Carrier Fan 30GK User Manual

30GK Series  
PRO-DIALOG  
Control  
Air-Cooled Liquid Chillers  
50 Hz  
Installation, operation and maintenance instructions  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 - PRO-DIALOG PLUS CONTROL OPERATION .................................................................................................................27  
5.1 - Start/stop control ................................................................................................................................................................27  
5.2 - Heating/cooling selection ...................................................................................................................................................27  
5.3 - Evaporator water pump control ..........................................................................................................................................28  
5.4 - Condenser water pump control...........................................................................................................................................28  
5.5 - Control interlock contact ....................................................................................................................................................28  
5.6 - Evaporator heater control ...................................................................................................................................................28  
5.7 - Control point......................................................................................................................................................................28  
5.7.1 - Active setpoint ...........................................................................................................................................................28  
5.7.2 - Reset...........................................................................................................................................................................28  
5.8 - Demand limit ......................................................................................................................................................................29  
5.9 - Capacity control ................................................................................................................................................................29  
5.10 - Determining the lead circuit............................................................................................................................................29  
5.11 - Circuit loading sequence ..................................................................................................................................................29  
5.12 - Slave compressor start-up sequence ................................................................................................................................30  
5.13 - Controlling the EXV ........................................................................................................................................................30  
5.14 - Head pressure control on air-cooled units .......................................................................................................................30  
5.15 - Head pressure control on water-cooled units...................................................................................................................30  
5.16 - Active setpoint selection ..................................................................................................................................................30  
5.17 - High pressure load shedding function..............................................................................................................................31  
5.18 - Pumping down ..................................................................................................................................................................31  
5.19 - Master/slave assembly .....................................................................................................................................................31  
5.20 - Controlling Pro-Dialog Plus units with a System Manager.............................................................................................31  
5.21 - Optional heat reclaim module ..........................................................................................................................................32  
6 - DIAGNOSTICS - TROUBLESHOOTING ............................................................................................................................32  
6.1 - General ...............................................................................................................................................................................32  
6.2 - Displaying alarms ...............................................................................................................................................................32  
6.3 - Resetting alarms .................................................................................................................................................................32  
6.4 - Alarm codes ........................................................................................................................................................................33  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 - SAFETY CONSIDERATIONS  
1.1 - General  
IMPORTANT:  
Risk of electrocution: Even when the main power isolator or  
circuit breaker is off, it is still possible for certain compo-  
nents such as crankcase heaters and trace heaters to be  
energised, since they are connected to a separate power source.  
Installation, start-up and servicing of equipment can be hazard-  
ous if factors particular to the installation are not considered:  
operating pressures, electrical components, voltages and the  
installation site itself (elevated plinths, rooftops and built-up  
structures).  
Even when the unit is switched off, the power circuit remains  
energised, as long as the unit or circuit disconnect is not open.  
Refer to the wiring diagram for details.  
Only highly trained and qualified installation engineers and  
technicians, who are fully trained on the product, are authorised  
to install and start up this equipment.  
Attach appropriate safety labels.  
Risk of burns: Electrical currents cause components to get  
hot either temporarily or permanently. Handle power cables,  
electrical cables and conduits, terminal box covers and motor  
frames with very great care.  
During all servicing operations, it is important to read, under-  
stand and follow all the recommendations and instructions  
given in the installation and service instructions for the product,  
including the tags and labels affixed to the equipment, compo-  
nents and any parts supplied separately, and to comply with all  
other relevant safety regulations.  
IMPORTANT: This equipment uses and emits electromagnetic  
signals. The tests carried out on this product have shown that  
it complies with all applicable codes regarding electromagnetic  
compatibility.  
Apply all safety codes and practices.  
Wear safety glasses and gloves.  
Use the proper tools to move heavy objects. Move units  
carefully and set them down gently.  
IMPORTANT : If the boards need to be handled wear anti-  
static gloves to avoid exposing the electronic components to a  
destructive voltage. Only unpack the boards from their anti-  
static bag when they need to be installed.  
1.2 - Avoiding electrocution  
Only personnel qualified in accordance with the recommendat-  
ions of the IEC (International Electrotechnical Commission)  
may be permitted access to electrical components. It is parti-  
cularly recommended that all sources of electricity to the unit  
be shut off before any work is begun. Shut off the main power  
supply at the main circuit breaker or isolator.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 - GENERAL DESCRIPTION  
2.1 - General  
2.2 - Abbreviations used  
In this manual the circuits are called circuit A and circuit B.  
The compressors in circuit A are labelled A1, A2, A3 and A4.  
Those in circuit B are labelled B1, B2, B3 and B4. A1 and B1  
are the lead compressors.  
PRO-DIALOG Plus is a system for controlling units which use  
reciprocating compressors*:  
Single or dual circuit  
Air or water-cooled condensers  
Non-reversible heat pumps  
Split systems  
The following abbreviations are frequently used:  
AI  
- Analogue Input  
- Analogue Output  
AO  
CCn - Operating type: CCN  
* At present only air-cooled models are available.  
CCN - Carrier Comfort Network.  
This is the Carrier communication network  
- Discrete Input  
- Discrete Output  
PRO-DIALOG Plus controls compressor start-up and demand  
limits needed to maintain the desired entering or leaving tem-  
perature setpoint for water. It automatically sets the position of  
the electronic expansion valve (if used) to optimise the evapo-  
rator charge. It controls operation of the fans (on air-cooled  
units) or water valves (on water-cooled units) to maintain the  
correct head pressure in each circuit.  
DI  
DO  
EXV - Electronic Expansion Device  
LED - Light Emitting Diode  
LOFF - Operating type: Local off  
L-ON - Operating type: Local operation  
MASt - Master unit operating type (master/slave assembly)  
RCPM - Reciprocating Compressor Protection Module  
rEM - Operating type: by remote control contacts  
SCT - Saturated disCharge Temperature  
Safety circuits are constantly monitored by PRO-DIALOG  
Plus to ensure safe operation of the unit. PRO-DIALOG Plus  
also gives access to a Quick Test program covering all inputs  
and outputs.  
SIO  
- Standard Input/Output - internal communication bus  
linking the basic board to the slave boards  
SST - Saturated Suction Temperature  
All PRO-DIALOG Plus controls can work in accordance with  
three independent modes:  
Local mode: the machine is controlled by commands from  
the user interface.  
Remote mode: the machine is controlled by remote  
contacts (volt-free contacts, analogue signals).  
CCN mode: the machine is controlled by commands from  
the Carrier Comfort Network (CCN). In this case a data  
communication cable is used to connect the unit to the  
CCN communication bus.  
The operating mode must be chosen with the Operating Type  
selection button described in section 4.2.1.  
When the PRO-DIALOG Plus system operates autonomously  
(Local or Remote mode) it retains all of its own control capa-  
bilities but does not offer any of the features of the CCN network.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 - HARDWARE DESCRIPTION  
3.1 - General  
The various control components are arranged in modules  
within the control cabinet:  
Control module: This comprises the basic board, the  
user interface, the EXV control board and option boards,  
as well as the customer’s terminal block.  
Start-up module: This consists of the start-up boards,  
compressor protection boards, as well as the compressor  
circuit breakers and contactors.  
Fan module (air-cooled unit): Consists of one or two  
4xDO boards together with the fan circuit breakers and  
contactors.  
Control board  
2
9
1
3
4
8
3.2 - Electronic boards  
3.2.1 - The basic board  
It can be used alone or in conjunction with slave boards. It  
holds the program that controls the machine. It continuously  
manages the information coming in from the various pressure  
and temperature sensors, and communicates with the slave  
boards via the SIO bus. It can also communicate with elements  
of the Carrier Comfort Network via the CCN bus.  
5
Legend  
1
2
3
4
5
6
7
8
9
CCN connector  
Red LED, status of the board  
Green LED, communication bus SIO  
Orange LED, communication bus CCN  
NOTE: After a power cut the unit restarts in the same  
operating mode as before the power cut.  
Remote master board customer control connection contacts  
Remote master board customer control connection signal  
Remote master board customer report connection contacts  
Master PD4 basic board  
3.2.2 - Slave boards  
Compressor board RCPM: This board is used to control  
a compressor. Up to eight RCPM boards can be connected  
to the basic board.  
CCN/clock board  
The control system consists of at least a PD4 basic board, a  
user interface, a PD4-EXV slave board and, depending on the  
application, one or more RCPM compressor boards, 4xDO  
boards or 4xAI-2xAO boards and an NRCP-BASE slave board.  
Slave boards are connected to the basic board via an internal  
communication bus (SIO).  
4xDO board: This board can be used to control fan stages.  
PD4-EXV board: This board can control two EXV valves  
and two suction temperature sensors.  
4xAI-2xAO board: This optional board can be used to  
read sensors (oil pressure), or to control variable speed  
fans (air-cooled units) or the condenser valve (water-cooled  
units).  
The CCN/clock board is connected and screwed to the master  
basic board. It permits communication with elements of the  
Carrier Comfort Network via the CCN bus.  
NRCP-BASE board: This optional board is used to control  
the inputs and outputs of the heat reclaim option.  
Control box  
Legend  
3
4
5
Compressor start-up module  
Control system  
User interface  
1
2
Power supply disconnect switch  
Fan start-up module  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.7 - Light emitting diodes on boards  
3.2.3 - The user interface  
All boards continuously check and indicate the proper  
operation of their electronic circuits. A light emitting diode  
(LED) lights on each board when it is operating properly.  
The user interface is in two parts:  
The main interface: This gives access to all of the  
control parameters for the unit. It consists of a 2-digit  
primary display block and a secondary 4-digit display  
block with 10 LEDs and 5 buttons.  
Red LED  
The summary interface: This gives quick access to just  
the main control parameters for the unit. It comprises 12  
buttons and 16 LEDs, and includes a schematic diagram  
of the unit.  
The MAIN red LED flashes at about 2 second intervals to  
show that the module is working properly.  
Irregular flashing or no flashing is a sign of a defective  
board.  
3.2.4 - Connections between boards  
Green LED  
(item SIO on the board)  
The basic board and slave boards communicate with each other  
over an internal three-wire RS485 communication bus (SIO  
bus). These three wires link all the boards in parallel.  
This LED flashes continuously to show that the board is  
communicating correctly over its internal bus.  
If this LED is not flashing, check the wiring of the SIO  
bus and the address of the board (slave board only). If the  
basic board is not linked to any slave boards, this LED  
should not flash.  
If all slave boards indicate a communication fault, check  
the SIO bus connection on the basic board. If this  
connection is correct and the fault persists, replace the  
basic board.  
Terminals 1, 2 and 3 on connector J9 (A, B, C are connected  
internally) of the basic board are connected to terminals 1, 2  
and 3 of terminal J9 of the NRCP-BASE board, terminal J4 of  
the PD4-EXV board respectively, except for terminal J3 of the  
4xDO and 4xAI-2xAO boards where terminals 2 and 3 are  
reversed.  
Incorrect connection will render the system inoperative.  
3.2.5 - Slave board addresses  
Orange LED - CCN/clock board  
Every slave board (except the NRCP-BASE board) has a  
unique address controlled by 8 DIP switches. The switch is  
disabled when it is in the open position (OPEN or OFF). On  
RCPM boards SIO address switch is labelled 'ADDR'.  
This LED flashes to show that the basic board is commu-  
nicating via the CCN bus.  
3.3 - The controls  
NOTE: Any incorrect address will prevent the unit from  
starting. Turn off the power before amending the address of  
any auxiliary board.  
3.3.1 - Electronic expansion valve (EXV)  
The EXV is used to adjust the refrigerant flow to changes in  
the operating conditions of the machine. For this purpose, a  
series of calibrated orifices are machined into the wall of the  
refrigerant inlet port. As the refrigerant passes through these  
orifices, it expands and becomes a bi-phase mixture (liquid and  
gas).  
Board addresses  
Board  
Address switch  
8
7
6
5
4
3
2
1
PD4-EXV  
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
1
1
1
1
1
0
1
1
1
1
0
0
0
1
1
1
1
1
1
0
0
0
1
1
1
1
0
0
1
0
1
1
0
1
1
1
0
1
1
0
1
0
1
0
1
1
0
1
0
1
1
0
1
0
1
1
0
0
1
1
1
0
0
1
0
0
1
0
1
1
1
1
1
1
0
0
1
1
0
0
1
1
0
4xDO Fan board # 1  
4xDO Fan board # 2  
To adjust the refrigerant flow to changes in operating conditions,  
a piston moves constantly up or down to vary the cross-section  
of the refrigerant path. This piston is driven by an electronically  
controlled linear stepper motor. The high degree of accuracy  
with which the piston is positioned ensures that the flow of  
refrigerant is precisely controlled.  
4xAI-2xAO board # 1  
4xAI-2xAO board # 2  
RCPM # 1 (compressor A1)  
RCPM # 2 (compressor A2)  
RCPM # 2 (compressor A3)  
RCPM # 2 (compressor A4)  
RCPM # 3 (compressor B1)  
RCPM # 4 (compressor B2)  
RCPM # 4 (compressor B3)  
RCPM # 4 (compressor B4)  
NOTE: The external connector of the EXV must be cleaned  
and coated with silicone grease (Part No. 397 EE) to keep out  
condensation and prevent corrosion.  
3.3.2 - The head pressure controls  
The controller can deal with the following:  
3.2.6 - Power supply to the boards  
All boards are supplied by a 24 V source, referred to earth. In the  
event of a power supply interrupt, the unit restarts automatically  
without the need for an external command. However, any faults  
active when the supply is interrupted are saved and may in  
certain cases prevent a circuit or unit from restarting.  
in the case of air-cooled units, for each circuit, fan stages  
together with, if necessary, a variable speed fan (controlled  
by an optional 4xAI-2xAO board)  
in the case of water-cooled units, a water valve. This valve  
is controlled by an optional 4xAI-2xAO board which can  
deliver a 0-10 V d.c. or 4-20 mA signal, depending on the  
configuration.  
NOTE: When connecting the power supply for the boards,  
maintain polarity.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3.3 - The evaporator pumps  
3.3.6 - Thermistors  
The controller can regulate one or two evaporator pumps, with  
automatic changeover between the two pumps.  
These all have similar characteristics.  
Evaporator entering water temperature sensor  
The evaporator entering water temperature sensor is installed in  
the evaporator wall in the free space at the side of the tube  
bundle.  
3.3.4 - The condenser pump  
In appropriate cases the controller can regulate a condenser  
pump (for water-cooled units or air-cooled units with heat  
reclaim option). This control does not require an additional  
board.  
Evaporator leaving water temperature sensor  
The evaporator leaving water temperature sensor is installed in  
evaporator leaving water piping: The sensor bulb is directly  
immersed in the water.  
3.3.5 - Pressure sensors  
These are used to measure the following pressures in each  
circuit:  
Discharge gas pressure (high pressure type)  
Suction pressure (low pressure type)  
Oil pressure (option)  
Compressor suction sensor  
This is located in the lead compressor of each circuit in the  
suction gas line situated between the motor and the cylinders  
above the oil pump.  
These electronic sensors deliver 0 to 5 V d.c. to the main board  
or to a 4xAI-2xAO slave board. Two sensor versions are used;  
one is calibrated for high pressure and the other for low  
pressure and oil pressure.  
Condenser entering and leaving water temperature sensors  
These are used to control the heating capacity on heat pumps.  
In cooling only units they have no control function. They are  
installed in the common condenser entering and leaving line.  
Discharge pressure sensors  
These are on the high pressure side of the lead compressor in  
each circuit. They replace the usual discharge gas pressure  
gauges and can be used to control head pressure or by the high  
pressure load shedding option.  
Heat reclaim condenser entering/leaving water temperatures  
These sensors measure the entering and leaving water tempera-  
tures of heat reclaim condensers and are used on air-cooled  
units equipped with the heat reclaim option. If not, they may be  
fitted as options. In this case they only have informative  
character.  
Oil pressure sensors  
If installed, these sensors are used to measure the compressor  
oil pressure on the oil pressure discharge side. The suction  
pressure is subtracted from the oil pressure value to arrive at  
the differential oil pressure.  
Temperature setpoint reset sensor  
This is an optional 0-10 V sensor which can be installed  
remotely from the unit. It is used to reset the cooling and  
heating setpoint on the unit as a function of either the outdoor  
air temperature or ambient room temperature. The sensor is not  
Suction pressure sensors  
They are located in the low-pressure side of the unit on the lead supplied by Carrier, and must be configured by the User Menu.  
compressor of each circuit. The suction pressure sensor reading  
is used to control the electronic expansion devices EXV. They  
permit replacement of the low-pressure switches, low-pressure  
gauges and possibly of the oil pressure safety switch.  
Outdoor temperature sensor  
Mounted on the control box. It is used for start-up, setpoint  
temperature reset and frost protection control.  
Master/slave assembly temperature control  
The optional water temperature sensor can be used for master/  
slave assembly control.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4 - User connections  
The connections below are available at the customer’s terminal  
block. Some of them can only be used in special operating  
modes. For further details see the sections that describe the  
functions (section 5) and the configurations (section 4.2.1).  
NOTE: The bridge between terminals 32, 63 and 65 on the  
customer’s terminal block must not be removed.  
CONNECTION BLOCK  
DESCRIPTION  
CONNECTOR/CHANNEL TERMINAL DESCRIPTION  
REMARKS  
Alarm relay output, circuit A  
Alarm relay output, circuit B  
J3 / CH24  
J3 / CH25  
30A - 31A  
30B - 31B  
Indicates alarms in circuit A  
Indicates alarms in circuit B  
Volt-free contacts 24 V a.c. 48  
V d.c. max, 20 V a.c. or V  
d.c., 3 A max, 80 mA min,  
external power supply.  
Connector: 6 pin WAGO  
231-306/026000 pitch 5.08.  
User safety loop and chilled water  
pump interlock  
J4 / CH15a  
34 - 35  
This contact is mounted in series with the water flow  
control contact. It can be used for any user safety loop  
that requires that the unit is shut down, if it is open. The  
chilled water pump operation auxiliary contact is  
connected between these two terminals.  
24 V a.c., 20 mA  
Connector: 10 pin WAGO  
734-110, pitch 3.5  
Remote start/stop  
J4 / CH11  
J4 / CH12  
32 - 33  
65 - 66  
The remote start/stop command is only used if the unit is  
under remote operation control (rEM). See section 4.2.1.  
Remote cooling setpoint selection  
The remote cooling setpoint selection command is only  
used if the unit is under remote operation control (rEM).  
See section 4.2.1.  
Remote heating/cooling control  
J4 / CH13  
J4 / CH13  
63 - 64  
63 - 64  
The remote heating/cooling control command is only used  
if the unit is under remote operation control (rEM). See  
section 4.2.1.  
or  
remote heat reclaim control  
The command allows selection of the second condensing  
setpoint or of the heat reclaim mode. It is only used if the  
unit is under remote operation control (rEM). See section  
4.2.1.  
Demand limit command  
J4 / CH14  
J8 / CH10  
73 - 74  
71 - 72  
This contact permits activating the unit demand limit  
function. See section 5.8. This contact is active, whatever  
the operating type.  
0-10 V d.c. setpoint reset or  
demand limit entry  
This 0-10 V d.c. input is used for setpoint reset or unit  
Connector: 2 pin WAGO 231-  
demand limit. It is active, whatever the unit operating type. 302/026000 pitch 5.08  
This 0-10 V signal can be supplied by a user command or  
a 0-10 V temperature sensor.  
Connection to CCN  
J12  
1 - 2 - 3  
A RS-485 bus is used for connection to the CCN.  
The CCN connector is located on the CCN/clock board  
(inserted on the PD4 Basic Board)  
- Pin 1: signal +  
- Pin 2: ground  
- Pin 3: signal -  
Use of a shielded cable (max.  
length: 1000 m)  
Shielding: braiding on 95% -  
100% of the cable surface.  
Shielding connection at the  
two cable ends.  
AVAILABLE TERMINALS  
Description  
Connector/  
Terminal  
Description  
Remarks  
channel  
Condenser water flow  
switch input  
J5/CH17  
This contact is used to detect lack of condenser water flow and 24 V a.c - 20mA  
shuts down the unit.  
Evaporator 1 and 2 pump J5/CH18  
operation input  
This contact is used to detect an evaporator pump operation  
fault and switches over to the other evaporator pump*.  
Evaporator 1 control  
Evaporator 2 control  
J2/CH19  
J2/CH20  
This contact permits control of evaporator 1 pump by the unit*. 24 V a.c. internal supply.  
This contact permits control of evaporator 2 pump by the unit*. Max. consumption  
Condenser pump control J2/CH21  
This contact permits control of condenser pump by the unit*.  
- each output: 20 VA/10W  
- for all 3: 40 VA/20 W if all are used  
Legend  
*
Associated functions, if selected: automatic changeover, pump 1 and 2; manual or CCN selection; periodical; by default.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 - SETTING UP PRO-DIALOG PLUS CONTROL  
4.1 - Local interface general features  
MAIN INTERFACE  
SUMMARY INTERFACE  
MAIN INTERFACE  
SUMMARY INTERFACE  
DUAL-CIRCUIT AIR-COOLED  
CHILLER INTERFACE  
DUAL-CIRCUIT WATER-COOLED  
CHILLER INTERFACE  
MENU BLOCK  
MENU BLOCK  
The local interface enables a number of operating parameters to Main interface  
be displayed and modified.  
It gives access to all PRO-DIALOG PLUS data and operating  
functions. It consists of:  
The interface consists of two distinct parts: the main interface  
(left hand section) and the summary interface (right hand  
section).  
A two-digit display showing the number of the item  
selected.  
A four-digit display showing the contents of the item  
selected.  
LEDs and buttons for unit start/stop, menu selection,  
menu item selection and value adjustment.  
MAIN INTERFACE  
BUTTON NAME  
DESCRIPTION  
Menu  
Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.  
Up arrow  
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises  
increase of the value of any parameter.  
Down arrow  
Enter  
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises  
decrease of the value of any parameter.  
Gives access to the modification mode, validates a modification or displays expanded item description.  
Start/stop  
Authorises start or stop of the chiller in local mode or modification of its operating type.  
MAIN INTERFACE MENU LEDS  
LED  
NAME  
DESCRIPTION  
INFORMATIONS menu  
Displays the general operating parameters for the unit.  
TEMPERATURES menu  
PRESSURES menu  
Displays the unit operating temperatures.  
Displays the unit operating pressures.  
kPa  
SETPOINTS menu  
INPUTS menu  
Displays the unit setpoints and enables them to be modified.  
Displays the status of the unit digital and analogue inputs.  
OUTPUTS/TESTS menu  
Displays the status of the unit outputs and enables them to be tested.  
CONFIGURATIONS menu  
ALARMS menu  
Displays the unit configuration and enables it to be modified.  
Displays active alarms.  
ALARMS HISTORY menu  
Displays the history of the alarms.  
OPERATING LOG menu  
Displays the operating times and number of starts for the unit and the compressors.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The summary interface (right hand section) includes a mimic  
diagram of the unit, together with push-buttons and LEDs. It  
gives quick access to the main operating parameters of the unit.  
The following operating types can be selected using the  
Start/Stop button:  
OPERATINGTYPES  
SUMMARY INTERFACE LEDS  
4-DIGIT DISPLAY DESCRIPTION  
LED  
INDICATION WHEN LIT  
LOFF  
L-On  
Local Off. The unit is halted in local mode.  
Green LED:  
Local On. The unit is in local control mode and is authorised  
to start.  
The unit is authorised to start or is already running  
Red LED:  
L-Sc*  
Local On - timer control. The unit is in local control mode. It  
is authorised to start if the period is occupied. If the timer  
program for unit operation is unoccupied, the unit remains  
shut down until the period next becomes occupied.  
- Lit: circuit A or unit shut down by alarm  
- Flashing: circuit A or unit running with alarm present  
Red LED:  
- Lit: circuit B or unit shut down by alarm  
- Flashing: circuit B or unit running with alarm present  
CCN*  
rEM*  
CCN. The unit is controlled by CCN commands.  
Remote. The unit is controlled by remote control contacts.  
Red LED:  
MAST*  
Master Unit. The unit runs as a master in a two unit lead/lag  
arrangement. This is displayed if the unit is configured for  
master/slave control. See section 5.19.  
Water flow switch default or user safety lock open.  
Green LED:  
The evaporator pump is running.  
Legend  
Yellow LEDs:  
*
Displayed if the configuration requires it.  
From top to bottom - start/stop status of compressors A1, A2, A3 and A4  
or B1, B2, B3 and B4. Flashing LED indicates that the circuit is in the  
protection or defrost mode (A or B).  
Section 5.1 gives a more detailed description of the commands to start/stop  
the unit, analysed by operating type.  
Green LED:  
The unit operates in heating mode.  
4.2.2 - Stopping the unit in local mode  
The unit can be stopped in local mode at any time by pressing  
the Start/Stop button.  
Green LED:  
The unit operates in cooling mode.  
TO STOP THE UNIT  
SUMMARY INTERFACE PUSH BUTTONS  
BUTTON DISPLAY  
BUTTON ACTION  
Press the Start/Stop  
2-DIGIT DISPLAY 4-DIGIT DISPLAY  
C
t
LOFF  
LOFF  
Blue button: evaporator leaving or entering water temperature in °C  
Gray button: outdoor air temperature in °C  
button for less than  
4 seconds (one short  
press is enough).  
Control point (setpoint + reset) in °C  
If the button is  
kPa  
Press 1: circuit A/B discharge pressure in kPa  
Press 2: circuit A/B saturated condensing temperature in °C  
released, the unit stops  
without the need for  
further action.  
kPa  
Press 1: circuit A/B suction pressure in kPa  
Press 2: circuit A/B saturated suction temperature in °C  
Press 1: compressor A1/B1 operating hours in h/10 or h/100  
Press 2: compressor A2/B2 operating hours in h/10 or h/100  
4.2.3 - Starting unit and selecting an operating type  
The unit can be started in local mode, or unit operating type  
can be changed at any time using the Start/Stop button. In the  
example that follows, the unit is stopped (LOFF) and the user  
wants to start the unit in local mode.  
4.2 - Unit start/stop control  
CHANGINGTHE OPERATINGTYPE  
4.2.1 - Description  
The unit start/stop can be controlled by one of the following  
methods:  
BUTTON ACTION  
2-DIGIT  
4-DIGIT  
DISPLAY  
DISPLAY  
Continually press the operating type selection  
button for more than 4 seconds.  
C
LOFF  
Locally on the actual unit (Local control type)  
By remote control with the aid of user contacts (remote  
control type)  
Hold down the Start/Stop button.  
The available operating types are displayed  
one by one until the button is released.  
L-On  
L-Sc  
By CCN control with the aid of the CCN (CCN control  
type)  
rEM  
The main interface includes a Start/Stop button which can be  
used to stop or start the unit in the local operating type or to  
select the remote or CCN operating type.  
Release the Start/Stop button if the operating  
type you want is displayed (in this example L-  
On). "C" flashes in the 2-digit display to show  
that the controller is awaiting confirmation.  
L-On  
L-On  
Press the Enter button to confirm the  
t
The available operating types are described in the following  
table.  
operating type selected (in this example: L-  
On). "t" is displayed in the 2-digit display to  
indicate the operating type selected. If the  
Enter button is not pressed soon enough, the  
controller will cancel the change and continue  
to use the previous operating type.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3 - Menus  
NOTE: The access to a sub-menu may require entering a  
password. This is automatically requested. See section 4.5.7.2.  
4.3.1 - Selecting a menu  
The MENU button authorises you to select a menu from the 10  
main menus that are available. Each time you press this button  
one of the 10 LEDs lights up in turn alongside each of the  
icons representing a main menu. The active menu is the one  
against which the LED is lit. If a menu is empty then its LED  
is not lit. To scroll quickly through the menus, hold the MENU  
button down.  
The example below shows how to modify the value of item 1  
in the Setpoint menu.  
MODIFYINGTHEVALUE OF A PARAMETER  
OPERATION  
PRESS MENU LED ITEM  
button NUMBER NUMBER  
2-DIGIT 4-DIGIT  
ITEM  
DISPLAY DISPLAY  
Hold on the MENU button until  
the LED for SETPOINT lights.  
0
4.3.2 - Selecting a menu item  
The up and down Arrow buttons let you scroll through the  
menu items. Menu item numbers are displayed in the two-digit  
display. The item number increases or decreases every time  
you press the up or down Arrow button. The menu items that are  
not in use or incompatible with the configuration are not  
displayed. The value or status associated with the active item  
is displayed in the four-digit display. To scroll quickly through  
the items, hold the up or down Arrow button down.  
0
1
Press one of the Arrow buttons  
until the two-digit display shows 1  
item number 1- cooling setpoint 2).  
The value for setpoint 2 is  
displayed in the four-digit display  
(6.0°C in this example).  
1
1
1
6.0  
6.0  
5.9  
Press the Enter button for more  
than 2 seconds to enable the  
value associated with item 1 to be  
modified. The Setpoint menu LED  
flashes indicating that modification  
mode is active.  
The following example shows how to access item 3 in the  
Pressures menu.  
Keep pressing the Down Arrow  
button until the value 5.7 is  
displayed in the four-digit display.  
The Setpoint menu LED keeps  
flashing.  
SELECTING A MENU ITEM  
OPERATION  
PRESS  
BUTTON  
MENU LED  
ITEM NUMBER  
2-DIGIT  
1
1
5.8  
5.7  
DISPLAY  
Press the MENU button until the  
LED marked PRESSURE lights.  
0
kPa  
kPa  
Press the Enter button again to  
validate the change. The new  
setpoint is 5.7°C. The Setpoint  
menu LED stops flashing, indicat-  
ing that modification mode no  
longer applies.  
0
1
1
5.7  
Press one of the Arrow buttons  
until the two-digit display shows 3  
(item number 3).  
2
3
4.3.4 - Expand display  
Pressing the Enter button causes a 23 character text expansion  
to be scrolled across the four-digit display. All user menus  
provide an expansion of the current displayed parameters. If  
the expansion is complete the four-digit display reverts to item  
value. This function can be inhibited through the User  
Configuration menu.  
4.3.3 - Modifying the value of a parameter/access to a sub-  
menu  
Press the Enter button for more than 2 seconds to enter the  
modification mode or to select a sub-menu. This lets you correct  
the value of an item or select a sub-menu with the aid of the up  
and down Arrow buttons (if you are authorised to overwrite the  
item concerned). When modification mode is activated, the  
LED for the main menu to which the item belongs flashes in  
menu block. Once the required value is obtained, press the  
Enter button again to validate the change or to access the sub-  
menu. The LED for the menu to which the item belongs then  
stops flashing, indicating that modification mode no longer  
applies.  
In modification mode, the value to be modified increases or  
decreases in steps of 0.1 every time you press the Arrow  
buttons. Holding one of these buttons down increases the rate  
of increase or decrease.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4 - General menu structure  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5 - Menu tree structure  
MENU  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.1 - Description of the Information menu  
INFORMATION MENU [3]  
ITEM  
FORMAT  
UNITS  
DESCRIPTION  
Automatic display mode. It cycles through the following displays:  
0
1:  
2:  
Controlled water temperature: temperature of the water that the unit tries to maintain at the control point.  
Unit operating type  
±nn.n  
°C  
Local Off  
Local On  
Local On - based on unit clock.  
CCN Control.  
Remote Control  
Master unit  
LOFF  
L-On  
L-Sc  
CCn  
rEM  
-
-
-
-
-
-
MASt  
3:  
Unit status  
Off: Unit is stopped and not authorised to start.  
Ready: Unit is authorised to start  
OFF  
rEADY  
dELAY  
-
-
-
Delay: Unit is in delay at start-up. This delay is active after the unit has been switched on. The delay can be  
configured in the User Configuration menu.  
Stopping: Unit is currently stopping.  
On: Unit is running or authorised to start.  
Fault shutdown.  
Limit: The operating conditions do not allow total unit operation.  
Unit occupied/unoccupied status  
Occupied: Unit in occupied mode  
StOPPing  
running  
triPout  
-
-
-
-
OvErridE  
4.  
5.  
OCCUPIEd  
UNOCCUPIEd -  
-
Unoccupied: Unit in unoccupied mode  
Heating/cooling operating mode  
Cooling: Unit operates in cooling mode  
Heating: Unit operates in heating mode  
Cooling: Unit is in auto cooling and heat reclaim demand is active  
Alarm mode  
Alarm: Unit is totally stopped because of failure.  
Alert: Unit is in failure but not completely stopped.  
Master/Slave status  
COOL  
HEAT  
rECLAIM  
-
-
-
6.  
7.  
ALArM  
ALErt  
-
-
Master: The master/slave control is active and the unit is the master  
Slave: The master/slave control is active and the unit is the slave  
MAStEr  
SLAvE  
-
-
1 [1]  
2 [2]  
nn  
-
Active mode codes. Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode code  
is displayed causes a character text expansion to be scrolled accross the four-digit display. See the description in the following table  
-
This item indicates the current chiller occupied/unoccupied mode.  
occu  
unoc  
Forc  
Occupied  
Unoccupied  
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
3
nn.n  
minutes Start-up delay. This item indicates the minutes left before the unit can be started. This delay at start-up is always active after the unit  
has been switched on. The delay can be configured in the User Configuration 1 menu.  
Heating/cooling on selection: This item is accessible in read/write, if the unit is in local control mode. It is only displayed, if the unit is  
4 [2]  
-
in LOFF, L-On or L-Sc operating type. Displayed for heat pumps.  
Heating mode selection  
Cooling mode selection  
HEAt  
COOL  
-
-
5 [2]  
Heat reclaim mode selection: This item is accessible in read/write, if the unit is in local control mode. It is only displayed, if the unit is  
in LOFF, L-On or L-Sc operating type. Displayed for air-cooled or water-cooled units with a condenser water valve.  
Heat reclaim mode selection, use of heat reclaim condensing setpoint.  
YES  
NO  
-
-
Normal cooling mode selection, use of standard condensing setpoint  
6
Nnn  
nnn  
nnn  
%
%
%
Total active capacity of unit.  
7
Total active capacity of circuit A.  
Total active capacity of circuit B.  
8 [2]  
9 [2]  
nnn  
Present demand limit. This is the authorised operating capacity of the unit. See section 5.8.  
Forc  
%
%
-
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
10  
nnn  
Present lag chiller demand limit. Displayed when the master/slave control is selected.  
11 [2]  
Setpoint select in local mode. This point is read/write accessible. Displayed only when the unit is LOFF, L-On or L-Sc operating type.  
SP-1  
SP-2  
AUtO  
SP-1 = cooling setpoint 1  
SP-2 = cooling setpoint 2  
AUtO = active setpoint depends on schedule 2 (setpoint selection schedule). See section 5.7.1 & 4.5.7.6.  
Setpoint occupied mode.  
12 [2]  
-
Occupied: cooling setpoint 1 is active  
Unoccupied: cooling setpoint 2 is active  
The value shall be displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
occu  
unoc  
Forc  
13  
14  
±nn.n  
°C  
°C  
Active setpoint. This is the current cooling/heating setpoint: it refers to cooling/heating setpoint 1 or 2.  
±nn.n  
Forc  
Control point. This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to  
configuration).  
Control point = active setpoint + reset. See section 5.7  
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
15  
16  
±nn.n  
°C  
Controlled water temperature. Water temperature that the unit tries to maintain at the control point.  
Condensing setpoint. The value is displayed in turn with 'Forc' if the unit is in CCN mode and this parameter is forced by CCN.  
±nn.n  
Forc  
°C  
°C  
17  
18  
n
n
Heat reclaim function indicator, circuit A (see heat reclaim section)  
Heat reclaim function indicator, circuit B (see heat reclaim section)  
Legend  
1
2
3
This item is masked when nil.  
This item is displayed in certain unit configurations only.  
Access to this menu is read-only except for item 10 that can be forced when the unit is in Local operating type.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)  
MODE # MODE NAME  
DESCRIPTION  
7
Delay at start-up active  
The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.  
The delay is configured in the User1 configuration menu.  
8
9
2nd cooling setpoint active  
Setpoint reset active  
The second cooling setpoint is active. See section 5.7.1  
In this mode, the unit uses the reset function to adjust the leaving or entering water temperature setpoint. See  
section 5.7.2.  
10  
11  
Demand limit active  
Ramp loading active  
In this mode, the capacity at which the unit is allowed to operate is limited. See section 5.8.  
Ramp loading is active. In this mode, the controlled high or low water temperature value (in °C/min) in heating mode  
is limited to a preset value in order to prevent compressor overload. The ramp function must be configured (see  
User1 configuration menu). The ramp values can be modified (see setpoint menu).  
12  
Low entering water temperature  
protection in heating mode  
The unit is in heating mode and the temperature of the evaporator leaving water is lower than the lesser of the two  
cooling setpoints. A capacity stage is removed. This mode only applies to heat pumps.  
13,14  
Low suction temperature protection  
13 = circuit A & 14 = circuit B. Protection for evaporator suction low temperature circuit is active. In this mode, circuit  
capacity is not authorised to rise if the unit is in cooling mode, and saturated suction temperature in the circuit is  
lower by more than 13°C at the leaving chilled water and lower than the frost protection threshold.  
15,16  
17,18  
Low discharge superheat protection  
15 = circuit A & 16 = circuit B.  
In this mode the circuit capacity is shut down by pumpout and not allowed to restart, when the low superheat alarm  
conditions are satisfied. During the shutdown/start-up sequence, mode 15 or 16 is active. See descriptions for  
alarms 48 and 49.  
High pressure protection  
17 = circuit A & 18 = circuit B. The circuit is in high pressure protection mode because the HP protection threshold  
has been exceeded. The circuit capacity is not authorised to rise and any slave compressor can be stopped in order  
to prevent a high pressure break.  
19,20  
21  
Not used  
Heat reclaim active  
Circuit A or circuit B operates in heat reclaim mode and not in standard cooling mode (pumpdown phase is  
activated).  
22  
23  
24  
Evaporator heater active  
Mode active if risk of frost exists.  
Evaporator pump reversal active  
Periodic evaporator pump start-up  
Two evaporator water pumps installed on the unit and pump reversal is active. See section 5.3  
The unit is shut down and is started every day at 14:00 hours for 2 seconds. This function must be configured in the  
User1 menu. See sections 5.3 and 4.5.7.3.  
25  
Low night-time capacity  
Unit capacity is limited. The period when this mode starts, as well as the limited capacity in night-time mode are  
controlled in Client1 menu.  
26  
27  
Unit under SM control  
Master/slave link active  
Unit is under control of a System Manager (FSM or CSM III).  
Unit is connected to a secondary unit by a master slave link and either:  
- the unit is configured as a master and this master is operating, or  
- the unit is configured as a slave and this slave is operating.  
4.5.2 - Description of the Temperatures menu  
4.5.3 - Description of the Pressures menu  
TEMPERATURES MENU [2]  
PRESSURES MENU [2]  
ITEM FORMAT UNITS COMMENTS  
ITEM  
0
FORMAT  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
nnnn  
UNITS  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
kPa  
COMMENTS  
0
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
Evaporator entering water temperature  
Evaporator leaving water temperature  
Condenser entering water temperature  
Condenser leaving water temperature  
Reclaim condenser entering water temperature  
Reclaim condenser leaving water temperature  
Saturated discharge temperature circuit A  
Saturated suction temperature circuit A  
Suction temperature compressor A1  
Superheat circuit A  
Discharge pressure circuit A  
1
1
Suction pressure circuit A  
2[1]  
3[1]  
4[1]  
5[1]  
6
2
Differential oil pressure compressor A1  
Discharge pressure circuit B  
3
4
Suction pressure circuit B  
5
Differential oil pressure compressor B1  
Differential oil pressure compressor A2  
Differential oil pressure compressor A3  
Differential oil pressure compressor A4  
Differential oil pressure compressor B2  
Differential oil pressure compressor B3  
Differential oil pressure compressor B4  
Pumpdown pressure, heat reclaim, circuit A  
Pumpdown pressure, heat reclaim, circuit B  
6[1]  
7[1]  
8[1]  
9[1]  
10[1]  
11[1]  
12[1]  
13[1]  
Legend  
7
8
9
10[1] ±nn.n  
11[1] ±nn.n  
12[1] ±nn.n  
13[1] ±nn.n  
14[1] ±nn.n  
15[1] ±nn.n  
Legend  
Saturated discharge temperature circuit B  
Saturated suction temperature circuit B  
Suction temperature compressor B1  
Superheat circuit B  
Outdoor temperature  
Water loop temperature, master/slave assembly  
1
2
This item is displayed in certain unit configurations only.  
Access to this menu is read-only  
1
2
This item is displayed in certain unit configurations only  
Access to this menu is read-only.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.4 - Description of the Setpoints menu  
SETPOINTS MENU [2]  
ITEM  
FORMAT UNITS  
RANGE  
COMMENTS  
0
±nn.n  
±nn.n  
nnn  
°C  
°C  
°C  
°C  
See table below  
See table below  
See table below  
See table below  
This item lets you display and modify Cooling setpoint 1*  
This item lets you display and modify Cooling setpoint 2*  
This item lets you display and modify Heating setpoint*, only displayed for heat pumps.  
1
2
3 [1]  
nnn  
This item lets you display and modify the condensing setpoint*. It is used by the control to regulate the fan  
stages or a variable-speed fan (air-cooled units) or the condenser water valve control (water-cooled  
units), if the unit is not in heat reclaim mode.  
4 [1]  
5
nnn  
°C  
See table below  
0 to 100  
This item lets you display and modify the heat reclaim setpoint*. As item 3, this is used for condensing  
setpoint control.  
nnn  
%
Capacity limit setpoint. Limitation by volt-free contact. This item is used to define the maximum capacity  
that the unit is authorised to use, if the capacity limit contact activate the limit. See section 5.8.  
6 [1]  
±nn.n  
°C/min  
0.1 to 1.1  
Cooling ramp loading rate. This parameter is only accessible if the ramp function is validated in the User  
Configuration 1 menu. This item refers to the maximum rate of temperature rise in °C in the water heat  
exchanger in cooling mode. When capacity loading is effectively limited by the ramp, mode 11 is active.  
7 [1]  
±nn.n  
°C/min  
0.1 to 1.1  
Heating ramp loading rate. This parameter is only accessible if the ramp function is validated in the User  
Configuration 1 menu. This item refers to the maximum rate of temperature drop in °C in the water heat  
exchanger in heating mode. When capacity loading is effectively limited by the ramp, mode 11 is active.  
8 [1]  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
[3]  
[3]  
°C  
[3]  
[3]  
°C  
See table below  
See table below  
See table below  
See table below  
See table below  
-16 to 16  
Zero reset threshold, cooling mode**  
Full reset threshold, cooling mode**  
Full reset value, cooling mode**  
Zero reset threshold, heating mode**  
Full reset threshold, heating mode**  
Full reset value, heating mode**  
9 [1]  
10 [1]  
11 [1]  
12 [1]  
13 [1]  
Legend  
1
2
*
This item is displayed in certain unit configurations only.  
All points contained in this table can be modified.  
Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature.  
Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.  
** These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.5.7.3.  
SETPOINT DESCRIPTION  
CONTROL FOR  
CONTROL FOR  
LEAVING WATER  
ENTERING WATER  
Cooling  
Minimum setpoint  
- Water  
3.3°C  
-10°C  
-20°C  
9.3°C  
-4°C  
-14°C  
- Medium Brine  
- Low Brine  
Maximum setpoint  
Heating  
Note:  
Maximum setpoint  
MCT - 4.0  
MCT - 10.0  
Three setpoint reset configuration modes can be selected in the Client1 menu:  
1 Reset using an external 0-10 V d.c. signal  
2 Reset using Delta T  
3 Reset by external temperature sensor (air-cooled units only)  
The items with zero reset or maximum reset are based on these three modes.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.5 - Description of the Inputs menu  
INPUTS MENU [2]  
ITEM  
FORMAT  
UNITS  
COMMENTS  
0
OPEn/CLoS  
-
Remote contact 1 status  
This contact is used to start (contact closed) and stop (contact open) the chiller. It is only valid, if the unit is in the remote operating  
control (rEM) mode.  
1
OPEn/CLoS  
OPEn/CLoS  
OPEn/CLoS  
-
-
-
Remote contact 2 status  
This contact is used to select a cooling only setpoint, if the unit is in cooling mode and in the remote operating control (rEM) type.  
Contact open = csp1  
Contact closed = csp2  
2[1]  
3[3]  
Remote contact 3 status  
This contact is used to select the heating or cooling mode, only if the unit is in the remote operating control type.  
Contact open: unit in cooling mode  
Contact closed: unit in heating mode  
Remote contact 4 status  
This contact is used to select the second condensing setpoint or the heat reclaim mode (for a heat reclaim unit), only if the unit is in  
the remote operating control type.  
Contact open = unit uses the normal condensing setpoint and is in normal mode (no heat reclaim)  
Contact closed = unit uses the heat reclaim setpoint and is in heat reclaim mode.  
4
OPEn/CLoS  
-
Remote contact 5 status*  
If this contact is closed, it permits limiting the unit demand, based on the demand limit setpoint, if the demand limit method by  
contact has been selected.  
5
OPEn/CLoS  
OPEn/CLoS  
-
-
Water flow and customer interlock control contact status*  
Opening of this contact shuts the unit off or prevents its start-up and generates an alarm. It is used to control the water circulation.  
6[1]  
Water pump operation status. If the contact opens when the evaporator pump has received a command to operate, this trips a  
pump failure alarm.  
7[1]  
8[1]  
OPEn/CLoS  
OPEn/CLoS  
-
-
Condenser water flow control. Controls the condenser water circulation.  
Control box thermostat and phase reversal interlock status*. Opening of this contact shuts the unit off or prevents its start-up  
and generates an alarm.  
9[1]  
nn.n  
-
External 0-10 V d.c. signal. This signal from an external source can be used (based on the configuration) for the reset or demand  
limit function of the unit.  
Legend  
1
2
*
This item is displayed in certain unit configurations only  
Access to this menu is read-only  
Active in all operating types  
See section 3.4  
4.5.6 - Description of the Outputs/Tests menu  
4.5.6.1 - General  
This menu displays the status of the controller outputs. More-  
over, when the machine is fully stopped (LOFF) the outputs  
can be activated for manual or automatic tests (the access to the  
tests is password controlled).  
4.5.6.2 - Menu description  
OUTPUTS STATUS AND TESTS MENU [2] [3]  
ITEM  
FORMAT  
UNITS  
DESCRIPTION.  
0
Compressor status  
-
-
-
-
b1 = compressor A1  
b2 = compressor A2  
b3 = compressor A3  
b4 = compressor A4  
This item permits display of the compressor status in circuit A. It also permits independent testing. In test mode the direction  
arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.  
1 [1]  
Compressor status  
-
-
-
-
b1 = compressor B1  
b2 = compressor B2  
b3 = compressor B3  
b4 = compressor B4  
This item permits display of the compressor status in circuit B. It also permits independent testing. In test mode the direction  
arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.  
2 [1]  
3 [1]  
tEST  
tESt  
Capacity reduction status, circuits A & B  
b1 = capacity reduction A1  
b2 = capacity reduction B1  
This item permits display of the capacity reduction status in circuit A. It also permits independent testing.  
-
-
Fan contactor status/test, circuit A  
-
b1 = fan contactor assembly 1  
-
-
-
b2 = fan contactor assembly 2  
b3 = fan contactor assembly 3  
b4 = fan contactor assembly 4  
This item permits display of the fan stages. It also permits independent testing. In test mode the direction arrows permit  
successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OUTPUTS STATUS 2 AND TESTS MENU [2] [3] - cont.  
ITEM  
FORMAT  
UNITS  
DESCRIPTION  
4 [1]  
tESt  
-
Fan contactor status/test, circuit B  
-
-
b1 = fan contactor assembly 1  
b2 = fan contactor assembly 2  
b3 = fan contactor assembly 3  
b4 = fan contactor assembly 4  
This item permits display of the fan stages. It also permits independent testing. In test mode the direction arrows permit  
successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.  
5
tESt  
Alarm command status/test  
-
-
b1 = alarm circuit A  
b2 = alarm circuit B  
In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each alarm  
output.  
6
7
tESt  
tESt  
%
EXV position, circuit A  
In the test mode the direction arrows permit forcing the valve to its fully open position.  
%
EXV position, circuit B  
In the test mode the direction arrows permit forcing the valve to its fully open position.  
8 [1]  
9 [1]  
10  
tESt  
tESt  
%
%
Variable speed fan, circuit A or condenser water valve position in %  
Variable speed fan, circuit B or condenser water valve position in %  
On  
-
Evaporator water pump No. 1 command status. Not displayed if unit does not control a pump.  
On: the pump operates  
Stop: the pump has stopped  
Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump  
without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is  
then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its  
status is forced by CCN.  
Stop  
tESt  
FAIL  
Good  
Forc  
-
-
-
-
-
During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display  
appears:  
- Fail: displayed if the test has failed, because the pump is not started  
- Good: displayed if the test succeeds  
11  
On  
-
-
-
-
-
-
Evaporator water pump No. 2 command status. Not displayed if unit does not control a pump.  
On: the pump operates  
Stop: the pump has stopped  
Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump  
without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is  
then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its  
status is forced by CCN.  
OFF  
tESt  
FAIL  
Good  
Forc  
During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display  
appears:  
- Fail: displayed if the test has failed, because the pump is not started  
- Good: displayed if the test succeeds  
12  
On  
-
-
Condenser pump status/test  
On: the pump operates  
Stop: the pump has stopped  
OFF  
tESt  
FAIL  
Good  
Forc  
Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump  
without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is  
then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its  
status is forced by CCN.  
-
During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display  
appears:  
- Fail: displayed if the test has failed, because the pump is not started  
- Good: displayed if the test succeeds  
13[1]  
nn  
Evaporator heater and heat reclaim condenser status  
b1 = evaporator heater  
b2 = heat reclaim condenser heater  
-
-
14[1]  
15[1]  
tESt  
%
Condenser water valve position in heat reclaim mode  
Solenoid valve status/test, heat reclaim function  
-
-
-
-
b1 = heat reclaim coil shutoff solenoid valve, circuit A  
b2 = heat reclaim coil drain solenoid valve, circuit A  
b3 = heat reclaim coil shutoff solenoid valve, circuit B  
b4 = heat reclaim coil drain solenoid valve, circuit B  
In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation  
of each output.  
16  
YES  
no  
Used only for local interface  
Cause all diodes and blocks to light up or flash, to verify that they are operating correctly  
tESt  
Legend  
1
2
3
This item is displayed in certain unit configurations only  
A test is only possible if the units are in local off mode and if all compressors have stopped  
The password is only valid for the test. 'Test' is displayed during the test, alternating with the item number  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.6.3 - Manual tests  
The menus User 1 [USEr 1] and User 2 [USEr 2] are pass-  
word-protected. The other menus are directly accessible, except  
if item 12 of the User 1 menu (password for all configurations)  
has been validated.  
This function allows the user to test the outputs individually, if  
the machine is completely shut down (LOFF). To carry out a  
manual test use the arrow keys to access the output to be tested  
and press the Enter key (longer than 2 seconds) to activate the  
modification mode. The password is automatically requested, if it  
has not previously been verified. The Outputs/Test LED on the  
user interface begins to flash. Enter the desired test value and  
again press Enter to start the test. 'TESt' is displayed on the 4-  
digit display alternately with the value tested. The Outputs/Test  
LED stops flashing. Press the Enter key or an arrow key to stop  
the test.  
4.5.7.2 - Password  
A password must be entered in order to access the test function  
or to modify a configuration. It is automatically requested, if  
necessary: 'EntEr PASS' is displayed on the 4-digit display and  
the configuration menu LED flashes, indicating that the modifi-  
cation mode is active. Press the arrow keys until the value '11'  
is displayed on the 4-digit display. Press Enter to validate this.  
The configuration menu LED stops flashing. If the password is  
correct, 'Good' is displayed. If the password is incorrect, 'PASS  
incorrEct' is displayed. The User password has a default value  
of 11.  
4.5.7 - Description of the Configuration menu  
4.5.7.1- General  
This menu can be used to display and modify all configura-  
tions: Factory, Service and User. Only the User Configuration  
can be modified by the end-user. The Factory, Service and  
master/slave configurations are not described in this docu-  
ment. A configuration can only be modified if the unit is fully  
stopped (LOFF).  
This value can be modified through the Service configuration.  
The password can be entered if the unit is fully stopped, other-  
wise 'ACCES dEniEd' (access denied) will be displayed on the  
4-digit display. The controller automatically deactivates the  
password after 5 minutes without activity (i.e. no buttons  
pressed) or after powering up.  
SUB-MENU USER CONFIGURATION  
ITEM USER 1  
USER 2  
[USER2]*  
DATE  
[dAtE]*  
SCHEDULE 1  
[ScHEduLE 1MEnu]*  
SCHEDULE 2  
[ScHEduLE 2 MEnu]* [HOLidAy MEnu]*  
HOLIDAYS  
BROADCAST  
[BrodCASt]*  
[USER1]  
0
Return to previous menu  
Return to previous  
menu*  
Return to previous Return to previous menu Return to previous  
Return to previous menu  
Return to previous menu  
menu  
menu  
1
Circuit selection  
Periodic pump start-  
up*  
Hour*  
SUB-MENU:  
Period 1 [PErIod 1]  
SUB-MENU:  
Period 1 [PErIod 1]  
SUB-MENU:  
Holidays 1 [HOLidAy 1]  
Broadcast acknowledger  
selection  
2
Circuit capacity increase  
sequence  
Night mode - start  
hour*  
Day of the week* SUB-MENU:  
Period 2 [PErIod 2]  
SUB-MENU:  
Period 2 [PErIod 2]  
SUB-MENU:  
Holidays 2 [HOLidAy 2]  
Broadcast activation  
3
Ramp selection*  
Night mode - end  
hour*  
Day and month*  
SUB-MENU:  
Period 3 [PErIod 3]  
SUB-MENU:  
Period 3 [PErIod 3]  
SUB-MENU:  
Holidays 3 [HOLidAy 3]  
Outdoor temperature  
broadcast bus  
4
Start-up delay*  
Night mode - demand Year*  
limit in %  
SUB-MENU:  
Period 4 [PErIod 4]  
SUB-MENU:  
Period 4 [PErIod 4]  
SUB-MENU:  
Holidays 4 [HOLidAy 4]  
Outdoor temperature  
broadcast element  
5
Water pump selection  
Number clock 1*  
-
-
-
-
-
-
-
-
-
-
-
-
SUB-MENU:  
Period 5 [PErIod 5]  
SUB-MENU:  
Period 5 [PErIod 5]  
SUB-MENU:  
Holidays 5 [HOLidAy 5]  
Start month daylight  
saving time  
6
Water pump changover  
delay*  
Number clock 2*  
SUB-MENU:  
Period 6 [PErIod 6]  
SUB-MENU:  
Period 6 [PErIod 6]  
SUB-MENU:  
Holidays 6 [HOLidAy 6]  
Start day daylight saving  
time  
7
Automatic reset  
selection*  
CCN address *  
SUB-MENU:  
Period 7 [PErIod 7]  
SUB-MENU:  
Period 7 [PErIod 7]  
SUB-MENU:  
Holidays 7 [HOLidAy 7]  
Start hour daylight saving  
time  
8
Demand limit selection  
CCN bus*  
SUB-MENU:  
Period 8 [PErIod 8]  
SUB-MENU:  
Period 8 [PErIod 8]  
SUB-MENU:  
Holidays 8 [HOLidAy 8]  
Minutes to add  
9
Voltage corresponding to  
100% of demand limit  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
SUB-MENU:  
Holidays 9 [HOLidAy 9]  
End month daylight saving  
time  
10  
11  
12  
13  
14  
15  
16  
Voltage corresponding to  
0% of demand limit  
SUB-MENU:  
Holidays 10 [HOLidAy 10]  
End day daylight saving  
time  
Extended display  
selection  
SUB-MENU:  
Holidays 11 [HOLidAy 11]  
End hour daylight saving  
time  
Password for all user  
configurations  
SUB-MENU:  
Holidays 12 [HOLidAy 12]  
Minutes to subtract  
Software version number  
SUB-MENU:  
Holidays 13 [HOLidAy 13]  
-
-
-
-
-
-
-
SUB-MENU:  
Holidays 14 [HOLidAy 14]  
SUB-MENU:  
Holidays 15 [HOLidAy 15]  
SUB-MENU:  
Holidays 16 [HOLidAy 16]  
Legend:  
*: only displayed if configuration requires.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONFIGURATION  
USER  
[USEr]  
USER1  
[USEr 1]  
USER2  
[USEr 2]  
SCHEDULE 1  
[SCHEduLE 1]*  
SCHEDULE 2  
[SCHEduLE 2]*  
HOLIDAYS  
[HOLIDAYS]*  
HOUR + DATE  
[dAtE]*  
BROADCAST  
[broAdCASE]*  
HOLIDAY 1  
PERIOD 1  
PERIOD 2  
PERIOD 3  
PERIOD 4  
PERIOD 5  
PERIOD 6  
PERIOD 7  
PERIOD 8  
PERIOD 1  
PERIOD 2  
PERIOD 3  
PERIOD 4  
PERIOD 5  
PERIOD 6  
PERIOD 7  
PERIOD 8  
HOLIDAY 2  
HOLIDAY 3  
HOLIDAY 4  
HOLIDAY 5  
HOLIDAY 6  
HOLIDAY 7  
HOLIDAY 8  
...  
...  
...  
HOLIDAY 15  
HOLIDAY 16  
SUB-MENU PERIOD CONFIGURATION*  
SUB-MENU HOLIDAY CONFIGURATION*  
Item  
PERIOD 1 to 8  
[PEriod X MEnu]*  
Item  
HOLIDAYS 1 to 16  
[HoLidAy X MEnu]*  
0
1
2
3
4
5
6
7
8
9
10  
Return to previous menu  
Start of occupied period  
End of occupied period  
Selection Monday  
0
1
3
4
Return to previous menu  
Start month holidays  
Start day holidays  
Number of days, holidays  
Selection Tuesday  
Selection Wednesday  
Selection Thursday  
Selection Friday  
Legend  
*: only displayed if configuration requires.  
NOTE: The items in brackets show what is displayed on the  
user interface.  
Selection Saturday  
Selection Sunday  
Selection holidays  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.7.3 - Description of the User 1 Configuration sub-menu  
USER 1 CONFIGURATION SUB-MENU [2]  
ITEM  
0
FORMAT  
USEr MEnu  
0/1/2  
UNITS  
DEFAULT  
COMMENTS  
-
-
When selected this item authorises return to the previous menu.  
1 [1]  
0
Lead circuit selection  
0 = automatic based on the number of start-ups and the operating hours of each circuit  
1 = lead circuit A  
2 = lead circuit B  
2 [1]  
3 [1]  
0/1  
-
-
0
Circuit capacity increase sequence  
0 = equal charge for both circuits  
1 = priority charge on one circuit  
YES/no  
no  
Ramp loading select. For units with more than one compressor per circuit.  
Yes = ramp enabled  
No = ramp disabled  
This configuration enables the ramp to be activated for heating or cooling (depending on configuration): the  
maximum rate (in °C/min) of temperature drop or rise for the heat exchanger water (leaving or entering, upon  
configuration). Ramp setting value can be configured in the Setpoint menu.  
4
5
1 to 15  
min  
-
1
0
Delay at start-up. This value is reinitialised after power-up or when both circuits are halted by local, remote  
or CCN command. No compressor will be started up until this pause has expired. However, the evaporator  
pump command will be activated immediately. The safety lockout loop will not be checked until the pause has  
expired.  
0/1/2/3/4  
Pump sequence select  
0 = no pump  
1 = one pump only  
2 = two pumps with auto rotation  
3 = pump #1 manual select  
4 = pump #2 manual select  
If the auto sequence is selected, the pump change-over occurs when the rotation delay is elapsed. If the  
manual sequence is selected then, the selected pump is used in priority. Change-over occurs if one pump  
fails.  
6 [1]  
7
24 to 3000  
0/1/2/3  
hours  
48  
0
Pump changeover delay. Displayed if auto pump sequence is selected. This parameter is used for pump  
auto-rotation: the control tries to limit the pump run time difference to the pump changeover delay value.  
Change-over between pumps occurs when this difference becomes greater than the configured pump  
changeover delay.  
-
Automatic heating/cooling changeover selection. Permits activation of automatic reset type  
0 = none  
1 = 0-10 V d.c. reference voltage  
2 = temperature difference  
3 = outdoor temperature  
8
0/1/2  
-
0
Demand limit selection  
0 = demand limit not selected  
1 = demand limit by contact  
2 = demand limit by external signal 0-10 V d.c.  
9 [1]  
10 [1]  
11  
0 to 10  
Volts  
Volts  
-
0
Voltage corresponding to 100% of the demand limit  
Voltage corresponding to 0% of the demand limit  
0 to 10  
0
«YES/no»  
yes  
Extended menu select  
Yes = menu description available  
No = menu description not available  
This item authorises activating or inhibiting the menu item expanded display.  
12  
«YES/no»  
-
-
no  
-
Password for all User Configurations  
Yes = password required for all User Configurations (Date, Time Schedule, Broadcast)  
No = password require for User menu only  
When this item is validated, the User Password will be required for all configurations accessible by the User.  
13  
nn.n  
Software version number  
This item shows the number of the software version used by this controller. Access is read only.  
Legend  
1
2
This item shall be masked when not used.  
Access to menu is read/write.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.7.4 - Description of the User 2 Configuration sub-menu  
USER 1 CONFIGURATION SUB-MENU  
ITEM  
0
FORMAT  
USEr 2 Menu  
YES/no  
UNITS  
DEFAULT  
COMMENTS  
When selected this item authorises return to the previous menu.  
1[1]  
-
no  
Periodic pump quick-start of the water pump(s)  
Yes = the pump is started periodically when the unit is manually stopped.  
No = periodic pump start is disabled  
When the unit is manually stopped (e.g. during the winter season) the pump is started each day at 14.00  
hours for 2 seconds. If two pumps are available, pump #1 is started on odd days and pump #2 on even days.  
2 [1]  
n1n2n3 n4  
Night control mode - start time*  
00:00 to 23:59  
-
00:00  
Authorises entering the time of day at which the night control mode starts. During this period the fan runs at  
low speed (to reduce fan noise) if permitted by operating conditions, and unit capacity is limited to the  
maximum night values.  
3 [1]  
4 [1]  
5 [1]  
n1n2n3 n4  
00:00 to 23:59  
Night control mode - end time*  
Authorises entering the time of day at which the night control mode ends.  
-
00:00  
-
0 to 100  
%
Night mode demand limit value.  
Authorises configuration of the maximum capacity authorised during the night mode.  
0 or 65 to 99  
-
-
0
0
Schedule 1 clock number (for unit on/off schedule, see section 4.5.7.6).  
0 = schedule in local operating mode  
65 to 99 = schedule in CCN operating mode  
6 [1]  
0 or 65 to 99  
Schedule 2 clock number (schedule for setpoint selection, see section 4.5.7.6).  
0 = schedule in local operating mode  
65 to 99 = schedule in CCN operating mode  
7 [1]  
1 to 239  
0 to 239  
-
-
1
0
CCN element address.  
No two network elements can have the same element number and bus number at the same time.  
8 [1]  
CCN bus number.  
No two network elements can have the same element number and bus number at the same time.  
Legend  
*
n1n2: hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.  
4.5.7.5 - Description of Date and Time configuration sub-  
menu  
4.5.7.6 - Description of the Time Schedules sub-menus  
The control provides two timer programs: time schedule 1 and  
time schedule 2.  
DATE & TIME CONFIGURATION SUB-MENU  
ITEM  
FORMAT  
COMMENTS  
The first timer program (schedule #1) provides a means to  
automatically switch the unit from an occupied mode to an  
unoccupied mode: the unit is started during occupied periods.  
0
dAtE MEnu  
When selected this item authorises return to the  
previous menu.  
1
2
n1n2n3n4  
Current time setting.  
00:00 to 23:59 n1n2: hours (00 to 23). The first time the Enter button is  
continuously pressed, the first two characters in the 4-  
digit display flash so that hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the  
Enter key again causes the last two characters to flash  
and minutes can be adjusted.  
The second timer program (schedule #2) provides a means to  
automatically switch (when auto mode is selected) the active  
setpoint from an occupied setpoint to an unoccupied setpoint.  
Cooling or heating setpoint 1 is used during occupied periods.  
Cooling setpoint 2 is used during unoccupied periods. For  
additional information on setpoint activation see section 5.7.1.  
Current day of week setting.  
«Mo»  
«tU»  
«uE»  
«tH»  
«Fr»  
Monday  
Tuesday  
Wednesday  
Thursday  
Friday  
Each schedule consists of eight time periods set by the  
operator. These time periods can be flagged to be in effect or  
not in effect on each day of the week plus a holiday period (see  
section 4.5.7.7 on public holidays). The day begins at 00.00  
hours and ends at 24.00 hours.  
«SA»  
«Su»  
Saturday  
Sunday  
3
4
n1n2n3n4  
Current day and month setting.  
01:01 to 31:12 n1n2:day (01 to 31). The first time the Enter button is  
continuously pressed, the first two characters in the 4-  
digit display flash so that day can be adjusted.  
n3n4:month (01 to 12). Continuous pressing of the  
Enter key again causes the last two characters to flash  
so that month can be adjusted.  
Program is in unoccupied mode unless a schedule time period is  
in effect. If two periods overlap and are both active on the same  
day, the occupied mode takes priority over the unoccupied period.  
nnnn  
Current year setting.  
Each of the eight periods can be displayed and changed with  
the aid of a sub-sub-menu. The table below shows how to  
access the period configuration. Method is the same for the  
time schedule #1 or the time schedule #2.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 8)  
4.5.7.7 - Description of the Holidays sub-menus  
ITEM # FORMAT  
COMMENTS  
This function is used to define 16 public holiday periods. Each  
period is defined with the aid of three parameters: the month,  
starting day and duration of the public holiday period. During  
these public holidays the controller will be in occupied or  
unoccupied mode, depending on the programmed periods  
validated for public holidays (see section 4.5.7.8).  
0
1
2
Period X Menu  
Indicates the period (X) you are going to  
configure. When selected this item authorises a  
return to the main menu.  
n1n2n3n4  
00:00 to 24:00  
Occupied period - Start time*.  
Authorises entering the time of day at which the  
occupied period starts.  
n1n2n3n4  
00:00 to 24:00  
Occupied period - End time*.  
Authorises entering the time of day at which the  
occupied period ends.  
Each of these public holiday periods can be displayed and  
changed with the aid of a sub-menu.  
3
4
5
Mo- 0 or Mo- 1  
tu- 0 or tu- 1  
1 = the period is in effect on Monday.  
0 = period not in effect on Monday  
1 = the period is in effect on Tuesday.  
0 = period not in effect on Tuesday.  
ATTENTION: The broadcast function must be activated to  
utilise the holiday schedule, even if the unit is running in  
stand-alone mode (not connected to CCN). See section  
4.5.7.6.  
UE-0 or UE- 1  
1 = the period is in effect on Wednesday.  
0 = period not in effect on Wednesday.  
6
tH- 0 or tH- 1  
Fr-0 or Fr- 1  
1 = the period is in effect on Thursday.  
0 = period not in effect on Thursday.  
HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 16)  
7
1 = the period is in effect on Friday.  
ITEM # FORMAT  
COMMENTS  
0 = period not in effect on Friday.  
0
HoLidAy X Sub-menu  
When selected this item authorises a return  
to the configuration menu.  
8
SA- 0 or SA- 1  
Su- 0 or Su- 1  
Ho- 0 or Ho- 1  
1 = the period is in effect on Saturday.  
0 = period not in effect on Saturday.  
1
0 to 12  
Start month of public holiday period  
0 = period not in use  
1 = January, 2 = February, etc.  
9
1 = the period is in effect on Sunday.  
0 = period not in effect on Sunday.  
10  
1 = the period is in effect on public holidays.  
0 = period not in effect on public holidays.  
2
3
0 to 31  
Start day of public holiday period. 0 period  
not in use.  
Legend  
*
0 to 99 days  
Duration of the public holiday period in  
days.  
n1n2: hours (00 to 24). The first time the Enter button is continuously pressed,  
the first two characters in the 4-digit display flash so that hours can be  
adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes  
the last two characters to flash so that minutes can be adjusted.  
NOTE: Typical programming for public holidays:  
-
A public holiday period lasting 1 day on 20th May, for  
instance, is configured as follows: start month = 5, start  
day = 20, duration = 1  
Typical timer program:  
-
A public holiday period lasting 2 day on 25th May, for  
instance, is configured as follows: start month = 5, start  
day = 25, duration = 2  
Time MON TUE WES THU FRI SAT SUN HOL  
P1  
P1  
P1  
0
1
2
4.5.7.8 - Description of the Broadcast sub-menu  
The controller provides a broadcast configuration menu which  
you can use to configure the unit to be the CCN’s broadcaster,  
responsible for transmitting the time, outdoor temperature, and  
holiday flags to all system elements.  
3
4
5
6
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P3  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P5  
P5  
P5  
P5  
P5  
7
8
9
This menu also authorises setting the date to begin and end  
daylight saving time. There should be only one broadcaster in a  
CCN, so this table should not be configured if any other system  
element is acting as broadcaster.  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
MON : Monday  
TUE : Tuesday  
WED : Wednesday  
THU : Thursday  
ATTENTION: If the unit operates in standalone mode (not  
CCN connected) this menu must be used if the holiday function  
is used, or to correct for daylight saving time.  
FRI :  
Friday  
SAT :  
Saturday  
SUN : Sunday  
HOL : Public holidays  
P3  
P3  
P6  
Occupied  
Unoccupied  
Starts at  
0h00,  
7h00,  
7h00,  
7h00,  
7h00,  
20h00,  
Not used in this example  
Not used in this example  
Ends at  
3h00,  
Active on  
Monday  
Monday and Tuesday  
Wednesday  
Thursday and Friday  
Saturday  
P1: period 1,  
P2: period 2,  
P3: period 3,  
P4: period 4,  
P5: period 5,  
P6: period 6,  
P7: period 7,  
P8: period 8,  
18h00,  
21h00,  
17h00,  
12h00,  
21h00,  
Public holidays  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BROADCAST CONFIGURATION SUB-MENU  
ITEM #  
FORMAT  
COMMENTS  
0
1
broAdCASt MEnu  
YES/no  
When selected this item authorises a return to the main menu.  
Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network. There must be  
only one broadcast acknowledger in a CCN.  
Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used  
(see section 4.5.7.8) or if you want to configure the daylight saving time function.  
2
YES/no  
This item authorises enabling or disabling the Broadcast function. When it is set to Yes, the control will make a periodic  
broadcast on the CCN. When it is set to No, the control is not the broadcaster and there is no need to configure the other choice in  
this table. There must be only one broadcaster in a CCN and this item should not be configured if any other system element is  
acting as broadcaster.  
Warning: if the unit operates in standalone (not CCN connected) this choice must be set to Yes if the holiday function is used (see  
section 4.5.7.8) or if you want to configure the daylight saving time function.  
3
4
5
6
7
nnn  
0 to 239  
OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.  
Used for CCN network function only.  
nnn  
0 to 239  
OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor  
connected to it. Used for CCN network function only.  
nn  
1 to 12  
Daylight saving start month. In this mode you enter the month in which the broadcaster will adjust its time for the start of  
daylight saving time.  
nn  
1 to 31  
Daylight saving start day. In this mode you enter the day on which the broadcaster will adjust its time for the start of daylight  
saving time.  
n1n2n3n4  
Authorises entering the hours and minutes for saving start. In this mode you enter the time of day when the broadcaster will  
00:00 to 24:00  
adjust its time for the start of daylight saving time.  
n1n2: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so  
that hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be  
adjusted.  
8
nnnn  
Daylight saving start minutes to add: number of minutes by which the broadcaster will adjust its time for the start of daylight  
1 to 1440 minutes  
saving time.  
9
nn  
Daylight saving stop month. In this mode you enter the month in which the broadcaster will adjust its time for the end of  
1 to 12  
daylight saving time.  
10  
11  
12  
nn  
1 to 31  
Daylight saving stop day. In this mode you enter the day on which the broadcaster will adjust its time for the end of daylight  
saving time.  
n1n2n3n4  
00:00 to 24:00  
Authorises entering the hours and minutes for saving stop. In this mode you enter the time of day when the broadcaster  
will adjust its time for the end of daylight saving time.  
nnnn  
Daylight saving start minutes to subtract: number of minutes by which the broadcaster will adjust its time for the end of  
1 to 1440 minutes  
daylight saving time.  
n1n2: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.  
4.5.8 - Description of the Alarms menu  
4.5.9 - Description of the Alarms History menu  
This menu is used to display and reset up to 5 active alarms. It  
also permits alarm reset. If no alarm is active this menu is not  
accessible. See section 6 for a complete description of the  
alarm codes and alarm reset.  
ALARMS HISTORY MENU  
ITEM #  
1 [1]  
FORMAT  
nn  
COMMENTS  
Alarm history code 1*  
Alarm history code 2*  
Alarm history code 3*  
Alarm history code 4*  
Alarm history code 5*  
Alarm history code 6*  
Alarm history code 7*  
Alarm history code 8*  
Alarm history code 9*  
Alarm history code 10*  
2 [1]  
nn  
3 [1]  
nn  
ALARMS MENU  
4 [1]  
nn  
ITEM #  
FORMAT  
DESCRIPTION  
5 [1]  
nn  
0 [1]  
X ALArM  
X alarms are active  
6 [1]  
nn  
rESEt ALArM Reset of alarms is requested  
7 [1]  
nn  
To reset all active alarms, continuously press the Enter  
key. rESET ALArMis then displayed. Press the select  
key again: all alarms are reset.  
8 [1]  
nn  
9 [1]  
nn  
10 [1]  
Legend  
nn  
1 [1]  
nn  
nn  
nn  
nn  
nn  
Current alarm code 1*  
Current alarm code 2*  
Current alarm code 3*  
Current alarm code 4*  
Current alarm code 5*  
2 [1]  
1
*
This item is masked when nil  
Pressing the Enter key when alarm code is displayed causes the following  
message to be scrolled:  
3 [1]  
4 [1]  
time of alarm” “date of alarm” “full CCN alarm message”  
- time of alarm: hh-mm  
- date: dd-mm  
5 [1]  
Legend  
1
*
This item is masked when nil  
Pressing the Enter key when alarm code is displayed causes the following  
message to be scrolled:  
- full CCN alarm message: up to 64 characters  
time of alarm” “date of alarm” “full CCN alarm message”  
- time of alarm: hh-mm  
- date: dd-mm  
- full CCN alarm message: up to 64 characters  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.10 - Runtime menu description  
4.5.10.2 - Description of the Runtimes 2 menu  
RUNTIMES MENU [2]  
RUNTIMES  
iTEM # FORMAT  
UNIT  
COMMENTS  
0
-
-
When selected this item  
authorises return to the previous  
menu  
RUNTIMES 1  
[runtiMES 1]  
RUNTIMES 2  
[runtiMES 2]  
MAINTENANCE  
[MAintEnAnCE]  
1
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
Pump #1 operating hours*  
Pump #2 operating hours*  
2
3 [1]  
Condenser pump operating  
hours  
NOTE: The items in brackets show what is displayed on the  
user interface.  
4 [1]  
5
nnnn  
nnnn  
-
-
Number of start-ups for the  
compressor with the highest  
number during the last hour  
Average number of compressor  
start-ups/hour for the last 24  
hours  
4.5.10.1 - Description of the Runtimes 1 menu  
RUNTIMES MENU [1]  
iTEM # FORMAT  
UNIT  
COMMENTS  
0
-
-
When selected this item  
authorises return to the previous  
menu  
4.5.10.3 - Maintenance menu description  
To be active, the maintenance function must be preset in the  
Service configuration.  
1
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
nnnn | M 10 | M100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
-/10 or 100  
Unit operating hours*  
2
Compressor A1 operating hours*  
Compressor A2 operating hours*  
Compressor A3 operating hours*  
Compressor A4 operating hours*  
Compressor B1 operating hours*  
Compressor B2 operating hours*  
Compressor B3 operating hours*  
Compressor B4 operating hours*  
Machine starts*  
3 [1]  
4 [1]  
5 [1]  
6 [1]  
7 [1]  
8 [1]  
9 [1]  
10  
ITEM # FORMAT  
DESCRIPTION  
0
MAintEnAnCE MEnu When selected this item authorises return to the  
previous menu.  
1 [1]  
2 [1]  
3 [1]  
4 [1]  
5 [1]  
Accessible with the Service password.  
For future use  
For future use  
ALErt  
Water loop rate to low  
nnn/ALErt  
Next primary pump maintenance operation in nnn  
days. 'ALErt' is displayed, when the delay before  
maintenance has elapsed.  
11  
-/10 or 100  
Compressor A1 starts*  
12 [1]  
13 [1]  
14 [1]  
15 [1]  
16 [1]  
17 [1]  
18 [1]  
-/10 or 100  
Compressor A2 starts*  
6 [1]  
nnn/ALErt  
nnn/ALErt  
Next secondary pump maintenance operation in  
nnn days. 'ALErt' is displayed, when the delay  
before maintenance has elapsed.  
-/10 or 100  
Compressor A3 starts*  
-/10 or 100  
Compressor A4 starts*  
-/10 or 100  
Compressor B1 starts*  
7 [1]  
Next water filter maintenance operation in nnn  
days. 'ALErt' is displayed, when the delay before  
maintenance has elapsed.  
-/10 or 100  
Compressor B2 starts*  
-/10 or 100  
Compressor B3 starts*  
Legend  
-/10 or 100  
Compressor B4 starts*  
1 This item is masked when not used.  
NOTES  
1
*
This item is masked when not used  
Certain values are divided by 10 or by 100, so that number of hours or start-  
ups of less then 10 are displayed as 0.  
When the value is divided by 10 or by 100 it is displayed in turn with M 10or  
M100.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 - PRO-DIALOG PLUS CONTROL OPERATION  
5.1 - Start/stop control  
-
-
Start/Stop schedule: occupied or unoccupied status of the  
unit as determined by the chiller start/stop program  
(Schedule #1). Used when the unit is equipped with an  
optional CCN/clock board, otherwise the chiller occupied  
mode is forced to occupied all the time.  
Master control type. This parameter is used when the  
unit is the master unit in a two chiller lead/lag arrange-  
ment. The master control type determines whether the unit  
is to be controlled locally, remotely or through CCN (this  
parameter is a Service configuration).  
The table below summarises the unit control type and stop or  
go status with regard to the following parameters.  
-
Operating type: this is selected using the start/stop button  
on the front of the user interface.  
-
Remote start/stop contacts: these contacts are used when  
the unit is in remote operating type (rEM). See sections  
3.6.2 and 3.6.3.  
-
-
CCN emergency shutdown: if this CCN command is  
activated, it shuts the unit down whatever the active  
operating type.  
-
CHIL_S_S: this network command relates to the chiller  
start/stop when the unit is in CCN control (CCn). Vari-  
able forced to disable: the unit is halted. Variable forced to  
Enable: the unit runs in accordance with schedule 1.  
General alarm: the unit is totally stopped due to failure.  
ACTIVE OPERATING TYPE  
STATUS OF PARAMETERS  
CONTROL UNIT  
TYPE  
MODE  
REMOTE  
MASTER  
START/STOP CCN  
GENERAL  
START/STOP CONTROL  
SCHEDULE EMERGENCY ALARM  
LOFF L-ON L-SC rEM  
CCN MASt CHIL_S_S  
CONTACT  
TYPE  
MODE  
SHUTDOWN  
-
-
-
-
-
-
-
-
-
-
Enable  
-
-
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
On  
On  
On  
On  
On  
On  
-
-
-
-
-
-
-
-
-.  
-.  
-
Yes  
-
Active  
-
-
-
-
-
-
-
-
-
-
-
Local  
Local  
Remote  
Remote  
CCN  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Active  
-
-
-
-
-
-
Unoccupied  
-
-
-
-
-
Active  
-
-
-
Off  
-
-
-
-
-
Active  
-
-
-
-
-
Unoccupied  
-
-
-
-
-
-
Active  
-
Disable  
-
-
-
-
-
-
-
Active  
-
-
-
-
-
-
-
Unoccupied  
Unoccupied  
-
-
-
CCN  
-
-
-
-
Active  
Active  
Active  
-
Local  
Remote  
Remote  
CCN  
CCN  
-
-
-
Local  
Remote  
Remote  
CCN  
-
-
-
-
Off  
-
-
-
-
-
-
-
Unoccupied  
-
-
-
-
-
-
-
Active Disable  
-
-
-
-
-
-
-
Active  
-
-
Unoccupied  
-
-
-
CCN  
Active  
-
-
-
-
-
-
Disable  
Disable  
Dsable  
Disable  
Disable  
Disable  
Disable  
No  
No  
No  
No  
No  
No  
No  
Local  
Local  
Remote  
CCN  
-
-
-
-
-
-
Active  
-
-
-
-
-
-
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
-
-
-
-
-
Active  
-
-
-
On  
-
-
-
-
-
Active  
-
Enable  
-
-
-
-
-
Active  
Active  
-
-
-
Local  
Remote  
CCN  
Local  
Remote  
CCN  
On  
-
Active Enable  
5.2 - Heating/cooling selection  
The current heat/cool operating mode on the unit is indicated  
by item 4 in the Information menu and by the heat/cool LEDs  
on the summary interface.  
On heat pumps, heating/cooling selection can be controlled  
differently depending on the active operating type:  
Locally on the unit, using operating types L-C1, L-C2,  
LC1r and LC2r (for cooling) and L-H (for heating).  
Remotely using the heat/cool selection volt-free contact  
when the unit is in Remote operating type (rEM).  
Via a CCN command when the unit is in CCN operating  
type (CCn).  
PARAMETER STATUS  
HEATING/COOLING  
SELECTION IN LOCAL MODE  
ON/OFF  
STATUS  
CONTROL TYPE  
REMOTE HEATING/  
COOLING CONTACTS  
HC_SEL  
OPERATING MODE  
Off  
On  
On  
On  
On  
On  
On  
-
-
-
-
Cooling  
Cooling  
Heating  
Cooling  
Heating  
Cooling  
Heating  
Local  
Local  
Remote  
Remote  
CCN  
CCN  
Cooling  
-
-
Heating  
-
-
-
-
-
-
Cooling mode  
-
Heating mode  
-
-
-
Cooling  
Heating  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.3 - Evaporator water pump control  
5.5 - Control interlock contact  
The unit can control one or two evaporator water pumps. The  
evaporator water pump is turned on when this option is confi-  
gured (see User configuration) and when the unit is in one of the  
on modes described above or in delay mode. Since the minimum  
This contact can control the status of the water loop. Its  
function is to prevent unit start-up, if it is open and if the start-  
up delay has passed. Furthermore, this contact must remain  
closed when the unit is not in local off, remote or CCN control  
value for the delay at start-up is 1 minute (configurable between 1 mode. Opening this contact for more than 8 seconds while the  
and 15 minutes), the pump will run for at least one minute  
before the first compressor starts.  
unit is operating, will cause immediate shut-down of the faulty  
unit.  
The pump is kept running for 20 seconds after the unit goes to  
stop mode. The pump keeps working when the unit switches  
from heating to cooling mode or vice-versa. It is turned off if  
the unit is shut down due to an alarm unless the fault is a frost  
protection error.  
5.6 - Evaporator heater control  
The evaporator heater can be activated to protect an evaporator  
that may be damaged by ice, if the unit is shut down for a long  
period at low outdoor air temperature. If the heater is not  
sufficient to increase the water temperature, the evaporator  
The pump can be started in particular operating conditions when pump can be started.  
the evaporator heater is active. See section 5.19 for the  
particular evaporator pump control for the follower unit  
(master/slave assembly). If two pumps are controlled and the  
reversing function has been selected (see User 1 configuration),  
the control tries to limit the pump run time delta to the  
NOTE: The evaporator heater control parameters may be  
modified using the Service Configuration menu.  
5.7 - Control point  
configured pump change-over delay. If this delay has elapsed,  
the pump reversing function is activated, when the unit is  
running. During the reversing function both pumps run together  
for two seconds. If a pump has failed and a secondary pump is  
available, the unit is stopped and started again with this pump.  
Control point represents the leaving water temperature that the  
unit must produce.  
In cooling mode: control point = active setpoint + reset  
In heating mode: control point = active setpoint - reset  
The control provides a means to automatically start the pump  
each day at 14.00 hours for 2 seconds when the unit is off. If  
the unit is fitted with two pumps, the first pump is started on  
odd days and the second pump is started on even days. Starting  
the pump periodically for few seconds increases the life-time  
of the pump bearings and the tightness of the pump seal.  
5.7.1 - Active setpoint  
Two setpoints can be selected as active in cooling mode.  
Usually, the second setpoint is used for unoccupied periods or  
for ice storage (medium or low brine unit). A single setpoint is  
available in heating mode.  
Depending on the current operating mode, the active setpoint  
can be selected with the operating type selector button, or with  
the user’s volt-free contacts, or with network commands (see  
section 3.4).  
NOTE: If this function is used, there should not be any  
chilled water pump interlock between terminals 34 and 35  
(see section 3.4).  
5.4 - Condenser water pump control  
5.7.2 - Reset  
Reset means that the active setpoint is modified so that less  
machine capacity is required (in cooling mode, the setpoint is  
increased, in heating mode it is decreased). This modification is  
in general a reaction to a drop in the load. For the Pro-Dialog  
Plus control system, the source of the reset can be configured  
in the User 1 configuration: it can be based on an external 0-10 V  
signal, provided either by the outdoor temperature (that gives a  
measure of the load trends for the building) or by the return  
water temperature (delta T that gives an average building load).  
In response to a drop in the outdoor temperature or to a drop in  
delta T, the cooling setpoint is normally reset upwards in order  
to optimise unit performance:  
Only available on water-cooled units and air-cooled units with  
heat reclaim.  
The condenser pump can be controlled by two modes, depend-  
ing on the configuration (only accessible by Carrier Service).  
1 - Control based on unit start/stop control. In this case it is  
controlled in the same way as the evaporator pump.  
2 - Control based on compressor status. In this case the pump  
is activated at the same time as the first compressor. It  
only switches off when no compressor is activated.  
In both cases the reset parameters, i.e. slope, source and maxi-  
mum value, are configurable in the Setpoints menu (see section  
4.5.4). Reset is a linear function based on three parameters.  
A reference at which reset is zero (outdoor temperature or  
delta T - no reset value).  
A reference at which reset is maximum (outdoor  
temperature or delta T - full reset value).  
The maximum reset value.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.8 - Demand limit  
NOTE: If the same compressor undergoes too many starts  
(per hour) this automatically brings about reduction of  
compressor starts, which makes leaving water temperature  
control less precise.  
Generally, demand limit is used by an energy management  
system in order to restrict the unit electricity consumption.  
The PRO-DIALOG Plus control system for 30GX & 30HX  
provides two methods of demand limit:  
5.10 - Determining the lead circuit  
By reference to a limiting signal from a user-controlled  
volt-free contact: the capacity of the unit cannot exceed  
the demand limit setpoint (which can be modified in the  
Setpoints menu) when the limit contact is closed.  
By reference to an external 0-10 V d.c. signal: the  
capacity of the unit cannot exceed the demand limit  
imposed by this external signal. It is a linear function and  
its para-meters are configurable in the User1 menu  
(voltages at 0% limitation and 100% of limitation). This  
function is not available if Reset by reference to an  
external 0-10 V d.c. signal has already been selected.  
This function commands the start/stop sequence of the two  
refrigerant circuits called A and B. The circuit authorised to  
start first is the lead circuit. Three methods can be configured  
by the user in the Configuration menu:  
Auto mode: the control system determines the lead circuit  
so as to equalise the number of starts on each circuit  
(value weighted by the operating times of each circuit).  
Thus, the circuit with the least number of starts is always  
given precedence to start. The lead circuit is stopped last.  
This function is only available in two-circuit units.  
NOTE: If one circuit has more unloaders than the other, this  
circuit is always the lead circuit, independent of the  
configuration and the operating hours of the two circuits.  
Whatever the method used, demand limit is active in all  
operating types: Local, Remote or CCN. However, in  
Local operating type, demand limit can be disabled with  
keypad commands (see section 4.3.3) and in CCN  
operating type, demand limit can be controlled directly  
with the aid of CCN commands.  
Circuit A as leader: Circuit A is always the lead circuit.  
It is the first to start and the last to stop.  
Circuit B as leader: Circuit B is always the lead circuit.  
It is the first to start and the last to stop. This choice is  
only available in two-circuit units.  
NOTE: A limitation value of 100% means that the unit may  
call upon the full array of its capacity stages.  
5.11 - Circuit loading sequence  
Here is an example of demand limit by an external 0-10 V d.c.  
signal. This example assumes that the limitation parameters are  
such that at 0 volt the authorised capacity shall be maximum  
capacity, and at 10 volts the authorised capacity shall be zero  
(this is the default configuration).  
Two circuit loading sequences are available. The choice of  
sequence can be configured by the user in the Configuration  
menu (see section 4.5.7.3). This function is only available in  
two-circuit units.  
Balanced circuit loading: If this sequence is selected, the  
control system tries to keep the capacity of circuits A and  
B equal as the total load on the unit increases or decreases.  
Loading with priority given to one circuit: If this  
sequence is selected, the control system loads the lead  
circuit completely before the second circuit starts up. When  
there is a demand limit, the second circuit is unloaded first.  
Demand limit by 0-10 V d.c. signal  
No demand limit  
Total demand limit  
NOTE: If the unit is air-cooled and if the saturated  
condensing temperature of one of the two circuits is lower  
than 0°C at the start-up of one circuit, the priority capacity  
loading sequence of the circuits is used by the control,  
independent of the configuration.  
0-10 V dc demand limit  
5.9 - Capacity control  
This function activates the compressors and capacity unloaders  
to keep the entering or leaving water temperature at its  
setpoint. The precision with which this is achieved depends on  
the capacity of the water loop, the flow rate, the load, and  
the number of stages available on the unit.  
The control system continuously takes account of the tempera-  
ture error with respect to the setpoint, as well as the rate of  
change in this error and the difference between entering and  
leaving water temperatures, in order to determine the optimum  
moment at which to add or withdraw a capacity stage.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.12 - Slave compressor start-up sequence  
5.15 - Head pressure control on water-cooled units  
Lag compressors are started and stopped in a sequence  
designed to equalise their number of start-ups (value weighted  
by their operating time).  
There are two configurable methods for controlling the conden-  
ser water valves (optional):  
Controlling head pressure by reference to a setpoint:  
Saturated head pressure is controlled by reference to a user-  
definable fixed setpoint. This temperature is maintained by  
using the valves to control the flow of water in each conden-  
ser circuit.  
Controlling head pressure by reference to the position of  
the EXV: Saturated head pressure is controlled by reference  
to the position of the EXV and the superheat, by adjusting  
the flow of water in each condenser circuit. The valve control  
system seeks to keep the EXVs as wide open as possible  
whilst maintaining the correct level of superheat. When the  
second head pressure setpoint is selected (reclaim setting),  
the control system will automatically revert to controlling by  
reference to a setpoint even if control by reference to the  
EXV has been selected. The original configuration is  
reinitialised when the first head pressure setpoint is re-  
selected.  
5.13 - Controlling the EXV  
EXVs, if used, control the flow of refrigerant in the evaporator.  
They are controlled in order to maintain a constant level of  
superheat at the thermistor for the lead compressor inlet gas  
(located between the compressor motor and the cylinders).  
A thermistor and a pressure sensor, in the lead compressor of  
each circuit, are used to measure this superheat. The thermistor  
measures the temperature of the superheated gas entering the  
cylinders. The pressure sensor measures the suction gas  
pressure. The controller converts this value into a saturated  
temperature. The difference between the superheated gas  
temperature and the saturated temperature is the superheat. The  
control system sets the position of the EXV to hold this  
superheat at the setpoint configured for the unit.  
5.16 - Active setpoint selection  
Since the EXVs are driven by the controller their positions are  
always known. During start-up of a circuit its EXV is fully closed  
Two setpoints can be selected as active in cooling mode, and  
to ensure pump down. After pump down, the system continuously one setpoint in heating mode. Usually, the second cooling  
controls and monitors the valve position. Similarly, on shutdown  
of a circuit the EXV is closed again to ensure pumping down.  
setpoint is used for unoccupied periods or for ice storage (brine  
unit). Depending on the current operating mode, the active  
setpoint can be selected either by choosing the item in the  
Information menu. or with the user volt-free contacts, or with  
network commands, or by the setpoint time schedule program  
(Schedule 2).  
EXVs are also used to restrict suction temperature, making it  
possible to start the unit at higher water and suction tempera-  
tures without overloading the compressors. This procedure  
controls what is known as Maximum Operating Pressure (MOP).  
The following tables show a summary of the possible selctions  
as a function of the control typpes (local, remote or network),  
and the parameters below:  
5.14 - Head pressure control on air-cooled units  
There are two methods, configurable only by Carrier Service,  
for controlling the condenser fans:  
Local setpoint selection: item No. 11 of the Information  
Menu permits selection of the active setpoint, if the unit is  
in the local operating type.  
Controlling condensation by reference to a setpoint  
(default): The saturated head pressure is controlled by  
reference to a fixed setpoint (user-definable in the Setpoints  
menu). This temperature is maintained by cycling fans on  
and off, as well as by varying the speed of a fan in  
appropriate cases.  
Controlling condensation by reference to the position of  
the EXV: The saturated head pressure is controlled by  
reference to the position of the EXV and the superheat, by  
cycling fans on and off as well as by varying the speed of a  
fan in appropriate cases. The control system seeks to keep  
the EXVs as wide open as possible whilst maintaining the  
correct level of superheat with the fans. When the second  
condensing setpoint is selected (reclaim setting), the control  
system will automatically revert to controlling by reference  
to a setpoint even if control by reference to the EXV has  
been selected. The original configuration is reinitialised  
when the first condensing setpoint is re-selected.  
Heating/cooling operating mode.  
Control contacts: status of the remote heating and  
cooling control contact. This contact is only active, if the  
unit is under remote operating control. See section 3.6.6.  
Schedule 2 program status: schedule program for  
setpoint selection. See section 4.3.11.6.  
NOTE  
Certain units can have up to 8 fan stages, of which one per  
circuit is a variable-speed fan, depending on their configura-  
tion and wiring.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCAL OPERATING MODE  
PARAMETER STATUS  
All control commands to the master/slave assembly (start/stop,  
setpoint, heating/cooling operation, load shedding, etc.) are  
handled by the unit which is configured as the master, and must  
therefore only be applied to the master unit. They will be trans-  
mitted automatically to the slave unit. The master unit can be  
controlled locally, remotely or by CCN commands. Therefore  
to start up the assembly, simply validate the Master operating  
type (MASt) on the master unit. If the Master has been confi-  
gured for remote control then use the remote volt-free contacts  
for unit start/stop. The slave unit must stay in CCN operating  
type continuously. To stop the master/slave assembly, select  
Local Off (LOFF) on the master unit or use the remote volt-  
free contacts if the unit has been configured for remote control.  
HEATING/  
COOLING  
OPERATING  
MODE  
LOCAL  
SETPOINT  
SELECTION  
SCHEDULE 2  
PROGRAM STATUS  
ACTIVE SETPOINT  
cooling  
cooling  
heating  
holidays  
holidays  
sp 1  
sp2  
-
auto  
auto  
-
-
-
cooling setpoint 1  
cooling setpoint 2  
heating setpoint  
cooling setpoint 1  
cooling setpoint 2  
occupied  
unoccupied  
REMOTE OPERATING MODE  
PARAMETER STATUS  
HEATING/  
COOLING  
OPOERATING  
MODE  
CONTROL  
CONTACT  
SCHEDULE 2  
PROGRAM STATUS  
ACTIVE SETPOINT  
heating  
-
-
-
-
heating setpoint  
cooling setpoint 1  
cooling setpoint 2  
cooling setpoint 1  
cooling setpoint 2  
cooling  
sp 1  
One of the functions of the master unit (depending on its con-  
figuration) may be the designation, whether the master or slave is  
to be the lead machine or the follower. The roles of lead machine  
and follower will be reversed when the difference in running  
hours between the two units exceeds a configurable value,  
ensuring that the running times of the two units are automatically  
equalised. The changeover between lead machine and follower  
may take place when the assembly is started up, or even whilst  
running. The running time balancing function is not active if it  
has not been configured: in this case the lead machine is  
always the master unit.  
cooling  
sp2  
-
-
holidays  
holidays  
occupied  
unoccupied  
CCN OPERATING MODE  
PARAMETER STATUS  
HEATING/COOLING  
OPERATING MODE  
SCHEDULE 2  
PROGRAM STATUS  
ACTIVE SETPOINT  
cooling  
cooling  
heating  
occupied  
unoccupied  
-
cooling setpoint 1  
cooling setpoint 2  
heating setpoint  
5.17 - High pressure load shedding function  
The lead machine will always be started first. When the lead  
machine is at its full available capacity, start-up delay (confi-  
gurable) is initialised on the follower. When this delay has  
expired, and if the error on the control point is greater than 1.7°C,  
the follower unit is authorised to start and the pump is activated.  
The follower will automatically use the master unit active set-  
point. The lead machine will be held at its full available capa-  
city for as long as the active capacity on the follower is not  
zero. When the follower unit receives a command to stop, its  
evaporator water pump is turned off with 20 seconds delay.  
This function does not require an additional board. It prevents  
high pressure a break on a circuit by the following means:  
Preventing any capacity increase on the circuit once the  
high pressure value has reached an initial threshold.  
Shedding one or more capacity stages once a second  
protection threshold has been reached.  
In the event of capacity stages being shed, no capacity increase  
will be authorised on the circuit concerned for a period of 5  
minutes.  
In the event of a communication fault between the two units,  
each shall return to an autonomous operating mode until the  
fault is cleared. If the master unit is halted due to an alarm, the  
slave unit is authorised to start without prior conditions.  
5.18 - Pumping down  
When the lead compressor in each circuit is started or stopped,  
that circuit goes through a pumping down cycle to purge the  
evaporator and suction line of refrigerant. The maximum  
duration of this cycle is 3 minutes.  
5.20 - Controlling Pro-Dialog Plus units with a System  
Manager  
5.19 - Master/slave assembly  
Up to eight PRO-DIALOG Plus units (or System Manager  
compatible units) can be controlled by one control module of  
the FSM or CSM III type which can handle multi-tasking of  
control functions such as starting units in sequence.  
Two PRO-DIALOG Plus units can be linked to produce a master/  
slave assembly. The two machines are interconnected over the  
CCN bus. All parameters required for the master/slave function  
must be configured through the Service configuration menu.  
Master/slave operation requires the connection of a temperature  
probe at the common manifold on each machine, if the heat  
exchanger leaving water temperature is controlled.  
The master/slave assembly can operate with constant or variable  
flow. In the case of variable flow each machine must control its  
own water pump and automatically shut down the pump, if the  
cooling capacity is zero. For constant flow operation the pumps  
for each unit are continuously operating, if the system is opera-  
ting. The master unit can control a common pump that will be  
activated, when the system is started. In this case the slave unit  
pump is not used.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.21 - Optional heat reclaim module  
6 - DIAGNOSTICS - TROUBLESHOOTING  
6.1 - General  
Change-over procedure from cooling mode to heat reclaim  
mode:  
Start-up of the condenser pump  
The PRO-DIALOG Plus control system has many fault tracing  
aid functions. The local interface and its various menus give  
access to all unit operating conditions. The test function makes  
it possible to run a quick test of all devices on the unit. If an  
operating fault is detected, an alarm is activated and an alarm  
code is stored in the Alarm menu.  
Verification of the condenser flow switch control contact.  
If this remains open after one minute of condenser pump  
operation, the circuit remains in cooling mode and alarm  
79 for circuit A (alarm 80 for circuit B) will be activated.  
As soon as the saturated condensing temperature reaches  
30°C, the pumpdown sequence is activated.  
Pumpdown: closing of the cooling mode coil shutoff valve.  
Opening of the drain valve, closing of the EXV valve.  
When the pumpdown pressure reaches the end of the  
pumpdown threshold, the pumpdown valve is closed and  
the heat reclaim function is effective.  
6.2 - Displaying alarms  
The alarm LEDs on the summary interface (see section 4.1)  
give a quick display of the status of each circuit and the unit as  
a whole.  
A flashing LED shows that the circuit is operating but  
there is an alarm.  
A steady LED shows that the circuit has been shut down  
due to a fault.  
The Alarm menu on the main interface displays up to 5 fault  
codes that are active on the unit.  
6.3 - Resetting alarms  
When the cause of the alarm has been corrected the alarm can  
be reset, depending on the type, either automatically on return  
to normal, or manually when action has been taken on the unit.  
Alarms can be reset even if the unit is running.  
This means that an alarm can be reset without stopping the  
machine. In the event of a power supply interrupt, the unit  
restarts automatically without the need for an external com-  
mand. However, any faults active when the supply is inter-  
rupted are saved and may in certain cases prevent a circuit or a  
unit from restarting.  
A manual reset must be run from the main interface using the  
following procedure:  
RESET OF ACTIVE ALARMS  
OPERATION  
ITEM NUMBER  
ITEM VALUE  
PRESS MENU  
2-DIGIT DISPLAY 4-DIGIT DISPLAY BUTTON LED  
Hold down the MENU  
button until the LED  
for alarms lights. The  
4-digit display shows  
the number of active  
alarms (2 in this  
0
0
0
0
2 ALArM  
example).  
Press the Enter button  
until "rESEt ALARrM"  
is shown in the 4-digit  
display.  
rESEt ALArM  
Press the Enter button  
again to validate the  
reset. "Good" is dis-  
played for 2 seconds  
then, "2 ALArM" and  
then, "no ALArM".  
Good  
then, 2 AL  
then, no ALArM  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4 - Alarm codes  
The following list gives a complete description of each alarm  
code and its possible cause.  
ALARM CODE DESCRIPTIONS  
Code  
Alarm name  
Description  
Action  
Pumpdown Reset type  
Probable cause  
1
Evaporator leaving water thermistor fault  
Thermistor outside range  
Unit shut down  
Yes  
Auto  
Thermistor or wiring fault or  
bad connection  
2
3
Evaporator entering water thermistor fault  
Condenser leaving water thermistor fault  
Ditto  
Ditto  
Unit shut down  
Yes  
Yes  
Auto  
Auto  
Ditto  
Ditto  
Heating mode: Unit shut down,  
if control on leaving water.  
Cooling mode: no action  
4
5
Condenser entering water thermistor fault  
Heat reclaim entering water thermistor fault  
Ditto  
Ditto  
Heating mode: Unit shut down,  
if control on entering water.  
Cooling mode: no action  
-
-
Auto  
Auto  
Ditto  
Ditto  
Unit with heat recalaim option:  
heat reclaim mode shut down,  
unit changes over to standard  
cooling mode. If not: no action  
6
7
Heat reclaim leaving water thermistor fault  
Outdoor temperature sensor fault  
Ditto  
Ditto  
None  
-
-
Auto  
Ditto  
Reset: normal setpoint used.  
Limitation or reset deactivated.  
Auto, if temp. mea- Thermistor faulty  
sured by sensor  
returns to normal  
8
CHWS (master/slave) fluid thermistor fault  
Suction thermistor fault, compressor A1  
Suction thermistor fault, compressor B1  
External 0-10 V dc signal fault  
Ditto  
Deactivated  
-
Ditto  
Auto  
Auto  
Auto  
Themistor faulty  
9
Ditto  
Circuit A shut down  
Circuit B shut down  
Yes  
Yes  
No  
Ditto  
10  
11  
Ditto  
Ditto  
Reset signal outside range  
Reset: normal setpoint used  
Signal incorrect, wiring error  
Limitation or reset deactivated  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
Discharge pressure sensor fault, circuit A  
Discharge pressure sensor fault, circuit B  
Suction pressure sensor fault, circuit A  
Suction pressure sensor fault, circuit B  
Oil pressure sensor fault, compressor A1  
Oil pressure sensor fault, compressor B1  
Oil pressure sensor fault, compressor A2  
Oil pressure sensor fault, compressor B2  
Oil pressure sensor fault, compressor A3  
Oil pressure sensor fault, compressor B3  
Oil pressure sensor fault, compressor A4  
Oil pressure sensor fault, compressor B4  
Pumpdown pressure sensor fault, circuit A  
Voltage transmitted by incorrect sensor Circuit A shut down  
Yes  
Yes  
No  
No  
No  
No  
-
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Sensor fault or wiring error  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Circuit B shut down  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Circuit A shut down  
Circuit B shut down  
Circuit A shut down  
Circuit B shut down  
Compressor A2 shut down  
Compressor B2 shut down  
Compressor A3 shut down  
Compressor B3 shut down  
Compressor A4 shut down  
Compressor B4 shut down  
-
-
-
-
-
If circuit is in heat reclaim  
mode, it goes to cooling mode.  
If not, no action  
-
Auto, if press. mea-  
sured by sensor  
returns to normal  
25  
26  
Pumpdown pressure sensor fault, circuit B  
Ditto  
Ditto  
-
Ditto  
Auto  
Ditto  
Loss of communication with compressor board A1  
Communication with the compressor  
board is lost  
Circuit A shut down  
No  
Wiring fault, faulty module,  
incorrect module address  
27  
28  
29  
30  
31  
32  
33  
34  
Loss of communication with compressor board A2  
Loss of communication with compressor board A3  
Loss of communication with compressor board A4  
Loss of communication with compressor board B1  
Loss of communication with compressor board B2  
Loss of communication with compressor board B3  
Loss of communication with compressor board B4  
Loss of communication with EXV board  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Compressor A2 shut down  
Compressor A3 shut down  
Compressor A4 shut down  
Circuit B shut down  
No  
No  
No  
No  
No  
-
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Compressor B2 shut down  
Compressor B3 shut down  
Compressor B4 shut down  
Unit shut down  
-
No  
Wiring bus faulty, incorrect  
address or board faulty  
35  
36  
Loss of communication with NRCP board  
Loss of communication with fan board 1  
The board does not respond  
Ditto  
Unit shut down, if heat reclaim mode No  
is selected  
Auto, if board is  
again detected  
NRCP board faulty  
Unit shut down, if the number of  
fan stages per circuit is less than 3.  
If not, circuit A shut down  
No  
Auto  
Wiring bus faulty, incorrect  
address or board faulty  
37  
38  
Loss of communication with fan board 2  
Ditto  
Ditto  
Circuit B shut down  
No  
No  
Auto  
Auto  
Ditto  
Loss of communication with 4xAI - 2xAO board 1  
Unit shut down or no action  
Ditto, depending on  
configuration  
39  
40  
Loss of communication with 4xAI - 2xAO board 2  
Pumpdown fault, circuit A  
Ditto  
Compressors or circuit shut down  
Circuit A shut down  
No  
No  
Auto  
Ditto, depending on  
configuration  
End of pumpdown conditions not  
satisfied  
Manual  
Manual  
EXV or sensor faulty  
41  
42  
Pumpdown fault, circuit B  
Evaporator frost protection  
Ditto  
Circuit B shut down  
Unit shut down  
No  
No  
Ditto  
Unit operating: units shut down if  
temp. < defrost threshold.  
Auto first time,  
then manual  
Low water flow or  
thermistor defective  
Unit shut down: if temp < threshold  
and evaporator heater on for more  
than 10 mins.  
43  
44  
Low evaporator water flow rate.  
Low suction temperature, circuit A  
Unit shut down  
No  
No  
Manual  
Manual  
Water pump faulty  
Circuit operating: saturated suction  
temp. < defrost threshold and < leaving  
water -16°C for more than 10 mins.  
Circuit A shut down  
Low charge, filter dirty  
ot thermistor faulty  
45  
46  
47  
48  
Low suction temperature, circuit B  
High suction overheat, circuit A  
High suction overheat, circuit B  
Low suction overheat, circuit A  
Ditto  
Circuit B shut down  
Circuit A shut down  
Circuit B shut down  
Circuit A shut down  
No  
Manual  
Manual  
Manual  
Manual  
Ditto  
Ditto  
Ditto  
EXV fully open  
Ditto  
Yes  
Yes  
Yes  
EXV in min. position, and circuit  
superheat below superheat setpoint  
-5.5 K, saturated suction temp. above  
MOP for 5 mins.  
EXV or thermistor or  
transducer defective  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALARM CODE DESCRIPTIONS  
Code Alarm name  
Description  
Action  
Pumpdown  
Reset type  
Manual  
Probable cause  
49  
50  
Low suction overheat, circuit B  
Low oil pressure, compressor A1  
Circuit B shut down  
Circuit A shut down  
Yes  
No  
Ditto  
Oil pressure < min. threshold  
Manual  
Compressor, crankcase  
heater, pressure sensor or  
EXV faulty, refrigerant  
charge too high, low oil  
charge  
51  
52  
53  
54  
55  
56  
57  
58  
Low oil pressure, compressor B1  
Low oil pressure, compressor A2  
Low oil pressure, compressor B2  
Low oil pressure, compressor A3  
Low oil pressure, compressor B3  
Low oil pressure, compressor A4  
Low oil pressure, compressor B4  
Evaporator water flow control fault  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Circuit B shut down  
No  
Manual  
Manual  
Manual  
Manual  
Manual  
Manual  
Manual  
Manual  
Ditto  
Compressor A2 shut down  
Compressor B2 shut down  
Compressor A3 shut down  
Compressor B3 shut down  
Compressor A4 shut down  
Compressor B4 shut down  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
Ditto  
1. Interlock not closed before end  
of start-up delay  
2. Pump shut down for 2 mins  
and water flow contact closed  
Unit shut down.  
Pump shut down  
No  
No  
Evaporator water flow fault  
59  
Low pressure fault, circuit A  
Circuit operating, and suction pressure Circuit A shut down  
below permitted threshold for more  
than 3 mins.  
Auto first time,  
then manual*  
Low refrigerant charge, EXV  
faulty or filter dirty  
60  
61  
Low pressure fault, circuit B  
Ditto  
Circuit B shut down  
None  
No  
No  
Ditto  
Auto  
Ditto  
Repeated high pressure load sheds, circuit A  
More than 6 successive capacity load  
sheds in the circuit due to exceeded  
high pressure  
Transducer faulty, condenser  
ent. air temp., evaporator ent.  
water temp. too high, cond.  
blocked or fan flow rate too  
low  
62  
63  
Repeated high pressure load sheds, circuit B  
Ditto  
Ditto  
Ditto  
Ditto  
High pressure switch not reset or reverse compressor The high pressure switch has not been Circuit A shut down  
rotation, circuit A  
No  
No  
Manual  
The high pressure switch has  
not been reset, poor electrical  
connection of lead compr.  
reset after a high pressure cut-out,  
or the lead compressor does not work  
64  
65  
66  
High pressure switch not reset or reverse compressor Ditto  
rotation, circuit B  
Circuit B shut down  
Manual  
Manual  
Auto  
Ditto  
Control box thermostat fault  
Sensor overheat  
Unit shut down  
Control box poorly  
ventilated  
Loss of communication with System Manager  
Units controlled by SM, and  
communication with the module over  
2 mins. faulty  
Unit operates in autonomous mode  
CCN network fault  
67  
68  
Loss of communication with the master or slave  
Master/slave configuration error  
Master/slave connection interrupted  
beween the two units for more than  
2 mins.  
Unit operates in autonomous mode  
Master/slave control not allowed  
Auto  
CCN network fault  
Poor master/slave configuration  
Auto/manual in  
case of heating/  
cooling fault  
Master/slave configuration  
fault  
69  
70  
Initial factory configuration necessary  
All factory parameters are at zero  
Poor factory configuration  
Unit prevented from starting  
Ditto  
Auto  
Ditto  
No factory configuration  
Factory configuration error  
Poor factory configuration.  
1. Compr. A3 configured and A2 absent  
2. Compr. A4 configured and A2 or A3 absent  
3. No lead compr. in circuit B  
4. Compr. B3 configured and B2 absent  
5. Compr. B4 configured and B2 or B3 absent  
6. Difference of compressors in circ. A and B too high  
7. Fan configured for a water-cooled condenser  
8. No fans configured  
9. Heat reclaim option configured, and heat reclaim  
sensors not configured  
71  
72  
73  
CCN/Clock Board fault  
The CCN/Clock Board is no longer  
detected  
Unit shut down  
No  
No  
No  
Auto, if the board CCN/Clock Board faulty  
is again detected  
Emergency stop  
An emergncy stop commend has been Unit shut down  
transmitted by the CCN network.  
CCN  
CCN network command  
Pump No. 1 fault  
Evaporator water pump operating  
contact open, when the pump has  
received a commmand to operate.  
Unit shut down  
Manual  
Pump overheat or poor  
pump connection  
74  
75  
Pump No. 2 fault  
Ditto  
Unit shut down  
No  
No  
Manual  
Auto  
Ditto  
Condenser anti-freeze protection, circuit A  
Saturated temperature is under the  
frost cut-out point  
Unit shut down. Condenser pump  
started, if unit is shut down  
Discharge pressure trans-  
ducer faulty, refrigerant leak,  
or low cond. water temp.  
76  
77  
Condenser anti-freeze protection, circuit B  
Lack of water flow, condenser  
Ditto  
Ditto  
No  
No  
Auto  
Ditto  
Water flow switch (water-cooled units) Unit shut down  
not closed for 1 min.  
Manual  
Condenser pump, low water  
flow, water flow switch  
78  
79  
Condenser water flow fault, heat reclaim mode  
Heat reclaim mode fault, circuit A  
Ditto  
Units stays in cooling mode  
No  
No  
Manual  
Manual  
Manual  
Ditto  
More than two consecutive pumpdown Circuit A stays in cooling mode  
sequences not successful  
Leak or heat reclaim or drain  
solenoid shut-off valve fault  
80  
81  
Heat reclaim mode fault, circuit B  
High pressure fault, circuit A  
Ditto  
Circuit B stays in coolng mode  
No  
No  
Ditto  
Circuit operating and discharge pressure Unit shut down  
exceeds the high pressure cut-out point  
Manual, the high Fan circuit fault, air or  
pressure command condenser temperature too  
must be reset  
high  
manually by the  
button on the HP  
pressure switch  
82  
83  
High pressure fault, circuit B  
Ditto  
Ditto  
None  
No  
Ditto  
Ditto  
Maintenance alert  
A maintenance alert is active  
Manual  
1. Charge too low  
2. Water loop too low  
3. Air filter maintenance delay elapsed  
4. Pump 1 maintenance delay elapsed  
5. Pump 2 maintenance delay elapsed  
6. Water filter maintenance delay elapsed  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DGT (only for units with low-temperature option):  
The discharge gas thermostat detects and protects the  
compressor against abnormally high discharge temperatures.  
6.4.1 - Compressor faults  
6.4.1.1 - General  
Each compressor is protected against multiple faults by two  
digital inputs located on the control board. If one of these  
inputs opens, it causes an immediate shutdown on the  
compressor without any action from the basic board.  
Starter Guard:  
This board patented by Carrier (also called AM board)  
monitors both the compressor regime and the status of its  
crankcase heaters which ensure correct lubrication when the  
compressor starts.  
6.4.1.2 - Compressor protection devices  
On PRO-DIALOG Plus units, compressors are individually  
protected by the following devices connected to the digital  
inputs on the compressor control board:  
ALARM CODE DESCRIPTIONS  
Code Alarm name  
Action  
Pumpdown  
Reset type  
Manual  
Ditto  
Probable cause  
101  
102  
DGT fault, compressor A1  
Circuit A shut down  
Circuit A shut down  
No  
No  
Hot gas thermostat contact open  
Starter Guard fault compressor A1  
Crankcase heater fault and open motor current  
fault detection board contact  
201  
202  
DGT fault, compressor A2  
Compressor A2 shut down  
Compressor A2 shut down  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor A 2  
Crankcase heater fault and open motor current  
fault detection board contact  
301  
302  
DGT fault, compressor A3  
Compressor A3 shut down  
Compressor A3 shut down  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor A 3  
Crankcase heater fault and open motor current  
fault detection board contact  
401  
402  
DGT fault, compressor A4  
Compressor A4 shut down  
Compressor A4 shut down  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor A 4  
Crankcase heater fault and open motor current  
fault detection board contact  
501  
502  
DGT fault, compressor B1  
Circuit B shut down  
Circuit B shut down  
No  
No  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor B1  
Crankcase heater fault and open motor current  
fault detection board contact  
601  
602  
DGT fault, compressor B2  
Compressor B2 shut down  
Compressor B2 shut down  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor B 2  
Crankcase heater fault and open motor current  
fault detection board contact  
701  
702  
DGT fault, compressor B3  
Compressor B3 shut down  
Compressor B3 shut down  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor B3  
Crankcase heater fault and open motor current  
fault detection board contact  
801  
802  
DGT fault, compressor B4  
Compressor B4 shut down  
Compressor B4 shut down  
Ditto  
Ditto  
Hot gas thermostat contact open  
Starter Guard fault compressor B4  
Crankcase heater fault and open motor current  
fault detection board contact  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Order No. 13040-76, 05.2000. Supersedes order No.: New  
Manufactured by: Carrier S.A., Montluel, France.  
Manufacturer reserves the right to change any product specifications without notice.  
Printed in the Netherlands on totally chlorine-free paper.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Switch FSU234ea User Manual
Bertazzoni Ventilation Hood KIN 36 PRO X User Manual
Blaupunkt Car Stereo System RCR 128 User Manual
Blomberg Clothes Dryer TKF 8451 A 50 User Manual
Bowers Wilkins Portable Speaker CCM20 User Manual
Campbell Hausfeld Nail Gun IFN102 User Manual
Canon Fax Machine H12251 User Manual
Char Broil Gas Grill 466231203 User Manual
Chauvet Power Supply CH 202B User Manual
Chief Manufacturing Indoor Furnishings KSY220 User Manual