Bryant Furnace 330JAV User Manual

service and  
330JAV  
331JAV  
Series D  
maintenance procedures  
PLUS 80 2-STAGE GAS-FIRED  
INDUCED-COMBUSTION FURNACES  
Cancels: SP04-65  
SP04-73  
11-01  
NOTE: Read the entire instruction manual before starting the  
installation.  
This symbol indicates a change since the last issue.  
TABLE OF CONTENTS  
SAFETY CONSIDERATIONS.....................................................1  
INTRODUCTION..........................................................................2  
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS  
PROCEDURE ................................................................................2  
CARE AND MAINTENANCE.....................................................2  
Cleaning and/or Replacing Air Filter.......................................2  
Blower Motor and Wheel.........................................................3  
Cleaning Heat Exchanger.........................................................4  
Electrical Controls and Wiring.................................................6  
WIRING DIAGRAMS...................................................................7  
TROUBLESHOOTING .................................................................7  
EFFICIENCY  
RATING  
CERTIFIED  
A94086  
Fig. 2—Model 331JAV Downflow  
CERTIFIED  
R
M
®
I
REGISTERED QUALITY SYSTEM  
A95137  
Fig. 1—Model 330JAV Horizontal  
SAFETY CONSIDERATIONS  
A94085  
Installing and servicing heating equipment can be hazardous due to  
gas and electrical components. Only trained and qualified person-  
nel should install, repair, or service heating equipment.  
Untrained personnel can perform basic maintenance functions  
such as cleaning and replacing air filters. All other operations must  
be performed by trained service personnel. When working on  
heating equipment, observe precautions in the literature, tags, and  
labels attached to or shipped with the unit and other safety  
precautions that may apply.  
Fig. 3—Model 330JAV Upflow  
Follow all safety codes. In the United States, follow all safety  
codes including the National Fuel Gas Code (NFGC) NFPA No.  
54-1999/ANSI Z223.1-1999. In Canada, refer to the current  
edition of the National Standard of Canada CAN/CGA-B149.1-  
and .2-M00 Natural Gas and Propane Gas Installation Codes  
(NSCNGPIC) and Amendment No. 1. Wear safety glasses and  
work gloves. Have fire extinguisher available during start-up and  
adjustment procedures and service calls.  
—1—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLUE  
COLLAR  
AIRFLOW  
BLOCKED  
MOUNTING  
SCREWS  
VENT  
INSTALLATION  
POSITION  
SAFEGUARD  
OF FILTERS  
PRESSURE  
SWITCH  
RELIEF  
BOX  
RETURN-AIR  
FLUE  
COLLECTOR  
BOX  
PLENUM  
GAS  
VALVE  
CONTROL  
FILTER  
RETAINER  
H U M  
C
2V4  
OM  
W
Y
R
G
WASHABLE  
FILTER  
FURNACE  
WASHABLE  
FILTER OR  
DISPOSIBLE  
MEDIA FILTER  
IN FILTER  
CABINET  
A00293  
ACCESS DOOR  
Fig. 5Model 330JAV Upflow  
e. Rinse and let dry. Oiling or coating of filter is not  
recommended or required.  
A88486  
f. Place filter in furnace.  
Fig. 4Downflow Filter Arrangement  
g. Replace blower and control access doors and turn on  
electrical supply to furnace.  
f. Rinse and let dry. Oiling or coating of filters is not  
recommended or required.  
II. BLOWER MOTOR AND WHEEL  
g. Reinstall filters.  
The following items should be performed by a qualified service  
technician:  
h. Replace blower access door and turn on electrical supply  
to furnace.  
For long life, economy, and high efficiency, clean accumulated dirt  
and grease from blower wheel and motor annually.  
2. Upflow/Horizontalfilters installed in media cabinet adja-  
The inducer and blower motors are pre-lubricated and require no  
additional lubrication. These motors can be identified by the  
absence of oil ports on each end of the motor.  
cent to furnace (See Fig. 5.)  
a. Turn off electrical supply to furnace  
b. Remove filter cabinet door.  
c. Slide filter out of cabinet.  
Clean blower motor and wheel as follows:  
1. Turn off electrical supply to furnace.  
2. Remove blower access door.  
3. Downflow only:  
d. If equipped with permanent, washable filter, clean filter  
by spraying cold tap water through filter in opposite  
direction of airflow. Rinse filter and let dry. Oiling or  
coating of the filter is not recommended.  
a. Disconnect vent connector from furnace flue collar. (See  
Fig. 6.)  
e. If equipped with factory-specified disposable media  
filter, replace only with media filter having the same part  
number and size.  
b. Remove internal vent pipe enclosure cover.  
c. Disconnect and remove short piece of vent pipe from  
within furnace.  
f. Slide filter into cabinet.  
d. Disconnect and remove vent pipe enclosure. Push bot-  
tom side backward to release tabs.  
g. Replace filter cabinet door.  
h. Turn on electrical supply to furnace.  
NOTE: Vent pipe is SCREWED and RTV sealed to relief box.  
3. Upflow/Horizontalfilter(s) installed in side(s) and/or bot-  
4. Disconnect blower leads from furnace control. Note wire  
color and location for reassembly. Also, disconnect auxil-  
iary limit switch leads (downflow only, if present).  
All other factory wires can be left connected, but field  
thermostat connections may need to be disconnected de-  
pending on their length and routing.  
tom of blower compartment (See Fig. 5.)  
a. Turn off electrical supply before removing blower and  
control access doors.  
b. Release filter retainer from clip at front of furnace  
casing. (See Fig. 5.) For side return, clips may be used  
on either or both sides of the furnace.  
5. Remove 2 screws securing control and transformer support  
to furnace.  
c. Slide filter out.  
d. Clean filters by spraying tap water through filter from  
opposite direction of airflow.  
6. Hang control and transformer support to front of furnace  
casing.  
3—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: Refer to Table 1 for motor speed lead relocation if leads  
were not identified before disconnection.  
FLUE  
COLLAR  
VENT PIPE  
ENCLOSURE  
TABLE 1SPEED SELECTOR  
AUXILIARY  
LIMIT  
FACTORY-  
SWITCH  
COLOR  
SPEED  
ATTACHED  
TO  
CONTROL  
Black  
High  
Medium High  
Medium Low  
Low  
Cool  
Spare  
Heat  
Yellow (When Present)  
Blue  
Red  
White  
Spare  
COM  
MOUNTING  
SCREWS  
Common  
Medium  
Orange (When Present)  
Spare  
DRAFT  
SAFEGUARD  
SWITCH  
CAUTION: Heating speed selection MUST be adjusted  
to provide proper temperature rise as specified on the  
rating plate. Failure to adjust the heating speed may  
shorten heat exchanger life.  
PRESSURE  
SWITCHES  
RELIEF  
BOX  
14. Reinstall internal vent pipe and enclosure on downflow  
furnaces only by reversing items 3a through 3c.  
NOTE: A releasing agent such as PAM cooking spray or equiva-  
lent (must not contain corn or canola oil, aromatic or halogenated  
hydrocarbons or inadequate seal may occur) and RTV sealant  
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting  
installation. DO NOT substitute any other type of RTV sealant.  
G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.  
MANUAL  
RESET  
LIMIT  
SWITCHES  
15. Reinstall vent connector to furnace flue collar. After fully  
assembling vent connector to furnace flue collar, securely  
fasten vent connector to flue collar with 2 field-supplied,  
corrosion-resistant, sheet metal screws located 180 degrees  
apart and midway up the collar.  
A99092  
Fig. 6Model 331JAV Downflow  
7. Remove screws holding blower assembly to blower deck  
and slide blower assembly out of furnace.  
16. Turn on electrical supply. Manually close blower access  
door switch. Use a piece of tape to hold switch closed.  
Check for proper rotation and speed changes between  
heating and cooling by jumpering R to W and then R to Y  
on furnace control thermostat terminals.  
8. Clean blower wheel and motor using a vacuum with soft  
brush attachment. Do not remove or disturb balance weights  
(clips) on blower wheel blades. The blower wheel should  
not be dropped or bent as balance will be affected.  
9. If greasy residue is present on blower wheel, remove wheel  
from the blower housing and wash it with an appropriate  
degreaser. To remove wheel:  
WARNING: Blower access door switch opens 115-v  
power to furnace control. No component operation can  
occur. Caution must be taken when manually closing this  
switch for service purposes. Failure to follow this warn-  
ing could result in electrical shock, personal injury, or  
death.  
a. Mark blower wheel location on shaft before disassembly  
to ensure proper reassembly.  
b. Loosen setscrew holding blower wheel on motor shaft.  
NOTE: Mark blower mounting arms, motor, and blower housing  
so motor and each arm is positioned at the same location during  
reassembly.  
NOTE: If thermostat terminals are jumpered before blower ac-  
cess door switch is closed, blower will run for 90 sec before  
beginning a heating or cooling cycle.  
c. Mark blower wheel orientation and cutoff plate location  
to ensure proper reassembly.  
d. Remove screws securing cutoff plate and remove cutoff  
plate from housing.  
17. If furnace is operating properly, remove tape to release  
blower access door switch, replace blower access door.  
e. Remove bolts holding motor mounts to blower housing  
and slide motor and mounts out of housing. Disconnect  
capacitor and ground wire attached to blower housing  
before removing motor.  
III. CLEANING HEAT EXCHANGER  
The following steps should be performed by a qualified service  
technician:  
NOTE: If the heat exchangers get a heavy accumulation of soot  
and carbon, they should be replaced rather than trying to clean  
them thoroughly due to their intricate design. A build-up of soot  
and carbon indicates that a problem exists which needs to be  
corrected, such as improper adjustment of manifold pressure,  
insufficient or poor quality combustion air, incorrect size, or  
damaged manifold orifice(s), improper gas, or a restricted heat  
exchanger. Action must be taken to correct the problem.  
If it becomes necessary to clean heat exchanger because of light  
dust or corrosion proceed as follows:  
f. Remove blower wheel from housing.  
10. Reassemble motor and blower by reversing items 9a  
through 9f. Be sure to reattach ground wire.  
11. Reinstall blower assembly in furnace.  
12. Reinstall control box and support assembly in furnace.  
13. Reconnect blower leads to furnace control and auxiliary  
limit switch leads (downflow only).  
Refer to furnace wiring diagram, and connect thermostat  
leads if previously disconnected. (See Fig. 11.)  
4—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Turn gas and power to furnace to OFF.  
11  
13  
32"  
32"  
BURNER  
2. Remove control and blower access doors.  
3. Disconnect vent connector from furnace flue collar.  
4. Disconnect internal vent pipe and enclosure on downflow  
furnaces only.  
CELL  
PANEL  
a. Remove vent pipe enclosure cover.  
b. Disconnect and remove short piece of vent pipe from  
within furnace.  
HOT  
NOTE: Vent pipe is SCREWED and RTV sealed to relief box.  
SURFACE  
IGNITOR  
c. Remove vent pipe enclosure by removing screw in upper  
back. Push bottom side backward to release tabs.  
ASSEMBLY  
5. Remove 2 screws that secure relief box. (See Fig. 5 or 6.)  
6. Disconnect wires to the following components. Mark wires  
to aid in reconnection of:  
a. Draft safeguard switch.  
b. Inducer motor.  
c. Pressure switch(es).  
C
IGNITOR  
BURNER  
L
7
8"  
d. Limit overtemperature switch(es).  
e. Gas valve.  
C
L
f. Hot surface ignitor.  
IGNITOR  
ASSEMBLY  
g. Flame-sensing electrode.  
h. Flame rollout switch(es), if applicable.  
A93347  
7. Remove complete inducer assembly and relief box from  
furnace.  
Fig. 7Position of Ignitor to Burner  
8. Remove screws that secure flue collector box to center  
panel. Be careful not to damage collector box.  
9. Remove cell outlet plates.  
IMPORTANT: Replace screws in center panel before cleaning.  
10. Remove burner assembly and cell inlet plates.  
IMPORTANT: Replace screws in center panel before cleaning.  
NOTE: Be very careful when removing burner assembly to avoid  
breaking ignitor. See Fig. 7 for correct ignitor location.  
11. Using field-provided small wire brush, steel spring cable,  
reversible electric drill, and vacuum cleaner, clean cells as  
follows:  
A91252  
a. Assemble wire brush and steel spring cable.  
Fig. 8Cleaning Heat Exchanger Cell  
(1.) Use 48 in. of 1/4-in. diameter high-grade steel  
spring cable (commonly known as drain clean-out  
or Roto-Rooter® cable).  
(3.) Work cable in and out of cell 3 or 4 times to obtain  
sufficient cleaning. DO NOT pull cable with great  
force. Reverse drill and gradually work cable out.  
(2.) Use 1/4-in. diameter wire brush (commonly known  
as 25-caliber rifle cleaning brush).  
(4.) Insert brush end of cable in lower opening of cell,  
and proceed to clean 2 lower passes of cell in same  
manner as 2 upper passes.  
NOTE: The materials needed in items (1.) and (2.) can usually be  
purchased at local hardware stores.  
(3.) Insert twisted wire end of brush into end of spring  
cable, and crimp tight with crimping tool or strike  
with ball-peen hammer. TIGHTNESS IS VERY  
IMPORTANT.  
(5.) Repeat foregoing procedures until each cell in  
furnace has been cleaned.  
(6.) Using vacuum cleaner, remove residue from each  
cell.  
(4.) Remove metal screw fitting from wire brush to  
allow insertion into cable.  
(7.) Using vacuum cleaner with soft brush attachment,  
clean burner assembly.  
b. Clean each heat exchanger cell.  
(8.) Reinstall cell outlet plates and screws FIRST; then,  
reinstall cell inlet plates and burner assembly. Care  
must be exercised to center burners in cell openings.  
(1.) Attach variable-speed, reversible drill to end of  
spring cable (end opposite brush).  
(2.) Insert brush end of cable into upper opening of cell  
and slowly rotate with drill. DO NOT force cable.  
Gradually insert at least 36 in. of cable into 2 upper  
passes of cell. (See Fig. 8.)  
12. Remove old sealant from center panel and collector box  
flange and apply new sealant to collector box flange and  
reinstall on center panel, making sure all screws are secure.  
5—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD 24-V WIRING  
FIELD 115-, 208/230-, 460-V WIRING  
FACTORY 24-V WIRING  
FACTORY 115-V WIRING  
1-STAGE THERMOSTAT TERMINALS  
W
Y
R
G
C
FIVE  
WIRE  
FIELD-SUPPLIED  
FUSED DISCONNECT  
TWO-WIRE  
HEATING-  
ONLY  
208/230- OR  
460-V  
THREE  
PHASE  
W2  
BLK  
BLK  
GND  
GND  
GND  
COM  
W/W1  
WHT  
WHT  
208/230-V  
SINGLE  
PHASE  
GND  
GND  
Y/Y2  
115-V FUSED  
DISCONNECT  
SWITCH  
JUNCTION  
BOX  
GND  
R
G
CONTROL  
CONDENSING  
UNIT  
(WHEN REQUIRED)  
BOX  
24-V  
TERMINAL  
BLOCK  
NOTES: 1. Connect Y-terminal as shown for proper operation.  
FURNACE  
2. Some thermostats require a "C" terminal connection as shown.  
3. If any of the original wire, as supplied, must be replaced,  
use same type or equivalent wire.  
A99071  
Fig. 9Heating and Cooling Application Wiring Diagram  
for Single-Stage Thermostats and Single-Speed Condensing Units  
NOTE: A releasing agent such as PAM cooking spray or equiva-  
lent (must not contain corn or canola oil, aromatic or halogenated  
hydrocarbons or inadequate seal may occur) and RTV sealant  
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting  
installation. DO NOT substitute any other type of RTV sealant.  
G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.  
19. Set thermostat and check furnace for proper operation.  
20. Verify blower airflow and speed changes between heating  
and cooling.  
21. Check for gas leaks.  
22. Replace control door.  
13. Reinstall relief box and inducer assembly.  
WARNING: Never use a match or other open flame to  
check for gas leaks. Use a soap-and-water solution. A  
failure to follow this warning could result in fire, personal  
injury, or death.  
NOTE: If inducer assembly gasket is damaged, use RTV sealant  
to seal inducer assembly to collector box.  
14. Reconnect wires to the following components:  
a. Draft safeguard switch.  
b. Inducer motor.  
IV. ELECTRICAL CONTROLS AND WIRING  
c. Pressure switches.  
NOTE: There may be more than 1 electrical supply to unit.  
d. Limit overtemperature switch(es).  
e. Gas valve.  
The electrical ground and polarity for 115-v wiring must be  
maintained properly. Refer to Fig. 9 and 10 for field wiring  
information and to Fig. 11 for unit wiring information. If the  
polarity is NOT correct, the furnace control will display rapid  
flashing on the status LED and prevent heat operation. The control  
system also requires an earth ground for proper operation of the  
microprocessor.  
f. Hot surface ignitor.  
g. Flame-sensing electrode.  
h. Flame rollout switch(es), if applicable.  
15. Reinstall internal vent pipe and enclosure on downflow  
furnaces only by reversing items 4a through 4c.  
With power disconnected to unit, check all electrical connections  
for tightness. Tighten all screws on electrical connections. If any  
smoky or burned connections are noticed, disassemble the connec-  
tion, clean all parts and stripped wire, and reassemble properly and  
securely. Electrical controls are difficult to check without proper  
instrumentation; therefore, reconnect electrical power to unit and  
observe unit through 1 complete operating cycle.  
NOTE: A releasing agent such as PAM cooking spray or  
equivalent (must not contain corn or canola oil, aromatic or  
halogenated hydrocarbons or inadequate seal may occur) and RTV  
sealant (G.E. 162, 6702, or Dow-Corning 738) are needed before  
starting installation. DO NOT substitute any other type of RTV  
sealant. G.E. 162 (P771-9003) is available through RCD in 3-oz  
tubes.  
The 24-v circuit contains an automotive-type, 3-amp fuse located  
on the main control. Any 24-v electrical shorts during installation,  
service, or maintenance could cause this fuse to blow. If fuse  
replacement is required, use ONLY a 3-amp fuse. The control will  
display code 24 when fuse needs replacement.  
16. Reinstall vent connector to furnace flue collar. After fully  
assembling vent connector to furnace flue collar, securely  
fasten vent connector to flue collar with 2 field-supplied,  
corrosion-resistant, sheet metal screws located 180 degrees  
apart and midway up the collar.  
The control in this furnace is equipped with an LED status light to  
aid in installation, servicing, and troubleshooting. It can be viewed  
through the sight glass or window on blower access door. The  
control indicates status with the LED on continuously, rapid  
17. Replace blower access door only.  
18. Turn power and gas to ON.  
6—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD 24-V WIRING  
FIELD 115-, 208/230-, 460-V WIRING  
FACTORY 24-V WIRING  
FACTORY 115-V WIRING  
2-STAGE THERMOSTAT TERMINALS  
W2 W1 Y2  
R
G
Y1  
C
SEVEN  
WIRE  
FIELD-SUPPLIED  
FUSED DISCONNECT  
THREE-WIRE  
HEATING-  
ONLY  
208/230- OR  
460-V  
THREE  
PHASE  
W2  
COM  
W/W1  
BLK  
BLK  
GND  
C
GND  
GND  
WHT  
WHT  
208/230-V  
SINGLE  
PHASE  
GND  
GND  
Y/Y2  
115-V FUSED  
DISCONNECT  
SWITCH  
JUNCTION  
BOX  
Y1  
Y2  
GND  
R
G
CONTROL  
2-SPEED  
CONDENSING  
UNIT  
(WHEN REQUIRED)  
BOX  
24-V  
TERMINAL  
BLOCK  
NOTES: 1. Connect Y-terminal as shown for proper operation.  
FURNACE  
2. Some thermostats require a "C" terminal connection as shown.  
3. If any of the original wire, as supplied, must be replaced,  
use same type or equivalent wire.  
A99072  
Fig. 10Heating and Cooling Application Wiring Diagram  
for 2-Stage Thermostats and/or 2-Speed Condensing Units  
flashing, or a code composed of 2 digits. (The first digit is the  
number of short flashes, the second is the number of longs flashes.)  
Refer to service label on blower compartment door for code  
explanations and useful troubleshooting suggestions. (See Fig. 12.)  
Use any recorded fault codes, service label, and troubleshooting  
diagram on following pages to diagnose and correct any problem  
condition.  
It is important to note that power to furnace must not be interrupted  
and furnace blower door must not be removed until the LED status  
code(s) is recorded. When power to control is interrupted, status  
memory is erased.  
WIRING DIAGRAMS  
Refer to Fig. 9, 10, and 11 for appropriate wiring diagrams.  
TROUBLESHOOTING  
The control will store up to 5 previous codes but will not store  
non-current codes longer than 48 hr. To retrieve previous codes, if  
present, no thermostat inputs to control must be present and all  
time delays must expire. Remove 1 of the red main limit wires 1  
to 4 sec until the LED light goes out, then reconnect it. (See Fig.  
5 and 6.) (Do not leave red wire disconnected for longer than 4 sec  
as control will assume an overtemperature condition exists and  
will respond with indoor blower operation.) This places control in  
status recall mode and displays first code stored in memory.  
Record code and repeat the disconnect and reconnect of red wire,  
recording each code until code 11 is displayed indicating no  
additional faults. After last code is displayed or after 2 minutes in  
the code recall mode, the control will return to normal standby  
mode.  
Refer to service label. (See Fig. 12.) The Troubleshooting Guide  
can be a useful tool in isolating furnace operation problems.  
Beginning with the word Start,answer each question and follow  
the appropriate arrow to the next item.  
The Guide will help you identify the problem or failed component.  
After replacing any component, verify correct operation sequence.  
More information is available in a seperate Troubleshooting Guide  
for 2-stage Gas-Fired Induced-Combustion Furnaces.  
7—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECTION DIAGRAM  
SCHEMATIC DIAGRAM (NATURAL GAS & PROPANE)  
NOTE #1  
TO 115VAC FIELD  
DISCONNECT SWITCH  
ILK  
EQUIPMENT  
GROUND  
LPS  
LS  
FRS2  
NOTE #8  
RED  
HI  
HPS  
BRN  
GRY  
BRN  
LO-GAS-HEAT  
P
BHI / LOR  
BHT / CLR  
L2  
LO  
MED LO  
BLWM  
BRN  
GV  
LGPS  
HI-GAS-HEAT  
NOTE #15  
HI  
DSS  
C
M
BLU  
MED  
MED HI  
SPARE  
SPARE  
GRN/YEL  
L1  
GRN/YEL  
BLWR  
COM  
NOTE #4  
HI-COOL  
IDM  
FRS1  
BRN  
CAP  
HSI  
PL6  
FUSED DISCONNECT  
SWITCH (WHEN REQD)  
NOTE #1  
COMMON  
(WHEN USED)  
ALS1  
GRN/YEL  
ILK  
JB  
EAC-1  
EAC-2  
HSIR  
IDR  
BLK  
L1  
L2  
(WHEN USED)  
NOTE #6  
1
3
9
PL2  
ORN  
ORN  
HSI  
WHT  
HEAT  
FU2  
PL6  
PL3  
2
WHT  
SET-UP  
SWITCH  
SWITCH  
1
2
IHI / LOR  
GND  
1
2
LO  
NORM  
HI HT  
LO HT  
BLK  
1
ALS2  
*
BLK  
2
1
4
HI  
COM  
2
3
PL3  
7
8
3
IDM  
PR2  
PR1  
BLOWER-  
OFF DELAY  
(SEC.)  
115VAC  
SWITCH  
RED  
FU1  
TRAN  
3
4
SEC1  
SEC2  
1
5
6
90 SEC  
N/A  
N/A  
PL2  
24VAC  
HPSR  
BLK  
135 SEC  
180 SEC  
225 SEC  
*
WHT  
NOTE #5  
2-STAGE  
FURNACE  
CONTROL  
2
12  
2
N/A  
FRS2  
BLK  
PR1  
L1  
PR2  
L2  
MGVR-2  
WHT  
HUM  
R
BLK  
FRS1  
(WHEN USED)  
CAP  
LS  
WHT  
3
COMMON  
BRN  
ORN  
RED  
BRN  
NOTE #4  
*
HI-COOL  
ALS2  
ALS1  
9
6
BLOWER-OFF DELAY  
COM  
HI  
MED HI  
NOTE #15  
WHT  
BLK  
YEL  
TWIN  
TEST  
TRAN  
BLOWER-OFF DELAY  
LOW-HEAT ONLY  
HIGH-HEAT ONLY  
RED  
HI-GAS  
HEAT  
LO-GAS  
HEAT  
EAC-2  
TWINNING  
JUMPER  
TJ  
P1  
S
DSS  
NOTE #8 LPS  
MED  
PL1  
ORN  
BLU  
EAC-1  
TWIN  
TEST  
MED LO  
BLWM  
TJ  
SPARE  
SPARE  
SEC1  
LO  
RED  
W/W1  
M
RED  
(WHEN USED)  
LGPS  
M
S
W2 Com W/W1 Y/Y2  
24V  
R
G
HUM  
LED  
BLU  
SEC2  
FU1  
5
4
SW1  
NOTE #8  
LEGEND  
HPS  
MGVR  
MA-IN1 =GAVASLVVAELVE RELAY-,2D=PHSUTM(NID.OIF.)IER  
12-CIRCUIT CONNECTOR  
9-CIRCUIT CONNECTOR  
3-CIRCUIT IDM CONNECTOR  
2-CIRCUIT HSI CONNECTOR  
ALS1  
ALS2  
AUXILIARY LIMIT SWITCH, OVERTEMP. MANUAL RESET, SPST (N.C.)  
AUXILIARY LIMIT SWITCH, OVERTEMP. AUTO RESET, SPST (N.C.)  
W2  
CPU  
P
PL1  
PL2  
PL3  
PL6  
MGVR-1  
BHI / LOR BLOWER MOTOR SPEED CHANGE RELAY, SPDT  
BHT / CLR BLOWER MOTOR SPEED CHANGE RELAY, SPDT  
HI  
1
M
BLWM  
BLWR  
CAP  
CPU  
DSS  
EAC-1  
EAC-2  
FRS1  
FRS2  
FSE  
BLOWER MOTOR, 4 or 5 -SPEED, PERMANENT-SPLIT-CAPACITOR  
BLOWER MOTOR RELAY, SPST (N.O.)  
CAPACITOR  
MICROPROCESSOR AND CIRCUITRY  
DRAFT SAFEGUARD SWITCH (N.C.)  
ELECTRONIC AIR CLEANER CONNECTION (115 VAC, 1 AMP MAX.)  
ELECTRONIC AIR CLEANER CONNECTION (COMMON)  
FLAME ROLLOUT SWITCH OVERTEMP. MANUAL RESET, SPST (N.C.)  
FLAME ROLLOUT SWITCH OVERTEMP. MANUAL RESET, SPST (N.C.)  
FLAME-PROVING SENSOR ELECTRODE  
10  
GV  
Y/Y2  
C
SW1  
SW2  
SW3 & 4  
HIGH-HEAT-ONLY SWITCH, SPST (MANUAL)*  
LOW-HEAT-ONLY SWITCH, SPST (MANUAL)*  
BLOWER-OFF DELAY SETTING SWITCHES,  
SPST (MANUAL)*  
NOTE#7  
G
TJ  
TWINNING JUMPER, SPDT FOR MAIN OR  
SECONDARY STATUS (MANUAL CHANGE OVER)  
TRANSFORMER-115VAC/24VAC  
FSE  
7
8
TRAN  
N/A  
N/A  
TWIN/TEST 1-CIRCUIT TWINNING BUSS CONNECTOR,  
ALSO STATUS CODE RECALL  
11  
COM  
FU1  
FU2  
GV  
HPS  
HPSR  
HSI  
HSIR  
HUM  
IDM  
FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED  
FUSE, FIELD INSTALLED  
GAS VALVE, REDUNDANT LOW-HEAT OPERATORS, 2-STAGE  
HIGH-HEAT PRESSURE SWITCH, SPST (N.O.)  
HIGH-HEAT PRESSURE SWITCH RELAY, SPST (N.C.)  
HOT-SURFACE IGNITER (115 VAC)  
HOT-SURFACE IGNITOR RELAY, SPST (N.O.)  
24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.)  
INDUCED DRAFT MOTOR, 2-SPEED, SHADED-POLE  
INDUCER MOTOR RELAY, SPST (N.O.)  
JUNCTION  
TERMINAL  
NOTES:  
CONTROL TERMINAL  
1. Use only copper wire between the disconnect switch and  
the unit.  
9. Symbols are an electrical representation only.  
10. BLOWER-ON DELAY: Gas heating 45 seconds,  
Cooling/Heat Pump 2 seconds.  
11. Cooling/Heat Pump BLOWER-OFF DELAY is 90  
seconds.  
12. IGNITION-LOCKOUT will occur after four  
consecutive unsuccessful trials-for-ignition.  
Control will automatically reset after three hours.  
13. Control must be grounded at pin 10 of 12-pin  
connector.  
FACTORY POWER WIRING (115VAC)  
FACTORY CONTROL WIRING (24VAC)  
FIELD POWER WIRING (115VAC)  
FIELD CONTROL WIRING (24VAC)  
CONDUCTOR ON CONTROL  
FIELD WIRING SCREW TERMINAL  
FIELD GROUND  
2. If any of the original wire, as supplied, must be replaced,  
use the same or equivalent type wire.  
3. Inducer (IDM) and blower (BLWM) motors contain  
internal auto-reset thermal overload switches.  
4. Blower motor speed selections are for average  
conditions. See Installation Instructions for details on  
optimum speed selection.  
IDR  
IHI / LOR INDUCER MOTOR SPEED CHANGE RELAY, SPDT  
ILK  
JB  
BLOWER DOOR INTERLOCK SWITCH, SPST (N.O.)  
JUNCTION BOX  
5. Replace only with a 3-AMP fuse.  
6. Auxiliary limit switches (ALS1 & 2) used on some  
horizontal and some downflow models.  
LED  
LGPS  
LPS  
LS  
LIGHT-EMITTING DIODE FOR STATUS CODES  
LOW GAS-PRESSURE SWITCH, SPST (N.O.)  
LOW-HEAT PRESSURE SWITCH, SPST (N.O.)  
LIMIT SWITCH, OVERTEMPERATURE-AUTO RESET, SPST (N.C.)  
EQUIPMENT GROUND  
FIELD SPLICE  
14. NA - Not Applicable  
15. Spare terminal and wire not available on some  
applications. Insulate connector if not available.  
7. This wire must be connected to furnace sheet metal for  
control to prove flame.  
PLUG RECEPTACLE  
8. Factory connected when LGPS not used.  
324459-101 REV. D  
A01365  
Fig. 11Unit Wiring Diagram  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
If sta tus c od e re c a ll is ne e d e d , d o not re mo ve p owe r or b lowe r d oor. Brie fly re move  
a nd the n re c onne c t one ma in lim it wire to d isp la y store d sta tus c od e .  
LED CODE  
STATUS  
CONTINUOUS OFF - Che c k for 115VAC a t L1 a nd L2, a nd 24VAC a t SEC1 a nd SEC2 .  
CONTINUOUS ON - Control ha s 24VAC p owe r.  
RAPID FLASHING - Line volta ge (115VAC) p ola rity re ve rse d . If twinne d , re fe r to  
twinning kit instruc tions.  
Ea c h o f the following sta tus c od e s is a two-d ig it numb e r with the first d ig it d e te rm ine d b y  
the numb e r of short fla she s a nd the se c ond d ig it b y the num b e r of long fla she s.  
11 NO PREVIOUS CODE - Store d sta tus c ode s a re e ra se d whe n p owe r (115VAC or  
24VAC) to c ontrol is inte rrup te d or 48 hours a fte r e a c h fa ult is c le a re d .  
12 BLOWER ON AFTER POWER UP (115VAC or 24VAC) - Blowe r runs for 90 se c onds,  
if unit is p owe re d up d uring a c a ll for he a t (R-W c lose d ).  
13 LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Control will a uto re se t a fte r thre e  
hours. Re se t switc h or re pla c e fuse link. Re fe r to #33.  
14 IGNITION LOCKOUT - Control will a uto-re se t a fte r thre e hours. Re fe r to #34.  
21 GAS HEATING LOCKOUT - Control will NOT a uto-re se t.  
Che c k for: - Mis-wire d ga s va lve  
- De fe c tive c ontrol (va lve re la y)  
22 ABNORMAL FLAME-PROVING SIGNAL - Fla me is p rove d while g a s va lve is d e -  
e ne rgize d . Ind uc e r will run until fa ult is c le a re d . Che c k for:  
- Le a ky ga s va lve  
- Stuc k-op e n ga s va lve  
23 PRESSURE SWITCH DID NOT OPEN Che c k for:  
- Ob struc te d p re ssure tubing  
- Pre ssure switc h stuc k c lose d .  
24 SECONDARY VOLTAGE FUSE IS OPEN Che c k for: - Short-c irc uit in se c ond a ry  
volta ge (24VAC) wiring  
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED  
Che c k for: -Control re la y ma y b e d e fe c tive  
- Re fe r to #32  
32 LOW-HEAT PRESSURE, DRAFT SAFEGUARD (whe n use d ), OR AUX-LIMIT(whe n use d *)  
SWITCH DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY*) If op e n longe r tha n  
five minute s, ind uc e r shuts off for 15 minute s b e fore re try. If it op e ns a fte r tria l for  
ig nition p e riod , b lowe r will c ome on for 90 se c ond re c yc le d e la y. Che c k for:  
*- De fe c tive b lowe r motor or c a p a c itor  
- Prop e r ve nt sizing  
- Re stric te d ve nt  
- Low ind uc e r volta ge (115VAC)  
- Exc e ssive wind  
- Disc onne c te d or ob struc te d p re ssure tubing  
- De fe c tive ind uc e r motor  
- De fe c tive p re ssure switc h  
- Low p ropa ne inle t ga s p re ssure  
- Ina d e q ua te c omb ustion a ir sup p ly  
33 LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If op e n longe r tha n thre e minute s,  
c od e c ha nge s to #13. Fla me roll-out switc h re q uire s ma nua l re se t. Che c k for:  
- Dirty filte r or re stric te d d uc t syste m.  
- De fe c tive b lowe r motor or c a p a c itor.  
- Loose b lowe r whe e l.  
- De fe c tive switc h or c onne c tions.  
- Ina d e q ua te c omb ustion a ir supp ly (Fla me roll-out switc h or fuse link op e n).  
- Op e n fla me roll-out switc h, or fuse link. Ma nua l re se t or re p la c e .  
34 IGNITION PROVING FAILURE - Control will try thre e more time s b e fore loc kout #14  
oc c urs. If fla me signa l is lost a fte r tria l for ig nition pe riod , b lowe r will c ome on for  
90 se c ond re c yc le d e la y. Che c k for:  
- Ga s va lve d e fe c tive or ga s va lve turne d off.  
- Oxid e build up on fla me se nsor (c le a n with fine ste e l wool).  
- Prop e r fla me se nse c urre nt (.5 mic roa mp s D.C. min., 4.0 - 6.0 nom. in HIGH HEAT).  
- Gre e n wire MUST b e c onne c te d to furna c e she e t me ta l.  
- Fla me se nsor must b e ungrounde d .  
- De fe c tive hot surfa c e ignitor  
- Ina d e q ua te fla me c a rryove r or roug h ignition.  
- Ma nua l va lve shut-off.  
- Control ground c ontinuity.  
- Low inle t g a s p re ssure .  
43 LOW-HEAT PRESSURE, DRAFT SAFEGUARD (whe n use d ), OR AUX-LIMIT (whe n use d *)  
SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED Che c k for:  
- Pre ssure switc h stuc k op e n  
- Re fe r to #32 a nd #33  
45 REPLACE CONTROL  
- Disc onne c te d or ob struc te d p re ssure tub ing  
- Low p ropa ne inle t ga s p re ssure  
COMPONENT TEST  
TWIN  
TEST  
12 - CIRCUIT  
CONNECTOR  
OM  
C
R
G
LED  
HUM  
W2  
W/ W1 Y/Y2  
24 V  
To initia te the c ompone nt se lf-te st se que nc e , shut off the room the rmosta t or  
disc onne c t the "R" the rmosta t le a d. Brie fly short the TWIN/ TEST te rmina l to the  
Com24V te rmina l. Sta tus LED will turn off. NON-CONDENSING FURNACE: The  
c ontrol will turn ON the induc e r motor low spe e d, the n high spe e d a nd re ma in on  
high spe e d for the e ntire te st. The othe r c ompone nts will be ON for 7 to 15  
se c onds: Hot surfa c e ignitor, Low he a t blowe r spe e d, High he a t blowe r spe e d,  
High c ooling blowe r spe e d. CONDENSING FURNACE: The induc e r motor will sta rt  
in high spe e d a nd re ma in on high spe e d until the e nd of the te st, the n shift to low  
spe e d for 7 to 15 se c onds. All othe r c ompone nts will be te ste d in the sa me  
se que nc e a s the NON-CONDENSING.  
320893-101 REV. F  
A01368  
Fig. 12Service Label  
9—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
GUIDE  
NOTES:  
WARNING  
!
1. Refer to information label on blower compartment door  
for procedure for use of LED status codes and problem  
solving suggestions.  
2. LED indicator is viewed through window in blower  
compartment door.  
ELECTRICAL SHOCK HAZARD  
3. If 115-vac power is de-energized or interrupted during a  
call for heat, the indoor blower will run for 90 sec before  
a gas heating cycle begins Code 12.  
4. After replacing any component, verify correct operating  
sequence.  
ONLY QUALIFIED AND TRAINED  
SERVICE PERSONNEL SHOULD  
PERFORM THIS PROCEDURE  
If LED is flashing rapidly, check line voltage polarity.  
If Code 24 is displayed, check for blown fuse.  
If LED is OFF, check line voltage and 24-v transformer.  
If Code 45 is displayed, replace control.  
START  
24v should be present across R  
and Com. If not, check for:  
1. Open flame rollout switch  
(FRS) Code 33.  
2. Open limit switch (LS) –  
Code 33.  
Yes  
Turn thermostat OFF.  
Is indoor blower on ?  
No  
On furnace control, note current  
settings for setup switches 1 (SW-1)  
and 2 (SW-2) then set SW-1 to OFF  
and SW-2 to ON.  
24v should be present across Com and W at furnace control. If  
not, check for:  
1. Open thermostat.  
3. Check all low-voltage wiring  
connections.  
2. Open 24-v fuse (FU1) Code 24.  
3. Failed transformer.  
No  
Cycle 115-v power  
off for 3 sec, then on.  
No  
Replace control only if all checks  
are OK.  
If Code 23 is displayed, the pressure switch(es) is stuck closed.  
Replace switch and/or check pressure tube for blockage.  
System malfunction Code 21.  
No  
115v should be present at the inducer motor. If so, replace inducer  
motor. If not, check 115-v wiring.  
Continuous LED?  
Yes  
If Code 32 is displayed check for:  
Set thermostat to call for heat.  
1. Open gas inlet pressure switch (when used).  
2. Open pressure switch (LPS) and/or tube Code 32.  
3. Open draft safeguard switch (DSS) Code 32.  
4. Open auxiliary switch (ALS)(downflow only) Code 32.  
5. Check all low-voltage wiring connections.  
Set FAN to AUTO mode.  
No  
Replace control only if Code 45 is  
displayed, or if all checks are OK.  
No  
Draft inducer motor starts.  
115v should be present at the ignitor. If so, replace the ignitor; if not,  
check 115-vac wiring to ignitor.  
Yes  
No  
LPS, DSS, or ALS open while HPS if closed (high-gas-heat only) –  
Code 43.  
Is Code 22 displayed?  
Yes  
Control will attempt to light burners 4 times (approximately 1 minute  
between attempts Code 34). Voltage is present at the gas valve for 7  
sec during each ignition trial. System will lockout after 4 attempts.  
Flame present when not normal.  
Replace gas valve.  
Is the gas valve control knob or switch in the OPEN or ON position?  
24v should be present across the gas valve terminals C and M/P  
(and C and HI for high-stage gas test) during the 7 sec ignition  
trial. If not, check all low-voltage wiring connections to valve.  
15-sec inducer pre-purge.  
Yes  
If 24v are present, and main gas does not flow:  
1. Supply pressure between 4.5- and 13.6-in. wc. If not, adjust  
supply pressure.  
2. If supply pressure is between 4.5- and 13.6-in. wc, replace gas  
valve.  
No  
Replace control only if Code 45 is  
displayed, or if all checks are OK.  
No  
Ignitor warms up and glows  
orange/yellow; 17-sec warm-up.  
Yes  
Check ignitor position.  
No  
Main burners ignite.  
Check burner carryover gap.  
Check gas supply pressure (4.5-in. wc minimum).  
Yes  
Check manifold pressure (1.3- to 1.7-in. wc for low-stage gas;  
3.2- to 3.8-in. wc for high-stage gas).  
Check for proper orifice size.  
Is Code 31 (high-gas-heat only), 32, 33, or 34 displayed? Check  
code information label to diagnose.  
Replace control if Code 45 is dis-  
played, or if all checks are OK.  
Clean flame sensor if microamps  
are below nominal.  
No  
No  
No  
Main burners stay on.  
Check polarity of 115-v power at J-box and control. Twinned  
furnace polarities must match rapid flashing LED.  
Yes  
Check ground continutity from J-box to control.  
Check flame sensor microamps (4.0 nominal; 0.5 minimum for  
control to recognize flame).  
Indoor blower motor starts on  
No  
Replace control only if Code 45 is  
displayed, or if all checks are OK.  
heating speed after 45-sec  
warm-up period.  
115v should be present at the blower motor. If so, check capacitor.  
If capacitor is OK, replace blower motor. If 115v are not present at  
the blower motor, check all 115-v wiring to motor.  
Yes  
If not, check for:  
1. Satisfied thermostat.  
No  
Furnace runs until call for  
heat ends.  
2. Open inlet gas pressure switch (when used).  
3. Open pressure switch (LPS) Code 32.  
4. Open draft safeguard switch (DSS) Code 32.  
5. Open auxilliary limit (ALS)(downflow only) Code 32.  
6. Open 24-v fuse (FU1) Code 24.  
7. Open limit switch (LS) Code 13 or 33.  
8. Open flame rollout switch (FRS) Code 13 or 33.  
9. Check 115-v line voltage LED off.  
No  
Replace control only if Code 45 is  
Yes  
displayed, or if all checks are OK.  
Turn thermostat to OFF; gas valve  
shuts off burners; 5-sec inducer  
post purge.  
No  
No  
Yes  
Check for sources of electrical noise interference (electronic air  
cleaners, nearby TV, or radio antennas).  
Indoor blower motor stops after  
90, 135, 180, or 225 sec.  
No  
No  
Replace control only if Code 45 is  
displayed, or if all checks are OK.  
If inducer and burners continue to operate, check for 24v at the  
gas valve. If 24v are present, verify that the thermostat is open  
across R and W. If no voltage is present, turn the gas valve  
control knob or switch to the OFF position. Replace gas valve.  
Yes  
Heating sequence of operation  
complete. Remove blower door,  
move setup switch 1 (SW-1) to ON  
position and repeat process to check  
high-stage gas heat operation.  
(When finished return SW-1 and  
SW-2 to original desired settings.)  
Replace control only if Code 45 is  
displayed, or if all checks are OK.  
24v should be present across R and Com. If not, check for:  
1. Open limit switch (LS) Code 13 or 33.  
2. Open flame rollout switch (FRS) Code 13 or 33.  
24v should not be present across R and G. If so, set thermostat  
FAN to AUTO mode.  
A97544  
10—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE TRAINING  
Packaged Service Training programs are an excellent way to increase your  
knowledge of the equipment discussed in this manual, including:  
Unit Familiarization  
Installation Overview  
Maintenance  
Operating Sequence  
A large selection of product, theory, and skills programs is available, using popular  
video-based formats and materials. All include video and/or slides, plus companion  
book.  
Classroom Service Training plus "hands-on" the products in our labs can mean  
increased confidence that really pays dividends in faster troubleshooting, fewer  
callbacks. Course descriptions and schedules are in our catalog.  
CALL FOR FREE CATALOG 1-800-962-9212  
[ ] Packaged Service Training  
[ ] Classroom Service Training  
A94328  
11—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2001 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231  
Printed in U.S.A.  
sp0473  
Catalog No. 5333-025  
12—  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blanco Indoor Furnishings 531 430 User Manual
Bosch Appliances Security Camera NDC 225 P User Manual
Bosch Power Tools Cordless Drill 17614 User Manual
Bradford White Corp Water Heater Commercial Electric Energy Saver Medium Duty E32 Series Models User Manual
Brother Sewing Machine HE 240 User Manual
Bush Hog Tiller RTH60 03 User Manual
Casio Electronic Keyboard CTK 1100 User Manual
Char Broil Gas Grill 8301390 User Manual
Chrysler Automobile 300SRT User Manual
Chrysler Automobile 2006 Sebring Sedan User Manual