American Standard Air Conditioner UV05 User Manual

Operation Maintenance Manual  
OM 751-1  
Group: Applied Systems  
Part Number: OM 751  
Date: November 2006  
MicroTechII® UnitVentilatorControls  
®
®
forAAF -HermanNelson ClassroomUnitVentilators  
DXCoolingOnly-  
SoftwareModelUV05  
UsedwithAAF-HermanNelsonClassroomUnitVentilator  
ModelAVV-FloorMounted  
ModelAHV-CeilingMounted  
ModelAZV,AZU-FloorMountedSelfContainedAirConditioner  
IMPORTANT  
Before unit commissioning, please read this publication in its entirety.  
Develop a thorough understanding before starting the commissioning procedure.  
This manual is to be used by the commissioner as a guide. Each installation is unique, only general topics are covered.  
The order in which topics are covered may not be those required for the actual commissioning.  
© 2006 McQuay International  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Introduction  
This manual provides information on the MicroTech II® control system used in the AAF®-  
HermanNelson® Unit Ventilator product line. It describes the MicroTech II components, input/  
output configurations, field wiring options and requirements, and service procedures.  
For installation and general information on the MicroTech II Unit Ventilator Controller, refer  
to IM 747, MicroTech II Unit Ventilator Controller.  
For installation, commissioning instructions, and general information on a particular unit  
ventilator model, refer to the appropriate manual (Table 1), as well as accompanying software  
operating instruction manual (Table 4), and possible accessory manuals that may pertain to the  
unit (Table 3).  
For installation and maintenance instructions on a plug-in communications card, refer to the  
appropriate protocol-specific installation and maintenance manual (Table 2). For a description  
of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED  
15065.  
Table 1: Model-specific unit ventilator installation literature  
Description  
Manual #  
IM 502  
Air Source Heat Pump  
X
DDC Control Components AED-Q-MTII-811 X  
Self-Contained  
IM 503  
X X X X X X  
X X X X X  
Self-Contained DDC  
Control Components  
Vertical Split-system  
Horizontal Split-system  
Ceiling Vent  
AZS Q V U R MII  
810  
IM 817-1  
IM 830  
X
X X X X X  
X X X X  
X X X  
X X X  
AH IM 830  
Table 2: Protocol-specific communication card installation literature and protocol data  
Description  
Unit Ventilator Unit Controller LonWorks®  
Communications Module  
Manual #  
IM 729  
Unit Ventilator Unit Controller JCI N2 Open®  
Communications Module  
IM 730  
Unit Ventilator Unit Controller BACnet®  
Communications Module  
IM 731  
Protocol Data Packet  
ED-15065  
Table 3: Accessory-specific installation literature  
Description  
Manual #  
MTII Unit Ventilator Controls Installation  
Room Temperature Sensors Installation  
ATS Service Cable Installation for Unit Ventilators  
IM 747  
IM 629-1  
IM 762-0  
McQuay OM 751  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Introduction  
Table 4: Software program literature  
Description  
Manual #  
OM 748  
Air Source Heat Pump with Electric Heat (Software Model 00)  
Water Source Heat Pump with Electric Heat (Software Model 02)  
Water Source Heat Pump without Electric Heat (Software Model 03)  
DX Cooling with Electric Heat (Software Model 04)  
OM 749  
OM 750  
OM 751  
OM 752  
OM 753  
DX Cooling Only (Software Model 05)  
Electric Heat Only (Software Model 06)  
DX Cooling with Hydronic Heat - Valve Control (Software Model 07)  
DX Cooling with Hydronic Heat - F&BP Damper Control (Software Model 08)  
2-Pipe Hydronic Heat Only - Valve Control (Software Model 09)  
2-Pipe Hydronic Heat Only - F&BP Damper Control (Software Model 10)  
OM 754  
2-Pipe Chilled Water Cooling and Hot Water Heat - Valve Control (Software Model 11) OM 755  
2-Pipe Chilled Water Cooling and Hot Water Heat - F&BP Damper Control (Software  
Model 12)  
4-Pipe Chilled Water Cooling and Hydronic Heat - Valve Control (Software Model 13) OM 756  
4-Pipe Chilled Water Cooling and Hydronic Heat - F&BP Damper Control (Software  
Model 14)  
2-Pipe Chilled Water Cooling Only - Valve Control (Software Model 15)  
2-Pipe Chilled Water Cooling Only - F&BP Damper Control (Software Model 16)  
2-Pipe Chilled Water Cooling with Electric Heat - Valve Control (Software Model 17)  
2-Pipe Chilled Water Cooling with Electric Heat - F&BP Damper Control (Software  
Model 18)  
OM 757  
OM 758  
NOTICE  
This equipment generates, uses, and can radiate radio frequency energy and, if not installed  
and used in accordance with this instruction manual, may cause interference to radio  
communications. It has been tested and found to comply with the limits for a Class A digital  
device, pursuant to part 15 of the FCC rules. These limits are designed to provide  
reasonable protection against detrimental interference when the equipment is operated in a  
commercial environment. Operation of this equipment in a residential area is likely to cause  
detrimental interference in which case users are required to correct the interference at their  
own expense. McQuay International disclaims any liability resulting from any  
interference or for the correction thereof.  
WARNING  
Electric shock hazard. Can cause personal injury or equipment damage.  
This equipment must be properly grounded. Connections and service to the MicroTech II  
control panel must be performed only by personnel that are knowledgeable in the operation  
of the equipment being controlled.  
CAUTION  
Extreme temperature can damage system components.  
The MicroTech II controller is designed to operate in ambient temperatures from -20°F to  
125°F. It can be stored in ambient temperatures from -40°F to 140°F. It is designed to be  
stored and operated in relative humidity up to 95% (non-condensing).  
CAUTION  
Static sensitive components. A static discharge while handling electronic circuit  
boards can damage components.  
Discharge any static electrical charge by touching the bare metal inside the main control  
panel before performing any service work. Never unplug any cables, circuit board terminal  
blocks, relay modules, or power plugs while power is applied to the panel.  
4
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
Acronyms/Abbreviations  
The following table list acronyms and abbreviations that may or may not be used within this  
manual. Other abbreviations for keypad displays and parameters can be found in Table 8 on  
Table 5: Acronyms and abbreviations  
Acronym/  
Description  
Abr.  
Air Fan  
AF  
Auxiliary Heat End Differential  
AHED  
AHSD  
ASCII  
ASHRAE  
Auxiliary Heat Start Differential  
American Standard Code for Information Interchange  
American Society of Heating, Refrigerating, and Air  
Conditioning Engineers, Inc  
Compressorized Cooling Lockout  
CCLO  
Space CO Setpoint  
2
CO S  
2
Chilled Water  
CW  
Chilled Water Valve Position  
Discharge Air  
CWVP  
DA  
Discharge Air High Limit  
DAHL  
DAT  
Discharge Air Temperature  
Discharge Air Temperature Setpoint  
Demand Controlled Ventilation  
DX Cooling Discharge Air Low Limit  
Economizer Compare Differential  
Economizer IA/OA Enthalpy Differential  
Economizer OA Enthalpy Setpoint  
Emergency Heat Setpoint  
Exhaust Interlock OAD Min Position Setpoint  
Outdoor Air Temperature Setpoint  
End-of-Cycle  
DATS  
DCV  
DXLL  
ECD  
EED  
EES  
EHS  
EOAD  
EOAT  
EOC  
EOCS  
EORH  
ERH  
ETD  
EOC OAT Low Setpoint  
Outdoor Air Humidity Output  
Space Humidity Setpoint  
Economizer IA/OA Temp Differential  
Economizer OA Temp Setpoint  
Source (water in) Temperature  
Face and Bypass Damper Position  
Federal Communications Commission  
Face and Bypass  
ETS  
EWIT  
FBDP  
FCC  
F & BP  
HVACR  
HEOC  
HW  
Heating, Ventilating, Air Conditioning Refrigeration  
Heating EOC Valve Setpoint  
Hot Water  
Indoor Air  
IA  
Indoor Air Fan  
IAF  
Indoor Air Temperature  
IAT  
Light Emitting Diode  
LED  
Local User Interface  
LUI  
Mixed Air Low Limit  
MALL  
MCLL  
NEC  
OA  
Mechanical Cooling Low Limit Setpoint  
National Electric Code  
Outside Air  
Outside Air Dampers  
OAD  
OADE  
OADH  
OADL  
OADM  
OADP  
OALS  
OAMX  
OAT  
Energize Exhaust Fan OAD Setpoint  
OAD Min Position High-Speed Setpoint  
OAD Min Position Low-Speed Setpoint  
OAD Min Position Med-Speed Setpoint  
Outdoor Air Damper Position  
OAD Lockout Setpoint  
OAD Max Position Setpoint  
Outside Air Temperature  
McQuay OM 751  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
Acronym/  
Abr.  
Description  
Occupied Cooling Setpoint  
OCS  
Occupied Heating Setpoint  
Occupancy Override Input  
Occupancy Sensor Input  
Proportional Integral  
OHS  
OOI  
OSI  
PI  
Parts Per Million  
PPM  
PTC  
RH  
Positive Temperature Coefficient  
Relative Humidity  
Space Humidity Setpoint  
Read Only  
RHS  
RO  
Read Write  
RW  
Standby Cooling Setpoint  
Standby Heating Setpoint  
Thermal Expansion Valve  
Unoccupied Cooling Setpoint  
Unoccupied Heating Setpoint  
Unit Ventilator  
SCS  
SHS  
TXV  
UCS  
UHS  
UV  
Unit Ventilator Controller  
UVC (Heat/Cool) Mode Output  
UVC State Output  
UVC  
UVCM  
UVCS  
VALP  
VCLL  
VCLO  
VCS  
WH  
Wet Heat Valve Position  
Ventilation Cooling Low Limit Setpoint  
Ventilation Cooling Lockout  
Ventilation Cooling Setpoint  
Wet Heat  
Source (water in) Temperature Differential  
WITD  
6
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
Getting Started  
The MicroTech II Unit Vent Controller (UVC) is a self-contained device that is capable of  
complete, stand-alone operation. Information in the controller can be displayed and modified  
by using the keypad/display (local user interface). The following sections describe how to use  
the keypad/display.  
Note – Many UVC parameters are accessible both through the keypad/display and the network  
interface. The shared keypad/display and the network interface variables have a “last-  
change-wins” relationship.  
Using the Keypad/Display  
The keypad/display shown in Figure 1 is provided with all MicroTech II Applied Unit  
Ventilator unit controllers. With the keypad/display, operating conditions, system alarms, and  
control parameters can be monitored. Set points and other parameters also can be modified.  
Figure 1: Keypad/display  
TM  
MicroTech II  
FAN ONLY  
COOL  
HIGH  
MED  
FUNC  
HEAT  
LOW  
AUTO  
AUTO  
ON /  
STOP  
MODE  
FAN  
Display Format  
The keypad/display’s 2-digit, 7-segment display normally shows the effective heating or  
cooling temperature set point (Effective Set Point Output). The display also is used to view  
and modify UVC parameters as explained in the following sections.  
Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.  
All other LEDs are switched off.  
Keypad Functions  
Security Levels  
The keypad/display provides a 4-level password security feature that can be used to restrict  
access. The available security levels are shown in Table 6.  
Note – All unit ventilator controllers ship with the lowest security (level 0) enabled. To change  
security levels, see Figure 2. Once a security level is changed, the keypad/display  
remains at that security level until the next time it is changed.  
Why can’t I use the MODE or FAN key or adjust Set Point Offset?  
Most likely this is due to the security feature being used. If the security feature is set higher  
than level 0, then some keypad/display functionality is locked out. To ensure this is not the  
problem, enter the level 0 password then try to use the keypad/display again.  
McQuay OM 751  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Getting Started  
Table 6: Keypad/display security levels  
Level Display  
What is restricted?  
Default level (access all)  
Password  
0
U0  
10  
Does not allow set point offset changes;  
also locks out keypad/display menu  
access.  
1
U1  
21  
32  
43  
Does not allow set point offset changes  
nor MODE key changes; also locks out  
keypad/display menu access.  
2
3
U2  
U3  
Does not allow set point offset changes  
nor MODE and FAN key changes; also  
locks out keypad/display menu access.  
Figure 2: Changing keypad/display security levels  
ON/STOP Key and LED  
Use the ON/STOP key to toggle the UVC between OFF mode and running (Application Mode  
Input). The ON/STOP LED is off when the UVC is in the OFF mode.  
Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.  
All other LEDs are switched off.  
The UVC archives each change to the keypad/display FAN and MODE keys. When the  
ON/STOP key is used to bring the unit out of OFF mode, the UVC implements the last  
active fan and unit modes.  
Each time the UVC power cycles, the UVC is in the auto fan and auto unit modes when  
power is returned.  
WARNING  
Off mode is a “stop” state for the unit ventilator. It is not a “power  
off” state. Power may still be provided to the unit.  
FAN Key  
Use the FAN key to toggle through each of the fan speeds (Fan Speed Command Input): Auto,  
Low, Medium, and High.  
MODE Key  
Use the MODE key to toggle through the keypad/display accessible unit modes (Heat/Cool  
Mode Input): Auto, Heat, Cool, and Fan Only.  
Arrow Keys  
Use the arrow keys to scroll between parameters and to adjust parameters.  
FUNC Key  
Use the Func key to view the actual space temperature or to confirm selection and changes to  
user-adjustable parameters.  
8
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
Using the Keypad/Display  
Viewing Actual Indoor Air Temperature (IAT)  
Normally, the effective set point temperature appears on the keypad/display. You also can use  
the keypad/display to view the indoor air temperature (IAT). See Figure 3.  
Note – When the actual indoor air temperature (Effective Space Temp Output) equals the  
effective set point temperature (Effective Set Point Output), you there is no change to the  
keypad/display when you view space temperature.  
Figure 3: Viewing indoor air temperature  
FUNC  
70  
71  
70  
Effective  
set point  
Enter  
(5-sec)  
Actual space  
temperature  
Effective  
set point  
Changing Set Points  
The keypad/display can be used to make a +/–5°F (+/–3°C) offset adjustment to the effective  
temperature set point. See Figure 4. Also see “Space Temperature Set Points” on page 26 to  
learn more about temperature set points.  
Figure 4: Adjusting the set point offset  
FUNC  
So  
0
0
70  
Effective  
set point  
Set point  
offset  
Current  
Enter  
offset  
FUNC  
-1  
So  
69  
-1  
Adjusted  
offset  
Save  
change  
Flash  
value  
Effective  
set point  
Note – The set point offset clears whenever UVC power is cycled. When you change the set point  
offset after a power cycle, or for the very first time, this cleared value shows as the highest  
allowed value (5°F/3°C) but is not an actual offset value.  
When using the +/–3°F (+/–1.7°C) remote wall sensor, any set point offset adjustment  
made at the keypad/display causes the UVC to override and ignore the remote wall  
sensor set point adjustment knob. To use the remote wall sensor set point adjustment  
knob after you changed the set point offset on the keypad/display, clear the keypad/  
display set point offset by cycling UVC power.  
When using the 55°F to 85°F remote wall sensor, the UVC ignores any LUI set point offset  
adjustments.  
Menu Reference  
The keypad/display menu eases troubleshooting and simplifies UVC configuration. The user  
can access the most common parameters and system status values without a PC or network  
interface.  
The keypad/display menu is accessed via an unmarked, hidden key. This hidden key is located  
approximately behind the letter “h” in the MicroTech II logo on the keypad/display face.  
The keypad/display menu consists of two levels. The first level is the keypad/display Menu  
Item List containing alphanumeric characters representing each parameter. The second level is  
where the parameter’s value is viewed and adjusted if the parameter is adjustable. After 15-  
seconds, an inactivity timer automatically causes the display to back out of the menu levels,  
returning to the effective set point display.  
McQuay OM 751  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Getting Started  
Figure 5: Changing a keypad/display menu item  
Table 7: Keypad/display menu item list  
RO 05  
RW1  
Display Keypad menu item list Abr.  
Description  
Default  
Reset Alarm Input  
Enter 1 to clear alarms (clears all inactive alarms, except filter alarm). To enable  
the alarm again, enter 0.  
Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg.  
Heat, 9 = Fan Only  
Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 =  
Heat, 6 = ActiveDehum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11  
= Heat Mode Cant Heat, 12 = CantCool, 13 = Emerg Heat Mode Cant Heat, 14 =  
Heat Mode Low Limit, 15 = Cool Mode Low Limit  
2
RW  
RO  
x
x
//  
rA  
UVC (Heat/Cool) Mode  
Output  
UVC State Output  
UVCM  
HC  
UVCS  
RO  
x
St  
Discharge Air Temp Set  
point Output  
Discharge Air Temp  
Output  
Ventilation Cooling Low  
Limit set point  
Mechanical Cooling Low  
Limit set point  
Slave Type Configuration  
DATS Display current DA temperature set point.  
DAT Display current DA temperature.  
RO  
RO  
RW  
RW  
x
x
x
x
d0  
d1  
d2  
d3  
54°F  
(12°C)  
45°F  
VCLL Adjust economizer cooling DA temperature low limit.  
MCLL Adjust mechanical cooling DA temperature low limit.  
(7°C)  
Set slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave  
follows master). This feature requires a network over which the master and slave RW  
UVCs can communicate.  
x
x
x
0
SL  
Eo  
o(  
Effective Occupancy  
Output  
Occupancy Override  
Input  
Display current occupancy.  
RO  
Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting  
this variable is intended only for troubleshooting. Once you are done, cycle unit  
power to clear this variable and return the UVC to normal operation.  
//2  
RW  
Occupied Cooling set  
point  
Standby Cooling Set  
point  
Unoccupied Cooling Set  
point  
Occupied Heating Set  
point  
Standby Heating Set  
point  
Unoccupied Heating Set  
point  
73.4°F  
(23°C)  
77°F  
OCS Adjust occupied cooling set point.  
SCS Adjust standby cooling set point.  
UCS Adjust unoccupied cooling set point.  
OHS Adjust occupied heating set point.  
SHS Adjust standby heating set point.  
RW  
RW  
RW  
RW  
RW  
x
x
x
x
x
(o  
(S  
(U  
ko  
kS  
kU  
rS  
o1  
o2  
(25°C)  
82.4°F  
(28°C)  
69.8°F  
(21°C)  
66.2°F  
(19°C)  
60.8°F  
(16°C)  
UHS Adjust unoccupied heating set point.  
Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F.  
OADP Display OA damper position.  
RW  
RW  
RO  
x
x
x
Wall Sensor Type  
0
Outside Air Damper  
Position Output  
OAD Min Position High-  
Speed Set point  
OAD Min Position Med-  
Speed Set point  
Adjust OA damper minimum position with IAF at high speed. (This variable is  
OADH  
RW  
x
x
20%  
25%  
factory set to 5% open when the unit is ordered with optional CO2 DCV.)  
Adjust OA damper minimum position with IAF at medium speed. (This variable is  
OADM not used when the optional CO2 DCV is enabled. Only OADH is active as the OA RW  
damper minimum regardless of fan speed.)  
Adjust OA damper minimum position with IAF at low speed. (This variable is not  
OADL used when the optional CO2 DCV is enabled. Only OADH is active as the OA  
damper minimum regardless of fan speed.)  
o3  
o4  
OAD Min Position Low-  
Speed Set point  
RW  
x
30%  
10  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
RO 05  
Display Keypad menu item list Abr.  
Description  
Default  
99%  
12%  
99%  
0
RW1  
Exhaust Interlock OAD  
Min Position set point  
Energize Exhaust Fan  
OAD Set point  
OAD Max Position Set  
Adjust OA damper position above which the exhaust fan output will be energized.  
There is a fixed –5% differential associated with this set point.  
Adjust OA damper minimum position when the exhaust interlock input is  
energized.  
EOAD  
RW  
x
x
x
x
o5  
OADE  
RW  
RW  
RW  
o6  
OAMX Adjust OA damper maximum position.  
o7  
o8  
point  
Set OA damper lockout feature status: 0 = disable, 1 = enable. (This variable is  
factory set to 1 when the unit is ordered as a recirc unit with no OAD.)  
Adjust OA temperature below which the OA damper closes if the OA damper  
OAD Lockout Enable  
35.6°F  
(2°C)  
°
OAD Lockout Set point  
Economizer Enable  
OALS lockout is enabled. (This variable is factory set to –99 C when the unit is ordered  
RW  
x
o9  
as a recirc unit with no OAD.)  
Set economizer status: 0 = disable, 1 = enable.  
RW  
RW  
x
x
1
E1  
E2  
E3  
E5  
Economizer OA Temp  
Set point  
Economizer IA/OA Temp  
Differential  
Economizer OA Enthalpy  
Set point  
Adjust economizer OA temperature set point. DO NOT lower this set point below  
CCLO or you risk creating a deadband where no cooling occurs.  
68°F  
(20°C)  
ETS  
ETD Adjust economizer IA/OA temperature differential.  
EES Adjust economizer OA enthalpy set point.  
RW  
RW  
x
x
1.8°F (1°C)  
25 Btu/lb  
(58 kJ/kg)  
Economizer IA/OA  
Enthalpy Differential  
1.3 Btu/lb  
(3 kJ/kg)  
EED Adjust economizer IA/OA enthalpy differential.  
RW  
RO  
RO  
x
x
x
E6  
r1  
r3  
ot  
k1  
k2  
Space Humidity Output  
ERH Display room humidity (optional). 00 = No sensor connected.  
EORH Display OA humidity (optional). 00 = No sensor connected.  
Outdoor Air Humidity  
Output  
Outdoor Air Temp Output EOAT Display OA temperature.  
RO  
RW  
x
x
Emergency Heat Enable  
Set emergency heat status: 0 = disable, 1 = enable.  
1
Emergency Heat Set  
point  
Emergency Heat  
Shutdown Configuration  
Auxiliary Heat Start  
Differential  
Auxiliary Heat End  
Differential  
Auxiliary Heat  
Configuration  
External BI-3  
Configuration  
External BO-3  
Configuration  
53.6°F  
(12°C)  
EHS Adjust emergency heat set point.  
RW  
RW  
RW  
RW  
RW  
RW  
RW  
RW  
x
x
x
x
x
x
x
x
Set emergency heat operation during shutdown, 0 = no emergency heat during  
shutdown: 1 = allow emergency heat during shutdown.  
0
k3  
A1  
A2  
A3  
b3  
b6  
AHSD Adjust auxiliary heat start differential.  
AHED Adjust auxiliary heat stop differential.  
Set auxiliary heat type: 0 = N.O. device, 1 = N.C. device.  
1.8°F (1°C)  
1.8°F (1°C)  
0
0
0
2
Set the function external binary Input 3: 0 = ventilation lockout, 1 = exhaust  
interlock.  
Set the function of external binary output 3: 0 = exhaust fan on/off signal, 1 =  
auxiliary heat.  
Set space fan cycles (switches off) during occupied, bypass, and standby mode: 2  
= continuous, 3 = cycling.  
Fan Cycling  
Configuration  
(F  
(E  
(r  
(1  
Filter Alarm Enable  
Reset Filter Alarm Input  
Compressor Enable  
Set filter alarm status: 0 = disable, 1 = enable.  
Enter 1 to clear filter alarm.  
RW  
RW  
RW  
x
x
x
0
//2  
1
Set compressor status: 0 = disable, 1 = enable.  
Adjust compressor cooling lockout set point. When the OA temperature falls below  
Compressor Cooling  
Lockout Set point  
this set point, compressor cooling is not allowed. DO NOT make this setting lower  
than the factory default. There is a fixed +3.6°F (2°C) differential associated with  
this set point.  
Adjust compressor heating lockout set point. When the OA temperature falls below  
this set point, compressor heating is not allowed and only electric heat will be used.  
Adjust compressor start delay. Where several units (inductive loads) are  
connected to the same electrical supply, make this set point unique for every UVC  
to prevent multiple compressors from energizing at the same time after a power  
failure or occupancy change.  
63.5°F  
(17.5°C)  
CCLO  
RW  
RW  
RW  
x
x
x
(2  
(3  
(6  
Compressor Heating  
Lockout Set point  
25°F  
(-4°C)  
CHLO  
Compressor Start Delay  
0 sec  
Space Temp Sensor  
Offset  
Adjust this setting to bias the UVC measured space temperature.  
RW  
RW  
x
x
0
F
SP  
Un  
Set keypad/display temperature units in English or SI. This set point also effects  
which unit types displayed over Metasys N2 and BACnet MS/TP networks using  
the appropriate optional communications modules.  
Keypad/display  
Temperature Units  
1. RW = read and write capable, RO = read only.  
2. If a menu value is greater than 2-digits (higher than 99), then // will be displayed on the keypad/display.  
McQuay OM 751  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of Operation  
Description of Operation  
State Programming  
The MicroTech II UVC takes advantage of “state” machine programming to define and  
control unit ventilator operation. “State” defines specific states or modes of operation for each  
process within the unit ventilator (e.g., heating, cooling, etc.) and contain the specific logic for  
each state. This eliminates some of the most common problems associated with control  
sequences such as the possibility of simultaneous heating and cooling, rapid cycling, etc.  
State machine programming, and the unique nature of state diagrams, can be easily used to  
describe operation. It can simplify sequence verification during unit commissioning, as well as  
simplify troubleshooting. With the unique combination of state machine programming and the  
keypad/display’s ability to allow a technician to easily determine the active UVC state,  
troubleshooting the UVC can be very simple.  
The state diagrams presented in the following sections consist of several “elements” including  
super states, states, conditional jumps (also called transitions) and transition points. Super  
states are used as a means to group two or more related states into a single control function  
such as cooling, or heating, etc. States are where all the actual work takes place, within each  
state the UVC enables PI-loops and other logic sequences required to control unit ventilator  
operation within that particular state, while other functions and PI-loops not needed during  
that state may be disabled. Conditional jumps, or transitions, are the logic paths used by the  
UVC to determine which state should be made active, these are the “questions” the UVC  
continually considers. The transition point is simply a point through which a number of  
conditional jumps meet. Think of it as a point where a number of questions must be  
considered from which the UVC then determines which path is followed and which state is  
then made active.  
The UVC states and super states are used to define the “normal” unit modes, such as Off,  
Night Purge, Fan Only, Emergency Heat, Auto, Cool, and Heat. The UVC also supports  
several “special purpose” unit modes such as Purge, Pressurize, De-pressurize, and Shutdown,  
which can be forced via a network connection and override typical UVC operation.  
Note – Not all states or modes are available for all UV configurations, and some states (such as  
Active Dehum) are optional.  
In the state descriptions below the terms, saturated high and saturated low, indicate that  
the heating or cooling function being described has reached 100% or 0%, respectively.  
12  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Description of Operation  
Figure 6: Complete UVC—state diagram  
Off  
9
NightPurge  
8
EmergencyHeat  
ModeSuperState  
FullHeat  
7
FanOnly  
A
CantHeat  
D
AutoMode  
HeatMode  
SuperState  
CoolMode  
SuperState  
Heat  
5
Econ  
3
DAHeat  
4
CantHeat  
B
LowLimit  
E
CantCool  
C
EconMech  
1
LowLimit  
F
Mech  
2
UVC Unit Modes  
The UVC provides several “normal” modes of unit operation. These include: Off, Night  
Purge, Fan Only, Cool, Emergency Heat, Auto, Heat, and Cool.  
Normal UVC modes can contain a single state or several states depending upon the  
functionality required for each particular mode. Each UVC state is assigned a number, which  
can be very helpful when trying to understand which state is currently active within the UVC.  
To view the current UVC state number, use the keypad/display.  
McQuay OM 751  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Description of Operation  
Table 8: UVC state names and numbers  
State numbers  
Normal UVC modes  
State names  
Decimal  
ASCII  
Hex  
57  
56  
65  
55  
68  
53  
66  
69  
49  
50  
51  
52  
67  
70  
OFF  
OFF  
Night Purge  
Fan Only  
Full Heat  
Cant Heat  
Heat  
9
8
9
8
Night purge  
Fan only  
10  
7
A
7
Emergency heat  
13  
5
D
5
Heat  
Cant Heat  
Low Limit  
EconMech  
Mech  
11  
14  
1
B
E
1
Auto  
2
2
Econ  
3
3
Cool  
DA Heat  
Cant Cool  
Low Limit  
4
4
12  
15  
C
F
WARNING  
Off mode is a “stop” state for the unit ventilator. It is not a “power  
off” state. Power may still be provided to the unit.  
OFF Mode (State 9)  
Off mode is provided so that the UVC can be forced into a powered OFF condition. OFF mode  
is a “stop” state for the unit ventilator; it is not a power off state. OFF mode consists of a  
single UVC state: OFF [9].  
When OFF mode becomes active, the UVC stops all normal heating, cooling, and ventilation  
(OA damper is closed), and fan operation ends. The UVC continues to monitor space  
conditions, indicate faults, and provide network communications (if connected to a network)  
in the OFF mode while power is maintained to the unit.  
While in OFF mode, the UVC does not maintain DA temperatures. If the space temperature  
drops below EHS while in the OFF mode, the UVC is forced into the Emergency Heat mode  
The space lighting output continues to operate based upon the current occupancy mode.  
Note – Special purpose unit modes such as Purge, Pressurize, and De-pressurize can force the  
UVC to perform “special” functions during which the display appears to be in the OFF  
mode.  
Figure 7: Off state diagram  
OFF  
9
UVC Mode  
OFF  
=
OFF  
UVC Mode  
Transition  
point  
14  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Description of Operation  
Night Purge Mode (State 8)  
Night Purge mode is provided as a means to more easily and quickly ventilate a space. Night  
purge can be useful in helping to remove odor build up at the end of each day, or after  
cleaning, painting, or other odor generating operations occur within the space. Night Purge  
mode consists of a single UVC state: Night Purge [8].  
Night Purge is a full ventilation with exhaust mode, during which room comfort is likely to be  
compromised. Therefore, McQuay strongly recommends using Night Purge only when the  
space is unoccupied.  
When Night Purge mode becomes active, the UVC stops all normal heating and cooling. Since  
any new energy used to treat the incoming air would be wasted in the purge process. In the  
Night Purge mode, the space fan is set to high speed, the OA damper is set to 100% open, and  
the Exhaust Fan binary output (see “External Binary Outputs” on page 38) is set to ON. If the  
UVC is not set to another mode within 1 hour (fixed), the UVC automatically switches to the  
While in Purge mode, the UVC does not maintain DA temperatures. If the space temperature  
drops below the EHS, the UVC is forced into the Emergency Heat mode (see “Emergency  
Figure 8: Night purge state diagram  
Night Purge  
8
UVC Mode  
Night purge  
UVC Mode  
Night purge  
=
Transition  
point  
Fan Only Mode (State A)  
The Fan Only mode is provided so that the UVC can be forced into a Fan Only operation via a  
keypad/display or a network connection. Fan Only mode consists of a single UVC state: Fan  
Only [A].  
When Fan Only mode becomes active, the UVC stops all normal heating and cooling.  
While in Fan Only mode, the UVC does not maintain DA temperatures. If the space  
temperature drops below the EHS, the UVC is forced into the Emergency Heat mode (see  
Figure 9: Fan only state diagram  
UVC Mode  
Fan Only  
Fan Only  
UVC Mode  
Fan Only  
=
Transition  
point  
A
McQuay OM 751  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Description of Operation  
Emergency Heat Mode (Super State)  
The Emergency Heat mode is provided for situations where the UVC is in a mode that does  
not normally allow heating, such as OFF, Cool, Night Purge, or Fan Only. If Emergency Heat  
mode is enabled, the UVC can automatically force itself into the Emergency Heat mode from  
OFF, Cool, Night Purge, Fan Only, Purge, Pressurize, De-pressurize, and Shutdown.  
Emergency Heat mode consists of UVC states: Full Heat [7] and Cant Heat [D].  
Software model 05 does not have the primary or secondary heating devices. The UVC uses  
auxiliary heat (if field provided and field connected) when emergency heat is required.  
When the Emergency Heat mode becomes active, the UVC automatically determines which  
state to make active, Full Heat [7], or Cant Heat [D], based on the transitions for each of those  
states.  
Figure 10: Emergency heat state diagram  
Emergency Heat Mode  
Super State  
Full Heat  
7
UVC Mode  
Emergency Heat  
=
Heat  
Available  
Transition  
point  
UVC Mode  
Emergency Heat  
Heat  
Available  
=
Cant Heat  
D
Full Heat State (State 7)  
The Full Heat [7] state is the “normal” state that the UVC goes into when Emergency Heat  
mode is active. It is activated when the space temperature is lower than the EHS.  
When Emergency Heat mode becomes active, the UVC goes into 100% heating until the space  
temperature raises to the EHS plus a fixed differential (5.4°F/3°C). In the Emergency Heat  
mode, the space fan is set to high speed, and the OA damper operates normally.  
If the UVC automatically forces itself into the Emergency Heat mode from another mode  
(e.g., Cool, Fan Only, etc.), then the UVC returns to the appropriate unit mode once the space  
temperature rises to the EHS plus a fixed differential (5.4°F/3°C).  
The UVC monitors the DAT to ensure it does not exceed DAHL. If the DAT does exceed  
DAHL, then heating is set to 0% for a minimum of 2-minutes (fixed) and until the DAT drops  
36°F (20°C) fixed differential below DAHL.  
Cant Heat State (State D)  
The Cant Heat [D] state is a “non-normal” state that the UVC can go into when Emergency  
Heat mode is active. An IAT or DAT sensor fault during Emergency Heat mode causes the  
UVC to make this state active.  
When the Cant Heat state becomes active, the space fan remains at high speed as set during  
the Full Heat state.  
The UVC will remain in the Cant Heat state until heat becomes available.  
16  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Description of Operation  
Auto Mode  
Auto mode is provided so that the UVC can be set to automatically determine if heating or  
cooling is required. Auto mode is the default power-up UVC mode. Auto mode is made up of  
the Heat and Cool modes. When the UVC is set to auto mode, the UVC automatically  
determines which mode (Heat or Cool) to use.  
Heat Mode (Super State)  
When in Heat mode, the UVC will use auxiliary heat (if field provided and field connected to  
the unit) as needed to maintain the effective heating setpoint (see “Space Temperature Set  
Points” on page 26). The keypad/display or a network connection can be used to force the unit  
into the Heat mode. Additionally, the UVC when set to Auto mode can automatically force the  
unit into the Heat mode as needed. When the UVC is in Auto mode, it is “normal” for the  
UVC to “idle” in Heat mode when there is no need to switch to another mode.  
The Heat mode super state consists of UVC states: Heat [5], Low Limit [E], and Cant Heat  
[B].  
When the Heat mode super state becomes active, the UVC automatically determines which of  
the Heat Mode states to make active based upon the transitions for each state.  
Figure 11: Heat mode super state diagram  
Transition  
point  
UVC Mode = Heat  
OR  
UVC Mode  
Space  
=
Auto AND  
Warm  
UVC Mode  
UVC Mode  
OR  
Heat AND  
Auto  
UVC Mode  
Warm AND Heat Pl = Sat Low  
=
Auto AND Space =  
Heat Mode  
Super State  
Heat  
Available  
Heat = Available  
Heat  
5
AND  
Low Limit = Inactive  
Heat Pl = Sat Hi  
(2 minutes)  
AND  
DAT<VCLL LLPl = Sat Lo  
(2 minutes)  
Cant Heat  
AND  
B
DAT<(VCLL + 1.8F)  
Heat = Available  
AND  
Low Limit = Inactive  
Heat  
Available  
Low Limit  
E
Heat State (State 5)  
The Heat state is the “normal” state during Heat mode. When the Heat state becomes active,  
the UVC will (within State) continually calculate the DATS (“Discharge Air Temperature  
Control” on page 29) required to maintain the effective heat setpoint (see “Space Temperature  
Set Points” on page 26). The calculated DATS will not be allowed to go above DAHL. The  
UVC will use auxiliary heat (if field provided and field connected to the unit) as needed to  
maintain the current DATS.The auxiliary heat binary output will be used as needed. The Heat  
Timer (3-minutes fixed) will begin counting. The CO demand controlled ventilation function  
2
will be active, if the unit is equipped for CO control (see “CO2 Demand Controlled  
2
Ventilation (optional)” on page 34), and the OA damper will be adjusted as needed to maintain  
the CO setpoint. The UVC will remain in this state until one of the transition out conditions  
2
become true, or until one of the super state transition out conditions becomes true.  
McQuay OM 751  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Description of Operation  
Note – The OAD is considered to be in “alarm” when the OAD is forced below the active minimum  
position in the Low Limit state. This is not an actual unit “alarm” or “fault” condition, but  
only a condition used for the purpose of transition arguments.  
Low Limit State (State E)  
The Low Limit state is a “non-normal” state the UVC can go into while Heat mode is active  
when the unit reaches 100% heating and still cannot meet the current DATS (see “Discharge  
Air Temperature Control” on page 29) required to maintain the effective heating set point (see  
“Space Temperature Set Points” on page 26). This is likely to occur only if the OA  
temperature is very cold, the OA damper minimum position is set too high, the unit ventilator  
is oversized for the application, or if the electric heating has failed, or is set incorrectly.  
When the Low Limit state becomes active, the Low Limit PI-loop can override the OA  
damper position (see “Outdoor Air Damper Operation” on page 32) and adjust the OA damper  
toward closed as necessary to maintain the current DATS (see “Discharge Air Temperature  
Cant Heat State (State B)  
The Cant Heat state is a “non-normal” state the UVC can go to when Heat mode is active. An  
IAT or DAT sensor fault during the Heat mode causes the UVC to make this state active.  
When the Cant Heat state becomes active, no heating or ventilation takes place. The OA  
damper goes to the minimum position unless it is forced closed by other functions such as  
freezestat (T6) or morning warm-up.  
Cool Mode (Super State)  
When in Cool mode the UVC uses primary cooling (economizer) and secondary cooling  
(mechanical, DX) as needed to maintain the effective cooling set point (see “Space  
Temperature Set Points” on page 26). The keypad/display or network connection can be used  
to force the unit into the Cool mode. When the UVC is in Auto mode, it is “normal” for the  
UVC to “idle” in Cool mode when there is no need to switch to another mode. The Cool mode  
super state consists of the following UVC states: Econ Mech [1], Mech [2], Econ [3], DA Heat  
[4], Low Limit [F], and Cant Cool [C].  
When the Cool mode super state becomes active, the UVC will automatically determine which  
UVC state to make active based upon the transitions for each state.  
If the space temperature drops below EHS, and the Emergency Heat function is enabled, the  
UVC will be forced into the Emergency Heat mode (see “Emergency Heat Mode (Super  
18  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Description of Operation  
Figure 12: Cool mode super state diagram  
Transition  
Point  
UVCModeCool AND UVCModeAuto  
OR  
UVCMode=Auto AND Space=Cold AND  
MechPI=SatLow(3min) AND  
EconPI=SatLow  
UVCMode=Cool  
OR  
UVCMode=Auto AND Space=Warm  
CoolMode  
SuperState  
Space=HighCO2  
OR  
DAT<VCLL  
DAHeat  
4
EconAvailable  
AND  
MechCoolAvailable  
Econ  
3
SpaceHighCO2  
AND  
HeatPI=SatLow  
AND  
EconTimer=Expired  
(3 minutes) AND  
EconPI=SatHi AND  
MechCool=Available  
DAT>VCLL  
Econ = Available  
AND  
MechCoolAvailable  
HeatPI=SatHi(2min)  
AND DAT<VCLL  
LLPI=SatLow (2min)  
MechPI=SatLow (3min) AND  
EconMechTimer=Expired  
AND  
DAT>(VCLL+1.8F)  
(3 minutes) OR  
MechCoolAvailable  
EconAvailable  
AND  
MechCool=Available  
LowLimit  
F
CantCool  
C
EconMech  
1
EconAvailable  
EconAvailable  
AND  
MechCool=Available  
Econ=Available  
MechCoolAvailable  
Mech  
2
Econ State (State 3)  
The Econ state is a “normal” state during Cool mode. The Econ state typically is active in the  
Cool mode when primary cooling (economizer) is available and adequate to meet the cooling  
requirements.  
When the Econ state becomes active, the UVC uses economizer cooling (see “Economizer  
Operation” on page 32) as needed to maintain the effective cooling set point (see “Space  
Temperature Set Points” on page 26). If cooling is not required while in the Econ state, the  
UVC can “idle” in the Econ state until cooling is required or until there is a call to switch to  
another mode or state.  
The UVC monitors the DAT to ensure it does not fall below VCLL.  
The CO demand controlled ventilation function (optional) will be active (see “CO2 Demand  
2
Controlled Ventilation (optional)” on page 34) and the OA damper is adjusted as needed to  
maintain the CO set point.  
2
McQuay OM 751  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of Operation  
Figure 13: Econ state operation (occupied mode and auto fan)  
Econ Mech State (State 1)  
The Econ Mech state is a “normal” state during Cool mode. The Econ Mech state typically is  
active in the Cool mode when primary cooling (economizer) alone is not adequate to meet the  
cooling requirements and both primary cooling and secondary cooling (compressor) are  
available.  
When the Econ Mech state becomes active, the OA damper is set to 100% open, and the UVC  
uses the units mechanical cooling capabilities as needed to maintain the effective cooling set  
The UVC monitors the DAT to ensure it does not fall below MCLL.  
Figure 14: Econ mech state operation (occupied mode and auto fan)  
Mech State (State 2)  
The Mech state is a “normal” state during Cool mode. The Mech state typically is active in the  
Cool mode when primary cooling (economizer) is not available and secondary cooling  
(compressor) is available.  
When the Mech state becomes active, the UVC uses the unit’s mechanical cooling capabilities  
as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on  
page 26). If cooling is not required while in the Mech state, the UVC can “idle” in the Mech  
state until cooling is required or until there is a call to switch to another mode or state.The  
UVC monitors the DAT to ensure it does not fall below MCLL.  
20  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of Operation  
The CO demand controlled ventilation function (optional) is active (see “CO2 Demand  
2
Controlled Ventilation (optional)” on page 34), and the OA damper is adjusted as needed to  
maintain the CO set point.  
2
Figure 15: Mech state operation (occupied mode and auto fan)  
Discharge Air (DA) Heat State (State 4)  
The DA Heat state is a “normal” state during Cool mode. The DA Heat state typically is active  
when reheat is required to maintain DATS while maintaining the required OA damper  
position. The DA Heat state can also be made active if the optional CO DCV feature is  
2
provided and CO levels are high, requiring the OA damper to open beyond what is required  
2
for economizer cooling.  
When DA Heat state is active, the UVC uses the units heating capability as needed to maintain  
VCLL. The CO demand controlled ventilation function (optional) is active (see “CO2  
2
Demand Controlled Ventilation (optional)” on page 34), and the OA damper is adjusted as  
needed to maintain the CO set point.  
2
Low Limit State (State F)  
The Low Limit state is a “non-normal” state during Cool mode. The Low Limit state typically  
follows the DA Heat state when the UVC reaches 100% heat and still cannot maintain VCLL.  
When the Low Limit state becomes active, the Low Limit PI-loop overrides the OAD  
toward closed as necessary to maintain the DAT set point (see “Discharge Air Temperature  
Cant Cool State (State C)  
The Cant Cool state is a “non-normal” state during Cool mode. The Cant Cool state typically  
becomes active when both primary (economizer) and secondary (compressor) cooling are not  
available (or they are disabled) or when an IAT, DAT or OAT sensor failure occurs.  
When the Cant Cool state becomes active, no cooling is available.  
Special Purpose Unit Modes  
There are some additional UVC modes that are considered special purpose unit modes. These  
special purpose modes include Pressurize, Depressurize, Purge, Shutdown, and Energy Hold  
Off. These modes force the UVC to perform very specific and limited functions. Use these  
with caution and only for short periods as needed.  
McQuay OM 751  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Description of Operation  
In each of these special purpose UVC modes, if the space temperature drops below EHS and  
the Emergency Heat function is enabled, the UVC is forced into the Emergency Heat mode  
Heat function is satisfied.  
Table 9: Actions during special purpose unit modes  
Indoor air fan  
Outdoor air  
damper (OAD)  
100% Open  
Closed  
Exhaust fan  
Action  
(IAF)  
High  
Off  
output  
Off  
Pressurize  
Depressurize  
Purge  
On  
High  
Off  
100% Open  
Closed  
On  
Shutdown  
Off  
Energy hold off  
Off  
Closed  
Off  
Pressurize Mode  
When in Pressurize mode, the UVC uses the IAF, OAD, and exhaust output as needed to  
pressurize the space. The UVC stops all normal heating and cooling but does allow emergency  
heat if required. The pressurize mode can only be accessed via a network connection.  
Depressurize Mode  
When in Depressurize mode the UVC will use the IAF, OAD, and exhaust output as needed to  
depressurize the space. The UVC stops all normal heating and cooling but does allow  
emergency heat if required. The de-pressurize mode can only be accessed via a network  
connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).  
Purge Mode  
When in Purge mode, the UVC uses the IAF, OAD, and exhaust output as needed to purge the  
space. The UVC stops all normal heating and cooling but does allow emergency heat if  
required. The purge mode can only be accessed via a network connection or with ServiceTools  
for MicroTech II Applied Terminal Unit Controllers (ATS).  
Shutdown Mode  
Shutdown mode is the equivalent of the Off mode, but is an Off mode forced by a network  
connection. When in Shutdown mode, the UVC stops all normal heating, cooling, ventilation  
(OA damper is closed), and fan operation. By default emergency heat is not be used during the  
shutdown mode, however, the UVC can be configured (Emergency Heat Shutdown  
Configuration) to allow emergency heat operation during shutdown mode. The shutdown  
mode can be accessed via a network connection, a binary input to the UVC, or with  
ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).  
WARNING  
Shutdown mode and energy hold off mode are a “stop” state for  
the unit ventilator. It is not a “power off” state.  
Energy Hold Off Mode  
The UVC supports an energy hold off state, which when active forces the UVC to stop all  
normal heating, cooling and ventilation. Typically used by a network connection to force the  
UVC to cease heating, cooling and ventilation when conditions exist where heating, cooling  
and ventilation are not required or desired. Energy hold off mode is very similar to shutdown  
mode except that energy hold off always allows emergency heat if required. The energy hold  
off mode can only be accessed via a network connection or with ServiceTools for  
MicroTech II Applied Terminal Unit Controllers (ATS).  
22  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of Operation  
Unit Mode Priority  
The UVC uses the network variables and binary inputs listed in Table 10 and Table 11 to  
determine the current unit mode. Special purpose UVC unit modes have higher priority than  
the normal UVC unit modes as shown in the tables.  
Each table lists the highest priority items on the left to the lower priority items to the right. The  
right-most columns indicate unit operation as a result of the left-most columns. The term  
“Don’t care” in these tables implies that another network variable or binary input to the left  
has a higher priority.  
Table 10: Special purpose UVC unit mode priority  
Priority result  
Emergency override  
input1  
Remote shutdown  
binary input  
Energy hold  
off input1  
Energy hold  
off output2  
Unit mode  
output2  
Actual UVC action  
See the normal  
UVC mode priority (Table 11)  
Normal  
Normal  
4
De-energized  
3
Normal  
Energy hold off  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Energy hold off  
Energy hold off  
Don’t care  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
5
Energized  
Pressurize  
De-pressurize  
Purge  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Pressurize  
De-pressurize  
Purge  
Don’t care  
Don’t care  
Shutdown  
Don’t care  
Off  
1. Network input.  
2. Network output.  
3. Normal indicates the UVC power-up condition.  
4. De-energized indicates that the contacts connected to this binary input are open.  
5. Energized indicates that the contacts connected to this binary input are closed.  
Table 11: Normal UVC mode priority  
Priority result  
Application override Unit mode override  
Unit mode output 2  
input 1  
input1  
Heat  
Cool  
3
Normal (Auto)  
Emergency heat  
Heat  
Heat  
Cool  
3
Normal (Auto)  
Cool  
Night purge  
Off  
Night purge  
Off  
Emergency heat  
Fan only  
Emergency heat  
Fan only  
Heat  
Heat  
Cool  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Cool  
Night purge  
Off  
Night purge  
Off  
Emergency heat  
Fan only  
1. Network input.  
2. Network output.  
Emergency heat  
Fan only  
3. Normal (Auto) is the normal UVC power-up state.  
McQuay OM 751  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description of Operation  
Occupancy Modes  
The UVC is provided with four occupancy modes: Occupied, Standby, Unoccupied, and  
Bypass. The occupancy mode affects which heating and cooling temperature set points are  
used, affects IAF operation, and affects OAD operation. The Manual Adjust Occupancy and  
Networked Occupancy Sensor network variables, along with the Unoccupied and Tenant  
Override binary inputs, are used to determine the Effective Occupancy. The term “Don’t care”  
in Table 12 implies that another network variable or binary input to the left has a higher  
priority.  
Note – The Occupancy Override Input is provided as a way for a network connection to manually  
force the UVC into a particular occupancy mode. The Occupancy Override Input can  
override the tenant override feature. For example, if the network uses the Occupancy  
Override Input to force the unit into unoccupied mode, then the tenant override switch  
does not operate as expected. Therefore, McQuay strongly recommends using the  
Occupancy Sensor Input to control occupancy modes over a network and only using the  
Occupancy Override Input if there is reason to ensure tenant override does not occur.  
Table 12: Occupancy mode priority  
Priority result  
Effective  
occupancy  
output2  
Occupancy  
Occupancy  
Unoccupied binary input  
Override input sensor input1  
Occupied  
Don’t care  
Don’t care  
Occupied  
Don’t care  
Don’t care  
Occupied  
Unoccupied  
Occupied  
Bypass  
Unoccupied  
Don’t care  
Unoccupied  
Don’t care  
Bypass  
Contacts open (Occupied)  
Contacts Closed (Unoccupied)  
Don’t care  
Occupied  
Bypass  
Null (default)  
Standby  
Don’t care  
Occupied  
Standby  
Don’t care  
Occupied  
4
Unoccupied  
Don’t care  
Unoccupied  
Occupied  
3
Null (default)  
Contacts open (Occupied)  
Contacts closed (Unoccupied)  
Null (default)  
4
Unoccupied  
1. Network input.  
2. Network output.  
3. Typical operation is defined in this row of the table.  
4. The tenant override switch (unit or wall sensor mounted) can be used here to force the UVC  
into bypass.  
Occupied Mode  
The occupied mode is the normal day time mode of UVC operation. During occupied mode  
the UVC uses the occupied heating and cooling set points, the OAD operates normally, and by  
default the IAF remains on.  
Unoccupied Mode  
The unoccupied occupancy mode is the normal night time mode of UVC operation. During  
unoccupied mode the UVC uses the unoccupied heating and cooling set points, the OAD  
remains closed, and the IAF cycles as needed for heating or cooling. The IAF remains off  
when there is no need for heating or cooling.  
Standby Mode  
The standby mode is a special purpose daytime mode of UVC operation. During standby,  
mode the UVC uses the standby heating and cooling set points, the OAD remains closed, and  
by default the IAF remains on.  
24  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Description of Operation  
Bypass Mode  
The bypass mode (also called Tenant Override) is the equivalent of a temporary occupied  
mode. Once the bypass mode is initiated, it remains in effect for a set period of time (120  
minutes, default). During the bypass mode, the UVC uses the occupied heating and cooling set  
points, the OAD operates normally, and by default the IAF remains on.  
Additional Occupancy Features  
Networked Occupancy Sensor Capability  
A networked occupancy sensor can be interfaced with the Occupancy Sensor Input variable to  
select occupancy modes. When the Occupancy Sensor Input variable is used, it automatically  
overrides any hard-wired unoccupied binary input signal.  
Unit-Mounted Time-Clock  
An optional unit-mounted factory-installed electronic 24-hour/7-day time clock can be  
provided on stand-alone unit ventilator configurations. It is factory wired to the UVC  
unoccupied binary input and can be set to automatically place the unit into occupied and  
unoccupied modes based upon its user configured schedule.  
Unit-Mounted Tenant Override Switch  
A tenant override switch is factory installed in all floor mounted units and is located near the  
LUI on the unit. This switch provides a momentary contact closure that can be used by room  
occupants to temporarily force the UVC into the bypass occupancy mode from unoccupied  
mode.  
Note – The Occupancy Override Input can override the tenant override feature. For example, if  
the network uses the Occupancy Override Input to force the unit into unoccupied mode,  
then the unit-mounted tenant override switch does not operate as expected. Therefore,  
McQuay strongly recommends using the Occupancy Sensor Input to control occupancy  
modes over a network and only using the Occupancy Override Input if there is reason to  
ensure tenant override does not occur.  
Remote Wall-Mounted Sensor Tenant Override Switch  
The optional remote wall-mounted sensors include a tenant override switch. This switch  
provides a momentary contact closure that can be used by room occupants to temporarily force  
the UVC into the bypass occupancy mode from unoccupied mode.  
Note – The Occupancy Override Input can override the tenant override feature. For example, if  
the network uses the Occupancy Override Input to force the unit into unoccupied mode,  
then the wall sensor tenant override switch does not operate as expected. Therefore,  
McQuay strongly recommends using the Occupancy Sensor Input to control occupancy  
modes over a network and only using the Occupancy Override Input if there is reason to  
ensure tenant override does not occur.  
Remote Wall-Mounted Sensor Status LED  
The optional remote wall-mounted sensors each include a UVC status LED. This status LED  
aids diagnostics by indicating the UVC occupancy mode and fault condition.  
Table 13: Remote wall-mounted sensor status LED  
Indication  
Occupied  
Unoccupied  
Bypass  
LED operation  
On continually  
On 1 second/off 9 seconds  
On continually  
Standby  
Fault  
On 9 seconds/off 1 second  
On 5 seconds/off 5 seconds  
McQuay OM 751  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Description of Operation  
Space Temperature Set Points  
The UVC uses the six occupancy-based temperature set points as the basis to determine the  
Effective Set point Output. The effective set point is calculated based on the unit mode, the  
occupancy mode, and the values of several network variables. The effective set point then is  
used as the temperature set point that the UVC maintains.  
Table 14: Default occupancy-based temperature set points  
Temperature set point Abbreviation  
Defaults  
Unoccupied cool  
Standby cool  
UCS  
SCS  
OCS  
OHS  
SHS  
UHS  
82.4°F (28.0°C)  
77.0°F (25.0°C)  
73.4°F (23.0°C)  
69.8°F (21.0°C)  
66.2°F (19.0°C)  
60.8°F (16.0°C)  
Occupied cool  
Occupied heat  
Standby heat  
Unoccupied heat  
Networked Set Point Capability  
The Space Temp Setpoint Input variable is used to allow the temperature set points for the  
occupied and standby modes to be changed via the network; the unoccupied set points are not  
affected by this variable.  
Networked Set Point Offset Capability  
The Networked Set Point Offset Input variable is used to shift the effective occupied and  
standby temperature set points by adding the value of the Setpoint Offset Input variable to the  
current set points; the unoccupied points are not affected by this variable. This variable is  
typically set bound to a supervisory network controller or to a networked wall module having  
a relative set point knob.  
Use the keypad/display to make adjustments to the value of the Setpoint Offset Input variable.  
Note – The keypad/display and the network both affect the Set Point Offset Input variable. Keep  
in mind that changes to this variable are last-one-wins.  
Networked Set Point Shift Capability  
The Set Point Shift Input variable is used to shift the effective heat/cool set points. It typically  
is bound to a networked supervisory controller or system that provides functions such as  
outdoor air temperature compensation. All occupied, standby, and unoccupied set points are  
shifted upward (+) or downward () by the corresponding value of the Set Point Shift Input  
variable.  
®
Note – The Set Point Shift Input capability is not available through the BACnet interface.  
Networked Space Temperature Sensor Capability  
A networked space temperature sensor can be interfaced with the Space Temp Input variable.  
When the Space Temp Input variable is used (valid value), it automatically overrides the hard-  
wired space temperature sensor.  
26  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Description of Operation  
Remote Wall-Mounted Sensor with +/–3°F  
Adjustment (optional)  
When the optional remote wall-mounted sensor with +/–3°F adjustment dial is used, the UVC  
effectively writes the value of the set point adjustment dial to the Set Point Offset Input  
variable.  
Note – If a network connection is used to adjust the Set Point Offset Input variable, you must not  
use the optional remote wall-mounted sensor with +/–3°F adjustment.  
If the keypad/display is used by room occupants to adjust the Set Point Offset, do not use  
the optional remote wall-mounted sensor with +/–3°F adjustment.  
If you have the optional remote wall-mounted sensor with +/–3°F adjustment and an  
occupant uses the keypad to make Set Point Offset adjustments, this overrides any  
+/–3°F adjustment on the optional remote wall-mounted sensor since the keypad/display  
has higher priority. If you find that changes to the +/–3°F adjustment on the remote wall-  
mounted sensor have no effect, it is likely that an occupant used the keypad/display to  
make a Set Point Offset change. Cycle unit power to clear this situation and restore the  
ability to change the Set Point Offset from the +/–3°F adjustment on the remote  
wall-mounted sensor.  
Remote Wall-Mounted Sensor with 55°F to 85°F  
Adjustment (optional)  
When the optional remote wall-mounted sensor with 55°F to 85°F adjustment dial is used, the  
UVC will effectively write the value of the set point dial to the Space Temp Set Point Input  
variable.  
Note – If a network connection is using the Space Temp Set Point Input variable, do not use the  
optional remote wall-mounted sensor with 55°F to 85°F adjustment.  
If it is intended that the LUI will be used by room occupants to adjust the Setpoint Offset,  
then you must not use the optional remote wall-mounted sensor with 55°F to 85°F  
adjustment. When using the optional remote wall-mounted sensor with 55°F to 85°F  
adjustment, the UVC will ignore any Setpoint Offset changes made at the LUI.  
Effective Set Point Calculations  
The UVC calculates the effective set point (Effective Set Point Output) based on several  
factors. These factors include the six occupancy set points for heating and cooling (Occupancy  
Temperature Set Point), occupancy mode, the value of the network variables Space Temp Set  
Point Input, Set Point Offset Input, and the Set Point Shift Input as well as the optional wall-  
mounted sensor’s set point adjustment knob. As always, network inputs have priority over  
hardwired connections.  
The UVC determines if heating or cooling is required based on the current unit mode (Heat/  
Cool Mode Output) and then calculates the required set point for heating or cooling. After  
calculating, the Effective Set Point Output network variable is set equal to the calculated set  
point. The Effective Set Point Output is the temperature set point that the UVC maintains,  
which normally appears on the keypad/display.  
McQuay OM 751  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description of Operation  
Figure 16: Effective set point calculations  
Occupancy Temperature Setpoints  
(network configuration variables)  
Effective Set Point Calculations for each Occupancy Mode  
Occupied Cooling Set Point (OCS)  
Standby Cooling Set Point (SCS)  
Unoccupied Cooling Set Point (UCS)  
Occupied Heating Set Point (OHS)  
Standby Heating Set Point (SHS)  
Unoccupied Heating Set Point (UHS)  
AbsOffsetOccupied = Setpoint - (OCS + OHS)/2  
AbsOffsetStandby = Setpoint - (SCS + SHS)/2  
Occupied and Bypass Modes  
EffectiveCoolSetpoint = OCS + AbsOffsetOccupied + SetptOffset + OCSS  
EffectiveHeatSetpoint = OHS + AbsOffsetOccupied + SetptOffset + OHSS  
Space Temp  
Set Point Input  
(network input)  
Network Value  
55°F/85°F  
Set Point  
Wall Sensor  
Standby Mode  
1
WallSensorType  
Config. Value  
EffectiveCoolSetpoint = SCS + AbsOffsetStandby + SetptOffset + SCSS  
EffectiveHeatSetpoint = SHS + AbsOffsetStandby + SetptOffset + SHSS  
0
+3°F/–3°F  
Wall Sensor  
Unoccupied Mode  
EffectiveCoolSetpoint = UCS + UCSS  
EffectiveHeatSetpoint = UHS + UHSS  
Local User  
Interface  
+5°F/–5°F  
SetptOffset  
Set Point  
Offset Input  
(network input)  
Network Value  
SetptShift (network inputs)  
If both entering paths have  
valid values, then the network  
value has priority.  
Occupied Cooling Set Point Shift (OCSS)  
Standby Cooling Set Point Shift (SCSS)  
Unoccupied Cooling Set Point Shift (UCSS)  
Occupied Heating Set Point Shift (OCSS)  
Standby Heating Set Point Shift (SHSS)  
Unoccupied Heating Set Point Shift (UHSS)  
If both entering paths have  
valid values, then the keypad/display value  
has priority.  
Table 15: Set point calculation examples  
Given  
OccupancyMode = Occupied or BypassHeat/CoolMode = Heat  
SpaceTempSetpoint = (not used)  
SetpointOffset = (not used) = 0.0°F  
SetpointShift = (not used) = 0.0°F  
OHS = 69.8°F  
Effective set point calculations  
EffectiveSetpoint = OHS + SetpointOffset + SetpointShift = 69.8 + 0.0 + 0.0 = 69.8°F  
Given  
OccupancyMode = Occupied or BypassHeat/CoolMode = Heat  
SpaceTempSetpoint = 71.0°F  
SetpointOffset = -1.0°F (occupant adjustment on remote wall sensor, or LUI)  
SetpointShift = (not used) = 0.0°F  
OCS = 73.4°F, OHS = 69.8F  
Effective set point calculations  
AbsoluteOffset = (OCS – OHS) / 2 =(73.4°F – 69.8°F) / 2 = 1.8°F  
EffectiveSetpoint = SpaceTempSetpoint – AbsoluteOffset + SetpointOffset + SetpointShift = 71.0 -  
1.0 - 1.0 + 0.0 = 68.2°F  
28  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of Operation  
Proportional Integral (PI) Control Loops  
The MicroTech II UVC uses PI-loop control for heating, cooling and ventilation processes  
within the unit ventilator. Numerous PI algorithms can be used depending upon the unit  
ventilator configuration. The UVC uses “single” and “cascading” PI loops where needed.  
Table 16: PI loop list  
Feedback  
PI loops  
PI loop type  
Set point  
(controlled  
variable)  
Output  
Effective Heating or Cooling  
Temperature Setpoint  
Calculated Discharge Air  
Temperature Setpoint Output  
PI-1  
Space Temperature  
Space Temperature  
Calculated Discharge Air Temperature  
Setpoint Output  
Discharge Air  
Temperature  
Discharge Air  
Temperature  
PI-2 Primary Cooling (Economizer)  
Position the OA Damper  
Operate the Compressor  
Cascading  
Calculated Discharge Air Temperature  
Setpoint Output  
PI-3  
Secondary Cooling  
Primary Heating  
Calculated Discharge Air Temperature  
Setpoint Output  
Discharge Air  
Temperature  
Position the Wet Heat Valve or  
F&BP Damper  
PI-4  
PI-5  
PI-6  
CO (optional)  
2
Single  
Single  
Effective CO Setpoint  
2
Calculated Discharge Air Temperature  
Space CO  
2
Discharge Air  
Temperature  
Position the OA Damper  
Low Limit  
Position the OA Damper  
Setpoint  
Figure 17: PI loop graphic for CO  
2
Effective  
CO2 set point  
Position the  
OA damper  
+
PI - 5  
-
Space CO2  
sensor  
Discharge Air Temperature Control  
The UVC uses two “cascading” PI loops to aid in providing very stable space temperature  
control. The Space Temperature PI-loop is used to calculate the Discharge Air Temperature  
Setpoint Output required to meet the Effective Temperature Setpoint Output. A second PI-loop  
(Primary Cooling, Secondary Cooling, or Primary Heating) is then activated to control the  
heating or cooling device required to achieve the calculated Discharge Air Temperature  
Setpoint Output.  
Figure 18: Cascading PI loop graphic 1 (primary heat)  
Figure 19: Cascading PI loop graphic 2 (primary cool—economizer)  
McQuay OM 751  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Description of Operation  
PI Control Parameters  
Associated with each PI loop is a set of two adjustable parameters: Proportional Band and  
Integral Time. When the unit ventilator is properly sized for the space, the factory settings for  
these parameters provides the best and most robust control action (see Figure 20).  
If field problems arise, first ensure these parameters are set back to the factory default settings.  
If adjustment is required, only make small adjustments to one parameter at a time. After each  
adjustment, allow enough time for the system to stabilize before making further adjustments.  
If you do not have the means to graph the space performance, record the actual measured  
value and set point for several minutes and then plot the results using a spreadsheet to  
determine the correct action to change the PI parameter.  
CAUTION  
Adjusting PI parameters can cause erratic unit operation,  
and potentially damage the equipment.  
PI control parameters should only be adjusted by trained  
personnel having a complete understanding of how these  
parameters affect system operation. Generally these parameters  
do not need to be adjusted from the factory default settings.  
Figure 20: Optimized PI loop control  
Proportional Band  
The proportional band, or proportional action, causes the controlled output to changes in  
proportion to the magnitude of the difference between the sensor value and set point.  
A proportional band setting that is too small (see Figure 21) causes control oscillations that go  
fully above and below the set point.  
Figure 21: Proportional bands  
A proportional band setting that is too large (see Figure 21) causes an offset between the actual  
measured oscillation center and the set point. A small offset is not necessarily a problem since  
most systems have a small “natural” offset and the integral function automatically works to  
eliminate or reduce this effect.  
30  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description of Operation  
In general, it is best to start with a relatively large proportional band setting (the factory  
default setting is best) and adjust to smaller values.  
If you want the system to respond strongly to small changes in the space, adjust the  
proportional band to a higher setting.  
If you want the system to react weakly to small changes in the space, adjust the proportional  
band to a higher setting.  
Integral Time  
The integral time, or integral action, causes the controlled output to change in proportion to  
time difference between the sensor value and set point. The difference over time between the  
actual value and set point forms an “area under the curve” (see Figure 22). The integral action  
works to reduce this “area under the curve” and to eliminate any natural system offset.  
Figure 22: Integral time  
Too Small  
Area Under The Curve  
The smaller the integral time, the faster the output ramps up or down with small changes in the  
space. The smaller the integral time, the quicker the system reacts to small changes in the  
space. If the Integral Time is set too small, long oscillations occur (see Figure 22).  
In general, it is best to start with a relatively large integral time setting (the factory default  
setting is best) and adjust to smaller values. If you want the system respond strongly to small  
changes in the space, lower the integral time. If you want the system to react weakly to small  
changes in the space, adjust the integral time to a higher setting.  
Indoor Air Fan Operation  
The UVC supports a three-speed indoor air (IA) fan; low, medium, and high. The UVC  
calculates the effective fan speed and operation based on the unit mode, the occupancy mode,  
and the values of several network variables.  
Auto Mode  
The UVC is provided with a user selectable auto fan mode feature. When in auto fan mode,  
the UVC uses the space temperature PI loop to automatically adjust the fan speed as needed to  
maintain space temperature. This ensures that the UVC maintains the lowest and quietest fan  
speeds whenever possible. When in auto fan mode, a maximum of six fan speed changes per  
hour is allowed (by default). This prevents frequent automatic fan speed changes from  
disturbing room occupants.  
Occupied, Standby, and Bypass Operation  
During occupied standby and bypass modes, the IA fan, by default, remains On.  
McQuay OM 751  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Description of Operation  
Unoccupied Operation  
During unoccupied mode, the IA fan typically remains off and cycles with calls for heating  
and cooling.  
Cycle Fan  
The UVC is provided with a Fan Cycling Configuration variable that can be used to force the  
IA fan to cycle with calls for heating and cooling during the occupied, standby, and bypass  
occupancy modes. When the fan is off, the OA damper is closed. McQuay recommends using  
this feature only when it is acceptable that normal ventilation is not required.  
When the IA fan is set to cycle, the UVC is configured to continue fan operation for a time  
period after heating or cooling is complete.  
Off Delay  
When the UVC is placed into off mode or shutdown mode, the UVC is configured to continue  
fan operation for a short time period and then shutdown.  
Outdoor Air Damper Operation  
The UVC is configured for an OA damper operated by a floating-point actuator. The OA  
damper actuator contains a spring that ensures the OA damper is closed upon loss of power.  
The floating-point actuator is driven by the UVC using two binary (Triac) outputs. The OA  
damper typically is open to the current minimum position during the occupied and bypass  
occupancy modes and closed during the unoccupied and standby occupancy modes.  
A Triac output is best tested under load using a 24 V relay for verification. To verify:  
1
2
3
Put a relay across the Triac outputs.  
Cycle the power.  
Verify the relay’s closed contacts during calibration.  
Minimum Position  
The UVC is configured to maintain three OA damper minimum positions based on the  
operation of the IAF fan. This allows each unit to be field configured to provide the amount of  
fresh air required to the space at each of the three IA fan speeds.  
Table 17: Default OA damper minimum positions  
IAF speed  
High  
Without CO2  
20%  
With CO2  
5%  
Medium  
Low  
25%  
5%  
30%  
5%  
Note – If the CO Demand Controlled Ventilation (DCV) option is used, the UVC only uses the IA  
2
fan high speed OA damper minimum position regardless of fan speed. The DCV function  
adjusts the OA damper above this minimum as needed to maintain CO set point.  
2
Economizer Operation  
The economizer function is used by the UVC to determine if the OA is adequate for  
economizer (primary) cooling. When both the economizer and mechanical cooling are  
available, the economizer is used as primary cooling and the UVC adds mechanical cooling  
only if the economizer is not adequate to meet the current cooling load (e.g., the OA damper  
reaches 100% and cooling is still required).  
The UVC supports three economizer functions:  
Basic (default)—Temperature Comparison Economizer  
32  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Description of Operation  
Expanded (optional)—Temperature Comparison with OA Enthalpy Setpoint Economizer  
(Strategy 1)  
Leading Edge (optional)—Temperature Comparison with Enthalpy Comparison Economizer  
(Strategy 2)  
Temperature Comparison Economizer (default)  
If the default Basic economizer function is selected, the unit ventilator is provided from the  
factory without the optional IA and OA humidity sensors. In this case, the UVC is factory set  
for Economizer Strategy 1—the UVC automatically detects that no OA humidity sensor is  
present and adjusts to use the Temperature Comparison Economizer function.  
Temperature Comparison with OA Enthalpy Setpoint Economizer (optional)  
If the optional Expanded economizer function is selected, the unit ventilator is provided from  
the factory with the optional OA humidity sensor, which is used along with the OA  
temperature sensor to calculate OA enthalpy. In this case, the UVC is factory set for  
Economizer Strategy 1 and uses the Temperature Comparison with OA Enthalpy Setpoint  
Economizer function.  
Note – Temperature Comparison with OA Enthalpy Setpoint Economizer requires an optional OA  
humidity sensor.  
Temperature Comparison with Enthalpy Comparison Economizer (optional)  
If the optional Leading Edge economizer function is selected, the unit ventilator is provided  
from the factory with both the IA humidity and OA humidity sensors, which are used along  
with the IA temperature and OA temperature sensors to calculate IA enthalpy and OA  
enthalpy. In this case, the UVC is factory set for Economizer Strategy 2 and uses the  
Temperature Comparison with Enthalpy Comparison Economizer function.  
Note – Temperature Comparison with Enthalpy Comparison requires both an optional OA  
humidity sensor and an optional IA humidity sensor.  
Table 18: Economizer enable/disable tests defined  
Economizer  
enable/disable tests  
OA temp set point  
Tests  
Enable test  
Disable test  
A
B
EffectiveOATemp < (EconOATempSetpt – EconTempDiff)  
EffectiveOATemp >= EconOATempSetpt  
IA/OA differential temp EffectiveOATemp < (EffectiveSpaceTemp – 3.6°F – EconTempDiff) EffectiveOATemp >= (EffectiveSpaceTemp – 3.6°F)  
EffectiveOAEnthalpy < (EconOAEnthalpySetpt –  
C
D
OA enthalpy set point  
EffectiveOAEnthalpy >= EconOAEnthalpySetpt  
EffectiveOAEnthalpy >= EffectiveSpaceEnthalpy  
EconEnthalpyDiff)  
EffectiveOAEnthalpy < (EffectiveSpaceEnthalpy –  
EconEnthalpyDiff)  
IA/OA differential  
enthalpy  
Table 19: How economizer enable/disable tests are selected  
Economizer  
strategy  
Space humidity  
Economizer enable/  
disable tests  
OA damper closed  
OA damper closed  
Test B  
Space temp sensor  
OA temp sensor  
OA humidity sensor  
sensor  
Unreliable  
Don’t care  
Reliable  
Don’t care  
Unreliable  
Reliable  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Don’t care  
Unreliable  
Reliable  
All  
Basic  
Reliable  
Reliable  
Test C  
Test C and Either  
Test B or Test A  
Test D and Test B  
Test B  
Expanded  
Reliable  
Reliable  
Don’t care  
Reliable  
Reliable  
Reliable  
Reliable  
Reliable  
Reliable  
Reliable  
Reliable  
Reliable  
Reliable  
Unreliable  
Reliable  
Reliable  
Reliable  
Leading Edge  
Unreliable  
Unreliable  
Test B  
Unreliable  
Test B  
Note: The hard-wired sensor and the equivalent input must both be unreliable for the value to be considered  
unreliable.  
McQuay OM 751  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of Operation  
Networked Space Humidity Sensor Capability  
A networked space humidity sensor can be network interfaced with the Space Humidity Input  
variable. When the Space Humidity Input variable is used (valid value), it automatically  
overrides the hard-wired space humidity sensor (if present).  
Networked Outdoor Humidity Sensor Capability  
A networked outdoor humidity sensor can be network interfaced with the Outdoor Humidity  
Input variable. When the Outdoor Humidity Input variable is used (valid value), it  
automatically overrides the hard-wired outdoor humidity sensor (if present).  
CO2 Demand Controlled Ventilation (optional)  
Ventilation equipment typically uses fixed damper positions to determine the amount of OA  
for proper ventilation within the space. Most commonly, the fixed position of the OA damper  
is based on the maximum number of occupants the space is designed to accommodate.  
However, this fixed OA damper operation ignores the fact that most spaces during the day  
have varying occupancy levels and may only rarely reach maximum design occupancy levels.  
This type of fixed damper control for ventilation is energy wasteful since you are treating OA  
not actually needed for ventilation during low occupancy levels.  
People produce CO when they breath; the CO level within the space has a direct relationship  
2
2
with the number of people within that space.  
The UVC can optionally be factory configured to provide CO -based Demand Controlled  
2
Ventilation (DCV). The CO DCV function is useful in saving the energy typically wasted in  
2
treating OA not actually needed for ventilation within a space during occupancy levels below  
maximum design. The CO DCV function uses a PI-loop control to adjust the OA damper  
2
above the minimum position as needed to maintain the Space CO Setpoint (1200 PPM  
2
default).  
The minimum damper position used with CO DCV typically can be set at ~20% of the  
2
minimum position that would be used without CO DCV. For example, if the minimum OA  
2
damper position typically is 20% then when using CO DCV, you could set the new minimum  
2
OA damper position as low as 4% (e.g., 20% × 0.20 = 4%). This new, smaller minimum OA  
damper position then should provide enough ventilation to keep odors in check within the  
space for most applications.  
Note – The CO DCV function can increase the OA damper position past that required by the  
2
economizer and vice versa.  
If odors within the space become a problem, increase the OA damper minimum position  
as needed to eliminate these odors. It may be necessary with new construction or after  
renovation to raise the minimum position for some time period to help reduce odor build-  
up due to the out-gassing of new construction material and then return the minimum OA  
damper position at a later date.  
If the CO Demand Controlled Ventilation (DCV) option is used, the UVC only uses the IA  
2
fan high speed OA damper minimum position regardless of fan speed. The DCV function  
adjusts the OA damper above this minimum as needed. In this case, the IA fan high speed  
OA damper minimum position is factory set at 5%.  
Networked Space CO2 Sensor Capability  
A networked space CO sensor can be network interfaced with the Space CO Input variable.  
2
2
When the Space CO Input variable is used (valid value), it automatically overrides the hard-  
2
wired space CO sensor (if present).  
2
34  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Description of Operation  
ASHRAE Cycle II  
The UVC supports ASHRAE Cycle II operation. The basis of ASHRAE Cycle II is to  
maintain the required minimum amount of ventilation whenever possible, which can be  
increased during normal operation for economizer cooling or CO DCV control or reduced to  
2
prevent excessively cold discharge air temperatures.  
A discharge air temperature sensor is installed in all unit ventilators. If necessary, the  
ASHRAE II control algorithm overrides room control and modifies the heating, ventilating,  
and cooling functions (as available) to prevent the discharge air temperature from falling  
below the VCLL set point.  
Compressor Operation  
The UVC is configured to operate the compressor as secondary (mechanical) cooling when the  
economizer is available. When the economizer is not available and the compressor is  
available, the UVC uses the compressor when cooling is required.  
Compressor Envelope  
The compressor envelope protects the compressor from adverse operating conditions that can  
cause damage and or shortened compressor life by ending compressor operation if coil  
temperatures exceed the defined operating envelope.  
For self-contained units, the UVC is configured to monitor both the inside air/refrigerant and  
outside air/refrigerant coil temperatures to prevent compressor operation under adverse  
conditions.  
For split-system units, the UVC is configured at the factory to only monitor the inside air/  
refrigerant coil as part of the compressor envelope function.  
Figure 23: Compressor envelope in self-contained units  
DX cooling  
160˚F (71.1˚C)  
2
40˚F (4.4˚C)  
1
28˚F (-2.2˚C) 120˚F (48.9˚C)  
Condenser temperature  
(outdoor air coil)  
Area for compressor operation envelope.  
1
2
Area where liquid slugging could occur.  
Area where starving could occur.  
Compressor Cooling Lockout  
The UVC is configured to lockout compressor cooling when the OA temperature falls below  
the Compressor Cooling Lockout set point (63.5°F/17.5°C). Below this point, only  
economizer cooling is available.  
McQuay OM 751  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Description of Operation  
Compressor Minimum On and Off Timers  
The UVC is provided with minimum On (3-minute default) and minimum Off (5-minute  
default) timers to prevent adverse compressor cycling.  
Compressor Start Delay  
The UVC is provided with a Compressor Start Delay configuration variable, which is intended  
to be adjusted as part of the start-up procedure for each unit. This variable is used to delay  
compressor operation each time the compressor is required.  
Note – To prevent strain on a building’s electrical supply system from multiple unit compressors  
all starting at the same time after a power failure or after an unoccupied-to-occupied  
changeover, McQuay strongly recommends configuring each unit or groups of units at  
start-up with different start delays.  
Outdoor Air Fan Operation  
The UVC is configured with a fan on delay that delays OA fan operation for a time period (10  
seconds, default) after the compressor starts. The OA fan stops with the compressor.  
Floating-Point Actuator Auto-Zero, Overdrive and Sync  
The UVC at power-up auto-zeros all floating-point actuators (OA damper) before going into  
normal operation to ensure proper positioning. During auto-zero, the unit remains off. The  
actuators all open approximately 30% and then are driven full closed. The overdrive feature  
then is used to continue forcing the actuators closed for one full stroke period. Once the  
zeroing process is complete, normal unit operation begins.  
The UVC is configured such that whenever a floating-point actuator is commanded to go to  
0% or 100%, the UVC overdrives the actuator one full stroke period past the 0% or 100%  
position to ensure proper positioning.  
Additionally, the UVC is configured to sync all floating-point actuators once every six hours  
of operation. To do this, the UVC forces the actuator to the closest rail position (0% or 100%),  
uses the overdrive feature, and then returns to the required position. For example, if the  
actuator is at 20% when the six-hour limit is reached, the UVC then forces the actuator to 0%,  
overdrive for one full stroke and then returns to the 20% position.  
36  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Description of Operation  
External Binary Inputs  
The UVC is provided with three binary inputs that provide the functions described below.  
Figure 24: Binary inputs  
Binary Inputs  
3 sets of dry contacts to signal UVC  
Input 1: Unoccupied (default)  
Input 2: Remote shutdown  
Input 3: Ventilation lockout (default)  
or  
Exhaust interlock system  
These inputs each allow a single set of dry contacts to be used as a signal to the UVC. Multiple  
units can be connected to a single set of dry contacts. For wiring examples, see MicroTech II  
Unit Ventilator Controller IM 747.  
Note – Not all of the functions listed can be used at the same time. The UVC is provided with  
configuration parameters that can be adjusted to select which function is used for these  
inputs where multiple functions are indicated below.  
External Binary Input 1  
This input can be configured as an unoccupied (default) or dew point/humidity signal.  
Unoccupied Input Signal  
This input allows a single set of dry contacts to be used to signal the UVC to go into  
unoccupied or occupied mode. When the contacts close, the UVC goes into unoccupied mode.  
When the contacts open, the UVC goes into occupied mode. Additional variables can effect  
occupancy mode and override this binary input. See “Occupancy Modes” on page 24.  
External Binary Input 2  
This input can only be used for remote shutdown.  
Remote Shutdown Input Signal  
This input allows a single set of dry contacts to be used to signal the UVC to go into shutdown  
mode. When the contacts close (shutdown), the UVC goes into shutdown mode. When the  
contacts open. the UVC returns to normal operation. See “Special Purpose Unit Modes” on  
External Binary Input 3  
This input can be configured as a ventilation lockout (default) or exhaust interlock signal.  
Ventilation Lockout Input Signal  
This input allows a single set of dry contacts to be used to signal the UVC to close the OA  
damper. When the contacts close (ventilation lockout signal), the UVC closes the OA damper.  
When the contacts open, the UVC returns to normal OA damper operation.  
McQuay OM 751  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Description of Operation  
Exhaust Interlock Input Signal  
This input allows a single set of dry contacts to be used to signal the UVC that an exhaust fan  
within the space is energized. The UVC repositions the OA damper to a user adjustable  
minimum position (Exhaust Interlock OA Damper Min Position Setpoint). When the contacts  
close (exhaust fan on signal), the UVC uses the value defined by the Exhaust Interlock OA  
Damper Min Position Setpoint as the new minimum OA damper position regardless of IA fan  
speed. When the contacts open, the UVC returns to normal OA damper operation.  
External Binary Outputs  
The UVC is provided with three binary outputs that provide the functions described below.  
Figure 25: Binary outputs  
Binary Outputs  
3 relay type outputs w/signal voltage  
Output 1: Relay output for light signal  
Output 2: Fault signal  
Output 3: Exhaust fan operation (default)  
or  
Auxiliary heat device  
These outputs are relay type outputs that are intended to be used with signal level voltages (24  
VAC maximum) only. For wiring examples, see MicroTech II Unit Ventilator Controller IM  
747.  
Note – Not all of the functions listed can be used at the same time. The UVC is provided with  
configuration parameters that can be adjusted to select which function will be used for  
these outputs when multiple functions are indicated below.  
External Binary Output 1  
This output can only be used as a signal for space lights.  
Lights On/Off Signal  
This relay output provides one set of Normally Open dry contacts that can be used to signal  
the operation of the space lights. When the UVC is in occupied, standby, or bypass occupancy  
modes, the relay output signals the lights ON (contacts closed). When the UVC is in  
unoccupied occupancy mode, the relay output signals the lights OFF (contacts open).  
External Binary Output 2  
This output can only be used as a fault signal.  
Fault Signal  
This relay output provides Normally Open, Normally Closed, and Common connections that  
can be used to signal a fault condition. When a fault exists, the UVC energizes this relay  
output. When the fault or faults are cleared, the UVC de-energizes this relay output.  
External Binary Output 3  
This output can only be used to signal exhaust fan operation (default) or operate an auxiliary  
heat device.  
38  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Description of Operation  
Exhaust Fan ON/OFF Signal  
This relay output provides one set of Normally Open dry contacts that can be used to signal  
the operation of an exhaust fan. When the OA damper opens more than the Energize Exhaust  
Fan OA Damper set point, then the relay output signals the exhaust fan ON (contacts closed).  
When the OA damper closes below this set point, the relay output signals the exhaust fan OFF  
(contacts open).  
Auxiliary Heat Signal  
This relay output provides one set of Normally Open dry contacts that can be used to operate  
an auxiliary heat device. The UVC by default is configured to operate a Normally Open  
auxiliary heat device (de-energize when heat is required), such as a wet heat valve actuator  
with a spring setup to open upon power failure. However, the Auxiliary Heat Configuration  
variable can be used to set the UVC to use a Normally Closed auxiliary heat device (energize  
when heat is required), such as electric heat.  
Table 20: Auxiliary heat start/stop calculation  
Start/Stop  
Auxiliary heat  
starts when:  
Calculation  
Primary Heat PI-Loop = saturated high (100%) for  
more than two minutes  
AND  
EffectiveSpaceTemp  
AuxiliaryHeatStartDifferential  
EffectiveSpaceTemp (EffectiveSetpoint –  
AuxiliaryHeatStartDifferential) +  
AuxiliaryHeatStopDifferential  
EffectiveSetpoint –  
Auxiliary heat  
stops when:  
McQuay OM 751  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVC Input and Output Table  
UVC Input and Output Table  
All UVC input and output connections and their corresponding unit ventilator usage are shown  
in the following table.  
Table 21: Inputs and outputs, software model 05—DX cooling only  
I/O  
Description  
BO-1 Inside Fan High  
BO-2 Inside Fan Medium  
BO-3 Electric Heat 1  
BO-4 Electric Heat 2  
BO-5 Electric Heat 3  
1
BO-6 External Output Option 2: Fault Indication  
BO-7  
BO-8  
2
BO-9 Compressor  
BI-1 Condensate Overflow  
BI-2  
BI-3  
External Input Option 3:Ventilation Lockout (default) or Exhaust  
BI-4  
3
Interlock  
3
BI-5 External Input Option 2: Remote Shutdown  
BI-6 External Input Option 1: Unoccupied (default)  
BI-7  
BI-8  
BI-9  
BI-10  
BI-11  
4
BI-12 DX Press Switch (NC)  
AI-1 IA Temp. Sensor + T.O.  
AI-2 Remote Setpt. Adjust. Pot.  
5
AI-3 OA Coil DX Temp Sensor  
AI-4 OA Temp Sensor  
AI-5 IA Coil DX Temp Sensor  
AI-6 DA Temp Sensor  
Expansion board  
1
xBO-1 External Output Option 1: Lights On/Off  
External Output Option 3: Exhaust Fan On/Off (default) or  
Auxiliary Heat  
xBO-2  
1
xBO-3 OA Damper Open  
xBO-4 OA Damper Close  
xBO-5  
xBO-6  
5
xBO-7 Outdoor Fan  
xBO-8 Inside Fan Low  
6
xAI-1 IA Humidity Sensor  
6
xAI-2 OA Humidity Sensor  
6
xAI-3 Indoor CO Sensor  
2
xAI-4  
1. Field selectable external output options (all possible options are shown).  
2. This is the condensing unit on/off signal on split-systems.  
3. Field selectable external input options (all possible options are shown).  
4. DX pressures switch not installed on split-systems; this input is then wired  
for constant no-fault condition.  
5. Not installed or wired on split-systems.  
6. Optional.  
40  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Diagnostics and Service  
Diagnostics and Service  
The most important aspect of troubleshooting unit ventilator controls is to isolate the source of  
the problem into one of two categories:  
1 The problem resides within the UVC.  
2 The problem is external to the UVC. Under most circumstances the problem is external to  
the UVC.  
Alarm and Fault Monitoring  
The UVC is programmed to monitor the unit for specific alarm conditions. If an alarm  
condition exists, a fault occurs. When a fault exists, the following occurs:  
The UVC indicates the fault condition by displaying the fault code on the keypad/display.  
The remote wall-mounted sensor (optional) LED flashes a pattern indicating that a fault  
condition exists.  
The fault signal binary output energizes.  
The fault performs the appropriate control actions as described for each fault.  
Manual reset faults can be reset in one of three ways:  
By cycling the unit power.  
Via the keypad/display menu.  
Via the network interface.  
Table 22: Alarm and fault code summary  
Keypad/  
Priority  
Fault description  
Space Temp Sensor Failure  
Reset  
display fault  
codes  
1
2
Auto  
F0  
DX Pressure Fault  
2-Auto in 7 days, then Manual  
F1  
Compressor Envelope Fault  
2-Auto in 7 days, then  
3
F2  
Manual*  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
4
5
Discharge Air DX Cooling Low Limit Indication  
Condensate Overflow Indication  
Space Coil DX Temp Sensor Failure  
Outdoor Temp Sensor Failure  
F3  
F4  
F5  
F6  
F7  
F8  
F9  
FA  
Fb  
FC  
Fd  
FE  
FF  
EE  
--  
6
7
8
Discharge Air Temp Sensor Failure  
Water Coil DX Temp Sensor Failure  
Water-out Temp Sensor Failure  
Space Humidity Sensor Failure  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
Outdoor Humidity Sensor Failure  
Space CO Sensor Failure  
2
Not used  
Not used  
Change Filter Indication  
EPROM Memory Indicator  
Configuration Display  
Manual  
Replace conroller board  
Download file  
* Rev 1_27 has auto reset  
McQuay OM 751  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Diagnostics and Service  
Space Temp Sensor Failure (F0)  
The Space Temp Sensor Failure fault occurs when the UVC detects open or short conditions  
from the sensor.  
Effect:  
Space fan de-energizes (unless in emergency heat mode).  
Compressor immediately de-energizes.  
Outdoor fan (if present) de-energizes.  
Outside air damper is forced closed.  
Electric heat stages are de-energized.  
Fault is indicated.  
DX Pressure Fault (F1)  
The DX Pressure Fault occurs when the UVC detects a switch open condition from the  
refrigerant pressure switch.  
Effect:  
Compressor immediately de-energizes.  
Outdoor fan (if present) de-energizes.  
Fault is indicated.  
Compressor Envelope Fault (F2)  
The UVC monitors refrigerant temperatures. The Compressor Envelope Fault occurs when the  
UVC detects compressor operation that exceeded the allowed operating parameters.  
Effect:  
Compressor immediately de-energizes.  
Outdoor fan (if present) de-energizes.  
Fault is indicated.  
Cause:  
Poor air or water flow through the refrigerant coils. Check fans for proper rpm. Check air  
filters.  
If the unit has a three-phase scroll compressor, check for proper electrical phasing.  
Refrigerant circuit component failure or improper adjustment. Check refrigerant pressures  
and TXV adjustment.  
Coil sensors may have lost proper contact with the refrigerant coil. Check coil sensors.  
Discharge Air DX Cooling Low Limit Indication (F3)  
The Discharge Air DX Cooling Low Limit Indication fault occurs when the UVC detects a  
low discharge air temperature (DAT < MCLL) during compressor cooling.  
Effect:  
Compressor immediately de-energizes.  
Outdoor fan (if present) de-energizes.  
Fault is indicated (on earlier software versions).  
42  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Diagnostics and Service  
Condensate Overflow Indication (optional) (F4)  
The Condensate Overflow Indication fault will occur when the UVC detects high condensate  
levels within the units indoor coil drain pan.  
Effect:  
Compressor is immediately de-energized if in cooling.  
Outdoor fan (if present) is de-energized.  
Fault is indicated.  
Space Coil DX Temp Sensor Failure (F5)  
The Space Coil DX Temp Sensor Failure fault occurs when the UVC detects open or short  
conditions from the sensor.  
Effect:  
Compressor immediately de-energizes.  
Outdoor fan (if present) de-energizes.  
Fault is indicated.  
Outdoor Temp Sensor Failure (F6)  
The Outdoor Temp Sensor Failure fault occurs when the UVC detects open or short conditions  
from the sensor.  
Effect:  
Outside air damper is forced closed.  
Compressor immediately de-energizes.  
Fault is indicated.  
Discharge Air Temp Sensor Failure (F7)  
The Discharge Air Temp Sensor Failure fault occurs when the UVC detects open or short  
conditions from the sensor. Emergency heat mode is available during this fault condition.  
Effect:  
Space fan is immediately de-energized (unless in emergency heat mode).  
Outside air damper is forced closed.  
Electric heat stages are de-energized.  
Compressor immediately de-energizes.  
Outdoor fan (if present) immediately de-energizes.  
Fault is indicated.  
Outdoor Coil DX Temp Sensor Failure (F8)  
The Outdoor Coil DX Temp Sensor Failure fault occurs when the UVC detects open or short  
conditions from the sensor.  
Effect:  
Compressor immediately de-energizes.  
Outdoor fan (if present) de-energizes.  
Fault is indicated.  
McQuay OM 751  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Diagnostics and Service  
Space Humidity Sensor Failure (optional) (FA)  
The Space Humidity Sensor Failure fault occurs when the UVC detects open or short  
conditions from the sensor.  
Effect:  
IA/OA Enthalpy comparison economizer (if used) is disabled.  
Dehumidification function (optional) is disabled.  
Fault is indicated.  
Outdoor Humidity Sensor Failure (optional) (Fb)  
The Outdoor Humidity Sensor Failure fault occurs when the UVC detects open or short  
conditions from the sensor.  
Effect:  
IA/OA Enthalpy comparison or OA Enthalpy economizer (if used) is disabled.  
Fault is indicated.  
Space CO Sensor Failure (optional) (FC)  
2
The Space CO Sensor Failure fault occurs when the UVC detects open or short conditions  
2
from the sensor.  
Effect:  
CO Demand Controlled Ventilation function is disabled.  
2
Fault is indicated.  
Change Filter Indication (FF)  
The Change Filter Indication fault occurs when the UVC calculates that the total fan run time  
has exceeded the allowed number of hours since the last filter change.  
Effect:  
Fault is indicated.  
EPROM Memory Indicator (EE)  
The EPROM Memory Indicator occurs when an unusual electrical event has scrambled the  
EPROM memory within the controller board. In the event that this happens, the controller  
board must be replaced.  
Configuration Display (--)  
The Configuration Display occurs when the display file “**.cfg” is incorrect or has not been  
downloaded with the appropriate file from service tools.  
Troubleshooting Temperature Sensors  
The UVC is configured to use passive positive temperature coefficient (PTC) sensor whose  
resistance increases with increasing temperature. The element has a reference resistance of  
1035 ohms at 77°F (25°C). Each element is calibrated according to the tables shown.  
Use the following procedure to troubleshoot a suspect sensor.  
1 Disconnect both sensor leads from the UVC.  
2 Using some other calibrated temperature sensing device, take a temperature reading at the  
sensor location.  
44  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Diagnostics and Service  
3 Use the temperature reading from Step 2 to determine the expected sensor resistance from  
4 Using a calibrated ohmmeter, measure the actual resistance across the two sensor leads.  
5 Compare the expected resistance to the actual resistance.  
6 If the actual resistance value deviates substantially (more than 10%) from the expected  
resistance, replace the sensor.  
Table 23: Temperature versus resistance  
°F (°C)  
–40 (–40)  
–31 (–35)  
–22 (–30)  
–13 (–25)  
–4 (–20)  
5 (–15)  
14 (–10)  
23 (–5)  
32 (0)  
Resistance in ohms  
°F (°C)  
113 (45)  
122 (50)  
131 (55)  
140 (60)  
149 (65)  
158 (70)  
167 (75)  
176 (80)  
185 (85)  
194 (90)  
203 (95)  
212 (100)  
221 (105)  
230 (110)  
239 (115)  
248 (120)  
Resistance in ohms  
1195  
613  
640  
668  
697  
727  
758  
789  
822  
855  
889  
924  
960  
997  
1035  
1074  
1113  
1153  
1237  
1279  
1323  
1368  
1413  
1459  
1506  
1554  
41 (5)  
1602  
50 (10)  
59 (15)  
68 (20)  
77 (25)  
86 (30)  
95 (35)  
104 (40)  
1652  
1702  
1753  
1804  
1856  
1908  
Troubleshooting Humidity Sensors  
The UVC is configured to use a 0–100% RH, 0–5 VDC, capacitive humidity sensor. Each  
sensor is calibrated according to the table shown.  
CAUTION  
The humidity sensor is not protected against reversed polarity.  
Check carefully when connecting the device or damage can  
result.  
Use the following procedure to troubleshoot a suspect sensor:  
1 Disconnect the sensors output voltage lead from the UVC analog input.  
2 Using some other calibrated humidity sensing device, take a humidity reading at the sensor  
location.  
3 Use the humidity reading from Step 2 determine the expected sensor voltage from  
4 Using a calibrated multi-meter, measure the actual voltage across the yellow and white  
sensor leads.  
Wire color definitions:  
White = ground  
Yellow = output VDC  
Blue = supply VDC  
5 Compare the expected voltage to the actual voltage.  
6 If the actual voltage value deviates substantially (more than 10%) from the expected  
voltage, replace the sensor.  
McQuay OM 751  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Diagnostics and Service  
Table 24: Humidity versus voltage.  
RH (%)  
10  
VDC (mV)  
1330  
RH (%)  
55  
VDC (mV)  
2480  
15  
1475  
60  
2600  
20  
1610  
65  
2730  
25  
1740  
70  
2860  
30  
1870  
75  
2980  
35  
1995  
80  
3115  
40  
2120  
85  
3250  
45  
2235  
90  
3390  
50  
2360  
95  
3530  
Troubleshooting Carbon Dioxide (CO2) Sensors  
The UVC is configured to use a 0–2000 PPM, 0–10 VDC, single beam absorption infrared gas  
sensor. Each sensor is calibrated according to the table shown.  
Use the following procedure to troubleshoot a suspect sensor.  
1 Disconnect the sensors output voltage lead from the UVC analog input (xAI-3).  
2 Using some other calibrated CO sensing device, take a CO reading at the sensor location.  
2
2
3 Use the CO reading from Step 2 to determine the expected sensor voltage from Table 25.  
2
4 Using a calibrated multi-meter, measure the actual voltage across the lead removed from  
xAI-3 and ground.  
5 Compare the expected voltage to the actual voltage.  
6 If the actual voltage value deviates substantially (more than 10%) from the expected  
voltage, replace the sensor.  
In the unlikely event that the CO sensor requires calibration, consult the factory for  
2
information on obtaining calibration equipment and instructions.  
Table 25: CO versus voltage table  
2
CO2 (PPM)  
300  
VDC (V)  
1.5  
CO2 (PPM)  
1200  
VDC (V)  
6.0  
400  
2.0  
1300  
6.5  
500  
2.5  
1400  
7.0  
600  
3.0  
1500  
7.5  
700  
3.5  
1600  
8.0  
800  
4.0  
1700  
8.5  
900  
4.5  
1800  
9.0  
1000  
5.0  
1900  
9.5  
46  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
UVC Configuration Parameters  
UVC Configuration Parameters  
The UVC is been provided with a number of configuration variables as listed in the following  
table. These configuration variables are stored in UVC non-volatile memory. For a description  
of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED  
15065.  
Table 26: UVC configuration parameters (OM 751)  
LUI Menu  
Configuration Parameter Name  
Occupied Cooling Setpoint  
Standby Cooling Setpoint  
Abr.  
Notes  
Default  
Item1  
Co  
C5  
CU  
Ho  
H5  
HU  
OCS  
SCS  
UCS  
OHS  
SHS  
UHS  
73°F (23°C)  
77°F (25°C)  
82°F (28°C)  
70°F (21°C)  
66°F (19°C)  
61°F (16°C)  
120 min  
Unoccupied Cooling Setpoint  
Occupied Heating Setpoint  
Standby Heating Setpoint  
Unoccupied Heating Setpoint  
Local Bypass Time  
2
Tenant override  
Space CO Setpoint  
2
CO S  
2
1200 PPM  
2
Space Humidity Setpoint  
Emergency Heat Enable  
used with both active (reheat) and passive dehumidification  
sequences  
RHS  
60% Rh  
0 = disable, 1 = enable (uses auxiliary heat where primary heat is  
not applicable)  
1
H1  
H2  
H3  
Emergency Heat Setpoint  
EHS  
54°F (12°C)  
0
Emergency Heat Shutdown  
Configuration  
0 = no emergency heat during shutdown, 1 = emergency heat  
available during shutdown  
2
Wall Sensor Type  
0 = +/- 3°F, 1 = 55°F to 85°F  
0
0
r5  
SL  
2
Slave Type Configuration  
0 = independent slave, 1 = dependent slave  
OAD Min Position High-Speed Setpoint  
OAD Min Position Med-Speed Setpoint  
OAD Min Position Low-Speed Setpoint  
(this variable will be factory set to 5% open when the unit is ordered  
OADH  
OADM  
OADL  
EOAD  
20% open  
25% open  
30% open  
99% open  
o2  
o3  
o4  
o5  
with optional CO DCV)  
2
(this variable is ignored when the unit is ordered with optional CO  
DCV)  
2
2
(this variable is ignored when the unit is ordered with optional CO  
DCV)  
Exhaust Interlock OAD Min Position  
Setpoint  
OA damper minimum position when the exhaust interlock input is  
energized  
Energize Exhaust Fan OAD Setpoint  
defines position above which exhaust fan output will be energized  
OADE  
OAMX  
12% open  
99% open  
o6  
o7  
OAD Max Position Setpoint  
OAD Lockout Enable  
0 = disable, 1 = enable (this variable will be factory set to 1 when  
the unit is ordered as a recirc unit with no OAD)  
0
o8  
OAD Lockout Setpoint  
OA temperature below which the OA damper will remain closed  
OALS (this variable will be factory set to –99°C when the unit is ordered  
as a recirc unit with no OAD)  
36°F (2°C)  
o9  
Economizer Enable  
0 = disable, 1 = enable  
1
E1  
E2  
e3  
e5  
e6  
B3  
B6  
CE  
Economizer OA Temp Setpoint  
Economizer IA/OA Temp Differential  
Economizer OA Enthalpy Setpoint  
Economizer IA/OA Enthalpy Differential  
External BI-3 Configuration  
External BO-3 Configuration  
Filter Alarm Enable  
ETS  
ETD  
EES  
68°F (20°C)  
2°F (1°C)  
25 btu/lb (58 kJ/kg)  
EED  
1.3 btu/lb (3 kJ/kg)  
0 = Ventilation Lockout, 1 = Exhaust Interlock  
0
0 = Exhaust Fan On/Off, 1 = Auxiliary Heat  
0 = disable, 1 = enable  
0
0
Filter Change Hours Setpoint  
fan run hours between filter change alarms  
700 hrs  
McQuay OM 751  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
UVC Configuration Parameters  
LUI Menu  
Item1  
Configuration Parameter Name  
Primary Cool Proportional Band  
Primary Cool Integral Time  
Abr.  
Notes  
Default  
18°F (10°C)  
180 sec  
Secondary Cool Proportional Band  
Secondary Cool Integral Time  
18°F (10°C)  
600 sec  
Discharge Air Temp Proportional Band  
4°F (2.22°C)  
300 sec  
Discharge Air Temp Integral Time  
2
CO Proportional Band  
2
100 PPM  
600 sec  
2
CO Integral Time  
2
Ventilation Cooling Low Limit Setpoint  
Mechanical Cooling Low Limit Setpoint  
Discharge Air High Limit  
discharge air low limit during ventilation or economizer cooling  
discharge air low limit during mechanical (compressor) cooling  
VCLL  
MCLL  
DAHL  
54°F (12°C)  
45°F (7°C)  
140°F (60°C)  
30 sec  
d2  
d3  
Space Fan Off Delay  
Fan Cycling Configuration  
space fan operation during occupied, standby and bypass  
occupancy modes: 2 = continuous, 3 = cycle  
example: 6/60min = 10min (maximum of 1 fan speed change every  
10min when fan in auto)  
2
6
0
0
CF  
C!  
Space Fan Speed Changes Per Hour  
Space Fan Run Time Reset  
reset total run time: 1 = reset (you must return the variable back to  
0 after reset)  
Compressor Run Time Reset  
reset total run time: 1 = reset (you must return the variable back to  
0 after reset)  
Compressor Enable  
0 = disable, 1 = enable  
1
Compressor Minimum On Time  
Compressor Minimum Off Time  
Compressor Cooling Lockout Setpoint  
Compressor Envelope Cool Max In  
Compressor Envelope Cool Min In  
Compressor Envelope Cool Max Out  
Compressor Envelope Cool Min Out  
Compressor Envelope Cool Max Ratio  
Compressor Envelope Cool Max Offset  
Compressor Envelope Cool Min Ratio  
Compressor Envelope Cool Min Offset  
Auxiliary Heat Start Differential  
180 sec  
300 sec  
OA temperature below which compressor cooling is not allowed  
CCLO  
63.5°F (17.5°C)  
120°F (48.89°C)  
28°F (-2.22°C)  
160°F (71.11°C)  
40°F (4.44°C)  
0.00  
88°F (48.89°C)  
0.0  
-4°F (-2.22°C)  
2°F (1°C)  
degrees above auxiliary heat start point where auxiliary heat ends  
degrees above auxiliary heat start point where auxiliary heat ends  
AHSD  
AHED  
A1  
A2  
Auxiliary Heat End Differential  
2°F (1°C)  
Auxiliary Heat Configuration  
0 = normally open heat device (hot water valve, etc.),  
1 = normally closed heat device (electric heat, etc.)  
0 = disable, 1 = enable (this variable will be factory set to 1 when  
the unit is ordered with optional humidity sensor)  
0
0
0
A3  
2
Space Humidity Sensor Enable  
2
Outdoor Humidity Sensor Enable  
0 = disable, 1 = enable (this variable will be factory set to 1 when  
the unit is ordered with optional humidity sensor)  
48  
McQuay OM 751  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVC Configuration Parameters  
LUI Menu  
Configuration Parameter Name  
OAD Stroke Time  
Abr.  
Notes  
Default  
Item1  
90 sec  
Split-System OA/DX Coil Temp  
used on split-system units only to partially disable the compressor  
envelope by setting the outside DX coil temperature to a fixed valid  
value, enter 122°F (50°C) on split-systems, use 327.67 for self-  
contained units (327.67 = invalid)  
327.76  
Application Name and Version Label  
Compressor Start Delay  
adjust the compressor delay used to prevent multiple compressor  
units from starting simultaneously (each unit or group of units  
should have a different delay setting)  
0 sec  
C6  
Outdoor Fan Delay  
10 sec  
1. Indicates parameters accessible through the keypad/display.  
2. Requires optional equipment.  
McQuay OM 751  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
McQuay Training and Development  
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority.  
call 540-248-9646 and ask for the Training Department.  
Warranty  
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product  
Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your  
This document contains the most current product information as of this printing. For the most up-to-date product  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acer Personal Computer Altos G500 User Manual
Adaptec Network Card APA 1350 User Manual
ADC Network Router Intelligent Patching User Manual
Aiphone Intercom System C 123LW User Manual
Aiphone TV Mount KMB 45 User Manual
Alienware Personal Computer X51 R2 User Manual
Allegro Industries Plumbing Product 04066XX0 User Manual
Allied Telesis Network Card AT AR040 10 User Manual
Alpine CD Player CDA 7865R User Manual
BK Stereo Amplifier 7250 User Manual