BB Electronics Power Supply M3LDY User Manual

INSTRUCTION MANUAL  
CURRENT LOOP SUPPLY  
MODEL  
M3LDY  
(linearizing; field- and PC-configurable)  
WIRING  
• Do not install cables (power supply, input and output) close  
to noise sources (relay drive cable, high frequency line, etc.).  
• Do not bind the unit's cables together with cables where  
high noise levels are present. Do not install them in the same  
duct.  
BEFORE USE ....  
Thank you for choosing M-System. Before use, check the  
package you received as below.  
If you have any problems or questions with the product,  
please contact M-System’s Sales Office or representatives.  
AND ....  
PACKAGE INCLUDES:  
• The unit is designed to function as soon as power is  
supplied, however, a warm up for 10 minutes is required for  
satisfying complete performance described in the data sheet.  
Signal conditioner ....................................................... (1)  
I/O range and tag name label sheet ........................... (1)  
MODEL NO.  
Check that the model No. described on the specification label  
is exactly what you ordered.  
COMPONENT IDENTIFICATION  
INSTRUCTION MANUAL  
Body  
This manual describes the necessary points of caution when  
you use this product, including installation, connection and  
basic maintenance procedures.  
Specification Label  
The M3LDY with Option /A is programmable using the PC  
configurator software. For detailed information on the PC  
configuration, refer to the M3CON instruction manual. The  
M3CON PC Configurator Software is downloadable at M-  
(side)  
SW Setting Label  
HOW TO OPEN THE COVER WHEN SETTING DIP SW  
Hold at the top and bottom of the unit as shown below and  
slidethehousingcovergentlytoopenuntilithitsthelatching  
inside the unit.  
POINTS OF CAUTION  
CONFORMITY WITH UL  
(UL is unavailable for certain model suffix options.)  
• This equipment is suitable for use in a Pollution Degree 2  
environment.  
• This equipment is to be used with the maximum operating  
voltage 30Vrms and 42.4Vpeak or 60V DC.  
• The equipment must be mounted inside a suitable fire  
enclosure.  
Caution:  
Handle the cover carefully to protect internal components from damage.  
DO NOT pull beyond where the housing cover is latched. The plastic  
housing may be damaged.  
• Operating temperature: -25 to +55°C (-13 to +131°F)  
POWER INPUT RATING & OPERATIONAL RANGE  
• Check the power rating for the unit on the specification  
label.  
Rating 24V DC: 24V ±10%, approx. 3W  
• Power fuse: A power fuse of the rating as shown below is  
incorporated for safety. However, DO NOT replace it by the  
user.  
T 0.25A 125V  
SAFETY PRECAUTION  
• Housing Cover Fully Opened  
• Before you remove the unit or mount it, turn off the power  
supply and input signal for safety.  
ENVIRONMENT  
• Indoor use  
• When heavy dust or metal particles are present in the air,  
install the unit inside proper housing with sufficient ventila-  
tion.  
• Do not install the unit where it is subjected to continuous  
vibration. Do not subject the unit to physical impact.  
• Environmental temperature must be within -25 to +65°C  
(-13 to +149°F) with relative humidity within 0 to 95% RH in  
order to ensure adequate life span and operation.  
P. 1 / 6  
EM-2664 Rev.2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M3LDY  
EXTERNAL & INTERNAL VIEWS  
FRONT VIEW  
SIDE VIEW  
LED1 (LD1)  
10 11 12  
LED2 (LD2)  
Configuration DIP SW  
7
8
9
LED3 (LD3)  
MODE Button  
UP Button  
4 3 2 1  
OFF  
ON  
DOWN Button  
SW1  
Configurator Jack  
SW2  
8 7 6 5 4 3 2 1  
OFF  
4
5
6
SW3  
ON  
OFF  
ON  
CONFIGURATION MODE (SW2)  
Table 1  
CONFIGURATION MODE & DIP SW SETTINGS  
MODE  
DIP SW  
PC  
SW2-8  
OFF  
ON  
Configuration mode can be  
confirmed with the front LED.  
When you program the transmitter module, two configura-  
tion modes are available: Field Configuration using DIP SW  
/ control buttons, and PC Software. (The Option B type is for  
the field configuration only.)  
INPUT TYPE (SW2 & 3)  
Table 2  
INPUT TYPE  
DC current  
(isolator use)  
2-wire loop  
SW2-7  
SW3  
The internal DIP switches are used to configure input and  
output type. Once the module is configured, precise ranges  
are set up with the front control buttons using a simulator  
connectedtotheinputterminalsandamultimeterconnected  
to the output terminals as a reference.  
ON  
OFF  
OFF  
ON  
(DC supply use)  
The calibrated input and output ranges are stored in the  
internal memory. The module reads the DIP-switch-cali-  
brated configuration only once after the power supply is  
turned on. Set the switches with the power supply removed.  
Selectable I/O type and ranges are listed in Table 5 and 6.  
OUTPUT TYPE (SW2 & 1)  
Table 3  
OUTPUT  
0 – 20mA  
SW2-4 SW2-3 SW1-4 SW1-3 SW1-2 SW1-1  
OFF OFF  
OFF  
ON  
ON  
OFF OFF  
-2.5 – +2.5V  
-10 – +10V  
OFF  
ON  
ON  
OFF OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
DIP SW CONFIGURATION MODE  
Turn the SW2-8 OFF to enable the DIP SW (Field Configura-  
tion) mode as shown in Table 1.  
OUTPUT TYPE / PC CONFIG (SW1)  
Table 4  
OUTPUT  
0 – 20mA  
SW1-4  
OFF  
ON  
SW1-3  
ON  
SW1-2  
OFF  
OFF  
ON  
SW1-1  
OFF  
ON  
See Table 2 to configure the input and Table 3 for the output.  
-2.5 – +2.5V  
-10 – +10V  
OFF  
OFF  
PC CONFIGURATION MODE  
ON  
OFF  
Turn the SW2-8 ON to enable the PC Configuration mode as  
shown in Table 1. All programmable features can be set up  
on a PC regardless of other DIP SW setting except that the  
output type must be selected with the DIP SW1-1 through  
SW1-4 (See Table 4).  
For detailed information on the PC configuration, refer to the  
M3CON instruction manual.  
INPUT TYPE & RANGE  
Table 5  
Table 6  
INPUT TYPE  
MINIMUM SPAN  
2mA  
MAXIMUM RANGE  
DC Current  
0 to 20mA  
OUTPUT TYPE & RANGE  
OUTPUT TYPE  
MINIMUM SPAN  
MAXIMUM RANGE  
CONFORMANCE RANGE  
0 to 24mA  
DC Current  
1mA  
250mV  
1V  
0 to 20mA  
-2.5 to +2.5V  
-10 to +10V  
DC Voltage, Narrow Spans  
DC Voltage, Wide Spans  
-3 to +3V  
-11.5 to +11.5V  
P. 3 / 6  
EM-2664 Rev.2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M3LDY  
CHECKING  
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.  
2) DIP SW setting: Check that the switches are set to appropriate positions.  
3) Power input voltage: Check voltage across the terminal 11 – 12 with a multimeter.  
4) Input: Check that the input signal is within 0 – 100% of full-scale.  
5) Output: Check that the load resistance meets the described specifications.  
I/O RANGING & FINE ADJUSTMENTS  
After the DIP SW setting is complete, set up the precise input and output range using the front control buttons.  
The front LEDs’ colors and flashing patterns help you to easily identify the transmitter’s status and confirm the setup actions  
in each step of Calibration Modes. Please read the following explanations referring to “Calibration Flow Chart” below.  
CALIBRATION FLOW CHART  
POWER ON  
MODE  
UP  
Amber LED  
Green LED  
Red LED  
OFF  
ON  
A
G
R
LD1  
G
Control  
Buttons  
LD2  
Fine Adjustments ?  
I/O Ranging ?  
RUN MODE  
DOWN  
Blink  
LD3  
G
MODE  
MODE  
> 5s  
PUSH  
1 – 2 s  
PRESS & HOLD  
Apply simulated 0% input signal.  
1
*
LD1  
R
LD1  
0% INPUT  
CONFIGURED  
DOWN  
UP  
PUSH  
PUSH  
R
LD2  
FINE ZERO  
CALIBRATION MODE  
INPUT  
LD2  
CALIBRATION  
MODE  
G
R
100% INPUT  
CONFIGURED  
LD3  
LD3  
UP or DOWN  
Apply simulated 100% input signal.  
MODE  
MODE  
PUSH  
PUSH  
Adjust simulated input until the output meter  
shows desired 0% output.  
1
*
LD1  
R
LD1  
R
0% OUTPUT  
CONFIGURED  
DOWN  
UP  
PUSH  
PUSH  
FINE SPAN  
CALIBRATION MODE  
OUTPUT  
CALIBRATION  
MODE  
LD2  
LD2  
100% OUTPUT  
CONFIGURED  
LD3  
LD3  
UP or DOWN  
G
R
Adjust simulated input until the output meter  
shows desired 100% output.  
MODE  
MODE  
PUSH  
PUSH  
When you set 0% or 100% input/output ranges,  
keep pressing UP or DOWN button until the  
LD1 flashes for approx. 2 seconds and turns off,  
which indicates the setup is complete.  
When you release the button, the LD1 is returned  
to ON.  
LD1  
G
LD2  
RUN MODE  
If the LED does not change, the entered level may  
be inappropriate, i.e. out of usable range.  
LD3  
*1. Fine zero and calibrations are performed for 0% and 100% output regardless of the input value.  
P. 4 / 6  
EM-2664 Rev.2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M3LDY  
PREPARATION (e.g. M3LDY-R/A)  
4) Fine Span Calibration Mode: Push MODE button and  
confirm that the LD3 green light instead of LD2 is blink-  
ing.  
5) UseUP(increase)andDOWN(decrease)buttonstoadjust  
the output to 100%.  
1) Mount the DIP-SW-configured M3LDY on to a DIN rail.  
2) Connect the M3LDY to a simulator and a multimeter and  
to a DC power source as shown to the right.  
3) Turn the power supply on and wait for 10 minutes.  
6) Run Mode: Push MODE button and confirm that only the  
LD1 green light is blinking.  
Multimeter  
M3LDY  
Simulator  
+
Note 1: Calibration steps can be skipped when not needed by  
repeating pushing MODE buttons.  
+
2
3
7
8
Note 2: There is no stated order of setting 0% and 100% levels  
or no limitation of entering values for multiple times within  
one step of Calibration Mode. Signal level is stored each time  
the respective UP or DOWN button is pressed.  
DC Power Source  
11  
+
12  
I/O RANGE LABEL  
Blank I/O range labels are included in the product pack-  
age. Write in the configured ranges and put the label on  
the side above the specification label as shown below.  
INPUT & OUTPUT RANGING  
[Example]  
Setting input to 4 – 20mA DC and output to 1 – 5V DC  
1) Run Mode: Confirm that the LD1 green light is blinking.  
2) Input Configuration Mode: Press MODE button for longer  
than 5 seconds until the LD1 red light is ON and the LD2  
red light is blinking.  
3) 0% Input Ranging: Apply the desired minimum input  
level (e.g. 4mA) from the simulator and push DOWN  
button until the LD1 flashes for approx. 2 sec. and then  
turns OFF. When you release the button, the LD1 is  
returned to ON.  
The flashing LD1 means that the value is stored in the  
memory. If the LED does not change, the entered level  
may be inappropriate: too small a span, or out of usable  
range (same for all steps).  
INPUT  
OUTPUT  
4) 100% Input Ranging: Apply the desired maximum input  
level (e.g. 20mA) from the simulator and push UP button  
until the LD1 flashes for approx. 2 sec. and then turns  
OFF. When you release the button, the LD1 is returned to  
ON.  
I/O Range Label (included in the product package)  
5) Output Configuration Mode: Push MODE button and  
confirm that the LD3 red light instead of LD2 is blinking.  
6) 0% Output Ranging: Increase or decrease the simulated  
input until the meter shows the desired minimum output  
level (e.g. 1V). Push DOWN button until the LD1 flashes  
for approx. 2 sec. and then turns OFF. When you release  
the button, the LD1 is returned to ON.  
7) 100%OutputRanging:Increaseordecreasethesimulated  
input until the meter shows the desired maximum output  
level (e.g. 5V). Push UP button until the LD1 flashes for  
approx. 2 sec. and then turns OFF. When you release the  
button, the LD1 is returned to ON.  
8) Run Mode: Programming complete, push MODE button  
and confirm that only the LD1 green light is blinking.  
ZERO & SPAN ADJUSTMENTS  
After the transmitter is installed and operational, fine zero  
and span tuning can be performed as explained below. Both  
zero and span are adjustable within ±15%.  
1) Run Mode: Confirm that the LD1 green light is blinking.  
2) Fine Zero Calibration Mode: Press MODE button for 1 or  
2 seconds until the LD1 red light is ON and the LD2 green  
light is blinking.  
3) UseUP(increase)andDOWN(decrease)buttonstoadjust  
the output to 0%.  
P. 5 / 6  
EM-2664 Rev.2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M3LDY  
STATUS INDICATOR LED  
Combinations of the three front LEDs (LD1, LD2, LD3)  
indicatethetransmitter’soperatingstatusbydifferentflash-  
ing patterns.  
Amber LED  
Green LED  
OFF  
ON  
A
G
Examples are shown below.  
R Red LED  
Blink  
NORMAL OPERATION (RUN) MODE  
LD1  
LD1  
G
PC Configuration RUN Mode (Option A)  
The transmitter is configured via PC and  
is in normal operating conditions.  
DIP SW Configuration RUN Mode  
The transmitter is configured via DIP SW and  
is in normal operating conditions.  
G
LD2  
LD2  
LD3  
LD3  
ERROR MODE  
LD1  
LD1  
R
System Error  
Indicates the CPU’s communication error.  
DIP SW Error  
DIP SW configuration is inappropriate.  
A
LD2  
LD2  
Check the DIP SW setting referring to Tables 2 – 11.  
A
LD3  
A
R
LD3  
R
LD1  
LD1  
G
Output Saturated in PC Configuration Mode  
(Option A)  
Output Saturated in DIP SW Configuration Mode  
The output is saturated.  
G
LD2  
LD2  
The output is saturated.  
(approximately below -15% or above +115%)  
(approximately below -15% or above +115%)  
LD3  
LD3  
A
A
M-SYSTEM WARRANTY  
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such  
productwasoriginallypurchasedifsuchproducthasbeenusedundernormaloperatingconditionsandproperlymaintained,M-System'ssoleliability,andpurchaser'sexclusiveremedies,  
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To  
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.  
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED  
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR  
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.  
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]  
P. 6 / 6  
EM-2664 Rev.2  
Download from Www.Somanuals.com. All Manuals Search And Download.  

3M Snowshoes 747 User Manual
Actiontec electronic Network Router GE344000 01 User Manual
Adder Technology Network Router AVM208MP User Manual
AKG Acoustics Microphone D12 VR User Manual
Alesis Portable Speaker MK2 User Manual
Altec Lansing Speaker IM5 User Manual
Alvin Mobility Aid DC207B User Manual
American Standard Hot Tub T038990 User Manual
BC Speakers Speaker 18 RXB User Manual
Beko CRT Television 24 User Manual