TM
Rooftop Water Source Heat Pump Units
50RTG
Installation, Start-Up, and
Service Instructions
Page
CONTENTS
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Units with Aquazone™ Complete C Control . . . . . 19
Units with Aquazone Deluxe D Control . . . . . . . . . . 19
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19,20
Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Aquazone Deluxe D Control LED Indicators . . . . . 20
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-22
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 21
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 21
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 22
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 22
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
• PROTECTION
• INSPECT UNIT
Step 3 — Location of Unit . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 4 — Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . 6
Step 5 — Condensate Drain . . . . . . . . . . . . . . . . . . . . . . 6
Step 6 — Piping Connections . . . . . . . . . . . . . . . . . . . . 6
• WATER LOOP APPLICATIONS
• GROUND-WATER APPLICATIONS
• GROUND-LOOP APPLICATIONS
Step 7 — Electrical Wiring. . . . . . . . . . . . . . . . . . . . . . . . 7
• SUPPLY VOLTAGE
• 208-VOLT OPERATION
• BLOWER SELECTION
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 22-25
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Step 8 — Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . 14
• THERMOSTAT CONNECTIONS
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1, CL-2
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
IMPORTANT: Read the entire instruction manual before
starting installation.
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14,15
System Checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SAFETY CONSIDERATIONS
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .15,16
C Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 15
C Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 15
D Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 15
D Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 15
D Control Accessory Relay Configurations . . . . . 16
Water Valve (Slow Opening) . . . . . . . . . . . . . . . . . . . 16
Outside Air Damper (OAD) . . . . . . . . . . . . . . . . . . . . 16
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-18
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 17
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 17
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 17
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 18
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 18
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Improper installation, adjustment, alteration, service, main-
tenance, or use can cause explosion, fire, electrical shock or
other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the individ-
ual instructions packaged with the kits or accessories when
installing.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 535-004 Printed in U.S.A. Form 50R-2SI Pg 1 8-02 Replaces: New
Book 1
4
Tab 5a 5a
Download from Www.Somanuals.com. All Manuals Search And Download.
INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
7. Remove any blower support cardboard from inlet of the
blower if present.
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Verify that the unit is the correct model for the entering
water temperature of the job.
3. Do not remove the packaging until the unit is ready for
installation.
4. Verify that the refrigerant tubing is free of kinks or dents,
and that it does not touch other unit components.
5. Inspect all electrical connections. Be sure connections are
clean and tight at the terminals.
6. Compressors are internally spring-mounted. Compressors
equipped with external spring vibration isolators must
have bolts loosened and shipping clamps removed.
8. Locate and verify any accessory kit located in compressor
section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
Step 3 — Location of Unit — The following guide-
lines should be considered when choosing a location for
WSHP. Refer to Fig. 1 and 2 for unit dimensional data:
• Provide sufficient space for water, electrical and duct
connections
• Locate unit in an area that allows for easy access and
removal of filter and access panels
• Allow enough space for service personnel to perform
maintenance
Table 1 — Physical Data — Aquazone™ 50RTG03-20 Units
UNIT 50RTG
OPERATING WEIGHT (lb)
SHIPPING WEIGHT (lb)
03
735
750
04
785
800
05
835
850
07
880
900
08
1080
1100
10
1125
1150
12
1175
1200
15
1770
1800
20
1960
2000
REFRIGERANT TO AIR HEAT EXCHANGER
Face Area (sq ft)
5
5
5
7.5
9.3
9.3
10.5
20
20
Rows Deep
2
3
3
3
3
3
3
4
4
3
3
3
3
3
3
3
3
3
Copper Tube Size (in.)
No. Fins per Inch
REFRIGERANT CHARGE R-22/Ckt (oz)
NUMBER OF CIRCUITS
/
8
/
8
/
/
/
8
/
8
/
/
/
8
8
8
8
8
12
52
1
12
68
1
12
86
1
12
132
1
12
68
2
12
86
2
12
88
2
12
141
2
12
160
2
BLOWER DATA
Diameter (qty-in.)
Width (in.)
1-10
6
1-10
6
1-10
10
1-12
11
1-15
11
1-15
11
1-15
11
2-15
11
2-15
11
FILTER DATA
Size (in.)
Quantity
16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20
10
4
4
4
4
6
6
6
6
3
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
WATER LOOP APPLICATIONS — Water loop applications
usually include a number of units plumbed to a common pip-
ing system. Maintenance to any of these units can introduce air
into the piping system. Therefore, air elimination equipment
comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.25 and 3 gpm per ton
of cooling capacity. For proper maintenance and servicing,
pressure-temperature (P/T) ports are necessary for temperature
and flow verification.
Step 4 — Mounting the Unit — For proper opera-
tion, units must be mounted on a roof curb as shown in Fig. 3.
Follow these guidelines when installing the roof curb:
1. Set unit on curb.
2. Align unit so that its return and supply air direction match
the return and supply air opening in the roof curb frame.
3. Run both the return and supply loop piping, as well as the
electrical supply line, through the pipe chase provided in
the curb.
In addition to complying with any applicable codes, consid-
er the following for system piping:
Step 5 — Condensate Drain
• Piping systems utilizing water temperatures below
1. Install a condensate trap at each unit with the top of
the trap positioned below the unit condensate drain
connection.
1
50 F require /2-in. closed cell insulation on all piping
surfaces to eliminate condensation.
• All plastic to metal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize
internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• The piping system should be flushed prior to operation to
remove dirt and foreign materials from the system.
2. Design the length of the trap (water seal) based on the
amount of positive or negative pressure on the drain pan.
As a rule, 1 in. of trap is required for each inch of nega-
tive pressure on the unit.
Note that condensate is allowed to drain onto the roof.
Step 6 — Piping Connections — Depending on the
application, there are 3 types of WSHP piping systems to
choose from: water loop, ground-water and ground loop. Refer
to Piping Section of Carrier System Design Manual for addi-
tional information.
GROUND-WATER APPLICATIONS — In addition to com-
plying with any applicable codes, consider the following for
system piping:
All WSHP units use low temperature soldered female pipe
thread fittings for water connections to prevent annealing and
out-of-round leak problems which are typically associated with
high temperature brazed connections. Refer to Table 1 for con-
nection sizes. When making piping connections, consider the
following:
• Install shut-off valves for servicing.
• Install pressure-temperature plugs to measure flow and
temperature.
• Boiler drains and other valves should be connected using
a “T” connector to allow acid flushing for the heat
exchanger.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material.
NOTE: PVC SCH40 should not be used due to system high
pressure and temperature extremes.
• Use a backup wrench when making screw connections to
unit to prevent internal damage to piping.
• Insulation may be required on piping to avoid condensa-
tion in the case where fluid in loop piping operates at
temperatures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may
be subject to galvanic corrosion. Dielectric fittings may
be used to isolate the steel parts of the system to avoid
galvanic corrosion.
Water Supply and Quantity — Check water supply. Water
supply should be plentiful and of good quality. See Table 2 for
water quality guidelines.
IMPORTANT: Failure to comply with the above required
water quality and quantity limitations and the closed-
system application design requirements may cause damage
to the tube-in-tube heat exchanger that is not the responsi-
bility of the manufacturer.
50 RTG
UNIT
In all applications, the quality of the water circulated
through the heat exchanger must fall within the ranges listed in
the Water Quality Guidelines table. Consult a local water treat-
ment firm, independent testing facility, or local water authority
for specific recommendations to maintain water quality within
the published limits.
GROUND-LOOP APPLICATIONS — Temperatures between
25 to 110 F and a cooling capacity of 2.25 to 3 gpm of flow per
ton is recommended. In addition to complying with any appli-
cable codes, consider the following for system piping:
• Piping materials should be limited to only polyethylene
fusion in the buried sections of the loop.
• Galvanized or steel fittings should not be used at any
time due to corrosion.
FLASHING
GASKET
ROOF
• All plastic to metal threaded fittings should be avoided
due to the potential to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Pressure-temperature (P/T) plugs should be used to mea-
sure flow of pressure drop.
CURB
Fig. 3 — 50RTG Curb Installation
6
Download from Www.Somanuals.com. All Manuals Search And Download.
AB = 452 volts
BC = 464 volts
AC = 455 volts
Step 7 — Electrical Wiring
452 + 464 + 455
3
Average Voltage =
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in
an open position during installation.
1371
3
=
=
457
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
All field installed wiring, including the electrical ground,
MUST comply with the National Electrical Code (NEC) as
well as applicable local codes. In addition, all field wiring must
conform to the Class II temperature limitations described in the
NEC.
Refer to unit wiring diagram Fig. 4 for a schematic of the
field connections which must be made by the installing (or
electrical) contractor.
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup.
The installing (or electrical) contractor must make the field
connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as
shown in Electrical Data shown in Table 3.
Make all final electrical connections with a length of flexi-
ble conduit to minimize vibration and sound transmission to
the building.
SUPPLY VOLTAGE — Operating voltage to unit must be
within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must
be balanced within 2%. Use the following formula to deter-
mine the percentage voltage imbalance:
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electri-
cal components.
NOTE: If more than 2% voltage imbalance is present, contact
local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory
wired for 208 volts. The transformers may be switched to
230-volt operation (as illustrated on the wiring diagram) by
switching the red (208 volt) wire with the orange (230 volt)
wire at the L1 terminal.
BLOWER SELECTION — All water source heat pumps are
factory set with the appropriate motor and sheave combination
to achieve the desired airflow performance. Performance is
selected by matching the desired performance with the appro-
priate region in Tables 4-12. Per the table notes, regions desig-
nated by A, B, C and D represent motor drive options.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
NOTE: Factory-installed sheaves are field adjustable. Refer to
Tables 4-12 for adjustment points.
Example: Supply voltage is 460-3-60.
Table 2 — Water Quality Guidelines
CONDITION
pH
Total Hardness Calcium and magnesium carbonate should not exceed 20 grains per gallon (350 ppm).
ACCEPTABLE LEVEL
7 to 9 range for copper. Cupro-nickel may be used in the 5 to 9 range.
Iron Oxides
Iron Bacteria
Corrosion*
Less than 1 ppm.
No level allowable.
Max Allowable Level
0.5 ppm
Coaxial Metal
Ammonia, Ammonium Hydroxide
Ammonium Chloride, Ammonium Nitrate
Ammonium Sulfate
Chlorine/Chlorides
Hydrogen Sulfide†
Cu
Cu
0.5 ppm
0.5 ppm
Cu
CuNi
—
0.5 ppm
None Allowable
Brackish
Use Cupro-nickel heat exchanger when concentrations of calcium or sodium chloride are greater
than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
*If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion
problems exists.
†Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken.
Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate
solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause sys-
tem problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality
of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral
water contains a pH of 7.0.
NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
50RTG03-07 WITH ECONOMIZER AND COMPLETE C CONTROLLER
WHT
GRN
BLK
Ground
115V / 1PH
Field
Wiring
BLK
L1
L2
L3
BLK
BLK
L1
L1
L2
L3
T1
T3
BLK
BLK
Power Supply
Refer to Data Plate
Use copper conductors only.
BLK
BLK
BLK
BLK
L2
L3
GFI
(Optional)
T2
Compressor
Disconnect
OR
CB
CC
Power
Distribution
Block
BLK
BLK
(Optional)
BLK
BLK
BLK
BLK
Blower Motor
ES
BC
Logic Module
(Damper Actuator)
MAS
-
+
GRY
BRN
150 Ohm
GRY
BLU
600 Ohm
TR1
TR
+
+
5
2
1
4
3
T1
P1
BRN
SO
4
SR
T
P
LAR
4
3
GRY
VIO
RED
(208V)
2
YEL
BLK
SEE
BRN
YEL
YEL
VIO or
NOTE 7
BC
3
6
BLK/RED
SEE
NOTE 7
CC
(460V)
BLU
or
BLK
BRN
BRN
GRY
YEL
8
OAT
BRN
R
B
CC
BRG
BR
CCG
7
SEE
NOTE 3
WHT
TAN
BLU
LAR
24V
CB
C
R
ORG
230V
ECR
Test Pins
BRN
P2
YEL
Compressor
Relay
1
RED
HP
HP
RED
BLU
BRN
GRY
GRY
VIO
2
3
Y
LOC
FP1
P1
SEE
NOTE 4
LOC
FP1
Compressor
Cooling
4
5
Y
O
Y
W
O
G
Dip Switch
FP1
FP2
PM
Not Used
1
2
RVS
6
7
Off On
Fan
FP2
FP2
RV
BRN
ORG
G
R
C
L
VIO
8
9
24 VAC
Common
Alarm
BRN
ECR
R
C
Status
LED
G
ORG
10
JW1
Not Used
AL1
AL2
CO 12
P3
C
Typical T-stat
SEE NOTE 5
SEE NOTE 6
Microprocessor
Control Logic
Alarm
Relay
A
24V
DC
EH1
EH2
CO
NOTES:
1. Compressor and blower motor thermally protected
internally.
LEGEND
2. All wiring to the unit must comply with NEC and
local codes.
AL
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Alarm Relay Contacts
Blower Mtr Contactor
Circuit Breaker
Compressor Contactor
Economizer Relay
Auxiliary Heat Stage 1
Auxiliary Heat Stage 2
Enthalpy Sensor
PM
P1
RVS
—
—
—
Performance Monitor
3. 208/230
v
transformers will be connected for
BC
Field Wiring Terminal Block
Reversing Valve Solenoid
208 v operations. For 230 v operations, discon-
nect Red lead at L1, and attach Orange lead to
L1. Close open end of Red Lead with insulating
tape.
CB
CC
ECR
EH1
EH2
ES
FP1
FP2
HP
JW1
LAR
LOC
MAS
NEC
OAT
Relay Contactor Coil
Solenoid Coil
4. FP1 jumper provides freeze protection for
WATER. When using ANTI-FREEZE solutions, cut
FP1 jumper.
5. Typical thermostat wiring shown. Refer to thermo-
stat Installation Instructions for wiring to the unit.
6. 24 v alarm signal shown. For dry alarm contact,
cut JW1 jumper and dry contact will be available
between AL1 and AL2.
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)
Sensor, Water Coil Freeze Protection
Sensor, Air Coil Freeze Protection
High Pressure Switch
Thermistor
Ground
Jumper, Alarm Mode
Low Ambient Relay
Loss-of-Charge Pressure Switch
Mixed Air Sensor
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
National Electrical Code
Outside Air Thermostat
Fig. 4 — Typical Aquazone™ Complete C Control Wiring
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — 50RTG Electrical Data
POWER
SUPPLY
COMPRESSOR
(each)
BLOWER
MOTOR
FLA
MAX. FUSE
OR HACR
BREAKER
MINIMUM
CIRCUIT
AMPACITY
UNIT
50RTG
Voltage
Hz
Ph
RLA
LRA
QTY
HP
QTY
208/230
460
208/230
460
575
60
60
60
60
60
3
3
3
3
3
10.7
5.0
13.9
6.4
5.3
63.0
31.0
88.0
44.0
34.0
1
1
1
1
1
1
1
1
1
1
3.6
1.8
3.6
1.8
1.6
1
1
1
1
1
25 Amp
15 Amp
30 Amp
15 Amp
15 Amp
17.0
8.1
21.0
9.8
8.2
03
04
208/230
460
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
20.0
7.5
123.0
49.5
40.0
156.0
70.0
54.0
88.0
44.0
34.0
123.0
49.5
40.0
123.0
62.0
50.0
156.0
70.0
54.0
232.0
116.0
97.0
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
5
5
5
3.6
1.8
1.6
6.2
3.1
2.3
6.2
3.1
2.3
6.2
3.1
2.3
9.2
4.3
3.4
9.2
4.3
3.4
13.2
6.6
5.6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
45 Amp
15 Amp
15 Amp
50 Amp
25 Amp
20 Amp
50 Amp
20 Amp
15 Amp
70 Amp
25 Amp
20 Amp
70 Amp
35 Amp
25 Amp
70 Amp
35 Amp
30 Amp
125 Amp
60 Amp
45 Amp
28.6
11.2
9.6
32.1
15.6
12.6
37.5
17.5
14.2
51.2
20.0
16.7
52.6
26.8
21.0
55.8
26.8
21.9
88.1
44.9
34.4
05
07
08
10
12
15
20
575
6.4
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
20.7
10.0
8.2
13.9
6.4
5.3
20.0
7.5
6.4
19.3
10.0
7.8
20.7
10.0
8.2
33.3
17.0
12.8
LEGEND
Full Load Amps
FLA
—
HACR — Heating, Air Conditioning and Refrigeration
LRA
RLA
—
—
Lock Rotor Amps
Rated Load Amps
NOTE: Contact factory for oversize blower motor electrical data.
Table 4 — 50RTG03 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
BHP
RPM
0.12
0.14
0.17
667
4.5
0.19
691
4.0
0.23
721
3.5
0.26
752
3.00
0.31
777
2.5
0.35
807
2.5
0.19
724
3.5
0.22
745
3.0
0.21
779
2.5
0.24
798
2.5
0.23
833
1.5
0.26
849
1.5
0.31
870
1.0
0.35
892
1.0
0.40
911
0.5
0.44
935
0.0
0.50
963
2.5
0.26
885
1.0
0.30
898
0.5
0.33
917
0.5
0.37
937
0.0
0.42
954
2.5
0.47
976
2.0
0.53
1003
2.0
0.29
933
0.0
0.32
946
0.0
0.36
963
2.5
0.41
982
2.0
0.45
997
2.0
0.51
1017
1.4
0.56
1041
1.5
0.31
980
2.0
0.35
991
2.0
0.39
1008
2.0
0.44
1025
1.5
0.33
1024
1.5
0.37
1035
1.5
0.42
1051
1.0
0.46
1066
1.0
0.52
1079
1.0
0.57
1096
0.5
0.64
1118
0.5
975
1050
1125
1200
1275
1350
1425
550 B 609
Turns Out
5.0
3.5
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
0.14
580
4.0
0.18
619
3.5
0.22
658
4.5
0.26
688
4.0
0.29
721
3.5
0.4
763
3.0
0.17
636
3.0
0.20
670
4.5
0.24
705
4.00
0.29
732
3.5
0.32
764
3.0
0.40
803
2.5
0.25
0.28
772 A 821
3.0
2.0
0.29
799
2.5
0.33
822
2.0
0.39
850
1.5
0.44
883
1.0
0.32
846
1.5
0.36
867
1.5
0.41
893
1.0
0.46
923
0.5
0.48
C 1038
1.5
0.54
1057
1.0
0.42
843
1.5
0.61
1080
1.0
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. For applications requiring higher static pressures, contact your local representative.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — 50RTG04 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
BHP
RPM
0.26
633
5
0.30
694
3.5
0.33
755
4.5
0.40
782
4.0
0.48
819
3.5
0.57
851
3.0
0.66
887
2.0
0.76
923
1.5
0.89
961
1.0
0.36
812
3.5
0.43
836
3.0
0.52
871
2.5
0.40
869
2.5
0.46
890
2.0
0.55
922
1.5
0.42
925
1.5
0.50
943
1.0
0.58
970
0.5
0.67
995
0.0
0.78
1024
3.5
0.89
1053
3.0
1.02
1086
2.5
1300
1400
1500
1600
1700
1800
1900
Turns Out
0.33 B0.36
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
0.53
995
0.5
Operation Not Recommended
668
4
725
3.0
0.45
766
4.5
0.54
801
3.5
0.62
840
3.0
0.72
878
2.5
0.85
919
1.5
0.418
712
3.0
0.506
750
4.5
0.572
792
4.0
0.671
832
3.0
0.62
1017
3.5
0.65
1063
3.0
0.61 A 0.64
0.70
1040
3.5
0.81
1068
3.0
0.75
1083
1.5
0.86
1110
2.5
0.78
1125
2.0
0.89
1152
1.5
0.83
1166
1.5
0.94
1194
1.0
900
2.0
948
1.0
0.74
979
0.5
0.85
1010
0.0
0.98
1045
3.0
C
0.70
934
1.5
0.80
967
1.0
0.94
1003
0.0
0.94
1095
2.5
1.07
1127
2.0
0.97
1136
2.0
1.11
1166
1.5
1.01
1176
1.5
1.16
1204
1.0
1.06
1219
1.0
1.20
1242
0.5
D
0.80
875
2.5
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
Table 6 — 50RTG05 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
BHP
RPM
0.37
797
3.5
0.42
845
2.5
0.48
882
1.5
0.56
923
3.5
0.65
967
3.0
0.74
1005
2.0
0.84
1047
1.5
0.96
1091
4.5
0.45
892
1.5
0.53
927
3.5
0.61
966
3.0
0.69
1007
2.0
0.78
1044
1.5
0.89
1084
1.0
1.00
1126
4.0
0.50
938
3.0
0.56
971
2.5
0.65
1008
2.0
0.54
984
2.5
0.61
1015
2.0
0.69
1049
1.5
0.58
1029
1.5
0.65
1057
1.0
0.74
1090
0.5
0.84
1126
0.5
0.94
1158
0.0
1.05
1193
3.0
1.17
1231
2.5
0.63
1072
1.0
0.70
1099
0.5
0.78
1131
0.5
0.88
1164
0.0
0.98
1195
3.0
1.09
1229
2.5
1.22
1265
2.0
0.67
1114
0.5
0.75
1140
0.5
0.84
1170
0.0
0.94
1203
3.0
Operation Not
Recommended
1700
1800
1900
2000
2100
2200
2300
Turns Out
0.44 B
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
0.79
1180
0.0
836
2.5
0.52
880
1.5
0.61
926
3.5
0.69
966
3.0
0.79
1009
2.0
0.88
1208
3.0
0.98
1240
2.5
0.94
1246
2.5
C
0.74 A0.78
1.03
1277
2.0
1047
1.5
1087
1.0
0.88
1120
0.5
0.99
1157
3.5
1.11
1196
3.0
0.84
1082
1.0
0.94
1120
0.5
1.06
1161
3.5
1.03
1.09
1268
2.0
1.14
1303
1.5
1231 D
2.5
1.14
1264
2.0
1.20
1298
1.5
1.25
1333
1.0
0.9
1055
1.0
1.28
1299
1.5
1.33
1332
1.0
1.39
1365
0.5
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7 — 50RTG07 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
BHP
RPM
0.42 0.46 0.51
0.56
750
4.5
0.73
793
3.5
0.88
830
3.0
0.62
792
3.5
0.78
831
3.0
0.95
865
2.0
1.12
901
1.5
1.33
939
0.5
1.56
978
5.0
1.90
1029
4.0
0.67
832
2.5
0.85
869
2.0
1.00
900
1.5
1.19
933
0.5
1.40
970
5.0
1.64
1007
4.5
1.98
1056
3.5
0.73
870
2.0
0.90
905
1.5
1.07
935
0.5
1.25
965
0.0
1.47
1000
4.5
1.72
1035
4.0
2.06
1082
3.0
0.78
908
1.5
0.97
941
0.5
1.14
969
0.0
1.33
997
4.5
1.54
1030
4.0
1.79
1064
3.5
2.13
1109
2.5
1950
2200
2400
2600
2800
3000
3250
620
4.5
664
3.5
707
2.5
Operation Not Recommended
Turns Out
B
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
0.56 0.62 0.67
1.03
975
5.0
1.21
1002
4.5
1.40
1029
4.0
1.62
1059
3.5
1.87
1091
3.0
2.22
1135
2.5
1.10
1007
3.0
1.17
1038
2.5
675
3
716
2.0
755
4.5
0.70 0.76 0.83
1.28
1034
4.0
1.34
1066
3.5
1.41
1097
3.0
721
2.0
758
4.5
795
3.5
A
C
0.87 0.94 0.99
1.06
868
2.0
1.27
908
1.5
1.47
1060
3.5
1.55
1090
3.0
1.63
1120
2.5
1.69
1149
2.0
1.77
1178
1.5
2.01
1203
1.0
2.28
1228
1.0
2.65
1263
0.5
765
4
800
3.5
835
3.0
1.07 1.13 1.20
1.69
1089
3.0
1.77
1118
2.5
1.86
1147
2.0
1.94
1175
1.5
812
3.5
845
2.5
877
2.0
1.28 1.35 1.42
1.50
949
0.5
1.83
1001
4.5
1.95
1119
2.5
2.30
1161
2.0
2.02
1147
2.0
2.39
1187
1.5
2.11
1174
1.5
2.20
1202
1.0
857
2.5
889
1.5
919
1.0
2.48D2.56
1.60 1.67 1.75
915
1.0
945
0.5
974
5.0
1212
1.0
1238
1.0
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
Table 8 — 50RTG08 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
BHP
RPM
0.40
482
4.5
0.51
514
4
0.64
549
2.5
0.81
588
5
1.00
623
3.5
1.20
657
2.5
1.47
699
1.5
0.45
521
3.5
0.56
550
2.5
0.69
583
4.5
0.88
619
3.5
1.07
652
3.0
1.28
685
2.0
1.56
725
1.0
0.50
559
2.0
0.62
585
4.5
0.76
615
4.0
0.55
594
4.5
0.67
619
3.5
0.83
647
3.0
1.02
679
2.0
1.21
709
1.5
1.43
739
0.5
1.73
775
5.0
0.61
629
3.5
0.74
651
3.0
0.88
677
2.0
1.09
707
1.5
1.29
736
0.5
1.51
764
5.0
1.82
799
4.5
0.66
661
2.5
0.79
683
2.0
0.95
707
1.5
1.16
735
0.5
1.36
763
5.0
1.60
790
4.5
1.89
823
4.0
0.72
693
1.5
0.86
713
1.0
1.01
736
0.5
1.23
763
5.0
1.44
789
4.5
1.67
815
4.0
1.98
847
3.5
0.77
723
1.0
0.91
742
0.5
1.08
764
5.0
1.30
789
4.5
1.52
814
4.0
1.75
839
3.5
2.07
870
3.0
0.83
751
0.0
0.98
770
4.5
1.14
791
4.5
1.38
815
4.0
1.60
839
3.5
1.84
863
3.0
2.16
892
2.5
0.87
779
4.5
1.05
797
4.0
1.22
818
4.0
1.45
841
3.5
1.67
863
3.0
1.91
886
2.5
2.24
915
2.0
0.91
806
4.0
1.10
823
3.5
1.29
843
3.5
0.98
832
3.5
1.16
848
3.0
1.35
868
3.0
1.03
858
3.0
1.21
872
2.5
1.42
894
2.5
1.67
913
2.0
1.90
934
1.5
2.17
954
1.0
1.10
883
2.5
1.27
895
2.0
1.49
915
2.0
1.74
936
1.5
1.99
956
1.0
2.26
976
0.5
2.61
1001
0.0
2400
2650
2900
3200
3450
3700
4000
Turns Out
B
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
A
1.52C1.60
0.95
649
3.0
865
3.0
890
2.5
1.83
911
2.0
2.08
932
1.5
1.14
681
2.0
1.35
712
1.0
1.64
750
0.0
1.75
887
2.5
2.00
909
2.0
2.33
937
1.5
2.42D2.51
958
1.0
980
0.5
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9 — 50RTG10 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
BHP
RPM
0.69
563
4.5
0.76
596
3.5
0.83
628
2.5
1.03
664
1.5
1.28
703
4.5
1.64
750
3.5
1.99
794
4.5
2.52
848
3.5
2.96
889
3.0
0.89
658
1.5
1.10
693
4.5
1.35
730
4.0
0.96
688
1.0
1.18
721
4.0
1.43
756
3.5
1.82
799
2.5
2.18
840
4.0
2.71
891
3.0
1.02
718
4.0
1.24
748
3.5
1.51
782
2.5
1.89
823
2.0
2.27
863
3.5
2.81
912
2.5
1.09
746
3.5
1.32
775
3.0
1.58
807
2.0
1.98
847
4.0
2.35
885
3.0
2.90
933
2.0
1.16
773
3.0
1.39
801
2.5
1.66
832
1.5
2.07
870
3.5
1.22
800
2.5
1.46
827
2.0
1.75
856
1.0
2.16
892
3.0
1.29
826
2.0
1.54
852
1.0
1.83
880
0.5
2.24
915
2.5
1.36
851
1.5
1.62
876
0.5
1.90
903
0.0
2.33
937
2.0
1.43
876
0.5
1.69
900
0.0
1.99
926
2.5
2.42
958
1.5
1.50
900
0.0
1.57
923
2.5
1.85
946
2.0
2.16
971
1.5
2.61
1001
0.5
3000
3300
3600
4000
4300
4700
5000
Turns Out
B0.96
0.89
604
3
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Tur ns Out
BHP
RPM
Tur ns Out
BHP
RPM
Tur ns Out
1.77
923
2.5
2.07
949
2.0
635
2.5
1.20
676
1.0
1.56
725
4.0
1.90
770
3.0
2.42
825
4.0
2.86
868
3.5
C
1.12
647
2.0
1.47
699
4.5
1.82
746
3.5
2.32
803
4.5
A
1.73
775
3.0
2.09
817
4.5
2.61
869
3.5
2.51
980
1.0
2.93
1012
0.5
2.73D2.83
2.45
907
2.5
2.54
929
2.0
2.64
950
1.5
971
1.0
991
1.0
Operation Not Recommended
2.76
847
3.5
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
Table 10 — 50RTG12 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
BHP
RPM
1.02
609
5.5
1.10 1.18
1.25
695
2.5
1.62
742
5.5
1.33
722
1.5
1.71
767
4.5
2.13
812
3.5
2.63
854
2.5
3.25
908
4.5
3.93
957
3.5
4.70
1007
2.5
1.41
748
5.5
1.78
792
4.0
2.23
835
3.0
2.73
876
1.5
3.36
928
4.0
4.04
976
3.0
4.82
1025
2.0
1.49
774
4.5
1.87
816
3.5
2.32
858
2.0
2.83
897
1.0
3.47
948
3.5
4.16
995
2.5
4.95
1042
1.5
1.56
800
3.5
1.96
839
2.5
2.41
879
1.5
2.93
918
4.5
3.58
968
3.5
4.27
1013
2.0
1.64
825
3.0
2.05
863
2.0
2.51
901
5.0
3.03
938
4.0
3.69
987
3.0
4.39
1031
1.5
1.72
849
2.5
2.13
886
1.5
2.61
923
4.5
3.12
959
3.5
1.80
873
1.5
2.22
908
4.5
2.70
944
4.0
3.23
978
3.0
1.88
896
1.0
1.97
919
4.5
2.40
952
3.5
2.89
985
3.0
3.43
1018
2.0
4.11
1062
1.0
2.05
942
4.0
2.49
973
3.0
2.98
1006
2.5
3.54
1037
1.5
3600
4000
4400
4800
5200
5600
6000
639
4.5
667
3.5
Turns Out
1.38B1.45
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
1.54
717
2.0
2.31
930
4.0
2.79
965
3.5
664
4.5
691
3.0
C
1.77
716
2.0
2.23
765
5.5
2.82
825
4.5
3.47
879
5.5
1.86 1.96
2.05
789
4.0
2.53
833
3.0
741
5.5
765
4.5
A
2.33 2.43
3.33
998
2.5
4.00
1044
1.5
788
4.0
810
3.5
3.78D3.89
2.93 3.04
3.14
888
5.0
3.81
938
4.0
4.58
989
3.0
846
2.5
867
5.5
1006
2.5
1025
2.0
4.62
1067
1.0
3.58 3.70
4.51
1050
1.5
899
5.0
918
4.5
Operation Not
Recommended
4.20
933
4.0
4.33 4.46
952
3.5
970
3.0
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11 — 50RTG15 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
BHP
RPM
0.68
465
5.0
0.87
493
4.0
0.78
506
3.5
0.98
531
3.0
0.88
545
2.5
1.09
568
2.0
1.33
595
4.5
1.62
621
4.0
1.97
654
3.0
2.34
683
2.5
2.77
714
1.5
0.98
582
4.5
1.20
603
4.5
1.45
627
4.0
1.08
617
4.0
1.31
636
3.5
1.57
659
3.0
1.88
682
2.5
2.24
711
1.5
2.64
737
1.0
3.09
766
4.0
1.17
650
3.5
1.42
669
3.0
1.71
690
2.0
2.01
712
1.5
2.39
739
1.0
2.79
764
4.0
3.26
791
3.5
1.28
681
2.5
1.52
701
2.0
1.83
720
1.5
2.15
740
1.0
2.53
766
4.0
2.95
790
3.5
3.41
816
3.0
1.39
711
2.0
1.65
732
1.0
1.94
749
4.5
2.28
768
4.0
2.67
793
3.5
3.10
815
3.0
3.58
840
2.5
1.43
740
1.0
1.76
762
4.0
2.07
777
4.0
2.42
795
3.5
2.83
819
3.0
3.26
840
2.5
3.74
864
2.0
1.54
768
4.0
1.87
791
3.5
1.65
795
3.5
1.94
819
3.0
1.76
821
3.0
2.07
846
2.5
2.44
855
2.0
2.84
871
2.0
3.26
890
1.5
3.73
911
1.0
4.25
933
0.5
Operation Not
Recommended
4500
5000
5500
6000
6500
7000
7500
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
2.16
872
1.5
2.31
897
1
B1.22
2.20C2.31
1.10
525
3.0
2.51
879
1.5
2.64
902
1
561
2.0
1.49
589
4.5
1.83
624
4.0
2.19
654
3.0
804
3.0
830
2.5
2.71
846
2.5
3.12
868
2.0
3.56
888
1.5
1.36
556
2.0
1.69
593
4.5
2.05
625
4.0
2.46
660
3.0
1.75
652
3.0
2.10
683
2.5
2.55
821
3.0
2.97
844
2.5
3.41
864
2.0
2.97
895
1.0
3.102
918
0.5
A
3.41
913
1.0
3.564
936
0.5
2.49
710
2.0
2.94
740
1.0
3.88
934
0.5
3.91D4.08
2.62
687
2.5
Operation Not
Recommended
887
1.5
910
1.0
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
Table 12 — 50RTG20 Blower Performance
EXTERNAL STATIC PRESSURE (in. wg)
SCFM
AIRFLOW
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
BHP
RPM
1.38
560
5.5
1.51
592
4.0
1.63
624
3.0
2.10
673
5.0
2.60
711
3.5
3.27
747
2.5
4.06
803
0.5
4.97
850
4.0
5.84
881
3.0
1.76
655
5.5
2.24
702
4.0
2.75
738
3.0
1.89
685
4.5
2.39
729
3.0
2.90
764
2.0
2.02
715
3.5
2.53
757
2.0
3.06
790
1.0
3.77
821
0.0
4.61
872
3.5
5.56
914
2.0
2.16
743
2.5
2.67
783
1.5
3.22
815
0.0
3.95
844
4.0
4.79
894
3.0
5.75
935
1.5
2.30
771
1.5
2.83
809
0.5
3.38
839
4.5
4.13
867
3.5
4.97
916
2.0
5.95
955
1.0
6.89
981
0.0
2.43
797
1.0
2.97
834
4.5
3.54
863
3.5
4.30
890
3.0
5.16
937
1.5
6.15
976
0.5
2.57
823
0.0
3.12
859
3.5
3.70
887
3.0
4.47
912
2.0
2.71
849
4.0
3.28
883
3.0
2.84
874
3.5
3.34
895
2.5
2.99
897
2.5
3.50
919
2.0
4.20
957
1.0
5.01
978
0.5
3.12
921
2.0
3.65
941
1.5
4.27
966
0.5
6,000
6,600
7,200
8,000
8,600
9,300
10,000
Turns Out
1.83B1.73
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
BHP
RPM
Turns Out
614
3.5
644
2.0
2.44
684
4.5
3.10
722
3.5
3.88
780
1.5
4.77
828
4.5
5.63
859
3.5
3.86C4.03
2.30
656
5.5
2.94
696
4.0
3.71
756
2.0
4.59
805
0.5
910
2.5
933
1.5
4.83
956
1.0
3.44A3.61
4.65
935
1.5
5.53
979
0.5
772
1.5
797
1.0
4.42
849
4.0
5.36
893
2.5
6.26
922
2.0
4.25
827
4.5
5.16
872
3.5
6.05
901
2.5
5.35
958
1.0
Operation Not
Recommended
6.47D6.68
5.43
838
4.5
942
1.5
962
0.5
LEGEND
BHP
—
Brake Horsepower
SCFM — Standard Cubic Feet Per Minute
NOTES:
1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 8 — Low Voltage Wiring
THERMOSTAT CONNECTIONS — The thermostat should
be wired directly to the Aquazone™ control board. See
Fig. 4 and 5.
WATER FREEZE PROTECTION — The Aquazone control
allows the field selection of source fluid freeze protection
points through jumpers. The factory setting of jumper JW3
(FP1) is set for water at 30 F. In earth loop applications, jumper
JW3 should be clipped to change the setting to 13 F when
using antifreeze in colder earth loop applications. See Fig. 6.
AIR COIL FREEZE PROTECTION — The air coil freeze
protection jumper JW2 (FP2) is factory set for 30 F and should
not need adjusting, unless using anti-freeze.
ACCESSORY CONNECTIONS — Terminal labeled A on
the control is provided to control accessory devices such as
water valves, electronic air cleaners, humidifiers, etc. This sig-
nal operates with the compressor terminal. See Fig. 7. Refer to
the specific unit wiring schematic for details.
NOTE: The A terminal should only be used with 24 volt
signals — not line voltage signals.
AQUAZONE CONTROL (C Control Shown)
WATER SOLENOID VALVES — Water solenoid valves may
be used on primary secondary pump and ground water installa-
tions. A typical well water control valve wiring which can
limit waste water in a lockout condition is shown in Fig. 7. A
slow closing valve may be required to prevent water hammer.
When using a slow closing valve, special wiring conditions
need to be considered. The valve takes approximately 60 sec-
onds to open (very little water will flow before 45 seconds) and
it activates the compressor only after the valve is completely
opened by closing its end switch. When wired as shown, the
valve will have the following operating characteristics:
Fig. 6 — Typical Aquazone Control Board
Jumper Locations
Terminal Strip P2
C
Typical
Water
Valve
24 VAC
A
1. Remain open during a lockout.
Fig. 7 — Typical D Control Accessory Wiring
2. Draw approximately 25 to 35 VA through the “Y” signal
of the thermostat.
PRE-START-UP
IMPORTANT: This can overheat the anticipators of
electromechanical thermostats. Only use relay based
electronic thermostats.
System Checkout — When the installation is complete
and the system is cleaned and flushed, follow the System
Checkout procedure outlined below.
1. Voltage: Ensure that the voltage is within the utilization
range specifications of the unit compressor and fan motor.
2. System Water Temperature: Ensure that the system
water temperature is within an acceptable range to facili-
tate start-up. (When conducting this check, also verify
proper heating and cooling set points.)
3. System Water pH: Verify system water acidity
(pH = 7.5 or 8.5). Proper pH promotes the longevity of
hoses and heat exchangers.
Capacitor
Circ Brkr
Grnd
Contactor-CC
L2
L1
4. System Flushing: Properly clean and flush the system
periodically. Ensure that all supply and return hoses are
connected end-to-end to facilitate system flushing and
prevent fouling of the heat exchanger by system water.
Water used in the system must be potable and should not
contain dirt, piping slag, and chemical cleaning agents.
BR
Transformer
Aquazone “C”
5. Closed-Type Cooling Tower or Open Tower with Heat
Exchanger: Check equipment for proper temperature set
points and operation.
See Note
Low Voltage
Connector
CB
6. Verify Balanced Water Flow Rate to Heat Pump.
THERMOSTAT
WIRED DIRECTLY
TO CONTROL
BOARD
7. Standby Pump: Verify that the standby pump is properly
installed and in operating condition.
8. Access Panels: Assure that all access panels in the filter
and fan section are securely closed.
NOTE: Low voltage connector may be removed for easy installation.
9. Air Dampers: Assure that all air dampers are properly
Fig. 5 — Low Voltage Field Wiring
set.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
10. System Controls: To ensure that no catastrophic system
failures occur, verify that system controls are functioning
and that the sequencing is correct.
11. Freeze Protection for Water System: Verify that freeze
protection is provided for the building loop water system
when outdoor design conditions require it. Inadequate
freeze protection can lead to expensive tower and system
piping repairs.
D Control Jumper Settings
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 limit of 10 F or 30 F. To select 30 F as the limit, DO
NOT clip the jumper. To select 10 F as the limit, clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-
TING — Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT
clip the jumper. To select 10 F as the limit (for anti-freeze sys-
tems), clip the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)
or to remain as a dry contact (no connection). To connect AL2
to R, do not clip the jumper. To set as dry contact, clip the
jumper.
LOW PRESSURE SETTING — The D Control can be con-
figured for Low Pressure Setting (LP). Select jumper 1 (JW1-
LP Norm Open) for choosing between low pressure input
normally opened or closed. To configure for normally closed
operation, do not clip the jumper. To configure for normally
open operation, clip the jumper.
12. System Water Loop: Verify that all air is bled from the
system. Air in the system impedes unit operation and
causes corrosion in the system piping.
13. Unit Filters: To avoid system damage, check that the unit
filter is clean.
14. Unit Fans: Manually rotate fans to assure free rotation.
Ensure that fans are properly secured to the fan shaft. Do
not oil fan motors on start-up since they are lubricated at
the factory.
15. System Control Center: Examine the system control
and alarm panel for proper installation and operation to
ensure control of the temperature set-points for operation
of the system’s heat rejector and boiler (when used).
16. Miscellaneous: Note any questionable aspects of the
D Control DIP Switches — The D Control has 2 DIP
switch blocks. Each DIP switch block has 8 switches and is
labeled either S1 or S2 on the circuit board.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers
the following options for D Control configuration:
Performance Monitor (PM) — Set switch 1 to enable or dis-
able performance monitor. To enable the PM, set the switch to
ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation — Switch 2 will en-
able or disable compressor relay staging operation. The com-
pressor relay can be set to turn on with stage 1 or stage 2 call
from the thermostat. This setting is used with dual stage units
(units with 2 compressors and 2 D controls) or in master/slave
applications. In master/slave applications, each compressor and
fan will stage according to its switch 2 setting. If switch is set to
stage 2, the compressor will have a 3-second delay before ener-
gizing during stage 2 demand.
installation.
17. Air Coil: To obtain maximum performance, the air coil
should be cleaned before starting the unit. A ten percent
solution of dishwasher detergent and water is recom-
mended for both sides of the coil. Rinse thoroughly with
water.
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the
control board are used to customize unit operation and can be
configured in the field.
IMPORTANT: Jumpers and DIP switches should only
be clipped when power to control board has been turned
off.
NOTE: If DIP switch is set for stage 2, the alarm relay will not
cycle during Test mode.
C Control Jumper Settings (See Fig. 4)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 limit of 10 F or 30 F. To select 30 F as the limit,
DO NOT clip the jumper. To select 10 F as the limit, clip the
jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-
TING — Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT
clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)
or to remain as a dry contact (no connection). To connect AL2
to R, do not clip the jumper. To set as dry contact, clip the
jumper.
Heating/Cooling Thermostat Type — Switch 3 provides selec-
tion of thermostat type. Heat pump or heat/cool thermostats
can be selected. Select OFF for heat/cool thermostats. When in
heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for
cooling stage 2, W1 is used for heating stage 1 and O/W2 is
used for heating stage 2. Select ON for heat pump applications.
In heat pump mode, Y1 used is for compressor stage 1, Y2 is
used for compressor stage 2, W1 is used for heating stage 3 or
emergency heat, and O/W2 is used for RV (heating or cooling)
depending upon switch 4 setting.
O/B Thermostat Type — Switch 4 provides selection for heat
pump O/B thermostats. O is cooling output. B is heating out-
put. Select ON for heat pumps with O output. Select OFF for
heat pumps with B output.
C Control DIP Switches — The C Control has 1 DIP
Dehumidification Fan Mode (Not used on 50RTG) — Switch
5 provides selection of normal or dehumidification fan mode.
Select OFF for dehumidification mode. The fan speed relay
will remain OFF during cooling stage 2. Select ON for normal
mode. The fan speed relay will turn on during cooling stage 2
in normal mode.
switch block with two switches. See Fig. 4.
PERFORMANCE MONITOR (PM) — DIP switch 1 will
enable or disable this feature. To enable the PM, set the switch
to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor
delay. Set DIP switch to OFF for stage 2 in which the compres-
sor will have a 3-second delay before energizing.
Switch 6 — Not used.
Boilerless Operation — Switch 7 provides selection of boiler-
less operation and works in conjunction with switch 8. In
boilerless operation mode, only the compressor is used for
heating when FP1 is above the boilerless changeover tempera-
ture set by switch 8 below. Select ON for normal operation or
select OFF for boilerless operation.
NOTE: The alarm relay will not cycle during Test mode if
switch is set to OFF, stage 2.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Boilerless Changeover Temperature — Switch 8 on S1 pro-
vides selection of boilerless changeover temperature set point.
Select OFF for set point of 50 F or select ON for set point
of 40 F.
If switch 8 is set for 50 F, then the compressor will be used
for heating as long as the FP1 is above 50 F. The compressor
will not be used for heating when the FP1 is below 50 F and the
compressor will operates in emergency heat mode, staging on
EH1 and EH2 to provide heat. If a thermal switch is being used
instead of the FP1 thermistor, only the compressor will be used
for heating mode when the FP1 terminals are closed. If the FP1
terminals are open, the compressor is not used and the control
goes into emergency heat mode.
DIGITAL NIGHT SET BACK (NSB) — In this configura-
tion, the relay will be ON if the NSB input is connected to
ground C.
NOTE: If there are no relays configured for digital NSB, then
the NSB and OVR inputs are automatically configured for
mechanical operation.
MECHANICAL NIGHT SET BACK — When NSB input is
connected to ground C, all thermostat inputs are ignored. A
thermostat set back heating call will then be connected to the
OVR input. If OVR input becomes active, then the D control
will enter Night Low Limit (NLL) staged heating mode. The
NLL staged heating mode will then provide heating during the
NSB period.
DIP SWITCH BLOCK 2 (S2) — This set of DIP switches is
used to configure accessory relay options.
Water Valve (Slow Opening) — If relay is config-
ured for Water Valve (slow opening), the relay will start 60 sec-
onds prior to starting compressor relay.
Switches 1 to 3 — These DIP switches provide selection
of Accessory 1 relay options. See Table 13 for DIP switch
combinations.
Switches 4 to 6 — These DIP switches provide selection
of Accessory 2 relay options. See Table 14 for DIP switch
combinations.
Outside Air Damper (OAD) — If relay is configured
for OAD, the relay will normally be ON any time the Fan
Enable relay is energized. The relay will not start for 30 min-
utes following a return to normal mode from NSB, when NSB
is no longer connected to ground C. After 30 minutes, the relay
will start if the Fan Enable is set to ON.
Table 13 — DIP Switch Block S2 —
Accessory 1 Relay Options
DIP SWITCH POSITION
ACCESSORY 1
RELAY OPTIONS
1
2
3
To avoid equipment damage, DO NOT leave system filled
in a building without heat during the winter unless anti-
freeze is added to system water. Condenser coils never
fully drain by themselves and will freeze unless winterized
with antifreeze.
Cycle with Fan
Digital NSB
Water Valve — Slow Opening
OAD
On
Off
On
On
On
On
Off
On
On
On
On
Off
LEGEND
NSB — Night Setback
OAD — Outside Air Damper
START-UP
Use the procedure outlined below to initiate proper unit
start-up.
NOTE: All other DIP switch combinations are invalid.
NOTE: This equipment is designed for indoor installation only.
Table 14 — DIP Switch Block S2 —
Accessory 2 Relay Options
Operating Limits
ENVIRONMENT — This equipment is designed for outdoor
installation ONLY. Extreme variations in temperature, humidi-
ty and corrosive water or air will adversely affect the unit per-
formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name-
plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — All units start and op-
erate with entering air at 40 F, entering water at 20 F and with
both air and water at the flow rates used.
NOTE: These operating limits are not normal or continuous
operating conditions. It is assumed that such a start-up is for
the purpose of bringing the building space up to occupancy
temperature. See Table 15 for operating limits.
DIP SWITCH POSITION
ACCESSORY 2
RELAY OPTIONS
4
5
6
Cycle with Fan
Digital NSB
Water Valve — Slow Opening
OAD
On
Off
On
On
On
On
Off
On
On
On
On
Off
LEGEND
NSB — Night Setback
OAD — Outside Air Damper
NOTE: All other switch combinations are invalid.
Auto Dehumidification Mode or High Fan Mode (Not used
on 50RTG) — Switch 7 provides selection of auto dehumidifi-
cation fan mode or high fan mode. In auto dehumidification fan
mode the fan speed relay will remain off during cooling stage 2
if terminal H is active. In high fan mode, the fan enable and fan
speed relays will turn on when terminal H is active. Set the
switch to ON for auto dehumidification fan mode or to OFF for
high fan mode.
When the disconnect switch is closed, high voltage is
present in some areas of the electrical panel. Exercise
caution when working with the energized equipment.
Switch 8 — Not used.
1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.
3. Balance airflow at registers.
4. Adjust all valves to the full open position and turn on the
line power to all heat pump units.
5. Operate unit in the cooling cycle. Room temperature
should be approximately 70 to 75 F dry bulb. Loop water
temperature entering the heat pumps should be between
60 and 110 F.
D Control Accessory Relay Configurations —
The following accessory relay settings are applicable for both
D controls only:
CYCLE WITH FAN — In this configuration, the relay will be
ON any time the Fan Enable relay is on.
CYCLE WITH COMPRESSOR — In this configuration, the
relay will be ON any time the Compressor relay is on.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: Three factors determine the operating limits of a unit:
(1) entering air temperature, (2) water temperature and (3)
ambient temperature. Whenever any of these factors are at a
minimum or maximum level, the other two factors must be at a
normal level to ensure proper unit operation. See Table 15.
5. Air temperature drop across the coil should be checked
when compressor is operating. Air temperature drop
should be between 15 and 25 F.
Unit Start-Up Heating Mode
NOTE: Operate the unit in heating cycle after checking the
cooling cycle. Allow five minutes between tests for the pres-
sure or reversing valve to equalize.
1. Turn thermostat to lowest setting and set thermostat
switch to HEAT position.
Table 15 — Operating Limits — 50RTG Units
AIR LIMITS
Rated Ambient Air
Min. Entering Air
COOLING
80° F
HEATING
70° F
50° F
40° F
Rated Entering Air db/wb
Max. Entering Air db/wb
WATER LIMITS
Min. Entering Water
Normal Entering Water
Max. Entering Water
80/67° F
110/83° F
70° F
80° F
2. Slowly turn the thermostat to a higher temperature until
the compressor activates.
3. Check for warm air delivery at the unit grille within a few
minutes after the unit has begun to operate.
4. Check the temperature of both supply and discharge
water. If temperature is within range, proceed. If tempera-
ture is outside the range, check the heating refrigerant
pressures.
5. Once the unit has begun to run, check for warm air deliv-
ery at the unit grille.
25° F
85° F
115° F
25° F
70° F
115° F
LEGEND
db — Dry Bulb
wb — Wet Bulb
NOTE: Value in heating column is dry bulb only. Any wet bulb read-
ing is acceptable.
6. Air temperature rise across the coil should be checked
when compressor is operating. Air temperature rise
should be between 20 and 30 F after 15 minutes at load.
Scroll Compressor Rotation — It is important to be
certain compressor is rotating in the proper direction. To
determine whether or not compressor is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
7. Check for vibration, noise and water leaks.
Flow Regulation — Flow regulation can be accom-
plished by two methods. Most water control valves have a flow
adjustment built into the valve. By measuring the pressure drop
through the unit heat exchanger, the flow rate can be deter-
mined. See Table 16. Adjust the water control valve until
the flow of 1.5 to 2 gpm is achieved. Since the pressure con-
stantly varies, two pressure gages may be needed in some
applications.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
An alternative method is to install a flow control device.
These devices are typically an orifice of plastic material de-
signed to allow a specified flow rate that are mounted on the
outlet of the water control valve. Occasionally these valves
produce a velocity noise that can be reduced by applying some
back pressure. To accomplish this, slightly close the leaving
isolation valve of the well water setup.
1. Turn off power to the unit. Install disconnect tag.
2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move
to their normal start-up levels.
When the compressor is rotating in the wrong direction, the
unit makes an elevated level of noise and does not provide
cooling.
After a few minutes of reverse operation, the scroll com-
pressor internal overload protection will open, thus activating
the unit lockout. This requires a manual reset. To reset, turn the
thermostat on and then off.
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in
an open position before flushing system.
NOTE: There is a 5-minute time delay before the compressor
will start.
Flushing — Once the piping is complete, final purging and
loop charging is needed. A flush cart pump of at least 1.5 hp is
needed to achieve adequate flow velocity in the loop to purge
air and dirt particles from the loop. Flush the loop in both direc-
tions with a high volume of water at a high velocity. Follow the
steps below to properly flush the loop:
Unit Start-Up Cooling Mode
1. Adjust the unit thermostat to the warmest position.
Slowly reduce the thermostat position until the compres-
sor activates.
2. Check for cool air delivery at unit grille a few minutes
after the unit has begun to operate.
3. Verify that the compressor is on and that the water flow
rate is correct by measuring pressure drop through the
heat exchanger using P/T plugs. Check the elevation and
cleanliness of the condensate lines; any dripping could be
a sign of a blocked line. Be sure the condensate trap in-
cludes a water seal.
4. Check the temperature of both supply and discharge
water. If temperature is within range, proceed. If tempera-
ture is outside the range, check the cooling refrigerant
pressures.
1. Verify power is off.
2. Fill loop with water from hose through flush cart before
using flush cart pump to ensure an even fill. Do not allow
the water level in the flush cart tank to drop below the
pump inlet line to prevent air from filling the line.
3. Maintain a fluid level in the tank above the return tee to
avoid air entering back into the fluid.
4. Shutting off the return valve that connects into the flush
cart reservoir will allow 50 psi surges to help purge air
pockets. This maintains the pump at 50 psi.
5. To purge, keep the pump at 50 psi until maximum pump-
ing pressure is reached.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Open the return valve to send a pressure surge through
the loop to purge any air pockets in the piping system.
7. A noticeable drop in fluid level will be seen in the flush
cart tank. This is the only indication of air in the loop.
NOTE: If air is purged from the system while using a 10 in.
PVC flush tank, only a 1 to 2 in. level drop will be noticed
since liquids are incompressible. If the level drops more than
this, flushing should continue since air is still being com-
pressed in the loop. If level is less than 1 to 2 in., reverse the
flow.
Antifreeze — In areas where entering loop temperatures
drop below 40 F or where piping will be routed through areas
subject to freezing, antifreeze is needed.
Alcohols and glycols are commonly used as antifreeze
agents. Freeze protection should be maintained to 15 F below
the lowest expected entering loop temperature. For example, if
the lowest expected entering loop temperature is 30 F, the leav-
ing loop temperature would be 22 to 25 F. Therefore, the freeze
protection should be at 15 F (30 F – 15 F = 15 F).
IMPORTANT: All alcohols should be pre-mixed and
pumped from a reservoir outside of the building or
introduced under water level to prevent fumes.
8. Repeat this procedure until all air is purged.
9. Restore power.
Antifreeze may be added before, during or after the flushing
process. However, depending on when it is added in the
process, it can be wasted. Refer to the Antifreeze section for
more detail.
Loop static pressure will fluctuate with the seasons. Pres-
sures will be higher in the winter months than during the warm-
er months. This fluctuation is normal and should be considered
when charging the system initially. Run the unit in either heat-
ing or cooling for several minutes to condition the loop to a
homogenous temperature.
Calculate the total volume of fluid in the piping system. See
Table 17. Use the percentage by volume in Table 18 to deter-
mine the amount of antifreeze to use. Antifreeze concentration
should be checked from a well mixed sample using a hydrome-
ter to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1 fac-
tory setting (water) should be used to avoid freeze damage to
the unit.
Once antifreeze is selected, the JW3 jumper (FP1) should
be clipped on the control to select the low temperature (anti-
freeze 13 F) set point to avoid nuisance faults.
When complete, perform a final flush and pressurize the
loop to a static pressure of 40 to 50 psi for winter months or 15
to 20 psi for summer months.
Table 17 — Approximate Fluid Volume (gal.)
After pressurization, be sure to remove the plug from the
end of the loop pump motor(s) to allow trapped air to be
discharged and to ensure the motor housing has been flooded.
Be sure the loop flow center provides adequate flow through
the unit by checking pressure drop across the heat exchanger.
Compare the results to the data in Table 16.
per 100 Ft of Pipe
PIPE
DIAMETER (in.)
VOLUME (gal.)
Copper
1
1.25
1.5
4.1
6.4
9.2
Rubber Hose
Polyethylene
1
3.9
Table 16 — 50RTG Coaxial Water Pressure Drop
3
/ IPS SDR11
2.8
4.5
8.0
10.9
18.0
8.3
10.9
17.0
4
1 IPS SDR11
WATER TEMPERATURE (F)
UNIT
1
1 / IPS SDR11
4
1
GPM
30
50
70
90
/ IPS SDR11
2
50RTG
2 IPS SDR11
Pressure Drop (ft. H O)
2
1
1
1 / IPS SCH40
4
2
4.0
6.0
3.1
6.1
2.8
5.3
2.8
5.3
2.8
5.3
1 / IPS SCH40
03
2 IPS SCH40
8.0
9.9
8.9
8.9
8.9
10.0
14.3
12.9
12.9
12.9
LEGEND
5.5
8.5
4.2
8.9
3.4
7.8
3.4
7.8
3.4
7.8
IPS — Internal Pipe Size
SCH — Schedule
04
05
07
08
10
12
15
20
11.5
14.0
14.8
20.5
13.2
18.6
13.2
18.6
13.2
18.6
SDR — Standard Dimensional Ratio
NOTE: Volume of heat exchanger is approximately 1.0 gallon.
Table 18 — Antifreeze Percentages by Volume
MINIMUM TEMPERATURE FOR
7.0
11.0
15.0
18.0
10.0
15.0
20.0
24.0
11.0
17.0
22.0
27.0
14.0
22.0
30.0
36.0
17.0
25.0
34.0
40.0
21.0
32.0
42.0
51.0
31.0
47.0
62.0
74.0
8.1
16.9
28.5
38.8
3.4
10.1
16.0
22.3
4.5
9.4
14.2
20.0
8.3
17.6
29.4
39.9
4.8
9.4
13.1
22.0
5.3
11.2
18.9
25.6
2.3
6.7
10.7
14.9
3.5
8.1
12.7
18.2
5.5
11.7
19.7
26.7
3.2
6.0
10.3
13.5
2.9
7.4
11.6
16.5
6.4
13.1
20.8
28.0
5.3
11.2
18.9
25.6
2.3
6.7
10.7
14.9
3.5
8.1
12.7
18.2
5.5
11.7
19.7
26.7
3.2
6.0
10.3
13.5
2.9
7.4
11.6
16.5
6.4
13.1
20.8
28.0
5.3
11.2
18.9
25.6
2.3
6.7
10.7
14.9
3.5
8.1
12.7
18.2
5.5
11.7
19.7
26.7
3.2
6.0
10.3
13.5
2.9
7.4
11.6
16.5
6.4
13.1
20.8
28.0
FREEZE PROTECTION (F)
ANTIFREEZE
10
25
15
21
20
16
25
10
Methanol (%)
100% USP Food Grade
Propylene Glycol (%)
38
30
22
15
Cooling Tower/Boiler Systems — These systems
typically use a common loop maintained at 60 to 90 F. The use
of a closed circuit evaporative cooling tower with a secondary
heat exchanger between the tower and the water loop is recom-
mended. If an open type cooling tower is used continuously,
chemical treatment and filtering will be necessary.
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems — These systems al-
low water temperatures from 30 to 110 F. The external loop
field is divided up into 2 in. polyethylene supply and return
lines. Each line has valves connected in such a way that upon
system start-up, each line can be isolated for flushing using
only the system pumps. Air separation should be located in the
piping system prior to the fluid re-entering the loop field.
5.2
10.7
17.4
24.3
10.6
21.2
34.2
46.2
18
Download from Www.Somanuals.com. All Manuals Search And Download.
HEATING STAGE 3 — In Heating Stage 3 mode, the Fan
Enable, Fan Speed and Compressor relays remain on. The EH1
output is turned on immediately. With continuing Heat Stage 3
demand, EH2 will turn on after 10 minutes. EH1 and EH2 are
turned off immediately when the Heating Stage 3 demand is re-
moved. The control reverts to Heating Stage 2 mode.
Output EH2 will be off if FP1 is greater than 45 F AND
FP2 (when shorted) is greater than 110 F during Heating
Stage 3 mode. This condition will have a 30-second recogni-
tion time. Also, during Heating Stage 3 mode, EH1, EH2, Fan
Enable, and Fan Speed will be ON if G input is not active.
EMERGENCY HEAT — In Emergency Heat mode, the Fan
Enable and Fan Speed relays are turned on. The EH1 output is
turned on immediately. With continuing Emergency Heat de-
mand, EH2 will turn on after 5 minutes. Fan Enable and Fan
Speed relays are turned off after a 60-second delay. The control
reverts to Standby mode.
OPERATION
Power Up Mode — The unit will not operate until all the
inputs, terminals and safety controls are checked for normal
operation.
NOTE: The compressor will have a 5-minute anti-short cycle
upon power up.
Units with Aquazone™ Complete C Control
STANDBY — Y and W terminals are not active in standby
mode, however the O and G terminals may be active, depend-
ing on the application. The compressor will be off.
COOLING — Y and O terminals are active in Cooling mode.
After power up, the first call to the compressor will initiate a
5 to 80 second random start delay and a 5-minute anti-short
cycle protection time delay. After both delays are complete, the
compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
Output EH1, EH2, Fan Enable, and Fan Speed will be ON if
the G input is not active during Emergency Heat mode.
HEATING STAGE 1 — Terminal Y is active in heating
stage 1. After power up, the first call to the compressor will
initiate a 5 to 80 second random start delay and a 5-minute anti-
short cycle protection time delay. After both delays are
complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
HEATING STAGE 2 — To enter Stage 2 mode, terminal W
is active (Y is already active). Also, the G terminal must be
active or the W terminal is disregarded. The compressor relay
will remain on and EH1 is immediately turned on. EH2 will
turn on after 10 minutes of continual stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1 tem-
perature is greater than 45 F and FP2 is greater than 110 F.
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan
Enable, compressor and RV relays are turned on immediately.
If configured as stage 2 (DIP switch set to OFF) then the com-
pressor and fan will not turn on until there is a stage 2 demand.
The fan Enable and compressor relays are turned off immedi-
ately when the Cooling Stage 1 demand is removed. The con-
trol reverts to Standby mode. The RV relay remains on until
there is a heating demand. If there is a master/slave or dual
compressor application, all compressor relays and related func-
tions will track with their associated DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan
Enable, compressor and RV relays remain on. The Fan Speed
relay is turned on immediately and turned immediately once
the Cooling Stage 2 demand is removed. The control reverts to
Cooling Stage 1 mode. If there is a master/slave or dual com-
pressor application, all compressor relays and related functions
will track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL
staged Heating mode, the override (OVR) input becomes ac-
tive and is recognized as a call for heating and the control will
immediately go into a Heating Stage 1 mode. With an addition-
al 30 minutes of NLL demand, the control will go into Heating
Stage 2 mode. With another additional 30 minutes of NLL
demand, the control will go into Heating Stage 3 mode.
EMERGENCY HEAT — In emergency heat mode, terminal
W is active while terminal Y is not. Terminal G must be active
or the W terminal is disregarded. EH1 is immediately turned
on. EH2 will turn on after 5 minutes of continual emergency
heat demand.
Units with Aquazone Deluxe D Control
STANDBY/FAN ONLY — The compressor will be off. The
Fan Enable, Fan Speed, and reversing valve (RV) relays will be
on if inputs are present. If there is a Fan 1 demand, the Fan
Enable will immediately turn on. If there is a Fan 2 demand,
the Fan Enable and Fan Speed will immediately turn on.
SYSTEM TEST
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1
and Fan 2 outputs.
System testing provides the ability to check the control
operation. The control enters a 20-minute Test mode by mo-
mentarily shorting the test pins. All time delays are increased
15 times. See Fig. 4.
HEATING STAGE 1 — In Heating Stage 1 mode, the Fan
Enable and Compressor relays are turned on immediately.
Once the demand is removed, the relays are turned off and the
control reverts to Standby mode. If there is a master/slave or
dual compressor application, all compressor relays and related
functions will operate per their associated DIP switch 2 setting
on S1.
HEATING STAGE 2 — In Heating Stage 2 mode, the Fan
Enable and Compressor relays remain on. The Fan Speed relay
is turned on immediately and turned off immediately once the
demand is removed. The control reverts to Heating Stage 1
mode. If there is a master/slave or dual compressor application,
all compressor relays and related functions will operate per
their associated DIP switch 2 setting on S1.
Test Mode — To enter Test mode on C or D controls, cycle
the power 3 times within 60 seconds. The LED (light-emitting
diode) will flash a code representing the last fault when enter-
ing the Test mode. The alarm relay will also power on and off
during Test mode. See Tables 19 and 20. To exit Test mode,
short the terminals for 3 seconds or cycle the power 3 times
within 60 seconds.
NOTE: Deluxe D Control has a flashing code and alarm relay
cycling code that will both have the same numerical label.
For example, flashing code 1 will have an alarm relay cycling
code 1. Code 1 indicates the control has not faulted since the
last power off to power on sequence.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 19 — C Control Current LED Status
again satisfy the thermostat used to terminal Y. Once the ther-
mostat input calls are satisfied, the control will continue normal
operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
and Alarm Relay Operations
LED STATUS
DESCRIPTION OF OPERATION
ALARM RELAY
Normal Mode
Open
Cycle
(closed 5 sec.,
Open 25 sec.)
On
Normal Mode with
PM Warning
Off
Slow Flash
Fast Flash
C Control is non-functional
Fault Retry
Open
Open
Aquazone™ Deluxe D Control LED Indica-
tors — There are 3 LED indicators on the D Control:
STATUS LED — Status LED indicates the current status or
mode of the D control. The Status LED light is green.
Lockout
Closed
Open
(Closed after
15 minutes)
Slow Flash
Over/Under Voltage Shutdown
Flashing Code 1 Test Mode — No fault in memory
Flashing Code 2 Test Mode — HP Fault in memory
Flashing Code 3 Test Mode — LP Fault in memory
Flashing Code 4 Test Mode — FP1 Fault in memory
Flashing Code 5 Test Mode — FP2 Fault in memory
Flashing Code 6 Test Mode — CO Fault in memory
Cycling Code 1
Cycling Code 2
Cycling Code 3
Cycling Code 4
Cycling Code 5
Cycling Code 6
TEST LED — Test LED will be activated any time the D
control is in test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will
always flash a code representing the last fault in memory. If
there is no fault in memory, the fault LED will flash code 1 on
and appear as 1 fast flash alternating with a 10-second pause.
See Table 21.
Test Mode — Over/Under
shutdown in memory
Flashing Code 7
Cycling Code 7
Cycling Code 8
Cycling Code 9
Flashing Code 8
Flashing Code 9
Test Mode — PM in memory
Test Mode — Test Mode — FP1/
FP2 Swapped Fault in memory
SERVICE
Perform the procedures outlined below periodically, as
indicated.
LEGEND
CO
FP
HP
—
—
—
Condensate Overflow
Freeze Protection
High Pressure
IMPORTANT: When a compressor is removed from this
unit, system refrigerant circuit oil will remain in the com-
pressor. To avoid leakage of compressor oil, the refrigerant
lines of the compressor must be sealed after it is removed.
LED — Light-Emitting Diode
LP
PM
—
—
Low Pressure
Performance Monitor
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a
10-second pause. This sequence will repeat continually until the fault is
cleared.
IMPORTANT: All refrigerant discharged from this unit
must be recovered without exception. Technicians must fol-
low industry accepted guidelines and all local, state and fed-
eral statutes for the recovery and disposal of refrigerants.
Table 20 — C Control LED Code and
Fault Descriptions
IMPORTANT: To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must only be
serviced by technicians which meet local, state and federal
proficiency requirements.
LED
CODE
1
FAULT
DESCRIPTION
No fault in memory
There has been no fault since
the last power-down to power-up
sequence
2
3
High-Pressure Switch
Low-Pressure Switch
HP Open Instantly
IMPORTANT: To prevent injury or death due to electrical
shock or contact with moving parts, open unit disconnect
switch before servicing unit.
LP open for 30 continuous sec-
onds before or during a call
(bypassed for first 60 seconds)
4
5
Freeze Protection Coax
— FP1
FP1 below Temp limit for 30 con-
tinuous seconds (bypassed for
first 60 seconds of operation)
Filters — Filters must be clean for maximum performance.
Inspect filters every month under normal operating conditions.
replace when necessary.
Freeze Protection Air Coil
— FP2
FP2 below Temp limit for 30 con-
tinuous seconds (bypassed for
first 60 seconds of operation)
6
7
Condensate overflow
Over/Under Voltage
Sense overflow (grounded) for
30 continuous seconds
IMPORTANT: Units should never be operated with-
out a filter.
"R" power supply is <19VAC or
>30VAC
(Autoreset) Shutdown
8
9
PM Warning
Performance Monitor Warning
has occurred.
Water Coil — Keep all air out of the water coil. Check
open loop systems to be sure the well head is not allowing air
to infiltrate the water line. Always keep lines airtight.
Inspect heat exchangers regularly, and clean more frequent-
ly if the unit is located in a “dirty” environment. The heat
exchanger should be kept full of water at all times. Open loop
systems should have an inverted P trap placed in the discharge
line to keep water in the heat exchanger during off cycles.
Closed loop systems must have a minimum of 15 PSI during
the summer and 40 PSI during the winter.
FP1 and FP2 Thermistors FP1 temperature is higher than
are Swapped
FP2 in heating/test mode, or FP2
temperature is higher than FP1
in cooling/test mode.
LEGEND
FP
HP
—
—
Freeze Protection
High Pressure
LED — Light-Emitting Diode
LP
PM
—
—
Low Pressure
Performance Monitor
Retry Mode — In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
Check P trap frequently for proper operation.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Aquazone D Control Current LED Status and Alarm Relay Operations
STATUS LED
(Green)
TEST LED
(Yellow)
DESCRIPTION
Normal Mode
FAULT LED (Red)
Flash Last Fault Code in Memory
Flashing Code 8
ALARM RELAY
On
Off
Open
Cycle (closed 5 sec,
open 25 sec, …)
Normal Mode with PM
On
Off
D Control is non-functional
Test Mode
Off
—
Off
On
—
—
—
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Open
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flashing Code 1
Cycling Appropriate Code
Night Setback
ESD
Invalid T-stat Inputs
No Fault in Memory
HP Fault
Flashing Code 2
Flashing Code 3
Flashing Code 4
On
—
—
—
Open
Open
Open
Open
Open
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Fast Flash
Fast Flash
Fast Flash
Fast Flash
Fast Flash
Flashing Code 2
Flashing Code 3
Flashing Code 4
Flashing Code 5
Flashing Code 6
Flashing Code 7
Flashing Code 2
Flashing Code 3
LP Fault
FP1 Fault
FP2 Fault
CO Fault
Open
Over/Under Voltage
HP Lockout
Open (closed after 15 minutes)
Closed
Closed
Closed
Closed
Closed
LP Lockout
FP1 Lockout
FP2 Lockout
CO Lockout
Flashing Code 4
Flashing Code 5
Flashing Code 6
LEGEND
NOTES:
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
CO — Condensate Overflow
ESD — Emergency Shutdown
FP — Freeze Protection
HP — High Pressure
LP — Low Pressure
PM — Performance Monitor
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes
followed by a 10-second pause. This sequence will repeat contin-
ually until the fault is cleared.
Proper water treatment can minimize tube fouling and
pitting. If such conditions are anticipated, water treatment
analysis is recommended. Refer to the Carrier System Design
Manual, Part 5, for general water conditioning information.
To avoid fouled machinery and extensive unit clean-up,
DO NOT operate units without filters in place. DO NOT
use equipment as a temporary heat source during
construction.
Follow all safety codes. Wear safety glasses and rubber
gloves when using inhibited hydrochloric acid solution.
Observe and follow acid manufacturer’s instructions.
Condensate Drain Pans — Check condensate drain
pans for algae growth twice a year. If algae growth is apparent,
consult a water treatment specialist for proper chemical treat-
ment. The application of an algaecide every three months will
typically eliminate algae problems in most locations.
Clean condensers with an inhibited hydrochloric acid solu-
tion. The acid can stain hands and clothing, damage concrete,
and, without inhibitor, damage steel. Cover surroundings to
guard against splashing. Vapors from vent pipe are not harmful,
but take care to prevent liquid from being carried over by the
gases.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuit-
ry integrity, do not install service gauges unless unit operation
appears abnormal. Check to see that unit is within the super-
heat and subcooling ranges.
Warm solution acts faster, but cold solution is just as effec-
tive if applied for a longer period.
Condensate Drain Cleaning — Clean the drain line
and unit drain pan at the start of each cooling season. Check
flow by pouring water into drain. Be sure trap is filled to main-
tain an air seal.
GRAVITY FLOW METHOD — Do not add solution faster
than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight,
then drain condenser and flush with clean water. Follow acid
manufacturer’s instructions. See Fig. 8.
FORCED CIRCULATION METHOD — Fully open vent
pipe when filling condenser. The vent may be closed when
condenser is full and pump is operating. See Fig. 9.
Regulate flow to condenser with a supply line valve. If
pump is a nonoverloading type, the valve may be fully closed
while pump is running.
For average scale deposit, allow solution to remain in con-
denser overnight. For heavy scale deposit, allow 24 hours.
Drain condenser and flush with clean water. Follow acid manu-
facturer’s instructions.
Air Coil Cleaning — Remove dirt and debris from evap-
orator coil as required by condition of the coil. Clean coil with
a stiff brush, vacuum cleaner, or compressed air. Use a fin
comb of the correct tooth spacing when straightening mashed
or bent coil fins.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly
maintained closed-loop water systems. Sludge build-up may
need to be cleaned in an open water tower system due to
induced contaminants.
Local water conditions may cause excessive fouling or
pitting of tubes. Condenser tubes should therefore be cleaned at
least once a year, or more often if the water is contaminated.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant Charging
FILL CONDENSER WITH
CLEANING SOLUTION. DO
NOT ADD SOLUTION
MORE RAPIDLY THAN
VENT CAN EXHAUST
GASES CAUSED BY
PAIL
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system —
this can cause compressor flooding.
FUNNEL
CHEMICAL ACTION.
1”
PIPE
NOTE: Do not vent or depressurize unit refrigerant to atmo-
sphere. Remove and reclaim refrigerant following accepted
practices.
VENT
PIPE
5’ APPROX
Air Coil Fan Motor Removal
3’ TO 4’
CONDENSER
Before attempting to remove fan motors or motor mounts,
place a piece of plywood over evaporator coils to prevent
coil damage.
Motor power wires need to be disconnected from motor
terminals before motor is removed from unit.
PAIL
1. Shut off unit main power supply.
2. Loosen bolts on mounting bracket so that fan belt can be
removed.
Fig. 8 — Gravity Flow Method
3. Loosen and remove the 2 motor mounting bracket bolts
on left side of bracket.
4. Slide motor/bracket assembly to extreme right and lift out
through space between fan scroll and side frame. Rest
motor on a high platform such as a step ladder. Do not
allow motor to hang by its power wires.
GAS VENT
PUMP
PRIMING
CONN.
GLOBE
VALVES
SUCTION
SUPPLY
PUMP
SUPPORT
1” PIPE
TROUBLESHOOTING
(Fig. 10 and 11, and Table 22)
CONDENSER
When troubleshooting problems with a WSHP, consider the
following.
TANK
REMOVE WATER
REGULATING VALVE
Thermistor — A thermistor may be required for single-
phase units where starting the unit is a problem due to low
voltage. See Fig. 10 for thermistor nominal resistance.
RETURN
FINE MESH
SCREEN
Control Sensors — The control system employs 2 nom-
inal 10,000 ohm thermistors (FP1 and FP2) that are used for
freeze protection. Be sure FP1 is located in the discharge fluid
and FP2 is located in the air discharge. See Fig. 11.
Fig. 9 — Forced Circulation Method
Checking System Charge — Units are shipped with
full operating charge. If recharging is necessary:
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
1. Insert thermometer bulb in insulating rubber sleeve on
liquid line near filter drier. Use a digital thermometer for
all temperature measurements. DO NOT use a mercury
or dial-type thermometer.
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure
on discharge line gage.
NOTE: Operate unit a minimum of 15 minutes before
checking charge.
4. From standard field-supplied Pressure-Temperature chart
for R-22, find equivalent saturated condensing
temperature.
5. Read liquid line temperature on thermometer; then
subtract from saturated condensing temperature. The dif-
ference equals subcooling temperature.
0.0
20.0
40.0
60.0
80.0 100.0 120.0 140.0
Temperature (F)
6. ADD refrigerant to raise the temperature or REMOVE
refrigerant (using standard practices) to lower the temper-
ature (allow a tolerance of ± 3° F), as required.
Fig. 10 — Thermistor Nominal Resistance
22
Download from Www.Somanuals.com. All Manuals Search And Download.
AIR
COIL
SUCTION
°F
°F
COMPRESSOR
THERMISTOR
EXPANSION
VALVE
COAX
DISCHARGE
FP2
FP1
CONDENSATE
OVERFLOW
(CO)
LIQUID
LINE
WATER IN
WATER OUT
AIR COIL
WATER
COIL
PROTECTION
FREEZE
PROTECTION
LEGEND
COAX — Coaxial Heat Exchanger
Airflow
Refrigerant Liquid Line Flow
Fig. 11 — FP1 and FP2 Thermistor Location
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Troubleshooting
FAULT
HEATING COOLING
POSSIBLE CAUSE
SOLUTION
Main Power Problems
X
X
Green Status LED Off
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24 VAC between R and C on controller.
Check primary/secondary voltage on transformer.
HP Fault — Code 2
High Pressure
X
X
Reduced or no water flow in Check pump operation or valve operation/setting.
cooling
Check water flow adjust to proper flow rate.
Water temperature out of
range in cooling
Bring water temperature within design parameters.
X
X
Reduced or no airflow in
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Dirty air coil — construction dust etc.
External static too high. Check Tables 4-12.
Air temperature out of range Bring return air temperature within design parameters.
in heating
X
X
X
X
X
X
X
Overcharged with refrigerant Check superheat/subcooling vs typical operating condition.
Bad HP switch
Insufficient charge
Check switch continuity and operation. Replace.
Check for refrigerant leaks.
LP/LOC Fault — Code 3
Low Pressure/Loss of
Charge
Compressor pump down at Check charge and start-up water flow.
start-up
FP1 Fault — Code 4
Water Freeze Protection
X
Reduced or no water flow in Check pump operation or water valve operation/setting.
heating
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
X
Inadequate antifreeze level Check antifreeze density with hydrometer.
Improper freeze protect set- Clip JW2 jumper for antifreeze (10 F) use.
ting (30 F vs 10 F)
X
X
Water temperature out of
range
Bring water temperature within design parameters.
X
X
Bad thermistor
Reduced or no airflow in
cooling
Check temperature and impedance correlation.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check Tables 4-12.
FP2 Fault — Code 5
Air Coil Freeze
Protection
X
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within
design parameters.
Improper freeze protect set- Normal airside applications will require 30°F only.
ting (30 F vs 10 F)
X
X
X
X
X
X
X
Bad thermistor
Blocked drain
Improper trap
Poor drainage
Check temperature and impedance correlation.
Check for blockage and clean drain.
Check trap dimensions and location ahead of vent.
Check for piping slope away from unit.
Condensate Fault —
Code 6
Check slope of unit toward outlet.
Poor venting. Check vent location.
X
X
Moisture on sensor
Under voltage
Check for moisture shorting to air coil.
Over/Under Voltage —
Code 7
(Auto Resetting)
X
Check power supply and 24 VAC voltage before and during operation.
Check power supply wire size.
Check compressor starting.
Check 24 VAC and unit transformer tap for correct power supply voltage.
Check power supply voltage and 24 VAC before and during operation.
Check 24 VAC and unit transformer tap for correct power supply voltage.
Check for poor airflow or overcharged unit.
Check for poor water flow or airflow.
X
X
X
X
Over voltage
Performance Monitor —
Code 8
Heating mode FP2>125 F
Cooling mode FP1>125 F
OR FP2< 40 F
FP1 and FP2
Thermistors — Code 9
X
FP1 temperature is higher
than FP2 temperature
FP2 temperature is higher
than FP1 temperature
Swap FP1 and FP2 thermistors.
Swap FP1 and FP2 thermistors.
X
No Fault Code Shown
Unit Short Cycles
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
No compressor operation
Compressor overload
Control board
See scroll compressor rotation section.
Check and replace if necessary.
Reset power and check operation.
Dirty air filter
Unit in 'Test Mode'
Unit selection
Compressor overload
Thermostat position
Unit locked out
Check and clean air filter.
Reset power or wait 20 minutes for auto exit.
Unit may be oversized for space. Check sizing for actual load of space.
Check and replace if necessary.
Only Fan Runs
Ensure thermostat set for heating or cooling operation.
Check for lockout codes. Reset power.
Compressor overload
Thermostat wiring
Check compressor overload. Replace if necessary.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in Test mode.
LEGEND
RV — Reversing Valve
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Troubleshooting (cont)
FAULT
HEATING COOLING
POSSIBLE CAUSE
SOLUTION
Only Compressor Runs
X
X
X
X
Thermostat wiring
Fan motor relay
Check G wiring at heat pump. Jumper G and R for fan operation.
Jumper G and R for fan operation. Check for line voltage across BR
contacts.
Check fan power enable relay operation (if present).
Check for line voltage at motor. Check capacitor.
X
X
X
X
Fan motor
Thermostat wiring
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in test mode.
Unit Does Not Operate in
Cooling
X
Reversing valve
Set for cooling demand and check 24 VAC on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating engage and disengage RV coil voltage to push valve.
X
X
X
Thermostat setup
Thermostat wiring
Dirty filter
Check for 'O' RV setup not 'B'.
Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.
Replace or clean.
Insufficient capacity/
Not cooling or heating
properly
X
X
Reduced or no airflow in
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 4-12.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 4-12.
X
X
Reduced or no airflow in
cooling
X
Leaky ductwork
Check supply and return air temperatures at the unit and at distant duct
registers if significantly different, duct leaks are present.
X
X
X
X
X
X
Low refrigerant charge
Restricted metering device Check superheat and subcooling. Replace metering device.
Check superheat and subcooling .
Defective reversing valve
Thermostat improperly
located
Perform RV touch test.
Check location and for air drafts behind thermostat.
X
X
X
X
X
X
Unit undersized
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
Perform Scaling check and clean if necessary.
Scaling in water heat
exchanger
Inlet water too hot or cold
X
X
Check load, loop sizing, loop backfill, ground moisture.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 4-12.
High Head Pressure
Reduced or no airflow in
heating
X
X
Reduced or no water flow in Check pump operation or valve operation/setting.
cooling
Check water flow and adjust to proper flow rate.
Inlet water too hot
Check load, loop sizing, loop backfill, ground moisture.
X
Air temperature out of range Bring return air temperature within design parameters.
in heating
X
Scaling in water heat
exchanger
Perform Scaling check and clean if necessary.
X
X
X
X
Unit overcharged
Check superheat and subcooling. Reweigh in charge.
Vacuum system and reweigh in charge.
Non-condensables in
system
X
X
X
Restricted metering device Check superheat and subcooling. Replace metering device.
Low Suction Pressure
Reduced water flow in
heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Water temperature out of
range
Bring water temperature within design parameters.
X
Reduced airflow in cooling Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower Tables 4-12.
X
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within design
parameters.
X
X
X
Insufficient charge
Airflow too high
Poor performance
Airflow too high
Unit oversized
Check for refrigerant leaks.
Check blower Tables 4-12.
See 'Insufficient Capacity'.
Check blower Tables 4-12.
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
Low discharge air
temperature in heating
High humidity
X
X
LEGEND
RV — Reversing Valve
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 535-004 Printed in U.S.A. Form 50R-2SI Pg 26 8-02 Replaces: New
Book 1
4
Tab 5a 5a
Download from Www.Somanuals.com. All Manuals Search And Download.
50RTG
START-UP CHECKLIST
CUSTOMER:___________________________
MODEL NO.:___________________________
JOB NAME: _______________________________________
SERIAL NO.:____________________
DATE:_________
I. PRE-START-UP
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS
TIGHT? (Y/N)
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER?
(Y/N)
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)
IS AN AIR FILTER INSTALLED? (Y/N)
II. START-UP
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)
IF 3-PHASE SCROLL COMPRESSOR IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS.
(Y/N)
UNIT VOLTAGE — COOLING OPERATION
PHASE AB VOLTS
PHASE BC VOLTS
(if 3 phase)
PHASE CA VOLTS
(if 3 phase)
PHASE AB AMPS
PHASE BC AMPS
(if 3 phase)
PHASE CA AMPS
(if 3 phase)
CONTROL VOLTAGE
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N)
.
IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.
TEMPERATURES
FILL IN THE ANALYSIS CHART ATTACHED.
COAXIAL HEAT COOLING CYCLE:
EXCHANGER
FLUID IN
F
F
F
F
FLUID OUT
FLUID OUT
AIR OUT
F
PSI
PSI
FLOW
FLOW
HEATING CYCLE:
FLUID IN
F
F
F
AIR COIL
COOLING CYCLE:
AIR IN
HEATING CYCLE:
AIR IN
AIR OUT
CL-1
Download from Www.Somanuals.com. All Manuals Search And Download.
HEATING CYCLE ANALYSIS
PSI
°F
SAT
AIR
COIL
SUCTION
°F
°F
COMPRESSOR
DISCHARGE
EXPANSION
VALVE
COAX
°F
LIQUID LINE
°F
PSI
°F
PSI
WATER IN
WATER OUT
LOOK UP PRESSURE DROP IN TABLE 16
TO DETERMINE FLOW RATE
COOLING CYCLE ANALYSIS
PSI
°F
SAT
AIR
COIL
SUCTION
°F
°F
COMPRESSOR
DISCHARGE
EXPANSION
VALVE
COAX
°F
LIQUID LINE
°F
°F
PSI
PSI
WATER IN
WATER OUT
LOOK UP PRESSURE DROP IN TABLE 16
TO DETERMINE FLOW RATE
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x
FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
(DEG F)
=
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
(DEG F)
=
*Use 500 for water, 485 for antifreeze.
*97B0014N02*
97B0014N02
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
Tab
1
4
PC 111
Catalog No. 535-004
Printed in U.S.A.
Form 50R-2SI
Pg CL-2
8-02
Replaces: New
5a 5a
Download from Www.Somanuals.com. All Manuals Search And Download.
|