BB Electronics Network Card DTB Series User Manual

DELTA Temperature Controller  
DTB Series  
User Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Specifications  
Input Voltage  
100 to 240VAC 50/60Hz  
85% to 110% of rated voltage  
5VA max.  
EEPROM 4K bit (non-volatile memory (number of writes: 100,000)  
2 line x 4 character 7-segment LED display Process value(PV): Red color, Set point(SV): Green color  
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK  
Operation Voltage Range  
Power Consumption  
Memory Protection  
Display Method  
Sensor Type  
Control Mode  
3-wire Platinum RTD: Pt100, JPt100  
Analog input: 0~5V, 0~10V, 0~ 20 m A, 4~20 m A, 0~50mV  
PID, ON/OFF, Manual or PID program control (Ramp/Soak control)  
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load  
Voltage pulse output: DC 14V, Max. output current 40mA  
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω)  
Linear voltage output: 0~5V, 0~10V  
Control Output  
Display Accuracy  
Sampling Rate  
0 or 1 digit to the right of the decimal point (selectable)  
Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan  
MODBUS ASCII / RTU communication protocol  
RS-485 Communication  
Vibration Resistance  
Shock Resistance  
Ambient Temperature  
Storage Temperature  
Altitude  
10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions  
Max. 300m/ s2, 3 times in each 3 axes, 6 directions  
0 oC to +50 oC  
-20 oC to +65 oC  
2000m or less  
Relative Humidity  
35% to 80% (non-condensing)  
5
Temperature Sensor Type and Temperature Range  
Input Temperature Sensor Type  
Register Value  
LED Display  
Temperature Range  
0~50mV Analog Input  
17  
-999 ~ 9999  
4~20mA Analog Input  
0~20mA Analog Input  
0V~10V Analog Input  
0V~5V Analog Input  
16  
15  
14  
13  
12  
11  
10  
9
-999 ~ 9999  
-999 ~ 9999  
-999 ~ 9999  
-999 ~ 9999  
-200 ~ 600oC  
-20 ~ 400oC  
-200 ~ 800oC  
-200 ~ 500oC  
-200 ~ 850oC  
100 ~ 1800oC  
0 ~ 1700oC  
0 ~ 1700oC  
-200 ~ 1300oC  
0 ~ 600oC  
-200 ~ 400oC  
-100 ~ 1200oC  
-200 ~ 1300oC  
Platinum Resistance (Pt100)  
Platinum Resistance (JPt100)  
Thermocouple TXK type  
Thermocouple U type  
Thermocouple L type  
Thermocouple B type  
Thermocouple S type  
Thermocouple R type  
Thermocouple N type  
Thermocouple E type  
Thermocouple T type  
Thermocouple J type  
Thermocouple K type  
8
7
6
5
4
3
2
1
0
Note 1 : An external 250Ω precision resistor should be connected when the current input is selected as the input temperature sensor type..  
Note 2 :  
(Operation mode) must be set if user wish to specify decimal point position. Except for the thermocouple B, S, R type, the decimal  
point positions of all the other thermocouple type input sensors can be set.  
The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the input temperature sensor type, -999  
indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~ 2000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is  
equal to 0.01mA.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
Operation  
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation mode.  
Press the  
key to switch to regulation mode. If the  
key is pressed for more than 3 seconds, controller will switch to the initial setting  
mode. Pressing the  
key while in the regulation mode or initial setting mode, forces the controller to return to the operation mode.  
PV/SV: Sets the temperature set point and displays the temperature process value. Use  
Setting method: While in any function mode, press the key to select the desired function and use the  
Press key to save the changes.  
The next flow chart shows how to switch for settings and internal functions:  
Press key less than 3 sec  
keys to set the temperature set point.  
keys to change settings.  
Press  
key more than 3 sec  
Press key  
Regulation Mode  
Operation Mode  
Initial Setting Mode  
Press  
key  
Regulation Mode  
Auto-tuning  
Operation Mode  
Initial Setting Mode  
Use  
key to  
Set input type  
set temperature set point  
(Set in PID control and RUN mode)  
Press  
Press  
Press  
Press  
4 groups PID modes (n=0~3). When n=4,  
PID control is auto regulated.  
Control setting RUN or STOP  
Set temperature unit  
do not display when analog input  
Press  
Press  
PD control offset  
setting  
(When PID control is ON and Ti=0,  
set the value of PdoF.  
Set upper-limit of  
temperature range  
Start pattern setting (PID  
program control and  
Time setting.  
Press  
Press  
Press  
Press  
Set lower-limit of  
temperature range  
Decimal point position selection  
(except for B, S, R type, all the  
other types can be set)  
Heating hystereisis setting  
(Set in ON/OFF control mode)  
Press  
Press  
Cooling hystereisis setting  
(Set in ON/OFF control mode)  
Press  
Upper-limit alarm 1  
Select control mode  
(This parameter is available only when  
ALA1 function enables)  
(See "Pattern and set Editing  
selection" for detail)  
Press  
Press  
Heating/Cooling  
or  
Select heating/cooling control  
or dual loop output control  
Lower-limit alarm 1  
control cycle setting  
(This parameter is available only when  
ALA1 function enables)  
(Set in PID control mode)  
Press  
Press  
Press  
Control cycle setting  
of 2nd output group  
(Set in PID control and Dual Loop  
output control mode)  
Alarm 1 mode setting  
Press  
Upper-limit alarm 2  
(This parameter is available only when  
ALA2 function enables)  
Press  
Press  
P value of 1st & 2nd output grou  
during dual loop output control  
P value of 2nd output group =  
(P value of 1st output group) x  
Lower-limit alarm 2  
Alarm 2 mode setting  
Press  
(This parameter is available only when  
ALA2 function enables)  
Press  
Press  
Dead Band (Set in Dual Loop  
output control mode)  
Alarm 3 mode setting  
Press  
Upper-limit alarm 3  
(This parameter is available only when  
ALA3 function enables)  
Press  
Press  
Switch setting for feedback  
Lower-limit alarm 3  
Set system alarm  
Press  
signal of valve. (Display when  
valve control is ON)  
Press  
(This parameter is available only when  
ALA3 function enables)  
Press  
Communication write function  
enable/disable  
Automatically regulate  
feedback value.  
(Display when valve control is ON)  
Setting lock mode  
Press  
Press  
Press  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Display and adjust output value  
ASCII, RTU communication  
format selection  
Time setting for valve from  
of 1st output group  
(Display in PID control mode and manual  
RUN mode)  
full close to full open. (Display when  
valve control is ON)  
Press  
Press  
Press  
Press  
Display and adjust output value  
of 2nd output group  
(Display in dual loop PID control mode and  
manual RUN mode)  
Valve Dead Band setting.  
Communication address  
setting  
(Display when valve control is ON)  
Press  
Press  
In case of using an external CT,  
the controller displays the current  
value being measured by CT, if  
the control output is ON  
Communication baud  
rate setting  
Upper-limit regulation of  
valve output with feedback to  
controller. (Display when valve  
signal feedback function is ON)  
Press  
Press  
Press  
to return to set target temperature  
Press  
Data length setting  
Parity bit setting  
Lower-limit regulation of  
valve output with feedback to  
controller. (Display when valve  
signal feedback function is ON)  
Valve output with feedback.  
(Display when valve feedback  
function is ON)  
Press  
Press  
Regulate temperature  
deviation value  
DA value feedback of valve.  
(Display when valve feedback  
function is ON)  
Press  
Press  
Press  
Press  
Back to target temperature  
Regulate upper-limit of analog  
output value  
(The setting display when analog output)  
Press  
Stop bit setting  
to return input type setting  
Regulate lower-limit of analog  
output value  
(The setting display when analog output)  
Press  
to return to auto-tuning mode  
* 1 Scale = 2.8uA = 1.3mV for tuning output value  
PID mode selection: any one of 4 groups PID modes (n=0~3) can be selected. When n=4, program will automatically select 1 group PID that is  
most useful for target temperature.  
Select n=0~4 to  
decide PID mode.  
Press  
PID setting: n=3.  
Press  
PID setting: n=0.  
0~3 groups PID  
Press  
Proportion band setting: n=3.  
Press  
Proportion band setting: n=0.  
Press  
Press  
Ti setting: n=3.  
Press  
Ti setting: n=0.  
Press  
Td setting: n=3.  
Press  
Td setting: n=0.  
Integral deviation setting: n=3.  
AT setting.  
Integral deviation setting: n=0.  
AT setting.  
Press  
back to PID deviation setting  
Press  
back to PID deviation setting  
Pattern and step editing selection: edit  
in  
parameter. The following display is the example operation of pattern No. 0.  
Select desired editing pattern  
number  
select OFF  
Edit temperature of step No. 0  
of pattern No. 0  
Select actual step No. when  
program control is executing  
Press  
Press  
Press  
Press  
select number  
Press  
Exit pattern and step editing selection  
Edit time of step No. 0 of  
pattern No. 0, unit is hh.mm  
Set additional execution cycle  
number(0 to 99)  
Switch to and continue setting  
Set link pattern, OFF indicates  
the program end  
Set step No. 07 in order  
Edit temperature of step No. 7  
of pattern No. 0  
Press  
mode  
to return pattern No. editing  
Press  
Press  
Edit time of step No. 7 of  
pattern No. 0, unit is hh.mm  
to set actual step No.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
Dual Loop Output Control (Heating / Cooling Control)  
Dead band  
Temperature control can be achieved either by heating or cooling. In DTB series, heating and  
cooling can be operated simultaneously (Dual Loop output control) to perform temperature  
control. When Dual Loop output control are used, two control outputs must be connected to the  
heating and cooling devices. Please refer to the following for the operation:  
Heating hysteresis  
Cooling hysteresis  
ON  
: This parameter is used to select heating or cooling action if operate either heating or  
Heating  
OFF  
Cooling  
cooling function in this controller. When selecting  
control, and when selecting , 1st output group is cooling (forward) control. At this  
moment, 2nd output group is regarded as an alarm output. If user select or , it  
indicates that user can operate Dual Loop output control function in this controller. When  
selecting , 1st output group is heating (reverse) control and 2nd output group is cooling  
, 1st output group is heating (reverse)  
PV  
Set point  
Figure 1. Output operation of ON/OFF control  
during dual loop output control  
Dead band: dead  
band width=positive  
Output  
(forward) control. When selecting  
, 1st output group is cooling (forward) control and 2nd  
output group is heating (reverse) control.  
In DTB series, P (Proportional Band), I(Integral Time) and D(Derivative Time) parameters are  
automatically set by using the Auto-tuning (AT) function.  
Heating  
Cooling  
PV  
: This parameter is for the control mode that must be Dual Loop output control with PID  
control method configured. The value of P, I and D of 1st output group can be set immediately.  
0
Set point  
The P value of 2nd output group is equal to (P value of 1st output group) x  
and the  
value of I and D of 2nd output group are the same as the value of I and D of 1st output group.  
Figure 2. PID control, Dead Band is positive  
: Dead Band, shown as the following figure 1, 2 and 3. This parameter sets an area in  
which the heating and cooling control output is 0 centering around the set point in a Dual Loop  
output control mode.  
Dead band: dead  
Output  
band width=negative  
: Settings lock. To avoid incorrect operation, two key lock functions are provided.  
: Lock 1 can lock all settings. All parameters and temperature settings can be locked to  
disable changes.  
: Lock 2 can lock settings except the SV (Set point) value. All  
Heating  
Cooling  
parameters and temperature settings can be locked with the exception of the SV value. Press  
PV  
0
and key simultaneously, the “Lock” status can be released.  
Set point  
Figure 3. PID control, Dead Band is negative  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
Alarm Outputs  
There are up to three groups of alarm outputs and each group allows thirteen alarm types in the initial setting mode. The alarm output is  
activated whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.  
Set  
Value  
Alarm Type  
Alarm Output Operation  
0
1
Alarm function disabled  
Deviation upper- and lower-limit:  
This alarm output operates when PV value is higher than the setting value SV+(AL-H) or lower than the  
setting value SV-(AL-L).  
Output is OFF  
ON  
OFF  
SV  
SV  
SV+(AL-H)  
SV+(AL-H)  
SV-(AL-L)  
ON  
2
3
Deviation upper-limit:  
OFF  
This alarm output operates when PV value is higher than the setting value SV+(AL-H).  
ON  
Deviation lower-limit:  
OFF  
This alarm output operates when PV value is lower than the setting value SV-(AL-L).  
SV  
SV-(AL-L)  
ON  
4
5
6
Reverse deviation upper- and lower-limit:  
This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and the setting  
value SV-(AL-L).  
OFF  
SV-(AL-L) SV  
SV+(AL-H)  
AL-H  
ON  
Absolute value upper- and lower-limit:  
This alarm output operates when PV value is higher than the setting value AL-H or lower than the setting OFF  
value AL-L.  
AL-L  
AL-L  
ON  
Absolute value upper-limit:  
This alarm output operates when PV value is higher than the setting value AL-H.  
OFF  
AL-H  
ON  
7
8
9
Absolute value lower-limit:  
This alarm output operates when PV value is lower than the setting value AL-L.  
OFF  
ON  
Deviation upper- and lower-limit with standby sequence:  
This alarm output operates when PV value reaches set point (SV value) and the value is higher than the  
setting value SV+(AL-H) or lower than the setting value SV-(AL-L).  
OFF  
SV-(AL-L)  
ON  
SV+(AL-H)  
SV+(AL-H)  
SV  
SV  
Deviation upper-limit with standby sequence:  
This alarm output operates when PV value reaches set point (SV value) and the reached value is higher  
than the setting value SV+(AL-H).  
OFF  
ON  
10  
11  
Deviation lower-limit with standby sequence: this alarm output operates when PV value reaches the set  
point (SV value) and the reached value is lower than the setting value SV-(AL-L).  
OFF  
SV-(AL-L) SV  
ON  
OFF  
Hysteresis upper-limit alarm output:  
This alarm output operates if PV value is higher than the setting value SV+(AL-H). This alarm output is  
OFF when PV value is lower than the setting value SV+(AL-L).  
AL-L  
AL-H  
ON  
12  
13  
Hysteresis lower-limit alarm output:  
This alarm output operates if PV value is lower than the setting value SV-(AL-H). This alarm output is OFF  
when PV value is higher than the setting value SV-(AL-L).  
OFF  
AL-L  
AL-H  
ON  
CT alarm output:  
This alarm operates when the current measured by transformer (CT) is lower than AL-L or higher than  
AL-H (This alarm output is available only for the controller with current transformer).  
OFF  
AL-L  
AL-H  
SV  
14  
15  
16  
17  
18  
When program control is end status, alarm output is ON.  
When RAMP UP status happens to PID program control, alarm output is ON.  
When RAMP DOWN status happens to PID program control, alarm output is ON.  
When SOAK status happens to PID program control, alarm output is ON.  
When RUN status happens to PID program control, alarm output is ON.  
Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
Current Transformer (CT) Function  
The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the controller, change the  
corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn to operation mode and set the current lower-limit and  
current upper-limit. You can set current alarm range between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A.  
10  
EVENT Inputs Function  
5
There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series.  
EVENT1: RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the communication. User also can  
control RUN/STOP operation by EVENT 1 in DTB series. The control output is ON if the circuit of EVENT 1 is open when the  
controller is operating. Otherwise, the controller will stop output if the circuit of EVENT 1 is short or when the system parameter of  
the controller is set to STOP mode.  
EVENT2: DTB series allows user can switch two temperature setting value by changing the status (open/short) of EVENT 2. Each  
temperature setting value has independent control parameters.  
11  
PID Program Control (Ramp/Soak Program Control)  
Description of Function and Parameters Setting:  
PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps (step No. 0 ~ 7), one Link  
Pattern parameter, one Cycle parameter and one Actual Step parameter.  
Start Pattern:  
is in operation mode and it is used to set the Start Pattern of PID program control (This parameter appear in  
mode only).  
Steps : Include set point X and execution time T, these two parameters setting. The set point (SV) should reach temperature X after the period  
of execution time T. If the set point is the same as the result of the previous setting, then it is called Soak program control. If not, then it  
is called Ramp program control. Therefore, PID program control is also called Ramp/Soak program control. The default of step No. 0  
in this controller is Soak program control. The controller will control the temperature (PV) to reach the set point X and then keep the  
temperature at set point X. The period of execution time is time T which provided by step No. 0.  
Link Pattern Parameter : For example, when set  
to 2, it indicates that pattern No. 2 will execute next after the execution of pattern No.  
0. If set to  
, it indicates the program will stop after executing the current pattern and the temperature will keep at the set point of  
the last step.  
Cycle Parameter : Additional execution cycle number. For example, when set  
to 2, it indicates that pattern No. 4 should execute twice  
in addition. Include origin one time execution, total execute three times.  
Actual Step Parameter : Execution step number per pattern (can set to 0 ~ 7). For example, when set  
to 2, it indicates that pattern No  
7 will not execute other steps than step 0 to step2.  
Execution : When  
is set to  
, the program will start to execute in order from the step 0 of start pattern. When  
is set to  
, the program will stop and the control output is disabled. When  
is set to  
, the program will stop and the temperature  
at that time will be controlled at the set point before program stop. Select  
again, then the program will restart and execute from  
step 0 of start pattern. When  
is set to  
, the program will hold and the temperature at that time will be controlled at the set  
point before program hold. Select  
of the time.  
again, then the program will follow the step before hold and start to execute through the rest  
Display : During PID program control, the SV default display is P-XX, P indicates the current execution pattern and XX indicates the current  
execution step. Press  
to change the display item. After select  
, press  
, press  
key, and then the temperature set point of the  
key, and then the residual time of the current  
current execution step will display on SV display. After select  
execution step will display on SV display.  
12  
PID Control  
One group can be selected from any one of 4 groups PID parameters (P, I, D, IOF) for PID control. After AT, PID value and temperature setting  
will be stored in the selected one group. : PIDn, n=0~4 from which 0~3 correspond to each PID parameter. : n=4, auto PID  
parameter. Program will automatically select a most useful PID parameter based on current temperature setting. Displayed SV values  
correspond to  
: Temperature setting corresponded to the selected PID parameter via user-defined or AT.  
~
~
~
Valve Control:  
When use valve control as output control, there are 2 Relay outputs for motor forward/reverse control, one (output 1) for valve open the other  
(output 2) for valve close. The output volume is controlled by valve open/close and it can be set with feedback function enabled or disabled.  
When feedback is disabled, output 1 will keep output while valve fully opens and output 2 will keep output while valve fully closes. But if  
feedback is enabled, please follow the parameter setting for valve control as follows:  
: Time for valve from full close to full open.  
: Dead Band setting of valve. The value of current valve output minus previous one must be greater than Dead Band value; otherwise,  
valve will remain OFF.  
: Signal feedback setting, ON for enabling feedback and OFF for disabling feedback.  
When  
a.  
set to ” 1”, it means signal feedback function is activated and will come up selections as follows:  
: Upper/Lower limit of valve feedback by auto-tuning. must set to for showing up this selection.  
b.  
: D/A value when value fully opens. Set  
: D/A value when value fully closes. Set  
to be ”1” for auto setting or ”0” for manual setting.  
to be ”1” for auto setting or “0” for manual setting.  
c.  
Note: If feedback function setting is with problem, program will see the setting as feedback disabled.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
RS-485 Communication  
Supporting transmission speed: 2400, 4800, 9600, 19200, 38400bps  
1.  
2.  
3.  
4.  
Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2  
Communication protocol: Modbus (ASCII or RTU)  
Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits data (Max.  
16 bits). 05H to write 1 (one) bit into register.  
5.  
Address and Content of Data Register:  
Address  
Content  
Explanation  
Measuring unit is 0.1, updated one time in 0.4 second  
The following reading value display indicates error occurs:  
8002H : Initial process (Temperature value is not got yet)  
8003H : Temperature sensor is not connected  
1000H Process value (PV)  
8004H : Temperature sensor input error  
8006H : Cannot get temperature value, ADC input error  
8007H : Memory read/write error  
1001H Set point (SV)  
Unit is 0.1, oC or oF  
1002H Upper-limit of temperature range  
1003H Lower-limit of temperature range  
1004H Input temperature sensor type  
1005H Control method  
The data content should not be higher than the temperature range  
The data content should not be lower than the temperature range  
Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail  
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control  
0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating  
1006H Heating/Cooling control selection  
1007H 1st group of Heating/Cooling control 0~99, 0:0.5 sec  
cycle  
1008H 2nd group of Heating/Cooling control 0~99, 0:0.5 sec  
cycle  
1009H PB Proportional band  
100AH Ti Integral time  
0.1 ~ 999.9  
0~9999  
100BH Td Derivative time  
100CH Integration default  
0~9999  
0~100%, unit is 0.1%  
100DH Proportional control offset error value, 0~100%, unit is 0.1%  
when Ti = 0  
100EH The setting of COEF when Dual Loop 0.01 ~ 99.99  
output control are used  
100FH The setting of Dead band when Dual -999 ~ 9999  
Loop output control are used  
1010H Hysteresis setting value of the 1st  
output group  
0 ~ 9999  
1011H Hysteresis setting value of the 2nd  
output group  
0 ~ 9999  
1012H Output value read and write of Output Unit is 0.1%, write operation is valid under manual tuning mode only.  
1
1013H Output value read and write of Output Unit is 0.1%, write operation is valid under manual tuning mode only.  
2
1014H Upper-limit regulation of analog linear 1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)  
output  
1015H Lower-limit regulation of analog linear 1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)  
output  
1016H Temperature regulation value  
1017H Analog decimal setting  
1018H Time for valve from full open to full  
close  
-999~+999, unit: 0.1  
0 ~ 3  
0.1~999.9  
1019H Dead Band setting of valve  
0~100%; unit: 0.1%  
101AH Upper-limit of feedback signal set by 0~1024  
valve  
101BH Lower-limit of feedback signal set by 0~1024  
valve  
101CH PID parameter selection  
0~4  
101DH SV value corresponded to PID value Only valid within available range, unit: 0.1 scale  
1020H Alarm 1 type  
1021H Alarm 2 type  
1022H Alarm 3 type  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
0 : None (default), 1~3 : Set Alarm 1 to Alarm 3  
1023H System alarm setting  
1024H Upper-limit alarm 1  
1025H Lower-limit alarm 1  
1026H Upper-limit alarm 2  
1027H Lower-limit alarm 2  
1028H Upper-limit alarm 3  
1029H Lower-limit alarm 3  
102AH Read LED status  
102BH Read pushbutton status  
102CH Setting lock status  
102DH CT read value  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
Please refer to the contents of the “Alarm Outputs” for detail  
b0 : Alm3, b1: Alm2, b2: F, b3: oC, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT  
b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push  
0 : Normal, 1 : All setting lock, 11 : Lock others than SV value  
Unit: 0.1A  
102FH Software version  
V1.00 indicates 0x100  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
1030H Start pattern number  
0 ~ 7  
1040H~ Actual step number setting inside the  
1047H correspond pattern  
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N  
1050H~ Cycle number for repeating the  
1057H execution of the correspond pattern  
1060H~ Link pattern number setting of the  
1067H correspond pattern  
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times  
0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution pattern number after executing  
the current pattern  
Pattern 0~7 temperature set point  
setting; Pattern 0 temperature is set to -999 ~ 9999  
2000H~2007H  
2000H~  
203FH  
2080H~ Pattern 0~7 execution time setting  
20BFH Pattern 0 time is set to 2080H~2087H  
Time 0 ~ 900 (1 minute per scale)  
6.  
Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit clear)  
0810H Communication write-in selection  
Communication write in disabled: 0 (default), Communication write in enabled: 1  
0811H Temperature unit display selection  
0812H Decimal point position selection  
0813H AT setting  
oC / linear input (default) : 1 , oF : 0  
Except for the thermocouple B, S, R type, all the other thermocouple type are valid. (0 or 1)  
OFF: 0 (default), ON : 1  
0814H Control RUN/STOP setting  
0: STOP, 1 : RUN (default)  
STOP setting for PID program  
control  
0: RUN (default), 1: STOP  
0815H  
Temporarily STOP for PID program  
control  
0: RUN (default), 1: Temporarily STOP  
0816H  
0817H Valve feedback setting status  
0818H Auto-tuning valve feedback status  
0: w/o feedback (default), 1: feedback function  
0: Stop AT (default), 1: Start AT  
7.  
Communication Transmission Format : Command Code: 02: read N bits, 05: write 1 bits, 03: read N words, 06:  
write 1 words  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
Panel Cutout and Terminals Identification  
Terminals Identification  
Panel Cutout (dimensions are in millimeter and inch)  
65.0 min.  
(2.56)  
DTB4824  
DTB4824  
OUT 2/  
OUT 1  
ALM  
RS-485  
-
+
DATA+ DATA-  
V
-
+
-
V
+
10  
8
2
9
3
11  
5
12  
6
7
1
4
L
N
Tc  
IN  
-
RTD  
AC 100~240V  
50/60 Hz 5VA  
+
!
+0.6  
-0  
+0.02  
-0  
+
-
44.8  
(1.76)  
mm  
(in)  
DTB4848  
DTB4848  
(EVENT & CT selection)  
DTB4848  
(NO EVENT & CT)  
65.0 min.  
(2.56)  
OUT1  
L
14VDC  
or  
NO  
-
OUT2/  
ALM3  
11  
1
2
3
4
6
7
8
9
AC 100~240V  
50/60 Hz  
5VA  
4~20mA  
or  
0~10V  
NO  
-
12  
+
COM  
N
ALM2  
14VDC  
13  
RTD  
+ +  
COM  
DATA-  
+
3A  
250Vac  
ALM1  
143A  
Tc  
IN  
RS-485  
DATA+  
5 10  
15250Vac  
-
-
COM  
+0.6  
-0  
+0.02  
-0  
45.0  
(1.77)  
mm  
(in)  
DTB4896  
DTB4896/DTB9696  
DATA+  
L
1
11  
12  
13  
14  
15  
16  
17  
18  
19  
AC 100~240V  
50/60 Hz  
5VA  
RS-485  
2
3
4
5
6
7
8
9
DATA-  
SG  
N
ALM2  
COM  
Ev1  
OUTPUT2/ALM3  
CT  
Ev2  
COM  
+
ALM1  
NC  
14VDC  
5A  
250Vac  
NO  
NC  
-
COM  
OUTPUT1  
RTD  
5A  
250Vac  
NO  
+
IN  
+
Tc  
-
-
14VDC or 4~20mA  
or  
0~10V  
10 20 COM  
-
+
DTB9696  
DTB9696RRV  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
External Dimensions  
Dimensions are in millimeter (inch)  
DTB4824  
DTB4848  
44.75 mm  
(1.76 in)  
45.0 mm+0.6  
0
(1.77 in)+0.02  
0
44.8 mm  
(1.76 in)  
9.5 mm  
(0.37 in)  
80.0 mm  
(3.15 in)  
48.0 mm  
(1.89 in)  
3.4 mm  
(0.13 in)  
48.0 mm  
(1.89 in)  
99.8 mm  
(3.93 in)  
DTB4896  
DTB9696  
44.0 mm  
(1.73 in)  
91.0 mm+0.6  
(3.58 in)+00.02  
44.5 mm+0.6  
0
0
(1.75 in)+0.02  
0
96.0 mm  
(3.78 in)  
15.8 mm  
(0.62 in)  
79.2 mm  
(3.12 in)  
12.8 mm  
(0.50 in)  
48.0 mm  
(1.89 in)  
79.2 mm(3.12 in)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Mounting  
Mounting Method  
Step 1 : Insert the controller through the panel cutout.  
Mounting Bracket Installation  
Step 2 : Insert the mounting bracket into the mounting groove at the top and  
bottom of the controller  
Step 3 : Push the mounting bracket forward until the bracket stops at panel  
wall.  
Step 4 : Insert and tighten screws on bracket to secure the controller in place.  
(The screw torque should be 0.8kgf-cm to 1.5kgf-cm)  
DTB4824 Mounting Method:  
CT Wiring Method (if CT function is selected)  
DTB4848/4896/9696 Mounting Method:  
3
2
1
17  
Error Acknowledge and Display  
Communication error code response description:  
Error status 102EH/4750H  
PV read back 1000H/4700H  
Error status  
0001H  
0002H  
0003H  
0004H  
0005H  
0006H  
0007H  
N/A  
8002H  
8003H  
8004H  
N/A  
PV unstable  
Re-initial, No temperature at this time  
Input sensor did not connect  
Input signal error  
Over input range  
ADC fail  
8006H  
N/A  
EEPROM read/write error  
Display message:  
Power ON  
Normal display  
Present value  
PV  
DTB series, Firmware V1.50  
SV  
Output VR type with Event option  
Set value  
Sensor didn’t connect  
No  
Input error  
Error  
PV  
SV  
Connect  
Input  
EEPROM error  
Error  
Input over range  
PV flash when over  
PV  
SV  
EEPROM  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

ADTRAN Two Way Radio ISU 2X64 User Manual
AEG Washer Dryer 12700 User Manual
Airlink101 Network Router 300N User Manual
Alesis Stereo System MultiMix 4 USB FX User Manual
Alpine CD Player CDA 7892E User Manual
Alpine CD Player CDA 7998 User Manual
Atlona Stereo Receiver AT HD V216 User Manual
Axor Plumbing Product 10920001 User Manual
BB Electronics Network Card TS W Family User Manual
Beko Freezer CFA1300W User Manual