AQUAZONE™
50PTH, PTV, PTD026-072
Two-Stage Water Source Heat Pumps
with PURON® Refrigerant (R-410A)
Installation, Start-Up, and Service Instructions
Page
CONTENTS
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-38
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 34
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 34
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 34
Unit Start-Up with WSHP Open Controls . . . . . . . . 36
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 38
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 38
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-42
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Units with Aquazone™ Complete C Control . . . . . 39
Units with Aquazone Deluxe D Control . . . . . . . . . . 39
Units with WSHP Open Multiple Protocol. . . . . . . . 39
Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Step 1 — Check Jobsite. . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
• PROTECTION
• INSPECT UNIT
Step 3 — Locate Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• FIELD CONVERSION OF DISCHARGE AIR
Step 4 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . . . . . 9
• HORIZONTAL UNIT
• VERTICAL UNITS
Step 5 — Check Duct System . . . . . . . . . . . . . . . . . . . . 9
• SOUND ATTENUATION
• EXISTING DUCT SYSTEM
COMPLETE C AND DELUXE D BOARD
Step 6 — Install Condensate Drain . . . . . . . . . . . . . . . 9
• HORIZONTAL UNIT
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42,43
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
WSHP Open Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . 43
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Aquazone Deluxe D Control LED Indicators . . . . . 43
• VERTICAL UNITS
• VENTING
Step 7 — Pipe Connections . . . . . . . . . . . . . . . . . . . . . 10
• WATER LOOP APPLICATIONS
• GROUND-WATER APPLICATIONS
• GROUND-LOOP APPLICATIONS
• INSTALLATION OF SUPPLY AND RETURN HOSE
KIT
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44,45
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Water Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 44
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 45
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 45
Replacing the WSHP Open Controller’s
Step 8 — Wire Field Power Supply . . . . . . . . . . . . . . 12
• POWER CONNECTION
• SUPPLY VOLTAGE
• 208-VOLT OPERATION
• 460-VOLT OPERATION
• WSHP OPEN WIRING
Step 9 — Wire Field Controls. . . . . . . . . . . . . . . . . . . . 25
• THERMOSTAT CONNECTIONS
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
Step 10 — Operate ECM Interface Board . . . . . . . . 27
• STANDALONE — NO DDC CONTROLS
• WSHP OPEN CONTROLS
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 45-53
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
WSHP Open Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Thermostatic Expansion Valves . . . . . . . . . . . . . . . . . . 46
Stopped or Malfunctioned ECM Motor. . . . . . . . . . . . 50
Moisture Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29,30
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
FIELD SELECTABLE INPUTS. . . . . . . . . . . . . . . . . 30-33
Complete C Control Jumper Settings. . . . . . . . . . . . 30
Deluxe D Control Jumper Settings . . . . . . . . . . . . . . 30
Complete C Control DIP Switches. . . . . . . . . . . . . . . 30
Deluxe D Control DIP Switches. . . . . . . . . . . . . . . . . . 30
Units with Modulating Hot Water Reheat
(HWR) Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
• STANDALONE — NO DDC CONTROLS
• WSHP OPEN CONTROLS
APPENDIX A — WSHP OPEN SCREEN
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 54-59
50PTH,PTV,PTD START-UP
CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before
starting installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
• HWR APPLICATION CONSIDERATIONS
• HWR COMPONENT FUNCTIONS
Deluxe D Control Accessory
Relay Configurations. . . . . . . . . . . . . . . . . . . . . . . . . 32
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500079-01 Printed in U.S.A. Form 50PT-4SI Pg 1 7-10 Replaces: 50PT-3SI
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Provide an unobstructed path to the unit within the closet
or mechanical room. Space should be sufficient to allow
removal of unit if necessary.
9. Provide ready access to water valves and fittings, and
screwdriver access to unit side panels, discharge collar,
and all electrical connections.
10. Where access to side panels is limited, pre-removal of the
control box side mounting screws may be necessary for
future servicing.
INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Do not remove the packaging until the unit is ready for
installation.
3. Verify that the unit’s refrigerant tubing is free of kinks or
dents, and that it does not touch other unit components.
STORAGE — If the equipment is not needed immediately at
the jobsite, it should be left in its shipping carton and stored in a
clean, dry area of the building or in a warehouse. Units must be
stored in an upright position at all times. If carton stacking is
necessary, stack units a maximum of 3 high. Do not remove
any equipment from its shipping package until it is needed for
installation.
PROTECTION — Once the units are properly positioned on
the jobsite, cover them with either a shipping carton, vinyl film,
or an equivalent protective covering. Cap open ends of pipes
stored on the jobsite. This precaution is especially important in
areas where painting, plastering, or spraying of fireproof mate-
rial, etc. is not yet complete. Foreign material that accumulates
within the units can prevent proper start-up and necessitate
costly clean-up operations.
4. Inspect all electrical connections. Be sure connections are
clean and tight at their terminations.
5. Loosen compressor bolts until the compressor rides freely
on springs. Remove shipping restraints.
1
6. Remove the four / in. shipping bolts from compressor
4
support plate (two bolts on each side) to maximize vibra-
tion and sound alternation.
CAUTION
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
7. Remove any blower support cardboard from inlet of the
blower.
8. Locate and verify any accessory kit located in compressor
and/or blower section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
Before installing any of the system components, be sure to
examine each pipe, fitting, and valve, and remove any dirt or
foreign material found in or on these components.
CAUTION
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
units in an upright position. Tilting units on their sides may
cause equipment damage.
Table 1 — Physical Data — 50PTH, PTV, PTD026-072 Units
UNIT 50PTH, PTV, PTD
COMPRESSOR (1 each)
FACTORY CHARGE R-410A (oz)
026
038
049
Two-Stage, Scroll
81
064
072
58
78
144
156
ECM FAN MOTOR AND BLOWER
Fan Motor Type
VAR
1
VAR
1
VAR
1
11x10
VAR
1
11x10
VAR
1
11x10
Fan Motor (Hp)
/
/
2
2
Blower Wheel Size (D x W) (in.)
9 x 7
11 x 10
COAXIAL COIL VOLUME (gal.)
WATER CONNECTION SIZE (FPT) (in.)
HWG CONNECTION SIZE (FPT) (in.)
.76
3
.92
3
1.24
1.56
1.56
/
/
/
/
1
1
1
1
1
1
4
2
4
2
1
1
/
2
/
/
2
2
VERTICAL
Air Coil
Dimensions (H x W) (in.)
Filter Standard — 1-in. Throwaway
(Qty — Size) (in.)
Weight (lb)
28 x 20
28 x 25
32 x 25
36 x 25
36 x 25
1 — 16 x 30
1 — 20 x 30
1 — 16 x 30
1 — 20 x 30
1 — 28 x 24
1 — 28 x 30
2 — 16 x 30
Operating
Packaged
266
276
327
337
416
426
443
453
443
453
HORIZONTAL
Air Coil
Dimensions (H x W) (in.)
Filter Standard — 1-in. Throwaway
(Qty — Size) (in.)
Weight (lb)
18 x 31
20 x 25
20 x 40
20 x 45
20 x 45
1 — 12 x 20
1 — 20 x 24
1 — 18 x 20
1 — 20 x 24
2 — 18 x 18
2 — 20 x 24
2 — 20 x 24
Operating
Packaged
266
276
327
337
416
426
443
453
443
453
LEGEND
ECM
HWG — Hot Water Generator
VAR Variable Speed
—
Electronically Commutated Motor
—
NOTE: All units have spring compressor mountings, TXV (thermostatic expan-
1
3
sion valve) expansion devices, and
/
2
and / -in. electrical knockouts.
4
3
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
ASP
BSP
CAP
CSP
FPT
—
—
—
—
—
Alternate Service Panel
Blower Service Panel
Control Access Panel
Compressor Service Panel
Female Pipe Thread
2
Service
CSP
Front
2
Service Access
HWG — Hot Water Generator
HWR Hot Water Reheat
Access
Front
2
Service Access
Left Return
—
Power Supply
3/4” Knockout
2
Service Access
Right Return
1/2”
Knockout
1.6”
CSP
ASP
3.25”
3.25”
Low Voltage
1/2” Knockout
L
G
K
F
E
CAP
J
H
H
Left
Discharge
Right
Discharge
D
A
Condensate
3/4” FPT
Condensate
3/4” FPT
Back
Discharge
Back
Discharge
P
R
Size
P
Q
BSP
Blower
Outlet
BSP
O
Q
Y
Z
C
C
Blower
Outlet
O
, 072
R
A
A
X
Y Configuration - Left Return/Back Discharge
P Configuration - Right Return/Back Discharge - Air Coil Opening
P
M
O
N
P
Blower
Outlet
BSP
Left
View
ASP
CSP
BSP
Right
View
Blower
Outlet
O
N
Front
M
W Configuration - Left Return/Right Discharge - Air Coil Opening
N Configuration - Right Return/Left Discharge - Air Coil Opening
Air Coil
1.1”
V
Air Coil
S
U
S
Right
View
CSP
ASP
T
T
C
C
Front
Front
B
B
W Configuration - Left Return/Right Discharge - Air Coil Opening
N Configuration - Right Return/Left Discharge - Air Coil Opening
WATER
CONNEC-
TIONS (in.)
- UNITS
DISCHARGE CONNECTIONS (in.) RETURN CONNECTION
OVERALL CABINET
WATER CONNECTIONS (in.)
(in.)
ELECTRICAL
KNOCKOUTS (in.)
DUCT FLANGE INSTALLED
USING AIR COIL
OPENING (in.)
( 0.10 in.)
WITH HWR
50PTH
UNIT
J
2
K
2
L
4
1
1
3
1
2
3
F
4
5
1
2
/ -in. / -in. / -in.
Loop
Water
FPT
HWG
FPT
(in.)
M
O
P
Q
S
T
Cond Cond Cond
A
B
C
(LH
rtn)
N
Supply Supply (RH
Height Width rtn)
R
Return Return
Width Height
U
V
Width Depth Height
G
H
D
In
E
Out
Low
Ext Power
Loop Loop
in D out E
(in.)
HWG HWG Cond-
Voltage Pump Supply
In
Out ensate
3
1
026
038
049
22.4
25.4
25.4
62.2
71.2
76.2
81.2
19.3
21.3
21.3
21.3
2.1 10.0 13.9 16.9
3.4 10.8 14.6 18.9
3.4 10.8 15.6 18.9
3.4 10.8 15.6 18.9
3.5
3.4
3.4
3.4
/
/
/
2.1 10.0
3.6
6.1
6.1
6.1
6.1
8.6
8.6
8.6
8.6
3.6 2.0 12.5
3.1 1.2 19.0
3.1 1.2 19.0
3.1 1.2 19.0
15.5 3.6 2.0 33.8
17.5 3.1 1.0 34.8
17.5 3.1 1.0 39.8
17.5 3.1 1.0 44.8
16.2 2.3 1.5
18.2 3.1 1.5
18.2 3.1 1.5
18.2 3.1 1.5
4
2
2
2
2
3
1
/
5.96 13.13 3.4
5.96 13.13 3.6
5.96 13.13 3.6
4
1
1
1
/
1
064,072 25.4
/
NOTES:
1. Condensate connection is stainless steel
AIRFLOW CONFIGURATION
3
/
in. female pipe thread (FPT).
4
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without
CODE
RETURN
Right
Right
Left
DISCHARGE
Left
additional support.
N
P
3. Discharge flange is factory-installed.
4. Hanger kit is factory-installed.
5. Shaded areas are recommended service areas, not required.
6. Discharge can be modified in field. Return cannot be modified.
Back
W
Y
Right
Left
Back
Fig. 1 — 50PTH026-072 Dimensional Data
4
Download from Www.Somanuals.com. All Manuals Search And Download.
3/8” threaded rods
(by others)
FilterAccess
Return Air
(Ductwork
not shown)
Thermostat
Wiring
Field-supplied transition to
minimize pressure loss
Balancing Valve (field-
installed accessory)
Power Wiring
Stainless steel
braid hose
Supply Air
with integral
“J” swivel
Low Pressure Drop Water
Control Valve (optional)
(field-installed accessory)
Unit Power
Building
Loop
Flexible
Connection
Insulated supply duct with
at least one 90 degree elbow
to reduce air noise
Unit Power
Disconnect
(by others)
Water Out
Water In
Field-Supplied
Electric Heat
(if applicable)
(field-supplied)
Ball Valve with optional
Unit Hanger
integral P/Tplug (typical for supply
(field-installed
accessory)
(factory-
Aux Electric
and return piping) (field-installed accessory)
supplied)
Heat Disconnect
3/8” Threaded
Rod (by others)
Vibration Isolator
(white-compressor end
and red-blower end)
Washer
(by others)
Double Hex Nuts
(by others)
Integral hanger support-
pre-attached in factory
UNIT HANGER ISOLATION DETAIL
Fig. 2 — Typical Installation — 50PTH Unit
5
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
Field-Installed
ASP
BSP
CAP
CSP
FPT
HV
—
—
—
—
—
—
Alternate Service Panel
Blower Service Panel
Control Access Panel
Compressor Service Panel
Female Pipe Thread
High Voltage
Discharge Flange
(shipped loose inside
blower section)
Access Panels
Filter Bracket
HWG — Hot Water Generator
HWR
LV
—
—
Hot Water Reheat
Low Voltage
Air Coil
B
P
N
P
ASP
ASP
N
BSP
CAP
O
A
O
Q
2ʼ Service Access
CSP
M
Air Coil Side
Air Coil Side
K - Configuration - Right Return
/Top Discharge
J - Configuration - Left Return
/Top Discharge
(Top View)
(Top View)
2ʼ Service Access
Isometric View
S
R
S
R
1.00”
U
C
U
Air Coil
Air Coil
T
T
1.68”
C
Condensate
Power Supply
3/4” FPT
3/4”
HV Knockout
CAP
1.63”
1/2”
Knockout
1.18”
CSP
Low Voltage
1/2”
ASP
G
LV Knockout
F
E
CSP
L
K
Back
Back
Front
Front
J
H
D
K - Configuration - Right Return -
Air Coil Opening
J - Configuration - Left Return -
Air Coil Opening
Front View
(Right Side View)
(Left Side View)
WATER
CONNEC-
DISCHARGE CONNECTIONS (in.)
DUCT FLANGE INSTALLED
( 0.10 in.)
RETURN CONNECTION
USING AIR COIL OPENING
(in.)
OVERALL CABINET
(in.)
ELECTRICAL
KNOCKOUTS (in.)
WATER CONNECTIONS (in.)
TIONS (in.)
- UNITS
WITH HWR
50PTV
UNIT
J
K
L
1
1
3
1
2
3
F
4
5
1
2
/ -in.
2
/ -in.
2
/ -in.
4
Loop
Water
FPT
HWG
FPT
(in.)
M
O
P
Q
S
T
Cond Cond Cond
A
B
C
(LH
rtn)
N
Supply Supply (RH
Width Depth rtn)
R
Return Return
Depth Height
U
Width Depth Height
G
H
D
In
E
Out
Low
Ext
Power
Loop Loop
in D out E
(in.)
HWG HWG Cond-
Voltage Pump Supply
In
Out ensate
3
1
026
038
049
22.4
25.4
25.4
25.4
25.6
30.6
30.6
30.6
48.5
50.5
54.5
58.5
2.1
3.4
3.4
3.4
10.0 13.9 16.9
10.8 15.6 18.9
10.8 15.6 18.9
10.8 15.6 18.9
7.8
7.8
7.8
7.8
/
/
/
2
2.1 10.0
5.96 13.13
5.96 13.13
5.96 13.13
3.6
3.6
3.6
3.6
6.1
6.1
6.1
6.1
8.6
8.6
8.6
8.6
7.2
6.4
6.4
6.4
5.8
6.3
6.3
6.3
14.0
18.0
18.0
18.0
14.0
18.0
18.0
18.0
4.9 2.2
5.3 2.2
5.3 2.2
5.3 2.2
21.1
26.1
26.1
26.1
27.2
27.2
31.2
35.2
1.0
1.0
1.0
1.0
4
3
1
1
1
/
4
2
1
1
/
2
064,
072
/
2
NOTES:
AIRFLOW CONFIGURATION
3
1. Condensate connection is stainless steel
/
in. female pipe thread (FPT).
4
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without
additional support.
3. Discharge flange is field-installed.
4. Shaded areas are recommended service areas, not required.
CODE
RETURN
Left
DISCHARGE
J
Top
Top
K
Right
Fig. 3 — 50PTV Dimensional Data
6
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
ASP
BSP
CAP
CSP
FPT
—
—
—
—
—
Alternate Service Panel
Blower Service Panel
Control Access Panel
Compressor Service Panel
Female Pipe Thread
HWG — Hot Water Generator
HWR
—
Hot Water Reheat
WATER
CONNEC-
TIONS (in.)
DISCHARGE CONNECTIONS (in.)
DUCT FLANGE INSTALLED
( 0.10 in.)
OVERALL CABINET
(in.)
ELECTRICAL
KNOCKOUTS (in.)
RETURN CONNECTION (in.)
USING AIR COIL OPENING
WATER CONNECTIONS (in.)
- UNITS
WITH HWR
50PTD
UNIT
J
2
Cond
K
L
4
Cond
1
1
3
/ -in.
1
2
3
F
4
5
1
2
/ -in.
/ -in.
2
Loop
HWG
M
O
P
Q
S
T
Cond
A
B
C
Water
FPT
FPT
(in.)
(LH
rtn)
N
Supply Supply (RH
Width Depth rtn)
R
Return Return
Depth Height
U
Width Depth Height
G
H
D
E
Low
Ext
Power
Loop Loop
in D out E
(in.)
HWG HWG Cond-
In Out
Voltage Pump Supply
In
Out ensate
3
1
026
038
049
22.4
25.4
25.4
25.6
30.6
30.6
30.6
52.5
54.5
58.5
62.5
2.1 10.0 13.9 16.9
3.4 10.8 15.6 18.9
3.4 10.8 15.6 18.9
3.4 10.8 15.6 18.9
3.6
3.6
3.6
3.6
/
/
2.1 10.0
5.96 13.13
5.96 13.13
5.96 13.13
3.6
3.6
3.6
3.6
6.1
6.1
6.1
6.1
8.6
8.6
8.6
8.6
6.7 8.4
7.2 9.0
7.2 9.0
7.2 9.0
10.1
13.4
13.4
13.4
9.1
12.9
12.9
12.9
10.8 2.2
10.4 2.2
10.4 2.2
10.4 2.2
21.1
26.1
26.1
26.1
27.2
27.2
31.4
35.2
1.0
1.0
1.0
1.0
4
4
2
2
2
2
3
1
/
/
1
1
1
/
1
064,072 25.4
/
NOTES:
AIRFLOW CONFIGURATION
3
1. Condensate connection is stainless steel
/
4
in. female pipe thread (FPT).
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without
additional support.
3. Downflow unit does not have discharge flange, and is rated for zero clearance installation.
4. Shaded areas are recommended service areas, not required.
CODE
RETURN
Left
DISCHARGE
J
Bottom
Bottom
K
Right
Fig. 4 — 50PTD Dimensional Data
7
Download from Www.Somanuals.com. All Manuals Search And Download.
• Provide adequate clearance for filter replacement and
drain pan cleaning. Do not block filter access with pip-
ing, conduit or other materials. Refer to Fig. 1, 3, and 4
for dimensional data.
• Provide access for fan and fan motor maintenance and
for servicing the compressor and coils without removing
the unit.
• Provide an unobstructed path to the unit within the closet
or mechanical room. Space should be sufficient to allow
removal of the unit, if necessary.
• In limited side access installations, pre-removal of the
control box side mounting screws will allow control box
removal for future servicing.
Supply Air
Building
Loop
Flexible
Connection
Water
Out
Water
In
Balancing Valve
(field-installed
accessory)
Stainless steel
braid hose
with integral
“J” swivel
(field-installed
accessory)
Low Pressure
Drop Water
Control Valve
(optional)
Power
• Provide access to water valves and fittings and screw-
driver access to the unit side panels, discharge collar and
all electrical connections.
Thermostat
Wiring
(field-installed
accessory)
Ball Valve with optional
NOTE: Correct placement of the horizontal unit can play an
important part in minimizing sound problems. Since duct-
work is normally applied to these units, the unit can be
placed so that the principal sound emission is outside the oc-
cupied space in sound-critical applications. A fire damper
may be required by the local code if a fire wall is penetrated.
integral P/T plug
Compressor
Access Panel
(typical for supply and
return piping) (field-Installed
accessory)
NOTE: Ball valve with integral pressure temperature plug recommended.
Fig. 5 — Typical Vertical Installation — 50PTV Unit
FIELD CONVERSION OF DISCHARGE AIR — The dis-
charge air of the 50PTH horizontal units can be converted
between side and back discharge in the field. The conversion
process is the same for right and left return configurations. See
Fig. 7 and 8.
NOTE: It is not possible to convert return air between left or
right return models in the field due to refrigerant piping
changes.
Building
Loop
Flexible
Connection
Water
Out
Water
In
Stainless
steel
braid hose
with
Balancing Valve
(field-installed
accessory)
integral ”J”
swivel(field-
installed
accessory)
Water
Connection End
Low Pressure
Drop Water
Control Valve
(optional)
Return Air
Power
Thermostat
(field-installed
accessory)
Wiring
Supply
Duct
Compressor
Ball Valve with
optional integral
Access Panel
Flexible
P/T plug (typical for
supply and return
piping)(field-installed
accessory)
Connection
Side Discharge
Water
Connection End
Supply Air
NOTE: Ball valve with integral pressure temperature plug recommended.
Return Air
Drain
Fig. 6 — Typical Downflow Installation —
50PTD Unit
Step 3 — Locate Unit — The following guidelines
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
Back Discharge
Discharge Air
• Locate in areas where ambient temperatures are between
39 F and 102 F and relative humidity is no greater than
75%.
• Provide sufficient space for water, electrical and duct
connections.
• Locate unit in an area that allows easy access and removal
of filter and access panels.
• Allow enough space for service personnel to perform
maintenance.
Fig. 7 — Conversion Right Return,
Side Discharge to Back Discharge
Preparation — The unit should be on the ground in a well lit
area. Hung units should be taken down to ground level before
converting.
Side to Back Discharge Conversion
1. Remove screws to free the top and discharge panels. Set
screws aside for later use. See Fig. 8.
• Return air must be able to freely enter the space if unit needs
to be installed in a confined area such as a closet.
2. Remove the access panel and set aside.
• Install the unit on a piece of rubber, neoprene or other
mounting pad material for sound isolation. The pad
3. Lift the discharge panel from side of unit and rotate it to
back using care not to damage blower wiring.
4. Check blower wire routing and connections for undue
tension or contact with sheet metal edges. Re-route if
necessary.
3
1
should be at least / in. [10 mm] to / in. [13 mm] in
8
2
thickness. Extend the pad beyond all four edges of the
unit.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Check refrigerant tubing for contact with other compo-
nents. Adjust if necessary.
6. Reinstall top panel using screws set aside in Step 1.
NOTE: Location for some screws at bottom of discharge
panel may have to be changed.
7. Manually spin fan wheel to check for obstructions.
Adjust for any obstruction found.
8. Replace access panel.
Remove Screws
Water
Connection End
Return Air
Fig. 9 — 50PTV Units Mounted With
Vibration Absorption Pad
Side Discharge
Water
Connection End
Step 5 — Check Duct System — Size the duct sys-
tem to handle the design airflow quietly.
Rotate
Return Air
NOTE: Depending on the unit, the fan wheel may have a ship-
ping support installed at the factory. This must be removed
before operating unit.
SOUND ATTENUATION — To eliminate the transfer of
vibration to the duct system, a flexible connector is recom-
mended for both discharge and return air duct connections on
metal duct systems. The supply and return plenums should in-
clude internal duct liner of fiberglass or be made of duct board
construction to maximize sound attenuation of the blower.
Installing the WSHP unit to uninsulated ductwork in an uncon-
ditioned space is not recommended since it will sweat and
adversely affect the unit’s performance.
Move to Side
Replace Screws
Water
Connection End
To reduce air noise, at least one 90-degree elbow could be
included in the supply and return air ducts, provided system
performance is not adversely impacted. The blower speed can
also be changed in the field to reduce air noise or excessive air-
flow, provided system performance is not adversely impacted.
Return Air
Drain
EXISTING DUCT SYSTEM — If the unit is connected to
existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small, install
larger ductwork.
Discharge Air
Back Discharge
Fig. 8 — Conversion Left Return,
Side Discharge to Back Discharge
• Check existing ductwork for leaks and repair as necessary.
NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation
may be required for the ventilating air supply. If hard
ducted ventilation is not required, be sure that a proper air
path is provided for ventilation air to unit to meet ventila-
tion requirement of the space.
Back to Side Discharge Conversion — Follow instructions
above for Side to Back Discharge Conversion, noting the
panels would be reversed.
Step 4 — Mount the Unit
HORIZONTAL UNIT (50PTH) — Horizontal units should
be mounted using the factory-installed hangers. Proper attach-
ment of hanging rods to building structure is critical for safety.
See Fig. 1. Rod attachments must be able to support the weight
of the unit. See Table 1 for unit operating weights.
VERTICAL UNITS (50PTV,PTD) — Vertical and downflow
units are available in left or right return air configurations. See
Fig. 3 and 4. Mount the unit (except 50PTD) on a vibration
absorption pad slightly larger than the entire base to minimize
vibration transmission. It is not necessary to mount the unit on
the floor. See Fig. 9.
Step 6 — Install Condensate Drain
HORIZONTAL UNIT (50PTH) — Slope the unit toward the
1
drain at / in. See Fig. 10. If it is not possible to meet the re-
4
quired pitch, install a condensate at the unit to pump conden-
sate to building drain.
Horizontal units are not internally trapped, therefore an ex-
ternal trap is necessary. Install each unit with its own individual
trap and means to flush or blow out the condensate drain line.
Do not install units with a common trap or vent. See Fig. 11 for
typical condensate connections.
NOTE: Never use a pipe size smaller than the connection.
NOTE: Some codes require the use of a secondary drain pan
under vertical units. Check local codes for more information.
VERTICAL UNITS (50PTV,PTD) — Each unit uses a con-
densate hose inside all cabinets as a trapping loop, therefore an
external trap is not necessary. See Fig. 12.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Each unit must be installed with its own individual vent and
means to flush or blow out the condensate drain line. Do not in-
stall units with a common trap or vent.
• Be sure to support the line where anticipated sagging from
the condensate or when “double trapping” may occur.
• If condensate pump is present on unit, be sure drain connec-
tions have a check valve to prevent back flow of condensate
into other units.
Step 7 — Pipe Connections — Depending on the
application, there are 3 types of WSHP piping systems to
choose from: water loop, ground-water and ground loop. Refer
to Piping Section of Carrier System Design Manual for addi-
tional information.
1/4” Pitch for
Drainage
All WSHP units use low temperature soldered female pipe
thread fittings for water connections to prevent annealing and
out-of-round leak problems which are typically associated with
high temperature brazed connections. Refer to Table 1 for con-
nection sizes. When making piping connections, consider the
following:
• Use a backup wrench when making screw connections to
unit to prevent internal damage to piping.
Pitch Toward
Drain
• Insulation may be required on piping to avoid condensation
in the case where fluid in loop piping operates at tempera-
tures below dew point of adjacent air.
Drain Connection
Fig. 10 — Horizontal Unit Pitch
• Piping systems that contain steel pipes or fittings may be
subject to galvanic corrosion. Dielectric fittings may be
used to isolate the steel parts of the system to avoid galvanic
corrosion.
WATER LOOP APPLICATIONS — Water loop applications
usually include a number of units plumbed to a common pip-
ing system. Maintenance to any of these units can introduce air
into the piping system. Therefore, air elimination equipment
comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.25 and 3.5 gpm per
ton of cooling capacity. For proper maintenance and servicing,
pressure-temperature (P/T) ports are necessary for temperature
and flow verification.
Cooling tower/boiler systems typically utilize a common
loop maintained at 60 to 95 F. The use of a closed circuit evap-
orative cooling tower with a secondary heat exchange between
the tower and the water loop is recommended. If an open type
cooling tower is used continuously, chemical treatment and fil-
tering will be necessary.
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
In addition to complying with any applicable codes, consid-
er the following for system piping:
Fig. 11 — Trap Condensate Drain
• Piping systems using water temperatures below 50 F
3/4” Copper FPT/PVC
3/4” PVC
1
require / -in. closed cell insulation on all piping surfaces to
2
Vent
eliminate condensation.
1/2”
• Avoid all plastic to metal threaded fittings due to the poten-
1/4” per foot
slope to drain
tial to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize
internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Flush the piping system prior to operation to remove dirt
and foreign materials from the system.
1/2”
Water
Connections
Alternate
Condensate
Location
GROUND-WATER APPLICATIONS — Typical ground-
water piping is shown in Fig. 13. In addition to complying
with any applicable codes, consider the following for sys-
tem piping:
NOTE: Unit does not need to be sloped toward drain.
• Install shut-off valves for servicing.
Fig. 12 — Vertical Condensate Connection
• Install pressure-temperature plugs to measure flow and
temperature.
VENTING — Install a vent in the condensate line of any
application that may allow dirt or air to collect in the line. Con-
sider the following:
• Connect boiler drains and other valves using a “T” connec-
tor to allow acid flushing for the heat exchanger.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material.
• Always install a vent where an application requires a long
horizontal run.
• Always install a vent where large units are working against
higher external static pressure and to allow proper drainage
for multiple units connected to the same condensate main.
NOTE: PVC SCH40 should not be used due to system high
pressure and temperature extremes.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Water
Flow
Control
Regulator
(field-installed
accessory)
Valve
Pressure
Tank
(field-installed
accessory)
Water Out
Water In
From Pump
Shut-Off
Valve (field-installed accessory)
Strainer (field-installed accessory)
(16 to 20 mesh recommended for
filter sediment)
Boiler
Drains
(field-installed)
Fig. 13 — Typical Ground-Water Piping Installation
Water Supply and Quantity — Check water supply. Water
supply should be plentiful and of good quality. See Table 2 for
water quality guidelines.
5. Refer to Table 3. Do not exceed the minimum bend radius
for the hose selected. Exceeding the minimum bend radi-
us may cause the hose to collapse, which reduces water
flow rate. Install an angle adapter to avoid sharp bends
in the hose when the radius falls below the required
minimum.
IMPORTANT: Failure to comply with the above required
water quality and quantity limitations and the closed-
system application design requirements may cause damage
to the tube-in-tube heat exchanger. This damage is not the
responsibility of the manufacturer.
NOTE: Piping must comply with all applicable codes.
Insulation is not required on loop water piping except where
the piping runs through unheated areas or outside the building
or when the loop water temperature is below the minimum ex-
pected dew point of the pipe ambient. Insulation is required if
loop water temperature drops below the dew point.
In all applications, the quality of the water circulated
through the heat exchanger must fall within the ranges listed in
the Water Quality Guidelines table. Consult a local water treat-
ment firm, independent testing facility, or local water authority
for specific recommendations to maintain water quality within
the published limits.
GROUND-LOOP APPLICATIONS — Temperatures between
25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow
per ton is recommended. In addition to complying with any
applicable codes, consider the following for system piping:
CAUTION
Do not bend or kink supply lines or hoses.
Pipe joint compound is not necessary when Teflon threaded
tape is pre-applied to hose assemblies or when flared-end
connections are used. If pipe joint compound is preferred, use
compound only in small amounts on the male pipe threads of
the fitting adapters. Prevent sealant from reaching the flared
surfaces of the joint.
NOTE: When anti-freeze is used in the loop, assure that it is
compatible with Teflon tape or pipe joint compound employed.
Maximum allowable torque for brass fittings is 30 ft-lb. If a
torque wrench is not available, tighten finger-tight plus one
quarter turn. Tighten steel fittings as necessary.
Optional pressure-rated hose assemblies designed specifi-
cally for use with Carrier units are available. Similar hoses can
be obtained from alternate suppliers. Supply and return hoses
are fitted with swivel-joint fittings at one end to prevent kink-
ing during installation.
• Limit piping materials to only polyethylene fusion in the
buried sections of the loop.
• Do not use galvanized or steel fittings at any time due to
corrosion.
• Avoid all plastic to metal threaded fittings due to the poten-
tial to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use pressure-temperature (P/T) plugs to measure flow of
pressure drop.
INSTALLATION OF SUPPLY AND RETURN HOSE
KIT — Follow these piping guidelines.
1. Install a drain valve at the base of each supply and return
riser to facilitate system flushing.
CAUTION
2. Install shutoff/balancing valves and unions at each unit to
permit unit removal for servicing.
3. Place strainers at the inlet of each system circulating
pump.
Backup wrench is required when tightening water connec-
tions to prevent water line damage.
4. Select the proper hose length to allow slack between con-
nection points. Hoses may vary in length by +2% to –4%
under pressure.
Refer to Fig. 14 for an illustration of a supply/return hose
kit. Male adapters secure hose assemblies to the unit and risers.
Install hose assemblies properly and check them regularly to
avoid system failure and reduced service life.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — Water Quality Guidelines
HX
MATERIAL*
CONDITION
CLOSED RECIRCULATING†
OPEN LOOP AND RECIRCULATING WELL**
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium
Hardness Method
All
N/A
pH < 7.5 and Ca Hardness, <100 ppm
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be
implemented.
Ryznar Stability Index
6.0 - 7.5
If >7.5 minimize steel pipe use.
–0.5 to +0.5
All
N/A
Langelier Saturation Index
All
N/A
If <–0.5 minimize steel pipe use.
Based upon 150 F HWG and direct well, 85 F indirect well HX.
Iron Fouling
2+
Iron Fe (Ferrous)
<0.2 ppm (Ferrous)
All
All
N/A
N/A
(Bacterial Iron Potential)
2+
If Fe (ferrous) >0.2 ppm with pH 6 - 8, O <5 ppm check for iron bacteria.
2
Iron Fouling
<0.5 ppm of Oxygen
Above this level deposition will occur.
Corrosion Prevention††
pH
6 - 8.5
Minimize steel pipe below 7 and no open tanks with pH <8.
<0.5 ppm
6 - 8.5
All
All
Monitor/treat as needed.
Hydrogen Sulfide (H S)
2
At H S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.
2
N/A
N/A
Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
Ammonia Ion as Hydroxide,
Chloride, Nitrate and Sulfate
Compounds
<0.5 ppm
All
Maximum Chloride Levels
Maximum allowable at maximum water temperature.
50 F (10 C)
75 F (24 C)
100 F (38 C)
Copper
Cupronickel
304 SS
N/A
N/A
N/A
N/A
N/A
<20 ppm
<150 ppm
<400 ppm
<1000 ppm
>1000 ppm
NR
NR
NR
NR
<250 ppm
<550 ppm
>550 ppm
<150 ppm
<375 ppm
>375 ppm
316 SS
Titanium
Erosion and Clogging
Particulate Size and Erosion
<10 ppm of particles and a
maximum velocity of 6 fps.
Filtered for maximum
800 micron size.
<10 ppm (<1 ppm “sandfree” for reinjection) of particles and a maximum velocity
of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not
removed can potentially clog components.
All
All
Brackish
Use cupronickel heat exchanger when concentrations of calcium or sodium chlo-
ride are greater than 125 ppm are present. (Seawater is approximately 25,000
ppm.)
N/A
LEGEND
††If the concentration of these corrosives exceeds the maximum allowable
level, then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that no
agitation occur as the sample is taken. Unless tested immediately at the
site, the sample will require stabilization with a few drops of one Molar zinc
acetate solution, allowing accurate sulfide determination up to 24 hours
after sampling. A low pH and high alkalinity cause system problems, even
when both values are within ranges shown. The term pH refers to the acid-
ity, basicity, or neutrality of the water supply. Below 7.0, the water is consid-
ered to be acidic. Above 7.0, water is considered to be basic. Neutral water
contains a pH of 7.0.
HWG — Hot Water Generator
HX
—
—
Heat Exchanger
N/A
Design Limits Not Applicable Considering Recirculating
Potable Water
NR
SS
—
—
Application Not Recommended
Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS
(stainless steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping
system.
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is
equivalent to ppm.
**Recirculating open wells should observe the open recirculating design
considerations.
Step 8 — Wire Field Power Supply
WARNING
Table 3 — Metal Hose Minimum Bend Radii
HOSE DIAMETER (in.)
MINIMUM BEND RADII (in.)
1
1
/
/
2 /
4
2
2
3
4
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in
an open position during installation.
1
1
5 /
2
Swivel
Brass
Fitting
Brass
Fitting
Rib Crimped
CAUTION
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
Length
(2 ft Length Standard)
MPT
Fig. 14 — Supply/Return Hose Kit
All field-installed wiring, including the electrical ground,
MUST comply with the National Electrical Code (NEC) as
well as applicable local codes. In addition, all field wiring must
12
Download from Www.Somanuals.com. All Manuals Search And Download.
conform to the Class II temperature limitations described in the
NEC.
452 + 464 + 455
3
Average Voltage =
=
Refer to unit wiring diagrams Fig. 15-24 for a schematic of
the field connections, which must be made by the installing (or
electrical) contractor. For Deluxe D with WSHP Open controls
3-phase units and Complete C with Open controls single-phase
and 3-phase units contact Application Engineering. Refer to
Table 4 for fuse sizes.
1371
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup.
The installing (or electrical) contractor must make the field
connections when using field-supplied disconnect.
Maximum deviation is 7 v.
Operating voltage must be the same voltage and phase as
shown in electrical data shown in Table 4.
Make all final electrical connections with a length of flexi-
ble conduit to minimize vibration and sound transmission to
the building.
Determine percent voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
POWER CONNECTION — Make line voltage connection
by connecting the incoming line voltage wires to the line
side of the compressor contactor terminal as shown in
Fig. 25. See Table 4 for amperage ratings to provide correct
wire and maximum overcurrent protection sizing.
SUPPLY VOLTAGE — Operating voltage to unit must be
within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must
be balanced within 2%. Use the following formula to deter-
mine the percentage voltage imbalance:
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electri-
cal components.
NOTE: If more than 2% voltage imbalance is present, contact
your local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory
wired for 208 volts. The transformers may be switched to
230-volt operation by switching the red (208 volt) wire with
the orange (230 volt) wire at the L1 terminal.
% Voltage Imbalance
max voltage deviation from average voltage
460-VOLT OPERATION — Units using 460-v and an ECM
(electronically commutated motor) fan motor, modulating
HWR, and/or internal secondary pump will require a neutral
wire from the supply side in order to feed accessory with
265-v.
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 volts
BC = 464 volts
AC = 455 volts
Table 4 — 50PTH,PTV,PTD Electrical Data
COMPRESSOR
UNITS WITH HWR
50PTH,
PTV, PTD
UNITS
FAN
MOTOR
FLA
MIN
MAX
FUSE/
HACR
VOLTAGE
MIN/MAX
TOTAL
REHEAT TOTAL
MIN
MAX
V-PH-Hz*
CIRCUIT
AMPS
UNIT FLA
RLA
LRA
PUMP
UNIT
CIRCUIT FUSE/
FLA
FLA
AMP
18.0
26.0
19.1
10.4
34.6
24.9
16.0
40.1
30.1
19.2
42.1
HACR
25
40
30
15
50
35
20
60
026
038
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
197/254
197/254
197/254
414/506
197/254
197/254
414/506
197/254
197/254
414/506
197/254
10.3
16.7
11.2
4.5
52.0
82.0
58.0
4.3
4.3
4.3
4.1
7.0
7.0
6.9
7.0
7.0
6.9
7.0
14.6
21.0
15.5
8.6
28.2
20.5
13.3
32.6
24.6
15.9
34.2
17.2
25.2
18.3
9.7
33.5
23.9
14.9
39.0
29.0
18.2
41.0
25
40
25
15
50
35
20
60
45
25
60
0.8
0.8
0.8
15.4
21.8
16.3
9.3
29.0
0.7
21.2
13.5
6.4
96.0
88.0
41.0
1.07
1.07
1.07
1.07
1.07
1.07
1.07
29.3
21.6
14.4
33.7
25.7
17.7
35.3
049
25.6
17.6
9.0
118.0
123.0
62.0
064
072
45
25
60
208/230-1-60
27.2
150.0
LEGEND
FLA — Full Load Amps
*The 460-v units using an ECM (electronically commutated motor) fan
motor, modulating HWR, and/or an internal secondary pump will require
a neutral wire from the supply side in order to feed the accessory with
265-v.
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
RLA — Rated Load Amps
HWR — Hot Water Reheat
13
Download from Www.Somanuals.com. All Manuals Search And Download.
G
Y
R
G
G
G
G
14
Download from Www.Somanuals.com. All Manuals Search And Download.
G
Y
R
G
G
G
G
15
Download from Www.Somanuals.com. All Manuals Search And Download.
G
Y
R
G
G
G
G
16
Download from Www.Somanuals.com. All Manuals Search And Download.
G
Y
R
G
G
G
G
17
Download from Www.Somanuals.com. All Manuals Search And Download.
G
Y
R
G
G
G
G
18
Download from Www.Somanuals.com. All Manuals Search And Download.
G
Y
R
G
G
G
G
19
Download from Www.Somanuals.com. All Manuals Search And Download.
a50-8363
20
Download from Www.Somanuals.com. All Manuals Search And Download.
a50-8364
21
Download from Www.Somanuals.com. All Manuals Search And Download.
a50-8570
22
Download from Www.Somanuals.com. All Manuals Search And Download.
a50-8571
D B
8
7
6
4
5 3
1
2
1
D
L E
1
2
4
3
1
2
G n d
n e R t +
N
E E G R
E I T W H
B L A C K
R E
t - R n e
V
+ 1 2
D
To WSHP Controller
Rnet Terminals (J13)
23
Download from Www.Somanuals.com. All Manuals Search And Download.
CAPACITOR
COMPLETE C CONTROL
COMPRESSOR CONTACTOR
LINE
L O A D
ECM CONTROL
BOARD
TRANSFORMER
Fig. 25 — 50PTH,PTV,PTD Typical Single-Phase Line Voltage Power Connection
WSHP OPEN WIRING — The WSHP Open controller will Table 6 — SPT Sensors
be factory mounted to the unit control panel and wired to the
Complete C or Deluxe D control board, however, the system
wiring will need to be completed utilizing WSHP Open con-
troller wiring diagrams and the Third Party Integration (TPI)
Guide. Factory installation includes harness, LWT (leaving
water temperature), supply air, and condensate sensor.
PART
SENSOR
FEATURES
NUMBER
SPT
Standard
• Local access port
• No operator control
SPS
• Slide potentiometer to adjust set point
• Manual on button to override schedule
• LED to show occupied status
• Local access port
SPT Plus
SPT Pro
SPPL
SPP
• LCD display
WARNING
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside
air temperatures, set points, and local override
time
Disconnect all power to the unit before performing mainte-
nance or service. Unit may automatically start if power is
not disconnected. Failure to follow this warning could
cause personal injury, death, and/or equipment damage.
• Local access port
• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside
air temperatures, set points, and local override
time
Wiring Sensors to Inputs — Sensors can be wired to the
WSHP Open controller’s inputs. See Table 5.
All field control wiring that connects to the WSHP Open con-
troller must be routed through the raceway built into the corner
post. The raceway provides the UL required clearance between
high and low-voltage wiring.
SPT Pro
Plus
SPPF
• Local access port
• Fan speed*
*The SPT Pro Plus fan speed adjustment has no effect in this application.
Wire SPT sensors to the WSHP Open controller’s Rnet
port. An Rnetbus can consist of any of the following combina-
tions of devices wired in a daisy-chain configuration:
1. Pass control wires through the hole provided in the corner
post.
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor
• 1 to 4 SPT Standard sensors
2. Feed the wires through the raceway to the WSHP Open
controller.
3. Connect the wires to the removable Phoenix connectors.
4. Reconnect the connectors to the board.
Field-Supplied Sensor Hardware — The WSHP Open con-
troller is configurable with the following field-supplied sen-
sors. See Table 5.
• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or
SPT Pro Plus sensor
6
• Any of the above combinations, plus up to 2 BACview
Handheld but no more than 6 total devices
NOTE: If the Rnetbus has multiple SPT Standard sensors, each
sensor must be given a unique address on the Rnetbus. See the
Carrier Open Sensor Installation Guide.
Use the specified type of wire and cable for maximum signal
integrity. See Table 7.
Table 5 — Field-Supplied Sensors for
WSHP Open Controller
SENSOR
NOTES
Space Temperature Sensor
(SPT)
Field Installed (Must be used with
WSHP Open controller.)
Table 7 — Rnet Wiring Specifications
RNET WIRING SPECIFICATIONS
Outdoor Air
Network Sensor
Temperature Sensor
4 conductor, unshielded, CMP,
Description
plenum rated cable
Indoor Air Quality Sensor
(Separate Sensor)
Required only for demand
control ventilation.
Conductor
Maximum Length
18 AWG
500 ft
Space Relative
Humidity Sensor
Separate Sensor
Jacket: white
Wiring: black, white, green, red
Recommended Coloring
6
NOTE: BACview Handheld or Virtual BACview can be used as the user
interface.
UL Temperature
Voltage
32 to 167 F
For specific details about sensors, refer to the literature sup-
plied with the sensor.
300-vac, power limited
UL: NEC CL2P, or better
Listing
Wiring a SPT Sensor — A WSHP Open controller is connect-
ed to a wall-mounted space temperature (SPT) sensor to moni-
tor room temperature using a Molex plug.
The WSHP Open system offers the following SPT sensors.
See Table 6.
LEGEND
AWG — American Wire Gage
CMP — Communications Plenum Cable
NEC — National Electrical Code
UL
— Underwriters Laboratories
24
Download from Www.Somanuals.com. All Manuals Search And Download.
To wire the SPT sensor to the controller:
Wiring a Relative Humidity (RH) Sensor — The RH sensor
is used for zone humidity control (dehumidification) if the
WSHP unit has a dehumidification device. If not, the sensor
only monitors humidity.
1. Partially cut , then bend and pull off the outer jacket of
the Rnet cable(s), being careful not to nick the inner
insulation.
NOTE: Do not use a relative humidity sensor and CO sensor
1
2
2. Strip about / in. of the inner insulation from each wire.
4
on the same zone controller if both sensors are powered off the
board. If sensors are externally powered, both sensors may be
used on the same zone controller.
See Fig. 26.
OUTER JACKET
If the cable used to wire the RH sensor to the controller will
be less than 100 ft, an unshielded 22 AWG (American Wire
Gage) cable should be used. If the cable will be greater than
100 ft, a shield 22 AWG cable should be used. The cable
should have a maximum length of 500 ft.
To wire the RH sensor to the controller:
1. Strip the outer jacket from the cable for at least 4 inches.
a50-8443
.25 IN.
INNER INSULATION
Fig. 26 — Rnet Cable Wire
3. Wire each terminal on the sensor to the same terminal on
the controller. See Fig. 15-24. Table 8 shows the recom-
mended Rnet wiring scheme.
1
2. Strip / in. of insulation from each wire.
4
3. Wire the sensor to the controller.
Table 8 — Rnet Wiring
Step 9 — Wire Field Controls
THERMOSTAT CONNECTIONS — The thermostat
should be wired directly to the ECM control board. See
Fig. 27.
WIRE
Red
Black
White
Green
TERMINAL
+12-v
.Rnet–
Rnet+
Gnd
WATER FREEZE PROTECTION — The Aquazone™ con-
trol allows the field selection of source fluid freeze protection
points through jumpers. The factory setting of jumper JW3
(FP1) is set for water at 30 F. In earth loop applications, jumper
JW3 should be clipped to change the setting to 10 F when
using antifreeze in colder earth loop applications. See Fig. 28.
NOTE: The extended range option should be selected
with water temperatures below 60 F to prevent internal
condensation.
NOTE: The wire should be connected to the terminal shown.
Wiring a Supply Air Temperature (SAT) Sensor
SAT sensor is required for reheat applications.
If the cable used to wire the SAT sensor to the controller
will be less than 100 ft, an unshielded 22 AWG (American
Wire Gage) cable should be used. If the cable will be greater
than 100 ft, a shield 22 AWG cable should be used. The cable
should have a maximum length of 500 ft.
To wire the SAT sensor to the controller:
1. Wire the sensor to the controller. See Fig. 15-24.
2. Verify that the Enable SAT jumper is on.
—
The
AIR COIL FREEZE PROTECTION — The air coil freeze
protection jumper JW2 (FP2) is factory set for 30 F and should
not need adjusting.
3. Verify that the Enable SAT and Remote jumper is in the
left position.
ACCESSORY CONNECTIONS — Terminal A on the control
is provided to control accessory devices such as water valves,
electronic air cleaners, humidifiers, etc. This signal operates
with the compressor terminal. See Fig. 29. Refer to the specific
unit wiring schematic for details.
NOTE: The A terminal should only be used with 24-volt
signals — not line voltage signals.
WATER SOLENOID VALVES — An external solenoid
valve(s) should be used on ground water installations to shut
off flow to the unit when the compressor is not operating. A
slow closing valve may be required to help reduce water
hammer. Figure 29 shows typical wiring for a 24-vac external
solenoid valve. Figures 30 and 31 illustrate typical slow closing
water control valve wiring for Taco 500 Series and Taco ESP
Series valves. Slow closing valves take approximately 60 sec.
to open (very little water will flow before 45 sec.). Once fully
open, an end switch allows the compressor to be energized (on-
ly on valves with end switches). Only relay or triac based elec-
tronic thermostats should be used with slow closing valves.
When wired as shown, the slow closing valve will operate
properly with the following notations:
Wiring an Indoor Air Quality (IAQ) Sensor
—
An IAQ
sensor monitors CO levels. The WSHP Open controller uses
2
this information to adjust the outside-air dampers to provide
proper ventilation. An IAQ sensor can be wall-mounted or
mounted in a return air duct. (Duct installation requires an aspi-
rator box assembly.)
The sensor has a range of 0 to 2000 ppm and a linear 4 to
20 mA output. This is converted to 1 to 5 vdc by a 250-ohm,
1
/ watt, 2% tolerance resistor connected across the zone con-
4
troller’s IAQ input terminals.
NOTE: Do not use a relative humidity sensor and CO sensor
2
on the same zone controller if both sensors are powered off the
board. If sensors are externally powered, both sensors may be
used on the same zone controller.
If the cable used to wire the IAQ sensor to the controller
will be less than 100 ft, an unshielded 22 AWG (American
Wire Gage) cable should be used. If the cable will be greater
than 100 ft, a shield 22 AWG cable should be used. The cable
should have a maximum length of 500 ft.
To wire the IAQ sensor to the controller:
1. Wire the sensor to the controller. See Fig. 15-24.
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25 to 35 VA through
the “Y” signal of the thermostat.
1
2. Install a field-supplied 250-ohm, / watt, 2% tolerance
4
IMPORTANT: Connecting a water solenoid valve can
overheat the anticipators of electromechanical thermo-
stats. Only use relay based electronic thermostats.
resistor across the controller’s RH/IAQ and Gnd
terminals.
3. Verify the the RH/IAQ jumper is set to 0 to 5 vdc.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
CAPACITOR
COMPLETE C CONTROL
COMPRESSOR CONTACTOR
a50-8141
LINE
A D
L O
J1
S1
W
O
CFM
SW1
TRANSFORMER
SW2
SW3
SW4
SW5
SW6
SW7
SW8
SW9
Y2
Y1
G
ON
OFF
DEHUM
TB1
R
C
Y2 Y1
G
O
W
C
R
DH AL1
A
A
AL1
THERMOSTAT CONNECTION
Fig. 27 — Low Voltage Field Wiring
a50-7764tf
a50-8441
2
AMV
TACO VALVE
3
1
HEATER SWITCH
AQUAZONE CONTROL (Complete C Shown)
THERMOSTAT
Fig. 28 — Typical Aquazone™ Control Board
Jumper Locations
Fig. 30 — AMV Valve Wiring
TERMINAL STRIP P2
C
TYPICAL
WATER
VALVE
24 VAC
A
a50-8442
Fig. 31 — Taco SBV Valve Wiring
Fig. 29 — Typical Accessory Wiring
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Dehumidification Mode — The dehumidification mode
setting provides field selection of humidity control. When op-
erating in the normal mode, the cooling airflow settings are de-
termined by the cooling tap setting in Table 12.
Step 10 — Operate ECM Interface Board
STANDALONE — NO DDC CONTROLS — The ECM
fan is controlled by an interface board that converts thermostat
inputs and field selectable cfm settings to signals used by the
ECM (electronically commutated motor) controller. See
Fig. 32.
Table 12 — Dehumidificaton Mode Settings
DIP SWITCH
TAP SETTING
NOTE: Power must be off to the unit for at least three seconds
before the ECM will recognize a speed change. The motor will
recognize a change in the CFM Adjust or Dehumidification
mode settings while the unit is powered.
SW9
NORM
ON
Dehumid
OFF
When dehumidification is enabled, there is a reduction in
airflow in cooling to increase the moisture removal of the heat
pump. The Dehumidification mode can be enabled in two
ways:
There are four different airflow settings from lowest airflow
rate (speed tap 1) to the highest airflow rate (speed tap 4).
Tables 9-13 indicate settings for the ECM interface board, fol-
lowed by detailed information for each setting.
1. Constant Dehumidification mode: When the Dehumidifi-
cation mode is selected via DIP switch, the ECM will
operate with a multiplier applied to the cooling CFM
settings (approximately 20 to 25% lower airflow). Any
time the unit is running in the Cooling mode, it will oper-
ate at the lower airflow to improve latent capacity. The
“DEHUM” LED will be illuminated at all times. Heating
airflow is not affected.
CAUTION
When the disconnect switch is closed, high voltage is pres-
ent in some areas of the electrical panel. Exercise caution
when working with energized equipment.
Cooling — The cooling setting determines the cooling (nor-
mal) cfm for all units with ECM motor. Cooling (normal) set-
ting is used when the unit is not in Dehumidification mode. Tap
1 is the lowest cfm setting, while tap 4 is the highest cfm set-
ting. To avoid air coil freeze-up, tap 1 may not be used if the
Dehumidification mode is selected. See Table 9.
NOTE: Do not select Dehumidification mode if cooling
setting is tap 1.
2. Automatic (humidistat-controlled) Dehumidification
mode: When the Dehumidification mode is selected
via DIP switch AND a humidistat is connected to termi-
nal DH, the cooling airflow will only be reduced when
the humidistat senses that additional dehumidification is
required. The DH terminal is reverse logic. Therefore,
a humidistat (not dehumidistat) is required. The
“DEHUM” LED will be illuminated only when the hu-
midistat is calling for Dehumidification mode. Heat-
Table 9 — Cooling Settings
DIP SWITCH
TAP SETTING
SW1
ON
ON
OFF
OFF
SW2
ON
OFF
ON
1
2
3
4
ing
airflow is not affected.
NOTE: Do not select Dehumidification mode if cooling
setting is tap 1.
OFF
Heating — The heating setting determines the heating cfm
for 50PTH,PTV,PTD units. Tap 1 is the lowest cfm setting,
while tap 4 is the highest cfm setting. See Table 10.
1/4" SPADE
CONNECTIONS
TO COMPLETE C OR
DELUXE D BOARD
THERMOSTAT
INPUT LEDS
Table 10 — Heating Settings
G
G
G
G
R
DIP SWITCH
TAP SETTING
SW3
ON
ON
OFF
OFF
SW4
ON
OFF
ON
1
2
3
4
CFM COUNTER
THERMOSTAT
CONNECTIONS
1 FLASH PER 100 CFM
Y
OFF
ECM MOTOR
LOW VOLTAGE
CONNECTOR
CFM Adjust — The CFM Adjust setting allows four selec-
tions. The NORM setting is the factory default position. The +
or – settings adjust the airflow by ±15%. The + or – settings are
used to “fine tune” airflow adjustments. The TEST setting runs
the ECM at 70% torque, which causes the motor to operate
like a standard PSC motor, and disables the cfm counter. See
Table 11.
G
DEHUMIDIFICATION
LED
Table 11 — CFM Adjust Settings
FAN SPEED SELECTION DIP SWITCH
DIP SWITCH
TAP SETTING
Fig. 32 — ECM Interface Board Physical Layout
SW7
ON
ON
OFF
OFF
SW8
ON
OFF
ON
TEST
–
+
NORM
OFF
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13 — Blower Performance Data
FAN
MOTOR
(hp)
COOLING MODE (cfm)
Stage 1 Stage 2 Fan
DEHUMIDIFICATION MODE (cfm)
HEATING MODE (cfm)
50PT
MAX ESP
TAP
SETTING
UNIT SIZE (in. wg)
Stage 1
Stage 2
Fan
Stage 1
Stage 2
Fan
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
810
725
620
950
850
730
475
425
370
300
700
630
540
450
870
780
670
560
1020
920
790
660
1050
980
910
850
630
560
490
—
870
780
670
—
1140
1020
870
—
1300
1160
1000
—
740
660
570
—
1090
980
840
—
1350
1210
1040
—
1600
1430
1230
—
475
425
370
—
700
630
540
—
870
780
670
—
1020
920
790
—
920
825
710
1060
950
820
475
425
370
300
700
630
540
450
870
780
670
560
1020
920
790
660
1050
980
910
850
1
026
038
049
064
072
0.50
0.50
0.75
0.75
0.75
/
/
2
520
610
600
690
1120
1000
860
1400
1250
1080
900
1120
1000
860
1400
1250
1080
900
1
2
730
730
1460
1300
1120
940
1670
1500
1280
1080
1620
1500
1400
1320
1730
1550
1330
1120
2050
1825
1580
1320
2190
1950
1830
1700
1560
1400
1200
1010
1860
1650
1430
1200
1690
1600
1400
1240
1850
1650
1430
1200
2280
2050
1750
1470
2230
2100
1850
1620
1
1
1
1270
1170
1100
—
1650
1520
1420
—
1050
980
910
—
WSHP OPEN CONTROLS — The ECM fan is controlled by
an interface board that converts the fan speed outputs from the
WSHP Open control board to the signal used by the ECM mo-
tor (see Fig 35). The indicator LEDs allow the service techni-
cian to view the airflow mode that the WSHP Open control is
commanding. The table below indicates the illuminated LEDs
for each fan mode.
Table 14A). The fan speed and airflow is independent from the
compressor capacity control. During Fan Only operation, the
fan will operate at the Fan Only airflow value specified in the
table for the appropriate tap setting. Once either cooling or
heating is required and the compressor is energized, the fan
will increase the minimum airflow across the coil to the value
defined by the low fan selection. Coil freeze protection and ex-
cessive discharge air temperature protection are integral parts
of the WSHP Open controller function so the fan airflow can
increase to medium or high airflow as required and indepen-
dent of compressor capacity to prevent excessively hot or cold
supply air temperature and coil freeze-up. The selection of the
high fan airflow setting is independent of the other fan airflow
settings and is defined in Table 14B. The high airflow must be
chosen so that it is equal to or greater than the medium fan air-
flow. Therefore the tap setting for high fan (SW5 and SW6)
MUST equal or exceed the tap chosen for the SW3 and SW4.
ECM INDICATORS LEDs
SPEED
Fan Only
Low Fan
Med Fan
High Fan
G
G + Y1
G + Y1 + Y2
G + Y1 +W
NOTE: Power must be off to the unit for at least three seconds
before the ECM will recognize a speed change. The motor will
recognize a change in the CFM Adjust setting (SW7 and SW8)
while the unit is powered.
Dehumidification — When Dehumidification is used, the fan
operates at the airflow setting defined by the Medium Fan air-
flow setting and the tap position of SW3 and SW4.
CFM Adjust — The CFM Adjust setting allows the balancer
to fine tune the actual airflow. SW7 and SW8 are used to set
the CFM Adjustment if necessary. The NORM setting is the
factory default. The (+) or (-) settings provide the ability to ad-
just the airflow by either +15% or -15% as needed. A test posi-
tion is also provided but should not be used (see Table 11).
The WSHP Open controller provides four different airflow
settings which can be set between the lowest airflow (tap 1) to
the highest airflow (tap 4). The lowest three airflow settings
(Fan Only, Low, and Medium) are set using SW3 and SW 4
while the highest airflow (High) is set independently using
SW5 and SW6. This provides the ability to better adjust the fan
performance of the unit to meet the required load conditions.
Cooling and Heating — The SW3 and SW4 DIP switch set-
tings determine the fan airflow (cfm) to be used during normal
Fan Only, Cooling, Heating, and Dehumidification modes (see
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14A — WSHP Open — Fan Only / Low Fan and Med Fan Airflow
50PT UNIT MAX FAN MOTOR
SW 3
(SW 1)
SW 4
(SW 2)
COOLING AND
HEATING LOW FAN
COOLING AND
HEATING MED FAN
TAP SETTING
FAN ONLY
SIZE
ESP
HP
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
OFF
OFF
ON
OFF
ON
475
425
370
300
700
630
540
450
870
780
670
560
1020
920
780
660
1050
980
910
850
920
825
1050
950
26
0.5
0.5
OFF
ON
OFF
ON
710
600
1120
1000
860
820
690
1400
1250
1080
900
1850
1650
1430
1200
2280
2040
1750
1470
2230
2100
1850
1620
ON
OFF
OFF
ON
38
49
64
72
0.5
0.5
1
OFF
ON
OFF
ON
ON
730
OFF
OFF
ON
1560
1400
1200
1010
1860
1650
1430
1200
1600
1600
1400
1240
0.75
0.75
0.75
OFF
ON
OFF
ON
ON
OFF
OFF
ON
1
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
1
ON
NOTE: Factory default setting shown bold.
IMPORTANT: The tap setting for high fan MUST equal or exceed the
tap setting for fan only/low/med fan
Table 14B — WSHP Open — High Fan Airflow
50PT UNIT SIZE MAX ESP
FAN MOTOR HP
TAP SETTING
SW 5
OFF
OFF
ON
SW 6
OFF
ON
COOLING AND HEATING HIGH FAN
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
1060
950
26
38
49
64
72
0.5
0.5
0.5
0.5
1
OFF
ON
820
690
ON
OFF
OFF
ON
OFF
ON
1400
1350
1350
1350
1850
1660
1430
1350
2280
2050
1750
1470
2230
2100
1870
1670
OFF
ON
ON
OFF
OFF
ON
OFF
ON
0.75
0.75
0.75
OFF
ON
ON
OFF
OFF
ON
OFF
ON
1
OFF
ON
ON
OFF
OFF
ON
OFF
ON
1
OFF
ON
ON
NOTE: Factory default setting shown bold.
IMPORTANT: The tap setting for high fan MUST equal or exceed the
tap setting for fan only/low/med fan
5. Air is purged from closed loop system.
6. System is balanced as required. Monitor if necessary.
7. Isolation valves are open.
PRE-START-UP
8. Water control valves or loop pumps are wired.
9. Condensate line is open and correctly pitched.
10. Transformer switched to lower voltage tap if necessary.
11. Blower rotates freely — shipping support is removed.
12. Blower speed is on correct setting.
13. Air filter is clean and in position.
14. Service/access panels are in place.
15. Return-air temperature is between 40 to 80 F heating and
50 to 110 F cooling.
System Checkout — When the installation is complete,
follow the system checkout procedure outlined below before
starting up the system. Be sure:
1. Voltage is within the utilization range specifications of the
unit compressor and fan motor and voltage is balanced
for 3-phase units.
2. Fuses, breakers and wire are correct size.
3. Low voltage wiring is complete.
4. Piping and system flushing is complete.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
16. Air coil is clean.
17. Control field-selected settings are correct.
AIR COIL — To obtain maximum performance, clean the air
coil before starting the unit. A 10% solution of dishwasher
detergent and water is recommended for both sides of the coil.
Rinse thoroughly with water.
NOTE: The alarm relay will not cycle during Test mode if
switch is set to OFF, stage 2.
SWITCH 3 — Not used.
DDC OUTPUT AT EH2 — Switch 4 provides a selection for
Direct Digital Control (DDC) operation. If set to DDC output
at EH2, the EH2 terminal will continuously output the last
fault code of the controller. If the control is set to EH2 Normal,
then EH2 will operate as standard electric heat output. Set the
switch to ON to set the EH2 to normal. Set the switch to OFF
to set the DDC output at EH2.
FACTORY SETTING — Switch 5 is set to ON. Do not
change the switch to OFF unless instructed to do so by the
factory.
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the
control board are used to customize unit operation and can be
configured in the field.
IMPORTANT: Jumpers and DIP switches should only
be clipped when power to control board has been turned
off.
Deluxe D Control DIP Switches — The Deluxe D
control has 2 DIP (dual in-line package) switch banks. Each
bank has 8 switches and is labeled either S1 or S2 on the cir-
cuit board. See Fig. 16, 18, 20, 22, and 23.
DIP SWITCH BANK 1 (S1) — This set of switches offers
the following options for Deluxe D control configuration:
Performance Monitor (PM) — The PM is a unique feature
that monitors water temperature and will display a warning
when heat pump is beyond typical operating range. Set switch 1
to enable or disable performance monitor. To enable the PM, set
the switch to ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation — Switch 2 will en-
able or disable compressor relay staging operation. The com-
pressor relay can be set to turn on with stage 1 or stage 2 call
from the thermostat. This setting is used with dual stage units
(units with 2 compressors and 2 Deluxe D controls) or in mas-
ter/slave applications. In master/slave applications, each com-
pressor and fan will stage according to its switch 2 setting. If
switch is set to stage 2, the compressor will have a 3-second
delay before energizing during stage 2 demand.
Complete C Control Jumper Settings
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3 (JW3-FP1 Low Temp) to
choose FP1 limit of either 30 F or 10 F. To select 30 F as the
limit, DO NOT clip the jumper. To select 10 F as the limit, clip
the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-
TING — Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of either 30 F or 10 F. To select 30 F as the limit, DO
NOT clip the jumper. To select 10 F as the limit, clip the
jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2
Dry) to either connect alarm relay terminal (AL2) to 24 vac (R)
or to remain as a dry contact (no connection). To connect AL2
to R, DO NOT clip the jumper. To set as dry contact, clip the
jumper.
Deluxe D Control Jumper Settings
NOTE: If DIP switch is set for stage 2, the alarm relay will not
cycle during Test mode.
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3 (JW3-FP1 Low Temp) to
choose FP1 limit of either 30 F or 10 F. To select 30 F as the
limit, DO NOT clip the jumper. To select 10 F as the limit, clip
the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-
TING — Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of either 30 F or 10 F. To select 30 F as the limit, DO
NOT clip the jumper. To select 10 F as the limit, clip the
jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2
Dry) to either connect alarm relay terminal (AL2) to 24 vac (R)
or to remain as a dry contact (no connection). To connect AL2
to R, DO NOT clip the jumper. To set as dry contact, clip the
jumper.
Heating/Cooling Thermostat Type — Switch 3 provides se-
lection of thermostat type. Heat pump or heat/cool thermostats
can be selected. Select OFF for heat/cool thermostats. When in
heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for
cooling stage 2, W1 is used for heating stage 1 and O/W2 is
used for heating stage 2. Select ON for heat pump thermostats.
In heat pump mode, Y1 used is for compressor stage 1, Y2 is
used for compressor stage 2, W1 is used for heating stage 3 or
emergency heat, and O/W2 is used for reversing valve (heating
or cooling) depending upon switch 4 setting.
O/B Thermostat Type — Switch 4 provides selection for heat
pump O/B thermostats. O is cooling output. B is heating out-
put. Select ON for thermostats with O output. Select OFF for
thermostats with B output.
LOW PRESSURE SETTING — The Deluxe D control can
be configured for Low Pressure Setting (LP). Select jumper 1
(JW1-LP Norm Open) for choosing between low pressure
input normally opened or closed. To configure for normally
closed operation, DO NOT clip the jumper. To configure for
normally open operation, clip the jumper.
Dehumidification Fan Mode — Switch 5 provides selection
of normal or dehumidification fan mode. Select OFF for
dehumidification mode. The fan speed relay will remain OFF
during cooling stage 2. Select ON for normal mode. The fan
speed relay will turn on during cooling stage 2 in normal mode.
Output — Switch 6 provides selection for DDC operation. If
set to DDC output at EH2, the EH2 terminal will continuously
output the last fault code of the controller. If the control is set to
EH2 normal, then the EH2 will operate as standard electric
heat output. Set the switch to ON to set the EH2 to normal. Set
the switch to OFF to set the DDC output at EH2.
Boilerless Operation — Switch 7 provides selection of boil-
erless operation and works in conjunction with switch 8. In
boilerless operation mode, only the compressor is used for
heating when FP1 is above the boilerless changeover tempera-
ture set by switch 8 below. Select ON for normal operation or
select OFF for boilerless operation.
Complete C Control DIP Switches — The Com-
plete C control has 1 DIP (dual in-line package) switch bank
with five switches labeled SW1. See Fig. 15, 17 , 19, and 21.
PERFORMANCE MONITOR (PM) — The PM is a unique
feature that monitors water temperature and will display a warn-
ing when heat pump is beyond typical operating range. Refer to
Control Operation section for detailed information. DIP switch
1 will enable or disable this feature. To enable the PM, set the
switch to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor
delay. Set DIP switch to OFF for stage 2 in which the compres-
sor will have a 3-second delay before energizing.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Boilerless Changeover Temperature — Switch 8 on S1
provides selection of boilerless changeover temperature set
point. Select OFF for set point of 50 F or select ON for set
point of 40 F.
If switch 8 is set for 50 F, then the compressor will be used
for heating as long as the FP1 is above 50 F. The compressor
will not be used for heating when the FP1 is below 50 F and the
compressor will operates in emergency heat mode, staging on
EH1 and EH2 to provide heat. If a thermal switch is being used
instead of the FP1 thermistor, only the compressor will be used
for heating mode when the FP1 terminals are closed. If the FP1
terminals are open, the compressor is not used and the control
goes into emergency heat mode.
DIP SWITCH BANK 2 (S2) — This set of DIP switches is
used to configure accessory relay options. See Fig. 16, 18, 20,
22, and 23.
Switches 1 to 3 — These DIP switches provide selection of
Accessory 1 relay options. See Table 15A for DIP switch
combinations.
pump. The reversing valve ("O" signal) is energized in cool-
ing, along with the compressor contactor(s) and blower relay.
In the heating mode, the reversing valve is deenergized.
Almost any thermostat will activate the heat pump in heating
or cooling modes. The Deluxe D microprocessor board, which
is standard with the HWR option, will accept either heat pump
(Y,O) thermostats or non-heat pump (Y,W) thermostats.
The reheat mode requires either a separate humidistat/
dehumidistat or a thermostat that has an integrated dehumidifi-
cation function for activation. The Deluxe D board is config-
ured to work with either a humidistat or dehumidistat input to
terminal “H” (DIP switch settings for the Deluxe D board are
shown in Table 16). Upon receiving an “H” input, the Deluxe
D board will activate the cooling mode and engage reheat.
Table 16 — Humidistat/Dehumidistat Logic and
Deluxe D DIP Switch Settings
Reheat
Reheat
Sensor
2.1 2.2 2.3
Off Off Off
Logic
(ON) - H (OFF) - H
Humidistat
Reverse
0 VAC
24 VAC
0 VAC
Switches 4 to 6 — These DIP switches provide selection of
Accessory 2 relay options. See Table 15B for DIP switch
combinations.
Dehumidistat Off On Off Standard 24 VAC
Table 17 shows the relationship between thermostat input
signals and unit operation. There are four operational inputs for
single-stage units and six operational inputs for dual-stage
units:
Table 15A — DIP Switch Block S2 —
Accessory 1 Relay Options
• Fan Only
DIP SWITCH POSITION
ACCESSORY 1
RELAY OPTIONS
• Cooling Stage 1
• Cooling Stage 2
• Heating Stage 1
• Heating Stage 2
• Reheat Mode
WSHP OPEN CONTROLS — A heat pump equipped with
the hot water reheat option and the WSHP Open controller,
operates in three modes: Cooling, Heating and Dehumidifica-
tion. Cooling and Heating modes follow the standard water
source heat pump operation with the reversing valve control-
ling the operating mode (Heating or Cooling) and the compres-
sor.
1
2
3
Cycle with Fan
Digital NSB
Water Valve — Slow Opening
OAD
Reheat — Humidistat
Reheat — Dehumidistat
On
Off
On
On
Off
Off
On
On
Off
On
Off
On
On
On
On
Off
Off
Off
LEGEND
NSB — Night Setback
OAD — Outside Air Damper
NOTE: All other DIP switch combinations are invalid.
Table 15B — DIP Switch Block S2 —
Accessory 2 Relay Options
The hot water reheat option uses the Deluxe D board and
the optional humidity sensor to provide dehumidification oper-
ation that is separate from the standard heating or cooling cy-
cle. The Dehumidification mode is active when the value of the
humidity sensor exceeds the appropriate (occupied or unoccu-
pied) humidity setpoint in the WSHP Open controller. When
this occurs, the WSHP Open controller outputs a signal to the
H terminal of the Deluxe D board which starts dehumidifica-
tion with hot water reheat. The WSHP Open controller also
sets the fan to operate at the airflow defined by the medium fan
speed and the tap setting of SW3 and SW4. Dehumidification
is ONLY active when neither cooling nor heating is required
and the humidity sensor value exceeds the humidity setpoint.
Also, both the HWR option and the Optional RH sensor must
be set to Enable in the WSHP Open control for dehumidifica-
tion.
HWR APPLICATION CONSIDERATIONS — Unlike
most hot gas reheat options, the HWR option will operate
over a wide range of entering-water temperatures (EWTs).
Special flow regulation (water regulating valve) is not
required for low EWT conditions. However, below 55 F,
supply-air temperatures cannot be maintained at 72 F
because the cooling capacity exceeds the reheat coil capac-
ity at low water temperatures. Below 55 F, essentially all
water is diverted to the reheat coil (no heat of rejection to
the building loop). Although the HWR option will work fine
with low EWTs, overcooling of the space may result with
well water systems or, on rare occasions, with ground loop
(geothermal) systems (NOTE: Extended range units are
required for well water and ground loop systems). Since
dehumidification is generally only required in cooling, most
DIP SWITCH POSITION
ACCESSORY 2
RELAY OPTIONS
4
5
6
Cycle with Compressor
Digital NSB
Water Valve — Slow Opening
OAD
On
Off
On
On
On
On
Off
On
On
On
On
Off
LEGEND
NSB — Night Setback
OAD — Outside Air Damper
NOTE: All other switch combinations are invalid.
Auto Dehumidification Mode or High Fan Mode — Switch 7
provides selection of auto dehumidification fan mode or high
fan mode. In auto dehumidification fan mode, the fan speed
relay will remain off during cooling stage 2 if terminal H is
active. In high fan mode, the fan enable and fan speed relays will
turn on when terminal H is active. Set the switch to ON for auto
dehumidification fan mode or to OFF for high fan mode.
Factory Setting — Switch 8 is set to ON. Do not change the
switch to OFF unless instructed to do so by the factory.
Units with Modulating Hot Water Reheat
(HWR) Option
STANDALONE — NO DDC CONTROLS — A heat
pump equipped with hot water reheat (HWR) can operate in
three modes: cooling, cooling with reheat, and heating. The
cooling and heating modes are like any other water source heat
31
Download from Www.Somanuals.com. All Manuals Search And Download.
ground loop systems will not experience overcooling of the
supply-air temperature. If overcooling of the space is a con-
cern (e.g., computer room well water application), auxiliary
heating may be required to maintain space temperature
when the unit is operating in the dehumidification mode.
Water source heat pumps with HWR should not be used as
makeup air units. These applications should use equipment
specifically designed for makeup air.
CYCLE WITH FAN — In this configuration, the accessory
relay 1 will be ON any time the Fan Enable relay is on.
CYCLE WITH COMPRESSOR — In this configuration, the
accessory relay 2 will be ON any time the Compressor relay is
on.
DIGITAL NIGHT SET BACK (NSB) — In this configura-
tion, the relay will be ON if the NSB input is connected to
ground C.
HWR COMPONENT FUNCTIONS — The proportional
controller operates on 24 VAC power supply and automatically
adjusts the water valve based on the supply-air sensor. The
supply-air sensor senses supply-air temperature at the blower
inlet, providing the input signal necessary for the proportional
control to drive the motorized valve during the reheat mode of
operation. The motorized valve is a proportional actuator/three-
way valve combination used to divert the condenser water
from the coax to the hydronic reheat coil during the reheat
mode of operation. The proportional controller sends a signal
to the motorized valve based on the supply-air temperature
reading from the supply air sensor.
The loop pump circulates condenser water through the hy-
dronic reheat coil during the reheat mode of operation (refer to
Fig. 33). In this application, the loop pump is only energized
during the reheat mode of operation. The hydronic coil is uti-
lized during the reheat mode of operation to reheat the air to the
set point of the proportional controller. Condenser water is di-
verted by the motorized valve and pumped through the hydron-
ic coil by the loop pump in proportion to the control set point.
The amount of reheating is dependent on the set point and how
far from the set point the supply air temperature is. The factory
set point is 70 to 75 F, generally considered "neutral" air.
NOTE: If there are no relays configured for digital NSB, then
the NSB and override (OVR) inputs are automatically config-
ured for mechanical operation.
MECHANICAL NIGHT SET BACK — When NSB input is
connected to ground C, all thermostat inputs are ignored. A
thermostat set back heating call will then be connected to the
OVR input. If OVR input becomes active, then the Deluxe D
control will enter night low limit (NLL) staged heating mode.
The NLL staged heating mode will then provide heating dur-
ing the NSB period.
WATER VALVE (SLOW OPENING) — If relay is configured
for Water Valve (slow opening), the relay will start 60 seconds
prior to starting compressor relay.
OUTSIDE AIR DAMPER (OAD) — If relay is configured for
OAD, the relay will normally be ON any time the Fan Enable
relay is energized. The relay will not start for 30 minutes fol-
lowing a return to normal mode from NSB, when NSB is no
longer connected to ground C. After 30 minutes, the relay will
start if the Fan Enable is set to ON.
CAUTION
To avoid equipment damage, DO NOT leave system filled
in a building without heat during the winter unless anti-
freeze is added to system water. Condenser coils never
fully drain by themselves and will freeze unless winterized
with antifreeze.
Deluxe D Control Accessory Relay Configura-
tions — The following accessory relay settings are applica-
ble for Deluxe D control:
Table 17 — HWR Operating Modes
INPUT
Y1
Off
Off
On
On
On
Off
On
OUTPUT
MODE
O
On/Off
On/Off
On
On
On
On/Off
Off
Off
G
Y2*
Off
Off
Off
On
On/Off
Off
Off
On
On/Off
H
O
On/Off
On/Off
On
On
On
On
Off
Off
Off
G
Y1
Off
Off
On
On
On
On
On
On
On
Y2*
Off
Off
Off
On
On/Off
On
Off
On
On/Off
Reheat
Off
Off
Off
Off
Off
On
Off
Off
No Demand
Fan Only
Off
On
On
On
On
Off
On
On
On
Off
Off
Off
Off
On
On
Off
Off
On
Off
On
On
On
On
On
On
On
On
Cooling Stage 1
Cooling Stage 2
Cooling and Dehumidistat
Dehumidistat Only
Heating Stage 1
†
Heating Stage 2
Heating and Dehumidistat**
On
On
Off
Off
*Not applicable for single stage units; Full load operation for dual capacity
**Deluxe D is programmed to ignore the H demand when the unit is in heating
units.
mode.
†Cooling input takes priority over dehumidify input.
NOTE: On/Off is either on or off.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Out
(To Water Loop)
a50-8145
Refrigerant In
(Cooling)
Mixing Valve
Water In
(From Water Loop)
Internal Pump
COAX
Refrigerant Out
(Cooling)
Leaving
Air
Entering Air
Reheat
Coil
NOTE: All components shown are
internal to the heat pump unit.
Evaporator Coil
Fig. 33 — HWR Schematic
3. Balance airflow at registers.
START-UP
4. Adjust all valves to the full open position and turn on the
line power to all heat pump units.
5. Operate unit in the cooling cycle first, then the heating
cycle. Refer to Table 18 for unit operating limits. Al-
low 15 minutes between cooling and heating tests for
pressure to equalize.
NOTE: Two factors determine the operating limits of a unit:
entering-air temperature and water temperature. Whenever any
of these factors are at a minimum or maximum level, the other
two factors must be at a normal level to ensure proper unit
operation. See Table 18.
Use the procedure outlined below to initiate proper unit
start-up.
NOTE: This equipment is designed for indoor installation only.
Operating Limits
ENVIRONMENT — This equipment is designed for indoor
installation ONLY. Extreme variations in temperature, humidi-
ty and corrosive water or air will adversely affect the unit per-
formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name-
plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — Units start and operate
in an ambient temperature of 45 F with entering-air tempera-
ture at 50 F, entering-water temperature at 60 F and with both
air and water at the flow rates used.
NOTE: These operating limits are not normal or continuous
operating conditions. Assume that such a start-up is for the
purpose of bringing the building space up to occupancy tem-
perature. See Table 18 for operating limits.
Table 18 — Operating Limits —
50PTH, PTV, PTD Units
AIR LIMITS
Min. Ambient Air
Rated Ambient Air
Max. Ambient Air
Min. Entering Air
Rated Entering Air db/wb
Max. Entering Air db/wb
WATER LIMITS
COOLING (F)
HEATING (F)
45
80
100
50
80/67
110/83
40
70
85
40
70
80
Min. Entering Water
Normal Entering Water
Max. Entering Water
LEGEND
30
50-110
120
20
30-70
90
WARNING
When the disconnect switch is closed, high voltage is pres-
ent in some areas of the electrical panel. Exercise caution
when working with the energized equipment.
db
—
—
Dry Bulb
Wet Bulb
wb
NOTE: Value in heating column is dry bulb only. Any wet bulb reading is
acceptable.
1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Check the temperature of both supply and discharge
water. Compare to Tables 20-23. If temperature is within
range, proceed. If temperature is outside the range, check
the cooling refrigerant pressures in Tables 20-23.
5. Check air temperature drop across the coil when com-
pressor is operating. Air temperature drop should be
between 15 and 25 F.
Scroll Compressor Rotation — It is important to be
certain compressor is rotating in the proper direction. To
determine whether or not compressor is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
Unit Start-Up Heating Mode
pressure should rise, as is normal on any start-up.
NOTE: Operate the unit in heating cycle after checking the
cooling cycle. Allow 5 minutes between tests for the pressure
or reversing valve to equalize.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Turn off power to the unit. Install disconnect tag.
2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move
to their normal start-up levels.
When the compressor is rotating in the wrong direction, the
unit makes more noise and does not provide cooling.
After a few minutes of reverse operation, the scroll com-
pressor internal overload protection will open, thus activating
the unit lockout. This requires a manual reset. To reset, turn the
thermostat on and then off.
1. Turn thermostat to lowest setting and set thermostat
switch to HEAT position.
2. Slowly turn the thermostat to a higher temperature until
the compressor activates.
3. Check for warm air delivery at the unit grille within a few
minutes after the unit has begun to operate.
4. Check the temperature of both supply and discharge
water. Compare to Tables 20-23. If temperature is within
range, proceed. If temperature is outside the range, check
the heating refrigerant pressures in Tables 20-23.
5. Once the unit has begun to run, check for warm air deliv-
ery at the unit grille.
6. Check air temperature rise across the coil when compres-
sor is operating. Air temperature rise should be between
20 and 30 F after 15 minutes at load.
NOTE: There is a 5-minute time delay before the compressor
will start.
Unit Start-Up Cooling Mode
1. Adjust the unit thermostat to the warmest position.
Slowly reduce the thermostat position until the compres-
sor activates.
2. Check for cool air delivery at unit grille a few minutes
after the unit has begun to operate.
3. Verify that the compressor is on and that the water flow
rate is correct by measuring pressure drop through the
heat exchanger using P/T plugs. See Table 19. Check the
elevation and cleanliness of the condensate lines; any
dripping could be a sign of a blocked line. Be sure the
condensate trap includes a water seal.
7. Check for vibration, noise and water leaks.
Table 19 — Water Temperature Change
Through Heat Exchanger
COOLING
RISE (F)
HEATING
DROP (F)
WATER FLOW RATE (GPM)
Min
Max
Min
Max
For Closed Loop: Ground Source or
Cooling/Boiler Systems at 3 gpm/ton
9
12
4
8
For Open Loop: Ground Water Systems at
1.5 gpm/ton
20
26
10
17
Table 20 — Typical 50PTH,PTV,PTD026 Unit Operating Pressures and Temperatures
FULL LOAD COOLING WITHOUT HWG ACTIVE
Water
FULL LOAD HEATING WITHOUT HWG ACTIVE
Water
ENTERING
WATER
TEMP (F)
(EWT)
WATER
FLOW
(Gpm/Ton)
Air
Temp
Drop (F)
DB
Air
Suction Discharge Super-
Sub-
cooling
(F)
Suction Discharge Super-
Sub-
cooling
(F)
Temp
Rise
(F)
Temp
Drop
(F)
Temp
Rise (F)
DB
Pressure Pressure
heat
(F)
Pressure Pressure
heat
(F)
(psig)
(psig)
(psig)
(psig)
1.5
2.25
3
1.5
2.25
3
118-128
118-128
118-128
128-138
128-138
128-138
159-179
146-166
132-152
186-206
172-192
158-178
25-30
25-30
25-30
18-23
18-23
18-23
9-14
7-12
7-12
8-13
6-11
6-11
16.7-18.7
12.3-14.3
7.9- 9.9
16.3-18.3
12.1-14.1
7.8- 9.8
19-25
20-26
20-26
19-25
20-26
20-26
73- 83
75- 85
78- 88
102-112
106-116
110-120
273-293
275-295
277-297
302-322
303-323
305-325
6-11
6-11
6-11
8-12
8-12
8-12
3- 8
3- 8
3- 8
6-11
6-11
6-11
5.9- 7.9
4.2- 6.2
2.7- 4.7
8.9-10.9
6.7- 8.7
4.5- 6.5
16-22
17-23
18-24
22-28
23-29
23-29
30
50
1.5
2.25
3
136-146
136-146
136-146
281-301
267-287
253-273
7-12
7-12
7-12
7-12
5-10
4- 9
15.7-17.7
11.6-13.6
7.6- 9.6
19-25
19-25
19-25
128-138
134-144
141-151
330-350
332-352
334-354
10-15
10-15
10-15
8-13
8-13
8-13
11.3-13.3
8.5-10.5
5.8- 7.8
27-34
28-35
28-35
70
1.5
2.25
3
139-149
139-149
139-149
368-388
354-374
340-360
6-11
6-11
6-11
7-12
5-10
5-10
14.9-16.9
11.0-13.0
7.2- 9.2
18-24
18-24
18-24
162-172
166-176
171-181
367-387
372-392
377-397
14-19
15-20
17-22
10-15
10-15
10-15
14.4-16.4
10.8-12.8
7.1- 9.1
33-41
34-42
34-42
90
1.5
2.25
3
143-153
143-153
143-153
465-485
450-470
433-453
6-11
6-11
6-11
7-12
5-10
5-10
13.9-15.9
10.2-12.2
6.5- 8.5
17-23
17-23
17-23
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
110
LEGEND
DB
HWG — Hot Water Generator
— No heating operation in this temperature range
— Dry Bulb
—
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Typical 50PTH,PTV,PTD038 Unit Operating Pressures and Temperatures
FULL LOAD COOLING WITHOUT HWG ACTIVE
Water
FULL LOAD HEATING WITHOUT HWG ACTIVE
Water
ENTERING
WATER
TEMP (F)
(EWT)
WATER
FLOW
(Gpm/Ton)
Air
Temp
Drop (F)
DB
Air
Temp
Rise (F)
DB
Suction Discharge Super-
Sub-
cooling
(F)
Suction Discharge Super-
Sub-
cooling
(F)
Temp
Rise
(F)
Temp
Drop
(F)
Pressure Pressure
heat
(F)
Pressure Pressure
heat
(F)
(psig)
(psig)
(psig)
(psig)
1.5
2.25
3
1.5
2.25
3
120-130
119-129
119-129
129-139
128-138
128-138
156-176
148-168
138-158
225-245
211-231
197-217
25-30
25-30
25-30
15-20
15-20
15-20
9-14
8-13
8-13
10-15
9-14
9-14
22.1-24.1
16.8-18.8
10.5-12.5
21.9-23.9
16.1-18.1
10.3-12.3
18-24
19-25
19-25
18-24
19-25
19-25
69- 79
73- 83
76- 86
96-106
100-110
105-115
293-313
297-317
300-320
322-342
326-346
331-351
7-12
7-12
7-12
10-15
10-15
10-15
14-19
14-19
14-19
17-22
17-22
17-22
8.9-10.9
6.7- 8.7
4.5- 6.5
12.2-14.2
9.3-11.3
6.4- 8.4
17-23
18-24
19-25
23-29
24-30
24-30
30
50
1.5
2.25
3
136-146
135-145
135-145
302-322
283-303
265-285
9-14
9-14
9-14
13-18
12-17
12-17
21.5-23.5
15.8-17.8
10.0-12.0
18-24
19-25
19-25
123-133
129-139
135-145
352-372
358-378
364-384
11-16
11-16
11-16
19-24
19-24
19-24
15-17
11.6-13.6
8.2-10.2
28-35
29-36
30-37
70
1.5
2.25
3
140-150
140-150
140-150
390-410
369-389
349-369
7-12
8-13
8-13
13-18
8-13
8-13
20.5-22.5
14.9-16.9
9.3-11.3
17-23
17-23
17-23
157-167
169-179
181-191
390-410
399-419
408-428
13-18
18-23
21-23
36-44
37-45
39-47
90
13-18 16.5-21.5 15.5-17.5
14-19
15-20
10.5-12.5
1.5
2.25
3
145-155
145-155
145-155
488-508
467-487
447-467
7-12
8-13
8-13
13-18
8-13
8-13
19.0-21.0
14.0-16.0
9.0-11.0
17-23
17-23
17-23
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
110
LEGEND
DB
HWG — Hot Water Generator
— No heating operation in this temperature range
— Dry Bulb
—
Table 22 — Typical 50PTH,PTV,PTD049 Unit Operating Pressures and Temperatures
FULL LOAD COOLING WITHOUT HWG ACTIVE
Water
FULL LOAD HEATING WITHOUT HWG ACTIVE
Water
ENTERING
WATER
FLOW
(Gpm/Ton)
Air
Temp
Drop (F)
DB
Air
Temp
Rise (F)
DB
WATER
TEMP (F)
(EWT)
Suction Discharge Super-
Sub-
cooling
(F)
Suction Discharge Super-
Sub-
cooling
(F)
Temp
Rise
(F)
Temp
Drop
(F)
Pressure Pressure
heat
(F)
Pressure Pressure
heat
(F)
(psig)
(psig)
(psig)
(psig)
1.5
2.25
3
1.5
2.25
3
112-122
111-121
111-121
125-135
123-133
122-132
187-207
167-187
147-167
242-262
224-244
205-225
22-27
22-27
23-28
13-18
13-18
14-19
14-19
12-17
11-16
10-15
9-14
7-12
20.7-22.7
15.5-17.5
10.2-12.2
20.9-22.9
15.6-17.6
10.2-12.2
18-24
18-24
18-24
19-25
19-25
19-25
66- 76
69- 79
72- 82
93-103
98-108
103-113
286-306
289-309
292-312
314-334
320-340
326-346
7-12
7-12
7-12
8-13
8-13
8-13
8-13
9-14
9-14
10-15
10-15
10-15
8-10
6- 8
4- 6
11.5-13.5
8.7-10.7
5.9- 7.9
18-24
19-25
19-25
23-29
24-30
25-31
30
50
1.5
2.25
3
133-143
132-142
131-141
310-330
290-310
270-290
8-13
8-13
9-14
8-13
7-12
5-10
20.5-22.5
15.2-17.2
9.9-11.9
19-25
19-25
19-25
123-133
130-140
137-147
344-364
354-374
361-381
9-14
9-14
9-14
9-14
9-14
9-14
15-17
11.5-13.5
7.9- 9.9
28-35
29-36
30-37
70
1.5
2.25
3
138-148
137-147
136-146
396-416
374-394
352-372
7-12
7-12
7-12
7-12
6-11
4- 9
19.2-21.2
14.3-16.3
9.3-11.3
18-24
18-24
18-24
165-175
175-185
185-195
390-410
401-421
413-433
13-18
15-20
17-22
8-13
8-13
8-13
19.6-21.6
15-17
10.3-12.3
37-45
38-46
39-47
90
1.5
2.25
3
144-154
143-153
142-152
497-517
472-492
447-467
7-12
7-12
7-12
5-10
4- 9
3- 8
18.0-20.0
13.3-15.3
8.5-10.5
17-23
17-23
17-23
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
110
LEGEND
DB
HWG — Hot Water Generator
— No heating operation in this temperature range
— Dry Bulb
—
Table 23 — Typical 50PTH,PTV,PTD064,072 Unit Operating Pressures and Temperatures
FULL LOAD COOLING WITHOUT HWG ACTIVE
Water
FULL LOAD HEATING WITHOUT HWG ACTIVE
Water
ENTERING
WATER
FLOW
(Gpm/Ton)
Air
Temp
Drop (F)
DB
Air
Temp
Rise (F)
DB
WATER
TEMP (F)
(EWT)
Suction Discharge Super-
Sub-
cooling
(F)
Suction Discharge Super-
Sub-
cooling
(F)
Temp
Rise
(F)
Temp
Drop
(F)
Pressure Pressure
heat
(F)
Pressure Pressure
heat
(F)
(psig)
(psig)
(psig)
(psig)
1.5
2.25
3
1.5
2.25
3
117-127
116-126
115-125
128-138
126-136
125-135
170-190
143-163
135-155
238-258
222-242
205-225
27-32
28-33
29-34
16-21
21-26
26-31
15-20
13-18
12-17
14-19
13-18
12-17
18.2-20.2
12.6-14.6
7.0- 9.0
20.5-22.5
14.9-16.9
9.2-11.2
17-23
17-23
17-23
21-27
21-27
21-27
66- 76
69- 79
72- 82
90-100
95-105
99-109
282-302
285-305
289-309
310-330
313-333
316-336
10-16
10-16
10-16
11-17
11-17
11-17
9-14
9-14
8-10
6- 8
4- 6
11.3-13.3
8.5-10.5
5.7- 7.7
19-25
19-25
20-26
24-30
25-31
26-32
30
50
10-15
12-17
12-17
12-17
1.5
2.25
3
135-145
134-144
133-143
315-335
296-316
276-296
10-15
12-17
15-20
14-19
13-18
11-16
21.0-23.0
15.5-17.5
10.0-12.0
22-28
22-28
22-28
115-125
120-130
126-136
337-357
341-361
345-365
12-18
12-18
12-18
14-19
14-19
15-20
14-16
10.6-12.6
7.3- 9.3
28-35
29-36
30-37
70
1.5
2.25
3
139-149
138-148
138-148
408-428
386-406
364-384
10-15
10-15
10-15
15-20
13-18
11-16
20.1-22.1
14.8-16.8
9.5-11.5
21-27
21-27
21-27
157-167
161-171
166-176
390-410
394-414
398-418
15-20
15-20
15-20
14-19
14-19
15-20
18.2-20.2
13.9-15.9
9.6-11.6
37-45
38-46
39-47
90
1.5
2.25
3
144-154
143-153
142-152
515-535
493-513
469-489
8-13
8-13
8-13
14-19
13-18
12-17
19.0-21.0
14.0-16.0
9.0-11.0
20-26
20-26
20-26
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
110
LEGEND
DB
HWG — Hot Water Generator
— No heating operation in this temperature range
— Dry Bulb
—
35
Download from Www.Somanuals.com. All Manuals Search And Download.
b. To program the beginning and end dates, scroll
down to the beginning month and press the enter
key. The softkeys (INCR and DECR) will activate
to increment the month in either direction, Jan,
Feb, March, etc.
c. Use number keys to select the day of month and
year.
Unit Start-Up with WSHP Open Controls —
The WSHP Open is a multi-protocol (default BACnet*) con-
troller with extensive features, flexible options and powerful
capabilities. The unit comes from the factory pre-programmed
and needs minimal set up to function in a BAS (Building
Automation System) system or provide additional capabilities
to Carrier's WSHP product line. Most settings on the controller
have factory defaults set for ease of installation. There are a
few settings that must be configured in the field and several
settings that can be adjusted if required by unique job condi-
tions. Refer to Appendix A — WSHP Open Screen Configura-
d. Push the OK softkey to finalize the data.
6. To view configuration settings:
a. Select the Config softkey.
6
tion. In order to configure the unit, a BACview display is
b. Select the Service Config softkey. Scroll through
the factory settings by using the up and down
arrow keys. See below for factory settings.
required. See Fig. 34.
NOTE: If the WSHP Open control has lost its programming,
all display pixels will be displayed on the SPT sensor. See the
WSHP Third Party Integration Guide.
Only the following settings will need to be
checked.
When the unit is OFF, the SPT sensor will indicate OFF.
When power is applied, the SPT sensor will indicate tempera-
ture in the space at 78 F.
• # of Fan Speeds — This should be set to "1" for
units with PSC motors and set to "3" for units with
ECM motors.
• Compressor Stages — This should be set to "1."
• Factory Dehumidification Reheat Coil — This
should be set to "none" unless the modulating hot
water reheat option is supplied in the unit, then set
to "installed."
To start-up a unit with WSHP Open controls:
6
1. To plug in the BACview handheld display into a SPT
sensor, point the two ears on the connector up and tilt the
bottom of the plug toward you. Insert the plug up into the
SPT sensor while pushing the bottom of the plug away
from you.
• The condenser water limit needs to be verified
depending on design parameters and application,
whether geothermal or boiler/tower.
6
2. BACview should respond with "Establishing Connec-
tion." The Home screen will then appear on the display
showing operating mode and space temperature. Press
any button to continue.
7. To view unit configuration settings:
a. Select the Unit Configuration softkey, then select
Unit.
See Appendix A — WSHP Open Screen Configuration
for the hierarchal structure of the WSHP Open controller.
All functions of the controller can be set from the Home
screen.
b. Scroll through the unit settings by using the up and
down arrow keys. Unit settings include:
• Fan Mode: Default Continuous
• Fan Delay:
3. When the Login is requested, type 1111 and push the OK
softkey. The Logout will then be displayed to indicate the
password was accepted.
• Minimum SAT Cooling: Default 50 F
• Maximum SAT Heating: Default 110 F
• Filter Service Alarm: Must be set from 0 to 9999 hr
4. To set the Clock if it is not already displayed:
8. To set local schedules:
a. Select System Settings from the Home screen, then
press Clockset.
b. Scroll to hour, minute and second using the arrow
keys. Use the number keypad to set actual time.
c. Scroll to day, month and year using arrow keys.
Use number keypad to set date.
a. Select the Schedule softkey from the Configuration
screen, then press enter.
b. Select Weekly, then press enter (7 schedules
available).
c. Select day and press enter.
d. Press enter again and select ADD or DEL (DECR
or INCR) set schedule.
5. To set Daylight Savings Time (DST):
a. Push the DST softkey. The display will indicate
02:00:060 which is equal to 2:00AM.
e. Enter ON/OFF time, then press continue.
a50-8444
6
Fig. 34 — BACview Display Interface
*Sponsored by ASHRAE (American Society of Heating, Refrigerat-
ing and Air Conditioning Engineers).
36
Download from Www.Somanuals.com. All Manuals Search And Download.
f. Press OK to apply and save to a particular day of
the week.
g. Continue to add the same or different schedule spe-
cific days of the week.
the water level in the flush cart tank to drop below the
pump inlet line in order to prevent air from filling the line.
3. Maintain a fluid level in the tank above the return tee in
order to avoid air entering back into the fluid.
4. Shutting off the return valve that connects into the flush
cart reservoir will allow 50 psig surges to help purge air
pockets. This maintains the pump at 50 psig.
To add exceptions to the schedule:
i. Press Add softkey.
ii. Select exception type from following:
• Date
5. To purge, keep the pump at 50 psig until maximum
pumping pressure is reached.
• Date Range
6. Open the return valve to send a pressure surge through
the loop to purge any air pockets in the piping system.
7. A noticeable drop in fluid level will be seen in the flush
cart tank. This is the only indication of air in the loop.
• Week-N-Day
• Calender Reference
9. Go back to Home Screen.
6
10. Remove BACview cable from SPT sensor by reversing
NOTE: If air is purged from the system while using a
10 in. PVC flush tank, the level drop will only be 1 to
2 in. since liquids are incompressible. If the level drops
more than this, flushing should continue since air is still
being compressed in the loop. If level is less than 1 to
2 in., reverse the flow.
the process in Step 1.
11. Perform system test.
Flow Regulation — Flow regulation can be accom-
plished by two methods. Most water control valves have a flow
adjustment built into the valve. By measuring the pressure drop
through the unit heat exchanger, the flow rate can be deter-
mined. See Table 24. Adjust the water control valve until the
flow of 1.5 to 2 gpm is achieved. Since the pressure constantly
varies, two pressure gages may be needed in some
applications.
8. Repeat this procedure until all air is purged.
9. Restore power.
Antifreeze may be added before, during, or after the flush-
ing process. However, depending on when it is added in the
process, it can be wasted. Refer to the Antifreeze section for
more detail.
Loop static pressure will fluctuate with the seasons. Pres-
sures will be higher in the winter months than during the warm-
er months. This fluctuation is normal and should be considered
when charging the system initially. Run the unit in either
heating or cooling for several minutes to condition the loop to a
homogenous temperature.
When complete, perform a final flush and pressurize the
loop to a static pressure of 40 to 50 psig for winter months or
15 to 20 psig for summer months.
Table 24 — Coaxial Water Pressure Drop
WATER TEMPERATURE (F)
UNIT 50PTH, PTV,
GPM
30 F
50 F
70 F
90 F
PTD
Pressure Drop (psi)
4.0
6.0
7.0
8.0
4.0
6.0
8.0
9.0
5.5
1.5
3.1
4.1
5.1
1.2
2.6
4.5
5.7
1.1
2.2
3.9
4.5
0.5
1.9
3.9
4.8
1.3
2.6
3.4
4.3
1.0
2.5
4.2
5.2
0.9
2.1
3.6
4.2
0.3
1.8
3.5
4.3
1.1
2.3
3.0
3.8
0.8
2.3
4.0
4.8
0.8
2.0
3.2
3.8
0.2
1.7
3.2
3.9
1.0
2.1
2.7
3.4
0.6
2.1
3.7
4.4
0.7
1.8
3.1
3.5
0.1
1.6
2.9
3.5
026
038
049
After pressurization, be sure to remove the plug from the
end of the loop pump motor(s) to allow trapped air to be
discharged and to ensure the motor housing has been flooded.
Be sure the loop flow center provides adequate flow through
the unit by checking pressure drop across the heat exchanger.
Compare the results to the data in Table 24.
8.3
11.0
12.0
7.0
10.5
14.0
15.0
Antifreeze — In areas where entering loop temperatures
drop below 40 F or where piping will be routed through areas
subject to freezing, antifreeze is needed.
064,072
Alcohols and glycols are commonly used as antifreeze
agents. Freeze protection should be maintained to 15 F below
the lowest expected entering loop temperature. For example, if
the lowest expected entering loop temperature is 30 F, the
leaving loop temperature would be 22 to 25 F. Therefore, the
freeze protection should be at 15 F (30 F – 15 F = 15 F).
An alternative method is to install a flow control device.
These devices are typically an orifice of plastic material de-
signed to allow a specified flow rate that are mounted on the
outlet of the water control valve. Occasionally these valves
produce a velocity noise that can be reduced by applying some
back pressure. To accomplish this, slightly close the leaving
isolation valve of the well water setup.
IMPORTANT: All alcohols should be pre-mixed and
pumped from a reservoir outside of the building or
introduced under water level to prevent fuming.
WARNING
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in
an open position before flushing system.
Calculate the total volume of fluid in the piping system. See
Table 25. Use the percentage by volume in Table 26 to deter-
mine the amount of antifreeze to use. Antifreeze concentration
should be checked from a well-mixed sample using a hydrom-
eter to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1
factory setting (water) should be used to avoid freeze damage
to the unit.
Flushing — Once the piping is complete, units require final
purging and loop charging. A flush cart pump of at least 1.5 hp
is needed to achieve adequate flow velocity in the loop to purge
air and dirt particles from the loop. Flush the loop in both direc-
tions with a high volume of water at a high velocity. Follow the
steps below to properly flush the loop:
Once antifreeze is selected, the JW3 jumper (FP1) should
be clipped on the control to select the low temperature (anti-
freeze 13 F) set point to avoid nuisance faults.
1. Verify power is off.
2. Fill loop with water from hose through flush cart before
using flush cart pump to ensure an even fill. Do not allow
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 25 — Approximate Fluid Volume (gal.)
per 100 Ft of Pipe
HEATING STAGE 2 — To enter Stage 2 mode, terminal W is
active (Y is already active). Also, the G terminal must be
active or the W terminal is disregarded. The compressor relay
will remain on and EH1 is immediately turned on. EH2 will
turn on after 10 minutes of continual stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1 tem-
perature is greater than 45 F and FP2 is greater than 110 F.
LOCKOUT MODE — The status LED will flash fast in
Lockout mode and the compressor relay will be turned off
immediately. Lockout mode can be “soft” reset via the Y input
or can be “hard” reset via the disconnect. The last fault causing
the lockout is stored in memory and can be viewed by entering
test mode.
PIPE
DIAMETER (in.)
VOLUME (gal.)
Copper
1
1.25
1.5
4.1
6.4
9.2
Rubber Hose
Polyethylene
1
3.9
3
/ IPS SDR11
2.8
4.5
8.0
10.9
18.0
8.3
10.9
17.0
4
1 IPS SDR11
1
1 / IPS SDR11
4
1
/ IPS SDR11
2
2 IPS SDR11
1
1
1 / IPS SCH40
4
2
1 / IPS SCH40
2 IPS SCH40
LEGEND
LOCKOUT WITH EMERGENCY HEAT — While in Lock-
out mode, if W becomes active, then Emergency Heat mode
will occur.
IPS
— Internal Pipe Size
SCH — Schedule
SDR — Standard Dimensional Ratio
EMERGENCY HEAT — In Emergency Heat mode, terminal
W is active while terminal Y is not. Terminal G must be active
or the W terminal is disregarded. EH1 is immediately turned
on. EH2 will turn on after 5 minutes of continual emergency
heat demand.
NOTE: Volume of heat exchanger is approximately 1.0 gallon.
Table 26 — Antifreeze Percentages by Volume
MINIMUM TEMPERATURE FOR
FREEZE PROTECTION (F)
ANTIFREEZE
Methanol (%)
Units with Aquazone Deluxe D Control
10
15
20
25
10
25
21
16
EXTENDED COMPRESSOR OPERATION MONITOR —
If the compressor has been on for 4 continuous hours the con-
trol will automatically turn off the compressor relay and wait
the short cycle time protection time. All appropriate safeties,
including the low-pressure switch, will be monitored. If all
operations are normal and the compressor demand is still pres-
ent, the control will turn the compressor back on.
STANDBY/FAN ONLY — The compressor will be off. The
Fan Enable, Fan Speed, and reversing valve (RV) relays will be
on if inputs are present. If there is a Fan 1 demand, the Fan
Enable will immediately turn on. If there is a Fan 2 demand,
the Fan Enable and Fan Speed will immediately turn on.
100% USP Food Grade
38
29
30
25
22
20
15
14
Propylene Glycol (%)
Ethenol
Cooling Tower/Boiler Systems — These systems
typically use a common loop temperature maintained at 60 to
95 F. Carrier recommends using a closed circuit evaporative
cooling tower with a secondary heat exchanger between the
tower and the water loop. If an open type cooling tower is used
continuously, chemical treatment and filtering will be necessary.
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems — These systems al-
low water temperatures from 30 to 110 F. The external loop
field is divided up into 2 in. polyethylene supply and return
lines. Each line has valves connected in such a way that upon
system start-up, each line can be isolated for flushing using
only the system pumps. Locate air separation in the piping sys-
tem prior to the fluid re-entering the loop field.
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1
and Fan 2 outputs.
HEATING STAGE 1 — In Heating Stage 1 mode, the Fan
Enable and Compressor relays are turned on immediately.
Once the demand is removed, the relays are turned off and the
control reverts to Standby mode. If there is a master/slave or
dual compressor application, all compressor relays and related
functions will operate per their associated DIP switch 2 setting
on S1.
OPERATION
Power Up Mode — The unit will not operate until all the
inputs, terminals and safety controls are checked for normal
operation.
NOTE: The compressor will have a 5-minute anti-short cycle
upon power up.
HEATING STAGE 2 — In Heating Stage 2 mode, the Fan
Enable and Compressor relays are remain on. The Fan Speed
relay is turned on immediately and turned off immediately
once the demand is removed. The control reverts to Heating
Stage 1 mode. If there is a master/slave or dual compressor
application, all compressor relays and related functions will
operate per their associated DIP switch 2 setting on S1.
Units with Aquazone™ Complete C Control
STANDBY — Y and W terminals are not active in Standby
mode, however the O and G terminals may be active, depend-
ing on the application. The compressor will be off.
COOLING — Y and O terminals are active in Cooling mode.
After power up, the first call to the compressor will initiate a
5 to 80 second random start delay and a 5-minute anti-short
cycle protection time delay. After both delays are complete, the
compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
HEATING STAGE 1 — Terminal Y is active in heating
stage 1. After power up, the first call to the compressor will
initiate a 5 to 80 second random start delay and a 5-minute
anti-short cycle protection time delay. After both delays are
complete, the compressor is energized.
HEATING STAGE 3 — In Heating Stage 3 mode, the Fan
Enable, Fan Speed and Compressor relays remain on. The EH1
output is turned on immediately. With continuing Heat Stage 3
demand, EH2 will turn on after 10 minutes. EH1 and EH2 are
turned off immediately when the Heating Stage 3 demand is re-
moved. The control reverts to Heating Stage 2 mode.
The output signal EH2 will be off if FP1 is greater than 45 F
AND FP2 (when shorted) is greater than 110 F during Heating
Stage 3 mode. This condition will have a 30-second recogni-
tion time. Also, during Heating Stage 3 mode, EH1, EH2, Fan
Enable, and Fan Speed will be ON if G input is not active.
EMERGENCY HEAT — In Emergency Heat mode, the Fan
Enable and Fan Speed relays are turned on. The EH1 output is
turned on immediately. With continuing Emergency Heat de-
mand, EH2 will turn on after 5 minutes. Fan Enable and Fan
Speed relays are turned off after a 60-second delay. The control
reverts to Standby mode.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Output EH1, EH2, Fan Enable, and Fan Speed will be ON if
the G input is not active during Emergency Heat mode.
Occupancy Input Contact — The WSHP Open controller has
the capability to use an external dry contact closure to deter-
mine the occupancy status of the unit. The Occupancy Sched-
ules will need to be disabled in order to utilize the occupancy
contact input.
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan
Enable, compressor and RV relays are turned on immediately.
If configured as stage 2 (DIP switch set to OFF) then the com-
pressor and fan will not turn on until there is a stage 2 demand.
The Fan Enable and compressor relays are turned off immedi-
ately when the Cooling Stage 1 demand is removed. The con-
trol reverts to Standby mode. The RV relay remains on until
there is a heating demand. If there is a master/slave or dual
compressor application, all compressor relays and related func-
tions will track with their associated DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan
Enable, compressor and RV relays remain on. The Fan Speed
relay is turned on immediately and turned off immediately
once the Cooling Stage 2 demand is removed. The control
reverts to Cooling Stage 1 mode. If there is a master/slave or
dual compressor application, all compressor relays and related
functions will track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL
staged Heating mode, the override (OVR) input becomes ac-
tive and is recognized as a call for heating and the control will
immediately go into a Heating Stage 1 mode. With an addition-
al 30 minutes of NLL demand, the control will go into Heating
Stage 2 mode. With another additional 30 minutes of NLL
demand, the control will go into Heating Stage 3 mode.
NOTE: Scheduling can only be controlled from one source.
BAS (Building Automation System) On/Off
—
A
BAS
system that supports network scheduling can control the unit
through a network communication and the BAS scheduling
function once the Occupancy Schedules have been disabled.
NOTE: Scheduling can either be controlled via the unit or the
BAS, but not both.
INDOOR FAN — The indoor fan will operate in any one of
three modes depending on the user configuration selected.
Fan mode can be selected as Auto, Continuous, or Always
On. In Auto mode, the fan is in intermittent operation during
both occupied and unoccupied periods. Continuous fan mode
is intermittent during unoccupied periods and continuous dur-
ing occupied periods. Always On mode operates the fan con-
tinuously during both occupied and unoccupied periods. In the
default mode, Continuous, the fan will be turned on whenever
any one of the following is true:
• The unit is in occupied mode as determined by its occu-
pancy status.
• There is a demand for cooling or heating in the unoccu-
pied mode.
• There is a call for dehumidification (optional).
When power is reapplied after a power outage, there will be
a configured time delay of 5 to 600 seconds before starting the
fan. There are also configured fan delays for Fan On and Fan
Off. The Fan On delay defines the delay time (0 to 30 seconds;
default 10) before the fan begins to operate after heating or
cooling is started while the Fan Off delay defines the delay
time (0 to 180 seconds; default 45) the fan will continue to op-
erate after heating or cooling is stopped. The fan will continue
to run as long as the compressors, heating stages, or the dehu-
midification relays are on. If the SPT failure alarm or conden-
sate overflow alarm is active; the fan will be shut down imme-
diately regardless of occupancy state or demand.
Automatic Fan Speed Control — The WSHP Open controller
is capable of controlling up to three fan speeds using the ECM
(electronically commutated motor). The motor will operate at
the lowest speed possible to provide quiet and efficient fan op-
eration with the best latent capability. The motor will increase
speed if additional cooling or heating is required to obtain the
desired space temperature set point. The control increases the
motor's speed as the space temperature rises above the cooling
or below the heating set point. The amount of space tempera-
ture increase above or below the set point required to increase
the fan speed is user configurable in the set point.
Units with WSHP Open Multiple Protocol —
The WSHP Open multi-protocol controller will control me-
chanical cooling, heating and waterside economizer outputs
based on its own space temperature input and set points. An
optional CO IAQ (indoor air quality) sensor mounted in the
2
space can maximize the occupant comfort. The WSHP Open
controller has its own hardware clock that is automatically set
when the heat pump software is downloaded to the board. Oc-
cupancy types are described in the scheduling section below.
The following sections describe the functionality of the WSHP
Open multi-protocol controller. All point objects referred to in
this sequence of operation will be referenced to the objects as
6
viewed in the BACview handheld user interface.
SCHEDULING — Scheduling is used to start/stop the unit
based on a time period to control the space temperature to spec-
ified occupied heating and cooling set points. The controller is
defaulted to control by occupied set points all the time, until ei-
6
ther a time schedule is configured with BACview , Field Assis-
®
tant, i-Vu Open, or a third party control system to enable/dis-
able the BAS (Building Automation System) on/off point. The
local time and date must be set for these functions to operate
properly. The occupancy source can be changed to one of the
following:
Occupancy Schedules — The controller will be occupied 24/7
until a time schedule has been configured using either Field
The Low Fan speed range is configured by the width of the
Yellow (for cooling) and Light Blue (for heating) setpoint
bands. The fan will operate at low speed as long as the space
temperature remains within the yellow or light blue band
range. The Medium Fan speed range is determined by the Or-
ange and Dark Blue setpoint band. The fan will operate at me-
dium speed when the space temperature enters this range. If the
space temperature rises or falls into the red range, the fan will
operate at High Fan speed.
6
Assistant, i-Vu Open, BACview or a third party control sys-
tem to enable/disable the BAS on/off point. The BAS point can
be disabled by going to Config, then Unit, then Occupancy
Schedules and changing the point from enable to disable then
clicking OK.
NOTE: This point must be enabled in order for the i-Vu Open,
6
Field Assistant, or BACview control system to assign a time
schedule to the controller.
Schedule_schedule — The unit will operate according to the
schedule configured and stored in the unit. The schedule is
As the temperature returns toward setpoint, a configurable
hysteresis is used to prevent the fan from changing speeds er-
ratically. The default value is 0.5° F (shown above).
Also, the control will increase the fan speed as the Supply
Air Temperature approaches the configured Minimum or Max-
imum SAT limits.
Fan Speed Control (During Heating) — Whenever heat is re-
quired and active, the control continuously monitors the sup-
ply-air temperature to verify it does not rise above the config-
6
accessible via the BACview Handheld tool, i-Vu Open, or
Field Assistant control system. The daily schedule consists of a
start/stop time (standard or 24-hour mode) and seven days of
the week, starting with Monday and ending on Sunday. To
enter a daily schedule, navigate to Config, then Sched, then
6
enter BACview Admin Password (1111), then go to
schedule_schedule. From here, enter either a Weekly or Excep-
tion schedule for the unit.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
ured maximum heating SAT limit (110 F default). As the SAT
approaches this value, the control will increase the fan speed as
required to ensure the SAT will remain within the limit. This
feature provides the most quiet and efficient operation by oper-
ating the fan at the lowest speed possible.
Fan Speed Control (During Cooling) — Whenever mechani-
cal cooling is required and active, the control continuously
monitors the supply-air temperature to verify it does not fall be-
low the configured minimum cooling SAT limit (50 F default).
As the SAT approaches this value, the control will increase the
fan speed as required to ensure the SAT will remain within the
limit. The fan will operate at lowest speed to maximize latent
capacity during cooling.
COOLING — The WSHP Open controller will operate one or
two stages of compression to maintain the desired cooling set
point. The compressor outputs are controlled by the PI (propor-
tional-integral) cooling loop and cooling stages capacity algo-
rithm. They will be used to calculate the desired number of
stages needed to satisfy the space by comparing the space tem-
perature (SPT) to the appropriate cooling set point. The water
side economizer, if applicable, will be used for first stage cool-
ing in addition to the compressor(s). The following conditions
must be true in order for the cooling algorithm to run:
HEATING — The WSHP Open controller will operate one or
two stages of compression to maintain the desired heating set
point. The compressor outputs are controlled by the heating PI
(proportional-integral) loop and heating stages capacity algo-
rithm. They will be used to calculate the desired number of
stages needed to satisfy the space by comparing the space tem-
perature (SPT) to the appropriate heating set point. The follow-
ing conditions must be true in order for the heating algorithm to
run:
• Heating is set to Enable.
• Cooling mode is not active and the compressor time
guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is less than the occupied heating set
point.
• Space temperature reading is valid.
• If unoccupied, the SPT is less than the unoccupied heat-
ing set point.
• OAT (if available) is less than the heating lockout
temperature.
If all the above conditions are met, the heating outputs will
be energized as required, otherwise they will be deenergized. If
the heating is active and should the SAT approach the maxi-
mum SAT limit, the fan will be indexed to the next higher
speed. Should this be insufficient, and the SAT rises further
reaching the maximum heating SAT limit, the fan will be
indexed to the maximum speed. If the SAT still continues to
rise 5F above the maximum limit, all heating stages will be
disabled.
• Cooling is set to Enable.
• Heating mode is not active and the compressor time
guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is greater than the occupied cooling
set point.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied
cooling set point.
• If economizer cooling is available and active and the
economizer alone is insufficient to provide enough cool-
ing.
• OAT (if available) is greater than the cooling lockout
temperature.
During Heating mode, the reversing valve output will be
held in the heating position (either B or O type as configured)
even after the compressor is stopped. The valve will not switch
position until the Cooling mode is required.
The configuration screens contain the maximum SAT
parameter as well as heating lockout based on outdoor-air
temperature (OAT); both can be adjusted to meet various
specifications.
If all the above conditions are met, the compressors will be
energized as required, otherwise they will be deenergized. If
cooling is active and should the SAT approach the minimum
SAT limit, the fan will be indexed to the next higher speed.
Should this be insufficient and if the SAT falls further (equal to
the minimum SAT limit), the fan will be indexed to the maxi-
mum speed. If the SAT continues to fall 5F below the mini-
mum SAT limit, all cooling stages will be disabled.
During Cooling mode, the reversing valve output will be
held in the cooling position (either B or O type as configured)
even after the compressor is stopped. The valve will not switch
position until the Heating mode is required.
The configuration screens contain the minimum SAT
parameter as well as cooling lockout based on outdoor-air
temperature (OAT) Both can be adjusted to meet various
specifications.
There is a 5-minute off time for the compressor as well as a
5-minute time delay when staging up to allow the SAT to
achieve a stable temperature before energizing a second stage
of capacity. Likewise, a 45-second delay is used when staging
down.
After a compressor is staged off, it may be restarted again
after a normal time-guard period of 5 minutes and if the sup-
ply-air temperature has increased above the minimum supply-
air temperature limit.
The WSHP Open controller provides a status input to moni-
tor the compressor operation. The status is monitored to deter-
mine if the compressor status matches the commanded state.
This input is used to determine if a refrigerant safety switch or
other safety device has tripped and caused the compressor to
stop operating normally. If this should occur, an alarm will be
generated to indicate the faulted compressor condition.
There is a 5-minute off time for the compressor as well as a
5-minute time delay when staging up to allow the SAT to
achieve a stable temperature before energizing a second stage
of capacity. Likewise, a 45-second delay is used when staging
down.
After a compressor is staged off, it may be restarted again
after a normal time-guard period of 5 minutes and if the sup-
ply-air temperature has fallen below the maximum supply air
temperature limit.
The WSHP Open controller provides a status input to moni-
tor the compressor operation. The status is monitored to deter-
mine if the compressor status matches the commanded state.
This input is used to determine if a refrigerant safety switch or
other safety device has tripped and caused the compressor to
stop operating normally. If this should occur, an alarm will be
generated to indicate the faulted compressor condition. Also, if
auxiliary heat is available (see below), the auxiliary heat will
operate to replace the reverse cycle heating and maintain the
space temperature as required.
AUXILIARY HEAT — The WSHP Open controller can con-
trol a two-position, modulating water, or steam valve connect-
ed to a coil on the discharge side of the unit and supplied by a
boiler or a single-stage ducted electric heater in order to main-
tain the desired heating set point. Should the compressor capac-
ity be insufficient or a compressor failure occurs, the auxiliary
heat will be used. Unless the compressor fails, the auxiliary
heat will only operate to supplement the heat provided by the
compressor if the space temperature falls more than one degree
below the desired heating set point (the amount is configu-
rable). The heat will be controlled so the SAT will not exceed
the maximum heating SAT limit.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Auxiliary Modulating Hot Water/Steam Heating Reheat
— The control can modulate a hot water or steam valve con-
nected to a coil on the discharge side of the unit and supplied
by a boiler in order to maintain the desired heating set point
should the compressor capacity be insufficient or a compressor
failure occurs. Unless a compressor fault condition exists, the
valve will only operate to supplement the heat provided by the
compressor if the space temperature falls more than one degree
below the desired heating set point. The valve will be con-
trolled so the SAT will not exceed the maximum heating SAT
limit.
Two-Position Hot Water/Steam Heating Reheat — The con-
trol can operate a two-position, NO or NC, hot water or steam
valve connected to a coil on the discharge side of the unit and
supplied by a boiler in order to maintain the desired heating set
point should the compressor capacity be insufficient or a com-
pressor failure occurs. Unless a compressor fault condition ex-
ists, the valve will only open to supplement the heat provided
by the compressor if the space temperature falls more than one
degree below the desired heating set point. The valve will be
controlled so the SAT will not exceed the maximum heating
SAT limit. The heat stage will also be subject to a 2-minute
minimum OFF time to prevent excessive valve cycling.
Single Stage Electric Auxiliary Heat — The control can op-
erate a field-installed single stage of electric heat installed on
the discharge side of the unit in order to maintain the desired
heating set point should the compressor capacity be insufficient
or a compressor failure occurs. Unless a compressor fault con-
dition exists, the heat stage will only operate to supplement the
heat provided by the compressor if the space temperature falls
more than one degree below the desired heating set point. The
heat stage will be controlled so the SAT will not exceed the
maximum heating SAT limit. The heat stage will also be sub-
ject to a 2-minute minimum OFF time to prevent excessive
cycling.
units that are equipped with the modulating hot water reheat
(HWR) option. This function requires an accessory space rela-
tive humidity sensor. When using a relative humidity sensor to
control dehumidification during occupied or unoccupied times,
the dehumidification set points are used accordingly. When the
indoor relative humidity becomes greater than the dehumidifi-
cation set point, a dehumidification demand will be acknowl-
edged. Once acknowledged, the dehumidification output will
be energized, bringing on the supply fan (medium speed), me-
chanical cooling, and the integral hot water reheat coil. The
controls will engage Cooling mode and waste heat from the
compressor cooling cycle will be returned to the reheat coil si-
multaneously, meaning that the reversing valve is causing the
compressor to operate in the Cooling mode. During Cooling
mode, the unit cools, dehumidifies, and disables the HWR coil;
however, once the call for cooling has been satisfied and there
is still a call for dehumidification, the unit will continue to op-
erate using the reheat mode and HWR coil.
WATERSIDE ECONOMIZER — The WSHP Open control-
ler has the capability of providing modulating or two-position
water economizer operation (for a field-installed economizer
coil mounted to the entering air side of the unit and connected
to the condenser water loop) in order to provide free cooling
(or preheating) when water conditions are optimal. Water econ-
omizer settings can be accessed through the equipment status
screen. The following conditions must be true for economizer
operation:
• SAT reading is available.
• LWT reading is available.
• If occupied, the SPT is greater than the occupied cooling
set point or less than the occupied heating set point and
the condenser water is suitable.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied
cooling set point or less than the unoccupied heating set
point and the condenser water is suitable.
INDOOR AIR QUALITY (IAQ) AND DEMAND CON-
TROLLED VENTILATION (DCV) — If the optional in-
door air quality sensor is installed, the WSHP Open controller
can maintain indoor air quality via a modulating OA damper
providing demand controlled ventilation. The control operates
the modulating OA damper during occupied periods. The con-
Modulating Water Economizer Control — The control has
the capability to modulate a water valve to control condenser
water flowing through a coil on the entering air side of the unit.
Cooling — The purpose is to provide an economizer cooling
function by using the water loop when the entering water loop
temperature is suitable (at least 5F below space temperature).
If the water loop conditions are suitable, then the valve will
modulate open as required to maintain a supply-air temperature
that meets the load conditions. Should the economizer coil ca-
pacity alone be insufficient for a period greater than 5 minutes,
or should a high humidity condition occur, then the compressor
will also be started to satisfy the load. Should the SAT ap-
proach the minimum cooling SAT limit, the economizer valve
will modulate closed during compressor operation.
Heating — Additionally, the control will modulate the water
valve should the entering water loop temperature be suitable
for heating (at least 5F above space temperature) and heat is
required. The valve will be controlled in a similar manner ex-
cept to satisfy the heating requirement. Should the economizer
coil capacity alone be insufficient to satisfy the space load con-
ditions for more than 5 minutes, then the compressor will be
started to satisfy the load. Should the SAT approach the maxi-
mum heating SAT limit, the economizer valve will modulate
closed during compressor operation.
trol monitors the CO level and compares it to the configured
2
set points, adjusting the ventilation rate as required. The control
provides proportional ventilation to meet the requirements of
ASHRAE (American Society of Heating, Refrigerating and
Air Conditioning Engineers) specifications by providing a base
ventilation rate and then increasing the rate as the CO level in-
2
creases. The control will begin to proportionally increase venti-
lation when the CO level rises above the start ventilation set
2
point and will reach the full ventilation rate when the CO level
2
is at or above the maximum set point. A user-configurable min-
imum damper position ensures that proper base ventilation is
delivered when occupants are not present. The IAQ configura-
tions can be accessed through the configuration screen. The
following conditions must be true in order for this algorithm to
run:
• Damper control is configured for DCV.
• The unit is in an occupied mode.
• The IAQ sensor reading is greater than the DCV start
control set point.
The control has four user adjustable set points: DCV start
control set point, DCV maximum control set point, minimum
damper position, and DCV maximum damper position.
Two-Position OA Damper — The control can be configured
to operate a ventilation damper in a two-position ventilation
mode to provide the minimum ventilation requirements during
occupied periods.
Two-Position Water Economizer Control — The control has
the capability to control a NO or NC, two-position water valve
to control condenser water flow through a coil on the entering
air side of the unit.
Cooling — The purpose is to provide a cooling economizer
function directly from the condenser water loop when the en-
tering water loop temperature is suitable (at least 5 F below
space temperature). If the optional coil is provided and the wa-
ter loop conditions are suitable, then the valve will open to pro-
DEHUMIDIFCATION — The WSHP Open controller will
provide occupied and unoccupied dehumidification only on
41
Download from Www.Somanuals.com. All Manuals Search And Download.
vide cooling to the space when required. Should the capacity
be insufficient for a period greater than 5 minutes, or should a
high humidity condition occur, then the compressor will be
started to satisfy the load. Should the SAT reach the minimum
cooling SAT limit, the economizer valve will close during
compressor operation.
Heating — Additionally, the economizer control will open the
water valve should the entering water loop temperature be suit-
able for heating (at least 5 F above space temperature) and
heat is required. The valve will be controlled in a similar man-
ner except to satisfy the heating requirement. Should the coil
capacity be insufficient to satisfy the space load for more than
5 minutes, then the compressor will be started to satisfy the
load. Should the SAT reach the maximum heating SAT limit,
the economizer valve will close during compressor operation.
Table 27 — Complete C Control Current LED
Status and Alarm Relay Operations
LED STATUS
DESCRIPTION OF OPERATION
ALARM RELAY
Normal Mode
Open
Cycle
(closed 5 sec.,
open 25 sec.)
On
Normal Mode with
PM Warning
Complete C Control is
non-functional
Off
Open
Slow Flash
Fast Flash
Fault Retry
Lockout
Open
Closed
Open,
(Closed after
15 minutes)
Slow Flash
Over/Under Voltage Shutdown
Flashing Code 1 Test Mode — No fault in memory
Cycling Code 1
Test Mode —
HP Fault in memory
Flashing Code 2
Cycling Code 2
Test Mode —
DEMAND LIMIT — The WSHP Open controller has the
ability to accept three levels of demand limit from the network.
In response to a demand limit, the unit will decrease its heating
set point and increase its cooling set point to widen the range in
order to immediately lower the electrical demand. The amount
of temperature adjustment in response is user adjustable for
both heating and cooling and for each demand level. The re-
sponse to a particular demand level may also be set to zero.
Flashing Code 3
Cycling Code 3
Cycling Code 4
Cycling Code 5
Cycling Code 6
LP Fault in memory
Test Mode —
FP1 Fault in memory
Test Mode —
FP2 Fault in memory
Test Mode —
CO Fault in memory
Test Mode — Over/Under
shutdown in memory
Flashing Code 4
Flashing Code 5
Flashing Code 6
Flashing Code 7
Cycling Code 7
Cycling Code 8
Cycling Code 9
Flashing Code 8
Flashing Code 9
Test Mode — PM in memory
Test Mode — FP1/FP2
Swapped Fault in memory
CONDENSER WATER LINKAGE — The control pro-
vides optimized water loop operation using an universal con-
troller (UC) open loop controller. Loop pump operation is auto-
matically controlled by WSHP equipment occupancy sched-
ules, unoccupied demand and tenant override conditions.
Positive pump status feedback prevents nuisance fault trips.
The condenser water linkage operates when a request for con-
denser water pump operation is sent from each WSHP to the
loop controller. This request is generated whenever any WSHP
is scheduled to be occupied, is starting during optimal start (for
warm-up or pull down prior to occupancy), there is an unoccu-
pied heating or cooling demand, or a tenant pushbutton over-
ride. At each WSHP, the water loop temperature and the loop
pump status is given. The WSHP will NOT start a compressor
until the loop pumps are running or will shutdown the com-
pressors should the pumps stop. This prevents the WSHP from
operating without water flow and thus tripping out on refriger-
ant pressure, causing a lockout condition. The WSHP Open
controller control will prevent this from occurring. Also, the
loop controller can be configured to start the pumps only after a
configurable number of WSHPs are requesting operation (from
1-"N"). This can be used to prevent starting the entire loop op-
eration for only one WSHP. Meanwhile, the WSHPs will not
operate if the loop pump status is off and therefore the WSHP
compressor will not run.
LEGEND
CO
FP
—
—
—
—
—
—
Condensate Overflow
Freeze Protection
High Pressure
Light-Emitting Diode
Low Pressure
Performance Monitor
HP
LED
LP
PM
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by
a 10-second pause. This sequence will repeat continually until the fault is
cleared.
Table 28 — Complete C Control LED Code and
Fault Descriptions
LED
CODE
1
FAULT
DESCRIPTION
No fault in memory
There has been no fault since
the last power-down to power-
up sequence
HP switch opens instantly
LP switch opens for
30 continuous seconds before
or during a call (bypassed for
first 60 seconds)
FP1 below Temp limit for
30 continuous seconds
(bypassed for first 60 seconds of
operation)
2
3
High-Pressure Switch
Low-Pressure Switch
4
5
Freeze Protection Coax
— FP1
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST
Freeze Protection Air Coil — FP2 below Temp limit for
FP2
30 continuous seconds
(bypassed for first 60 seconds of
operation)
Sense overflow (grounded) for
30 continuous seconds
"R" power supply is <19VAC or
>30VAC
Performance Monitor Warning
has occurred.
Test mode provides the ability to check the control opera-
tion in a timely manner. The control enters a 20-minute test
mode by momentarily shorting the test terminals. All time de-
lays are sped up 15 times. The following operations are com-
mon to both Complete C and Deluxe D controls.
6
7
Condensate overflow
Over/Under Voltage
(Autoreset) Shutdown
8
PM Warning
Test Mode — To enter Test mode, cycle the fan 3 times
within 60 seconds. The LED will flash a code representing the
last fault when entering the Test mode. The alarm relay will
also power on and off during Test mode. See Tables 27 and 28.
To exit Test mode, short the terminals for 3 seconds or cycle
the fan 3 times within 60 seconds.
NOTE: The flashing code and alarm relay cycling code will
both have the same numerical label. For example, flashing
code 1 will have an alarm relay cycling code 1. Code 1 indi-
cates the control has not faulted since the last power off to
power on sequence.
9
FP1 and FP2
FP1 temperature is higher than
FP2 in heating/test mode, or
FP2 temperature is higher than
FP1 in cooling/test mode.
Thermistors are swapped
LEGEND
FP
—
Freeze Protection
High Pressure
HP
LED
LP
—
—
—
—
Light-Emitting Diode
Low Pressure
PM
Performance Monitor
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Once tests are complete, set unit test back to disable. Unit will
automatically reset to disable after 1 hour.
WSHP Open Test Mode — To enter WSHP Open test
6
mode, navigate from the BACview home screen to the config-
uration screen. Choose the service screen and enable unit test.
The controller will then test the following:
FAN TEST — Tests all fan speeds, sequences fan from low to
high, and operates each speed for one minute. Resets to disable
on completion.
COMPRESSOR TEST — Tests compressor cooling and
heating operation. Sequences cooling stage 1 then cooling
stage 2 followed by heating stage 2 then reduces capacity to
heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION TEST — Tests dehumidification
mode. Operates for 2 minutes.
Retry Mode — In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
again satisfy the thermostat used to terminal Y. Once the ther-
mostat input calls are satisfied, the control will continue normal
operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indica-
tors — There are 3 LED indicators on the Deluxe D control:
STATUS LED — Status LED indicates the current status or
mode of the D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the D
control is in test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will
always flash a code representing the last fault in memory. If
there is no fault in memory, the fault LED will flash code 1 and
appear as one fast flash alternating with a 10-second pause.
See Table 29.
AUXILIARY HEATING TEST — Tests auxiliary heat.
Sequences fan on and enables heating coil for 1 minute.
H O ECONOMIZER TEST — Tests entering/returning
2
water loop economizer operation. Sequences fan and opens
economizer water valve for one minute.
OPEN VENT DAMPER 100% TEST — Tests outside air
(OA) damper operation.
PREPOSITION OA DAMPER — Prepositions OA damper
actuator to set proper preload.
NOTE: The auxiliary heating test, H O economizer test, open
2
vent damper 100% test, and preposition OA damper features
will not be visible on the screen unless configured.
Table 29 — Aquazone Deluxe D Control Current LED Status and Alarm Relay Operations
STATUS LED
(Green)
TEST LED
(Yellow)
DESCRIPTION
Normal Mode
FAULT LED (Red)
Flash Last Fault Code in Memory
Flashing Code 8
ALARM RELAY
On
Off
Open
Cycle (closed 5 sec,
open 25 sec, …)
Normal Mode with PM
On
Off
Deluxe D Control
is non-functional
Off
Off
Off
Open
Test Mode
Night Setback
ESD
—
On
—
—
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flashing Code 1
Cycling Appropriate Code
Flashing Code 2
Flashing Code 3
Flashing Code 4
On
—
—
—
Open
Open
Open
Open
Open
Invalid T-stat Inputs
No Fault in Memory
HP Fault
—
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Fast Flash
Fast Flash
Fast Flash
Fast Flash
Fast Flash
Flashing Code 2
Flashing Code 3
Flashing Code 4
Flashing Code 5
Flashing Code 6
Flashing Code 7
Flashing Code 2
Flashing Code 3
LP Fault
FP1 Fault
FP2 Fault
CO Fault
Open
Over/Under Voltage
HP Lockout
LP Lockout
FP1 Lockout
FP2 Lockout
CO Lockout
Open (closed after 15 minutes)
Closed
Closed
Closed
Closed
Closed
Flashing Code 4
Flashing Code 5
Flashing Code 6
LEGEND
NOTES:
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
CO — Condensate Overflow
ESD — Emergency Shutdown
FP — Freeze Protection
HP — High Pressure
LP — Low Pressure
PM — Performance Monitor
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes
followed by a 10-second pause. This sequence will repeat con-
tinually until the fault is cleared.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE
Compressor — Conduct annual amperage checks to en-
sure that amp draw is no more than 10% greater than indicated
on the serial plate data.
Perform the procedures outlined below periodically, as
indicated.
Fan Motors — All units have lubricated fan motors. Fan
motors should never be lubricated unless obvious, dry
operation is suspected. Periodic maintenance oiling is NOT
recommended as it will result in dirt accumulating in the excess
oil and cause eventual motor failure. Conduct annual dry oper-
ation check and amperage check to ensure amp draw is no
more than 10% greater than indicated on serial plate data.
WARNING
To prevent injury or death due to electrical shock or contact
with moving parts, open unit disconnect switch before ser-
vicing unit.
IMPORTANT: When a compressor is removed from this
unit, system refrigerant circuit oil will remain in the com-
pressor. To avoid leakage of compressor oil, the refrigerant
lines of the compressor must be sealed after it is removed.
Condensate Drain Cleaning — Clean the drain line
and unit drain pan at the start of each cooling season. Check
flow by pouring water into drain. Be sure trap is filled to main-
tain an air seal.
Air Coil Cleaning — Remove dirt and debris from evap-
orator coil as required by condition of the coil. Clean coil with
a stiff brush, vacuum cleaner, or compressed air. Use a fin
comb of the correct tooth spacing when straightening mashed
or bent coil fins.
IMPORTANT: All refrigerant discharged from this unit
must be recovered without exception. Technicians must fol-
low industry accepted guidelines and all local, state and fed-
eral statutes for the recovery and disposal of refrigerants.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly
maintained closed-loop water systems. Sludge build-up may
need to be cleaned in an open water tower system due to
induced contaminants.
IMPORTANT: To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must only be
serviced by technicians who meet local, state and federal
proficiency requirements.
Local water conditions may cause excessive fouling or
pitting of tubes. Condenser tubes should therefore be cleaned at
least once a year, or more often if the water is contaminated.
Filters — Filters must be clean for maximum performance.
Inspect filters every month under normal operating conditions.
Replace when necessary.
Proper water treatment can minimize tube fouling and
pitting. If such conditions are anticipated, water treatment
analysis is recommended. Refer to the Carrier System Design
Manual, Part 5, for general water conditioning information.
IMPORTANT: Units should never be operated without
a filter.
Water Coil — Keep all air out of the water coil. Check
open loop systems to be sure the well head is not allowing air
to infiltrate the water line. Always keep lines airtight.
Inspect heat exchangers regularly, and clean more frequent-
ly if the unit is located in a “dirty” environment. Keep the heat
exchanger full of water at all times. Open loop systems should
have an inverted P trap placed in the discharge line to keep
water in the heat exchanger during off cycles. Closed loop
systems must have a minimum of 15 psig during the summer
and 40 psig during the winter.
CAUTION
Follow all safety codes. Wear safety glasses and rubber
gloves when using inhibited hydrochloric acid solution.
Observe and follow acid manufacturer’s instructions.
Clean condensers with an inhibited hydrochloric acid solu-
tion. The acid can stain hands and clothing, damage concrete,
and, without inhibitor, damage steel. Cover surroundings to
guard against splashing. Vapors from vent pipe are not harmful,
but take care to prevent liquid from being carried over by the
gases.
Check P trap frequently for proper operation.
CAUTION
Warm solution acts faster, but cold solution is just as effec-
tive if applied for a longer period.
To avoid fouled machinery and extensive unit clean-up,
DO NOT operate units without filters in place. DO NOT
use equipment as a temporary heat source during
construction.
GRAVITY FLOW METHOD — Do not add solution faster
than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight,
then drain condenser and flush with clean water. Follow acid
manufacturer’s instructions. See Fig. 35.
FORCED CIRCULATION METHOD — Fully open vent
pipe when filling condenser. The vent may be closed when
condenser is full and pump is operating. See Fig. 36.
Regulate flow to condenser with a supply line valve. If
pump is a nonoverloading type, the valve may be fully closed
while pump is running.
Condensate Drain Pans — Check condensate drain
pans for algae growth twice a year. If algae growth is apparent,
consult a water treatment specialist for proper chemical treat-
ment. Applying an algaecide every three months will typically
eliminate algae problems in most locations.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuit-
ry integrity, do not install service gages unless unit operation
appears abnormal.
Check to see that unit is within the superheat and subcool-
ing temperature ranges shown in Tables 20-23. If the unit is not
within these ranges, recover and reweigh in refrigerant charge.
For average scale deposit, allow solution to remain in con-
denser overnight. For heavy scale deposit, allow 24 hours.
Drain condenser and flush with clean water. Follow acid manu-
facturer’s instructions.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant Charging
WARNING
FILL CONDENSER WITH
CLEANING SOLUTION. DO
NOT ADD SOLUTION
MORE RAPIDLY THAN
VENT CAN EXHAUST
GASES CAUSED BY
PAIL
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system —
this can cause compressor flooding.
FUNNEL
CHEMICAL ACTION.
1”
PIPE
NOTE: Do not vent or depressurize unit refrigerant to atmo-
sphere. Remove and recover refrigerant following accepted
practices.
VENT
PIPE
5’ APPROX
3’ TO 4’
Air Coil Fan Motor Removal
CAUTION
CONDENSER
Before attempting to remove fan motors or motor mounts,
place a piece of plywood over evaporator coils to prevent
coil damage.
Disconnect motor power wires from motor terminals before
motor is removed from unit.
1. Shut off unit main power supply.
PAIL
Fig. 35 — Gravity Flow Method
2. Loosen bolts on mounting bracket so that fan belt can be
removed.
3. Loosen and remove the 2 motor mounting bracket bolts
on left side of bracket.
Slide motor/bracket assembly to extreme right and lift out
through space between fan scroll and side frame. Rest motor on
a high platform such as a step ladder. Do not allow motor to
hang by its power wires.
GAS VENT
PUMP
PRIMING
CONN.
GLOBE
VALVES
SUCTION
SUPPLY
PUMP
SUPPORT
1” PIPE
CONDENSER
Replacing the WSHP Open Controller’s Bat-
tery — The WSHP Open controller’s 10-year lithium
CR2032 battery provides a minimum of 10,000 hours of data
retention during power outages.
TANK
REMOVE WATER
REGULATING VALVE
RETURN
NOTE: Power must be ON to the WSHP Open controller
when replacing the battery, or the date, time and trend data will
be lost.
1. Remove the battery from the controller, making note of
the battery's polarity.
FINE MESH
SCREEN
Fig. 36 — Forced Circulation Method
Checking System Charge — Units are shipped with
full operating charge. If recharging is necessary:
2. Insert the new battery, matching the battery's polarity
with the polarity indicated on the WSHP Open controller.
1. Insert thermometer bulb in insulating rubber sleeve on
liquid line near filter drier. Use a digital thermometer for
all temperature measurements. DO NOT use a mercury
or dial-type thermometer.
TROUBLESHOOTING
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure
on discharge line gage.
When troubleshooting problems with a WSHP, consider the
following:
Thermistor — A thermistor may be required for single-
phase units where starting the unit is a problem due to low
voltage. See Fig. 37 for thermistor nominal resistance.
NOTE: Operate unit a minimum of 15 minutes before
checking charge.
4. From standard field-supplied Pressure-Temperature chart
for R-410A refrigerant, find equivalent saturated con-
densing temperature.
5. Read liquid line temperature on thermometer; then
subtract from saturated condensing temperature. The dif-
ference equals subcooling temperature.
Control Sensors — The control system employs 2 nom-
inal 10,000 ohm thermistors (FP1 and FP2) that are used for
freeze protection. Be sure FP1 is located in the discharge fluid
and FP2 is located in the air discharge. See Fig. 38.
6. Compare the subcooling temperature with the normal
temperature listed in Tables 20-23. If the measured liquid
line temperature does not agree with the required liquid
line temperature, ADD refrigerant to raise the tempera-
ture or REMOVE refrigerant (using standard practices) to
lower the temperature (allow a tolerance of ± 3° F).
45
Download from Www.Somanuals.com. All Manuals Search And Download.
important for the most efficient operation of the unit and for the
life of the compressor.
Packaged heat pumps typically use one bi-flow TXV to me-
ter refrigerant in both modes of operation. When diagnosing
possible TXV problems it may be helpful to reverse the refrig-
erant flow to assist with the diagnosis.
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
Geothermal and water source heat pumps are designed to
operate through a wide range of entering-water temperatures
that will have a direct effect on the unit refrigerant oper-
ating pressures. Therefore, diagnosing TXV problems can be
difficult.
TXV FAILURE — The most common failure mode of a TXV
is when the valve fails while closed. Typically, a TXV uses
spring pressure to close the valve and an opposing pressure,
usually from a diaphragm, to open the valve. The amount of
pressure exerted by the diaphragm will vary, depending on the
pressure inside of the sensing bulb. As the temperature of and
pressure within the bulb decreases, the valve will modulate
closed and restrict the refrigerant flow through the valve. The
result is less refrigerant in the evaporator and an increase in the
superheat. As the temperature at the bulb increases the dia-
phragm pressure will increase, which opens the valve and
allows more refrigerant flow and a reduction in the superheat.
0.0
20.0
40.0
60.0
80.0 100.0 120.0 140.0
Temperature (degF)
Fig. 37 — Thermistor Nominal Resistance
WSHP Open Controller — With the WSHP Open con-
troller option, the 100 most recent alarms can be viewed using
6
the BACview alarm status and alarm history.
To view the alarms:
If the sensing bulb, connecting capillary, or diaphragm
assembly are damaged, pressure is lost and the spring will force
the valve to a closed position. Often, the TXV will not close
completely so some refrigerant flow will remain, even if inade-
quate flow for the heat pump to operate.
1. Navigate to the Alarm Status screen from the Home
screen using the arrow softkeys. The screen will display
the current alarm status, either normal or Alarm, and al-
low for scrolling through the unit’s alarm status.
2. From the Alarm Status screen, press the Alarm softkey to
view the 100 most recent alarms which are labeled with
date and time for easy reference.
The TXV sensing bulb must be properly located, secured,
and insulated as it will attempt to control the temperature of the
line to which it is connected. The sensing bulb must be located
on a dedicated suction line close to the compressor. On a pack-
aged heat pump, the bulb may be located almost any place on
the tube running from the compressor suction inlet to the
reversing valve. If the bulb is located on a horizontal section, it
should be placed in the 10:00 or 2:00 position for optimal
performance.
NOTE: Active faults can be viewed by scrolling down,
these faults indicate a possible bad sensor or some condi-
tion which may not merit an alarm.
3. To view alarms which have been corrected, scroll down
through the Alarm screen to Return Top Normal screen.
NOTE: Alarms are automatically reset once alarm con-
dition has been corrected.
See Table 32 for possible alarm cause and solution.
CAUTION
Use caution when tightening the strap. The strap must be
tight enough to hold the bulb securely but caution must be
taken not to over-tighten the strap, which could dent, bend,
collapse or otherwise damage the bulb.
Thermostatic Expansion Valves — Thermostat-
ic expansion valves (TXV) are used as a means of metering the
refrigerant through the evaporator to achieve a preset superheat
at the TXV sensing bulb. Correct superheat of the refrigerant is
AIR
COIL
SUCTION
AIRFLOW
(°F)
AIRFLOW
(°F)
COMPRESSOR
THERMISTOR
EXPANSION
VALVE
COAX
DISCHARGE
FP2
FP1
CONDENSATE
OVERFLOW
(CO)
LIQUID
LINE
WATER IN
WATER OUT
AIR COIL
WATER
COIL
PROTECTION
FREEZE
PROTECTION
LEGEND
COAX
—
Coaxial Heat Exchanger
Airflow
Refrigerant Liquid Line Flow
Fig. 38 — FP1 and FP2 Thermistor Location
46
Download from Www.Somanuals.com. All Manuals Search And Download.
The bulb must be secured to the pipe using a copper strap.
The use of heat transfer paste between the bulb and the pipe
will also help ensure optimum performance.
Diagnostics—Several tests may be required to determine if
a TXV has failed. The following tools may be required for
testing:
The bulb must also be properly insulated to eliminate any
influence on valve operation by the surrounding conditions.
Cork tape is the recommended insulation as it can be molded
tight to the bulb to prevent air infiltration.
1. Refrigerant gage manifold compatible with the refriger-
ant in the system
2. Digital thermometer, preferably insulated, with wire leads
that can be connected directly to the tubing
Causes of TXV Failure — The most common causes of TXV
failure are:
3. Refrigerant pressure-temperature chart for the refrigerant
used
1. A cracked, broken, or damaged sensing bulb or capillary
can be caused by excessive vibration of the capillary dur-
ing shipping or unit operation.
To determine that a TXV has failed, verify the following:
• The suction pressure is low and the valve is non-responsive.
The TXV sensing bulb can be removed from the suction
line and warmed by holding the bulb in your hand. This
action should result in an increase in the suction pressure
while the compressor is operating. The sensing bulb can
also be chilled by immersion in ice water, which should
result in a decrease in the suction pressure while the
compressor is operating. No change in the suction pres-
sure would indicate a nonresponsive valve.
If the sensing bulb is damaged or if the capillary is
cracked or broken, the valve will be considered failed and
must be replaced. Replacement of the TXV “power head”
or sensing bulb, capillary, diaphragm assembly is possi-
ble on some TXVs. The power head assembly screws
onto most valves, but not all are intended to be replace-
able. If the assembly is not replaceable, replace the entire
valve.
• Simultaneous LOW suction pressure, HIGH refrigerant
2. Particulate debris within the system can be caused by sev-
eral sources including contaminated components, tubing,
and service tools, or improper techniques used during
brazing operations and component replacement.
subcooling and HIGH superheat.
• LOW suction pressure, LOW subcooling and HIGH super-
heat may indicate an undercharge of refrigerant. HIGH sub-
cooling and LOW superheat may indicate an overcharge of
refrigerant. The suction pressure will usually be normal or
high if there is an overcharge of refrigerant.
• LOW suction pressure and frosting of the valve and/or
equalizer line may indicate a failed valve. However, these
symptoms may also indicate an undercharge of refrigerant.
Calculate the subcooling and superheat to verify a failed
valve or refrigerant charge issue.
Problems associated with particulate debris can be com-
pounded by refrigerant systems that use POE (polyol es-
ter oil). POE oil has solvent-like properties that will clean
the interior surfaces of tubing and components. Particu-
lates can be released from interior surfaces and may mi-
grate to the TXV strainer, which can lead to plugging of
the strainer.
3. Corrosive debris within the system may happen after a
failure, such as a compressor burn out, if system was not
properly cleaned.
Repair
WARNING
4. Noncondensables may be present in the system. Non-
condensables includes any substance other than the
refrigerant or oil such as air, nitrogen, or water. Contami-
nation can be the result of improper service techniques,
use of contaminated components, and/or improper evacu-
ation of the system.
Symptoms — The symptoms of a failed TXV can be varied
and will include one or more of the following:
• Low refrigerant suction pressure
®
Puron refrigerant (R-410A) operates at higher pressure
than R-22, which is found in other WSHPs. Tools such as
manifold gages must be rated to withstand the higher pres-
sures. Failure to use approved tools may result in a failure
of tools, which can lead to severe damage to the unit, injury
or death.
WARNING
• High refrigerant superheat
• High refrigerant subcooling
Most TXVs are designed for a fixed superheat setting and
are therefore considered non-adjustable. Removal of the
bottom cap will not provide access for adjustment and can
lead to damage to the valve or equipment, unintended vent-
ing of refrigerant, personal injury, or possibly death.
• TXV and/or low pressure tubing frosting
• Equalizer line condensing and at a lower temperature than
the suction line or the equalizer line frosting
• FP1 faults in the heating mode in combination with any of
the symptoms listed above
• FP2 faults in the cooling mode in combination with any of
the symptoms listed above. Some symptoms can mimic a
failed TXV but may actually be caused be another problem.
CAUTION
Always recover the refrigerant from the system with suit-
able approved tools, recovery equipment, and practices
prior to attempting to remove or repair any TXV.
Before conducting an analysis for a failed TXV the follow-
ing must be verified:
• Confirm that there is proper water flow and water tempera-
ture in the heating mode.
CAUTION
• Confirm that there is proper airflow and temperature in the
Use caution when tightening the strap. The strap must be
tight enough to hold the bulb securely but caution must be
taken not to over-tighten the strap, which could dent, bend,
collapse or otherwise damage the bulb.
cooling mode.
• Ensure coaxial water coil is clean on the inside; this applies
to the heating mode and may require a scale check.
• Refrigerant may be undercharged. To verify, subcooling and
superheat calculations may be required.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT: Repair of any sealed refrigerant system
requires training in the use of refrigeration tools and proce-
dures. Repair should only be attempted by a qualified ser-
vice technician. A universal refrigerant handling certificate
will be required. Local and/or state license or certificate
may also be required.
CAUTION
®
Puron refrigerant (R-410A) requires the use of synthetic
lubricant (POE oil). Do not use common tools on systems
that contain R-22 refrigerants or mineral oil. Contamina-
tion and failure of this equipment may result.
See Tables 30-32 for additional troubleshooting
information.
IMPORTANT: Due to the hygroscopic nature of the
POE oil in Puron refrigerant (R-410A) and other envi-
ronmentally sound refrigerants, any component replace-
ment must be conducted in a timely manner using
caution and proper service procedure for these types of
refrigerants. A complete installation instruction will be
included with each replacement TXV/filter drier assem-
bly. It is of critical importance these instructions are
carefully understood and followed. Failure to follow
these instructions can result in a system that is contami-
nated with moisture to the extent that several filter drier
replacements may be required to properly dry the
system.
CAUTION
Disconnect power from unit before removing or replacing
connectors, or servicing motor. Wait 5 minutes after dis-
connecting power before opening motor.
Table 30 — ECM Troubleshooting
FAULT
DESCRIPTION
SOLUTION
Motor rocks slightly when
starting
Motor will not start
This is normal start-up for ECM.
Check power at motor.
No movement
Check low voltage (24-vac R to C) at motor.
Check low voltage connections (G,Y, W, R, C) at motor.
Check for unseated pins in connectors on motor harness. See Fig. 39.
Test with a temporary jumper between R and G.
Check motor for tight shaft.
Perform motor/control replacement check.
Run moisture check. See Moisture Check section in Troubleshooting.
Check for loose or non-compliant motor mount.
Make sure blower wheel is tight on shaft.
Motor rocks
Perform motor/control replacement check.
Motor oscillates up and down
while being tested off of blower
It is normal for motor to oscillate with no load on shaft.
Motor starts, but runs erratically Varies up and down or intermittent Check line voltage for variation or “sag.”
Check low voltage connections (G,Y, W, R, C) at motor, unseated pins in motor harness
connectors. See Fig. 39.
Check “Bk” for erratic cfm command (in variable speed applications).
Check system controls, thermostat.
Perform moisture check. See Moisture Check section in Troubleshooting.
If removing panel or filter reduces “puffing,” reduce restriction or reduce maximum airflow.
“Hunts” or “puffs” at high cfm
(speed)
Stays at low cfm despite system
call for cool or heat cfm
Check low voltage (thermostat) wires and connections.
Verify fan is not in delay mode. Wait until delay is complete.
Check to see if “R” is missing/not connected at motor.
Perform motor/control replacement check.
Stays at high cfm
Check to see if “R” is missing/not connected at motor.
Verify fan is not in delay mode. Wait until delay is complete.
Perform motor/control replacement check.
Blower will not shut off
Noisy blower or cabinet
Check to see if there is current leakage from controls into G, Y, or W. Check for Triac switched
thermostat or solid state relay.
Excessive noise
Determine if it’s air, cabinet, duct, or motor noise.
Check for loose blower housing, panels, etc.
If high static is creating high blower speed, check for air whistling through seams in ducts,
cabinets, or panels.
If high static is creating high blower speed, check for cabinet/duct deformaton.
“Hunts” or “puffs” at high cfm
(speed)
If removing panel or filter reduces “puffing,” reduce restriction or reduce maximum airflow.
Evidence of moisture
Motor failure or malfunction has
occurred and moisture is present
Replace motor and perform moisture check. See Moisture Check section in Troubleshooting.
Perform moisture check. See Moisture Check section in Troubleshooting.
Evidence of moisture present
inside air mover
48
Download from Www.Somanuals.com. All Manuals Search And Download.
a50-8448
Fig. 39 — ECM Pin Connectors
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Stopped or Malfunctioned ECM Motor — Refer
to Fig. 40 to determine the possible cause of a stopped or mal-
functioned ECM motor. Follow the instructions in the boxes.
a50-8447
Fig. 40 — ECM Troubleshooting Flow Diagram
50
Download from Www.Somanuals.com. All Manuals Search And Download.
• Check if condensate drain is plugged.
• Check for low airflow (too much latent capacity).
• Check for undercharged condition.
Moisture Check — To perform moisture check:
• Check that connectors are orientated “down” (or as recom-
mended by equipment manufacturer).
• Arrange harnesses with “drip loop” under motor.
• Check and plug leaks in return ducts, cabinet.
Table 31 — Good Practices
DO
DO NOT
Check motor, controls wiring, and connections thoroughly before replac- Automatically assume the motor is bad.
ing motor.
Orient connectors down so water cannot get in. Install “drip loops.”
Locate connectors above 7 and 4 o’clock positions.
Use authorized motor and control model numbers for replacement.
Replace one motor or control model number with another (unless
replacement is authorized).
Keep static pressure to a minimum by:
Use high pressure drop filters.
Use restricted returns.
•
•
•
•
Using high efficiency, low-static filters.
Keeping filters clean.
Designing ductwork for minimum static and maximum comfort.
Improving ductwork when replacement is necessary.
Size equipment wisely.
Oversize system then compensate with low airflow.
Check orientation before inserting motor connectors.
Plug in power connector backwards.
Force plugs.
Table 32 — WSHP Troubleshooting
FAULT
Main Power Problems
HEATING COOLING
POSSIBLE CAUSE
Green Status LED Off
SOLUTION
X
X
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24 vac between R and C on controller.
Check primary/secondary voltage on transformer.
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
HP Fault — Code 2
High Pressure
X
X
Reduced or no water flow in cooling
Water temperature out of range in
cooling
Bring water temperature within design parameters.
X
Reduced or no airflow in heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Dirty air coil — construction dust etc.
External static too high. Check blower performance per Tables 9-13.
X
X
Air temperature out of range in heating Bring return-air temperature within design parameters.
X
Overcharged with refrigerant
Check superheat/subcooling vs typical operating condition per
Tables 20-23.
X
X
X
X
X
Bad HP switch
Insufficient charge
Compressor pump down at start-up
Check switch continuity and operation. Replace.
Check for refrigerant leaks.
Check charge and start-up water flow.
LP/LOC Fault — Code 3
Low Pressure/Loss of
Charge
FP1 Fault — Code 4
Water Freeze Protection
X
Reduced or no water flow in heating Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
X
Inadequate antifreeze level
Improper freeze protect setting (30F Clip JW2 jumper for antifreeze (10F) use.
vs 10F)
Check antifreeze density with hydrometer.
X
X
Water temperature out of range
Bad thermistor
Reduced or no airflow in cooling
Bring water temperature within design parameters.
Check temperature and impedance correlation.
Check for dirty air filter and clean or replace.
X
X
FP2 Fault — Code 5
Air Coil Freeze Protection
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
X
X
Air temperature out of range
Too much cold vent air. Bring entering air temperature within design
parameters.
Improper freeze protect setting (30F Normal airside applications will require 30 F only.
vs 10F)
X
X
X
X
X
X
X
Bad thermistor
Blocked drain
Improper trap
Poor drainage
Check temperature and impedance correlation.
Check for blockage and clean drain.
Check trap dimensions and location ahead of vent.
Check for piping slope away from unit.
Check slope of unit toward outlet.
Condensate Fault —
Code 6
Poor venting. Check vent location.
X
Moisture on sensor
Check for moisture shorting to air coil.
LEGEND
LED — Light-Emitting Diode
RV
— Reversing Valve
TXV — Thermostatic Expansion Valve
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 32 — WSHP Troubleshooting (cont)
FAULT
Over/Under Voltage —
Code 7 (Auto Resetting)
HEATING COOLING
POSSIBLE CAUSE
Under voltage
SOLUTION
X
X
Check power supply and 24 vac voltage before and during operation.
Check power supply wire size.
Check compressor starting.
Check 24 vac and unit transformer tap for correct power supply voltage.
Check power supply voltage and 24 vac before and during operation.
Check 24 vac and unit transformer tap for correct power supply voltage.
Check for poor airflow or overcharged unit.
X
X
X
X
Over voltage
Performance Monitor —
Code 8
Heating mode FP2>125F
Cooling mode FP1>125F OR
FP2<40F
Check for poor water flow or airflow.
FP1 and FP2 Thermistors
— Code 9
X
FP1 temperature is higher
than FP2 temperature.
Swap FP1 and FP2 thermistors.
Swap FP1 and FP2 thermistors.
X
FP2 temperature is higher
than FP1 temperature.
No Fault Code Shown
X
X
X
X
X
X
X
X
No compressor operation
Compressor overload
Control board
See Scroll Compressor Rotation section.
Check and replace if necessary.
Reset power and check operation.
Reverse position of thermistors.
Swapped Thermistor —
Code 9
FP1 and FP2 swapped
Unit Short Cycles
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Dirty air filter
Check and clean air filter.
Unit in 'Test Mode'
Unit selection
Reset power or wait 20 minutes for auto exit.
Unit may be oversized for space. Check sizing for actual load of space.
Check and replace if necessary.
Compressor overload
Thermostat position
Unit locked out
Only Fan Runs
Ensure thermostat set for heating or cooling operation.
Check for lockout codes. Reset power.
Compressor overload
Thermostat wiring
Check compressor overload. Replace if necessary.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in Test mode.
Only Compressor Runs
X
X
X
X
Thermostat wiring
Check G wiring at heat pump. Jumper G and R for fan operation.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in test mode.
X
Fan motor relay
Jumper G and R for fan operation. Check for line voltage across BR
contacts.
Check fan power enable relay operation (if present).
Check for line voltage at motor. Check capacitor.
X
X
Fan motor
Unit Does Not Operate in
Cooling
Reversing valve
Set for cooling demand and check 24 vac on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating, engage and disengage RV coil voltage to push valve.
X
X
X
Thermostat setup
Thermostat wiring
Dirty filter
Check for 'O' RV setup not 'B'.
Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.
Replace or clean.
Insufficient Capacity/
Not Cooling or Heating
Properly
X
X
Reduced or no airflow in heating Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
X
X
Reduced or no airflow in cooling Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
X
Leaky ductwork
Check supply and return air temperatures at the unit and at distant duct
registers if significantly different, duct leaks are present.
X
X
X
X
X
Low refrigerant charge
Restricted metering device
Defective reversing valve
Check superheat and subcooling per Tables 20-23.
Check superheat and subcooling per Tables 20-23. Replace.
Set for cooling demand and check 24 vac on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating, engage and disengage RV coil voltage to push valve.
X
X
X
X
Thermostat improperly located
Unit undersized
Check location and for air drafts behind thermostat.
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
X
X
X
X
Scaling in water heat exchanger Perform condenser cleaning.
Inlet water too hot or cold Check load, loop sizing, loop backfill, ground moisture.
LEGEND
LED — Light-Emitting Diode
RV
— Reversing Valve
TXV — Thermostatic Expansion Valve
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 32 — WSHP Troubleshooting (cont)
FAULT
HEATING COOLING
POSSIBLE CAUSE
SOLUTION
High Head Pressure
X
Reduced or no airflow in heating Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
Check pump operation or valve operation/setting.
X
X
Reduced or no water flow in
cooling
Check water flow adjust to proper flow rate. See Tables 19 and 24.
Check load, loop sizing, loop backfill, ground moisture.
Bring return-air temperature within design parameters.
Inlet water too hot
X
Air temperature out of range in
heating
X
X
X
X
Scaling in water heat exchanger Perform condenser cleaning.
X
X
X
X
Unit overcharged
Check superheat and subcooling. Reweigh in charge.
Noncondensables in system
Restricted metering device
Reduced water flow in heating
Remove refrigerant, evacuate system and charge unit.
Check superheat and subcooling per Tables 20-23. Replace.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Low Suction Pressure
Check water flow adjust to proper flow rate.
X
Water temperature out of range
Reduced airflow in cooling
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace.
X
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
X
X
Air temperature out of range
Too much cold vent air. Bring entering air temperature within design
parameters.
X
X
X
Insufficient charge
Too high airflow
Poor performance
Too high airflow
Unit oversized
Check for refrigerant leaks.
Check blower performance per Tables 9-13.
See “Insufficient Capacity.”
Low Discharge Air
Temperature in Heating
High Humidity
X
X
Check blower performance per Tables 9-13
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
Low Refrigerant Suction
Pressure
X
X
Normal operation
Check/compare with unit Installation Manual for typical operating temper-
atures and pressures chart.
Reduced water flow
Check pump operation.
Check strainer or filter.
Improper flow regulator.
X
X
Water temperature out of range
Bring water temperature within proper range.
Conduct water quality analysis.
Scaling in water to refrigerant
heat exchanger
X
Reduced airflow
Check for dirty air filter.
Check for dirty air coil.
Check fan motor operation.
External static pressure exceeds fan operating parameters.
Space temperature too cold.
X
X
X
Return air temperature below
minimum
Excessive fresh air.
Supply air bypassing to return air Check for leaking ductwork.
stream (zone systems).
X
X
X
X
Insufficient refrigerant charge
Locate and repair leak.
Improperly located TXV sensing Locate bulb on suction line between reversing valve and compressor.
bulb
X
X
Failed or restricted metering
device
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
High Refrigerant Superheat
X
X
X
X
Insufficient refrigerant charge
Locate and repair leak.
Improperly located TXV sensing Locate bulb on suction line between reversing valve and compressor.
bulb
X
X
Failed or restricted metering
device
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
High Refrigerant
Subcooling
X
X
X
X
Excessive refrigerant charge
Remove refrigerant as needed.
Failed or restricted metering
device
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
TXV and/or Low Pressure
Tubing Frosting
X
X
X
Normal operation
May occur when entering water temperature is close to minimum.
Locate and repair leak.
X
X
Insufficient refrigerant charge
Failed or restricted metering
device
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
Equalizer Line Condensing
or Frosting
X
X
Failed or restricted metering
device
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
LEGEND
LED — Light-Emitting Diode
RV
— Reversing Valve
TXV — Thermostatic Expansion Valve
53
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
PASSWORD
LEVEL
SCREEN NAME
POINT NAME
EDITABLE
RANGE
DEFAULT
NOTES
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
Operating Mode
Displays unit operating mode
SPT
SAT
F
F
Displays SPT
Displays SAT
Condenser Leaving
Temperature
Displays leaving condenser
water temperature
F
Displays entering condenser
water temperature (Value
will not update when compressor
is operating)
Condenser Entering
Temperature
F
Off/Low Speed/
Medium Speed
High Speed/On
Fan
Displays fan speed status
Equipment
Status
No Password
Required
Compressor Capacity
Damper Position
0 - 100%
0 - 100%
0 - 100%
Displays compressor capacity
Displays current damper position
(Viewable only if Ventilation DMP
Type = 2 position or DCV)
H O Economizer
2
Displays position of economizer valve
Displays position of auxiliary
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
1 stage Elect or Modulating)
Auxiliary Heat
0 - 100%
Displays space RH% (Viewable only if
Humidity Sensor = Installed)
Space RH
0 - 100%
Displays if dehumidification is active
(Viewable only if Factory
Dehumidification Reheat = Installed)
Dehumidification
Inactive/Active
IAQ CO
0 - 9999 ppm
Normal/Alarm
Displays the space CO level
2
2
Displays current space
temperature condition
SPT Alarm Status
Displays the SPT that
exceeded the alarm limit (when SPT
alarm above is in Alarm)
Alarming SPT
F
F
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
SPT Alarm Limit
Displays the status of the Rnet
SPT sensor - ALARM is displayed
should the sensor fail to communicate
with the control module
SPT Sensor Alarm
Status
Normal/Alarm
IAQ Alarm Status
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Current IAQ/ventilation condition
Current compressor condition
Current SAT condition
Compressor Alarm
Status
No Password
Required
Alarm Status
SAT Alarm Status
Condensate Overflow
Alarm Status
Current status of the condensate
drain (overflow switch)
Condenser Water Tem-
perature Alarm Status
Current status of the
condenser water
Normal/Alarm
Filter Alarm Status
Normal/Alarm
Normal/Alarm
Current filter condition
Space RH Alarm Status
Current space RH condition
Current status of the OAT
broadcast function
OAT Alarm Status
Normal/Alarm
Normal/Alarm
Normal/Alarm
Airside Linkage Status
Current linkage status if enabled
Condenser Water
Linkage
Current linkage status if enabled
SAT
F
Display SAT
SAT Offset
X
X
-9.9 - 10.0
F
F
F
0
0
0
F
F
F
Used to correct sensor reading
Leaving Condenser
Water Temperature
Displays Leaving Condenser
Water Temperature
F
Leaving CW Offset
-9.9 - 10.0
Used to correct sensor reading
Sensor
Calibration
Admin Password
level access only
Rnet Sensor
Temperature
F
Displays SPT
Rnet Offset
RH
X
X
-9.9 - 10.0
%
Used to correct sensor reading
Displays Space RH value
RH Sensor Offset
-15% - 15%
0 %
Used to correct sensor reading
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration
54
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
PASSWORD
LEVEL
SCREEN NAME
POINT NAME
EDITABLE
RANGE
DEFAULT
NOTES
Off, Fan Only,Economize,
Cooling, Heating, Cont Fan, Test,
Start Delay, Dehumidify
Operating Mode
Displays unit operating mode
Displays how the fan is configured
to operate
Fan Operating Mode
Occupancy Status
Auto/Continuous/Always On
Unoccupied/Occupied
Displays the current occupancy status
Always Occupied/Local Schedule/
BACnet Schedule/BAS Keypad/
Occupied Contact/Holiday Schedule/
Override Schedule/Pushbutton
Override/Unoccupied None
Displays the origin of the
occupancy control
Occupancy Control
Outside Air
Displays OAT (Viewable only if OAT
is a network broadcast)
F
F
Temperature
SPT
Displays SPT
Normal/Above Limit/Below
Limit/Sensor Failure
SPT Status
Displays the SPT status
Displays the connection status
of the Rnet sensor
SPT Sensor Status
Condensate Overflow
Cooling Set Point
Inactive/Connected
Normal/Alarm
Displays the status of the
condensate overflow
Displays the actual set point
being used for cooling control
F
F
Displays the actual set point
being used for heating control
Heating Set Point
Unit
Maintenance
No Password
required
Displays the offset values from the Rnet
user set point adjustment that is being
applied to the configured set points
Set Point Adjustment
F
Auxiliary Heat Control
Set Point
Displays the calculated set point being
used for auxiliary heating control
F
F
H O Economizer
2
Control Set Point
Displays the calculated set point being
used for economizer control
Calculated IAQ/
Ventilation Damper
position
Displays the ventilation damper
position calculated by the DCV control
%
Active Compressor
Stages
Displays the actual number of
compressor stages operating
0/1/2
SAT
F
Displays SAT
Used to reset the filter alarm timer after
the filter has been cleaned or replaced
Reset Filter Alarm
X
X
No/Yes
Displays the state of the condensate
overflow switch contact
Overflow Contact
Closed/Open
Closed/Open
Displays the state of the external/
remote occupancy input switch contact
Occupancy Contact
Provides capability to force the
equipment to operate in an
occupied or unoccupied mode
Inactive/Occupied/
Unoccupied
BAS/Keypad Override
OAT Input
Inactive
Displays if an OAT value is being
received from the Network
N/A / Network
BACnet
Keypad Configuration
Password
X
X
X
X
X
X
See TPI
Mapping
Changes password
See TPI
System Settings
Network
BACnet Time Master
Clock Set
See TPI
Changes clock/time setting
Override Schedules
Pushbutton Override
Inactive/Active Occupied
Inactive/Active Occupied
Inactive/Active Occupied/Active
Unoccupied
Keypad Override
Occupancy
Maintenance
No Password
required
Used to display the active and
inactive occupancy control inputs
Schedules
Occupancy Contact
BAS on/off
Inactive/Active Occupied
Inactive/Active Occupied
Inactive/Active Occupied
Local Occupancy
Schedules
X
X
X
X
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Enable
Disable
Disable
Disable
Local Holiday
Schedules
User/Admin
Password level
access
Used to define which occupancy inputs
are used to determine
Schedule
Configuration
Local Override
Schedules
occupancy mode.
BACnet Occupancy
Schedules
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration
55
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
PASSWORD
LEVEL
SCREEN NAME
POINT NAME
Occupied Heating
Occupied Cooling
Unoccupied Heating
Unoccupied Cooling
EDITABLE
RANGE
DEFAULT
NOTES
Defines the Occupied
Heating Set Point
X
X
X
X
X
X
40 - 90
55 - 99
40 - 90
55 - 99
F
F
F
F
72
76
55
90
F
F
F
F
Defines the Occupied
Cooling Set Point
Defines the Unoccupied
Heating Set Point
Defines the Unoccupied
Cooling Set Point
Effective Heating
Set Point
Takes into effect bias (maximum
allowable set point deviation)
0 - 10
0 - 10
F
Effective Cooling
Set Point
Takes into effect bias (maximum
allowable set point deviation)
F
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Optimal Start
Configuration
Set Points
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
User/Admin
Password level
access
Occupied RH
Set Point
X
0 - 100%
65%
Dehumidification when occupied)
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
Unoccupied RH
Set Point
X
X
0 - 100%
90%
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
DCV CTRL Start
Set Point
0 - 9999 ppm
500 ppm
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
DCV Max CTRL
Set Point
X
0 - 9999 ppm
1050 ppm occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine DCV ending control
point)
Defines the start time for an
Start Time
End Time
Mon
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
00:00 - 23:59
00:00 - 24:00
No/Yes
06:00
occupied period
Defines the ending time of an
18:00
occupied period
Determines if this day is included
Yes
Configuration
Schedule
in this schedule
Determines if this day is included
Tue
No/Yes
Yes
in this schedule
User/Admin
Password level
access
Determines if this day is included
Wed
No/Yes
Yes
in this schedule
Determines if this day is included
Thur
No/Yes
Yes
in this schedule
Determines if this day is included
Weekly Schedule
Fri
No/Yes
Yes
in this schedule
Determines if this day is included
Sat
No/Yes
No
in this schedule
Determines if this day is included
Sun
No/Yes
No
in this schedule
Defines the start month of this
Start Month
Start Day
Start Time
End Month
End Day
End Time
0 - 12
0
hoilday schedule
Configuration
Schedule
Defines the start day of this holiday
0 - 31
0
schedule
Determines the start time for this
00:00 - 23:59
0 - 12
0:00
User/Admin
Password level
access
schedule
Defines the month to end this
0
hoilday schedule
Defines the day to end this holiday
0 - 31
0
Exception
Schedules 1 - 12
schedule
Determines the time to end this
00:00 - 24:00
0:00
schedule
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration
56
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
PASSWORD
LEVEL
SCREEN NAME
POINT NAME
EDITABLE
RANGE
DEFAULT
NOTES
Auto= Intermittant operation during both
occupied and unoccupied periods/
Continuous = Intermittant during unoccupied
periods and continuous during occupied
periods/Always on = fan operates
continuously during both occupied and
unoccupied periods
Auto/Continuous/
Always On
Fan Mode
X
Continuous
Defines the delay time before the fan begins
to operate after heating or cooling is started
Fan On Delay
Fan Off Delay
X
X
0 - 30 sec
10 sec
45 sec
Defines the amount of time the fan will
continue to operate after heating or
cooling is stopped
0 - 180 sec
Provides capability to manually
disable heating operation
Heating Enable
Cooling Enable
X
X
X
X
Disable/Enable
Disable/Enable
Enable
Enable
Provides capability to manually
disable cooling operation
Minimum SAT in
Cooling
Defines the minimum acceptable operating
temperature for the Supply Air
40 - 60
F
50
F
Configuration
Maximum SAT in
Heating
Defines the maximum acceptable operating
temperature for the Supply Air
80 - 140
F
110
F
Admin Password
level access only
Normally set to 100% if 2 position damper
type or set to minimum ventilation position if
damper type = DCV
Damper Ventilation
Position
X
X
0 - 100%
100%
Unit
Configuration
DCV Maximum Vent
Position
Usually set at 100% - Used to limit maximum
damper opening in DCV mode
0 - 100%
100%
Filter Alarm Timer
X
X
0 - 9999 hrs
0 hrs
Disables Filter Alarm if set to 0
Pushbutton Override
Disable/Enable
Enable
Enables Override Feature on Rnet sensor
SPT Sensor Set Point
Adjustment
Enables Set Point adjustment capability
on Rnet Sensor
X
Disable/Enable
Enable
Cooling is locked out when OAT is less than
configured value and OAT is actively being
broadcast
Lockout Cooling if
OAT <
X
-65 - 80
35 - 150
F
F
-65
F
F
Heating is locked out when OAT is greater
than configured value and OAT is actively
being broadcast
Lockout Heating if
OAT >
X
150
Power Fail Restart
Delay
X
X
X
0 - 600 sec
60 sec
Enable
Delay before equipment starts
Occupancy Schedules
Disable/Enable
Enables unit occupied
Used to enforce minimum
set point separation
Set Point Separation
2 - 9
F
4
F
Used to enable test mode. Will automatically
reset to disable after 1 hour
Test Mode
Fan Test
X
X
Disable/Enable
Disable/Enable
Disable
Disable
Used to test all fan speeds. Sequences fan
from low to high and operates each speed for
1 minute. Resets to disable on completion
Off/Low Speed/Medium
Speed/High Speed/On
Fan Speed
Displays current fan operation
Used to test compressor cooling and heating
operation. Sequences cooling stage 1, then
stage 2, then heating stage 2 and reduces
capacity to stage 1. Operates for 1 minute per
step. Resets to disable on completion.
Compressor Test
X
X
Disable/Enable
Disable
Disable
Used to test dehumification mode -
Operates for 2 minutes. Resets to
disable on completion.
Configuration
Service
Dehumidification Test
Testing Compressor
Disable/Enable
Inactive/Heating/Cooling/
Dehumidify/TimeGard
Wait
Admin Password
level access only
Displays compressor test mode
Used to test auxiliary heat.
Sequences fan on and enables
heating coil for 1 minute. Resets to
disable on completion
Aux Heating Test
X
X
Disable/Enable
Disable/Enable
Disable
Disable
Test
Used to test entering/return air water loop
economizer coil operation. Sequences fan on
and opens economizer coil water valve for 1
minute. Resets to disable on completion
H O Economizer Test
2
Preposition OA
Damper
Used to preposition OA damper
actuator to set proper preload
X
X
Disable/Enable
Disable/Enable
Disable
Disable
Open Vent
Damper 100%
Used to test OA damper operation
Displays SAT
SAT
F
F
Displays Leaving Condenser
Water Temperature
LCWT
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration
57
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
PASSWORD
LEVEL
SCREEN NAME
POINT NAME
EDITABLE
RANGE
DEFAULT
NOTES
Used to set number of
fan motor speeds
# of Fan Speeds
X
1,2,3
3
When set to Fan On, G output is
energized when ever any fan speed
is active (required for ECM and Fan
control board). When set to Fan
Low, output is only energized for
Low Speed
G Output Type
X
Fan On/Fan Low
Fan On
Defines the number of
stages of compression
Compressor Stages
Reversing Valve Type
X
X
X
X
X
X
X
One Stage/Two Stages
One Stage
O type
None
Determines reversing valve
signal output type
O type output/B type output
Leaving Air Auxiliary
Heat Type
None/2-Position HW/1 Stage
Electric/Modulating HW
Determines Auxiliary
Reheat Coil Type
Entering Air Water
Economizer Type
Determines Entering Air
Economizer Coil Type
None/2-Position/Modulating
Normally Closed/Normally Open
Normally Closed/Normally Open
None/2-Position/DCV
None
2-Position Water
Valve Type
Normally
Closed
Determines type of 2-position
water valve used
Modulating Water
Valve Type
Normally
Closed
Determines type of modulating
water valve used
Ventilation Damper
Type
Determines type of ventilation
damper control to be used
None
0-10 volt
None
Used to determine ventilation
damper output signal range
(closed - open)
Damper Actuator Type
Humidity Sensor
X
X
X
(0-10 volt)/(2-10 volt)
None/Installed
Set to Installed if humidity
sensor is present
Configuration
Admin Password
level access only
Set to Installed if factory-installed
dehumidification reheat coil
is present
Factory Dehumidifica-
tion Reheat Coil
None/Installed
None
Service
Configuration
Occupancy
Input Logic
Occupied
Used to determine external occu-
X
X
X
Occupied Open/Occupied Closed
5 - 600 seconds
CLOSED pancy switch contact occupied state
Condensate Switch
Alarm Delay
Delay before equipment alarms on
10 sec
high condensate level
Condensate Switch
Alarm State
Alarm
CLOSED
Determine Alarm state of
condensate switch input
Alarm OPEN/Alarm CLOSED
Minimum Condenser
Water Temperature in
Heating
Determines the minimum
acceptable water loop temperature
to start heating
X
X
X
X
25 - 60
F
60
90
60
95
F
F
F
F
Maximum Condenser
Water Temperature in
Heating
Determines the maximum
acceptable water loop temperature
to start heating
65 - 100
F
Minimum Condenser
Water Temperature in
Cooling
Determines the minimum
acceptable water loop temperature
to start cooling
30 - 60
F
Maximum Condenser
Water Temperature in
Cooling
Determines the maximum
acceptable water loop temperature
to start cooling
85 - 120
F
IAQ sensor
Minimum output current (mA)
for IAQ sensor
X
X
X
X
0 - 5 ma
4 ma
20 ma
minimum input
IAQ sensor
maximum input
Maximum output current (mA) for
IAQ sensor
5 - 20 ma
IAQ sensor
minimum output
Corresponding value in ppm for
minimum output current
0 - 9999 ppm
0 - 9999 ppm
0 ppm
IAQ sensor
maximum output
Corresponding value in ppm for
maximum output current
2000 ppm
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration
58
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
PASSWORD
LEVEL
SCREEN NAME
POINT NAME
EDITABLE
RANGE
DEFAULT
NOTES
Defines the hysteresis applied above
the cooling and below the heating set
points before an alarm condition will
occur
SPT Occupied Alarm
Hysteresis
X
2 - 20
F
5
F
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
SPT Alarm Delay
X
0 - 30 min per degree
10 min
SPT Unoccupied Low
Alarm Temperature
Defines the fixed unoccupied
ow SPT alarm limit
X
X
X
X
35 - 90
F
45
95
45
F
F
F
SPT Unoccupied High
Alarm Temperature
Defines the fixed unoccupied
high SPT alarm limit
45 - 100
F
SAT Low SAT
Alarm Limit
Defines the fixed minimum
SAT alarm limit
15 - 90
F
SAT High SAT
Alarm Limit
Defines the fixed maximum
SAT alarm limit
90 - 175
F
120
F
Defines the delay time before an alarm
is generated after the alarm condition
occurs
Condensate Overflow
Alarm Delay
X
X
X
5 - 600 sec
45% - 100%
10 sec
100%
5 min
Space Humidity Occupied
High Alarm Limit
Defines the fixed occupied
high space RH alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Space Humidity Alarm
Delay
0 - 30 min per % RH
Configuration
Space Humidity Unoccu- Admin Password
Defines the fixed unnoccupied
high space RH alarm limit
X
X
45% - 100%
0 - 9999 ppm
100%
pied High Alarm Limit
level access only
Alarm
Configuration
IAQ/Ventilation Occupied
High Alarm Limit
Defines the fixed occupied high
space IAQ/Ventilation alarm limit
1100 ppm
Used to calculate the delay time before
0.25 min an alarm is generated after the alarm
condition occurs
IAQ/Ventilation
Alarm Delay
X
0.1 - 1.0 min per ppm
Determines if the SPT alarm is
Ignore
Rnet Sensor SPT Alarm
Rnet Sensor SAT Alarm
X
X
Ignore/Display
Ignore/Display
displayed on the local Rnet sensor
Determines if the SAT alarm is
Ignore
displayed on the local Rnet sensor
Determines if the Compressor Lockout
Rnet Sensor Compressor
Lockout Alarm
X
X
Ignore/Display
Ignore/Display
Display
Display
alarm is displayed on the local Rnet
sensor
Determines if the Condenser Water
Temperature alarm is displayed on the
local Rnet sensor
Rnet Sensor Condenser
Water Temperature Alarm
Determines if the Condensate
Overflow alarm is displayed on the
local Rnet sensor
Rnet Sensor Condensate
Overflow Alarm
X
X
X
Ignore/Display
Ignore/Display
Ignore/Display
Display
Display
Ignore
Rnet Sensor Dirty
Filter Alarm
Determines if the Dirty Filter alarm is
displayed on the local Rnet sensor
Determines if the High Space
RH alarm is displayed on the
local Rnet sensor
Rnet Sensor Space
High Humidity Alarm
Loop Control Network
Number
See TPI
See TPI
See TPI
Configuration
Linkage
Loop Control Network
Address
Number of Linked Heat
Pumps
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500079-01
Printed in U.S.A.
Form 50PT-4SI
Pg 62
7-10
Replaces: 50PT-3SI
Download from Www.Somanuals.com. All Manuals Search And Download.
50PTH,PTV,PTD
START-UP CHECKLIST
CUSTOMER:___________________________
MODEL NO.:___________________________
JOB NAME: _______________________________________
SERIAL NO.:____________________
DATE:_________
I. PRE-START-UP
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS
TIGHT? (Y/N)
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER?
(Y/N)
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)
IS AN AIR FILTER INSTALLED? (Y/N)
II. START-UP
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)
IF 3-PHASE SCROLL COMPRESSOR IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS.
(Y/N)
UNIT VOLTAGE — COOLING OPERATION
PHASE AB VOLTS
PHASE BC VOLTS
(if 3 phase)
PHASE CA VOLTS
(if 3 phase)
PHASE AB AMPS
PHASE BC AMPS
(if 3 phase)
PHASE CA AMPS
(if 3 phase)
CONTROL VOLTAGE
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N)
.
IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.
TEMPERATURES
FILL IN THE ANALYSIS CHART ATTACHED.
COAXIAL HEAT COOLING CYCLE:
EXCHANGER
FLUID IN
F
F
F
F
FLUID OUT
FLUID OUT
AIR OUT
F
PSI
PSI
FLOW
FLOW
HEATING CYCLE:
FLUID IN
F
F
F
AIR COIL
COOLING CYCLE:
AIR IN
HEATING CYCLE:
AIR IN
AIR OUT
CL-1
Download from Www.Somanuals.com. All Manuals Search And Download.
HEATING CYCLE ANALYSIS
PSI
°F
SAT
AIR
COIL
SUCTION
°F
°F
COMPRESSOR
DISCHARGE
EXPANSION
COAX
VALVE
°F
a50-8449
LIQUID LINE
°F
PSI
°F
PSI
FLUID IN
FLUID OUT
LOOK UP PRESSURE DROP IN TABLES 20-23
TO DETERMINE FLOW RATE
COOLING CYCLE ANALYSIS
PSI
°F
SAT
AIR
COIL
SUCTION
°F
°F
COMPRESSOR
DISCHARGE
EXPANSION
COAX
VALVE
°F
a50-8450
LIQUID LINE
°F
°F
PSI
PSI
FLUID OUT
FLUID IN
LOOK UP PRESSURE DROP IN TABLES 20-23
TO DETERMINE FLOW RATE
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x
FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
(DEG F)
=
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
(DEG F)
=
*Use 500 for water, 485 for antifreeze.
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500079-01
Printed in U.S.A.
Form 50PT-4SI
Pg CL-2
7-10
Replaces: 50PT-3SI
Download from Www.Somanuals.com. All Manuals Search And Download.
|