SMOKE&
STROBE
COMBO
PHOTOELECTRIC
CAT.
120V AC, 60Hz Wire-in
with two AAA Battery Backup for Alarm
Description:
7010BSL
The BRK Brands, Inc. Model Number 7010BSL is a wire-in, 120V AC 60Hz single
and/or multiple station photoelectric smoke alarm with integrated 177 candela
strobe light specifically designed for residential and institutional applications
including sleeping rooms of hospitals, hotels, motels, dormitories and other multi-
family dwellings as defined in standard NFPA 101. Model 7010BSL complies
with UL217, UL1971, CSFM, NFPA 72, HUD, FHA and other agencies that model
their codes after the above agencies. They meet building codes where AC with
battery backup, silence, photoelectric smoke alarms are required. The alarms are
interconnectable with up to 18 devices, of which 12 can be smoke alarms.
INTEGRATED
SMOKE ALARM &
STROBE LIGHT
One device includes both a strobe light
and photoelectric smoke alarm. Re-
quires only one electrical box. Saves
installation time.
The BRK 7010BSL alarms feature a photoelectric smoke sensing chamber, an in-
tegrated 177 candela strobe light, an 85dB horn and AAA battery back-up for
alarm. The Strobe Light is designed to provide hearing impaired individuals with a
visual warning of a fire. The Smart Strobe has separate flash patterns for smoke/
heat and carbon monoxide dangers (when connected to a First Alert CO alarm).
This helps a hearing impaired person better distinguish the danger present. The
177 candela Xenon strobe meets UL 1971 requirements and flashes at a rate of
an average of 60 times a minute. This alarm features two latching features and
two silence features.Alarm Latch: Easily identifies initiating alarm even after alarm
condition has subsided. Low Battery Latch: Identifies which unit is in low bat-
SMART STROBE
Separate flash patterns to distinguish
between smoke and carbon monoxide.
177 CANDELA
XENON STROBE
Powerful 177 candela xenon strobe light tery condition by blinking the green power light. Low Battery Silence: Temporarily
silence the low battery chirp for up to eight hours. Alarm Silence: Silence alarm
provides effective visual warning to
hearing impaired residents.
for several minutes. Optipath 360 technology provides 360 degrees of direct ac-
cess to the smoke sensing chamber. Replace battery without removing alarm from
ceiling. Other Contractor preferred features include a dust cover, keyhole slots
1Hz FLASH RATE
in the mounting bracket eliminate the need
60 flashes per minute rate meets
to remove the electrical box screws for
installation, two locking features
and a “Quick-Connect” wiring
harness.
ADA, ANSI 117.1, NFPA 72 and UL1971
requirements for visual signal devices.
OPTIPATH 360
TM
TECHNOLOGY
Provides 360 degrees of direct access
to the smoke sensing chamber.
BATTERY BACKUP
Two AAA batteries provide backup for
the smoke alarm during power outages.
(Note: will not power the strobe light).
Download from Www.Somanuals.com. All Manuals Search And Download.
|