Installation
Instructions
S19-690LHS, S19-690H
10-Gallon Tank with
Eye Wash and Optional
Heater Jacket
S19-690LHS
Table of Contents
Pre-Installation Information . . . . . . . . . . . . . . .2
Installation Instructions . . . . . . . . . . . . . . . . .3–4
Maintenance Instructions . . . . . . . . . . . . . . . . .5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .5
Assembly of Components . . . . . . . . . . . . . . . .6
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
IMPORTANT
This equipment should be inspected,
tested, and recorded weekly to maintain
proper operation.
Read this installation manual thoroughly
before beginning installation.
S19-690H
This installation manual should be filed
by the owner’s maintenance department.
P.O. Box 309, Menomonee Falls, WI 53052-0309
TEL. 1-800-BRADLEY FAX 262-251-5817
215-084 Rev. L; EN 02-586
Page 1 of 6
Download from Www.Somanuals.com. All Manuals Search And Download.
10-Gallon Tank with Eye Wash and Optional Heater Jacket
S19-690LHS, S19-690H
Installation Instructions
Installation Instructions
Step 1: Install eye wash
1. Attach the eye wash to the tank
outlet with pipe sealant (supplied
by installer) (see Figure 1).
Back View
IMPORTANT: When attaching the
eye wash to the tank outlet, hold
the adapter (Item 3) with a
wrench to prevent stripping.
Failure to do so may damage
the seal and cause leakage.
2. Attach the pressure gauge to the
adapter on the pressure side of the
tank with pipe sealant (supplied
by installer) as shown in Figure
2 on page 6.
3. FOR OPTIONAL HEATER
JACKET:
• Secure the pipe insulation and
yellow jacket to the eye wash
assembly.
• Wrap the heater belt around
the tank at a height of four
inches from the bottom of the
tank and fasten securely.
• Connect the heat trace cable to
the junction box.
• Slide the jacket up the side of
the tank and pull the draw-
string at the top of the jacket.
Figure 1
• Place the junction box in the
pocket on the inside of the
jacket.
Bradley Corporation • 215-084 Rev. L; EN 02-586
3
Download from Www.Somanuals.com. All Manuals Search And Download.
10-Gallon Tank with Eye Wash and Optional Heater Jacket
S19-690LHS, S19-690H
Installation Instructions
Installation Instructions continued . . .
Step 2: Fill tank and pressurize
1. If the tank is pressurized, relieve the tank pressure by pulling up on the relief tank tab in the
center of the cover until the pressure gauge reads “0.”
IMPORTANT: DO NOT open the cover until the pressure gauge reads “0”!
2. Open the tank by pulling up on the wire handle located on top of the Quicklock cover. Push
down, rotate and remove. Fill the container with 7 gallons of potable water. Replace the cover.
3. Pressurize the tank to 95 PSI by applying air pressure to the valve located beneath the pressure gauge.
NOTE: Relief valve is designed to automatically vent at 100-130 PSI to prevent the tank from over-
pressurizing.
Step 3: Flush tank
1. Discharge the water through the eye wash for at least five minutes to flush the system.
2. Refill the tank and pressurize as explained in Step 2 outlined above.
NOTE: Let unit stand for one hour. If there is a noticeable pressure drop, repressurize back to 95 PSI
and let stand for one hour. If problems persist, consult the Troubleshooting guide found on page 5.
NOTE: This unit will provide at least 15 minutes of cleansing action. Take the injured person immediately
to a normal emergency station for additional cleansing and treatment.
3. FOR OPTIONAL HEATER JACKET: Plug the jacket’s electrical cord into an electric outlet.
4
Bradley Corporation • 215-084 Rev. L; EN 02-586
Download from Www.Somanuals.com. All Manuals Search And Download.
10-Gallon Tank with Eye Wash and Optional Heater Jacket
S19-690LHS, S19-690H
Installation Instructions
Maintenance Instructions
WARNING: Water preservatives protect potable water from bacteria, fungi and algae
growth for up to four months. If a water preservative is not used with this eye wash, it is
recommended that the tank be cleaned weekly or as often as needed. Infection, loss of
vision or other serious injury may result from misuse of this eye wash. DO NOT use
expired, cloudy, colored or contaminated solution. DO NOT open preservative bottle if
safety seal is broken. DO NOT save unused solution.
Step 1: Inspect eye wash unit
1. Visually inspect the pressure gauge weekly to ensure the unit is maintaining the proper pressure.
If the unit is not working properly, remove it from the hazard area immediately and refer to the
troubleshooting instructions. For further assistance, contact the Bradley Corporation.
Step 2: Clean eye wash unit
When using potable water only:
1. Empty the tank any time from once per week to once per month, depending on the quality of
your water supply. The manufacturer is not responsible for variations in the water supply.
2. Clean the inside of the tank using warm water and mild soap. Rinse the tank thoroughly with
warm water.
3. Refill the eye wash tank following the procedure outlined in Step 2 found on page 4.
When using potable water and water preservative (recommended):
1. Empty the tank at least once every 120 days.
2. Clean the inside of the tank using warm water and mild soap. Rinse the tank thoroughly with
warm water.
3. Refill the eye wash tank with potable water and the contents of an 8-ounce bottle of water
preservative (refer to the procedure outlined in Step 2 found on page 4).
• To order potable water preservative, contact your Bradley representative or local distributor
and ask for part number S19-865.
Troubleshooting
1. If pressure relief valve relieves prior to the required pressure, do the following (when in the
unpressurized condition):
• Tighten the valve completely into the cap by turning the gray hex head portion of the pressure
relief valve clockwise. Do not use a wrench.
• Pull up on the relief valve ring and ensure that the ring is not preventing the valve from closing
completely. Push on the center pin of the relief valve to ensure that it is completely closed.
Repressurize tank to required pressure. This may have to be done several times to get the valve
to seat completely.
2. If the pressurized tank loses pressure over time, check the connections with diluted liquid dish
soap or children’s bubbles to identify the leak location. Tighten the connection slightly and test
again.
Bradley Corporation • 215-084 Rev. L; EN 02-586
5
Download from Www.Somanuals.com. All Manuals Search And Download.
10-Gallon Tank with Eye Wash and Optional Heater Jacket
S19-690LHS, S19-690H
Installation Instructions
Assembly of Components
Figure 2
Parts List
Item Part No.
Qty
1
Description
Item Part No.
Qty
2
Description
1
2
3
4
5
6
7
8
S27-252
153-429
153-217
169-786
S27-161
204-095
169-043
S05-116
TANK – 10 GALLON
ADAPTER
9
107-371
269-1671
261-007B
S83-167
230-022
269-1669
204-421
114-051
TETHERED DUST COVER
PIPE WRAP
1
10
11
1
1
ADAPTER
1
HEATER BELT, 4 "
JUNCTION BOX ASSEMBLY
POWER SUPPLY CORD
HEATER JACKET
1
PRESSURE GAUGE
TANK VALVE ASSY.
OPERATING INSTR. LABEL
PIPE PLUG, 1-3/8"
EYE WASH VALVE ASSY.
12
13
14
15*
16*
1
1
1
1
1
1
1
EMERGENCY TAG
SAFETY SIGN
1
1
* Not Shown
6
Bradley Corporation • 215-084 Rev. L; EN 02-586