Carrier Heat Pump 50RTG User Manual

TM  
Rooftop Water Source Heat Pump Units  
50RTG  
Installation, Start-Up, and  
Service Instructions  
Page  
CONTENTS  
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Units with Aquazone™ Complete C Control . . . . . 19  
Units with Aquazone Deluxe D Control . . . . . . . . . . 19  
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19,20  
Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Aquazone Deluxe D Control LED Indicators . . . . . 20  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-22  
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 21  
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 22  
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 22  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2  
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14  
Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2  
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
• STORAGE  
• PROTECTION  
• INSPECT UNIT  
Step 3 — Location of Unit . . . . . . . . . . . . . . . . . . . . . . . . 3  
Step 4 — Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . 6  
Step 5 — Condensate Drain . . . . . . . . . . . . . . . . . . . . . . 6  
Step 6 — Piping Connections . . . . . . . . . . . . . . . . . . . . 6  
WATER LOOP APPLICATIONS  
• GROUND-WATER APPLICATIONS  
• GROUND-LOOP APPLICATIONS  
Step 7 — Electrical Wiring. . . . . . . . . . . . . . . . . . . . . . . . 7  
• SUPPLY VOLTAGE  
• 208-VOLT OPERATION  
• BLOWER SELECTION  
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 22-25  
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
Step 8 — Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . 14  
• THERMOSTAT CONNECTIONS  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1, CL-2  
WATER FREEZE PROTECTION  
• AIR COIL FREEZE PROTECTION  
• ACCESSORY CONNECTIONS  
WATER SOLENOID VALVES  
IMPORTANT: Read the entire instruction manual before  
starting installation.  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14,15  
System Checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
SAFETY CONSIDERATIONS  
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .15,16  
C Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 15  
C Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 15  
D Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 15  
D Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 15  
D Control Accessory Relay Configurations . . . . . 16  
Water Valve (Slow Opening) . . . . . . . . . . . . . . . . . . . 16  
Outside Air Damper (OAD) . . . . . . . . . . . . . . . . . . . . 16  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-18  
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 17  
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 17  
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 17  
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 18  
Ground Coupled, Closed Loop and Plateframe  
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 18  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All other  
operations should be performed by trained service personnel.  
When working on air-conditioning equipment, observe precau-  
tions in the literature, tags and labels attached to the unit, and  
other safety precautions that may apply.  
Improper installation, adjustment, alteration, service, main-  
tenance, or use can cause explosion, fire, electrical shock or  
other conditions which may cause personal injury or property  
damage. Consult a qualified installer, service agency, or your  
distributor or branch for information or assistance. The  
qualified installer or agency must use factory-authorized kits or  
accessories when modifying this product. Refer to the individ-  
ual instructions packaged with the kits or accessories when  
installing.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 535-004 Printed in U.S.A. Form 50R-2SI Pg 1 8-02 Replaces: New  
Book 1  
4
Tab 5a 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSPECT UNIT — To prepare the unit for installation, com-  
plete the procedures listed below:  
7. Remove any blower support cardboard from inlet of the  
blower if present.  
1. Compare the electrical data on the unit nameplate with  
ordering and shipping information to verify that the  
correct unit has been shipped.  
2. Verify that the unit is the correct model for the entering  
water temperature of the job.  
3. Do not remove the packaging until the unit is ready for  
installation.  
4. Verify that the refrigerant tubing is free of kinks or dents,  
and that it does not touch other unit components.  
5. Inspect all electrical connections. Be sure connections are  
clean and tight at the terminals.  
6. Compressors are internally spring-mounted. Compressors  
equipped with external spring vibration isolators must  
have bolts loosened and shipping clamps removed.  
8. Locate and verify any accessory kit located in compressor  
section.  
9. Remove any access panel screws that may be difficult to  
remove once unit is installed.  
Step 3 Location of Unit The following guide-  
lines should be considered when choosing a location for  
WSHP. Refer to Fig. 1 and 2 for unit dimensional data:  
• Provide sufficient space for water, electrical and duct  
connections  
• Locate unit in an area that allows for easy access and  
removal of filter and access panels  
• Allow enough space for service personnel to perform  
maintenance  
Table 1 Physical Data Aquazone50RTG03-20 Units  
UNIT 50RTG  
OPERATING WEIGHT (lb)  
SHIPPING WEIGHT (lb)  
03  
735  
750  
04  
785  
800  
05  
835  
850  
07  
880  
900  
08  
1080  
1100  
10  
1125  
1150  
12  
1175  
1200  
15  
1770  
1800  
20  
1960  
2000  
REFRIGERANT TO AIR HEAT EXCHANGER  
Face Area (sq ft)  
5
5
5
7.5  
9.3  
9.3  
10.5  
20  
20  
Rows Deep  
2
3
3
3
3
3
3
4
4
3
3
3
3
3
3
3
3
3
Copper Tube Size (in.)  
No. Fins per Inch  
REFRIGERANT CHARGE R-22/Ckt (oz)  
NUMBER OF CIRCUITS  
/
8
/
8
/
/
/
8
/
8
/
/
/
8
8
8
8
8
12  
52  
1
12  
68  
1
12  
86  
1
12  
132  
1
12  
68  
2
12  
86  
2
12  
88  
2
12  
141  
2
12  
160  
2
BLOWER DATA  
Diameter (qty-in.)  
Width (in.)  
1-10  
6
1-10  
6
1-10  
10  
1-12  
11  
1-15  
11  
1-15  
11  
1-15  
11  
2-15  
11  
2-15  
11  
FILTER DATA  
Size (in.)  
Quantity  
16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20 16 x 20  
10  
4
4
4
4
6
6
6
6
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER LOOP APPLICATIONS — Water loop applications  
usually include a number of units plumbed to a common pip-  
ing system. Maintenance to any of these units can introduce air  
into the piping system. Therefore, air elimination equipment  
comprises a major portion of the mechanical room plumbing.  
The flow rate is usually set between 2.25 and 3 gpm per ton  
of cooling capacity. For proper maintenance and servicing,  
pressure-temperature (P/T) ports are necessary for temperature  
and flow verification.  
Step 4 Mounting the Unit For proper opera-  
tion, units must be mounted on a roof curb as shown in Fig. 3.  
Follow these guidelines when installing the roof curb:  
1. Set unit on curb.  
2. Align unit so that its return and supply air direction match  
the return and supply air opening in the roof curb frame.  
3. Run both the return and supply loop piping, as well as the  
electrical supply line, through the pipe chase provided in  
the curb.  
In addition to complying with any applicable codes, consid-  
er the following for system piping:  
Step 5 Condensate Drain  
• Piping systems utilizing water temperatures below  
1. Install a condensate trap at each unit with the top of  
the trap positioned below the unit condensate drain  
connection.  
1
50 F require /2-in. closed cell insulation on all piping  
surfaces to eliminate condensation.  
• All plastic to metal threaded fittings should be avoided  
due to the potential to leak. Use a flange fitted substitute.  
• Teflon tape thread sealant is recommended to minimize  
internal fouling of the heat exchanger.  
• Use backup wrench. Do not overtighten connections.  
• Route piping to avoid service access areas to unit.  
• The piping system should be flushed prior to operation to  
remove dirt and foreign materials from the system.  
2. Design the length of the trap (water seal) based on the  
amount of positive or negative pressure on the drain pan.  
As a rule, 1 in. of trap is required for each inch of nega-  
tive pressure on the unit.  
Note that condensate is allowed to drain onto the roof.  
Step 6 Piping Connections Depending on the  
application, there are 3 types of WSHP piping systems to  
choose from: water loop, ground-water and ground loop. Refer  
to Piping Section of Carrier System Design Manual for addi-  
tional information.  
GROUND-WATER APPLICATIONS — In addition to com-  
plying with any applicable codes, consider the following for  
system piping:  
All WSHP units use low temperature soldered female pipe  
thread fittings for water connections to prevent annealing and  
out-of-round leak problems which are typically associated with  
high temperature brazed connections. Refer to Table 1 for con-  
nection sizes. When making piping connections, consider the  
following:  
• Install shut-off valves for servicing.  
• Install pressure-temperature plugs to measure flow and  
temperature.  
• Boiler drains and other valves should be connected using  
a “T” connector to allow acid flushing for the heat  
exchanger.  
• Do not overtighten connections.  
• Route piping to avoid service access areas to unit.  
• Use PVC SCH80 or copper piping material.  
NOTE: PVC SCH40 should not be used due to system high  
pressure and temperature extremes.  
• Use a backup wrench when making screw connections to  
unit to prevent internal damage to piping.  
• Insulation may be required on piping to avoid condensa-  
tion in the case where fluid in loop piping operates at  
temperatures below dew point of adjacent air.  
• Piping systems that contain steel pipes or fittings may  
be subject to galvanic corrosion. Dielectric fittings may  
be used to isolate the steel parts of the system to avoid  
galvanic corrosion.  
Water Supply and Quantity — Check water supply. Water  
supply should be plentiful and of good quality. See Table 2 for  
water quality guidelines.  
IMPORTANT: Failure to comply with the above required  
water quality and quantity limitations and the closed-  
system application design requirements may cause damage  
to the tube-in-tube heat exchanger that is not the responsi-  
bility of the manufacturer.  
50 RTG  
UNIT  
In all applications, the quality of the water circulated  
through the heat exchanger must fall within the ranges listed in  
the Water Quality Guidelines table. Consult a local water treat-  
ment firm, independent testing facility, or local water authority  
for specific recommendations to maintain water quality within  
the published limits.  
GROUND-LOOP APPLICATIONS — Temperatures between  
25 to 110 F and a cooling capacity of 2.25 to 3 gpm of flow per  
ton is recommended. In addition to complying with any appli-  
cable codes, consider the following for system piping:  
• Piping materials should be limited to only polyethylene  
fusion in the buried sections of the loop.  
• Galvanized or steel fittings should not be used at any  
time due to corrosion.  
FLASHING  
GASKET  
ROOF  
• All plastic to metal threaded fittings should be avoided  
due to the potential to leak. Use a flange fitted substitute.  
• Do not overtighten connections.  
• Route piping to avoid service access areas to unit.  
• Pressure-temperature (P/T) plugs should be used to mea-  
sure flow of pressure drop.  
CURB  
Fig. 3 50RTG Curb Installation  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
AB = 452 volts  
BC = 464 volts  
AC = 455 volts  
Step 7 Electrical Wiring  
452 + 464 + 455  
3
Average Voltage =  
To avoid possible injury or death due to electrical shock,  
open the power supply disconnect switch and secure it in  
an open position during installation.  
1371  
3
=
=
457  
Use only copper conductors for field-installed electrical  
wiring. Unit terminals are not designed to accept other  
types of conductors.  
Determine maximum deviation from average voltage:  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent voltage imbalance.  
All field installed wiring, including the electrical ground,  
MUST comply with the National Electrical Code (NEC) as  
well as applicable local codes. In addition, all field wiring must  
conform to the Class II temperature limitations described in the  
NEC.  
Refer to unit wiring diagram Fig. 4 for a schematic of the  
field connections which must be made by the installing (or  
electrical) contractor.  
Consult the unit wiring diagram located on the inside of the  
compressor access panel to ensure proper electrical hookup.  
The installing (or electrical) contractor must make the field  
connections when using field-supplied disconnect.  
Operating voltage must be the same voltage and phase as  
shown in Electrical Data shown in Table 3.  
Make all final electrical connections with a length of flexi-  
ble conduit to minimize vibration and sound transmission to  
the building.  
SUPPLY VOLTAGE — Operating voltage to unit must be  
within voltage range indicated on unit nameplate.  
On 3-phase units, voltages under load between phases must  
be balanced within 2%. Use the following formula to deter-  
mine the percentage voltage imbalance:  
7
% Voltage Imbalance = 100 x  
457  
= 1.53%  
This amount of phase imbalance is satisfactory as it is  
below the maximum allowable 2%.  
Operation on improper line voltage or excessive phase  
imbalance constitutes abuse and may cause damage to electri-  
cal components.  
NOTE: If more than 2% voltage imbalance is present, contact  
local electric utility.  
208-VOLT OPERATION — All 208-230 volt units are factory  
wired for 208 volts. The transformers may be switched to  
230-volt operation (as illustrated on the wiring diagram) by  
switching the red (208 volt) wire with the orange (230 volt)  
wire at the L1 terminal.  
BLOWER SELECTION — All water source heat pumps are  
factory set with the appropriate motor and sheave combination  
to achieve the desired airflow performance. Performance is  
selected by matching the desired performance with the appro-  
priate region in Tables 4-12. Per the table notes, regions desig-  
nated by A, B, C and D represent motor drive options.  
% Voltage Imbalance  
max voltage deviation from average voltage  
= 100 x  
average voltage  
NOTE: Factory-installed sheaves are field adjustable. Refer to  
Tables 4-12 for adjustment points.  
Example: Supply voltage is 460-3-60.  
Table 2 Water Quality Guidelines  
CONDITION  
pH  
Total Hardness Calcium and magnesium carbonate should not exceed 20 grains per gallon (350 ppm).  
ACCEPTABLE LEVEL  
7 to 9 range for copper. Cupro-nickel may be used in the 5 to 9 range.  
Iron Oxides  
Iron Bacteria  
Corrosion*  
Less than 1 ppm.  
No level allowable.  
Max Allowable Level  
0.5 ppm  
Coaxial Metal  
Ammonia, Ammonium Hydroxide  
Ammonium Chloride, Ammonium Nitrate  
Ammonium Sulfate  
Chlorine/Chlorides  
Hydrogen Sulfide†  
Cu  
Cu  
0.5 ppm  
0.5 ppm  
Cu  
CuNi  
0.5 ppm  
None Allowable  
Brackish  
Use Cupro-nickel heat exchanger when concentrations of calcium or sodium chloride are greater  
than 125 ppm are present. (Seawater is approximately 25,000 ppm.)  
*If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion  
problems exists.  
†Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken.  
Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate  
solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause sys-  
tem problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality  
of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral  
water contains a pH of 7.0.  
NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
50RTG03-07 WITH ECONOMIZER AND COMPLETE C CONTROLLER  
WHT  
GRN  
BLK  
Ground  
115V / 1PH  
Field  
Wiring  
BLK  
L1  
L2  
L3  
BLK  
BLK  
L1  
L1  
L2  
L3  
T1  
T3  
BLK  
BLK  
Power Supply  
Refer to Data Plate  
Use copper conductors only.  
BLK  
BLK  
BLK  
BLK  
L2  
L3  
GFI  
(Optional)  
T2  
Compressor  
Disconnect  
OR  
CB  
CC  
Power  
Distribution  
Block  
BLK  
BLK  
(Optional)  
BLK  
BLK  
BLK  
BLK  
Blower Motor  
ES  
BC  
Logic Module  
(Damper Actuator)  
MAS  
-
+
GRY  
BRN  
150 Ohm  
GRY  
BLU  
600 Ohm  
TR1  
TR  
+
+
5
2
1
4
3
T1  
P1  
BRN  
SO  
4
SR  
T
P
LAR  
4
3
GRY  
VIO  
RED  
(208V)  
2
YEL  
BLK  
SEE  
BRN  
YEL  
YEL  
VIO or  
NOTE 7  
BC  
3
6
BLK/RED  
SEE  
NOTE 7  
CC  
(460V)  
BLU  
or  
BLK  
BRN  
BRN  
GRY  
YEL  
8
OAT  
BRN  
R
B
CC  
BRG  
BR  
CCG  
7
SEE  
NOTE 3  
WHT  
TAN  
BLU  
LAR  
24V  
CB  
C
R
ORG  
230V  
ECR  
Test Pins  
BRN  
P2  
YEL  
Compressor  
Relay  
1
RED  
HP  
HP  
RED  
BLU  
BRN  
GRY  
GRY  
VIO  
2
3
Y
LOC  
FP1  
P1  
SEE  
NOTE 4  
LOC  
FP1  
Compressor  
Cooling  
4
5
Y
O
Y
W
O
G
Dip Switch  
FP1  
FP2  
PM  
Not Used  
1
2
RVS  
6
7
Off On  
Fan  
FP2  
FP2  
RV  
BRN  
ORG  
G
R
C
L
VIO  
8
9
24 VAC  
Common  
Alarm  
BRN  
ECR  
R
C
Status  
LED  
G
ORG  
10  
JW1  
Not Used  
AL1  
AL2  
CO 12  
P3  
C
Typical T-stat  
SEE NOTE 5  
SEE NOTE 6  
Microprocessor  
Control Logic  
Alarm  
Relay  
A
24V  
DC  
EH1  
EH2  
CO  
NOTES:  
1. Compressor and blower motor thermally protected  
internally.  
LEGEND  
2. All wiring to the unit must comply with NEC and  
local codes.  
AL  
Alarm Relay Contacts  
Blower Mtr Contactor  
Circuit Breaker  
Compressor Contactor  
Economizer Relay  
Auxiliary Heat Stage 1  
Auxiliary Heat Stage 2  
Enthalpy Sensor  
PM  
P1  
RVS  
Performance Monitor  
3. 208/230  
v
transformers will be connected for  
BC  
Field Wiring Terminal Block  
Reversing Valve Solenoid  
208 v operations. For 230 v operations, discon-  
nect Red lead at L1, and attach Orange lead to  
L1. Close open end of Red Lead with insulating  
tape.  
CB  
CC  
ECR  
EH1  
EH2  
ES  
FP1  
FP2  
HP  
JW1  
LAR  
LOC  
MAS  
NEC  
OAT  
Relay Contactor Coil  
Solenoid Coil  
4. FP1 jumper provides freeze protection for  
WATER. When using ANTI-FREEZE solutions, cut  
FP1 jumper.  
5. Typical thermostat wiring shown. Refer to thermo-  
stat Installation Instructions for wiring to the unit.  
6. 24 v alarm signal shown. For dry alarm contact,  
cut JW1 jumper and dry contact will be available  
between AL1 and AL2.  
7. Transformer secondary ground via Complete C  
board standoffs and screws to control box.  
(Ground available from top two standoffs as  
shown.)  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
High Pressure Switch  
Thermistor  
Ground  
Jumper, Alarm Mode  
Low Ambient Relay  
Loss-of-Charge Pressure Switch  
Mixed Air Sensor  
Field Line Voltage Wiring  
Field Low Voltage Wiring  
Printed Circuit Trace  
National Electrical Code  
Outside Air Thermostat  
Fig. 4 Typical AquazoneComplete C Control Wiring  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 50RTG Electrical Data  
POWER  
SUPPLY  
COMPRESSOR  
(each)  
BLOWER  
MOTOR  
FLA  
MAX. FUSE  
OR HACR  
BREAKER  
MINIMUM  
CIRCUIT  
AMPACITY  
UNIT  
50RTG  
Voltage  
Hz  
Ph  
RLA  
LRA  
QTY  
HP  
QTY  
208/230  
460  
208/230  
460  
575  
60  
60  
60  
60  
60  
3
3
3
3
3
10.7  
5.0  
13.9  
6.4  
5.3  
63.0  
31.0  
88.0  
44.0  
34.0  
1
1
1
1
1
1
1
1
1
1
3.6  
1.8  
3.6  
1.8  
1.6  
1
1
1
1
1
25 Amp  
15 Amp  
30 Amp  
15 Amp  
15 Amp  
17.0  
8.1  
21.0  
9.8  
8.2  
03  
04  
208/230  
460  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
60  
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
20.0  
7.5  
123.0  
49.5  
40.0  
156.0  
70.0  
54.0  
88.0  
44.0  
34.0  
123.0  
49.5  
40.0  
123.0  
62.0  
50.0  
156.0  
70.0  
54.0  
232.0  
116.0  
97.0  
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
5
5
5
3.6  
1.8  
1.6  
6.2  
3.1  
2.3  
6.2  
3.1  
2.3  
6.2  
3.1  
2.3  
9.2  
4.3  
3.4  
9.2  
4.3  
3.4  
13.2  
6.6  
5.6  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
45 Amp  
15 Amp  
15 Amp  
50 Amp  
25 Amp  
20 Amp  
50 Amp  
20 Amp  
15 Amp  
70 Amp  
25 Amp  
20 Amp  
70 Amp  
35 Amp  
25 Amp  
70 Amp  
35 Amp  
30 Amp  
125 Amp  
60 Amp  
45 Amp  
28.6  
11.2  
9.6  
32.1  
15.6  
12.6  
37.5  
17.5  
14.2  
51.2  
20.0  
16.7  
52.6  
26.8  
21.0  
55.8  
26.8  
21.9  
88.1  
44.9  
34.4  
05  
07  
08  
10  
12  
15  
20  
575  
6.4  
208/230  
460  
575  
208/230  
460  
575  
208/230  
460  
575  
208/230  
460  
575  
208/230  
460  
575  
208/230  
460  
575  
20.7  
10.0  
8.2  
13.9  
6.4  
5.3  
20.0  
7.5  
6.4  
19.3  
10.0  
7.8  
20.7  
10.0  
8.2  
33.3  
17.0  
12.8  
LEGEND  
Full Load Amps  
FLA  
HACR Heating, Air Conditioning and Refrigeration  
LRA  
RLA  
Lock Rotor Amps  
Rated Load Amps  
NOTE: Contact factory for oversize blower motor electrical data.  
Table 4 50RTG03 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
BHP  
RPM  
0.12  
0.14  
0.17  
667  
4.5  
0.19  
691  
4.0  
0.23  
721  
3.5  
0.26  
752  
3.00  
0.31  
777  
2.5  
0.35  
807  
2.5  
0.19  
724  
3.5  
0.22  
745  
3.0  
0.21  
779  
2.5  
0.24  
798  
2.5  
0.23  
833  
1.5  
0.26  
849  
1.5  
0.31  
870  
1.0  
0.35  
892  
1.0  
0.40  
911  
0.5  
0.44  
935  
0.0  
0.50  
963  
2.5  
0.26  
885  
1.0  
0.30  
898  
0.5  
0.33  
917  
0.5  
0.37  
937  
0.0  
0.42  
954  
2.5  
0.47  
976  
2.0  
0.53  
1003  
2.0  
0.29  
933  
0.0  
0.32  
946  
0.0  
0.36  
963  
2.5  
0.41  
982  
2.0  
0.45  
997  
2.0  
0.51  
1017  
1.4  
0.56  
1041  
1.5  
0.31  
980  
2.0  
0.35  
991  
2.0  
0.39  
1008  
2.0  
0.44  
1025  
1.5  
0.33  
1024  
1.5  
0.37  
1035  
1.5  
0.42  
1051  
1.0  
0.46  
1066  
1.0  
0.52  
1079  
1.0  
0.57  
1096  
0.5  
0.64  
1118  
0.5  
975  
1050  
1125  
1200  
1275  
1350  
1425  
550 B 609  
Turns Out  
5.0  
3.5  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
0.14  
580  
4.0  
0.18  
619  
3.5  
0.22  
658  
4.5  
0.26  
688  
4.0  
0.29  
721  
3.5  
0.4  
763  
3.0  
0.17  
636  
3.0  
0.20  
670  
4.5  
0.24  
705  
4.00  
0.29  
732  
3.5  
0.32  
764  
3.0  
0.40  
803  
2.5  
0.25  
0.28  
772 A 821  
3.0  
2.0  
0.29  
799  
2.5  
0.33  
822  
2.0  
0.39  
850  
1.5  
0.44  
883  
1.0  
0.32  
846  
1.5  
0.36  
867  
1.5  
0.41  
893  
1.0  
0.46  
923  
0.5  
0.48  
C 1038  
1.5  
0.54  
1057  
1.0  
0.42  
843  
1.5  
0.61  
1080  
1.0  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. For applications requiring higher static pressures, contact your local representative.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 50RTG04 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
BHP  
RPM  
0.26  
633  
5
0.30  
694  
3.5  
0.33  
755  
4.5  
0.40  
782  
4.0  
0.48  
819  
3.5  
0.57  
851  
3.0  
0.66  
887  
2.0  
0.76  
923  
1.5  
0.89  
961  
1.0  
0.36  
812  
3.5  
0.43  
836  
3.0  
0.52  
871  
2.5  
0.40  
869  
2.5  
0.46  
890  
2.0  
0.55  
922  
1.5  
0.42  
925  
1.5  
0.50  
943  
1.0  
0.58  
970  
0.5  
0.67  
995  
0.0  
0.78  
1024  
3.5  
0.89  
1053  
3.0  
1.02  
1086  
2.5  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
Turns Out  
0.33 B0.36  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
0.53  
995  
0.5  
Operation Not Recommended  
668  
4
725  
3.0  
0.45  
766  
4.5  
0.54  
801  
3.5  
0.62  
840  
3.0  
0.72  
878  
2.5  
0.85  
919  
1.5  
0.418  
712  
3.0  
0.506  
750  
4.5  
0.572  
792  
4.0  
0.671  
832  
3.0  
0.62  
1017  
3.5  
0.65  
1063  
3.0  
0.61 A 0.64  
0.70  
1040  
3.5  
0.81  
1068  
3.0  
0.75  
1083  
1.5  
0.86  
1110  
2.5  
0.78  
1125  
2.0  
0.89  
1152  
1.5  
0.83  
1166  
1.5  
0.94  
1194  
1.0  
900  
2.0  
948  
1.0  
0.74  
979  
0.5  
0.85  
1010  
0.0  
0.98  
1045  
3.0  
C
0.70  
934  
1.5  
0.80  
967  
1.0  
0.94  
1003  
0.0  
0.94  
1095  
2.5  
1.07  
1127  
2.0  
0.97  
1136  
2.0  
1.11  
1166  
1.5  
1.01  
1176  
1.5  
1.16  
1204  
1.0  
1.06  
1219  
1.0  
1.20  
1242  
0.5  
D
0.80  
875  
2.5  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
Table 6 50RTG05 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
BHP  
RPM  
0.37  
797  
3.5  
0.42  
845  
2.5  
0.48  
882  
1.5  
0.56  
923  
3.5  
0.65  
967  
3.0  
0.74  
1005  
2.0  
0.84  
1047  
1.5  
0.96  
1091  
4.5  
0.45  
892  
1.5  
0.53  
927  
3.5  
0.61  
966  
3.0  
0.69  
1007  
2.0  
0.78  
1044  
1.5  
0.89  
1084  
1.0  
1.00  
1126  
4.0  
0.50  
938  
3.0  
0.56  
971  
2.5  
0.65  
1008  
2.0  
0.54  
984  
2.5  
0.61  
1015  
2.0  
0.69  
1049  
1.5  
0.58  
1029  
1.5  
0.65  
1057  
1.0  
0.74  
1090  
0.5  
0.84  
1126  
0.5  
0.94  
1158  
0.0  
1.05  
1193  
3.0  
1.17  
1231  
2.5  
0.63  
1072  
1.0  
0.70  
1099  
0.5  
0.78  
1131  
0.5  
0.88  
1164  
0.0  
0.98  
1195  
3.0  
1.09  
1229  
2.5  
1.22  
1265  
2.0  
0.67  
1114  
0.5  
0.75  
1140  
0.5  
0.84  
1170  
0.0  
0.94  
1203  
3.0  
Operation Not  
Recommended  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
Turns Out  
0.44 B  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
0.79  
1180  
0.0  
836  
2.5  
0.52  
880  
1.5  
0.61  
926  
3.5  
0.69  
966  
3.0  
0.79  
1009  
2.0  
0.88  
1208  
3.0  
0.98  
1240  
2.5  
0.94  
1246  
2.5  
C
0.74 A0.78  
1.03  
1277  
2.0  
1047  
1.5  
1087  
1.0  
0.88  
1120  
0.5  
0.99  
1157  
3.5  
1.11  
1196  
3.0  
0.84  
1082  
1.0  
0.94  
1120  
0.5  
1.06  
1161  
3.5  
1.03  
1.09  
1268  
2.0  
1.14  
1303  
1.5  
1231 D  
2.5  
1.14  
1264  
2.0  
1.20  
1298  
1.5  
1.25  
1333  
1.0  
0.9  
1055  
1.0  
1.28  
1299  
1.5  
1.33  
1332  
1.0  
1.39  
1365  
0.5  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 50RTG07 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
BHP  
RPM  
0.42 0.46 0.51  
0.56  
750  
4.5  
0.73  
793  
3.5  
0.88  
830  
3.0  
0.62  
792  
3.5  
0.78  
831  
3.0  
0.95  
865  
2.0  
1.12  
901  
1.5  
1.33  
939  
0.5  
1.56  
978  
5.0  
1.90  
1029  
4.0  
0.67  
832  
2.5  
0.85  
869  
2.0  
1.00  
900  
1.5  
1.19  
933  
0.5  
1.40  
970  
5.0  
1.64  
1007  
4.5  
1.98  
1056  
3.5  
0.73  
870  
2.0  
0.90  
905  
1.5  
1.07  
935  
0.5  
1.25  
965  
0.0  
1.47  
1000  
4.5  
1.72  
1035  
4.0  
2.06  
1082  
3.0  
0.78  
908  
1.5  
0.97  
941  
0.5  
1.14  
969  
0.0  
1.33  
997  
4.5  
1.54  
1030  
4.0  
1.79  
1064  
3.5  
2.13  
1109  
2.5  
1950  
2200  
2400  
2600  
2800  
3000  
3250  
620  
4.5  
664  
3.5  
707  
2.5  
Operation Not Recommended  
Turns Out  
B
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
0.56 0.62 0.67  
1.03  
975  
5.0  
1.21  
1002  
4.5  
1.40  
1029  
4.0  
1.62  
1059  
3.5  
1.87  
1091  
3.0  
2.22  
1135  
2.5  
1.10  
1007  
3.0  
1.17  
1038  
2.5  
675  
3
716  
2.0  
755  
4.5  
0.70 0.76 0.83  
1.28  
1034  
4.0  
1.34  
1066  
3.5  
1.41  
1097  
3.0  
721  
2.0  
758  
4.5  
795  
3.5  
A
C
0.87 0.94 0.99  
1.06  
868  
2.0  
1.27  
908  
1.5  
1.47  
1060  
3.5  
1.55  
1090  
3.0  
1.63  
1120  
2.5  
1.69  
1149  
2.0  
1.77  
1178  
1.5  
2.01  
1203  
1.0  
2.28  
1228  
1.0  
2.65  
1263  
0.5  
765  
4
800  
3.5  
835  
3.0  
1.07 1.13 1.20  
1.69  
1089  
3.0  
1.77  
1118  
2.5  
1.86  
1147  
2.0  
1.94  
1175  
1.5  
812  
3.5  
845  
2.5  
877  
2.0  
1.28 1.35 1.42  
1.50  
949  
0.5  
1.83  
1001  
4.5  
1.95  
1119  
2.5  
2.30  
1161  
2.0  
2.02  
1147  
2.0  
2.39  
1187  
1.5  
2.11  
1174  
1.5  
2.20  
1202  
1.0  
857  
2.5  
889  
1.5  
919  
1.0  
2.48D2.56  
1.60 1.67 1.75  
915  
1.0  
945  
0.5  
974  
5.0  
1212  
1.0  
1238  
1.0  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
Table 8 50RTG08 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
BHP  
RPM  
0.40  
482  
4.5  
0.51  
514  
4
0.64  
549  
2.5  
0.81  
588  
5
1.00  
623  
3.5  
1.20  
657  
2.5  
1.47  
699  
1.5  
0.45  
521  
3.5  
0.56  
550  
2.5  
0.69  
583  
4.5  
0.88  
619  
3.5  
1.07  
652  
3.0  
1.28  
685  
2.0  
1.56  
725  
1.0  
0.50  
559  
2.0  
0.62  
585  
4.5  
0.76  
615  
4.0  
0.55  
594  
4.5  
0.67  
619  
3.5  
0.83  
647  
3.0  
1.02  
679  
2.0  
1.21  
709  
1.5  
1.43  
739  
0.5  
1.73  
775  
5.0  
0.61  
629  
3.5  
0.74  
651  
3.0  
0.88  
677  
2.0  
1.09  
707  
1.5  
1.29  
736  
0.5  
1.51  
764  
5.0  
1.82  
799  
4.5  
0.66  
661  
2.5  
0.79  
683  
2.0  
0.95  
707  
1.5  
1.16  
735  
0.5  
1.36  
763  
5.0  
1.60  
790  
4.5  
1.89  
823  
4.0  
0.72  
693  
1.5  
0.86  
713  
1.0  
1.01  
736  
0.5  
1.23  
763  
5.0  
1.44  
789  
4.5  
1.67  
815  
4.0  
1.98  
847  
3.5  
0.77  
723  
1.0  
0.91  
742  
0.5  
1.08  
764  
5.0  
1.30  
789  
4.5  
1.52  
814  
4.0  
1.75  
839  
3.5  
2.07  
870  
3.0  
0.83  
751  
0.0  
0.98  
770  
4.5  
1.14  
791  
4.5  
1.38  
815  
4.0  
1.60  
839  
3.5  
1.84  
863  
3.0  
2.16  
892  
2.5  
0.87  
779  
4.5  
1.05  
797  
4.0  
1.22  
818  
4.0  
1.45  
841  
3.5  
1.67  
863  
3.0  
1.91  
886  
2.5  
2.24  
915  
2.0  
0.91  
806  
4.0  
1.10  
823  
3.5  
1.29  
843  
3.5  
0.98  
832  
3.5  
1.16  
848  
3.0  
1.35  
868  
3.0  
1.03  
858  
3.0  
1.21  
872  
2.5  
1.42  
894  
2.5  
1.67  
913  
2.0  
1.90  
934  
1.5  
2.17  
954  
1.0  
1.10  
883  
2.5  
1.27  
895  
2.0  
1.49  
915  
2.0  
1.74  
936  
1.5  
1.99  
956  
1.0  
2.26  
976  
0.5  
2.61  
1001  
0.0  
2400  
2650  
2900  
3200  
3450  
3700  
4000  
Turns Out  
B
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
A
1.52C1.60  
0.95  
649  
3.0  
865  
3.0  
890  
2.5  
1.83  
911  
2.0  
2.08  
932  
1.5  
1.14  
681  
2.0  
1.35  
712  
1.0  
1.64  
750  
0.0  
1.75  
887  
2.5  
2.00  
909  
2.0  
2.33  
937  
1.5  
2.42D2.51  
958  
1.0  
980  
0.5  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 50RTG10 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
BHP  
RPM  
0.69  
563  
4.5  
0.76  
596  
3.5  
0.83  
628  
2.5  
1.03  
664  
1.5  
1.28  
703  
4.5  
1.64  
750  
3.5  
1.99  
794  
4.5  
2.52  
848  
3.5  
2.96  
889  
3.0  
0.89  
658  
1.5  
1.10  
693  
4.5  
1.35  
730  
4.0  
0.96  
688  
1.0  
1.18  
721  
4.0  
1.43  
756  
3.5  
1.82  
799  
2.5  
2.18  
840  
4.0  
2.71  
891  
3.0  
1.02  
718  
4.0  
1.24  
748  
3.5  
1.51  
782  
2.5  
1.89  
823  
2.0  
2.27  
863  
3.5  
2.81  
912  
2.5  
1.09  
746  
3.5  
1.32  
775  
3.0  
1.58  
807  
2.0  
1.98  
847  
4.0  
2.35  
885  
3.0  
2.90  
933  
2.0  
1.16  
773  
3.0  
1.39  
801  
2.5  
1.66  
832  
1.5  
2.07  
870  
3.5  
1.22  
800  
2.5  
1.46  
827  
2.0  
1.75  
856  
1.0  
2.16  
892  
3.0  
1.29  
826  
2.0  
1.54  
852  
1.0  
1.83  
880  
0.5  
2.24  
915  
2.5  
1.36  
851  
1.5  
1.62  
876  
0.5  
1.90  
903  
0.0  
2.33  
937  
2.0  
1.43  
876  
0.5  
1.69  
900  
0.0  
1.99  
926  
2.5  
2.42  
958  
1.5  
1.50  
900  
0.0  
1.57  
923  
2.5  
1.85  
946  
2.0  
2.16  
971  
1.5  
2.61  
1001  
0.5  
3000  
3300  
3600  
4000  
4300  
4700  
5000  
Turns Out  
B0.96  
0.89  
604  
3
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Tur ns Out  
BHP  
RPM  
Tur ns Out  
BHP  
RPM  
Tur ns Out  
1.77  
923  
2.5  
2.07  
949  
2.0  
635  
2.5  
1.20  
676  
1.0  
1.56  
725  
4.0  
1.90  
770  
3.0  
2.42  
825  
4.0  
2.86  
868  
3.5  
C
1.12  
647  
2.0  
1.47  
699  
4.5  
1.82  
746  
3.5  
2.32  
803  
4.5  
A
1.73  
775  
3.0  
2.09  
817  
4.5  
2.61  
869  
3.5  
2.51  
980  
1.0  
2.93  
1012  
0.5  
2.73D2.83  
2.45  
907  
2.5  
2.54  
929  
2.0  
2.64  
950  
1.5  
971  
1.0  
991  
1.0  
Operation Not Recommended  
2.76  
847  
3.5  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
Table 10 50RTG12 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
BHP  
RPM  
1.02  
609  
5.5  
1.10 1.18  
1.25  
695  
2.5  
1.62  
742  
5.5  
1.33  
722  
1.5  
1.71  
767  
4.5  
2.13  
812  
3.5  
2.63  
854  
2.5  
3.25  
908  
4.5  
3.93  
957  
3.5  
4.70  
1007  
2.5  
1.41  
748  
5.5  
1.78  
792  
4.0  
2.23  
835  
3.0  
2.73  
876  
1.5  
3.36  
928  
4.0  
4.04  
976  
3.0  
4.82  
1025  
2.0  
1.49  
774  
4.5  
1.87  
816  
3.5  
2.32  
858  
2.0  
2.83  
897  
1.0  
3.47  
948  
3.5  
4.16  
995  
2.5  
4.95  
1042  
1.5  
1.56  
800  
3.5  
1.96  
839  
2.5  
2.41  
879  
1.5  
2.93  
918  
4.5  
3.58  
968  
3.5  
4.27  
1013  
2.0  
1.64  
825  
3.0  
2.05  
863  
2.0  
2.51  
901  
5.0  
3.03  
938  
4.0  
3.69  
987  
3.0  
4.39  
1031  
1.5  
1.72  
849  
2.5  
2.13  
886  
1.5  
2.61  
923  
4.5  
3.12  
959  
3.5  
1.80  
873  
1.5  
2.22  
908  
4.5  
2.70  
944  
4.0  
3.23  
978  
3.0  
1.88  
896  
1.0  
1.97  
919  
4.5  
2.40  
952  
3.5  
2.89  
985  
3.0  
3.43  
1018  
2.0  
4.11  
1062  
1.0  
2.05  
942  
4.0  
2.49  
973  
3.0  
2.98  
1006  
2.5  
3.54  
1037  
1.5  
3600  
4000  
4400  
4800  
5200  
5600  
6000  
639  
4.5  
667  
3.5  
Turns Out  
1.38B1.45  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
1.54  
717  
2.0  
2.31  
930  
4.0  
2.79  
965  
3.5  
664  
4.5  
691  
3.0  
C
1.77  
716  
2.0  
2.23  
765  
5.5  
2.82  
825  
4.5  
3.47  
879  
5.5  
1.86 1.96  
2.05  
789  
4.0  
2.53  
833  
3.0  
741  
5.5  
765  
4.5  
A
2.33 2.43  
3.33  
998  
2.5  
4.00  
1044  
1.5  
788  
4.0  
810  
3.5  
3.78D3.89  
2.93 3.04  
3.14  
888  
5.0  
3.81  
938  
4.0  
4.58  
989  
3.0  
846  
2.5  
867  
5.5  
1006  
2.5  
1025  
2.0  
4.62  
1067  
1.0  
3.58 3.70  
4.51  
1050  
1.5  
899  
5.0  
918  
4.5  
Operation Not  
Recommended  
4.20  
933  
4.0  
4.33 4.46  
952  
3.5  
970  
3.0  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 50RTG15 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
BHP  
RPM  
0.68  
465  
5.0  
0.87  
493  
4.0  
0.78  
506  
3.5  
0.98  
531  
3.0  
0.88  
545  
2.5  
1.09  
568  
2.0  
1.33  
595  
4.5  
1.62  
621  
4.0  
1.97  
654  
3.0  
2.34  
683  
2.5  
2.77  
714  
1.5  
0.98  
582  
4.5  
1.20  
603  
4.5  
1.45  
627  
4.0  
1.08  
617  
4.0  
1.31  
636  
3.5  
1.57  
659  
3.0  
1.88  
682  
2.5  
2.24  
711  
1.5  
2.64  
737  
1.0  
3.09  
766  
4.0  
1.17  
650  
3.5  
1.42  
669  
3.0  
1.71  
690  
2.0  
2.01  
712  
1.5  
2.39  
739  
1.0  
2.79  
764  
4.0  
3.26  
791  
3.5  
1.28  
681  
2.5  
1.52  
701  
2.0  
1.83  
720  
1.5  
2.15  
740  
1.0  
2.53  
766  
4.0  
2.95  
790  
3.5  
3.41  
816  
3.0  
1.39  
711  
2.0  
1.65  
732  
1.0  
1.94  
749  
4.5  
2.28  
768  
4.0  
2.67  
793  
3.5  
3.10  
815  
3.0  
3.58  
840  
2.5  
1.43  
740  
1.0  
1.76  
762  
4.0  
2.07  
777  
4.0  
2.42  
795  
3.5  
2.83  
819  
3.0  
3.26  
840  
2.5  
3.74  
864  
2.0  
1.54  
768  
4.0  
1.87  
791  
3.5  
1.65  
795  
3.5  
1.94  
819  
3.0  
1.76  
821  
3.0  
2.07  
846  
2.5  
2.44  
855  
2.0  
2.84  
871  
2.0  
3.26  
890  
1.5  
3.73  
911  
1.0  
4.25  
933  
0.5  
Operation Not  
Recommended  
4500  
5000  
5500  
6000  
6500  
7000  
7500  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
2.16  
872  
1.5  
2.31  
897  
1
B1.22  
2.20C2.31  
1.10  
525  
3.0  
2.51  
879  
1.5  
2.64  
902  
1
561  
2.0  
1.49  
589  
4.5  
1.83  
624  
4.0  
2.19  
654  
3.0  
804  
3.0  
830  
2.5  
2.71  
846  
2.5  
3.12  
868  
2.0  
3.56  
888  
1.5  
1.36  
556  
2.0  
1.69  
593  
4.5  
2.05  
625  
4.0  
2.46  
660  
3.0  
1.75  
652  
3.0  
2.10  
683  
2.5  
2.55  
821  
3.0  
2.97  
844  
2.5  
3.41  
864  
2.0  
2.97  
895  
1.0  
3.102  
918  
0.5  
A
3.41  
913  
1.0  
3.564  
936  
0.5  
2.49  
710  
2.0  
2.94  
740  
1.0  
3.88  
934  
0.5  
3.91D4.08  
2.62  
687  
2.5  
Operation Not  
Recommended  
887  
1.5  
910  
1.0  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
Table 12 50RTG20 Blower Performance  
EXTERNAL STATIC PRESSURE (in. wg)  
SCFM  
AIRFLOW  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
BHP  
RPM  
1.38  
560  
5.5  
1.51  
592  
4.0  
1.63  
624  
3.0  
2.10  
673  
5.0  
2.60  
711  
3.5  
3.27  
747  
2.5  
4.06  
803  
0.5  
4.97  
850  
4.0  
5.84  
881  
3.0  
1.76  
655  
5.5  
2.24  
702  
4.0  
2.75  
738  
3.0  
1.89  
685  
4.5  
2.39  
729  
3.0  
2.90  
764  
2.0  
2.02  
715  
3.5  
2.53  
757  
2.0  
3.06  
790  
1.0  
3.77  
821  
0.0  
4.61  
872  
3.5  
5.56  
914  
2.0  
2.16  
743  
2.5  
2.67  
783  
1.5  
3.22  
815  
0.0  
3.95  
844  
4.0  
4.79  
894  
3.0  
5.75  
935  
1.5  
2.30  
771  
1.5  
2.83  
809  
0.5  
3.38  
839  
4.5  
4.13  
867  
3.5  
4.97  
916  
2.0  
5.95  
955  
1.0  
6.89  
981  
0.0  
2.43  
797  
1.0  
2.97  
834  
4.5  
3.54  
863  
3.5  
4.30  
890  
3.0  
5.16  
937  
1.5  
6.15  
976  
0.5  
2.57  
823  
0.0  
3.12  
859  
3.5  
3.70  
887  
3.0  
4.47  
912  
2.0  
2.71  
849  
4.0  
3.28  
883  
3.0  
2.84  
874  
3.5  
3.34  
895  
2.5  
2.99  
897  
2.5  
3.50  
919  
2.0  
4.20  
957  
1.0  
5.01  
978  
0.5  
3.12  
921  
2.0  
3.65  
941  
1.5  
4.27  
966  
0.5  
6,000  
6,600  
7,200  
8,000  
8,600  
9,300  
10,000  
Turns Out  
1.83B1.73  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
BHP  
RPM  
Turns Out  
614  
3.5  
644  
2.0  
2.44  
684  
4.5  
3.10  
722  
3.5  
3.88  
780  
1.5  
4.77  
828  
4.5  
5.63  
859  
3.5  
3.86C4.03  
2.30  
656  
5.5  
2.94  
696  
4.0  
3.71  
756  
2.0  
4.59  
805  
0.5  
910  
2.5  
933  
1.5  
4.83  
956  
1.0  
3.44A3.61  
4.65  
935  
1.5  
5.53  
979  
0.5  
772  
1.5  
797  
1.0  
4.42  
849  
4.0  
5.36  
893  
2.5  
6.26  
922  
2.0  
4.25  
827  
4.5  
5.16  
872  
3.5  
6.05  
901  
2.5  
5.35  
958  
1.0  
Operation Not  
Recommended  
6.47D6.68  
5.43  
838  
4.5  
942  
1.5  
962  
0.5  
LEGEND  
BHP  
Brake Horsepower  
SCFM Standard Cubic Feet Per Minute  
NOTES:  
1. Fan BHP includes drive losses.  
2. Region “A” is standard drive package.  
3. Regions “B” and “C” require optional drive packages.  
4. Region “D” represents oversized motor and special sheaves.  
5. For applications requiring higher static pressures, contact your local representative.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 8 Low Voltage Wiring  
THERMOSTAT CONNECTIONS The thermostat should  
be wired directly to the Aquazonecontrol board. See  
Fig. 4 and 5.  
WATER FREEZE PROTECTION The Aquazone control  
allows the field selection of source fluid freeze protection  
points through jumpers. The factory setting of jumper JW3  
(FP1) is set for water at 30 F. In earth loop applications, jumper  
JW3 should be clipped to change the setting to 13 F when  
using antifreeze in colder earth loop applications. See Fig. 6.  
AIR COIL FREEZE PROTECTION The air coil freeze  
protection jumper JW2 (FP2) is factory set for 30 F and should  
not need adjusting, unless using anti-freeze.  
ACCESSORY CONNECTIONS Terminal labeled A on  
the control is provided to control accessory devices such as  
water valves, electronic air cleaners, humidifiers, etc. This sig-  
nal operates with the compressor terminal. See Fig. 7. Refer to  
the specific unit wiring schematic for details.  
NOTE: The A terminal should only be used with 24 volt  
signals not line voltage signals.  
AQUAZONE CONTROL (C Control Shown)  
WATER SOLENOID VALVES Water solenoid valves may  
be used on primary secondary pump and ground water installa-  
tions. A typical well water control valve wiring which can  
limit waste water in a lockout condition is shown in Fig. 7. A  
slow closing valve may be required to prevent water hammer.  
When using a slow closing valve, special wiring conditions  
need to be considered. The valve takes approximately 60 sec-  
onds to open (very little water will flow before 45 seconds) and  
it activates the compressor only after the valve is completely  
opened by closing its end switch. When wired as shown, the  
valve will have the following operating characteristics:  
Fig. 6 Typical Aquazone Control Board  
Jumper Locations  
Terminal Strip P2  
C
Typical  
Water  
Valve  
24 VAC  
A
1. Remain open during a lockout.  
Fig. 7 Typical D Control Accessory Wiring  
2. Draw approximately 25 to 35 VA through the Ysignal  
of the thermostat.  
PRE-START-UP  
IMPORTANT: This can overheat the anticipators of  
electromechanical thermostats. Only use relay based  
electronic thermostats.  
System Checkout When the installation is complete  
and the system is cleaned and flushed, follow the System  
Checkout procedure outlined below.  
1. Voltage: Ensure that the voltage is within the utilization  
range specifications of the unit compressor and fan motor.  
2. System Water Temperature: Ensure that the system  
water temperature is within an acceptable range to facili-  
tate start-up. (When conducting this check, also verify  
proper heating and cooling set points.)  
3. System Water pH: Verify system water acidity  
(pH = 7.5 or 8.5). Proper pH promotes the longevity of  
hoses and heat exchangers.  
Capacitor  
Circ Brkr  
Grnd  
Contactor-CC  
L2  
L1  
4. System Flushing: Properly clean and flush the system  
periodically. Ensure that all supply and return hoses are  
connected end-to-end to facilitate system flushing and  
prevent fouling of the heat exchanger by system water.  
Water used in the system must be potable and should not  
contain dirt, piping slag, and chemical cleaning agents.  
BR  
Transformer  
Aquazone C”  
5. Closed-Type Cooling Tower or Open Tower with Heat  
Exchanger: Check equipment for proper temperature set  
points and operation.  
See Note  
Low Voltage  
Connector  
CB  
6. Verify Balanced Water Flow Rate to Heat Pump.  
THERMOSTAT  
WIRED DIRECTLY  
TO CONTROL  
BOARD  
7. Standby Pump: Verify that the standby pump is properly  
installed and in operating condition.  
8. Access Panels: Assure that all access panels in the filter  
and fan section are securely closed.  
NOTE: Low voltage connector may be removed for easy installation.  
9. Air Dampers: Assure that all air dampers are properly  
Fig. 5 Low Voltage Field Wiring  
set.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. System Controls: To ensure that no catastrophic system  
failures occur, verify that system controls are functioning  
and that the sequencing is correct.  
11. Freeze Protection for Water System: Verify that freeze  
protection is provided for the building loop water system  
when outdoor design conditions require it. Inadequate  
freeze protection can lead to expensive tower and system  
piping repairs.  
D Control Jumper Settings  
WATER COIL FREEZE PROTECTION (FP1) LIMIT  
SETTING Select jumper 3, (JW3-FP1 Low Temp) to  
choose FP1 limit of 10 F or 30 F. To select 30 F as the limit, DO  
NOT clip the jumper. To select 10 F as the limit, clip the jumper.  
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-  
TING Select jumper 2 (JW2-FP2 Low Temp) to choose  
FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT  
clip the jumper. To select 10 F as the limit (for anti-freeze sys-  
tems), clip the jumper.  
ALARM RELAY SETTING Select jumper 4 (JW4-AL2  
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)  
or to remain as a dry contact (no connection). To connect AL2  
to R, do not clip the jumper. To set as dry contact, clip the  
jumper.  
LOW PRESSURE SETTING The D Control can be con-  
figured for Low Pressure Setting (LP). Select jumper 1 (JW1-  
LP Norm Open) for choosing between low pressure input  
normally opened or closed. To configure for normally closed  
operation, do not clip the jumper. To configure for normally  
open operation, clip the jumper.  
12. System Water Loop: Verify that all air is bled from the  
system. Air in the system impedes unit operation and  
causes corrosion in the system piping.  
13. Unit Filters: To avoid system damage, check that the unit  
filter is clean.  
14. Unit Fans: Manually rotate fans to assure free rotation.  
Ensure that fans are properly secured to the fan shaft. Do  
not oil fan motors on start-up since they are lubricated at  
the factory.  
15. System Control Center: Examine the system control  
and alarm panel for proper installation and operation to  
ensure control of the temperature set-points for operation  
of the systems heat rejector and boiler (when used).  
16. Miscellaneous: Note any questionable aspects of the  
D Control DIP Switches The D Control has 2 DIP  
switch blocks. Each DIP switch block has 8 switches and is  
labeled either S1 or S2 on the circuit board.  
DIP SWITCH BLOCK 1 (S1) This set of switches offers  
the following options for D Control configuration:  
Performance Monitor (PM) Set switch 1 to enable or dis-  
able performance monitor. To enable the PM, set the switch to  
ON. To disable the PM, set the switch to OFF.  
Compressor Relay Staging Operation Switch 2 will en-  
able or disable compressor relay staging operation. The com-  
pressor relay can be set to turn on with stage 1 or stage 2 call  
from the thermostat. This setting is used with dual stage units  
(units with 2 compressors and 2 D controls) or in master/slave  
applications. In master/slave applications, each compressor and  
fan will stage according to its switch 2 setting. If switch is set to  
stage 2, the compressor will have a 3-second delay before ener-  
gizing during stage 2 demand.  
installation.  
17. Air Coil: To obtain maximum performance, the air coil  
should be cleaned before starting the unit. A ten percent  
solution of dishwasher detergent and water is recom-  
mended for both sides of the coil. Rinse thoroughly with  
water.  
FIELD SELECTABLE INPUTS  
Jumpers and DIP (dual in-line package) switches on the  
control board are used to customize unit operation and can be  
configured in the field.  
IMPORTANT: Jumpers and DIP switches should only  
be clipped when power to control board has been turned  
off.  
NOTE: If DIP switch is set for stage 2, the alarm relay will not  
cycle during Test mode.  
C Control Jumper Settings (See Fig. 4)  
WATER COIL FREEZE PROTECTION (FP1) LIMIT  
SETTING Select jumper 3, (JW3-FP1 Low Temp) to  
choose FP1 limit of 10 F or 30 F. To select 30 F as the limit,  
DO NOT clip the jumper. To select 10 F as the limit, clip the  
jumper.  
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-  
TING Select jumper 2 (JW2-FP2 Low Temp) to choose  
FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT  
clip the jumper. To select 10 F as the limit, clip the jumper.  
ALARM RELAY SETTING Select jumper 1 (JW1-AL2  
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)  
or to remain as a dry contact (no connection). To connect AL2  
to R, do not clip the jumper. To set as dry contact, clip the  
jumper.  
Heating/Cooling Thermostat Type Switch 3 provides selec-  
tion of thermostat type. Heat pump or heat/cool thermostats  
can be selected. Select OFF for heat/cool thermostats. When in  
heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for  
cooling stage 2, W1 is used for heating stage 1 and O/W2 is  
used for heating stage 2. Select ON for heat pump applications.  
In heat pump mode, Y1 used is for compressor stage 1, Y2 is  
used for compressor stage 2, W1 is used for heating stage 3 or  
emergency heat, and O/W2 is used for RV (heating or cooling)  
depending upon switch 4 setting.  
O/B Thermostat Type Switch 4 provides selection for heat  
pump O/B thermostats. O is cooling output. B is heating out-  
put. Select ON for heat pumps with O output. Select OFF for  
heat pumps with B output.  
C Control DIP Switches The C Control has 1 DIP  
Dehumidification Fan Mode (Not used on 50RTG) Switch  
5 provides selection of normal or dehumidification fan mode.  
Select OFF for dehumidification mode. The fan speed relay  
will remain OFF during cooling stage 2. Select ON for normal  
mode. The fan speed relay will turn on during cooling stage 2  
in normal mode.  
switch block with two switches. See Fig. 4.  
PERFORMANCE MONITOR (PM) DIP switch 1 will  
enable or disable this feature. To enable the PM, set the switch  
to ON. To disable the PM, set the switch to OFF.  
STAGE 2 DIP switch 2 will enable or disable compressor  
delay. Set DIP switch to OFF for stage 2 in which the compres-  
sor will have a 3-second delay before energizing.  
Switch 6 Not used.  
Boilerless Operation Switch 7 provides selection of boiler-  
less operation and works in conjunction with switch 8. In  
boilerless operation mode, only the compressor is used for  
heating when FP1 is above the boilerless changeover tempera-  
ture set by switch 8 below. Select ON for normal operation or  
select OFF for boilerless operation.  
NOTE: The alarm relay will not cycle during Test mode if  
switch is set to OFF, stage 2.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boilerless Changeover Temperature Switch 8 on S1 pro-  
vides selection of boilerless changeover temperature set point.  
Select OFF for set point of 50 F or select ON for set point  
of 40 F.  
If switch 8 is set for 50 F, then the compressor will be used  
for heating as long as the FP1 is above 50 F. The compressor  
will not be used for heating when the FP1 is below 50 F and the  
compressor will operates in emergency heat mode, staging on  
EH1 and EH2 to provide heat. If a thermal switch is being used  
instead of the FP1 thermistor, only the compressor will be used  
for heating mode when the FP1 terminals are closed. If the FP1  
terminals are open, the compressor is not used and the control  
goes into emergency heat mode.  
DIGITAL NIGHT SET BACK (NSB) In this configura-  
tion, the relay will be ON if the NSB input is connected to  
ground C.  
NOTE: If there are no relays configured for digital NSB, then  
the NSB and OVR inputs are automatically configured for  
mechanical operation.  
MECHANICAL NIGHT SET BACK When NSB input is  
connected to ground C, all thermostat inputs are ignored. A  
thermostat set back heating call will then be connected to the  
OVR input. If OVR input becomes active, then the D control  
will enter Night Low Limit (NLL) staged heating mode. The  
NLL staged heating mode will then provide heating during the  
NSB period.  
DIP SWITCH BLOCK 2 (S2) This set of DIP switches is  
used to configure accessory relay options.  
Water Valve (Slow Opening) If relay is config-  
ured for Water Valve (slow opening), the relay will start 60 sec-  
onds prior to starting compressor relay.  
Switches 1 to 3 These DIP switches provide selection  
of Accessory 1 relay options. See Table 13 for DIP switch  
combinations.  
Switches 4 to 6 These DIP switches provide selection  
of Accessory 2 relay options. See Table 14 for DIP switch  
combinations.  
Outside Air Damper (OAD) If relay is configured  
for OAD, the relay will normally be ON any time the Fan  
Enable relay is energized. The relay will not start for 30 min-  
utes following a return to normal mode from NSB, when NSB  
is no longer connected to ground C. After 30 minutes, the relay  
will start if the Fan Enable is set to ON.  
Table 13 DIP Switch Block S2 —  
Accessory 1 Relay Options  
DIP SWITCH POSITION  
ACCESSORY 1  
RELAY OPTIONS  
1
2
3
To avoid equipment damage, DO NOT leave system filled  
in a building without heat during the winter unless anti-  
freeze is added to system water. Condenser coils never  
fully drain by themselves and will freeze unless winterized  
with antifreeze.  
Cycle with Fan  
Digital NSB  
Water Valve Slow Opening  
OAD  
On  
Off  
On  
On  
On  
On  
Off  
On  
On  
On  
On  
Off  
LEGEND  
NSB Night Setback  
OAD Outside Air Damper  
START-UP  
Use the procedure outlined below to initiate proper unit  
start-up.  
NOTE: All other DIP switch combinations are invalid.  
NOTE: This equipment is designed for indoor installation only.  
Table 14 DIP Switch Block S2 —  
Accessory 2 Relay Options  
Operating Limits  
ENVIRONMENT This equipment is designed for outdoor  
installation ONLY. Extreme variations in temperature, humidi-  
ty and corrosive water or air will adversely affect the unit per-  
formance, reliability and service life.  
POWER SUPPLY A voltage variation of ± 10% of name-  
plate utilization voltage is acceptable.  
UNIT STARTING CONDITIONS All units start and op-  
erate with entering air at 40 F, entering water at 20 F and with  
both air and water at the flow rates used.  
NOTE: These operating limits are not normal or continuous  
operating conditions. It is assumed that such a start-up is for  
the purpose of bringing the building space up to occupancy  
temperature. See Table 15 for operating limits.  
DIP SWITCH POSITION  
ACCESSORY 2  
RELAY OPTIONS  
4
5
6
Cycle with Fan  
Digital NSB  
Water Valve Slow Opening  
OAD  
On  
Off  
On  
On  
On  
On  
Off  
On  
On  
On  
On  
Off  
LEGEND  
NSB Night Setback  
OAD Outside Air Damper  
NOTE: All other switch combinations are invalid.  
Auto Dehumidification Mode or High Fan Mode (Not used  
on 50RTG) Switch 7 provides selection of auto dehumidifi-  
cation fan mode or high fan mode. In auto dehumidification fan  
mode the fan speed relay will remain off during cooling stage 2  
if terminal H is active. In high fan mode, the fan enable and fan  
speed relays will turn on when terminal H is active. Set the  
switch to ON for auto dehumidification fan mode or to OFF for  
high fan mode.  
When the disconnect switch is closed, high voltage is  
present in some areas of the electrical panel. Exercise  
caution when working with the energized equipment.  
Switch 8 Not used.  
1. Restore power to system.  
2. Turn thermostat fan position to ON. Blower should start.  
3. Balance airflow at registers.  
4. Adjust all valves to the full open position and turn on the  
line power to all heat pump units.  
5. Operate unit in the cooling cycle. Room temperature  
should be approximately 70 to 75 F dry bulb. Loop water  
temperature entering the heat pumps should be between  
60 and 110 F.  
D Control Accessory Relay Configurations —  
The following accessory relay settings are applicable for both  
D controls only:  
CYCLE WITH FAN In this configuration, the relay will be  
ON any time the Fan Enable relay is on.  
CYCLE WITH COMPRESSOR In this configuration, the  
relay will be ON any time the Compressor relay is on.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: Three factors determine the operating limits of a unit:  
(1) entering air temperature, (2) water temperature and (3)  
ambient temperature. Whenever any of these factors are at a  
minimum or maximum level, the other two factors must be at a  
normal level to ensure proper unit operation. See Table 15.  
5. Air temperature drop across the coil should be checked  
when compressor is operating. Air temperature drop  
should be between 15 and 25 F.  
Unit Start-Up Heating Mode  
NOTE: Operate the unit in heating cycle after checking the  
cooling cycle. Allow five minutes between tests for the pres-  
sure or reversing valve to equalize.  
1. Turn thermostat to lowest setting and set thermostat  
switch to HEAT position.  
Table 15 Operating Limits 50RTG Units  
AIR LIMITS  
Rated Ambient Air  
Min. Entering Air  
COOLING  
80° F  
HEATING  
70° F  
50° F  
40° F  
Rated Entering Air db/wb  
Max. Entering Air db/wb  
WATER LIMITS  
Min. Entering Water  
Normal Entering Water  
Max. Entering Water  
80/67° F  
110/83° F  
70° F  
80° F  
2. Slowly turn the thermostat to a higher temperature until  
the compressor activates.  
3. Check for warm air delivery at the unit grille within a few  
minutes after the unit has begun to operate.  
4. Check the temperature of both supply and discharge  
water. If temperature is within range, proceed. If tempera-  
ture is outside the range, check the heating refrigerant  
pressures.  
5. Once the unit has begun to run, check for warm air deliv-  
ery at the unit grille.  
25° F  
85° F  
115° F  
25° F  
70° F  
115° F  
LEGEND  
db Dry Bulb  
wb Wet Bulb  
NOTE: Value in heating column is dry bulb only. Any wet bulb read-  
ing is acceptable.  
6. Air temperature rise across the coil should be checked  
when compressor is operating. Air temperature rise  
should be between 20 and 30 F after 15 minutes at load.  
Scroll Compressor Rotation It is important to be  
certain compressor is rotating in the proper direction. To  
determine whether or not compressor is rotating in the proper  
direction:  
1. Connect service gages to suction and discharge pressure  
fittings.  
2. Energize the compressor.  
3. The suction pressure should drop and the discharge  
pressure should rise, as is normal on any start-up.  
7. Check for vibration, noise and water leaks.  
Flow Regulation Flow regulation can be accom-  
plished by two methods. Most water control valves have a flow  
adjustment built into the valve. By measuring the pressure drop  
through the unit heat exchanger, the flow rate can be deter-  
mined. See Table 16. Adjust the water control valve until  
the flow of 1.5 to 2 gpm is achieved. Since the pressure con-  
stantly varies, two pressure gages may be needed in some  
applications.  
If the suction pressure does not drop and the discharge  
pressure does not rise to normal levels:  
An alternative method is to install a flow control device.  
These devices are typically an orifice of plastic material de-  
signed to allow a specified flow rate that are mounted on the  
outlet of the water control valve. Occasionally these valves  
produce a velocity noise that can be reduced by applying some  
back pressure. To accomplish this, slightly close the leaving  
isolation valve of the well water setup.  
1. Turn off power to the unit. Install disconnect tag.  
2. Reverse any two of the unit power leads.  
3. Reapply power to the unit and verify pressures are correct.  
The suction and discharge pressure levels should now move  
to their normal start-up levels.  
When the compressor is rotating in the wrong direction, the  
unit makes an elevated level of noise and does not provide  
cooling.  
After a few minutes of reverse operation, the scroll com-  
pressor internal overload protection will open, thus activating  
the unit lockout. This requires a manual reset. To reset, turn the  
thermostat on and then off.  
To avoid possible injury or death due to electrical shock,  
open the power supply disconnect switch and secure it in  
an open position before flushing system.  
NOTE: There is a 5-minute time delay before the compressor  
will start.  
Flushing Once the piping is complete, final purging and  
loop charging is needed. A flush cart pump of at least 1.5 hp is  
needed to achieve adequate flow velocity in the loop to purge  
air and dirt particles from the loop. Flush the loop in both direc-  
tions with a high volume of water at a high velocity. Follow the  
steps below to properly flush the loop:  
Unit Start-Up Cooling Mode  
1. Adjust the unit thermostat to the warmest position.  
Slowly reduce the thermostat position until the compres-  
sor activates.  
2. Check for cool air delivery at unit grille a few minutes  
after the unit has begun to operate.  
3. Verify that the compressor is on and that the water flow  
rate is correct by measuring pressure drop through the  
heat exchanger using P/T plugs. Check the elevation and  
cleanliness of the condensate lines; any dripping could be  
a sign of a blocked line. Be sure the condensate trap in-  
cludes a water seal.  
4. Check the temperature of both supply and discharge  
water. If temperature is within range, proceed. If tempera-  
ture is outside the range, check the cooling refrigerant  
pressures.  
1. Verify power is off.  
2. Fill loop with water from hose through flush cart before  
using flush cart pump to ensure an even fill. Do not allow  
the water level in the flush cart tank to drop below the  
pump inlet line to prevent air from filling the line.  
3. Maintain a fluid level in the tank above the return tee to  
avoid air entering back into the fluid.  
4. Shutting off the return valve that connects into the flush  
cart reservoir will allow 50 psi surges to help purge air  
pockets. This maintains the pump at 50 psi.  
5. To purge, keep the pump at 50 psi until maximum pump-  
ing pressure is reached.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Open the return valve to send a pressure surge through  
the loop to purge any air pockets in the piping system.  
7. A noticeable drop in fluid level will be seen in the flush  
cart tank. This is the only indication of air in the loop.  
NOTE: If air is purged from the system while using a 10 in.  
PVC flush tank, only a 1 to 2 in. level drop will be noticed  
since liquids are incompressible. If the level drops more than  
this, flushing should continue since air is still being com-  
pressed in the loop. If level is less than 1 to 2 in., reverse the  
flow.  
Antifreeze In areas where entering loop temperatures  
drop below 40 F or where piping will be routed through areas  
subject to freezing, antifreeze is needed.  
Alcohols and glycols are commonly used as antifreeze  
agents. Freeze protection should be maintained to 15 F below  
the lowest expected entering loop temperature. For example, if  
the lowest expected entering loop temperature is 30 F, the leav-  
ing loop temperature would be 22 to 25 F. Therefore, the freeze  
protection should be at 15 F (30 F 15 F = 15 F).  
IMPORTANT: All alcohols should be pre-mixed and  
pumped from a reservoir outside of the building or  
introduced under water level to prevent fumes.  
8. Repeat this procedure until all air is purged.  
9. Restore power.  
Antifreeze may be added before, during or after the flushing  
process. However, depending on when it is added in the  
process, it can be wasted. Refer to the Antifreeze section for  
more detail.  
Loop static pressure will fluctuate with the seasons. Pres-  
sures will be higher in the winter months than during the warm-  
er months. This fluctuation is normal and should be considered  
when charging the system initially. Run the unit in either heat-  
ing or cooling for several minutes to condition the loop to a  
homogenous temperature.  
Calculate the total volume of fluid in the piping system. See  
Table 17. Use the percentage by volume in Table 18 to deter-  
mine the amount of antifreeze to use. Antifreeze concentration  
should be checked from a well mixed sample using a hydrome-  
ter to measure specific gravity.  
FREEZE PROTECTION SELECTION The 30 F FP1 fac-  
tory setting (water) should be used to avoid freeze damage to  
the unit.  
Once antifreeze is selected, the JW3 jumper (FP1) should  
be clipped on the control to select the low temperature (anti-  
freeze 13 F) set point to avoid nuisance faults.  
When complete, perform a final flush and pressurize the  
loop to a static pressure of 40 to 50 psi for winter months or 15  
to 20 psi for summer months.  
Table 17 Approximate Fluid Volume (gal.)  
After pressurization, be sure to remove the plug from the  
end of the loop pump motor(s) to allow trapped air to be  
discharged and to ensure the motor housing has been flooded.  
Be sure the loop flow center provides adequate flow through  
the unit by checking pressure drop across the heat exchanger.  
Compare the results to the data in Table 16.  
per 100 Ft of Pipe  
PIPE  
DIAMETER (in.)  
VOLUME (gal.)  
Copper  
1
1.25  
1.5  
4.1  
6.4  
9.2  
Rubber Hose  
Polyethylene  
1
3.9  
Table 16 50RTG Coaxial Water Pressure Drop  
3
/ IPS SDR11  
2.8  
4.5  
8.0  
10.9  
18.0  
8.3  
10.9  
17.0  
4
1 IPS SDR11  
WATER TEMPERATURE (F)  
UNIT  
1
1 / IPS SDR11  
4
1
GPM  
30  
50  
70  
90  
/ IPS SDR11  
2
50RTG  
2 IPS SDR11  
Pressure Drop (ft. H O)  
2
1
1
1 / IPS SCH40  
4
2
4.0  
6.0  
3.1  
6.1  
2.8  
5.3  
2.8  
5.3  
2.8  
5.3  
1 / IPS SCH40  
03  
2 IPS SCH40  
8.0  
9.9  
8.9  
8.9  
8.9  
10.0  
14.3  
12.9  
12.9  
12.9  
LEGEND  
5.5  
8.5  
4.2  
8.9  
3.4  
7.8  
3.4  
7.8  
3.4  
7.8  
IPS Internal Pipe Size  
SCH Schedule  
04  
05  
07  
08  
10  
12  
15  
20  
11.5  
14.0  
14.8  
20.5  
13.2  
18.6  
13.2  
18.6  
13.2  
18.6  
SDR Standard Dimensional Ratio  
NOTE: Volume of heat exchanger is approximately 1.0 gallon.  
Table 18 Antifreeze Percentages by Volume  
MINIMUM TEMPERATURE FOR  
7.0  
11.0  
15.0  
18.0  
10.0  
15.0  
20.0  
24.0  
11.0  
17.0  
22.0  
27.0  
14.0  
22.0  
30.0  
36.0  
17.0  
25.0  
34.0  
40.0  
21.0  
32.0  
42.0  
51.0  
31.0  
47.0  
62.0  
74.0  
8.1  
16.9  
28.5  
38.8  
3.4  
10.1  
16.0  
22.3  
4.5  
9.4  
14.2  
20.0  
8.3  
17.6  
29.4  
39.9  
4.8  
9.4  
13.1  
22.0  
5.3  
11.2  
18.9  
25.6  
2.3  
6.7  
10.7  
14.9  
3.5  
8.1  
12.7  
18.2  
5.5  
11.7  
19.7  
26.7  
3.2  
6.0  
10.3  
13.5  
2.9  
7.4  
11.6  
16.5  
6.4  
13.1  
20.8  
28.0  
5.3  
11.2  
18.9  
25.6  
2.3  
6.7  
10.7  
14.9  
3.5  
8.1  
12.7  
18.2  
5.5  
11.7  
19.7  
26.7  
3.2  
6.0  
10.3  
13.5  
2.9  
7.4  
11.6  
16.5  
6.4  
13.1  
20.8  
28.0  
5.3  
11.2  
18.9  
25.6  
2.3  
6.7  
10.7  
14.9  
3.5  
8.1  
12.7  
18.2  
5.5  
11.7  
19.7  
26.7  
3.2  
6.0  
10.3  
13.5  
2.9  
7.4  
11.6  
16.5  
6.4  
13.1  
20.8  
28.0  
FREEZE PROTECTION (F)  
ANTIFREEZE  
10  
25  
15  
21  
20  
16  
25  
10  
Methanol (%)  
100% USP Food Grade  
Propylene Glycol (%)  
38  
30  
22  
15  
Cooling Tower/Boiler Systems These systems  
typically use a common loop maintained at 60 to 90 F. The use  
of a closed circuit evaporative cooling tower with a secondary  
heat exchanger between the tower and the water loop is recom-  
mended. If an open type cooling tower is used continuously,  
chemical treatment and filtering will be necessary.  
Ground Coupled, Closed Loop and Plateframe  
Heat Exchanger Well Systems These systems al-  
low water temperatures from 30 to 110 F. The external loop  
field is divided up into 2 in. polyethylene supply and return  
lines. Each line has valves connected in such a way that upon  
system start-up, each line can be isolated for flushing using  
only the system pumps. Air separation should be located in the  
piping system prior to the fluid re-entering the loop field.  
5.2  
10.7  
17.4  
24.3  
10.6  
21.2  
34.2  
46.2  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING STAGE 3 In Heating Stage 3 mode, the Fan  
Enable, Fan Speed and Compressor relays remain on. The EH1  
output is turned on immediately. With continuing Heat Stage 3  
demand, EH2 will turn on after 10 minutes. EH1 and EH2 are  
turned off immediately when the Heating Stage 3 demand is re-  
moved. The control reverts to Heating Stage 2 mode.  
Output EH2 will be off if FP1 is greater than 45 F AND  
FP2 (when shorted) is greater than 110 F during Heating  
Stage 3 mode. This condition will have a 30-second recogni-  
tion time. Also, during Heating Stage 3 mode, EH1, EH2, Fan  
Enable, and Fan Speed will be ON if G input is not active.  
EMERGENCY HEAT In Emergency Heat mode, the Fan  
Enable and Fan Speed relays are turned on. The EH1 output is  
turned on immediately. With continuing Emergency Heat de-  
mand, EH2 will turn on after 5 minutes. Fan Enable and Fan  
Speed relays are turned off after a 60-second delay. The control  
reverts to Standby mode.  
OPERATION  
Power Up Mode The unit will not operate until all the  
inputs, terminals and safety controls are checked for normal  
operation.  
NOTE: The compressor will have a 5-minute anti-short cycle  
upon power up.  
Units with AquazoneComplete C Control  
STANDBY Y and W terminals are not active in standby  
mode, however the O and G terminals may be active, depend-  
ing on the application. The compressor will be off.  
COOLING Y and O terminals are active in Cooling mode.  
After power up, the first call to the compressor will initiate a  
5 to 80 second random start delay and a 5-minute anti-short  
cycle protection time delay. After both delays are complete, the  
compressor is energized.  
NOTE: On all subsequent compressor calls the random start  
delay is omitted.  
Output EH1, EH2, Fan Enable, and Fan Speed will be ON if  
the G input is not active during Emergency Heat mode.  
HEATING STAGE 1 Terminal Y is active in heating  
stage 1. After power up, the first call to the compressor will  
initiate a 5 to 80 second random start delay and a 5-minute anti-  
short cycle protection time delay. After both delays are  
complete, the compressor is energized.  
NOTE: On all subsequent compressor calls the random start  
delay is omitted.  
HEATING STAGE 2 To enter Stage 2 mode, terminal W  
is active (Y is already active). Also, the G terminal must be  
active or the W terminal is disregarded. The compressor relay  
will remain on and EH1 is immediately turned on. EH2 will  
turn on after 10 minutes of continual stage 2 demand.  
NOTE: EH2 will not turn on (or if on, will turn off) if FP1 tem-  
perature is greater than 45 F and FP2 is greater than 110 F.  
COOLING STAGE 1 In Cooling Stage 1 mode, the Fan  
Enable, compressor and RV relays are turned on immediately.  
If configured as stage 2 (DIP switch set to OFF) then the com-  
pressor and fan will not turn on until there is a stage 2 demand.  
The fan Enable and compressor relays are turned off immedi-  
ately when the Cooling Stage 1 demand is removed. The con-  
trol reverts to Standby mode. The RV relay remains on until  
there is a heating demand. If there is a master/slave or dual  
compressor application, all compressor relays and related func-  
tions will track with their associated DIP switch 2 on S1.  
COOLING STAGE 2 In Cooling Stage 2 mode, the Fan  
Enable, compressor and RV relays remain on. The Fan Speed  
relay is turned on immediately and turned immediately once  
the Cooling Stage 2 demand is removed. The control reverts to  
Cooling Stage 1 mode. If there is a master/slave or dual com-  
pressor application, all compressor relays and related functions  
will track with their associated DIP switch 2 on S1.  
NIGHT LOW LIMIT (NLL) STAGED HEATING In NLL  
staged Heating mode, the override (OVR) input becomes ac-  
tive and is recognized as a call for heating and the control will  
immediately go into a Heating Stage 1 mode. With an addition-  
al 30 minutes of NLL demand, the control will go into Heating  
Stage 2 mode. With another additional 30 minutes of NLL  
demand, the control will go into Heating Stage 3 mode.  
EMERGENCY HEAT In emergency heat mode, terminal  
W is active while terminal Y is not. Terminal G must be active  
or the W terminal is disregarded. EH1 is immediately turned  
on. EH2 will turn on after 5 minutes of continual emergency  
heat demand.  
Units with Aquazone Deluxe D Control  
STANDBY/FAN ONLY The compressor will be off. The  
Fan Enable, Fan Speed, and reversing valve (RV) relays will be  
on if inputs are present. If there is a Fan 1 demand, the Fan  
Enable will immediately turn on. If there is a Fan 2 demand,  
the Fan Enable and Fan Speed will immediately turn on.  
SYSTEM TEST  
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1  
and Fan 2 outputs.  
System testing provides the ability to check the control  
operation. The control enters a 20-minute Test mode by mo-  
mentarily shorting the test pins. All time delays are increased  
15 times. See Fig. 4.  
HEATING STAGE 1 In Heating Stage 1 mode, the Fan  
Enable and Compressor relays are turned on immediately.  
Once the demand is removed, the relays are turned off and the  
control reverts to Standby mode. If there is a master/slave or  
dual compressor application, all compressor relays and related  
functions will operate per their associated DIP switch 2 setting  
on S1.  
HEATING STAGE 2 In Heating Stage 2 mode, the Fan  
Enable and Compressor relays remain on. The Fan Speed relay  
is turned on immediately and turned off immediately once the  
demand is removed. The control reverts to Heating Stage 1  
mode. If there is a master/slave or dual compressor application,  
all compressor relays and related functions will operate per  
their associated DIP switch 2 setting on S1.  
Test Mode To enter Test mode on C or D controls, cycle  
the power 3 times within 60 seconds. The LED (light-emitting  
diode) will flash a code representing the last fault when enter-  
ing the Test mode. The alarm relay will also power on and off  
during Test mode. See Tables 19 and 20. To exit Test mode,  
short the terminals for 3 seconds or cycle the power 3 times  
within 60 seconds.  
NOTE: Deluxe D Control has a flashing code and alarm relay  
cycling code that will both have the same numerical label.  
For example, flashing code 1 will have an alarm relay cycling  
code 1. Code 1 indicates the control has not faulted since the  
last power off to power on sequence.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 19 C Control Current LED Status  
again satisfy the thermostat used to terminal Y. Once the ther-  
mostat input calls are satisfied, the control will continue normal  
operation.  
NOTE: If 3 consecutive faults occur without satisfying the  
thermostat input call to terminal Y, the control will go into  
lockout mode. The last fault causing the lockout is stored in  
memory and can be viewed by entering Test mode.  
and Alarm Relay Operations  
LED STATUS  
DESCRIPTION OF OPERATION  
ALARM RELAY  
Normal Mode  
Open  
Cycle  
(closed 5 sec.,  
Open 25 sec.)  
On  
Normal Mode with  
PM Warning  
Off  
Slow Flash  
Fast Flash  
C Control is non-functional  
Fault Retry  
Open  
Open  
AquazoneDeluxe D Control LED Indica-  
tors There are 3 LED indicators on the D Control:  
STATUS LED Status LED indicates the current status or  
mode of the D control. The Status LED light is green.  
Lockout  
Closed  
Open  
(Closed after  
15 minutes)  
Slow Flash  
Over/Under Voltage Shutdown  
Flashing Code 1 Test Mode No fault in memory  
Flashing Code 2 Test Mode HP Fault in memory  
Flashing Code 3 Test Mode LP Fault in memory  
Flashing Code 4 Test Mode FP1 Fault in memory  
Flashing Code 5 Test Mode FP2 Fault in memory  
Flashing Code 6 Test Mode CO Fault in memory  
Cycling Code 1  
Cycling Code 2  
Cycling Code 3  
Cycling Code 4  
Cycling Code 5  
Cycling Code 6  
TEST LED Test LED will be activated any time the D  
control is in test mode. The Test LED light is yellow.  
FAULT LED Fault LED light is red. The fault LED will  
always flash a code representing the last fault in memory. If  
there is no fault in memory, the fault LED will flash code 1 on  
and appear as 1 fast flash alternating with a 10-second pause.  
See Table 21.  
Test Mode Over/Under  
shutdown in memory  
Flashing Code 7  
Cycling Code 7  
Cycling Code 8  
Cycling Code 9  
Flashing Code 8  
Flashing Code 9  
Test Mode PM in memory  
Test Mode Test Mode FP1/  
FP2 Swapped Fault in memory  
SERVICE  
Perform the procedures outlined below periodically, as  
indicated.  
LEGEND  
CO  
FP  
HP  
Condensate Overflow  
Freeze Protection  
High Pressure  
IMPORTANT: When a compressor is removed from this  
unit, system refrigerant circuit oil will remain in the com-  
pressor. To avoid leakage of compressor oil, the refrigerant  
lines of the compressor must be sealed after it is removed.  
LED Light-Emitting Diode  
LP  
PM  
Low Pressure  
Performance Monitor  
NOTES:  
1. Slow flash is 1 flash every 2 seconds.  
2. Fast flash is 2 flashes every 1 second.  
3. EXAMPLE: Flashing Code 2is represented by 2 fast flashes followed by a  
10-second pause. This sequence will repeat continually until the fault is  
cleared.  
IMPORTANT: All refrigerant discharged from this unit  
must be recovered without exception. Technicians must fol-  
low industry accepted guidelines and all local, state and fed-  
eral statutes for the recovery and disposal of refrigerants.  
Table 20 C Control LED Code and  
Fault Descriptions  
IMPORTANT: To avoid the release of refrigerant into the  
atmosphere, the refrigerant circuit of this unit must only be  
serviced by technicians which meet local, state and federal  
proficiency requirements.  
LED  
CODE  
1
FAULT  
DESCRIPTION  
No fault in memory  
There has been no fault since  
the last power-down to power-up  
sequence  
2
3
High-Pressure Switch  
Low-Pressure Switch  
HP Open Instantly  
IMPORTANT: To prevent injury or death due to electrical  
shock or contact with moving parts, open unit disconnect  
switch before servicing unit.  
LP open for 30 continuous sec-  
onds before or during a call  
(bypassed for first 60 seconds)  
4
5
Freeze Protection Coax  
FP1  
FP1 below Temp limit for 30 con-  
tinuous seconds (bypassed for  
first 60 seconds of operation)  
Filters Filters must be clean for maximum performance.  
Inspect filters every month under normal operating conditions.  
replace when necessary.  
Freeze Protection Air Coil  
FP2  
FP2 below Temp limit for 30 con-  
tinuous seconds (bypassed for  
first 60 seconds of operation)  
6
7
Condensate overflow  
Over/Under Voltage  
Sense overflow (grounded) for  
30 continuous seconds  
IMPORTANT: Units should never be operated with-  
out a filter.  
"R" power supply is <19VAC or  
>30VAC  
(Autoreset) Shutdown  
8
9
PM Warning  
Performance Monitor Warning  
has occurred.  
Water Coil Keep all air out of the water coil. Check  
open loop systems to be sure the well head is not allowing air  
to infiltrate the water line. Always keep lines airtight.  
Inspect heat exchangers regularly, and clean more frequent-  
ly if the unit is located in a dirtyenvironment. The heat  
exchanger should be kept full of water at all times. Open loop  
systems should have an inverted P trap placed in the discharge  
line to keep water in the heat exchanger during off cycles.  
Closed loop systems must have a minimum of 15 PSI during  
the summer and 40 PSI during the winter.  
FP1 and FP2 Thermistors FP1 temperature is higher than  
are Swapped  
FP2 in heating/test mode, or FP2  
temperature is higher than FP1  
in cooling/test mode.  
LEGEND  
FP  
HP  
Freeze Protection  
High Pressure  
LED Light-Emitting Diode  
LP  
PM  
Low Pressure  
Performance Monitor  
Retry Mode In Retry mode, the status LED will start to  
flash slowly to signal that the control is trying to recover from  
an input fault. The control will stage off the outputs and try to  
Check P trap frequently for proper operation.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 Aquazone D Control Current LED Status and Alarm Relay Operations  
STATUS LED  
(Green)  
TEST LED  
(Yellow)  
DESCRIPTION  
Normal Mode  
FAULT LED (Red)  
Flash Last Fault Code in Memory  
Flashing Code 8  
ALARM RELAY  
On  
Off  
Open  
Cycle (closed 5 sec,  
open 25 sec, )  
Normal Mode with PM  
On  
Off  
D Control is non-functional  
Test Mode  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Open  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flashing Code 1  
Cycling Appropriate Code  
Night Setback  
ESD  
Invalid T-stat Inputs  
No Fault in Memory  
HP Fault  
Flashing Code 2  
Flashing Code 3  
Flashing Code 4  
On  
Open  
Open  
Open  
Open  
Open  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Flashing Code 2  
Flashing Code 3  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
Flashing Code 7  
Flashing Code 2  
Flashing Code 3  
LP Fault  
FP1 Fault  
FP2 Fault  
CO Fault  
Open  
Over/Under Voltage  
HP Lockout  
Open (closed after 15 minutes)  
Closed  
Closed  
Closed  
Closed  
Closed  
LP Lockout  
FP1 Lockout  
FP2 Lockout  
CO Lockout  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
LEGEND  
NOTES:  
1. If there is no fault in memory, the Fault LED will flash code 1.  
2. Codes will be displayed with a 10-second Fault LED pause.  
3. Slow flash is 1 flash every 2 seconds.  
CO Condensate Overflow  
ESD Emergency Shutdown  
FP Freeze Protection  
HP High Pressure  
LP Low Pressure  
PM Performance Monitor  
4. Fast flash is 2 flashes every 1 second.  
5. EXAMPLE: Flashing Code 2is represented by 2 fast flashes  
followed by a 10-second pause. This sequence will repeat contin-  
ually until the fault is cleared.  
Proper water treatment can minimize tube fouling and  
pitting. If such conditions are anticipated, water treatment  
analysis is recommended. Refer to the Carrier System Design  
Manual, Part 5, for general water conditioning information.  
To avoid fouled machinery and extensive unit clean-up,  
DO NOT operate units without filters in place. DO NOT  
use equipment as a temporary heat source during  
construction.  
Follow all safety codes. Wear safety glasses and rubber  
gloves when using inhibited hydrochloric acid solution.  
Observe and follow acid manufacturers instructions.  
Condensate Drain Pans Check condensate drain  
pans for algae growth twice a year. If algae growth is apparent,  
consult a water treatment specialist for proper chemical treat-  
ment. The application of an algaecide every three months will  
typically eliminate algae problems in most locations.  
Clean condensers with an inhibited hydrochloric acid solu-  
tion. The acid can stain hands and clothing, damage concrete,  
and, without inhibitor, damage steel. Cover surroundings to  
guard against splashing. Vapors from vent pipe are not harmful,  
but take care to prevent liquid from being carried over by the  
gases.  
Refrigerant System Verify air and water flow rates  
are at proper levels before servicing. To maintain sealed circuit-  
ry integrity, do not install service gauges unless unit operation  
appears abnormal. Check to see that unit is within the super-  
heat and subcooling ranges.  
Warm solution acts faster, but cold solution is just as effec-  
tive if applied for a longer period.  
Condensate Drain Cleaning Clean the drain line  
and unit drain pan at the start of each cooling season. Check  
flow by pouring water into drain. Be sure trap is filled to main-  
tain an air seal.  
GRAVITY FLOW METHOD Do not add solution faster  
than vent can exhaust the generated gases.  
When condenser is full, allow solution to remain overnight,  
then drain condenser and flush with clean water. Follow acid  
manufacturers instructions. See Fig. 8.  
FORCED CIRCULATION METHOD Fully open vent  
pipe when filling condenser. The vent may be closed when  
condenser is full and pump is operating. See Fig. 9.  
Regulate flow to condenser with a supply line valve. If  
pump is a nonoverloading type, the valve may be fully closed  
while pump is running.  
For average scale deposit, allow solution to remain in con-  
denser overnight. For heavy scale deposit, allow 24 hours.  
Drain condenser and flush with clean water. Follow acid manu-  
facturers instructions.  
Air Coil Cleaning Remove dirt and debris from evap-  
orator coil as required by condition of the coil. Clean coil with  
a stiff brush, vacuum cleaner, or compressed air. Use a fin  
comb of the correct tooth spacing when straightening mashed  
or bent coil fins.  
Condenser Cleaning Water-cooled condensers may  
require cleaning of scale (water deposits) due to improperly  
maintained closed-loop water systems. Sludge build-up may  
need to be cleaned in an open water tower system due to  
induced contaminants.  
Local water conditions may cause excessive fouling or  
pitting of tubes. Condenser tubes should therefore be cleaned at  
least once a year, or more often if the water is contaminated.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant Charging  
FILL CONDENSER WITH  
CLEANING SOLUTION. DO  
NOT ADD SOLUTION  
MORE RAPIDLY THAN  
VENT CAN EXHAUST  
GASES CAUSED BY  
PAIL  
To prevent personal injury, wear safety glasses and gloves  
when handling refrigerant. Do not overcharge system —  
this can cause compressor flooding.  
FUNNEL  
CHEMICAL ACTION.  
1”  
PIPE  
NOTE: Do not vent or depressurize unit refrigerant to atmo-  
sphere. Remove and reclaim refrigerant following accepted  
practices.  
VENT  
PIPE  
5APPROX  
Air Coil Fan Motor Removal  
3TO 4’  
CONDENSER  
Before attempting to remove fan motors or motor mounts,  
place a piece of plywood over evaporator coils to prevent  
coil damage.  
Motor power wires need to be disconnected from motor  
terminals before motor is removed from unit.  
PAIL  
1. Shut off unit main power supply.  
2. Loosen bolts on mounting bracket so that fan belt can be  
removed.  
Fig. 8 Gravity Flow Method  
3. Loosen and remove the 2 motor mounting bracket bolts  
on left side of bracket.  
4. Slide motor/bracket assembly to extreme right and lift out  
through space between fan scroll and side frame. Rest  
motor on a high platform such as a step ladder. Do not  
allow motor to hang by its power wires.  
GAS VENT  
PUMP  
PRIMING  
CONN.  
GLOBE  
VALVES  
SUCTION  
SUPPLY  
PUMP  
SUPPORT  
1PIPE  
TROUBLESHOOTING  
(Fig. 10 and 11, and Table 22)  
CONDENSER  
When troubleshooting problems with a WSHP, consider the  
following.  
TANK  
REMOVE WATER  
REGULATING VALVE  
Thermistor A thermistor may be required for single-  
phase units where starting the unit is a problem due to low  
voltage. See Fig. 10 for thermistor nominal resistance.  
RETURN  
FINE MESH  
SCREEN  
Control Sensors The control system employs 2 nom-  
inal 10,000 ohm thermistors (FP1 and FP2) that are used for  
freeze protection. Be sure FP1 is located in the discharge fluid  
and FP2 is located in the air discharge. See Fig. 11.  
Fig. 9 Forced Circulation Method  
Checking System Charge Units are shipped with  
full operating charge. If recharging is necessary:  
90.0  
80.0  
70.0  
60.0  
50.0  
40.0  
30.0  
20.0  
10.0  
0.0  
1. Insert thermometer bulb in insulating rubber sleeve on  
liquid line near filter drier. Use a digital thermometer for  
all temperature measurements. DO NOT use a mercury  
or dial-type thermometer.  
2. Connect pressure gage to discharge line near compressor.  
3. After unit conditions have stabilized, read head pressure  
on discharge line gage.  
NOTE: Operate unit a minimum of 15 minutes before  
checking charge.  
4. From standard field-supplied Pressure-Temperature chart  
for R-22, find equivalent saturated condensing  
temperature.  
5. Read liquid line temperature on thermometer; then  
subtract from saturated condensing temperature. The dif-  
ference equals subcooling temperature.  
0.0  
20.0  
40.0  
60.0  
80.0 100.0 120.0 140.0  
Temperature (F)  
6. ADD refrigerant to raise the temperature or REMOVE  
refrigerant (using standard practices) to lower the temper-  
ature (allow a tolerance of ± 3° F), as required.  
Fig. 10 Thermistor Nominal Resistance  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIR  
COIL  
SUCTION  
°F  
°F  
COMPRESSOR  
THERMISTOR  
EXPANSION  
VALVE  
COAX  
DISCHARGE  
FP2  
FP1  
CONDENSATE  
OVERFLOW  
(CO)  
LIQUID  
LINE  
WATER IN  
WATER OUT  
AIR COIL  
WATER  
COIL  
PROTECTION  
FREEZE  
PROTECTION  
LEGEND  
COAX Coaxial Heat Exchanger  
Airflow  
Refrigerant Liquid Line Flow  
Fig. 11 FP1 and FP2 Thermistor Location  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 Troubleshooting  
FAULT  
HEATING COOLING  
POSSIBLE CAUSE  
SOLUTION  
Main Power Problems  
X
X
Green Status LED Off  
Check line voltage circuit breaker and disconnect.  
Check for line voltage between L1 and L2 on the contactor.  
Check for 24 VAC between R and C on controller.  
Check primary/secondary voltage on transformer.  
HP Fault Code 2  
High Pressure  
X
X
Reduced or no water flow in Check pump operation or valve operation/setting.  
cooling  
Check water flow adjust to proper flow rate.  
Water temperature out of  
range in cooling  
Bring water temperature within design parameters.  
X
X
Reduced or no airflow in  
heating  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
Dirty air coil construction dust etc.  
External static too high. Check Tables 4-12.  
Air temperature out of range Bring return air temperature within design parameters.  
in heating  
X
X
X
X
X
X
X
Overcharged with refrigerant Check superheat/subcooling vs typical operating condition.  
Bad HP switch  
Insufficient charge  
Check switch continuity and operation. Replace.  
Check for refrigerant leaks.  
LP/LOC Fault Code 3  
Low Pressure/Loss of  
Charge  
Compressor pump down at Check charge and start-up water flow.  
start-up  
FP1 Fault Code 4  
Water Freeze Protection  
X
Reduced or no water flow in Check pump operation or water valve operation/setting.  
heating  
Plugged strainer or filter. Clean or replace.  
Check water flow adjust to proper flow rate.  
X
X
Inadequate antifreeze level Check antifreeze density with hydrometer.  
Improper freeze protect set- Clip JW2 jumper for antifreeze (10 F) use.  
ting (30 F vs 10 F)  
X
X
Water temperature out of  
range  
Bring water temperature within design parameters.  
X
X
Bad thermistor  
Reduced or no airflow in  
cooling  
Check temperature and impedance correlation.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check Tables 4-12.  
FP2 Fault Code 5  
Air Coil Freeze  
Protection  
X
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within  
design parameters.  
Improper freeze protect set- Normal airside applications will require 30°F only.  
ting (30 F vs 10 F)  
X
X
X
X
X
X
X
Bad thermistor  
Blocked drain  
Improper trap  
Poor drainage  
Check temperature and impedance correlation.  
Check for blockage and clean drain.  
Check trap dimensions and location ahead of vent.  
Check for piping slope away from unit.  
Condensate Fault —  
Code 6  
Check slope of unit toward outlet.  
Poor venting. Check vent location.  
X
X
Moisture on sensor  
Under voltage  
Check for moisture shorting to air coil.  
Over/Under Voltage —  
Code 7  
(Auto Resetting)  
X
Check power supply and 24 VAC voltage before and during operation.  
Check power supply wire size.  
Check compressor starting.  
Check 24 VAC and unit transformer tap for correct power supply voltage.  
Check power supply voltage and 24 VAC before and during operation.  
Check 24 VAC and unit transformer tap for correct power supply voltage.  
Check for poor airflow or overcharged unit.  
Check for poor water flow or airflow.  
X
X
X
X
Over voltage  
Performance Monitor —  
Code 8  
Heating mode FP2>125 F  
Cooling mode FP1>125 F  
OR FP2< 40 F  
FP1 and FP2  
Thermistors Code 9  
X
FP1 temperature is higher  
than FP2 temperature  
FP2 temperature is higher  
than FP1 temperature  
Swap FP1 and FP2 thermistors.  
Swap FP1 and FP2 thermistors.  
X
No Fault Code Shown  
Unit Short Cycles  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
No compressor operation  
Compressor overload  
Control board  
See scroll compressor rotation section.  
Check and replace if necessary.  
Reset power and check operation.  
Dirty air filter  
Unit in 'Test Mode'  
Unit selection  
Compressor overload  
Thermostat position  
Unit locked out  
Check and clean air filter.  
Reset power or wait 20 minutes for auto exit.  
Unit may be oversized for space. Check sizing for actual load of space.  
Check and replace if necessary.  
Only Fan Runs  
Ensure thermostat set for heating or cooling operation.  
Check for lockout codes. Reset power.  
Compressor overload  
Thermostat wiring  
Check compressor overload. Replace if necessary.  
Check Y and W wiring at heat pump. Jumper Y and R for compressor  
operation in Test mode.  
LEGEND  
RV Reversing Valve  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 Troubleshooting (cont)  
FAULT  
HEATING COOLING  
POSSIBLE CAUSE  
SOLUTION  
Only Compressor Runs  
X
X
X
X
Thermostat wiring  
Fan motor relay  
Check G wiring at heat pump. Jumper G and R for fan operation.  
Jumper G and R for fan operation. Check for line voltage across BR  
contacts.  
Check fan power enable relay operation (if present).  
Check for line voltage at motor. Check capacitor.  
X
X
X
X
Fan motor  
Thermostat wiring  
Check Y and W wiring at heat pump. Jumper Y and R for compressor  
operation in test mode.  
Unit Does Not Operate in  
Cooling  
X
Reversing valve  
Set for cooling demand and check 24 VAC on RV coil and at control.  
If RV is stuck, run high pressure up by reducing water flow and while  
operating engage and disengage RV coil voltage to push valve.  
X
X
X
Thermostat setup  
Thermostat wiring  
Dirty filter  
Check for 'O' RV setup not 'B'.  
Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.  
Replace or clean.  
Insufficient capacity/  
Not cooling or heating  
properly  
X
X
Reduced or no airflow in  
heating  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower Tables 4-12.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower Tables 4-12.  
X
X
Reduced or no airflow in  
cooling  
X
Leaky ductwork  
Check supply and return air temperatures at the unit and at distant duct  
registers if significantly different, duct leaks are present.  
X
X
X
X
X
X
Low refrigerant charge  
Restricted metering device Check superheat and subcooling. Replace metering device.  
Check superheat and subcooling .  
Defective reversing valve  
Thermostat improperly  
located  
Perform RV touch test.  
Check location and for air drafts behind thermostat.  
X
X
X
X
X
X
Unit undersized  
Recheck loads and sizing check sensible cooling load and heat pump  
capacity.  
Perform Scaling check and clean if necessary.  
Scaling in water heat  
exchanger  
Inlet water too hot or cold  
X
X
Check load, loop sizing, loop backfill, ground moisture.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower Tables 4-12.  
High Head Pressure  
Reduced or no airflow in  
heating  
X
X
Reduced or no water flow in Check pump operation or valve operation/setting.  
cooling  
Check water flow and adjust to proper flow rate.  
Inlet water too hot  
Check load, loop sizing, loop backfill, ground moisture.  
X
Air temperature out of range Bring return air temperature within design parameters.  
in heating  
X
Scaling in water heat  
exchanger  
Perform Scaling check and clean if necessary.  
X
X
X
X
Unit overcharged  
Check superheat and subcooling. Reweigh in charge.  
Vacuum system and reweigh in charge.  
Non-condensables in  
system  
X
X
X
Restricted metering device Check superheat and subcooling. Replace metering device.  
Low Suction Pressure  
Reduced water flow in  
heating  
Check pump operation or water valve operation/setting.  
Plugged strainer or filter. Clean or replace.  
Check water flow adjust to proper flow rate.  
X
Water temperature out of  
range  
Bring water temperature within design parameters.  
X
Reduced airflow in cooling Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower Tables 4-12.  
X
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within design  
parameters.  
X
X
X
Insufficient charge  
Airflow too high  
Poor performance  
Airflow too high  
Unit oversized  
Check for refrigerant leaks.  
Check blower Tables 4-12.  
See 'Insufficient Capacity'.  
Check blower Tables 4-12.  
Recheck loads and sizing check sensible cooling load and heat pump  
capacity.  
Low discharge air  
temperature in heating  
High humidity  
X
X
LEGEND  
RV Reversing Valve  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 2002 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 535-004 Printed in U.S.A. Form 50R-2SI Pg 26 8-02 Replaces: New  
Book 1  
4
Tab 5a 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
50RTG  
START-UP CHECKLIST  
CUSTOMER:___________________________  
MODEL NO.:___________________________  
JOB NAME: _______________________________________  
SERIAL NO.:____________________  
DATE:_________  
I. PRE-START-UP  
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)  
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS  
TIGHT? (Y/N)  
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER?  
(Y/N)  
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)  
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)  
IS AN AIR FILTER INSTALLED? (Y/N)  
II. START-UP  
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)  
IF 3-PHASE SCROLL COMPRESSOR IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS.  
(Y/N)  
UNIT VOLTAGE COOLING OPERATION  
PHASE AB VOLTS  
PHASE BC VOLTS  
(if 3 phase)  
PHASE CA VOLTS  
(if 3 phase)  
PHASE AB AMPS  
PHASE BC AMPS  
(if 3 phase)  
PHASE CA AMPS  
(if 3 phase)  
CONTROL VOLTAGE  
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N)  
.
IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.  
TEMPERATURES  
FILL IN THE ANALYSIS CHART ATTACHED.  
COAXIAL HEAT COOLING CYCLE:  
EXCHANGER  
FLUID IN  
F
F
F
F
FLUID OUT  
FLUID OUT  
AIR OUT  
F
PSI  
PSI  
FLOW  
FLOW  
HEATING CYCLE:  
FLUID IN  
F
F
F
AIR COIL  
COOLING CYCLE:  
AIR IN  
HEATING CYCLE:  
AIR IN  
AIR OUT  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING CYCLE ANALYSIS  
PSI  
°F  
SAT  
AIR  
COIL  
SUCTION  
°F  
°F  
COMPRESSOR  
DISCHARGE  
EXPANSION  
VALVE  
COAX  
°F  
LIQUID LINE  
°F  
PSI  
°F  
PSI  
WATER IN  
WATER OUT  
LOOK UP PRESSURE DROP IN TABLE 16  
TO DETERMINE FLOW RATE  
COOLING CYCLE ANALYSIS  
PSI  
°F  
SAT  
AIR  
COIL  
SUCTION  
°F  
°F  
COMPRESSOR  
DISCHARGE  
EXPANSION  
VALVE  
COAX  
°F  
LIQUID LINE  
°F  
°F  
PSI  
PSI  
WATER IN  
WATER OUT  
LOOK UP PRESSURE DROP IN TABLE 16  
TO DETERMINE FLOW RATE  
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =  
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x  
FLUID FACTOR* =  
(Btu/hr)  
SUPERHEAT = SUCTION TEMPERATURE SUCTION SATURATION TEMPERATURE  
(DEG F)  
=
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE LIQUID LINE TEMPERATURE  
(DEG F)  
=
*Use 500 for water, 485 for antifreeze.  
*97B0014N02*  
97B0014N02  
Copyright 2002 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab  
1
4
PC 111  
Catalog No. 535-004  
Printed in U.S.A.  
Form 50R-2SI  
Pg CL-2  
8-02  
Replaces: New  
5a 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Cordless Drill CD1202 User Manual
Blue Rhino Electric Heater 82300C User Manual
Bodum Hot Beverage Maker 5500 16 User Manual
Bogen Stereo Amplifier PM 3000 User Manual
Briggs Stratton Lawn Mower 1695354 User Manual
Brother Label Maker TD 4000 User Manual
Chauvet Camera Accessories ST 200 User Manual
Chauvet Power Supply CH 202B User Manual
Cisco Systems DVR 8389DVB User Manual
Cisco Systems Network Card WIC 1B U User Manual