WEATHERMASTER®
48P2,P3,P4,P5030-100
Single Package Gas Heating and Electric Cooling Units
with Direct Spark Ignition and COMFORTLINK™ Controls
Installation Instructions
For additional information and service instructions, refer to
the Controls and Troubleshooting literature.
A factory-installed optional integral economizer and high-
capacity power exhaust is available on size 075-100 units.
A factory-installed optional return fan is available on size
075-100 units.
The staged gas control (SGC) option adds the capability to
control the rooftop unit’s gas heating system to a specified
supply-air temperature set point for purposes of tempering a
cool mixed-air condition.
CONTENTS
Page
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-68
Step 1 — Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 3 — Roof Mount Unit. . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Slab Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 5 — Install Curb Gasketing. . . . . . . . . . . . . . . . . . 2
Step 6 — Install Field-Fabricated Ductwork . . . . . . 2
Step 7 — Rig Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 8 — Connect Condensate Drain. . . . . . . . . . . . 16
Step 9 — Install Outdoor Hoods (Units without
Optional High-Capacity Power Exhaust). . . . . . 32
• UNIT SIZES 030-050
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
• UNIT SIZES 055-100
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes, including ANSI (American Nation-
al Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
Step 10 — Install Economizer Hoods (Units with
Optional High-Capacity Power Exhaust). . . . . . 33
• INSTALL SMALL HOODS
• INSTALL LARGE HOODS
Step 11 — Route Field Wiring . . . . . . . . . . . . . . . . . . . 35
• UNIT SIZES 030-060
• UNIT SIZES 070-100
Step 12 — Make Field Electrical Connections . . . 35
• POWER WIRING
Step 13 — Connect Air Pressure Tubing . . . . . . . . 58
• VARIABLE FRQUENCY DRIVE
• MODULATING POWER EXHAUST
• RETURN FAN POWER EXHAUST
WARNING
Step 14 — Remove Supply-Fan Shipping
Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Step 15 — Remove Optional Return-Fan
Shipping Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Step 16 — Connect Gas Piping. . . . . . . . . . . . . . . . . . 61
Step 17 — Configure Optional Staged Gas
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Step 18 — Install Flue/Inlet Hoods and Baffles . . 62
Step 19 — Install Supply-Air Thermistors
(Staged and Modulating Gas Units Only) . . . . . 62
Step 20 — Install Optional Motormaster® V
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Step 21 — Install Unit Accessories. . . . . . . . . . . . . . 68
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electri-
cal switch; do not use any phone in your building. Immedi-
ately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions. If you cannot reach
your gas supplier, call the fire department.
CONTROLS INSTALLATION . . . . . . . . . . . . . . . . . . 68-76
Constant Volume Units. . . . . . . . . . . . . . . . . . . . . . . . . . 68
• CONTROL WIRING
Variable Air Volume (VAV) Units . . . . . . . . . . . . . . . . . 68
Optional and Accessory Control Wiring . . . . . . . . . 68
Carrier Comfort Network® (CCN) Interface. . . . . . . 73
Optional UPC Open Installation . . . . . . . . . . . . . . . . . 74
Smoke Control Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . 74
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information, con-
sult a qualified installer, service agency, or the gas supplier.
GENERAL
This installation instruction contains basic unit installation
information, including installation of thermostats and remote
temperature sensors.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480079-01 Printed in U.S.A. Form 48P-4SI Pg 1 11-10 Replaces: 48P-3SI
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1A — Physical Data 48P2,P3,P4,P5030-050
BASE UNIT
48P2,P3,P4,P5030
48P2,P3,P4,P5035
NOMINAL CAPACITY (tons)
30
35
OPERATING WEIGHT (lb)
Base Unit
Standard Chassis
Extended Chassis
Standard Chassis
Extended Chassis
Low Heat
5310
5440
5810
5940
5410
5540
5910
6040
High Heat
With Economizer
Low Heat
5610
5740
6110
6240
5710
5840
6210
6340
High Heat
COMPRESSORS
Scroll
Quantity...Type
1...ZP154/1...ZP154
1...ZP182/1...ZP182
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
110
2
110
2
REFRIGERANT
R-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
15.4/14.8
15.4/24.9
18.4/17.7
18.4/27.8
18.4/17.6
18.4/27.7
N/A
Standard Evaporator with Humidi-MiZer®
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with Humidi-MiZer
N/A
CONDENSER COILS
Quantity
Total Face Area (sq ft)
Aluminum Novation® Heat Exchanger with Microchannel Coils
1
1
33.3
33.3
EVAPORATOR COILS
Quantity
1
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
32.1
TXV...1
3...15.0
4...15.0
Double Wavy
Cross Hatched
Fin Type
Tube Type
Double Wavy
Cross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
4...15.0
Double Wavy
Cross Hatched
N/A
N/A
N/A
Fin Type
Tube Type
HEATING SECTION
Low Heat
7
High Heat
14
Low Heat
7
High Heat
14
Number of Heat Exchangers
Input (MBtuh)
325
650
325
650
Output (MBtuh) (Vertical/Horizontal)
Temperature Rise Range (F)
Efficiency (%) (Vertical/Horizontal)
Burner Orifice Diameter
Quantity (in. ...drill no.)
Manifold Pressure (in. wg)
Line Pressure (in. wg) (min...max)
Firing Stages
263/260
10-40
81/80
527/520
25-55
81/80
263/260
10-40
81/80
527/520
25-55
81/80
7 (.1285...30)
14 (.1285...30)
7 (.1258...30)
14 (.1258...30)
3.5
3.5
3.5
3.5
5.0...13.0
5.0...13.0
5.0...13.0
5.0...13.0
2
1
2
2
2
1
2
2
Number of Gas Valves
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Propeller Type
2...30
18,000
1.0...1140
2...30
19,500
1.0...1140
Motor Hp...Rpm
SUPPLY FAN
Centrifugal 25 x 25 in.
Nominal Cfm
10,500
15,000
900
10,500
15,000
900
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
111
/
111/
16
16
SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
(Any motor available on any unit)
15
7.5
10
215T
20
25
Motor Frame Size
213T
254T
256T
284T
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency
88.5
91.7
89.5
91.7
91.0
93.0
91.0
93.6
13.7
5.5
91.7
93.6
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Speed (rpm)
Belts Quantity...Type
13.7
13.7
13.7
13.7
3.4
4.3
549
4.9
626
6.5
438
703
830
2...BX60
17.74-14.30
2...5VX630
17.74-14.30
2...5VX630
17.63...14.01
2...5VX630
2...5VX650
16.63...12.87
Center Distance Range (in.)
17.63...14.01
OPTIONAL POWER EXHAUST†
Quantity...Motor Hp
Centrifugal, 18 x 15 in. (Any motor available on any unit)
2...3.0
56HZ
182T
81.0/88.5
11
2...5.0
184T
2...7.5
213T
213T
88.5/91.7
12
2...10
215T
215T
89.5/91.7
12
Motor Frame Size
High Eff
Prem Eff
184T
Efficiency at Full Load (%) High/Premium
Fan Pulley Pitch Diameter (in.)
87.5/89.5
10.4
High Eff
Prem Eff
High Eff
Prem Eff
11.0
10.4
12
12
Motor Pulley Pitch Diameter Range (in.)
4.1-3.1
4.1-3.1
4.1
4.7-3.7
4.7-3.7
4.2
6.0-4.8
6.0-4.8
5.4
7.0-5.8
7.0-5.8
6.4
Motor Pulley Pitch Diameter Factory Setup (in.)
Blower Shaft Diameter at Pulley (in.)
Fan Rpm Range
Factory Setup Fan Rpm
Maximum Allowable Rpm
17/16
17/16
17/16
17/16
500-656
656
621-785
703
1000
717-882
800
1000
854-1000
927
1000
1000
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
8...20 x 25 x 2, 8...20 x 20 x 2
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Bag Filter
Prefilter
6...20 x 24 x 22, 6...20 x 20 x 22
12...16 x 20 x 2, 3...20 x 24 x 2
6...20 x 24 x 22, 6...20 x 20 x 22
12...16 x 20 x 2, 3...20 x 24 x 2
MERV 15 Cartridge Filters with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Cartridge Filter
Prefilter
6...20 x 24 x 12, 6...20 x 20 x 12
12...16 x 20 x 2, 3...20 x 24 x 2
6...20 x 24 x 12, 6...20 x 20 x 12
12...16 x 20 x 2, 3...20 x 24 x 2
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
None
None
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
Aluminum Frame, Permanent
5...20 x 20 x 2
2...20 x 25 x 1
5...20 x 20 x 1
2...20 x 25 x 1
LEGEND
* 460-3-60 only.
MBtuh
TXV
—
—
Btuh in Thousands
Thermostatic Expansion Valve
†See Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1A — Physical Data 48P2,P3,P4,P5030-050 (cont)
BASE UNIT
48P2,P3,P4,P5040
48P2,P3,P4,P5050
NOMINAL CAPACITY (tons)
40
50
OPERATING WEIGHT (lb)
Base Unit
Standard Chassis
Extended Chassis
Standard Chassis
Extended Chassis
Low Heat
5810
5940
6310
6440
6025
6155
6525
6655
High Heat
With Economizer
Low Heat
6110
6240
6610
6740
6325
6455
6825
6955
High Heat
COMPRESSORS
Scroll
Quantity...Type
2...ZP103/1...ZP182
2...ZP120/2...ZP137
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
110
2
110
2
REFRIGERANT
R-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
21.6/26.7
21.6/39.1
35.1/37.2
31.1/49.6
29.4/29.0
29.4/41.4
38.2/36.5
38.2/48.9
Standard Evaporator with Humidi-MiZer®
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with Humidi-MiZer
CONDENSER COILS
Quantity
Total Face Area (sq ft)
Aluminum Novation® Heat Exchanger with Microchannel Coils
2
2
66.7
66.7
EVAPORATOR COILS
Quantity
1
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
45.5
TXV...2
3...15.0
4...15.0
Double Wavy
Cross Hatched
Fin Type
Tube Type
Double Wavy
Cross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
6...16.0
Double Wavy
Cross Hatched
6...16.0
Double Wavy
Cross Hatched
Fin Type
Tube Type
HEATING SECTION
Low Heat
7
High Heat
14
Low Heat
7
High Heat
14
Number of Heat Exchangers
Input (MBtuh)
325
650
325
650
Output (MBtuh) (Vertical/Horizontal)
Temperature Rise Range (F)
Efficiency (%) (Vertical/Horizontal)
Burner Orifice Diameter
Quantity (in. ...drill no.)
Manifold Pressure (in. wg)
Line Pressure (in. wg) (min...max)
Firing Stages
263/260
10-40
81/80
527/520
25-55
81/80
263/260
10-40
81/80
527/520
25-55
81/80
7 (.1285...30)
14 (.1285...30)
7 (.1285...30)
14 (.1285...30)
3.5
3.5
3.5
3.5
5.0...13.0
5.0...13.0
5.0...13.0
5.0...13.0
2
1
2
2
2
1
2
2
Number of Gas Valves
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Propeller Type
3...30
30,000
1.0...1140
4...30
38,000
1.0...1140
Motor Hp...Rpm
SUPPLY FAN
Centrifugal 25 x 25 in.
Nominal Cfm
14,000
20,000
900
14,000
20,000
900
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
111
/
111/
16
16
SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
(Any motor available on any unit)
7.5
10
15
20
25
30*
Motor Frame Size
213T
215T
254T
256T
284T
286T
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency
88.5
91.7
89.5
91.7
91.0
93.0
91.0
93.6
91.7
93.6
13.7
6.5
92.4
93.6
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Speed (rpm)
Belts Quantity...Type
13.7
13.7
13.7
13.7
12.5
3.4
4.3
4.9
626
5.5
703
6.5
438
549
830
910
2...BX60
17.74-14.30
2...5VX630
17.74-14.30
2...5VX630
17.63...14.01
2...5VX630
17.63...14.01
2...5VX650
3...5VX630
16.63...12.87
Center Distance Range (in.)
16.63...12.87
OPTIONAL POWER EXHAUST†
Quantity...Motor Hp
Centrifugal, 18 x 15 in. (Any motor available on any unit)
2...3.0
56HZ
182T
81.0/88.5
11
2...5.0
184T
2...7.5
213T
213T
88.5/91.7
12
2...10
215T
215T
89.5/91.7
12
Motor Frame Size
High Eff
Prem Eff
184T
Efficiency at Full Load (%) High/Premium
Fan Pulley Pitch Diameter (in.)
87.5/89.5
10.4
High Eff
Prem Eff
High Eff
Prem Eff
11.0
10.4
12
12
Motor Pulley Pitch Diameter Range (in.)
4.1-3.1
4.1-3.1
4.1
4.7-3.7
4.7-3.7
4.2
6.0-4.8
6.0-4.8
5.4
7.0-5.8
7.0-5.8
6.4
Motor Pulley Pitch Diameter Factory Setup (in.)
Blower Shaft Diameter at Pulley (in.)
Fan Rpm Range
Factory Setup Fan Rpm
Maximum Allowable Rpm
17/16
17/16
17/16
17/16
500-656
656
621-785
703
1000
717-882
800
1000
854-1000
927
1000
1000
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
8...20 x 25 x 2, 8...20 x 20 x 2
8...20 x 25 x 2, 8...20 x 20 x 2
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Bag Filter
Prefilter
6...20 x 24 x 22, 6...20 x 20 x 22
12...16 x 20 x 2, 3...20 x 24 x 2
6...20 x 24 x 22, 6...20 x 20 x 22
12...16 x 20 x 2, 3...20 x 24 x 2
MERV 15 Cartridge Filters with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Cartridge Filter
Prefilter
6...20 x 24 x 12, 6...20 x 20 x 12
12...16 x 20 x 2, 3...20 x 24 x 2
6...20 x 24 x 12, 6...20 x 20 x 12
12...16 x 20 x 2, 3...20 x 24 x 2
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
None
None
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
Aluminum Frame, Permanent
5...20 x 20 x 2
2...20 x 25 x 1
5...20 x 20 x 1
2...20 x 25 x 1
LEGEND
* 460-3-60 only.
MBtuh
TXV
—
—
Btuh in Thousands
Thermostatic Expansion Valve
†See Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1B — Physical Data 48P2,P3,P4,P5055-070
BASE UNIT
48P2,P3,P4,P5055
48P2,P3,P4,P5060
48P2,P3,P4,P5070
NOMINAL CAPACITY (tons)
55
60
70
OPERATING WEIGHT (lb)
Base Unit
Standard Chassis
Extended Chassis
Standard Chassis
Extended Chassis
Standard Chassis
Extended Chassis
Low Heat
7810
7940
8360
8490
7865
7995
8415
8545
8205
8335
8755
8885
High Heat
With Economizer
Low Heat
8340
8470
8890
9020
8395
8525
8945
9075
8735
8865
9285
9415
High Heat
COMPRESSORS
Scroll
Quantity...Type
2...ZP137/2...ZP137
2...ZP154/2...ZP154
1...ZP54,1...ZP182/1...ZP54,1...ZP182
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
110
2
110
2
110
2
REFRIGERANT
R-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
37.6/37.9
37.6/50.3
46.5/45.8
46.5/58.2
42.2/41.8
42.2/54.2
47.6/46.5
47.6/58.9
43.5/44.8
43.5/57.2
55.4/55.5
55.4/67.9
Standard Evaporator with Humidi-MiZer®
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with
Humidi-MiZer
CONDENSER COILS
Quantity
Total Face Area (sq ft)
Aluminum Novation® Heat Exchanger with Microchannel Coils
2
66.7
2
4
66.7
106.7
EVAPORATOR COILS
Quantity
2
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
61.5
TXV...2
4...15
4...15
Double Wavy
Cross Hatched
4...15
Double Wavy
Cross Hatched
Fin Type
Tube Type
Double Wavy
Cross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
6...16
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
Fin Type
Tube Type
HEATING SECTION
Low Heat
High Heat
21
Low Heat
14
High Heat
21
Low Heat
High Heat
21
Number of Heat Exchangers
Input (MBtuh)
14
650
14
650
975
650
975
975
Output (MBtuh) (Vertical/Horizontal)
Temperature Rise Range (F)
Efficiency (%) (Vertical/Horizontal)
Burner Orifice Diameter
Quantity (in. ...drill no.)
Manifold Pressure (in. wg)
Line Pressure (in. wg) (min...max)
Firing Stages
527/520
10-40
81/80
790/780
20-50
81/80
527/520
10-40
81/80
790/780
20-50
81/80
527/520
10-40
81/80
790/780
20-50
81/80
14 (.1285...30)
21 (.1285...30)
14 (.1285...30)
21 (.1285...30)
14 (.1285...30)
21 (.1285...30)
3.5
3.5
3.5
3.5
3.5
3.5
5.0...13.0
5.0...13.0
5.0...13.0
5.0...13.0
5.0...13.0
5.0...13.0
2
2
2
3
2
2
2
3
2
2
2
3
Number of Gas Valves
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Propeller Type
4...30
4...30
36,600
4...30
36,000
39,000
Motor Hp...Rpm
1.0...1140
1.0...1140
1.0...1140
SUPPLY FAN
Centrifugal 30 x 27.5 in.
Nominal Cfm
17,500
25,000
800
21,000
30,000
800
24,500
30,000
800
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
111
/
111
/
111/
16
16
16
SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
(Any motor available on any unit)
15
20
25
30
40†
Motor Frame Size
254T
256T
284T
286T
S324T
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency
91.0
93.0
91.0
93.6
91.7
93.6
92.4
93.6
93.0
94.5
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Speed (rpm)
Belts Quantity...Type
13.7
13.7
13.7
15.5
16.1
4.5
5.1
651
5.5
703
5.9
6.7
575
711
740
2...5VX1230
48.25-44.00
2...5VX1230
48.25-44.00
2...5VX1230
48.50-44.25
2...5VX1230
48.50-44.25
3...5VX1250
48.25-44.00
Center Distance Range (in.)
OPTIONAL POWER EXHAUST*
Quantity...Motor Hp
Centrifugal, 18 x 15 in. (Any motor available on any unit)
2...5
184T
2...7.5
213T
2...10
215T
Motor Frame Size
Efficiency at Full Load (%) High/Premium
Resulting Fan Rpm
Maximum Allowable Rpm
87.5/89.5
740
88.5/91.7
820
1000
89.5/91.7
920
1000
1000
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Optional)
Quantity...Size (in.)
Bag Filter
Prefilter
6...24 x 24 x 22, 6...24 x 20 x 22
6...24 x 24 x 2, 6...20 x 24 x 2
6...24 x 24 x 22, 6...24 x 20 x 22
6...24 x 24 x 2, 6...20 x 24 x 2
6...24 x 24 x 22, 6...24 x 20 x 22
6...24 x 24 x 2, 6...20 x 24 x 2
MERV 15 Cartridge Filters with
High Velocity Prefilters (Optional)
Quantity...Size (in.)
Cartridge Filter
Prefilter
6...24 x 24 x 12,, 6...24 x 20 x 12
6...24 x 24 x 2, 6...20 x 24 x 2
6...24 x 24 x 12,, 6...24 x 20 x 12
6...24 x 24 x 2, 6...20 x 24 x 2
6...24 x 24 x 12, 6...24 x 20 x 12
6...24 x 24 x 2, 6...20 x 24 x 2
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
4...25 x 16 x 1, 2...20 x 16 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
Aluminum Frame, Permanent
12...16 x 25 x 1, 2...16 x 20 x 1
LEGEND
*See Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
MBtuh
TXV
—
—
Btuh in Thousands
Thermostatic Expansion Valve
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1C — Physical Data 48P2,P3,P4,P5075-100
BASE UNIT
48P2,P3,P4,P5075
48P2,P3,P4,P5090
48P2,P3,P4,P5100
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
75
90
100
Standard
Extended
Chassis
Standard
Extended
Chassis
Standard
Extended
Chassis
Chassis
Chassis
Chassis
Base Unit
Low Heat
9065
9195
9615
9745
9665
9795
10,215
10,345
9685
9815
10,235
10,365
High Heat
With Economizer
Low Heat
9595
9725
10,145
10,275
10,195
10,325
10,745
10,875
10,215
10,345
10,765
10,895
High Heat
COMPRESSORS
Scroll
Quantity...Type
2...ZP82/2...ZP182
3...ZP154,3...ZP154
3...ZP154,3...ZP182
Oil Charge (oz) per Compressor
Number of Refrigerant Circuits
110
2
110
2
110
2
REFRIGERANT
R-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil
43.8/45.0
43.8/57.4
55.1/54.9
55.1/67.3
50.4/51.3
50.4/69.1
61.5/62.9
61.5/80.7
50.8/52.8
50.8/70.6
59.3/62.8
59.3/80.6
Standard Evaporator with Humidi-MiZer®
Alternate High-Capacity Evaporator Coil
Alternate High-Capacity Evaporator with
Humidi-MiZer
CONDENSER COILS
Quantity
Aluminum Novation® Heat Exchanger with Microchannel Coils
4
6
6
Total Face Area (sq ft)
106.7
160.0
160.0
EVAPORATOR COILS
Quantity
2
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
Standard Evaporator Coils
Rows...Fins/in.
61.5
TXV...2
4...15
4...15
4...15
Double Wavy
Cross Hatched
Fin Type
Tube Type
Double Wavy
Double Wavy
Cross Hatched
Cross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.
6...16
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
6...16
Double Wavy
Cross Hatched
Fin Type
Tube Type
HEATING SECTION
Low Heat
High Heat
3
Low Heat
High Heat
3
Low Heat
High Heat
3
Number of Heat Exchangers
Input (MBtuh)
2
2
2
650
975
650
975
650
975
Output (MBtuh) (Vertical/Horizontal)
Temperature Rise Range (F)
Efficiency (%) (Vertical/Horizontal)
Burner Orifice Diameter
527/520
10-40
81/80
790/780
20-50
81/80
527/520
10-40
81/80
790/780
20-50
81/80
527/520
10-40
81/80
790/780
20-50
81/80
Quantity (in. ...drill no.)
7 (.1285...30)
7 (.1285...30)
7 (.1285...30)
7 (.1285...30)
7 (.1285...30)
7 (.1285...30)
Manifold Pressure (in. wg)
Line Pressure (in. wg) (Min...Max)
Number of Gas Valves
3.5
5.0...13.0
2
3.5
5.0...13.0
3
3.5
5.0...13.0
2
3.5
5.0...13.0
3
3.5
5.0...13.0
2
3.5
5.0...13.0
3
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Propeller Type
4...30
6...30
58,000
6...30
39,000
58,000
Motor Hp (ea)...rpm
1.0...1140
1.0...1140
1.0...1140
STANDARD SUPPLY FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
Forward Curved Centrifugal 36 x 30 in.
24,500
30,000
680
29,750
34,000
680
35,000
40,000
680
111
/
111
/
16
111
/
16
16
STANDARD SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
(Any motor available on any unit)
30
40
50
60
Motor Frame Size
S268T
S324T
S36T
S364T
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency
92.4
93.6
93.0
94.5
93.0
94.5
93.6
95.4
18.5
7.1
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
18.5
18.5
18.5
5.3
5.7
539
6.5
615
501
672
4...5VX1320
47.42-44.52
Belts Quantity...Type
Center Distance Range (in.)
3...5VX1320
47.88-45.01
4...5VX1320
47.64-44.76
4...5VX1320
47.42-44.52
ALTERNATE, AIRFOIL FAN
Airfoil
29,750
34,000
1846
Nominal Airflow (cfm)
24,500
30,000
1846
35,000
40,000
1846
Maximum Allowable Airflow (cfm)
Maximum Allowable Wheel Speed (rpm)
Shaft Diameter at Pulley (in.)
211
/
211
/
16
211
/
16
16
ALTERNATE SUPPLY-FAN MOTOR AND DRIVE
Motor Hp
(Any motor available on any unit)
50
30
40
60
75
Motor Frame Size
S268T
S324T
S36T
S364T
365T
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency
92.4
93.6
93.0
94.5
93.0
94.5
8.9
93.6
95.4
94.1
95.4
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
9.7
10.2
8.9
10.8
7.5
8.7
8.1
1593
8.7
11.1
1353
1493
1711
1799
Belts Quantity...Type
Center Distance Range (in.)
2...5VX1150
42.96...45.82
2...5VX1180
42.96...45.57
3...5VX1150
42.96...45.57
3...5VX1150
42.45...45.35
3...5VX1230
42.45...45.35
LEGEND
*See Table 3 — High-Capacity Power Exhaust Data for more information. See
Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
MBtuh — Btuh in Thousands
TXV
—
Thermostatic Expansion Valve
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1C — Physical Data 48P2,P3,P4,P5075-100 (cont)
BASE UNIT
48P2,P3,P4,P5075
48P2,P3,P4,P5090
48P2,P3,P4,P5100
OPTIONAL POWER EXHAUST*
Quantity...Motor Hp
Centrifugal, 18 x 15 in. (Any motor available on any unit.)
2...5
2...7.5
213T
2...10
215T
Motor Frame Size
184T
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency
87.5
89.5
10.6
4.5
88.5
91.7
10.6
5.0
89.5
91.7
10.6
5.6
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
17/16
740
17/16
820
17/16
920
Maximum Allowable Rpm
1000
1000
1000
FILTERS
Standard Efficiency Throwaway
(Standard)
Quantity...Size (in.)
30% and 65% Pleated (Optional)
Quantity...Size (in.)
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
12...20 x 25 x 2, 12...20 x 20 x 2
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)
4...25 x 16 x 1, 2...20 x 16 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
12...16 x 25 x 1, 2...16 x 20 x 1
OPTIONAL ECONOMIZER FILTER
Quantity...Size (in.)
Aluminum Frame, Permanent
12...16 x 25 x 1, 2...16 x 20 x 1
LEGEND
*See Table 3 — High-Capacity Power Exhaust Data for more information. See
Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
MBtuh — Btuh in Thousands
TXV
—
Thermostatic Expansion Valve
Table 2 — Optional Return Fan Physical Data (48P075-100 Only)
BASE UNIT
48P2,P3,P4,P5075-100
RETURN FAN
Plenum Fan, 47.13 in. (Any motor available on any unit.)
1...25 1...30
284T 286T
Quantity...Motor Hp
1...20
256T
1...40
324T
Motor Frame Size
Efficiency at Full Load (%) High/Premium
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
91.0/93.6
8.5
91.7/93.6
9.8
92.4/93.6
8.5
93.0/93.8
8.5
5.3
6.7
6.1
6.7
215
/
215
/
215
/
215
/
16
16
16
16
1104
1447
1209
1447
1271
1447
1396
1447
Maximum Allowable Rpm
Table 3 — Optional High-Capacity Power Exhaust Physical Data (48P075-100 Only)
BASE UNIT
48P2,P3,P4,P5075-100
POWER EXHAUST
Centrifugal, 22 x 20 in., 111
/16 in. shaft diameter (Any motor available on any unit)
Total Hp
20
30
40
2...20
S256T
50
60
Quantity...Motor Hp
2...10
S215T
2...15
D254T
2...25
S284T
2...30
S286T
Motor Frame Size
Efficiency at Full Load (%)
High Efficiency
89.5
91.7
91
93
91
93.6
91.7
93.6
92.4
93.6
Premium Efficiency
Fan Sheave Pitch Diameter (in.)
Motor Sheave Pitch Diameter (in.)
Resulting Fan Rpm
12.4
12.4
5.8
11.1
11.1
11.1
4.8
714
1175
2...BX93
5.9
6.5
6.9
841
1175
2...BX93
928
1020
1094
Maximum Allowable Rpm
Belts — Quantity...Type
1175
2...5VX950
1175
1175
2...5VX950
2...5VX950
Table 4 — Optional Humidi-MiZer® Coil Data
UNIT SIZE 48/50P
Humidi-MiZer Coil Construction
Quantity
030-075
090,100
Aluminum Novation® Coil
1
1
Face Area (sq ft)
26.7
33.3
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Operating Weights of Options and Accessories (lb)
48/50P UNIT SIZE
OPTION OR ACCESSORY
Condenser Section Roof Curb
Economizer
Power Exhaust
Barometric Relief
Double Wall Construction
030,035
—
300*
710*
200
040,050
—
300*
710*
200
055
540
530*
710*
200
900
060
540
530*
710*
200
900
070
625
530*
710*
200
900
075
625
530*
710*
200
900
090
625
530*
710*
200
900
100
625
530*
710*
200
900
700
800
Roof Curb
Standard Length
455
545
—
495
545
—
605
1200
—
605
1200
—
605
—
—
605
—
700
605
—
700
605
—
700
Extended Length
With High-Capacity Power Exhaust
High-Efficiency Filters
Bag Filters and Cartridge Filters
Hail Guard
20
35
120
95
20
35
150
95
20
40
145
115
20
40
145
115
20
40
210
115
20
—
210
115
20
—
210
115
20
—
210
115
Inlet Guide Vanes
Variable Frequency Drive
7.5 hp
10 hp
15 hp
20 hp
25 hp
30 hp
40 hp
50 hp
60 hp
75 hp
20
20
35
35
53
—
—
—
—
—
20
20
35
35
53
—
—
—
—
—
—
—
35
35
53
53
53
—
—
—
—
—
35
35
53
53
53
—
—
—
—
—
35
35
53
53
53
—
—
—
—
—
—
—
—
—
—
—
—
—
—
53
53
53
53
152
—
—
53
53
53
53
152
—
—
53
53
53
53
152
High-Capacity Evaporator Coil
Airfoil Fan
Humidi-MiZer® Adaptive Dehumidification System
150
—
72
300
—
72
300
—
72
300
—
72
300
—
72
300
350
72
300
350
92
300
350
92
*Includes hood.
Table 6 — Supply Fan Drive Data
SHAFT
DIA (in.)
SPEED
(rpm)
MOTOR
SHEAVE
MOTOR
PITCH DIA (in.)
WHEEL
SHEAVE
WHEEL
PITCH DIA (in.)
QUANTITY
...BELT
HP
Sizes 030-050
7.5
10
15
20
25
13/8
438
549
626
703
830
910
2BK36
2B5V42
2B5V48
2B5V54
2B5V64
3B5V64
3.4
4.3
4.9
5.5
6.5
6.5
2B5V136
2B5V136
2B5V136
2B5V136
2B5V136
3B5V124
13.7
13.7
13.7
13.7
13.7
12.5
2...BX60
13/8
15/8
15/8
17/8
17/8
2...5VX630
2...5VX630
2...5VX630
2...5VX650
3...5VX630
30*
Sizes 055-070
15
20
25
30
40
15/8
575
651
703
711
740
2B5V44
2B5V50
2B5V54
2B5V62
3B5V66
4.5
5.1
5.5
6.3
6.7
2B5V136
2B5V136
2B5V136
2B5V154
3B5V160
13.7
13.7
13.7
15.5
16.1
2...5VX1230
2...5VX1230
2...5VX1230
2...5VX1230
3...5VX1250
15/8
17/8
17/8
21/8
Sizes 075-100 (Forward-Curved Fan)
30
40
50
60
17/8
21/8
21/8
23/8
501
539
615
672
3B5V52
4B5V56
4B5V64
4B5V70
5.33
5.74
6.54
7.14
B5V184
B5V184
B5V184
B5V184
18.5
18.5
18.5
18.5
3...5VX1320
4...5VX1320
4...5VX1320
4...5VX1320
Sizes 075-100 (Airfoil Fan)
30
40
50
60
75
17/8
21/8
21/8
23/8
23/8
1353
1493
1593
1711
1799
2B5V74
2B5V86
3B5V80
3B5V86
3B5V110
7.5
8.7
8.1
8.7
11.1
2Q5V97
2Q5V103
3R5V90
3R5V90
3R5V109
9.7
10.2
8.9
8.9
10.8
2...5VX1150
2...5VX1180
3...5VX1150
3...5VX1150
3...5VX1230
*Sizes 040,050 only.
NOTE: Part numbers are Browning Manufacturing Corp. reference.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7 — Power Exhaust Fan Drive Data
MOTOR SHEAVE
BLOWER SHEAVE
48P2,P3 UNITS
48P4,P5 UNITS
MOTOR
SHAFT
FAN
SPEED
RPM
TOTAL MOTOR
Pitch
Pitch
CENTER
DISTANCE
CENTER
DISTANCE
Part
Part
BELTS
QTY...P/N
BELTS
QTY...P/N
HP
QTY...HP DIAMETER
(in.)
Diameter
Number
(in.)
Diameter
Number
(in.)
RANGE (in.)
RANGE (in.)
Sizes 030-050
7
6*
6†
10**
15**
20**
2...3
/
656/500 1VL44
656/500 1VP44L
785/621 1VP50L
882/717 1VP65
1000/854 1VP75
4.1-3.1
4.1-3.1
4.7-3.7
6.0-4.8
7.0-5.8
BK115
BK115
BK110
BK130
BK130
11
11
1...BX71 23.62-26.50 1...BX46 11.40-13.26
1...BX71 23.62-26.50 1...BX46 11.40-13.26
1...BX71 23.62-26.50 1...BX46 11.16-13.05
1...BX77 23.62-26.50 1...BX53 11.40-13.26
1...BX79 23.62-26.50 1...BX53 11.04-12.95
8
2...3
2...5
11/8
11/8
13/8
13/8
10.4
12
2...7.5
2...10
12
Sizes 055-100
10
15
20
2...5
11/8
13/8
13/8
740
820
920
2P3V45
2P3V50
2P3V56
4.5
5.0
5.6
2Q3V106
2Q3V106
2Q3V106
10.6
10.6
10.6
2...3VX71 22.71-26.38 2...3VX50 10.91-13.30
2...3VX71 22.71-26.38 2...3VX50 10.78-13.20
2...3VX75 22.71-26.38 2...3VX50 10.78-13.20
2...7.5
2...10
*High-efficiency motor option.
†Premium-efficiency motor option.
**Applies to both motor options.
NOTE: Part numbers are Browning Manufacturing Corp. reference.
Table 8 — Optional High-Capacity Power Exhaust Fan Drive Data
MOTOR SHEAVE
Part Pitch Diameter
BLOWER SHEAVE
Part Pitch Diameter
MOTOR
SHAFT
TOTAL MOTOR
SPEED
RPM
CENTER DISTANCE
RANGE (in.)
QTY...BELT
HP
QTY...HP
DIA. (in.)
Number
2B5V48
2B5V58
2B5V58
2B5V64
2B5V68
(in.)
4.8
5.8
5.9
6.5
6.9
Number
2B5V124
2B5V124
2B5V110
2B5V110
2B5V110
(in.)
12.4
12.4
11.1
11.1
11.1
20
30
40
50
60
2...10
2...15
2...20
2...25
2...30
1.375
1.625
1.625
1.875
1.875
714
841
928
1020
1094
2...BX93
2...BX93
2...5VX950
2...5VX950
2...5VX950
32.8 to 36.7
32.6 to 36.5
32.6 to 36.5
32.5 to 36.3
32.5 to 36.3
Table 9 — Optional Return Fan Drive Data
MOTOR SHEAVE
BLOWER SHEAVE
MOTOR
TOTAL
HP
MOTOR
QTY...HP
SPEED
RPM
CENTER DISTANCE
RANGE (in.)
Pitch
Pitch
SHAFT
QTY...BELT
Part
Part
Diameter
Number
Diameter
Number
DIA. (in.)
(in.)
(in.)
20
25
30
40
1...20
1...25
1...30
1...40
1.625
1.875
1.875
2.125
1104
1209
1271
1396
3B5V52
3B5V66
3B5V60
3B5V66
5.3
6.7
6.1
6.7
3R5V85
3R5V97
3R5V85
3R5V85
8.5
9.8
8.5
8.5
3...5VX1000
3...5VX1060
3...5VX1030
3...5VX1060
38.1 to 41.0
38.9 to 41.8
38.9 to 41.8
39.9 to 42.8
9
Download from Www.Somanuals.com. All Manuals Search And Download.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
"X"
A
A
CONDENSER
END SUPPORT
4
1
4 REF.
9 3/4"
2
3
"X"-
NO GASKET
DETAIL A-A
Fig. 6 — Gasket Location on Roof Curb (Size 070-100 Units)
5
5
Fig. 7 — Gasket Location — Condenser Section Roof Curb (Size 070-100 Units)
15
Download from Www.Somanuals.com. All Manuals Search And Download.
4
1
3
3
2
Fig. 8 — Gasket Location on Roof Curb (48P075-100 Units with Optional High-Capacity Power Exhaust)
four 0.20-in. engagement holes. Install a drain coupling assem-
bly using screws provided at each secondary drain hole loca-
tion. See Fig. 26. Do not attach any drain coupling assemblies
in the condenser section base rail.
Step 8 — Connect Condensate Drain — There
are a total of five drain connections required on each unit: one
primary drain (on right-hand side of the unit) and four second-
ary drains (two on each side of unit).
Using field-supplied fittings and pipe sections, assemble U-
traps at each secondary drain fitting. See Fig. 27. Provide a
minimum size of ½-in. pipe for secondary drains. Use a trap at
least 4-in. deep for size 030-070 units and 7-in. deep for size
075-100 units. Apply a bead of RTV or similar sealant around
the drain assemblies.
Consult local plumbing codes for direction on joining multi-
ple drain lines. Total size of any combined line does not need
to exceed nominal 2-in. size of primary drain connection.
PRIMARY DRAIN — The primary drain is a 2-in. FPT pipe
connection located on the right-hand side of the unit looking at
the unit from the return air end. See Fig. 12-21. Fig. 22 shows
the additional length of units with an extended chassis.
With field-supplied fittings and pipe sections, plumb the pri-
mary condensate drain to the 2-in. FPT connector on the base
rail. Use a trap height of at least 4-in. for size 030-070 units
and 7-in. for size 075-100 units. See Fig. 23 and 24. Install with
a height dimension of at least 2-in. from the top of the exit pipe
from the trap section to the bottom of the connector. Apply a
bead of RTV or similar sealant around the pipe joint at the con-
nector in the base rail.
Fill the U-traps at the secondary drain locations prior to unit
start-up. Also check the U-traps before each cooling season to
ensure the traps are filled and functioning properly.
SECONDARY
DRAINS
(Units
Installed
on
SECONDARY DRAINS (Units Installed on Steel Beam or
Slab) — There are two secondary drain connections required
on each side of the unit. There are secondary drains on the bot-
tom of the base rail on each side of the unit in the filter section
and on each side of the unit in the supply fan section. There are
labels marking each location on the unit base rail. See Fig. 12-
21. Drain holes will need to be drilled in these locations at the
side of the base rail. The existing secondary drain holes in the
bottom of the base rail must be sealed. Prior to final positioning
of the unit, apply a bead of RTV or similar sealant around each
secondary drain hole in the bottom of the unit base rail. See
Fig. 27. Install the metal seal plates then position the unit into
final location.
Curb) — There are two secondary drain connections on each
side of the unit. See Fig. 25. There are secondary drains on
each side of the unit in the filter section and on each side of the
unit in the supply fan section. There are labels marking each lo-
cation on the unit base rail. See Fig. 12-21.
Locate the four 11/4-in. drain coupling assemblies and
mounting screws (shipped in a bag taped to the basepan in the
supply fan section, located behind the access panel marked
FAN SECTION). The drain couplings are a 10-gage plate with
a 11/4 in. half coupling welded to the plate.
At each secondary drain hole location, there is a 13/8-in.
hole pre-drilled in the bottom of the base rail, surrounded by
16
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
NOTE: Rig with four cables and spread with two 95 inch (2413 MM) spreader bars.
CENTER OF GRAVITY
B
LIFTING LUGS
C
MODEL POSITION
4
WEIGHT
KGS
A
SIZE
UNITS
1,2,3
48P
5
LBS
6019
6169
6710
6925
9220
9275
9615
10665
11265
11285
6149
6299
6840
7055
9350
9405
9745
10795
11395
11415
6519
6669
7210
7425
9770
9825
9825
11215
11815
11835
6649
6799
7340
7555
9900
9955
10295
11345
11945
11965
5519
5669
6210
6425
8230
8285
8625
10265
10865
10885
5819
5969
6510
6725
8780
8835
9175
6019
6169
6710
6925
8780
8835
9175
10815
11415
11435
6319
6469
7010
7225
9330
9385
9725
IN
MM
4334
4342
5035
5113
5814
5803
6215
6429
6628
6603
4310
4319
5012
5090
5816
5805
6218
6462
6657
6637
4753
4768
5456
5534
6164
6151
6575
6775
6976
6944
4726
4742
5431
5507
6166
6153
6564
6808
7005
6978
4043
4049
4727
4807
5401
5392
6362
6354
6562
6535
3867
3863
4576
4665
5885
5874
6287
4456
4475
5151
5228
5741
5731
6725
6722
6932
6899
4237
4244
4961
5050
6226
6214
6625
IN
MM
1164
1164
1164
1164
1164
1164
1021
1021
1054
1054
1164
1164
1164
1164
1164
1164
1021
1021
1054
1054
1164
1164
1164
1164
1164
1164
1021
1021
1054
1054
1164
1164
1164
1164
1164
1164
1021
1021
1054
1054
1164
1164
1164
1164
1164
1164
1021
1021
1054
1054
1164
1164
1164
1164
1164
1164
1021
1164
1164
1164
1164
1164
1164
1021
1021
1054
1054
1164
1164
1164
1164
1164
1164
1164
IN
MM
4227
4227
4707
4707
6541
6541
5563
6495
6495
6495
4227
4227
4707
4707
6541
6541
5563
6495
6495
6495
4867
4867
5288
5288
6939
6939
6355
7132
7132
7132
4867
4867
5288
5288
6939
6939
6355
7132
7132
7132
3762
3762
4305
4305
5347
5347
4483
6495
6495
6495
4227
4227
4707
4707
6541
6541
5563
4402
4402
4945
4945
5288
5288
5123
7132
7132
7132
4867
4867
5288
5288
6939
6939
6355
2,3,4,5
2,3,4,5
2,3,4,5
2,3,4,5
B,D,H
C,E,J
P,R,W
Q,S,X
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
2730
2798
3044
3141
4182
4207
4361
4838
5110
5119
2789
2857
3103
3200
4241
4266
4420
4897
5169
5178
2957
3025
3270
3368
4432
4457
4457
5087
5359
5368
3016
3084
3329
3427
4491
4516
4670
5146
5418
5427
2503
2571
2817
2914
3733
3758
3912
4656
4928
4937
2639
2708
2953
3050
3983
4008
4162
2730
2798
3044
3141
3983
4008
4162
4906
5178
5187
2866
2934
3180
3277
4232
4257
4411
170.6
170.9
198.2
201.3
228.9
228.5
244.7
253.1
260.9
260.0
169.7
170.0
197.3
200.4
229.0
228.5
244.8
254.4
262.1
261.3
187.1
187.7
214.8
217.9
242.7
242.2
258.8
266.7
274.7
273.4
186.1
186.7
213.8
216.8
242.7
242.3
258.4
268.0
275.8
274.7
159.2
159.4
186.1
189.3
212.6
212.3
250.5
250.1
258.4
257.3
152.3
152.1
180.2
183.6
231.7
231.3
247.5
175.4
176.2
202.8
205.8
226.0
225.6
264.8
264.6
272.9
271.6
166.8
167.1
195.3
198.8
245.1
244.7
260.8
45.8
45.8
45.8
45.8
45.8
45.8
40.2
40.2
41.5
41.5
45.8
45.8
45.8
45.8
45.8
45.8
40.2
40.2
41.5
41.5
45.8
45.8
45.8
45.8
45.8
45.8
40.2
40.2
41.5
41.5
45.8
45.8
45.8
45.8
45.8
45.8
40.2
40.2
41.5
41.5
45.8
45.8
45.8
45.8
45.8
45.8
40.2
40.2
41.5
41.5
45.8
45.8
45.8
45.8
45.8
45.8
40.2
45.8
45.8
45.8
45.8
45.8
45.8
40.2
40.2
41.5
41.5
45.8
45.8
45.8
45.8
45.8
45.8
45.8
166.4
166.4
185.3
185.3
257.5
257.5
219.0
255.7
255.7
255.7
166.4
166.4
185.3
185.3
257.5
257.5
219.0
255.7
255.7
255.7
191.6
191.6
208.2
208.2
273.2
273.2
250.2
280.8
280.8
280.8
191.6
191.6
208.2
208.2
273.2
273.2
250.2
280.8
280.8
280.8
148.1
148.1
169.5
169.5
210.5
210.5
176.5
255.7
255.7
255.7
166.4
166.4
185.3
185.3
257.5
257.5
219.0
173.3
173.3
194.7
194.7
208.2
208.2
201.7
280.8
280.8
280.8
191.6
191.6
208.2
208.2
273.2
273.2
250.2
48 P2, P3, P4, P5
Vertical Supply/ Return
Horizontal Supply/ Return
Low Gas Heat
48P
48P
48P
50P
48 P2, P3, P4, P5
Vertical Supply/ Return
Horizontal Supply/ Return
High Gas Heat
48 P2, P3, P4, P5
Vertical Supply/ Return
Horizontal Supply/ Return
Low Gas Heat
Extended Chassis
48 P2, P3, P4, P5
Vertical Supply/ Return
Horizontal Supply/ Return
High Gas Heat
Extended Chassis
2,3
-,A,B,C
-,B,C
50 P2, P3
Vertical Supply/ Return
50P
50P
2,3,4,5
50 P2, P3, P4, P5
Vertical Supply/ Return
Horizontal Supply/ Return
2,3
4,5
H
-
50 P2, P3
Vert Supply/ Return w/ Ext Plenum
50 P4, P5
Horizontal Supply/ Return
50P
2,3
R,S,T,V,W
50 P2, P3
Vertical Supply/ Return
w/ Extended Chassis
50P
50P
2,3,4,5
R,T,V,W
50 P2, P3, P4, P5
Vert, Horz Supply/ Return
w/ Extended Chassis
2,3
4,5
P,Y
R,W
50 P2, P3
Vert Supply/ Return w/ Ext Plenum
w/ Extended Chassis
50 P4, P5
Horizontal Supply/ Return
w/ Extended Chassis
NOTE:
1. Weights do not include economizer or
power exhaust.
a48-8455
48ZZ501077 2.0
Fig. 9 — Rigging Label — Units without Optional Return Fan or High-Capacity Power Exhaust
17
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
NOTE: Rig with four cables and spread with two 95 inch (2413 MM) spreader bars.
CENTER OF GRAVITY
LIFTING LUGS
C
MODEL POSITION
WEIGHT
LBS KGS
A
B
SIZE
UNITS
1,2,3
4
5
IN
MM
IN
MM
IN
MM
50P 2,3,4,5
48P 2,3,4,5
48P 2,3,4,5
-,B,C
50 P2, P3, P4, P5
075 11921 5407 220.1 5590
090 12521 5679 228.4 5800
100 12541 5689 227.8 5786
075 12321 5589 224.6 5706
090 12921 5861 232.6 5908
100 12941 5870 230.4 5853
075 12451 5648 226.9 5764
090 13051 5920 233.7 5936
100 13071 5929 232.9 5915
40.2
41.5
41.5
40.2
41.5
41.5
40.2
41.5
41.5
1021 255.7 6495
1054 255.7 6495
1054 255.7 6495
1021 255.7 6495
1054 255.7 6495
1054 255.7 6495
1021 255.7 6495
1054 255.7 6495
1054 255.7 6495
Vert Supply/Return w/ RE Fan
Horz Supply Vert Return w/ RE Fan
B,D,H
C,E,J
48 P2, P3, P4, P5 Low Gas Heat
Vert Supply/Return w/ RE Fan
Horz Supply Vert Return w/ RE Fan
48 P2, P3, P4, P5 High Gas Heat
Vert Supply/Return w/ RE Fan
Horz Supply Vert Return w/ RE Fan
50P 2,3,4,5 R,T,V,W
50 P2, P3, P4, P5
075 12471 5657 231.7 5885
090 13071 5929 240.1 6098
100 13091 5938 239.2 6075
40.2
41.5
41.5
1021 280.8 7132
1054 280.8 7132
1054 280.8 7132
a48-8456
Vert Sup/Ret, Horz Sup/ Vert Ret
w/ RE Fan, w/ Ext Chassis
48P 2,3,4,5
48P 2,3,4,5
48P 2,3,4,5
48P 2,3,4,5
50P 2,3,4,5
P,R,W
Q,S,X
B,D,H
C,E,J
-,B,C
48 P2, P3, P4, P5 Low Gas Heat
Vert Sup/Ret, Horz Sup/ Vert Ret
w/ RE Fan, w/ Ext Chassis
48 P2, P3, P4, P5 High Gas Heat
Vert Sup/Ret, Horz Sup/ Vert Ret
w/ RE Fan, w/ Ext Chassis
48 P2, P3, P4, P5 Low Gas Heat
Vert Sup/Ret, Horz Sup/Ret
w/ Hi Cap PE
48 P2, P3, P4, P5 High Gas Heat
Vert Sup/Ret, Horz Sup/Ret
w/ Hi Cap PE
075 12871 5838 236.2 6000
090 13471 6110 244.3 6205
100 13491 6119 241.8 6142
075 13001 5897 238.5 6058
090 13601 6169 245.4 6234
100 13621 6178 244.2 6203
075 13499 6123 290.1 7367
090 14097 6394 297.7 7561
100 14119 6404 297.1 7546
075 13629 6182 291.3 7400
090 14227 6453 298.9 7593
100 14249 6463 298.2 7575
40.2
41.5
41.5
40.2
41.5
41.5
40.2
41.5
41.5
40.2
41.5
41.5
1021 280.8 7132
1054 280.8 7132
1054 280.8 7132
1021 280.8 7132
1054 280.8 7132
1054 280.8 7132
1021 312.1 7927
1054 312.1 7927
1054 312.1 7927
1021 312.1 7927
1054 312.1 7927
1054 312.1 7927
50 P2, P3, P4, P5
Vert Sup/Ret, Horz Sup/Ret
w/ Hi Cap PE
075 13099 5942 287.1 7293
090 13697 6213 295.1 7496
100 13719 6223 294.4 7478
40.2
41.5
41.5
1021 312.1 7927
1054 312.1 7927
1054 312.1 7927
48P 2,3,4,5 R,T,V,W
48 P2, P3, P4, P5 Low Gas Heat
Vert Sup/Ret, Horz Sup/Ret
w/ Hi Cap PE w/ Ext Chassis
075 14049 6373 483.5 12280 40.2
090 14647 6644 484.3 12302 41.5
100 14669 6654 493.8 12542 41.5
1021 337.3 8567
1054 337.3 8567
1054 337.3 8567
48P 2,3,4,5
50P 2,3,4,5
P,R,W
Q,S,X
48 P2, P3, P4, P5 High Gas Heat
Vert Sup/Ret, Horz Sup/Ret
w/ Hi Cap PE w/ Ext Chassis
50 P2, P3, P4, P5
Vert Sup/Ret, Horz Sup/Ret
w/ Hi Cap PE w/ Ext Chassis
075 14179 6432 483.5 12280 40.2
090 14777 6703 484.3 12301 41.5
100 14799 6713 493.8 12542 41.5
075 13649 6191 483.5 12281 40.2
090 14247 6462 484.4 12304 41.5
100 14269 6472 493.8 12543 41.5
1021 337.3 8567
1054 337.3 8567
1054 337.3 8567
1021 337.3 8567
1054 337.3 8567
1054 337.3 8567
48ZZ501078 2.0
Fig. 10 — Rigging Label — Units with Optional Return Fan or High-Capacity Power Exhaust
18
Download from Www.Somanuals.com. All Manuals Search And Download.
4
3
2
B
1
A
CORNER WEIGHTS (lb)
A
in.
B
in.
TOTAL
(lb)
48P2,P3,P4,P5 UNITS
SIZE
1
2
3
4
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
2002
2056
1983
2079
2408
2417
2950
3385
3255
3248
2034
2088
2013
2108
2443
2452
2991
3444
3307
3303
1009
1031
1374
1386
2205
2223
2450
2604
2911
2929
1042
1064
1410
1422
2236
2254
2481
2618
2931
2946
1008
1029
1372
1384
2202
2220
1913
2033
2407
2422
1041
1062
1408
1420
2233
2250
1937
2044
2424
2436
2000
2053
1981
2076
2404
2414
2303
2643
2691
2686
2032
2085
2010
2105
2439
2449
2335
2689
2734
2731
6,019
6,169
6,710
6,925
9,220
9,275
9,615
10,665
11,265
11,285
6,149
6,299
6,840
7,055
9,350
9,405
9,745
10,795
11,395
11,415
170 5/8
170 7/8
198 1/4
201 1/4
228 7/8
228 1/2
244 5/8
253 1/8
261
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
No Extended Chassis
41 1
/
/
2
260
41 1
2
169 3/4
170
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
Vertical Supply/Return
Horizontal Supply/Return
High Heat
197 3/8
200 3/8
229
No Extended Chassis
228 1/2
244 3/4
254 3/8
262 1/8
261 1/4
030
035
040
050
055
060
070
075
090
100
030
035
040
050
055
060
070
075
090
100
2166
2223
2148
2244
2558
2567
3117
3551
3419
3409
2197
2253
2177
2272
2592
2602
3158
3610
3471
3463
1096
1114
1460
1471
2331
2349
2541
2747
3048
3070
1130
1148
1496
1508
2361
2379
2623
2761
3068
3086
1094
1112
1458
1469
2328
2346
2023
2145
2521
2538
1129
1147
1494
1506
2358
2376
2048
2156
2537
2552
2163
2220
2145
2241
2554
2563
2434
2773
2827
2819
2194
2250
2174
2269
2589
2598
2466
2818
2870
2864
6,519
6,669
187 1/8
187 3/4
214 3/4
217 7/8
242 5/8
242 1/8
258 7/8
266 3/4
274 5/8
273 3/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
40 1/4
41 1/2
41 1/2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
7,210
7,425
with Extended Chassis
9,770
9,825
10,165
11,215
11,815
11,835
6,649
6,799
186 1/8
186 5/8
213 3/4
216 7/8
242 3/4
242 1/4
258 1/2
268
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
45 7/8
40 1/4
Vertical Supply/Return
Horizontal Supply/Return
High Heat
7,340
7,555
with Extended Chassis
9,900
9,955
10,295
11,345
11,945
11,965
40 1
/
4
275 3/4
274 3/4
41 1/2
41 1/2
CORNER WEIGHTS (lb)
A
in.
B
48P2,P3,P4,P5 UNITS WITH
OPTIONAL HIGH-CAPACITY POWER EXHAUST
TOTAL
(lb)
SIZE
1
2
3
4
in.
075
090
100
075
090
100
4171
4004
4002
4230
4058
4054
3410
3712
3726
2662
3070
3081
3256
3311
3309
3302
3356
3352
13,499
14,097
14,119
13,629
14,227
14,249
290
40 1
/
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
Vertical Supply/Return
Horizontal Supply/Return
High Heat
297 5/8
297 1/8
41 1/42
41 1/2
3424
3730
3745
2673
3084
3097
291 3/8
299
40 1/4
41 1
/
2
298 1/4
41 1/2
075
090
100
075
090
100
6905
6484
6620
6969
6541
6679
984
1534
1409
993
1547
1422
768
1268
1165
776
1280
1176
5391
5362
5474
5441
5409
5523
14,049
14,647
14,669
14,179
14,777
14,799
483 1/2
484 3/8
493 3/4
483 1/2
484 1/4
493 3/4
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat with Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
High Heat with Extended Chassis
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
Fig. 11 — Weight Distribution and Center of Gravity
19
Download from Www.Somanuals.com. All Manuals Search And Download.
4
3
2
B
1
A
CORNER WEIGHTS (lb)
A
in.
B
in.
48P2,P3,P4,P5 UNITS
WITH OPTIONAL RETURN FAN
TOTAL
(lb)
SIZE
1
2
3
4
075
090
100
075
090
100
3470
3327
3302
3543
3377
3370
3449
3745
3782
3449
3767
3785
2693
3097
3127
2693
3115
3130
2709
2751
2730
2766
2793
2787
12,321
12,921
12,941
12,451
13,051
13,071
224 5/8
232 5/8
230 3/8
226 7/8
233 3/4
232 7/8
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
Vertical Supply/Return
Horizontal Supply/Return
High Heat
075
090
100
075
090
100
3609
3467
3437
3681
3517
3505
3618
3906
3948
3620
3928
3951
2825
3230
3264
2826
3248
3267
2818
2867
2842
2874
2908
2898
12,871
13,471
13,491
13,001
13,601
13,621
236 1/4
244 1/4
241 3/4
238 1/2
245 3/8
244 1/4
40 1/4
41 1/2
41 1/2
40 1/4
41 1/2
41 1/2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat with Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
High Heat with Extended Chassis
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
Fig. 11 — Weight Distribution and Center of Gravity (cont)
Locate the four 11/4-in. drain coupling assemblies and
mounting screws (shipped in a bag taped to the basepan in the
supply fan section, located behind the access panel marked
FAN SECTION). The drain couplings are a 10-gage plate with
a 11/4 in. half coupling welded to the plate.
4. Using field-supplied fittings and pipe sections, assemble
U-traps at each secondary drain fitting. See Fig. 24. Pro-
vide minimum size of ½-in. pipe for secondary drains.
Use a trap at least 4-in. deep for size 030-070 units and
7-in. deep for size 075-100 units.
After final positioning of the unit, perform the following
procedure:
5. Apply a bead of RTV or similar sealant around the drain
assemblies.
1. At each of the four secondary drain locations (marked
with labels on the unit base rail), position the drain cou-
pling assembly in the side of the base rail. Mark the
screw holes and the drain hole locations on the base rail.
Consult local plumbing codes for direction on joining multi-
ple drain lines. Total size of any combined line does not need to
exceed nominal 2-in. size of primary drain connection.
Fill the U-traps at the secondary drain locations prior to unit
start-up. Also check the U-traps before each cooling season to
ensure the traps are filled and functioning properly.
2. Drill holes for drain outlet (use 13/8-in. hole saw) and for
the mounting screws (use 3/16-in. drill bit).
3. Install a drain coupling assembly using screws provided
at each secondary drain hole location.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8613
21
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8614
22
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8615
23
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8616
24
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8617
25
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8618
26
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8619
27
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8620
28
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8621
29
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8622
30
Download from Www.Somanuals.com. All Manuals Search And Download.
B
A
AUXILIARY COIL LOCATION (in.)
UNIT
DISTANCE A HEIGHT B
a48457
SIZES
030,035
040,050
055-070
075-100
123.0
156.8
200.4
200.4
6.6
6.6
6.6
6.6
075-100 with High-
Capacity Power Exhaust
279.2
6.6
Fig. 22 — Units with Optional Extended Chassis — Location of Coil Tracks
Fig. 25 — Secondary Condensate Drain
Location (Curb Mount)
Fig. 23 — Primary Drain Connection
a48-8460
a48-8458
2” MIN.
(51 mm)
A
2” MIN.
(51 mm)
A
A = 4-in. (102 mm) min — Sizes 030-070
7-in. (178 mm) min — Sizes 075-100
A = 4-in. (102 mm) min — sizes 030-070
7-in. (178 mm) min — sizes 075-100
Fig. 24 — Slab-Mounted Condensate
Drain Piping Details
Fig. 26 — Curb-Mounted Condensate
Drain Pipe Details
31
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Apply a bead of RTV or similar sealant to corner of econ-
omizer hood at pivot points to prevent water leaks. See
Fig. 29.
a48-8459
OUTDOOR
AIR HOOD
16-GAGE METAL
SEAL PLATE
(FIELD SUPPLIED
FIELD INSTALLED)
BOTTOM OF
BASE RAIL
OUTDOOR
AIR HOOD
Fig. 28 — Outdoor Air Hood Installation
(Sizes 030-050)
Fig. 27 — Secondary Drain Seal Plate
Location (Slab Mount)
Step 9 — Install Outdoor Hoods (Units without
Optional High-Capacity Power Exhaust)
UNIT SIZES 030-050
a48-8461
25% Outdoor-Air Hoods (Units without Economizer
Option) (Fig. 28)
OUTDOOR-AIR HOOD
1. Outdoor-air hoods are shipped bolted to the unit in a ship-
ping position. Remove the 6 screws holding each 25%
outdoor air hood shipping cover in place.
4”
2. Remove the holddown screw from each upper corner of
each hood.
3. Pivot hoods outward (2 hoods).
RTV
(ALL HOODS)
4. Install 17 screws around outside of each hood. (Screws
are in the fastener package taped to the basepan inside the
fan section.)
Fig. 29 — Outdoor-Air and Economizer Hood
5. Apply a bead of RTV or similar sealant to corner of each
hood at pivot points to prevent water leaks. See Fig. 29.
Economizer Hoods (Units with Economizer Option)
(Fig. 30 and 31)
SIDE HOOD
(ROTATE
OPEN)
1. Remove the 4 screws holding each of the 2 economizer
side hoods in place.
2. Pivot hoods outwards (2 hoods).
3. Apply seal strip to vertical flange of hood sides.
4. Install hood sides of hood top using 19 screws (7 each
side, 5 top). Screws are in fastener package located with
the hood sides and seal strip which is taped inside the
unit.
SIDE HOOD
(ROTATE
OPEN)
END HOOD
(FIXED)
5. Apply a bead of RTV or similar sealant to corners of
economizer hoods at pivot points to prevent water leaks.
See Fig. 29.
Fig. 30 — Economizer Outdoor-Air Hood
Installation (Sizes 030-050)
UNIT SIZES 055-100
25% Outdoor-Air Hoods (Fig. 32) — The outdoor-air hoods
are factory installed on the 055-100 units.
SIDE HOOD
(ROTATE
OPEN)
Economizer Hoods (Units with Economizer Option) (Fig. 33-35)
END HOOD
(FIXED)
1. Remove the 6 screws holding each of the 4 economizer
shipping covers in place.
2. Remove the holddown screw from each upper corner of
each economizer hood.
3. Pivot hoods outward (4 hoods).
4. Apply seal strip to vertical flange of hood sides.
5. Install 18 screws (5 each side, 6 top, and 2 bottom)
around the outside of each hood. (Screws are in the fas-
tener package taped to the basepan inside the fan section.)
SIDE HOOD
(ROTATE
OPEN)
POWER EXHAUST (FIXED)
Fig. 31 — Economizer with Power Exhaust
Outdoor-Air Hood Installation (Sizes 030-050)
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 10 — Install Economizer Hoods (Units
with Optional High-Capacity Power
Exhaust) — The economizer uses a total of 4 outdoor
intake hoods, 2 on each side of the unit. See Fig. 36. Two small
hoods (one per side) are factory-installed and are pivoted
inside the unit chassis for shipment. Two large hoods are
shipped in packages located inside the unit. The large hoods
(one on each side) require field assembly and mounting.
INSTALL SMALL HOODS — To install the small econo-
mizer hoods, perform the following procedure:
1. Remove the 10 screws holding each of the small econo-
mizer hood shipping covers in place.
OUTDOOR
AIR HOODS
(FIXED)
2. Pivot hoods outward. (There are a total of 2 hoods.)
3. Apply seal strip to vertical flange of hood sides.
Fig. 32 — 25% Outdoor-Air Hood Location
4. Install 15 screws (4 each side, 7 across top) around the
outside of each hood. Screws are in the fastener package
taped to the basepan inside the fan section.
5. Apply a bead of RTV or similar sealant to corner of econ-
omizer hood at pivot points to prevent water leaks. (See
Fig. 29.)
SIDE HOODS
(ROTATE OPEN)
INSTALL LARGE HOODS — Large hoods are shipped dis-
assembled in the economizer section of the unit behind the
large economizer hood shipping cover. See Fig. 37 for assem-
bly details for large economizer hoods. To install the large
economizer hoods, perform the following procedure:
END HOODS
(FIXED)
1. Remove the 17 screws holding each of the large econo-
mizer hood shipping covers in place.
SIDE HOODS
(ROTATE
OPEN)
2. Remove the packages containing the disassembled large
economizer hoods (total of 2 packages). Each package
contains the following (see Fig. 37 for Item numbers): left
hood side (Item 1), right hood side (Item 2), hood top
(Item 3), hood front (Item 4), top filter flange (Item 5), 4
side filter flanges (Item 6), bottom support (Item 7), front
support (Item 8), 6 filters (Item 9), 9 filter clips (Item 10),
seal strip, and fasteners.
Fig. 33 — Economizer Outdoor-Air Hood
Installation (Sizes 055-100)
SIDE HOODS
(ROTATE OPEN)
3. Place seal strip on backside of bottom support (Item 7)
along entire length of support, covering 6 clearance holes.
4. Attach bottom support piece (Item 7) to unit. Be sure seal
strip is between bottom support and panel on unit.
5. Place seal strip on 3/4-in. flange on both the left and right
hood sides (Items 1 and 2).
6. Attach the side filter flanges (Item 6) to the left and right
hood sides (Items 1 and 2), 2 on each hood side.
END HOODS
(FIXED)
7. Attach left and right hood sides (Items 1 and 2) to unit. Be
sure seal strip is between hood side and unit.
8. Place seal strip on 3/4-in. flange on hood top (Item 3).
9. Attach top filter flange (Item 5) to hood top (Item 3).
10. Attach top hood to unit and to hood sides. Be sure seal
strip is between hood top and unit.
SIDE HOODS
POWER
(ROTATE
EXHAUST (FIXED)
OPEN)
Fig. 34 — Economizer with Power Exhaust
Outdoor-Air Hood Installation (Sizes 055-100)
SIDE HOODS
(ROTATE OPEN)
11. Attach front support (Item 8) between left and right hood
sides.
12. Place seal strip on all filter flanges.
13. Attach filter clips (Item 10) to front and bottom supports
(Items 7 and 8).
14. Install filters (Item 9). Filters are held in place with filter
clips.
15. Attach hood front (Item 4) to hood top and sides.
END HOODS
(FIXED)
16. Apply RTV or similar sealant to 6 places shown in
Fig. 37.
SIDE HOODS
RETURN/
(ROTATE
EXHAUST (FIXED)
OPEN)
Fig. 35 — Economizer with Return
Fan Outdoor-Air Hood Installation
(Units with Optional Return Fan)
33
Download from Www.Somanuals.com. All Manuals Search And Download.
PE VFD
ACCESS DOOR
AUXILIARY
CONTROL BOX
LARGE ECONOMIZER
HOOD LOCATION
EXHAUST
AIR
POWER EXHAUST
ACCESS DOOR
SMALL ECONOMIZER
HOOD LOCATION
LEGEND
PE VFD — Power Exhaust Variable Frequency Drive
Fig. 36 — Economizer Hood Location — Units with High-Capacity Power Exhaust
APPLYRTV INTHE
INDICATED AREAS
ITEM 5
ITEM 3
SEE DETAIL Z
ITEM 6
DETAILZ
SCALE 3:4
ITEM 1
ITEM 8
ITEM 7
ITEM 2
AND BOTH ENDS OF
BOTTOM FILTER ROW
ITEM 10
ITEM 9
ITEM 4
a48-8462
Fig. 37 — Large Economizer Hood Assembly
34
Download from Www.Somanuals.com. All Manuals Search And Download.
terminal block and equipment ground. Maximum wire size is
two (2) 500 MCM (maximum wire size) conductors per pole.
Step 11 — Route Field Wiring
UNIT SIZES 030-060 — Field wiring can be brought into the
unit through the basepan and roof curb or through the corner
post in the side of the unit next to the control box.
Units with Factory-Installed Disconnect — The factory-
installed disconnect is an interlocking, door-type. The discon-
nect handle locks the door when it is in the ON position. The
disconnect handle must be in the OFF position to open the con-
trol box door. The disconnect is located in the control box be-
hind the control box door for all units. See Fig. 42.
All field wiring must comply with NEC and all local codes.
Wire must be sized based on MCA (minimum circuit amps) on
the unit informative plate. See Fig. 43 for power wiring con-
nections to the unit disconnect and equipment ground.
A 31/2-in. FPT coupling for field power and a /4-in. FPT
3
coupling for 24 v control wiring are provided in the basepan.
There are two 7/8-in. pilot holes in the corner post as shown on
the certified drawings. Use these holes as pilot holes for mak-
ing the hole for field-supplied conduit in the corner post for
field power wiring.
CAUTION
QUANTITY...MAXIMUM WIRE SIZE
DISCONNECT SIZE
(MCM)
Use care when drilling near condenser coil. Damage to unit
could result.
250 Amps
400 Amps
600 Amps
1...300
1...600
2...600
If field power wiring is brought through the roof curb, route
wiring out through one of the holes to the field-supplied dis-
connect and then back into the unit through the other hole. See
Fig. 38 and 39 for recommended disconnect location.
If power wiring is brought through the side of the unit, route
wiring from field-supplied disconnect through top hole into
unit.
Operating Voltage — Operating voltage to the compressor
must be within the voltage range indicated on the unit name-
plate. Voltages between phases must be balanced within 2%,
and the current must be balanced within 10%. See Tables 10-25
for unit electrical data.
Use the following formula to determine the percentage of
voltage imbalance.
If control wiring is to be brought in through the side of the
7
unit, a /8-in. diameter hole must be drilled in the corner post
Voltage Imbalance
next to the control box.
UNIT SIZES 070-100 — Field wiring is brought into the unit
through the bottom of the control box. Wiring can be brought
through the roof curb through field-supplied watertight connec-
tions. See Fig. 40.
A 45/32-in. hole for field power wiring and a 7/8-in. hole for
24 v control wiring are provided in the bottom of the control
box. Field-supplied couplings must be used when routing wir-
ing into the control box.
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
455 + 464 + 455
Average Voltage =
3
See Fig. 40 for recommended disconnect location.
Step 12 — Make Field Electrical Connections
1371
=
3
IMPORTANT: Units with VFDs (variable frequency
drives) generate, use, and can radiate radio frequency
energy. If units are not installed and used in accordance
with these instructions, they may cause radio interfer-
ence. They have been tested and found to comply with
limits of a Class A computing device as defined by FCC
(Federal Communications Commission) regulations,
Subpart J of Part 15, which are designed to provide rea-
sonable protection against such interference when oper-
ated in a commercial environment.
=
457
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
7
% Voltage Imbalance = 100 x
457
POWER WIRING — Units are factory wired for the voltage
shown on the unit nameplate. The main terminal block is suit-
able for use with aluminum or copper wires. Maximum wire
size varies according to disconnect size.
Units without Factory-Installed Disconnect — When install-
ing units, provide a disconnect per NEC (National Electrical
Code) of adequate size (MOCP [maximum overcurrent protec-
tion] of unit is on the informative plate). All field wiring must
comply with NEC and all local codes. Size wire based on
MCA (minimum circuit amps) on the unit informative plate.
See Fig. 41 for power wiring connections to the unit power
= 1.53%
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact local utility immediately.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL BOX
RECOMMENDED
FIELD-SUPPLIED
DISCONNECT LOCATION
CAUTION
a48-8463
Use care when drilling into corner post to avoid damage to con-
denser coil.
Fig. 38 — Disconnect Location — Size 030 and 035 Units
CAUTION
a48-8464
Use care when drilling into corner post to avoid damage to con-
denser coil.
Fig. 39 — Disconnect Location — Size 040-060 Units
CONTROL BOX
RECOMMENDED
FIELD-SUPPLIED
DISCONNECT
LOCATION
CAUTION
a48-8465
Use care when drilling into corner post to avoid damage to con-
denser coil.
Fig. 40 — Disconnect Location — Size 070-100 Units
36
Download from Www.Somanuals.com. All Manuals Search And Download.
FACTORY
WIRE
TB1
21
22
11
12
23
22
21
DISCONNECT PER NEC
13
23
DISCONNECT
PER NEC
EQUIP
GND
EQUIP GND
LEGEND
13
12
11
EQUIP — Equipment
GND — Ground
NEC — National Electrical
Code
LEGEND
EQUIP — Equipment
GND
NEC
TB
— Ground
a48-8466
FIELD
WIRE
— National Electrical Code
— Terminal Block
Fig. 43 — Field Power Wiring Connections
for Factory-Installed Disconnect
Fig. 41 — Field Power Wiring Connections
FACTORY-INSTALLED
DISCONNECT
HANDLE LOCATION
FACTORY-INSTALLED
DISCONNECT
(HIDDEN)
a48-8467
Fig. 42 — Factory-Installed Disconnect Location (End of Unit Shown)
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Electrical Data, 48P2,P3,P4,P5030 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FUSE OR
HACR
BRKR*
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
3
5
—
10.6
16.7
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
—
152.8/150.6 200/200
9.6 174.0/169.8 225/200
15.2 186.2/181.0 225/225
22.0 201.2/194.6 250/225
28.0 214.4/206.6 250/250
7 1/2 24.2 / 22.0
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
159.4/156.6 200/200
9.6 180.6/175.8 225/225
15.2 192.8/187.0 225/225
22.0 207.8/200.6 250/250
28.0 221.0/212.6 250/250
10
15
30.8 / 28.0
46.2 / 42.0
59.4 / 54.0
74.8 / 68.0
88.0 / 80.0
11.0
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
174.8/170.6 225/200
9.6 196.0/189.8 225/225
15.2 208.2/201.0 250/250
22.0 223.2/214.6 250/250
28.0 236.4/226.6 250/250
5
7.5 24.2
10 30.8
—
3
6.6
208/230
187
253
1
51.3
300
1
51.3
300
2
—
10.6
16.7
—
190.1/183.3 225/225
(ea)
9.6 211.3/202.5 250/250
15.2 223.5/213.7 250/250
22.0 238.5/227.3 250/250
28.0 251.7/239.3 300/250
20
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
209.3/200.8 250/250
9.6 230.5/220.0 300/250
15.2 242.7/231.2 300/250
22.0 257.7/244.8 300/300
28.0 270.9/256.8 300/300
25
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
225.8/215.8 300/250
9.6 247.0/235.0 300/300
15.2 259.2/246.2 300/300
22.0 274.2/259.8 350/300
28.0 287.4/271.8 350/350
30
5
7.5 24.2
10 30.8
69.6
79.2
84.8
91.6
97.6
—
2
2
2
2
—
3
5
7.5
10
—
4.8
7.6
11.0
14.0
90
100
100
110
110
7 1/2
72.6
82.2
87.8
94.6
100.6
—
2
2
2
2
—
3
5
7.5
10
—
4.8
7.6
11.0
14.0
90
100
110
110
110
10
15
20
25
30
14.0
21.0
27.0
34.0
40.0
79.6
89.2
94.8
101.6
107.6
—
2
2
2
2
—
3
5
7.5
10
—
4.8
7.6
11.0
14.0
100
110
110
110
125
3.3
460
414
508
1
23.1
150
1
23.1
150
2
86.6
96.2
101.8
108.6
114.6
(ea)
—
2
2
2
2
—
3
5
7.5
10
—
4.8
7.6
11.0
14.0
110
110
125
125
125
95.3
104.9
110.5
117.3
123.3
—
2
2
2
2
—
3
5
7.5
10
—
4.8
7.6
11.0
14.0
125
125
125
150
150
102.8
112.4
118.0
124.8
130.8
—
2
2
2
2
—
3
5
7.5
10
—
4.8
7.6
11.0
14.0
125
150
150
150
150
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Electrical Data, 48P2,P3,P4,P5030 Units (cont)
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
FUSE OR
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
(ea)
Hp
(ea)
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
HACR
(ea)
(ea)
(ea)
BRKR*
59.0
66.8
71.2
77.0
81.0
70
80
90
90
100
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
7 1/2
9.0
61.0
68.8
73.2
79.0
83.0
80
80
90
90
100
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
10
11.0
17.0
22.0
27.0
32.0
67.0
74.8
79.2
85.0
89.0
80
90
90
100
100
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
15
2.6
575
518 632
1
19.9
109
1
19.9
109
2
72.5
80.3
84.7
90.5
94.5
90
100
100
110
110
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
(ea)
20
78.8
86.6
91.0
96.8
100.8
100
110
110
110
125
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
25
85.0
92.8
97.2
103.0
107.0
110
110
125
125
125
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
30
LEGEND
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11 — Electrical Data, 48P2,P3,P4,P5035 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER EVAPORATOR FAN
FAN MOTOR MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FUSE OR
HACR
BRKR*
3 PH,
60 Hz
FLA
(ea)
RLA LRA
(ea) (ea)
RLA LRA
(ea) (ea)
Hp
(ea)
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
3
5
—
10.6
16.7
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
—
163.0/160.8
200/200
225/225
250/225
250/250
250/250
225/200
225/225
250/250
250/250
250/250
225/225
250/250
250/250
250/250
300/250
250/225
250/250
250/250
300/250
300/300
250/250
300/250
300/300
300/300
350/300
300/300
300/300
350/300
350/300
350/350
100
110
110
125
125
100
110
110
125
125
110
110
125
125
125
110
125
9.6 184.2/180.0
15.2 196.4/191.2
22.0 211.4/204.8
28.0 224.6/216.8
7 1/2
24.2 / 22.0
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
169.6/166.8
9.6 190.8/186.0
15.2 203.0/197.2
22.0 218.0/210.8
28.0 231.2/222.8
10 30.8 / 28.0
15 46.2 / 42.0
20 59.4 / 54.0
25 74.8 / 68.0
30 88.0 / 80.0
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
185.0/180.8
9.6 206.2/200.0
15.2 218.4/211.2
22.0 233.4/224.8
28.0 246.6/236.8
5
7.5 24.2
10 30.8
—
3
6.6
208/230 187 253
1
55.8 340
1
55.8 340
2
—
10.6
16.7
—
199.1/192.8
(ea)
9.6 220.3/212.0
15.2 232.5/223.2
22.0 247.5/236.8
28.0 260.7/248.8
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
218.3/209.8
9.6 239.5/229.0
15.2 251.7/240.2
22.0 266.7/253.8
28.0 279.9/265.8
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
234.8/224.8
9.6 256.0/244.0
15.2 268.2/255.2
22.0 283.2/268.8
28.0 296.4/280.8
78.1
5
7.5 24.2
10 30.8
—
3
5
7.5
10
—
3
/
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
87.7
93.3
100.1
106.1
81.1
90.7
96.3
103.1
109.1
88.1
97.7
103.3
110.1
116.1
94.2
103.8
109.4
116.2
122.2
102.9
112.5
118.1
124.9
130.9
110.4
120.0
125.6
132.4
7 1/2
11.0
14.0
21.0
27.0
34.0
40.0
10
5
7.5
10
—
3
15
5
7.5
10
—
3
3.3
460
414 508
1
26.9 179
1
26.9 179
2
(ea)
20
5
125
125
125
125
125
150
150
150
150
150
150
150
7.5
10
—
3
25
5
7.5
10
—
3
5
7.5
10
30
138.4
175
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11 — Electrical Data, 48P2,P3,P4,P5035 Units (cont)
COMPRESSOR
VOLTAGE
RANGE
CONDENSER EVAPORATOR FAN
FAN MOTOR MOTOR
POWER EXHAUST
POWER SUPPLY
VOLTAGE
No. A1
No. B1
3 PH,
60 Hz
FLA
(ea)
RLA LRA
(ea) (ea)
RLA LRA
(ea) (ea)
Hp
(ea)
FUSE OR
HACR BRKR*
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
67.5
75.3
79.7
85.5
89.5
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
90
100
100
110
7 1/2
9.0
69.5
77.3
81.7
87.5
91.5
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
100
100
110
110
10
15
20
25
30
11.0
17.0
22.0
27.0
32.0
75.5
83.3
87.7
93.5
97.5
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
100
110
110
110
2.6
575
518 632
1
23.7 132
1
23.7 132
2
80.5
88.3
92.7
98.5
102.5
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
100
110
110
110
125
(ea)
86.4
94.2
98.6
104.4
108.4
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
110
110
125
125
125
92.6
100.4
104.8
110.6
114.6
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
110
125
125
125
125
LEGEND
Full Load Amps
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — Electrical Data, 48P2,P3,P4,P5040 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
3
5
—
10.6
16.7
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
—
174.0/171.8
225/225
250/225
250/250
250/250
250/250
225/225
250/250
250/250
250/250
250/250
250/225
250/250
250/250
300/250
300/300
250/250
250/250
300/250
300/300
300/300
300/250
300/300
300/300
350/300
350/300
300/300
350/300
350/300
350/350
350/350
110
110
125
125
125
110
125
125
125
125
110
125
125
125
150
125
125
9.6 195.2/191.0
15.2 207.4/202.2
22.0 222.4/215.8
28.0 235.6/227.8
7 1/2 24.2 / 22.0
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
180.6/177.8
9.6 201.8/197.0
15.2 214.0/208.2
22.0 229.0/221.8
28.0 242.2/233.8
10
15
20
25
30
7 1/2
10
15
20
25
30
30.8 / 28.0
46.2 / 42.0
59.4 / 54.0
74.8 / 68.0
88.0 / 80.0
11.0
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
196.0/191.8
9.6 217.2/211.0
15.2 229.4/222.2
22.0 244.4/235.8
28.0 257.6/247.8
5
7.5 24.2
10 30.8
—
3
6.6
208/230
187 253
1
55.8
340
2
30.1
225
3
—
10.6
16.7
—
210.1/203.8
(ea)
9.6 231.3/223.0
15.2 243.5/234.2
22.0 258.5/247.8
28.0 271.7/259.8
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
229.3/220.8
9.6 250.5/240.0
15.2 262.7/251.2
22.0 277.7/264.8
28.0 290.9/276.8
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
245.8/235.8
9.6 267.0/255.0
15.2 279.2/266.2
22.0 294.2/279.8
28.0 307.4/291.8
87.9
5
7.5 24.2
10 30.8
—
3
5
7.5
10
—
3
/
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
97.5
103.1
109.9
115.9
90.9
100.5
106.1
112.9
118.9
97.9
107.5
113.1
119.9
125.9
104.0
113.6
119.2
126.0
132.0
112.7
122.3
127.9
134.7
140.7
120.2
129.8
135.4
142.2
14.0
5
7.5
10
—
3
21.0
5
7.5
10
—
3
3.3
460
414 508
1
26.9
179
2
16.7
114
3
(ea)
27.0
5
125
150
150
125
150
150
150
150
150
150
175
175
7.5
10
—
3
34.0
5
7.5
10
—
3
5
7.5
10
40.0
148.2
175
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — Electrical Data, 48P2,P3,P4,P5040 Units (cont)
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
70.8
78.6
83.0
88.8
92.8
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
100
100
110
110
7 1/2
9.0
72.8
80.6
85.0
90.8
94.8
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
100
100
110
110
10
11.0
17.0
22.0
27.0
32.0
78.8
86.6
91.0
96.8
100.8
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
100
110
110
110
110
15
2.6
575
518 632
1
23.7
132
2
12.2
80
3
83.8
91.6
96.0
101.8
105.8
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
100
110
110
125
125
(ea)
20
89.7
97.5
101.9
107.7
111.7
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
110
110
125
125
125
25
95.9
103.7
108.1
113.9
117.9
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
125
125
125
125
125
30
LEGEND
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13 — Electrical Data, 48P2,P3,P4,P5050 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
2
2
2
2
—
3
5
—
10.6
16.7
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
—
225.4/223.2
250/250
250/250
300/300
300/300
300/300
250/250
300/250
300/300
300/300
300/300
250/250
300/300
300/300
300/300
350/300
300/300
300/300
350/300
350/350
350/350
350/300
350/350
350/350
400/350
400/350
350/350
400/350
400/350
400/400
400/400
110
125
125
125
150
110
125
125
150
150
125
125
150
150
150
125
150
9.6 246.6/242.4
15.2 258.8/253.6
22.0 273.8/267.2
28.0 287.0/279.2
7 1/2 24.2 / 22.0
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
232.0/229.2
9.6 253.2/248.4
15.2 265.4/259.6
22.0 280.4/273.2
28.0 293.6/285.2
10
15
20
25
30
7 1/2
10
15
20
25
30
30.8 / 28.0
46.2 / 42.0
59.4 / 54.0
74.8 / 68.0
88.0 / 80.0
11.0
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
247.4/243.2
9.6 268.6/262.4
15.2 280.8/273.6
22.0 295.8/287.2
28.0 309.0/299.2
5
7.5 24.2
10 30.8
—
3
6.6
208/230
187 253
2
33.3
239
2
48.1
245
4
—
10.6
16.7
—
263.5/256.7
(ea)
9.6 284.7/275.9
15.2 296.9/287.1
22.0 311.9/300.7
28.0 325.1/312.7
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
282.7/274.2
9.6 303.9/293.4
15.2 316.1/304.6
22.0 331.1/318.2
28.0 344.3/330.2
5
7.5 24.2
10 30.8
—
3
—
10.6
16.7
—
299.2/289.2
9.6 320.4/308.4
15.2 332.6/319.6
22.0 347.6/333.2
28.0 360.8/345.2
101.9
5
7.5 24.2
10 30.8
—
3
5
7.5
10
—
3
/
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
—
4.8
7.6
11.0
14.0
111.5
117.1
123.9
129.9
104.9
114.5
120.1
126.9
132.9
112.5
122.1
127.7
134.5
140.5
120.0
129.6
135.2
142.0
148.0
128.7
138.3
143.9
150.7
156.7
136.2
145.8
151.4
158.2
14.0
5
7.5
10
—
3
21.0
5
7.5
10
—
3
3.3
460
414 508
2
17.9
125
2
18.6
125
4
(ea)
27.0
5
150
150
150
150
150
175
175
175
175
175
175
175
7.5
10
—
3
34.0
5
7.5
10
—
3
5
7.5
10
40.0
164.2
200
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13 — Electrical Data, 48P2,P3,P4,P5050 Units (cont)
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
78.1
85.9
90.3
96.1
100.1
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
100
100
110
110
7 1/2
9.0
80.1
87.9
92.3
98.1
102.1
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
90
100
100
110
110
10
11.0
17.0
22.0
27.0
32.0
86.7
94.5
98.9
104.7
108.7
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
100
110
110
110
125
15
2.6
575
518 632
2
12.8
80
2
14.7
100
4
92.9
100.7
105.1
110.9
114.9
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
110
110
125
125
125
(ea)
20
99.2
107.0
111.4
117.2
121.2
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
125
125
125
125
125
25
105.4
113.2
117.6
123.4
127.4
—
2
2
2
2
—
3
5
7.5
10
—
3.9
6.1
9.0
11.0
125
125
125
150
150
30
LEGEND
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14 — Electrical Data, 48P2,P3,P4,P5055 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER EVAPORATOR
FAN MOTOR FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
/
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
—
—
—
277.0/272.8
300/300
350/350
350/350
350/350
350/300
350/350
400/350
400/350
350/350
400/400
400/400
400/400
400/350
450/400
450/400
450/450
450/450
500/450
500/450
500/500
125
150
150
150
125
150
150
175
150
175
175
175
175
175
175
200
200
200
225
225
100
110
125
125
110
125
125
125
125
125
125
150
125
150
150
150
150
150
175
175
5.0 16.7 / 15.2 310.4/303.2
7.5 24.2 / 22.0 325.4/316.8
10.0 30.8 / 28.0 338.6/328.8
15
20
25
30
46.2/42.0
—
—
/
—
293.1/286.3
5.0 16.7 / 15.2 326.5/316.7
7.5 24.2 / 22.0 341.5/330.3
10.0 30.8 / 28.0 354.7/342.3
59.4/54.0
74.8/68.0
88.0/80.0
—
—
/
—
312.3/303.8
6.6
5.0 16.7 / 15.2 345.7/334.2
7.5 24.2 / 22.0 360.7/347.8
10.0 30.8 / 28.0 373.9/359.8
208/230
187 253
414 508
518 632
2
2
2
48.1
245
2
48.1
245
4
(ea)
—
—
/
—
328.8/318.8
5.0 16.7 / 15.2 362.2/349.2
7.5 24.2 / 22.0 377.2/362.8
10.0 30.8 / 28.0 390.4/374.8
—
—
/
—
361.3/348.8
5.0 16.7 / 15.2 394.7/379.2
7.5 24.2 / 22.0 409.7/392.8
10.0 30.8 / 28.0 422.9/404.8
40 114.0/104.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
113.9
129.1
135.9
141.9
121.4
136.6
143.4
149.4
130.1
145.3
152.1
158.1
137.6
152.8
159.6
165.6
152.6
167.8
174.6
180.6
90.5
15
20
25
30
40
15
20
25
30
40
21.0
27.0
34.0
40.0
52.0
17.0
22.0
27.0
32.0
41.0
3.3
460
18.6
125
2
18.6
125
4
(ea)
102.7
108.5
112.5
96.7
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
108.9
114.7
118.7
103.0
115.2
121.0
125.0
109.2
121.4
127.2
131.2
120.5
132.7
138.5
142.5
2.6
575
14.7
100
2
14.7
100
4
(ea)
5.0
7.5
10.0
—
5.0
7.5
10.0
6.1
9.0
11.0
—
6.1
9.0
11.0
2
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 15 — Electrical Data, 48P2,P3,P4,P5060 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER EVAPORATOR
FAN MOTOR FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
/
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
—
—
—
290.6/286.4
300/300
350/350
350/350
400/350
350/350
350/350
400/350
400/400
350/350
400/400
400/400
450/400
400/400
450/400
450/450
450/450
450/450
500/450
500/500
500/500
150
150
175
175
150
175
175
175
175
175
200
200
175
200
200
200
200
225
225
250
125
125
150
150
125
150
150
150
150
150
150
150
150
150
175
175
175
175
200
200
5.0 16.7 / 15.2 324.0/316.8
7.5 24.2 / 22.0 339.0/330.4
10.0 30.8 / 28.0 352.2/342.4
15
20
25
30
46.2/42.0
—
—
/
—
305.9/299.1
5.0 16.7 / 15.2 339.3/329.5
7.5 24.2 / 22.0 354.3/343.1
10.0 30.8 / 28.0 367.5/355.1
59.4/54.0
74.8/68.0
88.0/80.0
—
—
/
—
325.1/316.6
6.6
5.0 16.7 / 15.2 358.5/347.0
7.5 24.2 / 22.0 373.5/360.6
10.0 30.8 / 28.0 386.7/372.6
208/230
187 253
414 508
518 632
2
2
2
51.3
300
2
51.3
300
4
(ea)
—
—
/
—
341.6/331.6
5.0 16.7 / 15.2 375.0/362.0
7.5 24.2 / 22.0 390.0/375.6
10.0 30.8 / 28.0 403.2/387.6
—
—
/
—
374.1/361.6
5.0 16.7 / 15.2 407.5/392.0
7.5 24.2 / 22.0 422.5/405.6
10.0 30.8 / 28.0 435.7/417.6
40 114.0/104.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
132.4
147.6
154.4
160.4
139.4
154.6
161.4
167.4
148.1
163.3
170.1
176.1
155.6
170.8
177.6
183.6
170.6
185.8
192.6
198.6
112.0
124.2
130.0
134.0
117.5
129.7
135.5
139.5
123.8
136.0
141.8
145.8
130.0
142.2
148.0
152.0
141.3
153.5
159.3
163.3
15
20
25
30
40
15
20
25
30
40
21.0
27.0
34.0
40.0
52.0
17.0
22.0
27.0
32.0
41.0
3.3
460
23.1
150
2
23.1
150
4
(ea)
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2.6
575
19.9
109
2
19.9
109
4
(ea)
5.0
7.5
10.0
—
5.0
7.5
10.0
6.1
9.0
11.0
—
6.1
9.0
11.0
2
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16 — Electrical Data, 48P2,P3,P4,P5070 Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER EVAPORATOR
FAN MOTOR FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR
HACR BRKR*
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
—
—
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
—
300.8/ 296.6
350/350
350/350
400/350
400/400
350/350
400/350
400/400
400/400
400/350
400/400
450/400
450/400
400/400
450/450
450/450
500/450
450/450
500/500
500/500
500/500
150
175
175
175
150
175
175
200
175
200
200
200
200
200
225
225
225
225
250
250
125
150
150
150
150
150
150
150
150
150
175
175
150
175
175
175
175
200
200
200
5.0 16.7
7.5 24.2
10.0 30.8
15.2 334.2/ 327.0
22.0 349.2/ 340.6
28.0 362.4/ 352.6
15
20
25
30
46.2/42.0
—
—
—
314.9/ 308.6
5.0 16.7
7.5 24.2
10.0 30.8
15.2 348.3/ 339.0
22.0 363.3/ 352.6
28.0 376.5/ 364.6
59.4/54.0
74.8/68.0
88.0/80.0
—
—
—
334.1/ 325.6
6.6
5.0 16.7
7.5 24.2
10.0 30.8
15.2 367.5/ 356.0
22.0 382.5/ 369.6
28.0 395.7/ 381.6
208/230
187 253
414 508
518 632
2
2
2
51.3
300
2
55.8
340
4
(ea)
—
—
—
350.6/ 340.6
5.0 16.7
7.5 24.2
10.0 30.8
15.2 384.0/ 371.0
22.0 399.0/ 384.6
28.0 412.2/ 396.6
—
—
—
383.1/ 370.6
5.0 16.7
7.5 24.2
10.0 30.8
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
/
/
/
—
15.2 416.5/ 401.0
22.0 431.5/ 414.6
28.0 444.7/ 426.6
140.9
40 114.0/104.0
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
156.1
162.9
168.9
147.0
162.2
169.0
175.0
155.7
170.9
177.7
183.7
163.2
178.4
185.2
191.2
178.2
193.4
200.2
206.2
120.5
132.7
138.5
142.5
125.5
137.7
143.5
147.5
131.4
143.6
149.4
153.4
137.6
15
20
25
30
40
15
20
25
30
40
21.0
27.0
34.0
40.0
52.0
17.0
22.0
27.0
32.0
41.0
3.3
460
23.1
150
2
26.9
179
4
(ea)
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2.6
575
19.9
109
2
23.7
132
4
(ea)
6.1
9.0
11.0
—
6.1
9.0
11.0
149.8
155.6
159.6
148.9
161.1
166.9
170.9
2
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 17 — Electrical Data — 48P2,P3,P4,P5075 Standard Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER
POWER SUPPLY
No. A1,A2
No. B1,B2
EXHAUST
VOLTAGE
3 PH, 60 Hz
RLA LRA
RLA LRA
Hp
FLA
(ea)
FUSE OR
HACR BRKR*
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
(ea)
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
170.8
186.0
192.8
198.8
185.8
201.0
207.8
213.8
202.1
217.3
224.1
230.1
217.1
232.3
239.1
245.1
240.8
256.0
262.8
268.8
145.2
157.4
163.2
167.2
156.5
168.7
174.5
178.5
170.2
182.4
188.2
192.2
182.7
194.9
200.7
204.7
201.5
213.7
219.5
223.5
200
225
225
225
225
250
250
250
250
250
250
250
250
300
300
300
300
350
350
350
175
175
175
175
175
200
200
200
200
225
225
225
225
250
250
250
250
250
250
300
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
2
26.9
179
2
26.9
179
4
(ea)
2.6
575
518 632
2
23.7
132
2
23.7
132
4
(ea)
5.0
7.5
10.0
—
5.0
7.5
10.0
6.1
9.0
11.0
—
6.1
9.0
11.0
2
2
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 18 — Electrical Data — 48P2,P3,P4,P5075 Units with Optional High-Capacity Power Exhaust
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER
POWER SUPPLY
No. A1,A2
No. B1,B2
EXHAUST
VOLTAGE
3 PH, 60 Hz
RLA LRA
RLA LRA
Hp
FLA
(ea)
FUSE OR
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
(ea)
HACR BRKR*
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
198.8
212.8
224.8
238.8
250.8
213.8
227.8
239.8
253.8
265.8
230.1
244.1
256.1
270.1
282.1
245.1
259.1
271.1
285.1
297.1
268.8
282.8
294.8
308.8
320.8
167.2
179.2
189.2
199.2
209.2
178.5
190.5
200.5
210.5
220.5
192.2
204.2
214.2
224.2
234.2
204.7
216.7
226.7
236.7
246.7
223.5
235.5
245.5
255.5
265.5
225
250
250
250
300
250
250
250
300
300
250
300
300
300
300
300
300
300
350
350
350
350
350
400
400
175
200
200
225
225
200
225
225
250
250
225
250
250
250
250
250
250
250
250
300
300
300
300
300
300
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
2
26.9
179
2
26.9
179
4
(ea)
2.6
575
518 632
2
23.7
132
2
23.7
132
4
(ea)
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
50
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 19 — Electrical Data — 48P2,P3,P4,P5075 Units with Optional Return Fan
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
197.8
204.8
210.8
225.8
212.8
219.8
225.8
237.8
229.1
236.1
242.1
254.1
244.1
251.1
257.1
269.1
267.8
274.8
280.8
292.8
167.2
172.2
177.2
188.5
178.5
183.5
188.5
197.5
192.2
197.2
202.2
211.2
204.7
209.7
214.7
223.7
223.5
228.5
233.5
242.5
225
225
250
250
250
250
250
250
250
300
300
300
300
300
300
300
350
350
350
350
175
200
200
225
200
200
225
225
225
225
250
250
250
250
250
250
300
300
300
300
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
2
26.9
179
2
26.9
179
4
(ea)
2.6
575
518 632
2
23.7
132
2
23.7
132
4
(ea)
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 20 — Electrical Data — 48P2,P3,P4,P5090 Standard Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
—
5
7.5
10.0
—
5
7.5
10
—
5
7.5
10
—
5
7.5
10
—
5
7.5
10
—
5
7.5
10.0
—
5
7.5
10
—
5
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
208.4
223.6
230.4
236.4
223.4
238.6
245.4
251.4
239.7
254.9
261.7
267.7
254.7
269.9
276.7
282.7
278.4
293.6
300.4
306.4
175.0
187.2
193.0
197.0
186.3
198.5
204.3
208.3
200.0
212.2
218.0
222.0
212.5
224.7
230.5
234.5
231.3
243.5
249.3
253.3
225
250
250
250
250
250
250
300
300
300
300
300
300
300
350
350
350
350
350
400
200
200
200
225
225
225
225
225
250
250
250
250
250
250
250
250
300
300
300
300
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
3
23.1
150
3
23.1
150
6
(ea)
2.6
575
518 632
3
19.9
109
3
19.9
109
6
7.5
10
—
5
7.5
10
—
5
(ea)
6.1
9.0
11.0
—
6.1
9.0
11.0
2
2
7.5
10
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Electrical Data — 48P2,P3,P4,P5090 Units with Optional High-Capacity Power Exhaust
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
236.4
250.4
262.4
276.4
288.4
251.4
265.4
277.4
291.4
303.4
267.7
281.7
293.7
307.7
319.7
282.7
296.7
308.7
322.7
334.7
306.4
320.4
332.4
346.4
358.4
197.0
209.0
219.0
229.0
239.0
208.3
220.3
230.3
240.3
250.3
222.0
234.0
244.0
254.0
264.0
234.5
246.5
256.5
266.5
276.5
253.3
265.3
275.3
285.3
295.3
250
300
300
300
300
300
300
300
300
350
300
300
350
350
350
350
350
350
350
400
400
400
400
400
450
225
225
250
250
250
225
250
250
250
300
250
250
250
300
300
250
300
300
300
300
300
300
350
350
350
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
3
23.1
150
3
23.1
150
6
(ea)
2.6
575
518 632
3
19.9
109
3
19.9
109
6
(ea)
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Electrical Data — 48P2,P3,P4,P5090 Units with Optional Return Fan
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
235.4
242.4
248.4
263.4
250.4
257.4
263.4
275.4
266.7
273.7
279.7
291.7
281.7
288.7
294.7
306.7
305.4
312.4
318.4
330.4
197.0
202.0
207.0
218.3
208.3
213.3
218.3
227.3
222.0
227.0
232.0
241.0
234.5
239.5
244.5
253.5
253.3
258.3
263.3
272.3
250
250
250
300
300
300
300
300
300
300
300
350
350
350
350
350
400
400
400
400
225
225
225
250
225
250
250
250
250
250
250
250
250
300
300
300
300
300
300
300
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
3
23.1
150
3
23.1
150
6
(ea)
2.6
575
518 632
3
19.9
109
3
19.9
109
6
(ea)
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 23 — Electrical Data — 48P2,P3,P4,P5100 Standard Units
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
2
2
—
2
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
5.0
7.5
10.0
—
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
7.6
11.0
14.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
6.1
9.0
11.0
—
219.8
235.0
241.8
247.8
234.8
250.0
256.8
262.8
251.1
266.3
273.1
279.1
266.1
281.3
288.1
294.1
289.8
305.0
311.8
317.8
186.4
198.6
204.4
208.4
197.7
209.9
215.7
219.7
211.4
223.6
229.4
233.4
223.9
236.1
241.9
245.9
242.7
254.9
260.7
264.7
250
250
250
250
250
300
300
300
300
300
300
300
300
350
350
350
350
400
400
400
200
225
225
225
225
250
250
250
250
250
250
250
250
250
300
300
300
300
300
300
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
3
23.1
150
3
26.9
179
6
(ea)
2.6
575
518 632
3
19.9
109
3
23.7
132
6
(ea)
5.0
7.5
10.0
—
5.0
7.5
10.0
6.1
9.0
11.0
—
6.1
9.0
11.0
2
2
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 24 — Electrical Data — 48P2,P3,P4,P5100 Units with Optional High-Capacity Power Exhaust
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
10
15
20
25
30
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
14.0
21.0
27.0
34.0
40.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
11.0
17.0
22.0
27.0
32.0
247.8
261.8
273.8
287.8
299.8
262.8
276.8
288.8
302.8
314.8
279.1
293.1
305.1
319.1
331.1
294.1
308.1
320.1
334.1
346.1
317.8
331.8
343.8
357.8
369.8
208.4
220.4
230.4
240.4
250.4
219.7
231.7
241.7
251.7
261.7
233.4
245.4
255.4
265.4
275.4
245.9
257.9
267.9
277.9
287.9
264.7
276.7
286.7
296.7
306.7
250
300
300
300
300
300
300
300
350
350
300
350
350
350
350
350
350
350
400
400
400
400
400
450
450
225
250
250
250
300
250
250
250
300
300
250
250
300
300
300
300
300
300
300
300
300
350
350
350
350
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
3
23.1
150
3
26.9
179
6
(ea)
2.6
575
518 632
3
19.9
109
3
23.7
132
6
(ea)
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 25 — Electrical Data — 48P2,P3,P4,P5100 Units with Optional Return Fan
COMPRESSOR
VOLTAGE
RANGE
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
VOLTAGE
FLA
(ea)
RLA LRA
RLA LRA
Hp
(ea)
FUSE OR HACR
3 PH, 60 Hz
Min Max Qty
Qty
Qty
FLA
Hp
FLA
Qty
MCA
(ea)
(ea)
(ea)
(ea)
BRKR*
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
20
25
30
40
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
27.0
34.0
40.0
52.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
22.0
27.0
32.0
41.0
246.8
253.8
259.8
274.8
261.8
268.8
274.8
286.8
278.1
285.1
291.1
303.1
293.1
300.1
306.1
318.1
316.8
323.8
329.8
341.8
208.4
213.4
218.4
229.7
219.7
224.7
229.7
238.7
233.4
238.4
243.4
252.4
245.9
250.9
255.9
264.9
264.7
269.7
274.7
283.7
250
300
300
300
300
300
300
300
300
350
350
350
350
350
350
350
400
400
400
400
225
225
250
250
250
250
250
250
250
250
250
300
300
300
300
300
300
300
350
350
30
40
50
60
75
30
40
50
60
75
40.0
52.0
65.0
77.0
96.0
32.0
41.0
52.0
62.0
77.0
3.3
460
414 508
3
23.1
150
3
26.9
179
6
(ea)
2.6
575
518 632
3
19.9
109
3
23.7
132
6
(ea)
LEGEND
FLA
HACR
Hp
LRA
MCA
RLA
—
—
—
—
—
—
Full Load Amps
Heating, Air Conditioning, and Refrigeration
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Rated Load Amps
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
57
Download from Www.Somanuals.com. All Manuals Search And Download.
area near the entrance lobby (or other appropriate and sensitive
location) so that location is controlled as closely to design pres-
sures as possible.
These units use a pressure transducer for sensing building
pressure. The BP transducer is located in the unit auxiliary con-
trol box. See Fig. 44 and 45 for auxiliary control box location.
See Fig. 46 and 47 for auxiliary control box details. Use a nom-
inal 1/4-in. plastic tubing.
Step 13 — Connect Air Pressure Tubing — Be-
fore options such as the variable frequency drive (VFD) and/or
modulating power exhaust can operate properly, the pneumatic
tubing for pressure sensing must be installed. Use fire-retardant
1
plenum tubing (field-supplied). All control devices use /4-in.
tubing. Tubing must be run from the appropriate sensing loca-
tion (in the duct or in the building space) to the control device
location in the unit.
VARIABLE FREQUENCY DRIVE — The tubing for the
duct pressure (DP) control option should sample supply duct
pressure approximately 2/3 of the way out from the unit in the
main trunk duct, at a location where a constant duct pressure is
desired.
On these units, the duct pressure is sensed by a pressure
transducer. The pressure transducer output is directed to the unit
control module. On all sizes, the DP transducer is located in the
unit auxiliary control box. See Fig. 44 and 45 for auxiliary
control box location. See Fig. 46-48 for auxiliary control box
details. Use a nominal 1/4-in. plastic tubing.
Refer to appropriate base unit Controls and Troubleshooting
book for instructions on adjusting set points for duct pressure
controls.
MODULATING POWER EXHAUST — The tubing for the
building pressure (BP) control (achieved via the modulating
power exhaust option) should sample building pressure in the
For instructions on adjusting BP control set points, refer to
the Controls and Troubleshooting book.
RETURN FAN POWER EXHAUST — The tubing for the
building pressure (BP) control (achieved via the return power
exhaust option) should sample building pressure in the area
near the entrance lobby (or other appropriate and sensitive lo-
cation) so that location is controlled as closely to design pres-
sures as possible.
The units use a pressure transducer for sensing building
pressure. The BP transducer is located in the unit auxiliary con-
trol box. See Fig. 45 for auxiliary control box location. See
Fig. 48 for auxiliary control box details. Use a nominal 1/4 in.
plastic tubing.
For instructions on adjusting BP control set points, refer to
the Controls and Troubleshooting book.
AUXILIARY
CONTROL
BOX
Fig. 44 — Auxiliary Control Box Location (Sizes 030-050)
58
Download from Www.Somanuals.com. All Manuals Search And Download.
AUXILIARY
CONTROL
BOX
Fig. 45 — Auxiliary Control Box Location (Sizes 055-100)
FS
DP
BP
FS
DP
OACFM
TRANSDUCER
BP
OACFM
TRANSDUCER
LEGEND
LEGEND
BP
DP
FS
— Building Pressure Transducer
— Duct Pressure Transducer
— Filter Switch
BP
DP
FS
— Building Pressure Transducer
— Duct Pressure Transducer
— Filter Switch
OACFM — Outdoor Air Cfm Sensor Transducer
OACFM — Outdoor Air Cfm Sensor Transducer
Fig. 46 — Auxiliary Control Box Details
(Sizes 030-050)
Fig. 47 — Auxiliary Control Box Details
(Sizes 055-100 without Optional Return Fan)
59
Download from Www.Somanuals.com. All Manuals Search And Download.
FS
DP
BP
OACFM
TRANSDUCER
RF
CFM
PP
SS
Fig. 49 — Shipping Brackets; Size 030-050 Units
LEGEND
Building Pressure OACFM — Outdoor Air Cfm
BP
DP
FS
—
—
—
Transducer
Duct Pressure
Transducer
Filter Switch
Sensor Transducer
Plenum Pressure
Safety Switch
PPSS
—
RFCFM — Return Fan Cfm Sensor Transducer
Fig. 48 — Auxiliary Control Box Details
(Size 075-100 Units with Optional Return Fan)
Step 14 — Remove Supply-Fan Shipping
Brackets — Supply-fan shipping brackets (4 per unit) must
be removed from each corner of the fan sled before starting
unit.
UNIT SIZES 030-050
1. To remove brackets, raise fan sled by turning adjusting
bolt counterclockwise until spring is compressed slightly.
2. Remove screws holding shipping bracket to unit cross
rail.
3. Remove shipping bracket (top of bracket is slotted so that
it will slide out).
4. After removing all shipping brackets, level fan sled using
the adjusting screws. On all 4 corners, dimension from
cross rail to fan sled should be as shown in Fig. 49.
UNIT SIZES 055-070 — To remove shipping brackets, re-
move the 6 screws holding each bracket to the cross rail. There
are 8 brackets per unit. See Fig. 50.
After removing all shipping brackets, level fan sled using
the adjusting screws. On all 4 corners dimension from cross
rail to fan sled should be as shown in Fig. 50.
UNIT SIZES 075-100 — To remove shipping brackets, re-
move the 6 screws holding each bracket to the cross rail. There
are 4 brackets per unit. See Fig. 51.
After removing all shipping brackets, level fan sled using
the adjusting screws. On all 4 corners dimension from cross
rail to fan sled should be as shown in Fig. 51.
Fig. 50 — Shipping Brackets;
Size 055-070 Units
Step 15 — Remove Optional Return-Fan Ship-
ping Brackets — Optional return fan shipping brackets
must be removed from each corner of the fan sled before start-
ing unit.
To remove shipping brackets, remove 2 screws holding
each bracket to the cross rail. There are 4 brackets per unit.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8468
Fig. 51 — Shipping Brackets (Sizes 075-100)
After removing all shipping brackets, level the fan using the
adjustment screws. On all 4 corners the dimension from cross
rail to fan sled should be as shown in Fig. 52.
Step 16 — Connect Gas Piping — Unit is
equipped for use with natural gas only. Installation must con-
form with local building codes, or in the absence of local
codes, with the National Fuel Gas Code (NFGC), ANSI
Z223.1.
A 1/8-in. NPT tapping plug, accessible for test gage connec-
tion, must be field installed immediately upstream of gas sup-
ply connection to unit, but after manual gas valve. See Fig. 53.
Natural gas pressure at unit gas connection must not be less
than 5 in. wg or greater than 13 in. wg.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
CAUTION
Disconnect gas piping from unit when leak testing at pres-
sures greater than 0.5 psig. Pressures greater than 0.5 psig
will cause gas valve damage resulting in a hazardous con-
dition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced.
Step 17 — Configure Optional Staged Gas
or Modulating Gas Control — The 48P Series large
rooftop units may be ordered with an optional factory-installed
staged gas or modulating gas control system that monitors
heating operation of the rooftop.
Refer to the Unit Controls and Troubleshooting book for in-
formation on configuring staged gas or modulating gas control.
NOTE: All dimensions are in inches.
Fig. 52 — Optional Return
Fan Shipping Brackets
61
Download from Www.Somanuals.com. All Manuals Search And Download.
together with screw provided. Refer to Table 26 for
usage.
4. Install flue deflector hood assembly over each flue outlet
hood. See Fig. 64. Observe the offset mounting hole loca-
tions in the deflector hood flanges when attaching hood to
panel. Holes in the mounting flange must be at the bottom
when attached.
5. Inlet hoods are shipped unassembled and must be assem-
bled on the access panel (see Fig. 65-67). Flanges of the
hood top and sides should be installed on the inside of the
access panel openings with the screws provided. The
sides should be placed on the inside of top hoods for all
hood assemblies (6-in., 14-in., and 30-in.). Attach speed
clips to screen. Insert screen into bottom opening of 6-in.
and 14-in. hoods and secure it with 3 screws. To ease the
installation, the 30-in. hood screen may be inserted from
inside of access panel (gas section door) into bottom
opening of hood. Secure with 5 screws. Attached view
port cover over 14-in. inlet hood opening (Fig. 66). Se-
cure with two screws.
*NPT plug is field supplied.
NOTE: Follow all local codes.
Fig. 53 — Gas Piping Details
Step 18 — Install Flue/Inlet Hoods and
Baffles — The flue/inlet hoods and baffles are shipped in a
package taped to the basepan in the fan section. The flue (out-
let) hoods are pre-assembled. The flue deflector, inlet hoods,
and baffles require assembly.
The hoods are located on the heating section access panel as
shown in Fig. 54 (sizes 030-050), Fig. 55 (sizes 055-100 with
low heat and vertical supply), Fig. 56 (sizes 055-100 with low
heat and horizontal supply), and Fig. 57 (sizes 055-100 with
high heat). The inlet baffles are located inside the access panel
as illustrated in Fig. 58 (sizes 030-050), Fig. 59 (sizes 055-100
with modulating low heat and horizontal supply), and Fig. 60
(sizes 055-100 with modulating high heat). See Table 26 for a
list of parts used to assemble each hood and quantities of each
hood type and baffle used with each unit.
6. Install inlet baffle on the access panel with the screw(s)
provided. See Fig. 68 for 14-in baffle and Fig. 69 for
30-in baffle. Attach 14-in baffle from the outside of the
access panel. The 30-in baffle should be installed from in-
side of the access panel. Secure with three screws.
Step 19 — Install Supply-Air Thermistors
(Staged and Modulating Gas Units Only) —
Supply-air thermistors are a field-installed, factory-provided
component. Three supply-air thermistors are shipped with
staged and modulating gas units inside the unit control box.
Thermistor wires must be connected to the SGC in the unit
control box. See Table 27. The supply-air thermistors should
be located in the supply duct with the following criteria:
1. Remove shipping block-offs and shipping tape from all
openings in the access panel.
2. Attach flue outlet hoods (see Fig. 61) to access panel us-
ing screws provided. Hoods are placed over each com-
bustion outlet.
•
•
downstream of the heat exchanger cells
equally spaced as far as possible from the heat
exchanger cells
•
•
a duct location where none of the supply air thermistors
are within sight of the heat exchanger cells
a duct location with good mixed supply air portion of the
unit.
3. Install flue deflector baffle inside flue deflector hood. See
Fig 62 for V-type deflector and Fig. 63 for curve-type
deflector. For V-type deflector, screw the baffle and hood
14-IN.
INLET HOOD
FLUE HOOD AND
FLUE DEFLECTOR
HOOD (48 SERIES
HIGH-HEAT ONLY)
FLUE OUTLET
HOOD
14-IN.
INLET HOOD
FLUE HOOD
AND FLUE
DEFLECTOR
HOOD
VIEW PORT
COVER
FLUE HOOD AND
DEFLECTOR
HOOD
14-IN. INLET
HOOD
14-IN.
INLET HOOD
6-IN. INLET
HOOD
a48-8470
Fig. 54 — Flue/Inlet Hood Locations, 030-050 Units
Fig. 55 — Flue/Inlet Hood Locations, Sizes 055-100,
Low Heat, Vertical Supply Units
a48-8469
62
Download from Www.Somanuals.com. All Manuals Search And Download.
FLUE OUTLET
HOOD
FLUE HOOD
AND FLUE
DEFLECTOR
HOOD
6-IN. INLET
HOOD
30-IN. INLET
HOOD
INLET BAFFLE
(14-in.)
a48-8584
a48-8471
Fig. 58 — Baffle Location, 030-050 Units
Fig. 56 — Flue/Inlet Hood Locations, Sizes 055-100,
Low Heat, Horizontal Supply Units
a48-8585
30-IN. INLET
HOOD
FLUE OUTLET
HOOD
INLET BAFFLE
(30-in.)
FLUE HOOD
AND FLUE
DEFLECTOR
HOOD
30-IN. INLET
HOOD
6-IN. INLET
HOOD
a48-8472
Fig. 57 — Flue/Inlet Hood Locations, Sizes 055-100,
High Heat, Vertical and Horizontal Supply Units
Fig. 59 — Baffle Location, Sizes 055-100,
Modulating Low Heat, Horizontal Supply Units
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 26 — Flue Hood, Inlet Hood, and Baffle Usage
QUANTITY USED
HOOD OR
BAFFLE TYPE
PARTS LIST
FIG. NO.
Sizes 030-050 Sizes 030-050 Sizes 055-070 Sizes 055-070 Sizes 075-100 Sizes 075-100
(Low Heat)
(High Heat)
(Low Heat)
(High Heat)
(Low Heat)
(High Heat)
Top (6-in.)
Side (Left)
Side (Right)
Screen
Speed Clips
Screws
6-in. Inlet
Hood
65
—
—
1
1
1
1
Top (14-in.)
Side (Left)
Side (Right)
Screen
1
1
14-in. Inlet
Hood
65,66
67
3
3
(Vertical
—
2
(Vertical
—
2
Cover
Supply Only)
Supply Only)
Speed Clips
Screws
Top (30-in.)
Side (Left)
Side (Right)
Screen
Speed Clips
Screws
1
1
30-in. Inlet
Hood
—
—
(Horizontal
Supply Only)
(Horizontal
Supply Only)
Flue Outlet
Hood
Pre-assembled
61
62
1
1
2
2
2
3
3
2
2
3
3
Hood
2
Flue Deflector
(V-Type)
Deflector
Baffle
(Horizontal
Supply Only)
Screws
Hood
2
Flue Deflector
(Curve-Type)
Deflector
Baffle
63
68
69
—
1
—
2
(Vertical
—
—
2
—
—
—
—
2
Supply Only)
Screws
Baffle
Screws
Baffle
Screws
14-in. Baffle
30-in. Baffle
—
1
1
(Modulating
Horizontal
Supply Only)
(Modulating
Horizontal
Supply Only)
—
—
Fig. 61 — Flue Outlet Hood
FLUE DEFLECTOR
BAFFLE
FLUE
DEFLECTOR
HOOD
PUSH
BAFFLE
DOWN SO
THESE 2
SCREW
HOLES
INLET BAFFLE
(30-in.)
ALIGN
Fig. 60 — Baffle Locations, Sizes 055-100,
Modulating High Heat, Vertical and
Horizontal Supply Units
a48-8587
a48-8586
Fig. 62 — Flue Deflector Baffle (V-Type)
64
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESS PANEL
OPENING
COVER
(14-IN. HOOD ONLY)
FLUE DEFLECTOR
HOOD
MAKE
SCREW
HOLES
ALIGN
FLUE DEFLECTOR
BAFFLE (BOTH HOODS)
a48-8588
Fig. 63 — Flue Deflector Baffle (Curve-Type)
HOOD
SIDE (TYP
BOTH SIDES)
SCREEN
SPEED CLIP
(TYP 3)
Fig. 65 — Inlet Hood Assembly (6-in. and 14-in.)
VIEW PORT
COVER
OBSERVE OFFSET
MOUNTING HOLE
LOCATIONS WHEN
INSTALLING FLUE
DEFLECTOR HOODS.
Fig. 64 — Mounting Deflector Hoods
Fig. 66 — 14-in. Inlet Hood View Port Cover
Installation
65
Download from Www.Somanuals.com. All Manuals Search And Download.
INLET HOOD
SIDE
INLET
HOOD
SCREEN
(WITH SPEED CLIPS)
INLET HOOD
SIDE
a48-8473
Fig. 67 — Inlet Hood Assembly (30-in.)
Fig. 68 — Air Baffle (14-in.)
a48-8590
a48-8591
Fig. 69 — Air Baffle (30-in.)
Table 27 — SGC Thermistor Designations
PIN
FUNCTION AND LOCATION
Thermistors
THERMISTOR
SAT1
CONNECTION
POINT
PART NO.
Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)
Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)
Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)
J8 – 1,2 (SGC)
J8 – 3,4 (SGC)
J8 – 5,6 (SGC)
SAT2
HH79NZ033
SAT3
Limit Switch Thermistor (LIMTTEMP) — Inserted next the
lower limit switch (factory-installed)
LIMTTEMP
J8 – 15,16 (SGC)
SGC — Staged Gas Controller
Step 20 — Install Optional Motormaster®
V
On size 040-060 units, in areas with prevailing winds of
more than 5 mph and where temperatures drop below 32 F,
wind baffles must be field fabricated to ensure proper cooling
cycle operation at low-ambient temperatures with Motormaster
V controls. Wind baffles are not needed on size 030, 035, and
070-100 units. See Fig. 70 for baffle details. Use 20-gage galva-
nized sheet metal, or similar corrosion-resistant material for the
baffles. Use field-supplied screws to attach baffles to unit.
Screws should be 1/4-in. diameter or larger. Screws should not
be more than 1/2-inch in length. Drill required screw holes for
mounting baffles.
Control — The Motormaster V control is a motor speed
control device which adjusts condenser fan motor speed in re-
sponse to varying liquid refrigerant pressure. A properly applied
Motormaster V control extends the operating range of air-condi-
tioning systems and permits operation at lower outdoor ambient
temperatures.
The optional Motormaster V controls are factory-installed.
Field-fabricated and installed wind baffles are also required for
units in areas with prevailing winds of more than 5 mph and
where temperatures drop below 32 F. The Motormaster V con-
trol permits operation of the unit to an ambient temperature of
–20 F. The control regulates the speed of one or two 3-phase fan
motors depending on unit size. Replacement of the fan motor on
most units is not necessary.
CAUTION
To avoid damage to refrigerant coils, electrical compo-
nents, and wiring use extreme care when drilling screw
holes and screwing in fasteners.
INSTALL FIELD-FABRICATED WIND BAFFLES
WARNING
To avoid the possibility of electrical shock, open all discon-
nects before installing or servicing this accessory.
66
Download from Www.Somanuals.com. All Manuals Search And Download.
WIND BAFFLE
a48-8561
BAFFLE INSTALLATION LOCATION (SIZES 050 AND 060 SHOWN)
a48-8560
DIMENSION “A”
in.
UNIT SIZE
QUANTITY
mm
030,035
040-060
070-100
Not Used
2
Not Used
—
78.125 0.125
—
—
1984
3
—
NOTE: 48/50P030, 035, and 070-100 units do not require
baffles.
Fig. 70 — Wind Baffle Details
67
Download from Www.Somanuals.com. All Manuals Search And Download.
VAV CONTROL WIRING — The recommended types of
control wiring are shown below:
Step 21 — Install Unit Accessories — For appli-
cations requiring accessories, the following packages are
available:
PART NO.
MANUFACTURER
All units:
Regular Wiring
1895
Plenum Wiring
•
•
•
•
•
•
•
barometric relief
Alpha
American
Belden
Columbia
Manhattan
Quabik
—
A48301
884421
—
space temperature sensor
CO2 sensor
A21451
8205
D6451
space temperature sensor with CO2 sensor
airflow switch
filter switch
smoke detector
M13402
6130
M64430
—
SENSORS — Sensors should be wired using single twisted
pairs of 20 AWG (American Wire Gage) conductor cable rated
for the application, except for the T-56 accessory sensor which
requires 3-conductor cable.
HUMIDITY CONTROL AND HOT WATER AND
STEAM VALVES — These devices require 20 AWG twisted
pair conductor cables rated for the application for the 4 to
20 mA signal.
SPACE TEMPERATURE SENSOR (T-55) — The space tem-
perature sensor (P/N 33ZCT55SPT), if used, is wired to termi-
nals in the unit main control box. To connect the space temper-
ature sensor, see Fig. 72.
SPACE TEMPERATURE SENSOR (T-56) — The space tem-
perature sensor (P/N 33ZCT56SPT), if used, is wired to termi-
nals in the unit main control box. To connect the space temper-
ature sensor, see Fig. 72.
COMMUNICATING SPACE TEMPERATURE SENSOR
(T-58) — The communicating space temperature sensor (P/N
33ZCT58SPT) is wired to the Carrier Comfort Network®
(CCN) connections on TB202.
SPACE TEMPERATURE AVERAGING — Applications that
require averaging using multiple space temperature sensors can
be satisfied using either 4 or 9 sensors as shown in Fig. 73.
NOTE: Only Carrier sensors may be used for standard T-55
space averaging. Sensors must be used in multiples of 1, 4, and
9 only, with total sensors wiring not to exceed 1000 ft.
NOTE: Do not use T-56 sensors for space temperature averag-
ing because the 5-degree offset function will not work in a
multiple sensor application.
All 48P2,P4 (constant volume) units:
modulating power exhaust
•
All 48P3,P5 (variable air volume) units:
•
modulating power exhaust
Refer to the individual accessory installation instructions in
each accessory package for information on installing accessories.
CONTROLS INSTALLATION
Constant Volume (CV) Units — The 48P2,P4 units
may be used in applications with additional control features,
options, or accessories. Refer to the appropriate accessory
installation instructions for more information on installing that
accessory. Control options and accessories available for CV
units are:
• thermostats
• enthalpy sensor
• enthalpy switch
• relative humidity sensor
• CEM (controls expansion module)
• Navigator™ hand-held display
CONTROL WIRING — The unit can be controlled with a
Carrier-approved accessory electro-mechanical or electronic
thermostat that has two stages of cooling, two stages of heating
control, and an output for fan control. The thermostat may also
include time of day scheduling or use scheduling routines built
into the ComfortLink™ controls.
Install the thermostat according to the installation instruc-
tions shipped with the accessory thermostat. Locate thermostat
assembly on a solid interior wall to sense average temperature.
HEAT INTERLOCK RELAY (VAV Units Only — Not Neces-
sary for Digital Air Volume Applications) — Variable air vol-
ume (VAV) units using morning warm-up and/or occupied
heating require that room terminals be controlled to a position
that provides the minimum required heating cfm or greater
when the unit goes into Heating mode. The HIR (heat interlock
relay) function is provided for this control. When the unit goes
into Heating mode, the HIR is energized to provide switch clo-
sure or opening (depending on how the field-supplied power
source is set up) to open the room terminals. The field connec-
tions for the HIR are at TB201 terminals 9 and 10. See Fig. 74.
Route thermostat cable or equivalent leads of colored wire
from subbase terminals through conduit into the low voltage
connections in the main control box. For thermostat TB201
connections, see Fig. 71.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35 C minimum). All wire larger
than no. 18 AWG cannot be directly connected at the thermostat
and will require a junction box and splice at the thermostat.
Variable Air Volume (VAV) Units — The 48P3,P5
units may be used in applications with additional control fea-
tures, options, or accessories. Refer to the appropriate accesso-
ry installation instructions for more information on installing
that accessory. Refer to the Controls and Troubleshooting man-
ual for more information concerning installation and configura-
tion of options and accessories. Control options and accessories
available for VAV units are:
Option and Accessory Control Wiring — The P
Series units may be used in applications with additional control
features, options, or accessories. Refer to the Controls and
Troubleshooting manual for more information concerning
installation and configuration of options and accessories.
Figures 74-84 contain wiring information on the following
features:
• enthalpy sensor
• heat interlock relay (Fig. 74)
• enthalpy switch
• outdoor air enthalpy switch (Fig. 75)
• CO2 space sensor (Fig. 76)
• relative humidity sensor
• CEM (controls expansion module)
• Navigator hand-held display
• filter status switch (Fig. 77)
• fan status switch (Fig. 78)
• space humidity sensor (Fig. 79)
• return air humidity sensor (Fig. 79)
• return air CO2 sensor (Fig. 80)
• return air smoke detector (Fig. 81)
• smoke control — fire shutdown (Fig. 82)
68
Download from Www.Somanuals.com. All Manuals Search And Download.
• smoke control — purge (Fig. 83)
• smoke control — evacuation (Fig. 83)
• smoke control — pressurization (Fig. 83)
• CCN connections (Fig. 84)
JUMPER
TERMINALS
T55- SPT
SEN
T56- SPT
SEN
SET
FIELD SUPPLIED THERMOSTAT
11
12
1
2
13
14
3
4
5
6
9
7
8
15
16
RC
Y1
Y1
Y2
Y2
W1
W1
W2
W2
G
G
R
R
UNIT
TB201
10
X
C
TB201
Fig. 72 — T55 or T56 Wiring
a48-8474
a48-8475
Fig. 71 — Field Control Thermostat Wiring
TB201
RED
1
BLK
2
SENSOR 4
SENSOR 3
SENSOR 1
SENSOR 2
TB202
1
2
SENSOR 1
SENSOR 2
SENSOR 3
SENSOR 6
SENSOR 5
SENSOR 4
SENSOR 9
SENSOR 8
SENSOR 7
NOTE: Use T55 sensor only.
a48-8476
Fig. 73 — Space Temperature Averaging Wiring
69
Download from Www.Somanuals.com. All Manuals Search And Download.
13
14
15
RCB
J8
RELAY 5
10
9
a48-8477
Fig. 74 — Heat Interlock Relay Wiring
a48-8481
6
RCB
J4
FIELD INSTALLED (FIELD
SUPPLIED) JUMPER WHEN
ENTHALPY SWITCH NOT USED
5
a48-8478
Fig. 75 — Outdoor Air Enthalpy Switch Wiring
TB201
8
MBB
J8
7
a48-8479
Fig. 76 — CO2 Space Sensor Wiring
FILTER STATUS
MBB
J8
a48-8480
Fig. 77 — Filter Status Wiring
70
Download from Www.Somanuals.com. All Manuals Search And Download.
RCB
J4
Fig. 78 — Fan Status Switch Wiring
4
3
CEM
J6
a48-8482
Fig. 79 — Space and Return Air Humidity Sensor Wiring
RED
BRN
a48-8483
Fig. 80 — Return Air CO2 Sensor Wiring
71
Download from Www.Somanuals.com. All Manuals Search And Download.
TB201
1
2
a48-8483
Fig. 81 — Return Air Smoke Detector Wiring
FIRE SHUTDOWN
2
BLU
MBB
J6
1 WHT
TB201
a48-8485
Fig. 82 — Fire Shutdown Wiring
14
15
16
17
18
19
TB 202
RCB J4
a48-8486
Fig. 83 — Purge, Evacuation, and Pressurization Wiring
72
Download from Www.Somanuals.com. All Manuals Search And Download.
a48-8487
TB201
MBB
J5
Fig. 84 — CCN Connections
Carrier Comfort Network® (CCN) Interface —
The 48P Series units can be connected to the CCN system if
desired. The communication bus wiring is supplied and
installed in the field. It consists of shielded, 3-conductor cable
with shield wire.
IMPORTANT: When connecting the CCN communica-
tion bus to a system element, use a color coding system for
the entire network to simplify installation and checkout.
The following color code is recommended:
The system elements are connected to the communication
bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to the
positive pins of the system element on either side of it, the
negative pins must be wired to the negative pins, and the signal
pins must be wired to common pins. Wiring connections for
the CCN system should be made at the terminal block using the
screw terminals. The board also contains an RJ14 CCN plug
that can be used to connect a field service computer. There is
also another RJ14 LEN (Local Equipment Network) connec-
tion that is used to download software or connect a Naviga-
tor™ device.
NOTE: Conductors and drain wire must be 20 AWG minimum
stranded, tinned copper. Individual conductors must be insu-
lated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An
aluminum/polyester 100% foil shield and an outer jacket of
PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum
operating temperature range of –4 to 140 F (–20 C to 60 C) is
required. See Table 28 for cables that meet the requirements.
SIGNAL
TYPE
+
COMMON
–
CCN BUS CONDUCTOR
INSULATION COLOR
COMM1 PLUG
PIN NO.
RED
WHITE
BLACK
1
2
3
NOTE: If a cable with a different color scheme is selected, a
similar color code should be adopted for the entire network.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous field
must be connected to a ground at one point only. If the commu-
nication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only).
To connect the unit to the network (Fig. 84):
1. Turn off power to the control box.
Table 28 — CCN Connection Approved
Shielded Cables
2. Cut the CCN wire and strip the ends of the red (+), white
(common) and black (–) conductors. (If a different net-
work color scheme is used, substitute appropriate colors.)
3. Wire the CCN to the screw terminals on the COMM
board as follows (Fig. 84):
MANUFACTURER
Alpha
CABLE PART NO.
2413 or 5463
A22503
American
Belden
a. Secure the red (+) wire to CCN screw terminal +
on the COMM board.
b. Secure the white (common) wire to CCN screw
terminal C on the COMM board.
8772
Columbia
02525
73
Download from Www.Somanuals.com. All Manuals Search And Download.
c. Secure the black (–) wire to CCN screw terminal –
on the COMM board.
using the BACview keypad/display unit, press and hold
the “FN” key then press the “.” Key.
d. Secure shield wire to CCN screw terminal
SHIELD on the COMM board.
To install a BT485 terminator, push the BT485 on to the
BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
i-Vu® Open Control System Master Prices.
MS/TP WIRING RECOMMENDATIONS — Recommen-
dations are shown in Tables 29 and 30. The wire jacket and UL
temperature rating specifications list two acceptable alterna-
tives. The Halar specification has a higher temperature rating
and a tougher outer jacket than the SmokeGard specification,
and it is appropriate for use in applications where the user is
concerned about abrasion. The Halar jacket is also less likely to
crack in extremely low temperatures.
IMPORTANT: A shorted CCN bus cable will prevent
some routines from running and may prevent unit from
starting. If abnormal conditions occur, unplug the connec-
tor. If conditions return to normal, check CCN connector,
and run new cable if necessary. A short in one section of
the bus can cause problems with all system elements on
the bus.
Optional UPC Open Installation
WIRING THE UPC OPEN TO THE MS/TP NET-
WORK — The UPC Open controller communicates using
BACnet on an MS/TP network segment communications at
9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a dai-
sy-chain configuration. Wire specifications for the cable are
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,
twisted, stranded, shielded copper wire. The maximum length
is 2000 ft.
Install a BT485 terminator on the first and last controller on
a network segment to add bias and prevent signal distortions
due to echoing. See Fig. 85-87.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's
BAS Port.
2. Check the communications wiring for shorts and
grounds.
3. Connect the communications wiring to the BAS port’s
screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not current-
ly connected.
NOTE: Use the specified type of wire and cable for maximum
signal integrity.
Smoke Control Modes — Rooftop units can be used
for aid in building smoke control in the event of a building fire.
The available functions include: Fire Shutdown, Pressuriza-
tion, Evacuation, and Smoke Purge. These functions are
enhanced when multiple rooftop units are used to zone a build-
ing. See Table 31 and Fig. 82 and 83.
FIRE SHUTDOWN — Fire Shutdown mode terminates all
unit operation (cooling, heating, supply fan, and power
exhaust). This mode prevents recirculation of contaminated air
back into the space. The mode will not allow admission into
the space of unsuitable outside air. See Fig. 82 for wiring.
PRESSURIZATION — Pressurization mode is intended to
keep smoke out of a zone. The factory-installed optional econ-
omizer is required for this function. Pressurization is accom-
plished by the following:
• opening the economizer (option)
• running the supply fan (optional inlet guide vanes open
or optional VFD at normal duct static pressure set point)
• closing the power exhaust dampers (if installed as option
or accessory)
• shutting off the power exhaust fans (if installed as option
or accessory)
5. Verify communication with the network by viewing a
module status report. To perform a module status report
Table 29 — MS/TP Wiring Recommendations
SPECIFICATION
Cable
Conductor
Insulation
Color Code
Twist Lay
RECOMMMENDATION
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
22 or 24 AWG stranded copper (tin plated)
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Black/White
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Aluminum/Mylar shield with 24 AWG TC drain wire
Shielding
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
Jacket
DC Resistance
Capacitance
Characteristic Impedance
Weight
15.2 Ohms/1000 feet (50 Ohms/km) nominal
12.5 pF/ft (41 pF/meter) nominal conductor to conductor
100 Ohms nominal
12 lb/1000 feet (17.9 kg/km)
SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)
UL Temperature Rating
Voltage
Listing
300 Vac, power limited
UL: NEC CL2P, or better
LEGEND
AWG
CL2P
DC
— American Wire Gage
— Class 2 Plenum Cable
— Direct Current
FEP
NEC
O.D.
TC
— Fluorinated Ethylene Polymer
— National Electrical Code
— Outside Diameter
— Tinned Copper
— Underwriters Laboratories
UL
74
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 30 — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
Description
RECOMMENDED VENDORS AND PART NUMBERS
Connect Air
International
Contractors
Wire and Cable
Wire Type
Belden RMCORP
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
W221P-22227
W241P-2000F
—
25160PV
CLP0520LC
MS/TP
Network (RS-485)
82841 25120-OR
21450
—
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
W184C-2099BLB 6302UE
CLP0442
LEGEND
— American Wire Gage
— Class 2 Plenum Cable
— Communications Plenum Rated
— Fluorinated Ethylene Polymer
— Tinned Copper
AWG
CL2P
CMP
FEP
TC
BT485
TERMINATOR
BACNET
CONNECTION
POWER LED
Tx1 LED
Rx1 LED
BACNET
BAUD RATE
DIP SWITCHES
Tx2 LED
Rx2 LED
ADDRESS
ROTARY
SWITCHES
RUN LED
ERROR LED
Fig. 85 — UPC Open Controller
This allows the space to be overpressurized relative to adjacent
zones and prevents or slows entry of smoke into this space
from adjacent zones. See Fig. 82 for wiring.
accessory power exhaust is required for this function. Evacua-
tion is accomplished by the following:
• turning the supply fan off
EVACUATION — Evacuation mode removes smoke or un-
desirable air from interior spaces without reintroducing unsuit-
able air. The factory-installed optional economizer with option/
• opening the economizer (option required)
• running the exhaust fans (option or accessory required)
• opening the exhaust dampers.
See Fig. 82 for wiring.
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 86 — Open System Network Wiring
Fig. 86 — BT485 Installation
SMOKE PURGE — Smoke Purge mode removes smoke
Table 31 — Smoke Control Modes
from the interior spaces and replaces it with fresh outside air.
The factory-installed optional economizer with option/
accessory power exhaust are required for this function. Smoke
purge is accomplished by the following:
MODE
FUNCTION
Fire
Shutdown
Pressur-
ization
Smoke
Purge*
On
Open/On
Open
Evacuation*
Supply Fan
VFD†
Economizer
Off
—
Closed
On
Open/On
Open
Off
—
Open
• turning supply fan on
• opening the economizer (option required)
• running the exhaust fans (option or accessory required)
• opening the exhaust dampers
Return Air
Damper
Open
Off
Closed
Off
Closed
On
Closed
On
See Fig. 82 for wiring.
Exhaust
Fans
Exhaust
Damper
SMOKE CONTROL INSTALLATION — Implementation of
the various smoke control modes on these units requires the in-
staller to modify the unit wiring to add contacts (via either
manual switches or relays) that will selectively interrupt and
override standard factory control sequences. See Table 31 and
Fig. 81 and 82 for more information.
Closed
Closed
Open
Open
LEGEND
VAV — Variable Air Volume
VFD — Variable Frequency Drive
*Power exhaust option required for this mode.
†Applicable to VAV units with appropriate options.
Copyright 2010 Carrier Corporation