in millimeters.  
Fig. 24— Chilled Water Flow Switch  
5/8 in. HEX  
1/4-18 NPT  
6" MINIMUM  
CLEARANCE FOR  
THERMISTOR  
REMOVAL  
Fig. 22 — Thermistor Well  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 32 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop  
(Voltage Drop for EWT, LWT, RGT, CNDE, CNDL, Dual Chiller, and OAT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
59  
60  
1.982  
1.956  
1.930  
1.905  
1.879  
1.854  
1.829  
1.804  
1.779  
1.754  
1.729  
1.705  
1.681  
1.656  
1.632  
1.609  
1.585  
1.562  
1.538  
1.516  
1.493  
1.470  
1.448  
1.426  
1.404  
1.382  
1.361  
1.340  
1.319  
1.298  
1.278  
1.257  
1.237  
1.217  
1.198  
1.179  
1.160  
1.141  
1.122  
1.104  
1.086  
1.068  
1.051  
1.033  
1.016  
0.999  
0.983  
0.966  
0.950  
0.934  
0.918  
0.903  
0.888  
0.873  
0.858  
0.843  
0.829  
0.815  
0.801  
0.787  
0.774  
0.761  
0.748  
0.735  
0.723  
0.710  
0.698  
0.686  
0.674  
0.663  
0.651  
0.640  
0.629  
0.618  
0.608  
0.597  
0.587  
0.577  
0.567  
0.557  
0.548  
0.538  
0.529  
0.520  
7,686  
7,665  
7,468  
7,277  
7,091  
6,911  
6,735  
6,564  
6,399  
6,238  
6,081  
5,929  
5,781  
5,637  
5,497  
5,361  
5,229  
5,101  
4,976  
4,855  
4,737  
4,622  
4,511  
4,403  
4,298  
4,196  
4,096  
4,000  
3,906  
3,814  
3,726  
3,640  
3,556  
3,474  
3,395  
3,318  
3,243  
3,170  
3,099  
3,031  
2,964  
2,898  
2,835  
2,773  
2,713  
2,655  
2,597  
2,542  
2,488  
2,436  
2,385  
2,335  
2,286  
2,239  
2,192  
2,147  
2,103  
2,060  
2,018  
1,977  
1,937  
1,898  
1,860  
1,822  
1,786  
1,750  
1,715  
1,680  
1,647  
1,614  
1,582  
1,550  
1,519  
1,489  
1,459  
1,430  
1,401  
1,373  
1,345  
1,318  
1,291  
1,265  
1,240  
1,214  
143  
144  
145  
146  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
0.511  
0.502  
0.494  
0.485  
0.477  
0.469  
0.461  
0.453  
0.445  
0.438  
0.430  
0.423  
0.416  
0.408  
0.402  
0.395  
0.388  
0.381  
0.375  
0.369  
0.362  
0.356  
0.350  
0.344  
0.339  
0.333  
0.327  
0.322  
0.317  
0.311  
0.306  
0.301  
0.296  
0.291  
0.286  
0.282  
0.277  
0.272  
0.268  
0.264  
0.259  
0.255  
0.251  
0.247  
0.243  
0.239  
0.235  
0.231  
0.228  
0.224  
0.220  
0.217  
0.213  
0.210  
0.206  
0.203  
0.200  
0.197  
0.194  
0.191  
0.188  
0.185  
0.182  
0.179  
0.176  
0.173  
0.171  
0.168  
0.165  
0.163  
0.160  
0.158  
0.155  
0.153  
0.151  
0.148  
0.146  
0.144  
0.142  
0.140  
0.138  
0.135  
0.133  
1,190  
1,165  
1,141  
1,118  
1,095  
1,072  
1,050  
1,029  
1,007  
986  
965  
945  
925  
906  
887  
868  
850  
832  
815  
798  
782  
765  
750  
734  
719  
705  
690  
677  
663  
650  
638  
626  
614  
602  
591  
581  
570  
561  
551  
542  
533  
524  
516  
508  
501  
494  
487  
480  
473  
467  
461  
456  
450  
445  
439  
434  
429  
424  
419  
415  
410  
405  
401  
396  
391  
386  
382  
377  
372  
367  
361  
356  
350  
344  
338  
332  
325  
318  
311  
304  
297  
289  
282  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
–8  
–7  
–6  
–5  
–4  
–3  
–2  
–1  
0
3.699  
3.689  
3.679  
3.668  
3.658  
3.647  
3.636  
3.624  
3.613  
3.601  
3.588  
3.576  
3.563  
3.550  
3.536  
3.523  
3.509  
3.494  
3.480  
3.465  
3.450  
3.434  
3.418  
3.402  
3.386  
3.369  
3.352  
3.335  
3.317  
3.299  
3.281  
3.262  
3.243  
3.224  
3.205  
3.185  
3.165  
3.145  
3.124  
3.103  
3.082  
3.060  
3.038  
3.016  
2.994  
2.972  
2.949  
2.926  
2.903  
2.879  
2.856  
2.832  
2.808  
2.784  
2.759  
2.735  
2.710  
2.685  
2.660  
2.634  
2.609  
2.583  
2.558  
2.532  
2.506  
2.480  
2.454  
2.428  
2.402  
2.376  
2.349  
2.323  
2.296  
2.270  
2.244  
2.217  
2.191  
2.165  
2.138  
2.112  
2.086  
2.060  
2.034  
2.008  
98,010  
94,707  
91,522  
88,449  
85,486  
82,627  
79,871  
77,212  
74,648  
72,175  
69,790  
67,490  
65,272  
63,133  
61,070  
59,081  
57,162  
55,311  
53,526  
51,804  
50,143  
48,541  
46,996  
45,505  
44,066  
42,679  
41,339  
40,047  
38,800  
37,596  
36,435  
35,313  
34,231  
33,185  
32,176  
31,202  
30,260  
29,351  
28,473  
27,624  
26,804  
26,011  
25,245  
24,505  
23,789  
23,096  
22,427  
21,779  
21,153  
20,547  
19,960  
19,393  
18,843  
18,311  
17,796  
17,297  
16,814  
16,346  
15,892  
15,453  
15,027  
14,614  
14,214  
13,826  
13,449  
13,084  
12,730  
12,387  
12,053  
11,730  
11,416  
11,112  
10,816  
10,529  
10,250  
9,979  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
1
86  
2
87  
3
88  
4
89  
5
90  
6
91  
7
92  
8
93  
9
94  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
9,717  
9,461  
9,213  
8,973  
8,739  
8,511  
8,291  
8,076  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 33 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop  
(Voltage Drop for EWT, LWT, RGT, CNDE, CNDL, Dual Chiller, and OAT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
1.982  
1.935  
1.889  
1.844  
1.799  
1.754  
1.710  
1.666  
1.623  
1.580  
1.538  
1.497  
1.457  
1.417  
1.378  
1.340  
1.302  
1.265  
1.229  
1.194  
1.160  
1.126  
1.093  
1.061  
1.030  
0.999  
0.969  
0.940  
0.912  
0.885  
0.858  
0.832  
0.807  
0.782  
0.758  
0.735  
0.713  
0.691  
0.669  
0.649  
0.629  
0.610  
0.591  
0.573  
0.555  
0.538  
0.522  
7,855  
7,499  
7,161  
6,840  
6,536  
6,246  
5,971  
5,710  
5,461  
5,225  
5,000  
4,786  
4,583  
4,389  
4,204  
4,028  
3,861  
3,701  
3,549  
3,404  
3,266  
3,134  
3,008  
2,888  
2,773  
2,663  
2,559  
2,459  
2,363  
2,272  
2,184  
2,101  
2,021  
1,944  
1,871  
1,801  
1,734  
1,670  
1,609  
1,550  
1,493  
1,439  
1,387  
1,337  
1,290  
1,244  
1,200  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
0.506  
0.490  
0.475  
0.461  
0.447  
0.433  
0.420  
0.407  
0.395  
0.383  
0.371  
0.360  
0.349  
0.339  
0.329  
0.319  
0.309  
0.300  
0.291  
0.283  
0.274  
0.266  
0.258  
0.251  
0.244  
0.237  
0.230  
0.223  
0.217  
0.211  
0.204  
0.199  
0.193  
0.188  
0.182  
0.177  
0.172  
0.168  
0.163  
0.158  
0.154  
0.150  
0.146  
0.142  
0.138  
0.134  
1,158  
1,118  
1,079  
1,041  
1,006  
971  
938  
906  
876  
836  
805  
775  
747  
719  
693  
669  
645  
623  
602  
583  
564  
547  
531  
516  
502  
489  
477  
466  
456  
446  
436  
427  
419  
410  
402  
393  
385  
376  
367  
357  
346  
335  
324  
312  
299  
285  
–32  
3.705  
3.687  
3.668  
3.649  
3.629  
3.608  
3.586  
3.563  
3.539  
3.514  
3.489  
3.462  
3.434  
3.406  
3.376  
3.345  
3.313  
3.281  
3.247  
3.212  
3.177  
3.140  
3.103  
3.065  
3.025  
2.985  
2.945  
2.903  
2.860  
2.817  
2.774  
2.730  
2.685  
2.639  
2.593  
2.547  
2.500  
2.454  
2.407  
2.360  
2.312  
2.265  
2.217  
2.170  
2.123  
2.076  
2.029  
100,260  
94,165  
88,480  
83,170  
78,125  
73,580  
69,250  
65,205  
61,420  
57,875  
54,555  
51,450  
48,536  
45,807  
43,247  
40,845  
38,592  
38,476  
34,489  
32,621  
30,866  
29,216  
27,633  
26,202  
24,827  
23,532  
22,313  
21,163  
20,079  
19,058  
18,094  
17,184  
16,325  
15,515  
14,749  
14,026  
13,342  
12,696  
12,085  
11,506  
10,959  
10,441  
9,949  
–31  
–30  
–29  
–28  
–27  
–26  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
–8  
–7  
–6  
–5  
–4  
–3  
–2  
–1  
0
1
2
3
4
5
6
7
8
9
10  
11  
9,485  
12  
9,044  
13  
8,627  
14  
8,231  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 34 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop  
(For SPT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
–8  
–7  
–6  
–5  
–4  
–3  
–2  
–1  
0
4.758  
4.750  
4.741  
4.733  
4.724  
4.715  
4.705  
4.696  
4.686  
4.676  
4.665  
4.655  
4.644  
4.633  
4.621  
4.609  
4.597  
4.585  
4.572  
4.560  
4.546  
4.533  
4.519  
4.505  
4.490  
4.476  
4.461  
4.445  
4.429  
4.413  
4.397  
4.380  
4.363  
4.346  
4.328  
4.310  
4.292  
4.273  
4.254  
4.235  
4.215  
4.195  
4.174  
4.153  
4.132  
4.111  
4.089  
4.067  
4.044  
4.021  
3.998  
3.975  
3.951  
3.927  
3.903  
3.878  
3.853  
3.828  
3.802  
3.776  
3.750  
3.723  
3.697  
3.670  
3.654  
3.615  
3.587  
3.559  
3.531  
3.503  
3.474  
3.445  
3.416  
3.387  
3.357  
3.328  
3.298  
3.268  
3.238  
3.208  
3.178  
3.147  
3.117  
3.086  
3.056  
3.025  
196,453  
189,692  
183,300  
177,000  
171,079  
165,238  
159,717  
154,344  
149,194  
144,250  
139,443  
134,891  
130,402  
126,183  
122,018  
118,076  
114,236  
110,549  
107,006  
103,558  
100,287  
97,060  
94,020  
91,019  
88,171  
85,396  
82,729  
80,162  
77,662  
75,286  
72,940  
70,727  
68,542  
66,465  
64,439  
62,491  
60,612  
58,781  
57,039  
55,319  
53,693  
52,086  
50,557  
49,065  
47,627  
46,240  
44,888  
43,598  
42,324  
41,118  
39,926  
38,790  
37,681  
36,610  
35,577  
34,569  
33,606  
32,654  
31,752  
30,860  
30,009  
29,177  
28,373  
27,597  
26,838  
26,113  
25,396  
24,715  
24,042  
23,399  
22,770  
22,161  
21,573  
20,998  
20,447  
19,903  
19,386  
18,874  
18,384  
17,904  
17,441  
16,991  
16,552  
16,131  
15,714  
15,317  
61  
62  
2.994  
2.963  
2.932  
2.901  
2.870  
2.839  
2.808  
2.777  
2.746  
2.715  
2.684  
2.653  
2.622  
2.592  
2.561  
2.530  
2.500  
2.470  
2.439  
2.409  
2.379  
2.349  
2.319  
2.290  
2.260  
2.231  
2.202  
2.173  
2.144  
2.115  
2.087  
2.059  
2.030  
2.003  
1.975  
1.948  
1.921  
1.894  
1.867  
1.841  
1.815  
1.789  
1.763  
1.738  
1.713  
1.688  
1.663  
1.639  
1.615  
1.591  
1.567  
1.544  
1.521  
1.498  
1.475  
1.453  
1.431  
1.409  
1.387  
1.366  
1.345  
1.324  
1.304  
1.284  
1.264  
1.244  
1.225  
1.206  
1.187  
1.168  
1.150  
1.132  
1.114  
1.096  
1.079  
1.062  
1.045  
1.028  
1.012  
0.996  
0.980  
0.965  
0.949  
0.934  
0.919  
0.905  
14,925  
14,549  
14,180  
13,824  
13,478  
13,139  
12,814  
12,493  
12,187  
11,884  
11,593  
11,308  
11,031  
10,764  
10,501  
10,249  
10,000  
9,762  
9,526  
9,300  
9,078  
8,862  
8,653  
8,448  
8,251  
8,056  
7,869  
7,685  
7,507  
7,333  
7,165  
6,999  
6,838  
6,683  
6,530  
6,383  
6,238  
6,098  
5,961  
5,827  
5,698  
5,571  
5,449  
5,327  
5,210  
5,095  
4,984  
4,876  
4,769  
4,666  
4,564  
4,467  
4,370  
4,277  
4,185  
4,096  
4,008  
3,923  
3,840  
3,759  
3,681  
3,603  
3,529  
3,455  
3,383  
3,313  
3,244  
3,178  
3,112  
3,049  
2,986  
2,926  
2,866  
2,809  
2,752  
2,697  
2,643  
2,590  
2,539  
2,488  
2,439  
2,391  
2,343  
2,297  
2,253  
2,209  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
0.890  
0.876  
0.862  
0.848  
0.835  
0.821  
0.808  
0.795  
0.782  
0.770  
0.758  
0.745  
0.733  
0.722  
0.710  
0.699  
0.687  
0.676  
0.666  
0.655  
0.645  
0.634  
0.624  
0.614  
0.604  
0.595  
0.585  
0.576  
0.567  
0.558  
0.549  
0.540  
0.532  
0.523  
0.515  
0.507  
0.499  
0.491  
0.483  
0.476  
0.468  
0.461  
0.454  
0.447  
0.440  
0.433  
0.426  
0.419  
0.413  
0.407  
0.400  
0.394  
0.388  
0.382  
0.376  
0.370  
0.365  
0.359  
0.354  
0.349  
0.343  
0.338  
0.333  
0.328  
0.323  
0.318  
0.314  
0.309  
0.305  
0.300  
0.296  
0.292  
0.288  
0.284  
0.279  
0.275  
0.272  
0.268  
0.264  
2,166  
2,124  
2,083  
2,043  
2,003  
1,966  
1,928  
1,891  
1,855  
1,820  
1,786  
1,752  
1,719  
1,687  
1,656  
1,625  
1,594  
1,565  
1,536  
1,508  
1,480  
1,453  
1,426  
1,400  
1,375  
1,350  
1,326  
1,302  
1,278  
1,255  
1,233  
1,211  
1,190  
1,169  
1,148  
1,128  
1,108  
1,089  
1,070  
1,052  
1,033  
1,016  
998  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
1
87  
2
88  
3
89  
4
90  
5
91  
6
92  
7
93  
8
94  
9
95  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
981  
964  
947  
931  
915  
900  
885  
870  
855  
841  
827  
814  
800  
787  
774  
762  
749  
737  
725  
714  
702  
691  
680  
670  
659  
649  
639  
629  
620  
610  
601  
592  
583  
574  
566  
557  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 35 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop  
(For SPT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
–32  
–31  
–30  
–29  
–28  
–27  
–26  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
4.762  
4.748  
4.733  
4.716  
4.700  
4.682  
4.663  
4.644  
4.624  
4.602  
4.580  
4.557  
4.533  
4.508  
4.482  
4.455  
4.426  
4.397  
4.367  
4.335  
4.303  
4.269  
4.235  
4.199  
4.162  
4.124  
4.085  
4.044  
4.003  
3.961  
3.917  
3.873  
3.828  
3.781  
3.734  
3.686  
3.637  
3.587  
3.537  
3.485  
3.433  
3.381  
3.328  
3.274  
3.220  
3.165  
3.111  
200,510  
188,340  
177,000  
166,342  
156,404  
147,134  
138,482  
130,402  
122,807  
115,710  
109,075  
102,868  
97,060  
91,588  
86,463  
81,662  
77,162  
72,940  
68,957  
65,219  
61,711  
58,415  
55,319  
52,392  
49,640  
47,052  
44,617  
42,324  
40,153  
38,109  
36,182  
34,367  
32,654  
31,030  
29,498  
28,052  
26,686  
25,396  
24,171  
23,013  
21,918  
20,883  
19,903  
18,972  
18,090  
17,255  
16,464  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
3.056  
3.000  
2.944  
2.889  
2.833  
2.777  
2.721  
2.666  
2.610  
2.555  
2.500  
2.445  
2.391  
2.337  
2.284  
2.231  
2.178  
2.127  
2.075  
2.025  
1.975  
1.926  
1.878  
1.830  
1.784  
1.738  
1.692  
1.648  
1.605  
1.562  
1.521  
1.480  
1.439  
1.400  
1.362  
1.324  
1.288  
1.252  
1.217  
1.183  
1.150  
1.117  
1.086  
1.055  
1.025  
0.996  
0.968  
15,714  
15,000  
14,323  
13,681  
13,071  
12,493  
11,942  
11,418  
10,921  
10,449  
10,000  
9,571  
9,164  
8,776  
8,407  
8,056  
7,720  
7,401  
7,096  
6,806  
6,530  
6,266  
6,014  
5,774  
5,546  
5,327  
5,117  
4,918  
4,727  
4,544  
4,370  
4,203  
4,042  
3,889  
3,743  
3,603  
3,469  
3,340  
3,217  
3,099  
2,986  
2,878  
2,774  
2,675  
2,579  
2,488  
2,400  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
0.940  
0.913  
0.887  
0.862  
0.837  
0.813  
0.790  
0.767  
0.745  
0.724  
0.703  
0.683  
0.663  
0.645  
0.626  
0.608  
0.591  
0.574  
0.558  
0.542  
0.527  
0.512  
0.497  
0.483  
0.470  
0.457  
0.444  
0.431  
0.419  
0.408  
0.396  
0.386  
0.375  
0.365  
0.355  
0.345  
0.336  
0.327  
0.318  
0.310  
0.302  
0.294  
0.287  
0.279  
0.272  
0.265  
2,315  
2,235  
2,157  
2,083  
2,011  
1,943  
1,876  
1,813  
1,752  
1,693  
1,637  
1,582  
1,530  
1,480  
1,431  
1,385  
1,340  
1,297  
1,255  
1,215  
1,177  
1,140  
1,104  
1,070  
1,037  
1,005  
974  
–8  
–7  
–6  
–5  
944  
–4  
915  
–3  
889  
–2  
861  
–1  
836  
0
811  
1
787  
2
764  
3
742  
4
721  
5
700  
6
680  
7
661  
8
643  
9
626  
10  
609  
11  
592  
12  
576  
13  
561  
14  
Strainer — Periodic cleaning of the required field-installed  
strainer is required. Pressure drop across strainer in excess of  
3 psi (21 kPa) indicates the need for cleaning. Normal (clean)  
pressure drop is approximately 1 psi (6.9 kPa). Open the  
blowdown valve to clean the strainer. If required, shut the chill-  
er down and remove the strainer screen to clean. When strainer  
has been cleaned, enter ‘YES’ for Strainer Maintenance Done  
(Run StatusPMS.T.MN.  
WARNING  
Electrical shock can cause personal injury and death. Shut  
off all power to this equipment during installation. There  
may be more than one disconnect switch. Tag all discon-  
nect locations to alert others not to restore power until work  
is completed.  
Replacing Defective Modules — The Comfort-  
Linkreplacement modules are shown in Table 36. If the main  
base board (MBB) has been replaced, verify that all configura-  
tion data is correct. Follow the Configuration mode table and  
verify that all items under sub-modes UNIT, OPT1 and OPT2  
are correct. Any additional field-installed accessories or op-  
tions (RSET, SLCT sub-modes) should also be verified as well  
as any specific time and maintenance schedules.  
Refer to the Start-Up Checklist for 30MP Liquid Chillers  
(completed at time of original start-up) found in the job folder.  
This information is needed later in this procedure. If the check-  
list does not exist, fill out the current information in the Config-  
uration mode on a new checklist. Tailor the various options and  
configurations as needed for this particular installation.  
1. Check that all power to unit is off. Carefully disconnect  
all wires from the defective module by unplugging its  
connectors.  
2. Remove the defective module by removing its mounting  
screws with a Phillips screwdriver, and removing the  
module from the control box. Save the screws later use.  
3. Verify that the instance jumper (MBB) or address switch-  
es (all other modules) exactly match the settings of the  
defective module.  
NOTE: Handle boards by mounting standoffs only to  
avoid electrostatic discharge.  
4. Package the defective module in the carton of the new  
module for return to Carrier.  
5. Mount the new module in the unit’s control box using a  
Phillips screwdriver and the screws saved in Step 2.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Reinstall all module connectors. For accessory Naviga-  
tor™ device replacement, make sure the plug is installed  
at TB3 in the LEN connector.  
7. Carefully check all wiring connections before restoring  
power.  
UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS  
OFF — When the switch is OFF, the unit will stop immediate-  
ly. Place the switch in the ENABLE position for local switch  
control or in the REMOTE CONTACT position for control  
through remote contact closure.  
CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN —  
After the problem causing the loss of flow has been corrected,  
reset is manual by resetting the alarm with the scrolling  
marquee.  
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De-  
termine the cause of the failure and correct. Reset circuit break-  
er(s). Restart is automatic after MBB start-up cycle is com-  
plete.  
8. Verify the ENABLE/OFF/REMOTE CONTACT switch  
is in the OFF position.  
9. Restore control power. Verify that all module red LEDs  
blink in unison. Verify that all green LEDs are blinking  
and that the scrolling marquee or Navigator™ display is  
communicating correctly.  
10. Verify all configuration information, settings, set points  
and schedules. Return the ENABLE/OFF/REMOTE  
CONTACT switch to its previous position.  
COOLING LOAD SATISFIED — Unit shuts down when  
cooling load has been satisfied. Unit restarts when required to  
satisfy leaving fluid temperature set point.  
Table 36 — Replacement Modules  
THERMISTOR FAILURE — If a thermistor fails in either an  
open or shorted condition, the unit will be shut down. Replace  
EWT, or LWT as required. Unit restarts automatically, but must  
be reset manually by resetting the alarm with the scrolling  
marquee.  
REPLACEMENT  
MODULE  
PART NO.  
(with Software)  
Main Base Board (MBB)  
Scrolling Marquee Display  
Energy Management Module (EMM)  
Navigator Display  
30MP500346  
HK50AA031  
30GT515218  
HK50AA033  
CAUTION  
If unit stoppage occurs more than once as a result of any of  
the safety devices listed, determine and correct cause  
before attempting another restart.  
MAINTENANCE  
Recommended Maintenance Schedule — The fol-  
lowing are only recommended guidelines. Jobsite conditions  
may dictate that maintenance schedule is performed more often  
than recommended.  
LOW SATURATED SUCTION — Several conditions can  
lead to low saturated suction alarms and the chiller controls  
have several override modes built in which will attempt to keep  
the chiller from shutting down. Low fluid flow, low refrigerant  
charge and plugged filter driers are the main causes for this  
condition. To avoid permanent damage and potential freezing  
of the system, do NOT repeatedly reset these alert and/or alarm  
conditions without identifying and correcting the cause(s).  
Routine:  
Every month:  
Check moisture indicating sight glass for possible refrig-  
erant loss and presence of moisture.  
Every 3 months (for all machines):  
COMPRESSOR SAFETIES — The 30MP units with Com-  
fortLink™ controls include a compressor protection board that  
protects the operation of each of the compressors. Each board  
senses the presence or absence of current to each compressor.  
If there is a command for a compressor to run and there is  
no current, then one of the following safeties or conditions  
have turned the compressor off:  
Compressor Overcurrent — All compressors have internal  
line breaks or a motor protection device located in the com-  
pressor electrical box.  
Compressor Short Circuit — There will not be current if the  
compressor circuit breaker that provides short circuit protection  
has tripped.  
Compressor Motor Over Temperature — The internal line-  
break or over temperature switch has opened.  
High-Pressure Switch Trip — The high pressure switch has  
opened. See Table 31 for the factory settings for the fixed high  
pressure switch.  
ASTP Protection Trip — All non-digital Copeland compres-  
sors are equipped with an advanced scroll temperature protec-  
tion (ASTP). A label located above the terminal box identifies  
models that contain this technology. See Fig. 25.  
Check refrigerant charge.  
Check all refrigerant joints and valves for refrigerant  
leaks, repair as necessary.  
Check chilled water flow switch operation.  
Check compressor oil level.  
Every 12 months (for all machines):  
Check all electrical connections, tighten as necessary.  
Inspect all contactors and relays, replace as necessary.  
Check accuracy of thermistors, replace if greater than  
± 2° F (1.2° C) variance from calibrated thermometer.  
Check to be sure that the proper concentration of anti-  
freeze is present in the chilled water loop, if applicable.  
Verify that the chilled water loop is properly treated.  
Check refrigerant filter driers for excessive pressure  
drop, replace as necessary.  
Check chilled water and condenser strainers, clean as  
necessary.  
Perform Service Test to confirm operation of all  
components.  
Check for excessive cooler approach (Leaving Chilled  
Water Temperature — Saturated Suction Temperature)  
which may indicate fouling. Clean evaporator if  
necessary.  
Advanced scroll temperature protection is a form of internal  
discharge temperature protection that unloads the scroll com-  
pressor when the internal temperature reaches approximately  
300 F. At this temperature, an internal bi-metal disk valve  
opens and causes the scroll elements to separate, which stops  
compression. Suction and discharge pressures balance while  
the motor continues to run. The longer the compressor runs un-  
loaded, the longer it must cool before the bi-metal disk resets.  
See Fig. 26 for approximate reset times.  
TROUBLESHOOTING  
Complete Unit Stoppage and Restart Possi-  
ble causes for unit stoppage and reset methods are shown be-  
low and in Table 37. Refer to Fig. 3-7 for component arrange-  
ment and control wiring diagrams.  
GENERAL POWER FAILURE — After power is restored,  
restart is automatic through normal MBB start-up.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the compressor is commanded OFF and the current sensor  
reads ON, an alert is generated. This will indicate that a com-  
pressor contactor has failed closed. In this case, a special mode,  
Compressor Stuck on Control, will be enabled and all other  
compressors will be turned off. An alarm will then be enabled  
to indicate that service is required. Outdoor fans will continue  
to operate. The condenser output is turned on immediately.  
Alarms and Alerts — These are warnings of abnormal  
or fault conditions, and may cause either one circuit or the  
whole unit to shut down. They are assigned code numbers as  
described in Table 38.  
Automatic alarms will reset without operator intervention if  
the condition corrects itself. The following method must be  
used to reset manual alarms:  
Fig. 25 — Advanced Scroll Temperature  
Protection Label  
Before resetting any alarm, first determine the cause of the  
alarm and correct it. Enter the Alarms mode indicated by the  
LED on the side of the scrolling marquee display. Press  
To manually reset ASTP, the compressor should be stopped  
and allowed to cool. If the compressor is not stopped, the motor  
will run until the motor protector trips, which occurs up to  
90 minutes later. Advanced scroll temperature protection will  
reset automatically before the motor protector resets, which  
may take up to 2 hours.  
High Discharge Gas Temperature Protection — Units  
equipped with optional digital compressors have an additional  
thermistor located on the discharge line, If discharge tempera-  
ture exceeds 265 F (129.4 C), the digital compressor will be  
shut off.  
and  
until the sub-menu item RCRN “RESET  
ENTER  
ALL CURRENT ALARMS” is displayed. Press  
.
ENTER  
The control will prompt the user for a password, by displaying  
PASS and WORD. Press to display the default pass-  
ENTER  
for each character. If the password  
word, 1111. Press  
ENTER  
has been changed, use the arrow keys to change each individu-  
al character. Toggle the display to “YES” and press  
The alarms will be reset.  
.
ENTER  
Alarms will also occur if the current sensor board malfunc-  
tions or is not properly connected to its assigned digital input. If  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
Compressor Unloaded Run Time (Minutes)  
*Times are approximate.  
NOTE: Various factors, including high humidity, high ambient temperature,  
and the presence of a sound blanket will increase cool-down times.  
Fig. 26 — Recommended Minimum Cool Down Time After Compressor is Stopped*  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 37 — Troubleshooting  
SYMPTOMS  
Compressor Cycles  
Off on Loss of Charge  
CAUSE  
REMEDY  
Repair leak and recharge.  
Loss of charge control. Acting erratically.  
Replace control.  
Low refrigerant charge  
Low suction temperature  
Thermistor failure  
Add refrigerant.  
Raise cooler leaving fluid temperature set point.  
Replace thermistor.  
Compressor Cycles Off on Out  
of Range Condition  
System load was reduced faster than controller could  
remove stages  
Unit will restart after fluid temperature rises back into the  
control band. Avoid rapidly removing system load or  
increase loop volume.  
Temperature controller deadband setting is too low  
High-pressure control acting erratically  
Noncondensables in system  
Raise deadband setting.  
Replace control.  
Compressor Shuts Down on  
High-Pressure Control  
Purge system.  
Condenser scaled/dirty  
Clean condenser.  
Fans in remote condensing unit (30MPA only) not operating Repair or replace if defective.  
System overcharged with refrigerant  
Low refrigerant charge  
Control contacts fused  
Air in system  
Reduce charge.  
Unit Operates Too Long  
or Continuously  
Add refrigerant.  
Replace control.  
Purge system.  
Partially plugged or plugged expansion valve or filter drier  
Defective insulation  
Clean or replace as needed.  
Replace or repair as needed.  
Keep doors and windows closed.  
Check compressor and replace if necessary.  
Support piping as required.  
Check for loose pipe connections or damaged compressor  
Add refrigerant.  
Service load  
Damaged compressor  
Unusual or Loud System  
Noises  
Piping vibration  
Expansion valve hissing  
Compressor noisy  
Check for plugged liquid line filter drier.  
Replace compressor (worn bearings).  
Check for loose compressor holddown bolts.  
Repair leak.  
Compressor Loses Oil  
Leak in system  
Mechanical damage (Failed seals or broken scrolls)  
Oil trapped in line  
Replace compressor.  
Check piping for oil traps.  
Repair leak and recharge.  
Replace filter drier.  
Hot Liquid Line  
Shortage of refrigerant due to leak  
Restricted filter drier  
Frosted Liquid Line  
Frosted Suction Line  
Expansion valve admitting excess refrigerant (note: this is a Replace valve if defective.  
normal condition for brine applications)  
Stuck TXV  
Replace valve if defective.  
Freeze-Up  
Improper charging  
Make sure a full quantity of fluid is flowing through the cooler  
while charging, and suction pressure in cooler is equal to or  
greater than pressure corresponding to 32 F (0° C).  
System not drained for winter shutdown  
Loose Thermistor  
Recommended that system be filled with an appropriate gly-  
col mixture to prevent freezing of pumps and fluid tubing.  
Verify thermistors are fully inserted in wells.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 38 — Alarm and Alert Codes  
ALARM/ ALARM  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
ALERT  
CODE  
OR  
DESCRIPTION  
BY CONTROL  
GENERATED?  
ALERT  
Circuit A Compressor  
Availability Alarm  
Two compressors on circuit  
Circuit shut down  
failed  
Only one compressor  
operating.  
A048  
T051  
Alarm  
Alert  
Manual  
Manual  
High-pressure switch open,  
faulty CSB, loss of condenser  
flow, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Circuit A, Compressor 1  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor A1 shut  
down.  
High-pressure switch open,  
faulty CSB, loss of condenser  
flow, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit A, Compressor 1  
Failure  
A051  
T052  
A052  
T053  
Alarm  
Alert  
Unit shut down  
Manual  
Manual  
Manual  
Manual  
High-pressure switch open,  
faulty CSB, loss of condenser  
flow, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Circuit A, Compressor 2  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor A2 shut  
down.  
High-pressure switch open,  
faulty CSB, loss of condenser  
flow, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit A, Compressor 2  
Failure  
Alarm  
Alert  
Unit shut down  
High-pressure switch open,  
faulty CSB, loss of condenser  
flow, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Circuit A, Compressor 3  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor A3 shut  
down.  
High-pressure switch open,  
faulty CSB, loss of condenser  
flow, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit A, Compressor 3  
Failure  
A053  
A060  
Alarm  
Alarm  
Unit shut down  
Manual  
Cooler Leaving Fluid  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Chiller shut down  
immediately  
Thermistor failure, damaged  
cable/wire or wiring error.  
Automatic  
Cooler Entering Fluid  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Chiller shut down  
immediately  
Thermistor failure, damaged  
cable/wire or wiring error.  
A061  
T062  
Alarm  
Alert  
Automatic  
Automatic  
Condenser Leaving Fluid  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Alert only.  
No action taken.  
Thermistor failure, damaged  
cable/wire or wiring error.  
T063  
Alert  
Condenser Entering Fluid  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Alert only.  
No action taken.  
Automatic  
Thermistor failure, damaged  
cable/wire or wiring error.  
If return gas sensors are  
enabled (RG.EN) and  
thermistor is outside range of  
–40 to 245 F (–40 to 118 C)  
Circuit A Return Gas  
Thermistor Failure  
Thermistor failure, damaged  
cable/wire or wiring error.  
T068  
None  
Circuit A shut down  
Automatic  
Temperature reset  
disabled. Chiller runs  
under normal control/set  
points.  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
(if enabled)  
Outside Air Thermistor  
Failure  
Thermistor failure, damaged  
cable/wire or wiring error.  
T073  
T074  
A077  
Alert  
Alert  
Automatic  
Automatic  
Manual  
Temperature reset  
disabled. Chiller runs  
under normal control/set  
points.  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
(if enabled)  
Space Temperature/Dual Chiller  
Thermistor Failure  
Thermistor failure, damaged  
cable/wire or wiring error.  
Circuit A Saturated  
Suction Temperature  
exceeds Cooler Leaving  
Fluid Temperature  
Faulty expansion valve,  
suction pressure transducer  
or leaving fluid thermistor.  
Faulty expansion valve or  
suction pressure transducer  
or leaving fluid thermistor.  
Circuit A shutdown after  
pumpdown complete.  
Alarm  
Dual LWT thermistor failure,  
damaged cable/wire or  
wiring error.  
Lead/Lag LWT  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Chiller runs as a stand  
alone machine  
T079  
A090  
Alert  
Automatic  
Automatic  
Thermistor Failure  
Transducer failure, poor  
connection to MBB, or wiring  
damage/error.  
Circuit A Discharge  
Pressure Transducer Failure  
Alarm  
Outside of range (0 - 667 psig) Circuit A shut down  
Transducer failure, poor  
connection to MBB, or wiring  
damage/error.  
Circuit A Suction  
A092  
T094  
Alarm  
Alert  
Outside of range (0 - 420 psig) Circuit A shut down  
Discharge thermistor (DTT) is Digital compressor shut  
Automatic  
Automatic  
Pressure Transducer Failure  
Discharge Gas  
Thermistor Failure  
Thermistor failure, damaged  
cable/wire or wiring error.  
either open or shorted  
down.  
If the compressors are off  
and discharge pressure  
reading is < 26 psig for  
30 sec.  
Circuit not allowed to  
start.  
Refrigerant leak or  
transducer failure  
A110  
A112  
Alarm Circuit A Loss of Charge  
Manual  
Manual  
Circuit saturated suction  
temperature pressure  
transducer > 70 F (21.1 C)  
for 5 minutes  
Faulty Expansion valve,  
faulty suction pressure  
transducer or high entering  
fluid temperature.  
Circuit A High Saturated  
Alarm  
Circuit shut down  
Suction Temperature  
Automatic restart Faulty expansion valve,  
Suction superheat is  
less than 5° F (2.8 C) for 5  
minutes. (if RGT installed)  
after first daily  
occurrence.  
Manual restart  
thereafter.  
faulty suction pressure  
transducer, faulty suction gas  
thermistor, circuit  
Circuit A Low Suction  
Superheat  
A114  
Alarm  
Circuit A shut down.  
overcharged  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 38 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
Mode 7 caused the com-  
Faulty expansion valve, low  
refrigerant charge, plugged  
filter drier, faulty suction  
pressure transducer, low  
cooler fluid flow  
pressor to unload 6 consecu-  
Circuit A Low Cooler  
Suction Temperature  
A116  
A122  
Alarm  
Alarm  
tive times with less than a  
30-minute interval between  
each circuit shutdown.  
Circuit shut down  
Circuit shut down  
Manual  
High Pressure Switch  
Trip Circuit A  
High Pressure A Switch  
Input opento MBB  
Faulty transducer/high  
pressure switch.  
Manual  
Automatic, only  
after first 3 daily  
occurrences.  
Faulty transducer/high  
pressure switch, low/  
restricted condenser  
airflow  
SCT >Maximum condensing  
temperature from operating  
envelope  
Manual reset  
Circuit A High  
A126  
T133  
Alarm  
Alert  
Circuit shut down  
Circuit shut down  
thereafter. Read-  
ing from OAT sen-  
sor must drop 5 F  
(2.8 C) before  
restart  
Discharge Pressure  
Automatic  
Faulty or plugged EXV, low  
refrigerant charge, EXV out  
of adjustment, liquid  
Suction pressure below  
34 psig for 8 seconds or  
below 23 psig  
restart after first  
daily occurrence.  
Manual restart  
thereafter.  
Circuit A Low Suction  
Pressure  
line valve partially closed  
Reverse any two incoming  
power leads to correct. Check  
for correct fan rotation first.  
Reverse Rotation  
Detected  
Incoming chiller power leads Chiller not allowed to  
A140  
A150  
A151  
Alert  
Alarm  
Alarm  
Manual  
not phased correctly  
start.  
Automatic once  
Chiller shutdown  
without going through  
pumpdown.  
CCN emergency stop  
command received  
CCN command for CCN Network  
EMSTOP returns to command.  
normal  
Emergency Stop  
Manual once  
configuration errors  
are corrected  
One or more illegal  
configurations exists.  
Chiller is not allowed to  
start.  
Configuration error.  
Check unit settings.  
Illegal Configuration  
Automatic once  
alarms/alerts are  
cleared that pre-  
Alarm notifies user  
that chiller is 100%  
Unit Down Due to  
Failure  
Both circuits are down due  
to alarms/alerts.  
Chiller is unable  
to run.  
A152  
Alarm  
vent the chiller from down.  
starting.  
Occupancy schedule  
will not be used. Chiller  
defaults to Local On  
mode.  
Automatic when  
correct clock con-  
trol restarts.  
Time/Date/Month/  
Real Time Clock  
Hardware Failure  
T153  
A154  
Alert  
Internal clock on MBB fails  
Hardware failure with MBB  
Day/Year not  
properly set.  
Serial EEPROM  
Hardware Failure  
Chiller is unable  
to run.  
Main Base Board  
failure.  
Alarm  
Manual  
Potential failure of  
MBB. Download  
Serial EEPROM  
Storage Failure  
Configuration/storage  
failure with MBB  
T155  
Alert  
No Action  
Manual  
current operating  
software. Replace  
MBB if error occurs again.  
Critical Serial EEPROM  
Storage Failure  
Configuration/storage  
failure with MBB  
Chiller is not allowed  
to run.  
Main Base Board  
failure.  
A156  
A157  
Alarm  
Alarm  
Manual  
Manual  
Hardware failure with  
peripheral device  
Chiller is not allowed  
to run.  
Main Base Board  
failure.  
A/D Hardware Failure  
4 to 20 mA  
temperature reset  
disabled. Demand  
Limit set to 100%. 4 to  
20 mA set point  
disabled.  
Wiring error, faulty  
wiring or failed  
Energy Management Module  
(EMM).  
Loss of Communication  
with EMM  
MBB loses communication  
with EMM  
T173  
Alert  
Automatic  
If configured with EMM and  
input less than 2 mA or  
greater than 22 mA  
Set point function  
disabled. Chiller  
controls to CSP1.  
Faulty signal  
4 to 20 mA Cooling Set  
Point Input Failure  
T174  
T176  
Alert  
Alert  
Automatic  
Automatic  
generator, wiring  
error, or faulty EMM.  
Reset function  
4 to 20 mA  
Temperature Reset  
Input Failure  
If configured with EMM  
and input less than 2 mA or  
greater than 22 mA  
Faulty signal  
generator, wiring  
error, or faulty EMM.  
disabled. Chiller  
returns to normal set  
point control.  
Demand limit function  
disabled. Chiller  
returns to 100%  
demand limit  
If configured with EMM and  
input less than 2 mA or  
greater than 22 mA  
Faulty signal  
generator, wiring  
error, or faulty EMM.  
4 to 20 mA Demand  
Limit Input Failure  
T177  
Alert  
Automatic  
control.  
See legend on page 51.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 38 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
Cooler flow switch contacts  
failed to close within  
1 minute (if cooler pump  
control is enabled) or  
within 5 minutes (if cooler  
pump control is not  
Chiller not allowed to  
start. For models with  
dual pumps, the  
second pump will be  
started if available  
Cooler Flow/Interlock  
Contacts failed to Close  
at start-up  
Faulty flow switch or  
interlock.  
T200  
Alert  
Manual  
Manual  
enabled) after start-up  
All compressors shut  
down. For models with  
dual pumps, the  
Cooler Flow/Interlock  
Contacts Opened  
During Normal  
Operation  
Flow switch opens for at  
least 3 seconds after  
being initially closed  
Cooler pump failure,  
faulty flow switch or  
interlock.  
A201  
A202  
Alarm  
Alarm  
second pump will be  
started if available  
If configured for cooler  
pump control and flow  
switch input is closed for  
5 minutes while pump  
output(s) are off  
Cooler Pump Interlock  
Closed When Pump is  
Off  
Wiring error, faulty  
pump contactor  
(welded contacts)  
Automatic when  
aux contacts open  
Chiller shut down  
Wiring error, faulty  
wiring, failed Slave  
chiller MBB module,  
power loss at slave  
chiller, wrong slave  
address.  
Dual chiller control  
disabled. Chiller runs  
as a stand-alone  
machine.  
Master chiller MBB  
loses communication  
with slave chiller MBB  
Loss of Communication  
with slave chiller  
T203  
T204  
Alert  
Alert  
Automatic  
Automatic  
Wiring error, faulty  
wiring, failed master  
chiller MBB module,  
power loss at Master  
chiller.  
Dual chiller control  
disabled. Chiller runs  
as a stand-alone  
machine  
Slave chiller MBB loses  
communication with  
master chiller MBB  
Loss of Communication  
with master chiller  
CCN Address for  
both chillers is the  
same. Must be  
different. Check  
CCN.A under the  
OPT2 sub-mode in  
Configuration at both  
chillers.  
Dual chiller routine  
disabled. Master/slave  
run as stand-alone  
chillers.  
Master and slave chiller  
have the same CCN  
address (CCN.A)  
Master and slave chiller  
with same address  
T205  
Alert  
Automatic  
Building load greater  
than unit capacity,  
low water/brine flow  
or compressor fault.  
Check for other  
LWT read is greater than  
LCW Alert Limit, Total  
capacity is 100% and LWT  
is greater than LWT  
High Leaving Chilled  
Water Temperature  
Alert only. No action  
taken.  
T206  
A207  
Alert  
Automatic  
reading one minute ago  
alarms/alerts.  
Chiller shutdown  
without going through  
pumpdown. Cooler  
pump continues to  
run a minimum of  
5 minutes (if control  
enabled).  
Both EWT and LWT  
must be at least 6 F  
(3.3 C) above Brine  
Freeze point  
(BR.FZ). Automatic  
for first, Manual reset  
there after.  
Faulty thermistor  
(T1/T2), low water  
flow.  
Cooler Freeze  
Protection  
Cooler EWT or LWT is less  
than Brine Freeze (BR.FZ)  
Alarm  
Cooler EWT is less than  
LWT by 3° F (1.7° C) for  
1 minute after a circuit is  
started  
Faulty cooler pump,  
low water flow,  
plugged fluid  
strainer.  
Chiller shutdown.  
EWT or LWT  
A208  
A220  
Alarm  
Alarm  
Cooler pump shut off  
(if control enabled).  
Manual  
Manual  
Thermistor failure  
Condenser Pump  
Interlock Failure to  
Close  
If configured for con-  
denser pump interlock  
and the flow switch  
Condenser and cooler  
pumps shut off.  
Chiller shutdown with-  
out going through  
pumpdown.  
Failure of condenser  
pump or controls.  
Wiring error.  
at Start-Up  
input fails to close with-  
in 5 minutes after start-  
up. Also valid when  
configured for con-  
denser pump control.  
A221  
A222  
Alarm  
Condenser Pump  
If configured for con-  
denser pump interlock  
and the flow switch  
opens for 15 seconds  
during normal  
operation (or when  
the condenser pump  
relay is on when con-  
denser pump control  
is configured.)  
Condenser and cooler  
pumps shut off. Chiller  
shutdown without  
going through pump-  
down.  
Manual  
Failure of condenser  
pump or controls.  
Wiring error.  
Interlock Opened During  
Normal Operation  
Alarm  
Condenser Pump  
Interlock Closed When  
Pump is Off  
If configured for con-  
denser pump interlock  
condenser pump con-  
trol, and the flow  
switch is closed  
when pump relay is off.  
Chiller is not allowed to  
start.  
Manual  
Failure of condenser  
pump relays or inter-  
locks, welded  
contacts.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 38 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
Strainer Service  
Countdown (S.T.DN)  
Strainer Blowdown  
Scheduled  
Maintenance Due  
Routine strainer  
maintenance  
required  
expired. Complete strainer  
T302  
Alert  
None  
Automatic  
blowdown and enter 'YES'  
for Strainer Maintenance  
Done (S.T.MN) item.  
Current Sensor Board  
A1 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor A1 shut  
down  
CSB failure.  
CSB failure.  
CSB failure.  
T500  
T501  
Alert  
Alert  
Automatic  
Automatic  
Current Sensor Board  
A2 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor A2 shut  
down  
Current Sensor Board  
A3 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor A3 shut  
down  
T502  
T950  
Alert  
Alert  
Automatic  
Automatic  
Loss of Communication  
with Water System  
Manager  
No communications have  
been received by the MBB  
within 5 minutes of last  
transmission  
WSM forces removed.  
Chiller runs under own  
control  
Failed module, wiring  
error, failed  
transformer, loose  
connection plug,  
wrong address  
T951  
Alert  
Loss of Communication  
with Chillervisor System  
Manager  
No communications have  
been received by the MBB  
within 5 minutes of last  
transmission  
CSM forces removed.  
Chiller runs under own  
control  
Automatic  
Failed module, wiring  
error, failed  
transformer, loose  
connection plug,  
wrong address  
LEGEND  
CCN  
Carrier Comfort Network  
Current Sensor Board  
CSB  
CSM  
CXB  
Chiller System Manager  
Compressor Expansion Board  
EEPROM  
EMM  
EWT  
EXV  
Electronic Eraseable Programmable Read Only Memory  
Energy Management Module  
Entering Fluid Temperature  
Electronic Expansion Valve  
Hydronic System Manager  
Leaving Chilled Water  
HSM  
LCW  
LWT  
Leaving Fluid Temperature  
Main Base Board  
MBB  
OAT  
Outdoor-Air Temperature  
RGT  
Return Gas Thermistor  
WSM  
Water System Manager  
COMPRESSOR FAILURE ALERTS  
To check out alerts T051-T053:  
A048 (Circuit A Compressor Availability Alarm) — This  
alarm occurs when two compressors are unavailable to run on  
a 3 compressor circuit. The control ensures proper oil return by  
ensuring a circuit does not operate with one compressor for  
longer than one hour of cumulative run time.  
1. Turn on the compressor in question using Service Test  
mode. If the compressor does not start, then most likely  
the problem is one of the following: HPS open, open in-  
ternal protection, circuit breaker trip, incorrect safety wir-  
ing, or incorrect compressor wiring.  
T051, T052, T053 (Circuit A Compresser Failures) — Alert  
codes 051, 052, and 053 are for compressors A1, A2, and A3  
respectively. These alerts occur when the current sensor (CS)  
does not detect compressor current during compressor opera-  
tion. When this occurs, the control turns off the compressor.  
If the current sensor board reads OFF while the compressor  
relay has been commanded ON, an alert is generated.  
2. If the compressor does start, verify it is rotating in the cor-  
rect direction.  
IMPORTANT: Prolonged operation in the wrong direction  
can damage the compressor. Correct rotation can be veri-  
fied by a gage set and looking for a differential pressure  
rise on start-up.  
POSSIBLE CAUSES  
IMPORTANT: If the CS is always detecting current, verify  
that the compressor is on. If the compressor is on, check  
the contactor and the relay on the MBB. If the compressor  
is off and there is no current, verify the CSB wiring and  
replace if necessary.  
Compressor Overload — Either the compressor internal over-  
load protector is open or the external overload protector (Kri-  
wan module) has activated. The external overload protector  
modules are mounted in the compressor wiring junction box.  
Temperature sensors embedded in the compressor motor wind-  
ings are the inputs to the module. The module is powered with  
24 vac from the units main control box. The module output is a  
normally closed contact that is wired in series with the com-  
pressor contactor coil. In a compressor motor overload condi-  
tion, contact opens, deenergizing the compressor contactor.  
IMPORTANT: Return to Normal mode and observe com-  
pressor operation to verify that compressor current sensor  
is working.  
COMPRESSOR STUCK ON FAILURE ALARMS  
Low Refrigerant Charge — If the compressor operates for an  
extended period of time with low refrigerant charge, the com-  
pressor ASTP device will open, which will cause the compres-  
sor to trip on its overload protection device.  
Circuit A A051, A052, A053 — Alarm codes 051, 052, and  
053 are for compressors A1, A2, and A3. These alarms occur  
when the CSB detects current when the compressor should be  
off. When this occurs, the control turns off the compressor.  
Circuit Breaker Trip — The compressors are protected from  
short circuit by a breaker in the control box.  
Wiring Error — A wiring error might not allow the compres-  
sor to start.  
If the current sensor board reads ON while the compressor  
relay has been commanded OFF for a period of 4 continuous  
seconds, an alarm is generated. These alarms are only moni-  
tored for a period of 10 seconds after the compressor relay has  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
been commanded OFF. This is done to facilitate a service tech-  
nician forcing a relay to test a compressor.  
In addition, if a compressor stuck failure occurs and the cur-  
rent sensor board reports the compressor and the request off,  
certain diagnostics will take place as follows:  
leaving water for 5 minutes. This alarm will occur if either the  
suction pressure transducer reading, which is used to calculate  
SST, or cooler leaving water is incorrect. Potential causes for  
this alarm are loose wiring connection, sensor not located in  
well or bad Schrader fitting. Reset is manual.  
T079 (Dual Chiller Thermistor Failure) — This alert occurs  
when the dual chiller temperature sensor is outside its range of  
–40 to 240 F. Failure of this thermistor will disable Dual Chill-  
er operation and return to stand-alone operation. The unit must  
be configured for Dual Chiller operation for this alert to occur.  
The cause of the alert is usually a faulty thermistor, a shorted or  
open thermistor caused by a wiring error, or a loose connection.  
Reset is automatic.  
1. If any of the compressors are diagnosed as stuck on and  
the current sensor board is on and the request is off, the  
control will command the condenser fans to maintain  
normal head pressure.  
2. The control will shut-off all other compressors.  
The possible causes include welded contactor or frozen  
compressor relay on the MBB.  
To check out alarms A051 to A053:  
A090 (Circuit A Discharge Pressure Transducer Failure) —  
This alarm occurs when the pressure is outside the range of 0.0  
to 667.0 psig. A circuit cannot run when this alarm is active.  
Use the scrolling marquee to reset the alarm. The cause of the  
alarm is usually a faulty transducer, faulty 5-v power supply, or  
a loose connection.  
1. Place the unit in Service Test mode. All compressors  
should be off.  
2. Verify that there is not 24-v at the contactor coil. If there  
is 24 v at the contactor, check relay on MBB and wiring.  
3. Check for welded contactor.  
4. Verify CSB wiring.  
5. Return to Normal mode and observe compressor opera-  
tion to verify that compressor current sensor is working  
and condenser fans are energized.  
A092 (Circuit A Suction Pressure Transducer Failure)  
This alarm occurs when the pressure is outside the range of 0.0  
to 420.0 psig. A circuit cannot run when this alarm is active.  
Use the scrolling marquee to reset the alarm. The cause of the  
alarm is usually a faulty transducer, faulty 5-v power supply, or  
a loose connection.  
A060 (Cooler Leaving Fluid Thermistor Failure)  
The  
T094 (Discharge Gas Thermistor Failure) — This alert oc-  
curs for units which have the digital compressor installed on  
circuit A. If discharge gas temperature is open or shorted, the  
circuit will be shut off. The alert will reset itself when discharge  
temperature is less than 250 F (121.1 C). The cause of the alert  
is usually low refrigerant charge or a faulty thermistor.  
A110 (Circuit A Loss of Charge) — This alarm occurs when  
the compressor is OFF and the discharge pressure is less than  
26 psig.  
sensor reading is outside the range of –40 to 245 F (–40 to  
118 C) then the alarm will occur. The cause of the alarm is usu-  
ally a faulty thermistor, a shorted or open thermistor caused by  
a wiring error, or a loose connection. Failure of this thermistor  
will shut down the entire unit.  
A061 (Cooler Entering Thermistor Failure) — If the sensor  
reading is outside the range of –40 to 240 F (–40 to116 C) then  
the alarm will occur. The cause of the alarm is usually a faulty  
thermistor, a shorted or open thermistor caused by a wiring er-  
ror, or a loose connection. Failure of this thermistor will shut  
down the entire unit.  
T062 (Condenser Leaving Fluid Thermistor Failure) — The  
sensor reading is outside the range of –40 to 245 F (–40 to  
118 C) then the alert will occur. The cause of the alert is usually  
a faulty thermistor, a shorted or open thermistor caused by a  
wiring error, or a loose connection. Failure of this thermistor  
will send out an alert only.  
T063 (Condenser Entering Thermistor Failure) — If the sen-  
sor reading is outside the range of –40 to 240 F (–40 to116 C)  
then the alert will occur. The cause of the alert is usually a  
faulty thermistor, a shorted or open thermistor caused by a wir-  
ing error, or a loose connection.Failure of this thermistor will  
send out an alert only.  
T068 (Circuit A Compressor Return Gas Temperature  
Thermistor Failure) — This alert occurs if the RGT is config-  
ured and the compressor return gas temperature sensor is out-  
side the range of –40 to 240 F (–40 to 116 C). Failure of this  
thermistor will shut down the appropriate circuit.  
A112 (Circuit A High Saturated Suction Temperature)  
Alarm code 112 occurs when compressors in a circuit have  
been running for at least 5 minutes and the circuit saturated  
suction temperature is greater than 70 F (21.1 C). The high sat-  
urated suction alarm is generated and the circuit is shut down.  
A114 (Circuit A Low Superheat) — Alarm code 114 occurs  
when the superheat of a circuit is less than 5 F (2.8 C) for 5  
continuous minutes. The low superheat alarm is generated and  
the circuit is shut down. The RGT sensor must be installed.  
A122 (Circuit A, High Pressure Switch Failure) — The  
high pressure switch is wired in series with the compressor  
contactor coils of each compressor on the circuit to disable  
compressor operation immediately upon a high discharge pres-  
sure condition. The normally closed contacts in the switches  
are calibrated to open at 650 ± 10 psig which corresponds to a  
saturated condensing temperature of 155.6 ± 1.3 F. The pres-  
sure switches will automatically reset when the discharge pres-  
sure is reduced to 500 ± 15 psig which corresponds to a saturat-  
ed condensing temperature of 134.1 ± 2.4 F.  
The output of the high pressure switch is wired to inputs on  
the MBB to provide the control with an indication of a high  
pressure switch trip. This alert could occur when compressors  
are off if the wiring to the switch is broken or the switch has  
failed open.  
T073 (Outside Air Temperature Thermistor Failure) — This  
alert occurs when the outside air temperature sensor is outside  
the range of –40 to 240 F (–40 to 116 C). Failure of this therm-  
istor will disable any elements of the control which requires its  
use. The OAT must be configured.  
If the high pressure switch trips on a circuit with compres-  
sors commanded on, the discharge pressure is recorded. If the  
recorded discharge pressure is between 630 to 660 psig (satu-  
rated condensing temperature between 153.0 and 156.9 F), and  
is also less than the value recorded on any previous high pres-  
sure switch trip, the upper horizontal portion of the compressor  
operating envelope (see Fig. 12) is lowered 0.4 F (3 psig). The  
control will not allow the compressor operating envelope to be  
lowered below 153.0 F (630 psig).  
T074 (Space Temperature Thermistor Failure) — This alert  
occurs when the space temperature sensor is outside the range  
of –40 to 245 F (–40 to 118 C). Failure of this thermistor will  
disable any elements of the control which requires its use. The  
cause of the alert is usually a faulty thermistor in the T55, or  
T58 device, a shorted or open thermistor caused by a wiring er-  
ror, or a loose connection. The SPT must be configured.  
A077 (Circuit Saturated Suction Temperature Exceeds  
Cooler Leaving Water Temperature) — This alarm occurs  
when the saturated suction temperature (SST) is greater than  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This is done to make a rough calibration of the high pres-  
sure switch trip point. In most cases this allows the control to  
detect a high head pressure condition prior to reaching the high  
pressure switch trip point.  
When the trip occurs, all mechanical cooling on the circuit  
is shut down for 15 minutes. After 15 minutes, the circuit is al-  
lowed to restart.  
A126 (Circuit A High Head Pressure) — This alarm occurs  
when the appropriate saturated condensing temperature is  
greater than the operating envelope shown in Fig 12. Prior to  
the alarm, the control will shut down one compressor on a cir-  
cuit if that circuit's saturated condensing temperature is greater  
than the maximum SCT minus 5° F (2.7° C). If SCT continues  
to rise to greater than the maximum SCT, the alarm will occur  
and the circuit's remaining compressor will shut down. The  
cause of the alarm is usually an overcharged system, high out-  
door ambient temperature coupled with dirty outdoor coil  
(30MPA only), plugged filter drier, a faulty high-pressure  
switch, or loss of condenser water flow.  
• Invalid unit size has been entered.  
• Unit configuration set to invalid type.  
A152 (Unit Down Due to Failure) — Reset is automatic  
when all alarms are cleared. This alarm indicates the unit is at  
0% capacity.  
T153 (Real Time Clock Hardware Failure) — A problem  
has been detected with MBB real time clock hardware. Try re-  
setting the power and check the indicator lights. If the alarm  
continues, the board should be replaced.  
A154 (Serial EEPROM Hardware Failure) — A problem  
has been detected with the EEPROM on the MBB. Try  
resetting the power and check the indicator lights. If the alarm  
continues, the board should be replaced.  
T155 (Serial EEPROM Storage Failure Error) — A problem  
has been detected with the EEPROM storage on the MBB. Try  
resetting the power and check the indicator lights. If the alert  
continues, the board should be replaced.  
A156 (Critical Serial EEPROM Storage Failure Error) — A  
problem has been detected with the EEPROM storage on the  
MBB. Try resetting the power and check the indicator lights. If  
the alarm continues, the board should be replaced.  
A140 (Reverse Rotation Detected) — A test is made once, on  
power up, for suction pressure change on the first activated cir-  
cuit. The unit control determines failure as follows:  
A157 (A/D Hardware Failure) — A problem has been detect-  
ed with A/D conversion on the boards. Try resetting the power  
and check the indicator lights. If the alarm continues, the board  
should be replaced.  
T173 (Energy Management Module Communication Fail-  
ure) — This alert indicates that there are communications  
problems with the energy management. All functions per-  
formed by the EMM will stop, which can include demand lim-  
it, reset and capacity input. The alert will automatically reset.  
T174 (4 to 20 mA Cooling Set point Input Failure) — This  
alert indicates a problem has been detected with cooling set  
point 4 to 20 mA input. The input value is either less than 2 mA  
or greater than 22 mA.  
T176 (4 to 20 mA Reset Input Failure) — This alert indi-  
cates a problem has been detected with reset 4 to 20 mA input.  
The input value is either less than 2 mA or greater than 22 mA.  
The reset function will be disabled when this occurs.  
1. The suction pressure is sampled 5 seconds before the  
compressor is brought on, right when the compressor is  
brought on and 5 seconds afterwards.  
2. The rate of suction pressure change from 5 seconds be-  
fore the compressor is brought on to when the compres-  
sor is brought on is calculated.  
3. The rate of suction pressure change from when the  
compressor is brought on to 5 seconds afterwards is  
calculated.  
4. With the above information, the test for reverse rotation is  
made. If the suction pressure change 5 seconds after com-  
pression is greater than the suction pressure change 5 sec-  
onds before compression – 1.25, then there is a reverse  
rotation error.  
This alarm will disable mechanical cooling and will require  
manual reset. This alarm may be disabled once the reverse ro-  
tation check has been verified by setting REV.R = Yes.  
A150 (Unit is in Emergency Stop) — If the CCN emergency  
stop command is received, the alarm is generated and the unit  
will be immediately stopped.  
If the CCN point name "EMSTOP" in the system table is set  
to emergency stop, the unit will shut down immediately and  
broadcast an alarm back to the CCN, indicating that the unit is  
down. This alarm will clear when the variable is set back to  
"enable."  
A151 (Illegal Configuration) — An A151 alarm indicates an  
invalid configuration has been entered. The following are ille-  
gal configurations.  
T177 (4 to 20 mA Demand Limit Input Failure)  
This  
alert indicates a problem has been detected with demand limit  
4 to 20 mA input. The input value is either less than 2 mA or  
greater than 22 mA. The reset function will be disabled when  
this occurs.  
T500, T501, T502 (Current Sensor Board Failure — A xx  
Circuit A — Alert codes 500, 501, and 502 are for compres-  
sors A1, A2, and A3 respectively. These alerts occur when the  
output of the CSB is a constant high value. These alerts reset  
automatically. If the problem cannot be resolved, the CSB must  
be replaced.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES  
Run Status Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
AUTO VIEW OF RUN STATUS  
Entering Fluid Temp  
Leaving Fluid Temp  
Active Setpoint  
CCN POINT  
COMMENT  
EWT  
LWT  
xxx.x ºF  
xxx.x ºF  
xxx.x ºF  
xxx.x ºF  
xxx  
EWT  
LWT  
SP  
SETP  
CTPT  
LOD.F  
STAT  
OCC  
Control Point  
Load/Unload Factor  
Control Mode  
Occupied  
Override Modes in  
Effect  
CTRL_PNT  
SMZ  
STAT  
OCC  
NO/YES  
NO/YES  
VIEW  
MODE  
MODE  
CAP  
STGE  
ALRM  
TIME  
xxx  
x
xxx  
xx.xx  
Percent Total Capacity  
Requested Stage  
Current Alarms & Alerts  
Time of Day  
CAP_T  
STAGE  
ALRMALRT  
TIMECOPY  
00:00-23:59  
1 - 12 (1 = January,  
2 = February, etc.)  
MNTH  
xx  
Month of Year  
MOY  
DATE  
YEAR  
xx  
xx  
Day of Month  
Year of Century  
DOM  
YOCDISP  
01-31  
UNIT RUN HOUR AND START  
Machine Operating  
Hours  
Machine Starts  
Cooler Pump Run  
Hours  
HRS.U  
STR.U  
HR.P1  
xxxx HRS  
xxxx  
HR_MACH  
CY_MACH  
HR_CPUMP  
0 to 999999  
0 to 1000000  
0 to 999999.9  
RUN  
xxxx HRS  
Condenser Pump Run  
Hours  
HR.P2  
xxxx HRS  
HR_DPUMP  
0 to 999999.9  
CIRC AND COMP RUN HOURS  
Compressor A1 Run  
Hours  
Compressor A2 Run  
Hours  
Compressor A3 Run  
Hours  
HR.A1  
HR.A2  
HR.A3  
xxxx HRS  
xxxx HRS  
xxxx HRS  
HOURS_A1  
HOURS_A2  
HOURS_A3  
0 to 999999  
0 to 999999  
0 to 999999  
HOUR  
STRT  
COMPRESSOR STARTS  
Compressor A1 Starts  
Compressor A2 Starts  
ST.A1  
ST.A2  
ST.A3  
xxxx  
xxxx  
xxxx  
CY_A1  
CY_A2  
CY_A3  
0 to 999999  
0 to 999999  
0 to 999999  
Compressor A3 Starts  
PREVENTIVE MAINTENANCE  
STRN  
SI.ST  
STRAINER MAINTENANCE  
xxxx HRS  
xxxx HRS  
NO/YES  
Strainer Srvc Interval  
Strainer Srvc Count-  
down  
SI_STRNR  
ST_CDOWN  
ST_MAINT  
0 to 65535  
0 to 65535  
S.T.DN  
S.T.MN  
ST.DT  
Strainer Maint. Done  
PM  
STRAINER MAINT. DATES  
S.T.M0  
S.T.M1  
S.T.M2  
S.T.M3  
S.T.M4  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
SOFTWARE VERSION NUMBERS  
AUX  
MBB  
CESR131333-xx-xx  
CESR131279-xx-xx  
CESR131174-xx-xx  
CESR131171-xx-xx  
CESR130227-xx-xx  
VERS  
EMM  
MARQ  
NAVI  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Service Test Mode and Sub-Mode Directory  
SUB-MODE  
TEST  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
CCN POINT  
COMMENT  
To enable Service Test mode, move  
Enable/Off/Remote contact switch  
to  
ON/OFF  
Service Test Mode  
MAN_CTRL  
OFF. Change TEST to ON.  
Move switch to ENABLE  
OUTPUTS AND PUMPS  
CLR.P  
CND.P  
UL.TM  
CC.H  
CW.VO  
CW.VC  
LL.SV  
RMT.A  
OFF/ON  
OFF/ON  
xx  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
Cooler Pump Relay  
Condenser Pump  
Comp A1 Unload Time  
Crankcase Heater  
Condenser Valve Open  
Condenser Valve Close  
Liquid Line Solenoid  
Remote Alarm Relay  
CIRCUIT A COMPRESSOR TST  
Compressor A1 Relay  
Comp A1 Unload Time  
Compressor A2 Relay  
Compressor A3 Relay  
Minimum Load Valve Relay  
S_CLPMP  
S_CNDPMP  
S_A1ULTM  
S_CCH  
S_CWVO  
S_CWVC  
S_LLSV  
0 to 15  
OUTS  
CMPA  
S_ALM  
CC.A1  
UL.TM  
CC.A2  
CC.A3  
MLV  
OFF/ON  
xx  
OFF/ON  
OFF/ON  
OFF/ON  
S_A1_RLY  
S_A1ULTM  
S_A2_RLY  
S_A3_RLY  
S_MLV  
0 to 15  
Temperature Mode and Sub-Mode Directory  
SUB-MODE  
UNIT  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
CCN POINT  
ENT AND LEAVE UNIT TEMPS  
CEWT  
CLWT  
CDET  
CDLT  
OAT  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
Cooler Entering Fluid  
Cooler Leaving Fluid  
Condenser Entering Fluid  
Condenser Leaving Fluid  
Outside Air Temperature  
Space Temperature  
COOL_EWT  
COOL_LWT  
COND_EWT  
COND_LWT  
OAT  
SPT  
DLWT  
SPT  
DUAL_LWT  
Lead/Lag Leaving Fluid  
TEMPERATURES CIRCUIT A  
SCT.A  
SST.A  
RGT.A  
D.GAS  
SH.A  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x ΔF  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Discharge Gas Temp  
TMP_SCTA  
TMP_SSTA  
TMP_RGTA  
DISGAS  
CIR.A  
Suction Superheat Temp  
SH_A  
Pressures Mode and Sub-Mode Directory  
SUB-MODE  
PRC.A  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
CCN POINT  
PRESSURES CIRCUIT A  
xxx.x PSIG  
xxx.x PSIG  
DP.A  
SP.A  
Discharge Pressure  
Suction Pressure  
DP_A  
SP_A  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Set Points Mode and Sub-Mode Directory  
SUB-MODE  
COOL  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COOLING SETPOINTS  
Cooling Setpoint 1  
RANGE  
CCN POINT  
CSP.1  
CSP.2  
CSP.3  
xxx.x °F  
xxx.x °F  
xxx.x °F  
–20 to 70  
–20 to 70  
–20 to 32  
CSP1  
CSP2  
CSP3  
Cooling Setpoint 2  
ICE Setpoint  
HEAD PRESSURE SETPOINTS  
Head Setpoint  
BRINE FREEZE SETPOINT  
Brine Freeze Point  
HEAD  
FRZ  
H.DP  
xxx.x °F  
xx.x °F  
85 to 120  
–20 to 34  
HSP  
BR.FZ  
BRN_FRZ  
Inputs Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
GENERAL INPUTS  
Start/Stop Switch  
CCN POINT  
STST  
FLOW  
CD.FL  
DLS1  
DLS2  
ICED  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
START  
Cooler Flow Switch  
Condenser Flow Switch  
Demand Limit Switch 1  
Demand Limit Switch 2  
Ice Done  
COOLFLOW  
CONDFLOW  
DMD_SW1  
DMD_SW2  
ICE_DONE  
DUAL_IN  
GEN.I  
DUAL  
Dual Setpoint Switch  
CIRCUIT INPUTS  
FKA1  
FKA2  
FKA3  
HPS.A  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
Compressor A1 Feedback  
Compressor A2 Feedback  
Compressor A3 Feedback  
High Pressure Switch A  
K_A1_FBK  
K_A2_FBK  
K_A3_FBK  
HPSA  
CRCT  
4-20  
4-20 MA INPUTS  
DMND  
RSET  
CSP  
xx.x  
xx.x  
xx.x  
4-20 ma Demand Signal  
4-20 ma Reset Signal  
4-20 ma Cooling Setpoint  
LMT_MA  
RST_MA  
CSP_IN  
Outputs Mode and Sub-Mode Directory  
SUB-MODE  
GEN.O  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
CCN POINT  
GENERAL OUTPUTS  
C.LWP  
C.DWP  
ALRM  
CDWO  
CDWC  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
Cooler Pump Relay  
Condenser Pump  
Alarm State  
Condenser Valve Open  
Condenser Valve Close  
COOLPUMP  
CONDPUMP  
ALM  
COND_WVO  
COND_WVC  
OUTPUTS CIRCUIT A  
CC.A1  
D.SOL  
CC.A2  
CC.A3  
CCH  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
Compressor A1 Relay  
Digital Scroll Solenoid  
Compressor A2 Relay  
Compressor A3 Relay  
Crankcase Heater Relay  
Liquid Line Solenoid  
K_A1_RLY  
DISCRSOL  
K_A2_RLY  
K_A3_RLY  
CCH_RLY  
LLSV_A  
CIR.A  
LLSV  
MLV.R  
Minimum Load Valve Relay  
MLV_RLY  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory  
SUB-MODE  
DISP  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
DISPLAY CONFIGURATION  
Test Display LEDs  
CCN POINT  
COMMENT  
TEST  
OFF/ON  
OFF/ON  
DISPTEST  
DISPUNIT  
METR  
Metric Display  
Off = English On = Metric  
Default: 0  
0 = English  
1 = Espanol  
2 = Francais  
3 = Portuguese  
LANG  
X
Language Selection  
LANGUAGE  
PAS.E  
PASS  
DSBL/ENBL  
XXXX  
Password Enable  
Service Password  
PASS_EBL  
PASSCOPY  
0 to 9999  
UNIT CONFIGURATION  
2=Water Cooled, 3=Split  
System  
TYPE  
X
Unit Type  
UNIT_TYP  
SIZE  
SZA.1  
SZA.2  
SZA.3  
A1.TY  
MAX.T  
XXX  
XX  
Unit Size  
SIZE  
10 to 100  
Compressor A1 Size  
Compressor A2 Size  
Compressor A3 Size  
Compressor A1 Digital?  
Maximum A1 Unload Time  
UNIT OPTIONS 1 HARDWARE  
Cooler Fluid  
SIZE_A1  
SIZE_A2  
SIZE_A3  
CPA1TYPE  
MAXULTME  
UNIT  
XX  
XX  
NO/YES  
XX  
0 to 15  
FLUD  
X
1 = Water  
2 = Medium Temperature  
Brine  
FLUIDTYP  
MLV.S  
RG.EN  
OAT.E  
D.G.EN  
CSB.E  
CPC  
NO/YES  
DSBL/ENBL  
DSBL/ENBL  
DSBL/ENBL  
DSBL/ENBL  
OFF/ON  
Minimum Load Vlv Select  
Return Gas Sensor Enable  
Enable OAT Sensor  
Dischrge Gas Temp Enable  
CSB Boards Enable  
MLV_FLG  
RGT_ENA  
OAT_ENA  
DISGASEN  
CSB_ENA  
CPC  
OPT1  
Cooler Pump Control  
PM.DY  
DPME  
DFLS  
XX MIN  
Cooler Pump Shutdown Dly  
PUMP_DLY  
0 to 10  
0 to 2  
X
Enable Condenser Pump  
Enable Cond Flow Switch  
Enable Cond Wtr Sensors  
CONDPMPE  
CONDFLSW  
CONDWTRS  
DSBL/ENBL  
DSBL/ENBL  
CDWS  
UNIT OPTIONS 2 CONTROLS  
0=Switch, 1=Occupancy,  
2=Occupancy, 3=CCN  
CTRL  
X
Control Method  
CONTROL  
OPT2  
CCN  
LCWT  
DELY  
ICE.M  
XX  
XX  
High LCW Alert Limit  
Minutes Off Time  
LCW_LMT  
DELAY  
ICE_CNFG  
2 to 60  
0 to 15  
DSBL/ENBL  
Ice Mode Enable  
CCN NETWORK CONFIGS  
CCN Address  
CCNA  
CCNB  
XXX  
XXX  
CCNADD  
CCNBUS  
1 to 239  
0 to 239  
1 = 2400  
2 = 4800  
3 = 9600  
4 =19,200  
5 =38,400  
CCN Bus Number  
BAUD  
X
CCN Baud Rate  
CCNBAUDD  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory (cont)  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
RESET COOL TEMP  
CCN POINT  
COMMENT  
0 = No Reset  
1 = 4 to 20 mA Input  
2 = Outdoor Air Tempera-  
ture  
CRST  
X
Cooling Reset Type  
CRST_TYP  
3 = Return Fluid  
4 = Space Temperature  
MA.DG  
RM.NO  
RM.F  
XX.XΔF  
XXX.X °F  
XXX.X °F  
XX.X °F  
XXX.XΔF  
XXX.XΔF  
XX.X °F  
4-20 - Degrees Reset  
Remote - No Reset Temp  
Remote - Full Reset Temp  
Remote - Degrees Reset  
Return - No Reset Temp  
Return - Full Reset Temp  
Return - Degrees Reset  
420_DEG  
REM_NO  
REM_FULL  
REM_DEG  
RTN_NO  
-30 to 30  
0 to125  
0 to125  
-30 to 30  
0 to 30  
RM.DG  
RT.NO  
RT.F  
RTN_FULL  
RTN_DEG  
0 to 10  
-30 to 30  
RT.DG  
0 = None  
1 = Switch  
2 - 4 to 20 mA Input  
3 = CCN Loadshed  
DMDC  
X
Demand Limit Select  
DMD_CTRL  
RSET  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
XXX%  
XXX  
Demand Limit at 20 mA  
Loadshed Group Number  
Loadshed Demand Delta  
Maximum Loadshed Time  
Demand Limit Switch 1  
Demand Limit Switch 2  
DMT20MA  
SHED_NUM  
SHED_DEL  
SHED_TIM  
DLSWSP1  
DLSWSP2  
0 to 100  
0 to 99  
XXX%  
XXX  
0 to 60  
0 to 120  
0 to 100  
0 to 100  
XXX%  
XXX%  
LLEN  
Lead/Lag Chiller Enable  
LL_ENA  
DSBL/ENBL  
MSSL  
SLVA  
SLVE/MAST  
XXX  
Master/Slave Select  
Slave Address  
MS_SEL  
SLV_ADDR  
0 to 239  
0 = Master Leads  
1 = Slave Leads  
2 = Automatic  
LLBL  
X
Lead/Lag Balance Select  
LL_BAL  
LLBD  
LLDY  
PARA  
XXX  
XXX  
Lead/Lag Balance Delta  
Lag Start Delay  
LL_BAL_D  
LL_DELAY  
PARALLEL  
40 to 400 hours  
0 to 30 minutes  
NO/YES  
Parallel Configuration  
SETPOINT AND RAMP LOAD  
0 = Single  
1 = Dual Switch  
2 = Dual CCN Occupied  
3 = 4 to 20 mA Input  
CLSP  
X
Cooling Set Point Select  
CLSP_TYP  
SLCT  
RL.S  
DSBL/ENBL  
X.X  
Ramp Load Select  
RAMP_EBL  
CRAMP  
0.2 to 2  
CRMP  
Cooling Ramp Loading  
SCHD  
Z.GN  
XX  
Schedule Number  
Deadband Multiplier  
SCHEDNUM  
Z_GAIN  
0 to 99  
1 to 4  
X.X  
SERVICE CONFIGURATION  
Enable Compressor A1  
Enable Compressor A2  
Enable Compressor A3  
Reverse Rotation Enable  
BROADCAST CONFIGURATION  
CCN Time/Date Broadcast  
CCN OAT Broadcast  
EN.A1  
EN.A2  
EN.A3  
REV.R  
DSBL/ENBL  
DSBL/ENBL  
DSBL/ENBL  
DSBL/ENBL  
ENABLEA1  
ENABLEA2  
ENABLEA3  
REVR_ENA  
SERV  
BCST  
T.D.BC  
OAT.B  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
CCNBC  
OATBC  
GSBC  
G.S.BC  
BC.AK  
Global Schedule Broadcst  
CCN Broadcast Ack'er  
CCNBCACK  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory  
SUB-MODE  
TIME  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
TIME OF DAY  
Hour and Minute  
CCN POINT  
COMMENT  
HH.MM  
XX.XX  
TIME  
MONTH, DATE, DAY, AND YEAR  
1 to 12 (1 = January,  
2 = February, etc.)  
1 to 31  
1 - 7 (1 = Sunday,  
2 = Monday, etc.)  
MNTH  
DOM  
DAY  
XX  
XX  
Month of Year  
Day of Month  
Day of Week  
MOY  
DOM  
DATE  
X
DOWDISP  
YOCDISP  
YEAR  
XXXX  
Year of Century  
1999 to 2098  
DAYLIGHT SAVINGS TIME  
STR.M  
STR.W  
STR.D  
XX  
X
X
Month  
Week  
Day  
STARTM  
STARTW  
STARTD  
Default: 4 Range 1 to 12  
Default: 1 Range 1 to 5  
Default: 7 Range 1 to 7  
Default: 60 Range 0 to  
90  
Default: 10 Range 1 to  
12  
MIN.A  
STP.M  
XX  
XX  
Minutes to Add  
Month  
MINADD  
STOPM  
DST  
STP.W  
STP.D  
XX  
XX  
Week  
Day  
STOPW  
STOPD  
Default: 5 Range 1to 5  
Default: 7 Range 1 to 7  
Default: 60 Range 0 to  
90  
MIN.S  
XX  
Minutes to Subtract  
MINSUB  
HOL.L  
HD.01  
LOCAL HOLIDAY SCHEDULES  
HOLIDAY SCHEDULE 01  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON01  
HOLDAY01  
HOLLEN01  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 02  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON02  
HOLDAY02  
HOLLEN02  
0 to 12  
0 to 31  
0 to 99  
HD.02  
HD.03  
HD.04  
HD.05  
HD.06  
HD.07  
HD.08  
Duration (days)  
HOLIDAY SCHEDULE 03  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON03  
HOLDAY03  
HOLLEN03  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 04  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON04  
HOLDAY04  
HOLLEN04  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 05  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON05  
HOLDAY05  
HOLLEN05  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 06  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON06  
HOLDAY06  
HOLLEN06  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 07  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON07  
HOLDAY07  
HOLLEN07  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 08  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON08  
HOLDAY08  
HOLLEN08  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
HD.09  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
HOLIDAY SCHEDULE 09  
Holiday Start Month  
Start Day  
CCN POINT  
COMMENT  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON09  
HOLDAY09  
HOLLEN09  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 10  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON10  
HOLDAY10  
HOLLEN10  
0 to 12  
0 to 31  
0 to 99  
HD.10  
HD.11  
HD.12  
HD.13  
HD.14  
HD.15  
HD.16  
HD.17  
HD.18  
HD.19  
Duration (days)  
HOLIDAY SCHEDULE 11  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON11  
HOLDAY11  
HOLLEN11  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 12  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON12  
HOLDAY12  
HOLLEN12  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 13  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON13  
HOLDAY13  
HOLLEN13  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 14  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON14  
HOLDAY14  
HOLLEN14  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 15  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON15  
HOLDAY15  
HOLLEN15  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 16  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON16  
HOLDAY16  
HOLLEN16  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 17  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON17  
HOLDAY17  
HOLLEN17  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 18  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON18  
HOLDAY18  
HOLLEN18  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 19  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON19  
HOLDAY19  
HOLLEN19  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
HD.20  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
HOLIDAY SCHEDULE 20  
Holiday Start Month  
Start Day  
CCN POINT  
COMMENT  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON20  
HOLDAY20  
HOLLEN20  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 21  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON21  
HOLDAY21  
HOLLEN21  
0 to 12  
0 to 31  
0 to 99  
HD.21  
HD.22  
HD.23  
HD.24  
HD.25  
HD.26  
HD.27  
HD.28  
HD.29  
HD.30  
Duration (days)  
HOLIDAY SCHEDULE 22  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON22  
HOLDAY22  
HOLLEN22  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 23  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON23  
HOLDAY23  
HOLLEN23  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 24  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON24  
HOLDAY24  
HOLLEN24  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 25  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON25  
HOLDAY25  
HOLLEN25  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 26  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON26  
HOLDAY26  
HOLLEN26  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 27  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON27  
HOLDAY27  
HOLLEN27  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 28  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON28  
HOLDAY28  
HOLLEN28  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 29  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON29  
HOLDAY29  
HOLLEN29  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
HOLIDAY SCHEDULE 30  
Holiday Start Month  
Start Day  
MON  
DAY  
LEN  
XX  
XX  
XX  
HOLMON30  
HOLDAY30  
HOLLEN30  
0 to 12  
0 to 31  
0 to 99  
Duration (days)  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
SCH.N  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
Schedule Number 0  
CCN POINT  
SCHEDNUM  
COMMENT  
0 to 99  
SCH.L  
LOCAL OCCUPANCY SCHEDULE  
OCCUPANCY PERIOD 1  
Period Occupied Time  
OCC.1  
UNC.1  
XX:XX  
XX:XX  
PER1OCC  
PER1UNC  
Period Unoccupied  
Time  
MON.1  
TUE.1  
WED.1  
THU.1  
FRI.1  
SAT.1  
SUN.1  
HOL.1  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER1MON  
PER1TUE  
PER1WED  
PER1THU  
PER1FRI  
PER1SAT  
PER1SUN  
PER1HOL  
PER.1  
PER.2  
PER.3  
PER.4  
PER.5  
OCCUPANCY PERIOD 2  
Period Occupied Time  
OCC.2  
UNC.2  
XX:XX  
XX:XX  
PER2OCC  
PER2UNC  
Period Unoccupied  
Time  
MON.2  
TUE.2  
WED.2  
THU.2  
FRI.2  
SAT.2  
SUN.2  
HOL.2  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER2MON  
PER2TUE  
PER2WED  
PER2THU  
PER2FRI  
PER2SAT  
PER2SUN  
PER2HOL  
OCCUPANCY PERIOD 3  
Period Occupied Time  
OCC.3  
UNC.3  
XX:XX  
XX:XX  
PER3OCC  
PER3UNC  
Period Unoccupied  
Time  
MON.3  
TUE.3  
WED.3  
THU.3  
FRI.3  
SAT.3  
SUN.3  
HOL.3  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER3MON  
PER3TUE  
PER3WED  
PER3THU  
PER3FRI  
PER3SAT  
PER3SUN  
PER3HOL  
OCCUPANCY PERIOD 4  
Period Occupied Time  
OCC.4  
UNC.4  
XX:XX  
XX:XX  
PER4OCC  
PER4UNC  
Period Unoccupied  
Time  
MON.4  
TUE.4  
WED.4  
THU.4  
FRI.4  
SAT.4  
SUN.4  
HOL.4  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER4MON  
PER4TUE  
PER4WED  
PER4THU  
PER4FRI  
PER4SAT  
PER4SUN  
PER4HOL  
OCCUPANCY PERIOD 5  
Period Occupied Time  
OCC.5  
UNC.5  
XX:XX  
XX:XX  
PER5OCC  
PER5UNC  
Period Unoccupied  
Time  
MON.5  
TUE.5  
WED.5  
THU.5  
FRI.5  
SAT.5  
SUN.5  
HOL.5  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER5MON  
PER5TUE  
PER5WED  
PER5THU  
PER5FRI  
PER5SAT  
PER5SUN  
PER5HOL  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
OCCUPANCY PERIOD 6  
Period Occupied Time  
CCN POINT  
COMMENT  
OCC.6  
UNC.6  
XX:XX  
XX:XX  
PER6OCC  
PER6UNC  
Period Unoccupied  
Time  
MON.6  
TUE.6  
WED.6  
THU.6  
FRI.6  
SAT.6  
SUN.6  
HOL.6  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER6MON  
PER6TUE  
PER6WED  
PER6THU  
PER6FRI  
PER6SAT  
PER6SUN  
PER6HOL  
PER.6  
OCCUPANCY PERIOD 7  
Period Occupied Time  
OCC.7  
UNC.7  
XX:XX  
XX:XX  
PER7OCC  
PER7UNC  
Period Unoccupied  
Time  
MON.7  
TUE.7  
WED.7  
THU.7  
FRI.7  
SAT.7  
SUN.7  
HOL.7  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER7MON  
PER7TUE  
PER7WED  
PER7THU  
PER7FRI  
PER7SAT  
PER7SUN  
PER7HOL  
PER.7  
OCCUPANCY PERIOD 8  
Period Occupied Time  
OCC.8  
UNC.8  
XX:XX  
XX:XX  
PER8OCC  
PER8UNC  
Period Unoccupied  
Time  
MON.8  
TUE.8  
WED.8  
THU.8  
FRI.8  
SAT.8  
SUN.8  
HOL.8  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
NO/YES  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Saturday In Period  
Sunday In Period  
Holiday In Period  
PER8MON  
PER8TUE  
PER8WED  
PER8THU  
PER8FRI  
PER8SAT  
PER8SUN  
PER8HOL  
PER.8  
SCHEDULE OVERRIDE  
Timed Override Hours  
Override Time Limit  
Timed Override  
OVR.T  
OVR.L  
T.OVR  
X
X
OVR_EXT  
OTL  
TIMEOVER  
0 to 4 hours  
0 to 4 hours  
OVR  
NO/YES  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Operating Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
MODES CONTROLLING UNIT  
FSM controlling Chiller  
WSM controlling Chiller  
Master/Slave control  
Ramp Load Limited  
Timed Override in effect  
Low Cooler Suction TempA  
Slow Change Override  
Minimum OFF time active  
Dual Setpoint  
Temperature Reset  
Demand Limited  
Cooler Freeze Protection  
Low Temperature Cooling  
High Temperature Cooling  
Making ICE  
CCN POINT  
COMMENT  
MD01  
MD02  
MD03  
MD05  
MD06  
MD07  
MD09  
MD10  
MD13  
MD14  
MD15  
MD16  
MD17  
MD18  
MD19  
MD20  
MD21  
MD23  
MD24  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
MODE_1  
MODE_2  
MODE_3  
MODE_5  
MODE_6  
MODE_7  
MODE_9  
MODE_10  
MODE_13  
MODE_14  
MODE_15  
MODE_16  
MODE_17  
MODE_18  
MODE_19  
MODE_20  
MODE_21  
MODE_23  
MODE_24  
MODE  
Storing ICE  
High SCT Circuit A  
Minimum Comp. On Time  
Pump Off Delay Time  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — LOCAL DISPLAY TABLES (cont)  
Alarms Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
CCN POINT  
COMMENT  
CURRENTLY ACTIVE ALARMS  
AA01  
AA02  
AA03  
AA04  
AA05  
AA06  
AA07  
AA08  
AA09  
AA10  
AA11  
AA12  
AA13  
AA14  
AA15  
AA16  
AA17  
AA18  
AA19  
AA20  
AA21  
AA22  
AA23  
AA24  
AA25  
AXXX  
TXXX  
PXXX  
Alarms are shown as  
AXXX  
Alerts are shown as TXXX  
CRNT  
Current Alarms 1-25  
RCRN  
NO/YES  
Reset All Current Alarms  
ALARM HISTORY  
ALRESET  
AL01  
AL02  
AL03  
AL04  
AL05  
AL06  
AL07  
AL08  
AL09  
AL10  
AL11  
AL12  
AL13  
AL14  
AL15  
AL16  
AL17  
AL18  
AL19  
AL20  
AXXX  
TXXX  
PXXX  
Alarms are shown as  
AXXX  
Alerts are shown as TXXX  
HIST  
Alarm History 1-20  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES  
CCN DISPLAY TABLES — A_UNIT (General Unit Parameters  
DESCRIPTION  
Control Mode  
Occupied  
CCN Chiller  
Alarm State  
Active Demand Limit  
Override Modes in Effect  
Percent Total Capacity  
Requested Stage  
Active Setpoint  
VALUE  
10-char ASCII  
No/Yes  
Stop/Start  
6-char ASCII  
NNN  
No/Yes  
NNN  
NN  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
Enable/EMStop  
5-char ASCII  
UNITS  
POINT NAME  
STAT  
OCC  
CHIL_S_S  
ALM  
DEM_LIM  
MODE  
CAP_T  
STAGE  
SP  
CTRL_PNT  
EWT  
LWT  
FORCIBLE  
N
N
Y
N
Y
N
N
N
N
Y
N
N
Y
N
%
%
degF  
degF  
degF  
degF  
Control Point  
Entering Fluid Temp  
Leaving Fluid Temp  
Emergency Stop  
Minutes Left for Start  
PUMPS  
EMSTOP  
MIN_LEFT  
Cooler Pump Relay  
Condenser Pump  
Cooler Flow Switch  
Off/On  
Off/On  
Off/On  
COOLPUMP  
CONDPUMP  
COOLFLOW  
N
N
N
CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters)  
DESCRIPTION  
CIRCUIT A ANALOG VALUES  
Percent Total Capacity  
Percent Available Cap.  
Discharge Pressure  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
NNN  
NNN  
%
%
CAPA_T  
CAPA_A  
DP_A  
SP_A  
HSP  
TMP_SCTA  
TMP_SSTA  
TMP_RGTA  
DISGAS  
SH_A  
N
N
N
N
N
N
N
N
N
N
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
PSIG  
PSIG  
degF  
degF  
degF  
degF  
degF  
deltaF  
Suction Pressure  
Head Setpoint  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Discharge Gas Temp  
Suction Superheat Temp  
CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs)  
DESCRIPTION  
CIRC. A DISCRETE OUTPUTS  
Compressor A1 Relay  
Compressor A2 Relay  
Compressor A3 Relay  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
Off/On  
K_A1_RLY  
K_A2_RLY  
K_A3_RLY  
MLV_RLY  
N
N
Off/On  
Off/On  
Off/On  
Minimum Load Valve Relay  
N
CIRC. A DISCRETE INPUTS  
Compressor A1 Feedback  
Compressor A2 Feedback  
Compressor A3 Feedback  
Off/On  
Off/On  
Off/On  
K_A1_FBK  
K_A2_FBK  
K_A3_FBK  
N
N
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN DISPLAY TABLES — OPTIONS (Unit Parameters)  
DESCRIPTION  
UNIT ANALOG VALUES  
Cooler Entering Fluid  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
NNN.n  
degF  
COOL_EWT  
COOL_LWT  
COND_EWT  
COND_LWT  
DUAL_LWT  
N
N
N
N
N
Cooler Leaving Fluid  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
degF  
degF  
degF  
degF  
Condenser Entering Fluid  
Condenser Leaving Fluid  
Lead/Lag Leaving Fluid  
TEMPERATURE RESET  
4-20 ma Reset Signal  
Outside Air Temperature  
Space Temperature  
NN.n  
NNN.n  
NNN.n  
milliAmps  
degF  
degF  
RST_MA  
OAT  
SPT  
N
Y
Y
DEMAND LIMIT  
4-20 ma Demand Signal  
Demand Limit Switch 1  
Demand Limit Switch 2  
CCN Loadshed Signal  
NN.n  
Off/On  
Off/On  
N
milliAmps  
LMT_MA  
N
N
N
N
DMD_SW1  
DMD_SW2  
DL_STAT  
MISCELLANEOUS  
Dual Setpoint Switch  
Cooler LWT Setpoint  
Ice Done  
Off/On  
NNN.n  
Off/On  
DUAL_IN  
LWT_SP  
ICE_DONE  
N
N
N
degF  
CCN MAINTENANCE TABLES — STRTHOUR  
DESCRIPTION  
Machine Operating Hours  
Machine Starts  
VALUE  
NNNNNN  
NNNNNN  
UNITS  
hours  
POINT NAME  
HR_MACH  
CY_MACH  
Compressor A1 Run Hours  
Compressor A2 Run Hours  
Compressor A3 Run Hours  
NNNNNN.n  
NNNNNN.n  
NNNNNN.n  
hours  
hours  
hours  
HR_A1  
HR_A2  
HR_A3  
Compressor A1 Starts  
Compressor A2 Starts  
Compressor A3 Starts  
NNNNNN  
NNNNNN  
NNNNNN  
CY_A1  
CY_A2  
CY_A3  
PUMP HOURS  
Cooler Pump Run Hours  
Condenser Pump Run Hours  
NNNNNN.n  
NNNNNN.n  
hours  
hours  
HR_CPUMP  
HR_DPUMP  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — CURRMODS  
DESCRIPTION  
CSM controlling Chiller  
VALUE  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
POINT NAME  
MODE_1  
MODE_2  
MODE_3  
MODE_5  
MODE_6  
MODE_7  
MODE_9  
MODE_10  
MODE_13  
MODE_14  
MODE_15  
MODE_16  
MODE_17  
MODE_18  
MODE_19  
MODE_20  
MODE_21  
MODE_23  
MODE_24  
MODE_25  
WSM controlling Chiller  
Master/Slave control  
Ramp Load Limited  
Timed Override in effect  
Low Cooler Suction TempA  
Slow Change Override  
Minimum OFF time active  
Dual Setpoint  
Temperature Reset  
Demand Limited  
Cooler Freeze Protection  
Low Temperature Cooling  
High Temperature Cooling  
Making ICE  
Storing ICE  
High SCT Circuit A  
Minimum Comp. On Time  
Pump Off Delay Time  
Low Sound Mode  
Off/On  
Off/On  
Off/On  
Off/On  
CCN MAINTENANCE TABLES — ALARMS  
DESCRIPTION  
Active Alarm #1  
Active Alarm #2  
Active Alarm #3  
Active Alarm #4  
Active Alarm #5  
Active Alarm #6  
Active Alarm #7  
Active Alarm #8  
Active Alarm #9  
Active Alarm #10  
Active Alarm #11  
Active Alarm #12  
Active Alarm #13  
Active Alarm #14  
Active Alarm #15  
Active Alarm #16  
Active Alarm #17  
Active Alarm #18  
Active Alarm #19  
Active Alarm #20  
Active Alarm #21  
Active Alarm #22  
Active Alarm #23  
Active Alarm #24  
Active Alarm #25  
VALUE  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
4-char ASCII  
POINT NAME  
ALARM01C  
ALARM02C  
ALARM03C  
ALARM04C  
ALARM05C  
ALARM06C  
ALARM07C  
ALARM08C  
ALARM09C  
ALARM10C  
ALARM11C  
ALARM12C  
ALARM13C  
ALARM14C  
ALARM15C  
ALARM16C  
ALARM17C  
ALARM18C  
ALARM19C  
ALARM20C  
ALARM21C  
ALARM22C  
ALARM23C  
ALARM24C  
ALARM25C  
CCN MAINTENANCE TABLES — VERSIONS  
DESCRIPTION  
VERSION  
CESR131333-  
CESR131279-  
CESR131174-  
CESR131171-  
CESR130227-  
VALUE  
AUX  
MBB  
EMM  
MARQUEE  
NAVIGATOR  
5-char ASCII  
5-char ASCII  
5-char ASCII  
5-char ASCII  
5-char ASCII  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — LOADFACT  
DESCRIPTION  
CAPACITY CONTROL  
Load/Unload Factor  
Control Point  
Entering Fluid Temp  
Leaving Fluid Temp  
VALUE  
UNITS  
POINT NAME  
SMZ  
CTRL_PNT  
EWT  
NNN  
NNN.n  
NNN.n  
NNN.n  
degF  
degF  
degF  
LWT  
Ramp Load Limited  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
MODE_5  
MODE_9  
MODE_16  
MODE_17  
MODE_18  
MODE_23  
Slow Change Override  
Cooler Freeze Protection  
Low Temperature Cooling  
High Temperature Cooling  
Minimum Comp. On Time  
CCN MAINTENANCE TABLES — LEARNFNS  
DESCRIPTION  
SCT Delta for Comp A1  
SCT Delta for Comp A2  
SCT Delta for Comp A3  
SAGP for Compressor A1  
SAGM for Compressor A1  
SAGP for Compressor A2  
SAGM for Compressor A2  
SAGP for Compressor A3  
SAGM for Compressor A3  
Reset short loop gain  
VALUE  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
Yes/No  
UNITS  
deltaF  
deltaF  
deltaF  
POINT NAME  
A1SCTDT  
A2SCTDT  
A3SCTDT  
SAGA1P  
SAGA1M  
SAGA2P  
SAGA2M  
SAGA3P  
SAGA3M  
RESET_GN  
CCN MAINTENANCE TABLES — PM-STRN  
DESCRIPTION  
Strainer Srvc Interval  
Strainer Srvc Countdown  
Strainer Maint. Done  
VALUE  
NNNNN  
NNNNN  
No/Yes  
UNITS  
hours  
hours  
POINT NAME  
SI_STRNR  
ST_CDOWN  
ST_MAINT  
Strainer Maint. Date  
Strainer Maint. Date  
Strainer Maint. Date  
Strainer Maint. Date  
Strainer Maint. Date  
15-char ASCII  
15-char ASCII  
15-char ASCII  
15-char ASCII  
15-char ASCII  
STRN_PM0  
STRN_PM1  
STRN_PM2  
STRN_PM3  
STRN_PM4  
CCN MAINTENANCE TABLES — TESTMODE  
DESCRIPTION  
Service Test Mode  
Compressor A1 Relay  
Compressor A2 Relay  
Compressor A3 Relay  
Cooler Pump Relay  
Condenser Pump  
Comp A1 Unload Time  
Remote Alarm Relay  
VALUE  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
NN  
UNITS  
POINT NAME  
NET_CTRL  
S_A1_RLY  
S_A2_RLY  
S_A3_RLY  
S_CLPMP  
S_CNDPMP  
S_A1ULTM  
S_ALM  
secs  
Off/On  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — RUNTEST  
DESCRIPTION  
Percent Total Capacity  
VALUE  
NNN  
UNITS  
POINT NAME  
CAPA_T  
%
Percent Available Cap.  
Discharge Pressure  
Suction Pressure  
NNN  
%
CAPA_A  
DP_A  
SP_A  
TMP_SCTA  
TMP_SSTA  
TMP_RGTA  
DISGAS  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
Off/On  
PSIG  
PSIG  
degF  
degF  
degF  
degF  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Discharge Gas Temp  
Suction Superheat Temp  
Compressor A1 Relay  
Compressor A2 Relay  
Compressor A3 Relay  
Minimum Load Valve Relay  
Compressor A1 Feedback  
Compressor A2 Feedback  
Compressor A3 Feedback  
deltaF  
SH_A  
K_A1_RLY  
K_A2_RLY  
K_A3_RLY  
MLV_RLY  
K_A1_FBK  
K_A2_FBK  
K_A3_FBK  
Outside Air Temperature  
Space Temperature  
Cooler Pump Relay  
Condenser Pump  
Cooler Entering Fluid  
Cooler Leaving Fluid  
Cooler Flow Switch  
NNN.n  
NNN.n  
Off/On  
Off/On  
NNN.n  
NNN.n  
Off/On  
degF  
degF  
OAT  
SPT  
COOLPUMP  
CONDPUMP  
COOL_EWT  
COOL_LWT  
COOLFLOW  
degF  
degF  
CCN MAINTENANCE TABLES — DUALCHIL  
DESCRIPTION  
Dual Chiller Link Good?  
Master Chiller Role  
Slave Chiller Role  
Lead Chiller Ctrl Point  
Lag Chiller Ctrl Point  
Control Point  
VALUE  
No/Yes  
12-char ASCII  
12-char ASCII  
NNN.n  
UNITS  
POINT NAME  
DC_LINK  
MC_ROLE  
SC_ROLE  
LEAD_CP  
LAG_CP  
degF  
degF  
degF  
NNN.n  
NNN.n  
CTRL_PNT  
Cool EnteringFluid-Slave  
Cool Leaving Fluid-Slave  
Cooler Entering Fluid  
Cooler Leaving Fluid  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
NNN.n  
degF  
degF  
degF  
degF  
degF  
COOLEWTS  
COOLLWTS  
COOL_EWT  
COOL_LWT  
DUAL_LWT  
Lead/Lag Leaving Fluid  
Percent Avail.Capacity  
Percent Avail.Cap.Slave  
NNN  
NNN  
%
%
CAP_A  
CAP_A_S  
Lag Start Delay Time  
Load/Unload Factor  
5-char ASCII  
NNN  
LAGDELAY  
SMZ  
Load/Unload Factor-Slave  
Lead SMZ Clear Commanded  
Lag SMZ Clear Commanded  
Lag Commanded Off?  
NNNN  
SMZSLAVE  
LEADSMZC  
LAG_SMZC  
LAG_OFF  
No/Yes  
No/Yes  
No/Yes  
Dual Chill Lead CapLimit  
Dual Chill Lag CapLimit  
NNN.n  
NNN.n  
%
%
DCLDCAPL  
DCLGCAPL  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN CONFIGURATION TABLES — UNIT (Unit Configuration)  
DESCRIPTION  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
UNIT_TYP  
SIZE  
SIZE_A1  
SIZE_A2  
SIZE_A3  
SH_SP  
Unit Type  
Unit Size  
N
NNN  
NNN  
NNN  
NNN  
NN.n  
tons  
tons  
tons  
tons  
deltaF  
Compressor A1 Size  
Compressor A2 Size  
Compressor A3 Size  
Suction Superheat Setpt  
Compressor A1 Digital?  
Maximum A1 Unload Time  
No/Yes  
NN  
CPA1TYPE  
MAXULTME  
secs  
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)  
DESCRIPTION  
Cooler Fluid  
Minimum Load Vlv Select  
Return Gas Sensor Enable  
Enable OAT Sensor  
Dischrge Gas Temp Enable  
CSB Boards Enable  
Reverse Rotation Enable  
Cooler Pump Control  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
FLUIDTYP  
MLV_FLG  
RGT_ENA  
OAT_ENA  
DISGASEN  
CSB_ENA  
REVR_ENA  
CPC  
N
No/Yes  
Dsable/Enable  
Dsable/Enable  
Dsable/Enable  
Dsable/Enable  
Dsable/Enable  
Off/On  
Cooler Pump Shutdown Dly  
EMM Module Installed  
Enable Condenser Pump  
Enable Cond Wtr Sensors  
Enable Cond Flow Switch  
NN  
No/Yes  
N
Dsable/Enable  
Dsable/Enable  
mins  
PUMP_DLY  
EMM_BRD  
CONDPMPE  
CONDWTRS  
CONDFLSW  
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)  
DESCRIPTION  
Control Method  
Loading Sequence Select  
Lead/Lag Circuit Select  
Cooling Setpoint Select  
Ramp Load Select  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
CONTROL  
SEQ_TYPE  
LEAD_TYP  
CLSP_TYP  
RAMP_EBL  
LCW_LMT  
DELAY  
N
N
N
N
Dsable/Enable  
NN.n  
NN  
High LCW Alert Limit  
Minutes off time  
deltaF  
mins  
Deadband Multiplier  
Ice Mode Enable  
N.n  
Z_GAIN  
ICE_CNFG  
Dsable/Enable  
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)  
DESCRIPTION  
Schedule Number  
Override Time Limit  
Timed Override Hours  
Timed Override  
VALUE  
NN  
N
DEFAULT  
1
0
0
UNITS  
POINT NAME  
SCHEDNUM  
OTL  
OVR_EXT  
TIMEOVER  
hours  
hours  
N
No/Yes  
No  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)  
DESCRIPTION  
COOLING RESET  
Cooling Reset Type  
4-20 MA RESET  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
CRST_TYP  
420_DEG  
N
0
4-20 - Degrees Reset  
NNN.n  
deltaF  
REMOTE RESET  
Remote - No Reset Temp  
Remote - Full Reset Temp  
Remote - Degrees Reset  
NNN.n  
NNN.n  
NNN.n  
degF  
degF  
deltaF  
REM_NO  
REM_FULL  
REM_DEG  
RETURN TEMPERATURE RESET  
Return - No Reset Temp  
Return - Full Reset Temp  
Return - Degrees Reset  
NNN.n  
NNN.n  
NNN.n  
deltaF  
deltaF  
deltaF  
RTN_NO  
RTN_FULL  
RTN_DEG  
DEMAND LIMIT  
Demand Limit Select  
Demand Limit at 20 mA  
Loadshed Group Number  
Loadshed Demand Delta  
Maximum Loadshed Time  
Demand Limit Switch 1  
Demand Limit Switch 2  
N
NNN  
NN  
DMD_CTRL  
DMT20MA  
SHED_NUM  
SHED_DEL  
SHED_TIM  
DLSWSP1  
DLSWSP2  
%
NN  
%
mins  
%
NNN  
NNN  
NNN  
%
CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)  
DESCRIPTION  
LEAD/LAG  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
Lead/Lag Chiller Enable  
Master/Slave Select  
Slave Address  
Lead/Lag Balance Select  
Lead/Lag Balance Delta  
Lag Start Delay  
Dsable/Enable  
Master/Slave  
NNN  
N
NNN  
LL_ENA  
MS_SEL  
SLV_ADDR  
LL_BAL  
LL_BAL_D  
LL_DELAY  
PARALLEL  
hours  
mins  
NN  
No/Yes  
Parallel Configuration  
CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)  
DESCRIPTION  
Service Password  
Password Enable  
Metric Display  
VALUE  
NNNN  
Dsable/Enable  
Off/On  
N
DEFAULT  
UNITS  
POINT NAME  
PASSWORD  
PASS_EBL  
DISPUNIT  
Language Selection  
LANGUAGE  
CCN CONFIGURATION TABLES — HPA  
DESCRIPTION  
SCT Delta for Comp A1  
SCT Delta for Comp A2  
VALUE  
NNN.n  
NNN.n  
DEFAULT  
UNITS  
deltaF  
deltaF  
POINT NAME  
A1SCTDT  
A2SCTDT  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN SERVICE TABLES — SERVICE  
DESCRIPTION  
SERVICE  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
Brine Freeze Point  
NNN.n  
degF  
BRN_FRZ  
COMPRESSOR ENABLE  
Enable Compressor A1  
Enable Compressor A2  
Enable Compressor A3  
Dsable/Enable  
Dsable/Enable  
Dsable/Enable  
ENABLEA1  
ENABLEA2  
ENABLEA3  
CCN SETPOINT TABLES — SETPOINT  
DESCRIPTION  
COOLING  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
Cooling Setpoint 1  
Cooling Setpoint 2  
ICE Setpoint  
NNN.n  
NNN.n  
NNN.n  
degF  
degF  
degF  
CSP1  
CSP2  
CSP3  
RAMP LOADING  
Cooling Ramp Loading  
N.n  
CRAMP  
Brine Freeze Point  
NNN.n  
degF  
BRN_FRZ  
Copyright 2010 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300053-01 Printed in U.S.A. Form 30MP-1T Pg 72 1-10 Replaces: New  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST FOR 30MP LIQUID CHILLER  
(Remove and use for job file.)  
A. Preliminary Information  
JOB NAME _______________________________________________________________________________  
LOCATION _______________________________________________________________________________  
INSTALLING CONTRACTOR _________________________________________________________________  
DISTRIBUTOR ____________________________________________________________________________  
START-UP PERFORMED BY _________________________________________________________________  
EQUIPMENT: Chiller:  
COMPRESSORS:  
MODEL NO.  
SERIAL NO.  
CIRCUIT A  
MODEL NO.  
SERIAL NO.  
B. Preliminary Equipment Check (Yes or No)  
IS THERE ANY SHIPPING DAMAGE?  
IF SO, WHERE  
_________________________________________________________________________________________  
WILL THIS DAMAGE PREVENT UNIT START-UP?  
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?  
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions)  
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions)  
HAS THE GROUND WIRE BEEN CONNECTED?  
ARE ALL ELECTRICAL TERMINALS TIGHT?  
ON BRINE UNITS, HAS THE COOLER FLUID BEEN PROPERLY PROTECTED FROM FREEZING TO AT  
LEAST 15° F (8.3° C) BELOW THE LOWEST ANTICIPATED LEAVING FLUID TEMPERATURE SET POINT?  
HAVE THE MAIN BASE BOARD, ENERGY MANAGEMENT MODULE (OPTION) AND CONTROL RELAY  
CONNECTIONS BEEN CHECK FOR TIGHTNESS?  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300053-01  
Printed in U.S.A.  
Form 30MP-1T  
Pg CL-1  
1-10  
Replaces: New  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (insert check mark as each item is completed)  
CHILLER HAS BEEN PROPERLY INTERLOCKED WITH THE AUXILIARY CONTACTS OF THE CHILLED  
FLUID PUMP STARTER.  
CHILLER HAS BEEN PROPERLY INTERLOCKED WITH THE AUXILIARY CONTACTS OF THE  
CONDENSER WATER PUMP STARTER.  
CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR A MINIMUM OF 24 HOURS PRIOR TO START-UP.  
(30MPA UNITS ONLY)  
COMPRESSOR OIL LEVEL IS CORRECT.  
LIQUID LINE SERVICE VALVE IS BACKSEATED (30MPA UNITS ONLY).  
SET POINT SHOULD BE ADJUSTED TO THE DESIRED COOLER LEAVING FLUID TEMPERATURE.  
(refer to installation instructions).  
LEAK CHECK THOROUGHLY: CHECK ALL COMPRESSORS, CONDENSER MANIFOLDS AND HEADERS,  
TXVs, SOLENOID VALVES, FILTER DRIERS, FUSIBLE PLUGS, THERMISTORS, AND COOLER CONNEC-  
TIONS USING ELECTRONIC LEAK DETECTOR.  
LOCATE, REPAIR, AND REPORT ANY REFRIGERANT LEAKS.  
CHECK VOLTAGE IMBALANCE:  
AB  
AC  
BC  
AB + AC + BC (divided by 3) = AVERAGE VOLTAGE =  
V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
(MAX. DEVIATION)  
VOLTAGE IMBALANCE =  
x 100 =  
% VOLTAGE IMBALANCE  
AVERAGE VOLTAGE  
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START CHILLER!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
INCOMING POWER VOLTAGE TO CHILLER MODULES IS WITHIN RATED UNIT VOLTAGE  
RANGE.  
SYSTEM FLUID VOLUME IN LOOP:  
GAL (L)  
REFER TO INSTALLATION INSTRUCTIONS FOR MINIMUM FLUID VOLUME  
CL-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (cont)  
CHECK PRESSURE DROP ACROSS COOLER.  
FLUID ENTERING COOLER:  
FLUID LEAVING COOLER:  
PSIG (kPa)  
PSIG (kPa)  
(PSIG DIFFERENCE) x 2.31 = FT OF FLUID PRESSURE DROP =  
PLOT COOLER PRESSURE DROP ON PERFORMANCE DATA CHART (LOCATED IN INSTALLATION  
INSTRUCTIONS LITERATURE) TO DETERMINE TOTAL GPM (L/s).  
TOTAL GPM (L/s) =  
UNIT’S RATED MIN GPM (L/s) =  
JOB’S SPECIFIED GPM (L/s) (if available):  
NOTE: IF UNIT HAS LOW FLUID FLOW, FIND SOURCE OF PROBLEM: CHECK FLUID PIPING, IN-LINE  
FLUID STRAINER, SHUT-OFF VALVES, CWP ROTATION, ETC.  
COOLER LOOP FREEZE PROTECTION IF REQUIRED:  
GALLONS (LITERS) ADDED:  
PIPING INCLUDES ELECTRIC TAPE HEATERS IF PIPNG IS EXPOSED TO TEMPERATURES  
BELOW FREEZING (Y/N):  
COOLER/CONDENSER PROTECTION:  
IN-LINE MINIMUM 40-MESH STRAINER INSTALLED WITHIN 10 FT OF THE COOLER/CONDENSER  
WATER INLET.  
COOLER: YES  
NO  
CONDENSER: YES  
NO  
VISUALLY CHECK MAIN BASE BOARD FOR THE FOLLOWING:  
INSPECT ALL THERMISTORS AND TRANSDUCERS FOR POSSIBLE CROSSED WIRES.  
CHECK TO BE SURE ALL WELL-TYPE THERMISTORS ARE FULLY INSERTED INTO THEIR  
RESPECTIVE WELLS.  
TO START THE CHILLER:  
TURN THE EMERGENCY ON/OFF SWITCH (SW2) TO ON POSITION.  
TURN THE ENABLE/OFF/REMOTE CONTACT SWITCH (SW1) TO THE ENABLE POSITION.  
IF EQUIPPED WITH THE OPTIONAL SCROLLING MARQUEE, LEAVE THE ENABLE/OFF/REMOTE CONTACT  
SWITCH (SW1) IN THE OFF POSITION.  
NOTE: USE ESCAPE KEY TO GO UP ONE LEVEL IN THE STRUCTURE.  
USE ARROW/ESCAPE KEYS TO ILLUMINATE RUN STATUS LED. PRESS ENTER KEY UNTIL  
‘VERS’ IS DISPLAYED. PRESS ENTER KEY. RECORD INFORMATION ON THE FOLLOWING PAGE.  
CL-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (cont)  
Record Software Versions  
MODE — RUN STATUS  
SOFTWARE VERSION NUMBERS  
CESR131333-xx-xx  
AUX  
MBB  
CESR131279-xx-xx  
CESR131174-xx-xx  
CESR131171-xx-xx  
CESR130227-xx-xx  
VERS  
EMM  
MARQ  
NAVI  
(PRESS ENTER AND ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS)  
USE ARROW/ESCAPE KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER KEY. RECORD  
INFORMATION BELOW.  
UNIT (Configuration Settings)  
SUBMODE  
UNIT  
ITEM  
ITEM EXPANSION  
UNIT CONFIGURATION  
UNIT SIZE  
DISPLAY  
ENTRY  
SIZE  
SZA.1  
SZA.2  
SZA.3  
A1.TY  
MAX.T  
XXX  
XX  
XX  
XX  
NO/YES  
XX  
COMPRESSOR A1 SIZE  
COMPRESSOR A2 SIZE  
COMPRESSOR A3 SIZE  
COMPRESSOR A1 DIGITAL?  
MAXIMUM A1 UNLOAD TIME  
PRESS ESCAPE KEY TO DISPLAY UNIT’. PRESS DOWN ARROW KEY TO DISPLAY OPT1’.  
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:  
OPTIONS1 (Options Configuration)  
SUBMODE  
ITEM  
ITEM EXPANSION  
UNIT OPTIONS 1 HARDWARE  
COOLER FLUID  
MINIMUM LOAD VALVE SELECT  
RETURN GAS SENSOR ENABLE  
ENABLE OAT SENSOR  
DISPLAY  
ENTRY  
FLUD  
MLV.S  
RG.EN  
OAT.E  
D.G.EN  
CSB.E  
CPC  
PM.DY  
DPME  
DFLS  
X
NO/YES  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
ON/OFF  
DISCHRGE GAS TEMP ENABLE  
CSB BOARDS ENABLE  
OPT1  
COOLER PUMP CONTROL  
COOLER PUMP SHUTDOWN DLY  
ENABLE CONDENSER PUMP  
ENABLE COND FLOW SWITCH  
ENABLE COND WTR SENSORS  
XX MIN  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
CDWS  
PRESS ESCAPE KEY TO DISPLAY OPT1’. PRESS DOWN ARROW KEY TO DISPLAY OPT2’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION ON NEXT PAGE.  
CL-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (cont)  
OPTIONS2 (Options Configuration)  
SUBMODE  
OPT2  
ITEM  
ITEM EXPANSION  
UNIT OPTIONS 2 CONTROLS  
CONTROL METHOD  
HIGH LCW ALERT LIMIT  
MINUTES OFF TIME  
DISPLAY  
ENTRY  
CTRL  
LCWT  
DELY  
ICE.M  
X
XX.X F  
XX  
ENBL/DSBL  
ICE MODE ENABLE  
PRESS ESCAPE KEY TO DISPLAY OPT2’. PRESS DOWN ARROW KEY TO DISPLAY CCN’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
CCN (CCN Network Configuration)  
SUB-MODE  
CCN  
ITEM  
CCNA  
CCNB  
BAUD  
ITEM EXPANSION  
CCN ADDRESS  
DISPLAY  
XXX  
ENTRY  
CCN BUS NUMBER  
CCN BAUD RATE  
XXX  
X
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE  
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.  
RECORD CONFIGURATION INFORMATION BELOW:  
SETPOINT  
SUBMODE  
COOL  
ITEM  
ITEM EXPANSION  
COOLING SETPOINTS  
COOLING SETPOINT 1  
COOLING SETPOINT 2  
ICE SETPOINT  
DISPLAY  
ENTRY  
CSP.1  
CSP.2  
CSP.3  
XXX.X °F  
XXX.X °F  
XXX.X °F  
HEAD PRESSURE SETPOINTS  
HEAD SET POINT  
BRINE FREEZE SETPOINT  
BRINE FREEZE POINT  
HEAD  
FRZ  
H.DP  
XXX.X °F  
XXX.X °F  
BR.FZ  
COMPONENT TEST  
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY DISP’.  
PRESS ENTER AGAIN TO DISPLAY TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT  
‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD  
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR  
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.  
AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ON’ AND PRESS ENTER. ALL LED  
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO  
RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-  
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY TEST’. PRESS ENTER TO STOP DISPLAY  
AT OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE  
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. TURN SWITCH (SW1) TO  
THE ENABLE POSITION.  
PRESS THE DOWN ARROW TO DISPLAY OUTS’. PRESS THE ENTER KEY TO DISPLAY LL.SV’. PRESS  
THE ENTER KEY TO STOP DISPLAY AT OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP  
ARROW KEY AND ENTER TO TURN THE OUTPUT ON. PRESS ENTER SO THE ‘ON’ DISPLAY FLASHES,  
PRESS THE DOWN ARROW KEY AND THEN ENTER TO TURN THE OUTPUT OFF. OUTPUTS WILL ALSO BE  
TURNED OFF OR SENT TO 0% WHEN ANOTHER OUTPUT IS TURNED ON. CHECK OFF THE ITEMS IN THE  
SERVICE TEST TABLE ON THE NEXT PAGE THAT APPLY AFTER BEING TESTED.  
CL-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (cont)  
USE ESCAPE KEY TO RETURN TO ‘OUTS’ DISPLAY. PRESS DOWN ARROW TO DISPLAY CMPA’.  
PRESS ENTER KEY TO DISPLAY CC.A1’. NOTE THAT UNLOADERS AND HOT GAS BYPASS SOLENOIDS  
CAN BE TESTED BOTH WITH AND WITHOUT COMPRESSOR(S) RUNNING. MAKE SURE ALL SERVICE  
VALVES ARE OPEN AND COOLER/CONDENSER PUMPS HAVE BEEN TURNED ON BEFORE STARTING  
COMPRESSORS. CHECK OFF EACH ITEM AFTER SUCCESSFUL TEST. THE CONTROL WILL ONLY START  
ONE COMPRESSOR PER MINUTE. WHEN AT THE DESIRED ITEM, PRESS THE ENTER KEY TWICE TO  
MAKE THE ‘OFF’ FLASH. PRESS THE UP ARROW KEY AND ENTER TO TURN THE OUTPUT ON. CHECK  
OFF THE ITEMS IN THE SERVICE TEST TABLE BELOW THAT APPLY AFTER BEING TESTED.  
SERVICE TEST  
KEYPAD  
ENTRY  
ITEM  
Completed  
(Yes/No)  
SUB-MODE  
TEST  
ITEM DISPLAY  
COMMENT  
EXPANSION  
ON/OFF  
SERVICE TEST MODE  
To Enable Service Test Mode,  
move Enable/Off/Remote  
Contact switch to OFF. Change  
TEST to ON. Move switch to  
ENABLE.  
ENTER  
OUTPUTS AND PUMPS  
COOLER PUMP RELAY  
ENTER  
CLR.P ON/OFF  
CND.P ON/OFF  
UL.TM 0 TO 15  
CONDENSER PUMP  
COMP A1 UNLOAD TIME  
CRANKCASE HEATER  
CC.H  
ON/OFF  
OUTS  
CW.VO ON/OFF  
CW.VC ON/OFF  
LL.SV ON/OFF  
RMT.A ON/OFF  
CONDENSER VALVE OPEN  
CONDENSER VALVE CLOSE  
LIQUID LINE SOLENOID  
REMOTE ALARM RELAY  
CIRCUIT A COMPRESSOR TEST  
COMPRESSOR A1 RELAY  
ENTER  
CC.A1 ON/OFF  
UL.TM 0 TO 15  
CC.A2 ON/OFF  
CC.A3 ON/OFF  
COMP A1 UNLOAD TIME  
COMPRESSOR A2 RELAY  
COMPRESSOR A3 RELAY  
MINIMUM LOAD VALVE RELAY  
CMPA  
MLV  
ON/OFF  
USE ARROW/ESCAPE KEYS TO ILLUMINATE THE TEMPERATURES LED. PRESS ENTER TO DISPLAY  
‘UNIT’. PRESS ENTER AND USE THE ARROW KEYS TO RECORD TEMPERATURES FOR  
SENSORS BELOW.  
TEMPERATURE  
CLWT  
CEWT  
CDET  
CDLT  
OAT or DLWT  
SPT  
CL-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (cont)  
ALL UNITS:  
MEASURE THE FOLLOWING (MEASURE WHILE MACHINE IS IN A STABLE OPERATING CONDITION):  
CIRCUIT A  
DISCHARGE PRESSURE  
SUCTION PRESSURE  
DISCHARGE LINE TEMP  
SUCTION LINE TEMP  
SATURATED COND TEMP  
COOLER ENTERING FLUID  
COOLER LEAVING FLUID  
CONDENSER ENTERING FLUID  
CONDENSER LEAVING FLUID  
CHECK AND ADJUST SUPERHEAT AS REQUIRED.  
CL-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Unit Start-Up (cont)  
COMMENTS:  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
SIGNATURES:  
START-UP TECHNICIAN ___________________________________________________________________  
DATE __________________________________  
CUSTOMER REPRESENTATIVE_____________________________________________________________  
DATE___________________________________  
Copyright 2010 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300053-01  
Printed in U.S.A.  
Form 30MP-1T  
Pg CL-8  
1-10  
Replaces: New  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Computer Accessories F4D162 2 User Manual
Black Decker Cordless Sander KW750 User Manual
Black Decker Power Hammer 5021 User Manual
Blue Rhino Charcoal Grill CBT802WB C User Manual
Bravetti Rice Cooker KC255H User Manual
Canon All in One Printer 5784B020 User Manual
Canon Projector WUX400ST User Manual
Casio Digital Camera MA1010 BMF User Manual
Cecilware Hot Beverage Maker GB1CP User Manual
Century Baby Accessories PM 1645AA User Manual