Carrier Furnace 58PAV User Manual

58PAV, 58RAV  
Induced-Combustion Furnaces  
Service and Maintenance Instructions  
For Sizes 045-155, Series 131  
NOTE: Read the entire instruction manual before performing any  
service or maintenance.  
This symbol indicates a change since the last issue.  
Index  
Page  
SAFETY CONSIDERATIONS..................................................1-2  
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS  
PROCEDURES.........................................................................2  
CARE AND MAINTENANCE................................................2-11  
Air Filter Arrangement..........................................................2-3  
Blower Motor and Wheel......................................................3-4  
Cleaning Heat Exchanger......................................................4-5  
Electrical Controls and Wiring.................................................6  
Troubleshooting...................................................................6-11  
Unit Wiring Diagram................................................................8  
Service Label ............................................................................9  
Troubleshooting Guide......................................................10-11  
A94087  
Fig. 1—Model 58RAV Horizontal  
®
SAFETY CONSIDERATIONS  
Installing and servicing heating equipment can be hazardous due to  
gas and electrical components. Only trained and qualified person-  
nel should install, repair, or service heating equipment.  
Untrained personnel can perform basic maintenance functions  
such as cleaning and replacing air filters. All other operations must  
be performed by trained service personnel. When working on  
heating equipment, observe precautions in the literature, on tags,  
and on labels attached to or shipped with the unit and other safety  
precautions that may apply.  
ama  
CANADIAN GAS ASSOCIATION  
Follow all safety codes. In the United States, follow all safety  
codes including the National Fuel Gas Code (NFGC) NFPA No.  
54-1992/ANSI Z223.1-1992. In Canada, refer to the current  
edition of the National Standard of Canada CAN/CGA-B149.1-  
and .2-M91 Natural Gas and Propane Installation Codes (NSC-  
NGPIC). Wear safety glasses and work gloves. Have fire extin-  
guisher available during start-up and adjustment procedures and  
service calls.  
A PPROVED  
R
Recognize safety information. This is the safety-alert symbol  
When you see this symbol on the furnace and in instructions or  
manuals, be alert to the potential for personal injury.  
.
A94086  
Fig. 2—Model 58RAV  
Downflow  
Understand the signal words DANGER, WARNING, and CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies a hazard which  
could result in personal injury or death. CAUTION is used to  
identify unsafe practices which would result in minor personal  
injury or product and property damage. NOTE is used to highlight  
suggestions which will result in enhanced installation, reliability,  
or operation.  
A94085  
Fig. 3—Model 58PAV  
Upflow  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 6a 8a  
1
4
PC 101  
Catalog No. 535-835  
Printed in U.S.A.  
Form 58P,R-9SM  
Pg 1  
9-94  
Replaces: 58P,R-8SM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
d. Furnaces are equipped with permanent, washable filters.  
Clean filters with tap water. Spray water through filter in  
opposite direction of airflow.  
e. Rinse and let dry. Oiling or coating of filters is not  
recommended or required.  
f. Reinstall filters.  
g. Replace blower access door.  
h. Restore electrical power to furnace.  
AIRFLOW  
2. Upflow  
Each furnace requires 1 or 2 filters which are installed in the  
blower compartment. (See Fig. 6.) To remove filters for  
cleaning or replacement, proceed as follows:  
A94307  
a. Disconnect electrical power before removing access doors.  
b. Remove blower and control access doors.  
Fig. 4—Horizontal Filter Arrangement  
c. Release filter retainer from clip at front of furnace casing.  
(See Fig. 6.) For side return, clips may be used on either or  
both sides of the furnace.  
AIRFLOW  
INSTALLATION  
POSITION  
d. Slide filter(s) out.  
OF FILTERS  
e. Furnaces are equipped with permanent, washable filters.  
Clean filters with tap water. Spray water through filter in  
opposite direction of airflow.  
RETURN-AIR  
PLENUM  
f. Rinse and let dry. Oiling or coating of filter is not  
recommended or required.  
g. Reinstall filter(s).  
h. Replace blower and control access doors.  
i. Restore electrical power to furnace.  
BLOWER MOTOR AND WHEEL  
For long life, economy, and high efficiency, clean accumulated dirt  
and grease from the blower wheel and motor annually.  
The following steps should be performed by a qualified service  
technician.  
Some motors have prelubricated sealed bearings and require no  
lubrication. These motors can be identified by the absence of oil  
ports on each end of the motor. For those motors with oil ports,  
lubricate motor every 5 years if motor is used on intermittent  
operation (thermostat FAN switch in AUTO position), or every 2  
years if motor is in continuous operation (thermostat FAN switch  
in ON position).  
ACCESS DOOR  
NOTE: Remember to disconnect the electrical supply before  
removing access doors.  
A88486  
Clean and lubricate as follows:  
Fig. 5—Downflow Filter Arrangement  
1. Remove  
2
screws  
from  
blower  
access  
door  
(downflow/horizontal furnace only) and remove blower access  
door.  
Never operate unit without a filter or with filter access door  
removed. A failure to follow this warning could result in fire,  
personal injury, or death.  
2. Remove vent pipe enclosure (downflow/horizontal furnace  
only) and disconnect short piece of vent pipe from relief box.  
3. Disconnect wires from auxiliary limit on blower housing  
(downflow/horizontal furnace only).  
1. Downflow/Horizontal  
4. Remove control.  
Each furnace requires 2 filters which are installed in the  
return-air duct. (See Fig. 4 and 5.) To remove filters for  
cleaning or replacement, proceed as follows:  
5. Disconnect electrical leads from control. (See Fig. 6 or 7.)  
Note location of wires for reassembly.  
a. Disconnect electrical power before removing blower access  
door.  
6. Remove screws holding blower assembly to blower deck and  
slide blower assembly out of furnace.  
b. Remove 2 screws from front of door and remove blower  
access door.  
7. Loosen screw in strap holding motor capacitor to blower  
housing and slide capacitor out from under strap.  
c. Reach up behind top plate, tilt filters toward center of  
return-air plenum, remove filters, and clean as needed.  
Replace if torn.  
8. Mark blower wheel, motor, and motor support in relation to  
blower housing before disassembly to ensure proper reassem-  
bly.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT PIPE  
DRAFT  
ENCLOSURE  
MOUNTING  
SCREWS  
SAFEGUARD  
SWITCH  
AUXILIARY  
LIMIT  
SWITCH  
RELIEF  
BOX  
(WHEN USED)  
FLUE  
COLLECTOR  
BOX  
CONTROL  
BOARD  
MOUNTING  
SCREWS  
CONTROL  
BOARD  
DRAFT  
SAFEGUARD  
SWITCH  
MANUAL  
RESET LIMIT  
SWITCH  
RELIEF  
BOX  
FILTER  
RETAINER  
MANUAL  
RESET LIMIT  
SWITCHES  
WASHABLE  
FILTER  
A92063  
A92064  
Fig. 6—Model 58PAV Upflow  
9. Loosen setscrew holding blower wheel on motor shaft.  
Fig. 7—Model 58RAV Downflow  
18. Reconnect wires to auxiliary limit switch on blower housing  
(downflow/horizontal furnace only).  
10. Remove bolts holding motor mount to blower housing and  
slide motor and mount out of housing. Disconnect ground wire  
attached to blower housing before removing motor.  
19. Reinstall vent pipe and enclosure (downflow/horizontal fur-  
nace only).  
11. Lubricate motor (when oil ports are provided).  
20. Turn on electrical power and check for proper rotation and  
speed changes between heating and cooling.  
a. Remove dust caps or plugs from oil ports located at each  
end of motor.  
21. Replace blower access door. Secure with  
(downflow/horizontal furnace only).  
2
screws  
b. Use a good grade of SAE 20 nondetergent motor oil and  
put 1 teaspoon, 5 cc, 3/16 oz, or 16 to 25 drops in each oil  
port. Do not over-oil.  
CLEANING HEAT EXCHANGER  
The following steps should be performed by a qualified service  
technician.  
c. Allow time for total quantity of oil to be absorbed by each  
bearing.  
NOTE: Deposits of soot and carbon indicate the existence of a  
problem which needs to be corrected. Take action to correct the  
problem.  
d. Wipe excess oil from motor housing.  
e. Replace dust caps or plugs on oil ports.  
12. Remove blower wheel from housing.  
a. Mark cutoff location to ensure proper reassembly.  
If it becomes necessary to clean the heat exchanger because of  
carbon deposits, soot, etc., proceed as follows:  
b. Remove screws holding cutoff plate and remove cutoff  
plate from housing.  
1. Turn off gas and electrical power to furnace.  
2. Remove  
2
screws from front of blower access door  
c. Lift blower wheel from housing through opening.  
(downflow/horizontal furnace only) and remove control and  
blower access doors.  
13. Clean blower wheel and motor using a vacuum cleaner with  
soft brush attachment. Do not remove or disturb balance  
weights (clips) on blower wheel blades. The blower wheel  
should not be dropped or bent as balance will be affected.  
3. Remove vent pipe enclosure (downflow/horizontal furnace  
only) and disconnect vent pipe from relief box.  
4. Remove 2 screws that secure relief box. (See Fig. 6 or 7.)  
5. Disconnect wires to the following components.  
a. Draft safeguard switch  
14. Reinstall blower wheel by reversing items 12 a through c. Be  
sure wheel is positioned for proper rotation.  
15. Reassemble motor and blower by reversing items 5 through  
10. If motor has ground wire, be sure it is connected as before.  
b. Inducer motor  
c. Pressure switch  
d. Limit overtemperature switch(es)  
e. Gas valve  
Be sure the motor is properly positioned in the blower  
housing. The motor oil ports must be at a minimum of 45°  
above the horizontal centerline of the motor after the blower  
assembly has been reinstalled in the furnace.  
f. Hot surface ignitor  
g. Flame-sensing electrode  
h. Two wiring connectors leading to control  
16. Reinstall blower assembly in furnace.  
6. Remove 8 screws that secure flue collector box to center  
panel. Be careful not to damage sealant.  
17. Reinstall control. Connect blower electrical leads to control.  
Please note that the common wire connection is 3/16 in. and  
all other wire connections are 1/4 in. for assembly. DO NOT  
FORCE.  
7. Remove complete inducer assembly from furnace, exposing  
flue openings.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
8. Clean cells using field-provided small wire brush, steel spring  
cable, reversible electric drill, and vacuum cleaner.  
13  
32"  
32"  
BURNER  
a. Assemble wire brush and steel spring cable.  
(1.) Use 48 in. of 1/4-in. diameter high-grade steel spring  
cable (commonly known as drain clean-out or Roto-  
Rooter cable).  
CELL  
PANEL  
(2.) Use 1/4-in. diameter wire brush (commonly known as  
25-caliber rifle cleaning brush).  
HOT  
SURFACE  
IGNITOR  
ASSEMBLY  
NOTE: The materials needed in items (1.) and (2.) can usually be  
purchased at local hardware stores.  
(3.) Insert twisted wire end of brush into end of steel spring  
cable, and crimp tight with crimping tool or strike with  
ball-peen hammer. TIGHTNESS is very important.  
(4.) Remove metal screw fitting from wire brush to allow  
insertion into cable.  
b. Clean each heat exchanger cell.  
C
IGNITOR  
BURNER  
L
(1.) Attach variable-speed, reversible drill to end of steel  
spring cable (end opposite brush).  
7
8"  
C
L
(2.) Insert brush end of cable into upper opening of cell  
and slowly rotate with drill. DO NOT force cable.  
Gradually insert at least 36 in. of cable into 2 upper  
passes of cell. (See Fig. 8.)  
IGNITOR  
ASSEMBLY  
A93347  
Fig. 9—Position of Ignitor to Burner  
9. After cleaning flue openings, check sealant on flue collector to  
ensure that it has not been damaged. If new sealant is needed,  
contact your dealer or distributor.  
10. Clean and replace flue collector assembly, making sure all 8  
screws are secure.  
11. Reinstall relief box.  
12. Reconnect wires to the following components.  
a. Draft safeguard switch  
b. Inducer motor  
A91252  
c. Pressure switch  
Fig. 8—Cleaning Heat Exchanger Cell  
d. Limit overtemperature switch(es)  
e. Gas valve  
(3.) Work cable in and out of cell 3 or 4 times to obtain  
sufficient cleaning. DO NOT pull cable with great  
force. Reverse drill and gradually work cable out.  
f. Hot surface ignitor  
g. Flame-sensing electrode  
h. Two wiring connectors leading to control  
(4.) Remove burner assembly and cell inlet plates.  
13. Reconnect vent pipe to relief box. Replace vent pipe enclosure  
(downflow/horizontal furnace only).  
Be very careful when removing the burner assembly to avoid  
breaking the ignitor. See Fig. 9 for the correct ignitor location.  
14. Replace blower access door only.  
15. Turn on electrical power and gas.  
(5.) Replace screws in center panel and cells before  
cleaning.  
16. Set thermostat and check furnace for proper operation.  
(6.) Insert brush end of cable in lower opening of cell, and  
proceed to clean 2 lower passes of cell in same manner  
as 2 upper passes.  
Never use a match or other open flame to check for gas leaks.  
Use a soap-and-water solution. A failure to follow this  
warning could result in fire, personal injury, or death.  
(7.) Repeat foregoing procedures until each cell in furnace  
has been cleaned.  
(8.) Remove residue from each cell using vacuum cleaner.  
17. Check for gas leaks.  
(9.) Clean burner assembly using vacuum cleaner with soft  
brush attachment.  
18. Replace control access door on upflow furnace.  
(10.) Reinstall cell inlet plates and burner assembly. Care  
must be exercised to center the burners in the cell  
openings.  
19. On downflow/horizontal furnaces, remove blower access  
door, replace control access door first, then replace blower  
access door and secure with 2 screws in front of door.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL CONTROLS AND WIRING  
a. LED flashes a fault code 4 times. Record this fault code for  
further troubleshooting.  
b. Inducer motor operates for 10 sec, then turns off.  
There may be more than 1 electrical supply to the unit. Check  
accessories and cooling unit for additional electrical supplies.  
c. Hot surface ignitor is energized for 15 sec, then de-  
energized.  
d. Main blower operates at cooling speed for 10 sec, then  
turns off.  
The electrical ground and polarity for 115-v wiring must be  
maintained properly. Refer to Fig. 10 for field wiring information  
and to Fig. 12 for unit wiring information.  
e. Main blower operates at heating speed for 10 sec, then  
turns off.  
NOTE: If the polarity is not correct, the STATUS LED on the  
control center will flash rapidly and prevent the furnace from  
operating. The control system also requires an earth ground for  
proper operation of the control board and flame-sensing electrode.  
Items a through e above will assist in furnace troubleshooting  
since all components are functionally operated except the gas  
valve. This procedure is also referred to as "Component Test."  
The 24-v circuit contains an automotive-type, 3-amp fuse located  
on the control board. (See Fig. 11.) Any direct shorts of the 24-v  
wiring during installation, service, or maintenance will cause this  
fuse to blow. If fuse replacement is required, use ONLY a fuse of  
identical size.  
3. Operate furnace through 1 heat cycle to test for proper  
operation and check LED status.  
4. If furnace is operating properly and LED indicates proper  
operation, replace control access door.  
5. Component Test can also be initiated by performing the  
following:  
With power to the unit disconnected, check all electrical connec-  
tions for tightness. Tighten all screws on electrical connections. If  
any smoky or burned connections are found, disassemble the  
connection, clean all parts, strip wire, and reassemble properly and  
securely.  
a. Remove control access door.  
b. Remove blower access door.  
c. Manually close blower access door switch.  
Reconnect electrical power to the unit and observe unit through 1  
complete operating cycle. Electrical controls are difficult to check  
without proper instrumentation; if there are any discrepancies in  
the operating cycle, contact your dealer and request service.  
Blower access door switch opens 115-v power to control  
center. No component operation can occur. Caution must be  
taken when manually closing this switch for service purposes.  
Failure to follow this warning could result in personal injury  
or death.  
For an explanation of fault codes, refer to service label located on  
blower access door or Fig. 13, and the troubleshooting guide.  
The control center stores 1 fault code (the last fault to occur) for a  
period of 48 hrs or until the 115- or 24-v power is interrupted.  
d. BRIEFLY short (jumper) TEST, 1/4-in. quick-connect  
terminal on control center (adjacent to LED diagnostic  
light) and Com terminal on thermostat connection block.  
(See Fig. 11.)  
NOTE: Removing blower access door will open blower access  
door switch and terminate 115-v power to control center, and fault  
code will be erased. Look into blower access door sight glass for  
current LED status.  
NOTE: If TEST to Com terminals are jumpered longer than 2 sec,  
LED will flash rapidly, and retrieval request will be ignored.  
1. To retrieve fault code, proceed with the following:  
NOTE: NO thermostat signal may be present at control center,  
and all blower time delay off periods must be completed.  
e. Component Test will function as described in item 2 above.  
f. Check LED status.  
a. Leave 115-v power to furnace turned on.  
g. If LED status indicates proper operation, release blower  
access door switch, replace blower access door, and replace  
control access door.  
b. Look into blower access door sight glass for current LED  
status.  
NOTE: Leave blower access panel installed to maintain power to  
control center to view current LED status.  
TROUBLESHOOTING  
Refer to the service label. (See Fig. 13.) Pages 10 and 11 contain  
a troubleshooting guide. This guide can be a useful tool in isolating  
furnace operation problems. Beginning with the word "Start,"  
answer each question and follow the appropriate arrow to the next  
item.  
c. Remove control access door.  
d. BRIEFLY remove either wire from the main limit switch  
until LED goes out, then reconnect it.  
NOTE: If wire to main limit is disconnected longer than 4 sec,  
main blower starts, and retrieval request is ignored.  
The guide will help to identify the problem or failed component.  
After replacing any component, verify correct operation sequence.  
2. When above items have been completed, the following will  
occur:  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD 24-VOLT WIRING  
FIELD 115-, 208/230-, 460-VOLT WIRING  
FACTORY 24-VOLT WIRING  
FACTORY 115-VOLT WIRING  
THERMOSTAT  
TERMINALS  
W
R
G
Y
FOUR  
WIRE  
FIELD-SUPPLIED  
FUSED DISCONNECT  
TWO-WIRE  
HEATING-  
ONLY  
208/230- OR  
460-VOLT  
THREE  
PHASE  
W
R
BLK  
BLK  
WHT  
WHT  
208/230-  
VOLT  
SINGLE  
PHASE  
GND  
GND  
G
AUXILIARY  
J-BOX  
115-VOLT FIELD-  
SUPPLIED  
FUSED  
DISCONNECT  
C
Y
GND  
CONTROL  
CONDENSING  
UNIT  
BOX  
TWO  
24-VOLT  
NOTE: If any of the original wire,  
as supplied, must be replaced, use  
same type or equivalent wire.  
WIRE  
TERMINAL  
BLOCK  
NOTE: Connect Y-terminal as  
shown for proper  
FURNACE  
operation.  
A78461  
Fig. 10—Heating and Cooling Application Wiring Diagram  
BLOWER OFF DELAY  
ADJUSTMENT SWITCH  
24V THERMOSTAT  
TERMINALS  
G
R
Y
W
Com  
24V  
TEST/TWIN  
HUMIDIFIER TERMINAL  
(24-VAC 0.5 AMP MAX)  
HUM  
LED OPERATION &  
DIAGNOSTIC LIGHT  
HARNESS CONNECTOR  
SEC-1  
24V TRANSFORMER SEC-2  
SPARE 1  
3-AMP FUSE  
COOL  
HEAT  
BLOWER SPEED  
SELECTION TERMINALS  
SPARE 2  
EAC 1 (BLACK)  
EAC-ELECTRONIC AIR CLEANER  
TERMINALS (115-VAC 1 AMP MAX)  
115-VAC (L1)  
EAC 2 (WHITE)  
POWER  
SUPPLY  
115-VAC (L2) NEUTRAL  
CONNECTION  
HOT SURFACE  
IGNITOR  
CONNECTOR  
INDUCER MOTOR  
CONNECTOR  
A93052  
Fig. 11—Control Board  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
N A R T  
P M A 5 . 1  
T H W  
T H W  
K L B  
K L B  
K L B  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE LABEL  
SERVICE  
LED CODE  
STATUS  
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.  
CONTINUOUS ON - Control has 24V power.  
RAPID FLASHING - Line voltage (115V) polarity reversed. If twinned, 24V power to  
one furnace may be out of phase with 24V power to other furnace.  
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST  
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT  
BY THE NUMBER OF LONG FLASHES.  
11  
12  
13  
NO PREVIOUS CODE - Stored status codes are erased when power (115V or 24V) to  
control is interrupted or 48 hours after each fault is cleared.  
BLOWER ON AFTER POWER UP (115V OR 24V) - Blower runs for 90 seconds, if unit  
is powered up during a call for heat (R-W closed).  
LIMIT OR FLAME ROLLOUT SWITCH LOCKOUT - Auto reset after three hours. Flame  
rollout switch requires manual reset. Refer to #33.  
14  
21  
IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.  
GAS HEATING LOCKOUT - Control will NOT auto reset.  
Check for: - Stuck gas valve relay on control or miswire to gas valve circuit.  
ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is  
de-energized. Inducer will run until fault is cleared.  
22  
Check for: - Stuck-open gas valve or leaky gas valve.  
23  
24  
31  
PRESSURE SWITCH DID NOT OPEN Check for:  
- Obstructed pressure tubing.  
- Defective pressure switch (stuck closed).  
SECONDARY VOLTAGE FUSE IS OPEN  
Check for: - Short circuit in secondary voltage (24V) wiring.  
PRESSURE, DRAFT SAFEGUARD, OR AUXILIARY LIMIT (when used) SWITCH DID  
NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for  
15 minutes before retry. Check for:  
- Proper vent sizing and condensate pitch. - Inadequate combustion air supply.  
- Vent restriction or high winds.  
- Low inducer voltage.  
- Defective inducer motor or start capacitor.  
- Defective pressure switch or connections. If it opens after trial for ignition  
period, blower will come on for 90 second recycle delay.  
- Disconnected or obstructed pressure tubing.  
LIMIT OR FLAME ROLLOUT SWITCH IS OPEN - If open longer than three minutes, code  
changes to #13. Check for:  
33  
34  
- Defective blower motor or start capacitor. - Dirty filter or restricted duct system.  
- Loose blower wheel.  
- Defective switch or connections.  
- Inadequate combustion air supply (flame rollout switch only).  
- Open flame rollout switch, manual reset.  
IGNITION PROVING FAILURE - Control will try three more times before a lockout #14  
occurs. If flame signal lost after trial for ignition period, blower will come on for 90 second  
recycle delay.  
Check for: - Oxide buildup on flame sensor (clean with fine sandpaper).  
- Proper flame sense microamps (.5 microamps D.C. minimum).  
- Gas valve turned off.  
- Manual shut-off valve.  
- Green wire MUST be connected to furnace sheet metal.  
- Inadequate flame carryover or rough ignition.  
- Low inlet gas pressure.  
COMPONENT TEST  
To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R"  
thermostat lead. Briefly short the TEST terminal to the "C" terminal. Status LED will flash code  
and then turn on the inducer motor, hot surface igniter, blower motor-heat speed, and blower  
motor-cool speed for 10-15 seconds each.  
BLOWER OFF  
DELAY SELECT  
HUM  
C
W
Y
R
G
320615-102 REV. A  
A93297  
Fig. 13—Service Label  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 1994 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231  
58pr9sm  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 6a 8a  
1
4
PC 101  
Catalog No. 535-835  
Printed in U.S.A.  
Form 58P,R-9SM  
Pg 12  
9-94  
Replaces: 58P,R-8SM  
Download from Www.Somanuals.com. All Manuals Search And Download.  

BenQ Projector MP512 ST User Manual
Blanco Dishwasher BID11 User Manual
Bowers Wilkins Speaker DM14 User Manual
Bradley Smoker Plumbing Product E19 120A User Manual
Cabletron Systems Switch ZX 250 User Manual
Camco Stereo Amplifier P Series User Manual
Canon Camera Accessories EOS 350D User Manual
Canon Camera Lens 5179B002 User Manual
Casio Electronic Keyboard SK 8 User Manual
CFM Ventilation Hood GEF10 User Manual