Carrier Air Conditioner 90MA MF MU User Manual

Marine/Industrial  
Single Package  
Cooling Unit  
Models  
90MA/MF/MU, Design Series Two  
Beginning Serial Number C00400  
62--10458--00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY SUMMARY  
GENERAL SAFETY NOTICES  
The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this  
manual. They are recommended precautions that must be understood and applied during operation and maintenance  
of the equipment covered herein. The general safety notices are presented in thefollowing threesections labeled: First  
Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautions appearing  
elsewhere in the manual follows the general safety notices.  
FIRST AID  
An injury, no matterhowslight, should nevergo unattended. Always obtain first aid ormedical attentionimmediately.  
OPERATING PRECAUTIONS  
Always wear safety glasses.  
Keep hands, clothing and tools clear of the evaporator and condenser fans.  
No work should beperformed on theunit until all circuit breakers, start-stop switches areturned off, and powersupply  
is disconnected.  
Always work in pairs. Never work on the equipment alone.  
In case of severe vibration or unusual noise, stop the unit and investigate.  
MAINTENANCE PRECAUTIONS  
Beware of unannounced starting of the evaporator fan. Do not open the evaporatoraccess panels before turning power  
off, disconnecting and securing the power source.  
Be sure power is turned off before working on motors, controls, solenoid valves and electrical control switches. Tag  
circuit breaker and power supply to prevent accidental energizing of circuit.  
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems  
with the system should be diagnosed, and any necessary repairs performed, by qualified service personnel.  
In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).  
SPECIFIC WARNING AND CAUTION STATEMENTS  
To help identify the label hazards on the unit and explain the level of awareness each one carries, an explanation is  
given with the appropriate consequences:  
WARNING -- means to warn against hazards or unsafe conditions which could result in severe personal injury or  
death.  
CAUTION -- means to warn against potential hazard or unsafe practice which could result in product or property  
damage.  
The statements listed below are applicable to the unit and appear elsewhere in this manual. These recommended  
precautions must be understood and applied during operation and maintenance of the equipment covered herein.  
WARNING  
Never reach into unit while fan is running. Lock open and tag unit disconnect before working on fan.  
Remove fuses and take them with you after noting this on tag.  
WARNING  
Follow all Safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid  
solution.  
WARNING  
Lock open and tag unit disconnect before working on fan motor. Remove fuses and takethem with you  
after noting this on tag.  
CAUTION  
Compressor crankcase heater must be energized for 24 hours prior to start up to prevent compressor  
bearing damage.  
62--10458--00  
Safety-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
Sharp edges ofcoil fins areexposed. To preventinjury, cover top of evaporatorwith cardboard or a few  
layers of heavy tape.  
CAUTION  
To avoid coil damage, cover evaporator face with plywood or other rigid sheet material. If any coil fins  
are mashed or bent, straighten with a coil fin comb of the proper tooth spacing (refer to “coil fins/inch”  
in Table 1 through Table 2). Check for refrigerant leaks.  
CAUTION  
Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator  
coils to prevent coil damage.  
62--10458--00  
Safety-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
PARAGRAPH NUMBER  
Page  
GENERAL SAFETY NOTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1  
FIRST AID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1  
OPERATING PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1  
MAINTENANCE PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1  
SPECIFIC WARNING AND CAUTION STATEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety-1  
1.  
2.  
3.  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MODEL CHART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Protect Unit from Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Install Accessory Heating Coil (if applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Install Accessory Plenum (If Supplied) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Install Ventilation--Air Ductwork (If required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Install Return Air Ductwork (If required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Check Return--Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
1
1
3.1  
3.2  
3.3  
3.4  
3.5  
3.6  
3.7  
3.8  
3.9  
1
1
1
1
1
1
1
1
5
3.10 Align Fan Shaft and Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.11 Check Compressor Spring Mounts (008 & 012 size only) . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.12 Make Condenser Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.13 Install Condensate Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3.14 Make Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5
6
6
7
7
4.  
5.  
8
4.1  
4.2  
4.3  
To Start Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
To Shut Down Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Return--Air Grille Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Access Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Evaporator Fan Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Return--Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Water Regulating Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
8
8
8
9
5.1  
5.2  
5.3  
5.4  
5.5  
5.6  
5.7  
5.8  
5.9  
9
9
9
10  
10  
10  
10  
10  
11  
12  
12  
12  
12  
12  
12  
5.10 Evaporator Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5.11 Pressure Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5.12 Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5.13 Cycle--LocTM -- Protection Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5.14 Discharge and Suction Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5.15 Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
i
62--10458--00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIST OF ILLUSTRATIONS  
FIGURE NUMBER  
Page  
1
Figure 1 Base Unit Interior Details (Typical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 2 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 3 Horizontal Wheel Centering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 4 Concentric Wheel Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 5 Connection Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 6 Typical Condenser Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 7 Condensate Drain Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 8 Fan Pulley Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 9 Gravity Flow Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 10 Forced Circulation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 11 Charging Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 12 Mounting Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 13 Wiring Schematic -- 90MA/MF/MU004/006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 14 Component Arrangement -- 90MA/MF/MU004/006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 15 Wiring Schematic -- 90MA/MF/MU008/012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 16 Component Arrangement -- 90MA/MF/MU008/012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5
5
5
6
6
7
9
10  
11  
11  
13  
14  
15  
16  
17  
LIST OF TABLES  
TABLE NUMBER  
Page  
Table 1 90MA/MF/MU Physical Data -- Refrigerant 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 2 90MA/MF/MU Physical Data -- Refrigerant 407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 3 90MA/MF Physical Data -- Refrigerant 134a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 4 Recommended Line Sizes, Remote Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2
3
4
7
62--10458--00  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. INTRODUCTION  
3.1  
Inspect Unit  
Check unit against shipping order. Inspect carefully for  
concealed shipping damage. If shipment is damaged or  
The 90M series single--package cooling units (See  
Figure 1) are designed to provide air conditioning  
aboard marine vessels and in industrial applications.  
The 90MA units are fitted with sea water cooled  
condensers while the 90MF units are fitted with fresh  
water cooled condensers. Both units are factory  
charged, wired and piped. The 90MU units are similar  
except they are configured for use with a remote  
mounted condenser.  
incomplete, fileclaimwith transportation companyand  
advise Carrier Transicold immediately.  
3.2  
Protect Unit from Damage  
To maintain warranty, protect unit against adverse  
weather, theft, or vandalism on job site.  
3.3  
Provide Unit Support  
Refer to Figure 2 and Table 1 through Table 2 for unit  
size and weight. If desired, construct a frame of I--beams  
or angle iron that adequately supports unit. See  
Figure 12.  
An accessory discharge plenum may be installed to  
provide free--blow into the conditioned space. Also, an  
accessory electric, hot water or steam coil heater may be  
installed to provide comfort heating.  
3.4  
Install Accessory Heating Coil (if applicable)  
Electric heaters are installed at the top of the unit. Water  
or steam coil must be installed through the back of the  
unit as described in the Installation Instructions shipped  
with the accessory coil.  
3.5  
Rig and Place Unit  
NOTE  
Install accessories before placing unit.  
a. Provide space around unit for service, filter access,  
and overhead clearance as indicated in Figure 2.  
b. Move and store unit in upright position.  
c. Useslings with spacerunderbaseskid to preventpan-  
el damage when using hoist.  
(90MA/MF  
ONLY)  
d. Units as shipped are adequately dampened against  
vibration. If additional dampening is desired, place  
sponge rubber or rubber mat, between deck and base  
of unit or install vibration isolators.  
Figure 1 Base Unit Interior Details (Typical)  
2.  
MODEL CHART  
e. Unit should be level. Unit leveling tolerance is 1/8  
inch per linear foot in any direction.  
This manual covers 90M design series two units as  
shown in the following model chart.  
3.6  
Install Accessory Plenum (If Supplied)  
Use plenum as template to mark hole locations in top  
panel. Drill 5/32--in. (0.4 cm) holes in top panel at  
marked locations and attach plenum with screws  
supplied.  
1
9
2
0
3
4
5
6
1
7
8
9
6
10 11  
1
3
2
---  
2
M
A
3.7  
Install Ventilation--Air Ductwork  
(If required)  
PRODUCT  
CODE  
Connect ventilation ducts to flanges on outside--air  
supply opening (See Figure 2) using a flexible  
connection. Attach ductwork to ship structure and  
insulate with fiberglass and vapor barrier to reduce  
sound transmission and prevent vapor condensation.  
MODEL  
VOLTAGE  
5 - 208/230-3-60  
6 - 460-3-60  
MA - 90/10 Copper Nickel  
Condenser  
MF - Copper Condenser  
MU - Condenserless  
9 - 400-3-50  
Weatherproof external ductwork, joints, and openings  
in accordance with applicable codes. Ducts passing  
through an unconditioned space must be insulated and  
covered with a vapor barrier.  
2 - R-22  
DESIGN  
SERIES  
3 - R-134a  
4 - R-407C  
NOMINAL COOLING  
CAPACITY (R--22)  
PACKAGING  
3.8  
Install Return Air Ductwork (If required)  
The unit back panel is to be field cut for alternate  
return--air (or outdoor--air inlet) opening as indicated in  
Figure 2. To install ductwork:  
3.  
INSTALLATION  
To install the unit, do the following:  
a. Cut out the alternate return--air opening as required.  
62--10458--00  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 90MA/MF/MU Physical Data -- Refrigerant 22  
R--22 -- English Units  
R--22 -- Metric Units  
BASE UNIT 90MA/MF/MU  
UNITS  
204  
3
206  
5
208  
7.5  
212  
10  
204  
206  
208  
212  
English (Metric)  
NOMINAL CAPACITY  
OPERATING WEIGHT  
Base Unit -- 90MA/MF  
Base Unit -- 90MU  
Tons (kW)  
10.5  
17.6  
26.4  
35.1  
Pounds (kg)  
Pounds (kg)  
Pounds (kg)  
390  
330  
25  
427  
360  
25  
895  
835  
50  
950  
890  
50  
177  
150  
11.3  
194  
163  
11.3  
406  
379  
22.7  
431  
404  
22.7  
Discharge Plenum  
COMPRESSOR TYPE  
Welded Hermetic  
Scroll  
Semi--Hermetic Welded Hermetic  
Reciprocating Scroll  
Semi--Hermetic  
Reciprocating  
Quantity of Cylinders  
--  
--  
--  
--  
--  
--  
4
0
1
6
2
2
--  
--  
--  
--  
--  
--  
4
0
1
6
2
2
Quantity of Unloading Cylinders  
Quantity of Capacity Steps  
DISCHARGE PRESSURE SWITCH  
Opens -- 90MA/MF  
Closes -- 90MA/MF  
Opens -- 90MU  
psig (kPa)  
psig (kPa)  
psig (kPa)  
psig (kPa)  
39510  
29520  
4267  
272569  
2034138  
293748  
2206138  
Closes -- 90MU  
32020  
SUCTION PRESSURE SWITCH  
Opens  
Closes  
OPERATING CHARGE -- 90MA/MF  
CONDENSER -- 90MA/MF  
Number & Type  
psig (kPa)  
psig (kPa)  
pounds (kg)  
274  
677  
18628  
46248  
3.1  
5.3  
11.2  
10  
1.4  
2.4  
5.1  
4.5  
1....Tube In Tube  
2.42 1.48  
Water Volume  
gallon (liter)  
0.39  
0.86  
3.3  
9.2  
EVAPORATOR AIR FAN  
Nominal Flow  
Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz  
2000 3000 4000 1698 2830 4245  
3
cfm (m /h)  
1200  
5660  
Standard Speed Range  
Maximum Allowable RPM  
Belt Quantity / Pulley Pitch Diameter  
Motor Pulley Pitch Diameter Range  
Motor Nominal Rating(@60 Hz)...Frame Size  
Standard  
Alternate (See Note 1)  
Alternate (See Note 1)  
EVAPORATOR COIL  
RPM  
525-750 647-915 495-700 600-850 427-652 593-762 412-583 500-708  
1050  
inches (cm)  
inches (cm)  
1 / 8.0  
1 / 6.4  
1 / 8.5  
1 / 7.0 1 / 20.3 1 / 16.3 1 / 21.6 1 / 17.8  
6.1 to 8.6  
2.4 to 3.4  
horse power 1/3...56 3/4...56 1...56  
horse power 3/4...56 1...56  
horse power -- -- -- --  
2...56 .25 / 56 .56 / 56 .75 / 56 1.5 / 56  
3...56 .56 / 56 .75 / 56 1.5 / 56 2.2 / 56  
2...56  
3...56  
-- --  
-- --  
-- --  
2.2 / 56  
-- --  
3/8 (.95 cm) OD, Copper Tubes, Aluminum Fins  
Prime  
Tube Type  
Quantity of Rows...fin Spacing  
Face Area  
fins/inch(cm) 2...14.4 3...14.4  
3...12.5  
7.3 8.5  
2...5.7  
0.46  
3...5.7  
0.46  
3...4.9  
0.68 0.79  
sq ft (sq m)  
5
5
RETURN AIR FILTERS  
Quantity...Size  
Factory Supplied, Cleanable  
4...16 x 20 x 1 2...40.6x63.5x2.5 4...40.6x50.8x2.5  
inches (cm)  
2...16 x 25 x 1  
CONDENSER CONNECTIONS  
Water Inlet (bottom) & Outlet (top)  
Maximum Working Pressure (refrigerant side)  
CONDENSATE DRAIN CONNECTIONS  
ACCESSORY HEATING COILS  
HOT WATER  
inches FPT  
psig (kPa)  
inches FPT  
1/2  
3/4  
1
1
1/2  
3/4  
1
1
400  
3/4  
2758  
3/4  
Quantity of Rows...fin spacing  
Face Area  
fins/inch(cm)  
sq ft (m)  
1...15  
5
1...15  
5
2...14  
6
2...14  
6
1...5.9  
0.46  
1...5.9  
0.46  
2...5.5  
0.56  
2...5.5  
0.56  
Water Inlet (top) & Outlet Connection (bottom)  
STEAM  
inches (cm)  
7/8 ODF  
1--1/4 MPT  
7/8 ODF  
1--1/4 MPT  
Quantity of Rows...fin spacing  
Face Area  
Water Inlet (top) & Outlet Connection (bottom)  
fins/inch(cm)  
sq ft (m)  
inches (cm)  
See Note 2  
See Note 2  
See Note 2  
1...14  
6.9  
1--1/4 MPT  
1...14  
6.9  
See Note 2  
See Note 2  
See Note 2  
1...5.5  
0.64  
1--1/4 MPT  
1...5.5  
0.64  
LEGEND  
FPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter Female  
NOTES:  
1. Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold represen-  
tative.  
2. Accessory heating coil in 004 and 006 units is combination hot water/steam. See hot water data.  
62--10458--00  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 90MA/MF/MU Physical Data -- Refrigerant 407C  
R--407C -- English Units  
R--407C -- Metric Units  
BASE UNIT 90MA/MF/MU  
UNITS  
404  
3
406  
5
408  
7.5  
412  
10  
404  
406  
408  
412  
English (Metric)  
NOMINAL CAPACITY  
OPERATING WEIGHT  
Base Unit -- 90MA/MF  
Base Unit -- 90MU  
Tons (kW)  
10.5  
17.6  
26.4  
35.1  
Pounds (kg)  
Pounds (kg)  
Pounds (kg)  
390  
330  
25  
427  
360  
25  
895  
835  
50  
950  
890  
50  
177  
150  
11.3  
194  
163  
11.3  
406  
379  
22.7  
431  
404  
22.7  
Discharge Plenum  
COMPRESSOR TYPE  
Welded Hermetic  
Scroll  
Semi--Hermetic Welded Hermetic  
Reciprocating Scroll  
Semi--Hermetic  
Reciprocating  
Quantity of Cylinders  
--  
--  
--  
--  
--  
--  
4
0
1
6
2
2
--  
--  
--  
--  
--  
--  
4
0
1
6
2
2
Quantity of Unloading Cylinders  
Quantity of Capacity Steps  
DISCHARGE PRESSURE SWITCH  
Opens -- 90MA/MF  
Closes -- 90MA/MF  
Opens -- 90MU  
psig (kPa)  
psig (kPa)  
psig (kPa)  
psig (kPa)  
39510  
29520  
4267  
272569  
2034138  
293748  
2206138  
Closes -- 90MU  
32020  
SUCTION PRESSURE SWITCH  
Opens  
Closes  
OPERATING CHARGE -- 90MA/MF  
CONDENSER -- 90MA/MF  
Number & Type  
psig (kPa)  
psig (kPa)  
pounds (kg)  
274  
677  
18628  
46248  
3.1  
5.3  
11.2  
10.0  
1.4  
2.4  
5.1  
4.5  
1....Tube In Tube  
2.42 1.48  
Water Volume  
gallon (liter)  
0.39  
0.86  
3.3  
9.2  
EVAPORATOR AIR FAN  
Nominal Flow  
Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz  
2000 3000 4000 1698 2830 4245  
3
cfm (m /h)  
1200  
5660  
Standard Speed Range  
Maximum Allowable RPM  
Belt Quantity / Pulley Pitch Diameter  
Motor Pulley Pitch Diameter Range  
Motor Nominal Rating(@60 Hz)...Frame Size  
Standard  
Alternate (See Note 1)  
Alternate (See Note 1)  
EVAPORATOR COIL  
Tube Type  
Quantity of Rows...fin Spacing  
Face Area  
RETURN AIR FILTERS  
Quantity...Size  
RPM  
525-750 647-915 495-700 600-850 427-652 593-762 412-583 500-708  
1050  
inches (cm)  
inches (cm)  
1 / 8.0  
1 / 6.4  
1 / 8.5  
1 / 7.0 1 / 20.3 1 / 16.3 1 / 21.6 1 / 17.8  
6.1 to 8.6  
2.4 to 3.4  
horse power 1/3...56 3/4...56 1...56  
horse power 3/4...56 1...56  
horse power -- -- -- --  
3/8 OD, Copper Tubes, Aluminum Fins  
Prime Prime  
fins/inch(cm) 2...14.4 3...14.4  
2...56 .25 / 56 .56 / 56 .75 / 56 1.5 / 56  
3...56 .56 / 56 .75 / 56 1.5 / 56 2.2 / 56  
2...56  
3...56  
-- --  
-- --  
-- --  
2.2 / 56  
-- --  
3...12.5  
7.3 8.5  
Factory Supplied, Cleanable  
2...16 x 25 x 1 4...16 x 20 x 1  
2...5.7  
0.46  
3...5.7  
0.46  
3...4.9  
sq ft (sq m)  
5
5
0.68  
0.79  
Factory Supplied, Cleanable  
2...40.6x63.5x2.5 4...40.6x50.8x2.5  
inches (cm)  
CONDENSER CONNECTIONS  
Water Inlet (bottom) & Outlet (top)  
Maximum Working Pressure (refrigerant side)  
CONDENSATE DRAIN CONNECTIONS  
ACCESSORY HEATING COILS  
HOT WATER  
inches FPT  
psig (kPa)  
inches FPT  
1/2  
3/4  
1
1
1/2  
3/4  
1
1
400  
3/4  
2758  
3/4  
Quantity of Rows...fin spacing  
Face Area  
fins/inch(cm)  
sq ft (m)  
1...15  
5
1...15  
5
2...14  
6
2...14  
6
1...5.9  
0.46  
1...5.9  
0.46  
2...5.5  
0.56  
2...5.5  
0.56  
Water Inlet (top) & Outlet Connection (bottom)  
STEAM  
inches (cm)  
7/8 ODF  
1--1/4 MPT  
7/8 ODF  
1--1/4 MPT  
Quantity of Rows...fin spacing  
Face Area  
Water Inlet (top) & Outlet Connection (bottom)  
fins/inch(cm)  
sq ft (m)  
inches (cm)  
See Note 2  
See Note 2  
See Note 2  
1...14  
6.9  
1--1/4 MPT  
1...14  
6.9  
See Note 2  
See Note 2  
See Note 2  
1...5.5  
0.64  
1--1/4 MPT  
1...5.5  
0.64  
LEGEND  
FPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter Female  
NOTES:  
1. Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold represen-  
tative.  
2. Accessory heating coil in 004 and 006 units is combination hot water/steam. See hot water data.  
62--10458--00  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 90MA/MF Physical Data -- Refrigerant 134a  
R--134a -- English Units  
R--134a -- Metric Units  
BASE UNIT 90MA/MF  
UNITS  
308  
312  
308  
312  
English (Metric)  
NOMINAL CAPACITY  
OPERATING WEIGHT  
Base Unit  
Tons (kW)  
5.5  
8
19.3  
28.1  
Pounds (kg)  
Pounds (kg)  
895  
50  
950  
50  
406  
22.7  
431  
22.7  
Discharge Plenum  
COMPRESSOR TYPE -- Reciprocating  
Quantity of Cylinders  
Quantity of Unloading Cylinders  
Quantity of Capacity Steps  
DISCHARGE PRESSURE SWITCH  
Opens  
Semi--Hermetic  
Semi--Hermetic  
4
0
1
6
2
2
4
0
1
6
2
2
psig (kPa)  
psig (kPa)  
33510  
23520  
231069  
1620138  
Closes  
SUCTION PRESSURE SWITCH  
Opens  
Closes  
OPERATING CHARGE  
CONDENSER  
psig (kPa)  
psig (kPa)  
pounds (kg)  
73  
225  
4821  
15235  
11.2  
10  
5.1  
4.5  
Number & Type  
Water Volume  
1....Tube In Tube  
2.42  
1....Tube In Tube  
9.2  
gallon (liter)  
EVAPORATOR AIR FAN  
Nominal Flow  
Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz  
3
cfm (m /h)  
3000  
4000  
4245  
5660  
Standard Speed Range  
Maximum Allowable RPM  
Belt Quantity / Pulley Pitch Diameter  
Motor Pulley Pitch Diameter Range  
Motor Nominal Rating(@60 Hz)...Frame Size  
Standard  
Alternate (See Note 1)  
Alternate (See Note 1)  
EVAPORATOR COIL  
Tube Type  
RPM  
495--700  
600--850  
412--583  
500--708  
1050  
inches (cm)  
inches (cm)  
1 / 8.5  
1 / 7.0  
1 / 21.6  
1 / 17.8  
2.4 to 3.4  
6.1 to 8.6  
horse power  
horse power  
horse power  
1...56  
2...56  
3...56  
2...56  
3...56  
-- --  
.75 / 56  
1.5 / 56  
2.2 / 56  
1.5 / 56  
2.2 / 56  
-- --  
3/8 OD(0.95) cm, Copper Tubes, Aluminum Fins  
Prime  
Quantity of Rows...fin Spacing  
Face Area  
fins/inch(cm)  
sq ft (sq m)  
3...12.5  
3...14.9  
7.3  
8.5  
0.68  
0.79  
RETURN AIR FILTERS  
Quantity...Size  
Factory Supplied, Cleanable  
inches (cm)  
4...16 x 20 x 1  
4...40.6 x 50.8 x 2.5  
CONDENSER CONNECTIONS  
Water Inlet (bottom) & Outlet (top)  
Maximum Working Pressure (refrigerant side)  
CONDENSATE DRAIN CONNECTIONS  
ACCESSORY HEATING COILS  
HOT WATER  
inches FPT  
psig (kPa)  
inches FPT  
1
1
1
1
400  
3/4  
2758  
3/4  
Quantity of Rows...fin spacing  
Face Area  
fins/inch(cm)  
sq ft (m)  
2...14  
6
2...14  
6
2...5.5  
0.56  
2...5.5  
0.56  
Water Inlet (top) & Outlet Connection (bottom)  
STEAM  
Quantity of Rows...fin spacing  
Face Area  
inches (cm)  
1--1/4 MPT  
1--1/4 MPT  
1--1/4 MPT  
1--1/4 MPT  
fins/inch(cm)  
sq ft (m)  
inches (cm)  
1...14  
6.9  
1...14  
6.9  
1...5.5  
0.64  
1...5.5  
0.64  
Water Inlet (top) & Outlet Connection (bottom)  
LEGEND  
FPT = Female Pipe Thread MPT = Male Pipe Thread ODF = Outside Diameter Female  
NOTES:  
1. Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold represen-  
tative.  
62--10458--00  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT  
004  
006  
008,012  
A
B
C
36.19(919)  
21.88(556)  
59.12(1501)  
48(1219)  
29.62(752)  
69.50(1765)  
D
E
SEE NOTE 2  
24(610)  
F
G
H
J
13.81(351)  
13.13(333)  
0.75(19)  
16.44(418)  
19.38(492)  
17.25(438)  
1.31(33)  
15(381)  
0.75(19)  
10.62(270)  
12.5(318)  
11.44(291)  
K
17.06(433)  
23.25(591)  
25.37(644)  
17(432)  
L
20.50(521)  
17(432)  
M
N
P
Q
R
31.88(810)  
2.06(52)  
42.62(1083)  
3(76)  
10(254)  
12.50(318)  
16(406)  
15.56(395)  
NOTES:  
1. Certified dimension drawings available upon request  
2. Minimum required clearance at back of unit is zero.  
Clearance above and at right (90MA008,012 only) and at leftof  
unit depends on space required for accessory plenum,  
ductwork, condenser piping, accessory heater piping,  
condensate drain line and power wiring  
3. Water connections are located on left side of unit (Refer to  
“Make Condenser Connections”, Condensate drain  
connections are located on left side of unit for 004 & 006, and  
on both sides of unit for 008 & 012.  
Figure 2 Unit Dimensions  
3.10 Align Fan Shaft and Wheel  
b. Attach a one--inch (2.5 cm) flange or attach aflanged,  
flexible duct connection directly to unit.  
HORIZONTAL WHEEL CENTERING -- All wheels must be  
horizontally centered between the inside edges of their  
fan scroll ventures (Figure 3). Adjust as follows:  
a. Loosen set screws holding wheel to shaft.  
b. Center the wheel by sliding it horizontally.  
c. Re--tighten set screws.  
CONCENTRIC ALIGNMENT -- Shaft and wheels must be  
concentrically centered with the venturi (Figure 4).  
Shaft bearings are supported by bearing supports. If  
shaft and wheels are concentrically misaligned from  
shipping shock, it is possibleto re--bend bearing support  
arms to original positions. Replace the bearing support  
if it has been extensively damaged during shipping.  
If an outdoor makeup air damper is to be installed, at-  
tach it directly to unit back panel and install flexible  
connection between damper and remaining duct-  
work. Use accepted ductwork installation proce-  
dures. Follow all applicable codes.  
c. Completely blank off the standard return--airopening  
with a field--fabricated fillerpanel. Thepanel must be  
removable for service access. Refer to paragraph 5.1.  
3.9  
Check Return--Air Filters  
Ensure filters shipped with unit are in place. Never  
operate unit without return air filters in place.  
DIMENSION “D” MUST BE EQUAL ALL AROUND  
Figure 3 Horizontal Wheel Centering  
Figure 4 Concentric Wheel Alignment  
62--10458--00  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
90MA/MU008/012 UNITS  
90MA/MF004/006 UNITS  
90MU008/012 UNITS  
90MU004/006 UNITS  
UNIT  
90MA/MF004  
90MA/MF006  
A*  
1/2  
3/4  
B*  
1/2  
-- --  
C*  
-- --  
3/4  
D*  
¾ FPT  
E
-- --  
-- --  
F
-- --  
-- --  
G
1.75  
(45)  
90MA/MF008/012  
90MU004  
90MU006  
90MU008/012  
1”  
-- --  
-- --  
-- --  
1”  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
1/2 flare  
1/2 flare  
5/8 O.D.  
1/2 flare  
1/2 flare  
3/4 O.D.  
* A = Condenser In, B & C = Condenser Out, D = Condensate, all Female Pipe Thread, E = Liquid Refrigerant (field cut), F =  
Refrigerant Discharge (field cut), G = Electrical Opening  
Figure 5 Connection Locations  
3.11 Check Compressor Spring Mounts  
(008 & 012 size only)  
Install water--regulating valve in water supply line  
outside cabinet as follows.  
The compressors are held rigid in shipment by bolts  
extending through a washer, grommet and compressor  
foot into a weld nut. Loosen each bolt (4 per  
compressor) until compressor floats freely on springs.  
Then re--tighten bolts until thereis slight pressure on the  
neoprene gasket. This will steady the compressor and  
prevent start and stop rocking.  
See Figure 5  
The compressors have reversible oil pumps that operate  
in either direction; therefore, the direction of rotation  
need not be checked.  
3.12 Make Condenser Connections  
UNIT MOUNTED CONDENSER (90MA/MF) -- Condenser  
water inlet and outlet connections are shown in  
Figure 5. Piping arrangements for condenser cooling  
water are shown in Figure 6.  
Figure 6 Typical Condenser Water Piping  
a. Route regulating valve capillary with its flare nut to  
the port on refrigerant discharge line (Figure 1), us-  
ing any convenient unused opening on side of unit.  
Use a grommet in panel to prevent chafing of capil-  
lary.  
b. Remove cap from discharge line fitting.  
c. Remove cotter pin taped to discharge line fitting. In-  
sert pin, split end first, into regulating valve flare.  
Connect condenser water supply and return lines as  
indicated. When connecting water lines, hold the  
condenser inlet and outlet stubs firmly with a wrench at  
the female pipe thread hex fitting to prevent twisting.  
Do not use water lines smaller than connection sizes  
shown in Figure 5. Observeall applicableplumbingand  
sanitary codes.  
62--10458--00  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 Recommended Line Sizes, Remote Condenser  
LENGTH OF RUN  
UNIT  
(90MU)  
0--25  
26--50  
DISCH  
51--75  
DISCH  
76--100  
DISCH  
DISCH  
LIQUID  
1/2(1.3)  
1/2(1.3)  
5/8(1.6)  
LIQUID  
1/2(1.3)  
1/2(1.3)  
5/8(1.6)  
LIQUID  
1/2(1.3)  
1/2(1.3)  
LIQUID  
1/2(1.3)  
1/2(1.3)  
004  
006  
008  
012  
1/2 (1.3)  
5/8(1.6)  
7/8(2.2)  
7/8(2.2)  
5/8(1.6)  
7/8(2.2)  
7/8(2.2)  
5/8(1.6)  
7/8(2.2)  
7/8(2.2)  
7/8(2.2)  
7/8(2.2)  
5/8(1.6) 1-1/8(2.9) 5/8(1.6)  
5/8(1.6) 1-1/8(2.9) 5/8(1.6) 1-1/8(2.9) 5/8(1.6) 1-1/8(2.9) 5/8(1.6)  
NOTES:  
1. Line sizes given in inches (cm).  
2. Line sizes should never be smaller than cooling unit connection size.  
3. A nominal number of fittings has been considered in determining line sizes. Smaller line sizes may be considered  
if run is simple and few fittings are used.  
d. Hold flare tightly against fitting while connecting  
flare nut. Round end of cotter pin will depress core of  
fitting. The opened fitting allows refrigerant pressure  
to act on water regulating valve. Tighten nut to pre-  
vent leakage. Fitting automatically seals when nut is  
removed.  
REMOTE MOUNTED CONDENSER (90MU) -- I n s t a l l  
remote mounted condenser in accordance with the  
installation instructions provided with condenser.  
Connection locations for liquid and discharge lines are  
shown in Figure 5. Recommended line sizes are given  
in Table 4. Additional instructions can be found in  
Carrier System Design Manual, Part 3, for standard  
refrigeration piping techniques. On 008 and 012 size  
units, secure discharge line to bracket at unit outlet  
using proper clamp from supplied fastener package  
Condenserless (90MU) units are shipped with a  
refrigerant holding charge. After refrigerant  
connections are made, leak test, reclaim refrigerant,  
evacuate, and charge system as described in paragraph  
5.9.  
Figure 7 Condensate Drain Trap  
Do not use drain line smaller than 3/4 inch. Use hole(s)  
provided in panel for drain line. Pitch drain line  
downward toward scupper. Installation of a plugged tee  
is recommended for cleaning. Fill trap with water to  
make an air seal. Observe all sanitary requirements.  
3.13 Install Condensate Drain Line  
Install a trapped condensate drain line at unit drain  
connection. The drain requires standard pipe connected  
to condensate pan nipple(s). Figure 7 shows proper trap  
design.  
3.14 Make Electrical Connections  
GENERAL -- Provide an adequate fused disconnect  
switch within sight of the unit. Provision for locking  
switch open (OFF) is advisable to prevent power from  
being turned on when unit is being serviced.  
Determine design negative static pressure. This  
pressure is not the same as fan total static pressure,  
which includes pressure losses downstream as well as  
upstream from the evaporator air fan. Always assume  
the worst conditions, such as having return air filters  
clogged with debris.  
POWER WIRING -- Conduit opening for all units is on left  
side of unit near control box. Connect field power wires  
at the compressor contactor.  
Supply voltage must be in accordance with nameplate  
voltage. Voltage between phases must be balanced  
within 2% and current within 10% with compressor  
running. Correct improper voltage or phase imbalance.  
Unit failure as a result of operation on improper line  
voltage or excessive phase imbalance constitutes abuse  
and shall void the Carrier warranty. Use the following  
formula to determine the percent voltage imbalance.  
Referring to Figure 7, differential 1 must be equal to or  
larger than negative static pressure at design operating  
condition. Store enough water in trap to prevent losing  
seal. Differential 2 must be equal to or larger than  
one--half the maximum negative static pressure. To  
avoid loss of seal when the fan starts, differential 3 must  
be greater than the maximum negative static pressure.  
62--10458--00  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
e. Allow crankcase heater to remain energized (unit  
power on) for at least 24 hours. Open any valves in  
condenser cooling water supply lines and then set se-  
lector switch at COOL position. If room temperature  
is above thermostat setting compressor will start. On  
first start--up, set water regulating valve. (Refer to  
paragraph5.7.)  
f. Set thermostat for comfort as desired.  
4.2  
To Shut Down Unit  
a. Turn selector switch to OFF position. Do not shut off  
main power except to service unit. The crankcase  
heater is operative only when main power is on. (Re-  
fer to paragraph 5.12).  
b. If unit is to be used for winter heating, set selector  
switch at HEAT position and re--set thermostat at de-  
sired setting.  
c. Ifunit may beexposed tofreezing temperatures, drain  
water from condenser and water piping. Add a non-  
corrosive antifreeze to residual water in system.  
CONTROL WIRING -- On extended voltage (208/230--v)  
units, the control transformer is factory wired for 208--v  
usage. If unit is to be used on 230--v system, reconnect  
primary wiring on transformer. See Figure 13 (004/006  
size) or Figure 15 (008/012 size).  
4.3  
Sequence Of Operation  
Unit operation is dependent on the position of the mode  
selector switch. (See note 3, Figure 14 or Figure 16.)  
Operation sequence for each switch position is provided  
in the following paragraphs.  
OFF POSITION: With correct voltage supplied at the  
field powersupply terminals, seeFigure 13 or Figure 15  
power flows through normally closed crankcase heater  
relay (CHR) contacts (CHR, 4/5) to energize the  
crankcase heater (CH).  
TO PLACE THE UNIT IN THE FAN MODE: The  
switch (SW) is placed in the FAN position to supply 24  
volt control power, to energize indoor fan contactor  
(IFC). Energizing IFC closes contacts (IFC, 11/21,  
12/22 & 13/23) to energize the motor. Operation of the  
crankcase heater is maintained.  
On all units, the thermostat is factory installed. A  
sensing element is provided in the return air. To wire  
these units to aremote thermostat, or to a remotecontrol  
switch and thermostat, refer to unit Wiring Diagram or  
contact your Carrier Transicold representative.  
4.  
OPERATION  
CAUTION  
Compressor crankcase heater must be ener-  
gized for 24 hours prior to startup toprevent  
compressor bearing damage.  
TO PLACE THE UNIT IN THE COOL MODE: The  
switch (SW) is placed in the COOL position. With  
thermostat (T--LOW) calling for cooling (closed to  
contacts R & W) control power flows from TRAN  
through T--LOW, SW and compressor lockout (CL)  
normally closed contacts to the discharge pressure  
switch (DPS). On 008/012 size units, flow continues  
through the compressor internal protector (IPC),  
compressor overloads (OLA & OLB) and the suction  
pressure switch (SPS), to energize CHR. On 004/006  
size units, flow continues directly thorough the suction  
pressure switch to energize CHR.  
Energizing CHR opens contacts CHR 4--5 to  
de--energize CH and closes contacts CHR 1--3 and  
energizethecompressor contactor(CC). Energizing CC  
closes its contacts to start the compressor motor (C).  
Operation of the indoor fan motor (IFM) is maintained.  
On 90MU units, power also flows from terminal TB1--5  
to energize condenser fan relay (CFR). Energizing CFR  
closes its contacts to supply power to the field supplied  
condenser fan relay.  
012 sizeunits arefitted with a two stage cooling system.  
On these units, if thermostat switch T--HIGH is also  
calling for cooling, power flows through thermostat  
4.1  
To Start Unit  
a. Thoroughly inspect exterior of unit. Clean and dust  
up debris, then wash with mild soap and water solu-  
tion.  
b. On 008 & 012 size units, ensure compressor dis-  
charge, suction and liquid service valves are open.  
The valves are accessible from the front of the unit.  
To open valve, turn counterclockwise. Afteropening,  
replace and tighten valve cap to prevent leakage.  
Check oil level in compressor sight glass. If level is  
below glass, add oil to bring level to approximately  
1/4 glass. If level is above bottom of glass, do not re-  
move any oil until the crankcase heater has been ener-  
gized for at least twenty--four hours.  
c. With selector switch in OFF position, turn main pow-  
er on. Leave power on for 24 hours so that crankcase  
heater can drive off accumulated refrigerant.  
d. If desired, the selector switch may be placed in the  
FAN position during the crankcase warm--up period.  
On first start--up, check fan speed (Table 1 through  
Table 2) and rotation (Figure 1). If fan requires ad-  
justment, refer to paragraph 5.3.  
62--10458--00  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2  
Access Panel Removal  
switch T--HIGH to energize liquid line solenoid (LLS)  
[to activate the full evaporator coil and all compressor  
cylinders]. If thermostat switch T--HIGH is not calling  
for cooling, power flows to energize compressor  
unloader solenoid (US) [to unload compressor  
cylinders].  
a. Remove return--air grille as described above.  
b. Remove the panel fastening screws now exposed.  
c. Pull out and down to remove top panel.  
d. Pull out and up to remove bottom panel.  
When room temperature falls to the cutout point of  
T--LOW, switch T--LOW opens to de--energize CHR,  
stopping the compressor motor and energizing CH. The  
machine enters a stand--by state, ready to restart  
automatically on room thermostat call for cooling.  
5.3  
Evaporator Fan Adjustment  
WARNING  
Never reach into unit while fan is running.  
Lock open and tag unit disconnect before  
working on fan. Remove fuses and take them  
with you after noting this on tag.  
Ifany safety deviceopens (CLO, SPS, DPS, IP, OLAor,  
OLB) relay CHR is de--energized, stopping the  
compressor motor and energizing the crankcase heater.  
SPEED ADJUSTMENT -- The fan motor pulleys are  
factory set at the fan speeds listed in Table 1, Table 3 or  
Table 2. to change fan speed, do the following:  
TO PLACE THE UNIT IN THE HEAT MODE: The  
switch (SW) is placed in the HEAT position. With  
thermostat (T--LOW) calling for heating (closed to  
contacts R & B), 24 volt control power flows through  
manual reset temperature cutout MC to energize safety  
relay H2. Poweralso flows through airflow switch (AS)  
and automatic cutout (AC) to energize operating relay  
(H1). Energizing relays H1 and H2 closes contacts to  
energize the heaters.  
a. Shut off unit power supply.  
b. Loosen fan belt by loosening fan motor from mount-  
ing bracket. Do not loosen fanmotormountingbrack-  
et from unit.  
c. Loosen movable pulley flange set screw (Figure 8).  
d. Screwmovableflangetoward fixed flangeto increase  
fan speed and away from fixed flange to decrease  
speed. Increasing fan speed increases load on motor.  
Do not exceed maximum allowable fan speed or mo-  
tor full load amps indicated on motor nameplate.  
e. Set movable flange set screw at nearest flat of pulley  
hub and tighten set screw.  
Placing SW in the FAN position de--energizes all  
cooling orheating control circuits in thesamemanneras  
activation of a safety switch. Placing SW in the OFF  
position also de--energizes IFC to stop the indoor fan  
motor.  
f. Check pulley alignment and belt tension adjustment  
as described below.  
5.  
SERVICE  
g. Check fan operation. Repeat above procedure as re-  
quired.  
WARNING  
Never reach into unit while fan is running.  
Lock open and tag unit disconnect before  
working on fan. Removefuses and take them  
with you after noting this on tag.  
CAUTION  
Sharp edges of coil fins are exposed. To pre-  
vent injury, cover top of evaporator with  
cardboard or a few layers of heavy tape.  
CAUTION  
To avoid coil damage, cover evaporator face  
with plywood or other rigid sheet material.  
If any coil fins are mashed or bent, straight-  
en with a coil fin comb of the proper tooth  
spacing (refer to “coil fins/inch” in Table 1  
through Table 2). Check for refrigerant  
leaks.  
5.1  
Return--Air Grille Removal  
Figure 8 Fan Pulley Adjustment  
a. Pull grille out from top.  
PULLEY ALIGNMENT -- Shut off unit power supply.  
Loosen fan motor pulley set screws and slide fan pulley  
along fan shaft. Make angular alignment by loosening  
motor from mounting bracket (See Figure 8).  
b. Pull grille up to release hinge pins from lower panel.  
c. To reassemble, reverse procedure.  
62--10458--00  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
BELT TENSION ADJUSTMENT -- Shut off unit power  
supply. Loosen fan motor from mounting bracket. Do  
not loosen motor mounting bracket from unit. Movefan  
motor up or down until proper belt tension is achieved  
(approximately 3/4--in. deflection with 8--pound  
tension at midpoint of belt span).  
spring tension, decrease water flow and increasepres-  
sure.  
If pressure reading is above operating range, rotate  
the square head adjusting screw clockwise; this will  
decrease spring tension, increase water flow and de-  
crease pressure.  
Lubrication -- Fan motor and fan shaft bearings are  
lubricated for the life of the bearings. No re--lubrication  
is required  
c. Only the water regulating valve opening point is ad-  
justable. The closing point is 3 to 7 psig below the  
opening point and is non--adjustable.  
5.4  
Return--Air Filter  
5.8  
Condenser  
Inspect filters twice monthly and clean as required by  
operating conditions. Filter size and type are listed in  
Table 1, Table 3 or Table 2. To clean filters flush with  
hot water or steam or soak in a mild water solution of  
soap or detergent. Refer to filter manufacturer’s  
instructions as applicable. Do not operate unit without  
return--air filters in place.  
Condensers may require cleaning of water--deposited  
scale.  
WARNING  
Follow all Safety codes. Wear safety glasses  
and rubber gloves when using inhibited hy-  
drochloric acid solution.  
5.5  
Condensate Drain  
Clean condensers with an inhibited hydrochloric acid  
solution. The acid can stain hands and clothing, attack  
concrete and, without inhibitor, can attack steel. Cover  
surroundings to guard against splashing. Vapors from  
vent pipe are not harmful, but take care to prevent liquid  
from being carried over by the gases.  
Clean the drain line and unit drain pan at the start of each  
cooling season. Check flowby pouring water into drain.  
Be sure trap is filled as shown in Figure 7 to maintain an  
air seal.  
5.6  
Evaporator Coil  
Warm solution acts faster, but cold solution is just as  
effective if applied for a longer period.  
WARNING  
Never reach into unit while fan is running.  
Lock open and tag unit disconnect before  
working on fan. Removefuses and takethem  
with you after noting this on tag.  
Remove dirt and debris from evaporatorcoil as required  
by condition. Clean coil with a stiff brush, vacuum  
cleaner or compressed air. Use a fin comb of the correct  
tooth spacing (Refer toTable 1, Table 3 or Table 2 for  
coil fins/inch) when straightening mashed or bent coil  
fins.  
5.7  
Water Regulating Valve  
PREPARATION FOR OPERATION.  
a. Open thewater regulating valve inlet and outlet isola-  
tion valves.  
b. Close the water regulating valve bypass valve.  
ADJUSTMENT  
Figure 9 Gravity Flow Method  
GRAVITY FLOW METHOD  
a. The compressor discharge pressure is controlled by  
the water regulating valve and may be monitored by  
observing liquid line pressure.  
a. Disconnect condenser piping at unit, including isola-  
tion valves and water regulating valve.  
NOTE  
b. Fill condenser as shown in Figure 9. Follow acid  
manufacturer’s instructions. When condenser is full,  
allow solution to remain overnight  
Adjustments to the water regulating valve must  
be made slowly, allowing ample time for re-  
sponse and stabilization.  
c. Drain condenser and flush with clean water.  
FORCED CIRCULATION METHOD  
b. Install a calibrated gauge at the liquid line service  
port. Operating liquid linerangefor R--22 units is 250  
to 270 psig (1724 to 1862 kPa), for R--134a units is  
155 to 180 psig (1069 to 1241 kPa) and for R--407C is  
267 to 288 psig (1841 to 1986 kPa). If pressure read-  
ing is below operating range, rotate the square head  
adjusting screw counterclockwise; this will increase  
a. Disconnect condenser piping at unit, including isola-  
tion valves and water regulating valve.  
b. Fill system as shown in Figure 10. Follow acid  
manufacturer’s instructions. Fully open vent pipe  
when filling system. The vent may be closed when  
system is full and pump is operating.  
62--10458--00  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
c. Regulate flow to condenser with a supply line valve.  
If pump is a non--overloading type, the valve may be  
fully closed while pump is running. For averagescale  
deposit, allow solution to remain in condenser over-  
night. For heavy scale deposit, allow 24 hours.  
(1607 kPa) for R--407C units. Charge to a clear sight  
glass.  
90MU004 UNITS R--22  
d. Drain condenser and flush with clean water.  
90MU006 UNITS R--22  
Figure 10 Forced Circulation Method  
5.9  
Refrigerant Charging  
90MA/MF -- These units are shipped with a full  
operating charge. If recharging is necessary (complete  
chargelost), weigh in amount ofrefrigerant indicated on  
unit nameplate and in Table 1, Table 3 or Table 2.  
If unit has partial charge, it must be recharged by  
removing existing charge and recharging by weighing  
in the required amount of refrigerant.  
90MU004 UNITS R--407C  
(TEA = TEMPERATURE, ENTERING AIR)  
2758  
2620  
2482  
2344  
2206  
2069  
1930  
1793  
1655  
1517  
1379  
400  
380  
360  
340  
320  
300  
280  
260  
240  
220  
200  
TEA120F/49C  
90MU004 & 006 -- These units, used with remote  
condensers, are shipped with a holding charge only. To  
charge:  
TEA110F/43C  
TEA100F/38C  
TEA90F/32C  
TEA80F/27C  
TEA70F/21C  
TEA60F/16C  
a. Open discharge and liquid service valves.  
b. Leak test, reclaim refrigerant and evacuate.  
c. Using standard refrigerant charging techniques and  
charging charts (Figure 11) add refrigerant as re-  
quired to maintain proper operating conditions.  
1241  
180  
70 75 80 85  
483 517 552 587 622 655 690  
90 95 100  
PSIG  
kPa  
COMPRESSOR SUCTION PRESSURE  
90MU008 & 012 -- These units, used with remote  
condensers, are shipped with a holding charge only. To  
charge:  
90MU006 UNITS R--407C  
(TEA = TEMPERATURE, ENTERING AIR)  
2758 400  
2620 380  
2482 360  
2344 340  
2206 320  
2069 300  
1930 280  
1793 260  
1655 240  
1517 220  
1379 200  
TEA110F/43C  
a. Open discharge line, liquid line, compressor dis-  
charge and compressor suction service valves.  
TEA100F/38C  
TEA90F/32C  
b. Leak test, reclaim refrigerant and evacuate.  
c. Add sufficient refrigerant vapor to permit continuous  
operation after starting unit.  
TEA80F/27C  
TEA70F/21C  
TEA60F/16C  
d. Start unit. Using standard charging techniques, add  
refrigerant as required to maintain normal operating  
conditions. Use charging chart supplied with con-  
denser, if available. If information is not available,  
block off enough of condenser or set water regulating  
valve as applicable to maintain a discharge pressure  
of 220 psig (1517 kPa) for R--22 units or 233 psig  
1241 180  
70 75 80 85  
90 95 100  
PSIG  
kPa  
483 517 552 587 622 655 690  
COMPRESSOR SUCTION PRESSURE  
Figure 11 Charging Charts  
62--10458--00  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TM  
5.10 Evaporator Fan Motor Removal  
5.13 Cycle--Loc -- Protection Device  
All units are equipped with Cycle--LOC  
current--sensing lockout relay. This device will lock out  
the compressor after any safety trip (discharge pressure  
switch, suction--pressure switch, or internal overload of  
the compressor). Check reason for lockout before  
resetting the device. Refer to unit label wiring diagram.  
To reset, turn the system switch to OFF, then back to  
COOL.  
a. Shut off unit main power supply.  
WARNING  
Lock open and tag unit disconnect before  
working on fan motor. Remove fuses and  
take them with you after noting this on tag.  
5.14 Discharge and Suction Pressure Switches  
Refer to Table 1 through Table 2 for opening and  
closing settings for these safety devices.  
CAUTION  
Before attempting to remove fan motors or  
motor mounts, place a piece of plywood over  
evaporator coils to prevent coil damage.  
The discharge pressure switch is located on the  
compressor on the 008 & 012 size units and on the  
discharge line on all other units. The suction pressure  
switch is located on top of the compressor on 06DR  
compressor equipped units and on the suction line on all  
other units.  
b. Loosen motor hold down bolts on mounting bracket  
so that fan belt can be removed. Motor power wires  
need not be disconnected from motor terminals be-  
fore motor is removed from unit.  
5.15 Oil Charge  
All units are factory charged with oil. On 06D  
compressors, observe the oil level in the sight glass at  
start--up. If unit oil level is below sight glass, add oil  
until level reaches approximately 1/4 sight glass.  
c. Loosen but do not remove the 2 motor mounting  
bracket bolts on left side of bracket.  
If oil charge is above sight glass, do not remove any oil  
until the compressor crankcase heater has been  
energized for at least 24 hours.  
d. Slide motor/bracket assembly to extreme right, re-  
move bolts and lift out through space between fan  
scroll and side. Rest motor on a high platform such as  
astep ladder. Do not allow motorto hang by its power  
wires.  
When additional oil or a complete charge is required,  
use only the following Carrier approved oil.  
R--22 Units  
5.11 Pressure Relief Device  
Design Series One 204/206 size units  
Witco part number 999--5170--55  
Design Series One 208/212 size units and all Design  
Series Two  
All units are equipped with a fusible--plug type safety  
relief device on the refrigerant tubing. The relief setting  
is 197 _F to 203 _F on all units.  
Witco -- Suniso 3GS  
Calumet -- RO--15  
5.12 Crankcase Heater  
R--134a Units  
Castrol -- Icematic E68  
ICI -- Emkarate RL68HP  
A crankcase heater is supplied on the 008 & 012 size  
units and on all 134a units. The heater prevents liquid  
refrigerant from accumulating in the compressor  
crankcase during extended shutdown periods. Heater is  
automatically energized whenever unit main power is  
on and compressor is stopped. Heater is de--energized  
when compressor starts.  
R--407C Units  
004 and 006  
Copeland Ultra 22CC  
Mobil Artic EAL 22CC  
ICI (Virginia KMP) Emkarate  
RL32C  
Do not shut off main power supply for an extended  
period except for servicing unit. Turn on power supply  
for at least 24 hours after an extended shutdown before  
starting compressor. Refer to “Operation”.  
Thermal Zone 22CC  
Castrol -- Icematic E68  
ICI -- Emkarate RL68HP  
008 and 012  
62--10458--00  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 12 Mounting Base  
62--10458--00  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRE PASSES THOUGH LOOP OF CL  
CC  
IPC  
11  
12  
13  
21  
22  
23  
BLK  
BLU  
YEL  
1
L1  
L2  
FIELD  
2
C
POWER  
SUPPLY  
3
L3  
G
IFC  
IPF  
GROUND  
YEL  
BLU  
BLK  
11  
12  
13  
21  
22  
23  
T3  
YEL  
BLU  
BLK  
T2  
T1  
IFM  
GRN  
BLK  
BLK  
ORN  
VIO  
BLU  
CHR  
BLK  
BLU  
4
5
H3 H5  
CH  
H1  
H2 H4  
H6  
SEE NOTE 1  
GRN  
TRAN  
X1  
RED  
X2  
RED  
F
BRN  
C2 CC  
24VOLT  
VIO  
(SEE NOTE 3)  
SW  
BRN  
CHR  
C2  
IFC  
BRN  
CC  
TB1--1  
NO  
NC  
NO  
RED  
ORN  
YEL  
BRN  
BRN  
TRAN  
IFC  
CHR  
1
TB1--4  
RED  
3
CC  
RED  
90MU UNITS ONLY  
BRN  
C2  
RED  
YEL  
RED  
CL  
CFR  
ORN  
LOGIC  
BRN  
TB1--3  
X
2
1
3
T--LOW  
R
W
B
RED  
TB1--5  
BRN  
CHR  
BRN  
BRN  
1
CL  
RED  
SPS  
DPS  
CHR  
BLU  
BLU  
IFC  
OPTIONAL ELECTRIC DUCT HEATER  
H1  
FOR HOT WATER/STEAM  
HEAT SEE NOTE 2  
HEATERS  
H2  
L1  
L2  
90MU CONDENSER FAN WIRING  
11  
12  
13  
21  
22  
23  
L3  
G
GROUND  
MC  
AS  
AC  
TB1--4  
H1  
H2  
CFR  
SHIPS POWER  
TO FAN  
TB1--3  
SINGLE OR THREE PAHSE AS REQUIRED  
Figure 13 Wiring Schematic -- 90MA/MF/MU004/006  
62--10458--00  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROL BOX  
11 12 13  
CONTROL PANEL  
COOL  
FAN  
OFF  
R
M
11 12 13  
21 22 23  
H1 H3 H2 H4  
TRAN  
A
A
B
B
W
E
R
HEAT  
X2  
X1  
21 22 23  
C
R
O
E
L
O
A
F
2
IFC  
CC  
C2  
C1  
C1  
C2  
DT1 DT2  
DT1 DT2  
1
4
3
6
TB1  
1 2 3 4 5  
TB1--1  
NO  
5
CHR  
C1  
C2  
11 12 13  
CLO  
X
VIEW A--A  
GROUND  
21 22 23  
C2  
2
1
3
TB1--5  
TB1--4  
NO  
NC  
CFR  
C1  
90MU ONLY  
LEGEND  
VIEW B--B  
AS  
AC  
C
AIR SWITCH  
AUTOMATIC CUTOUT  
COMPRESSOR  
CC  
CH  
COMPRESSOR CONTACTOR  
CRANKCASE HEATER  
NOTES:  
CFR CONDENSER FAN RELAY  
1. 208--230/3/60 VOLT UNITS FACTORY WIRED  
TO TRANSFORMER TERMINAL H2 (208 VOLT  
TAP). FOR 230 VOLT APPLICATIONS, RE--CON-  
NECT TO TERMINAL H3 (230 VOLT TAP).  
CHR CRANKCASE HEATER RELAY  
CL  
COMPRESSOR LOCKOUT  
DPS DISCHARGE PRESSURE SWITCH  
F
FUSE  
H1  
H2  
IFC  
CONTROLLING HEAT CONTACTOR  
BACKUP HEAT CONTACTOR  
INDOOR FAN CONTACTOR  
460/3/60 VOLT UNITS FACTORY WIRED TO  
TERMINAL H6. 400/3/50 VOLT UNITS FACTORY  
WIRED TO TERMINAL H5.  
IFM INDOOR FAN MOTOR  
IPC  
IPF  
MC  
INTERNAL PROTECTOR--COMPRESSOR  
INTERNAL PROTECTOR--FAN MOTOR  
MANUAL (RESET) CUTOUT  
2. CONNECTION POINTS AT TB--1 TERMINALS  
3 & 4 MAY BE USED FOR HEAT CONTROLS.  
MAXIMUM LOAD IS 250 VA INRUSH, 50 VA  
SEALED.  
SPS SUCTION PRESSURE SWITCH  
SW  
T
TB  
SWITCH  
THERMOSTAT  
TERMINAL BOARD  
3. SWITCH CONTACT ARRANGEMENT IS AS  
SHOWN BELOW.  
TRAN TRANSFORMER  
TERMINAL BOARD TERMINAL  
TERMINAL (MARKED)  
TERMINAL/SPLICE (UNMARKED)  
LOCKOUT TERMINAL  
FACTORY WIRING  
FIELD WIRING  
OFF  
FAN  
COOL  
HEAT  
INDICATES COMMON POTENTIAL,  
DOES NOT REPRESENT WIRING  
Figure 14 Component Arrangement -- 90MA/MF/MU004/006  
62--10458--00  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRE PASSES THOUGH  
LOOP OF CL  
CC  
OLB  
OLA  
11  
12  
13  
21 BLK  
4
4
3
3
1
FIELD  
L1  
L2  
(COLOR VARIES)  
(COLOR VARIES)  
22  
POWER  
SUPPLY  
2
BLU  
C
23 YEL  
3
L3  
G
IFC  
IPF  
YEL  
BLU  
BLK  
11  
12  
13  
21  
22  
23  
T3  
T2  
T1  
YEL  
BLU  
BLK  
GROUND  
IFM  
GRN  
ORN  
VIO  
BLK  
BLK  
BLU  
CHR  
4
5
BLK  
BLU  
H1  
H2 H4  
H3 H5  
CH  
H6  
SEE NOTE 1  
GRN  
TRAN  
X1  
RED  
VIO  
CC  
RED  
F
X2  
BRN  
C2  
C2  
24VOLT  
(SEE NOTE 3)  
SW  
BRN  
BRN  
CHR  
CC  
IFC  
TB1--1  
RED  
NO  
NC  
NO  
RED  
RED  
90MU UNITS ONLY  
BRN  
CHR  
1
IFC  
3
CC  
BRN  
BRN  
C2  
TRAN  
YEL  
TB1--4  
CFR  
RED  
RED  
LOGIC  
BRN  
CL  
RED  
1
3
TB1--3 JUMPER  
90MA012  
X
2
TB1--2  
US  
BRN  
YEL  
ORN  
T--LOW  
ORN  
TB1--5  
BRN  
LLS  
UNITS ONLY  
CHR  
BRN  
DPS  
W
B
BLK  
IPC  
BLK  
OLA  
R
BRN 1 CL  
OLB  
SPS  
BLU  
9
8
2
1
2
1
CHR  
BRN  
IFC  
RED  
RED  
BLU  
US  
ORN  
90MA012 UNITS ONLY  
LLS  
C DT1  
C DT2  
T--HIGH  
R
BLU  
BLU  
BLK  
W
B
BLU  
BLK  
BLU  
BLK  
TB1--2  
TB1--2  
BRN  
BRN  
OPTIONAL ELECTRIC DUCT HEATER  
H1  
FOR HOT WATER/STEAM  
HEAT SEE NOTE 2  
HEATERS  
H2  
L1  
L2  
90MU CONDENSER FAN WIRING  
11  
12  
13  
21  
22  
23  
L3  
G
GROUND  
MC  
AS  
AC  
TB1--4  
H1  
H2  
CFR  
SHIPS POWER  
TO FAN  
TB1--3  
SINGLE OR THREE PAHSE AS REQUIRED  
Figure 15 Wiring Schematic -- 90MA/MF/MU008/012  
62--10458--00  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROL BOX  
11 12 13  
CONTROL PANEL  
COOL  
FAN  
OFF  
R
M
11 12 13  
21 22 23  
H1 H3 H2 H4  
TRAN  
A
A W  
E
B
B
R
HEAT  
X2  
X1  
21 22 23  
C
R
O
E
O L  
A
F
IFC  
CC  
C2  
C1  
C1  
C2  
DT1 DT2  
DT1 DT2  
1
4
3
6
2
5
TB1  
1 2 3 4 5  
TB1--1  
NO  
CHR  
C1  
C2  
11 12 13  
CLO  
X
VIEW A--A  
GROUND  
21 22 23  
C2  
2
1
3
TB1--5  
TB1--4  
NO  
NC  
CFR  
C1  
90MU ONLY  
LEGEND  
AS  
AC  
C
AIR SWITCH  
AUTOMATIC CUTOUT  
COMPRESSOR  
VIEW B--B  
CC  
CH  
COMPRESSOR CONTACTOR  
CRANKCASE HEATER  
CFR CONDENSER FAN RELAY  
NOTES:  
CHR CRANKCASE HEATER RELAY  
CL  
DT  
COMPRESSOR LOCKOUT  
DUMMY TERMINAL  
1. 208--230/3/60 VOLT UNITS FACTORY WIRED  
TO TRANSFORMER TERMINAL H2 (208 VOLT  
TAP). FOR 230 VOLT APPLICATIONS, RE--CON-  
NECT TO TERMINAL H3 (230 VOLT TAP).  
DPS DISCHARGE PRESSURE SWITCH  
F
FUSE  
H1  
H2  
IFC  
CONTROLLING HEAT CONTACTOR  
BACKUP HEAT CONTACTOR  
INDOOR FAN CONTACTOR  
460/3/60 VOLT UNITS FACTORY WIRED TO  
TERMINAL H6. 400/3/50 VOLT UNITS FACTORY  
IFM INDOOR FAN MOTOR  
IPC  
INTERNAL PROTECTOR--COMPRESSOR WIRED TO TERMINAL H5.  
IPF  
INTERNAL PROTECTOR--FAN MOTOR  
2. CONNECTION POINTS AT TB--1 TERMINALS  
3 & 4 MAY BE USED FOR HEAT CONTROLS.  
MAXIMUM LOAD IS 250 VA INRUSH, 50 VA  
SEALED.  
LLS LIQUID LINE SOLENOID  
OL  
OVER LOAD  
MC  
MANUAL (RESET) CUTOUT  
SUCTION PRESSURE SWITCH  
SWITCH  
SPS  
SW  
3. SWITCH CONTACT ARRANGEMENT IS AS  
SHOWN BELOW.  
T
THERMOSTAT  
TB  
TERMINAL BOARD  
TRAN  
TRANSFORMER  
US  
UNLOADER SOLENOID  
TERMINAL BOARD TERMINAL  
TERMINAL (MARKED)  
TERMINAL/SPLICE (UNMARKED)  
LOCKOUT TERMINAL  
FACTORY WIRING  
OFF  
FAN  
COOL  
HEAT  
FIELD WIRING  
INDICATES COMMON POTENTIAL,  
DOES NOT REPRESENT WIRING  
Figure 16 Component Arrangement -- 90MA/MF/MU008/012  
62--10458--00  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M
Access Panel, 9  
Model Chart, 1  
Accessory Plenum, 1  
Air Filter, 5, 10  
Mounting Base, 13  
O
C
Oil Charge, 12  
Component Arrangement, 15, 17  
Condensate Drain, 7, 10  
Condenser, 10  
P
Condenser Connections, 6  
Crankcase Heater, 12  
Cycle--Loc, 12  
Pressure Relief Device, 12  
Pressure Switches, 12  
R
E
Refrigerant Charging, 11  
Remote Condenser, 7  
Return Air, 1  
Electrical Connections, 7  
Evaporator Coil, 10  
F
Fan Adjustment, 9  
Fan Motor, 12  
Fan Shaft, 5  
S
Sequence Of Operation, 8  
Shut Down Unit, 8  
Spring Mounts, 6  
Start Unit, 8  
H
Heating Coil, 1  
V
I
Ventilation, 1  
Installation, 1  
Introduction, 1  
W
L
Water Regulating Valve, 10  
Line Sizes, 7  
Wiring Schematic, 14, 16  
62--10458--00  
Index -- 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Box All in One Printer DP C262 C322 User Manual
Black Box Computer Accessories LBLPO1A KIT User Manual
Black Box Switch 410T User Manual
Bock Water heaters Water Heater Indirect Coil Tank Water Heater User Manual
Bogen Speaker System AE SB User Manual
Bose Stereo System AM325319 User Manual
Bushnell Camper 26 2429 User Manual
Cabin Laptop S Seriesbook User Manual
Canon Camera Lens EF S18 135MM F 35 56 IS User Manual
Casio Digital Camera YC 430 User Manual