Carrier Range 48EZ A User Manual

48EZ---A and 48VT---A  
Comfort™ and Performance™ 13 and 14 SEER  
Single Packaged Hybridr Heat Dual Fuel System  
With Puron (R---410A) Refrigerant  
Single and Three Phase  
2 --- 5 N om i n a l Ton s ( Si ze s 24 --- 60)  
Owner’s Information Manual  
A09034  
A09033  
48EZ--A Without Economizer  
48VT--A Without Economizer  
A10078  
48VT--A  
A10077  
48VT--A with Economizer  
Fig. 2 -- Unit 48VT--A  
48EZ--A With Economizer  
Fig. 1 -- Unit 48EZ--A  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT INTRODUCTION  
!
WARNING  
The 48EZ--A and 48VT--A units are small packaged gas  
heat/electric heat pump systems that can utilize both the efficiency  
of heat pump heating and the comfort of gas heating. The system  
will optimize for ideal heating, depending on several factors. This  
unit uses Puron®, the ozone friendly refrigerant, for cooling and  
heat pump heating.  
FIRE AND EXPLOSION HAZARD  
Failure to follow this hazard warning could result in  
personal injury, death and/or property damage.  
What to do if you smell gas:  
1. Do not try to light any appliance.  
2. Do not touch any electrical switch; do not use any phone  
in your building.  
Starting or Shutting Off Unit  
NOTE: Your combination heating/cooling unit is equipped with  
an automatic direct spark ignition and power combustion blower.  
To start unit gas heat:  
Refer to Fig. 3 for location of unit front access panel. Refer to Fig.  
4 for location of gas valve. Refer to Fig. 5 while proceeding with  
the following steps.  
3. Leave the building immediately.  
4. Immediately call your gas supplier from a nearby phone.  
Follow the gas supplier’s instructions.  
5. If you cannot reach your gas supplier, call the fire  
department.  
1. Set the temperature selector on room thermostat to the low-  
est temperature setting and set system switch to Emergency  
Heat.  
!
WARNING  
2. Close the external manual gas shutoff valve.  
3. Turn off the electrical supply to the unit.  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury and/or death.  
4. Remove the control access panel with a 5/16--in. nut driver.  
(See Fig. 3.)  
Before performing recommended maintenance, be sure the  
main power switch to unit is turned off and lock--out tag is  
installed.  
!
WARNING  
FIRE,  
EXPLOSION,  
ELECTRICAL  
SHOCK  
HAZARD  
Failure to follow this hazard warning could result in  
personal injury, death and/or property damage.  
1. Do not turn off the electrical power to unit without first  
turning off the gas supply.  
2. Before attempting to start the gas heating section,  
familiarize yourself with all the procedures that must be  
followed.  
Control  
Access  
Panel  
Blower  
Access  
Panel  
Filter Access Panel  
For Accessory Filter Rack  
Compressor  
Access  
Panel  
A09213  
WARNING  
FIRE, EXPLOSION HAZARD  
Fig. 3 -- Unit Access Panels  
!
5. Move the selector switch on the internal gas valve to the  
OFF position and wait 5 minutes.  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
6. Move the selector switch on the internal gas valve to the ON  
position.  
Do not attempt to light by hand.  
7. Replace the control access panel.  
8. Turn on the electrical supply to unit.  
9. Open the external manual gas shutoff valve.  
!
CAUTION  
10. Set the temperature selector on room thermostat slightly  
above room temperature to start unit. The induced--draft  
combustion air fan will start. Main gas valve will open and  
main burners should ignite within 5 seconds. If the burner  
does not light within 5 seconds, the ignition module will go  
into a Retry Mode after a period of approximately 22  
seconds (following the 5--second ignition period). If the  
burners do not light within 15 minutes of the initial call for  
heat, there is a lockout.  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
When removing access panels or performing maintenance  
functions inside your unit, be aware of sharp sheet metal  
parts and screws. Although special care is taken to reduce  
sharp edges to a minimum, be extremely careful when  
handling parts or reaching into the unit.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Set the temperature selector on room thermostat to desired  
setting.  
5. Move the selector switch on the internal gas valve to the  
OFF position.  
6. Replace the control access panel.  
WARNING  
To start unit electric cooling:  
Refer to Fig. 7 while proceeding with the following steps.  
!
FIRE AND EXPLOSION HAZARD  
1. Set the temperature selector on room thermostat to highest  
temperature setting and set system SWITCH to OFF.  
2. Close the external manual shutoff valve, if not already  
closed.  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
1. If the main burners fail to light, or the blower fails to  
start, shut down gas heating section and call your dealer for  
service.  
3. Turn ON the electrical power supply to the unit.  
4. Set system switch to COOL.  
2. Never attempt to manually light the main burners on unit  
with a match, lighter, or any other flame. If the electric  
sparking device fails to light the main burners, refer to the  
following shutdown procedures, then call your dealer as  
soon as possible.  
5. Set the temperature selector on room thermostat slightly be-  
low the room temperature to start unit.  
To shut off unit electric cooling:  
Refer to Fig. 8 while proceeding with the following steps.  
1. Set the temperature selector on room thermostat to highest  
temperature setting and set system SWITCH to OFF.  
2. Close the external manual shutoff valve, if not already  
closed.  
3. Turn off the electrical power supply to the unit.  
NOTE: Heat Pump heating mode procedure is similar to electric  
cooling mode except thermostat mode is HEAT and thermostat  
must operate on first stage heating above the balance point that has  
been determined by the Dealer.  
OPERATING YOUR UNIT  
The operation of your unit is controlled by the indoor temperature  
control (thermostat). You simply adjust the thermostat and it  
maintains the indoor temperature at the level you select. Most  
thermostats of heating and cooling systems have 3 controls: a  
temperature control selector, a FAN control, and a SYSTEM or  
MODE control. Refer to your thermostat owner’s manual for more  
information.  
Flue Hood  
Burners  
Gas Valve  
A09043  
To better protect your investment and to eliminate unnecessary  
service calls, familiarize yourself with the following facts:  
Fig. 4 -- Gas Heating/Electric Cooling Unit with Access Panel  
Removed  
1. During heat pump heating, increasing the thermostat setting  
more than 2_F (1.1_C) may cause the supplemental gas heat  
to be turned on for a short period of time to satisfy the  
thermostat. Needless use of the supplementary heat reduces  
potential energy savings.  
To shut off unit gas heat:  
WARNING  
EXPLOSION,  
!
2. Ice or frost tends to form on the coil during winter heating  
operation. Your heat pump is designed to automatically melt  
the ice. When in this defrost cycle, it is normal for steam  
or fog to rise from the outdoor unit. Do not be alarmed!  
FIRE,  
HAZARD  
ELECTRICAL  
SHOCK  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Cooling Mode  
With the SYSTEM control set to COOL, your unit will run in  
cooling mode until the indoor temperature is lowered to the level  
you have selected. On extremely hot days, your unit will run for  
longer periods at a time and have shorter “off” periods than on  
moderate days.  
Do not turn off the electrical power to unit without first  
turning off the gas supply.  
NOTE: If the unit is being shut down because of a malfunction,  
call your dealer as soon as possible.  
Heat Pump Heating Mode  
Should overheating occur or the gas supply fail to shut off, shut  
off the external manual gas valve to the unit before shutting off  
the electrical supply. Do not use this unit if any part has been under  
water. Immediately call a qualified service technician to inspect the  
unit and to replace any part of the control system and any gas  
control which has been under water.  
With the SYSTEM or MODE control of your indoor thermostat set  
to HEAT, your unit will run in heat pump heating mode until room  
temperature is raised to the level you have selected. Of course, your  
system will run for longer periods to maintain a comfortable  
environment on cooler days and nights than on moderate ones.  
Gas Heat Mode  
Refer to Fig. 6 while proceeding with the following steps.  
Your heat pump is your primary heating source. Your system is  
also equipped with a supplemental gas heating source. On cold  
days and nights, your system will automatically turn on the  
supplemental heat in order to maintain the level of comfort you  
have selected.  
1. Set the temperature selector on room thermostat to lowest  
temperature setting and set system SWITCH to OFF.  
2. Close the external manual shutoff valve.  
3. Turn off the electrical power supply to the unit.  
4. Remove the control access panel. (See Fig. 3.)  
When your heat pump needs additional heat to keep you  
comfortable, your thermostat will turn on the supplemental gas  
heat.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAIN  
ON  
55  
OFF  
STEP 1  
STEP 2  
STEP 3  
STEP 5  
STEP 4  
STEP 6  
STEP 7  
MAIN  
ON  
72  
OFF  
STEP 8  
STEP 9  
STEP 10  
A07662  
Fig. 5 -- To Start Unit Gas Heat  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAIN  
ON  
55  
OFF  
STEP 1  
STEP 2  
STEP 3  
STEP 4  
STEP 5  
STEP 6  
A07663  
Fig. 6 -- To Shut Off Unit Gas Heat  
MAIN  
ON  
72  
90  
OFF  
STEP 4 & 5  
STEP 2  
STEP 1  
STEP 3  
A09194  
Fig. 7 -- To Start Unit Electric Cooling  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAIN  
ON  
90  
OFF  
STEP 1  
STEP 2  
STEP 3  
A07797  
Fig. 8 -- To Shut Off Unit Electric Cooling  
Defrost Mode  
!
When your heat pump is providing heat to your home or office and  
the outdoor temperature drops below 45°F (7.2°C), moisture may  
begin to freeze on the surface of the coil. If allowed to build up,  
this ice would impede airflow across the coil and reduce the  
amount of heat absorbed from the outside air. So, to maintain  
energy--efficient operation, your heat pump has an automatic  
defrost mode.  
The defrost mode starts at a preset time interval of 60 minutes,  
although, it may be reset to 30, 90 or 120 minutes. Defrost will  
start at the preset time only if the ice is sufficient to interfere with  
normal heating operation.  
WARNING  
FIRE, EXPLOSION, ELECTRICAL SHOCK AND  
CUT HAZARD  
Failure to follow this warning could result in personal  
injury, death or property damage.  
1. Turn off gas supply first, then all electrical power to your  
unit and install lock--out tag before servicing or per-  
forming maintenance.  
2. When removing access panels or performing  
maintenance functions inside your unit, be aware of  
sharp sheet metal parts and screws. Although special care  
is taken to reduce sharp edges to a minimum, be  
extremely careful when handling parts or reaching into  
the unit. Wear safety glasses, gloves, and appropriate  
protective clothing.  
After the ice is melted from the coil, or after a maximum of 10  
minutes in defrost mode, the unit automatically switches back to  
normal heating operation.  
Do not be alarmed if steam or fog appears at the outdoor unit  
during defrost mode. Water vapor from the melting ice may  
condense into a mist in the cold outside air.  
During certain weather conditions such as heavy snow and freezing  
rain it is not uncommon for ice to build up on the unit grille. This  
is normal for these weather conditions. Do not attempt to remove  
the ice from the unit grille. This condition will not affect the proper  
function of the unit and will clear within a few days.  
Air Filters  
The air filter(s) should be checked every 3 or 4 weeks and  
changed or cleaned whenever it becomes dirty. Dirty filters  
produce excessive stress on the blower motor and can cause the  
motor to overheat and shut down.  
Emergency Heat Mode  
This unit must have air filters in place before it can be operated.  
These filters can be located in one of at least two places. In many  
applications, the installer will provide return air filter grilles  
mounted on the wall or ceiling of the conditioned structure. In the  
instance of filter grilles, the filters can simply be removed from the  
grille and replaced.  
The other typical application is an accessory filter rack installed  
inside the unit itself. The following information is given to assist in  
changing filters used in these internal filter racks.  
Table 1 indicates the correct indoor filter size for your unit. Refer  
to Fig. 3 to access filters installed in the accessory filter rack. If  
using an Accessory Filter Rack, refer to the Installation Instructions  
provided with it for correct filter sizes and quantities.  
Table 1 – Indoor Air Filter Data  
If you should have problems with the heat pump portion of your  
system, this mode allows your supplemental gas heating source to  
keep your home or office warm until your heat pump can be  
serviced.  
MAINTENANCE AND SERVICE  
This section discusses maintenance that should be performed on  
your system. Most maintenance should be performed by your  
dealer. You, as the owner, may wish to handle some minor  
maintenance for your new unit.  
Routine Maintenance  
All routine maintenance should be handled by skilled, experienced  
personnel. Your dealer can help you establish a standard procedure.  
For your safety, keep the unit area clear and free of combustible  
materials, gasoline, and other flammable liquids and vapors.  
Unit Size  
24040  
Filter Size in. (mm)  
20x20x1 (508x508x25)  
20x24x1 (508x610x25)  
24x30x1 (610x762x25)  
24x36x1 (610x914x25)  
To assure proper functioning of the unit, flow of condenser air  
must not be obstructed from reaching the unit. Clearance from the  
top of the unit is 48 in. (1219 mm). Clearance of at least 36 in.  
(914 mm) is required on sides except the power entry side (42 in.  
[1067 mm] clearance) and the duct side (12 in. [305 mm]  
minimum clearance.  
24060 and 30  
36 --- 42  
48 --- 60  
To replace or inspect filters in accessory filter rack (See Fig. 3):  
1. Remove the filter access panel using a 5/16--in. nut driver.  
Maintenance and Care for the Equipment Owner  
Before proceeding with those things you might want to maintain  
yourself, please carefully consider the following:  
2. Remove the filter(s) by pulling it out of the unit. If the  
filter(s) is dirty, clean or replace with a new one.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
When installing the new filter(s), note the direction of the airflow  
arrows on the filter frame, which should be pointing at the indoor  
coil.  
!
CAUTION  
3. Reinstall filter access panel ensuring opening is air and  
watertight.  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in property  
damage.  
If you have difficulty locating your air filter(s) or have questions  
concerning proper filter maintenance, contact your dealer for  
instructions. When replacing filters, always use the same size and  
type of filter that was supplied originally by the installer.  
Never operate your unit without filters in place. An  
accumulation of dust and lint on internal parts of your unit  
can cause loss of efficiency and blower motor and/or  
compressor damage.  
Replacing or inspecting filters in units with  
economizers  
Small Chassis (See Fig. 9)  
1. Remove return air duct cover at rear of unit using a 5/16--in.  
nut driver.  
2. Remove the filter(s) by pulling it out and through the unit  
duct opening. If filter is dirty, replace both filters with new  
ones.  
When installing the new filters, note the direction of the airflow  
arrows on the filter frame, which should be pointing at the indoor  
coil.  
3. Reinstall duct cover ensuring opening is air and watertight.  
Table 2 – Indoor Air Filter Data with Economizer  
48EZ Unit Size  
Filter Size in. (mm)  
2 each 20 x 12 x 1  
30-040/060  
(508 x 305 x 25)  
2 each 20 x 12 x 1  
36-060/090  
42-060/090  
(508 x 305 x 25)  
RETURN  
1 each 24 x 14 x 1 (610 x 356 x 25),  
24 x 16 x 1 (610 x 406 x 25)  
1 each 24 x 14 x 1 (610 x 356 x 25),  
24 x 16 x 1 (610 x 406 x 25)  
1 each 24 x 16 x 1 (610 x 406 x 25),  
24 x 18 x 1 (610 x 457 x 25)  
DUCT COVER  
(Remove for  
filter access)  
SMALL CHASSIS  
48-090/115/130  
60-090/115/130*  
*Units with bent indoor coil.  
A10063  
Fig. 9 -- Small Chassis Filter Access  
48VT Unit Size  
Filter Size in. (mm)  
2 each 20 x 12 x 1  
(508 x 305 x 25 mm)  
30-040/060  
1 each 24 x 14 x 1 (610 x 406 x 25),  
24 x 16 x 1 (610 x 406 x 25)  
1 each 24 x 14 x 1 (610 x 356 x 25),  
24 x 16 x 1 (610 x 406 x 25)  
1 each 24 x 16 x 1 (610 x 406 x 25),  
24 x 18 x 1 (610 x 457 x 25)  
1 each 24 x 16 x 1 (610 x 406 x 25),  
24 x 18 x 1 (610 x 457 x 25)  
36-060/090  
42-060/090  
48-090/115/130*  
60-090/115/130*  
*Units with bent indoor coil.  
Large Chassis (See Fig. 10)  
1. Remove filter access door using a 5/16--in. nut driver.  
FILTER  
ACCESS  
PANEL  
2. Remove the filter(s) by pulling it out and through the unit  
filter access door. If filter is dirty, replace both filters with  
new ones.  
Units with bent indoor coils, install 24 x 18 x 1 (610 x 457 x 25  
mm) filter first and then install 24 x 16 x 1 (610 x 406 x 25) filter.  
When installing the new filters, note the direction of the airflow  
arrows on the filter frame, which should be pointing at the indoor  
coil.  
LARGE CHASSIS  
A10062  
Fig. 10 -- Large Chassis Filter Access  
3. Reinstall filter access door ensuring opening is air and  
watertight.  
Fans and Fan Motors  
Periodically check the condition of fan wheels and housings and  
fan motor shaft bearings. Contact your dealer for the required  
annual maintenance.  
Indoor and Outdoor Coils  
Cleaning of the coils should only be done by qualified service  
personnel. Contact your dealer for the required annual  
maintenance.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Condensate Drain  
!
The drain pan and condensate drain line should be checked and  
cleaned at the same time the cooling coils are checked by your  
dealer.  
WARNING  
FIRE, EXPLOSION HAZARD  
Compressor  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
All compressors are factory shipped with a normal charge of the  
correct type and quantity of refrigeration grade oil. A compressor  
should rarely require additional oil.  
If your unit makes an especially loud noise when the main  
burners are ignited, shut down the heating section and call  
your dealer.  
Condenser (Outdoor) Fan  
!
WARNING  
!
CAUTION  
PERSONAL INJURY AND UNIT DAMAGE  
HAZARD  
BURN HAZARD  
Failure to follow this caution may result in personal injury.  
Failure to follow this warning could result in personal  
injury, death or property damage.  
Components in heating section may be hot after unit has  
been started up. When observing flame, be careful not to get  
close to or touch heating components.  
Do not insert sticks, screwdrivers, or any other objects into  
revolving fan blades.  
The fan must be kept free of all obstructions to ensure proper  
cooling. Contact your dealer for any required service.  
Regular Dealer Maintenance  
In addition to the type of routine maintenance you might be willing  
to perform, your unit should be inspected regularly by a properly  
trained service technician. An inspection (preferably each year, but  
at least every other year) should include the following:  
Electrical Controls and Wiring  
Electrical controls are difficult to check without proper  
instrumentation. If there are any discrepancies in the operating  
cycle, contact your local dealer and request service.  
1. Inspection of all flue product passages--including the burn-  
ers, heat exchanger, and flue collector box, Mare sure the  
burner flames are blue in color and in proper adjustment.  
Refer to Fig. 11 for burner flame.  
2. Inspection of all combustion--and ventilation--air passages  
and openings.  
Refrigerant Circuit  
The refrigerant circuit is difficult to check for leaks without the  
proper equipment. If inadequate cooling is suspected, contact your  
local dealer for service.  
3. Close inspection of all gas pipes leading to and inside of  
your unit.  
!
WARNING  
4. Inspection and, if required, cleaning of the outdoor and  
indoor coils.  
EXPLOSION,  
HAZARD  
BURN AND ENVIRONMENTAL  
5. Inspection and, if required, cleaning of the indoor coil con-  
densate drain pan.  
Failure to follow this warning could result in personal  
injury, death or property damage.  
6. Inspection and cleaning of blower wheel housing and  
motor.  
System under pressure. Relieve pressure and recover all  
refrigerant before system repair or final unit disposal. Use  
all service ports and open all flow--control devices,  
including solenoid valves.  
7. Inspection of all supply--air and return--air ducts for leaks,  
obstructions, and insulation integrity. Any problems found  
should be resolved at this time.  
8. Inspection of the unit base to ensure that no cracks, gaps,  
etc., exist which may cause a hazardous condition.  
Unit Panels  
9. Inspection of the unit casing for signs of deterioration.  
After performing any maintenance or service on the unit, be sure  
all panels are fastened securely in place to prevent rain from  
entering unit cabinet and to prevent disruption of the correct unit  
airflow pattern.  
10. Inspection of all electrical wiring and components to assure  
proper connection.  
11. Inspection for leaks in the refrigerant circuit. Pressure and  
temperature check to determine appropriate refrigerant  
charge.  
Combustion Area and Vent System  
For proper and safe operation, the furnace needs air for combustion  
and ventilation. The air openings, on the furnace, the air openings  
to the area in which the furnace is installed, and the spacing around  
the furnace must not be blocked or obstructed.  
12. Operational check of the unit to determine working  
conditions. Repair or adjustment should be made at this  
time.  
Your servicing dealer may offer an economical service contract that  
covers seasonal inspections. Ask for further details.  
Complete service instructions can be found in the unit Installation,  
Start--up and Service Instructions.  
The combustion area and vent system should be inspected visually  
before each heating season. The normal accumulation of dirt, soot,  
rust, and scale can result in loss of efficiency and improper  
performance if allowed to build up. This inspection should be done  
by a trained service person.  
Warranty Certificate  
Your unit has a limited warranty. Be sure to read the warranty  
carefully to determine the coverage for your unit.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM switch or MODE control is in the COOL or HEAT and  
not OFF.  
Before you call for service...  
...check for several easily--solved problems.  
If insufficient heating or cooling is suspected:  
(
) If your unit still fails to operate, call your servicing dealer for  
troubleshooting and repairs. Specify the model and serial numbers  
of your unit. (Record them in this manual in the space provided.) If  
the dealer knows exactly which unit you have, he may be able to  
offer suggestions over the phone, or save valuable time through  
knowledgeable preparation for the service call.  
(
) Check for sufficient airflow. Check the air filter for dirt. Check  
for blocked return--air or supply--air grilles. Be sure they are open  
and unobstructed. If these checks do not reveal the cause, call your  
servicing dealer.  
If your unit is not operating at all, check the following list for  
easy solutions:  
In Case of Trouble  
If you perform the steps above and unit performance is still  
unsatisfactory, shut off the unit and call your dealer.  
(
) Check to be sure that your thermostat temperature selector is  
set below the indoor temperature during the cooling season or  
above the indoor temperature during heating season. Be sure the  
BURNER FLAME  
BURNER  
MANIFOLD  
C99021  
Fig. 11 -- Monoport Burner  
C a t a l o g N o : O M 4 8 E Z --- V T --- 0 4  
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231  
Edition Date: 04/10  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
R e p l a ce s: OM 4 8 E Z --- VT --- 0 3  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Computer Accessories F4D517 User Manual
Bertazzoni Cooktop C36500X User Manual
Black Box Computer Monitor LE2801A User Manual
Black Decker Hot Beverage Maker JKC900 User Manual
Blue Rhino Insect Control Equipment SV5100 User Manual
Briggs Stratton Flat Panel Television 355ZB2654 DLR User Manual
Briggs Stratton Portable Generator 30201 User Manual
Bryant Heating System 378 User Manual
Carrier Refrigerator XRV User Manual
Chicago Electric Camera Accessories 42292 User Manual