Form No. 6700
(Rev. 5/07)
Bryan “Flexible Water Tube”
HE-CLM Series Water Boilers
900,000 to 3,000,000 BTUH
Forced draft gas fired
Quality Construction Features
A. Heavy steel boiler frame, built and stamped in accordance
with the ASME Boiler Code, Section IV.
B. Large volume water leg downcomers promote rapid internal
circulation, temperature equalization and efficient heat transfer.
C. Bryanbentwatertubesareflexible,individuallyreplaceablewith-
out welding or rolling. Never more than two tube configurations.
D. Boiler tube and furnace area access panel: heavy gauge
steelcasingwith2"hightemperatureceramic fiberandinsulation,
bolted and tightly sealed to boiler frame.
E. Jacket access panels make the interior of the boiler easily
accessible for service and inspection.
F. Steel boiler jacket with 16 gauge rust-resistant zinc coating
andattractiveenamelfinish, insulatedwith1½"fiberglasstoinsure
exceptionally cool outer surface.
G. Minimum sized flue vent.
H. Forced draft, flame retention head type burner. Efficient
combustion and quiet operation.
I. All controls, gauges, relief valve(s) are factory installed and
wired and easily accessible for servicing.
J. Electrical box: all controls installed and connected to terminal
strip.
K. Water side interior accessible for cleanout and inspection,
front and rear openings, upper and lower drums.
Model HE-CLM300-W-FDG
L. Steel plate boiler base with lightweight, high temperature
insulating firebrick combustion chamber, designed for maximum
combustion efficiency.
Guaranteed 85%
efficiency
• With HE-CLM Series Boilers,
Bryan HE-CLM Series Boiler Specifications
you get a guaranteed 85%
OUTPUT @ 85% EFFICIENCY(1) HTG.SURFACE APPROX. SHIP
MBH (KW)
combustion efficiency result-
ing from a uniquely designed
integrated extended surface
heat extractor.
BOILER
MODEL
INPUT
MBH (KW)
HP (KW)
23 (224)
30 (299)
38 (374)
46 (448)
53 (523)
61 (598)
69 (672)
76 (747)
SQ.FT.(M2)
171 (15.9)
227 (21.1)
282 (26.2)
338 (31.4)
394 (36.6)
451 (41.9)
506 (47.0)
564 (52.4)
LBS. (KG)
HE-CLM90
HE-CLM120
HE-CLM150
HE-CLM180
HE-CLM210
HE-CLM240
HE-CLM270
HE-CLM300
900 (264)
1,200 (352)
1,500 (440)
1,800 (527)
2,100 (615)
2,400 (703)
2,700 (791)
3,000 (879)
765 (224)
2,110 (957)
1,020 (299)
1,275 (374)
1,530 (448)
1,785 (523)
2,040 (598)
2,295 (672)
2,550 (747)
2,400 (1,089)
2,860 (1,297)
3,200 (1,452)
3,740 (1,697)
4,200 (1,905)
4,740 (2,150)
5,175 (2,348)
• What's more, HE-CLM Boilers
offer high operating
efficiency—at all normal
operation temperatures—
without the complications
of condensation concerns.
NOTES : (1) Output and horsepower based on an average natural gas combustion efficiency of 85%.
®
BRYAN BOILERS
Originators of the “Flexible Water Tube” design