Bradford White Corp Water Heater CN User Manual

Bradford White  
PDX Series  
Powered Direct Vent Gas Water Heaters  
SERVICE  
MANUAL  
Troubleshooting Guide  
and Instructions for Service  
(To be performed ONLY by qualified service providers)  
For Bradford White  
PDX Series Models:  
PDX250T6*F(BN,CX)  
PDX265T6*F(BN,CX)  
PDX275T6*F(BN,CX)  
PDX50S60F(B,C)*(N,X)  
PDX65S65F(B,C)*(N,X)  
PDX75S70F(B,C)*(N,X)  
(*) Denotes Warranty Years  
Manual 46925A  
Save this manual for future reference  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX Series  
CAUTION  
Incorrect operation of this  
appliance may create a hazard to  
life and property and will nullify the  
warranty.  
WARNING: If the information in these  
instructions is not followed exactly, a fire or  
explosion may result causing property damage,  
personal injury, or death.  
FOR YOUR SAFETY  
DANGER  
Do not store or use gasoline or other  
flammable, combustible, or corrosive vapors  
and liquids in the vicinity of this or any other  
appliance.  
Do not store or use gasoline or  
other flammable, combustible, or  
corrosive vapors and liquids in the  
vicinity of this or any other  
appliance.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
IMPORTANT  
Do not touch any electrical switch; do not use any  
phone in your building.  
Before proceeding, please inspect the  
water heater and its components for  
possible damage. DO NOT install any  
water heater with damaged  
Immediately call your gas supplier from a neighbor's  
phone. Follow the gas supplier's instructions.  
If you cannot reach your gas supplier, call the fire  
department.  
components. If damage is evident  
then please contact the supplier where  
the water heater was purchased or the  
manufacturer listed on the rating plate  
for replacement parts.  
Installation and service must be performed by a qualified  
installer, service agency or the gas supplier.  
WARNING  
WARNING  
Water heaters are heat producing appliances. To  
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE  
IF YOU ARE NOT CERTAIN OF THE FOLLOWING:  
Liquefied petroleum gases/propane gas and  
natural gas have an odorant added by the gas  
avoid damage or injury, do not store materials  
against the water heater or vent-air intake system.  
Use proper care to avoid unnecessary contact  
(especially by children) with the water heater and  
vent-air intake components. UNDER NO  
supplier that aids in the detection of the gas.  
Most people recognize this odor as a “sulfur” or  
“rotten egg” smell.  
CIRCUMSTANCES MUST FLAMMABLE  
MATERIALS, SUCH AS GASOLINE OR PAINT  
THINNER BE USED OR STORED IN THE VICINITY  
OF THIS WATER HEATER, VENT-AIR INTAKE  
SYSTEM OR IN ANY LOCATION FROM WHICH  
FUMES COULD REACH THE WATER HEATER  
OR VENT-AIR INTAKE SYSTEM.  
Other conditions, such as “odorant fade” can  
cause the odorant to diminish in intensity, or  
”fade”, and not be as readily detectable.  
If you have a diminished sense of smell, or are in  
any way unsure of the presence of gas,  
immediately contact your gas supplier from a  
neighbor's telephone.  
Gas detectors are available. Contact your gas  
supplier, or plumbing professional, for more  
information.  
CAUTION  
If sweat fittings are to be used DO NOT apply heat to  
the nipples on top of the water heater. Sweat the  
tubing to the adapter before fitting the adapter to the  
water connections. It is imperative that heat is not  
applied to the nipples containing a plastic liner.  
WARNING  
FAILURE TO INSTALL AND MAINTAIN A NEW,  
LISTED 3/4” X 3/4” TEMPERATURE AND PRESSURE  
RELIEF VALVE WILL RELEASE THE  
MANUFACTURER FROM ANY CLAIM THAT MIGHT  
RESULT FROM EXCESSIVE TEMPERATURE AND  
PRESSURES.  
WARNING  
Hydrogen gas can be produced in an operating  
water heater that has not had water drawn from the  
tank for a long period of time (generally two weeks or  
more). Hydrogen gas is extremely flammable. To  
prevent the possibility of injury under these  
conditions, we recommend the hot water faucet to be  
open for several minutes at the kitchen sink before  
you use any electrical appliance which is connected  
to the hot water system. If hydrogen is present,  
there will be an unusual sound such as air escaping  
through the pipes as hot water begins to flow. Do  
not smoke or have open flame near the faucet at the  
time it is open.  
CAUTION  
Turn off or disconnect the electrical power supply to the  
water heater before servicing. Label all wires prior to  
disconnection when servicing controls. Wiring errors  
can cause improper and dangerous operation. Verify  
proper operation after servicing.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX Series  
Introduction  
The new Bradford White PDX2 and PDX water heaters are designed to provide reliable  
performance with enhanced standard features. New design features include reliable spark to  
pilot ignition system, enhanced diagnostics, simplified servicing, significantly quieter  
operation, additional vent lengths and certified FVIR technology.  
Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes  
reliable and consistent pilot and main burner ignitions to provide hot water on demand.  
Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease  
of troubleshooting by providing simple diagnostic codes to pinpoint an installation or  
component performance issue.  
New Powerful Blower - will eliminate problems with difficult venting situations.  
Quieter and Cooler Blower Operation - blower noise is significantly reduced for both  
interior and exterior environments. Cooler operation increases blower life by reducing bearing  
wear and noise.  
Rugged Wiring Connections - receptacle type connections promote error free wiring.  
Increased Vent Lengths - increased venting performance is achieved while maintaining  
Energy Factor & FHSR performance.  
The PDX2 and PDX water heaters use a combustion system were flue gases are combined with  
dilution air to reduce the flue gas temperature in the blower, combustion air and dilution air are  
drawn from outside the building. The diluted flue gases are evacuated to the exterior through  
low temperature vent materials. The gas control maintains water temperature, ignition  
sequence and regulates gas flow. A safety circuit consisting of a pressure switch and blower  
temperature switch verifies proper conditions exist for safe and reliable operation. If a situation  
outside of normal operating parameters exists, the gas control diagnostic LED will flash a code  
to positively identify an operational issue.  
This service manual is designed to facilitate problem diagnosis and enhance service efficiency.  
To further promote quicker service times the new gas valve can be removed and replaced  
without draining the water heater. A special tool is required and will be provided with each gas  
valve kit shipped from our Service Parts department.  
Please read the service manual completely before attempting service on this new series of  
power vent models.  
How the Safety System Works  
During normal operation, air for combustion is drawn into the water heater though the vent pipe from outside your  
building. The air travels into the closed combustion chamber. The air then mixes with in a normal manner with  
supplied gas and its efficiently combusted, producing very low NOx emissions.  
In the unlikely event trace amounts of flammable vapors are present in the area surrounding the water heater, the  
sealed combustion system prevents the flammable vapors from reaching the ignition source. In addition the  
flammable vapors sensor will stop the water heater from operating if a significant amount of flammable vapors are  
present.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
How to Use This Manual  
PDX Series  
It is intended for this manual to be used by qualified service personal for the primary purpose of  
troubleshooting and repair of the Bradford White TTW Series water heaters. Understanding the  
sequence of operation section of this manual will contribute greatly to troubleshooting the water  
heater.  
The Honeywell WV4460E Electronic Gas Control will display error codes in the event of abnormal  
operation. Error codes are listed in the troubleshooting chart beginning on page 12 of this service  
manual. The troubleshooting chart will also indicate the probable cause for the error code and  
direct the service professional to a service procedure to properly diagnose the abnormal operation.  
In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent  
system to determine the problem.  
Contact the Bradford White technical support group immediately if diagnosis can not be made  
using the methods described in this service manual.  
Tools Required for Service  
Manometer:  
Multi-Meter:  
A liquid “U” tube type or a digital (magna-helic) type can be used. This  
device is used to measure gas and/or air pressure and vacuum.  
A digital type is strongly recommended. This device is used to measure  
electrical values. The meter you select must have the capability to  
measure volts AC, volts DC, Amps, micro-amps and ohms.  
Electronic Probes:  
In some cases, standard multi-meter probes will damage or simply  
not be effective to obtain certain voltage and ohm reading. It will be  
necessary to have special electronic “pin” type multi-meter probes.  
These probes are available at most electronic wholesale outlets.  
Thermometer:  
Used to measure water temperature. An accurate thermometer is  
recommended.  
Water Pressure Gage:  
Used to measure water supply pressure. Also used to determine tank  
pressure by adapting to the drain valve of the heater.  
Gas Control Service Tool: BWC part number 239-45991-00. A specialized tool designed to remove  
the gas control from gas control thermal well. Available from  
your Bradford White parts supplier.  
Various Hand Tools:  
Pipe wrench, channel locks, open end wrenchs (3/8",7/16",½"),  
12" crescent wrench, Allen wrench set, screw drivers (common &  
Phillips), ¼" nut driver, pliers (common & needle nose), socket set, side  
cutters wire cutters, wire strippers, wire crimpers, torpedo level, small  
shop vac, step ladder, and flashlight, 5 gallon pail.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
PDX Series  
Power supply  
Dedicated 115VAC, 60 Hz, 15A  
Gas Supply Pipe  
Approved Gas Type  
Gas Pressure  
Minimum 1/2" NPT (schedule 40 black iron pipe recommended)  
Natural or Propane. Unit must match gas type supplied.  
5.0" W.C. min. for Nat gas, 11.0" W.C. min. for L.P. gas, 14.0" W.C. maximum (Nat. & L.P.)  
Power vent through the wall or vertical through the roof  
Venting System  
Approved Vent Materials PVC, CPVC or ABS  
Minimum Clearance  
18" from top, 24" from front, 4" sides and rear.  
for Servicing  
Water Supply Pressure  
150 PSI maximum allowable working pressure. Check local codes for supply pressure  
Residential 188°F (87°C), Commercial 199°F (93°C)  
Thermal well TCO Limit  
Residential Temperature  
Set Point Range  
60°F (16°C) to 160°F (71°C) (Approximate temperatures)  
Commercial Temperature  
Set Point Range  
80°F (27°C) to 180°F (82°C) (Approximate temperatures)  
Blower Temperature  
Switch  
Normally closed, opens @ 165°F (74°C), auto reset @ 130°F (54°C).  
Exhaust-Normally open, closes on vacuum increase @ -1.30.  
Intake-Normally closed, opens on vacuum increase @ -1.15.  
Pressure switch  
Blower  
115VAC, 60Hz, 3.1 amps.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
PDX Series  
Vent Tables  
Venting Specifications for:  
48 Gallon  
65 Gallon  
75 Gallon  
This water heater is approved for installation with the following PVC, CPVC or ABS  
Schedule 40 venting material.  
The maximum and minimum vent lengths listed on this label are for the exhaust portion of  
the vent. The intake portion of the vent must be equal to or less than the length of the  
exhaust.  
3" Diameter (7.6 cm) PVC Vent Connector Lengths  
Maximum 48, 65 gal.  
Maximum Minimum  
Length ft (m) Length ft (m) Length ft (m) Length ft (m)  
Maximum 75 gal.  
# of  
Elbows  
Terminating  
Maximum Minimum  
Through the Wall  
Through the Wall  
Through the Wall  
Through the Wall  
1
2
3
4
55 (16.8)  
50 (15.2)  
45 (13.7)  
40 (12.2)  
2 (.6)  
2 (.6)  
2 (.6)  
2 (.6)  
45 (13.7)  
40 (12.2)  
35 (10.7)  
30 (9.1)  
2 (.6)  
2 (.6)  
2 (.6)  
2 (.6)  
Through the Roof  
Through the Roof  
Through the Roof  
Through the Roof  
0
1
2
3
60 (18.3)  
55 (16.8)  
50 (15.2)  
45 (13.7)  
7 (2.1)  
7 (2.1)  
7 (2.1)  
7 (2.1)  
50 (15.2)  
45 (13.7)  
40 (12.2)  
35 (10.7)  
7 (2.1)  
7 (2.1)  
7 (2.1)  
7 (2.1)  
4" Diameter (10.2 cm) PVC Vent Connector Lengths  
Maximum 48, 65 gal.  
Maximum Minimum  
Maximum 75 gal.  
# of  
Elbows  
Terminating  
Maximum  
Minimum  
Length ft (m) Length ft (m) Length ft (m) Length ft (m)  
Through the Wall  
Through the Wall  
Through the Wall  
Through the Wall  
Through the Wall  
1
2
3
4
5
95 (29.0)  
90 (27.4)  
85 (25.9)  
80 (24.4)  
75 (22.9)  
10 (3.1)  
10 (3.1)  
10 (3.1)  
10 (3.1)  
12 (3.6)  
85 (25.9)  
80 (24.4)  
75 (22.9)  
70 (21.3)  
65 (19.8)  
10 (3.1)  
10 (3.1)  
10 (3.1)  
10 (3.1)  
12 (3.6)  
Through the Roof  
Through the Roof  
Through the Roof  
Through the Roof  
Through the Roof  
0
1
2
3
4
100 (30.5)  
95 (29.0)  
90 (27.4)  
85 (25.9)  
80 (24.4)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
90 (27.4)  
85 (25.9)  
80 (24.4)  
75 (22.9)  
70 (21.3)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
PDX Series  
Control Timings  
Ignition State  
Timing  
Pre-purge  
2 Seconds  
90 Seconds  
3 Seconds  
15 Seconds  
Trial for Ignition  
Flame Stabilization Period  
Inter-purge  
Flame Failure Response Time  
Post-purge  
1.5 Seconds (2 second. Maximum; 1 second minimum.)  
15 Seconds  
PS Fault Delay (failed open/close)  
Soft Lockout  
Retry after 2 Minutes  
Retry after 5 Minutes  
TCO Limit Lockout  
Indefinite (cycle power to restart)  
Retry after 2 Minutes (repeats 5 times)  
Indefinite (cycle power to restart)  
Indefinite (self clears if fault clears for at least 15 seconds)  
Verify Resistive Delay  
Simulated Resistive Load Lockout  
Hardware Error Lockout  
Wiring Diagram  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sequence of Operation  
PDX Series  
Power up Sequence  
1
Start Up.  
Upon power up, the control runs a safe-start check with a typical start-up delay of 1-5 seconds.  
2
Flammable Vapor Check.  
To assure no outputs are energized if the “Flammable Vapor Sensor” is out of range, the control will test the  
the “Flammable Vapor Sensor” for proper operating range. If the “Flammable Vapor Sensor” is within range the  
control resumes normal operation with no perceptible delay. If the “Flammable Vapor Sensor” is out of range, the  
control LED immediately flashes 7 times with 3 second pause.  
Normal Heating Sequence  
1
Thermostat calls for heat.  
Prior to energizing blower, gas control checks safety circuit to insure the circuit is open. Normal switch positions  
in the safety circuit are as follows:  
a) Exhaust pressure switch normally open.  
b) Blower temperature switch normally closed.  
c) Inlet pressure switch normally closed.  
If the safety circuit is closed, the control waits 4 seconds, gas control LED flashes 2 times with 3 second pause.  
Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens.  
2
Blower energizes.  
3
Blower pre-purge period (2 seconds)  
4
Exhaust pressure switch proves blower/vent system operation.  
a) If the pressure switch does not close within 30 seconds, the control LED Flashes 3 times with 3 second pause.  
The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch  
to close. This cycle repeats as long as there is a call for heat.  
b) The normally closed inlet pressure switch allows the system to work as long as the inlet air is not blocked.  
5
Trial for pilot ignition (90 seconds).  
a) The gas control lights the pilot by activating spark igniter and gas flow to pilot burner.  
b) If flame is not sensed within 90 seconds, igniter and gas flow are deactivated, blower will post purge and  
control LED flashes 6 times with 3 second pause.  
6
Main burner Ignition  
After pilot flame is sensed, gas control activates main valve for main burner ignition. The gas control will ignore  
flame and pressure switch signals for 3 seconds allowing for main burner to stabilize.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sequence of Operation  
PDX Series  
Normal Heating Sequence (cont.)  
Steady state operation.  
7
During Steady State Operation the Control Monitors:  
Thermostat temperature sensor- When set point temperature is satisfied, gas valve is shut down and  
blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status  
code.  
Pressure switch / Blower temperature switch- If either switch opens, pilot valve and main valve is shut  
down. The blower continues to runs for 30 seconds attempting to close the circuit. The control LED Flashes  
3 times with 3 second pause.  
Flame Sense- If flame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts  
to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control  
re-attempts to light pilot starting at normal heating sequence #2.  
8
9
Thermostat satisfies.  
Burner off.  
10  
Blower post purge (15 seconds).  
Abnormal Operation  
1. Simulated Resistive Device Fault:  
a) If the Flammable Vapor Sensor resistance is greater than 70,000 Ohms - the gas control immediately turns  
off all outputs. Control waits and monitors resistance for 30 seconds. If the resistance is greater than 70,000 ohms  
after 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times with a three  
second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds  
to a lockout mode flashing 7 times with a 3 second pause.  
b) If the Flammable Vapor Sensor resistance is below 3000 ohms - The gas control immediately turns off all  
outputs and proceeds to flash 8 times then once with three second pause. The error self clears if the resistance  
returns to normal range for at least 15 seconds.  
2. Temperature Sensor Fault:  
a) Temperature sensor detected open circuit - The gas control Immediately turns off all outputs and proceeds to  
flash 8 times then three times with three second pause. The error self clears if the fault clears for at least 15  
seconds.  
b) Temperature sensors not reading the same temperature within 5.5 °F - The gas control Immediately turns off  
all outputs and proceeds to flash 8 times then three times with three second pause. The error self clears if the fault  
clears for at least 15 seconds.  
c) Water temperature in excess of TCO (Temperature Cut Off) limit - The gas control immediately turns off pilot &  
main valve and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset.  
Power needs to be cycled to remove gas control from TCO lockout.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sequence of Operation  
PDX Series  
Abnormal Operation (cont.)  
3. Pressure Switch/Blower Temperature Fault:  
a) Pressure switch closed at start of call for heat - The control waits four seconds then, proceeds to flash  
2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower  
turns off after 30 seconds and the control waits for pressure switch to open. Any time the Pressure switch opens,  
the blower turns on (or stays on) and the control proceeds to waiting for pressure switch to close.  
b) Pressure switch or blower temperature switch failed open - The control runs the blower for 30 seconds  
waiting for the pressure switch and/or blower temperature switch to close. If either switch does not close in 30  
seconds, the blower turns off and the control flashes 3 times with 3 second pause. The control waits two  
minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as  
there is a call for heat or until the circuit closes.  
c) Pressure switch or blower temperature switch opens during burner operation - The control turns off the  
pilot and main valve, runs blower for 15 seconds (inter-purge) waiting for pressure switch and/or blower  
temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above. If the  
circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count has  
not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the control  
turns off the blower and flashes 6 times then 2 times with 3 second pause. The control waits 5 minutes before  
repeating ignition sequence.  
d) Normally closed intake pressure switch opens at start of call for heat-the control runs the blower for 30  
seconds waiting for the pressure switch to close. If the switch does not close in 30 seconds, the blower turns off  
andthe control flashes 3 times with a 3 second pause. The control waits two minutes before turning on the blower  
for another 30 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the  
circuit closes.  
4. Trial For Ignition Fault:  
a) Pressure switch opens during trial - The control turns off igniter and pilot valve. The gas control proceeds  
as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for  
ignition starting at blower pre-purge.  
b) Flame Not Sensed - The control energizes the spark igniter attempting to light the pilot and prove flame. If  
flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the  
blower through post purge and flashes 6 times then once with 3 second pause. The control waits 5 minutes before  
repeating the ignition sequence.  
5. Flame Sensing Fault:  
a) Flame lost during run - The control turns off pilot and main valves, runs blower for 15 seconds (inter purge).  
The control increments the recycle count, if the recycle count has not reached its limit (4), another trial for  
ignition begins. If the recycle count has been reached, the control turns off the blower and flashes 6 times  
then 3 times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.  
b) Flame sensed out of sequence - the control only looks for pilot flame when the blower is running. If flame is  
present when the pilot valve is not open, the control proceeds to wait for flame loss and flashes 5 times with 3  
second pause. This continues until flame is lost, once the flame signal is lost, the control flashes 6 times then 4  
times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
PDX Series  
Green LED  
Indicator  
Observe green LED indicator on  
Electronic gas control. Error flash codes  
are displayed with a three second pause  
before repeating. Check and repair the  
system as noted in the troubleshooting  
table below.  
Control  
Status  
Service  
Procedure  
LED Status  
Probable Cause  
None, control LED not No electrical  
Control power switch in “OFF” position.  
Supply voltage interrupted.  
Turn power on  
on or flashing  
power  
Stand-by mode,  
Waiting for call for Temperature demand is satisfied  
heat (no fault).  
Normal operation.  
Adjust thermostat to  
temp level  
Short flash, once every  
four seconds  
Normal operation.  
Adjust thermostat to  
temp level  
“Heartbeat”, alternates Thermostat calling  
Tank temperature below set point of thermostat.  
bright/dim  
for heat (no fault).  
1. Unstable pilot.  
1. Page 14  
Weak pilot signal 2. Pilot tube block or restricted.  
Short flash once per  
second  
on last call for  
heat.  
3. Oxidation build up on pilot electrode.  
4. Wire damage to pilot assembly or bad  
connection at gas valve.  
2-4. Page 16  
Pressure switch  
not working-  
closed position.  
1. Pressure switch tubing kinked or blocked.  
2. Blocked pressure tap on switch or blower.  
3. Faulty pressure switch.  
Two flash, three  
second pause  
Page 17  
1. Vent blockage or improper vent configuration.  
2. Pressure switch tubing kinked or blocked.  
3. Faulty pressure switch.  
1. Check vent or vent tables.  
2 & 3 Page 17  
Pressure switch  
or blower temp.  
switch not working  
-open position.  
Three flash, three  
second pause  
4. Blower not spinning up to speed.  
4. Page 21  
5. Blower temp or exhaust temp too high  
6. Faulty blower temperature switch.  
7. Intake vent length exceeds exhaust vent length.  
5 & 6 Page 23  
Excessive tank  
temperature.  
System must be  
reset.  
1. Page 25  
1. Thermal well sensor out of calibration.  
2. Faulty gas control.  
3. Plumbing leak  
Four flash, three  
second pause  
2. Replace gas control,  
page 27  
Undesired-false  
pilot flame  
present.  
Five flash, three  
second pause  
Replace gas control,  
page 27  
1. Pilot valve stuck in open position.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
PDX Series  
Control  
Status  
Service  
Procedure  
LED Status  
Probable Cause  
1. Unstable pilot.  
Failed to light  
pilot.  
System auto  
resets.  
1. Page 14  
2. Pilot tube blocked or restricted.  
3. Oxidation build up on pilot electrode.  
4. Wire damage to pilot assembly or bad  
connection at gas valve.  
Six-one flash, three  
second pause  
2-4. Page 16  
1. Check vent or vent tables.  
2 & 3 Page 17  
Pressure switch  
or blower temp  
switch opened  
during burner  
operation.  
System auto  
resets.  
1. Vent blockage or improper vent configuration.  
2. Pressure switch tubing kinked or blocked.  
3. Faulty pressure switch.  
Six-two flash, three  
second pause  
4. Refer to venting section of  
installation manual  
4. Vent termination being affected by wind  
5. Blower not spinning up to speed.  
5. Page 21  
6. Blower temp or exhaust temp too high  
7. Faulty blower temperature switch.  
6 & 7 Page 23  
1. Unstable pilot.  
1. Page 14  
2. Pilot tube blocked or restricted.  
3. Oxidation build up on pilot electrode.  
4. Wire damage to pilot assembly or bad  
connection at gas valve.  
Pilot flame  
extinguished.  
System auto  
resets.  
Six-three flash, three  
second pause  
2-4. Page 16  
5. Refer to installation manual  
5. Insufficient combustion air.  
6. Gas pressure is out of specification.  
Undesired-false  
pilot flame  
sensed.  
System auto  
resets.  
Six-four flash, three  
second pause  
Replace gas control,  
page 27  
Pilot valve stuck in open position.  
WARNING: EXPLOSION HAZARD  
* Indicates gasoline vapors were detected at potentially  
explosive levels.  
Flammable Vapor  
Sensor fault  
detected  
Seven flash, three  
second pause  
* Verify no gasoline vapors are still present  
* Reset the control by cycling power to the appliance or  
by cycling the ON/OFF switch.  
Page 29  
* Replace the Flammable Vapors Sensor element if a  
gasoline spill event occurred.  
* Verify Flammable Vapor Sensor (FVS) resistance is  
not below 25 K Ohms.  
Flammable Vapor  
Sensor out of  
specification.  
Eight-one flash, three  
second pause  
Page 29  
Page 25  
* Check wiring to FVS and insure it is not shorted.  
* Replace control if everything above checks out OK.  
Thermal well  
sensor damaged  
or unplugged  
1. Damage to thermal well wire.  
2. Thermal well sensor resistance out of range.  
Eight-three flash, three  
second pause  
Gas valve  
electronics fault  
detected  
1. Interrupt power supply  
2. Replace gas control,  
page 27  
1. Control needs to be reset.  
2. Control is wet or physically damaged.  
1. Interrupt power supply  
2. Replace gas control,  
page 27  
Eight-four flash, three  
second pause  
Gas valve fault  
detected.  
1. Control needs to be reset.  
2. Control is wet or physically damaged.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE I  
Burner Operation Inspection,  
Adjustment, Cleaning and Replacement  
PDX Series  
Burner Inspection and Air Shutter Adjustment.  
At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main burner for proper  
operation and to assure no debris is accumulating.  
Pilot flame should be stable, some causes for an unstable pilot flame are:  
a) Water heater vent is less than the allowable vent length.  
b) Gas pressure is out of specification.  
c) Pilot flame not fully engulfing spark/flame sensor.  
Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips.  
Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter. Cast iron burner can  
have the gas and air mixture properly proportioned by adjusting the air shutter on the mixer face of the main burner  
(see cast iron burner adjustment below).  
Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning  
procedure on page 14).  
Cast Iron Burner Air Shutter Adjustment  
WARNING  
Inner door and burner components may be HOT when performing this operation. Take  
necessary precaution to prevent personal injury.  
Step 1.  
With main burner in operation, remove outer jacket door remove inner door as described in this manual,  
see inner door removal, inspection and replacement section (page 35).  
Step 2.  
To adjust for proper burning, loosen the air shutter nut, rotate the air shutter to close the opening in the  
burner, then slowly rotate the air shutter open until flame becomes as blue as possible with a minimum of  
yellow tips. Tighten the air shutter nut.  
Too much air will cause the flame to lift off the burner ports and create noisy burner operation.  
Too little air will result in soot formation.  
Step 3.  
Replace inner door as described in this manual, observe burner operation. Burner should operate as  
adjusted in step 2. If not, repeat air shutter adjustment compensating for proper burner operation with inner  
door closed.  
Air Shutter Nut  
Air Shutter  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE I  
Burner Operation Inspection,  
Adjustment, Cleaning and Replacement  
PDX Series  
Burner Cleaning  
Step 1.  
Position gas control power switch to the “OFF” position and unplug heater from wall  
outlet.  
Step 2.  
Step 3.  
Turn off gas supply to water heater.  
Remove outer jacket door and inner door per service procedure XIII on page 35.  
Igniter/flame  
sense wire  
Step 4.  
Disconnect pilot tube (7/16 wrench) and  
feedline (¾ wrench) from gas control.  
Feedline nut  
Step 5.  
Step 6.  
Step 7.  
Disconnect igniter/flame sensor wire from gas control.  
Remove burner assembly from combustion chamber.  
Pilot tubing nut  
Thoroughly inspect burner surface area and burner port area and  
remove any loose debris.  
Step 8.  
For cast iron burners, inspect for any debris build up inside  
burner casting.  
Burner  
surface area  
Burner  
port area  
Main burner  
Step 9.  
Unscrew burner from main burner  
orifice  
orifice. On cast iron burners, loosen  
air shutter nut and unscrew feedline  
from burner.  
Step 10. Remove main burner orifice from  
feedline (½" wrench on steel  
burners, 3/8" wrench on cast iron)  
inspect orifice, clean or replace if  
necessary.  
Step 11. Reassemble burner and reinstall into water heater. Restore gas supply  
and check for gas leaks.  
L.P. Main burner  
orifice. Left hand  
thread  
Step 12 To resume operation follow the instruction located on the lighting  
instruction label or the lighting instruction located in the installation  
and operating manual.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE II  
Pilot testing, Cleaning and Replacement  
PDX Series  
Pilot Inspection, Testing and Replacement  
Step 1.  
Position gas control power switch to the “OFF” position and unplug heater from wall  
outlet.  
Step 2.  
Step 3.  
Turn off gas supply to water heater.  
Remove outer jacket door and remove inner door per service proceedure XIII on page 35.  
Igniter/flame  
sense wire  
Step 4.  
Disconnect pilot tube nut (7/16 wrench) and feedline nut  
(¾ wrench) from gas control.  
Feedline nut  
Pilot tubing nut  
Step 5.  
Step 6.  
Disconnect igniter/flame sense wire from gas control.  
Remove burner assembly from combustion chamber.  
Step 7.  
Step 8.  
Remove pilot assembly from feedline (¼" nut driver).  
Visually inspect igniter/flame sense wire for damage. Replace  
pilot if damage is found.  
Step 9.  
With a multi-meter set to the ohms setting, check continuity  
Ferrule  
nut  
Pilot  
Pilot  
Pilot  
hood  
through igniter/flame sense wire. Replace pilot if no continuity.  
tubing orifice  
Step 10. Visually inspect igniter/flame sense electrode for deterioration.  
Replace pilot as necessary. Electrode should not be in contact  
with pilot hood, If so, carefully adjust electrode to a gap  
distance of 3/32" (.09) from pilot hood.  
Igniter/flame  
sense wire  
Igniter/flame  
sense electrode  
Step 11. Visually inspect igniter/flame sense electrode for oxidation  
build up. Carefully clean any oxidation using very fine emery  
cloth.  
Step 12. Visually inspect pilot tubing for kinks or cracks. If damage is  
found replace pilot.  
Step 13. Inspect pilot tubing and pilot orifice for blockage:  
a) Remove ferrule nut from bottom of pilot assembly (7/16" wrench).  
b) Remove pilot tube and pilot orifice.  
c) Inspect pilot tubing and pilot orifice for blockage. Clean  
or replace as necessary.  
Step 14. Reassemble pilot and install to feedline. Reinstall burner assembly to water heater. Restore gas supply  
and check for gas leaks.  
Step 15 To resume operation follow the instruction located on the lighting instruction label or the lighting  
instruction located in the installation and operating manual.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE III  
Pressure Switch Testing and  
Replacement  
PDX Series  
Exhaust Pressure Switch  
WARNING  
Testing  
120 volt potential exposure. Use caution  
making voltage checks to avoid personal injury.  
Step 1.  
Position power switch on gas control  
to the “OFF” position.  
Step 2.  
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and  
remove cover (see photo 1).  
Step 3.  
Step 4.  
Remove tubing and wires from inlet pressure switch.  
Carefully remove pressure switch from blower housing (see photo 2)  
Exhaust  
pressure switch  
1
2
Inlet pressure  
switch  
Pressure Switch  
Pressure switch  
wire leads  
With steps 1,2,3 & 4  
complete,  
disconnect wire leads from  
pressure switch.  
Slide pressure switch in direction  
of arrow while tilting slightly away  
from blower housing.  
Use a multi-meter set to the  
ohms setting. With blower off,  
check across pressure  
switch terminals.  
Are switch contacts open?  
(no electrical continuity)  
Check tubing and pressure  
tap on switch for blockage.  
Is there blockage?  
Replace switch  
(see page 18)  
N
N
Y
Y
Clear blockage  
Position gas valve power  
switch to the “ON” position  
and adjust thermostat  
to call for heat,  
this will start the blower.  
Check with multi-meter, do  
pressure switch contacts  
close with blower running  
with the switch in the  
vertical postition?  
Y
Y
Y
Check tubing and  
pressure tap on  
switch for blockage.  
Is there blockage?  
Is vent system length  
Is vent  
system  
blocked  
See blower testing  
within vent table  
specifications  
N
N
N
Y
(page 21)  
Is blower OK?  
listed on page 7  
N
N
Y
Reconfigure vent  
system to be  
compliant with  
vent tables.  
Correct blower  
problem.  
Switch contacts are OK.  
See safety circuit trace  
(page 30)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE III  
Pressure Switch Testing and  
Replacement  
PDX Series  
Exhaust Pressure Switch  
WARNING  
120 volt potential exposure. Use caution  
to avoid personal injury.  
Replacement  
Step 1.  
Position gas control power switch  
to “OFF” position.  
Step 2.  
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and  
remove cover (see photo 3).  
Step 3.  
Step 4.  
Disconnect the tubing and wires from inlet pressure switch.  
Pressure Switch  
4
3
Carefully remove pressure  
switch from blower  
housing (see photo 4)  
Slide pressure switch in direction  
of arrow while tilting slightly away  
from blower housing.  
5
6
Step 5.  
Step 6.  
Disconnect tubing from  
pressure switch.  
(see photo 5)  
Disconnect yellow wires  
from pressure switch  
(see photo 6)  
Step 7.  
Step 8.  
Step 9.  
Reconnect wires from step 5 to new pressure switch.  
Reconnect tubing to new pressure switch.  
Carefully position pressure switch into blower housing.  
Step 10. Reconnect wires and tubing to inlet pressure switch.  
Step 11. Position gas control power switch to “ON” position and verify proper heater operation.  
Step 12. Replace control access cover from step 2.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE III  
Pressure Switch Testing and  
Replacement  
PDX Series  
Inlet Pressure Switch  
Testing  
WARNING  
120 volt potential exposure. Use caution  
making voltage checks to avoid personal injury.  
Step 1.  
Step 2.  
Step 3.  
Position power switch on gas control  
to the “OFF” position.  
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and  
remove cover (see photo 7).  
Remove wires from inlet pressure switch.  
Exhaust  
pressure switch  
7
Inlet pressure  
switch  
Inlet pressure  
switch wire  
leads (found  
inside cover)  
With steps 1,2 & 3  
complete.  
Use a multi-meter set to the  
ohms setting. With blower off,  
check across pressure  
Check tubing and pressure  
tap on switch for blockage.  
Is there blockage?  
Replace switch  
(see page 20)  
N
N
switch terminals.  
Are switch contacts closed?  
Y
Y
Clear blockage  
Position gas valve power  
switch to the “ON” position  
and adjust thermostat  
to call for heat,  
this will start the blower.  
Check with multi-meter, do  
pressure switch contacts  
remain closed with blower  
running with the switch in  
the vertical postition?  
Y
Y
Y
Check tubing and  
pressure tap on  
switch for blockage.  
Is there blockage?  
Is vent system length  
Is vent  
system  
blocked  
See blower testing  
within vent table  
specifications  
N
N
N
Y
(page 21)  
Is blower OK?  
listed on page 7  
N
N
Y
Reconfigure vent  
system to be  
compliant with  
vent tables.  
Correct blower  
problem.  
Switch contacts are OK.  
See exhaust pressure  
switch testing (page 17)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE III  
Pressure Switch Testing and  
Replacement  
PDX Series  
Inlet Pressure Switch  
WARNING  
Replacement  
120 volt potential exposure. Use caution  
to avoid personal injury.  
Step 1.  
Step 2.  
Step 3.  
Position gas control power switch  
to “OFF” position.  
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and  
remove cover (see photo 8).  
Disconnect the tubing from the pressure switch (see photo 9).  
8
9
Step 4.  
Step 5.  
Step 6.  
Remove inlet pressure  
switch from blower access  
cover. (see photo 10).  
Disconnect yellow wires  
from pressure switch (see  
photo 11).  
Attach new inlet pressure  
switch to blower control  
Remove screws  
access cover.  
to remove inlet  
pressure switch  
10  
11  
Step 7.  
Step 8.  
Step 9.  
Reconnect wires from step 5 to new pressure switch.  
Reconnect tubing to new pressure switch.  
Replace control access cover from step 2.  
Step 10. Position gas control power switch to “ON” position and verify proper heater operation.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE IV  
Blower Testing and Replacement  
PDX Series  
WARNING  
Blower Testing  
115 volt potential exposure. Use caution when  
making voltage checks to avoid personal injury.  
Step 1.  
Position gas control power switch  
to “ON” position and adjust control to call for heat.  
12  
Step 2.  
Remove the three screws (Phillips Screw driver)  
from control access cover on blower assembly and  
remove cover (see photo 12).  
Disconnect vent  
system from top of  
blower and remove  
exhaust vent  
Connect  
Disconnect  
pressure switch  
tubing from blower.  
(see photo 13)  
manometer to  
pressure tap of  
blower.  
Does blower energize  
Y
Within 2 minutes?  
adapter.  
(see photo 13)  
15  
(see photo 15)  
N
Remove exhaust  
adapter  
14  
Pressure tap  
13  
With blower running, and exhaust  
adapter removed from top of  
blower, is there a negative  
Y
Blower OK  
pressure of -2.30" to -2.60" W.C.?  
N
Pressure  
switch tubing  
Is there 115vac across  
blue and green wires  
(see photo 18)  
N
Determine voltage  
problem and correct.  
Y
Replace blower  
Does blower energize after  
2 minutes, run for 30  
seconds and shut down?  
See pressure  
switch testing  
Page 17 & 19  
Y
16  
17  
N
Disconnect cord set  
shown in photo 9. Is  
there 115VAC across  
terminals shown in  
photo 16  
Is there 115VAC  
across terminals  
Y
Y
shown in photo 17 ?  
Reconnect cord set  
shown in photo 9, is  
there 115VAC between  
blue wire and green  
ground wire  
N
Y
Replace blower  
N
Incorrect supply  
voltage polarity  
(see photo 18)  
N
Green ground  
wire  
Does cord set  
Determine  
18  
Replace  
cord set  
N
have electrical  
N
Y
Is there 115 VAC  
at wall outlet?  
power source  
problem and  
correct.  
continuity?  
Y
Blue wire  
Y
Replace  
gas control  
Check power cord  
for damage.  
Repair or replace  
power cord  
N
Shown with pressure  
switch removed.  
Replace blower  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE IV  
Blower Testing and Replacement  
PDX Series  
Blower removal  
Remove exhaust  
adapter and retain for  
use on new blower.  
Step 1.  
Step 2.  
Step 3.  
Position gas control power switch to the “OFF” position.  
Blower Mounting  
Screws  
Unplug blower power cord from wall outlet.  
Disconnect vent system from exhaust adapter on top of  
blower.  
Step 4.  
Remove exhaust adapter from blower (blade screw driver)  
and retain for use on new blower  
Step 5.  
Step 6.  
Step 7.  
Step 8.  
Unplug cord sets from blower.  
Remove vertical air intake bracket.  
Disconnect vertical air intake from blower.  
Blower  
Cord Sets  
Remove the three blower mounting screws  
(¼" nut driver).  
Vertical air intake  
Step 9.  
Remove blower with gasket from water heater.  
Vertical air intake  
bracket  
Blower Installation  
Step 10. Clean any debris from jacket head of water heater.  
Step 11. Set new blower with gasket in place using locating pins on  
blower flange to line up with location holes in jacket head.  
Be sure not to damage gasket.  
Step 12. Secure blower in place using mounting screws from step 8.  
Step 13. Slide vertical air intake tee onto blower.  
Locating Pins  
on blower flange  
Step 14. Re-install vertical air intake bracket.  
Step 15. Re-install exhaust adapter from step 4.  
Step 16. Reconnect vent system to exhaust adapter.  
Step 17. Reconnect cord sets from step 5.  
Pin location holes in  
jacket head  
Step 18. Plug blower power cord into wall outlet.  
Step 19. Position gas control power switch to the “ON” position.  
Step 20. Verify proper blower operation.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE V  
Blower Temperature Switch Testing  
and Replacement  
PDX Series  
Blower Temperature Switch  
WARNING  
120 volt potential exposure. Use caution  
to avoid personal injury.  
Testing.  
Step 1.  
Position power switch on gas control  
to the “OFF” position.  
19  
Step 2.  
Step 3.  
Remove tubing from inlet pressure tap.  
Remove the three screws (Phillips screw driver) from  
control access cover on blower and remove cover (see  
photo 19).  
Step 4.  
Locate blower temperature switch (see photo 19)  
20  
Switch Setting  
Opens on rise @ approximately 165°F  
Auto resets on fall @ approximately 130°F  
Blower temperature  
switch location  
Cool switch to  
below 130°F  
Air mixing inlet  
Disconnect wire leads to  
N
switch. Using a multi-meter  
set to the ohms setting, is  
there continuity between  
the switch terminals?  
Replace switch  
(see page 24)  
Y
Common causes for  
N
Reconnect wire leads and  
observe heater operation.  
Do exhaust gas  
temperatures rise to or  
above 165°F?  
high exhaust temperature  
Exhaust  
temperature is  
too hot.  
1. Vent length is below minimum allowable.  
2. Vent diameter not to specification.  
3. Restricted dilution air inlet.  
4. Missing or deteriorated flue baffle.  
5. Gas pressure is out of specification.  
Y
Y
Do switch  
contacts open?  
N
Do switch  
contacts open?  
Replace switch  
(see page 23)  
Y
N
Switch OK  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE V  
Blower Temperature Switch Testing  
and Replacement  
PDX Series  
Blower Temperature Switch  
Replacement.  
WARNING  
120 volt potential exposure. Use caution  
to avoid personal injury.  
Step 1.  
Position gas control power switch to the “OFF” position  
20  
and unplug heater from wall outlet.  
Step 2.  
Step 3.  
Remove tubing from inlet pressure tap.  
Remove the three screws (Phillips screw driver) from the  
control access cover on blower and remove cover.  
(see photo 20)  
Step 4.  
Step 5.  
Step 6.  
Locate blower temperature switch (see photo 21)  
Disconnect red and yellow wire leads from switch.  
21  
Blower temperature  
switch location  
With an appropriate tool such as side cutters, snip the  
retaining lug from the blower housing to allow removal of  
temperature switch (see photo 22).  
Step 7.  
Step 8.  
Remove switch from blower housing.  
Install new switch. Be sure switch is properly seated in  
mounting area.  
22  
Snip retaining lug  
from blower housing  
Step 9.  
Reconnect red and yellows wires to new switch. Wires are  
interchangeable with either terminal.  
Step 10. Position gas control power switch to the “ON” position  
and verify proper heater operation.  
Step 11. Replace control access cover from step 2.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE VI  
Gas Control/Thermal Well Testing and  
Replacement  
PDX Series  
Gas Control Testing  
See pages 27 & 28 for gas control  
input & output testing.  
Thermal Well Testing  
Disconnect thermal  
well wire harness  
If Control has gone into TCO lockout due to  
excessive tank temperature (four flash, 3 second  
pause) reset control by rotating knob of temperature  
control to the minimum setting for at least 6 seconds  
before returning to desired temperature setting.  
Observe heater operation. If control  
continues to lockout due to  
excessive tank temperature,  
proceed to thermal well testing to  
determine cause.  
19  
20  
Thermal well testing  
Position gas control power switch to  
the “OFF” position and disconnect  
thermal well harness from gas  
control.  
CAUTION  
DO NOT use standard multimeter probes for this test.  
Doing so will damage connector. Use special pin type  
electronic probes or small diameter wire pins inserted  
into connector.  
Using a multi-meter set to the  
Ohms setting, determine the  
resistance of thermal well sensor  
(see caution photos 23 & 24)  
Using a multi-meter set to the ohms setting, insert one meter probe (see caution)  
into center wire position of thermal well connector, insert the second probe (see  
caution) into either of the outside wire positions (see photo 23).  
Alternate the probe on the outside position to the opposite outside wire position  
(see photo 24).  
Once the thermal well resistance values are known, the water  
temperature must also be known to determine if the resistance  
values are correct. See page 25 to obtain water temperature.  
N
Replace thermal well  
(see page 27)  
Are thermal well resistance values correct?  
Y
Replace gas control  
(see page 27)  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE VI  
Gas Control/Thermal Well Testing and  
Replacement  
PDX Series  
WARNING  
Stored water may be HOT when performing the following steps in this procedure.  
Take necessary precaution to prevent personal injury.  
Determine Water Temperature Inside Tank  
Note: It is important to understand once the resistance for the thermal well is determined from page 25, water flow  
through the heater should not occur. Prior to performing the steps below, turn off the cold water supply to the  
water heater. This will prevent cold water flow into the tank affecting the resistance value of thermal well.  
Step 1.  
Step 2.  
Position gas control power switch to “OFF” position.  
Draw approximately 4 gallons of water from drain valve into a container and discard. Draw an  
additional gallon and immediately measure water temperature using an accurate thermometer. It may  
be necessary to open a hot water faucet to allow heater to drain.  
Step 3.  
Using the chart below, determine correct resistance value for the water temperature from step 2.  
Example:  
If temperature of water is 84°F, then the resistance through the sensor would be  
8449 (see shaded area). NOTE: Sensor resistance increases as the temperature  
falls.  
Sensor Resistance at Various Temperatures  
In Degrees F  
°F  
40  
50  
60  
70  
80  
90  
100  
110  
120  
130  
140  
150  
160  
170  
180  
190  
200  
0
1
2
3
4
5
6
7
8
9
26109  
19906  
15314  
11884  
9299  
7333  
5827  
4663  
3758  
3048  
2488  
2043  
1688  
1402  
1170  
982  
25400  
19383  
14925  
11592  
9078  
7165  
5697  
4562  
3679  
2986  
2439  
2004  
1656  
1376  
1150  
965  
24712  
18876  
14548  
11308  
8862  
7000  
5570  
4464  
3602  
2925  
2391  
1966  
1625  
1351  
1129  
949  
24045  
18383  
14180  
11032  
8653  
6839  
5446  
4368  
3527  
2866  
2344  
1928  
1595  
1327  
1110  
933  
23399  
17905  
13823  
10763  
8449  
6683  
5326  
4274  
3453  
2808  
2298  
1891  
1566  
1303  
1090  
917  
22771  
17440  
13477  
10502  
8250  
6531  
5208  
4183  
3382  
2752  
2253  
1856  
1537  
1280  
1071  
901  
22163  
16990  
13140  
10248  
8057  
6383  
5094  
4094  
3312  
2697  
2209  
1820  
1509  
1257  
1953  
886  
21573  
16553  
12812  
1000  
7869  
6238  
4982  
4006  
3244  
2643  
2166  
1786  
1481  
1235  
1035  
871  
21000  
16128  
12494  
9760  
7685  
6098  
4873  
3922  
3177  
2590  
2124  
1753  
1454  
1213  
1017  
857  
20445  
15715  
12185  
9526  
7507  
5961  
4767  
3839  
3112  
2538  
2083  
1720  
1427  
1191  
999  
842  
713  
828  
814  
801  
788  
775  
762  
749  
737  
725  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE VI  
Gas Control & Thermal Well Testing  
and Replacement  
PDX Series  
Gas Control & Thermal Well Removal From Water Heater  
Gas Control  
Step 1.  
Step 2.  
Step 3.  
Step 4.  
Step 5.  
Position gas valve power switch to the “OFF”  
Thermal  
Well  
position and Unplug Heater from power supply.  
Drain heater to a point below the gas  
control level.  
Turn off gas supply to water heater and  
disconnect gas piping from gas control.  
Disconnect wire harnesses and burner assembly  
from gas control.  
Remove gas control & thermal well by rotating flats of Thermal Well counter clockwise (1-5/16"wrench).  
Gas Control Removal From Thermal Well  
Follow the steps below allows removal gas control from thermal well without  
removing thermal well from tank.  
Step 1.  
Step 2.  
Step 3.  
Step 4.  
Position gas control power switch to the “OFF” position and unplug water heater from power supply.  
Turn off gas supply to water heater and disconnect gas piping from gas control.  
Disconnect wire harnesses & burner assembly from gas control.  
Using gas control service tool (239-45991-00) available from your BWC parts supplier, Insert tool into  
back of gas control (see photos below)  
View from back of  
control for clarity  
Insert tool from  
back of control  
Service tool shown  
inserted in to back  
of control  
Step 5.  
Pivot tool towards heater as far as possible (see photo below). Lift straight up on gas control. The  
control should move about 1/8". Hold control in position and remove tool. Lift straight up on control to  
remove completely from Thermal Well.  
With service tool inserted, pivot tool back towards water  
heater as far as possible. Lift straight up on control,  
control will move 1/8". Remove tool and continue to lift  
straight up on control to remove from Thermal Well.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE VI  
Gas Control & Thermal Well Testing  
and Replacement  
PDX Series  
Gas Control Assembly to Thermal Well  
Step 1.  
Install threaded end of thermal well into tank. Be sure  
thermal well flange is positioned as shown in photo 24  
for proper control alignment.  
24  
Step 2.  
Step 3.  
Route wire leads back into relief opening.  
(see photo 24)  
Align slots located on thermal well flange with tabs  
located on back of gas control (see photo 24 & 25)  
Route wires  
through relief  
opening  
Thermal well  
flange slots  
Step 4.  
Step 5.  
Carefully push control back onto thermal well flange  
as far as possible towards water heater. Slide control  
down to lock into position.  
25  
Install burner and connect pilot tubing and feedline nut  
to gas control.  
Gas control Tabs  
Igniter/sensor  
connection  
Step 6.  
Step 7.  
Reconnect wire harnesses to gas control  
per the illustration.  
Reconnect gas piping to gas control.  
Restore gas supply and check for gas  
leaks.  
Ground Wire  
connection  
Step 8.  
To resume operation, follow the  
instruction located on the lighting  
instruction label or the lighting instruction  
located in the installation and operation  
manual.  
5 pin  
blower harness connection  
3 pin  
thermal well connection  
Flammable Vapor  
Sensor  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE VII  
Flammable Vapors Sensor Testing  
PDX Series  
Flammable Vapor Device Testing  
Step 1.  
Step 2.  
Step 3.  
Position power switch on gas control to the  
“OFF” position.  
Disconnect flammable vapor sensor from  
gas control.  
Using a multi-meter set to the ohms setting  
check resistance of flammable vapor sensor.  
(see caution below)  
Resistance must be within 3,000 ohms and  
48,000 ohms. If outside of this range replace  
flammable vapor sensor.  
Flammable Vapor  
Sensor  
Multi-meter set to  
ohms setting  
CAUTION  
Electronic  
DO NOT use standard multimeter probes for this test.  
Doing so will damage connector. Use special electronic  
“pin type” probes or small diameter wire pins inserted  
into connector.  
“pin type”  
Meter Probes  
Flammable Vapor  
Sensor  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE VIII  
Safety Circuit Voltage Trace  
PDX Series  
Safety Circuit Voltage  
WARNING  
Trace  
120 volt potential exposure. Use caution  
making voltage checks to avoid personal injury.  
NOTE: This procedure assumes a cool tank.  
27  
Step 2.  
Remove three screws (Phillips Screw driver) from control  
access cover on blower and remove cover (see photo 26).  
Position gas control switch to the “ON”  
position and adjust thermostat dial to call  
for heat, Is there 10 to 13 VAC between  
red wire leading to blower temperature  
switch and green ground wire?  
Blower must be running during this  
voltage check.  
Is LED on gas valve flashing  
N
No voltage from gas control,  
call for technical support.  
Y
the “heartbeat” code  
(alternating bright/dim)  
N
(see photo 28)  
Y
Verify 120VAC to gas  
control (see page 30)  
Is there 10 to 13 VAC between yellow  
wire leading from pressure switch and  
green ground wire?  
Is there continuity  
Check for loose or  
broken wire  
connection at switch  
terminals  
through blower  
temperature switch?  
(see page 21)  
N
Y
(see photo 28)  
N
Y
Determine cause of blower  
temperature switch  
activation and correct.  
Correct igniter/  
sensor problem.  
Check igniter/sensor  
(see page 16)  
is igniter/sensor OK?  
Do you hear or can you  
see the igniter sparking?  
Faulty cord set or  
gas control.  
N
Y
Green ground wire  
Y
28  
Safety circuit  
voltage is OK.  
Red wire leading to  
blower temp. switch  
If burner does not light,  
observe LED flash code  
on gas valve and refer to  
troubleshooting section  
on page 12  
Yellow wire  
leading from  
pressure switch  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE IX  
120 VAC Trace  
PDX Series  
WARNING  
120 VAC Circuit Trace  
120 volt potential exposure. Use caution  
making voltage checks to avoid personal injury.  
Step 1. Verify 120VAC and proper polarity at wall outlet.  
Step 2. With unit plugged in and control power switch in the “ON” position verify LED status.  
LED status  
None, Control LED not  
on or flashing.  
LED status  
Short flash, once every  
four seconds.  
LED status  
“Heartbeat”, alternates  
bright/dim.  
LED status  
Various flashing error  
codes.  
Waiting for  
call for heat.  
Thermostat calling  
for heat  
Verify error code as  
listed on page 12  
30  
31  
29  
Disconnect cord set as  
shown in photo 29  
Using a volt meter set  
to volts AC, is there  
120VAC across  
terminals shown in  
photo 30 ?  
Check for damage to  
AC supply power cord.  
N
Y
Y
Repair damage  
N
Y
Replace Blower  
Is there 120VAC  
across terminals  
shown in photo 31 ?  
Reconnect cord set  
shown in photo 29.  
32  
N
Disconnect wire harness  
from gas control  
Incorrect supply  
voltage polarity  
(see photo 32).  
Wire harness  
Locate black & white wires at  
connector, It may be necessary to pull  
back wire sheath to identify wire colors.  
(see photo 33)  
33  
Wire sheath pulled back to  
identify wire colors  
Is there 120VAC  
across black & white  
wires as shown in  
photo 33?  
Replace gas  
control.  
Y
Check for 120VAC between black & white wires.  
-NOTE-  
Electronic meter probes required. Use care not to  
damage connector during this check.  
N
Call for technical  
support.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE X  
Dip Tube  
PDX Series  
Inspection and replacement  
Dip Tube Inspection and Replacement  
WARNING  
Water Heater components and stored water may be HOT when performing the following  
steps in this procedure. Take necessary precaution to prevent personal injury.  
Step 1.  
Step 2.  
Position on/off switch of gas control valve to “OFF” position and unplug water heater from wall outlet.  
Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an  
open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water  
heater and allow heater to drain to a point below the inlet connection nipple.  
Step 3.  
Step 4  
Disconnect inlet nipple from plumbing system.  
With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater.  
Use caution not to damage pipe threads.  
Step 5.  
Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.  
Hydro-jet slots should be open and free of any blockage.  
Any damage such as cracks, restriction due to deformation or unintentional holes are not field  
repairable and the inlet nipple/dip tube must be replaced.  
Step 6.  
Step 7.  
Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water  
heater. Connect nipple to plumbing system, resume water supply and refill with water.  
To resume operation follow the instructions located on the lighting instruction label or the lighting  
instructions located in the installation and operation manual.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE XI  
Anode  
PDX Series  
Inspection and replacement  
Anode Inspection and Replacement  
WARNING  
Water Heater components and stored water may be HOT when performing the following  
steps in this procedure. Take necessary precaution to prevent personal injury.  
Step 1.  
Step 2.  
Position on/off switch of gas control valve to the “OFF” position and unplug water heater from wall  
outlet.  
Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an  
open drain. Open a nearby hot water faucet to vent water heater for draining. Open drain valve of  
water heater and allow water heater to drain to a point below the outlet connection nipple.  
Step 3.  
Step 4  
Disconnect outlet nipple from plumbing system.  
With an appropriate tool such as a pipe wrench, remove outlet nipple/anode from the water heater. Use  
caution not to damage pipe threads.  
Step 5.  
Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is  
normal. If depletion is ½ of the original anode diameter (approximately ¾” diameter), replacement is  
recommended. If any of the steel core of the anode is exposed, replacement is recommended.  
Step 6.  
Step 7.  
Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into water  
heater. Connect nipple to plumbing system, resume water supply and refill with water.  
To resume operation, follow the instructions located on the lighting instruction label or the lighting  
instructions located in the installation and operation manual.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE XII  
Flue Baffle  
PDX Series  
Inspection and replacement  
Disconnect vent  
system from exhaust  
adapter.  
Remove blower to gain access to  
flue baffle  
34  
Blower Mounting  
Screws  
Step 1.  
Position gas control power switch to the “OFF” position and  
unplug blower from wall outlet.  
Step 2.  
Step 3.  
Step 4.  
Step 5.  
Disconnect vent system from exhaust adapter on top of blower.  
Disconnect intake air piping.  
Unplug cord sets from blower. (see photo 34).  
Remove the three blower mounting screws  
(¼" nut driver) (see photo 34).  
Blower  
Cord Sets  
Step 6.  
Step 7.  
Step 8.  
Remove blower with gasket from water heater.  
Remove flue baffle from Heater (see photo 36).  
35  
Inspect baffle for deterioration, missing restrictors.  
Clean any scale or debris build up. Replace with new baffle as  
necessary.  
Step 9.  
Reinstall baffle into flue tube. Be sure baffle  
hanger tabs are inserted into notch location at the  
top of the flue tube (see photos 36 & 37).  
Remove support  
bracket  
Step 10. Check Burner to insure no scale has accumulated during this  
operation. See burner cleaning procedure on page 15.  
Step 11. Reinstall blower on water heater. Connect vent  
system and cords set to blower. Plug water heater  
into wall outlet.  
Step 12. To resume operation follow the lighting instruction  
located on the lighting instruction label or the lighting instruction  
located in the installation and operation  
manual.  
36  
Flue Baffle  
37  
38  
Baffle shown  
installed in flue  
tube notch.  
Flue tube  
notch  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE XIII  
Inner Door/Gasket Removal, Inspection  
Replacement and Reinstallation  
PDX Series  
Inner Door Removal Procedure.  
Step 1. Slide switch of the Electronic Gas Control to the “OFF” position and unplug from wall.  
Step 2. Remove outer jacket burner access door.  
Step 3. Disconnect wire connections from Electronic Gas Control.  
Step 4. Right side Inner Door Removal.  
a) Remove wire tie from feedline.  
b) Remove (2) 1/4" hex drive screws from right side inner door.  
c) Remove (2) 1/4" hex drive screws from flange section of inner door.  
d) Remove right side inner door and set aside. Be careful not to damage gasket material on inner door.  
¼" Hex Drive Screws shown on  
Right Side Inner Door.  
¼" Hex Drive Screws at  
Flange section of Inner Door  
Step 4. Fully inspect inner door gaskets for the following:  
>Tears  
>Other imperfection that will inhibit proper seal  
>Gasket adhesion to inner door  
>Missing Material  
>Cracks  
>Material left on combustion chamber (around opening)  
>Dirt or debris  
If the gasket is not effected by any of the above, gasket replacement is not required. If replacement is required,  
proceed to Inner Door Gasket Replacement Procedure.  
Inner Door Gasket Replacement Procedure.  
WARNING  
If the information in these instructions is not  
followed exactly, a fire or explosion may result causing  
property damage, personal injury or death.  
Step 5.  
Step 6.  
After inspection of inner door as noted in step 4, completely remove gasket and adhesive residue from right  
and left side inner doors as needed.  
Use RTV sealant (recommended bead size is 1/8") to secure the inner door gasket to the inner door sections  
(right & left). Refer to illustration below for proper application. Note the overlap configuration in the flange  
area of the inner door. Set the flange section first, this will help to achieve the proper over lap position.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE XIII  
Inner Door/Gasket Removal, Inspection  
Replacement and Reinstallation  
PDX Series  
Installation of Inner Door With Gasket.  
WARNING  
Stripped fastener connections may allow  
for seal breach of inner door. A seal  
breach may result in a fire or explosion  
causing property damage, personal  
injury or death. Do not over tighten  
screws in steps 8, 10 and 11.  
Step 7.  
Clean any residual gasket residue or other debris  
from combustion chamber surface before installing  
the inner door/gasket assembly.  
Step 8.  
Place the left side inner door into position first.  
Firmly position the radiused channel of the inner  
door aroundthe feedline. Using the 1/4” hex drive  
screws from step 3d, secure left side inner door in  
place. DO NOT OVER TIGHTEN SCREWS.  
If a fastener connection is stripped,  
contact the manufacturer listed on the  
water heater rating plate.  
Step 9  
Position thermocouple, pilot tube and Piezo wire  
against left side inner door flange gasket. DO  
NOT ROUTE THROUGH RADIUSED  
CHANNEL WITH FEEDLINE.  
Igniter wire and pilot tube  
shown in proper position.  
Radiused Channel  
for Feedline  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PDX SERVICE PROCEDURE XIII  
Inner Door/Gasket Removal, Inspection  
Replacement and Reinstallation  
PDX Series  
Installation of inner door with gasket (continued from page 36).  
Step 10. Firmly place right side inner door flange against the left side inner door flange and secure with two ¼” drive  
screws from step 3c. DO NOT OVER TIGHTEN SCREWS.  
Step 11. Align right side inner door to combustion chamber and verify the fastener holes of the combustion  
chamber are aligned with the right side inner door slotted opening. Verify seal integrity around combustion  
opening. Secure right side inner door using 1/4” hex drive screws from step 3b. DO NOT OVER TIGHTEN  
SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against the  
combustion chamber  
Verify threaded hole  
alignment with slotted  
openings in inner door.  
Step 12. Replace outer jacket burner access door.  
Step 13. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions  
located in the installation and operation manual.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary of Terms  
PDX Series  
BTU  
GPM  
Hz  
KW/h  
LED  
NPT  
Ohms  
PSI  
British Thermal Units  
Gallons per Minute  
Hertz  
Killo-watts per hour  
Light Emitting Diode  
National Pipe Thread  
Ohms of resistance  
Pounds per Square Inch  
Revolutions per Minute  
Temperature Cut Off  
Volts Alternating Current  
Inches of Water Column  
Degrees Centigrade  
Degrees Fahrenheit  
RPM  
TCO  
VAC  
W.C.  
°C  
°F  
NOTES  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts List  
PDX Series  
1. Blower Assembly  
15. Hot Water Outlet Anode 28. Screw-#8-18 x ¾ HWH  
16. Cold Water Inlet Diptube 29. Brass Drain Valve  
41. Gas Pilot Orifice (Nat.)  
42. Gas Feedline (Nat.)  
43. Gas Burner Assy (L.P.)  
44. Cast Iron Burner (L.P.)  
45. Gas Pilot Assy (L.P.)  
46. Gas Pilot Orifice (L.P.)  
47. Air Shutter (L.P.)  
48. LP Gas Feedline (L.P.)  
49. Air Shutter Nut (L.P.)  
50. Main Burner Orifice (L.P.)  
51. Inner Door Gasket  
52. Heat Trap Insert kit  
53. Mixing Valve  
2. Blower Temp. Switch  
3. Exhaust Pressure Switch  
4. Inlet Pressure Switch  
5. Blower Gasket  
17. Flue Baffle  
30. Flammable Vapor Sensor  
31. Sensor Harness  
18. Blower Harness  
19. T&P Relief Valve  
20. ¾ NPT PLUg  
32. Flammable Vapor Sensor  
Clip  
6. Tee and Vent Pipe Assy.  
7. Vent Adapter with Term.  
8. Intake Terminal  
21. Direct Vent Boot  
Escutcheon  
33. Thermal Well  
34. Gas Control Kit  
35. Gas Control Service tool  
36. Gas Control  
37. Gas Burner Assy (Nat.)  
38. Gas BN burner (Nat.)  
39. Main Burner Orifice (Nat.)  
9. Vent Terminal Elbow  
10. Exhaust Adapter  
22. Air Intake Boot  
23. Air Intake Boot Gasket  
24. Outer Door  
25. Right Side Inner Door  
26. Left Side Inner Door  
11. Condensate Hose Kit  
12. Flue Reducer  
13. Heat Trap Insert (outlet)  
14. Heat Trap Insert (inlet)  
27. Screw-#10-12 x ¾ HWH 40. Gas Pilot Assembly (Nat.)  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Email  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Beko Washer WMA 727 S User Manual
Belkin Computer Drive F5U210 User Manual
BenQ Computer Monitor FP731 User Manual
Black Box Network Hardware ACS2001A User Manual
Bosch Power Tools Drill 11241EVS User Manual
Brookstone Battery Charger 802209 User Manual
Brother All in One Printer 8060 User Manual
Cambridge Audio DVD Player 540D V2 User Manual
Cambridge Audio MP3 Docking Station iPod Docking System User Manual
Canon All in One Printer S830D User Manual