Carrier Heat Pump 50PEC09 18 User Manual

AQUAZONE™  
50PEC09-18  
Water Source Heat Pump Console Unit  
with PURON® Refrigerant (R-410A)  
Installation, Start-Up and Service Instructions  
Page  
CONTENTS  
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45-47  
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
System Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Condenser Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Condensate Pans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Blower Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Safety Control Reset. . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Checking System Charge . . . . . . . . . . . . . . . . . . . . . 47  
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . 47  
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . 47  
Replacing the WSHP Open Controller’s  
Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . .47-49  
Thermistor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
WSHP Open Controller. . . . . . . . . . . . . . . . . . . . . . . . 47  
APPENDIX A — WSHP OPEN SCREEN  
CONFIGURATION. . . . . . . . . . . . . . . . . . . . . . . . .50-55  
START-UP CHECKLIST. . . . . . . . . . . . . . . . . CL-1, CL-2  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2  
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33  
Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2  
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
• STORAGE  
• UNIT PROTECTION  
Step 3 — Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Step 4 — Wire Electrical Connections . . . . . . . . . . 17  
• SUPPLY VOLTAGE  
• EXTERNAL LOOP POWER CONNECTION  
• 230-V OPERATION  
Step 5 — Wire Low Voltage Connections . . . . . . . 30  
WATER FREEZE PROTECTION  
• ACCESSORY CONNECTIONS  
WATER SOLENOID VALVES  
• OPTIONAL WALL-MOUNTED THERMOSTAT  
• OPTIONAL PREMIERLINK™ CONTROLLER  
• WSHP OPEN WIRING  
Step 6 — Install Supply and Return Piping. . . . . . 32  
• SUPPLY AND RETURN HOSES  
IMPORTANT: Read the entire instruction manual before  
starting installation.  
• SUPPLY AND RETURN PIPING  
Step 7 — Install Condensate Piping . . . . . . . . . . . . 33  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-35  
System Cleaning and Flushing . . . . . . . . . . . . . . . . 33  
System Checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .36,37  
Complete C Control Jumper Settings. . . . . . . . . . . 36  
Complete C Control DIP Switches. . . . . . . . . . . . . . 36  
Deluxe D Control Jumper Settings . . . . . . . . . . . . . 36  
Deluxe D Control DIP Switches . . . . . . . . . . . . . . . . 36  
Deluxe D Control Accessory  
Relay Configurations . . . . . . . . . . . . . . . . . . . . . . . 37  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-40  
Unit Start-Up/Cooling . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Unit Start-Up/Heating . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Unit Start-Up with WSHP Open Controls. . . . . . . . 38  
Flow Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Antifreeze. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Cooling Tower/Boiler Systems. . . . . . . . . . . . . . . . . 40  
Ground Coupled, Closed Loop and Plateframe  
Heat Exchanger Well Systems . . . . . . . . . . . . . . . 40  
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-43  
Power Up Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Units with Aquazone Complete C Control. . . . . . . 40  
Units with Aquazone Deluxe D Control . . . . . . . . . 40  
Units with WSHP Open Multiple Protocol . . . . . . . 41  
COMPLETE C AND DELUXE D BOARD  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical components.  
Only trained and qualified service personnel should install,  
repair, or service air-conditioning equipment.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All other  
operations should be performed by trained service personnel.  
When working on air-conditioning equipment, observe precau-  
tions in the literature, tags and labels attached to the unit, and  
other safety precautions that may apply.  
Improper installation, adjustment, alteration, service, mainte-  
nance, or use can cause explosion, fire, electrical shock or other  
conditions which may cause personal injury or property  
damage. Consult a qualified installer, service agency, or your  
distributor or branch for information or assistance. The qualified  
installer or agency must use factory-authorized kits or accesso-  
ries when modifying this product. Refer to the individual  
instructions packaged with the kits or accessories when  
installing.  
Follow all safety codes. Wear safety glasses and work  
gloves. Use quenching cloth for brazing operations. Have fire  
extinguisher available. Read these instructions thoroughly and  
follow all warnings or cautions attached to the unit. Consult  
local building codes and applicable electrical codes for special  
installation requirements.  
SYSTEM TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . 43-45  
Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
WSHP Open Test Mode . . . . . . . . . . . . . . . . . . . . . . . 44  
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Aquazone Deluxe D Control LED Indicators. . . . . 44  
Understand the signal words — DANGER, WARNING, and  
CAUTION. DANGER identifies the most serious hazards  
which will result in severe personal injury or death. WARNING  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53500052-01 Printed in U.S.A. Form 50PEC-2SI Pg 1 7-09 Replaces: 50PEC-1SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL FLOW  
REGULATOR  
OPTIONAL  
MOTORIZED  
WATER VALVE  
1.62 (41)  
OUT  
IN  
2.00  
(51)  
CONTROL BOX  
WATER OUT  
WATER CONNECTIONS  
5/8” (15.9) OD  
2.25  
(57)  
COMPRESSOR  
ACCESS  
PANEL  
COPPER, 1/2” IPT, OR  
WATER IN  
1/2” EPT  
*11.25 (286)  
8.00 MIN  
(203)  
1.75 (44)  
CONDENSATE  
5/8" (15.9) ID  
VINYL HOSE  
a50-8335  
1.84  
(77)  
Right Hand Configuration  
WATER OUT  
WATER IN  
OUT  
IN  
WATER CONNECTIONS  
5/8” (15.9) OD  
COPPER, 1/2” IPT,  
OR 1/2” EPT  
1.50 (38)  
2.25  
(57)  
2.00  
(51)  
*11.25 (286)  
8.00 MIN  
(203)  
2.25  
(57)  
CONDENSATE  
5/8" (15.9) ID  
a50-8336  
2.72  
(96)  
VINYL HOSE  
Left Hand Configuration  
LEGEND  
EPT — External Pipe Thread  
IPT — Internal Pipe Thread  
*Dimension reduced by fitting if selected.  
NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters.  
Fig. 1 — 50PEC09-15 Piping Dimensions  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL AUTO FLOW  
VALVE  
1.75 (44)  
OPTIONAL  
OUT  
IN  
MOTORIZED  
WATER VALVE  
1.50  
(38)  
OPT  
CONTROL BOX  
WATER CONNECTIONS  
7/8” (22.2) OD  
COPPER, 3/4” IPT, OR  
3/4” EPT  
2.12  
(54)  
WATER  
IN  
WATER  
COMPRESSOR  
ACCESS  
PANEL  
*11.12 (282)  
OUT  
8.00 MIN  
(203)  
1.75 (44)  
a50-8337  
CONDENSATE  
5/8" (15.9) ID  
VINYL HOSE  
1.84  
(47)  
Right Hand Configuration  
OPTIONAL  
1.50  
(38)  
AUTOFLOW  
OUT  
IN  
VALVE  
1.75 (44)  
OPTIONAL  
MOTORIZED  
WATER VALVE  
WATER  
CONNECTIONS  
7/8” (22.2) OD  
COPPER, 3/4”  
IPT OR 3/4” EPT  
2.12  
WATER  
IN  
WATER  
OUT  
BLOWER DECK  
(54)  
*11.12 (282)  
8.00 MIN  
(203)  
BLOWER ACCESS PANEL  
2.25  
(286)  
CONDENSATE  
5/8" (15.9) ID  
a50-8338  
2.72  
(96)  
VINYL HOSE  
Left Hand Configuration  
LEGEND  
EPT — External Pipe Thread  
IPT — Internal Pipe Thread  
*Dimension reduced by fitting if selected.  
NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters.  
Fig. 2 — 50PEC18 Piping Dimensions  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5  
(89)  
16.0  
(406)  
5.0  
(127)  
DISCHARGE  
AIR  
30  
˚
Filter located inside and at  
top of air inlet area. Rotate  
filter latch forward, filter rack  
can be pulled forward 3” to 4”  
for filter access  
CONTROL ACCESS DOOR  
SIDE  
VIEW  
FRONT VIEW  
25.9  
(658)  
3.53  
(90)  
AIR  
INLET  
AIR INLET AREA  
33.5  
1.75  
(44.5)  
11.5  
(851)  
4.9  
(125)  
(292)  
48.0  
(1219)  
12.0  
(305)  
R.H. PIPE AND  
ELECTRIC AREA (NOTE 2)  
48.0  
(1219)  
10.0  
(254)  
6.88  
(174)  
BOTTOM VIEW  
2.12 (54)  
.75 (19)  
1.75  
(44)  
(25)  
1.0  
3.00  
(76)  
4.5  
(114)  
1.0 (25)  
R.H.  
REAR  
ACCESS  
(NOTE 2)  
REAR VIEW  
20.0  
(508)  
21.0  
(533)  
a50-8339  
1.63  
(41)  
0.59  
(15)  
4.9  
DAMPER OPENING  
(125)  
11.75  
(298)  
9.81  
(249)  
48.0  
(1219)  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
Fig. 3 — 50PEC09-15 Bottom Return Cabinet Dimensions — Right Hand Piping  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.50  
(89)  
16.00  
(406)  
5.00  
(127)  
DISCHARGE  
AIR  
30˚  
Filter located inside and at  
top of air inlet area. Push  
tabs up and back to release  
filter for replacement.  
CONTROL ACCESS DOOR  
SIDE  
VIEW  
FRONT VIEW  
25.90  
(658)  
3.53  
(90)  
AIR  
INLET  
AIR INLET AREA  
39.50  
1.75  
(44.5)  
11.50  
(1003)  
4.90  
(125)  
(292)  
54.00  
(1372)  
12.00  
(305)  
54.00  
(1372)  
R.H. PIPE AND  
ELECTRIC AREA  
(NOTE 2)  
10.00  
(254)  
6.88  
(174)  
BOTTOM VIEW  
2.12 (54)  
0.75 (19)  
1.75  
(44)  
3.00  
4.50  
(114)  
(25)  
1.00  
(76)  
1.00 (25)  
REAR VIEW  
RH REAR  
ACCESS  
(NOTE 2)  
20.00  
(508)  
21.00  
(533)  
1.63  
(41)  
0.59  
4.90  
DAMPER OPENING  
11.75  
(125)  
(15)  
9.81  
(249)  
(298)  
54.00  
(1372)  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
a50-8340  
Fig. 4 — 50PEC18 Bottom Return Cabinet Dimensions — Right Hand Piping  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5  
(89)  
12.6  
(320)  
DISCHARGE  
1.5  
(38)  
AIR  
30°  
Filter located inside and at  
top of air inlet area. Rotate  
CONTROL ACCESS DOOR  
filter latch forward, filter rack  
can be pulled forward 3” to 4”  
for filter access  
SIDE  
VIEW  
FRONT VIEW  
25.9  
(658)  
3.53  
(90)  
AIR  
INLET  
AIR INLET AREA  
33.5  
1.75  
(44.5)  
11.5  
(851)  
4.9  
(125)  
(292)  
48.0  
(1219)  
12.0  
(305)  
48.0  
(1219)  
L.H. PIPE AND  
ELECTRIC AREA  
NOTE 2  
10.0  
(254)  
6.88  
(174)  
BOTTOM VIEW  
0.75  
(19)  
2.12 (54)  
1.75  
(44)  
(25)  
1
3.00  
4.5  
(76)  
(114)  
1 (25)  
21.0  
(533)  
REAR VIEW  
L.H.  
REAR  
ACCESS  
(NOTE 2)  
20.0  
(508)  
1.63  
(41)  
0.59  
4.9  
(125)  
DAMPER OPENING  
(15)  
11.75  
(298)  
9.9  
(251)  
48.0  
(1219)  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
a50-8341  
Fig. 5 — 50PEC09-15 Bottom Return Cabinet Dimensions — Left Hand Piping  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.50  
(89)  
12.60  
(320)  
DISCHARGE  
1.50  
(38)  
AIR  
30˚  
Filter located inside and at  
top of air inlet area. Rotate  
CONTROL ACCESS DOOR  
filter latch forward, filter rack  
can be pulled forward 3” to 4”  
for filter access  
SIDE  
VIEW  
FRONT VIEW  
25.90  
(658)  
3.53  
(90)  
AIR INLET AREA  
AIR  
INLET  
39.50  
1.75  
(44.5)  
11.50  
(1003)  
4.90  
(125)  
(292)  
54.00  
(1372)  
12.00  
(305)  
54.00  
(1372)  
L.H. PIPE AND  
ELECTRIC AREA  
(Note 2)  
6.88  
(174)  
10.00  
(254)  
BOTTOM VIEW  
0.75  
(19)  
2.12 (54)  
1.75  
(44)  
1.00 (25)  
1.00 (25)  
3.00  
4.50  
(76)  
(114)  
REAR  
ACCESS  
(Note 2)  
21.00  
(533)  
REAR VIEW  
20.00  
(508)  
1.63  
(41)  
0.59  
4.90  
(125)  
DAMPER OPENING  
(15)  
11.75  
(298)  
9.90  
(251)  
54.00  
(1372)  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
a50-8342  
Fig. 6 — 50PEC18 Bottom Return Cabinet Dimensions — Left Hand Piping  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5  
(89)  
16.0  
(406)  
5.0  
(127)  
DISCHARGE  
AIR  
30  
˚
CONTROL ACCESS DOOR  
FRONT VIEW  
SIDE  
VIEW  
21.0  
(533)  
21.0  
(533)  
7.9  
(201)  
AIR  
INLET  
43.7  
(1110)  
12.0  
(305)  
48.0  
(1219)  
Filter located behind return  
air grille and requires removal of  
cabinet front for access.  
48.0  
(1219)  
.50 (13)  
12.0  
(305)  
BOTTOM VIEW  
11.50  
(292)  
R.H. PIPE AND  
ELECTRIC AREA  
.75 (19)  
4.12  
(105)  
4.5  
(25)  
1.0  
(114)  
1.0(25)  
REAR VIEW  
20.0  
(508)  
21.0  
(533)  
R.H.  
REAR  
ACCESS  
(NOTE 2)  
48.0  
(1219)  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
a50-8343  
Fig. 7 — 50PEC09-15 Front Return Cabinet Dimensions — Right Hand Piping  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.50  
(89)  
16.00  
(406)  
5.00  
(127)  
DISCHARGE  
AIR  
30˚  
CONTROL ACCESS DOOR  
FRONT VIEW  
SIDE  
VIEW  
21.00  
(533)  
21.00  
(533)  
7.90  
(201)  
AIR  
INLET  
48.00  
(1219)  
12.00  
(305)  
54.00  
(1372)  
Filter located behind return  
air grille and requires removal of  
cabinet front for access.  
54.00  
(1372)  
.50 (13)  
R.H. PIPE AND  
ELECTRIC AREA  
(NOTE 2)  
12.00  
(305)  
BOTTOM VIEW  
11.50  
(292)  
.75 (19)  
4.12  
4.12  
(105)  
(105)  
(25)  
1.00  
1.00(25)  
REAR VIEW  
20.00  
(508)  
21.00  
(533)  
RH REAR  
ACCESS  
(NOTE 2)  
54.00  
(1372)  
NOTES:  
a50-8344  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
Fig. 8 — 50PEC18 Front Return Cabinet Dimensions — Right Hand Piping  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(89)  
°
.50 (13)  
11.50  
(292)  
(Note 2)  
.75  
(19)  
4.12  
(105)  
L.H.  
(NOTE 2)  
a50-8345  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
Fig. 9 — 50PEC09-15 Front Return Cabinet Dimensions — Left Hand Piping  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12.60  
(320)  
DISCHARGE  
1.50  
(38.1)  
AIR  
3.50  
(89)  
30˚  
CONTROL ACCESS DOOR  
FRONT VIEW  
SIDE  
VIEW  
21.00  
(533)  
21.00  
(533)  
7.90  
(201)  
AIR  
INLET  
48.00  
(1219)  
12.00  
(305)  
54.00  
(1372)  
Filter located behind return  
air grille and requires removal of  
cabinet front for access.  
.50  
(13)  
54.00  
(1372)  
L.H. PIPE AND  
ELECTRIC AREA  
(Note 2)  
BOTTOM VIEW  
11.50  
(292)  
.75  
(19)  
4.12  
(105)  
1.00 (25)  
1.00 (25)  
4.50  
(114)  
21.00  
(533)  
REAR  
ACCESS  
(Note 2)  
REAR VIEW  
20.00  
(508)  
54.00  
(1372)  
NOTES:  
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.  
2. Access is reduced if optional disconnect box is selected.  
3. Optional autoflow valve, motorized water valve and disconnect box are shown.  
a50-8346  
Fig. 10 — 50PEC18 Front Return Cabinet Dimensions — Left Hand Piping  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8347  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8348  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Fasten the backplate onto the wall through the screw holes  
located in the back flange. Secure the subbase in place.  
Step 2 — Check Unit — Upon receipt of shipment at  
the jobsite, carefully check the shipment against the bill of lad-  
ing. Make sure all units have been received. Inspect the carton  
or crating of each unit, and inspect each unit for damage. En-  
sure the shipping company makes proper notation of any short-  
ages or damage on all copies of the freight bill. Concealed  
damage not discovered during unloading must be reported to  
the shipping company within 15 days of receipt of shipment.  
Step 4 — Wire Electrical Connections  
WARNING  
To avoid possible injury or death due to electrical shock,  
open the power supply disconnect switch and secure it in  
an open position during installation.  
NOTE: It is the responsibility of the purchaser to file all neces-  
sary claims with the shipping company.  
STORAGE  
CAUTION  
CAUTION  
Use only copper conductors for field-installed electrical  
wiring. Unit terminals are not designed to accept other  
types of conductors.  
DO NOT store or install console units in corrosive environ-  
ments or in locations subject to temperature or humidity  
extremes (e.g., attics, garages, rooftops, etc.). Corrosive  
conditions and high temperature or humidity can signifi-  
cantly reduce performance, reliability, and service life.  
Always move units in an upright position. Tilting units on  
their sides may cause equipment damage.  
All field-installed wiring, including the electrical ground,  
MUST comply with National Electrical Code (NEC) as well as  
all applicable local codes. In addition, all field wiring must  
conform to the Class II temperature limitations described in the  
NEC.  
Consult the unit wiring diagram located on the inside of the  
compressor access panel to ensure proper electrical hookup. The  
installing (or electrical) contractor must make the field connec-  
tions shown in Fig. 16 when using field-supplied disconnect.  
Refer to unit wiring diagrams Fig. 17-29 for a schematic of  
the field connections, which must be made by the installing (or  
electrical) contractor. Operating voltage must be within voltage  
range shown in Table 2.  
Make all final electrical connections with a length of flexi-  
ble conduit to minimize vibration and sound transmission to  
the building.  
SUPPLY VOLTAGE — Operating voltage to unit must be  
within voltage range indicated on unit nameplate.  
Upon the arrival of equipment at the jobsite, immediately  
store units in their shipping cartons in a clean, dry area. Store  
units in an upright position at all times. Stack units a maxi-  
mum of 3 units high. Use pallets to separate each layer of  
units. DO NOT remove equipment from shipping cartons  
until equipment is required for installation.  
UNIT PROTECTION — Cover console units on the jobsite  
with either shipping cartons, vinyl film, or an equivalent  
protective covering. Cap the open ends of pipes stored on the  
jobsite. In areas where painting, plastering, or the spraying of  
fireproof material has not been completed, all due precautions  
must be taken to avoid physical damage to the units and con-  
tamination by foreign material. Physical damage and contami-  
nation may prevent proper start-up and may result in costly  
equipment clean-up.  
EXTERNAL LOOP POWER CONNECTION — If the unit  
will be connected to an external loop pump or flow controller,  
connect the pump to the loop pump terminal block PB1. The  
maximum power handling is 4 amps at 240-v. The pumps will  
automatically cycle as required by the unit.  
Examine all pipes, fittings, and valves before installing any  
of the system components. Remove any dirt found on these  
components.  
230-V OPERATION — All 208/230-v units are factory-  
wired for 208-v. The transformer wiring may be switched for  
230-v operation (as illustrated on the wiring diagrams) by  
switching the RED and ORG leads at L1.  
Step 3 — Mount Unit  
1. Unpack the unit from the shipping carton. Remove the  
front cabinet by lifting up and away from the backplate.  
Protect the cabinet from damage during installation by re-  
turning it to its original vinyl pack until required.  
SHIPPING  
BOLTS  
2. Remove compressor isolation plate shipping bolts (4), as  
shown in Fig. 15.  
3. Using a carpenter’s square and a level, ensure the unit  
is level. Shim the unit if necessary to assure proper  
installation.  
Poor or inadequate installation may result in noisy  
unit operation or unattractive appearance.  
4. Select the proper fasteners to connect the backplate se-  
curely to the wall.  
Fig. 15 — Remove 4 Shipping Bolts on  
Compressor Isolator Plate  
A
WARNING  
FIELD SUPPLIED  
DISCONNECT SWITCH  
Disconnect electrical power source to prevent injury or death from electri-  
cal shock.  
ROOM THERMOSTAT  
HEAT PUMP  
CAUTION  
B
Use copper conductors only to prevent equipment damage.  
A = Two power wires for single-phase units.  
B = 1 heat/1 cool/manual or auto changeover remote 24-V thermostat.  
NOTE: All customer-supplied wiring to be copper only and must conform to national and local electrical codes. Wiring shown with dashed lines must be  
field-supplied and field-installed. “B” wiring only required with systems using remote-mounted thermostats.  
Fig. 16 — Typical Field-Installed Wiring  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8452  
Complete C  
SEE NOTE 9  
BLOWER MOTOR WIRING  
UNIT SIZE  
09-18  
POLE A POLE B  
Complete C  
5
4
NOTES:  
LEGEND  
1. Compressor and blower motor thermally pro-  
tected internally.  
AL  
Alarm Relay Contacts  
Blower Motor  
Relay/Contactor Coil  
Solenoid Coil  
BM  
BR  
2. All wiring to the unit must comply with local  
codes.  
Blower Relay  
CAP  
CB  
Capacitor  
Circuit Breaker  
Sensor, Condensate Overflow  
Compressor Relay  
Damper Motor  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
High-Pressure Switch  
Jumper Wire for Alarm  
Loss of Charge Pressure Switch  
Power Terminal Block  
Return Air Sensor  
3. Transformer is wired to 115-V (WHT) lead for  
115/1/60 units; 265-V (BRN) lead for 265/1/60  
units; or 208-V (RED) lead for 208/1/60 units.  
For 230/1/60 operation, switch the RED and  
ORG leads at L1 and insulate the RED lead.  
Transformer is energy limiting or may have a  
circuit breaker.  
4. FP1 thermistor provides freeze protection for  
WATER. When using ANTI-FREEZE solutions,  
cut JW3 jumper.  
5. For remote sensor, position jumper J1 on upper  
2 pins.  
6. For °F position, position jumper on both pins.  
For °C, position jumper on one pin.  
7. Transformer secondary ground via Complete C  
board standoffs and screws to control box.  
(Ground available from top two standoffs as  
shown.)  
8. Mate-N-Lok† plug is optional.  
9. Factory-cut jumper (JW1). Dry contact will be  
available between AL1 and AL2.  
CO  
Thermistor  
CR  
DM  
FP1  
FP2  
HP  
Circuit Breaker  
Relay Contacts-N.O.  
Switch-Temperature  
JW1  
LOC  
PB  
RAS  
RVS  
TRANS  
WV  
----------  
Switch-High Pressure  
Switch-Low Pressure  
Ground  
Reversing Valve Solenoid  
Transformer  
Water Valve  
Wire Nut  
Field Line Voltage Wiring  
Field Low-Voltage Wiring  
Printed Circuit Trace  
Mate-N-Lok  
*Optional wiring.  
†Registered trademark of AMP Incorporated.  
Option Low Voltage Wiring  
Fig. 17 — 50PEC Unit Manual or Auto Changeover with Complete C Controller Wiring  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPLETE C  
a50-8327.eps  
COMPLETE C  
PEC  
PEC12-18  
PEC  
LEGEND  
NOTES:  
1. Compressor and blower motor thermally pro-  
tected internally.  
AL  
Alarm Relay Contacts  
Blower Motor  
Relay/Contactor Coil  
Solenoid Coil  
BM  
2. All wiring to the unit must comply with local  
codes.  
3. Transformer is wired to 115-V (WHT) lead for  
115/1/60 units, 265-V (BRN) lead for 265/1/60  
units, 240-V (ORG) lead for 240/1/50 units, or  
208-V (RED) lead for 208/1/60 units.  
Rewire transformer L1 connection if voltage is  
230-1-60 or 220-1-50, insulate unused lead.  
4. FP1 thermistor provides freeze protection for  
WATER. When using ANTI-FREEZE solutions,  
cut JW3 jumper.  
BR  
Blower Relay  
CAP  
CB  
Capacitor  
Circuit Breaker  
Sensor, Condensate Overflow  
Compressor Relay  
Damper Motor  
CO  
Thermistor  
CR  
DM  
Circuit Breaker  
FP1  
FP2  
FSS  
HP  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
Fan Speed Switch  
Relay Contacts-N.O.  
Switch-Temperature  
High-Pressure Switch  
Jumper Wire for Alarm  
Loss of Charge Pressure Switch  
Power Terminal Block  
Reversing Valve Solenoid  
Transformer  
JW1  
LOC  
PB  
RVS  
TRANS  
WV  
Switch-High Pressure  
Switch-Low Pressure  
Ground  
5. Refer to LonWorks† Installation, Application, and  
Operation manual for control wiring to the unit.  
Low voltage wiring must be “class 1and voltage  
rated equal to or greater than unit supply  
voltage.  
Water Valve  
6. Factory-cut jumper (JW1). Dry contact will be  
available between AL1 and AL2.  
----------  
Field Line Voltage Wiring  
Field Low-Voltage Wiring  
Option Low-Voltage Wiring  
Printed Circuit Trace  
Wire Nut  
Mate-N-Lock  
7. Transformer secondary ground via Complete C  
board standoffs and screws to control box.  
*Optional wiring.  
†Registered trademark of Echelon Corporation.  
(Ground available from top  
shown.)  
2
standoffs as  
Fig. 18 — 50PEC Unit with Complete C and LON Controllers  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DELUXE D  
a50-8328  
DELUXE D  
LEGEND  
NOTES:  
1. Compressor and blower motor thermally pro-  
tected internally.  
AL  
Alarm Relay Contacts  
Blower Motor  
Relay/Contactor Coil  
Solenoid Coil  
BM  
CAP  
CB  
2. All wiring to the unit must comply with local  
codes.  
3. Transformer is wired to 115-V (WHT) lead for  
115/1/60 units, 265-V (BRN) lead for 265/1/60  
units, 240-V (ORG) lead for 240/1/50 units, or  
208-V (RED) lead for 208/1/60 units.  
Rewire transformer L1 connection if voltage is  
230-1-60 or 220-1-50, insulate unused lead.  
4. FP1 thermistor provides freeze protection for  
WATER. When using ANTI-FREEZE solutions,  
cut JW3 jumper.  
Capacitor  
Circuit Breaker  
CO  
CR  
Sensor, Condensate Overflow  
Compressor Relay  
Thermistor  
DM  
FP1  
FP2  
FSS  
HP  
Damper Motor  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
Fan Speed Switch  
High-Pressure Switch  
Jumper Wire for Alarm  
Loss of Charge Pressure Switch  
Power Terminal Block  
Reversing Valve Solenoid  
Transformer  
Circuit Breaker  
Relay Contacts-N.O.  
Switch-Temperature  
JW1  
LOC  
PB  
Switch-High Pressure  
Switch-Low Pressure  
Ground  
5. Refer to Microprocessor Control Installation,  
Application, and Operation manual for control  
wiring to the unit. Low voltage wiring must be  
“class 1and voltage rated equal to or greater  
than unit supply voltage.  
RVS  
TRANS  
WV  
----------  
Water Valve  
Field Line Voltage Wiring  
Field Low-Voltage Wiring  
Printed Circuit Trace  
6. Factory-cut jumper (JW4). Dry contact will be  
available between AL1 and AL2.  
Wire Nut  
Mate-N-Lock  
7. Transformer secondary ground via Deluxe D  
board standoffs and screws to control box.  
*Optional wiring.  
(Ground available from top  
shown.)  
2
standoffs as  
Fig. 19 — 50PEC Unit with Deluxe D and LON Controllers  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DELUXE D  
a50-8329  
DELUXE D  
PEC09-18  
LEGEND  
NOTES:  
1. Compressor and blower motor thermally pro-  
tected internally.  
AL  
Alarm Relay Contacts  
Blower Motor  
Relay/Contactor Coil  
BM  
2. All wiring to the unit must comply with local  
codes.  
3. Transformer is wired to 115-V (WHT) lead for  
115/1/60 units, 265-V (BRN) lead for 265/1/60  
units, 240-V (ORG) lead for 240/1/50 units, or  
208-V (RED) lead for 208/1/60 units.  
Rewire transformer L1 connection if voltage is  
230-1-60 or 220-1-50, insulate unused lead.  
4. FP1 thermistor provides freeze protection for  
WATER. When using ANTI-FREEZE solutions,  
cut JW3 jumper.  
BR  
Blower Relay  
CAP  
CB  
Capacitor  
Circuit Breaker  
Sensor, Condensate Overflow  
Compressor Relay  
Damper Motor  
Solenoid Coil  
Thermistor  
CO  
CR  
DM  
Circuit Breaker  
FP1  
FP2  
HP  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
High-Pressure Switch  
Jumper Wire for Alarm  
Loss of Charge Pressure Switch  
Night Low Limit Switch  
Power Terminal Block  
Return Air Sensor  
Relay Contacts-N.O.  
Switch-Temperature  
JW1  
LOC  
NLL  
PB  
Switch-High Pressure  
Switch-Low Pressure  
Ground  
5. Refer to Microprocessor Control Installation,  
Application, and Operation manual for control  
wiring to the unit. Low voltage wiring must be  
“class 1and voltage rated equal to or greater  
than unit supply voltage.  
RAS  
RVS  
TRANS  
WV  
Reversing Valve Solenoid  
Transformer  
Water Valve  
Field Line Voltage Wiring  
Field Low-Voltage Wiring  
Printed Circuit Trace  
6. Factory-cut jumper (JW4). Dry contact will be  
available between AL1 and AL2.  
Wire Nut  
----------  
Mate-N-Lock  
7. Transformer secondary ground via Deluxe D  
board standoffs and screws to control box.  
(Ground available from top  
shown.)  
2
standoffs as  
*Optional wiring.  
Fig. 20 — 50PEC Unit Manual or Auto Changeover and Deluxe D Controller  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GROUND  
COMPRESSOR  
S
R
C
NEUTRAL ON 265V  
SYSTEMS  
POWER SUPPLY  
REFER TO DATA PLATE  
USE COPPER CONDUCTORS ONLY.  
SEE NOTE 2  
H
BLU  
RED  
CAP  
RED  
8
4
6
2
RED  
C
L2  
L1  
REFER TO DISCONNECT  
BOX FOR OPTIONAL  
CR  
POWER SUPPLY CONNECTION  
F
BLK  
BLK  
L2 (ribbed)  
GROUND  
OPTIONAL  
CORD  
CONNECTION  
2
1
B (HIGH)  
BRN  
YEL  
BM  
L1 (plain)  
A (LOW)  
RED  
SEE  
NOTE 3  
TRANS  
COM  
NO  
BLK  
CB*  
24V  
BLK  
2
BLK  
BR  
1
BLK  
FSS  
ORG  
230V  
YEL  
ORG  
0
TRANSFORMER PRIMARY  
LEAD COLORS  
DM  
BR  
YEL  
BRN  
SEE  
NOTE 7  
1
1
0
VOLTAGE  
LEAD COLOR  
SEE  
NOTE 7  
CR  
115  
208  
230  
265  
WHT  
RED  
ORG  
BRN  
TRANS  
BLK  
YEL GRY BRN BRN BRN  
BR BRG CCG  
YEL  
CB  
24V  
RED  
CC  
(220V)  
BLU  
YEL  
ORG (240V)  
C
R
TEST PINS  
SEE  
BRN  
TYPICAL HEAT PUMP T-STAT  
SEE NOTE 5  
COMPR.  
RELAY  
RED  
RED  
BLU  
BRN  
GRY  
GRY  
VIO  
1
2
HP  
HP  
CLASS 1 WIRING  
REQUIRED INSIDE  
CONTROL BOX  
CLASS 1 OR 2  
WIRING ACCEPTABLE  
OUTSIDE  
NOTE 4  
Y
3
LOC  
4
5
FP1  
6
JW3  
LOC  
CONTROL BOX  
FP1  
COMPRESSOR  
Y
JW2  
Y
FP2  
FP1  
W
O
G
R
C
DIP SWITCH  
SEE  
COOLING  
FAN  
O
G
R
C
L
1 PM: DISABLED/  
ENABLED  
2 STAGE 2: 2/1  
3 NOT USED  
4 NOT USED  
NOTE 4  
7
FP2  
FP2  
VIO  
8
24 VAC  
COMMON  
ALARM  
BRN  
9
10  
RVS  
RV  
ORG  
5 FP1/FP2  
FAULTS: 3/1  
JW1  
NOT USED  
YEL  
AL1  
AL2  
OFF ON  
CO  
STATUS  
LED  
CO12  
P2  
G
SEE  
NOTE 6  
ALARM  
RELAY  
A
24V  
DC  
COMPLETE C  
MICRO-  
PROCESSOR  
CONTROL  
LOGIC  
P1  
BRN  
WV  
YEL  
EH1  
EH2  
P3  
GROUND  
PB  
BLOWER MOTOR WIRING  
UNIT SIZE POLE A POLE B  
CAP  
CO  
TRANSFORMER  
CR  
09  
12  
15  
18  
5
4
4
4
4
3
3
3
BR  
COMPLETE  
C
CONTROL  
*Optional wiring.  
NOTES:  
1. Compressor and blower motor thermally  
protected internally.  
LEGEND  
2. All wiring to the unit must comply with  
local codes.  
AL  
Alarm Relay Contacts  
Blower Motor  
Printed Circuit Trace  
Option Low Voltage  
Wiring  
3. Transformer is wired to 115-V (WHT) lead  
for 115/1/60 units; 265-V (BRN) lead for  
265/1/60 units; or 208-V (RED) lead for  
208/1/60 units.  
BM  
BR  
Blower Relay  
CAP  
CB  
Capacitor  
Circuit Breaker  
Sensor, Condensate Overflow  
Compressor Relay  
Damper Motor  
Relay/Contactor Coil  
For 230/1/60 operation, switch the RED  
and ORG leads at L1 and insulate the  
RED lead.  
CO  
CR  
Solenoid Coil  
DM  
FP1  
FP2  
FSS  
HP  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
Fan Speed Switch  
Transformer is energy limiting or may  
Thermistor  
have a circuit breaker.  
Circuit Breaker  
4. FP1 thermistor provides freeze protection  
for WATER. When using ANTI-FREEZE  
solutions, cut JW3 jumper.  
High-Pressure Switch  
Relay Contacts-N.O.  
JW1  
LOC  
PB  
Jumper Wire for Alarm  
Loss of Charge Pressure Switch  
Power Terminal Block  
5. Typical heat pump thermostat wiring  
shown. Refer to thermostat Installation  
Instructions for wiring to the unit.  
6. 24-V alarm signal shown. For dry alarm  
contact, cut JW1 jumper and dry contact  
will be available between AL1 and AL2.  
7. Transformer secondary ground via Com-  
plete C board standoffs and screws to  
control box. (Ground available from top  
two standoffs as shown.)  
Switch-High Pressure  
Switch-Low Pressure  
Ground  
PM  
Performance Monitor  
RVS  
Reversing Valve Solenoid  
TRANS — Transformer  
WV  
Water Valve  
Wire Nut  
---------- Field Line Voltage Wiring  
Field Low-Voltage Wiring  
Mate-N-Lock  
Fig. 21 — 50PEC Unit Remote-Mounted Thermostat with Complete C Controller Wiring  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GROUND  
COMPRESSOR  
BLU  
NEUTRAL ON 265V  
SYSTEMS  
POWER SUPPLY  
REFER TO DATA PLATE  
USE COPPER CONDUCTORS ONLY.  
SEE NOTE 2  
H
S
CAP  
RED  
R
8
4
6
2
C
RED  
RED  
C
L2  
L1  
REFER TO DISCONNECT  
BOX FOR OPTIONAL  
CR  
POWER SUPPLY CONNECTION  
F
BLK  
BLK  
L2 (ribbed)  
GROUND  
OPTIONAL  
CORD  
CONNECTION  
2
1
B (HIGH)  
BRN  
YEL  
BM  
L1 (plain)  
A (LOW)  
RED  
CB*  
24V  
BLK  
TRANS  
ORG  
230V  
BLK  
SEE  
NOTE 3  
YEL  
BLU  
TRANSFORMER PRIMARY  
LEAD COLORS  
BRN  
SEE  
NOTE 7  
1
3
VOLTAGE  
LEAD COLOR  
CLASS 1 OR 2 WIRING  
ACCEPTABLE  
115  
208  
230  
265  
WHT  
RED  
ORG  
BRN  
FSS  
2
C
R
FAN ENABLE  
RELAY  
COM  
R C S  
S
C
GRY  
GRY  
OUTSIDE  
CLASS 1 WIRING  
COM2 COM1  
CONTROL BOX REQUIRED INSIDE  
P1  
Y1  
NO  
COMPRESSOR  
Y
1
2
3
4
5
6
7
8
FAN  
Y1  
W1  
SPEED  
RELAY  
COM  
NO  
COOLING  
O
O/W2  
G
FAN  
NC  
G
DELUXE D  
MICROPROCESSOR  
CONTROL LOGIC  
24 VAC  
R
R
C
AL1  
COMMON  
C
1
RED  
HP  
HP  
ALARM  
X1  
2
3
SEE  
NOTE 6  
JW4  
RED  
BLU  
BRN  
GRY  
GRY  
VIO  
VIO  
BRN  
ORG  
ALARM  
RELAY  
LOC  
LOC  
FP1  
P2  
AL2  
R
NSB  
C
ESD  
OVR  
H
4
5
6
7
8
9
TYPICAL HEAT  
PUMP T-STAT  
G
STATUS  
RED  
AL2 DRY  
FP1  
FP2  
RV  
SEE NOTE 5  
SEE  
NOTE  
4
Y
TEST  
TIME CLOCK  
R
FAULT  
FP2  
BRN  
CLOSED=UNOCCUPIED  
RV  
BRN  
RELAY  
RVS  
10  
WHT  
NOT USED  
YEL  
TEST  
PINS  
CO12  
P7  
CO  
NLL  
BRN  
ORG  
YEL  
A
WV  
SEE  
JW3  
FP1 LOW  
JW2  
FP2 LOW  
JW1  
LP N.O.  
P3  
R
24V  
DC  
NOTE 4  
RED  
YEL  
YEL  
YEL  
NO1  
NC1  
COM  
NO2  
NC2  
COM  
R
EH1  
EH2  
P6  
DM  
ACC1  
OVERRIDE  
WITH DIGITAL T-STAT  
RELAY  
OFF ON  
CCG  
BRN  
1
1
PM: DISABLE/  
ENABLE  
BLOWER MOTOR WIRING  
UNIT SIZE POLE A POLE B  
COMPR.  
RELAY  
ACC2  
OVERRIDE  
OVERRIDE  
OV  
OV  
CR  
YEL  
OFF ON  
2 UNIT STAGE: 2/1  
3 T-STAT: HEAT COOL/  
HEAT PUMP  
RELAY  
1
2
3
4
5
6
7
8
0
ACC1  
GROUND  
CC  
FUNCTIONS  
LUG  
09  
12  
15  
18  
5
4
4
4
4
3
3
3
4 RV ON B/RV ON O  
5 DEHUMID/NORMAL  
6 NOT USED  
PB  
CAP  
ACC2  
FUNCTIONS  
H: HI FAN/DEHUMID  
NOT USED  
TRANSFORMER  
CR  
7 BOILERLESS:  
ENABLE/DISABLE  
8 BOILERLESS:  
40°F/50°F  
BR 1  
(LO)  
S1  
S2  
DIP SWITCH  
PACKAGE  
DIP SWITCH  
PACKAGE  
*Optional wiring.  
NOTES:  
DELUXE  
D
CONTROL  
1. Compressor and blower motor thermally  
protected internally.  
BR 2  
(HI)  
2. All wiring to the unit must comply with local  
codes.  
LEGEND  
AL  
Alarm Relay Contacts  
Blower Motor  
Field Low-Voltage Wiring  
Printed Circuit Trace  
Option Low Voltage Wiring  
3. Transformer is wired to 115-V (WHT) lead  
for 115/1/60 units; 265-V (BRN) lead for 265/  
1/60 units; or 208-V (RED) lead for 208/1/60  
units.  
BM  
BR  
Blower Relay  
CAP  
CB  
Capacitor  
Circuit Breaker  
Relay/Contactor Coil  
For 230/1/60 operation, switch the RED and  
ORG leads at L1 and insulate the RED lead.  
Transformer is energy limiting or may have a  
circuit breaker.  
CO  
Sensor, Condensate Overflow  
Compressor Relay  
Damper Motor  
CR  
Solenoid Coil  
DM  
FP1  
FP2  
FSS  
HP  
Sensor, Water Coil Freeze Protection  
Sensor, Air Coil Freeze Protection  
Fan Speed Switch  
Thermistor  
4. FP1 thermistor provides freeze protection  
for WATER. When using ANTI-FREEZE  
solutions, cut JW3 jumper.  
5. Typical heat pump thermostat wiring shown.  
Refer to thermostat Installation Instructions  
for wiring to the unit.  
6. 24-V alarm signal shown. For dry alarm con-  
tact, cut AL2 DRY (JW4) jumper and dry  
contact will be available between AL1 and  
AL2.  
7. Transformer secondary ground via Deluxe D  
board standoffs and screws to control box.  
(Ground available from top two standoffs as  
shown.)  
Circuit Breaker  
High-Pressure Switch  
Jumper Wire for Alarm  
Loss of Charge Pressure Switch  
Night Low Limit  
Relay Contacts-N.O.  
JW1  
LOC  
NLL  
OV  
Switch-High Pressure  
Switch-Low Pressure  
Ground  
Override  
PB  
Power Terminal Block  
Performance Monitor  
PM  
RVS  
Reversing Valve Solenoid  
TRANS — Transformer  
Wire Nut  
WV  
Water Valve  
Mate-N-Lock  
---------- Field Line Voltage Wiring  
Fig. 22 — 50PEC Unit Remote-Mounted Thermostat with Deluxe D Controller Wiring  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPLETE  
C
CONTROL  
PREMIER  
LINK  
PWR  
Y
HS1/EXH/RVS  
W
CR  
CR  
O
G
LEGEND  
Control Relay  
LWT — Leaving Water Temperature Sensor  
SAT — Supply Air Temperature Sensor  
SPT — Space Temperature Sensor  
CR  
R
C
CMP1  
FAN  
NOTE: Reversing valve is on in Cooling mode.  
AL1  
AL2  
A
J5  
J6  
J4  
L
W
T
S
P
T
S
A
T
Fig. 23 — PremierLink™ Controller Applications with Complete C Control  
PREMIER  
LINK  
PWR  
DELUXE  
D
CONTROL  
Y1  
Y2  
HS2  
HS1  
W1  
O/W2  
G
LEGEND  
CMP2  
CMP1  
FAN  
LWT — Leaving Water Temperature Sensor  
SAT — Supply Air Temperature Sensor  
SPT — Space Temperature Sensor  
NOTE: Reversing valve is on in Cooling mode.  
R
C
AL1  
J5  
J6  
J4  
L
W
T
S
P
T
S
A
T
Fig. 24 — PremierLink Controller Applications with Deluxe D Control  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A50-8355  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A50-8354  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A50-8356  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A50-8353  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8380  
D B  
8
7
6
4
5 3  
1
2
1
D
L E  
1
2
4
3
1
2
2
2
G n d  
N
E E G R  
W H I T E  
+ t e R n  
- t  
R n e  
+ 1 2  
B L A C K  
R E D  
V
To WSHP Controller  
Rnet Terminals (J13)  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — Electrical Data — 50PEC Units  
COMPRESSOR  
QTY RLA LRA  
50PEC  
UNIT SIZE  
VOLTAGE  
CODE  
MIN/MAX  
VOLTAGE  
FAN MOTOR TOTAL UNIT MIN CIRCUIT  
MAX  
FUSE/HACR  
V-PH-Hz  
FLA  
FLA  
AMPS  
1
3
4
1
3
4
3
4
3
4
115-1-60  
208/230-1-60  
265-1-60  
115-1-60  
208/230-1-60  
265-1-60  
208/230-1-60  
265-1-60  
208/230-1-60  
265-1-60  
104/126  
197/254  
239/292  
104/126  
197/254  
239/292  
197/254  
239/292  
197/254  
239/292  
1
1
1
1
1
1
1
1
1
1
8.1  
4.5  
3.1  
10.6  
5.2  
4.2  
6.1  
4.7  
6.8  
6.2  
46.5  
23.0  
24.0  
55.8  
24.0  
25.0  
30.0  
28.5  
38.0  
29.0  
0.6  
0.4  
0.4  
1.0  
0.6  
0.4  
0.8  
0.6  
0.7  
0.6  
8.6  
4.9  
3.5  
11.6  
5.8  
4.6  
6.9  
5.3  
7.5  
6.8  
10.7  
6.0  
4.3  
14.3  
7.1  
5.7  
8.4  
6.5  
9.2  
8.4  
15  
15  
15  
25  
15  
15  
15  
15  
15  
15  
09  
12  
15  
18  
LEGEND  
Full Load Amps  
FLA  
HACR — Heating, Air Conditioning and Refrigeration  
LRA  
RLA  
Locked Rotor Amps  
Rated Load Amps  
WATER SOLENOID VALVES — An external solenoid  
valve(s) should be used on ground water installations to shut  
off flow to the unit when the compressor is not operating. A  
slow closing valve may be required to help reduce water  
hammer. Figure 31 shows typical wiring for a 24-vac external  
solenoid valve. Figures 32 and 33 illustrate typical slow closing  
water control valve wiring for Taco 500 Series and Taco ESP  
Series valves. Slow closing valves take approximately 60 sec.  
to open (very little water will flow before 45 sec.). Once fully  
open, an end switch allows the compressor to be energized  
(only on valves with end switches). Only relay or triac based  
electronic thermostats should be used with slow closing valves.  
When wired as shown, the slow closing valve will operate  
properly with the following notations:  
Step 5 — Wire Low Voltage Connections  
WATER FREEZE PROTECTION — The Aquazone™ con-  
trol allows the field selection of source fluid freeze protection  
points through jumpers. The factory setting of jumper JW3  
(FP1) is set for water at 30 F. In earth loop applications, jumper  
JW3 should be clipped to change the setting to 10 F when  
using antifreeze in colder earth loop applications. See Fig. 30.  
1. The valve will remain open during a unit lockout.  
2. The valve will draw approximately 25 to 35 VA through  
the “Y” signal of the thermostat.  
IMPORTANT: Connecting a water solenoid valve can  
overheat the anticipators of electromechanical thermo-  
stats. Only use relay based electronic thermostats.  
a50-7467tf  
a50-8441  
AQUAZONE CONTROL (Complete C Control Shown)  
2
AMV  
TACO VALVE  
3
1
Fig. 30 — Typical Aquazone Control Board  
Jumper Locations  
HEATER SWITCH  
ACCESSORY CONNECTIONS — Terminal labeled A on  
the control is provided to control accessory devices such as  
water valves, electronic air cleaners, humidifiers, etc. This  
signal operates with the compressor terminal. See Fig. 31.  
Refer to the specific unit wiring schematic for details.  
NOTE: The A terminal should only be used with 24-v signals  
— not line voltage signals.  
THERMOSTAT  
Fig. 32 — AMV Valve Wiring  
Terminal Strip  
C
Typical  
Water  
Valve  
24 VAC  
A
a50-8442  
Fig. 31 — Typical Aquazone Accessory Wiring  
Fig. 33 — Taco SBV Valve Wiring  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL WALL-MOUNTED THERMOSTAT — The  
50PEC water source heat pump units are built with standard in-  
ternal thermostats in either manual changeover (MCO) or auto-  
matic changeover (ACO) configuration. Refer to Fig. 17-20.  
When desired, the unit can be furnished with a 24-v control  
circuit which is field wired to a Carrier-supplied accessory re-  
mote thermostat. Most heat pump thermostats can be used with  
the controller. Use a thermostat with Y, G, O and W outputs.  
Refer to unit wiring diagrams in Fig. 21 and 22 and Aquazone  
Controls, Operation, and Troubleshooting Instructions for addi-  
tional information.  
Vendor installation instructions and additional installation  
information is shipped with each thermostat.  
NOTE: Low-voltage wiring between the unit and the wall ther-  
mostat must comply with all applicable electrical codes  
(i.e., NEC and local codes), and be completed before the unit is  
installed.  
Field-Supplied Sensor Hardware — The WSHP Open con-  
troller is configurable with the following field-supplied sen-  
sors. See Table 4.  
Table 4 — Field-Supplied Sensors for  
WSHP Open Controller  
SENSOR  
NOTES  
Space Temperature Sensor  
(SPT)  
Field Installed (Must be used with  
WSHP Open controller.)  
Outdoor Air  
Temperature Sensor  
Network Sensor  
Indoor Air Quality Sensor  
(Separate Sensor)  
Required only for demand  
control ventilation.  
Space Relative Humidity  
Sensor  
Separate Sensor  
NOTE: BACview6 Handheld or Virtual BACview can be used as the  
user interface.  
For specific details about sensors, refer to the literature sup-  
plied with the sensor.  
Wiring a SPT Sensor — A WSHP Open controller is connect-  
ed to a wall-mounted space temperature (SPT) sensor to moni-  
tor room temperature using a Molex plug.  
Table 3 lists recommended wire sizes and lengths to install  
the thermostat. The total resistance of low-voltage wiring must  
not exceed 1 ohm. Any resistance in excess of 1 ohm may  
cause the control to malfunction because of high voltage drop.  
The WSHP Open system offers the following SPT sensors.  
See Table 5.  
Table 3 — Recommended Thermostat Wire Sizes  
WIRE SIZE  
MAX WIRE LENGTH*  
Table 5 — SPT Sensors  
18-Gage  
16-Gage  
14-Gage  
75 ft  
125 ft  
200 ft  
PART  
NUMBER  
SENSOR  
FEATURES  
SPT  
Standard  
• Local access port  
• No operator control  
SPS  
*Length = Physical distance from thermostat to unit.  
• Slide potentiometer to adjust set point  
• Manual on button to override schedule  
• LED to show occupied status  
• Local access port  
OPTIONAL PREMIERLINK™ CONTROLLER — This di-  
rect digital controller (DDC) allows the water source heat  
pump to be incorporated into a Carrier Comfort Network®  
(CCN) system installation. PremierLink control is factory-  
installed with the Complete C controller, or field-installed with  
the Deluxe D control option. Refer to Fig. 23 and 24.  
WSHP OPEN WIRING — The WSHP Open controller will  
be factory wired to the Complete C or Deluxe D control board,  
however, the system wiring will need to be completed utilizing  
WSHP Open controller wiring diagrams and the Third Party  
Integration (TPI) Guide. Factory installation includes harness,  
LWT (leaving water temperature), supply air, and condensate  
sensor.  
SPT Plus  
SPT Pro  
SPPL  
SPP  
• LCD display  
• Manual on button to override schedule  
• Warmer and cooler buttons to adjust set  
point  
• Info button to cycle through zone and  
outside air temperatures, set points, and  
local override time  
• Local access port  
• LCD display  
• Manual on button to override schedule  
• Warmer and cooler buttons to adjust set  
point  
• Info button to cycle through zone and  
outside air temperatures, set points, and  
local override time  
• Local access port  
• Fan speed*  
SPT Pro  
Plus  
SPPF  
WARNING  
Disconnect all power to the unit before performing mainte-  
nance or service. Unit may automatically start if power is  
not disconnected. Failure to follow this warning could  
cause personal injury, death, and/or equipment damage.  
*The SPT Pro Plus fan speed adjustment has no effect in this  
application.  
Wire SPT sensors to the WSHP Open controller’s Rnet port.  
An Rnetbus can consist of any of the following combinations  
of devices wired in a daisy-chain configuration:  
Wiring Sensors to Inputs — Sensors can be wired to the  
WSHP Open controller’s inputs. See Table 4.  
All field control wiring that connects to the WSHP Open con-  
troller must be routed through the raceway built into the corner  
post. The raceway provides the UL required clearance between  
high and low-voltage wiring.  
1. Pass control wires through the hole provided in the corner  
post.  
2. Feed the wires through the raceway to the WSHP Open  
controller.  
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor  
• 1 to 4 SPT Standard sensors  
• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or  
SPT Pro Plus sensor  
• Any of the above combinations, plus up to 2 BACview6  
Handheld but no more than 6 total devices  
NOTE: If the Rnetbus has multiple SPT Standard sensors, each  
sensor must be given a unique address on the Rnetbus. See the  
Carrier Open Sensor Installation Guide.  
Use the specified type of wire and cable for maximum signal  
integrity. See Table 6.  
3. Connect the wires to the removable Phoenix connectors.  
4. Reconnect the connectors to the board.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 — Rnet Wiring Specifications  
If the cable used to wire the IAQ sensor to the controller  
will be less than 100 ft, an unshielded 22 AWG (American  
Wire Gage) cable should be used. If the cable will be greater  
than 100 ft, a shield 22 AWG cable should be used. The cable  
should have a maximum length of 500 ft.  
RNET WIRING SPECIFICATIONS  
4 conductor, unshielded, CMP,  
Description  
plenum rated cable  
Conductor  
Maximum Length  
18 AWG  
500 ft  
To wire the IAQ sensor to the controller:  
1. Wire the sensor to the controller. See Fig. 25-29.  
Jacket: white  
Recommended Coloring  
Wiring: black, white, green, red  
1
2. Install a field-supplied 250-ohm, /4 watt, 2% tolerance  
UL Temperature  
Voltage  
32 to 167 F  
300-vac, power limited  
UL: NEC CL2P, or better  
resistor across the controller’s RH/IAQ and Gnd  
terminals.  
Listing  
3. Verify the the RH/IAQ jumper is set to 0 to 5-vdc.  
LEGEND  
Wiring a Relative Humidity (RH) Sensor — The RH sensor  
is used for zone humidity control (dehumidification) if the  
WSHP unit has a dehumidification device. If not, the sensor  
only monitors humidity.  
AWG — American Wire Gage  
CMP — Communications Plenum Cable  
NEC — National Electrical Code  
UL  
Underwriters Laboratories  
NOTE: Do not use a relative humidity sensor and CO2 sensor  
on the same zone controller if both sensors are powered off the  
board. If sensors are externally powered, both sensors may be  
used on the same zone controller.  
If the cable used to wire the RH sensor to the controller will  
be less than 100 ft, an unshielded 22 AWG (American Wire  
Gage) cable should be used. If the cable will be greater than  
100 ft, a shield 22 AWG cable should be used. The cable  
should have a maximum length of 500 ft.  
To wire the SPT sensor to the controller:  
1. Partially cut , then bend and pull off the outer jacket of  
the Rnet cable(s), being careful not to nick the inner  
insulation.  
2. Strip about 1/4 in. of the inner insulation from each wire.  
See Fig. 34.  
OUTER JACKET  
To wire the RH sensor to the controller:  
1. Strip the outer jacket from the cable for at least 4 inches.  
2. Strip 1/4 in. of insulation from each wire.  
3. Wire the sensor to the controller.  
a50-8443  
.25 IN.  
INNER INSULATION  
Fig. 34 — Rnet Cable Wire  
3. Wire each terminal on the sensor to the same terminal on  
the controller. See Fig. 25-29. Table 7 shows the recom-  
mended Rnet wiring scheme.  
Step 6 — Install Supply and Return Piping  
CAUTION  
Table 7 — Rnet Wiring  
To ensure proper functioning of unit and system, be sure to  
connect entering water to upper pipe on right-hand units.  
On left-hand units, connect entering water to lower pipe.  
Failure to do so could result in equipment damage.  
WIRE  
Red  
TERMINAL  
+12-v  
Black  
White  
Green  
.Rnet  
Rnet+  
Gnd  
SUPPLY AND RETURN HOSES — Optional pressure-rated  
hose assemblies are available for use with units. Use the fol-  
lowing guidelines when installing supply and return hose  
assemblies.  
NOTE: The wire should be connected to the terminal shown.  
Wiring a Supply Air Temperature (SAT) Sensor  
SAT sensor is required for reheat applications.  
The  
If the cable used to wire the SAT sensor to the controller  
will be less than 100 ft, an unshielded 22 AWG (American  
Wire Gage) cable should be used. If the cable will be greater  
than 100 ft, a shield 22 AWG cable should be used. The cable  
should have a maximum length of 500 ft.  
To wire the SAT sensor to the controller:  
1. Wire the sensor to the controller. See Fig. 25-29.  
2. Verify that the Enable SAT jumper is on.  
1. Install supply and return hoses fitted with swivel-joint  
fittings at one end to prevent the hose from twisting.  
2. Use male adapters to secure the hose assembly to the unit  
and the riser.  
3. Do not allow the hose to twist during installation. Twist-  
ing may damage the hose wall or the rubber compound.  
4. Use pipe joint compound sparingly on the fitting adapt-  
ers’ male pipe threads.  
5. Prevent sealant from reaching the joint’s flared surfaces.  
6. Do not use pipe joint compound when Teflon* thread  
tape is pre-applied to hose assemblies or when flared-end  
connections are used.  
7. Maximum torque that may be applied to brass fittings is  
30 ft-lb. When a torque wrench is not used, tighten brass  
fittings finger-tight plus one quarter turn.  
3. Verify that the Enable SAT and Remote jumper is in the  
left position.  
Wiring an Indoor Air Quality (IAQ) Sensor  
An IAQ  
sensor monitors CO2 levels. The WSHP Open controller uses  
this information to adjust the outside-air dampers to provide  
proper ventilation. An IAQ sensor can be wall-mounted or  
mounted in a return air duct. (Duct installation requires an aspi-  
rator box assembly.)  
8. Tighten steel fittings as necessary.  
9. Use shut-off/balancing valves, flow indicators, and drain  
tees in the supply runout and return at each floor to aid in  
loop balancing and servicing.  
SUPPLY AND RETURN PIPING — System piping MUST  
comply with all applicable codes.  
The sensor has a range of 0 to 2000 ppm and a linear 4 to  
20 mA output. This is converted to 1 to 5 vdc by a 250-ohm,  
1/4 watt, 2% tolerance resistor connected across the zone con-  
troller’s IAQ input terminals.  
NOTE: Do not use a relative humidity sensor and CO2 sensor  
on the same zone controller if both sensors are powered off the  
board. If sensors are externally powered, both sensors may be  
used on the same zone controller.  
1. Install a drain valve at the base of each supply and return  
riser to enable system flushing at start-up and during rou-  
tine servicing.  
*Teflon is a trademark of E. I. du Pont de Nemours and Company.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Install shut-off/balancing valves and unions at each unit  
to allow unit removal for servicing.  
NOTE: If flex hoses are used, unions are not necessary.  
3. Install strainers at the inlet of each system circulating  
pump.  
PRE-START-UP  
System Cleaning and Flushing Cleaning and  
flushing the unit and system is the single most important step to  
ensure proper start-up and continued efficient operation of the  
system.  
IMPORTANT: Since loop temperatures are normally  
between 60 and 90 F, pipe sweating and heat loss do not  
occur at normal ambient temperature conditions. Insulation  
must be installed on loop water piping on those sections  
that run through unheated areas or are located outside the  
building. If loop temperatures are expected below the  
ambient dew point, the optional internal insulation  
(extended range) package must be ordered.  
WARNING  
To prevent injury or death due to electrical shock or contact  
with moving parts, open unit disconnect before servicing  
unit.  
Follow the instructions below to properly clean and flush  
the system:  
CAUTION  
CAUTION  
DO NOT FLUSH SYSTEM THROUGH THE UNIT!  
DO NOT bend or kink supply lines or hoses. Damage to  
unit may result.  
1. Verify that electrical power to the units is disconnected,  
and that the circulation pump is deenergized.  
2. Connect the supply hose directly to the return riser valve.  
Use a single length of flexible hose, as shown in Fig. 35.  
NOTE: If the length of hose is too short (i.e., the resulting con-  
nection would exceed the minimum bend radius of the hose),  
substitute two lengths of flexible hose joined together with a  
field-supplied, standard NPT coupling and the flare-fitting-to-  
pipe adapters provided with the hose kit (Fig. 35).  
3. Open all air vents. Fill the system with water. Do not al-  
low system to overflow. Bleed all air from the system.  
Check the system for leaks and repair appropriately.  
4. Check and adjust the water and air level in the expansion  
tank.  
5. Verify all strainers are in place. Start the pumps, and sys-  
tematically check each vent to ensure all air is bled from  
the system.  
6. Verify make-up water is available. Adjust make-up water  
appropriately to replace the air that was bled from the  
system. Pressure test and inspect the system for leaks and  
make any necessary repairs. Check and adjust the water  
and air level in the expansion tank.  
4. Before making the final water connections, flush the sys-  
tem as described in the Pre-Start-Up section of this  
manual. After flushing the system, connect piping and  
hoses to the proper supply, return and condensate connec-  
tions of the unit.  
NOTE: When necessary, use adapters to connect hoses.  
5. Install any other system components, as required, follow-  
ing manufacturer’s instructions.  
6. Reinstall the front cabinet by carefully lowering the front  
cabinet over the chassis onto the backplate.  
Step 7 — Install Condensate Piping — Connect  
the unit condensate drain to the building condensate drain with  
5
a flexible, nonpressure-rated /8-in. (16 mm) ID plastic hose.  
Avoid kinks in this hose to ensure an unobstructed flow of con-  
densate from the unit to the drain.  
The horizontal run of the condensate hose is usually too  
short to pose any drainage problems, however, the horizontal  
run of condensate line should be pitched at least 1 in. for every  
10 ft of run (in the direction of flow). Avoid low points and un-  
pitched piping since dirt collects in these areas and may cause  
stoppage and overflow.  
Field installation of a trap or vent is not required unless  
specified by local codes. The 50PEC units are designed in a  
blow-thru configuration. The condensate drain pan is located  
on the outlet side of the blower so that the pressure in the drain  
pan is higher than the atmospheric pressure.  
7. Open a drain at the lowest point in the system. Adjust the  
make-up water replacement rate to equal the rate of bleed.  
Continue to bleed the system until the water appears  
clean or for at least three hours, whichever is longest;  
then, completely drain the system.  
1/2Flexible Hose  
Brass Adapter  
(1/2MPT x 1/2”  
Male Flare)  
Supply Valve  
Floor Line  
Return Valve  
NOTE: Use standard coupling (field-supplied)  
and hose adapters to join 2 hoses.  
Fig. 35 — Temporary Connection for Flushing System Piping  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Refill the system with clean, chemically treated water.  
Since water varies for each locality, contact a local water  
treatment company for the correct treatment chemicals to  
use in the area. Set the boiler to raise the loop temperature  
to approximately 85 F.  
3. System Water pH: Verify system water is slightly alkaline  
(pH = 7.5 to 8.5). Proper pH promotes the longevity of  
the hoses and heat exchangers. See Table 9.  
4. Closed-Type Cooling Tower (Open Tower with Heat Ex-  
changer): Check equipment for proper temperature set  
points and operation.  
5. Balanced Water Flow Rate to Heat Pump: Record the  
inlet and outlet water temperatures as each heat pump  
unit is started. This check will eliminate nuisance unit  
tripouts resulting from water velocities that are either too  
low or too high; it can also prevent erosive water flow  
rates.  
.
CAUTION  
To avoid possible damage to piping systems constructed of  
plastic piping DO NOT allow loop temperature to exceed  
110 F.  
Circulate the solution for a minimum of 8 to 24 hours. At  
the end of this period, shut off the circulating pump and  
drain the solution. Repeat system cleaning as necessary.  
9. When the cleaning process is complete, remove the short-  
circuited hoses. Connect the hoses to the proper supply  
and return connections on each unit. Refill the system and  
bleed off all air.  
10. Test the system pH with litmus paper. The system water  
should be slightly alkaline (pH 7.0 to 8.5). Add chemi-  
cals, as appropriate, to maintain acidity levels.  
6. Standby Pump: Verify the standby pump is properly in-  
stalled and in operating condition.  
7. System Control: To ensure no catastrophic system fail-  
ures occur, verify system controls are functioning and the  
sequencing is correct.  
8. Freeze Protection for Water Systems: Verify freeze  
protection is provided for the outdoor portion of the loop  
water system. Inadequate freeze protection leads to  
expensive repairs.  
CAUTION  
CAUTION  
To avoid equipment damage, DO NOT leave system filled  
in a building without heat during the winter unless anti-  
freeze is added to system water. Condenser coils never  
fully drain by themselves and will freeze unless winterized  
with antifreeze.  
DO NOT use “Stop-Leak” or any similar chemical agent in  
this system. Addition of these chemicals to the loop water  
will foul the system and will inhibit unit operation.  
11. When the system is successfully cleaned, flushed, refilled  
and bled, check the main system panels, safety cutouts  
and alarms. Set the controls to properly maintain loop  
temperatures.  
9. System Water Loop: Verify all air is bled from the sys-  
tem. Air in the system impedes unit operation and causes  
corrosion in the system piping.  
System Checkout — When the installation is complete  
and the system is cleaned and flushed, follow the system  
checkout procedure outlined below.  
1. Voltage: Ensure voltage is within the utilization range  
specifications of the unit compressor and fan motor.  
2. System Water Temperature: Ensure temperature is within  
an acceptable range shown in Table 8. (When conducting  
this check, also verify proper heating and cooling set  
points.)  
10. Unit Filters: To avoid system damage and to provide  
maximum performance, ensure the unit filter is clean.  
11. Unit Fans: Manually rotate fans to assure free rotation.  
Ensure fans are properly secured to the fan shaft. Do not  
oil fan motors on start-up since they are lubricated at the  
factory.  
12. System Control Center: To ensure control of the tempera-  
ture set points for operation of the system’s heat rejector  
and boiler, examine the system control and alarm panel  
for proper installation and operation.  
Table 8 — Air and Water Limits  
50PEC UNIT  
Min Ambient Air  
Rated Ambient Air  
Max Ambient Air  
Min Entering Air  
Rated Entering Air, dry bulb/wet bulb  
Max Entering Air, dry bulb/wet bulb  
Min Entering Water  
Normal Entering Water  
Max Entering Water  
COOLING (F)  
HEATING (F)  
50  
80  
50  
70  
85  
50  
70  
80  
20  
70  
90  
100  
50  
80/67  
100/83  
30  
85  
110  
NOTES:  
1. Minimum air and water conditions can only be used at nominal flow rates.  
2. 50PEC units may have up to two values at maximum or minimum with all  
other parameters at normal conditions.  
3. Operating limits shown are for start-up, not continuous operation. It is  
assumed that such a start-up is for the purpose of bringing the space to  
desired occupancy temperature.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Water Quality Guidelines  
HX  
MATERIAL*  
CLOSED  
RECIRCULATING†  
CONDITION  
OPEN LOOP AND RECIRCULATING WELL**  
Scaling Potential — Primary Measurement  
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.  
pH/Calcium  
Hardness Method  
All  
N/A  
pH < 7.5 and Ca Hardness, <100 ppm  
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)  
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be  
implemented.  
Ryznar Stability Index  
6.0 - 7.5  
If >7.5 minimize steel pipe use.  
–0.5 to +0.5  
All  
N/A  
Langelier Saturation Index  
All  
N/A  
If <–0.5 minimize steel pipe use.  
Based upon 150 F HWG and direct well, 85 F indirect well HX.  
Iron Fouling  
Iron Fe2+ (Ferrous)  
<0.2 ppm (Ferrous)  
If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.  
<0.5 ppm of Oxygen  
All  
All  
N/A  
N/A  
(Bacterial Iron Potential)  
Iron Fouling  
Above this level deposition will occur.  
Corrosion Prevention††  
pH  
6 - 8.5  
Minimize steel pipe below 7 and no open tanks with pH <8.  
<0.5 ppm  
6 - 8.5  
All  
All  
Monitor/treat as needed.  
Hydrogen Sulfide (H2S)  
At H2S>0.2 ppm, avoid use of copper and cupronickel piping of HXs.  
Rotten egg smell appears at 0.5 ppm level.  
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.  
N/A  
N/A  
Ammonia Ion as Hydroxide,  
Chloride, Nitrate and Sulfate  
Compounds  
<0.5 ppm  
All  
Maximum Chloride Levels  
Maximum allowable at maximum water temperature.  
50 F (10 C)  
75 F (24 C)  
100 F (38 C)  
Copper  
Cupronickel  
304 SS  
N/A  
N/A  
N/A  
N/A  
N/A  
<20 ppm  
<150 ppm  
<400 ppm  
<1000 ppm  
>1000 ppm  
NR  
NR  
<250 ppm  
<550 ppm  
>550 ppm  
NR  
NR  
<150 ppm  
<375 ppm  
>375 ppm  
316 SS  
Titanium  
Erosion and Clogging  
Particulate Size and Erosion  
<10 ppm of particles and a  
maximum velocity of 6 fps.  
Filtered for maximum  
800 micron size.  
<10 ppm (<1 ppm “sandfreefor reinjection) of particles and a maximum  
velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that  
is not removed can potentially clog components.  
All  
All  
Brackish  
Use cupronickel heat exchanger when concentrations of calcium or sodium  
chloride are greater than 125 ppm are present. (Seawater is approximately  
25,000 ppm.)  
N/A  
LEGEND  
††If the concentration of these corrosives exceeds the maximum allow-  
able level, then the potential for serious corrosion problems exists.  
Sulfides in the water quickly oxidize when exposed to air, requiring that  
no agitation occur as the sample is taken. Unless tested immediately  
at the site, the sample will require stabilization with a few drops of one  
Molar zinc acetate solution, allowing accurate sulfide determination up  
to 24 hours after sampling. A low pH and high alkalinity cause system  
problems, even when both values are within ranges shown. The term  
pH refers to the acidity, basicity, or neutrality of the water supply.  
Below 7.0, the water is considered to be acidic. Above 7.0, water is  
considered to be basic. Neutral water contains a pH of 7.0.  
HWG — Hot Water Generator  
HX  
Heat Exchanger  
N/A  
Design Limits Not Applicable Considering Recirculating  
Potable Water  
NR  
SS  
Application Not Recommended  
Stainless Steel  
*Heat exchanger materials considered are copper, cupronickel, 304 SS  
(stainless steel), 316 SS, titanium.  
†Closed recirculating system is identified by a closed pressurized piping  
system.  
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is  
equivalent to ppm.  
**Recirculating open wells should observe the open recirculating design  
considerations.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
compressor relay can be set to turn on with Stage 1 or Stage 2  
call from the thermostat. This setting is used with dual stage  
units (units with 2 compressors and 2 Deluxe D controls) or in  
master/slave applications. In master/slave applications, each  
compressor and fan will stage according to its switch 2 setting.  
If switch is set to Stage 2, the compressor will have a 3-second  
delay before energizing during stage 2 demand.  
FIELD SELECTABLE INPUTS  
Jumpers and DIP (dual in-line package) switches on the  
control board are used to customize unit operation and can be  
configured in the field.  
IMPORTANT: Jumpers and DIP switches should only  
be clipped when power to control board has been turned  
off.  
NOTE: If DIP switch is set for Stage 2, the alarm relay will not  
cycle during Test mode.  
Heating/Cooling Thermostat Type — Switch 3 provides selec-  
tion of thermostat type. Heat pump or heat/cool thermostats  
can be selected. Select OFF for heat/cool thermostats. When in  
heat/cool mode, Y1 is used for Cooling Stage 1, Y2 is used for  
Cooling Stage 2, W1 is used for Heating Stage 1 and O/W2 is  
used for Heating Stage 2. Select ON for heat pump applica-  
tions. In heat pump mode, Y1 used is for Compressor Stage 1,  
Y2 is used for Compressor Stage 2, W1 is used for Heating  
Stage 3 or emergency heat, and O/W2 is used for RV (heating  
or cooling) depending upon switch 4 setting.  
O/B Thermostat Type — Switch 4 provides selection for heat  
pump O/B thermostats. O is cooling output. B is heating out-  
put. Select ON for heat pumps with O output. Select OFF for  
heat pumps with B output.  
Dehumidification Fan Mode — Switch 5 provides selection  
of normal or dehumidification fan mode. Select OFF for dehu-  
midification mode. The fan speed relay will remain OFF dur-  
ing Cooling Stage 2. Select ON for normal mode. The fan  
speed relay will turn on during Cooling Stage 2 in normal  
mode.  
Complete C Control Jumper Settings (See  
Fig. 17, 18, and 21)  
WATER COIL FREEZE PROTECTION (FP1) LIMIT  
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to  
choose FP1 temperature limit of 10 F or 30 F. To select 30 F as  
the temperature limit, DO NOT clip the jumper. To select 10 F  
as the limit, clip the jumper.  
ALARM RELAY SETTING — Select jumper 1 (JW1) for  
connecting alarm relay terminal (AL2) to 24-vac (R) or to re-  
main as a dry contact (no connection). To connect AL2 to R, do  
not clip the jumper. To set as dry contact, clip the jumper.  
Complete C Control DIP Switches — The Com-  
plete C control has one DIP switch block with five switches.  
See Fig. 17, 18, and 21.  
PERFORMANCE MONITOR (PM) — DIP switch 1 will  
enable or disable this feature. To enable the PM, set the switch  
to ON. To disable the PM, set the switch to OFF.  
STAGE 2 — DIP switch 2 will enable or disable compressor  
delay. Set DIP switch to OFF for Stage 2 in which the compres-  
sor will have a 3-second delay before energizing.  
Switch 6 — Not used.  
Boilerless Operation — Switch 7 provides selection of boiler-  
less operation and works in conjunction with switch 8. In boil-  
erless operation mode, only the compressor is used for heating  
when FP1 is above the boilerless changeover temperature set  
by switch 8 below. Select ON for normal operation or select  
OFF for boilerless operation.  
Boilerless Changeover Temperature — Switch 8 on S1 pro-  
vides selection of boilerless changeover temperature set point.  
Select OFF for set point of 50 F or select ON for set point of  
40 F.  
If switch 8 is set for 50 F, then the compressor will be used  
for heating as long as the FP1 is above 50 F. The compressor  
will not be used for heating when the FP1 is below 50 F and the  
compressor will operate in emergency heat mode, staging on  
EH1 and EH2 to provide heat. If a thermal switch is being used  
instead of the FP1 thermistor, only the compressor will be used  
for heating mode when the FP1 terminals are closed. If the FP1  
terminals are open, the compressor is not used and the control  
goes into emergency heat mode.  
SWITCH 3 AND SWITCH 4 — Not used.  
FREEZE PROTECTION (FP1) — DIP switch 5 is used to  
initiate one or 3 tries for the FP1 fault. If there is water freeze  
protection for the water coil then DIP switch 5 can be set to  
lock out on the FP1 fault after one try. ON = One try.  
OFF = 3 tries.  
Deluxe D Control Jumper Settings (See Fig. 19,  
20, and 22)  
WATER COIL FREEZE PROTECTION (FP1) LIMIT  
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to  
choose FP1 temperature limit of 10 F or 30 F. To select 30 F as  
the temperature limit, DO NOT clip the jumper. To select 10 F  
as the limit, clip the jumper.  
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2  
Dry) for connecting alarm relay terminal (AL2) to 24-vac (R)  
or to remain as a dry contact (no connection). To connect AL2  
to R, do not clip the jumper. To set as dry contact, clip the  
jumper.  
LOW PRESSURE SETTING — The Deluxe D control can  
be configured for low pressure setting (LP). Select jumper 1  
(JW1-LP Norm Open) for choosing between low pressure in-  
put normally opened or closed. To configure for normally  
closed operation, do not clip the jumper. To configure for nor-  
mally open operation, clip the jumper.  
DIP SWITCH BLOCK 2 (S2) — The following set of DIP  
switches is used to configure accessory relay options.  
Switches 1 to 3 — These DIP switches provide selection of  
Accessory 1 relay options. See Table 10 for DIP switch  
combinations.  
Table 10 — DIP Switch Block S2 —  
Accessory 1 Relay Options  
Deluxe D Control DIP Switches — The Deluxe D  
control has 2 DIP switch blocks. Each DIP switch block has  
8 switches and is labeled either S1 or S2 on the circuit board.  
See Fig. 19, 20, and 22.  
DIP SWITCH BLOCK 1 (S1) — This set of switches offers  
the following options for Deluxe D control configuration:  
DIP SWITCH POSITION  
ACCESSORY 1  
RELAY OPTIONS  
1
2
3
Digital NSB  
Water Valve — Slow Opening  
Off  
On  
On  
Off  
On  
On  
LEGEND  
Performance Monitor (PM) — Set switch 1 to enable or dis-  
able performance monitor. To enable the PM, set the switch to  
ON. To disable the PM, set the switch to OFF.  
Compressor Relay Staging Operation — Switch 2 will en-  
able or disable compressor relay staging operation. The  
NSB  
Night Setback  
NOTE: All other DIP switch combinations are invalid.  
Switches 4 to 6 — These DIP switches provide selection of  
Accessory 2 relay options. See Table 11 for DIP switch  
combinations.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 — DIP Switch Block S2 —  
Accessory 2 Relay Options  
(i.e., approximately 50 to 80 F dry bulb). Loop water tem-  
perature entering the heat pumps should be at least 40 F  
but not in excess of 110 F. Refer to Table 8 for more spe-  
cific information on the operating parameters of units.  
DIP SWITCH POSITION  
ACCESSORY 2  
RELAY OPTIONS  
4
5
6
Digital NSB  
Water Valve — Slow Opening  
Off  
On  
On  
Off  
On  
On  
IMPORTANT: Three factors determine the operating limits  
of a unit: (1) return-air temperature, (2) water temperature  
and (3) ambient temperature. Whenever any one of these  
factors is at a minimum or maximum level, the other two  
factors must be at normal levels to ensure proper unit oper-  
ation. Flow rates must be at nominal ARI (Air Condition-  
ing and Refrigeration Institute)/ISO (International  
Organization for Standardization)/ ASHRAE (American  
Society of Heating, Refrigerating and Air Conditioning  
Engineers) 13256-1 standards.  
LEGEND  
NSB — Night Setback  
NOTE: All other switch combinations are invalid.  
Auto Dehumidification Mode or High Fan Mode — Switch  
7 provides selection of auto dehumidification fan mode or high  
fan mode. In auto dehumidification fan mode, the fan speed  
relay will remain off during Cooling Stage 2 if terminal H is  
active. In high fan mode, the fan enable and fan speed relays  
will turn on when terminal H is active. Set the switch to ON for  
auto dehumidification fan mode or to OFF for high fan mode.  
Unit Start-Up/Cooling  
1. Turn the unit thermostat to the cooling position and turn  
the fan speed switch to “HI.” If the unit has an optional  
MCO thermostat, set the selector switch to Cool. Both the  
fan and compressor should run.  
2. Check for cool air delivery at unit grille 15 minutes after  
the unit has begun operating. List the identification num-  
ber of any machines that do not function at this time.  
3. Check the elevation and cleanliness of the condensate  
lines; any dripping could be a sign of a blocked line.  
4. Select low fan speed. Airflow should decrease and com-  
pressor should operate.  
Switch 8 — Not used.  
Deluxe D Control Accessory Relay Configura-  
tions — The following accessory relay settings are applica-  
ble for Deluxe D control only:  
CYCLE WITH COMPRESSOR — In this configuration, the  
relay will be ON any time the compressor relay is on.  
DIGITAL NIGHT SETBACK (NSB) — In this configura-  
tion, the relay will be ON if the NSB input is connected to  
ground C.  
NOTE: If there are no relays configured for digital NSB, then  
the NSB and OVR (override) inputs are automatically config-  
ured for mechanical operation.  
MECHANICAL NIGHT SETBACK — When NSB input is  
connected to ground C, all thermostat inputs are ignored. A  
thermostat setback heating call will then be connected to the  
OVR input. If OVR input becomes active, then the Deluxe D  
control will enter night low limit (NLL) staged heating mode.  
The NLL staged heating mode will then provide heating during  
the NSB period.  
5. Slowly turn thermostat toward warmer position. Both fan  
and compressor should shut off when thermostat set point  
equals room temperature. Room temperature must be  
below 90 F for unit to shut off.  
6. Operate each heat pump in the heating cycle immediately  
after checking cooling cycle operation. A time delay will  
prevent the compressor from re-starting for approximate-  
ly 5 minutes.  
Operating Limits  
WATER VALVE (SLOW OPENING) — If relay is config-  
ured for water valve (slow opening), the relay will start 60 sec-  
onds prior to starting compressor relay.  
ENVIRONMENT — This equipment is designed for indoor  
installation ONLY.  
POWER SUPPLY — A voltage variation of ± 10% of name-  
plate utilization voltage is acceptable.  
CAUTION  
50PEC UNIT STARTING CONDITIONS — The 50PEC  
units will start and operate at an ambient temperature of 50 F  
with entering-air temperature at 50 F, entering water at 60 F,  
and with both air and water at the flow rates used in the  
ARI/ISO/ASHRAE Standard 13256-1 rating test, for initial  
start-up in winter.  
To avoid equipment damage, DO NOT leave system filled  
in a building without heat during the winter unless anti-  
freeze is added to system water. Condenser coils never  
fully drain by themselves and will freeze unless winterized  
with antifreeze.  
IMPORTANT: These operating limits are not normal or  
continuous operating conditions. It is assumed that such a  
start-up is for the purpose of bringing the building space up  
to occupancy temperature.  
START-UP  
Use the procedure outlined below to initiate proper unit  
start-up:  
Unit Start-Up/Heating  
IMPORTANT: This equipment is designed for indoor  
installation ONLY.  
1. Adjust the unit thermostat to the warmest setting and turn  
the fan speed switch to “HI.” If the unit has an optional  
MCO thermostat, set the selector switch to Heat. The  
blower should start immediately and after the time delay  
is complete, the compressor will start.  
WARNING  
2. Once the unit has begun to run, check for warm air delivery  
at the unit grille. Again, the installing contractor must list  
the serial number of any machine that does not function.  
When the disconnect switch is closed, high voltage is  
present in some areas of the electrical panel. Exercise cau-  
tion when working with the energized equipment.  
3. Log the unit operating conditions at initial start-up for  
each unit to establish a permanent operating record.  
4. Select low fan speed. Airflow should decrease and com-  
pressor should continue to operate.  
1. Adjust all valves to the full open position and turn on the  
line power to all heat pump units.  
2. Operate each unit in the Cooling mode first.  
Room temperature should be in the normal range  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Slowly turn thermostat toward cooler position. Both fan  
and compressor should shut off when thermostat set point  
equals room temperature. Room temperature must be  
above 65 F for unit to shut off.  
c. Scroll to day, month and year using arrow keys.  
Use number keypad to set date.  
5. To set Daylight Savings Time (DST):  
a. Push the DST softkey. The display will indicate  
02:00:060 which is equal to 2:00AM.  
b. To program the beginning and end dates, scroll  
down to the beginning month and press the enter  
key. The softkeys (INCR and DECR) will activate  
to increment the month in either direction, Jan,  
Feb, March, etc.  
Unit Start-Up with WSHP Open Controls —  
The WSHP Open is a multi-protocol (default BACnet*) con-  
troller with extensive features, flexible options and powerful  
capabilities. The unit comes from the factory pre-programmed  
and needs minimal set up to function in a BAS (Building  
Automation System) system or provide additional capabilities  
to Carrier's WSHP product line. Most settings on the controller  
have factory defaults set for ease of installation. There are a  
few settings that must be configured in the field and several  
settings that can be adjusted if required by unique job condi-  
tions. Refer to Appendix A — WSHP Open Screen Configura-  
tion. In order to configure the unit, a BACview6 display is  
required. See Fig. 36.  
NOTE: If the WSHP Open control has lost its programming,  
all display pixels will be displayed on the SPT sensor. See the  
WSHP Third Party Integration Guide.  
When the unit is OFF, the SPT sensor will indicate OFF.  
When power is applied, the SPT sensor will indicate tempera-  
ture in the space at 78 F.  
c. Use number keys to select the day of month and  
year.  
d. Push the OK softkey to finalize the data.  
6. To view configuration settings:  
a. Select the Config softkey.  
b. Select the Service Config softkey. Scroll through  
the factory settings by using the up and down  
arrow keys. See below for factory settings.  
Only the following settings will need to be  
checked.  
• # of Fan Speeds — This should be set to "1" for  
units with PSC motors and set to "3" for units with  
ECM motors.  
To start-up a unit with WSHP Open controls:  
• Compressor Stages — This should be set to "1."  
• Factory Dehumidification Reheat Coil — This  
should be set to "none" unless the modulating hot  
water reheat option is supplied in the unit, then set  
to "installed."  
The condenser water limit needs to be verified  
depending on design parameters and application,  
whether geothermal or boiler/tower.  
1. To plug in the BACview6 handheld display into a SPT  
sensor, point the two ears on the connector up and tilt the  
bottom of the plug toward you. Insert the plug up into the  
SPT sensor while pushing the bottom of the plug away  
from you.  
2. BACview6 should respond with "Establishing Connec-  
tion." The Home screen will then appear on the display  
showing operating mode and space temperature. Press  
any button to continue.  
7. To view unit configuration settings:  
a. Select the Unit Configuration softkey, then select  
Unit.  
See Appendix A — WSHP Open Screen Configuration  
for the hierarchal structure of the WSHP Open controller.  
All functions of the controller can be set from the Home  
screen.  
b. Scroll through the unit settings by using the up and  
down arrow keys. Unit settings include:  
• Fan Mode: Default Continuous  
3. When the Login is requested, type 1111 and push the OK  
softkey. The Logout will then be displayed to indicate the  
password was accepted.  
• Fan Delay:  
• Minimum SAT Cooling: Default 50 F  
• Maximum SAT Heating: Default 110 F  
• Filter Service Alarm: Must be set from 0 to 9999 hr  
4. To set the Clock if it is not already displayed:  
a. Select System Settings from the Home screen, then  
press Clockset.  
b. Scroll to hour, minute and second using the arrow  
keys. Use the number keypad to set actual time.  
8. To set local schedules:  
a. Select the Schedule softkey from the Configuration  
screen, then press enter.  
a50-8444  
Fig. 36 — BACview6 Display Interface  
*Sponsored by ASHRAE (American Society of Heating, Refrigerat-  
ing and Air Conditioning Engineers).  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. Select Weekly, then press enter (7 schedules  
available).  
applying some back pressure. To accomplish this, slightly close  
the leaving isolation valve of the water regulating device.  
c. Select day and press enter.  
d. Press enter again and select ADD or DEL (DECR  
or INCR) set schedule.  
e. Enter ON/OFF time, then press continue.  
f. Press OK to apply and save to a particular day of  
the week.  
CAUTION  
DO NOT use “Stop Leak” or any similar chemical agent in  
this system. Addition of these chemicals to the loop water  
will foul the system and inhibit unit operation.  
Antifreeze — In areas where entering loop temperatures  
drop below 40 F or where piping will be routed through areas  
subject to freezing, antifreeze is needed.  
Alcohols and glycols are commonly used as antifreeze  
agents. Freeze protection should be maintained to 15 F below the  
lowest expected entering loop temperature. For example, if the  
lowest expected entering loop temperature is 30 F, the leaving  
loop temperature would be 22 to 25 F. Therefore, the freeze pro-  
tection should be at 15 F (30 F –15 F) = 15 F.  
g. Continue to add the same or different schedule spe-  
cific days of the week.  
To add exceptions to the schedule:  
i. Press Add softkey.  
ii. Select exception type from following:  
• Date  
• Date Range  
• Week-N-Day  
• Calender Reference  
9. Go back to Home Screen.  
IMPORTANT: All alcohols should be pre-mixed and  
pumped from a reservoir outside of the building or intro-  
duced under water level to prevent alcohols from fuming.  
10. Remove BACview6 cable from SPT sensor by reversing  
the process in Step 1.  
11. Perform system test.  
Calculate the total volume of fluid in the piping system. See  
Table 13. Use the percentage by volume in Table 14 to deter-  
mine the amount of antifreeze to use. Antifreeze concentration  
should be checked from a well mixed sample using a hydrome-  
ter to measure specific gravity.  
FREEZE PROTECTION SELECTION — The 30 F FP1 fac-  
tory setting (water) should be used to avoid freeze damage to  
the unit.  
Flow Regulation — Flow regulation can be accom-  
plished by two methods. Most water control valves have a  
built-in flow adjustment valve. Determine the flow rate by  
measuring the pressure drop through the unit heat exchanger.  
See Table 12. Adjust the water control valve until a flow of 1.5  
to 2 gpm per ton cooling is achieved. Since the pressure  
constantly varies, two pressure gages may be needed.  
An alternative method for regulating flow is to install a flow  
control device. These devices are typically an orifice of plastic  
material mounted on the outlet of the water control valve,  
designed to allow a specified flow rate. Occasionally these  
valves produce a velocity noise that can be reduced by  
Once antifreeze is selected, the JW3 jumper (FP1) should  
be clipped on the control to select the low temperature  
(antifreeze 10 F) set point to avoid nuisance faults.  
Table 12 — Coaxial Water Pressure Drop  
PRESSURE DROP (ft wg)  
30 F  
50 F  
70 F  
90 F  
UNIT  
FLOW  
Without  
Motorized  
Valve  
Without  
Motorized  
Valve  
Without  
Motorized  
Valve  
Without  
Motorized  
Valve  
50PEC (GPM)  
With Cv = 2.9  
MOPD = 125 psi  
With Cv = 2.9  
MOPD = 125 psi  
With Cv = 2.9  
MOPD = 125 psi  
With Cv = 2.9  
MOPD = 125 psi  
1.3  
1.8  
3.2  
5.0  
1.8  
3.3  
5.3  
1.2  
2.6  
4.2  
2.1  
4.2  
6.8  
2.0  
3.6  
5.8  
1.3  
2.5  
3.9  
1.6  
2.9  
4.5  
1.2  
2.2  
3.5  
2.0  
3.7  
6.0  
1.5  
2.9  
4.6  
1.2  
2.2  
3.5  
1.4  
2.6  
4.1  
1.1  
2.0  
3.2  
1.8  
3.3  
5.5  
1.3  
2.7  
4.2  
6.5  
11.4  
19.6  
1.5  
2.9  
4.8  
2.4  
4.9  
8.2  
1.0  
2.0  
3.0  
1.3  
2.3  
3.7  
1.0  
1.9  
3.0  
1.6  
3.0  
4.9  
1.2  
2.4  
3.8  
6.5  
11.4  
19.6  
1.4  
2.7  
4.5  
2.3  
4.6  
7.7  
09  
12  
15  
18  
1.9  
2.5  
1.6  
2.3  
3.1  
1.8  
2.7  
3.6  
2.4  
3.6  
4.8  
6.5  
6.5  
11.4  
19.6  
1.6  
3.4  
5.7  
2.8  
5.8  
9.6  
11.4  
19.6  
1.6  
3.1  
5.0  
2.6  
5.2  
8.8  
LEGEND  
Cv  
Flow Coefficient  
MOPD — Maximum Operating Pressure Differential  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 — Approximate Fluid Volume (gal)  
per 100 ft of Pipe  
or the W terminal is disregarded. The compressor relay will re-  
main on and EH1 (emergency heat) is immediately turned on.  
EH2 will turn on after 10 minutes of continual Stage 2 demand.  
PIPE  
DIAMETER (in.)  
VOLUME (gal.)  
NOTE: EH2 will not turn on (or if on, will turn off) if FP1  
(freeze protection) temperature is greater than 45 F and FP2 is  
greater than 110 F.  
EMERGENCY HEAT — In Emergency Heat (EH) mode,  
terminal W is active while terminal Y is not. Terminal G must  
be active or the W terminal is disregarded. EH1 is immediately  
turned on. EH2 will turn on after 5 minutes of continuous  
emergency heat demand.  
Copper  
1
4.1  
6.4  
9.2  
1.25  
1.5  
Rubber Hose  
Polyethylene  
1
3.9  
3/4 IPS SDR11  
1 IPS SDR11  
11/4 IPS SDR11  
1/2 IPS SDR11  
2 IPS SDR11  
11/4 IPS SCH40  
11/2 IPS SCH40  
2 IPS SCH40  
2.8  
4.5  
8.0  
10.9  
18.0  
8.3  
10.9  
17.0  
Units with Aquazone Deluxe D Control  
LEGEND  
STANDBY/FAN ONLY — The compressor will be off. The  
fan enable, fan speed, and reversing valve (RV) relays will be  
on if inputs are present. If there is a Fan 1 demand, the fan  
enable will immediately turn on. If there is a Fan 2 demand, the  
fan enable and fan speed will immediately turn on.  
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1  
and Fan 2 outputs.  
IPS  
Internal Pipe Size  
Schedule  
SCH  
SDR  
Standard Dimensional Ratio  
NOTE: Volume of heat exchanger is approximately 1.0 gallon.  
Table 14 — Antifreeze Percentages by Volume  
MINIMUM TEMPERATURE FOR FREEZE  
PROTECTION (F)  
ANTIFREEZE  
10  
25  
15  
21  
20  
16  
25  
10  
HEATING STAGE 1 — In Heating Stage 1 mode, the fan en-  
able and compressor relays are turned on immediately. Once  
the demand is removed, the relays are turned off and the con-  
trol reverts to Standby mode. If there is a master/slave or dual  
compressor application, all compressor relays and related  
functions will operate per their associated DIP switch 2 setting  
on S1.  
HEATING STAGE 2 — In Heating Stage 2 mode, the fan en-  
able and compressor relays remain on. The fan speed relay is  
turned on immediately and turned off immediately once the de-  
mand is removed. The control reverts to Heating Stage 1 mode.  
If there is a master/slave or dual compressor application, all  
compressor relays and related functions will operate per their  
associated DIP switch 2 setting on S1.  
HEATING STAGE 3 — In Heating Stage 3 mode, the fan en-  
able, fan speed and compressor relays remain on. The EH1 out-  
put is turned on immediately. With continuing Heat Stage 3 de-  
mand, EH2 will turn on after 10 minutes. EH1 and EH2 are  
turned off immediately when the Heating Stage 3 demand is re-  
moved. The control reverts to Heating Stage 2 mode.  
Output EH2 will be off if FP1’s temperature is greater than  
45 F AND FP2 (when shorted) is greater than 110 F during  
Heating Stage 3 mode. This condition will have a 30-second  
recognition time. Also, during Heating Stage 3 mode, EH1,  
EH2, fan enable, and fan speed will be ON if G input is not  
active.  
EMERGENCY HEAT — In Emergency Heat mode, the fan  
enable and fan speed relays are turned on. The EH1 output is  
turned on immediately. With continuing emergency heat de-  
mand, EH2 will turn on after 5 minutes. Fan enable and fan  
speed relays are turned off after a 60-second delay. The control  
reverts to Standby mode.  
Methanol (%)  
100% USP Food Grade  
Propylene Glycol (%)  
38  
30  
22  
15  
Cooling Tower/Boiler Systems — These systems  
typically use a common loop maintained at 60 to 90 F. Carrier  
recommends using a closed circuit evaporative cooling tower  
with a secondary heat exchanger between the tower and the  
water loop. If an open type cooling tower is used continuously,  
chemical treatment and filtering will be necessary.  
Ground Coupled, Closed Loop and Plateframe  
Heat Exchanger Well Systems These systems al-  
low water temperatures from 30 to 110 F. The external loop  
field is divided up into 2 in. polyethylene supply and return  
lines. Each line has valves connected in such a way that upon  
system start-up, each line can be isolated for flushing using only  
the system pumps. Air separation should be located in the pip-  
ing system prior to the fluid re-entering the loop field.  
OPERATION  
Power Up Mode — The unit will not operate until all the  
inputs, terminals and safety controls are checked for normal  
operation.  
NOTE: The compressor will have a 5-minute anti-short cycle  
delay upon power up.  
Units with Aquazone™ Complete C Control  
STANDBY — The Y and W terminals are not active in Stand-  
by mode, however the O and G terminals may be active, de-  
pending on the application. The compressor will be off.  
COOLING — The Y and O terminals are active in Cooling  
mode. After power up, the first call to the compressor will ini-  
tiate a 5 to 80-second random start delay and a 5-minute anti-  
short cycle protection time delay. After both delays are com-  
plete, the compressor is energized.  
NOTE: On all subsequent compressor calls the random start  
delay is omitted.  
HEATING STAGE 1 — Terminal Y is active in Heating  
Stage 1. After power up, the first call to the compressor will  
initiate a 5 to 80-second random start delay and a 5-minute  
anti-short cycle protection time delay. After both delays are  
complete, the compressor is energized.  
Output EH1, EH2, fan enable, and fan speed will be ON if  
the G input is not active during Emergency Heat mode.  
COOLING STAGE 1 — In Cooling Stage 1 mode, the fan  
enable, compressor and RV relays are turned on immediately.  
If configured as stage 2 (DIP switch set to OFF) then the com-  
pressor and fan will not turn on until there is a stage 2 demand.  
The fan enable and compressor relays are turned off immedi-  
ately when the Cooling Stage 1 demand is removed. The con-  
trol reverts to Standby mode. The RV relay remains on until  
there is a heating demand. If there is a master/slave or dual  
compressor application, all compressor relays and related func-  
tions will track with their associated DIP switch 2 on S1.  
NOTE: On all subsequent compressor calls the random start  
delay is omitted.  
HEATING STAGE 2 — To enter Stage 2 mode, terminal W is  
active (Y is already active). Also, the G terminal must be active  
COOLING STAGE 2 — In Cooling Stage 2 mode, the fan  
enable, compressor and RV relays remain on. The fan speed re-  
lay is turned on immediately and turned off once the Cooling  
Stage 2 demand is removed. The control reverts to Cooling  
Stage 1 mode. If there is a master/slave or dual compressor  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
application, all compressor relays and related functions will  
track with their associated DIP switch on S1.  
both occupied and unoccupied periods. Continuous fan mode  
is intermittent during unoccupied periods and continuous dur-  
ing occupied periods. Always On mode operates the fan con-  
tinuously during both occupied and unoccupied periods. In the  
default mode, Continuous, the fan will be turned on whenever  
any one of the following is true:  
2
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL  
staged Heating mode, the override (OVR) input becomes  
active and is recognized as a call for heating and the control  
will immediately go into a Heating Stage 1 mode. With an  
additional 30 minutes of NLL demand, the control will go into  
Heating Stage 2 mode. With another additional 30 minutes of  
NLL demand, the control will go into Heating Stage 3 mode.  
• The unit is in occupied mode as determined by its occu-  
pancy status.  
• There is a demand for cooling or heating in the unoccu-  
pied mode.  
Units with WSHP Open Multiple Protocol —  
The WSHP Open multi-protocol controller will control me-  
chanical cooling, heating and waterside economizer outputs  
based on its own space temperature input and set points. An  
optional CO2 IAQ (indoor air quality) sensor mounted in the  
space can maximize the occupant comfort. The WSHP Open  
controller has its own hardware clock that is automatically set  
when the heat pump software is downloaded to the board. Oc-  
cupancy types are described in the scheduling section below.  
The following sections describe the functionality of the WSHP  
Open multi-protocol controller. All point objects referred to in  
this sequence of operation will be referenced to the objects as  
viewed in the BACview6 handheld user interface.  
• There is a call for dehumidification (optional).  
When power is reapplied after a power outage, there will be  
a configured time delay of 5 to 600 seconds before starting the  
fan. There are also configured fan delays for Fan On and Fan  
Off. The Fan On delay defines the delay time (0 to 30 seconds;  
default 10) before the fan begins to operate after heating or  
cooling is started while the Fan Off delay defines the delay  
time (0 to 180 seconds; default 45) the fan will continue to op-  
erate after heating or cooling is stopped. The fan will continue  
to run as long as the compressors, heating stages, or the dehu-  
midification relays are on. If the SPT failure alarm or conden-  
sate overflow alarm is active; the fan will be shut down imme-  
diately regardless of occupancy state or demand.  
SCHEDULING — Scheduling is used to start/stop the unit  
based on a time period to control the space temperature to spec-  
ified occupied heating and cooling set points. The controller is  
defaulted to control by occupied set points all the time, until ei-  
ther a time schedule is configured with BACview6, Field Assis-  
tant, i-Vu® Open, or a third party control system to enable/dis-  
able the BAS (Building Automation System) on/off point. The  
local time and date must be set for these functions to operate  
properly. The occupancy source can be changed to one of the  
following:  
Occupancy Schedules — The controller will be occupied 24/7  
until a time schedule has been configured using either Field  
Assistant, i-Vu Open, BACview6 or a third party control system  
to enable/disable the BAS on/off point. The BAS point can be  
disabled by going to Config, then Unit, then Occupancy Sched-  
ules and changing the point from enable to disable then click-  
ing OK.  
Fan Speed Control (During Heating) — Whenever heat is re-  
quired and active, the control continuously monitors the sup-  
ply-air temperature to verify it does not rise above the config-  
ured maximum heating SAT limit (110 F default). As the SAT  
approaches this value, the control will increase the fan speed as  
required to ensure the SAT will remain within the limit. This  
feature provides the most quiet and efficient operation by oper-  
ating the fan at the lowest speed possible.  
Fan Speed Control (During Cooling) — Whenever mechani-  
cal cooling is required and active, the control continuously  
monitors the supply-air temperature to verify it does not fall be-  
low the configured minimum cooling SAT limit (50 F default).  
As the SAT approaches this value, the control will increase the  
fan speed as required to ensure the SAT will remain within the  
limit. The fan will operate at lowest speed to maximize latent  
capacity during cooling.  
COOLING — The WSHP Open controller will operate one or  
two stages of compression to maintain the desired cooling set  
point. The compressor outputs are controlled by the PI (propor-  
tional-integral) cooling loop and cooling stages capacity algo-  
rithm. They will be used to calculate the desired number of  
stages needed to satisfy the space by comparing the space tem-  
perature (SPT) to the appropriate cooling set point. The water  
side economizer, if applicable, will be used for first stage cool-  
ing in addition to the compressor(s). The following conditions  
must be true in order for the cooling algorithm to run:  
• Cooling is set to Enable.  
• Heating mode is not active and the compressor time  
guard has expired.  
• Condensate overflow input is normal.  
• If occupied, the SPT is greater than the occupied cooling  
set point.  
• Space temperature reading is valid.  
• If unoccupied, the SPT is greater than the unoccupied  
cooling set point.  
NOTE: This point must be enabled in order for the i-Vu Open,  
Field Assistant, or BACview6 control system to assign a time  
schedule to the controller.  
Schedule_schedule — The unit will operate according to the  
schedule configured and stored in the unit. The schedule is  
accessible via the BACview6 Handheld tool, i-Vu Open, or  
Field Assistant control system. The daily schedule consists of a  
start/stop time (standard or 24-hour mode) and seven days of  
the week, starting with Monday and ending on Sunday. To  
enter a daily schedule, navigate to Config, then Sched, then  
enter BACview6 Admin Password (1111), then go to  
schedule_schedule. From here, enter either a Weekly or Excep-  
tion schedule for the unit.  
Occupancy Input Contact — The WSHP Open controller has  
the capability to use an external dry contact closure to deter-  
mine the occupancy status of the unit. The Occupancy Sched-  
ules will need to be disabled in order to utilize the occupancy  
contact input.  
NOTE: Scheduling can only be controlled from one source.  
• If economizer cooling is available and active and the  
economizer alone is insufficient to provide enough cool-  
ing.  
• OAT (if available) is greater than the cooling lockout  
temperature.  
BAS (Building Automation System) On/Off  
A
BAS  
system that supports network scheduling can control the unit  
through a network communication and the BAS scheduling  
function once the Occupancy Schedules have been disabled.  
If all the above conditions are met, the compressors will be  
energized as required, otherwise they will be deenergized. If  
cooling is active and should the SAT approach the minimum  
SAT limit, the fan will be indexed to the next higher speed.  
Should this be insufficient and if the SAT falls further (equal to  
the minimum SAT limit), the fan will be indexed to the  
NOTE: Scheduling can either be controlled via the unit or the  
BAS, but not both.  
INDOOR FAN — The indoor fan will operate in any one of  
three modes depending on the user configuration selected.  
Fan mode can be selected as Auto, Continuous, or Always  
On. In Auto mode, the fan is in intermittent operation during  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
maximum speed. If the SAT continues to fall 5
°
F below the  
After a compressor is staged off, it may be restarted again  
after a normal time-guard period of 5 minutes and if the sup-  
ply-air temperature has fallen below the maximum supply air  
temperature limit.  
The WSHP Open controller provides a status input to moni-  
tor the compressor operation. The status is monitored to deter-  
mine if the compressor status matches the commanded state.  
This input is used to determine if a refrigerant safety switch or  
other safety device has tripped and caused the compressor to  
stop operating normally. If this should occur, an alarm will be  
generated to indicate the faulted compressor condition. Also, if  
auxiliary heat is available (see below), the auxiliary heat will  
operate to replace the reverse cycle heating and maintain the  
space temperature as required.  
AUXILIARY HEAT — The WSHP Open controller can con-  
trol a two-position, modulating water, or steam valve connect-  
ed to a coil on the discharge side of the unit and supplied by a  
boiler or a single-stage ducted electric heater in order to main-  
tain the desired heating set point. Should the compressor capac-  
ity be insufficient or a compressor failure occurs, the auxiliary  
heat will be used. Unless the compressor fails, the auxiliary  
heat will only operate to supplement the heat provided by the  
compressor if the space temperature falls more than one degree  
below the desired heating set point (the amount is config-  
urable). The heat will be controlled so the SAT will not exceed  
the maximum heating SAT limit.  
Auxiliary Modulating Hot Water/Steam Heating Reheat  
— The control can modulate a hot water or steam valve con-  
nected to a coil on the discharge side of the unit and supplied  
by a boiler in order to maintain the desired heating set point  
should the compressor capacity be insufficient or a compressor  
failure occurs. Unless a compressor fault condition exists, the  
valve will only operate to supplement the heat provided by the  
compressor if the space temperature falls more than one degree  
below the desired heating set point. The valve will be con-  
trolled so the SAT will not exceed the maximum heating SAT  
limit.  
minimum SAT limit, all cooling stages will be disabled.  
During Cooling mode, the reversing valve output will be  
held in the cooling position (either B or O type as configured)  
even after the compressor is stopped. The valve will not switch  
position until the Heating mode is required.  
The configuration screens contain the minimum SAT  
parameter as well as cooling lockout based on outdoor-air  
temperature (OAT) Both can be adjusted to meet various  
specifications.  
There is a 5-minute off time for the compressor as well as a  
5-minute time delay when staging up to allow the SAT to  
achieve a stable temperature before energizing a second stage  
of capacity. Likewise, a 45-second delay is used when staging  
down.  
After a compressor is staged off, it may be restarted again  
after a normal time-guard period of 5 minutes and if the sup-  
ply-air temperature has increased above the minimum supply-  
air temperature limit.  
The WSHP Open controller provides a status input to moni-  
tor the compressor operation. The status is monitored to deter-  
mine if the compressor status matches the commanded state.  
This input is used to determine if a refrigerant safety switch or  
other safety device has tripped and caused the compressor to  
stop operating normally. If this should occur, an alarm will be  
generated to indicate the faulted compressor condition.  
HEATING — The WSHP Open controller will operate one or  
two stages of compression to maintain the desired heating set  
point. The compressor outputs are controlled by the heating PI  
(proportional-integral) loop and heating stages capacity algo-  
rithm. They will be used to calculate the desired number of  
stages needed to satisfy the space by comparing the space tem-  
perature (SPT) to the appropriate heating set point. The follow-  
ing conditions must be true in order for the heating algorithm to  
run:  
• Heating is set to Enable.  
• Cooling mode is not active and the compressor time  
guard has expired.  
• Condensate overflow input is normal.  
• If occupied, the SPT is less than the occupied heating set  
point.  
• Space temperature reading is valid.  
• If unoccupied, the SPT is less than the unoccupied heat-  
ing set point.  
• OAT (if available) is less than the heating lockout  
temperature.  
If all the above conditions are met, the heating outputs will  
be energized as required, otherwise they will be deenergized. If  
the heating is active and should the SAT approach the maxi-  
mum SAT limit, the fan will be indexed to the next higher  
speed. Should this be insufficient, and the SAT rises further  
reaching the maximum heating SAT limit, the fan will be  
indexed to the maximum speed. If the SAT still continues to  
rise 5
°
F above the maximum limit, all heating stages will be  
disabled.  
During Heating mode, the reversing valve output will be  
held in the heating position (either B or O type as configured)  
even after the compressor is stopped. The valve will not switch  
position until the Cooling mode is required.  
The configuration screens contain the maximum SAT  
parameter as well as heating lockout based on outdoor-air  
temperature (OAT); both can be adjusted to meet various  
specifications.  
There is a 5-minute off time for the compressor as well as a  
5-minute time delay when staging up to allow the SAT to  
achieve a stable temperature before energizing a second stage  
of capacity. Likewise, a 45-second delay is used when staging  
down.  
Two-Position Hot Water/Steam Heating Reheat The con-  
trol can operate a two-position, NO or NC, hot water or steam  
valve connected to a coil on the discharge side of the unit and  
supplied by a boiler in order to maintain the desired heating set  
point should the compressor capacity be insufficient or a com-  
pressor failure occurs. Unless a compressor fault condition ex-  
ists, the valve will only open to supplement the heat provided  
by the compressor if the space temperature falls more than one  
degree below the desired heating set point. The valve will be  
controlled so the SAT will not exceed the maximum heating  
SAT limit. The heat stage will also be subject to a 2-minute  
minimum OFF time to prevent excessive valve cycling.  
Single Stage Electric Auxiliary Heat — The control can op-  
erate a field-installed single stage of electric heat installed on  
the discharge side of the unit in order to maintain the desired  
heating set point should the compressor capacity be insufficient  
or a compressor failure occurs. Unless a compressor fault con-  
dition exists, the heat stage will only operate to supplement the  
heat provided by the compressor if the space temperature falls  
more than one degree below the desired heating set point. The  
heat stage will be controlled so the SAT will not exceed the  
maximum heating SAT limit. The heat stage will also be sub-  
ject to a 2-minute minimum OFF time to prevent excessive  
cycling.  
INDOOR AIR QUALITY (IAQ) AND DEMAND CON-  
TROLLED VENTILATION (DCV) — If the optional in-  
door air quality sensor is installed, the WSHP Open controller  
can maintain indoor air quality via a modulating OA damper  
providing demand controlled ventilation. The control operates  
the modulating OA damper during occupied periods. The con-  
trol monitors the CO2 level and compares it to the configured  
set points, adjusting the ventilation rate as required. The control  
provides proportional ventilation to meet the requirements of  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASHRAE (American Society of Heating, Refrigerating and  
Air Conditioning Engineers) specifications by providing a base  
ventilation rate and then increasing the rate as the CO2 level in-  
creases. The control will begin to proportionally increase venti-  
lation when the CO2 level rises above the start ventilation set  
point and will reach the full ventilation rate when the CO2 level  
is at or above the maximum set point. A user-configurable min-  
imum damper position ensures that proper base ventilation is  
delivered when occupants are not present. The IAQ configura-  
tions can be accessed through the configuration screen. The  
following conditions must be true in order for this algorithm to  
run:  
• Damper control is configured for DCV.  
• The unit is in an occupied mode.  
• The IAQ sensor reading is greater than the DCV start  
control set point.  
The control has four user adjustable set points: DCV start  
control set point, DCV maximum control set point, minimum  
damper position, and DCV maximum damper position.  
Two-Position OA Damper — The control can be configured  
to operate a ventilation damper in a two-position ventilation  
mode to provide the minimum ventilation requirements during  
occupied periods.  
WATERSIDE ECONOMIZER — The WSHP Open control-  
ler has the capability of providing modulating or two-position  
water economizer operation (for a field-installed economizer  
coil mounted to the entering air side of the unit and connected  
to the condenser water loop) in order to provide free cooling  
(or preheating) when water conditions are optimal. Water econ-  
omizer settings can be accessed through the equipment status  
screen. The following conditions must be true for economizer  
operation:  
Cooling — The purpose is to provide a cooling economizer  
function directly from the condenser water loop when the en-  
tering water loop temperature is suitable (at least 5
°
F below  
space temperature). If the optional coil is provided and the wa-  
ter loop conditions are suitable, then the valve will open to pro-  
vide cooling to the space when required. Should the capacity  
be insufficient for a period greater than 5 minutes, or should a  
high humidity condition occur, then the compressor will be  
started to satisfy the load. Should the SAT reach the minimum  
cooling SAT limit, the economizer valve will close during  
compressor operation.  
Heating — Additionally, the economizer control will open the  
water valve should the entering water loop temperature be suit-  
able for heating (at least 5
°
F above space temperature) and  
heat is required. The valve will be controlled in a similar man-  
ner except to satisfy the heating requirement. Should the coil  
capacity be insufficient to satisfy the space load for more than  
5 minutes, then the compressor will be started to satisfy the  
load. Should the SAT reach the maximum heating SAT limit,  
the economizer valve will close during compressor operation.  
DEMAND LIMIT — The WSHP Open controller has the  
ability to accept three levels of demand limit from the network.  
In response to a demand limit, the unit will decrease its heating  
set point and increase its cooling set point to widen the range in  
order to immediately lower the electrical demand. The amount  
of temperature adjustment in response is user adjustable for  
both heating and cooling and for each demand level. The re-  
sponse to a particular demand level may also be set to zero.  
CONDENSER WATER LINKAGE — The control pro-  
vides optimized water loop operation using an universal con-  
troller (UC) open loop controller. Loop pump operation is auto-  
matically controlled by WSHP equipment occupancy sched-  
ules, unoccupied demand and tenant override conditions.  
Positive pump status feedback prevents nuisance fault trips.  
The condenser water linkage operates when a request for con-  
denser water pump operation is sent from each WSHP to the  
loop controller. This request is generated whenever any WSHP  
is scheduled to be occupied, is starting during optimal start (for  
warm-up or pull down prior to occupancy), there is an unoccu-  
pied heating or cooling demand, or a tenant pushbutton over-  
ride. At each WSHP, the water loop temperature and the loop  
pump status is given. The WSHP will NOT start a compressor  
until the loop pumps are running or will shutdown the com-  
pressors should the pumps stop. This prevents the WSHP from  
operating without water flow and thus tripping out on refriger-  
ant pressure, causing a lockout condition. The WSHP Open  
controller control will prevent this from occurring. Also, the  
loop controller can be configured to start the pumps only after a  
configurable number of WSHPs are requesting operation (from  
1-"N"). This can be used to prevent starting the entire loop op-  
eration for only one WSHP. Meanwhile, the WSHPs will not  
operate if the loop pump status is off and therefore the WSHP  
compressor will not run.  
• SAT reading is available.  
• LWT reading is available.  
• If occupied, the SPT is greater than the occupied cooling  
set point or less than the occupied heating set point and  
the condenser water is suitable.  
• Space temperature reading is valid.  
• If unoccupied, the SPT is greater than the unoccupied  
cooling set point or less than the unoccupied heating set  
point and the condenser water is suitable.  
Modulating Water Economizer Control — The control has  
the capability to modulate a water valve to control condenser  
water flowing through a coil on the entering air side of the unit.  
Cooling — The purpose is to provide an economizer cooling  
function by using the water loop when the entering water loop  
temperature is suitable (at least 5
°
F below space temperature).  
If the water loop conditions are suitable, then the valve will  
modulate open as required to maintain a supply-air temperature  
that meets the load conditions. Should the economizer coil ca-  
pacity alone be insufficient for a period greater than 5 minutes,  
or should a high humidity condition occur, then the compressor  
will also be started to satisfy the load. Should the SAT ap-  
proach the minimum cooling SAT limit, the economizer valve  
will modulate closed during compressor operation.  
COMPLETE C AND DELUXE D BOARD  
SYSTEM TEST  
Heating — Additionally, the control will modulate the water  
valve should the entering water loop temperature be suitable  
for heating (at least 5
°
F above space temperature) and heat is  
required. The valve will be controlled in a similar manner ex-  
cept to satisfy the heating requirement. Should the economizer  
coil capacity alone be insufficient to satisfy the space load con-  
ditions for more than 5 minutes, then the compressor will be  
started to satisfy the load. Should the SAT approach the maxi-  
mum heating SAT limit, the economizer valve will modulate  
closed during compressor operation.  
Two-Position Water Economizer Control — The control has  
the capability to control a NO or NC, two-position water valve  
to control condenser water flow through a coil on the entering  
air side of the unit.  
System testing provides the ability to check the control  
operation. The control enters a 20-minute Test mode by  
momentarily shorting the test pins. All time delays are reduced  
by a factor of 15.  
Test Mode — To enter Test mode on Complete C or  
Deluxe D controls, cycle the power 3 times within 60 seconds.  
The LED (light-emitting diode) will flash a code representing  
the last fault when entering the Test mode. The alarm relay will  
also power on and off during Test mode. See Tables 15-17. To  
exit Test mode, short the terminals for 3 seconds or cycle the  
power 3 times within 60 seconds.  
NOTE: The Deluxe D control has a flashing code and alarm  
relay cycling code that will both have the same numerical  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
label. For example, flashing code 1 will have an alarm relay  
cycling code 1. Code 1 indicates the control has not faulted  
since the last power-off to power-on sequence.  
NOTE: The auxiliary heating test, H2O economizer test, open  
vent damper 100% test, and preposition OA damper features  
will not be visible on the screen unless configured.  
Once tests are complete, set unit test back to disable. Unit will  
automatically reset to disable after 1 hour.  
WSHP Open Test Mode — To enter WSHP Open test  
mode, navigate from the BACview6 home screen to the config-  
uration screen. Choose the service screen and enable unit test.  
The controller will then test the following:  
FAN TEST — Tests all fan speeds, sequences fan from low to  
high, and operates each speed for one minute. Resets to disable  
on completion.  
Retry Mode — In Retry mode, the status LED will start to  
flash slowly to signal that the control is trying to recover from an  
input fault. The control will stage off the outputs and try to again  
satisfy the thermostat used to terminal Y. Once the thermostat in-  
put calls are satisfied, the control will continue normal operation.  
NOTE: If 3 consecutive faults occur without satisfying the  
thermostat input call to terminal Y, the control will go into  
lockout mode. The last fault causing the lockout is stored in  
memory and can be viewed by entering Test mode.  
COMPRESSOR TEST — Tests compressor cooling and  
heating operation. Sequences cooling stage 1 then cooling  
stage 2 followed by heating stage 2 then reduces capacity to  
heating stage 1. Operates for 1 minute per step.  
DEHUMIDIFICATION TEST — Tests dehumidification  
mode. Operates for 2 minutes.  
AUXILIARY HEATING TEST — Tests auxiliary heat.  
Sequences fan on and enables heating coil for 1 minute.  
Aquazone™ Deluxe D Control LED Indica-  
tors — There are 3 LED indicators on the Deluxe D control:  
STATUS LED — Status LED indicates the current status or  
mode of the Deluxe D control. The Status LED light is green.  
H2O ECONOMIZER TEST — Tests entering/returning  
water loop economizer operation. Sequences fan and opens  
economizer water valve for one minute.  
OPEN VENT DAMPER 100% TEST — Tests outside air  
(OA) damper operation.  
TEST LED — Test LED will be activated any time the De-  
luxe D control is in Test mode. The Test LED light is yellow.  
FAULT LED — Fault LED light is red. The fault LED will  
always flash a code representing the last fault in memory. If  
there is no fault in memory, the fault LED will flash code 1 and  
appear as 1 fast flash alternating with a 10-second pause. See  
Table 17.  
PREPOSITION OA DAMPER — Prepositions OA damper  
actuator to set proper preload.  
Table 15 — Complete C Control Current LED Status and Alarm Relay Operations  
LED STATUS  
DESCRIPTION OF OPERATION  
ALARM RELAY  
Open  
Normal Mode  
On  
Off  
Normal Mode with PM Warning  
Complete C Control is non-functional  
Fault Retry  
Cycle (Closed 5 sec, Open 25 sec)  
Open  
Open  
Slow Flash  
Over/Under Voltage Shutdown  
Lockout  
Open (Closed after 15 minutes)  
Closed  
Fast Flash  
Flashing Code 1  
Flashing Code 2  
Flashing Code 3  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
Flashing Code 7  
Flashing Code 8  
Flashing Code 9  
Test Mode — No fault in memory  
Test Mode — HP Fault in memory  
Test Mode — LP Fault in memory  
Test Mode — FP1 Fault in memory  
Test Mode — FP2 Fault in memory  
Test Mode — CO Fault in memory  
Test Mode — Over/Under shutdown in memory  
Test Mode — PM in memory  
Cycling Code 1  
Cycling Code 2  
Cycling Code 3  
Cycling Code 4  
Cycling Code 5  
Cycling Code 6  
Cycling Code 7  
Cycling Code 8  
Cycling Code 9  
Test Mode — FP1/FP2 swapped fault in memory  
LEGEND  
NOTES:  
1. Slow flash is 1 flash every 2 seconds.  
2. Fast flash is 2 flashes every 1 second.  
3. EXAMPLE: “Flashing Code 2is represented by 2 fast flashes followed  
by a 10-second pause. This sequence will repeat continually until the  
fault is cleared.  
CO  
FP  
HP  
Condensate Overflow  
Freeze Protection  
High Pressure  
LED  
LP  
PM  
Light-Emitting Diode  
Low Pressure  
Performance Monitor  
Table 16 — Complete C Control LED Code and Fault Descriptions  
LED CODE  
FAULT  
No fault in memory  
DESCRIPTION  
There has been no fault since the last power-off to power-on sequence  
HP open instantly  
1
2
3
4
5
6
High-Pressure Switch  
Low-Pressure Switch  
LP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds)  
FP1 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)  
FP2 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)  
Sensor overflow (grounded) for 30 continuous seconds  
Freeze Protection Coax — FP1  
Freeze Protection Air Coil — FP2  
Condensate overflow  
7 (Autoreset)  
8
9
Over/Under Voltage Shutdown  
PM Warning  
"R" power supply is <19-vac or >30-vac  
Performance monitor Warning has occurred.  
FP1 and FP2 Thermistors are swapped  
FP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than FP1 in  
cooling/test mode.  
LEGEND  
FP  
Freeze Protection  
High Pressure  
Light-Emitting Diode  
LP  
PM  
Low Pressure  
Performance Monitor  
HP  
LED  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 17 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations  
STATUS LED  
(Green)  
TEST LED  
(Yellow)  
Off  
DESCRIPTION  
Normal Mode  
Normal Mode with PM  
D Control is non-functional  
Test Mode  
Night Setback  
ESD  
Invalid T-stat Inputs  
No Fault in Memory  
HP Fault  
LP Fault  
FP1 Fault  
FP2 Fault  
CO Fault  
Over/Under Voltage  
HP Lockout  
LP Lockout  
FP1 Lockout  
FP2 Lockout  
CO Lockout  
FAULT LED (Red)  
ALARM RELAY  
On  
On  
Off  
Flash Last Fault Code in Memory  
Flashing Code 8  
Open  
Off  
Off  
On  
Cycle (closed 5 sec, open 25 sec, …)  
Off  
Open  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flashing Code 1  
Cycling Appropriate Code  
Flashing Code 2  
Flashing Code 3  
Flashing Code 4  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Open  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Flashing Code 2  
Open  
Flashing Code 3  
Open  
Flashing Code 4  
Open  
Flashing Code 5  
Open  
Flashing Code 6  
Open  
Flashing Code 7  
Open (closed after 15 minutes)  
Flashing Code 2  
Closed  
Closed  
Closed  
Closed  
Closed  
Flashing Code 3  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
LEGEND  
Condensate Overflow  
Emergency Shutdown  
Freeze Protection  
High Pressure  
NOTES:  
1. If there is no fault in memory, the Fault LED will flash code 1.  
2. Codes will be displayed with a 10-second Fault LED pause.  
3. Slow flash is 1 flash every 2 seconds.  
CO  
ESD  
FP  
LED  
LP  
PM  
Light-Emitting Diode  
Low Pressure  
Performance Monitor  
4. Fast flash is 2 flashes every 1 second.  
HP  
5. EXAMPLE: “Flashing Code 2is represented by 2 fast flashes followed  
by a 10-second pause. This sequence will repeat continually until the  
fault is cleared.  
exchanger should be kept full of water at all times. Open loop  
systems should have an inverted P trap placed in the discharge  
line to keep water in the heat exchanger during off cycles.  
Closed loop systems must have a minimum of 15 psig during  
the summer and 40 psig during the winter.  
SERVICE  
Perform the procedures outlined below periodically, as  
indicated.  
WARNING  
Check P trap frequently for proper operation.  
To prevent injury or death due to electrical shock or contact  
with moving parts, open unit disconnect switch before ser-  
vicing unit.  
FILTERS — Inspect filters. Establish a regular maintenance  
schedule. Clean or replace filters frequently depending on  
need.  
To remove the filter from the 50PEC unit, slide the filter out  
of its frame located in the return air opening at the bottom front  
of the unit. When re-installing the filter, use the slide-in rails of  
the filter frame to guide the filter into the proper position.  
IMPORTANT: When a compressor is removed from this  
unit, system refrigerant circuit oil will remain in the com-  
pressor. To avoid leakage of compressor oil, the refrigerant  
lines of the compressor must be sealed after it is removed.  
CAUTION  
IMPORTANT: All refrigerant discharged from this unit  
must be recovered without exception. Technicians must fol-  
low industry accepted guidelines and all local, state and fed-  
eral statutes for the recovery and disposal of refrigerants.  
To avoid fouled machinery and extensive unit clean-up,  
DO NOT operate units without filters in place. DO NOT  
use equipment as a temporary heat source during  
construction.  
IMPORTANT: To avoid the release of refrigerant into the  
atmosphere, the refrigerant circuit of this unit must only be  
serviced by technicians who meet local, state and federal  
proficiency requirements.  
Refrigerant System — Verify air and water flow rates  
are at proper levels before servicing. To maintain sealed circuit-  
ry integrity, do not install service gages unless unit operation  
appears abnormal.  
Condenser Cleaning — Water-cooled condensers may  
require cleaning of scale (water deposits) due to improperly  
maintained closed-loop water systems. Open water tower  
systems may require removal of sludge build-up due to  
induced contaminants.  
Unit Inspection — Visually inspect the unit at least once  
a month. Pay special attention to hose assemblies. Repair any  
leaks and replace deteriorated hoses immediately. Note any  
signs of deterioration or cracking.  
System Flushing — Properly clean and flush system  
periodically. Refer to Pre-Start-Up, System Cleaning and  
Flushing section.  
Local water conditions may cause excessive fouling or  
pitting of tubes. Therefore, condenser tubes should be cleaned  
at least once a year, or more often if the water is contaminated.  
Use standard coil cleaning procedures which are compatible  
with both the heat exchanger material and copper water lines.  
Generally, the more water flowing through the unit, the less  
chance for scaling, however flow rates over 3 gpm per ton can  
Water Coil — Keep air out of the water coil. Check open  
loop systems to be sure the well head is not allowing air to in-  
filtrate the water line. Always keep lines airtight.  
Inspect heat exchangers regularly and clean more frequently  
if the unit is located in a “dirty” environment. The heat  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
produce water (or debris) velocities that can erode the heat ex-  
changer wall and ultimately produce leaks.  
Proper water treatment can minimize tube fouling and  
pitting. If such conditions are anticipated, water treatment anal-  
ysis is recommended. Refer to the Carrier System Design Man-  
ual, Part 5, for general water conditioning information.  
GAS VENT  
PUMP  
PRIMING  
CONN.  
GLOBE  
VALVES  
SUCTION  
SUPPLY  
PUMP  
SUPPORT  
1PIPE  
CAUTION  
CONDENSER  
Follow all safety codes. Wear safety glasses and rubber  
gloves when using inhibited hydrochloric acid solution.  
Observe and follow acid manufacturer’s instructions.  
TANK  
REMOVE WATER  
REGULATING VALVE  
Clean condensers with an inhibited hydrochloric acid solu-  
tion. The acid can stain hands and clothing, damage concrete,  
and, without inhibitor, damage steel. Cover surroundings to  
guard against splashing. Vapors from vent pipe are not harmful,  
but take care to prevent liquid from being carried over by the  
gases.  
RETURN  
FINE MESH  
SCREEN  
Fig. 38 — Forced Circulation Method  
Condensate Pans — Check condensate drain pans for  
algae growth every three months. If algae growth is apparent,  
consult a water treatment specialist for proper chemical treat-  
ment. The application of an algaecide every three months will  
typically eliminate algae problems in most locations. Check  
condensate hose for leaks and blockage and correct any  
problems.  
Warm solution acts faster, but cold solution is just as effec-  
tive if applied for a longer period.  
GRAVITY FLOW METHOD — Do not add solution faster  
than vent can exhaust the generated gases.  
When condenser is full, allow solution to remain overnight,  
then drain condenser and flush with clean water. Follow acid  
manufacturer’s instructions. See Fig. 37.  
Blower Motors — All units have lubricated fan motors.  
BLOWER MOTORS SHOULD NEVER BE LUBRICATED  
UNLESS OBVIOUS, DRY OPERATION IS SUSPECTED.  
Periodic maintenance oiling is not recommended because it  
will result in dirt accumulating on excess oil and cause eventu-  
al motor failure. Conduct annual dry operation check and am-  
perage check to ensure amp draw is no more than 10% greater  
than that indicated by serial plate data.  
FILL CONDENSER WITH  
CLEANING SOLUTION. DO  
PAIL  
NOT ADD SOLUTION  
MORE RAPIDLY THAN  
VENT CAN EXHAUST  
GASES CAUSED BY  
FUNNEL  
CHEMICAL ACTION.  
1  
Compressor — Conduct an amperage check annually on  
the compressor and fan motor. Amperage draw should not  
exceed normal full load amps. Maintain a log of amperage to  
detect deterioration prior to component failure.  
PIPE  
VENT  
PIPE  
5’ APPROX  
Safety Control Reset — The 50PEC heat pumps are  
furnished with high-pressure, low-pressure and low-  
temperature cutouts to prevent the machine from operating at  
abnormal conditions of temperature or water flow.  
3’ TO 4’  
CONDENSER  
The contacts of the high-pressure control used on 50PEC  
units are designed to open at 376 psig and automatically  
re-close at 304 psig. The Complete C or Deluxe D control  
monitors this and other functions such as refrigerant tempera-  
tures and pressures and condensate overflow and will interrupt  
unit heating or cooling operation.  
PAIL  
The machine must be reset manually. Reset is accomplished  
by pressing the STOP button and then pushing either HI HEAT,  
LOW HEAT, HI COOL or LO COOL to restart the unit in the  
desired mode of operation. (The 50PEC unit can also be reset  
by opening and closing the supply power disconnect switch.)  
Fig. 37 — Gravity Flow Method  
FORCED CIRCULATION METHOD — Fully open vent  
pipe when filling condenser. The vent may be closed when  
condenser is full and pump is operating. See Fig. 38.  
Regulate flow to condenser with a supply line valve. If  
pump is a nonoverloading type, the valve may be fully closed  
while pump is running.  
For average scale deposit, allow solution to remain in con-  
denser overnight. For heavy scale deposit, allow 24 hours.  
Drain condenser and flush with clean water. Follow acid manu-  
facturer’s instructions.  
IMPORTANT: If the unit must be reset more than twice,  
check the unit for a dirty filter, abnormal entering water  
temperature, inadequate or excessive water flow, and inter-  
nal malfunctions. If the unit continues to cut out, contact a  
trained service technician.  
WARNING  
When replacing the compressor contactor or lockout relay  
in a unit with electromechanical controls, use only Carrier  
factory authorized parts. Substitution of other components  
may result in an inoperative safety circuit and may cause a  
hazardous condition.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking System Charge — Units are shipped with  
Replacing the WSHP Open Controller’s Bat-  
tery — The WSHP Open controller’s 10-year lithium  
CR2032 battery provides a minimum of 10,000 hours of data  
retention during power outages.  
NOTE: Power must be ON to the WSHP Open controller  
when replacing the battery, or the date, time and trend data will  
be lost.  
full operating charge. If recharging is necessary:  
1. Insert thermometer bulb in insulating rubber sleeve on  
liquid line near filter drier. Use a digital thermometer for  
all temperature measurements. DO NOT use a mercury  
or dial-type thermometer.  
2. Connect pressure gage to discharge line near compressor.  
1. Remove the battery from the controller, making note of  
the battery's polarity.  
3. After unit conditions have stabilized, read head pressure  
on discharge line gage.  
2. Insert the new battery, matching the battery's polarity  
with the polarity indicated on the WSHP Open controller.  
NOTE: Operate unit a minimum of 15 minutes before  
checking charge. From standard field-supplied Pressure-  
Temperature chart for R-410A, find equivalent saturated  
condensing temperature.  
TROUBLESHOOTING  
4. Read liquid line temperature on thermometer, then  
subtract from bubble point temperature. The difference  
equals subcooling temperature.  
When troubleshooting problems with a WSHP, consider the  
following and refer to Table 18.  
Thermistor — A thermistor may be required for single-  
phase units where starting the unit is a problem due to low  
voltage.  
Refrigerant Charging  
WARNING  
WSHP Open Controller — With the WSHP Open con-  
troller option, the 100 most recent alarms can be viewed using  
the BACview6 alarm status and alarm history.  
To prevent personal injury, wear safety glasses and gloves  
when handling refrigerant. Do not overcharge system —  
this can cause compressor flooding.  
To view the alarms:  
1. Navigate to the Alarm Status screen from the Home  
screen using the arrow softkeys. The screen will display  
the current alarm status, either normal or Alarm, and al-  
low for scrolling through the unit’s alarm status.  
NOTE: Do not vent or depressurize unit refrigerant to atmo-  
sphere. Remove and recover refrigerant following accepted  
practices.  
2. From the Alarm Status screen, press the Alarm softkey to  
view the 100 most recent alarms which are labeled with  
date and time for easy reference.  
Air Coil Fan Motor Removal  
CAUTION  
NOTE: Active faults can be viewed by scrolling down,  
these faults indicate a possible bad sensor or some condi-  
tion which may not merit an alarm.  
Before attempting to remove fan motors or motor mounts,  
place a piece of plywood over evaporator coils to prevent  
coil damage.  
3. To view alarms which have been corrected, scroll down  
through the Alarm screen to Return Top Normal screen.  
Motor power wires need to be disconnected from motor  
terminals before motor is removed from unit.  
NOTE: Alarms are automatically reset once alarm con-  
dition has been corrected.  
1. Shut off unit main power supply.  
See Table 18 for possible alarm cause and solution.  
2. Loosen bolts on mounting bracket so that fan belt can be  
removed.  
3. Loosen and remove the 2 motor mounting bracket bolts  
on left side of bracket.  
4. Slide motor/bracket assembly to extreme right and lift out  
through space between fan scroll and side frame. Rest  
motor on a high platform such as a step ladder. Do not  
allow motor to hang by its power wires.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 — Troubleshooting  
FAULT  
HEATING COOLING  
POSSIBLE CAUSE  
SOLUTION  
Main Power Problems  
X
X
Green Status LED Off  
Check line voltage circuit breaker and disconnect.  
Check for line voltage between L1 and L2 on the contactor.  
Check for 24-vac between R and C on controller.  
Check primary/secondary voltage on transformer.  
HP Fault — Code 2  
High Pressure  
X
X
Reduced or no water flow in Check pump operation or valve operation/setting.  
cooling  
Check water flow adjust to proper flow rate.  
Water temperature out of  
range in cooling  
Bring water temperature within design parameters.  
X
X
Reduced or no airflow in  
heating  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
Dirty air coil — construction dust, etc. Perform preventative mainte-  
nance; Clean air coil.  
High external static. Check duct design and downstream interference.  
Air temperature out of range Bring return-air temperature within design parameters.  
in heating  
X
X
X
X
X
X
X
Overcharged with refrigerant Check superheat/subcooling vs. typical operating condition.  
Bad HP switch  
Insufficient charge  
Check switch continuity and operation. Replace.  
Check for refrigerant leaks.  
LP Fault — Code 3  
Low Pressure/Loss of  
Charge  
Compressor pump down at Check charge and start-up water flow.  
start-up  
FP1 Fault — Code 4  
Water Freeze Protection  
X
Reduced or no water flow in Check pump operation or water valve operation/setting.  
heating  
Plugged strainer or filter. Clean or replace.  
Check water flow adjust to proper flow rate.  
X
X
Inadequate antifreeze level Check antifreeze density with hydrometer.  
Improper freeze protect set- Clip JW3 jumper for antifreeze (10 F) use.  
ting (10 F vs. 30 F)  
X
X
Water temperature out of  
range  
Bad thermistor  
Reduced or no airflow in  
cooling  
Bring water temperature within design parameters.  
X
X
Check temperature and impedance correlation.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
High external static. Check duct design and downstream interference.  
FP2 Fault — Code 5  
Air Coil Freeze  
Protection  
X
X
Air temperature out of range Too much cold vent air. Bring entering-air temperature within design  
parameters.  
Improper freeze protect set- Normal airside applications will require 30 F only.  
ting (10 F vs. 30 F)  
X
X
X
X
X
X
X
Bad thermistor  
Blocked drain  
Improper trap  
Poor drainage  
Check temperature and impedance correlation.  
Check for blockage and clean drain.  
Check trap dimensions and location ahead of vent.  
Check for piping slope away from unit.  
Condensate Fault —  
Code 6  
Check slope of unit toward outlet.  
Poor venting. Check vent location.  
X
X
Moisture on sensor  
Under voltage  
Check for moisture shorting to air coil.  
Check power supply and 24-vac voltage before and during operation.  
Check power supply wire size.  
Over/Under Voltage —  
Code 7  
(Auto Resetting)  
X
Check compressor starting.  
Check 24-vac and unit transformer tap for correct power supply voltage.  
Check power supply voltage and 24 vac before and during operation.  
Check 24-vac and unit transformer tap for correct power supply voltage.  
Check for poor airflow or overcharged unit.  
Check for poor water flow or airflow.  
X
X
X
X
Over voltage  
Performance Monitor —  
Code 8  
Heating mode FP2>125 F  
Cooling mode FP1>125 F  
OR FP2< 40 F  
No Fault Code Shown  
Unit Short Cycles  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Compressor overload  
Control board  
Dirty air filter  
Unit in Test mode  
Unit selection  
Compressor overload  
Thermostat position  
Unit locked out  
Check and replace if necessary.  
Reset power and check operation.  
Check and clean air filter.  
Reset power or wait 20 minutes for auto exit.  
Unit may be oversized for space. Check sizing for actual load of space.  
Check and replace if necessary.  
Ensure thermostat set for heating or cooling operation.  
Check for lockout codes. Reset power.  
Check compressor overload. Replace if necessary.  
Check Y and W wiring at heat pump. Jumper Y and R for compressor  
operation in Test mode.  
Only Fan Runs  
Compressor overload  
Thermostat wiring  
LEGEND  
FP — Freeze Protection  
HP — High Pressure  
LED — Light-Emitting Diode  
LP — Low Pressure  
RV — Reversing Valve  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 — Troubleshooting (cont)  
FAULT  
HEATING COOLING  
POSSIBLE CAUSE  
SOLUTION  
Only Compressor Runs  
X
X
X
X
Thermostat wiring  
Check G wiring at heat pump. Jumper G and R for fan operation.  
Check Y and W wiring at heat pump. Jumper Y and R for compressor  
operation in Test mode.  
Jumper G and R for fan operation. Check for line voltage across BR  
contacts.  
Check fan power enable relay operation (if present).  
Check for line voltage at motor. Check capacitor.  
Set for cooling demand and check 24-vac on RV coil and at control.  
If RV is stuck, run high pressure up by reducing water flow and while  
operating engage and disengage RV coil voltage to push valve.  
X
Fan motor relay  
X
X
Fan motor  
Reversing valve  
Unit Does Not Operate in  
Cooling  
X
X
X
Thermostat setup  
Thermostat wiring  
Dirty filter  
Reduced or no airflow in  
heating  
Check for ‘O’ RV setup not ‘B’.  
Check O wiring at heat pump. Jumper O and R for RV coil.  
Replace or clean.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
High external static. Check duct design and downstream interference.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
High external static. Check duct design and downstream interference.  
Insufficient Capacity/  
Not Cooling or Heating  
Properly  
X
X
X
X
Reduced or no airflow in  
cooling  
X
Leaky ductwork  
Check supply and return-air temperatures at the unit and at distant  
duct registers if significantly different, duct leaks are present.  
X
X
X
X
X
X
Low refrigerant charge  
Restricted metering device Check superheat and subcooling. Replace.  
Defective reversing valve  
Thermostat improperly  
located  
Check superheat and subcooling.  
Perform RV touch test.  
Check location and for air drafts behind thermostat.  
X
X
X
X
X
X
Unit undersized  
Recheck loads and sizing check sensible cooling load and heat pump  
capacity.  
Perform scaling check and clean if necessary.  
Scaling in water heat  
exchanger  
Inlet water too hot or cold  
Reduced or no airflow in  
heating  
X
X
Check load, loop sizing, loop backfill, ground moisture.  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
High external static. Check duct design and downstream interference.  
High Head Pressure  
X
X
Reduced or no water flow in Check pump operation or valve operation/setting.  
cooling  
Check water flow adjust to proper flow rate.  
Inlet water too hot  
Check load, loop sizing, loop backfill, ground moisture.  
X
Air temperature out of range Bring return-air temperature within design parameters.  
in heating  
X
Scaling in water heat  
exchanger  
Perform scaling check and clean if necessary.  
X
X
X
X
Unit overcharged  
Non-condensables in  
system  
Check superheat and subcooling. Reweigh in charge.  
Vacuum system and reweigh in charge.  
X
X
X
Restricted metering device Check superheat and subcooling. Replace.  
Low Suction Pressure  
Reduced water flow in  
heating  
Check pump operation or water valve operation/setting.  
Plugged strainer or filter. Clean or replace.  
Check water flow adjust to proper flow rate.  
X
Water temperature out of  
range  
Bring water temperature within design parameters.  
X
Reduced airflow in cooling Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
High external static. Check duct design and downstream interference.  
X
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within design  
parameters.  
X
X
X
Insufficient charge  
Too high airflow  
Poor performance  
Too high airflow  
Unit oversized  
Check for refrigerant leaks.  
Check blower.  
See ‘Insufficient Capacity’ above.  
Check blower.  
Recheck loads and sizing check sensible cooling load and heat pump  
capacity.  
Low Discharge Air  
Temperature in Heating  
High Humidity  
X
X
LEGEND  
FP — Freeze Protection  
HP — High Pressure  
LED — Light-Emitting Diode  
LP — Low Pressure  
RV — Reversing Valve  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Off, Fan Only, Economize,  
Cooling, Heating, Cont Fan,  
Test, Start Delay, Dehumidify  
Operating Mode  
Displays unit operating mode  
°
°
SPT  
SAT  
F
F
Displays SPT  
Displays SAT  
Condenser Leaving  
Temperature  
Displays leaving condenser  
water temperature  
°
F
Displays entering condenser  
water temperature (Value  
will not update when compressor  
is operating)  
Condenser Entering  
Temperature  
°
F
Off/Low Speed/  
Medium Speed  
High Speed/On  
Fan  
Displays fan speed status  
Equipment  
Status  
No Password  
Required  
Compressor Capacity  
Damper Position  
H2O Economizer  
0 - 100%  
0 - 100%  
0 - 100%  
Displays compressor capacity  
Displays current damper position  
(Viewable only if Ventilation DMP  
Type = 2 position or DCV)  
Displays position of economizer valve  
Displays position of auxiliary  
reheat valve (Viewable only if Leaving  
Air Auxiliary Heat Type = 2 position,  
1 stage Elect or Modulating)  
Auxiliary Heat  
0 - 100%  
Displays space RH% (Viewable only if  
Humidity Sensor = Installed)  
Space RH  
0 - 100%  
Displays if dehumidification is active  
(Viewable only if Factory  
Dehumidification Reheat = Installed)  
Dehumidification  
Inactive/Active  
IAQ CO2  
0 - 9999 ppm  
Normal/Alarm  
Displays the space CO2 level  
Displays current space  
temperature condition  
SPT Alarm Status  
Displays the SPT that  
exceeded the alarm limit (when SPT  
alarm above is in Alarm)  
°
°
Alarming SPT  
F
F
Displays the SPT alarm limit that was  
exceeded; causing the alarm condition  
(when SPT alarm above is in Alarm)  
SPT Alarm Limit  
Displays the status of the Rnet  
SPT sensor - ALARM is displayed  
should the sensor fail to communicate  
with the control module  
SPT Sensor Alarm  
Status  
Normal/Alarm  
IAQ Alarm Status  
Normal/Alarm  
Normal/Alarm  
Normal/Alarm  
Normal/Alarm  
Current IAQ/ventilation condition  
Current compressor condition  
Current SAT condition  
Compressor Alarm  
Status  
No Password  
Required  
Alarm Status  
SAT Alarm Status  
Condensate Overflow  
Alarm Status  
Current status of the condensate  
drain (overflow switch)  
Condenser Water Tem-  
perature Alarm Status  
Current status of the  
condenser water  
Normal/Alarm  
Filter Alarm Status  
Normal/Alarm  
Normal/Alarm  
Current filter condition  
Space RH Alarm Status  
Current space RH condition  
Current status of the OAT  
broadcast function  
OAT Alarm Status  
Normal/Alarm  
Normal/Alarm  
Normal/Alarm  
Airside Linkage Status  
Current linkage status if enabled  
Condenser Water  
Linkage  
Current linkage status if enabled  
°
SAT  
F
Display SAT  
°
°
°
°
SAT Offset  
X
X
-9.9 - 10.0  
F
F
F
0
0
0
F
F
F
Used to correct sensor reading  
Leaving Condenser  
Water Temperature  
Displays Leaving Condenser  
Water Temperature  
°
F
°
Leaving CW Offset  
-9.9 - 10.0  
Used to correct sensor reading  
Sensor  
Calibration  
Admin Password  
level access only  
Rnet Sensor  
Temperature  
°
F
Displays SPT  
°
Rnet Offset  
RH  
X
X
-9.9 - 10.0  
%
Used to correct sensor reading  
Displays Space RH value  
RH Sensor Offset  
-15% - 15%  
0 %  
Used to correct sensor reading  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Off, Fan Only,Economize,  
Cooling, Heating, Cont Fan, Test,  
Start Delay, Dehumidify  
Operating Mode  
Displays unit operating mode  
Displays how the fan is configured  
to operate  
Fan Operating Mode  
Occupancy Status  
Auto/Continuous/Always On  
Unoccupied/Occupied  
Displays the current occupancy status  
Always Occupied/Local Schedule/  
BACnet Schedule/BAS Keypad/  
Occupied Contact/Holiday Schedule/  
Override Schedule/Pushbutton  
Override/Unoccupied None  
Displays the origin of the  
occupancy control  
Occupancy Control  
Outside Air  
Displays OAT (Viewable only if OAT  
is a network broadcast)  
°
°
F
F
Temperature  
SPT  
Displays SPT  
Normal/Above Limit/Below  
Limit/Sensor Failure  
SPT Status  
Displays the SPT status  
Displays the connection status  
of the Rnet sensor  
SPT Sensor Status  
Condensate Overflow  
Cooling Set Point  
Inactive/Connected  
Normal/Alarm  
Displays the status of the  
condensate overflow  
Displays the actual set point  
being used for cooling control  
°
°
F
F
Displays the actual set point  
being used for heating control  
Heating Set Point  
Unit  
Maintenance  
No Password  
required  
Displays the offset values from the Rnet  
user set point adjustment that is being  
applied to the configured set points  
°
Set Point Adjustment  
F
Auxiliary Heat Control  
Set Point  
Displays the calculated set point being  
used for auxiliary heating control  
°
°
F
F
H2O Economizer  
Control Set Point  
Displays the calculated set point being  
used for economizer control  
Calculated IAQ/  
Ventilation Damper  
position  
Displays the ventilation damper  
position calculated by the DCV control  
%
Active Compressor  
Stages  
Displays the actual number of  
compressor stages operating  
0/1/2  
°
SAT  
F
Displays SAT  
Used to reset the filter alarm timer after  
the filter has been cleaned or replaced  
Reset Filter Alarm  
X
X
No/Yes  
Displays the state of the condensate  
overflow switch contact  
Overflow Contact  
Closed/Open  
Closed/Open  
Displays the state of the external/  
remote occupancy input switch contact  
Occupancy Contact  
Provides capability to force the  
equipment to operate in an  
occupied or unoccupied mode  
Inactive/Occupied/  
Unoccupied  
BAS/Keypad Override  
OAT Input  
Inactive  
Displays if an OAT value is being  
received from the Network  
N/A / Network  
BACnet  
Keypad Configuration  
Password  
X
X
X
X
X
X
See TPI  
Mapping  
Changes password  
See TPI  
System Settings  
Network  
BACnet Time Master  
Clock Set  
See TPI  
Changes clock/time setting  
Override Schedules  
Pushbutton Override  
Inactive/Active Occupied  
Inactive/Active Occupied  
Inactive/Active Occupied/Active  
Unoccupied  
Keypad Override  
Occupancy  
Maintenance  
No Password  
required  
Used to display the active and  
inactive occupancy control inputs  
Schedules  
Occupancy Contact  
BAS on/off  
Inactive/Active Occupied  
Inactive/Active Occupied  
Inactive/Active Occupied  
Local Occupancy  
Schedules  
X
X
X
X
Disable/Enable  
Disable/Enable  
Disable/Enable  
Disable/Enable  
Enable  
Disable  
Disable  
Disable  
Local Holiday  
Schedules  
User/Admin  
Password level  
access  
Used to define which occupancy inputs  
are used to determine  
Schedule  
Configuration  
Local Override  
Schedules  
occupancy mode.  
BACnet Occupancy  
Schedules  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
Occupied Heating  
Occupied Cooling  
Unoccupied Heating  
Unoccupied Cooling  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Defines the Occupied  
Heating Set Point  
°
°
°
°
°
°
°
°
X
X
X
X
X
X
40 - 90  
55 - 99  
40 - 90  
55 - 99  
F
F
F
F
72  
76  
55  
90  
F
F
F
F
Defines the Occupied  
Cooling Set Point  
Defines the Unoccupied  
Heating Set Point  
Defines the Unoccupied  
Cooling Set Point  
Effective Heating  
Set Point  
Takes into effect bias (maximum  
allowable set point deviation)  
°
0 - 10  
0 - 10  
F
Effective Cooling  
Set Point  
Takes into effect bias (maximum  
allowable set point deviation)  
°
F
Uses historical data to calculate  
ramp up time so as to be at set point  
at occupied/unoccupied time  
Optimal Start  
Configuration  
Set Points  
Defines the control set point used  
during occupied periods (Viewable  
only if Humidity Sensor = Installed/  
Determines when to start  
User/Admin  
Password level  
access  
Occupied RH  
Set Point  
X
0 - 100%  
65%  
Dehumidification when occupied)  
Defines the control set point used  
during unoccupied periods  
(Viewable only if Humidity Sensor =  
Installed/Determines when to start  
Dehumidification when unoccupied)  
Unoccupied RH  
Set Point  
X
X
0 - 100%  
90%  
Defines the control set point used to  
start increasing ventilation during  
occupied periods (Viewable only if  
Ventilation DMP Type = DCV)  
DCV CTRL Start  
Set Point  
0 - 9999 ppm  
500 ppm  
Defines the control set point  
used to define where the ventilation  
will reach its maximum limit during  
DCV Max CTRL  
Set Point  
X
0 - 9999 ppm  
1050 ppm occupied periods (Viewable only if  
Ventilation DMP Type = DCV/Used  
to determine DCV ending control  
point)  
Defines the start time for an  
Start Time  
End Time  
Mon  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
00:00 - 23:59  
00:00 - 24:00  
No/Yes  
06:00  
occupied period  
Defines the ending time of an  
18:00  
occupied period  
Determines if this day is included  
Yes  
Configuration  
Schedule  
in this schedule  
Determines if this day is included  
Tue  
No/Yes  
Yes  
in this schedule  
User/Admin  
Password level  
access  
Determines if this day is included  
Wed  
No/Yes  
Yes  
in this schedule  
Determines if this day is included  
Thur  
No/Yes  
Yes  
in this schedule  
Determines if this day is included  
Weekly Schedule  
Fri  
No/Yes  
Yes  
in this schedule  
Determines if this day is included  
Sat  
No/Yes  
No  
in this schedule  
Determines if this day is included  
Sun  
No/Yes  
No  
in this schedule  
Defines the start month of this  
Start Month  
Start Day  
Start Time  
End Month  
End Day  
End Time  
0 - 12  
0
hoilday schedule  
Configuration  
Schedule  
Defines the start day of this holiday  
0 - 31  
0
schedule  
Determines the start time for this  
00:00 - 23:59  
0 - 12  
0:00  
User/Admin  
Password level  
access  
schedule  
Defines the month to end this  
0
hoilday schedule  
Defines the day to end this holiday  
0 - 31  
0
Exception  
Schedules 1 - 12  
schedule  
Determines the time to end this  
00:00 - 24:00  
0:00  
schedule  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Auto= Intermittant operation during both  
occupied and unoccupied periods/  
Continuous = Intermittant during unoccupied  
periods and continuous during occupied  
periods/Always on = fan operates  
continuously during both occupied and  
unoccupied periods  
Auto/Continuous/  
Always On  
Fan Mode  
X
Continuous  
Defines the delay time before the fan begins  
to operate after heating or cooling is started  
Fan On Delay  
Fan Off Delay  
X
X
0 - 30 sec  
10 sec  
45 sec  
Defines the amount of time the fan will  
continue to operate after heating or  
cooling is stopped  
0 - 180 sec  
Provides capability to manually  
disable heating operation  
Heating Enable  
Cooling Enable  
X
X
X
X
Disable/Enable  
Disable/Enable  
Enable  
Enable  
Provides capability to manually  
disable cooling operation  
Minimum SAT in  
Cooling  
Defines the minimum acceptable operating  
temperature for the Supply Air  
°
°
40 - 60  
F
50  
F
Configuration  
Maximum SAT in  
Heating  
Defines the maximum acceptable operating  
temperature for the Supply Air  
°
°
80 - 140  
F
110  
F
Admin Password  
level access only  
Normally set to 100% if 2 position damper  
type or set to minimum ventilation position if  
damper type = DCV  
Damper Ventilation  
Position  
X
X
0 - 100%  
100%  
Unit  
Configuration  
DCV Maximum Vent  
Position  
Usually set at 100% - Used to limit maximum  
damper opening in DCV mode  
0 - 100%  
100%  
Filter Alarm Timer  
X
X
0 - 9999 hrs  
0 hrs  
Disables Filter Alarm if set to 0  
Pushbutton Override  
Disable/Enable  
Enable  
Enables Override Feature on Rnet sensor  
SPT Sensor Set Point  
Adjustment  
Enables Set Point adjustment capability  
on Rnet Sensor  
X
Disable/Enable  
Enable  
Cooling is locked out when OAT is less than  
configured value and OAT is actively being  
broadcast  
Lockout Cooling if  
OAT <  
°
°
X
-65 - 80  
35 - 150  
F
F
-65  
F
F
Heating is locked out when OAT is greater  
than configured value and OAT is actively  
being broadcast  
Lockout Heating if  
OAT >  
°
°
X
150  
Power Fail Restart  
Delay  
X
X
X
0 - 600 sec  
60 sec  
Enable  
Delay before equipment starts  
Occupancy Schedules  
Disable/Enable  
Enables unit occupied  
Used to enforce minimum  
set point separation  
°
°
Set Point Separation  
2 - 9  
F
4
F
Used to enable test mode. Will automatically  
reset to disable after 1 hour  
Test Mode  
Fan Test  
X
X
Disable/Enable  
Disable/Enable  
Disable  
Disable  
Used to test all fan speeds. Sequences fan  
from low to high and operates each speed for  
1 minute. Resets to disable on completion  
Off/Low Speed/Medium  
Speed/High Speed/On  
Fan Speed  
Displays current fan operation  
Used to test compressor cooling and heating  
operation. Sequences cooling stage 1, then  
stage 2, then heating stage 2 and reduces  
capacity to stage 1. Operates for 1 minute per  
step. Resets to disable on completion.  
Compressor Test  
X
X
Disable/Enable  
Disable  
Disable  
Used to test dehumification mode -  
Operates for 2 minutes. Resets to  
disable on completion.  
Configuration  
Service  
Dehumidification Test  
Testing Compressor  
Disable/Enable  
Inactive/Heating/Cooling/  
Dehumidify/TimeGard  
Wait  
Admin Password  
level access only  
Displays compressor test mode  
Used to test auxiliary heat.  
Sequences fan on and enables  
heating coil for 1 minute. Resets to  
disable on completion  
Aux Heating Test  
X
X
Disable/Enable  
Disable/Enable  
Disable  
Disable  
Test  
Used to test entering/return air water loop  
economizer coil operation. Sequences fan on  
and opens economizer coil water valve for 1  
minute. Resets to disable on completion  
H2O Economizer Test  
Preposition OA  
Damper  
Used to preposition OA damper  
actuator to set proper preload  
X
X
Disable/Enable  
Disable/Enable  
Disable  
Disable  
Open Vent  
Damper 100%  
Used to test OA damper operation  
Displays SAT  
°
°
SAT  
F
F
Displays Leaving Condenser  
Water Temperature  
LCWT  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Used to set number of  
fan motor speeds  
# of Fan Speeds  
X
1,2,3  
3
When set to Fan On, G output is  
energized when ever any fan speed  
is active (required for ECM and Fan  
control board). When set to Fan  
Low, output is only energized for  
Low Speed  
G Output Type  
X
Fan On/Fan Low  
Fan On  
Defines the number of  
stages of compression  
Compressor Stages  
Reversing Valve Type  
X
X
X
X
X
X
X
One Stage/Two Stages  
One Stage  
O type  
None  
Determines reversing valve  
signal output type  
O type output/B type output  
Leaving Air Auxiliary  
Heat Type  
None/2-Position HW/1 Stage  
Electric/Modulating HW  
Determines Auxiliary  
Reheat Coil Type  
Entering Air Water  
Economizer Type  
Determines Entering Air  
Economizer Coil Type  
None/2-Position/Modulating  
Normally Closed/Normally Open  
Normally Closed/Normally Open  
None/2-Position/DCV  
None  
2-Position Water  
Valve Type  
Normally  
Closed  
Determines type of 2-position  
water valve used  
Modulating Water  
Valve Type  
Normally  
Closed  
Determines type of modulating  
water valve used  
Ventilation Damper  
Type  
Determines Type of ventilation  
damper control to be used  
None  
0-10 volt  
None  
Used to determine ventilation  
damper output signal range  
(closed - open)  
Damper Actuator Type  
Humidity Sensor  
X
X
X
(0-10 volt)/(2-10 volt)  
None/Installed  
Set to Installed if Humidity  
sensor is present  
Configuration  
Admin Password  
level access only  
Set to Installed if factory-installed  
dehumidification reheat coil  
is present  
Factory Dehumidifica-  
tion Reheat Coil  
None/Installed  
None  
Service  
Configuration  
Occupancy  
Input Logic  
Occupied  
Used to determine external occu-  
X
X
X
Occupied Open/Occupied Closed  
5 - 600 seconds  
CLOSED pancy switch contact occupied state  
Condensate Switch  
Alarm Delay  
Delay before equipment alarms on  
10 sec  
high condensate level  
Condensate Switch  
Alarm State  
Alarm  
CLOSED  
Determine Alarm state of  
condensate switch input  
Alarm OPEN/Alarm CLOSED  
Minimum Condenser  
Water Temperature in  
Heating  
Determines the minimum  
acceptable water loop temperature  
to start heating  
°
°
°
°
°
X
X
X
X
25 - 60  
F
60  
90  
60  
95  
F
F
F
F
Maximum Condenser  
Water Temperature in  
Heating  
Determines the maximum  
acceptable water loop temperature  
to start heating  
°
°
65 - 100  
F
Minimum Condenser  
Water Temperature in  
Cooling  
Determines the minimum  
acceptable water loop temperature  
to start cooling  
°
30 - 60  
F
Maximum Condenser  
Water Temperature in  
Cooling  
Determines the maximum  
acceptable water loop temperature  
to start cooling  
85 - 120  
F
IAQ sensor  
Minimum output current (mA)  
for IAQ sensor  
X
X
X
X
0 - 5 ma  
4 ma  
20 ma  
minimum input  
IAQ sensor  
maximum input  
Maximum output current (mA) for  
IAQ sensor  
5 - 20 ma  
IAQ sensor  
minimum output  
Corresponding value in ppm for  
minimum output current  
0 - 9999 ppm  
0 - 9999 ppm  
0 ppm  
IAQ sensor  
maximum output  
Corresponding value in ppm for  
maximum output current  
2000 ppm  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Defines the hysteresis applied above  
the cooling and below the heating set  
points before an alarm condition will  
occur  
SPT Occupied Alarm  
Hysteresis  
°
°
X
2 - 20  
F
5
F
Used to calculate the delay time before  
an alarm is generated after the alarm  
condition occurs  
SPT Alarm Delay  
X
0 - 30 min per degree  
10 min  
SPT Unoccupied Low  
Alarm Temperature  
Defines the fixed unoccupied  
ow SPT alarm limit  
°
°
°
°
X
X
X
X
35 - 90  
F
45  
95  
45  
F
F
F
SPT Unoccupied High  
Alarm Temperature  
Defines the fixed unoccupied  
high SPT alarm limit  
°
45 - 100  
F
SAT Low SAT  
Alarm Limit  
Defines the fixed minimum  
SAT alarm limit  
°
15 - 90  
F
SAT High SAT  
Alarm Limit  
Defines the fixed maximum  
SAT alarm limit  
°
°
90 - 175  
F
120  
F
Defines the delay time before an alarm  
is generated after the alarm condition  
occurs  
Condensate Overflow  
Alarm Delay  
X
X
X
5 - 600 sec  
45% - 100%  
10 sec  
100%  
5 min  
Space Humidity Occupied  
High Alarm Limit  
Defines the fixed occupied  
high space RH alarm limit  
Used to calculate the delay time before  
an alarm is generated after the alarm  
condition occurs  
Space Humidity Alarm  
Delay  
0 - 30 min per % RH  
Configuration  
Space Humidity Unoccu- Admin Password  
Defines the fixed unnoccupied  
high space RH alarm limit  
X
X
45% - 100%  
0 - 9999 ppm  
100%  
pied High Alarm Limit  
level access only  
Alarm  
Configuration  
IAQ/Ventilation Occupied  
High Alarm Limit  
Defines the fixed occupied high  
space IAQ/Ventilation alarm limit  
1100 ppm  
Used to calculate the delay time before  
0.25 min an alarm is generated after the alarm  
condition occurs  
IAQ/Ventilation  
Alarm Delay  
X
0.1 - 1.0 min per ppm  
Determines if the SPT alarm is  
Ignore  
Rnet Sensor SPT Alarm  
Rnet Sensor SAT Alarm  
X
X
Ignore/Display  
Ignore/Display  
displayed on the local Rnet sensor  
Determines if the SAT alarm is  
Ignore  
displayed on the local Rnet sensor  
Determines if the Compressor Lockout  
Rnet Sensor Compressor  
Lockout Alarm  
X
X
Ignore/Display  
Ignore/Display  
Display  
Display  
alarm is displayed on the local Rnet  
sensor  
Determines if the Condenser Water  
Temperature alarm is displayed on the  
local Rnet sensor  
Rnet Sensor Condenser  
Water Temperature Alarm  
Determines if the Condensate  
Overflow alarm is displayed on the  
local Rnet sensor  
Rnet Sensor Condensate  
Overflow Alarm  
X
X
X
Ignore/Display  
Ignore/Display  
Ignore/Display  
Display  
Display  
Ignore  
Rnet Sensor Dirty  
Filter Alarm  
Determines if the Dirty Filter alarm is  
displayed on the local Rnet sensor  
Determines if the High Space  
RH alarm is displayed on the  
local Rnet sensor  
Rnet Sensor Space  
High Humidity Alarm  
Loop Control Network  
Number  
See TPI  
See TPI  
See TPI  
Configuration  
Linkage  
Loop Control Network  
Address  
Number of Linked Heat  
Pumps  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 2009 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53500052-01  
Printed in U.S.A.  
Form 50PEC-2SI  
Pg 58  
7-09  
Replaces: 50PEC-1SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
50PEC UNIT  
START-UP CHECKLIST  
CUSTOMER:___________________________  
MODEL NO.:___________________________  
JOB NAME: _______________________________________  
SERIAL NO.:____________________  
DATE:_________  
I. PRE-START-UP  
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)  
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS  
TIGHT? (Y/N)  
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER?  
(Y/N)  
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)  
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)  
IS AN AIR FILTER INSTALLED? (Y/N)  
II. START-UP  
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)  
UNIT VOLTAGE — COOLING OPERATION  
PHASE AB VOLTS  
PHASE AB AMPS  
CONTROL VOLTAGE  
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N)  
.
IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.  
TEMPERATURES  
FILL IN THE ANALYSIS CHART ATTACHED.  
COAXIAL HEAT COOLING CYCLE:  
EXCHANGER  
WATER IN  
F WATER OUT  
F WATER OUT  
F AIR OUT  
F
F
F
F
ft wg  
ft wg  
gpm  
gpm  
HEATING CYCLE:  
WATER IN  
AIR COIL  
COOLING CYCLE:  
AIR IN  
HEATING CYCLE:  
AIR IN  
F AIR OUT  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING CYCLE ANALYSIS  
ft wg  
F
SST  
(SATURATED  
SUCTION  
TEMPERATURE)  
AIR  
COIL  
SUCTION  
F
F
COMPRESSOR  
DISCHARGE  
EXPANSION  
COAX  
VALVE  
F
a50-8453  
LIQUID LINE  
F
F
ft wg  
WATER IN  
ft wg  
WATER OUT  
LOOK UP PRESSURE DROP IN TABLE 12  
TO DETERMINE FLOW RATE  
COOLING CYCLE ANALYSIS  
ft wg  
F
SST  
(SATURATED  
SUCTION  
TEMPERATURE)  
AIR  
COIL  
SUCTION  
F
F
COMPRESSOR  
DISCHARGE  
EXPANSION  
COAX  
VALVE  
F
a50-8454  
LIQUID LINE  
F
F
ft wg  
WATER IN  
ft wg  
WATER OUT  
LOOK UP PRESSURE DROP IN TABLE 12  
TO DETERMINE FLOW RATE  
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =  
FLOW RATE (gpm) x TEMP. DIFF. (DEG. F) x  
FLUID FACTOR* =  
(Btu/hr)  
SUPERHEAT = SUCTION TEMPERATURE – SATURATED SUCTION TEMPERATURE  
(DEG F)  
=
SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE  
(DEG F)  
=
*Use 500 for water, 485 for antifreeze.  
97B0035N06  
Copyright 2009 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53500052-01 Printed in U.S.A. Form 50PEC-2SI CL-2 7-09 Replaces: 50PEC-1SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bogen Car Speaker VRS1 User Manual
Boston Acoustics Stereo System LCAi220 User Manual
Bravetti Fryer K4320H User Manual
Briggs Stratton Automobile Parts 09P700 User Manual
Briggs Stratton Lawn Mower 5900201 User Manual
Brother All in One Printer MFC J5910DW User Manual
Cadco Convection Oven XR130 User Manual
Campbell Hausfeld Nail Gun IN715703AV User Manual
Canon Printer Accessories GP200 User Manual
CH Tech Network Card i4000 User Manual