Amana Ventilation Hood HRV 150 User Manual

Heat Recovery  
Ventilators  
HRV-150 • HRV-150D  
HRV-200 • HRV-200D • HRV-300D  
IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT  
CAUTION - Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equip-  
ment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed  
by measuring the airflow’s of the Heat Recovery or Energy Recovery Ventilators by using the balancing procedure found in this manual.  
It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood  
Stoves, etc.).  
NEVER - install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper function-  
ing of vented combustion equipment!!!  
Your ventilation system should be installed in conformance with the appropriate provincial or state requirements or in the absence  
of such requirements with the current edition of the National Building Code, and / or ASHRAE’s “ Good Engineering Practices”.  
INSTALLATION, OPERATION AND MAINTENANCE MANUAL  
Goodman is a registered trademark of Goodman Company, L.P.  
Amana is a registered trademark of Maytag Corporation and used under license to Goodman Company, L..P.  
All rights reserved.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
HRV Series  
HRV 150D & HRV 200D  
SPECIFICATIONS  
CASE 22 gauge galvanized steel on the HRV-200D & 24  
gauge galvanized steel on the HRV 150D. Baked powder  
coated paint. Insulated with 1" (25 mm) high density  
polystyrene foam to prevent condensation and meet the  
requirements of the Underwriters Laboratories 94HF.  
MOTORS Two (2) German-manufactured, factory-balanced  
ebm™ motors with backward curved blades. Motors come  
with permanently lubricated sealed bearings guarantee long  
life and maintenance-free operation. Seven (7) year limited  
warranty.*  
CORE Aluminum heat recovery core configured for an  
efficient cross-flow ventilation. Core is 9" x 9" (229 x 229  
mm) with a 15" (380 mm) depth HRV 150D or 12" x 12"  
(305 x 305 mm) with a 15" (380 mm) depth HRV 200D.  
Cores are manufactured to withstand extreme temperature  
variations.  
Introducing the NEW Heat Recovery Ventilators (HRV). As  
with previous designs, incoming fresh outdoor air is filtered  
before it is heated by the stale outgoing air through a  
aluminum heat recovery core. The HRV then distributes the  
preheated fresh filtered air throughout the home by direct  
ductwork installed specifically for the HRV or through the  
ductwork of a forced-air system.  
FILTERS Two (2) Washable Electrostatic Panel Type Air Filters,  
HRV 150D is 8.5" (216mm) x 15" (380mm) x 0.125"  
(3mm), HRV 200D is 11.75" (298mm) x 15" (380mm) x  
0.125" (3mm).  
FEATURES:  
CONTROLS External three (3) position (Low/Stand  
By/Medium) rocker switch that will offer continuous  
ventilation. We offer a variety of external controls.  
(see optional controls)  
• Compact Design  
• Electrostatic Filters (washable)  
• Airflow Balancing Using Our Easy "TRUE" Motor  
Adjustment  
DEFROST A preset 5 minute defrost sequence is activated at  
an outdoor air temperature of 23˚F (-5˚C) and lower.  
• External Screw Type Dry Contacts For Push Button  
Timers, Dehumidistat, Crank Timer & Digital Control.  
• Easy Core Guide Channels For Removing Core  
• Better Packaging For More Protection In Shipping  
During the defrost sequence, its mechanism uses a  
motorized damper to temporarily block the incoming fresh  
air stream allowing the warm air from the home to circulate  
through the HRV. The exhaust blower shuts down & the  
supply blower switches into high speed to maximize the  
effectiveness of the defrost strategy.  
OPTIONAL CONTROLS  
• DMFC-REC – Digital Multi-Function Control  
• MD-4W  
– Mechanical Low Voltage Dehumidistat  
with On/Off Switch  
The unit then returns to normal operation for 25 minutes,  
and continues cycle.  
• MD-2W  
• RT-15M  
• CT-30M  
• AQS  
– Mechanical Low Voltage Dehumidistat  
– 15 Minute Push Button Timer  
– 30 Minute Crank Timer  
SERVICEABILITY Core, filters, motors and drain pan can be  
easily serviced through latched access door. Core  
conveniently slides out with ease on an improved railing  
system. Electrical box, placed on the outside of the unit,  
can also be easily accessed.  
– Air Quality Sensor  
External screw type dry contacts (provided)  
* For details concerning warranties, please visit your local dealer.  
3
The product is manufactured by Fantech, Inc. Fantech reserves the right to modify, at any time and without notice, any or all of this product's features, designs, components and specifications.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HRV-150D & HRV-200D  
Dimensions  
5TH port for recirculation defrost type models only  
E
6"  
A
B
C
D
Model  
A
B
C
D
E
HRV-150D  
HRV-200D  
2 ¹⁄₄" (56mm)  
2 ¹⁄₄" (56mm)  
23 ¹⁄₂" (596mm)  
27 ⁷⁄₈" (707mm)  
2 ⁵⁄₈" (67mm)  
2 ⁵⁄₈" (67mm)  
17 ³⁄₈" (441mm)  
17 ³⁄₈" (441mm)  
17 ³⁄₈" (441mm)  
20 ¹⁄₂" (520mm)  
Fan Performance  
Performance Data  
Airflow (L/s)  
57  
0
19  
38  
76  
94  
114  
300  
1.2  
1
Apparent Sensible Apparent Sensible  
Effectiveness at Effectiveness at -  
250  
200  
150  
100  
50  
Model  
32ºF (0ºC)  
13ºF (-25ºC)  
HRV-200D  
0.8  
0.6  
0.4  
0.2  
0
HRV-150D  
HRV-200D  
72 %  
71 %  
69 %  
76 %  
AIRFLOW CAP. cfm (L/s) @ 0.4 on High Speed  
Power  
• Volts  
120 VAC  
HRV-150D  
• Amperage  
HRV-150D  
HRV-200D  
• Phase  
1.5 Amps Total  
1.9 Amps Total  
Single Phase  
0
240  
0
40  
80  
120  
160  
200  
Airflow (cfm)  
TH  
5 port for recirculation defrost models  
only can be ducted or left open  
Airflow  
Fresh Air  
From Outside  
Stale Air  
From Inside  
Fresh Air  
To Inside  
Stale Air  
To Outside  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
HRV Series  
HRV 150 & HRV 200  
SPECIFICATIONS  
CASE 22 gauge galvanized steel on the HRV-200 & 24 gauge  
galvanized steel on the HRV-150. Baked powder coated  
paint. Insulated with 1" (25 mm) high density polystyrene  
foam to prevent condensation and meet the requirements of  
the Underwriters Laboratories 94HF.  
MOTORS Two (2) German-manufactured, factory-balanced  
ebm™ motors with backward curved blades. Motors come  
with permanently lubricated sealed bearings guarantee long  
life and maintenance-free operation. Seven (7) year limited  
limited warranty.*  
CORE Aluminum heat recovery core configured for an  
efficient cross-flow ventilation. Core is 9" x 9" (229 x 229  
mm) with a 15" (380 mm) depth HRV-150 or 12" x 12"  
(305 x 305 mm) with a 15" (380 mm) depth HRV-200.  
Cores are manufactured to withstand extreme temperature  
variations.  
Introducing the NEW Heat Recovery Ventilators (HRV). As  
with previous designs, incoming fresh outdoor air is filtered  
before it is heated by the stale outgoing air through a  
aluminum heat recovery core. The HRV then distributes the  
preheated fresh filtered air throughout the home by direct  
ductwork installed specifically for the HRV or through the  
ductwork of a forced-air system.  
FILTERS Two (2) Washable Electrostatic Panel Type Air Filters,  
HRV-150 is 8.5" (216mm) x 15" (380mm) x 0.125" (3mm),  
HRV-200 is 11.75" (298mm) x 15" (380mm) x 0.125"  
(3mm).  
FEATURES:  
CONTROLS External three (3) position (Low/Stand  
By/Medium) rocker switch that will offer continuous  
ventilation. We offer a variety of external controls. (see  
optional controls)  
• Compact Design  
• Electrostatic Filters (washable)  
• Balancing Dampers Included In Installation Kit  
(not factory installed)  
DEFROST A preset 5 minute defrost sequence is activated at  
an outdoor air temperature of 23˚F (-5˚C) and lower.  
• External Screw Type Dry Contacts For Push Button  
Timers, Dehumidistats, Crank Timer & Digital Control.  
• Easy Core Guide Channels For Removing Core  
• Better Packaging For More Protection In Shipping  
During the defrost sequence, the supply blower shuts down  
& the exhaust blower switches into high speed to maximize  
the effectiveness of the defrost strategy.  
OPTIONAL CONTROLS  
The unit then returns to normal operation for 25 minutes,  
and continues cycle.  
• DMFC  
• MD-4W  
– Digital Multi-Function Control  
– Mechanical Low Voltage Dehumidistat  
with On/Off Switch  
– Mechanical Low Voltage Dehumidistat  
– 15 Minute Push Button Timer  
– 30 Minute Crank Timer  
SERVICEABILITY Core, filters, motors and drain pan can be  
easily serviced through latched access door. Core  
conveniently slides out with ease on an improved railing  
system. Electrical box, placed on the outside of the unit, can  
also be easily accessed.  
• MD-2W  
• RT-15M  
• CT-30M  
• AQS  
– Air Quality Sensor  
External screw type dry contacts (provided)  
* For details concerning warranties, please visit your local dealer.  
5
The product is manufactured by Fantech, Inc. Fantech reserves the right to modify, at any time and without notice, any or all of this product's features, designs, components and specifications.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HRV-150 & HRV-200  
Dimensions  
E
6"  
B
D
A
C
Model  
A
B
C
D
E
HRV-150  
HRV-200  
2 ¹⁄₄" (56mm)  
2 ¹⁄₄" (56mm)  
23 ¹⁄₂" (596mm)  
27 ⁷⁄₈" (707mm)  
2 ⁵⁄₈" (67mm)  
2 ⁵⁄₈" (67mm)  
17 ³⁄₈" (441mm)  
17 ³⁄₈" (441mm)  
16 ¹⁄₈" (413mm)  
20 ¹⁄₂" (520mm)  
Fan Performance  
Performance Data  
Airflow (L/s)  
57  
0
19  
38  
76  
94  
114  
300  
1.2  
Apparent Sensible Apparent Sensible  
Effectiveness at Effectiveness at -  
Model  
1
250  
200  
150  
100  
50  
32ºF (0ºC)  
13ºF (-25ºC)  
SHR 2004  
HRV-200  
0.8  
0.6  
0.4  
0.2  
0
HRV-150  
HRV-200  
72 %  
71 %  
69 %  
76 %  
AIRFLOW CAP. cfm (L/s) @ 0.4 on High Speed  
Power  
• Volts  
120 VAC  
• Amperage  
HRV-150  
HRV-200  
• Phase  
1.5 Amps Total  
1.9 Amps Total  
Single Phase  
HRV-150  
0
240  
0
40  
80  
120  
Airflow (cfm)  
160  
200  
Airflow  
Fresh Air  
From Outside  
Stale Air  
From Inside  
Fresh Air  
To Inside  
Stale Air  
To Outside  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
HRV Series  
HRV-300D  
SPECIFICATIONS  
CASE 22 gauge galvanized steel. Baked powder coated paint.  
Insulated with 1" (25 mm) high density polystyrene foam to  
prevent condensation and meet the requirements of the  
Underwriters Laboratories 94HF.  
MOTORS Two (2) German-manufactured, factory-balanced  
ebm™ motors with backward curved blades. Motors come  
with permanently lubricated sealed bearings guarantee long  
life and maintenance-free operation. Seven (7) year limited  
warranty.*  
CORES Two (2) aluminum heat recovery cores configured for  
an efficient cross-flow ventilation. Core is 12" x 12" (305 x  
305 mm) with a 15" (380 mm) depth. Cores are  
manufactured to withstand extreme temperature variations.  
Introducing the NEW Heat Recovery Ventilators (HRV). As  
with previous designs, incoming fresh outdoor air is filtered  
before it is heated by the stale outgoing air. The HRV then  
distributes the preheated fresh filtered air throughout the  
home by direct ductwork installed specifically for the HRV or  
through the ductwork of a forced-air system.  
FILTERS Two (2) synthetic high quality filters for better indoor  
air quality and clean air.  
CONTROLS External three (3) position (Low/Stand  
By/Medium) rocker switch that will offer continuous  
ventilation. We offer a variety of external controls.  
(see optional controls)  
FEATURES:  
DEFROST A preset 5 minute defrost sequence is activated at  
an outdoor air temperature of 23˚F (-5˚C) and lower.  
• Balancing Dampers Included In Installation Kit  
(not factory installed  
)
• External Screw Type Dry Contacts For Push Button  
Timers, Dehumidistats, Crank Timer & Digital Control.  
During the HRV-300 defrost sequence, its mechanism uses  
a motorized damper to temporarily block the incoming fresh  
air stream allowing the warm air from the home to circulate  
through the HRV. The exhaust blower shuts down & the  
supply blower switches into high speed to maximize the  
effectiveness of the defrost strategy.  
OPTIONAL CONTROLS  
• DMFC-REC – Digital Multi-Function Control  
• MD-4W  
– Mechanical Low Voltage Dehumidistat  
with On/Off Switch  
The unit then returns to normal operation for 25 minutes,  
and continues cycle.  
• MD-2W  
• RT-15M  
• CT-30M  
• AQS  
– Mechanical Low Voltage Dehumidistat  
– 15 Minute Push Button Timer  
– 30 Minute Crank Timer  
SERVICEABILITY Core, filters, motors and drain pan can be  
easily serviced through latched access door.  
– Air Quality Sensor  
External screw type dry contacts (provided)  
* For details concerning warranties, please visit your local dealer.  
7
The product is manufactured by Fantech, Inc. Fantech reserves the right to modify, at any time and without notice, any or all of this product's features, designs, components and specifications.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HRV-300D  
Dimensions  
5TH port for recirculation defrost  
type models only  
22.20"  
564mm  
6"  
2.20"  
56mm  
50.87"  
1292mm  
2.20"  
56mm  
17.36"  
441mm  
Fan Performance  
Performance Data  
Airflow (L/s)  
0.00  
1.2  
19.00  
38.00  
57.00  
76.00  
94.00  
114.00  
123.00  
142.00  
162.00  
300.00  
Apparent Sensible Apparent Sensible  
Effectiveness at Effectiveness at -  
1
0.8  
0.6  
0.4  
0.2  
0
250.00  
200.00  
150.00  
100.00  
50.00  
Model  
32ºF (0ºC)  
13ºF (-25ºC)  
HRV-300D  
HRV-300D  
92 %  
91 %  
AIRFLOW CAP. cfm (L/s) @ 0.4 on High Speed  
Power  
0.00  
360.00  
• Volts  
120 VAC  
0.00  
40.00  
80.00  
120.00  
160.00  
200.00  
240.00  
280.00  
320.00  
Airflow (cfm)  
• Amperage  
• Phase  
2.7 Amps Total  
Single Phase  
TH  
5 port for recirculation defrost models  
only, can be ducted or left open  
Airflow  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
A Heat Recovery Ventilator (HRV) is designed to bring fresh air into a building while exhausting an equal amount of stale air. During the winter  
months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During  
summer months when the indoor space is air conditioned, the HRV will help in cooling the incoming fresh air with the stale air that is being  
exhausted.  
Our HRV’s are designed to run continuous or on intermittent, giving the homeowner complete control over their air quality. Continuous low speed  
ventilation is recommended, which will help eliminate carbon dioxide, voc’s and other gases as well as freshen up the home. Intermittent high  
speed ventilation can be obtained through a variety of optional remote controls found in this manual (page 13 ). Below are some examples of sea-  
sonal operation of an HRV.  
Winter:  
Spring:  
Humidity control is very important during the winter  
months. This is when problems will be most apparent  
since condensation on the windows will often occur. The  
colder the outside temperature, the greater the risk of  
condensation in the home. The average relative humidity  
should be maintained between (30-60) to avoid conden-  
sation. Low speed continuous ventilation with high speed override is rec-  
ommended.  
Temperatures are more moderate and become  
warmer each day. To keep the humidity and tem-  
perature uniform, set the dehumidistat higher (if  
installed). You may also switch the HRV to standby  
mode if desired.  
Summer:  
Fall:  
The air is sometimes hot and humid. To stop the warm  
humid air from entering, set the dehumidistat at its  
highest level. If the digital control is installed, the air  
exchanger can be set to cycle the unit on and off as  
desired from that wall control. However, continuous ven-  
tilation is recommended.  
Rain and rapid temperature changes make it diffi-  
cult to control the internal humidity level and may  
result in condensation on the windows. A remote  
dehumidistat may help give greater control over the  
inside environment.  
MODES OF OPERATION  
The entire line of Heat Recovery comes equipped with our new electronic uni-control board which offers a wide variety of features making it the ulti-  
mate ventilation control system. Our engineers have used the latest technology to provide solid, trouble free operation under any conditions.  
The uni-control board offers stand alone operating capabilities as well as an exclusive 2 wire communication to most external controls. The trouble-  
free optional controls include: two different rotary dial dehumidistats, an air quality sensor (3 wire communication required), a 15 minute remote  
push-button timer, as well as the most sophisticated line of remote wall mounted controls, the digital control.  
An on-board diagnostic LED helps find problems quickly and efficiently. For example the LED can be used to signal a broken or shorted electronic  
wall control wire. Electronic air temperature probe gives this board accurate readings in order to minimize unnecessary defrost operation, and the  
on-board jumpers provide the user with the option of adjusting defrost time and sequence to optimize performance under abnormal conditions. The  
defrost operation is automatic and is usually never adjusted.  
* no exchange of air  
2. Intermittent / Standby Mode  
The system is always on standby and operates  
at high speed when activated by an optional  
remote control. "Standby" should be selected  
if the user wishes to stop the unit from  
Air from  
1. Continuous / Ventilation Mode  
Air from  
House  
Outside  
In this mode of operation both fans  
are operating and exchanging air with  
the outside. The heat recovery venti-  
lator (HRV) constantly exchanges the  
Air to  
House  
Air to  
Outside  
continuous exchange. We recommend that  
air at the rate you select, either at low or medium speed, and switches  
to high speed when activated by an optional remote control. The "Low"  
and "Med" fan speed selection will cause the unit to operate in continuous  
exchange mode at an exchange rate of 35% and 50% maximum airflow  
rating respectively. Continuous mode is recommended, since pollutants  
are slowly but constantly being generated in your house.  
the "Standby" mode only be used if your system is equipped with an  
optional external control, in which case, the unit would activate to  
"High" fan speed, until the control is satisfied and then return to  
standby (off).  
4. Defrost (Fan shutdown 4 port  
Air from  
House  
3.Defrost/Recirculation Mode  
Air from  
House  
models)  
(5 port “R” Models)  
The automatic defrost cycle con-  
sists of a fan shutdown. When the  
supply air stream temperature  
The automatic defrost cycle consists  
of a damper defrost which allows air  
to recirculate throughout the unit &  
Air to  
outside  
Air to  
House  
goes below -5°C (23°F), the sup-  
ply motor shuts down and the exhaust motor goes into high speed.  
Ambient air is passed through the unit for a period of 5 minutes. The  
supply motor will then re-start and run at the preset speed. The  
exhaust motor will also slow down to the preset speed, and the unit  
will operate in the run cycle for 25 minutes. This fan shutdown  
defrost cycle continues until the supply air stream rises above 0°C  
(32°F).  
home. When the supply air stream  
temperature goes below -5°C (23°F), the exhaust motor shuts down, the  
supply motor goes to high speed, and a damper closes the supply, open-  
ing a 5th collar. The ambient air is then recirculated through the unit &  
home for a period of 5 minutes. The unit will then resume normal opera-  
tion for a time period of 25 minutes. This damper defrost cycle continues  
until the supply air stream rises above 0°C (32°F). The recirculation fea-  
ture can be obtained with the use of an optional digital control.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION (CONT'D)  
* All controls are low voltage. 18 to 24  
gauge wire is recommended.  
OPTIONAL REMOTE CONTROLS  
PRACTICAL  
TIPS  
Dehumidistat - MD-2W - The wall mount dehumidistat monitors the humidity  
level in the area it is installed. When the humidity level rises above the  
desired set-point, the HRV will activate to high speed/override mode. Once  
the humidity level returns to desired condition, the unit will return to the  
normal mode.  
To avoid window condensation:  
• It is not necessary to  
change the humidity control  
every day. Monitor the  
average weekly  
2 wire installation  
Dehumidistat - MD-4W - The wall mount dehumidistat offers the same  
features of the dehumidistat I plus additional off/on control for the HRV.  
Dial illuminates when in override mode.  
temperature or experiment  
with various settings until  
you find a level that is  
comfortable for you. Adjust  
the control when needed.  
NOTE:  
4 wire installation  
A dehumidistat is ideal for  
use in energy efficient  
houses where indoor  
humidity (during the  
heating season) is higher  
than outdoor levels. High  
humidity is a major cause  
of structure damage and  
IAQ problems such as mold  
and mildew.  
Air Quality Sensor - AQS - The wall mount Air Quality Sensor (AQS) monitors  
indoor air quality and activates the override mode when carbon monoxide,  
formaldehyde, benzene, volatile organic compounds and other pollutants are  
detected. The unit will then return to normal mode once the air pollutants  
are reduced to a pre-determined lower level.  
* This control is not a warning device.  
3 wire installation  
2 wire installation  
15-min Timer - RT-15M - The 15-minute remote timer is typically installed in  
areas where contaminated such as moisture and odors, are produced. Simply  
push the button and the HRV will activate to high speed for 15 minutes. Up  
to 5 electronic timers can be installed throughout the building at a distance  
of up to 500 feet (152 meters) from the HRV.  
PRACTICAL  
TIPS  
OPTIONAL DIGITAL CONTROL  
DEHUMIDISTAT CONTROL  
(see description on top of this page)  
DIGITAL DISPLAY  
DMFC-REC  
DIGITAL MULTI-FUNCTION  
WALL CONTROL WITH  
RECIRCULATION  
Control multiple functions of  
your HRV with one slimline  
wall control. Two wire connec-  
tion simplifies installation.  
Use one control per HRV  
installed.  
NOTE:  
Shows Indoor Humidity Level  
This control will not read  
below 29% RH  
When an digital control is  
installed, the rocker switch  
located on the right hand  
side of the HRV will be  
automatically deactivated  
giving the user complete  
control from wherever  
he/she wishes to mount the  
control pad.  
4 1/2"  
(114 mm)  
OVERRIDE TIMER  
When pressed, unit  
will provide high  
speed  
ventilation  
for one 15,  
30 or 60 minute  
period.  
NOTE:  
The override speed cannot  
be set at a fan speed lower  
or equal to the normal  
operating fan speed. For  
example, if the unit is  
normally operating at a  
medium fan speed, the  
override fan speed will be  
automatically set to high.  
5 1/8"  
(130 mm)  
MAINTENANCE LIGHT  
Light comes on when  
it’s time to clean  
unit.  
Width = 4 1/2" (114mm)  
Height = 5 1/8" (130mm)  
Thickness = 5/8" (16mm)  
NOTE:  
DMFC-REC model, changing  
the override speed will  
change default override  
speed for other external  
controls.  
* Both digital controls  
are the same size  
POWER  
On/Off and Reset  
EXAMPLES:  
If on the DMFC-REC control,  
you have set the override  
control at medium, and you  
start an external remote  
control, the unit will run at  
medium speed for 15 min.  
MODES  
MODE SPEED  
CYCLE CONTROL  
OVERRIDE SPEED  
CONTROL  
Push to select  
override speed of  
unit.  
Select Intermittent,  
Recirculation or  
Continuous  
Set Unit to Low,  
Medium or High  
Speed  
Set unit to cycle on  
15, 20, or 30 min-  
utes every hour  
Ventilation Modes  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION (CONT'D)  
OPTIONAL DIGITAL CONTROL  
DIGITAL DISPLAY  
DEHUMIDISTAT CONTROL  
Shows Indoor Humidity Level  
This control will not read below  
29% RH  
A Dehumidistat is ideal for use in energy efficient houses where  
indoor humidity (during the heating season) is higher than outdoor  
levels. High humidity is a major cause of structure damage and IAQ  
problems such as mold and mildew.  
DMFC  
DIGITAL MULTI-FUNCTION  
WALL CONTROL  
Control multiple functions of  
your HRV with one slimline  
wall control. Two wire connec-  
tion simplifies installation.  
Use one control per HRV  
installed.  
OVERRIDE TIMER  
When pressed, unit will  
provide high speed  
ventilation for 15 minute  
period. Once the time  
elapsed the unit will return  
to its normal function. To  
move from one time to the  
other, continue pressing the  
timer button until you reach  
the desired time.  
POWER  
On/Off and Reset  
MAINTENANCE LIGHT  
This function is to turn your  
unit on or off, in the off posi-  
tion the damper is open and  
you will feel the cold outside  
air come in. To go from the  
on to off position just press  
once.  
Light comes on when it’s time  
to clean unit. This function will  
let you know when it's time to  
check your filters and core. To  
reset your filter light, after  
you've cleaned or replaced the  
filters, just push the power but-  
ton and restart the unit. This  
will turn the light off and reset  
the clock for your filter check.  
FILTER LIGHT RESET & MODE FAN  
MODES  
The LCD (Liquid Crystal Display) indicates the percentage of Relative Select Intermittent, or  
DEHUMIDISTAT CONTROL  
SPEED SELECTOR  
Press to reset the filter mainte-  
nance reminder light. The combi-  
nation filter light reset and up  
setpoint selector buttons let’s  
you choose at which speed the  
HRV, ERV unit will operate in  
continuous or recirculation mode  
only. Pressing the filter light  
reset button once displays the  
mode fan speed on the LCD. The  
LCD should display one of the  
following three letters, L for  
Low, M for Medium and H for  
High. To change the mode  
speed, press the up setpoint  
until desired speed is displayed,  
selector. After 1 second of inac-  
tivity, the LCD will return to rel-  
ative humidity reading.  
Humidity in the air surrounding the control and ultimately in the Continuous Ventilation Modes.  
house. Pressing either of the setpoint selectors (  
,
) once, will Continuous  
display the desired RH level. The setpoint selection mode is now acti-  
vated and can be adjusted with either selectors to a newly desired  
setpoint. The LCD will return to the actual RH level display after a few air.  
This function will exchange  
outside air with your stale  
seconds.  
Intermittent  
This function will put your  
unit on stand by and can  
be over ride by timer, air quality  
sensor, etc  
To move from function to the  
other, continue pressing the  
mode button until you reach the  
desired function. This function  
goes from Recirculation,  
Continuous to Intermittent.  
Note: All controls are low voltage. 18 to 24 gauge wire is recommended.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
PRACTICAL TIPS  
LOCATION  
The HRV must be located in a heated space where it will be possible to conveniently service the  
unit. Typically the HRV would be located in the mechanical room or an area close to the outside  
wall where the weatherhoods will be mounted. If a basement area is not convenient or does not  
exist, a utility or laundry room may be used.  
Attic installations are not normally recommended due to:  
- the complexity of work to install  
• Install the unit close to  
the outside wall on  
which the supply and  
exhaust hoods will be  
mounted.  
- freezing conditions in the attic  
- difficulty of access for service and cleaning  
Connecting appliances to the HRV It is not recommended, including:  
- clothes dryer  
• Have a nearby power  
supply 120 Volts, 60Hz.  
- range top  
- stovetop fan  
- central vacuum system  
• Have the possibility of  
mounting the unit to  
supporting beams.  
These appliance may cause lint, dust or grease to collect in the HRV , damaging the unit.  
NOTE: Connecting any of these type of appliances to the HRV will invalidate your warranty  
• Mount the unit as  
level as possible in  
order to allow proper  
condensate drainage.  
MOUNTING  
• Have access to  
a water drain for the  
condensate of the unit  
during defrost.  
• Have a certain amount  
of heat around the unit  
(attic installation is not  
recommended).  
1 Place Fastening hooks  
on the strapping board  
or the floor joists.  
2 Attach a hanging chain  
(provided) to each 10 3/4”  
(19 mm) bolt (provided) in  
the top 4 corners of the  
unit and tighten.  
3 Hang the unit by  
slipping a link onto the  
hanging hooks, making  
sure the unit is level.  
• Minimize any noise  
level that would be  
created by the unit in  
the living area.  
Installing Drain Line  
• Have access for future  
maintenance.  
Through normal operation and during its defrost mode, the HRV may produce some condensation.  
This water should flow into a nearby drain, or be taken away by a condensate pump. The HRV and  
all condensate lines must be installed in a space where the temperature is maintained above the  
freezing point. A “P” trap should be made in the drain line. This will prevent odors from being  
drawn back up into the unit.  
1 Install the drain nipple.  
2 Install the drain hose,  
making a “P” trap  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLING DUCTS GOING TO / FROM OUTSIDE  
A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency.  
Always try to keep duct runs as short and straight as possible.  
See Installation Diagrams for installation examples.  
INSTALLING THE DUCTING  
TO THE WEATHERHOODS  
PRACTICAL  
TIPS  
The inner liner of the flexible insulated duct  
must be clamped to the sleeve of the weath-  
erhoods (as close to the outside as possible)  
and to the appropriate port on the HRV. The  
insulation should remain full and not be  
squished. The outer liner, which acts as a  
vapor barrier must be completely sealed to  
outer wall and the HRV using tape and or  
caulking. A good bead of high quality caulk-  
ing (preferably acoustical sealant) will seal  
•Decide where your intake and  
exhaust hoods will be located.  
Locating the Intake  
Weatherhood  
• Should be located upstream  
(if there are prevailing winds)  
from the exhaust outlet  
• At least 4' - 6’ (2m) from the  
exhaust weatherhood  
• At least 6’ (2m) away from  
dryer vents and furnace  
exhaust ( medium or high effi-  
ciency furnaces)  
• A minimum of at least 6’ (2m)  
from driveways, oil fill pipes,  
gas meters, or garbage con-  
tainers  
• At least 18” (457mm) above  
the ground, or above the  
depth of expected snow accu-  
mulation  
• At least 3’ (1m) from the cor-  
ner of the building  
the inner flexible duct to both the HRV port  
Model  
Description  
and the weatherhood prior to clamping.  
SEH-6P  
Supply & Exhaust Plastic Hood Kit  
Supply & Exhaust Metal Hood Kit  
To minimize air flow restriction, the flexible  
SEH-6M  
insulated duct that connects the two outside  
weatherhoods to the HRV should be  
stretched tightly and be as short as possible.  
Twisting of folding the duct will severely  
restrict air flow.  
* Application for Supply or Exhaust  
• Do not locate in a garage,  
attic or crawl space  
Locating the Exhaust  
Weatherhood  
• At least 4' - 6’ (1m - 2m)  
from the ventilation air intake  
• At least 18” (457mm) above  
ground or above the depth of  
expected snow accumulation  
• At least 3’ (1m) away from  
the corner of the building  
• Not near a gas meter, electric  
meter or a walkway where fog  
or ice could create a hazard  
• Not into a garage, workshop  
or other unheated space  
2 Pull the insulated  
flexible duct through  
the opening until it is  
well extended and  
straight. Slide the  
duct’s inner vinyl  
sleeve over the hood  
collar and secure, pull  
the insulation over  
the duct and then the  
vapor barrier over the  
sleeve and secure  
with duct tape.  
3 Push the hood into  
the opening. Attach  
the hood to the  
outside wall with  
mounting screws.  
Repeat the  
installation procedure  
for both the Supply  
and Exhaust hood.  
4 Using a caulking  
gun, seal around  
both hoods to  
prevent any  
1 Using the collar of  
the outside hood,  
outline the intake &  
exhaust holes to be  
cut. The holes should  
be slightly larger  
than the collar to  
allow for the  
leaks.  
thickness of the  
insulated flexible  
duct. Cut a hole  
for both the intake  
and exhaust hoods.  
When installing the weather-  
hood, it’s outside perimeter  
must be sealed with exterior  
caulking.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLING DUCTS TO / FROM INSIDE  
To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. Forty-five  
degree are preferred to 90º elbows. Use “Y” tees instead of 90º elbows whenever possible.  
All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage. Aluminum foil  
duct tape is recommended. Galvanized ducting from the HRV to the living areas in the house is recommended whenever possible,  
although flexible duct can be used in moderation when necessary.  
SUPPLY AIR DUCTING  
In homes without a forced air furnace, fresh air should be supplied to all habitable rooms including, bedrooms and living areas. It  
should be supplied from high wall or ceiling locations. Grilles that diffuse the air comfortably are recommended.To avoid possible noise  
transfer through the ductwork system, a short length (approximately 12”, 300 mm) of nonmetallic flexible insulated duct should be  
connected between the HRV and the supply/exhaust ductwork system.  
The main supply and return lines to/from the HRV must be 6 inches (150 mm) minimum. Branch lines to the individual rooms may be  
as small as 4 inches (100 mm), but 5 inch (125 mm) lines are preferred.If the floor is the only option available, then special care  
should be taken in locating grilles. Areas such as under baseboard heaters will help to temper the air. Also optional inline duct  
heaters are available for mounting in the supply duct work to add heat if required.In homes with a forced air furnace, you may want to  
connect the HRV to the furnace ductwork (see information below).  
PRACTICAL TIPS  
Direct Connection  
For minimum distance  
See local building codes  
and practical tips.  
• A direct connection requires that the fan of the furnace  
runs continuously. It may be inter-linked electrically  
(low voltage) with the HRV (Accessory Control  
Contacts) for intermittent demand. Should you wish to  
hard duct the supply air directly into the cold air return  
of the furnace, remember to check the airflow balance  
of the HRV with the furnace fan both “on” and “off” to  
determine that it does not imbalance the HRV more  
than 10%. Make sure you respect the 1m minimum  
distance from the supply air in of the HRV and the  
furnace (Refer to your local and National Building &  
Heating Codes for any variations in these notes).  
• Building Codes and  
Combustion Appliance  
Installation Codes do  
not allow location of  
return air grilles or any  
opening such as a  
“breathing tee” in an  
enclosed room with  
spillage susceptible  
combustion appliances.  
• The fresh air inlet from  
the HRV needs to  
from HRV  
respect a minimum  
distance from the furnace  
return drop to ensure  
proper air mixing and  
temperature at the  
furnace core.  
See furnace manufacturer  
for appropriate  
specifications.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLING DUCTS TO / FROM INSIDE (CONT'D)  
Exhaust Air Ducting  
The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is rec-  
ommended that return air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic  
locations (i.e. greenhouse, atrium, swimming pool, sauna, etc.) may be installed. The furnace return duct may be also used to  
exhaust from. In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc to the HRV with “dedicated lines”.  
This method has become popular and provides good ventilation when installed in accordance with the instructions. The furnace  
blower must be running when the HRV is operating for this method to be effective.  
Dedicated Installation for Existing Home -  
(non forced air heating / cooling system)  
PRACTICAL TIPS  
1 Begin with the duct collar marked “Exhaust Air In”. Slide a short piece  
(12”) of flexible duct over the duct collar. Using duct tape, tape the  
• For new construction,  
the rigid ducts are run  
flexible duct to the collar. Run the flexible ducting to the main rigid duct  
in the walls.  
trunk line, which connects to the remainder of the ducts going to and  
from rooms in the house. Repeat the steps for the “Supply Air Out” on  
the side of the HRV.  
• Choose the location for  
your Supply and Exhaust  
grilles. The Supply  
grilles should be located  
in every habitable room  
and the Exhaust Grilles  
should be located in the  
wet rooms.  
2 Working from a closet, attic or inside your joist wall, run the length of  
ducting required for the proper grille location and cut a hole in the  
drywall. Fasten the mounting collar (optional) to the ducting and fasten  
the collar to the wall or ceiling with screws.  
• A piece of flexible  
ducting should be  
placed between the  
Supply Air In and Out  
collar of the HRV and  
the rigid ducting to  
absorb any noise or  
vibrations.  
3 The grille airflow can be adjusted by rotating the inside unit. It is  
recommended that the grilles be completely opened at first and then  
adjusted later as needed.  
• For proper network  
of ducting, see TYPES OF  
INSTALLATIONS.  
• The grilles are to be  
installed on the ceiling  
or on the wall 6” (152  
mm) to 12” (305 mm)  
from the ceiling.  
4 Push the grille into the optional mounting collar or directly into installed elbow.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION EXAMPLES  
It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform  
as intended. All air movement devices have a performance curve. The amount of air (CFM) that an HRV/ERV will deliver is  
directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed  
on the blower by length of duct work/number of fittings used in duct work, duct heater etc.  
Ducting Fifth Port Units  
All HRV(D)’s have a fifth duct port on top of the unit. This duct port is for both defrost and the recirculation mode. A motorized  
damper installed in the port closes during defrost or recirculation temporarily blocking the incoming fresh air-stream, allowing the  
warm air from the house to circulate through the HRV. You may wish to duct this port to a common clean air room (living room or  
dining room) so when recirculation is activated, household odors from the kitchen, bathroom or basement won’t be introduced into  
the living spaces of the home environment.  
RADIANT HEATED HOMES  
NOTE:  
The recirculation function can be accessed with a optional digital control. It allows air to move gently throughout the home without  
exchanging air to the outside, until needed.  
Example diagram only-duct configuration may change depending on model  
Exhaust  
Fully Dedicated System  
Bathroom  
(new construction)  
Bedrooms  
Central Control - optional  
Fresh air to living room  
Stale air drawn from key areas  
of home (bathroom, kitchen,  
laundry)  
Fresh air supplied to main liv-  
ing areas  
HRV must be balanced  
1800  
mm  
HRV  
Fresh Air  
460 mm  
Exhaust Air  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION EXAMPLES (CONT'D)  
Example diagram only-duct configuration may change depending on model  
DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN  
(Stale air drawn from key areas of home)  
Partially Dedicated System  
Exhaust  
Central Control - optional  
Bathroom  
Stale air drawn from key areas of  
home (bathroom, kitchen, laundry)  
Bedrooms  
Return Air  
Furnace thermostat  
Fresh air supplied to main living  
areas via the forced air system.  
HRV must be balanced  
HRV  
Connection  
HRV  
Fresh Air  
460 mm  
Exhaust Air  
* Ducts connection may  
vary depending on model  
Return Air  
Exhaust Air from various parts of home.  
i.e. bathrooms (if required),  
kitchens (if required)  
1 m  
(3’-3”) min.  
recommended  
Outdoors  
Cool Air  
Return  
* Unit is normally balanced on HIGH speed with furnace blower ON.  
NOTES:  
1.Furnace blower may be required to operate when HRV/ERV is on to provide good air distribution.  
2.Weatherhood arrangement is for drawing purposes only. 6’ (2m) minimum separation recommended.  
18” (460mm) above grade minimum.  
3.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HRV/ERV’s airflow must be  
confirmed on site, using the balancing procedure found in the installation manual.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION EXAMPLES (CONT'D)  
Example diagram only-duct configuration may change depending on model  
DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and  
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN  
Simplified Installation  
Option 1  
(Return/Return Method)  
• HRV must be balanced  
• It is mandatory that the furnace blower  
run continuously or HRV operation  
be interlocked with the furnace blower  
• Check local codes/authority having  
jurisdiction for acceptance  
Note: Option 1 is the pre-  
ferred/recommended method  
when doing a simplified  
installation  
* Ducts connection may  
Return Air  
vary depending on model  
40”  
Min.  
1 m  
(3’-3”) min.  
recommended  
Outdoors  
* Unit is  
normally  
balanced  
on HIGH  
speed  
Cool Air  
Return  
NOTES:  
with  
1. Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be  
set to run continuously or interlocked with HRV/ERV.  
2. A minimum separation of 39 inches (1m) is recommended between the two direct connections.  
3. The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.  
4. Weatherhood arrangement is for drawing purposes only. 6’ (2m) minimum separation recommended. 18” (460  
mm) above grade minimum.  
furnace  
blower  
ON.  
5. Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the  
HR/ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION EXAMPLES (CONT'D)  
Example diagram only-duct configuration may change depending on model  
DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM &  
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE  
Simplified Installation  
Option 2  
(Supply/Return Method)  
• HRV must be balanced  
• It is recommended that the furnace blower  
run continuously or HRV operation  
be interlocked with the furnace blower  
• Check local codes /authority having  
jurisdiction for acceptance  
Note: Option 1 is the pre-  
ferred/recommended method  
when doing a simplified  
installation  
* Ducts connection may  
Return Air  
vary depending on model  
1m  
(3’-3”) min.  
recommended  
1 m  
(3’-3”) min.  
recom-  
Outdoors  
mended  
* Unit is  
normally  
balanced  
on HIGH  
speed  
Cool Air  
Return  
NOTES:  
with  
1. Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be  
set to run continuously or interlocked with HRV/ERV.  
2. The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.  
3. Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation recommended.  
Eighteen inches (460 mm) above grade minimum.  
furnace  
blower  
ON.  
4. Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the  
HR/ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIR FLOW BALANCING  
CAUTION  
• If the unit’s airflows are not properly balanced...  
- The unit may not operate at it’s maximum efficiency.  
- Heat recovery core damage may occur.  
- The unit’s use could cause negative or positive pressure in your home causing cold air to enter or other combustible equipment to backdraft.  
- The unit may not defrost properly.  
PITOT TUBE BALANCING PROCEDURE  
PITOT TUBE  
ing. The value read on the gauge is called the velocity pressure. The  
Pitot tube comes with a chart that will give the air flow velocity based  
on the velocity pressure indicated by the gauge. This velocity will be in  
BALANCING PROCEDURE  
The following is a method of field balancing an HRV/ERV using a Pitot either feet per minute or meters per second. To determine the actual  
tube, advantageous in situations when flow stations are not installed in airflow, the velocity is multiplied by the cross sectional areas of the  
the ductwork. Procedure should be performed with the HRV/ERV on high duct being measured.  
speed.  
This is an example for determining the airflow in a 6" duct.  
The first step is to operate all mechanical systems on high speed, which The Pitot tube reading was 0.025 inches of water.  
have an influence on the ventilation system, i.e. the HRV/ERV itself and From the chart, this is 640 feet per minute.  
the forced air furnace or air handler if applicable. This will provide the The 6" diameter (D) duct has cross sectional area (A) of  
maximum pressure that the HRV/ERV will need to overcome, and allow  
A = 3.14 x (D/24) 2  
for a more accurate balance of the unit.  
A = 3.14 x (6/24) 2  
Drill a small hole in the duct (about 3/16), three feet downstream of any A = 0.196 or about 0.2 ft2  
elbows or bends, and one foot upstream of any elbows or bends. These  
are recommended distances but the actual installation may limit the  
amount of straight duct.  
The Pitot tube should be connected to a magnehelic gauge or other  
manometer capable of reading from 0 to 0.25 in. (0-62 Pa) of water,  
preferably to 3 digits of resolution. The tube coming out of the top of the  
pitot is connected to the high pressure side of the gauge. The tube com-  
ing out of the side of the pitot is connected to the low pressure or ref-  
erence side of the gauge.  
The airflow is then: 640 ft/min x 0.2 ft2 = 128 cfm  
For your convenience, the cross sectional area of some common round  
duct is listed below:  
DUCT DIAM. (inches) CROSS SECTION AREA (sq ft.)  
5
6
7
8
0.14  
0.20  
0.27  
0.35  
Insert the Pitot tube into the duct; pointing the tip into the airflow. For  
general balancing it is sufficient to move the pitot tube around in the duct  
and take an average or typical reading. Repeat this procedure in the  
other (supply or return) duct. Determine which duct has the highest air-  
flow (highest reading on the gauge). Reduce this airflow using either the  
electronic balancing system (if applicable) or damper. The flows should  
now be balanced. Actual airflow can be determined from the gauge read-  
The accuracy of the airflow reading will be affected by how close to any  
elbows or bends the readings are taken. Accuracy can be increased  
by taking an average of multiple readings as outlined in the literature  
supplied with the Pitot tube.  
Place pitot tube a minimum of 18" from blower elbows.  
* Pitot tube should be kept at  
least 12” away from fans  
elbows and dampers to ensure  
accurate reading.  
Magnehelic  
* A calibration decal is included  
to place over electronic balanc-  
ing system adjustments after it  
has been balanced.  
Note: Duct connections may  
vary, depending on model.  
Magnehelic  
• The balancing procedure consists of measuring the exhaust air leaving the system and the supply air entering the system and ensuring that these  
two are equal. A deviation of 10% or less is acceptable. In such cases, it is recommended to have a greater amount of exhaust air than supply  
air as so to increase the supply air’s temperature.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIR FLOW BALANCING (CONT'D)  
AIRFLOW STATION (GRID) METHOD  
B
1 For this flow measuring station, cut  
the duct and place the flow  
2 Before taking the reading, make sure  
3 Adjust the “Supply Air Out” damper  
until you reach the desired velocity.  
Follow the previous steps to adjust  
the “Exhaust Air Out” damper, if  
needed.  
that the magnehelic gauge is level  
and at 0. Refer to the flow  
measuring station between each  
station. Make sure that the flow  
measuring station’s air direction  
arrow points in the direction of the  
airflow. Secure the flow measuring  
station with duct tape.  
measuring station’s chart to  
determine your unit’s airflow velocity.  
To avoid airflow  
turbulence and incorrect  
readings, the airflow  
velocity should be  
18”  
18”  
(457 mm)  
(457 mm)  
measured on steel  
Measure  
here  
ducting a minimum of  
18” (457 mm) from the  
unit or elbow and before  
any transition.  
Measure  
here  
ADJUSTING AIRFLOWS  
ELECTRONIC BALANCING MOTORS [HRV 150D & 200D only] -  
Motors will be factory set at their full potential depending on speed selected.  
When unit is installed you will need to balance the motors for proper operation.  
Insert screwdriver and turn clockwise to slow down the motor, you will notice the motor changing speeds  
while performing this operation. Set to desired cfm.  
Use slot screwdriver to  
adjust speed/airflow  
-
+
Fan  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
CAUTION  
MAKE SURE UNIT IS UNPLUGGED BEFORE ATTEMPTING ANY MAINTENANCE WORK  
The following components should also be inspected regularly and well maintained.  
PRACTICAL  
TIPS  
Filters need to be checked regularly  
To prevent electrical shock,  
check that the unit is  
unplugged before doing  
FILTERS  
The filters (2) need to be  
checked and cleaned every  
any  
repairs  
or  
three months or when they  
appear dirty. Wash in warm  
sudsy water (mild detergent)  
or use a soft brush vacuum.  
The filters should be replaced  
when they can no longer be  
cleaned properly.  
maintenance.  
• A yearly inspection is  
recommended to ensure  
the efficiency and trouble-  
free use of your system.  
Run through the system  
and verify the different  
operating modes.  
The motor - The motors are  
factory balanced and lubri-  
cated for life. They require  
no maintenance.  
HEAT RECOVERY CORE  
The heat recovery core needs to be checked and cleaned every six months. The core can be  
cleaned using a mild soap and water. Rinse thoroughly. Handle with care. Hot water and a strong  
detergent will damage the heat recovery core. It is recommended to clean the core in the sum-  
mer or when the temperature is mild. Never clean the heat recovery core during winter.  
The unit - The inside of the  
unit should be vacuumed  
yearly. Be careful not to  
damage any of the mechani-  
cal components and electri-  
cal connections.  
To Install the Clean Core and Filters.  
Clean Core and Filters Every 3-6 Months.  
Unplugged before doing any repairs or mainte-  
nance  
a) First mount the bottom flange of the core guide into the  
bottom channel approximately 1/4” (6mm).  
b) Mount the left or right side flange of the core guide  
approximately 1/4 “ (6mm) followed by the other side.  
c) Mount the top flange of the core guide into the top  
channel approximately 1/4” (6mm).  
d) With all four corners in place and the core straight and  
even, push hard in the center of the core until the core  
stops on the back of the cabinet.  
a) Open access door.  
b) Carefully grip ends of core and pull evenly out  
ward. Core may be snug, but will slide out of the  
channel.  
c) Once removed from the cabinet remove filters.  
d) Wash core in warm soapy water (do not use  
dishwasher).  
The drain pan and drain line -  
Units with drain lines should  
have their line and connec-  
tion checked regularly.  
e) Install the clean filters.  
f) Install clean core.  
Outside hoods - The outside  
hoods need to be checked  
every season to make sure  
there are no leaves or  
insects blocking the airflow.  
Check regularly that there  
are no pollutants near the  
intake hood. Make sure they  
are clear of any snow accu-  
mulation during the winter  
months.  
NOTE: Some products may not be exactly as illustrated in Installation, Operation and Maintenance manual.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Problem  
Causes  
Solutions  
Increase the desired level of humidity. Change ventilation mode from  
continuous mode to standby.  
Air is too dry  
Dehumidistat control is set too low  
HRV out of balance  
Balance HRV  
Reduce the desired level of humidity. Combine this step with use of con-  
tinuous exchange mode.  
Dehumidistat control is set too high  
Air is too humid  
Wait until outside temperature stabilizes (winter). Heating will also  
improve situation.  
Sudden change in temperature  
Store a majority of your wood outside. Even dried, a cord of wood con-  
tains more than 20 gallons of water.  
Storing too much wood for heating  
Dryer vent exhaust is inside home  
Arrange outside vent for dryer.  
Open curtains or blinds. Bay or bow windows may require mechanical  
method.  
Poor air circulating near windows  
HRV out of balance  
Balance HRV  
Open the door or install a grill on the door.  
Well sealed basement door is closed  
Persistent condensation  
on window  
Improper adjustment of dehumidistat con-  
trol  
Reduce the desired level of humidity. Combine this with the use of con-  
tinuous exchange mode.  
HRV out of balance  
Balance HRV  
-Clean exterior hoods or vents  
-Remove and clean filter  
-Remove and clean core  
-Check and open grilles  
-Have electrician check supply voltage at house  
-Check duct installation  
Poor Air Flows  
-1/4” (6mm) mesh on the outside hoods  
is plugged  
-Filters plugged  
-Core obstructed  
-House grilles closed or blocked  
-Dampers are closed if installed  
-Poor power supply at site  
-Ductwork is restricting HRV/ERV  
-Improper speed control setting  
-HRV/ERV airflow improperly balanced  
-Increase the speed of the HRV/ERV  
-Have contractor balance HRV/ERV  
-Locate the grilles high on the walls or under the baseboards, install  
ceiling mounted diffuser or grilles so as not to directly spill the supply  
air on the occupant (eg. Over a sofa)  
-Turn down the HRV/ERV supply speed. A small duct heater (1kw)  
could be used to temper the supply air  
-Poor location of supply grilles, the airflow  
may irritate the occupant  
-Outdoor temperature extremely cold  
Supply air feels cold  
-Placement of furniture or closed doors is restricting the movement of  
air in the home  
-If supply air is ducted into furnace return, the furnace fan may need to  
run continuously to distribute ventilation air comfortably  
-Note: minimal frost build-up is expected on cores before unit initiates  
defrost cycle functions  
-Have HVAC contractor balance the HRV  
HRV and / or Ducts  
Frosting up  
-HRV air flows are improperly  
balanced  
-Malfunction of the HRV defrost  
system  
Condensation or Ice  
Build Up in Insulated  
Duct to the Outside  
-Incomplete vapor barrier around  
insulated duct  
-A hole or tear in outer duct covering  
-Tape and seal all joints  
-Tape any holes or tears made in the outer duct covering  
-Ensure that the vapor barrier is completely sealed.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL CONNECTIONS  
Low Voltage Control Wiring Connections  
* Please see instruction on individual controls for proper wiring and set up of control selected.  
Standard Accessory Control Contact  
THERMOSTAT  
TERMINALS  
R
G
FOUR  
WIRE  
W
Y
TWO WIRE  
heating only  
W
R
G
C
Y
NEW CONNECTION PANEL  
FURNACE  
24-VOLT  
TERMINAL BLOCK  
COOLING SYSTEM  
TWO  
WIRE  
Alternate Accessory Control Contact  
DMFC-REC  
or  
THERMOSTAT  
TERMINALS  
DMFC  
R
G
W
Y
FOUR  
WIRE  
TWO WIRE  
heating only  
RT-15M  
W
R
WIRE JOINT  
G
MD-2W  
or  
CT-30M  
C
Y
FURNACE  
24-VOLT  
TERMINAL BLOCK  
COOLING SYSTEM  
TWO  
WIRE  
MD-4W  
MD-2W - Connect  
to positive (+) and  
negative (-)  
connections on elec-  
trical panel.  
DMFC-REC -  
This control is not  
polarity sensitive,  
therefore you may  
connect any wire to  
either positive (+) or  
negative (-)  
connection.  
2 wire connection  
2 wire connection  
2 wire connection  
RT-15M - Connect  
to positive (+) and  
negative (-)  
connections on elec-  
trical panel.  
DMFC -  
MD-4W - Connect  
to positive (+) and  
negative (-)  
connections on elec-  
trical panel.  
This control is not  
polarity sensitive,  
therefore you may  
connect any wire to  
either positive (+) or  
negative (-)  
Also connect to CUR  
SW  
connection.  
4 wire connection  
2 wire connection  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL CONNECTIONS (CONT'D)  
3 position mode  
selection switch  
Accessory Control Contact  
(Open & Closes contact when HRV/ERV is ON/OFF)  
Diagnostic  
LED  
Custom defrost  
mode jumper  
selection  
U
- +  
Air Quality  
Sensor  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The product is manufactured by Fantech, Inc. Fantech reserves the  
right to modify, at any time and without notice, any or all of this  
product's features, designs, components and specifications.  
United States  
1712 Northgate Blvd.,  
Sarasota, FL. 34234  
Phone: 800.747.1762;  
941.309.6000  
Canada  
50 Kanalflakt Way,  
Bouctouche, NB E4S 3M5  
Phone: 800.565.3548;  
506.743.9500  
Fax: 877.747.8116; 506.743.9600  
Item #: 402950 Rev. 1  
Rev Date: 11022006  
Fax: 800.487.9915; 941.309.6099  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Adaptec Network Card SATA AND SCSI RAID CONTROLLERS User Manual
ADTRAN Network Card D4 TRI C DP User Manual
AEG Vacuum Cleaner 1800 User Manual
Aiwa Speaker TS W42 U User Manual
Alpine CD Player CDE HD149BT User Manual
Aluratek Portable Speaker APS02F User Manual
Atlona Car Amplifier AT HDDA 8 User Manual
Avery Printer 676 User Manual
Barco Home Theater System R9010040 User Manual
Beko Freezer CF1100APW User Manual