installation, start-up,
362AAN
Series B
and operating instructions
LOW-BOY
OIL-FIRED FURNACE
Cancels: II 362A-75-1
II 362A-105-1
8-96
NOTE: Read the entire instruction manual before starting the
SAFETY CONSIDERATIONS
installation.
This symbol → indicates a change since the last issue.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR
OTHER FLAMMABLE VAPORS AND LIQ-
UIDS IN THE VICINITY OF THIS OR ANY
OTHER APPLIANCE.
Index
Page
SAFETY CONSIDERATIONS..................................................1-2
Minimum Clearance to Combustibles......................................2
INTRODUCTION..........................................................................2
LOCATION ................................................................................2-3
Air for Combustion and Ventilation.....................................2-3
Duct Work Recommendations..................................................3
VENTING INSTRUCTIONS ........................................................4
Pre-Installation Vent System Inspection..................................4
Masonry Chimney.....................................................................4
Factory-Built Chimneys............................................................4
Horizontal Venting....................................................................4
OIL BURNER................................................................................4
OIL CONNECTIONS....................................................................4
BAROMETRIC DRAFT CONTROL ...........................................4
ELECTRICAL................................................................................5
FILTERS ........................................................................................5
OPERATIONAL CHECKOUT..................................................5-6
Start-Up.....................................................................................5
Recommended Installation Practices and
DO NOT ATTEMPT TO START THE BURNER
WHEN EXCESS OIL HAS ACCUMULATED,
WHEN THE FURNACE IS FULL OF VAPOR,
OR WHEN THE COMBUSTION CHAMBER IS
VERY HOT.
→
→
WARNING: For use with grade 2 Fuel Oil maximum.
Do not use Gasoline, Crankcase Oil, or any Oil contain-
ing Gasoline! Failure to follow this warning could lead to
sooting, fire, explosion, and/or severe bodily harm.
CAUTION: Never burn garbage or paper in the heating
system and never leave rags, paper, or any flammable
items around the unit.
Combustion Check...........................................................5-6
Fan Adjustment Check .............................................................6
Limit Control Check.................................................................6
For Year-Round Air Conditioning...........................................6
Heating ......................................................................................6
Cooling......................................................................................6
Constant Blower Switch...........................................................6
MAINTENANCE......................................................................6-11
General ......................................................................................6
Oil Burner..............................................................................6-7
Heat Exchanger and Flue Pipe..............................................7-8
Blower Oiling and Removal.....................................................8
Keeping Filters Clean...............................................................8
Airflow Data .............................................................................8
Dimensional Drawing...............................................................9
Barometric Damper Locations................................................10
Wiring Diagram ......................................................................11
USER’S INFORMATION...........................................................12
Here’s How Your Heating System Works ............................12
Preparing Your Furnace For Operation .................................12
Lighting Your Furnace ...........................................................12
Turning Off Your Furnace .....................................................12
CAUTION: These instructions are intended to be used
by qualified personnel who have been trained in installing
this type of furnace. Installation of this furnace by an
unqualified person may lead to equipment damage and/or
a hazardous condition which may lead to bodily harm.
All local and national code requirements governing installation of
oil burning equipment, wiring, and flue connections must be
followed. Some of the codes (issued by the Canadian Standards
Association, the National Fire Protection Agency, and/or the
American National Standards Institute) that may be applicable are:
ANSI/NFPA 31
INSTALLATION OF OIL BURNING
EQUIPMENT
ANSI/NFPA 211 CHIMNEYS, FIREPLACES, VENTS,
AND SOLID FUEL BURNING
APPLIANCES
ANSI/NFPA 90B WARM AIR HEATING AND AIR
CONDITIONING SYSTEMS
ANSI/NFPA 70
CSA B139
NATIONAL ELECTRICAL CODE
INSTALLATION CODE FOR
OIL BURNING EQUIPMENT
CSA C22.1
CANADIAN ELECTRICAL CODE
—1—
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Caulking or sealants are applied to areas such as joints
around window and door frames; between sole plates and
floors; between wall-ceiling joints; between wall panels; at
penetrations for plumbing, electrical, and fuel lines; and at
other openings.
5. Lockouts on start-up.
II. DUCT WORK RECOMMENDATIONS
The proper sizing of warm air ducts is necessary to ensure
satisfactory furnace operation. Duct work should be in accordance
with the latest editions of NFPA-90A (Installation of Air Condi-
tioning and Ventilating Systems) and NFPA-90B (Warm Air
Heating and Air Conditioning Systems) or Canadian equivalent.
If combustion and ventilation air must be supplied to an uncon-
fined space from outside, an opening with a FREE AREA of not
less than 1 sq in. per 1000 Btuh of total input of all appliances
within unconfined space (but not less than 100 sq in.) must be
provided. This opening must be located such that it can not be
blocked at any time.
The supply duct work should be attached to flanged opening
provided at discharge end of furnace. See Fig. 5 for dimensions of
this opening.
The following recommendations should be followed when install-
ing duct work:
When furnace is installed in a closet or enclosure, 2 ventilation
openings, with OPEN AREA as dimensioned in example below
are required for combustion air. The openings should be located
about 6 in. from top and bottom of enclosure at front of furnace.
1. Install locking-type dampers in all branches of individual
ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of furnace.
→ For Example:
2. A flexible duct connector of noncombustible material
should be installed at unit on both supply- and return-air
systems. In applications where extremely quiet operation is
necessary, the first 10 ft (if possible) of supply and return
ducts should be internally lined with acoustical material.
UNIT
SIZE
LENGTH
(IN.)
HEIGHT
(IN.)
036105
048125
060155
18
20
20
9
10
10
3. In cases where return-air grille is located close to fan inlet,
there should be at least one 90° air turn between fan inlet
and grille. Further reduction in sound level can be accom-
plished by installing acoustical air turning vanes or lining
duct as described in item 2 above.
For a confined space, where air is taken from an interior space, 2
permanent openings of equal area are required. One opening must
be within 12 in. of ceiling and the other within 12 in. of floor. Each
opening must have a free area of at least 1 sq in. per 1000 Btuh of
total input rating but not less than 100 sq in.
4. When a single air grille is used, duct between grille and
furnace must be the same size as return opening in furnace.
If outside air is supplied to a confined space, then the 2 openings
must be equal and located as above. The free area of each must be:
CAUTION: Return-air grilles and warm air registers
MUST not be obstructed.
1. One sq in. per 4000 Btuh of total input rating when air is
directly communicated from outdoors.
2. One sq in. per 4000 Btuh of total input rating when air is
brought in through vertical ducts.
WARNING: When supply ducts carry air circulated by
furnace to areas outside spaces containing furnace, return
air MUST also be handled by a duct sealed to furnace
casing and terminating outside space containing furnace.
Incorrect duct work termination and sealing will create a
hazardous condition which could lead to bodily harm.
3. One sq in. per 2000 Btuh of total input rating when air is
transferred through horizontal ducts.
When ducts are used to supply air, they must be of the same cross
sectional area as free area of openings to which they connect.
The minimum dimension of rectangular air ducts must not be less
than 3 in.
When installing furnace with cooling equipment for year-round
operation, the following recommendations must be followed for
series or parallel airflow:
In calculating free area, consideration shall be given to blocking
effect of louvers, grilles, or screens protecting openings. Screens
used shall not be smaller than 1/4-in. mesh and shall be readily
accessible for cleaning. If free area through a design of louver or
grille is known, it shall be used in calculating size design and free
area specified. If design and free area are not known, it may be
assumed that wood louvers have 20 percent free area and metal
louvers and grilles have 60 percent free area. Louvers shall be
fixed in open position or interlocked with furnace so they open
automatically at furnace start-up and remain open during furnace
operation.
1. In series airflow applications, coil is mounted after furnace
in an enclosure in supply-air stream. The furnace blower is
used for both heating and cooling airflow.
WARNING: The coil MUST be installed on air dis-
charge side of furnace. Under no circumstances should
airflow be such that cooled, conditioned air can pass over
furnace heat exchanger. This will cause condensation in
heat exchanger and possible failure of heat exchanger
which could lead to a fire hazard and/or a hazardous
condition which may lead to bodily harm. Heat exchanger
failure due to improper installation may not be covered by
warranty.
WARNING: Do not block combustion-air openings in
the furnace. Any blockage will result in improper com-
bustion which may result in a fire hazard and/or cause
bodily harm.
→ The lack of a proper amount of combustion air can lead to serious
2. In parallel airflow applications, dampers must be provided
to direct air over furnace heat exchanger when heat is
desired and over cooling coil when cooling is desired.
furnace operational problems. Some of these problems are:
1. Excessive oil burner after drip and oil fumes.
2. Sooting.
IMPORTANT: The dampers should be adequate to prevent
cooled air from entering furnace. If manually operated, dampers
must be equipped with a means to prevent operation of either
cooling unit or furnace unless damper is in full cool or heat
position.
3. Melted oil burner couplings and/or ignitor/relay control.
4. A condition where air band or air shutter settings must be
more open than normal to achieve proper combustion.
—3—
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTING INSTRUCTIONS
Venting of furnace should be to the outside and in accordance with
local codes or requirements of local utility.
9. The chimney must extend 3 ft above highest point where it
passes through the roof of a building and at least 2 ft higher
than any portion of a building within a horizontal distance
of 10 ft. It shall also be extended at least 5 ft above highest
connected equipment flue collar.
OIL-FIRED APPLIANCES SHALL BE CONNECTED TO
FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO
ENSURE SAFE AND PROPER OPERATION OF APPLIANCE.
10. Check local codes for any variance.
For additional venting information, refer to ANSI/NFPA 211
Chimney, Fireplaces, Vents, and Solid Fuel Burning Appliances
and/or CSA B139 Installation Code.
III. FACTORY-BUILT CHIMNEYS
Listed factory-built chimneys may be used. Refer to chimney
manufacturer’s instructions for proper installation.
This furnace is certified for use with Type "L" vent (maximum flue
gas temperature 575°F).
→ IV. HORIZONTAL VENTING
This furnace may be vented horizontally through an outside wall
when installed with 1 of the following auxiliary inducer blowers:
I. PRE-INSTALLATION VENT SYSTEM INSPECTION
Before furnace is installed, it is highly recommended that any
existing vent system be completely inspected.
Tjernlund Products, Inc. Model SS1 (SS1C required in Canada)
available from: Tjernlund Products, Inc.
1601 Ninth Street
For any chimney or vent, this should include the following:
1. Inspection for any deterioration in chimney or vent. If
deterioration is discovered, chimney must be repaired or
vent must be replaced.
White Bear Lake, MN 55110-6795
(612) 426-2993
or
2. Inspection to ascertain that vent system is clear and free of
obstructions. Any blockage must be cleared before install-
ing furnace.
Fields Controls Model SWGII-5
(with a CK-60 or CK-61 control kit)
available from: Fields Controls Company
2308 Airport Road
3. Cleaning chimney or vent if previously used for venting a
solid fuel burning appliance or fireplace.
Kinston, NC 28051
(919) 522-3031
4. Confirming that all unused chimney or vent connections are
properly sealed.
NOTE: In both cases, the 24-v wiring schematic included with
inducer is the recommended wiring setup.
5. Verification that chimney is properly lined and sized per the
applicable codes. (Refer to list of codes in Safety Consid-
erations section.)
The use of either inducer can create a negative pressure in the area
where furnace is located if the proper combustion-air openings are
not available. This negative pressure can lead to excessive heat
being retained in heat exchanger, coking, and fumes. Refer to
NFPA-31 Section 1.5 for proper combustion-air requirements.
II. MASONRY CHIMNEY
This furnace can be vented into an existing masonry chimney. This
furnace must not be vented into a chimney servicing a solid fuel
burning appliance. Before venting furnace into a chimney, the
chimney MUST be checked for deterioration and repaired if
necessary. The chimney must be properly lined and sized per local
or national codes.
CAUTION: USE METALLIC VENT PIPE ONLY!
PLASTIC VENTING MATERIALS ARE PROHIB-
ITED!
If furnace is vented into a common chimney, the chimney must be
of sufficient area to accommodate the total flue products of all
appliances vented into chimney.
OIL BURNER
This furnace is supplied with a high-pressure atomizing retention
head type burner (for use with not heavier than grade 2 Fuel Oil).
The air tube length, from face of mounting plate to extreme face of
end cone, should be as shown in Table 3.
The following requirements are provided for a safe venting
system:
1. Be sure that chimney flue is clear of any dirt or debris.
2. Be sure that chimney is not servicing an open fireplace.
→ TABLE 3—OIL BURNER AIR TUBE LENGTH
UNIT SIZE
036105
LENGTH (IN.)
→
3. Never reduce pipe size below minimum certified furnace
pipe size as shown in Table 2.
5
5
7
048125
TABLE 2—MINIMUM CERTIFIED FURNACE PIPE SIZE
(IN.)
060155
UNIT SIZE
036105
MINIMUM PIPE DIAMETER
OIL CONNECTIONS
Complete instructions for installation of fuel oil piping will be
found in oil burner Installation Instructions included with furnace.
5
5
6
048125
060155
→ Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2-pipe system may be used if
desired.
4. All pipe should be supported using proper clamps and/or
straps. These supports should be at least every 4 ft.
→ A properly sized oil filter should be used with all oil burners and
should be installed as close to burner as possible. For a 2-pipe
system, a minimum capacity of 25 gph is needed.
5. All horizontal runs of pipe should have at least 1/4-in. per
ft of upward slope.
6. All runs of pipe should be as short as possible with as few
turns as possible.
BAROMETRIC DRAFT CONTROL
The barometric draft control shipped with furnace MUST be used
with furnace to ensure proper operation. Instructions for installing
control are packed with control. Refer to Fig. 6 for suggested
locations.
7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into chimney but be flush
with inside wall.
—4—
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTRICAL
DO NOT TAMPER WITH UNIT OR CONTROLS—CALL
YOUR SERVICE TECHNICIAN.
The appliance must be installed in accordance with current
ANSI/NFPA 70 National Electrical Code, CSA C22.1 Canadian
Electrical Code Part 1, and/or local codes.
II. RECOMMENDED INSTALLATION PRACTICES AND
COMBUSTION CHECK
The control system depends on correct polarity of power supply.
Connect HOT wire (H) and NEUTRAL wire (N) as shown in Fig.
7.
In order to obtain optimum performance from oil burner, the
following setup procedures must be followed:
1. A test kit (Bacharach No. 5022 kit or equivalent) to measure
smoke, stack draft, over-fire draft, CO2, and stack tempera-
tures MUST be used in order to obtain proper air band
setting. Although all of the above measurements are re-
quired for optimum setup and efficiency data, the most
important readings that must be taken are smoke number,
over-fire draft, and stack draft.
→ A separate line voltage supply MUST be used with a fused
disconnect switch or HACR-type circuit breaker between main
power panel and unit. (See Fig. 7.) Disconnecting means must be
within sight from furnace.
WARNING: The unit cabinet must have an uninter-
rupted or unbroken electrical ground to minimize per-
sonal injury if an electrical fault should occur. A green
ground screw is provided in control box for this connec-
tion.
2. The proper smoke number has been established by engi-
neering tests to be between 0 and 1. This degree of smoke
emission is commonly referred to as a "Trace" of smoke. It
is recommended to use a Bacharach true spot smoke test set
or equivalent.
Use only copper wire for 115-v supply service to unit.
3. In order to ensure proper draft through furnace, a baromet-
ric draft regulator (supplied with furnace) must be installed
as close to outlet of furnace as possible.
Metallic conduit (where required/used) may terminate at side panel
of unit. It is not necessary to extend conduit inside unit from side
panel to control box.
→
In order for this device to function properly, barometric
damper must be mounted with hinge pins horizontal and
face of damper vertical. (See instructions included with
damper.) The draft regulator should be adjusted after
furnace has been firing for at least 10 minutes, and stack
draft should be measured and set between -0.025 and -0.035
in. wc. The draft should be checked with a Bacharach MZF
draft gage or equivalent.
When replacing any original furnace wiring, use only 105°C No.
16 AWG copper wire.
Instructions for wiring thermostat (field supplied) are packed in
thermostat box. Make thermostat connections as shown in Fig. 7 at
24-v terminal board on control box.
When installing optional accessories to this appliance, follow
manufacturer’s Installation Instructions included with accessory.
Other than wiring for thermostat, wire with a minimum of type "T"
insulation (63°F rise) must be used for accessories.
4. The over-fire draft, which is taken through hole provided in
observation door, is a measurement necessary to determine
if there is a blockage between oil burner and flue outlet.
→ Two 1/4-in. quick-connect terminals marked EAC and N5 are
provided for electronic air cleaner (EAC) connection. (See Fig. 7.)
These terminals are energized with 115v (0.5-amp maximum)
during blower motor operation.
There should be a pressure drop of between 0.005 and 0.015
in. wc through furnace. This would set the range of the
over-fire draft between -0.01 and -0.03 in. wc. A reading
above -0.01 in. wc (for example +0.1 in. wc) would indicate
that furnace is in an extremely high-pressure condition in
primary section. This condition may be caused by excessive
combustion air due to air band being too wide open or a lack
of flue draft (chimney effect) or some other blockage, such
as soot, in secondary section of heat exchanger.
→ Two 1/4-in. quick-connect terminals marked HUM and N6 are
provided for 115-v humidifier connection. (See Fig. 7.) These
terminals are energized with 115v (0.5-amp maximum) during any
call for heat.
FILTERS
5. The CO2 and stack temperature instruments enable you to
obtain data required to determine thermal efficiency of
furnace.
WARNING: Never operate unit without a filter or with
filter access door removed. Failure to adhere to this
warning could lead to a hazardous condition which could
lead to equipment damage and bodily harm.
6. An oil filter should be installed as close to burner as
possible with ALL oil burners and is essential on lower
firing rate burners. We recommend the use of a low
pressure drop oil filter such as the General Filter, Inc. model
#1A-25A or equivalent. It is critical that oil capacity be
equivalent or greater than fuel pump gear capacity. For a
2-pipe system, this is 25 gph.
An internal filter is provided as standard equipment with furnace.
Refer to Keeping Filters Clean section for filter cleaning informa-
tion.
7. The oil pressure regulator is factory set to give nozzle oil
pressures of 100 psig. The firing rate noted on nameplate
may be obtained with "standard" nozzles by adjusting pump
pressure as noted in Table 4 or on label on furnace.
OPERATIONAL CHECKOUT
DO NOT START BURNER UNLESS BLOWER ACCESS
DOOR IS SECURED IN PLACE.
Installation of furnace is now complete and operational checkout
may be performed.
On a new installation, air entrapped in oil line leading from
tank to nozzle must be thoroughly purged in order to
prevent excessive after drip. The oil pump is provided with
a special fitting which allows purging of any air between
tank and oil pump. The proper procedure for performing
this operation is as follows:
I. START-UP
1. Check wiring against wiring diagram shown in Fig. 7.
2. Open valve on oil supply line.
3. Reset primary control.
a. Place a piece of clear plastic 1/4-in. diameter tubing over
purge fitting on oil pump.
4. Set thermostat above room temperature.
b. Start oil burner, then open purge fitting and allow burner
to run until purge tube is completely free of air bubbles.
5. Set main electrical switch to ON position. Burner should
start.
—5—
Download from Www.Somanuals.com. All Manuals Search And Download.
→ TABLE 4—BURNER, NOZZLE, AND PUMP
VIII. CONSTANT BLOWER SWITCH
PRESSURE CHART
This furnace is equipped with a constant low-speed blower option.
Whenever room thermostat is not calling for heating or cooling,
blower runs on low speed in order to provide air circulation. If
constant blower option is not desired, the rocker switch on side of
control box may be used to turn off constant speed.
FIRING
RATE
GAL/HR (US)
PUMP
PRESSURE
(PSIG)
BECKETT OIL BURNER
UNIT
SIZE
Model
AFG
Nozzle
0.75 gph
70° Hollow
036105
048125
060155
0.76
0.90
1.12
103
100
104
0.90 gph
70° Hollow
MAINTENANCE
AFG
AFG
1.10 gph
70° Hollow
→
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User’s Manual. FAILURE TO FOLLOW
THIS WARNING COULD RESULT IN POSSIBLE
DAMAGE TO THIS EQUIPMENT, SERIOUS PER-
SONAL INJURY, OR DEATH.
c. Tighten purge fitting. Allow oil to run to nozzle and fire
burner.
d. If purging takes longer than 30 sec and no flame has
been established, burner stops. Push reset button on top
of primary control to restart burner.
e. For detailed information on operation of primary control,
refer to instructions included with furnace.
III. FAN ADJUSTMENT CHECK
WARNING: Before performing any service functions,
unless operations specifically require power to be on,
make sure all utilities are turned off upstream of appli-
ance. Failure to comply with this warning will cause a fire
hazard and/or bodily harm.
This furnace is equipped with a 3-speed direct-drive motor to
deliver a temperature rise (between return and supply plenums)
within range specified on rating plate at external duct static
pressure noted on rating plate.
CAUTION: When operating furnace in heating mode,
static pressure and temperature rise (supply-air tempera-
ture minus return-air temperature) must be within those
limits specified on rating label. Failure to follow this
warning could lead to severe furnace damage.
WARNING: To avoid personal injury, make sure elec-
trical supply power is off before servicing.
→ I. GENERAL
Adjust fan speed so that temperature rise is within rise range
specified on rating plate. Consult wiring diagram for speed
changes on direct-drive motor.
To adjust fan off time, set DIP switches on control board to obtain
desired timing. (See Fig. 1.)
In order to keep this furnace in good operating condition and to
maintain its warranty, the furnace MUST be serviced on an annual
basis. This servicing includes a nozzle change, a burner inspection,
a visual check of tube passages through flue outlet and cleanout
ports, and a visual inspection of combustion chamber when burner
is removed.
Depending on above inspection, service could also include a
cleaning and vacuuming of heat exchanger tubes and possibly the
heat exchanger drum section.
1
2
1
2
1
2
1
2
60 Sec
90 Sec
120 Sec
150 Sec
DELAY OFF DIP SWITCH SETTINGS
Removal of any heat exchanger components which are sealed by
gaskets requires replacement of gasket.
A95115
WARNING: Failure to replace any heat exchanger gas-
kets with new gaskets when any heat exchanger plates or
covers are removed could lead to heat exchanger leakage,
sooting, and/or a hazardous condition capable of causing
bodily harm.
Fig. 1—Fan Off Time DIP Switch Settings
(Black Box Represents Switch Position)
IV. LIMIT CONTROL CHECK
After furnace has been in operation for at least 15 minutes, restrict
return-air supply by blocking filters or closing return registers and
allow furnace to shut down on high limit. The burner should shut
off, and main blower should continue to run.
Remove restriction, and burner should come back on in a few
minutes.
This furnace should never be operated without an air filter.
Disposable filters should be replaced at least once a year. If
equipped to provide cooling, filters should be replaced a minimum
of twice a year. Permanent filters should be cleaned at least twice
a year.
V. FOR YEAR-ROUND AIR CONDITIONING
This furnace is designed for use in conjunction with cooling
equipment to provide year-round air conditioning. The blower has
been sized for both heating and cooling, however, fan motor speed
may need to be changed to obtain necessary cooling airflow.
ALWAYS KEEP MAIN OIL VALVE TURNED OFF IF
BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF
TIME.
VI. HEATING
II. OIL BURNER
The blower speed is factory set to deliver required airflow at
normal duct static pressure.
Contact your service technician for service.
Lubricate burner motor with SAE 10 oil. Once each year, pour 2
teaspoons of oil slowly into each oil cup.
VII. COOLING
The blower speed may be field adjusted to deliver required airflow
for cooling application. (See Table 5.)
To maintain proper performance, oil burner nozzle must be
replaced once a year.
—6—
Download from Www.Somanuals.com. All Manuals Search And Download.
The procedure for nozzle installation and/or replacement is out-
lined in oil burner instruction manual which came with furnace.
For ease of maintenance, the oiling procedure for burner motor, as
outlined in burner manual, should be performed at this time.
FLUE BOX
PARTITION
PANEL
After replacement of nozzle, burner should be adjusted in accor-
dance with Combustion Check section of this instruction.
CLEANOUT
COVER
GASKET
CLEANOUT
PORT COVER
→ III. HEAT EXCHANGER AND FLUE PIPE
Ordinarily, it is not necessary to clean heat exchanger or flue pipe
every year, but it is necessary to have your service technician
check unit before each heating season to determine whether
cleaning or replacement of parts is required.
CLEANOUT
COVER
CLAMP
BRACKET
A. Cleaning Secondary Heat Exchanger Tubes and
Flue Pipe Only
If cleaning of only the secondary heat exchanger tubes and flue
pipe is necessary, the following steps should be performed:
WING
CLAMP
NUT
INSULATION
1. Turn off all oil and electrical supplies upstream of furnace.
CAUTION: If furnace has been in operation, some
surfaces may be hot. Allow time for unit to cool down.
A96311
Fig. 3—Reinstalling Cleanout Port Covers
10. Turn on power to unit and readjust burner for proper
operation. Inspect cleanout ports and flue connection to
make sure there are no leaks.
2. Disconnect flue pipe.
3. For access to cleanout ports, remove blower door and filter.
The 2 cleanout ports are located in blower compartment.
They protrude through the partition and are located on the
left and right of flue pipe. (See Fig. 2.)
B. Cleaning Both Primary and Secondary Heat
Exchangers
If a more thorough cleaning is required (both primary and
secondary heat exchanger sections), the following steps should be
performed:
4. Unscrew wing clamp nuts and remove cleanout port covers.
This allows access to tubes. (See Fig. 2.)
CLEANOUT
PORTS
1. Turn off all oil and electrical supplies upstream of furnace.
CAUTION: If furnace has been in operation, some
surfaces may be hot. Allow time for unit to cool down.
CLEANOUT
PORT COVER
& CLAMP
ASSEMBLY
2. Remove blower door.
3. Disconnect flue pipe.
4. Remove outside flue collar.
5. Remove top rear panel.
BLOWER
DOOR
NOTE: Blower removal as described in Blower Oiling and
Removal section may be desired for easier access when cleaning
with duct work attached.
6. Remove inside collar on flue pipe.
7. Remove top partition.
A96310
Fig. 2—Removing Cleanout Port Covers
8. Place field-fabricated cardboard on metal tray beneath
collector box to prevent debris from entering blower com-
partment.
5. Clean secondary tubes and flue pipe with a stiff brush and
vacuum cleaner.
9. Remove flue collector box from secondary heat exchanger
tube flange. This exposes inside surfaces of secondary tubes
of heat exchanger.
6. Before reinstalling cleanout port covers, the gasket on each
cover MUST be replaced. Use cleanout port gasket kit Part
No. 20196201.
10. Clean secondary tubes and flue pipe with a stiff brush and
vacuum cleaner.
7. Reinstall covers and tighten in place making sure that
covers are properly seated over ports and gasket has sealed
opening. (See Fig. 3.)
11. Remove louvered door.
12. Disconnect limit control wires.
13. Disconnect oil line and remove oil burner from furnace.
14. Remove observation door and collar on observation tube.
WARNING: Failure to replace cleanout port cover gas-
kets, failure to properly seat covers over ports, and/or
failure to securely tighten wing nuts could lead to flue gas
leakage. This could lead to furnace damage, oil fumes,
sooting, and severe bodily harm.
15. Remove intermediate panel. Care must be taken not to bend
or damage limit control.
16. Loosen to hand tightness the 3 nuts labeled "A" in Fig. 4.
Remove screws labeled "B" in Fig. 4. Slide combustion
chamber forward out of heat exchanger. Be careful not to
bump combustion chamber as it becomes brittle after
having been fired.
8. Reconnect flue pipe.
9. Reinstall filter and blower door.
—7—
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Remove screws securing blower legs to blower rails
mounted on bottom panel of furnace.
A
B
4. Slide blower forward on rails toward rear of unit until motor
wire connections at terminal block on motor can easily be
reached and disconnected.
5. Disconnect motor wires at terminal block on motor.
6. Remove blower from unit.
A96398
Fig. 4—Removing Combustion Chamber
7. Reverse items 1 through 6 to reinstall blower. Refer to
wiring diagram (Fig. 7) of these instructions or diagram
located on inside of louvered door to properly rewire unit.
17. Use a stiff brush and vacuum cleaner to clean inside of
primary drum.
CAUTION: Never use incendiary type cleaners (smoke
sticks) for cleaning!
V. KEEPING FILTERS CLEAN
WARNING: Never operate unit without a filter or with
filter access door removed. Failure to adhere to this
warning could lead to a hazardous condition which could
lead to equipment damage and bodily harm.
WARNING: For all heat exchanger plates that have
been removed, the gaskets MUST be replaced. Failure to
replace gaskets could lead to heat exchanger leakage,
sooting, and a hazardous condition which could lead to
bodily harm.
As a homeowner, keeping filters clean is your most important
responsibility. A dirty filter reduces efficiency of your system,
causes erratic performance of controls, and could result in damage
to motor or heating element.
18. Before reassembly, heat exchanger and combustion cham-
ber should be inspected to determine if replacement is
required. After cleaning, place combustion chamber back
into primary drum and secure with "B" screws. Ensure that
cover plate gasket is in place before tightening screws. Care
must be taken not to damage combustion chamber. The "B"
screws should be tightened to 35-45 lb-in.
1. Inspect filters at regular intervals depending upon dirt
conditions. For new homes, check filters every week for 4
consecutive weeks. In all cases, inspect filters at least every
3 to 4 weeks when system is in constant operation. Replace
or clean filter at least at beginning of each season (heating
and cooling) and thereafter as needed.
2. If a permanent filter is used, it can be cleaned with cold
water and soap.
19. Tighten "A" nuts to 30 lb-in. of torque (firm, but not overly
tight).
Be sure that filter is thoroughly dry before installing back into
furnace.
20. Replace intermediate panel, observation tube collar, obser-
vation door, limit wiring, and oil burner.
21. Replace collector box on secondary tube flange, ensuring
proper placement of gasket. Tighten screws to 35-45 lb-in.
of torque.
22. Replace top partition, inside collar on flue pipe, top rear
panel, outside flue collar, and blower door.
23. Reconnect flue pipe and oil line(s).
24. Readjust burner for proper operation. Check limit operation
as outlined in Limit Control Check section.
IV. BLOWER OILING AND REMOVAL
Periodic oiling of blower motor may be necessary. Check for
instructions on inside of blower access door.
If it is ever necessary to remove blower from furnace:
1. Turn off all electrical power to furnace.
2. Remove blower door.
A95103
→ TABLE 5—AIRFLOW DATA (CFM)
EXTERNAL STATIC PRESSURE IN. WC
0.4 0.5 0.6 0.7
1605 1550 1485 1425
UNIT
SIZE
BLOWER
SPEED
0.1
0.2
0.3
0.8
0.9
1.0
High
Medium
Low
1795
1365
995
1735
1335
965
1675
1305
945
1350
1105
775
1275
1050
725
1220
985
036105
048125
060155
1275
925
1255
900
1215
870
1155
825
670
High
1905
1750
1390
2025
1885
1555
1845
1675
1350
1960
1825
1490
1770
1620
1305
1905
1760
1445
1695
1560
1260
1850
1705
1410
1630
1500
1220
1800
1640
1350
1565
1440
1180
1665
1565
1280
1490
1370
1120
1575
1500
1230
1425
1305
1060
1500
1430
1155
1325
1235
985
1220
1130
880
Medium
Low
High
1415
1350
1085
1315
1265
1005
Medium
Low
NOTES: 1. Airflow values in cubic ft per minute (CFM) rounded to nearest 5 CFM.
2. Data taken without filters in place.
—8—
Download from Www.Somanuals.com. All Manuals Search And Download.
G
CLEAN-OUT PORTS
B
SUPPLY
DUCT
RETURN
DUCT
12 1⁄16″
3″
1″
A
E
H
1″
D
INSULATION
PARTITION
PANEL
ELECTRICAL
CONNECTIONS
F
C
FILTER
INSULATION
INTERMEDIATE
PANEL
OIL INLET
A96309
DIMENSIONS (IN.)
UNIT DIMENSIONS
FLUE
DIAMETER
DUCT SUPPLY OPENING
RETURN DUCT
UNIT
SIZE
Width
Depth
B
Height
C
A
D
E
F
6
6
6
G
H
036105
048125
060155
22
22
22
52
33
20
20
20
17-1/4
22-1/4
22-1/4
20
20
20
18
18
18
57
33
57
33
→ Fig. 5—Dimensional Drawing
—9—
Download from Www.Somanuals.com. All Manuals Search And Download.
BAROMETRIC DAMPER LOCATIONS
FIG. A
FIG. D
FIG. B
FIG. C
GOOD LOCATIONS
WRONG
FIG. G
FIG. H
WRONG
WRONG
FIG. K
WRONG
FIG. L
POOR
FIG. J
WRONG
BAD LOCATIONS
A95117
Fig. 6—Barometric Damper Locations
—10—
Download from Www.Somanuals.com. All Manuals Search And Download.
9
8
7
6
5
4
3
2
1
H o n e y w e l l
1
2
T Y P I C A L T H E R M O S T A T
—11—
Download from Www.Somanuals.com. All Manuals Search And Download.
USER’S INFORMATION
I. HERE’S HOW YOUR HEATING SYSTEM WORKS
3. Set thermostat to lowest setting.
4. Turn on electric power to furnace.
5. Open oil supply valve.
The furnace operates automatically. It is controlled by a thermostat
which you set at the temperature most comfortable to you. When
the inside temperature drops below this setting, your thermostat
will turn on heating system.
6. Check all connections to ensure there are no leaks.
III. LIGHTING YOUR FURNACE
When thermostat calls for heat, power from transformer energizes
fan control board. The fan control energizes ignition control. The
ignition control lights burner automatically.
CAUTION: This furnace is equipped with an interrupted
type electronic ignition system. DO NOT ATTEMPT TO
LIGHT WITH A MATCH.
The electronic fan control automatically turns on blower after 30
sec. Fan on control is not adjustable. The air which is moved over
heat exchanger by the blower is warmed and passes through ducts
to room registers.
When thermostat is satisfied, the circuit is de-energized and
primary control shuts off burner. The blower continues to run until
selectable fan off time period has expired.
→
DANGER: HIGH VOLTAGE AT IGNITOR. Severe
electrical shock, personal injury, or death could result.
The heat sensing switch performs as furnace high-temperature
limit switch. If furnace overheats for any reason, the limit switch
opens, breaking circuit to burner. The blower motor is energized,
and as unit cools, the limit switch closes. This relights burner, but
unless overheating condition is corrected, furnace will cycle on
limit.
1. This appliance is equipped with an ignition device which
automatically lights burner. Do NOT try to light burner by
hand.
2. After preparing furnace for heating operation (see previous
section) and checking for oil, proceed as follows.
→ This unit is equipped with an interrupted ignition electronic
control. If main burner does not ignite within 30 sec from call for
heat, the control locks out. The red button on top of control must
be depressed for 3 sec in order to reset control. The control
CANNOT be reset from room thermostat.
3. For heating/cooling system, set thermostat to HEAT and fan
to AUTO. Set thermostat to desired room temperature and
turn on electrical power to furnace.
4. The burner should light and system should be controlled by
thermostat.
II. PREPARING YOUR FURNACE FOR OPERATION
Before attempting to put your furnace into operation for the
heating season, you should perform the following procedures:
IV. TURNING OFF YOUR FURNACE
Follow these simple procedures to put your furnace into "retire-
ment" for the summer.
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property
damage, personal injury, or loss of life.
1. Set thermostat to lowest setting.
2. Turn off all electrical power to appliance.
3. Turn off oil supply.
1. Open all warm-air registers and make sure all return-air
grilles are unobstructed.
4. If applicable, turn off water supply to humidifier.
5. If furnace blower will be necessary for cooling system,
remember to turn electrical power back on when needed for
air conditioning.
2. If a humidifier is installed with your system, open water
supply valve.
FOR SERVICE CALL
NAME:
ADDRESS:
TELEPHONE: