310AAV/JAV
Induced-Combustion
4-Way Multipoise Furnace
Installation, Start-up, Operating, and
Service and Maintenance Instructions
-Series A
The 310AAV/JAV 4-Way Multipoise Gas Furnace was designed by Bryant
dealers for Bryant dealers. Applications are easy with 4-way multipoise
design, through-the-furnace downflow venting, 13 different venting options,
and a door designed for easy service access. An inner blower door is
provided for tighter sealing in sensitive applications. The 310AAV/JAV
furnace is approved for use with natural or propane gas, and the 310JAV is
also approved for use in Low NOx Air Quality Management Districts.
STANDARD FEATURES
• Noise elimination combustion system
• Microprocessor based control center
Adjustable heating air temperature rise
LED diagnostics and self test feature
• Patented blocked vent safeguard to ensure proper furnace venting
• All models are Chimney Friendly when used with accessory vent kit
• Four-position furnace: upflow, horizontal right, horizontal left,
downflow
Thirteen different vent options
• Heat pump compatible
• Hot surface ignition (HSI)
• Residential installations eligible for consumer financing through the Comfort
Credit Program
• Twinning in Upflow, Downflow and Horizontal
LIMITED WARRANTY
• 20-year warranty on “Super S™” heat exchanger
• 5-year parts warranty on all other components
Catalog No: 5331-007
Form No. II 310A-45-3
12-02
Download from Www.Somanuals.com. All Manuals Search And Download.
28-7/8"
25-1/4"
1-9/16"
2-9/16"
22-9/16"
A
D
AIRFLOW
19"
13/16"
11/16"
JUNCTION BOX
LOCATION
13/16"
OUTLET
4-13/16"
F
7/8" DIA
ACCESSORY
8-7/16"
1-1/2" DIA.
RIGHT HAND
GAS ENTRY
1/2" DIA THERMOSTAT
WIRE ENTRY
1/2" DIA. THERMOSTAT
WIRE ENTRY
3-15/16"
1-7/16"
LEFT HAND GAS
ENTRY
ALTERNATE
JUNCTION BOX
LOCATION (TYP)
33-5/16"
24-7/8"
VENT OUTLET
5 PLACES (TYP)
14-7/8"
7/8" DIA. ACCESSORY
7/8" DIA. ACCESSORY
3-3/4"
5-1/2"
11/16"
11/16"
1-1/4"
1"
E
21-5/8"
BOTTOM INLET
1-11/16"
22-1/16"
SIDE INLET
A02304
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings ar furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle.
b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle.
c. For 1600 CFM-22-in. round or 14 1/2 x 22-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific
use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the
bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
→ Fig. 1—Dimensional Drawing
SAFETY CONSIDERATIONS
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when han-
dling parts. Failure to follow this caution could result in
personal injury.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause carbon monoxide poisoning, explo-
sion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified
installer, service agency, local gas supplier, or your distribu-
tor or branch for information or assistance. The qualified
installer or agency must use only factory-authorized and
listed kits or accessories when modifying this product. Failure
to follow this warning could result in electrical shock, fire,
personal injury, or death.
Wear safety glasses and work gloves. Have fire extinguisher
available during start-up and adjustment procedures and service
calls.
This is the safety-alert symbol
. When you see this symbol on
the furnace and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
→
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air
temperature rise, unit leveling, and unit sizing. Improper
installation or misapplication of furnace can require excessive
servicing or cause premature component failure.
→ Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in literature, on tags, and
on labels attached to or shipped with unit and other safety
precautions that may apply.
1. Use only with type of gas approved for this furnace. Refer to
the furnace rating plate.
2. Install this furnace only in a location and position as specified
in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace
space as specified in “Air for Combustion and Ventilation”
section.
4. Combustion products must be discharged outdoors. Connect
this furnace to an approved vent system only, as specified in
the “Venting” section of these instructions.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum for a safe installation.
5. Never test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the detec-
tion of leaks to check all connections, as specified in the “Gas
Piping” section.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with This furnace is approved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the Cette fournaise est approuvée pour l´installation HORIZONTALE
et la circulation d´air VERS LE HAUT et VERS LE BAS.
manufacturer,shall be used to convert to propane
gas use or may be required for some natural gas
applications.
This furnace is for indoor installation in a
building constructed on site.
1"
Les fléches de dégagement
ne changent pas avec
l´orientation de la fournaise.
Clearance arrows
do not change with
furnace orientation.
This furnace may be installed on combustible
flooring in alcove or closet at minimum clearance
as indicated by the diagram from combustible
material .
This furnace may be used with a Type B-1 Vent
and may be vented in common with other gas-
fired appliances.
0"
A
0"
*
B
A
C
R
K
R
I
E
E
A
È
C
R
A
S
I
E
N
R
U
N
F
R
U
O
F
Cette fournaise à air pulsé est équipée
pour utilisation avec gaz naturel et altitudes
comprises entre 0-3,050m (0-10,000 pi).
Utiliser une trousse de conversion, fournie par
le fabricant, pour passer au gaz propane ou pour
certaines installations au gaz naturel.
S
E
E
R
E
N
V
T
I
I
T
R
C
E
E
F
R
O
A
N 30"
N
V
T
A
N
MIN
T 3"MIN
0"
*
Ø
Cette fournaise est prévue pour être
installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur
un plancher combustible dans une alcôve ou
dans un garde-robe en respectant le minimum
d'espace libre des matériaux combustibles, tel
q. u'indiqué sur le diagramme.
Cette fournaise peut être utilisée avec un
conduit d´évacuation de Type B-1 ou connectée
.au conduit commun d´autres appareils à gaz.
Clearance in inches
Dégagement (po).
"
0
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po).
For Type B-1 vent type 1 inch (1 po).
Dégagement de l´évent avec combustibles:
Pour conduit d´évacuation à paroi simple 6 po (6 inches).
Pour conduit d´évacuation de Type B-1 1 po (1 inch).
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-combustible floors only.
†
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
18 inches front clearance required for alcove.
Ø
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible
between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists,
studs or framing.
*
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COMBUSTIBLES
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur plancher non combustible seulement.
†
Pour l´installation sur un plancher combustible seulement quand on utilise la base spéciale, pièce
no KGASB0201ALL, l´ensemble serpentin, pièce no CD5 ou CK5, ou le carter de serpentin, pièce
no KCAKC.
Dans une alcôve, on doit maintenir un dégagement à l´avant de 18 po (450 mm).
La position indiquée concerne le côté d´entrée ou de retour quand la fournaise est dans la
position horizontale.
Le contact n´est permis qu´entre les lignes formées par les intersections du dessus et des
deux côtés de la chemise de la fournaise et les solives, montant sous cadre de charpente.
Ø
*
327590-101 REV. B
A02330
→ Fig. 2—Clearances to Combustibles
6. Always install furnace to operate within the furnace’s intended
temperature-rise range with a duct system which has an
external static pressure within the allowable range, as speci-
fied in the “Start-Up, Adjustments, and Safety Check” section.
See furnace rating plate.
8. A gas-fired furnace for installation in a residential garage must
be installed as specified in the warning box in the “Location”
section.
9. The furnace is not to be used for temporary heating of
buildings or structures under construction.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by duct(s)
sealed to the furnace casing and terminating outside the space
containing the furnace. See “Air Ducts” section.
→ 10. These Multipoise Gas-Fired Furnaces are CSA (A.G.A. and
C.G.A.) design-certified for natural and propane gases (see
furnace rating plate) and for installation in alcoves, attics,
basements, closets, utility rooms, crawlspaces, and garages.
The furnace is factory-shipped for use with natural gas. A
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1—Dimensions (IN.)
VENT
CONN*
UNIT SIZE
A
B
C
SHIP WT. (LB)
045-08/024045
045-12/036045
070-08/024070
070-12/036070
070-16/048070
090-14/042090
090-16/048090
090-20/060090
110-12/036110
110-16/048110
110-22/066110
135-16/048135
135-22/066135
155-20/060155
14-3/16
14-3/16
14-3/16
14-3/16
17-1/2
17-1/2
21
12-9/16
12-9/16
12-9/16
12-9/16
15-7/8
15-7/8
19-3/8
19-3/8
15-7/8
19-3/8
19-3/8
19-3/8
22-7/8
22-7/8
12-11/16
12-11/16
12-11/16
12-11/16
16
4
4
4
4
4
4
4
4
4
4
4
4
4
4
104
107
111
115
123
126
139
145
134
145
151
148
163
170
16
19-1/2
19-1/2
16
21
17-1/2
21
19-1/2
19-1/2
19-1/2
23
21
21
24-1/2
24-1/2
23
* 5” or 6” vent connector may be required in some cases.
CSA (A.G.A. and C.G.A.) listed gas conversion kit is required
to convert furnace for use with propane gas.
→ 11. See Fig. 2 for required clearances to combustibles.
→ 12. Maintain a 1-in. clearance from combustible materials to
supply air ductwork for a distance of 36 inches horizontally
from the furnace. See NFPA 90B or local code for further
requirements.
→ 13. These furnaces SHALL NOT be installed directly on carpet-
ing, tile, or any other combustible material other than wood
flooring. In downflow installations, factory accessory floor
base MUST be used when installed on combustible materials
and wood flooring. Special base is not required when this
furnace is installed on manufacturer’s Coil Assembly Part No.
CD5 or CK5, or when Coil Box Part No. KCAKC is used.
60
A02055
INTRODUCTION
Fig. 3—Return Air Temperature
→ This 4–way multipoise Category I fan-assisted furnace is CSA
(A.G.A. and C.G.A.) design-certified for natural and propane gas
and for installation in alcoves, attics, basements, closets, utility
rooms, crawlspaces, and garages. A fan-assisted furnace is an
appliance equipped with an integral mechanical means to either
draw or force products of combustion through the combustion
chamber and/or heat exchanger. The furnace is factory-shipped for
use with natural gas. A CSA (A.G.A. and C.G.A.) listed gas
conversion kit is required to convert furnace for use with propane
gas. This furnace is not approved for installation in mobile homes,
recreational vehicles, or outdoors.
other codes. In absence of local codes, the installation must
comply with the national codes listed below and all authorities
having jurisdiction.
In the United States and Canada, follow all codes and standards for
the following:
Step 1—Safety
•
US: National Fuel Gas Code (NFGC) NFPA 54–2002/ANSI
Z223.1–2002 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
This furnace is designed for minimum continuous return-air
temperature of 60°F db or intermittent operation down to 55°F db
such as when used with a night setback thermostat. Return-air
temperature must not exceed 85°F db. Failure to follow these
return-air limits may affect reliability of heat exchangers, motors,
and controls. (See Fig. 3.)
•
CANADA: CAN/CGA-B149.1–and .2–M00 National Standard
of Canada. Natural Gas and Propane Installation Codes (NSC-
NGPIC)
Step 2—General Installation
•
US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc.,
Batterymarch Park, Quincy, MA 02269; or for only the NFGC,
contact the American Gas Association, 400 N. Capitol, N.W.,
For accessory installation details, refer to the applicable instruction
literature.
NOTE: Remove all shipping brackets and materials before oper-
•
CANADA: NSCNGPIC. For a copy, contact Standard Sales,
CSA International, 178 Rexdale Boulevard, Etobicoke (Tor-
onto), Ontario, M9W 1R3 Canada
ating the furnace.
CODES AND STANDARDS
Step 3—Combustion and Ventilation Air
Follow all national and local codes and standards in addition to
these instructions. The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and
•
US: Section 5.3 of the NFGC, Air for Combustion and
Ventilation
4
Download from Www.Somanuals.com. All Manuals Search And Download.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4—Multipoise Orientations
•
CANADA: Part 7 of NSCNGPIC, Venting Systems and Air
Supply for Appliances
NOT move or shuffle your feet, do not touch ungrounded
objects, etc.).
Step 4—Duct Systems
4. If you touch ungrounded objects (and recharge your body with
static electricity), firmly touch a clean, unpainted metal
surface of the furnace again before touching control or wires.
•
US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Con-
tractors National Association (SMACNA), or American Soci-
ety of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 2001 Fundamentals Handbook Chapter 34.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 4 before bringing the control
or yourself in contact with the furnace. Put all used and new
controls into containers before touching ungrounded objects.
Step 5—Acoustical Lining and Fibrous Glass Duct
•
US and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6—Gas Piping and Gas Pipe Pressure Testing
•
US: NFGC; chapters 5, 6, 7, and 12 and National Plumbing
Codes
7. An ESD service kit (available from commercial sources) may
also be used to prevent ESD damage.
→ • CANADA: NSCNGPIC Parts 3, 4, 5, A, B, E and H.
Step 7—Electrical Connections
LOCATION
Step 1—General
•
•
US: National Electrical Code (NEC) ANSI/NFPA 70–2002
Some assembly and modifications are required when used in any
of the four applications shown in Figure 4.
CANADA: Canadian Electrical Code CSA C22.1
→
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
This furnace must:
•
•
•
•
be installed so the electrical components are protected from
water.
not be installed directly on any combustible material other than
wood flooring. Refer to Introduction section.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will pre-
vent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.
be located close to the chimney/vent and attached to an air
distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the
furnace clearance to combustible label.
1. Disconnect all power to the furnace. Multiple disconnects may
be required. DO NOT TOUCH THE CONTROL OR ANY
WIRE CONNECTED TO THE CONTROL PRIOR TO DIS-
CHARGING YOUR BODY’S ELECTROSTATIC CHARGE
TO GROUND.
Do not install furnace in a corrosive or contaminated atmo-
sphere. Make sure all combustion and circulating air require-
ments are met, in addition to all local codes and ordinances.
2. Firmly touch the clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example; DO
5
Download from Www.Somanuals.com. All Manuals Search And Download.
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless the
damper is in the full-heat or full-cool position.
This gas furnace may be used for construction heat provided
that:
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3 of the NFGC, Air for
Combustion and Ventilation, or applicable provisions of the local
building codes.
-The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the space
containing the furnace. This prevents a negative pressure
condition as created by the circulating air blower, causing a
flame rollout and/or drawing combustion products into the
structure.
Canadian installations must be installed in accordance with NSC-
NGPIC Part 7 and all authorities having jurisdiction.
-The furnace is controlled by a thermostat. It may not be ″hot
wired″ to provide heat continuously to the structure without
thermostatic control.
-Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other
construction materials. It also prevents the entrainment of
drywall dust into combustion air, which can cause fouling and
plugging of furnace components.
-The temperature of the return air to the furnace is no less
than 55 degrees F, with no evening setback or shutdown. The
use of the furnace while the structure is under construction is
deemed to be intermittent operation per our installation
instructions.
-The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
nameplate value.
18-IN. MINIMUM
TO BURNERS
A93044
-The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
Fig. 6—Installation in a Garage
-The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC
system components after construction is completed.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18 inches
above the floor. The furnace must be located or protected to
avoid damage by vehicles. When the furnace is installed in a
public garage, airplane hangar, or other building having a
hazardous atmosphere, the furnace must be installed in
accordance with the NFGC or NSCNGPIC. (See Fig. 6.)
→
DO NOT install the furnace on its back or facing down.
Safety control operation will be adversely affected. Never
connect return-air ducts to back of furnace. Failure to follow
this warning could result in fire, personal injury, or death.
(See Fig. 5.)
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements are found in aerosol sprays, deter-
gents, bleaches, cleaning solvents, salts, air fresheners, and
other household products.
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must be
made between the furnace cabinet and the return-air duct to
prevent pulling air from the burner area and from blocked vent
safeguard opening.
→
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up air MUST be provided for the ventilation devices, in
addition to that required by the furnace. Refer to Carbon
Monoxide Hazard warning in venting section of these instruc-
tions to determine amount of make-up air required.
A02054
Fig. 5—Prohibit Installation on Back
Step 2—Location Relative to Cooling Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
The requirements for combustion and ventilation air depend upon
whether the furnace is located in an unconfined or confined space.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2–Minimum Free Area of Combustion Air Opening*
AIR FROM INDOOR
UNCONFINED SPACE
OUTDOOR AIR THROUGH
VERTICAL DUCTS
OUTDOOR AIR THROUGH
HORIZONTAL DUCTS
OUTDOOR AIR THROUGH
SINGLE DUCT
FURNACE
INPUT
(BTUH)
Free Area
of Opening
(Sq In.)
Free Area of
Round Pipe
Opening and Duct
(in. Dia)
Free Area of
Round Pipe
Opening and Duct
(in. Dia)
Free Area of
Round Pipe
Opening and Duct
(In. Dia)
(Sq. In.)
(sq In.)
(Sq In.)
44,000
66,000
100
100
100
110
132
154
11
4
5
6
6
7
7
22
33
6
7
14.7
22.0
29.3
36.7
44.0
51.3
5
6
7
7
8
8
16.5
22.0
27.5
33
88,000
44.0
55
8
110,000
132,000
154,000
9
66
10
10
38.5
77
* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances
in the space require combustion air.
AIR
DUCTS
VENT THROUGH ROOF
Step 1—Unconfined Space
An unconfined space has a volume of at least 50 cu ft for each
1000 Btuh total input for all appliances (furnaces, clothes dryers,
water heaters, etc.) in the space.
For example:
12″ MAX
FURNACE
INPUT (BTUH)
44,000
MINIMUM WITH
7–1/2 FT CEILING (SQ. FT.)
1 SQ IN.
PER 1000
294
441
587
734
881
1028
BTUH IN DOOR
*
OR WALL
66,000
88,000
UNCONFINED
SPACE
INTERIOR
HEATED
SPACE
110,000
132,000
154,000
6″ MIN
(FRONT) †
If the unconfined space is constructed unusually tight, air for
combustion and ventilation must come from either the outdoors or
spaces freely communicating with the outdoors. Combustion and
ventilation openings must be equivalent to those used for a
confined space (defined below). Return air must not be taken from
the room unless an equal or greater amount of air is supplied to the
room.
1 SQ IN.
PER 1000
BTUH IN DOOR
*
OR WALL
12″ MAX
Step 2—Confined Space
AIR DUCTS
A confined space has a volume less than 50 cu ft per 1000 Btuh
of total input ratings of all appliances installed in that space. A
confined space must have provisions for supplying air for com-
bustion, ventilation, and dilution of flue gases using one of the
following methods in Table 2 and Fig. 7 and 8.
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
† Minimum of 3 in. when type-B1 vent is used.
A02038
NOTE: When determining the free area of an opening, the
blocking effect of louvers, grilles, and screens must be considered.
If the free area of the louver or grille design is unknown, assume
wood louvers have a 20 percent free area and metal louvers or
grilles have a 60 percent free area. Screens must not be smaller
than 1/4-in. mesh. Louvers and grilles must be constructed so they
cannot be closed.
Fig. 7—Confined Space: Air for Combustion and
Ventilation from an Unconfined Indoor Space
c. If the furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from the
hallway or space adjacent to furnace, all air for combustion
must come from outdoors.
The opening size depends upon whether air comes from outside of
the structure or an unconfined space inside the structure.
1. Air from inside the structure requires 2 openings (for struc-
tures not of unusually tight construction):
2. Air from outside the structure requires 1 of the following:
a. If combustion air is taken from outdoors through 2 vertical
ducts, the openings and ducts must have at least 1 sq in. of
free area per 4000 Btuh of total input for all equipment
within the confined space. (See Fig. 8 and Table 2.)
a. Each opening must have a minimum free area of not less
than 1 sq in per 1000 Btuh of total input rating for all gas
utilization equipment in the confined space, but not less
than 100 sq in. The minimum dimension of air openings
should be no smaller than 3 in. (See Table 2 and Fig. 7 ).
b. If combustion air is taken from outdoors through 2 hori-
zontal ducts, the openings and ducts must have at least 1 sq
in. of free area per 2000 Btuh of total input for all
equipment within the confined space. (See Fig. 8 and Table
2.)
b. If building construction is unusually tight, a permanent
opening directly communicating with the outdoors shall be
provided. (See next section).
7
Download from Www.Somanuals.com. All Manuals Search And Download.
1 SQ IN.
PER 4000
BTUH*
DUCTS
TO
OUTDOORS
12″ MAX
1 SQ IN.
PER 2000
BTUH*
D
12″
MAX
VENT
A
THROUGH
ROOF
F
AIR
DUCTS
1 SQ IN.
PER
4000
BTUH*
DUCTS
TO
OUTDOORS
A02098
1 SQ IN.
PER
Fig. 9—Removing Bottom Closure Panel
4000
BTUH*
1 SQ IN.
PER 2000
BTUH*
E
G
B
12″
MAX
12″ MAX
C
SIDE RETURN AIR INLET
12″ MAX
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only side return air is used.
AIR DUCTS
DUCT
TO
1 SQ IN.
PER 4000
BTUH*
→ NOTE: Side return-air openings can be used in UPFLOW and
most HORIZONTAL configurations. Do not use side return-air
openings in DOWNFLOW configuration.
OUTDOORS
*Minimum dimensions of 3 in.
NOTE: Use any of the following
LEVELING LEGS (IF DESIRED)
combinations of openings:
A & B C & D D & E F & G
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field-supplied, 5/16 X 1 1/2 in. (max)
corrosion-resistant machine bolts, washers and nuts.
A02165
Fig. 8—Confined Space: Air for Combustion and
Ventilation from Outdoors
NOTE: Bottom closure must be used when leveling legs are used.
It may be necessary to remove and reinstall bottom closure panel
to install leveling legs. To remove bottom closure panel, see Fig.
9.
c. If combustion air is taken from the outdoors through a
single opening or duct (horizontal or vertical) commencing
within 12 in. of the top of the confined space, the opening
and duct must have at least 1 sq in. of free area per 3000
Btuh of the total input for all equipment within the confined
space and not less than the sum of the areas of all vent
connectors in the confined space. Equipment clearances to
the structure shall be at least 1 in. from the sides and back
and 6 in. from the front of the appliances. See Table 2 and
Fig. 8.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each
bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in
hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside
nut to secure arrangement.
When ducts are used, they must be of the same cross sectional area
as the free area of the openings to which they connect. The
minimum dimension of ducts must not be less than 3 in.
5. Reinstall bottom closure panel if removed.
Step 2—Downflow Installation
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the 3 accessories are
used:
INSTALLATION
Step 1—Upflow Installation
•
•
•
Special Base, KGASB
BOTTOM RETURN AIR INLET
Cased Coil Assembly Part No. CD5 or CK5
Coil Box Part No. KCAKC
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Determine application being installed from Table 3.
2. Construct hole in floor per Table 3 and Fig. 11.
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
3. Construct plenum to dimensions specified in Table 3 and Fig.
11.
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. If downflow subbase, KGASB is used, install as shown in Fig.
12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part
No. KCAKC is used, install as shown in Fig. 13.
4. Reinstall bottom filler panel and screws.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
5⁄16″
PLATFORM UNIT SUPPORT
Construct working platform at location where all required furnace
clearances are met. (See Fig. 2 and 17.) For furnaces with 1-in.
clearance requirement on side, set unit on non-combustible blocks,
bricks or angle iron. For crawlspace installations, if the unit is not
suspended from the floor joists, the ground underneath unit must
be level and the unit set on blocks or bricks.
5⁄16″
1 3⁄4″
ROLL-OUT PROTECTION
1 3⁄4″
Provide a minimum 17 3/4″ X 22″ piece of sheet metal for roll-out
protection in front of burner area for units closer than 12 inches
above the combustible deck or suspended units closer than 12-in.
to joists. The sheet metal MUST extend underneath the furnace
casing by 1 in. with the door removed.
5⁄16″
The bottom closure pan on furnaces of widths 17 1/2 in. and larger
may be used for roll-out protection when bottom of furnace is used
for return air connection. See Fig. 17 for proper orientation of
roll-out shield.
5⁄16″
1 3⁄4″
1 3⁄4″
→ BOTTOM RETURN AIR INLET
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
A02071
Fig. 10—Leveling Legs
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
NOTE: It is recommended that the perforated supply-air duct
flanges be completely folded over or removed from furnace when
installing the furnace on a factory-supplied cased coil or coil box.
To remove the supply-air duct flange, use wide duct pliers or hand
seamers to bend flange back and forth until it breaks off. Be careful
of sharp edges. (See Fig. 14.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
→ SIDE RETURN AIR INLET
→ BOTTOM RETURN AIR INLET
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only one side return air is used.
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
→ Not all horizontal furnaces are approved for side return air
connections (See Fig. 20.)
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
Step 4—Filter Arrangement
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
Never operate a furnace without a filter or with filter access
door removed. Failure to follow this warning could result in
fire, personal injury, or death.
4. Reinstall bottom filler panel and screws.
Step 3—Horizontal Installation
There are no provisions for an internal filter rack in these furnaces.
A field-supplied accessory external filter rack is required.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control opera-
tion will be adversely affected. Never connect return-air ducts
to the back of the furnace. Failure to follow this warning
could result in fire, personal injury, or death.
This furnace requires KGAFR0301ALL 1″ external filter rack or a
suitable field-supplied substitute, such as the Media Cabinet.
Refer to the instructions supplied with external filter rack for
assembly and installation options.
The furnace can be installed horizontally in an attic or crawl space
on either the left-hand (LH) or right-hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a
platform, non-combustible blocks, bricks or pad.
Step 5—Air Ducts
GENERAL REQUIREMENTS
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design Guide-
lines reference tables available from your local distributor. The
duct system should be sized to handle the required system design
CFM at the design external static pressure.
SUSPENDED UNIT SUPPORT
The furnace may be supported under each end with threaded rod,
angle iron or metal plumber’s strap as shown. (See Fig. 15 and 16.)
Secure angle iron to bottom of furnace as shown. Heavy-gauge
sheet metal straps (plumber’s straps) may be used to suspend the
unit from each bottom corner. To prevent screws from pulling out,
use 2 # 8 x ¾-in. screw into the side and 2 # 8 x ¾-in. screw in the
bottom of the furnace casing for each strap. (See Fig. 15 and 16.)
9
Download from Www.Somanuals.com. All Manuals Search And Download.
FURNACE
(OR COIL CASING
WHEN USED)
A
PLENUM
OPENING
COMBUSTIBLE
FLOORING
B
D
FLOOR
OPENING
C
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96283
Fig. 11—Floor and Plenum Opening Dimensions
A96285
Fig. 12—Furnace, Plenum, and Subbase Installed on
a Combustible Floor
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A96284
Fig. 13—Furnace, Plenum, and Coil Assembly or Coil Box Installed on a Combustible Floor
When a furnace is installed so that the supply ducts carry air to
areas outside the space containing the furnace, the return air must
also be handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated and sealed to
enhance system performance. When air conditioning is used, a
vapor barrier is recommended.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer.
Maintain a 1-in. clearance from combustible materials to supply air
ductwork for a distance of 36 in. horizontally from the furnace. See
NFPA 90B or local code for further requirements.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3—Opening Dimensions (In.)
FURNACE
CASING
WIDTH
PLENUM OPENING
FLOOR OPENING
APPLICATION
A
B
C
D
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
12-11/16
21-5/8
13-5/16
22-1/4
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
12-9/16
19
19
13-3/16
13-7/16
19-5/8
20-5/8
14–3/16
17–1/2
21
Downflow applications on combustible flooring (KGASB
11-13/16
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
12-5/16
19
13-5/16
20
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
16
21-5/8
19
16-5/8
16-1/2
16-3/4
22-1/4
19-5/8
20-5/8
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
15-7/8
15-1/8
Downflow applications on combustible flooring (KGASB
19
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
15-1/2
19
16-1/2
20
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
19-1/2
19-3/8
18-5/8
21-5/8
19
20-1/8
20
22-1/4
19-5/8
20-5/8
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
19
20-1/4
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
19
19
20
20
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
23
21-1/8
19
23-5/8
23-1/2
23-3/4
22-1/4
19-5/8
20-5/8
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
22-7/8
22-1/8
24-1/2
Downflow applications on Combustible flooring (KGASB
19
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
22-1/2
19
23-1/2
20
W
DOWNFLOW
UPFLO
HORIZONTAL
90˚
90˚
PREFERRED
PREFERRED
PREFERRED
PREFERRED
PREFERRED
PREFERRED
120˚
MIN
120˚
MIN
120˚
MIN
PERMITTED
PERMITTED
PERMITTED
A02329
→ Fig. 14—Duct Flanges
DUCTWORK ACOUSTICAL TREATMENT
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
11
Download from Www.Somanuals.com. All Manuals Search And Download.
1/4" THREADED ROD
4 REQ.
OUTER DOOR
ASSEMBLY
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x 3/4" SCREWS
TYPICAL FOR 2 SUPPORTS
8" MIN FOR DOOR
REMOVAL
1" SQUARE, 11/4" x 11/4" x 1/4" ANGLE IRON
OR UNI-STRUT MAY BE USED
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
A02345
→ Fig. 15—Horizontal Unit Suspension
A02014
Fig. 16—Horizontal Suspension with Straps
Upflow and Horizontal Furnaces
SUPPLY AIR CONNECTIONS
→ For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
Connect supply-air duct to flange on furnace supply-air outlet.
Bend flange upward to 90° with wide duct pliers. The supply-air
duct attachment must ONLY be connected to furnace supply-
outlet-air duct flanges or air conditioning coil casing (when used).
DO NOT cut main furnace casing to attach supply side air duct,
humidifier, or other accessories. All accessories MUST be con-
nected external to furnace main casing.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
17 3/4″ OVER ALL
4 3/4″ UNDER DOOR
1″ UNDER FURNACE
GAS
ENTRY
TYPE-B
VENT
EXTEND OUT 12″ OUT
FROM FACE OF DOOR
MIN*
″
6
30-IN. MIN
WORK AREA
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
17 3/4
″
SHEET
METAL
22″
MANUAL SHUTOFF
GAS VALVE
SEDIMENT
TRAP
A02164
Fig. 17—Typical Attic Installation
Downflow Furnaces
Step 6—Gas Piping
Connect supply-air duct to supply-air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used). When
installed on combustible material, supply-air duct attachment must
ONLY be connected to the accessory subbase, KGASB0201ALL,
or factory approved air conditioning coil casing. DO NOT cut
main furnace casing to attach supply side air duct, humidifier, or
other accessories. All accessories MUST be connected external to
furnace casing.
→
Never purge a gas line into a combustion chamber. Never test
for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections. A failure to follow this
warning could result in fire, explosion, personal injury, or
death.
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S., the NSCNG-
PIC in Canada.
RETURN AIR CONNECTIONS
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
Never connect return-air ducts to the back of the furnace. A
failure to follow this warning can cause a fire, personal injury,
or death.
Refer to Table 4 for recommended gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. Joint compound (pipe dope) should be applied sparingly
and only to male threads of joints. Pipe dope must be resistant to
the action of propane gas.
Downflow Furnaces
The return-air duct must be connected to return-air opening
(bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and most
horizontal furnaces. Bypass humidifier connections should be
made at ductwork or coil casing sides exterior to furnace.
→
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a
connector which has previously serviced another gas appli-
ance. Black iron pipe shall be installed at the gas valve and
extend a minimum of 2-in. outside the furnace.
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace
casing as shown in Fig. 1. Bypass humidifier may be attached to
unused side return air portion of the furnace casing. (See Fig. 18,
19, and 20.)
Not all horizontal furnaces are approved for side return air
connections. (See Fig. 20.)
13
Download from Www.Somanuals.com. All Manuals Search And Download.
A02075
Fig. 18—Upflow Return Air Configurations and Restrictions
A02163
Fig. 19—Downflow Return Air Configurations and Restrictions
A02162
Fig. 20—Horizontal Return Air Configurations and Restrictions
14
Download from Www.Somanuals.com. All Manuals Search And Download.
→
Table 4—Maximum Capacity of Pipe*
GAS
SUPPLY
NOMINAL
LENGTH OF PIPE (FT)
MANUAL
SHUTOFF
VALVE
(REQUIRED
SEDIMENT
TRAP
IRON
PIPE
SIZE
(IN.)
INTERNAL
DIAMETER
(IN.)
10
20
30
40
82
50
73
1/2
3/4
0.622
0.824
1.049
1.380
1.610
175
360
120
250
465
950
97
200
375
770
170 151
320 285
660 580
UNION
1
680
1-1/4
1-1/2
1400
2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14–in. wc) or less and a
pressure drop of 0.5–in wc (based on a 0.60 specific gravity gas).
Ref: Table 12.2 NFPA 54-2002.
A02035
Fig. 21b—Typical Gas Pipe Arrangement
Connect gas pipe to gas valve using a backup wrench to avoid
damaging gas controls.
Use proper length of pipe to avoid stress on gas control
manifold. Failure to follow this warning could result in a gas
leak resulting in fire, explosion, personal injury, or death.
→ If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be
disconnected from furnace and capped before pressure test. If test
pressure is equal to or less than 0.5 psig (14-in. wc), turn off
electric shutoff switch located on furnace gas control valve and
accessible manual shutoff valve before test. After all connections
have been made, purge lines and check for leakage.
→ An accessible manual shutoff valve MUST be installed external to
furnace casing and within 6 ft of furnace. A 1/8-in. NPT plugged
tapping, accessible for test gage connection, MUST be installed
immediately upstream of gas supply connection to furnace and
downstream of manual shutoff valve.
→ NOTE: The gas valve inlet pressure tap connection is suitable to
use as test gage connection providing test pressure DOES NOT
exceed maximum 0.5 psig (14-in. wc) stated on gas control valve.
(See Fig. 50.)
→ The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with
the furnace burners ON and OFF.
→ Some installations require gas entry on right side of furnace (as
Step 7—Electrical Connections
viewed in upflow). (See Fig. 21a.)
Install a sediment trap in riser leading to furnace as shown in Fig
21b. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of gas controls. Place a ground joint
union between gas control manifold and exterior manual equip-
ment gas shutoff valve. A 1/8-in. NPT plugged tapping, accessible
for test gage connection, MUST be installed immediately upstream
of gas supply connection to furnace and downstream of manual
shutoff valve.
Blower access panel door switch opens 115-v power to
control center. No component operation can occur. Do not
bypass or close switch with panel removed. Failure to follow
this warning could result in personal injury or death.
See Fig. 24 for field wiring diagram showing typical field 115-v
wiring. Check all factory and field electrical connections for
tightness.
→ Piping should be pressure and leak tested in accordance with
NFGC in the United States or NSCNGPIC in Canada, local, and
national plumbing and gas codes before the furnace has been
connected. After all connections have been made, purge lines and
check for leakage at furnace prior to operating furnace.
→ Field-supplied wiring shall conform with the limitations of 63°F
(33°C) rise.
90° Elbow
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC ANSI/NFPA 70-2002 and Canadian Elec-
trical Code CSA C22.1 or local codes to minimize personal
injury if an electrical fault should occur. This may consist of
electrical wire, conduit approved for electrical ground or a
listed, grounded power cord (where permitted by local code)
when installed in accordance with existing electrical codes.
Refer to the power cord manufacturer’s ratings for proper
wire gage. Do not use gas piping as an electrical ground.
Failure to follow this warning could result in electrical shock,
fire, or death.
2" Nipple
Street Elbow
Gas Valve
A02327
→ Fig. 21a—Right Side Gas Entry Example
15
Download from Www.Somanuals.com. All Manuals Search And Download.
→ Table 5—Electrical Data
OPERATING
VOLTAGE RANGE
VOLTS-
HERTZ-
PHASE
MAXIMUM
FUSE OR CKT BKR
AMPS†
MAXIMUM
UNIT
MAXIMUM
MINIMUM
WIRE GAGE
UNIT SIZE
UNIT AMPS AMPACITY# WIRE LENGTH (FT)‡
Maximum* Minimum*
045-08/024045 115-60-1
045-12/036045 115-60-1
070-08/024070 115-60-1
070-12/036070 115-60-1
070-16/048070** 115-60-1
090-14/042090 115-60-1
090-16/048090 115-60-1
090-20/060090** 115-60-1
110-12/036110 115-60-1
110-16/048110 115-60-1
110-22/066110 115-60-1
135-16/048135 115-60-1
135-22/066135 115-60-1
155-22/060155 115-60-1
127
127
127
127
127
127
127
127
127
127
127
127
127
127
104
104
104
104
104
104
104
104
104
104
104
104
104
104
5.6
7.0
7.77
9.47
47
39
52
40
28
34
28
34
34
28
32
28
30
29
15
15
15
15
15
15
15
20
15
15
20
15
20
20
14
14
14
14
14
14
14
12
14
14
12
14
12
12
5.0
7.06
6.7
9.19
9.8
12.59
10.83
12.95
17.60
10.75
13.12
17.62
13.12
18.55
19.33
8.1
9.8
12.9
8.2
10.1
13.7
10.1
14.4
15.0
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps.
† Time-delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Preliminary
Furnace control must be grounded for proper operation or
control will lock out. Control is grounded through
green/yellow wire routed to gas valve and manifold bracket
screw.
TWO
115-V WIRING
Verify that the voltage, frequency, and phase correspond to that
specified on unit rating plate. Also, check to be sure that service
provided by utility is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 5 for equipment electrical
specifications. Make all electrical connections in accordance with
National Electrical Code (NEC) ANSI/NFPA 70-2002 and any
local codes or ordinances that might apply. For Canadian instal-
lations, all electrical connections must be made in accordance with
Canadian Electrical Code CSA C22.1 or authorities having juris-
diction.
A02099
Fig. 22—Relocating J-Box
3. Locate box to desired location.
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.
4. Fasten J-Box to casing with screws.
5. Route J-box wires within furnace away from sharp edges and
Use a separate, fused branch electrical circuit with a properly sized
hot surfaces.
fuse or circuit breaker for this furnace. See Table 5 for wire size
and fuse specifications. A readily accessible means of electrical
ELECTRICAL CONNECTION TO J-BOX
disconnect must be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115-v wiring. If
If manual disconnect switch is to be mounted on furnace,
polarity is incorrect, control LED status indicator light will flash
select a location where a drill or fastener will not contact
rapidly and furnace will NOT operate.
electrical or gas components.
J-BOX RELOCATION
1. Attach electrical box to J-Box bracket.
NOTE: If factory location of J-Box is acceptable, go to next
2. Route wires through hole in electrical box and J-Box bracket.
3. Secure ground wire to green screw on J-Box bracket.
4. Connect line voltage leads as shown in Fig. 24.
FOR POWER CORD INSTALLATION
section (J-Box Cover Installation).
NOTE: On 14″ wide casing models, the J-Box shall not be
relocated to other side of furnace casing when the vent pipe is
routed within the casing.
1. Remove screws holding auxiliary J-box. (See Fig. 22.)
2. Cut wire tie on loop in wires to J-box.
Power cords must be able to handle the electrical requirements
listed in Table 5. Refer to power cord manufacturer’s listings.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
TWINNING AND/OR
COMPONENT TEST
TERMINAL
BLOWER OFF-DELAY
J2 JUMPER
BLOWER OFF-DELAY
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
24-V THERMOSTAT
TERMINALS
TRANSFORMER 24-VAC
CONNECTIONS
TEST/TWIN
HUM
0.5 AMP@24VAC
3-AMP FUSE
FUSE 3-AMP
SEC-2 SEC-1
LED OPERATION &
DIAGNOSTIC LIGHT
EAC-2
L2
PL1-LOW VOLTAGE MAIN
HARNESS CONNECTOR
115-VAC(L2)NEUTRAL
CONNECTIONS
COOL
HEAT
1-AMP@
115VAC
SPARE-1 SPARE-2
PR-1
EAC-1
PL2
1
SPARE-1
SPARE-2
PL2-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115 VAC (L1) LINE
VOLTAGE CONNECTION
BLOWER SPEED
SELECTION TERMINALS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
A02100
Fig. 23—Furnace Control
1. Route listed power cord through hole in J-Box.
maintenance could cause this fuse to blow. If fuse replacement is
required, use ONLY a 3-amp fuse of identical size.
2. Secure power cord to J-Box bracket with a strain relief
bushing or a connector approved for the type of cord used.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
3. Secure ground wire to green screw on J-Box bracket.
4. Connect line voltage leads as shown in Fig. 24.
FOR BX CABLE INSTALLATION
Connect an accessory Electronic Air Cleaner (if used) using
1/4-in female quick connect terminals to the two male 1/4-in
quick-connect terminals on the control board marked EAC-1
and EAC-2. The terminals are rated for 115 VAC, 1.0 amps
maximum and are energized during blower motor operation.
1. Route BX cable to hole in J-Box.
2. Secure BX cable to J-Box bracket with connectors approved
for the type of cable used.
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp maximum humidifier
(if used) to the 1/4-in male quick-connect HUM terminal and
COM-24V screw terminal on the control board thermostat strip.
The HUM terminal is energized when pressure switch (PRS)
closes.
3. Secure ground wire to green screw on J-Box bracket.
4. Connect line voltage leads as shown in Fig. 24.
J-BOX COVER INSTALLATION
1. Remove J-Box cover from blower access door on furnace and
reinstall blower access door screw.
NOTE: A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
2. Fold tab on J-box cover to bracket with pliers.
3. Insert tab of J-box cover into slot of J-box bracket.
4. Secure J-Box cover to bracket with screw provided.
5. Remove U-shaped cut-out from outer door to clear J-box.
24-V WIRING
Make field 24-v connections at the 24-v terminal strip. (See Fig.
23.) Connect terminal Y as shown in Fig. 24 for proper cooling
operation. Use only AWG No. 18, color-coded, copper thermostat
wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control. Any direct shorts during installation, service, or
17
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
THERMOSTAT
TERMINALS
W
C
R
G
Y
FIVE WIRE
FIELD-SUPPLIED
DISCONNECT
THREE-WIRE
HEATING-ONLY
208/230- OR
460-V
BLOWER DOOR SWITCH
THREE
PHASE
W
BLK
BLK
WHT
C
R
WHT
O
N
T
208/230-V
SINGLE
PHASE
GND
GND
G
R
AUXILIARY
J-BOX
115-V FIELD-
SUPPLIED
DISCONNECT
O
COM
GND
L
NOTE 1
CONDENSING
UNIT
Y/Y2
TWO
WIRE
24-V
TERMINAL
BLOCK
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
FURNACE
A99440
Fig. 24—Heating and Cooling Application Wiring Diagram with 1–Stage Thermostat
→ When an existing furnace is removed or replaced in a venting
system, the venting system may not be properly sized to vent the
attached appliances. An improperly sized Category I venting
system could cause the formation of condensate in the furnace and
vent, leakage of condensate and combustion products, and spillage
of combustion products into the living space, etc.
DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermidistat™, Zone Controller or
similar device. See Thermidistat™, Zone Controller, thermo-
stat, or controller manufacturer’s instructions for proper
connection.
Step 8—Venting
→ The furnace shall be connected to a factory built chimney or vent
complying with a recognized standard, or a masonry or concrete
chimney lined with a lining material acceptable to the authority
having jurisdiction. Venting into an unlined masonry chimney or
concrete chimney is prohibited.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
The following information and warning must be considered in
addition to the requirements defined in the NFGC and the
NSCNGPIC.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and
Propane Installation Codes and these instructions. Deter-
mine that there is no blockage or restriction, leakage,
corrosion and other deficiencies, which could cause an
unsafe condition.
1. If a vent (common or dedicated) becomes blocked, the furnace
will be shut off by the draft safeguard switch located on the
vent elbow.
Do not bypass the draft safeguard switch, as an unsafe
condition could exist which must be corrected. Failure to
follow this warning could result in a build-up of carbon
monoxide and lead to personal injury or death.
2. Do not connect this appliance to a single-wall dedicated or
common vent. The dedicated or common vent is considered to
be the vertical portion of the vent system that terminates
outdoors.
3. Vent connectors serving Category I furnaces shall not be
connected into any portion of a mechanical draft system
operating under positive pressure.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
4. In the US, do not vent this appliance with any solid fuel
burning appliance. In Canada, check with the authority having
jurisdiction for approval on use with solid fuel burning
appliance.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to
the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operating
at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so appli-
ance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the
draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle.
→ 5. Category I furnaces must be vented vertically or nearly
vertically unless equipped with a listed power ventor.
→ 6. Do not vent this appliance into an unlined masonry chimney.
Refer to Chimney Inspection Chart, Fig. 25.
MASONRY CHIMNEY REQUIREMENTS
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in accordance
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CSA B149.1, Natural Gas and Propane Installation
Codes.
9. After it has been determined that each appliance connected
to the venting system properly vents when tested as
outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas-fired burning appli-
ance to their previous conditions of use.
These furnaces are CSA design-certified for use in exterior
clay tile-lined masonry chimneys with a factory accessory
Chimney Adapter Kit. Refer to the furnace rating plate for
correct kit usage. The Chimney Adapter Kits are for use with
ONLY furnaces having a Chimney Adapter Kit number
marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed
to the outdoors below the roof line, relining might be required.
Chimneys shall conform to the Standard for Chimneys, Fireplaces,
Vents, and Soild Fuel Burning Appliances ANSI/NFPA 211-2000
in the United States and to a Provincial or Territorial Building
Code in Canada (in its absence, the National Building Code of
Canada) and must be in good condition.
→ Vent system or vent connectors may need to be resized. For any
other appliances when resizing vent systems or vent connectors,
system or connector must be sized to approach minimum size as
determined using appropriate table found in the NFGC or NSC-
NGPIC.
U.S.A.-Refer to Sections 13.1.9 and 13.2.20 of the NFGC or the
authority having jurisdiction to determine whether relining is
required. If relining is required, use a properly sized listed metal
liner, Type-B vent, or a listed alternative venting design.
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel
Gas Code (NFGC) ANSI Z223.1-2002/NFPA 54-2002, Parts 7 and
13 in the United States or the National Standard of Canada, Natural
Gas and Propane Installation Code (NSCNGPIC) CSA-B149.1-00,
Section 7 and Appendix C in Canada.
These furnaces are design-certified as Category I furnaces in
accordance with ANSI Z21.47/CSA 2.3-2001 and operate with a
non-positive vent static pressure to minimize the potential for vent
gas leakage. Category I furnaces operate with a flue loss not less
than 17 percent to minimize the potential for condensation in the
venting system. These furnaces are approved for common venting
and multi-story venting with other fan assisted or draft hood
equipped appliances in accordance with the NFCG or the NSC-
NGPIC.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: See the NFGC, 13.1.9 and 13.2.20 regarding alternative
venting design and the exception, which cover installations such as
Table B—Minimum Allowable Input Rating of
Space-Heating Appliance in
the
Chimney
Adapter
Kits
KGACA02014FC
and
Thousands of BTU per Hour
KGACA02015FC, which are listed for use with these furnaces.
INTERNAL AREA OF CHIMNEY
The Chimney Adapter Kit is listed alternative venting design for
these furnaces. See the kit instructions for complete details.
VENT
HEIGHT (FT)
(SQ. IN.)
12
19
28
38
Local 99% Winter Design
Temperature: 17 to 26 degrees F*
Canada-This furnace is permitted to be vented into a clay
tile-lined masonry chimney that is exposed to the outdoors below
the roof line, provided:
6
0
55
74
99
141
154
169
212
258
362
8
52
111
125
167
212
NR
1. Vent connector is Type-B double-wall, and
10
15
20
30
NR
NR
NR
NR
90
2. This furnace is common vented with at least 1 draft hood-
equipped appliance, and
NR
NR
NR
3. The combined appliance input rating is less than the maximum
capacity given in Table A, and
Local 99% Winter Design
Temperature: 5 to 16 degrees F*
4. The input rating of each space heating appliance is greater
than the minimum input rating given in the appropriate Table
B for Masonry Chimneys for the local winter design tempera-
ture. Chimneys having internal areas greater than 38 square
inches require furnace input ratings greater than the input
ratings of these furnaces. See footnote at bottom of Table B,
and
6
NR
NR
NR
NR
NR
NR
78
94
121
135
149
193
NR
166
182
198
247
293
377
8
10
15
20
30
111
NR
NR
NR
NR
Local 99% Winter Design
Temperature: -10 to 4 degrees F*
5. The authority having jurisdiction approves.
6
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
145
159
175
NR
NR
NR
196
213
231
283
333
NR
If all of these conditions cannot be met, an alternative venting
design shall be used, such as the listed chimney adapter kit with
these furnaces listed for use with the kit, a listed chimney-lining
system, or a Type-B common vent.
8
10
15
20
30
Exterior Masonry Chimney,
FAN + NAT Installations with
Type-B Double-Wall Vent Connectors
Local 99% Winter Design
Temperature: -11 degrees F or lower*
Not recommended for any vent
configuration
Table A—Combined Appliance
Maximum Inut Rating in
Thousands of BTU per Hour
INTERNAL AREA OF CHIMNEY
VENT
HEIGHT (FT)
(SQ. IN.)
*The 99% Winter Design Dry-Bulb (db) temperatures are found in the 1993
ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and
2 (Canada), or use the 99.6% heating db temperatures found in the 1997 or
2001 ASHRAE Fundamentals Handbook, Climatic Design Information chap-
ter, Table 1A (United States) and 2A (Canada).
12
74
19
28
38
6
119
130
138
152
NR
NR
178
193
207
233
250
NR
257
279
299
334
368
404
8
80
10
15
20
30
84
Inspections before the sale and at the time of installation will
determine the acceptability of the chimney or the need for repair
and/or (re)lining. Refer to Fig. 25 to perform a chimney inspection.
If the inspection of a previously used tile-lined chimney:
NR
NR
NR
a. Shows signs of vent gas condensation, the chimney should
be relined in accordance with local codes and the authority
having jurisdiction. The chimney should be relined with a
listed metal liner, Type-B vent, or a listed chimney adapter
kit shall be used to reduce condensation. If a condensate
drain is required by local code, refer to the NFGC, Section
10.9 for additional information on condensate drains.
b. Indicates the chimney exceeds the maximum permissible
size in the tables, the chimney should be rebuilt or relined
to conform to the requirements of the equipment being
installed and the authority having jurisdiction.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
A chimney without a clay tile liner, which is otherwise in good
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be
lined with a UL listed (ULC listed in Canada) metal liner or UL
listed Type-B vent. Relining with a listed metal liner or Type-B
vent is considered to be a vent-in-a-chase.
NOTE: Vent connector length for connector sizing starts at
furnace vent elbow. The 4 inch vent elbow is shipped for upflow
configuration and may be rotated for other positions. Remove the
3 screws that secure vent elbow to furnace, rotate furnace vent
elbow to position desired, re-install screws. The factory-supplied
vent elbow does NOT count as part of the number of vent
connector elbows.
If a metal liner or Type-B vent is used to line a chimney, no other
appliance shall be vented into the annular space between the
chimney and the metal liner.
The vent connector can exit the door through one of 5 locations on
the door.
1. Attach the single wall vent connector to the furnace vent
elbow, and fasten the vent connector to the vent elbow with at
least two field-supplied, corrosion-resistant, sheet metal
screws located 180° apart.
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance
of the venting system. If the appliances are sized, installed,
adjusted, and operated properly, the venting system and/or the
appliances should not suffer from condensation and corrosion. The
venting system and all appliances shall be installed in accordance
with applicable listings, standards, and codes.
2. Vent the furnace with the appropriate connector as shown in
Fig. 26–38.
The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates
can be made using approved methods available from Air Condi-
tioning Contractors of America (Manual J); American Society of
Heating, Refrigerating, and Air-Conditioning Engineers; or other
approved engineering methods. Excessive oversizing of the fur-
nace could cause the furnace and/or vent to fail prematurely.
Personal injury can result form sharp metal edges, etc. Be
careful when removing parts. Gloves and safety glasses
should be worn when servicing equipment.
3. Orient the door to determine the correct location of the door
cutout to be removed.
4. Use aviation-type tin snips to remove the correct U-shaped
cut-out on door.
When a metal vent or metal liner is used, the vent must be in good
condition and be installed in accordance with the vent manufac-
turer’s instructions.
An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED
for downflow applications for use where the vent exits through the
lower portion of the furnace casing door. Refer to the Vent Guard
Kit Instructions for complete details.
To prevent condensation in the furnace and vent system, the
following precautions must be observed:
1. The return-air temperature must be at least 60°F db except for
brief periods of time during warm-up from setback at no lower
than 55°F db or during initial start-up from a standby
condition.
The horizontal portion of the venting system shall maintain a
minimum of 1/4-in. upward slope per linear ft and it shall be
rigidly supported every 5 ft or less with metal hangers or straps to
ensure there is no movement after installation.
2. Adjust the gas input rate per the installation instructions. Low
gas input rate causes low vent gas temperatures, causing
condensation and corrosion in the furnace and/or venting
system. Derating is permitted only for altitudes above 2000 ft.
SIDEWALL VENTING
This furnace is not approved for direct sidewall horizontal venting
without the use of an add-on power venter.
3. Adjust the air temperature rise range to the midpoint or
slightly above. Low air temperature rise can cause low vent
gas temperature and potential for condensation problems.
In the U.S.: Per the NFGC, any listed power venter may be used,
when approved by the authority having jurisdiction.
In Canada: Only power venters approved by the appliance
manufacturer and where allowed by the authority having jurisdic-
tion may be used for sidewall venting.
4. Set the thermostat heat anticipator or cycle rate to reduce short
cycling.
Air for combustion must not be contaminated by halogen com-
pounds which include chlorides, fluorides, bromides, and iodides.
These compounds are found in many common home products such
as detergent, paint, glue, aerosol spray, bleach, cleaning solvent,
salt, and air freshener, and can cause corrosion of furnaces and
vents. Avoid using such products in the combustion-air supply.
Furnace use during construction of the building could cause the
furnace to be exposed to halogen compounds, causing premature
failure of the furnace or venting system due to corrosion.
The only approved power venter is the Field Controls SWG-4D
and SWG-5D sidewall power venter. Select the power venter to
match the btuh input of the appliance being vented. Follow all
manufacturer’s installation requirements for venting and termina-
tion included with the power venter.
START-UP, ADJUSTMENT, AND SAFETY CHECK
Step 1—General
Vent dampers on any appliance connected to the common vent can
cause condensation and corrosion in the venting system. Do not
use vent dampers on appliances common vented with this furnace.
This furnace is equipped with manual reset limit switches in
the gas control area. The switches open and shut off power to
the gas valve if a flame rollout or overheating condition
occurs in the gas control area. DO NOT bypass the switches.
Correct inadequate combustion air supply problem and reset
the switches. Failure to follow this warning can cause fire,
explosion, personal injury, or death.
ADDITIONAL VENTING REQUIREMENTS
A 4″ round vent elbow is supplied with the furnace. A 5 inch or 6
inch vent connector may be required for some model furnaces. A
field-supplied 4 inch to 5 inch or 4 inch to 6 inch sheet metal
increaser fitting is required when 5 inch or 6 inch vent connector
is used. See Fig. 26–38 Venting Orientation for approved vent
configurations.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian
installation Codes CSA-B149.1 in Canada.
Crown
Rebuild
crown.
condition:
Missing mortar
or brick?
Yes
No
Is chimney
property lined with
clay tile liner?
No
Yes
Repair
Is
Reline
No
liner or top seal
or reline chimney as
necessary.
liner and top
seal in good
condition?
Repair
Yes
Debris
Mortar
or tile
debris?
in cleanout?
Yes
Yes
Remove mortar
and tile debris
Mortar, tile, metal vent
fuel oil residue?
No
Remove metal vent
or liner.
No
Clay
Yes
tile misalignment,
missing sections,
gaps?
Consult
Part B of
Not Suitable
chimney adapter venting
instructions for
application
No
No
suitability.
Is chimney
lined with properly
sized, listed liner or
Type-B vent?
Line chimney with property
sized, listed flexible metal
liner or Type-B vent per
NFGC or NSCNGPIC Vent
Sizing Tables and liner or
vent manufacturer’s
Condensate
drainage at bottom
of chimney?
Suitable
Yes
Yes
Install chimney
adapter per
instructions.
No
Installation instructions.
Not Suitable
Consult
Yes
Chimney
exposed to
outdoors below
roof line?
Part C of
chimney adapter venting
instructions for
application
Is chimney
to be dedicated to
a single
No
Suitable
Yes
furnace?
suitability
Install chimney
adapter per
instructions.
No
Chimney is
acceptable for use.
A02101
Fig. 25—Chimney Inspection Chart
22
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Verify furnace restarts by raising thermostat setting above
room temperature.
Personal injury can result form sharp metal edges, etc. Be
careful when removing parts. Gloves and safety glasses
should be worn when servicing equipment.
Step 3—Adjustments
1. Maintain 115-v wiring and ground. Improper polarity will
result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24-v terminal block
on the furance control. Failure to make proper connections
will result in improper operation. (See Fig. 24.)
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result in
excess overfire and heat exchanger failures.
3. Gas supply pressure to the furnace must be greater than 4.5-in.
wc (0.16 psig) but not exceed 14-in. wc (0.5 psig).
4. Check all manual-reset switches for continuity.
5. Install blower compartment door. Door must be in place to
operate furnace.
DO NOT redrill orifices. Improper drilling (burrs, out-of-
round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of heat exchangers, causing failures. (See Fig.
41.)
6. Replace outer door.
Step 2—Start-Up Procedures
Furnace gas input rate on rating plate is for installations at altitudes
up to 2000 ft. Furnace input rate must be within ±2 percent of
furnace rating plate input.
Never purge a gas line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition for the
purpose of checking leakage. Use a soap-and-water solution
to check for leakage. Failure to follow this warning can cause
fire, explosion, personal injury, or death.
In the U.S.A., the input rating for altitudes above 2,000 ft. must be
reduced by 4 percent for each 1,000 ft. above sea level. In Canada,
input rating must be reduced by 10 percent for altitudes of 2,000
ft. to 4,500 ft. above sea level.
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
1. Determine the correct gas input rate.
In the U.S.:
For installations below 2000 ft., refer to the unit rating plate.
For installations above 2000 ft., multiply the input on the
rating plate by the de-rate multiplier in Table 6 for the correct
input rate.
→
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes. Failure to follow this warning could result
in electrical shock, personal injury, or death.
In Canada:
At installation altitudes from 2000 to 4500 ft, this furnace must be
derated 10 percent by an authorized Gas Conversion Station or
Dealer. To determine correct input rate for altitude, see example 1
and use 0.90 as derate multiplier factor.
3. To Begin Component Self-Test: Disconnect the thermostat R
lead from furnace control board. Manually close the blower
door switch. Briefly short the TEST/TWIN terminal to the
COM 24V terminal until LED goes out. Remove jumper from
terminals. (See Fig. 23.)
EXAMPLE 1:
88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT.
Derate
Multiplier
Factor
0.90
Furnace Input Rate
at Installation
Altitude
Furnace Input Rate
at Sea Level
88,000
X
X
=
=
NOTE: The furnace control allows all components, except the gas
valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
79,200
2. Determine the correct orifice and manifold pressure adjust-
ment. There are two different orifice and manifold adjustment
tables.
All models in all positions, except Low NOx models in
downflow or horizontal positions, use Table 10 (22,000
BTUH/Burner)
Low NOx models in the downflow or horizontal positions
must use Table 11 (21,000BTUH/Burner). See input listed on
furnace rating plate.
Component test sequence is as follows:
Refer to service label attached to furnace or see Fig. 43.
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step f of
component test sequence.
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
c. Hot surface ignitor is energized for 15 sec., then off.
d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.
f. Inducer motor stops.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation altitude in Table 10 or 11.
g. Reconnect R lead to furnace control board, release blower
door switch and re-install blower door.
d. Find closest natural gas heat value and specific gravity in
Table 10 or 11.
4. Operate furnace per instruction on door.
e. Follow heat value and specific gravity lines to point of
intersection to find orifice size and manifold pressure
settings for proper operation.
5. Verify furnace shut down by lowering thermostat setting
below room temperature.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
SEE NOTES: 1,2,4,7,8,9
SEE NOTES: 1,2,3,4,7,8,9
SEE NOTES:1,2,3,4,5,7,8,9
A02060
A02058
A02059
Fig. 26—Upflow Application-
Fig. 27—Upflow Application-
Fig. 28—Downflow
Application-Vent Elbow Up
then Left
Vent Elbow Up
Vent Elbow Right
SEE NOTES: 1,2,4,5,7,8,9
A02061
SEE NOTES: 1,2,4,5,6,7,8,9
A02062
SEE NOTES: 1,2,3,4,7,8,9
A02063
Fig. 29—Downflow
Application-Vent Elbow Up
Fig. 30—Downflow
Application-Vent Elbow Left
then Up
Fig. 31—Downflow
Application-Vent Elbow Up
then Right
See Venting Notes on page 26.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
SEE NOTES: 1,2,4,7,8,9
A02064
SEE NOTES: 1,2,4,5,7,8,9
Fig. 32—Horizontal Left Application-Vent Elbow Left
A02067
Fig. 35—Horizontal Left Application-Vent Elbow Right
SEE NOTES: 1,2,4,5,7,8,9
A02065
SEE NOTES: 1,2,4,5,7,8,9
Fig. 33—Horizontal Left Application-Vent Elbow Right
then Up
A02068
Fig. 36—Horizontal Right Application-Vent Elbow Left
See Venting Notes on Page 26
SEE NOTES: 1,2,4,5,7,8,9
A02066
Fig. 34—Horizontal Left Application-Vent Elbow Up
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
c. Connect a water column manometer or similar device to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Set thermostat to call for heat.
g. Replace orifice with correct size if required by Table 13 or
14. Use only factory-supplied orifices. See EXAMPLE 2.
f. Jumper R and W thermostat connections on furnace control
board to start furnace.
22,000 BTUH burner applications use Table 10
EXAMPLE 2: (0–2000 ft altitude)
Heating value = 1000 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*
g. Remove regulator seal cap and turn regulator adjusting
screw counterclockwise (out) to decrease input rate of
clockwise (in) to increase input rate.
h. Install regulator seal cap.
Manifold pressure: 3.7-in. wc
i. Leave manometer or similar device connected and proceed
to Step 4.
* Furnace is shipped with No. 43 orifices. In this example
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.
NOTE: DO NOT set manifold pressure less than 3.2-in wc or
more than 3.8-in. wc for natural gas at sea level. If manifold
pressure is outside this range, change main burner orifices or refer
Table 10 or 11.
3. Adjust manifold pressure to obtain correct input rate.
a. Turn gas valve ON/OFF switch to OFF
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.
b. Remove manifold pressure tap plug from gas valve. (See
Fig. 40.)
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting Notes for Fig. 26-38
1. For common vent, vent connector sizing and vent material: United
States, latest edition of the National Fuel Gas Code (NFGC), ANSI
Z223.1/NFPA 54. In Canada, latest edition of the National Standards
of Canada, Natural Gas and Propane Installation Code (NSCNGPIC),
CSA B149.1-00.
2. Immediately increase to 5–inch vent connector outside furnace
casing when 5-inch vent connector required, refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use
Type B vent immediately after exiting the furnace, except when
KGAVG0101DFG is used in the downflow position.
A02069
SEE NOTES: 1,2,4,7,8,9
Fig. 37—Horizontal Right Application-Vent Elbow
Right
4. Type B vent where required, refer to Note 1 above.
5. 4” single wall (26 ga. min.) vent must be used inside furnace casing
and when the KGAVG0101DFG Downflow Vent Guard Kit is used
external to the furnace.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required
in downflow installations with bottom vent configuration.
7. Chimney Adapter Kit required for exterior masonry chimney
applications. Refer to Chimney Adapter Kit, KGACA02014FC and
KGACA02015FC for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant
sheet metal screws, spaced approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion
resistant screws spaced approximately 120° apart. Secure Type B vent
connectors per vent connector manufacturer’s recommendations.
SEE NOTES: 1,2,4,5,7,8,9
A02070
Fig. 38—Horizontal Right Application-Vent Elbow Left
then Up
4. Verify natural gas input rate by clocking meter.
NOTE: Gas valve regulator adjustment cap must be in place for
proper input to be clocked.
Disconnect 115-v electrical power before changing speed tap.
Failure to follow this warning could result in personal injury.
a. Turn off all other gas appliances and pilots.
b. Run furnace for 3 minutes in heating operation.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease
blower speed to increase temperature rise.
c. Measure time (in sec) for gas meter to complete 1 revolu-
tion and note reading. The 2 cubic feet dial provides a more
accurate measurement of gas flow.
d. Turn thermostat down below room temperature and re-
move blower access door.
d. Refer to Table 8 for cubic ft of gas per hr.
e. To change motor speed selection for heating, remove
blower motor lead from control HEAT terminal (See Fig.
39.) Select desired blower motor speed lead from one of the
other terminals and relocate it to the HEAT terminal (See
Table 7 for lead color identification). Reconnect original
lead to SPARE terminal.
e. Multiply gas rate (cu ft/hr) by heating value (Btu/cu ft) to
obtain input.
If clocked rate does not match required input from Step 1, increase
manifold pressure to increase input or decrease manifold pressure
to decrease input. Repeat steps b through e until correct input is
achieved. Re-install regulator seal cap on gas valve.
f. Repeat steps a through e.
5. Set temperature rise.
g. When correct input rate and temperature rise is achieved,
turn gas valve ON/OFF switch to OFF.
The furnace must operate within the temperature rise ranges
specified on the furnace rating plate. Do not exceed tempera-
ture rise range specified on unit rating plate. Determine the
temperature rise as follows:
h. Remove manometer or similar device from gas valve.
i. Re-install manifold pressure tap plug in gas valve.
a. Place thermometers in return and supply ducts as close to
furnace as possible. Be sure thermometers do not see
radiant heat from heat exchangers. Radiant heat affects
temperature rise readings. This practice is particularly
important with straight-run ducts.
Failure to reinstall manifold pressure tap plug in gas valve
will result in fire, explosion, personal injury, property damage
or death.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
j. Re-install blower access door if removed.
k. Turn gas valve ON/OFF switch to ON.
NOTE: Blower access door must be installed for proper tempera-
ture rise measurement.
NOTE: If the temperature rise is outside this range, first check:
1.) Gas input for heating operation.
2.) Derate for altitude if applicable.
3.) Return and supply ducts for excessive restrictions causing static
pressures greater than 0.50-in. wc.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the mid-
point of rise range or slightly above
4.) Dirty filter.
6. Set thermostat heat anticipator.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
. E
R E V 9 - 1 0 1 2 3 7 5 5
L 2
L
R A U T N E
PRINTED CIRCIUT BOARD
L
Y E
N A T R
I
H S
E L Y /
G R N
R E D
U B L
0 1
1 1
8
9
3
4
1 5 2 6
7
J 2
L
R A U T N E
T E O # N 8
W B L
PRINTED CIRCIUT BOARD
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Caution!! For the following applications, use the minimum vertical vent sections as specified below.
For all other applications, follow exclusively the National Fuel Gas Code.
MINIMUM
VENT DIAMETER (IN.)*
FURNACE ORIENTATION
VENT ORIENTATION
FURNACE INPUT(BTU/HR)
MINIMUM VERTICAL VENT HEIGHT (FT)**
154,000
132,000
110,000(036/-12 only)
Vent elbow left, then up
Fig. 30
Downflow
5
12
Vent elbow right,
then up
154,000
132,000
Horizontal Left
5
7
Fig. 33
Vent Elbow up
Fig. 34
154,000
132,000
Horizontal Left
Horizontal Left
Downflow
5
5
5
5
7
7
Vent elbow right
Fig. 35
154,000
Vent elbow up then left
Fig. 28
110,000
(036/-12 only)
10
10
Vent elbow up, then right
Fig. 31
110,000
(036/-12 only)
Downflow
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
*4 in. inside casing or vent guard
**Including 4 in. vent section(s)
Table 6–Altitude Derate Multipler for U.S.A.
ALTITUDE
(FT)
PERCENT
OF DERATE
DERATE MULTIPLIER
FACTOR*
0–2000
0
1.00
0.90
0.86
0.82
0.78
0.74
0.70
0.66
0.62
2001–3000
3001–4000
4001–5000
5001–6000
6001–7000
7001–8000
8001–9000
9001–10,000
8–12
12–16
16–20
20–24
24–28
28–32
32–36
36–40
BURNER
ORIFICE
* Derate multiplier factors are based on midpoint altitude for altitude range.
ON AND OFF
SWITCH
A93059
Fig. 41—Orifice Hole
Table 7—Speed Selection
GAS PRESSURE
COLOR
White
Black
SPEED
Common
High
AS SHIPPED
BLW
REGULATOR
ADJUSTMENT
COOL
Yellow†
Blue*
Med-High
Med-Low
Low
SPARE
SPARE
HEAT
Red*
* 1/5 HP motor models: BLUE to HEAT, RED to SPARE.
† Not available on 1/5 HP motors.
NOTE: Continuous blower is the HEAT speed.
(1.) Remove thermostat from subbase or from wall.
INLET
PRESSURE
TAP
(2.) Connect an amp meter as shown in Fig. 42 across the
R and W terminals or R and W wires.
MANIFOLD
PRESSURE TAP
A00157
(3.) Record amp draw across terminals when furnace is in
heating and after blower starts.
Fig. 40—Redundant Automatic Gas Control Valve
(4.) Set heat anticapator on thermostat per thermostat
instructions and install on subbase or wall.
a. Mechanical thermostat—Set thermostat heat anticipator to
match the amp draw of the electrical components in the
R-W circuit. Accurate amp draw readings can be obtained
at the wires normally connected to thermostat subbase
terminals, R and W. The thermostat anticipator should
NOT be in the circuit while measuring current.
b. Electronic thermostat: Set cycle rate for 4 cycles per hr.
7. Adjust blower off delay
The blower off delay has 4 adjustable settings from 90 sec to
180 sec. The blower off delay jumpers are located on the
furnace control board. (See Fig. 23.)
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8–GAS RATE (CU FT/HR)
SIZE OF TEST DIAL
SIZE OF TEST DIAL
SECONDS
FOR 1
REVOLUTION
SECONDS
FOR 1
REVOLUTION
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
1
2
5
1
2
5
Cu Ft Cu Ft Cu Ft
Cu Ft Cu Ft Cu Ft
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
360
327
300
277
257
240
225
212
200
189
180
171
164
157
150
144
138
133
129
124
120
116
113
109
106
103
100
97
720
655
600
555
514
480
450
424
400
379
360
343
327
313
300
288
277
267
257
248
240
232
225
218
212
206
200
195
189
185
180
176
172
167
164
160
157
153
150
147
1800
1636
1500
1385
1286
1200
1125
1059
1000
947
900
857
818
783
750
720
692
667
643
621
600
581
563
545
529
514
500
486
474
462
450
439
429
419
409
400
391
383
375
367
50
51
72
71
69
68
67
65
64
63
62
61
60
58
56
54
53
51
50
48
47
46
45
44
43
42
41
40
39
38
38
37
36
35
35
34
33
33
32
31
30
144
141
138
136
133
131
129
126
124
122
120
116
112
109
106
103
100
97
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
164
161
155
150
HOOK-AROUND
AMMETER
52
53
54
55
R
Y
W
G
56
57
58
59
60
62
64
66
10 TURNS
68
70
72
FROM UNIT 24-V
CONTROL TERMINALS
74
76
95
0.5 AMPS FOR THERMOSTAT
ANTICIPATOR SETTING
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
=
EXAMPLE:
78
92
80
90
A96316
82
88
84
86
Fig. 42—Amp Draw Check With Ammeter
86
84
88
82
d. Burners will re-light when furnace cools down.
90
80
2. Check draft safeguard switch.
92
78
The purpose of this control is to permit the safe shutdown of
the furnace during certain blocked vent conditions.
94
76
95
96
75
a. Verify vent pipe is cool to the touch.
92
98
74
90
100
102
104
106
108
110
112
116
120
72
b. Disconnect power to furnace and remove vent connector
from furnace vent elbow.
88
71
86
69
c. Restore power to furnace and set room thermostat above
room temperature.
84
68
82
67
d. After normal start-up, allow furnace to operate for 2
minutes, then block vent elbow in furnace 80 percent of
vent area with a piece of flat sheet metal.
80
65
78
64
76
62
75
60
e. Furnace should cycle off within 2 minutes.
73
f. Remove blockage and reconnect vent pipe to furnace vent
elbow.
g. Switch will auto-reset when it cools.
To change the blower off delay setting, move the jumper from
one set of pins on the control to the pins used for the selected
blower off delay. Factory off delay setting is 120 sec.
h. If control board locks out furnace, cycle 115 vac power to
reset control.
3. Check Pressure Switch(es)
Step 4—Check Safety Controls
This control proves operation of the draft inducer blower.
The flame sensor, gas valve, and pressure switch were all checked
in the Start-up procedure section as part of normal operation.
a. Turn off 115-v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115-v power to furnace.
1. Check Main Limit Switches
This control shuts off combustion control system and ener-
gizes air-circulating blower motor, if furnace overheats. By
using this method to check limit control, it can be established
that limit is functioning properly and will operate if there is a
restricted duct system or motor failure. If limit control does
not function during this test, cause must be determined and
corrected.
d. Set thermostat to ″call for heat″ and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter
should NOT glow and control diagnostic light flashes a
status code 32. If hot surface igniter glows when inducer
motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function properly
and correct condition.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or
sheet metal until the limit trips.
f. Turn off 115-v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and
turn on 115-v power.
c. Unblock return air to permit normal circulation.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 5—Checklist
The control system also requires an earth ground for proper
operation of the control and flame-sensing electrode.
1. Put away tools and instruments. Clean up debris.
2. Check that blower OFF-DELAY time is selected as desired.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control. (See Fig. 23.) Any shorts of the 24-v wiring during
installation, service, or maintenance will cause this fuse to blow. If
fuse replacement is required, use ONLY a 3-amp fuse. The control
LED will display status code 24 when fuse needs to be replaced.
3. Verify that blower and burner access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc-
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light-Emitting Diode) to aid in installation, servicing, and
troubleshooting. It can be viewed through the sight glass in blower
access door. The furnace control LED is either ON continuously,
rapid flashing, or a code composed of 2 digits. The first digit is the
number of short flashes, the second digit is the number of long
flashes.
tions.
6. Review User’s Guide with owner.
7. Leave literature packet near furnace.
SERVICE AND MAINTENANCE PROCEDURES
For an explanation of status codes, refer to service label located on
blower access door or Fig. 43, and the troubleshooting guide at the
end of this procedure. The furnace control will store 1 status code
for 72 hours.
The ability to properly perform maintenance on this equip-
ment requires certain knowledge, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User’s Manual. FAILURE
TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.
For Controls With a Red LED
The stored status codes WILL be erased from the control memory,
if 115- or 24-v power is interrupted.
1. To retrieve status code, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower-OFF delays must be completed.
a. Leave 115-v power to furnace turned on.
b. Remove outer access door.
→
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death, or property dam-
age.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnect-
ing. Reconnect wires correctly.
c. Look into blower access door sight glass for current LED
status. DO NOT remove blower access door or terminate
115-v power to control or status code will be lost.
d. BRIEFLY remove insulated terminal wire from the draft
safeguard switch (DSS) until LED goes out (1 to 2 sec),
then reconnect it.
2. When above items have been completed, the LED flashes
status code 4 times. Record this status code for further
troubleshooting.
- Verify proper operation after servicing.
3. Component self-test will begin. Refer to COMPONENT
TEST section for complete test sequence.
Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and dangerous
operation.
4. Check LED status.
5. Refer to the SERVICE label on the front of the blower access
door for more information.
Step 1—Introduction
Component Self-Test
GENERAL
Component Test can also be initiated by performing the following:
1. Remove outer access door.
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 4,
you must revise your orientation to component location accord-
ingly.
2. Remove blower access door.
3. Remove the wire from the ″R″ terminal of the control board.
4. Manually close blower access door switch.
ELECTRICAL CONTROLS AND WIRING
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes. Failure to follow this warning could result
in electrical shock, personal injury, or death.
There may be more than 1 electrical supply to the unit. Check
accessories and cooling unit for additional electrical supplies
The electrical ground and polarity for 115-v wiring must be
properly maintained. Refer to Fig. 24 for field wiring information
and to Fig. 39 for furnace wiring information.
5. BRIEFLY short (jumper) TEST/TWIN, 3/16-in. quick-
connect male terminal on control (behind Y terminal) to the
COM-24V terminal on furnace control. (See Fig. 23.)
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE
If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After
status code recall is completed component test will occur.
LED CODE
STATUS
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On
RED LED boards stored status codes can also be erased when power
(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds,
if unit is powered up during a call for heat (R-W closed) or R-W opens during blower
on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or
blocked vent switch (if used) is open longer than 3 minutes or 10 successive limit trips
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes,
inducer shuts off for 15 minutes before retry. Check for: - Excessive wind
- Proper vent sizing
- Defective inducer motor
- Low inducer voltage (115VAC)
- Inadequate combustion air supply
- Low inlet gas pressure (if LGPS used)
- Defective pressure switch
- Disconnected or obstructed pressure tubing
- Restricted vent
If it opens during blower on-delay period, blower will come on for the selected blower
off-delay.
occurred during high-heat. - Control will auto reset after three hours.
- Refer to #33.
33 LIMIT CIRCUIT FAULT - Indicates the limit, draft safeguard, flame rollout, or blocked vent
switch (if used) is open or the furnace is operating in high-heat only mode due to 2
successive low heat limit trips. Blower will run for 4 minutes or until open switch remakes
whichever is longer. If open longer than 3 minutes, code changes to lockout #13.
If open less than 3 minutes status code #33 continues to flash until blower shuts off.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve
-Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-
energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve
- Stuck-open gas valve
Flame rollout switch and BVSS require manual reset. Check for:
- Proper vent sizing - Loose blower wheel.
- Dirty filter or restricted duct system.
- Restricted vent
- Excessive wind
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing.
- Pressure switch stuck closed.
- Defective blower motor or capacitor. - Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch open).
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:
- Short circuit in secondary voltage (24VAC) wiring.
34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14
occurs. If flame signal lost during blower on-delay period, blower will come on for the
selected blower off-delay. Check for: - Flame sensor must not be grounded
- Oxide buildup on flame sensor (clean with fine steel wool).
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R"
thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED
will flash code and then turn ON the inducer motor. The inducer motor will run for the entire
component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards
only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15
seconds each. Gas Valve and Humidifier will not be turned on.
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).
- Gas valve defective or gas valve turned off
- Manual valve shut-off
- Defective Hot Surface Ignitor
- Low inlet gas pressure
- Control ground continuity
- Inadequate flame carryover or rough ignition
- Green/Yellow wire MUST be connected to furnace sheet metal
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open
- Flame sense circuit failure
- Software check error
Reset power to clear lockout. Replace control if status code repeats.
327596-101 REV. A
A02027
Fig. 43—Service Label
NOTE: If TEST/TWIN to COM-24V terminals are jumpered
longer than 2 sec, LED will flash rapidly, and test request will be
ignored.
Never store anything on, near, or in contact with the furnace,
such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum
cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning com-
pounds, plastic or plastic containers, gasoline, kerosene,
cigarette lighter fluid, dry cleaning fluids, or other volatile
fluids.
3. Paint thinners and other painting compounds, paper bags,
or other paper products.
6. Component Test will function as follows:
a. LED flashes a status code 4 times. Record this status code
for further troubleshooting.
b. Inducer motor starts and continues to run until step f of
component test sequence.
c. Hot surface igniter is energized for 15 sec, then de-
energized.
d. Blower operates at HEAT speed for 10 sec, then turns off.
e. Blower operates at COOL speed for 10 sec, then turns off.
f. Inducer motor turns off.
A failure to follow this warning could result in corrosion of
the heat exchanger, fire, personal injury, or death.
Items a through f above will assist in furnace troubleshooting since
all components are functionally operated except the gas valve. This
procedure is also referred to as ″Component Test Sequence.″
7. Check LED status. If no previous fault is in history, control
will flash status code 11.
Turn off the gas and electrical supplies to the unit before
performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace. A failure to
follow this warning could result in personal injury.
8. If LED status indicates proper operation, RELEASE
BLOWER ACCESS DOOR SWITCH, reattach wire to ″R″
terminal on furnace control board, replace blower access door,
and replace burner access door.
Never operate unit without a filter or with filter access door
removed. A failure to follow this warning could result in fire,
personal injury, or death.
Step 2—Care and Maintenance
For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment. Consult your local dealer about proper frequency of
maintenance and the availability of a maintenance contract.
→
Personal injury can result from sharp metal edges, etc. Be
careful when removing parts. Gloves and safety glasses
should be worn when servicing equipment
The minimum maintenance on this equipment is as follows:
1. Check and clean air filter each month or more frequently if
required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating
and cooling season. Clean as necessary.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
BLOWER MOTOR AND WHEEL
4. Inspect burner compartment before each heating season for
rust, corrosion, soot or excessive dust. If necessary, have
furnace and burner serviced by a qualified professional.
→
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes. Failure to follow this warning could result
in personal injury or death.
5. Inspect the vent pipe/vent system before each heating season
for rust, corrosion, water leakage, sagging pipes or broken
fittings. Have vent pipes/vent system serviced by a qualified
professional.
6. Inspect any accessories attached to the furnace such as a
humidifier or electronic air cleaner. Perform any service or
maintenance to the accessories as recommended in the acces-
sory instructions.
The blower wheel should not be dropped or bent as balance
will be affected.
The following steps should be performed by a qualified service
technician.
CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement may vary depending on the application.
The filter is exterior to the furnace casing.
To ensure long life and high efficiency, clean accumulated dirt and
grease from blower wheel and motor annually.
NOTE: If the filter has an airflow direction arrow, the arrow must
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
point towards the blower.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
Personal injury can result from sharp metal edges, etc. Be
careful when removing parts. Gloves and safety glasses
should be worn when servicing equipment
2. Unscrew the thumbscrew on outer door and remove outer
door.
Media cabinet filter procedures:
3. For downflow or horizontal furnaces having vent pipes within
the furnace that pass in from of the blower access door:
NOTE: Media cabinet or 1″ Filter Rack are accessories and are
not included from the factory with the standard furnace model.
a. Disconnect vent connector from furnace vent elbow.
1. Turn off electrical supply to furnace before removing filter
access door.
b. Disconnect and remove short piece of vent pipe from
within furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. Remove 2 screws from blower access door and remove blower
access door.
4. If equipped with permanent, washable 1″ filter, clean filter by
spraying cold tap water through filter in opposite direction of
airflow. Rinse filter and let dry. Oiling or coating of the filter
is not recommended. See Table 9 for size information.
5. Disconnect blower leads from furnace control. Note wire color
and location for reassembly. All other factory wires can be left
connected, but field thermostat connections may need to be
disconnected depending on their length and routing.
5. If equipped with factory-specified disposable media filter,
replace only with media filter having the same part number
and size. For expandable replacement media, refer to the
instructions included with the replacement media. If equipped
with KGAFR0301ALL external filter rack, See Table 9.
6. Remove 2 screws from control box to blower shelf.
7. Hang control box from front of furnace casing and away from
blower compartment.
8. Remove 2 screws holding blower assembly to blower deck
and slide blower assembly out of furnace.
6. Slide filter into cabinet.
9. Clean blower wheel and motor using a vacuum with soft brush
attachment. Blower wheel blades may be cleaned with a small
paint or flux brush. Do not remove or disturb balance weights
(clips) on blower wheel blades.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
10. Vacuum any loose dust from blower housing, wheel and
motor.
11. If a greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
Table 9—FILTER SIZE INFORMATION (IN.)
FILTER QUANTITY AND SIZE
Side Return Bottom Return
FURNACE
CASING WIDTH
FILTER
TYPE
NOTE: Before disassembly, mark blower motor, and blower
housing so motor and each arm is positioned at the same location
during reassembly.
14-1/2
17-1/2
(1) 16 X 25 X 1 (1) 14 X 25 X 1 Cleanable*
(1) 16 X 25 X 1 (1) 16 X 25 X 1 Cleanable*
(1) 16 X 25 X 1 (1) 20 X 25 X 1 Cleanable*
(1) 16 X 25 X 1 (1) 24 X 25 X 1 Cleanable*
21
a. Disconnect capacitor wires and ground wire attached to
blower housing.
24**
* Recommended
** Some furnaces may have 2 filters
b. Remove screws securing cutoff plate and remove cutoff
plate from housing.
c. Loosen set screw holding blower wheel on motor shaft.
d. Remove bolts holding motor to blower housing and slide
motor out of wheel.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
e. Remove blower wheel from housing.
f. Clean wheel and housing.
CLEANING HEAT EXCHANGER
The following steps should be performed by a qualified service
technician:
12. Reassemble motor and blower by reversing steps 11f, finish-
ing with 11a. Be sure to reattach ground wire to the blower
housing.
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, they should be replaced rather than trying to clean
them thoroughly. A build-up of soot and carbon indicates that a
problem exists which needs to be corrected, such as improper
adjustment of manifold pressure, insufficient or poor quality
combustion air, incorrect size or damaged manifold orifice(s),
improper gas, or a restricted heat exchanger. Action must be taken
to correct the problem.
13. Verify that blower wheel is centered in blower housing and set
screw contacts the flat portion of the motor shaft. Loosen set
screw on blower wheel and reposition if necessary.
14. Spin the blower wheel by hand to verify that the wheel does
not rub on the housing.
15. Reinstall blower assembly in furnace.
If it becomes necessary to clean the heat exchangers because of
dust or corrosion, proceed as follows:
16. Reinstall control box assembly in furnace.
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
Heating fan speed(s) MUST be adjusted to provide proper air
temperature rise as specified on the rating plate. Failure to
adjust the heating speed(s) may shorten heat exchanger life.
Recommended operation is at the midpoint of the rise range
or slightly above. Refer to ″SET TEMPERATURE RISE″
under START-UP, ADJUSTMENT, and SAFETY CHECK.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal vent
pipe, remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to
aid in reconnection of:
a. Draft safeguard switch.
b. Inducer motor.
NOTE: Refer to Table 7 for motor speed lead relocation if leads
were not identified before disconnection.
c. Pressure switch(es).
17. Reconnect blower leads to furnace control. Refer to furnace
wiring diagram, and connect thermostat leads if previously
disconnected. (See Fig. 39.)
d. Limit overtemperature switch.
e. Gas valve.
18. To check blower for proper rotation:
a. Turn on electrical supply.
f. Hot surface igniter.
g. Flame-sensing electrode
h. Flame rollout switches.
i. Remove NOx baffles on low NOx models.
Blower access door switch opens 115-v power to furnace
control. No component operation can occur. Caution must be
taken when manually closing this switch for service purposes.
Failure to follow this warning could result in electrical shock,
personal injury, or death.
6. Remove screws that fasten the collector box assembly to the
cell panel. Be careful not to damage the collector box. Inducer
assembly and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the 4 screws that attach the burner assembly to the
cell panel. The gas valve and individual burners need not be
removed from support assembly.
b. Manually close blower access door switch.
NOTE: If thermostat terminals are jumpered at the time blower
access door switch is closed, blower will run for 90 sec before
beginning a heating or cooling cycle.
NOTE: Be very careful when removing burner assembly to avoid
breaking igniter. See Fig. 44 and 45 for correct igniter location.
c. Perform component self-test as shown at the bottom of the
SERVICE label, located on the front of blower access door.
9/32”
d. Verify blower is rotating in the correct direction.
19. If furnace is operating properly, RELEASE BLOWER AC-
CESS DOOR SWITCH. Replace blower access door and
remove any jumpers or reconnect any disconnected thermostat
leads.
11/32”
20. Downflow or horizontal furnaces with vent pipe through
furnace only:
a. Install and connect short piece of vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
21. Reinstall casing door.
22. Turn on gas supply and cycle furnace through one complete
heating and cooling cycle. Verify the unit temperature rise as
shown in Adjustments Section. Adjust temperature rise as
shown in Adjustments Section. If outdoor temperature is
below 70° F, turn off circuit breaker to outdoor unit before
running furnace in the cooling cycle. Turn outdoor circuit
breaker on after completing cooling cycle.
A02150
Fig. 44—Position of Igniter to Burner
33
Download from Www.Somanuals.com. All Manuals Search And Download.
7/8”
A02151
A91252
Fig. 45—Position of Igniter to Burner
Fig. 46—Cleaning Heat Exchanger Cell
9. Using field-provided 25-caliber rifle cleaning brush, 1/4″
diameter steel spring cable, 36 in. long, a variable speed,
reversible electric drill, and vacuum cleaner, clean cells as
follows:
13. Reconnect wires to the following components (Use connection
diagram on wiring label, if wires were not marked for
reconnection locations.):
a. Remove metal screw fitting from wire brush to allow
insertion into cable.
a. Draft safeguard switch.
b. Inducer motor.
b. Insert the twisted wire end of brush into end of spring
cable, and crimp tight with crimping tool or crimp by
striking with ball-peen hammer. TIGHTNESS IS VERY
IMPORTANT.
c. Pressure switch(es).
d. Limit overtemperature switch.
e. Gas valve.
NOTE: The materials needed in item 9 can usually be purchased
at local hardware stores.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.
i. Install NOx baffles (if removed).
14. Reinstall internal vent pipe, if applicable.
(1.) Attach variable-speed, reversible drill to the end of
spring cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of cell
and slowly rotate with drill. DO NOT force cable.
Gradually insert cable into upper pass of cell. (See Fig.
46.)
15. Reinstall vent connector on furnace vent elbow. Securely
fasten vent connector to vent elbow with 2 field-supplied,
corrosion-resistant, sheet metal screws located 180° apart.
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.
16. Replace blower access door only.
17. Set thermostat above room temperature and check furnace for
proper operation.
(4.) Insert brush end of cable in burner inlet opening of
cell, and proceed to clean 2 lower passes of cell in
same manner as upper pass.
18. Verify blower airflow and speed changes between heating and
cooling.
(5.) Repeat foregoing procedures until each cell in furnace
has been cleaned.
19. Check for gas leaks.
(6.) Using vacuum cleaner, remove residue from each cell.
Never use a match or other open flame to check for gas leaks.
Use a soap-and-water solution. A failure to follow this
warning could result in fire, personal injury, or death.
(7.) Using vacuum cleaner with soft brush attachment,
clean burner assembly.
(8.) Clean flame sensor with fine steel wool.
20. Replace outer access door.
(9.) Reinstall burner assembly. Center burners in cell
openings.
Step 3—Sequence of Operation
10. Remove old sealant from cell panel and inducer backing plate
flange.
→ NOTE: Furnace control must be grounded for proper operation or
control will lock out. Control is grounded through green/yellow
wire routed to gas valve and manifold bracket screw.
11. Spray releasing agent on the heat exchanger cell panel where
collector box assembly contacts cell panel.
Using the schematic diagram in Fig. 39, follow the sequence of
operation through the different modes. Read and follow the wiring
diagram very carefully.
NOTE: A releasing agent such as cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting
installation. DO NOT substitute any other type of RTV sealant.
G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.
NOTE: If a power interruption occurs during a call for heat (W),
the control will start a 90-second blower-only ON period two
seconds after power is restored, if the thermostat is still calling for
gas heating. The red LED light will flash code 12 during the
90-second period, after which the LED will be ON continuous, as
long as no faults are detected. After the 90-second period, the
furnace will respond to the thermostat normally.
12. Apply new sealant to flange of inducer assembly and attach to
cell panel using existing screws, making sure all screws are
secure.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot-surface igniter HSI, and gas valve GV.
circuit starts the outdoor unit, and the R-to-G and Y circuits
start the furnace blower motor BLWM on COOL speed.
The electronic air cleaner terminal EAC-1 is energized with
115 vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuits are
opened. The outdoor unit will stop, and the furnace blower
motor BLWM will continue operating on the COOL speed for
an additional 90 seconds. Cut jumper J2 to reduce the cooling
off-delay to 5 seconds. (See Fig. 23.)
1. Heating
(See Fig. 24 for thermostat connections.)
The wall thermostat ″calls for heat″, closing the R to W
circuit. The furnace control performs a self-check, verifies the
pressure switch contacts PRS is open, and starts the inducer
motor IDM.
3. Continuous Blower Mode
When the R-to-G circuit is closed by the thermostat, the
blower motor BLWM will operate on continuous-blower
speed (same as HEAT speed). Terminal EAC-1 is energized as
long as the blower motor BLWM is energized.
During a call for heat, the blower BLWM will stop during
igniter warm-up (17 seconds), ignition, and blower-ON delay
(25 seconds), allowing the furnace heat exchangers to heat up
more quickly, then restarts at the end of the blower-ON delay
period at HEAT speed.
a. Inducer Prepurge Period- As the inducer motor IDM
comes up to speed, the pressure switch contacts PRS close,
24 vac power is supplied for a field installed humidifier at
the HUM terminal and the control begins a 15-second
prepurge period.
b. Igniter Warm-Up- At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second
igniter warm-up period.
c. Trial-for-Ignition Sequence- When the igniter warm-up
period is completed the main gas valve relay contacts GVR
close to energize the gas valve GV, the gas valve opens.
The gas valve GV permits gas flow to the burners where it
is ignited. After 5 seconds, the igniter HSI is de-energized
and a 2-second Flame-Proving period begins.
When the thermostat ″calls for cooling″, the blower motor
BLWM will operate at COOL speed. When the thermostat is
satisfied, the blower motor BLWM will operate an additional
90 seconds on COOL speed before reverting back to
continuous-blower speed.
When the R-to-G circuit is opened, the blower motor BLWM
will continue operating for an additional 5 seconds, if no other
function requires blower motor BLWM operation.
d. Flame-Proving- When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control
CPU begins the blower-ON delay period and continues to
hold the gas valve GV open. If the burner flame is not
proved within two seconds, the control CPU will close the
gas valve GV, and the control CPU will repeat the ignition
sequence for up to three more Trials-For-Ignition before
going to Ignition-Lockout. Lockout will be reset auto-
matically after three hours, by momentarily interrupting
115 vac power to the furnace, or by interrupting 24 vac
power at SEC1 or SEC2 to the furnace control CPU (not at
W, G, R, etc.)
4. Heat Pump
When installed with a heat pump, the furnace control auto-
matically changes the timing sequence to avoid long blower
off times during demand defrost cycles. When the R-to-W-
and-Y or R-to-W-and-Y-and-G circuits are energized the
furnace control CPU will continue to turn on the blower motor
BLWM at HEAT speed, and begin a heating cycle. The
blower motor BLWM will remain on until the end of the
prepurge period, then shut off for 24 seconds then come back
on at HEAT speed. When the W input signal disappears, the
furnace control begins a normal inducer post-purge period and
the blower switches to COOL speed after a 3 second delay. If
the R-to-W-and-Y-and-G signals disappear at the same time,
the blower motor BLWM will remain on for the selected
blower-OFF delay period. If the R-to-W-and-Y signals disap-
pear, leaving the G signal, the blower motor BLWM will
continue running the blower motor BLWM at HEAT speed
after the selected blower-OFF delay period is completed.
If flame is proved when flame should not be present, the
furnace control CPU will lock out of Gas-Heating mode
and operate the inducer motor IDM until flame is no longer
proved.
e. Blower-On Delay- If the burner flame is proven, the
blower motor is energized on HEAT speed 25 seconds after
the gas valve GV is energized.
Simultaneously, the electronic air cleaner terminal EAC-1
is energized and remains energized as long as the blower
motor BLWM is energized.
Step 4—Wiring Diagrams
f. Blower-Off Delay- When the thermostat is satisfied, the
R-to-W circuit is opened, de-energizing the gas valve GV,
stopping gas flow to the burners, and de-energizing the
humidifier terminal HUM. The inducer motor IDM will
remain energized for a 5-second post-purge period. The
blower motor BLWM and air cleaner terminal EAC-1 will
remain energized for 90, 120, 150, or 180 seconds (depend-
ing on the blower-OFF delay selection). The furnace
control CPU is factory-set for a 120-second blower-OFF
delay.
Refer to Fig. 24 and 39 for wiring diagrams.
Step 5—Troubleshooting
Refer to the service label. (See Fig. 43—Service Label.)
The Troubleshooting Guide can be a useful tool in isolating
furnace operation problems. Beginning with the word “Start,”
answer each question and follow the appropriate arrow to the next
item.
The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
2. Cooling Mode
(See Fig. 24 for thermostat connections)
The thermostat closes the R-to-G-and-Y circuits. The R-to-Y
35
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 10—Orifice Size* and Manifold Pressure For Gas Input Rate
(Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
SPECIFIC GRAVITY OF NATURAL GAS
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
Manifold
0.60
0.62
0.64
Manifold
Orifice
No.
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Pressure
Pressure
900
925
42
42
43
43
43
43
44
44
44
3.5
3.3
3.8
3.6
3.5
3.3
3.6
3.4
3.3
42
42
42
43
43
43
43
44
44
3.6
3.4
3.3
3.8
3.6
3.4
3.2
3.5
3.4
42
42
42
42
43
43
43
43
44
3.7
3.5
3.4
3.2
3.7
3.5
3.4
3.2
3.5
41
42
42
42
43
43
43
43
43
3.5
3.7
3.5
3.3
3.8
3.6
3.5
3.3
3.2
950
0
to
2000
975
1000
1025
1050
1075
1100
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
U.S.A.
800
825
850
875
900
925
950
975
1000
42
42
43
43
43
43
43
43
43
3.4
3.2
3.7
3.5
3.3
3.1
2.9
2.8
2.6
42
42
43
43
43
43
43
43
43
3.5
3.3
3.8
3.6
3.4
3.2
3.0
2.9
2.7
42
42
42
43
43
43
43
43
43
3.6
3.4
3.2
3.7
3.5
3.3
3.1
3.0
2.8
42
42
42
43
43
43
43
43
43
3.7
3.5
3.3
3.8
3.6
3.4
3.2
3.1
2.9
Altitudes
2001
to
3000
or
Canada
Altitudes
2000
to
4500
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
775
800
825
850
875
900
925
950
42
43
43
43
43
43
43
43
3.2
3.6
3.4
3.2
3.0
2.9
2.7
2.6
42
43
43
43
43
43
43
43
3.3
3.8
3.5
3.3
3.1
3.0
2.8
2.7
42
42
43
43
43
43
43
43
3.4
3.2
3.7
3.4
3.3
3.1
2.9
2.8
42
42
43
43
43
43
43
43
3.5
3.3
3.8
3.6
3.4
3.2
3.0
2.8
3001
to
4000
U.S.A. Only
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
750
775
800
825
850
875
900
925
43
43
43
43
43
43
43
43
3.6
3.4
3.2
3.0
2.8
2.7
2.5
2.4
43
43
43
43
43
43
43
43
3.8
3.5
3.3
3.1
2.9
2.8
2.6
2.5
42
43
43
43
43
43
43
43
3.2
3.6
3.4
3.2
3.0
2.9
2.7
2.6
42
43
43
43
43
43
43
43
3.3
3.8
3.5
3.3
3.1
2.9
2.8
2.6
4001
to
5000
* Orifice numbers 43 are factory installed
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)
(Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
0.58
0.60
0.62
0.64
Manifold
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Pressure
725
750
775
800
825
850
875
900
43
43
43
43
43
43
43
43
3.4
3.2
3.0
2.8
2.6
2.5
2.3
2.2
43
43
43
43
43
43
43
43
3.5
3.3
3.1
2.9
2.7
2.5
2.4
2.3
43
43
43
43
43
43
43
43
3.6
3.4
3.2
3.0
2.8
2.6
2.5
2.3
43
43
43
43
43
43
43
43
3.7
3.5
3.3
3.1
2.9
2.7
2.6
2.4
5001
to
6000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
675
700
725
750
775
800
825
850
43
43
43
43
43
43
43
43
3.4
3.1
2.9
2.7
2.6
2.4
2.3
2.1
43
43
43
43
43
43
43
43
3.5
3.3
3.0
2.8
2.7
2.5
2.3
2.2
43
43
43
43
43
43
43
43
3.6
3.4
3.1
2.9
2.7
2.6
2.4
2.3
43
43
43
43
43
43
43
43
3.7
3.5
3.2
3.0
2.8
2.7
2.5
2.4
6001
to
7000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
650
675
700
725
750
775
800
825
43
43
43
43
43
43
43
48
3.1
2.9
2.7
2.5
2.4
2.2
2.1
3.7
43
43
43
43
43
43
43
43
3.2
3.0
2.8
2.6
2.4
2.3
2.1
2.0
43
43
43
43
43
43
43
43
3.4
3.1
2.9
2.7
2.5
2.4
2.2
2.1
43
43
43
43
43
43
43
43
3.5
3.2
3.0
2.8
2.6
2.4
2.3
2.2
7001
to
8000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
625
650
675
700
725
750
775
43
43
43
43
43
43
48
2.9
2.7
2.5
2.3
2.2
2.0
3.6
43
43
43
43
43
43
48
3.0
43
43
43
43
43
43
43
3.1
43
43
43
43
43
43
43
3.2
3.0
2.8
2.6
2.4
2.2
2.1
2.8
2.9
2.6
2.7
8001
to
9000
2.4
2.5
2.2
2.3
2.1
2.2
3.7
2.0
* Orifice numbers 43 are factory installed
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)
(Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
0.58
0.60
0.62
0.64
Manifold
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Pressure
600
625
650
675
700
725
43
43
43
43
48
48
2.7
2.5
2.3
2.1
3.7
3.5
43
43
43
43
43
48
2.8
2.6
2.4
2.2
2.0
3.6
43
43
43
43
43
48
2.9
2.6
2.4
2.3
2.1
3.7
43
43
43
43
43
43
3.0
2.7
2.5
2.3
2.2
2.0
9001
to
10,000
* Orifice numbers 43 are factory installed
38
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 11—Orifice Size* and Manifold Pressure For Gas Input Rate
(Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
SPECIFIC GRAVITY OF NATURAL GAS
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
Manifold
0.60
0.62
0.64
Manifold
Orifice
No.
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Pressure
Pressure
900
925
42
43
43
43
44
44
44
45
46
3.2
3.7
3.5
3.3
3.6
3.4
3.3
3.8
3.8
42
43
43
43
43
44
44
44
45
3.3
3.8
3.6
3.4
3.3
3.6
3.4
3.2
3.7
42
42
43
43
43
43
44
44
44
3.4
3.2
3.7
3.5
3.4
3.2
3.5
3.3
3.2
42
42
43
43
43
43
43
44
44
3.5
3.3
3.8
3.7
3.5
3.3
3.2
3.4
3.3
950
0
to
2000
975
1000
1025
1050
1075
1100
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
U.S.A.
Altitudes
2001
to
3000
or
Canada
Altitudes
2000
to
800
825
850
875
900
925
950
975
1000
43
43
43
43
43
43
43
43
43
3.8
3.5
3.3
3.2
3.0
2.8
2.7
2.5
2.4
42
43
43
43
43
43
43
43
43
3.2
3.7
3.5
3.3
3.1
2.9
2.8
2.6
2.5
42
43
43
43
43
43
43
43
43
3.3
3.8
3.6
3.4
3.2
3.0
2.9
2.7
2.6
42
42
43
43
43
43
43
43
43
3.4
3.2
3.7
3.5
3.3
3.1
2.9
2.8
2.7
4500
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
775
800
825
850
875
900
925
950
43
43
43
43
43
43
43
43
3.5
3.3
3.1
2.9
2.8
2.6
2.5
2.4
43
43
43
43
43
43
43
43
3.7
3.4
3.2
3.0
2.9
2.7
2.6
2.4
43
43
43
43
43
43
43
43
3.8
3.5
3.3
3.1
3.0
2.8
2.7
2.5
42
43
43
43
43
43
43
43
3.2
3.7
3.4
3.2
3.1
2.9
2.7
2.6
3001
to
4000
U.S.A. Only
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
750
775
800
825
850
875
900
925
43
43
43
43
43
43
43
43
3.3
3.1
2.9
2.7
2.6
2.4
2.3
2.2
43
43
43
43
43
43
43
43
3.4
3.2
3.0
2.8
2.7
2.5
2.4
2.2
43
43
43
43
43
43
43
43
3.5
3.3
3.1
2.9
2.8
2.6
2.5
2.3
43
43
43
43
43
43
43
43
3.6
3.4
3.2
3.0
2.8
2.7
2.5
2.4
4001
to
5000
* Orifice numbers 43 are factory installed
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)
(Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
0.58
0.60
0.62
0.64
Manifold
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Pressure
725
750
775
800
825
850
875
900
43
43
43
43
43
43
43
43
3.1
2.9
2.7
2.5
2.4
2.2
2.1
2.0
43
43
43
43
43
43
43
43
3.2
3.0
2.8
2.6
2.5
2.3
2.2
2.1
43
43
43
43
43
43
43
43
3.3
3.1
2.9
2.7
2.5
2.4
2.3
2.1
43
43
43
43
43
43
43
43
3.4
3.2
3.0
2.8
2.6
2.5
2.3
2.2
5001
to
6000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
675
700
725
750
775
800
825
850
43
43
43
43
43
43
43
48
3.1
2.9
2.7
2.5
2.3
2.2
2.1
3.7
43
43
43
43
43
43
43
43
3.2
3.0
2.8
2.6
2.4
2.3
2.1
2.0
43
43
43
43
43
43
43
43
3.3
3.1
2.9
2.7
2.5
2.3
2.2
2.1
43
43
43
43
43
43
43
43
3.4
3.2
2.9
2.8
2.6
2.4
2.3
2.1
6001
to
7000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
650
675
700
725
750
775
800
825
43
43
43
43
43
43
48
48
2.9
2.7
2.5
2.3
2.1
2.0
3.6
3.3
43
43
43
43
43
43
48
48
3.0
2.7
2.6
2.4
2.2
2.1
3.7
3.5
43
43
43
43
43
43
43
48
3.1
2.8
2.6
2.5
2.3
2.2
2.0
3.6
43
43
43
43
43
43
43
48
3.2
2.9
2.7
2.5
2.4
2.2
2.1
3.7
7001
to
8000
SPECIFIC GRAVITY OF NATURAL GAS
0.60 0.62
Manifold Manifold
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
0.58
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Pressure
Pressure
625
650
675
700
725
750
775
43
43
43
43
48
48
49
2.7
2.5
2.3
2.1
3.7
3.5
3.8
43
43
43
43
43
48
48
2.7
2.5
2.4
2.2
2.0
3.6
3.4
43
43
43
43
43
48
48
2.8
2.6
2.4
2.3
2.1
3.7
3.5
43
43
43
43
43
43
48
2.9
2.7
2.5
2.3
2.2
2.0
3.6
8001
to
9000
* Orifice numbers 43 are factory installed
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)
(Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
SPECIFIC GRAVITY OF NATURAL GAS
AVG GAS
ALTITUDE
RANGE
(FT)
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
0.58
0.60
0.62
0.64
Manifold
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Pressure
600
625
650
675
700
725
43
43
43
48
48
49
2.4
2.3
2.1
3.6
3.4
3.7
43
43
43
48
48
49
2.5
2.3
2.2
3.8
3.5
3.8
43
43
43
43
48
48
2.6
2.4
2.2
2.1
3.6
3.4
43
43
43
43
48
48
2.7
2.5
2.3
2.1
3.7
3.5
9001
to
10,000
* Orifice numbers 43 are factory installed
41
Download from Www.Somanuals.com. All Manuals Search And Download.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 2002 Carrier Corporation
58st11si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
Tab 6a 8a
1
4
PC 101
Catalog No. See Cover
Printed in U.S.A.
Form 58ST-11SI
Pg 44
12-02
Replaces: 58ST-2SI
Download from Www.Somanuals.com. All Manuals Search And Download.
|