Black Box Network Cables BRTS 100 User Manual

OCTOBER 1994  
TS675A  
BRTS-100 ISDN Test Set  
A
1
8
TEST  
ASS  
P
ST  
F
A
TUS  
LINE  
TEST  
1
8
AIL  
PHAN  
POW  
ER  
B
TO  
M
PINS 7-8  
AUX  
TRACE  
RECEIVE  
T
LEVEL  
TRANSMIT  
ONE  
-6dB  
“D”  
GRN “1” RED  
ACTIV0ITY  
IMPEDANCE  
CONTINUITY  
BRTS-100  
ISDN T  
est Set  
INITIA  
TE  
LINE  
REV  
SPEAKERNORM  
TERMINA  
100 OHM  
TE  
OFF  
ON  
POWER  
ON  
OFF  
CUSTOMER  
SUPPORT  
INFORMATION  
Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500)  
FREE technical support 24 hours a day, 7 days a week: Call 724-746-5500 or fax 724-746-0746  
Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
NORMAS OFICIALES MEXICANAS (NOM)  
ELECTRICAL SAFETY STATEMENT  
INSTRUCCIONES DE SEGURIDAD  
1. Todas las instrucciones de seguridad y operación deberán ser leídas antes de  
que el aparato eléctrico sea operado.  
2. Las instrucciones de seguridad y operación deberán ser guardadas para  
referencia futura.  
3. Todas las advertencias en el aparato eléctrico y en sus instrucciones de  
operación deben ser respetadas.  
4. Todas las instrucciones de operación y uso deben ser seguidas.  
5. El aparato eléctrico no deberá ser usado cerca del agua—por ejemplo, cerca  
de la tina de baño, lavabo, sótano mojado o cerca de una alberca, etc..  
6. El aparato eléctrico debe ser usado únicamente con carritos o pedestales que  
sean recomendados por el fabricante.  
7. El aparato eléctrico debe ser montado a la pared o al techo sólo como sea  
recomendado por el fabricante.  
8. Servicio—El usuario no debe intentar dar servicio al equipo eléctrico más allá  
a lo descrito en las instrucciones de operación. Todo otro servicio deberá ser  
referido a personal de servicio calificado.  
9. El aparato eléctrico debe ser situado de tal manera que su posición no  
interfiera su uso. La colocación del aparato eléctrico sobre una cama, sofá,  
alfombra o superficie similar puede bloquea la ventilación, no se debe colocar  
en libreros o gabinetes que impidan el flujo de aire por los orificios de  
ventilación.  
10. El equipo eléctrico deber ser situado fuera del alcance de fuentes de calor  
como radiadores, registros de calor, estufas u otros aparatos (incluyendo  
amplificadores) que producen calor.  
11. El aparato eléctrico deberá ser connectado a una fuente de poder sólo del  
tipo descrito en el instructivo de operación, o como se indique en el aparato.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOM STATEMENT  
12. Precaución debe ser tomada de tal manera que la tierra fisica y la polarización  
del equipo no sea eliminada.  
13. Los cables de la fuente de poder deben ser guiados de tal manera que no  
sean pisados ni pellizcados por objetos colocados sobre o contra ellos,  
poniendo particular atención a los contactos y receptáculos donde salen del  
aparato.  
14. El equipo eléctrico debe ser limpiado únicamente de acuerdo a las  
recomendaciones del fabricante.  
15. En caso de existir, una antena externa deberá ser localizada lejos de las lineas  
de energia.  
16. El cable de corriente deberá ser desconectado del cuando el equipo no sea  
usado por un largo periodo de tiempo.  
17. Cuidado debe ser tomado de tal manera que objectos liquidos no sean  
derramados sobre la cubierta u orificios de ventilación.  
18. Servicio por personal calificado deberá ser provisto cuando:  
A: El cable de poder o el contacto ha sido dañado; u  
B: Objectos han caído o líquido ha sido derramado dentro del aparato; o  
C: El aparato ha sido expuesto a la lluvia; o  
D: El aparato parece no operar normalmente o muestra un cambio en su  
desempeño; o  
E: El aparato ha sido tirado o su cubierta ha sido dañada.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
TRADEMARKS USED IN THIS MANUAL  
Any trademarks mentioned in this manual are acknowledged to be the property of the  
trademark owners.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
Contents  
Chapter  
Page  
1.Specifications .....................................................................................................2  
2.Introduction .......................................................................................................3  
2.1 Overview .......................................................................................................3  
2.2 How to Use This Manual .............................................................................3  
2.3 Features ........................................................................................................4  
3.Operation ...........................................................................................................5  
3.1 Overview .......................................................................................................5  
3.2 Connecting the Unit....................................................................................5  
3.3 Powering Up the Unit..................................................................................7  
3.4 Controls and Indicators...............................................................................7  
3.5 Modes of Operation.....................................................................................8  
4.Test Procedures..................................................................................................9  
4.1 Overview .......................................................................................................9  
4.2 Comprehensive Troubleshooting Procedure ..........................................11  
4.3 Check Power...............................................................................................14  
4.4 Check Loop ................................................................................................15  
4.5 Passive Bus—Check Terminations............................................................19  
4.6 Pair Reversal...............................................................................................22  
4.7 Monitor.......................................................................................................26  
5.Technical Reference........................................................................................28  
5.1 Power-Source Indicators............................................................................28  
5.2 Activation/ Deactivation Modes ................................................................29  
5.3 AC Impedance ...........................................................................................32  
5.4 DC Continuity ............................................................................................32  
5.5 Speaker .......................................................................................................34  
Appendix: Maintenance.....................................................................................35  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
1. Specifications  
Input/ Output — (2) modular 8-pin jacks (included)  
ISDN Interface — S/ T  
Line Type — ISDN BRI  
Nominal Data Rate — 192 kbps  
Power — 9-VDC battery  
Size — 7.3"H x 3.3"W x 1.1"D (18.5 x 8.3 x 2.8 cm)  
Weight — 11 oz. (311.8 g)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 2: Introduction  
2. Introduction  
2.1 Overview  
The BRTS-100 ISDN Test Set is a portable, hand-held, communication-line  
tester that helps you troubleshoot and verify ISDN S/ T interface lines (see  
Figure 2-1). The Test Set supports a variety of comprehensive tests designed  
to help telephone and ISDN craft technicians isolate line problems.  
2.2 How to Use This Manual  
This manual is written for the user who wants a quick guide for  
troubleshooting—and for the more technical user who wants to understand  
how the unit operates.  
The novice user should read chapters one through three inclusively. The  
more advanced user can skip chapter three and read chapter four instead.  
Refer to the appendix at the end of this user’s guide for maintenance  
information, including how to change the 9-volt battery.  
The manual is divided into the following sections:  
1. Specifications  
2. Introduction Contains an overview of this manual and provides a brief  
description of the Test Set’s features.  
3. Operation Describes how the unit operates, including the controls and  
indicators. This chapter also contains suggested test configurations.  
4. Test Procedures — Explains various product applications and some  
suggested step-by-step troubleshooting guides.  
5. Technical Reference — Provides an in-depth discussion of Test Set  
components and how the Test Set performs a variety of tests.  
Appendix — Maintenance — Includes how to replace the 9- VDC battery  
and the 8-pin jack.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
A
1
8
TEST  
P
A
ST  
S
S
A
TUS  
L
IN  
1
8
T
F
A
E
E
S
IL  
T
P
H
POWER  
A
B
N
T
O
M
P
IN  
S
7
A
U
-
8
X
T
RECEIVE  
R
A
T
C
LEVEL  
TRANSMIT  
O
E
N
E
-6dB  
“D”  
GRN “1” RED “0”  
ACTIVITY  
IMPEDANCE  
CONTINUITY  
B
T
R
IS  
T
D
S
N
-100  
est S  
et  
INITIA  
TE  
LINE  
REV  
SPEAKERNORM  
TERMINA  
100 OHM  
TE  
OFF  
ON  
POWER  
ON  
OFF  
Figure 2-1. The BRTS-100 ISDN Test Set.  
2.3 Features  
This compact, rugged ISDN S/ T interface line test set provides many essential  
diagnostic functions. It’s easy to use, too, requiring very little knowledge  
about complex ISDN protocols. The Test Set:  
• Verifies physical layer (Layer 1) parameters.  
• Checks for D Channel Access.  
• Is lightweight and hand-held.  
• Derives power from a 9-volt battery.  
• Includes easy-to-use, Pass/ Fail LEDs that give instantaneous test results.  
• Can monitor a D Channel.  
• Samples every frame on the line (one every 250 microseconds).  
• Supports various modes of operation for fault isolation.  
• Can be used in either passive bus or point-to-point configurations.  
• Verifies DC Continuity.  
• Features Power Indication lamps that indicate battery presence and  
polarity.  
• Generates a 4-KHz test tone.  
• Includes a speaker that allows audio monitoring of line activity.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 3: Operation  
3. Operation  
3.1 Overview  
You can operate the BRTS-100 ISDN Test Set in a variety of modes. Select  
them by turning the selector dial on the left of the unit (see Figure 3-1). The  
indicator lights (LEDs) on top of the unit indicate test results. The various  
test modes and indicator lights are explained in more detail below.  
3.2 Connecting the Unit  
In the shipping box, youll find:  
• The BRTS-100 ISDN Test Set.  
(1) 9-volt battery.  
• An RJ-45-to-RJ-45 cable.  
(4) RJ-45-to-alligator-clips cable.  
Attach one end of the RJ-45-to-RJ-45 cable to either port A or port B at the top  
of the Test Set. Attach the other end to a standard 8-pin phone jack. Attach  
one end of the second cable (the RJ-45-to-alligator-clips) to the A or B port on  
the Test Set and the other end to a telephone block. The alligator clips are  
color coded as follows:  
COLOR  
Black  
Red  
Green  
Yellow  
SIGNAL  
TX  
RX  
RX  
TX  
PIN NUMBER  
3
4
5
6
You can use the Test Set in either a point-to-point or a passive-bus mode  
(see Figure 3-2).  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
INDICATOR LEDS  
I/O PORTS A & B  
(8-PIN CONNECTORS)  
TEST MODE  
SELECT DIAL  
A
1
8
TEST  
P
A
ST  
S
S
A
TUS  
L
IN  
1
8
T
F
A
E
E
S
I
L
T
SPEAKER  
P
H
POWER  
A
B
N
T
O
M
P
IN  
S
7
A
U
-
8
X
T
RECEIVE  
R
A
T
C
LEVEL  
TRANSMIT  
O
E
N
E
-6dB  
“D”  
GRN “1” RED “0”  
ACTIVITY  
IMPEDANCE  
CONTINUITY  
B
T
R
IS  
T
D
S
N
-100  
est S  
et  
INITIA  
TE  
LINE  
REV  
SPEAKERNORM  
TERMINA  
100 OHM  
TE  
OFF  
ON  
POWER  
ON  
OFF  
INDICATOR LED  
FEATURE BUTTONS  
Figure 3-1. BRTS-100 ISDN Test Set controls and indicators.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 3: Operation  
TO NT1  
A
TERMINAL  
1
8
1
8
B
BRTS-100  
ISDN TEST UNIT  
PASSIVE BUS  
TO NT1  
A
1
8
1
8
B
BRTS-100  
ISDN TEST UNIT  
POINT-TO-POINT  
Figure 3-2. Connecting the Test Set for point-to-point or passive-bus  
configurations.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
To connect the Test Set in a point-to-point configuration, simply connect the  
8-pin plug to either the A or B port located on top of the unit. To connect  
the Test Set in a passive bus configuration, connect the line from the NT1 to  
either the A or B port, and connect the termi-nal to the other port. The ports  
are parallel, so they can be used interchangeably (see Figure 3-2).  
3.3 Powering Up the Unit  
Power up the Test Set up by depressing the POWER feature button (Figure 3-  
1). During operation, the unit automatically performs a battery check. If the  
battery is low, the unit will beep for approximately 30 minutes.  
AUTOMATIC POWER DOWN. If the Test Set does not sense any activity on  
the line for approximately 10 minutes, it will automatically power down. In a  
4-KHz Tone Trace, the Automatic Power Down circuit is disabled.  
3.4 Controls and Indicators  
Feature Buttons  
Feature buttons (Figure 3-1) operate in two modes—in or out. Pushing the  
button will toggle it to the other mode.  
INITIATE — Certain test modes require that you press the INITIATE key.  
Whenever this is necessary, the INITIATE lamp (yellow LED) will light.  
LINE — Lets the user put the loop in NORMal or REVerse modes. In  
REVerse mode, the Test Set transposes the transmit and receive pairs.  
When the LINE button is out, the unit is in NORMal mode.  
SPEAKER — Turns on the speaker. The speaker lets you hear all the  
transmissions on the line. Voice transmissions are digitized over the ISDN  
line and therefore will not be decipherable over the speaker.  
TERMINATE — The Test Set normally provides a 100-ohm termination  
to the line. When pressed (in), the Test Set removes the 100-ohm  
termination from the line.  
POWER — Turns the Test Set on and off.  
Indicators  
PHANTOM LIGHT — Indicates the presence and polarity of battery power.  
Green light — Battery present, normal polarity.  
Red light — Battery present, polarity reversed.  
No light — No battery present.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 3: Operation  
NOTE: In reverse mode, the light indicators are opposite.  
AUXILIARY POWER LIGHT — Indicates the presence and polarity of  
auxiliary power.  
Green light — Auxiliary power present, normal polarity.  
Red light — Auxiliary power present, reverse polarity.  
No light — No auxiliary power present.  
TEST STATUS (PASS/ FAIL) LIGHTS — Reflects test status.  
INITIATE LIGHT (yellow LED) — The INITIATE button and light are  
used in testing modes. When performing certain test functions, this LED  
indicates that the INITIATE button must be pushed.  
3.5 Modes of Operation  
You can select a mode of operation by turning the selector dial  
(see Figure 3-1).  
LINE TEST — Verifies that a terminal will be able to access the D channel.  
NOTE: After selecting this function with the selector, depress the INITIATE button and the test  
will begin.  
Pass — Good line.  
Fail — Bad line.  
RECEIVE — Monitors activity on the terminal’s receive pair.  
Pass — Test Set is in SYNCH with the NT1.  
Fail — Test Set is not in SYNCH with the NT1.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
4. Test Procedures  
4.1 Overview  
This chapter gives you several suggested test procedures. However, it is by  
no means the only way to use the Test Set to isolate trouble or to verify lines.  
NOTE: The following procedures assume certain conditions exist (that procedures are  
followed in the correct order.) These conditions are described at the beginning  
of each procedure.  
TEST CONFIGURATIONS  
Test Configuration 1 — Point-to-Point — NT1 (Figure 4-1)  
To put the circuit in the point-to-point test configuration:  
1. Disconnect the terminal.  
NOTE: With a passive bus, testing the S/T interface may disrupt the operation of other  
devices on the bus.  
2. Connect the jack to either Port A or Port B of the Test Set.  
3. The Test Set should be terminated; the TERMINATE button should  
be out.  
BRTS-100 UNIT  
NT1  
POINT TO POINT — NT1  
Figure 4-1. Test Configuration 1.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
NT1  
TERMINAL  
UNDER  
TEST  
BRTS-100 UNIT  
Figure 4-2. Test Configuration 2.  
Test Configuration 2 — Passive Bus (Figure 4-2)  
To put the terminal in the Passive Bus Test Configuration:  
1. Disconnect the terminal.  
NOTE: With a passive bus, the S/T interface may disrupt the operation of the other devices  
on the bus.  
2. Connect the S/ T jack to Port B of the Test Set.  
3. Connect the terminal to Port A of the Test Set.  
4. The Test Set should be unter-minated; the TERMINATE button  
should be in.  
Test Configuration 3 — Point-to-Point — Terminal (Figure 4-3)  
To put the circuit in the Point-to-Point — Terminal configuration:  
1. Disconnect the terminal.  
2. Connect the terminal to the Test Set’s A or B port.  
3. Put the Test Set in REVerse mode, LINE button in.  
4. The Test Set should be terminated; the TERMINATE button should  
be out.  
TERMINAL  
BRTS-100 UNIT  
POINT TO POINT — TERMINAL  
Figure 4-3. Test Configuration 3.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
4.2 Comprehensive Troubleshooting Procedure  
This troubleshooting guide is for the user who is either installing a new line  
and wants to verify the S/ T interface, or has a problem with an in-service  
ISDN terminal. It is a comprehensive procedure which uses virtually all  
of the Test Set’s testing capabilities and features.  
This Procedure uses other test procedures outlined in this section.  
If you identify a problem at any point in this procedure, stop the test and  
fix the problem. Then repeat the procedure from the beginning. See the  
comprehensive flow chart, Figure 4-4, for an outline of the operations  
performed in this test.  
1. Put the circuit in the Point-to-Point Test Configuration (Configuration  
1). If youre installing a passive bus, start at the port closest to the NT1.  
2. Power up the Test Set.  
3. Perform the CHECK POWER test procedure (see page 14).  
4. Make sure that the Test Set is in NORMal mode; the LINE button should  
be out.  
5. Put the Test Set in the LINE TEST test mode.  
6. Press the INITIATE button.  
7. a. If the Red Test Status Light lights up, perform the CHECK LOOP test  
procedure (see page 15).  
b. If the Red Test Status Light flashes, the problem could be jitter in the  
NT1 or noise on the line. Check the NT1. There’s no need for any  
further testing.  
c. If the Green Test Status Lamp lights up, continue on to step eight.  
8. Put the circuit into its normal operating configuration. (Connect all  
terminals to the S/ T interface.)  
9. a. If the terminal works, there is no need to proceed any further.  
b. If the terminal does not work, proceed to step 10.  
10. a. If the circuit is point-to-point, skip steps 11 through 16, and go to  
step 17.  
b. If the circuit is a passive bus, proceed to step 11.  
11. The problem may be that all devices on the passive bus are not properly  
terminated. Verify this by performing the CHECK TERMINATIONS test  
procedure (see page 19).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
12. Put the circuit into its normal operating configuration. (Connect all  
terminals to the S/ T interface.)  
START  
Comprehensive Troubleshooting Flow Chart  
Initially, the Test Set should be in NORMAL mode  
PUT CIRCUIT IN  
POINT TO POINT  
CONFIGURATION  
(CONFIG. 1)  
CHECK POWER  
LINE TEST  
INITIATE  
NO  
GRN  
GOOD LINE,  
TERMINAL SHOULD  
WORK  
DOES RED  
LIGHT FLASH?  
TEST RESULT?  
RED  
YES  
PROBLEM  
COULD BE  
JITTER IN NT1,  
OR NOISE  
CHECK LOOP  
PUT CIRCUIT  
BACK TOGETHER  
ON LINE  
DONE  
YES  
TERMINAL  
WORK?  
GOOD LINE,  
DONE  
NO  
A
Figure 4-4. Comprehensive troubleshooting flow chart (1 of 2).  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
13. a. If the terminal works, there’s no need to proceed any further.  
b. If the terminal does not work, proceed to step 14.  
14. Perform the PAIR REVERSAL test procedure (see page 22).  
15. Put the circuit into its normal operating configuration. (Connect all  
terminals to the S/ T interface.)  
16. a. If the terminal works, there’s no need to proceed any further.  
b. If the terminal does not work, proceed to step 17.  
17. At this point, youve determined that theres nothing wrong physically  
with the S/ T interface. The problem is either within the terminal or  
NT1—or possibly the ISDN network. Perform the MONITOR test  
procedure (see page 26).  
A
NO  
USING PASSIVE  
MONITOR  
BUS?  
YES  
PB1 - CHECK  
DONE  
TERMINATIONS  
NO  
NO  
PB2 - PAIR  
REVERSAL  
TERMINAL  
WORK?  
TERMINAL  
WORK?  
YES  
YES  
GOOD LINE,  
DONE  
GOOD LINE,  
DONE  
Figure 4-4. Comprehensive troubleshooting flow chart (2 of 2).  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
4.3 Check Power  
Some (not all) ISDN terminals require power from the S/ T interface.  
This procedure verifies that power is received properly at the S/ T interface.  
See Figure 4-5 for an outline of the functions performed in this test.  
1. Put the circuit in Test Configuration 1.  
2. Make sure the Test Set is in NORMal mode; LINE button should be out.  
3. If the terminal requires Phantom Power (see terminal user guide) use  
the following table:  
Phantom  
Conclusion  
Light  
Green  
Power OK  
Red  
TX & RX pairs reversed  
No power being received  
None  
4. Certain terminals use what is known as PS2 power, which is delivered on  
pins 7 and 8. If your terminal uses PS2 power check the AUX light and  
use the following table:  
AUX  
Conclusion  
Light  
Green  
AUX power OK  
Red  
Pins 7 & 8 reversed  
No PS2 power being received  
None  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
CHECK POWER  
CHECK POWER  
If the terminal requires power from the line,  
this procedure will verify that power is being  
transmitted properly. Assumes the Test Set  
is in NORMAL mode.  
PUT CIRCUIT IN  
POINT TO POINT  
CONFIG. (CONFIG. 1)  
DOES  
TERMINAL  
NEED PHANTOM  
POWER?  
NO  
YES  
GRN  
DOES  
TERMINAL NEED  
PS2 POWER?  
RED  
YES  
PHANTOM  
LIGHT?  
NO  
NONE  
GRN  
RED  
AUX LIGHT?  
TX & RX  
PAIRS  
TRANSPOSED  
NO  
BATTERY  
FROM NT1  
NONE  
WIRES  
NO  
ON PINS 7  
& 8 ARE  
BATTERY  
ON PINS  
7 & 8  
POWER OK  
CROSSED  
Figure 4-5. Check power flow chart.  
4.4 Check Loop  
This procedure checks for physical impairments in the S/ T interface. See  
Figure 4-6 for an outline of the functions performed during this test. Before  
implementing this procedure, you must meet the following prerequisites:  
• The terminal should be receiving proper power (see CHECK POWER,  
page 14).  
• LINE TEST should fail.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
With the Check Loop procedure, first check to see if the transmit pairs  
(pins 3 and 6) and the receive pairs (pins 4 and 5) are reversed.  
1. Put the Test Set in REVerse mode; LINE button should be in.  
2. Put circuit in the Point-to-Point NT1 Test Configuration (Test  
Configuration 1).  
3. Put the Test Set in the LINE TEST test mode.  
4. Press the INITIATE button.  
5. a. If the Green Test Status light goes on, the Loop is reversed.  
b. If the Red Test Status light goes on, the Loop is wired properly.  
Now, try to isolate the problem between the Transmit Pair and the Receive  
Pairs.  
1. Put the Test Set back in NORMal mode by pressing the LINE button.  
2. Put the Test Set in the RECEIVE test mode.  
3. a. If the Red Test Status light goes on, there is a problem with the receive  
pair. Skip steps four and five and got to step nine.  
b. If the Green Test Status light goes on, the receive pair is good and  
theres a problem with the transmit pair.  
4. Put the Test Set in the CONTINUITY test mode.  
5. a. If the Red Test Status light goes on, there is an open in the TX pair.  
Theres no need to do any further testing.  
b. If the Green Test Status light goes on, got to step six.  
6. The problem could be that there is a short on the transmit pair. Put the  
Test Set back in the NORMal mode by pushing the LINE button (LINE  
should be out).  
7. Put the Test Set in the IMPEDANCE test mode.  
8. a. If the Red Test Status light goes on, either the NT1 is not terminated  
or theres a short in the TX pair. Theres no need to do any further  
testing.  
b. If the Green Test Status light goes on, there’s no problem with the NT1  
and no further testing is required.  
9. Perhaps the problem is that there’s no continuity on the RX pair between  
the terminal and the NT1. Put the Test Set in REVerse mode by pressing  
the LINE button (LINE button should be in).  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
CHECK LOOP  
CHECK LOOP  
Assume  
1. Power good  
2. LINE TEST failed  
3 Test Set is in NORMAL mode  
PUT CIRCUIT IN  
POINT TO POINT  
CONFIGURATION  
(CONFIG. 1)  
CHECK IF TX &  
RX PAIRS ARE  
TRANSPOSED  
SWITCH TO  
REVERSE, INITIATE  
LINE TEST  
LINE, LINE TEST  
INITIATE  
GRN  
TX & RX  
PAIRS ARE  
TRANSPOSED  
TEST STATUS?  
RED  
SWITCH TO  
NORMAL  
DONE  
LINE, RECEIVE  
A
Figure 4-6. Check loop flow chart (1 of 3)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
A
RED  
GRN  
TEST STATUS?  
SWITCH TO  
PROBLEM WITH  
TX PAIR  
REVERSE, DO  
CONTINUITY TEST  
LINE  
CONTINUITY  
CONTINUITY  
OPEN IN  
RX PAIR  
TEST STATUS?  
GRN  
GRN  
TEST STATUS?  
RED  
B
PUT BACK IN  
NORMAL MODE,  
PUT IN LEVEL  
TEST MODE  
OPEN IN  
TX PAIR  
LEVEL  
RED  
SIGNAL  
LEVEL TOO  
LOW  
TEST STATUS?  
GRN  
NT1 OR  
SWITCH NOT  
WORKING  
Figure 4-6. Check loop flow chart (2 of 3).  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
B
CHECK FOR SHORT  
IN TRANSMIT PAIR  
PUT BACK IN  
NORMAL MODE,  
PUT IN IMPEDANCE  
TEST MODE  
LINE IMPEDANCE  
NT1 NOT  
TERMINATED  
OR SHORT ON  
TX PAIR  
RED  
TEST STATUS?  
GRN  
PROBLEM  
WITH NT1  
Figure 4-6. Check loop flow chart (3 of 3).  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
10. Put the Test Set in the CONTINUITY Test Mode.  
11. a. If the Green Test Status light goes on, there is a physical connection  
between the terminal and the NT1.  
b. If the Red Test Status light goes on, there is no continuity on the  
receive pair between the terminal and the NT1. You should check  
the loop for opens. There’s no need for any further testing.  
12. The problem may be that the signal received at the NT1 is too low.  
To check this, put the Test Set back in the NORMAL mode by pushing  
the LINE button.  
13. Put the Test Set in the LEVEL test mode.  
14. a. If the Green Test Status light goes on, the terminal is receiving the  
proper level. The problem may be that either the switch or the NT1  
isnt working.  
b. If the Red Test Status light goes on, the signal level at the terminal  
is too low. Check the loop length.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
4.5 Passive Bus—Check Terminations  
When youre using a passive-bus configuration, it’s imperative that the last  
device on the bus be terminated at 100 ohms. The other devices on the bus  
must be left unterminated. Termination should be an option on each ISDN  
terminal. Refer to your terminal’s user manual to determine how to  
configure the terminal in terminated/ unterminated mode.  
See Figure 4-7 for an outline of the functions performed in this test.  
Passive Bus Configuration  
PB1  
Check Terminations  
Test Set should be in NORMAL mode  
GO TO FIRST  
DEVICE ON BUS  
NO  
YES  
IS TERMINAL  
LAST DEVICE?  
TERMINAL SHOULD  
BE TERMINATED  
TERMINAL SHOULD  
NOT BE TERMINATED  
PUT CIRCUIT IN  
CONFIG. 3, POWER  
DOWN TERMINAL  
PUT CIRCUIT IN  
CONFIG. 3, POWER  
DOWN TERMINAL  
IMPEDANCE  
IMPEDANCE  
GRN  
RED  
TEST STATUS?  
RED  
TEST STATUS?  
GRN  
ALL  
DEVICE PROPERLY  
TERMINATED  
UNTERMINATE  
TERMINAL  
DEVICES  
TERMINATE  
DEVICE  
PROPERLY  
TERMINATED  
POWER UP  
TERMINAL, GO TO  
NEXT DEVICE  
ON BUS  
Figure 4-7. Passive bus flow chart.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
1. Determine which devices are the first and last devices on the bus. The first  
device is the one closest to the NT1. The last device is the one furthest  
from the NT1. See Figure 4-8 for an example of proper device termination.  
2. Go to the first device on the bus.  
3. Put the Test Set in TERMINATED and NORMAL mode.  
4. Put circuit in Test Configuration 3.  
5. Make sure the Test Set is in REVerse mode; LINE button should be in.  
6. Power down the terminal.  
7. Put the Test Set in the IMPEDANCE test mode.  
8. a. If the Green Test Status light goes on, the terminal is terminated.  
Unterminate the terminal by following the instructions in the  
terminal’s user manual.  
b. If the Rest Test Status light goes on, no change in the termination  
is necessary.  
9. Go to the next device on the bus. If the terminal is NOT the last device on  
the bus, go to step four. Otherwise, continue on to step 10.  
10. You should be at the last device on the bus. Repeat steps four through  
seven.  
11. a. If the Green Test Status light goes on, the terminal is properly  
terminated.  
b. If the Red Test Status light goes on, the terminal is not terminated.  
Terminate the terminal by following the instructions in the terminal’s  
user guide.  
All devices on the bus should now be properly terminated.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
NT1  
FIRST DEVICE  
TERMINAL  
TERMINAL  
NOT  
TERMINAL  
TERMINATED  
NOT  
TERMINATED  
NOT  
TERMINATED  
TERMINAL  
TERMINAL  
TERMINAL  
TERMINAL  
LAST DEVICE  
NOT  
TERMINATED  
NOT  
TERMINATED  
TERMINAL  
NOT  
TERMINATED  
NOT  
TERMINATED  
SHOULD BE TERMINATED  
AT 100 OHMS  
Figure 4-8. Proper device terminations diagram.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
4.6 Pair Reversal  
When you use the passive-bus configuration, it’s imperative that all the  
transmit pairs (from terminal) be wired the same. That is to say, pins 3 and 6  
from each terminal on the bus must be wired to pins 3 and 6 of the NT1  
respectively. On a point-to-point configuration, the circuit will operate  
properly even if the pair is reversed (pin 3 [terminal] to pin 6 [NT1], pin 6  
[terminal] to pin 3 [NT1]). However, on a passive-bus configuration, if two  
terminals are wired differently, their signals, (having opposite polarity) will  
cancel each other.  
This problem, known as pair reversal, usually occurs when the installer  
accidentally transposes the pairs in the S/ T interface cable. A common  
symptom of pair reversal is that a device works when it is by itself on the bus,  
but doesnt work when other devices are present on the bus.  
To identify this condition, an additional Test Set or any terminal that  
initializes itself automatically is required (check with terminal manufacturer).  
Refer to the Pair Reversal Flow Chart in Figure 4-9 and the diagram in Figure  
4-10 for an outline of the functions performed during this test.  
This procedure assumes that LINE TEST passes on each individual port on  
the bus.  
1. Remove all terminals from the passive bus.  
2. Place the first Test Set or ISDN terminal on the last port of the passive bus.  
This will be referred to as terminal A.  
3. Terminate terminal A at 100 ohms. If youre using the Test Set as terminal  
A, the TERMINATE button should be out.  
4. If terminal A is:  
a. The Test Set, put it in the LINE TEST test mode.  
b. An ISDN terminal, power it on.  
5. Take the second Test Set, which will be known as terminal B, and connect  
it to another port on the bus.  
6. Unterminate terminal B by pressing the TERMINATE button.  
7. Put terminal B in the LINE TEST Test Mode.  
8. Press the INITIATE button.  
9. a. If the Green Test Status light goes on, terminals A and B are using the  
same polarity.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
b. If the Red Test Status light goes on, the terminals’ wires are crossed—  
pin 3 of terminal is electrically connected to pin 6 of the other  
terminal. At this point, you should check the wiring of both terminal  
A and terminal B.  
10. Repeat steps five through eight until all ports on the bus have been  
checked.  
Assume LINE TEST passe  
independently on every port.  
Test Set should be in  
NORMAL mode  
PB2  
UNPLUG ALL  
(IF ANY) TERMINALS  
FROM BUS  
PUT BRTS-100 (A)  
ON FIRST PORT ON  
BUS, UNTERMINATED  
TRANSMIT,  
INITIATE  
GREEN LIGHT  
SHOULD BE ON  
A
Figure 4-9. Pair reversal flow chart (1 of 2).  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
A
NEED TO CHECK  
ALL PORTS ON  
THE BUS  
GO TO NEXT  
OUTLET ON BUS  
PUT 2nd  
BRTS-100 (B) ON  
BUS, TERMINATED  
TERMINATE,  
TRANSMIT,  
INITIATE  
GRN  
RED  
TEST STATUS?  
WIRING THE SAME  
WIRING DIFFERENT  
ON PORT UNDER  
TEST AND PORT  
ON PORT UNDER  
TEST AND PORT  
BRTS-100 (A) IS ON  
BRTS-100 (A) IS ON  
CHECK WIRING,  
PINS 3 & 6  
NO  
YES  
ALL PAIR  
REVERSALS  
IDENTIFIED  
ALL PORTS  
CHECKED?  
UNPLUG 2nd  
BRTS-100 (B)  
Figure 4-9. Pair reversal flow chart (2 of 2).  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
NT1  
TERMINAL “A”  
BRTS-100 UNIT  
TERMINAL “B”  
BRTS-100 UNIT  
PASSIVE BUS  
MOVE BRTS-100 “B”  
TO EVERY PORT  
Figure 4-10. Pair reversal diagram.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 4: Test Procedures  
4.7 Monitor  
Use this test when youve determined theres nothing physically wrong with  
the circuit. The MONITOR procedure checks for any D channel activity.  
See the Monitor Flow Chart in Figure 4-11 for an outline of the functions  
performed during this test.  
Before using this procedure, the following prerequisites must be met:  
1. All terminals are properly terminated (CHECK TERMINATIONS).  
2. No pair reversals exist on a passive bus (PAIR REVERSAL).  
3. LINE TEST passes.  
4. Terminal does not work properly.  
5. Terminal receiving proper power (CHECK POWER).  
If all prerequisites exist, proceed with the MONITOR test procedure.  
1. Put the Test Set in UNTERMINATED and NORMAL modes.  
2. Put circuit in Test Configuration 2.  
3. Put the Test Set in the D Activity test mode.  
4. Press the INITIATE button.  
5. Try to initiate a call with the terminal.  
6. a. If the Red Test Status light flashes, the terminal is putting D channel  
data on the bus. There’s a problem with the switch. Possibly the switch  
parameters are set wrong.  
b. If the Red Test Status light does not flash, the terminal is not  
outputting any D channel data. Check your terminal.  
This section gives you the Test Set’s circuit-level information.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
MonitorAssumes
1. Test Set is in Normal Mode  
2. All Terminals are Properly  
Terminated  
3. No Pair Reversals on Passive Bus  
MONITOR  
4. LINE TEST Passes  
5. Terminal Does Not Work  
6. Terminal Receiving Proper Power  
PUT CIRCUIT IN  
PASSIVE BUS  
CONFIGURATION  
(CONFIGURATION 2)  
“D” ACTIVITY  
INITIATE  
CHECKING FOR  
D CHANNEL  
ACTIVITY  
TRY TO INITIATE  
A CALL WITH  
TERMINAL  
NO  
YES  
TERMINAL IS  
PUTTING OUT  
D CHANNEL DATA  
TERMINAL IS NOT  
SENDING ANYTHING  
RED LIGHT  
FLASH?  
CHECK  
SWITCH  
PARAMETERS  
CHECK  
TERMINAL  
Figure 4-11. Monitor flow chart.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 5: Technical Reference  
5. Technical Reference  
5.1 Power-Source Indicators  
The Phantom Feed light indicates the presence and polarity of battery power.  
In NORMal mode, the Test Set verifies that the terminal’s transmit pairs are  
positive and its receive pairs are negative. In REVerse mode, the Test Set  
verifies that the opposite (transmit negative and receive positive) is true.  
See Figure 5-1.  
The presence and polarity of Power Source 2 (Auxiliary Power), using pins  
7 and 8, can be determined by the AUX LED. Normally, Pin 7 should be  
negative and pin 8 should be positive.  
The maximum current consumption in Phantom Power (PS1) and  
Auxiliary Power (PS2) is approximately 5 mA at 34 VDC and 8.3 mA at 56  
VDC.  
POWER SOURCE 1 (PHANTOM FEED)  
POWER SOURCE 2 (AUXILIARY POWER)  
3
3
NETWORK  
TERMINAL  
+
TRANS.  
REC.  
6.6K  
6
5
6
5
POWER  
SOURCE  
1
GREEN  
RED  
PHANTOM  
FEED  
REC.  
TRANS.  
-
4
8
4
8
6.6K Ω  
+
AUX.  
FEED  
POWER 2  
-
GREEN  
RED  
7
7
POWER FEED 34-56 VPC  
CURRENT CONSUMPTION:  
APPROX. 5mA @ 34 VDC  
APPROX. 8.3mA @ 56 VDC  
7' LOOP  
Figure 5-1. Power source indicators.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
5.2 Activation/ Deactivation Modes  
The following information provides the steps that lead to an Active Link state  
and subsequent Activation/ Deactivation modes (Figure 5-2) between the Test  
Set (TE) and an NT device. The Test Set uses this Activation/ Deactivation  
procedure in Line Test, Transmit, and D Activity modes. See Figure 5-3 for a  
diagram of Info 0–Info 4.  
DIU—Deactivate Indication (Timer [32 ms] expired or Info 0 received  
[during 16 ms] after deactivation request).  
AIU—Activate Indication (Synchronous Receiver).  
ARUActivate Request (Info 1 Received).  
RSYD—Resynchronization of U-Interface (Transmission of pseudo ternary  
pulses at 96-KHz frequency after loss of synchronization of U-Interface;  
Info 2).  
ARD—Activate Request (Transmission of Info 3).  
AID—Activate Indication (Transmission of Info 4, Active Link).  
DR—Deactivate Request.  
INFO 0  
INFO 1  
ARU  
RSYD  
ARD  
INFO 2  
ARU  
INFO 3  
INFO 4  
AIU  
AID  
INFO 0  
INFO 0  
DR  
DR  
DIU  
Figure 5-2. Activation/ deactivation procedure.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 5: Technical Reference  
CCITT I.430 Info 0: No Signal  
48 bits in 250 microseconds  
TE to NT  
D
D
D
D
L
L
L
L
F
B1B1B1B1B1B1B1B1 L  
D
D
D
D
L
A
L
F
F
F
F
L B2B2B2B2B2B2B2B2 L  
D
L B1B1B1B1B1B1B1B1 L  
D
L B2B2B2B2B2B2B2B2 L  
D
D
D
D
L
L
L
L
F
F
F
F
L
L
L
L
CCITT I.430 Info 1:  
CCITT I.430 Info 2:  
CCITT I.430 Info 3:  
CCITT I.430 Info 4:  
48 bits in 250 microseconds  
NT to TE  
L B1B1B1B1B1B1B1B1 E  
F
N B2B2B2B2B2B2B2B2 E D S1B1B1B1B1B1B1B1B1 E D S2B2B2B2B2B2B2B2B2 E  
0
1
0
48 bits in 250 microseconds  
TE to NT  
L B1B1B1B1B1B1B1B1 L  
F
L B2B2B2B2B2B2B2B2 L  
D
L B1B1B1B1B1B1B1B1 L  
D
L B2B2B2B2B2B2B2B2 L  
48 bits in 250 microseconds  
NT to TE  
L B1B1B1B1B1B1B1B1 E  
F
A
N B2B2B2B2B2B2B2B2 E D S1B1B1B1B1B1B1B1B1 E D S2B2B2B2B2B2B2B2B2 E  
0
1
0
Figure 5-3. Info frames.  
Line Test/ Transmit (See Figure 5-4)  
Line Test and Transmit are exactly the same test. The test is conducted  
as follows.  
1. Upon pressing the INITIATE button, the Test Set tries to establish  
an ACTIVE link with the NT1.  
2. If the ACTIVE state is reached, the Test Set sends an alternating  
“101010” pattern over the D channel.  
3. The Test Set compares the incoming Echo bits with the outgoing D bits.  
If theyre not the same, the Test Set flashes the red LED.  
Receive Test  
The RECEIVE test checks the Test Set’s receive pair to ensure that the Test  
Set’s internal clock can synchronize itself to the master clock that’s provided  
by the NT1.  
Level Test  
In the LEVEL test mode, the Test Set measures the transmit level generated  
by the NT1 and verifies that the pulse level is above 375mVp or -6 dB, 0 to  
peak, ±10%, (per CCITT 1.430 specifications). Note that the LEVEL test is  
not included in the LINE TEST. Because many manufacturers of S/ T  
interface chips exceed the CCITT requirements, terminals using these chips  
will accept a lower pulse level.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
ECHO BITS=?  
D=01010101...  
REC.  
BRTS-100  
TRANS.  
REC.  
NT1  
TRANS.  
D=E, LINE IS GOOD, PASS  
DE, LINE IS BAD, FAIL  
Figure 5-4. Transmit and line test.  
D Activity (See Figure 5-5)  
The D Activity test is designed to run when the Test Set is bridged onto the  
S/ T interface with an ISDN terminal. D Activity will monitor the Echo bits  
for any D channel data transmitted by the terminal. The D Activity test is  
conducted as follows:  
1. Upon pressing the INITIATE button, the Test Set tries to establish an  
ACTIVE link with the NT1.  
2. If the ACTIVE state is established, the Test Set monitors the D bits and  
the red LED lights up whenever terminal activity is detected on the D  
channel (D = 0).  
ECHO BITS  
RX  
TX  
RX  
TX  
TERMINAL  
BRTS-100  
NT1  
D BITS  
RX  
TX  
Figure 5-5. D Activity.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 5: Technical Reference  
CCITT 1.430  
2.5K  
OHMS  
250  
2KHz  
20KHz 30KHz  
1MHz  
FREQUENCY  
NT & TE IMPEDANCE TEMPLATE  
FROM 0 - 30 KHz  
Figure 5-6. CCITT 1.430.  
5.3 AC Impedance  
As shown in Figure 5-6, CCITT recommends that the AC impedance at 20 to  
30 KHz should be greater than 2.5K ohms. To detect this, the Test Set puts  
an R-sense resistor in series with the device under test (Figure 5-7). A 21- KHz  
sinusoidal voltage, approximately 1V peak-to-peak, is generated. If the device  
is properly terminated, the AC voltage will be equally divided between the R-  
sense resistor and the terminating resistor. The AC impedance at 21 KHz is  
negligible compared to 100 ohms in parallel. The voltage drop across the R-  
sense resistor is fed through a pre-amp and then through a window  
comparator circuit. The window is set to detect impedance of between 40 and  
140 ohms. The low detect is 40 ohms. The high detect is 140 (min.) and 300  
(max) ohms.  
If there is no termination provided, the majority of the voltage will drop  
across the device under test, and the resultant impedance will fall outside the  
comparator window.  
5.4 DC Continuity  
The DC Continuity test assumes that the loop resistance will be within 0 to 5 K  
ohms (see Figure 5-8). A maximum of 5 mA of loop current is generated.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
AC IMPEDANCE  
DEVICE  
UNDER  
TEST  
+
-
21KHz  
GEN  
~ 1vpp  
TA/NT  
100  
3
6
ISPC  
I.C.  
SW1  
FILTER  
STATUS  
HIGH DETECT  
INDICATORS APPROX. 150 OHMS  
PRE AMP  
R-SENSE  
100Ω  
SAMPLE  
WINDOW  
&
COMPARATOR  
HOLD  
Figure 5-7. AC impedance.  
9V BATTERY  
VDD  
LOOP  
DETECT  
LOOP RESISTANCE  
0 - APPROX. 5K  
MAX. AMOUNT 5mA  
3
6
100Ω  
BRTS-100  
Figure 5-8. DC continuity.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHAPTER 5: Technical Reference  
5.5 Speaker  
The incoming frequency to the speaker is divided by eight. Since ISDN  
signals are transmitted at 96 KHz, it has to be reduced in order to be heard  
over the speaker.  
When the Test Set is in TRACE TONE mode, the incoming frequency to  
the speaker is divided by four. So a TRACE tone received by the Test Set  
will be heard at 1 KHz. See Figure 5-9.  
BRTS-100  
BRTS-100  
REC.  
4KHz  
4KHz  
TRANS.  
REC.  
÷4  
1KHz  
TRANS.  
÷4  
1KHz  
Figure 5-9. Two Test Set units used for tracing.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRTS-100 ISDN TEST SET  
Appendix: Maintenance  
The Test Set requires very little maintenance other than replacing the 9-VDC  
battery periodically and possibly replacing one or both of the two 8-pin RJ-45-  
type jack connectors.  
NOTE: Average battery life is approximately 15 hours of continuous use.  
Battery Replacement  
To replace the 9-VDC battery follow these steps and refer to Figure A-1.  
1. Using a #2 Phillips screwdriver, remove the battery cover retaining screw.  
2. Lift up on the battery cover and expose the 9-VDC battery.  
3. Replace the battery. Replace the battery cover and retaining screw.  
BATTERY COVER  
RETAINING SCREW  
BACK VIEW OF BRTS-100  
9 VOLT BATTERY  
Figure A-1. Battery replacement diagram.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX: Maintenance  
8-Pin Jack Replacement  
These connectors need to be replaced only when connections no longer  
permit a secure-tight connection or when connectors are damaged. In  
standard use, however, these connectors shouldn’t ever need to be replaced.  
Follow these steps and see Figure A-2.  
1. Remove the five screws from the Test Set back cover.  
2. Gently lift off the back cover to expose the inside of the unit. Remove the  
damaged connector(s) as indicated in Figure A-2.  
3. Secure the new jack connector to the Test Set as indicated in Figure A-2.  
4. Replace the back cover and retaining screws.  
PULL CONNECTOR(S)  
STRAIGHT OUT OF SOCKET  
RJ-45 JACKS  
FRONT PORTION OF BRTS-100  
WITH BACK COVER REMOVED  
Figure A-2. Replacing the 8-Pin Jack Connector(s).  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© Copyright 2002. Black Box Corporation. All rights reserved.  
1000 Park Drive  
Lawrence, PA 15055-1018  
724-746-5500  
Fax 724-746-0746  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Network Router F9K1003 User Manual
Brother Label Maker PT1090BK User Manual
Brother Sewing Machine Brother CP 6500 User Manual
Bushnell Telescope 78 8830 User Manual
Cabletron Systems Switch 9A426 01 User Manual
Cadco Microwave Oven CAPO 803 User Manual
Cambridge Audio Car Amplifier 550A User Manual
Casio Digital Camera QV 100 User Manual
Chromalox Electric Heater PD437 4 User Manual
Cisco Systems IP Phone OL 21853 01 User Manual